Thursday, 22 November 2017

Today’s Outline
Harmonic Mitigation
 The Definition  PQ Standard
 The Presence  Mitigation 
 The Characteristic  Active Harmonic Filter
 The Sources  Solution
 The Effect
Definition
 Harmonic are the presence of Multiples of 
fundamental frequency of current or voltage which 
distort the ideal sine waves.
the ideal sine waves

Ideal Sine Waves Distorted Sine Waves


Presence of Harmonic
 Distorted  Sine Wave
Presence of Harmonic
 The Composition of Distorted Sine Wave
Presence of Harmonic
 1 = 50Hz
 3 = 150Hz
 5 = 250Hz
 7 = 350Hz
 9 = 450Hz
 11 = 550Hz
 13 = 650Hz
Presence of Harmonic 
 Indicator of Measurement of Harmonic defined by 
THD (Total Harmonic Distortion) in scale of 
percentage (%).
percentage (%)

 Un or In : Individual Harmonic on order “n” (V/A)
 U1 or I1 : Fundamental Current / Voltage (V / A)
Presence of Harmonic
Ch i i fH i
Characteristic of Harmonic
Ch t i ti f H i
Characteristic of Harmonic

Harmonic Order No
Harmonic Order No.
Zero Sequence Harmonic 3,9,15,21,27,….
Negative Sequence Harmonic 5,11,17,23,29,….
Positive Sequence Harmonic 1,7,13,19,25,….
The Sources of Harmonics – by Sector
Sector Sources Application
pp

Industrial Variable Speed Drives • Manufacturing 


(VSD), UPS System,  Process
Lighting  Computers & 
Lighting, Computers &  • Welding
Electronic • Arc Furnacing
•Crane & Lift
Smelting
•Smelting
Commercial Computers, Electronic  • Elevator
Office Equipment,  • Escalator
Lighting  UPS for data 
Lighting, UPS for data  • HVAC System
centre, VSD  • Data Centre
Residential Personal Computers, • Lighting Control
Lighting, Electronic 
h l l
• Electronic
Devices
The Source – Linear Vs Non‐Linear
Linear Load Non‐Linear Load
Power Factor Watts / VA = Cos Phi Watts / VA ≠ Cos Phi (adds 
distortion factor)

Harmonics No Harmonics Odd Harmonics


Load Category Inductive or Capacitive Can’t be identified
Load Type Resistive, Inductive or  Equipment with Diode and 
Capacitive Capacitor (Rectifier, Inverters)
Neutral Current Zero Neutral Current if  Neutral Current could be 2.7 
1 Phase loads are  times even if 1 Phase loads are 
balance balance
The Source – Linear Vs Non‐Linear
Sinewaves Comparison
The Source – Converter & Inverter
The Source – Converter & Inverter
6 Pulse Rectifier Without Inductor
  l  R ifi  Wi h   d
The Source – Converter & Inverter
6 Pulse Rectifier + 4% Line Reactor
  l  R ifi     %  i  R
The Source – Converter & Inverter
6 Pulse Rectifier + 4% Line Reactor
  l  R ifi     %  i  R
The Source Converter & Inverter
The Source – Converter & Inverter
Eff C bli S
Effect on Cabling System

Copper / Core Losses : Energy losses which converted to 
heat through conductor.
 I (Current) will increased Quadratically
I (C )  ill i d Q d i ll along with 
l   i h 
increased current harmonics.
 R (Ohm) will increased along with harmonics due to 
high frequency properties carried by the harmonics.
Higher Copper losses = high temperature of the cable 
g pp g p
and less efficient of energy transferred.
Eff C bli S
Effect on Cabling System
Effect on Induction Motor

Effect by Harmonic Harmonic Effects Results


Profiles of High  • High Copper Losses • Low Motor Efficiency
Frequency • Derating Conductors • Excessive Heating
• Insulation Stress • Insulation Failure
• Shortened Motor 
Lifetime
Profiles of Harmonics  • Pulsating Torque
g q • Production Failure
Phase Sequence  • Motor Noises
Effect on Induction Motor
Effect on Other Components
Effect by Harmonic Harmonic Effects Results
Circuit Breakers •Lowered down the  • Increased number of 
fundamental Current Tripping Due to lower 
Fundamental Current and 
increased harmonic
•Shortened lifetime 
Power Electronics • Excessive Heating Communication
•Communication
•Voltage Distortion Disturbance
•Production Loss
•Control system failure
P  S l  F il
•Power Supply Failures
Lighting •Voltage Distortion • Flickering
Power Factor Capacitor •Resonance •Capacitor Failure
•Over current •Dielectric Loss
•Shortened Lifetime
PQ Standard – IEEE 519
PQ Standard – IEEE 519
 Sample Case
PQ Standard – IEEE 519
 Sample Case
Harmonic Mitigation
 Add Line Reactors (AC/DC Choke)
 Compensate up to 35% of Existing Load THD
 Use 12 or more Pulse Rectifier 
 Reduced down to 9‐10% of Existing Load THD
 Supplied by the Vendor
S li d b  th  V d
 Use External Active Harmonic Filter
 Reduced down to 2‐4% of Total THD
Reduced down to 2 4% of Total THD
Active Harmonic Filter
Active Harmonic Filter
Active Harmonic Filter
Active Harmonic Filter
Harmonic Mitigation Outline
Harmonic Mitigation Outline
For New Project

Choose 
Calculate the 
C l l t  th  
Load Profiling Compensation  Define AHF
Total Load
Level
Load Profiling
oad o g
Harmonic Estimation for New
Harmonic Estimation for New 
Project
 Example:
1.Load Profiling: Knowing what kind of non‐linear Load
 VSD 6 Pulse Rectifier with 2‐3% Line Reactor, 
VSD 6 P l  R ifi   i h  % Li  R  
 Specification : 75KW, at 400V, PF 0.8

2. Calculate the Total Current generated: 135 A
3. Find Estimation of THD of selected non linear load  : 44%
3. Find Estimation of THD of selected non‐linear load  : 44%

4. Active Harmonic Filter Needed : 44% x 135A = 60A ‐> 100A
with assumption of Total Compensation of Harmonic
Harmonic Mitigation Outline
Harmonic Mitigation Outline
For Existing Site

Analyse the 
Choose 
R
Report and 
t  d 
Measurement Compensation  Define AHF
Calculate 
Level
Amps
Measurement
Step During Measurement:
p g
 Analyse the Single Line Diagram
 Finding the PCC ( Point of Common Coupling )
 Define the Limit Tolerance and measure
D fi  th  Li it T l   d 

Goals during Measurement:
g
 Full Load Spectrum of Harmonics
 Sectoral Behaviour
 Factory Behavior :Usage of Machines, Working Shift
 B h i     f  hi  W ki  Shif
 Commercial Behavior : Peak Hours, Load Profiling
 Power Quality Analysis : Voltage Dip, Unbalance, 
Q y y g p, ,
Interruptions, etc.
Harmonic Estimation for Existing
Harmonic Estimation for Existing 
Site

 Statistical Report Analysis to find Total Harmonic 
Current:
 Average and Median
Harmonic Estimation for Existing
Harmonic Estimation for Existing 
Site
Assuming:
Total HarmonicDistortion Current : 20% x 800A = 160A 
C
Compensation Level IEEE 519 : Limit 8% Tolerance.
i  L l IEEE     Li i   % T l
 AHF Needed= 12% x 800A = 96A

Compensation Level  = Full Compensation
 AHF Needed = 20% x 800A = 160A
AHF Needed   20% x 800A   160A
Linear Forecasting Capacitor
12
ons

10
Billio

8
6
4
2
0
2004 2006 2008 2010 2012 2014 2016
Series2 Linear (Series2)