You are on page 1of 6

Submittal

Design Envelope Split-Coupled Vertical In-Line Pump


Model: Series Design Envelope Sensorless 4300 1217-150.0
Project name: undefined Representative:
Location: Phone number:
Date submitted: e-mail:
Engineer: Submitted by:
Application design data
Tag number: Configuration: Single
Service: Suction pressure: 0 ft
Location: Fluid: Non-Potable Fluid - Water
Total pump qty: 1 Operating temperature: 60 °F
Total system flow: 4500 USgpm Duty flow per pump: 4500 USgpm
System head: 100 ft Viscosity: 31 SSU
Environment: Indoors Specific gravity: 1.0000
Total dissolved solids: 0 ppm Safety factor % flow: 0%
Efficiency at Design: 87.26 % Safety factor % head: 0%
NPSHR: 8.06 ft Absorbed Power/BHP: 130.23 hp
%Mtr Safety*: 10.97% Impeller diameter: 17.3 in
Standby qty: 0 Pump/motor run qty: 1
Outlet velocity: Design Imp.: Min. maintained system 40 ft
pressure**:

*Motor safety factor above duty point.


**If minimum maintained system pressure is not known, default is 40% of design head.

Materials of construction
Construction: Bronze Fitted Impeller: Bronze
Rating: ANSI-125 Pump shaft: 416 Stainless Steel
Connections: Inlet: 12in, Outlet: 12in Flush line: Braided Stainless Steel
Casing (volute): Cast Iron Casing gasket: Confined Non-Asbestos Fiber

Mechanical seal data


Seal type: Outside Balanced Rotating face: Resin Bonded Carbon
Manufacturer code: C-SSC AB2 Stationary seat: Sintered Silicon Carbide
Springs: Stainless Steel Secondary seal: Viton
Rotating hardware: Stainless Steel

Motor electrical data


Supplier: Factory Choice Insulation class: Class F Insulation
Size: 150 hp Inverter motor type: Inverter duty
Frame size: 445TCZ Efficiency: NEMA Premium 12.12
Enclosure: ODP Motor power supply: 460/3/60
Operating speed @ 100% 1141 rpm Operating speed @ 50% 787 rpm
flow: flow***:
***Based on minimum pressure setting of 40% of design head.

www.armstrongfluidtechnology.com Page 1 of 5
IVS controller data
Sensorless control: Yes - Quadratic press control Communication port: RS 485
BMS protocol: BACnet Native Analog inputs: 2 (current or voltage)
Enclosure: UL Type 12/IP55 Analog outputs: 1 (current)
Fused disconnect switch: None Digital inputs: 4 (programmable)
Control orientation: L1 Digital outputs: 2 (programmable)
Expansion card: None Cooling: Fan cooled through back channel
Absorbed Power/BHP at 50% 32.56 hp Ambient temperature: 14°F to 113°F (up to 3280 ft
load/flow and 55% of elevation)
design head:
Meets ASHRAE 90.1: Yes EMI/RFI control: Integrated filter to meet
EN61800-3
Harmonic suppression: Integrated DC link reactor**
** The IVS control is a low harmonic control with a built-in DC link reactor equivalent in performance to a 5% AC line reactor.
This does not guarantee performance to any system wide harmonic specification or the costs to meet a system wide
specification. If supplied with the system electrical details, Armstrong will run a computer simulation of the system wide
harmonics. If system harmonic levels are exceeded, Armstrong can also recommend additional harmonic mitigation and the
cost for such mitigation.

Performance curve

----Admin Data—-
Tag Num:
Service:
Location:

----Motor Data----
Motor Size: 150 hp

----Design Duty Points---


Flow: 4500 USgpm
Head: 100 ft
Impeller: 17.3 in

----Performance Data---
 NPSHR: 8.06 ft
 Eff. @ Design: 87.26 %
 Absorbed Power/BHP @ Design:
130.23 hp
 Mtr Capability @ Rated Spd:
144.51
 Motor safety factor: 10.97%
 BEP @ Design Imp: 88.1 %
 %maximp.range: 100.00%
 Outlet velocity: Design Imp.:
 VFD Op.speed: @4016.1
 VFD setting: 57.5 Hz

www.armstrongfluidtechnology.com Page 2 of 5
--Control Data—

1. Hmax @ 57.5 Hz:


NPSHR: 8.0619 ft
Intersection Pt: 4500 usgpm @
100 ft
bhp=130.23 hp, eff=87.26%,
%bepq=110.2%

2. Control (QPC) @ 52.4 Hz:


NPSHR: 5.5077 ft
Intersection Pt: 3925.6 usgpm @
85.7 ft
bhp=96.68 hp, eff=87.83%,
%bepq=105.4%

3. Control (QPC) @ 47.4 Hz:


NPSHR: 3.475 ft
Intersection Pt: 3322.1 usgpm @
72.7 ft
bhp=69.19 hp, eff=88.14%,
%bepq=98.7%

4. Control (QPC) @ 42.4 Hz:


NPSHR: 1.942 ft
Intersection Pt: 2655 usgpm @
60.9 ft
bhp=46.63 hp, eff=87.54%,
%bepq=88.3%

5. Control (QPC) @ 37.3 Hz:


NPSHR: 0.908 ft
Intersection Pt: 1846.8 usgpm @
50.1 ft
bhp=28.11 hp, eff=83.14%,
%bepq=69.7%

6. Index @ 31.9 Hz:


NPSHR: 0.3362 ft
Intersection Pt: 0 usgpm @ 40 ft
bhp=0 hp, eff=0.00%,
%bepq=0.0%

7. Hmin: 40 ft 31.9 Hz:


NPSHR: 0.3351 ft
Intersection Pt: 0 usgpm @ 40 ft
(Head Q Min) Setting= 40.00%
Hmax

Design envelope pumping unit capability


Operating point Flow Head Efficiency
Full capability at 100% design flow 4500 USgpm 115.3 ft 87.91 %
Design point 4500 USgpm 100 ft 87.26 %
50% average flow (with default load profile) 2250 USgpm 55.1 ft 86.08 %

www.armstrongfluidtechnology.com Page 3 of 5
Operating limits (temperature - pressure)

Maximum pressure: 175 psi

Maximum temperature: 200 °F

Pump casings are hydrostatically tested to 150% of maximum pump working pressure rating.

Options
Sensorless Bundle: Yes Parallel Sensorless: No
Energy Performance Bundle: No Protection Bundle: No
Dual Season Setup: No Zone Optimization Bundle: No

Cooling Heating
Q1: N/A Q2: N/A
H1: N/A H2: N/A
H1min: N/A H2min: N/A
Maximum Flow: N/A Minimum Flow: N/A

Optional Services
On-Site Pump Commissioning: Cost not Included Extended Warranty: No
Pump Manager: Yes Include Spare Parts Qty: 0

Dimensional data (not for construction)


Side view Top view

Inverter motor type: Inverter duty

www.armstrongfluidtechnology.com Page 4 of 5
Weight: 4506 lb [2043.89 kg], Units of measure: inches [millimeters]
• R = minimum lifting clearance required above motor
• Coupling guard and flush line (not shown) are supplied
• Tolerance of ± 0.125 inch (± 3 mm) should be used
• For certified dimensions, please contact your Armstrong representative
• Pump equipped with casing drain plug and ¼ inch NPT suction and
discharge gauge ports

Connection details
Connection Size Rating OD Bolt quantity* BCD Bolt size
Inlet 12 ANSI-125 19 12 17 0.875
Outlet 12 ANSI-125 19 12 17 0.875
*Equally spaced straddling centreline

Special instructions
Reference Motor Specification AES 05007 and Armstrong Motor Specification EP-7-101.
The program has defaulted to a NEMA Premium Efficiency motor supplied with NEMA MG-1 Part 31.4.4.2 insulation
standards for inverter-fed polyphase motors.
OSHPD Seismic Certification OSP-0422-10
UL STD 778 & CSA STD C22.2 no.108 certified

Selected options
Testing: No Test Certification Required
Seal Environment Accessories: None
Pre-Wired Control Bridge: No
Sensorless Bundle: Sensorless control
Constant flow control
Constant pressure control
Flow readout
Pump Manager: Yes

Pump Manager:
Keep the system running as intended with Pump Manager.
Pump Manager is a cloud-based Performance Management Service that pro-actively tracks pump performance and provides
early diagnostic warnings, web accessible trends and analysis along with automated reports. Pump Manager helps your
customer make informed decisions and take immediate action to deliver the best possible HVAC performance.
In your project, when buying Design Envelope pumps, be sure to include Pump Manager to deliver real-time insights and
enjoy up to 30% in ongoing savings.

www.armstrongfluidtechnology.com Page 5 of 5
Single Curve

You might also like