ENGINEERING DATA

GEN-X Series
Elegant Range
Air Cooled, Water Cooled and Dual Coil Systems
GEN-X Series Elegant Range - Engineering Data

Contents

Sections Page
Introduction 3
Service Entry / Access Requirements 3
Dimensions 4
Typical Airflow Arrangement 5
Guide Specifications 6
Ancillaries and Options 8
General Details 11
Schematic Diagram 12
Cooling Performances 16
Electrical Details 17

2 Version: 1.0/2009/Gen-X/E02
GEN-X Series Elegant Range - Engineering Data

INTRODUCTION

The Product
The GEN-X Elegant Range of Precision Air Conditioning Units are compact and stylish with the better performance and quality
demanded by today’s market.

These units are designed and built within a Quality Assurance System conforming to BS EN ISO 9001, using our unrivalled experience
in Precision Air Conditioning, with extensive testing of components and complete systems. Every aspect is engineered to ensure
maximum reliability, economy of operation and long working life, together with ease of installation and maintenance.

The Range
The GEN-X Elegant Range comprises four types of systems, five models in five cabinet sizes, with nominal capacities from 50 kW to
90 kW.

Key to Type Codes


Example: E X D 50 A

Model Type = A – Air Cooled (W – Water Cooled,


DA/DW – Dual Coil)

Unit Size = Nominal Capacity in KW

Airflow type = D – Downflow (U – Upflow)

Series: X = GEN-X Series

Range: E = Elegant Range

SERVICE ENTRY / ACCESS REQUIREMENTS


800

Full Front Service

Version: 1.0/2009/Gen-X/E02 3
Edited by Foxit Reader
Copyright(C) by Foxit Corporation,2005-2009
For Evaluation Only.

GEN-X Series Elegant Range - Engineering Data

DIMENSIONS
50 65

1954
1800 2050 885*

70 80

1954
2300 2550 885*

90
1954

2800 885*

Notes:
* For “DA” and “DW” version, unit depth shall be 985mm.

Model Size 50 65 70 80 90
Weight “A” (kgs) 620 725 810 910 985
“W” (kgs) 635 740 830 930 1015
“DA” (kgs) 685 802 898 1010 1098
“DW” (kgs) 700 817 918 1030 1128

4 Version: 1.0/2009/Gen-X/E02
GEN-X Series Elegant Range - Engineering Data

TYPICAL AIRFLOW ARRANGEMENT

• Type “A” - Downflow, into raised floor


return from room or ceiling.

• Type “B” - Upflow, with horizontal discharge


plenum (as shown) or room/ceiling discharge,
and front grille return.

• Type “C” - Upflow, with ceiling duct extension


and underfloor return.

Version: 1.0/2009/Gen-X/E02 5
GEN-X Series Elegant Range - Engineering Data

GUIDE SPECIFICATIONS

Cabinet Compressor and Safety Controls


The cabinets are modular design for flexibility and scalability. Fully hermetic high efficiency scroll compressor(s) are located at
The cabinets are attractively designed with rounded corners and the service section of the units. The compressor(s) is resiliently
perfect fitting panels. All Units have a rigid powder coated frame mounted on a robust frame, which assists to minimize noise
for maximum strength and corrosion protection, with hinged front and vibration transmission to the structure. Each compressor is
panels to provide easy access for installation and maintenance. fitted with back-seating isolating valves and on larger models
Panels are lined with class “O” non-eroding insulation material oil level sight glass is fitted. Protection is provided by an internal
with both thermal and acoustic properties. External panels are self-setting overload device and pressure relief valve. An external
finished with epoxy coating in dark grey colors for corners and in adjustable high pressure cut off switch; with manual reset facility
light grey colors for access door and removable panels. is provided for high pressure protection, in addition to the internal
devices. To protect primarily against loss of refrigerant charge,
Cooling Coil a pressure transducer and temperature sensor is provided to
monitor the system superheat.
The coils shall be multi-row constructed from 3/8” OD copper
tubes with aluminium fins. Large surface areas shall ensure high
Filtration
sensible heat ratios and low airside pressure drops, resulting
in reduced fan power requirements and noise levels. Main and The filters shall have an efficiency of 30% ASHRAE 52/76 Eurovent
intermediate stainless steel drain trays shall be included to ensure 4/5 arrestance value 90% (EU4). They shall be fitted in the return
efficient removal of the condensate via factory fitted traps. air stream, held by quick release retaining clips, and be accessible
from the front of the unit. A differential pressure switch shall be
Units shall have two independent refrigeration circuits, each with
fitted which, through the alarm facility in the microprocessor
a liquid distributor, electronic expansion valve, ball valve, sight
controller, shall indicate when the filters need changing.
glass and filter drier; these components to be housed in the
services section at the right hand end of the cabinet.
Humidifier
For Dual Coil units, the chilled water circuit shall be fitted with a
The humidifier is a self contained, steam generating electrode
modulating 2 way valve with manual override facility and water
boiler type with disposable cylinder, located in the bottom section
pressure / temperature test points whilst the refrigeration section
of the unit. A humidifier includes proportional steam output and
shall have two independent refrigeration circuits.
microprocessor control with alarms and diagnostic facilities. The
control system allows the use of a wide range of water conditions
Fans and optimizes drain down frequency for maximum operational
For downflow units, large, low speed, double inlet, double width economy. To avoid earth leakage, the power supply is disconnected
fans with forward curved impellers and “sealed for life” ball or from the electrodes when the system is in drain mode.
roller bearings shall be used to minimise noise levels. Units shall
have one, two or three fans, depending on size, each fan to have Electrical and Control Panel
its own TEFC motor and speed variation by manually adjustable
The electrical panel is located within the unit and shall be
pulley. Units shall include fan fail / airflow alarm which shall in the
accessible from the front. The electrical panel includes:
event of an alarm condition disable all outputs except unit run.
• Controller baseboard and interface cards (if applicable).
For upflow units, energy efficient direct driven centrifugal plug
fans with backward curve impellers shall be used. Units shall • MCB’s and contactors for fans, compressors, heaters,
have one, two or three fans, depending on size, each fan to have humidifier as appropriate.
its own integrated TEFC motor. Units shall include fan fail / airflow
• Control circuit is 24VAC Class 2 low voltage including a
alarm which shall in the event of an alarm condition disable all
circuit breaker protection (if applicable).
outputs except unit run.
Low voltage, high voltage and grounding wires are color coded
Electric Heaters and numbered, and neatly run in trunking segregating high and
low voltages.
Electric heaters shall have Incoloy sheathed elements with
stainless steel finning balanced over three phases and rated to
operate at black heat. Control shall be in two or three stages,
each being protected by a high temperature safety cut-out.

6 Version: 1.0/2009/Gen-X/E02
GEN-X Series Elegant Range - Engineering Data

GUIDE SPECIFICATIONS

Electronic Expansion Valve (EEV)


Electronic Expansion Valve (EEV) shall be fitted for each
refrigerant circuit. EEV shall have a PID modulation control and
shall be capable of responding quickly to changes in the system,
ensuring a stable superheat.

Microprocessor Controls With In-house Program


Note: For more detailed information, refer to a separate -
“Engineering Data - Genius Controller”.
A unit fitted with the Genius III Controller, an advance
microprocessor controlling system developed by CITEC to
control and monitor the air conditioning unit. This provides
maximum economy in operation, a comprehensive intelligent
alarm system and a wide range of information for operators
and service engineers. The controller provides a user-friendly
environment to ease the system setup and operation.
In addition to precise control of temperature and humidity, the
system includes the following features:
Graphical icon functions: Unit Run, Cooling, Heating, Humidifying,
Dehumidifying and Alarm.
i) Auto Sequencing with either Automatic Rotation or Timezone
Rotation.
ii) Coded security access for set point parameter adjustment.
iii) Supporting various communication protocols whilst
maintaining a stable and reliable environment.
iv) Three choices of user interface, i.e. Liquid Crystal Display,
Monochrome Touch Screen Display and Colour Touch
Screen Display to satisfy wide range of application.
a) Basic LCD Display (CGD1) if selected indicates unit
function via icons, display control conditions and report
alarm events.
b) Touch Screen graphical display if selected allows
the management of complex graphical images up
to 320x240 pixels in size and with up to 256 colours
(CGD3 only), indicating function via various animated
icons, non-proportional fonts in Unicode format, alarms,
and trend graphs of temperature and humidity.
Versions available:
• Monochrome Touch Screen Version (CGD2)
• Colour Touch Screen Version (CGD3)

Version: 1.0/2009/Gen-X/E02 7
GEN-X Series Elegant Range - Engineering Data

ANCILLARIES AND OPTIONS

Ceiling Return Duct L.P.H.W. Heating


Ceiling return duct comprises unit matched panels lined with Units may be fitted with a Low Pressure Hot Water heating coil
25mm thick insulation bolted to the top of the Precision Air in place of the standard electrical heating. A modulating 2 way
Conditioning Unit on site. The duct is suitable for downflow units valve controls water flow through the coil.
only. Information on the height between the top of the Precision
Duties of these coils are nominally the same as standard electric
Air Conditioning Unit and the underside of the suspended ceiling
heating, based on flow and return hot water temperatures of
is needed when ordering. The overall height of the duct will be
82ºC and 71ºC respectively.
this dimension plus 50mm.
Note: Please consult factory before ordering.
Horizontal Discharge Section (Upflow Models
Only) Water Detection Kit
Horizontal discharge section consists of a double deflection grille Water sensors, connected directly to the Precision Air Conditioning
fitted into a rigid sheet metal box. The complete assembly is Unit microprocessor control system, are located in:-
bolted to the top of the Precision Air Conditioning Unit on site.
• Condensate drain pan – detecting undue water level.
The grille has two sets of blades, which allow for both vertical
and horizontal directional adjustment of airflow. The standard • Underfloor water tape, supplied loose with sufficient length
height for this section is 500mm. of cable to cover the entire length of the respective unit.
When water is detected, the Precision Air Conditioning Unit’s
Ceiling Discharge Section
alarm system is triggered and it shall stop the unit operation
For upflow units, where the Precision Air Conditioning Unit is (selectable option).
required to discharge into the ceiling void, a Ceiling Discharge
Extension is available. This consists of a rigid riveted sheet metal Sump Pump
assembly comprising of unit matched front; rear and end panels
Where, due to location, it is not possible to gravity drain units, a
lined with 25mm thick insulation. The extension is bolted to the
sump pump can be fitted to collect any condensate and pump
top of the Precision Air Conditioning Unit on site. Information on
it to the nearest convenient drain point (maximum available
height between the top of the Precision Air Conditioning Unit and
pump head 5.7 meters). For units fitted with humidifiers, a larger
the underside of the suspended ceiling is needed when ordering.
capacity sump pump is available to accommodate the additional
The overall height of the duct will be this dimension plus 50mm.
discharge of hot water during humidifier drain down cycles
(maximum available pump head 7 meters).
High Efficiency Filters
Note: When using sump pump a minimum of a 200mm high
High efficiency filters can be provided in place of the standard
plinth is required.
filters, with an efficiency of 80% ASHRAE52/76 (Eurovent F7).
These filters are fitted in the return air side of the Precision Air
EC Fan
Conditioning Unit within the main cabinett.
The Electronically Commutated Fan (EC Fan) is the state of the art
Serviceable Type Humidifier high efficiency direct driven backward curved fan with integrated
variable speed control capability. EC fans enable flexible air
The life of a humidifier bottle is considered over when the build up
volume control with highest efficiency operation. In addition,
of solid coats the electrodes such that full current levels can no
power consumption of EC fan is much lower than conventional
longer be achieved. A serviceable system can reuse the humidifier
AC fan and more reliable. In auto mode, fan speed will adjust
bottle, thereby dramatically increases the service life of the cylinder
accordingly to suit room’s cooling load, thereby providing further
and hence provides much reduced maintenance costs, particularly
energy saving.
in areas where the available water supply is a limitation.
Differential Pressure Transmitter
The transmitter is used to detect the pressure difference
between the room and the underfloor. This option is usually
used together with the frequency inverter or variable speed fan,
to maintain a constant pressure difference between the room
and the underfloor.

8 Version: 1.0/2009/Gen-X/E02
GEN-X Series Elegant Range - Engineering Data

ANCILLARIES AND OPTIONS

Remote Control and Supervisory Systems Fan Speed Controller (Air Cooled System Only)
Note: For more detailed information, refer to separate - Use to maintain the condensing pressure and thus condensing
“Engineering Data - Genius Controller”. temperature of the refrigerant system by modulating the fan speed
of the outdoor air cooled condenser. This is to ensure that the
The Control & Supervisory System is required to develop a
condensing pressure does not drop below the operational limit of
balanced function between economics, operating costs, safety
the compressor thereby damaging it. A pressure sensing probe is
and comfort with human considerations being most important.
attached to the discharge line to measure the condensing pressure
• Webgate and send its reading to the controller which in turn gives a 0 to
Webgate is an innovative electronic device that measures 10Vdc analogue signal to the FSC module to modulate the fan
the same size as a normal desktop modem. It can speed of the air cooled condenser.
connect the Genius controller to a local network based
on the standard Ethernet and TCP/IP protocol. Frequency Inverter
• pCOWEB The purpose of the frequency inverter is to vary the fan speed
of the unit by changing the frequency of the power supply to
pCOWEB is an add-on card that allows communication
the fan. In auto mode, fan speed will adjust accordingly to suit
between the Genius controller with BACnet Ethernet,
room’s cooling load.
BACnet over IP, SNMP protocol (v1 & v2c), HTTP
protocol, FTP and DHCP protocol.
Split Units
• pCONET
The coil/fan section & the compressor section of the unit can
pCONET is an add-on card that allows communication be split into 2 separate sections to allow transportation / access
with the BACnet MS/TP protocol. to areas with limited space. All access panels could also be
• Telemon removed & packaged separately. The 2 sections & the panels
could then be reassembled at site. All electrical cables crossing
Telemon designed to proactively monitor and control
the 2 sections should also be reconnected at site. These cables
Precision Air Conditioning Units in a critical environment.
are coiled in a tidy fashion for transit & will be labeled for easy
It monitors and changes the parameters of a precision air
identification. For the pipework, some brazing work would be
conditioning unit such as temperature, humidity, cooling &
required at site. All piping will be solder type by default unless
heating demands, rotation configuration and time control.
specified otherwise. The 2 sections could also be placed &
• PlantVisor crated separately as an additional option.
Plantvisor, with its web server function, can work on PCs
connected in an TCP/IP network. This allows sharing the Floor Sealing Plate (Upflow Models Only)
data and information dealt with by the plantvisor with A sealing plate can be provided to seal the bottom section of the
more than one user at the same time. upflow models to prevent air from being bypassed through the
• RS485 Serial Card bottom of the unit instead of from front grille. This would not be
necessary if unit is sitting on a solid floor.
This is an add-on card which allows the Genius controller
to interface directly with a RS485 supervisory network.
Water Flow Detection (Chilled Water System
• LonWorks Interface Card Only)
This is an add-on card that allows the Genius controller A differential pressure switch is used to detect the availability of
to interface with LonWork network. water flow through the system. Alarm shall be activated when
• PlantWatch Pro there is no water flow detected across the system.
PlantWatch PRO is a new solution for the supervision of
Precision Air Conditioning installations, with the possibility
to connect and control up to 100 units in a serial network.
It comes with a colour LCD touch screen and practical
easy to use menus that enables simple and convenient
navigation by the users. In addition, its supervisory task
can be performed without the use of a PC (although a PC
can be connected if necessary), thus providing a perfect
solution for environments that do not use a dedicated
computer system for this purpose. For alerting purpose,
alarm messages can be send via SMS, fax or e-mail.

Version: 1.0/2009/Gen-X/E02 9
GEN-X Series Elegant Range - Engineering Data

ANCILLARIES AND OPTIONS

Water Temperature Sensor (Chilled Water and


Water Cooled Systems Only)
The water temperature sensor is use for sensing the water in
from the cooling water source and water out temperature reading
from the unit.

Double Skin Panels


To reduce sound “break-out”, double skin panels are available.
The standard double skin panel consist of standard 25mm class
“O” insulation glued to the inside of the external panels which is
sandwiched between external panel and a 1mm thick galzanised
sheet. Double skin panels should preferably be specified with
Compression Locks because of their extra weight and to ensure
tight closure.

Fire Alarm Relay


A 24Vdc relay is used to receive external signal 24Vdc, probably
from fire control panel. When the signal is received, unit shall
stop operation.

Hot Gas Bypass (Air Cooled and Water Cooled


Systems Only)
DX models can be fitted with hot gas bypass compressor
capacity control. This consists of a solenoid valve & a hot gas
bypass valve located in between the discharge line & at a point
after the EEV & before the coil inlet. A sensing line will be fitted
to the suction & the hot gas valve can be adjusted to bypass
discharge gas accordingly to maintain the pressure at the suction
line above the preset level.

Water Regulating Valve (Water Cooled Systems


Only)
Used to maintain the condensing pressure and thus condensing
temperature of the refrigerant system by modulating the
amount of water flow into the water cooled condenser. This is
to ensure that the condensing pressure does not drop below
the operational limit of the compressor thereby damaging it. A
pressure line from the valve is attached to the discharge line to
sense the condensing pressure.

Note: Please note that certain combinations of options


are not available while some other combinations
might require further upgrades or additional
accessories to be added. To check whether
a certain combination of options is available,
please consult factory.

10 Version: 1.0/2009/Gen-X/E02
Edited by Foxit Reader
Copyright(C) by Foxit Corporation,2005-2009
For Evaluation Only.

GEN-X Series Elegant Range - Engineering Data

GENERAL DETAILS

MODELS 50 65 70 80 90
2
Coil Face Area m 1.6 1.9 2.3 2.7 3.0
No. of Fans - 2 2 2 3 3
Airflow m3/s 3.5 4.2 5.0 5.8 6.7
m3/hr 12600 15120 18000 20880 24120
Fan Motors kW 2 x 3.0 2 x 3.0 2 x 4.0 3 x 3.0 3 x 4.0
SPL dB(A) 71 72 72 73 74
Electric Reheat:
No. of Heater Banks - 2 2 3 3 3
Capacity kW 12 18 18 18 27
Humidifier:
kg/hr 8 15 15 15 15
Capacity
kW 6.00 11.25 11.25 11.25 11.25
Power
mm 3/4” 3/4” 3/4” 3/4” 3/4”
Feed Connection
mm 32 32 32 32 32
Drain Connection
“A” Version
Compressors Model ZR 108 125 144 160 190
No. of Compressors 2 2 2 2 2
Air Cooled Condensers Model CACR 326 326 506 506 506
No. of Air Cooled Condensers 2 2 2 2 2
Connections:
Liquid Line inch 5/8” 5/8” 3/4” 3/4” 7/8”
Discharge Line inch 1 1/8” 1 1/8” 1 1/8” 1 1/8” 1 3/8”
Condensate Drain inch 22 22 22 22 22
“W” Version
Compressors Model ZR 108 125 144 160 190
No. of Compressors 2 2 2 2 2
Air Cooled Condensers Model B 10/60 10/60 10/80 10/80 80/60
No. of Water Cooled Condensers 2 2 2 2 2
Connections:
Condenser Water In mm 42 42 54 54 54
Condenser Water Out mm 42 42 54 54 54
Condensate Drain inch 22 22 22 22 22
“DA” and “DW” Version
Connections:
Chilled Water In mm 42 42 54 54 54
Chilled Water Out mm 42 42 54 54 54
Condensate Drain inch 22 22 22 22 22
Air Filter Size
Downflow:
310X700X100 mm 4 - 2 4 -
372X700X100 mm - 4 3 2 6
Upflow:
390X800X100 mm 1 - 2 1 -
640X800X100 mm 1 2 1 2 3
Notes:
(1) For “DA” and “DW” Version DX system details, please refer to “A” and “W” Version.
(2) SPL measured at 1m distance, free field, with fans running, download version.
Version: 1.0/2009/Gen-X/E02 11
12
Notes:
PRECISION AIR CONDITIONING UNIT

Precision Unit AIR COOLED CONDENSER


Casing
P T Discharge line
S D

2.5mm sq 3 core
interconnecting

This schematic depicts a single circuit only.


Humidifier cable per circuit.
(if fitted)

Liquid line
Evaporator Coil.

Condensate LEGEND

Refer to General Details for actual number of circuits per model.


tray
Filter / Drier Ball Valve

Sight Glass P Pressure


Transducer

Condensate 400v Humidifier Access Valve S Compressor Suction


Humidifier
SCHEMATIC DIAGRAM: “A” VERSIONS

Drain 3ph + N Drain Water Supply Valve


supply (if fitted)
Compressor D Compressor
Discharge Valve
Electronic Expansion T
Valve Temperature Sensor

Version: 1.0/2009/Gen-X/E02
GEN-X Series Elegant Range - Engineering Data
Notes:
PRECISION AIR CONDITIONING UNIT

Precision Unit

Version: 1.0/2009/Gen-X/E02
Casing
P T Discharge line
S D

Condenser Water Out

Humidifier
(if fitted)
Condenser Water In
Water

This schematic depicts a single circuit only.


GEN-X Series Elegant Range - Engineering Data

Cooled
Condenser
Evaporator Coil
Liquid line

Condensate
tray

Refer to General Details for actual number of circuits per model.


400v Humidifier LEGEND
Condensate Humidifier
Drain 3ph + N Drain Water Supply
supply (if fitted) Ball Valve
Filter / Drier

Sight Glass P Pressure


Transducer
SCHEMATIC DIAGRAM: “W” VERSIONS

Access Valve S Compressor Suction


Valve

Compressor D Compressor
Discharge Valve
Electronic Expansion T
Valve Temperature Sensor

13
Edited by Foxit Reader
Copyright(C) by Foxit Corporation,2005-2009
For Evaluation Only.

GEN-X Series Elegant Range - Engineering Data

SCHEMATIC DIAGRAM: “DA” VERSIONS

PRECISION AIR CONDITIONING UNIT

Precision Unit Casing

CW CW

DX DX

Humidifier
400v (if fitted)
3ph + N
supply P
T
S D
P
T

S D

Condensate tray
A B

A - Chilled Water In Humidifier Humidifier


Condensate Drain Drain Water
B - Chilled Water Out Supply
(if fitted)
2.5mm sq 3 core 2.5mm sq 3 core
interconnecting cable interconnecting cable
per circuit. per circuit.

AIR COOLED CONDENSER AIR COOLED CONDENSER

Discharge Discharge
line line

Liquid line Liquid line

LEGEND

Filter / Drier Ball Valve

Sight Glass P Pressure Transducer

Access Valve S
Compressor Suction
Valve
Compressor D
Compressor Discharge
Valve
Electronic Expansion T Temperature Sensor
Valve
Modulating 2 way Pressure / Test Point
Chilled Water control Valve

14 Version: 1.0/2009/Gen-X/E02
GEN-X Series Elegant Range - Engineering Data

SCHEMATIC DIAGRAM: “DW” VERSIONS

PRECISION AIR CONDITIONING UNIT

Precision Unit Casing

CW CW

DX DX

P
T
S D
400v P
3ph + N T
supply S D
Humidifier
(if fitted)

A B

A - Chilled Water In
B - Chilled Water Out

Condensate
tray
WATER COOLED CONDENSER

Humidifier Humidifier
Condensate Drain LEGEND Drain Water
Supply
Filter / Drier Ball Valve (if fitted)

Sight Glass P Pressure Transducer


Access Valve S
Compressor Suction
Cooling Tower Valve
Compressor D Compressor Discharge
(Field Supplied) Valve
Electronic Expansion T Temperature Sensor
Valve
Modulating 2 way Pressure / Test Point
Chilled Water control Valve

Version: 1.0/2009/Gen-X/E02 15
Edited by Foxit Reader
Copyright(C) by Foxit Corporation,2005-2009
For Evaluation Only.

GEN-X Series Elegant Range - Engineering Data

COOLING PERFORMANCES

MODELS 50 65 70 80 90
m3/s 3.50 4.20 5.00 5.80 6.70
Airflow
m3/hr 12600 15120 18000 20880 24120
“A” Version
Air On: 22oC, 50 %RH
Total kW 48.18 55.06 68.06 72.54 84.97
Sensible kW 40.81 47.52 57.89 63.61 73.83
S.H.R. - 0.85 0.86 0.85 0.88 0.87

Air On: 24oC, 45 %RH


Total kW 49.55 56.85 70.02 74.54 87.23
Sensible kW 44.10 51.43 62.57 68.53 79.44
S.H.R. - 0.89 0.90 0.89 0.92 0.91
“W” Version
Air On: 22oC, 50 %RH
Total kW 50.94 59.81 69.41 76.49 92.74
Sensible kW 42.29 50.05 58.60 65.93 78.45
S.H.R. - 0.83 0.84 0.84 0.86 0.85
Condenser Water Flow Rate l/s 2.35 3.26 4.30 5.28 7.60
Unit Pressure Drop kPa 15.70 21.40 20.90 25.50 51.90
Air On: 24oC, 45 %RH
Total kW 52.25 61.39 71.33 78.96 95.32
Sensible kW 45.62 54.02 63.29 71.36 84.74
S.H.R. - 0.87 0.88 0.89 0.90 0.89
Condenser Water Flow Rate l/s 3.13 3.69 4.25 4.71 5.65
Unit Pressure Drop kPa 16.30 22.30 22.00 26.80 54.50
Chilled Water Coil Performance of “DA” and “DW” Version
Air On: 22oC, 50 %RH
Total kW 43.48 51.78 61.12 72.16 79.60
Sensible kW 38.78 46.26 54.68 64.36 71.58
S.H.R. - 0.89 0.89 0.90 0.89 0.90
Chilled Water Flow Rate l/s 2.08 2.48 2.92 3.44 3.80
Unit Pressure Drop kPa 18.20 29.70 20.80 30.90 14.20
Air On: 24oC, 45 %RH
Total kW 50.30 59.96 70.98 83.50 93.78
Sensible kW 45.20 53.96 64.00 75.02 84.70
S.H.R. - 0.90 0.90 0.90 0.90 0.90
Chilled Water Flow Rate l/s 2.40 2.86 3.40 3.98 4.48
Unit Pressure Drop kPa 24.30 38.60 27.30 40.80 19.60
Notes:
Cooling performances are GROSS and based on:
(1) Standard EU4 filtration and 50 Pa external static.
(2) Performance at ambient temperature 35ºC.
(3) Standard matching condenser.
(4) 0.5ºC suction line loss.
(5) R407C Refrigerant.
(6) Chilled water in/out based on 7/12ºC, Condenser water in/out based on 30/35ºC.

16 Version: 1.0/2009/Gen-X/E02
Edited by Foxit Reader
Copyright(C) by Foxit Corporation,2005-2009
For Evaluation Only.

GEN-X Series Elegant Range - Engineering Data

ELECTRICAL DETAILS: 400 VOLT / 3 PH+N / 50 HZ

“A” / “DA” Versions


MODELS 50 65 70 80 90
Operating Amps † FLA 49.3 60.9 69.3 77.2 93.3

Connected Loads Amps† CLA 60.0 76.0 86.1 95.0 112.8

Maximum Inrush Amps † LRA 158.3 182.6 190.7 238.5 281.2

Operating kW kW 26.8 35.1 39.2 42.9 52.5

Connected Load kW kW 34.2 45.1 50.7 55.0 63.6

“W” / “DW” Versions


MODELS 50 65 70 80 90
Operating Amps † FLA 46.8 58.4 64.3 72.2 88.3

Connected Loads Amps† CLA 57.5 73.5 81.1 90.0 107.8

Maximum Inrush Amps † LRA 155.8 180.1 185.7 233.5 276.2

Operating kW kW 26.2 35.1 38.1 41.8 51.4

Connected Load kW kW 33.6 44.5 49.6 53.8 62.5

† - Refer to Note 3.

Notes:

(1) Controls are 24 volt.


(2) Data may vary slightly depending on operating conditions.
(3) Maximum values depend on worst condition when operating automatically and could be:
(a) Fans + Cooling + Humidifying
(b) Fans + Heating + Humidifying
(c) Fans + Cooling + Reheating (Dehum)

Due to our policy of continuous development and improvements, the specifications and data herein are subject to change without prior notice. We
must therefore reserve the right to supply equipment that may differ from that described and illustrated herein.
All information, including illustrations, contained in this brochure, is believed to be accurate and reliable. Users, however, should independently
evaluate the suitability of each product for their own application. CITEC makes no warranties as to the accuracy or completeness of the information,
and disclaims any liability regarding this use.

Version: 1.0/2008/Gen-X/E02
1.0/2009/Gen-X/E02 17
NOTE

18 Version: 1.0/2009/Gen-X/E02
NOTE

Version: 1.0/2009/Gen-X/E02 19
CITEC INTERNATIONAL SDN. BHD. (372827-H)
No. 47, (PT 63846), Lorong Jala 14/KS10, Telok Gong,
42000 Port Klang, Selangor Darul Ehsan, Malaysia .
Tel: +603 3134 2668 Fax: +603 3134 2648
Website: www.citec.com.my
Email: enquiry@citec.com.my

Version: 1.0/2009/Gen-X/E02