Introduction
The Universal Reset Module 423 provides outdoor reset to a hydronic heating system in order to maximize comfort and
efficiency. The 423 can operate two on / off boilers or two modulating boilers. The 423 can override the outdoor reset
water temperature to provide Domestic Hot Water or Setpoint operations. The 423 can operate four outdoor reset water
temperatures, up to three of these water temperatures can be mixing water temperatures. To operate a mixing device, a
Mixing Expansion Module must be connected to the 423 for each mixing water temperature.
Features:
• tN4 Compatible • Equal Run Time Rotation
• Four tN4 Buses • Powered Pump Outputs
• Up to One Boiler and Three Mixing Water • DHW Operation
Temperatures • Optional DHW Sensor
• Two On-Off or Modulating Boilers • Setpoint Operation
Stage1/ Stage 2/ + – + – C1 tN4 C tN4 C2 tN4 C3 tN4 DHW Com Boil Com Out
Boil Enbl Setp Enbl Mod1 (dc) Mod2 (dc) Boiler 1 2 3
50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70
Do not apply power
Powered
Outputs Demands: 20 - 260 V (ac)
24 V (ac) Relay Rating: 115 V (ac) 5 A
Test 8 VA 1 VA 10 A
71 72 73 74 75 76 77 78 79 80 81 82 max
DHW 24 V (ac) DHW Setpoint DHW Primary
C Vlv C R Demand Demand Pump N Pump N
/
If you change a DIP switch setting while the control is Boil Sens Sup / Ret
powered up, the LCD display returns to the View Menu. Off / DHW Sensor
Off / tekmar Stager
Boilers On-Off / Mod
Off / RotationStage1/ Stage 2/ + – + – C1 tN4 C tN4 C2 tN4 C3 tN4 DHW Com Boil Com Out
Lock / Unlock
Boil Enbl Setp Enbl Mod1 (dc) Mod2 (dc) Boiler 1 2 3
50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70
Do not apply power
Use the Lock / Unlock DIP switch to lock and unlock the Access Made in Canada Menu
/
Level of the 423 and all connected tN4 devices, including Boil Sens Sup / Ret
Off / DHW Sensor
Off / tekmar Stager
Item
tektra 1006-01
tN4 thermostats. For details, see “Access Level”. Boilers On-Off / Mod
Off / Rotation
1 VA
Relay Rating: 115 V (ac) 5 A
10 A
71 72 73 74 75 76 77 78 79 80 81 82 max
Access Level
The Access Level restricts the number of Menus, Items, There are two Access Level settings:
and Adjustments that can be accessed by the user. The • Installer (InS): This is the factory default setting. This
Access Level setting is found in the Miscellaneous (MISC) access level is sufficient for the normal set up of the
Menu. Select the appropriate access level for the people control.
who work with the control on a regular basis. • Advanced (Ad): All of the control settings are available
to the user.
In the following menu tables, the access level the item is
visible in is shown in the access column.
Status Field
Number Field
Displays the current
status of the control’s Displays the
inputs, outputs and current value of
operation. Most symbols the selected item
in the status field are
only visible when the
VIEW Menu is selected
Symbols Description
BURNER
MIX 1 DEMAND
Displays when the Stage 1 or Stage 2
Displays when a Mix 1 Demand is present.
contacts are closed.
LOCK
MIX 2 DEMAND
Displays when the access levels are
Displays when a Mix 2 Demand is present.
locked.
COMMUNICATION BUS
DHW DEMAND
Displays when tN4 thermostats are
Displays when a DHW Demand is present.
connected.
Continue
to next Item
Continue
to next Item
Continue
to next Item
DHW SECTION H
InS Current DHW tank temperature as measured by the
-31 to 266°F DHW sensor.
(-35.0 to 130.0°C) Ad
VIEW MENU
After the last item, the control returns to the first item in the menu.
7 of 36 © 2007 D 423 - 08/07
Adjust Menu (1 of 7)
BUS 2 SECTION C
boil, M1 (Mix 1),
M2 (Mix 2), OFF Select the water temperature for tN4 Bus 2.
Ad
Default = boil Note: M1 is only available if Bus 1 is set to M1
(Mix 1).
BUS 3 SECTION C
boil, M1 (Mix 1),
M3 (Mix 3), OFF Select the water temperature for tN4 Bus 3.
Ad
Default = boil Note: M1 is only available if Bus 1 is set to M1
(Mix 1).
ADJUST MENU
1 HRF1
2 HRF2 MIX 1 TERMINAL SECTION B
3 Fancoil The type of heating terminal units that are being
InS
4 Fin-tube Convector used in Mix 1 zones.
5 Radiator Ad
6 Baseboard Note: This item is only available when Bus 1 is set
to Mix 1.
Default = 1
MIX 1 INDOOR SECTION B
The design indoor air temperature used in the heat
40 to 100°F
(4.5 to 38.0°C) loss calculation for Mix 1 zones. Typically set to
Ad
70°F (21.0°C).
Default = 70°F (21.0°C)
Note: This item is only available when Bus 1 is set
to Mix 1.
MIX 1 DESIGN SECTION B
70 to 220°F
The supply water temperature required for the Mix 1
(21.0 to 104.5°C) InS
zones on the typical coldest day of the year.
Default = 120°F Ad
(49.0°C) Note: This item is only available when Bus 1 is set
to Mix 1.
70 to 220°F
(21.0 to 104.5°C) InS The supply water temperature required for the Mix 3
zones on the typical coldest day of the year.
Default = 120°F Ad
(49.0°C) Note: This item is only available when Bus 3 is set
to Mix 3.
BOILER 1 SECTION C
Au (Auto) Selects Whether Boiler 1 is operational or not.
InS
OFF
Ad Note: This item is only available when the Boil Sensor
Default = Au Sup / Ret DIP Switch is set to Sup, and the tekmar
stager DIP switch is set to OFF.
OFF,
Mb1 (Member 1),
SCHEDULE
Mb2 (Member 2), InS
Mb3 (Member 3), Selects which network setback schedule the control
Ad
Mb4 (Member 4), will follow.
Default = OFF
OFF, DHW MODE SECTION H
1 (parallel, no priority)
2 (parallel, priority) InS Selects the DHW mode of operation. This determines
3 (pri-sec, no priority) the operation of the primary pump in combination
Ad
4 (pri-sec, priority) with the DHW Pump / Valve and whether or not DHW
Default = 1 priority is required.
Ad
Default = 180°F Note: This item is only available when DHW Mode
(82.0°C) is set 1 through 4 and the DHW Sensor DIP is set
to OFF.
OFF,
1 (parallel, no priority) SETPOINT MODE SECTION J
2 (parallel, priority) Selects the Setpoint mode of operation. This determines
3 (pri-sec, no priority) Ad
the operation of the primary pump and whether or
4 (pri-sec, priority)
not priority is required.
Default = 1
Member 1, 2, 3 or 4.
After the last item, the control returns to the first item in the menu.
BUS 1 DEVICES
Displays the number of devices on Bus 1.
0 to 24 Ad
Note: This item is only available when Bus 1 is set
to boil or Mix 1.
BUS 2 DEVICES
MISC MENU
BUS 3 DEVICES
Displays the number of devices on Bus 3.
0 to 24 Ad
Note: This item is only available when Bus 3 is set to
boil, Mix 1 or Mix 3.
FACTORY DEFAULT
OFF
Ad Loads the factory defaults when the Up and Down
SEL (Select)
buttons are held down for 1 second.
InS TYPE
423 Displays the type number of this product. Hold the Up
Ad button to display the software version.
After the last item, the control returns to the first item in the menu.
Test
Wait
Hold 3
for 6 seconds
seconds
Test
tN4 tN4
to 24 tN4 thermostats can connect to a single tN4 bus.
H7008B
Power Zone A1
Zone Group Pump A Zone A2
/
Item Zone Group Pump B Zone A3
Zone B1
Zone B2
Zone B3
Test
tekmarNet®4 tekmarNet®4
Thermostats Thermostats
Baseboard (6)
Terminal type 6 is a baseboard terminal unit is similar to a
radiator, but has a low profile and is installed at the base
of the wall. The proportion of heat transferred by radiation
Hydronic Radiant Floor (2) from a baseboard is greater than that from a fin-tube
Terminal type 2 is a light, or low mass, hydronic radiant convector.
floor system. Most commonly, this type of radiant heating
system is either attached to the bottom of a wood sub floor,
suspended in the joist space, or sandwiched between the
subfloor and the surface. This type of radiant system has
a relatively low thermal mass and responds faster than a
high mass system.
Outdoor Design Temperature
The outdoor design temperature is typically the coldest
outdoor air temperature of the year. This temperature is
used when doing the heat loss calculations for the building
and is used to size the heating system equipment. If a cold
outdoor design temperature is selected, the supply water
Fancoil (3) temperature rises gradually as the outdoor temperature
Terminal type 3 is a fancoil terminal unit or air handling drops. If a warm outdoor design temperature is selected,
unit (AHU) consisting of a hydronic heating coil and either the supply water temperature rises rapidly as the outdoor
a fan or blower. Air is forced across the coil at a constant temperature drops.
velocity by the fan or blower and is then delivered into the The outdoor design setting is found in the Adjust Menu.
building space.
Terminal Unit
Boiler Mix
Indoor Indoor
Terminal Unit BOIL DSGN BOIL MAX BOIL MIN Terminal Unit MIX DSGN MIX MAX MIX MIN
High Mass Radiant (1) 120°F (49°C) 140°F (60°C) OFF High Mass Radiant (1) 120°F (49°C) 140°F (60°C) OFF
Low Mass Radiant (2) 140°F (60°C) 160°F (71°C) OFF Low Mass Radiant (2) 140°F (60°C) 160°F (71°C) OFF
Fancoil (3) 190°F (88°C) 210°F (99°C) 140°F (60°C) Fancoil (3) 190°F (88°C) 210°F (99°C) 100°F (38°C)
Fin-Tube Convector (4) 180°F (82°C) 200°F (93°C) 140°F (60°C) Fin-Tube Convector (4) 180°F (82°C) 200°F (93°C) OFF
Radiator (5) 160°F (71°C) 180°F (82°C) 140°F (60°C) Radiator (5) 160°F (71°C) 180°F (82°C) OFF
Baseboard (6) 150°F (76°C) 170°F (77°C) 140°F (60°C) Baseboard (6) 150°F (76°C) 170°F (77°C) OFF
t er Boil MAX
a Mixing Expansion Module must be connected to Bus 1 B oil Wa
and the tN4 thermostats connected to Bus 1 operate the Boil MIN – ½ Boiler Differential
Mixing Expansion Module to heat their zones. MAX MAX
segment segment
on on
Burner On
Heating Load
Differential
Time On
Time
On-Off Boiler(s) Operation
If the heat source is an On-Off Boiler(s), the Boil On-Off / Mod
DIP switch must be set to On-Off.
Modulating Boiler Operation
Differential
The 423 can operate up to two modulating boilers. This
An on / off heat source must be operated with a differential requires the use of the Mod 1 (dc) and Mod 2 (dc) outputs
in order to prevent short cycling. With the control, either on the 423.
a fixed or an auto differential may be selected. The boiler
differential is divided around the boiler target temperature. To operate modulating boilers, the Boil On-Off / Mod DIP
The first stage contact closes when the supply water switch must be set to Mod. The control operates each boiler
temperature is 1/2 of the differential setting below the boiler by first closing the stage contact to allow the modulating
target temperature. The second stage is operated if the first boiler to go through the ignition sequence (the stage
stage is unable to bring the supply water temperature up to contact may not be required on all modulating boilers).
the boiler target temperature at a reasonable rate. As the Then, a 0-10 V (dc) analog signal is used to modulate the
supply temperature reaches 1/2 of the differential above boiler firing rate from the Minimum Modulation setting using
the boiler target temperature, the stages are staged off. Proportional, Integral and Derivative (PID) logic in order
to satisfy the boiler target temperature. The second stage
• Locate the Boiler Differential setting in the Adjust Menu.
is operated if the first stage is unable to bring the supply
water temperature up to the boiler target temperature at a
Differential = 10°F (6°C) reasonable rate.
165°F (74°C) Target + 1/2 Differential Modulating boilers require all the same settings as on-off
160°F (71°C) Target boilers in addition to the settings below.
155°F (68°C) Target – 1/2 Differential
Boiler Boiler Modulating Boiler Differential
On On Modulating boilers must be operated with a differential
while operating in low fire. The boiler differential is divided
around the boiler target temperature. The boiler burner
Fixed Differential
ignites at low fire when the supply water temperature is
If the user desires to have a fixed differential, this is set 1/2 of the Boiler Differential setting below the boiler target
using the Boiler Differential setting in the Adjust Menu. temperature. The boiler is shut off in low fire as the supply
temperature reaches at least 1/2 of the differential above
Stage Delay the boiler target temperature. With the control, either a fixed
or an auto differential may be selected.
The Stage Delay is the minimum time delay between the
When the boilers are modulating above low fire, the differential
firing of the first stage and the second stage. After this
does not apply. Instead, the modulation output signal is
delay has expired the control can fire the second stage if it
determined using Proportional, Integral and Derivative (PID)
is required. This setting can be adjusted manually or set to
logic in order to satisfy the boiler target temperature.
an automatic setting. When the automatic setting is used,
the control determines the best stage delay based on the
operation of the system.
• Locate the Stage Delay setting in the Adjust Menu.
Control
• Locate the Boiler Minimum Modulation setting in the
Range
Range
Boiler
Adjust Menu.
Voltage (dc) 0 1 2 3 4 5 6 7 8 9 10
Boiler Target Off 50°F (10°C) 68°F (20°C) 86°F (30°C) 103°F (40°C) 121°F (50°C) 139°F (60°C) 157°F (70°C) 174°F (80°C) 192°F (90°C) 210°F (99°C)
Powered DHW Demand When using a DHW Sensor, a DHW Demand is registered
A powered DHW Demand may be used to provide heat to when the DHW sensor drops 1/2 of the DHW Differential
the DHW system. A DHW aquastat or setpoint control is setting below the DHW setting. The DHW Demand is satisfied
used as a switch in the DHW Demand circuit. The control once the DHW Sensor rises 1/2 of the DHW Differential
registers a DHW Demand when a voltage between 24 and setting above the DHW setting.
230 V (ac) is applied across the DHW Demand terminals • Locate the DHW Differential setting in the Adjust
(75 and 76). Menu.
• The Off / DHW Sensor DIP must be set to Off.
Boiler Target Temperature
DHW Sensor
A DHW Sensor may be used to provide heat to the DHW The boiler target temperature is at least as hot as the DHW
system. A DHW Sensor must be connected to the DHW Exchange setting (when using a Powered DHW Demand)
Sensor terminals (66 and 67). Once the DHW sensor drops or at least as hot as the DHW setting plus 40°F (22°C)
1/2 of the DHW differential setting below the DHW setting, (when using a DHW Sensor). The DHW Demand overrides
the control registers a DHW Demand. the boiler reset target temperature, except when the boiler
• The Off / DHW Sensor DIP must be set to DHW Sensor. reset target is higher than the DHW target.
Once the control detects a DHW Demand, the DHW Demand • Locate the DHW Exchange setting in the Adjust
segment turns on in the LCD. Menu.
Primary
Mode = 1 Pump
DHW
Pump
DHW MODE 4 - DHW in Primary / Secondary with Priority
Primary When a DHW Demand is present, the DHW Pump and
Pump
Valve contacts are closed and the primary pump is operated.
Priority over space heating zones is achieved by shutting off
the zone pumps or zone valves through tN4 communication.
This is known as zone load shedding.
Mode = 4
OFF
DHW
Pump
Primary
Pump
Increasing Time
time, the heating zones may have cooled off considerably
after being off for a period of time. When restarting the
heating system after a DHW Demand with priority, the
control shuts off the boiler and continues to operate the
DHW Pump and DHW Valve while the primary pump is
turned on. This allows some of the DHW return water to
mix with the cool return water from the zones and temper
the boiler return water.
Primary
Primary Pump
Pump
The primary pump is switched on in the following The DHW Pump operates whenever there is a DHW Demand
situations: and the control is not in DHW Priority Override.
• There is a Boiler Demand and that zone’s thermostat
has H1 Pump set to ON.
• There is a Mix 1, Mix 2 or Mix 3 Demand.
• There is a DHW Demand and the control is set to DHW
Mode 3 or 4.
• The control is completing a DHW Purge.
• There is a Setpoint Demand and the control is set to
Setpoint Mode 3 or Mode 4.
If the error message is a Device Error (if “DEV” or “DEV ERR” is shown on screen), read the address shown and go to the
device with that address. That device will have a Local Error indicating specifically what the problem is. When the problem
is corrected, the error message will automatically clear.
Access Levels
In some cases, it is not desirable to let day-to-day users view error messages. In these cases, by lowering the access level
of the thermostat or setpoint device to ‘User’ or lower, error messages cannot be seen in the View menu and the warning
symbol only appears if there is a local error or a device error caused by a critical error on another device. If there is an error
message on the system that you cannot find on a particular thermostat, make sure that the access level on that thermostat
is set to Installer or Advanced.
Sensor Temperature Errors
If a control is unable to display a temperature due to a sensor malfunction or communication problem, the word “Err” is
displayed in place of the temperature. This usually indicates that there is an error somewhere on the system but is not the
actual error message. Keep looking through the View menu to find the actual error message.
ADJUST ERROR
The control failed to read the Adjust Menu settings, and reloaded the factory default settings.
Operation stops until you check all the Adjust Menu settings.
Note: To clear the error, the access level must be set to Advanced and the settings in the
Adjust menu must be checked.
MISCELLANEOUS ERROR
The control failed to read the Miscellaneous Menu settings, and reloaded the factory default
settings. Operation stops until you check all the Miscellaneous Menu settings.
Note: To clear the error, the access level must be set to Advanced and the settings in the
Misc menu must be checked.
BUS 1 ERROR
Communication has been lost on Bus 1. Check the tN4, C and R wires for each tN4 device.
Check the polarity of the C and R wires. Check for loose or broken wires. The error message
self clears once the error condition is corrected.
BUS 2 ERROR
Communication has been lost on Bus 2. Check the tN4, C and R wires for each tN4 device.
Check the polarity of the C and R wires. Check for loose or broken wires. The error message
self clears once the error condition is corrected.
BUS 3 ERROR
Communication has been lost on Bus 3. Check the tN4, C and R wires for each tN4 device.
Check the polarity of the C and R wires. Check for loose or broken wires. The error message
self clears once the error condition is corrected.
DHW ERROR
A DHW Sensor and a DHW Demand have been applied at the same time. The DHW tank
will not be heated until the DHW Demand signal is removed. The error message self clears
once the error condition is corrected.