GEN-X Series
Elegant Range
Air Cooled, Water Cooled and Dual Coil Systems
GEN-X Series Elegant Range - Engineering Data
Contents
Sections Page
Introduction 3
Service Entry / Access Requirements 3
Dimensions 4
Typical Airflow Arrangement 5
Guide Specifications 6
Ancillaries and Options 8
General Details 11
Schematic Diagram 12
Cooling Performances 16
Electrical Details 17
2 Version: 1.0/2009/Gen-X/E02
GEN-X Series Elegant Range - Engineering Data
INTRODUCTION
The Product
The GEN-X Elegant Range of Precision Air Conditioning Units are compact and stylish with the better performance and quality
demanded by today’s market.
These units are designed and built within a Quality Assurance System conforming to BS EN ISO 9001, using our unrivalled experience
in Precision Air Conditioning, with extensive testing of components and complete systems. Every aspect is engineered to ensure
maximum reliability, economy of operation and long working life, together with ease of installation and maintenance.
The Range
The GEN-X Elegant Range comprises four types of systems, five models in five cabinet sizes, with nominal capacities from 50 kW to
90 kW.
Version: 1.0/2009/Gen-X/E02 3
Edited by Foxit Reader
Copyright(C) by Foxit Corporation,2005-2009
For Evaluation Only.
DIMENSIONS
50 65
1954
1800 2050 885*
70 80
1954
2300 2550 885*
90
1954
2800 885*
Notes:
* For “DA” and “DW” version, unit depth shall be 985mm.
Model Size 50 65 70 80 90
Weight “A” (kgs) 620 725 810 910 985
“W” (kgs) 635 740 830 930 1015
“DA” (kgs) 685 802 898 1010 1098
“DW” (kgs) 700 817 918 1030 1128
4 Version: 1.0/2009/Gen-X/E02
GEN-X Series Elegant Range - Engineering Data
Version: 1.0/2009/Gen-X/E02 5
GEN-X Series Elegant Range - Engineering Data
GUIDE SPECIFICATIONS
6 Version: 1.0/2009/Gen-X/E02
GEN-X Series Elegant Range - Engineering Data
GUIDE SPECIFICATIONS
Version: 1.0/2009/Gen-X/E02 7
GEN-X Series Elegant Range - Engineering Data
8 Version: 1.0/2009/Gen-X/E02
GEN-X Series Elegant Range - Engineering Data
Remote Control and Supervisory Systems Fan Speed Controller (Air Cooled System Only)
Note: For more detailed information, refer to separate - Use to maintain the condensing pressure and thus condensing
“Engineering Data - Genius Controller”. temperature of the refrigerant system by modulating the fan speed
of the outdoor air cooled condenser. This is to ensure that the
The Control & Supervisory System is required to develop a
condensing pressure does not drop below the operational limit of
balanced function between economics, operating costs, safety
the compressor thereby damaging it. A pressure sensing probe is
and comfort with human considerations being most important.
attached to the discharge line to measure the condensing pressure
• Webgate and send its reading to the controller which in turn gives a 0 to
Webgate is an innovative electronic device that measures 10Vdc analogue signal to the FSC module to modulate the fan
the same size as a normal desktop modem. It can speed of the air cooled condenser.
connect the Genius controller to a local network based
on the standard Ethernet and TCP/IP protocol. Frequency Inverter
• pCOWEB The purpose of the frequency inverter is to vary the fan speed
of the unit by changing the frequency of the power supply to
pCOWEB is an add-on card that allows communication
the fan. In auto mode, fan speed will adjust accordingly to suit
between the Genius controller with BACnet Ethernet,
room’s cooling load.
BACnet over IP, SNMP protocol (v1 & v2c), HTTP
protocol, FTP and DHCP protocol.
Split Units
• pCONET
The coil/fan section & the compressor section of the unit can
pCONET is an add-on card that allows communication be split into 2 separate sections to allow transportation / access
with the BACnet MS/TP protocol. to areas with limited space. All access panels could also be
• Telemon removed & packaged separately. The 2 sections & the panels
could then be reassembled at site. All electrical cables crossing
Telemon designed to proactively monitor and control
the 2 sections should also be reconnected at site. These cables
Precision Air Conditioning Units in a critical environment.
are coiled in a tidy fashion for transit & will be labeled for easy
It monitors and changes the parameters of a precision air
identification. For the pipework, some brazing work would be
conditioning unit such as temperature, humidity, cooling &
required at site. All piping will be solder type by default unless
heating demands, rotation configuration and time control.
specified otherwise. The 2 sections could also be placed &
• PlantVisor crated separately as an additional option.
Plantvisor, with its web server function, can work on PCs
connected in an TCP/IP network. This allows sharing the Floor Sealing Plate (Upflow Models Only)
data and information dealt with by the plantvisor with A sealing plate can be provided to seal the bottom section of the
more than one user at the same time. upflow models to prevent air from being bypassed through the
• RS485 Serial Card bottom of the unit instead of from front grille. This would not be
necessary if unit is sitting on a solid floor.
This is an add-on card which allows the Genius controller
to interface directly with a RS485 supervisory network.
Water Flow Detection (Chilled Water System
• LonWorks Interface Card Only)
This is an add-on card that allows the Genius controller A differential pressure switch is used to detect the availability of
to interface with LonWork network. water flow through the system. Alarm shall be activated when
• PlantWatch Pro there is no water flow detected across the system.
PlantWatch PRO is a new solution for the supervision of
Precision Air Conditioning installations, with the possibility
to connect and control up to 100 units in a serial network.
It comes with a colour LCD touch screen and practical
easy to use menus that enables simple and convenient
navigation by the users. In addition, its supervisory task
can be performed without the use of a PC (although a PC
can be connected if necessary), thus providing a perfect
solution for environments that do not use a dedicated
computer system for this purpose. For alerting purpose,
alarm messages can be send via SMS, fax or e-mail.
Version: 1.0/2009/Gen-X/E02 9
GEN-X Series Elegant Range - Engineering Data
10 Version: 1.0/2009/Gen-X/E02
Edited by Foxit Reader
Copyright(C) by Foxit Corporation,2005-2009
For Evaluation Only.
GENERAL DETAILS
MODELS 50 65 70 80 90
2
Coil Face Area m 1.6 1.9 2.3 2.7 3.0
No. of Fans - 2 2 2 3 3
Airflow m3/s 3.5 4.2 5.0 5.8 6.7
m3/hr 12600 15120 18000 20880 24120
Fan Motors kW 2 x 3.0 2 x 3.0 2 x 4.0 3 x 3.0 3 x 4.0
SPL dB(A) 71 72 72 73 74
Electric Reheat:
No. of Heater Banks - 2 2 3 3 3
Capacity kW 12 18 18 18 27
Humidifier:
kg/hr 8 15 15 15 15
Capacity
kW 6.00 11.25 11.25 11.25 11.25
Power
mm 3/4” 3/4” 3/4” 3/4” 3/4”
Feed Connection
mm 32 32 32 32 32
Drain Connection
“A” Version
Compressors Model ZR 108 125 144 160 190
No. of Compressors 2 2 2 2 2
Air Cooled Condensers Model CACR 326 326 506 506 506
No. of Air Cooled Condensers 2 2 2 2 2
Connections:
Liquid Line inch 5/8” 5/8” 3/4” 3/4” 7/8”
Discharge Line inch 1 1/8” 1 1/8” 1 1/8” 1 1/8” 1 3/8”
Condensate Drain inch 22 22 22 22 22
“W” Version
Compressors Model ZR 108 125 144 160 190
No. of Compressors 2 2 2 2 2
Air Cooled Condensers Model B 10/60 10/60 10/80 10/80 80/60
No. of Water Cooled Condensers 2 2 2 2 2
Connections:
Condenser Water In mm 42 42 54 54 54
Condenser Water Out mm 42 42 54 54 54
Condensate Drain inch 22 22 22 22 22
“DA” and “DW” Version
Connections:
Chilled Water In mm 42 42 54 54 54
Chilled Water Out mm 42 42 54 54 54
Condensate Drain inch 22 22 22 22 22
Air Filter Size
Downflow:
310X700X100 mm 4 - 2 4 -
372X700X100 mm - 4 3 2 6
Upflow:
390X800X100 mm 1 - 2 1 -
640X800X100 mm 1 2 1 2 3
Notes:
(1) For “DA” and “DW” Version DX system details, please refer to “A” and “W” Version.
(2) SPL measured at 1m distance, free field, with fans running, download version.
Version: 1.0/2009/Gen-X/E02 11
12
Notes:
PRECISION AIR CONDITIONING UNIT
2.5mm sq 3 core
interconnecting
Liquid line
Evaporator Coil.
Condensate LEGEND
Version: 1.0/2009/Gen-X/E02
GEN-X Series Elegant Range - Engineering Data
Notes:
PRECISION AIR CONDITIONING UNIT
Precision Unit
Version: 1.0/2009/Gen-X/E02
Casing
P T Discharge line
S D
Humidifier
(if fitted)
Condenser Water In
Water
Cooled
Condenser
Evaporator Coil
Liquid line
Condensate
tray
Compressor D Compressor
Discharge Valve
Electronic Expansion T
Valve Temperature Sensor
13
Edited by Foxit Reader
Copyright(C) by Foxit Corporation,2005-2009
For Evaluation Only.
CW CW
DX DX
Humidifier
400v (if fitted)
3ph + N
supply P
T
S D
P
T
S D
Condensate tray
A B
Discharge Discharge
line line
LEGEND
Access Valve S
Compressor Suction
Valve
Compressor D
Compressor Discharge
Valve
Electronic Expansion T Temperature Sensor
Valve
Modulating 2 way Pressure / Test Point
Chilled Water control Valve
14 Version: 1.0/2009/Gen-X/E02
GEN-X Series Elegant Range - Engineering Data
CW CW
DX DX
P
T
S D
400v P
3ph + N T
supply S D
Humidifier
(if fitted)
A B
A - Chilled Water In
B - Chilled Water Out
Condensate
tray
WATER COOLED CONDENSER
Humidifier Humidifier
Condensate Drain LEGEND Drain Water
Supply
Filter / Drier Ball Valve (if fitted)
Version: 1.0/2009/Gen-X/E02 15
Edited by Foxit Reader
Copyright(C) by Foxit Corporation,2005-2009
For Evaluation Only.
COOLING PERFORMANCES
MODELS 50 65 70 80 90
m3/s 3.50 4.20 5.00 5.80 6.70
Airflow
m3/hr 12600 15120 18000 20880 24120
“A” Version
Air On: 22oC, 50 %RH
Total kW 48.18 55.06 68.06 72.54 84.97
Sensible kW 40.81 47.52 57.89 63.61 73.83
S.H.R. - 0.85 0.86 0.85 0.88 0.87
16 Version: 1.0/2009/Gen-X/E02
Edited by Foxit Reader
Copyright(C) by Foxit Corporation,2005-2009
For Evaluation Only.
† - Refer to Note 3.
Notes:
Due to our policy of continuous development and improvements, the specifications and data herein are subject to change without prior notice. We
must therefore reserve the right to supply equipment that may differ from that described and illustrated herein.
All information, including illustrations, contained in this brochure, is believed to be accurate and reliable. Users, however, should independently
evaluate the suitability of each product for their own application. CITEC makes no warranties as to the accuracy or completeness of the information,
and disclaims any liability regarding this use.
Version: 1.0/2008/Gen-X/E02
1.0/2009/Gen-X/E02 17
NOTE
18 Version: 1.0/2009/Gen-X/E02