~.Sheet AS.O: Please specify the roofing assembly fire rated class.
Response:~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~-

so. Sheet A6.0: Please provide attic ventilation calculations such that the net area of ventilation is minimum
1/150 of the area of the vented space. Show the size and location of the attic vents on the roof plan.
Response:~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~

51. Sheet A6.0: Please specify the insulation R-value of the ceiling/roof, exterior wall, and floor assemblies per
energy certificate of compliance forms.
Response:~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~

52. Sheet A6.0: Please revise the section to show the lower floor to have crawlspace and floor framing for
consistency with the structural drawings.
Response:~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~---

.
53. Sheet A6.0: Please provide a detail to show the insulation condition at the vaulted ceiling. Show minimum
1'' air space from the insulation to the bottom of the sheathing. (Verify rafter depth to accommodate the
depth of the insulation and the 1'' airspace).
Response:~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~

54. Sheet S-1: Please provide foundation and framing information for the exterior patio and steps .
.

55. Sheet S-1: Please show the interior strip foundation at load bearing walls and at shear walls/strong walls to
connect with the perimeter foundation.

56. Sheet S2-54: In the structural calculations of all framing members, please provide beam loading
explanations to separate the roof, wall, floor loads (for example, please separate total load to floor dead,
floor live, wall dead, roof dead, roof live, etc.). Additional comments may follow.
Response:~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~-

57. Sheet S3: On page 38 of the structural calculations, please verify the TJI joists include the point load from
the load bearing waif above (supporting ceiling joists).
Response=~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~-

58. Sheet S3: On page 38 of the structural calculations, please verify the beam on Line .4 includes the point
load from the load bearing waif above.
Response:~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~-

59. Sheet S3: Please revise structural calculations for beams supporting holdown/uplift loads (from shear walls
above) to multiply the uplift force by the required overstrength factor of 2.5 per ASCE 7-10 Table 12.2-1.
Verify supporting hardware/connector has adequate capacity to resist net uplift. Verify the beams on Lines
2, 6.1, 8, H, and L.

.oO. Sheet 54: Please clarify the support of the 4x8 cantilever beam at Line 3 per page 33 of the structural
I calculations. Verify rigidity of the 4x8 cantilever beam attachment to strong wall connection (for fixed end
per cantilever beam calc).
Response:--------------------------------

(End of Comments)