ELECTRICAL BOARDS FOR REFRIGERATING INSTALLATIONS

products index slim base kit


04
ECP300 EXPERT vd
24
ecp__ VD T
44
A001 C003 f001

ecp 200 base ECP300 EXPERT u vd ecp__ T U


06 26 46
A002 C004 f002

ecp__ base4 vd Plus300 EXPERT vd plus200 2plt


08 28 48
A003 C005 g001

ecp__ base4 u vd Plus300 EXPERT u VD plus100 thr


10 30 50
a004 C006 g002

plus1000 thr ecp 04 plus100 ab


12 32 52
B004 d001 g003

plus dl1 ecp 07 10 15 plus100 PAN


14 34 54
B005 d002 g004

Plus EXPERT dl3 ecp__ VD SC 600


16 36 56
b006 e001 g005

ECP200 EXPERT ecp__ VD cr telenet


20 38 58
C001 e002 z001

plus200 EXPERT ecp2000 VD cr ecp ape 03


22 40 60
C002 e003 z002

 
slim base kit Single-phase systems
SLIM series
A001.gb.02

The quickest, most economic cold room control


solution.

74
Out-of-room unit complete with assembly kit for
direct control of compressor up to 1 HP or to re-
mote control of the power board.
215 83

APPLICATIONS Slim Base2 K TECHNICAL CHARACTERISTICS Slim Base2 K Slim Base4 K

Weight 0,7 Kg 0,8 Kg


• Single-phase system with compressor up to 1 HP. Suitable for single-phase systems with programmable
Protection rating IP 55 IP 55
• Out-of-room unit for remote control of power off-cycle defrost.
Power supply 230 V AC ±10% 50/60Hz 230 V AC ±10% 50/60Hz
board. Controls:
Load type Single-phase Single-phase
• Room light ON/OFF (door switch). Working temperature -5 ÷ +50 °C -5 ÷ +50 °C
• System ON/OFF. Storage temperature -10 ÷ +70 °C -10 ÷ +70 °C
MAIN CHARACTERISTICS • Compressor enabling. Relative ambient humidity < 90% Rh < 90% Rh
• Self-extinguishing ABS keyboard/display with • Warning buzzer. Range of reading -45 ÷ +45 °C -45 ÷ +45 °C
IP55 protection rating. Defrost Off-cycle Electrical
• Compact.
Slim Base4 K Status indicators LED + Display LED + Display
• Innovative design. Alarm signals LED + Buzzer LED + Buzzer
• Complete assembly kit. Suitable for single-phase systems with programmable Inputs
electrical defrost. Ambient probe NTC 10 kΩ NTC 10 kΩ
Controls: Evaporator probe NTC 10 kΩ
• Room light ON/OFF (door switch). Door switch Present Present
• System ON/OFF. outputs
• Compressor enabling. Compressor 750 W (1 HP) 750 W (1 HP)
• Defrost elements. Evaporator fans 250 W
• Evaporator fans. Defrost 1500 W (ac1)
• Warning buzzer. Cold room light 400 W (ac1) 400 W (ac1)

Connection diagrams

The compact case contains everything required


by the installer and a practical assembly guide.
230 Vac 230 Vac
Slim100 Base2 Slim100 Base4

 
ecp 200 base Single-phase systems
Base series
A002.gb.02

193
A line of control panels for cold rooms with single-
phase compressor up to 2 HP, specially designed to
provide greater flexibility at a competitive cost.

203 79

MAIN CHARACTERISTICS ECP200 Base2 TECHNICAL CHARACTERISTICS ECP200 Base2 ECP200 Base4

Direct control of compressor, defrosting heaters, Allows user to control compressor and cold room Weight 0,5 Kg 0,5 Kg
evaporator fans and room light using free-voltage light. Configurable auxiliary relay or alarm output also Protection rating IP 65 IP 65
contacts. available on the ECP200 Base 2A version. Power supply 230 V AC ±10% 50/60Hz 230 V AC ±10% 50/60Hz

Compact, self-extinguishing ABS housing with Applications: Load type Single-phase Single-phase
Working temperature -5 ÷ +50°C -5 ÷ +50°C
IP65 protection rating. On “A” versions there is an • Single-phase system up to 2 HP, off-cycle
Storage temperature -10 ÷ +70°C -10 ÷ +70°C
auxiliary relay with parameter-configurable activation defrosting.
Relative ambient humidity < 90% Rh < 90% Rh
(alarm, temperature set-point, direct frontal • Remote control for compressor enabling to be
RANGE of reading -45 ÷ +45 °c -45 ÷ +45 °c
pushbutton control, door heater elements, freon linked to power board.
Defrost Off-cycle Electrical
solenoid control where pump-down compressor
Status indicators LED + Display LED + Display
operation is applied). Alarm signals LED + Buzzer LED + Buzzer
RS485 for connection to TeleNET industrial ECP200 Base4 Inputs
supervision network. Allows user to control all the components on the Ambient probe NTC 10 kΩ NTC 10 kΩ
refrigeration system: compressor, evaporator fans, Evaporator probe NTC 10 kΩ
defrosting heaters and room light. Configurable Overload protection Present Present

auxiliary relay or alarm output also available on the Door switch Present Present
outputs
ECP200 Base 4A version.
Compressor 1500 W (2 HP) 1500 W (2 HP)
Applications:
Defrost 3000 W (AC1)
• Single-phase static or ventilated system up to 2
Evaporator fans 500 W
HP, off-cycle or electrical defrosting with direct
Cold room light 800 W (AC1) 800 W (AC1)
compressor shutdown (or in pump-down mode,
Alarm relay / Aux PRESENT PRESENT
on the ECP 200 BASE4 A version). (contatto libero da tensione) (On “A” versions only) (On “A” versions only)

• Remote control for compressor, defrosting and Supervision system TeleNET TeleNET
230 V AC
SUPPLY
POWER

fans enabling to be linked to power board.


• Device of single-phase evaporating unit with cold
solenoid valve or remote motor condenser unit
enabling.
OPTIONAL SCHINT230 KIT
To make the installer’s task even easier we have
created the SCHINT 230 kit: this converts the
free-voltage contacts into live outputs (230 V AC)
for control of the various devices. There are also
terminals for connection of the PE circuit.
230 V AC
SUPPLY
POWER

 
ecp__ base4 vd Three-phase systems
Base series
A003.gb.02
ECP300 Base4 VD | ECP400 Base4 VD
ECP750 Base4 VD | ECP1000 Base4 VD

A line of control panels for cold rooms with three-


phase compressor up to 10 HP, specially designed
for complete cold room management.
Together with the various options, the different power

450
ranges allow the user to select a unit that is “custom-

340
made” to suit the refrigeration system.

290 145 350 160

APPLICATIONS MAIN CHARACTERISTICS TECHNICAL CHARACTERISTICS ECP300 Base4 VD ECP400 Base4 VD ECP750 Base4 VD ECP1000 Base4 VD

• Complete control of three-phase static or • Direct control of compressor, condenser fans, Box dimensions 290 x 340 x 145 mm 350 x 450 x 160 mm 350 x 450 x 160 mm 350 x 450 x 160 mm
Weight 5 Kg 6 Kg 6 Kg 7 Kg
ventilated refrigeration systems up to 10 HP, compressor oil heater, defrosting heaters,
Protection rating IP 65 IP 65 IP 65 IP 65
off-cycle or electrical defrosting. evaporator fans, solenoid valve, room light and all 400 V AC ±10% 400 V AC ±10% 400 V AC ±10% 400 V AC ±10%
Power supply
standard-compliant electrical protection devices. 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz
Load type Three-phase Three-phase Three-phase Three-phase
• Compact, self-extinguishing ABS housing with
OPTIONS IP65 protection rating and frontal circuit-breaker.
Working temperature -5 ÷ +50°C -5 ÷ +50°C -5 ÷ +50°C -5 ÷ +50°C
Storage temperature -10 ÷ +70°C -10 ÷ +70°C -10 ÷ +70°C -10 ÷ +70°C
• Installation of magnetothermic protection • Electronic control with wide LED display and Relative ambient humidity < 90% Rh < 90% Rh < 90% Rh < 90% Rh

devices instead of fuses. user-friendly keypad. RANGE of reading -45 ÷ +45 °c -45 ÷ +45 °c -45 ÷ +45 °c -45 ÷ +45 °c
Main switch 16 A 32 A 32 A 32 A
• Alarm output with free-voltage contact to activate • System status indicated by icons.
Overload protection Thermal relay Thermal relay Thermal relay Thermal relay
further warning devices such as siren or dialler. • RS485 for connection to TeleNET industrial General protection Fuses Fuses Fuses Fuses
• Pump-down compressor stop. supervision network. Control PEGO PEGO PEGO PEGO
• Hot-gas defrost control. Defrosting Electrical Electrical Electrical Electrical
Insulation transformer PRESENT PRESENT PRESENT
Status indicators LED + Display LED + Display LED + Display LED + Display
Alarm signals LED + Buzzer LED + Buzzer LED + Buzzer LED + Buzzer
Inputs
Ambient probe NTC 10 kΩ NTC 10 kΩ NTC 10 kΩ NTC 10 kΩ
Evaporator probe NTC 10 kΩ NTC 10 kΩ NTC 10 kΩ NTC 10 kΩ
Door switch Present Present Present Present

CONNECTION DIAGRAMS Oil differential pressure switch Present


High/low pressure switch Present Present Present Present
Kriwan® connection Present Present Present
outputs
Compressor 2200 W (0,5÷3 HP) 2200÷3000 W (3÷4 HP) 3000÷5500 W (4÷7,5 HP) 5500÷7500 W (7÷10 HP)
Condenser fans output 1 800 W (1 ph) 800 W (1 ph) 800 W (1 ph) 2000 W (1 ph / 3ph)
Condenser fans output 2 (separated) total (1 ph) total (1 ph) 2000 W (1 ph / 3ph)
Evaporator fans 800 W (1 ph) 2000 W (1 ph) 2000 W (1 ph) 2000 W (1 ph / 3ph)
Defrosting heaters 4000 W (AC1) 7500 W (AC1) 9000 W (AC1) 12000 W (AC1)
Room light Present Present Present Present
Solenoid valve Present Present Present Present
Compressor oil heater Present Present Present
PRESENT PRESENT PRESENT PRESENT
Alarm relay
( on request ) ( on request ) ( on request ) ( on request )
Supervision system TeleNET TeleNET TeleNET TeleNET

 
ecp__ base4 u vd Three-phase units
Base series
A004.gb.02
ECP300 Base4 U VD | ECP400 Base4 U VD
ECP750 Base4 U VD | ECP1000 Base4 U VD

A line of power and electronic control panels to man-


age the three-phase evaporating unit only where de-
vices are served by a compressor rack.
Various power ranges and a wide range of optionals al-

450
low you to choose the panel best suited to your system.

340
290 145 350 160

APPLICATIONS MAIN CHARACTERISTICS TECHNICAL CHARACTERISTICS ECP300 Base4 U VD ECP400 Base4 U VD ECP750 Base4 U VD ECP1000 Base4 U VD

• Enabling for condensing unit, defrosting Box dimensions 290 x 340 x 145 mm 350 x 450 x 160 mm 350 x 450 x 160 mm 350 x 450 x 160 mm
• Control of evaporating unit only with electrical
Weight 5 Kg 6 Kg 6 Kg 7 Kg
defrost up to 12 kW. elements, evaporator fans, solenoid valve,
Protection rating IP 65 IP 65 IP 65 IP 65
room light and all standard-compliant electrical 400 V AC ±10% 400 V AC ±10% 400 V AC ±10% 400 V AC ±10%
Power supply
OPTIONS safeguards. 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz

• Compact, self-extinguishing ABS housing with Load type Three-phase Three-phase Three-phase Three-phase
• Magnetothermic circuit breakers installed Working temperature -5 ÷ +50°C -5 ÷ +50°C -5 ÷ +50°C -5 ÷ +50°C
IP65 protection rating and circuit breaker on front
instead of fuses. Storage temperature -10 ÷ +70°C -10 ÷ +70°C -10 ÷ +70°C -10 ÷ +70°C
of panel.
• Free-voltage contact alarm output to activate Relative ambient humidity < 90% Rh < 90% Rh < 90% Rh < 90% Rh
• Control electronics with large backlit LCD and RANGE of reading -45 ÷ +45 °c -45 ÷ +45 °c -45 ÷ +45 °c -45 ÷ +45 °c
other warning devices such as sirens or dialers.
user-friendly keypad. Main switch 16 A 32 A 32 A 32 A
• LED system status indicators. General protection Fuses Fuses Fuses Fuses
Control PEGO PEGO PEGO PEGO
• RS485 for connection to TeleNET industrial
Defrosting Electrical Electrical Electrical Electrical
supervision network.
Insulation transformer PRESENT PRESENT PRESENT
Status indicators LED + Display LED + Display LED + Display LED + Display
Alarm signals LED + Buzzer LED + Buzzer LED + Buzzer LED + Buzzer
Inputs
Ambient probe NTC 10 kΩ NTC 10 kΩ NTC 10 kΩ NTC 10 kΩ
Evaporator probe NTC 10 kΩ NTC 10 kΩ NTC 10 kΩ NTC 10 kΩ
CONNECTION DIAGRAMS Door switch Present Present Present Present
Man in cold-room alarm Available Available Available Available
outputs

Evaporator fans 500 W (1 ph) 2000 W (1 ph) 2X 2000 W (1 ph) 3X 2000 W (1 ph / 3ph)

Defrosting heaters 4000 W 7500 W 9000 W 12000 W


Room light Present Present Present Present
Solenoid valve Present Present Present Present
Enable condensing unit Present Present Present Present
PRESENT PRESENT PRESENT PRESENT
Alarm relay
( on request ) ( on request ) ( on request ) ( on request )
Supervision system TeleNET TeleNET TeleNET TeleNET

10 11
plus1000 thr Three-phase seasoning
Plus Series
b004.GB.02

plus1000 thr (CR)

plus100 thr

Three-phase electric panel with control of tempera-


ture and humidity plus seasoning functions.

98 ( x 180 )
Flexible programming also makes it suitable for sim-

110

450
ple storage purposes.
Programming up to five formula, of seven phases
each, settable and customizable.

210 35

350 160

APPLICATIONS PLUS THR ELECTRONIC TECHNICAL CHARACTERISTICS Plus1000 THR


Plus100 THR +
Plus1000 THR CR
• Seasoning/drying rooms. CONTROLLER FUNCTIONS Weight 6 Kg 5.5 Kg (+0.7 Kg keyboard/display )
• Germination room with day/night phases. • Backlit LCD display. Protection rating IP 65 IP 65
• Storage rooms with or without humidity control. • Clock and calendar function. Status indicators Display LCD Display LCD
• Manual or automatic work mode. Alarm signals Display LCD + Buzzer Display LCD + Buzzer

• Up to 5 formula completely customazible. Control PEGO THR (integrated) PEGO THR (remote)
Available configurations Automatic management of 7 phases for each Power supply 400 V AC ±10% 50/60 Hz Other characteristics
Load type Three-phase such as PLUS1000 THR
• Plus1000 THR power board with integrated formula (dripping first phase, seasoning/
Working temperature -5 ÷ +50°C
electronics. conservation last phase). Simple programming
Storage temperature -10 ÷ +70°C
• Plus100 THR + Plus1000 THR CR and selection of set formula. Possibility of joining
Relative ambient humidity < 90% Rh
with remote keyboard/display separate from together more formula for exceeding the 7
range of reading -45 ÷ +45 °c
power board (THR CR). phases limit. Main switch 32 A
PLUS100 THR
• Heat and humidity can be excluded so as to Overload protection Thermal relay
manage storage room only with activation of General protection Fuses
opzioni defrosts.
Defrosting Off-cycle
• Plus1000 THR SE version with electric defrost. • Temperature to one decimal point. (Electrical on request)

INPUTS
• Plus1000 THR M single-phase version. • Keypad lock password.
Ambient probe NTC 10 kΩ
• Special boards available for dedicated applications. • Day/night cycle for germination systems with
Evaporator probe NTC 10 kΩ
double temperature set-point.
Humidity probe 4 ÷ 20 mA 0 ÷ 100% Rh
• Dehumidification programming with cold or heat call.
Door switch Present
PHigh/low pressure switch Present
Min. temperature sensor Present PLUS1000 THR cr
Max. temperature sensor Present
Connection diagrams Outputs
Compressor 2200 W ( 0,5 ÷3 HP )
Evaporator fans 800 W ( 1 ph )
Defrost on request
Hot heaters 4000 W (AC1)
Enable humidifiers Present
Enable dehumidifiers Present
Air change Present
Pause Present
Room light Present
Alarm relay present
Supervision system TeleNET

12 13
plus dl1 datalogger datalogger
b005.gb.02

dataprinteR plus

Single-channel temperature recorder which allows


recorded temperatures to be displayed directly on
the screen, printed out or transferred to PC.

193
146
65 88 203 79

APPLICATIONS MAIN CHARACTERISTICS TECHNICAL CHARACTERISTICS Plus DL1

• Recording of temperatures for the storage • Allows temperatures within the -45°C - +45°C Weight 1 Kg
Protection rating IP 65
and distribution of refrigerated, frozen and interval to be recorded at regular intervals.
Power supply 230 V AC ±10% 50/60 Hz
deep-frozen food products. • Up to 1 year of readings can be recorded: only the Working temperature -5 ÷ +50°C
oldest data are overwritten to ensure that a 1 year Storage temperature -10 ÷ +70°C
data history is always available. Relative ambient humidity < 90% Rz
• Recorded temperatures can be displayed on the range of reading -45 ÷ +45°C

LCD screen. Temperature indicator Display LCD


Alarm signals Display + Buzzer
• The temperature alarm history can be viewed
Recording characteristics
separately to keep track of past alarms. Maximum number of readings 1 year
• Available accessories include the DataPRINTER without overwrite (cyclic memory) PLUS dl1
Inputs
Plus to provide a paper copy of the data or the
Temperature ambient probe NTC 10 kΩ
SWPlus software to download data onto PC via a
Outputs
RS-232 serial connection. Alarm relay present
• The ABS housing can easily be installed and wall- Supervision system TELENET
mounted and features an IP65 protection rating.

TECHNICAL CHARACTERISTICS DataPRINTER Plus


swplus
Connection diagrams Weight 370 g
Power supply 12 ÷ 36 V DC
Working temperature -0 ÷ +50°C
Storage temperature -10 ÷ +70°C
Relative ambient humidity < 85% Rh
Resolution 203 Dpi ( 8 Dot/mm )
Paper dimension 57,5 mm
Printing system Thermal print

dataprinter plus

14 15
Plus EXPERT dl3 Datalogger DATALOGGER
EXPERT SERIES
B006.gb.02

Three-channels temperature recorder which allows, for


each channel, to monitor and record, at regular inter-
vals, temperature, digital input status and alarm events.
It allows visualization of registered data directly on

168
the LCD display or theirs download on personal
computer by an SD memory card. sd card

262 97

application MAIN CHARACTERISTICS Technical characteristics Plus Expert DL3


• Datalogger function up to 3 temperatures and • EN 12830 compliant Box dimensions 262 x 168 x 97 mm
3 digital inputs for storage and distribution cold • Allows up to three temperatures within the Weight 1 Kg
rooms of deep-frozen food products. -45°C - +45 °C interval to be recorded at regular Protection rating IP 65
intervals and until three digital inputs. Power supply 230Vac ±10% 50/60 Hz

• Temperatures visualization up to 1 year with cyclic Working temperature 0 ÷ +50 °C


opzioni memory (only the oldest data are overwritten). Storage temperature -20 ÷+60 °C
Relative ambient humidity < 90% Rh
• SD (Secure DIgital™) memory card for • Recorded temperatures can be displayed on the
Range of reading -45 ÷+45 °C
temperatures recorded data transfer onto LCD screen. Temperature indicator LCD Display
personal computer. • The temperature alarm and digital inputs history Alarm signals Display + Buzzer
can be viewed separately to keep track of past Maximum number of readings
1 year (cyclic memory)
alarms (as requested by HACCP). without overwrite
Inputs
• Secure Digital™ slot built into controller for data
Ambient probe 3 x NTC 10K 1%
downloads.
Digital input n°3 digital inputs
• TeleNET SD free software to download data on Outputs
personal computer. Alarm relay PRESENT
• The ABS housing can easily be installed and wall- Supervision system TeleNET
mounted and features an IP65 protection rating. Designation
• Calibration certificate enclosed. STANDARD REFERENCE EN 12830
SUITABILITY S (STORAGE)
LOCATION a
Accuracy class 1
Measurement range °c

16 17
EXPERIENCE
The experience reached manufacturing every type
of electrical panels in refrigeration field is our best
reference.
ECP200 EXPERT Single-Phase systems
Expert series
C001.gb.02

Control panel for cold rooms with single-phase com-


pressor up to 2 HP, specially designed to provide
safety, protection, control and easy-installation – all
in one unit.
Allows complete control of all the components on a

168
refrigeration system.

97 262

APPLICATIONS MAIN CHARACTERISTICS TECHNICAL CHARACTERISTICS ecp 200 expert

• Complete control of single-phase static or • Direct control of compressor, defrosting heaters, weight 0,6 Kg
ventilated refrigeration systems up to 2 HP, with evaporator fans and room light with live outputs Power supply
Voltage 230 V AC ± 10% 50/60 Hz
off-cycle or electrical defrosting and direct or directly connectable to the various devices.
Max absorbed power ~ 7 VA
pump-down compressor stop. • Built-in differential magnetothermic breaker for (electronic control)

• Control of evaporating unit only with freon protection and cut-off of refrigeration unit. Ambient conditions
Working temperature -5 ÷ +50°C
solenoid or remote motor condenser enabling. • Innovative, stylish design. Transparent cover for
Storage temperature -30 ÷ +70°C
access to magnetothermic breaker, all with IP 65 Relative humidity < 90% Rh
protection rating. General characteristics
• Auxiliary relay with parameter-configured Connectable sensor types NTC 10 kΩ
activation (alarm, temperature set-point, direct Resolution 0,1 °C
Probe read precision ± 0,5 °C
control via frontal pushbutton, door heater
Read range -45 ÷ +45 °C
elements, remote motor condenser unit POWER
Output characteristics SUPPLY
enabling, freon solenoid control enabling where Compressor 1500 W (2hp)
230 V AC

compressor pump-down operation is applied). Defrost 3000 W (AC1)


• RS485 for connection to TeleNET industrial Fans 500 W (AC3)

supervision network. Room light 800 W (AC1)


Configurable alarm contact /
• Easy installation and opening thanks to new Aux (voltage-free contact)
present

hinged cover. SUPERVISION SYSTEM telenet


General electric protection
16A Id = 300 mA
Bipolar differential magne-
Switching power 4,5 kA
tothermic circuit breaker
Id = 30 mA (on request)
Insulation and mechanical characteristics
Box Protection rating IP 65
Box material self-extinguishing ABS
insulation type Class II

20 21
plus200 EXPERT – datalogger Single-Phase systems
Expert Datalogger series
C002.gb.02

Control board for complete control of cold rooms with


single-phase compressor up to 2 HP and Datalogger
function.
A large backlit LCD allows for simultaneous display of
ambient temperature, evaporator temperature, calen-
dar and all other refrigeration system information. The
temperature recorder is independent from the control-
ler used to manage the refrigeration system and can
record (for up to 1 year) ambient temperature and rela-

168
tive alarms through an electronic circuit equipped with sd card
autonomous power and temperature sensor (as per
EN 12830). The recorder can be removed or replaced
without any interruption to normal cold room operation.
Moreover, defrosts can be carried out in real time clock
mode and it is possible to connect up to the TeleNET 262 97
supervision system.

APPLICATIONS MAIN CHARACTERISTICS TECHNICAL CHARACTERISTICS Plus200 Expert

• Complete control of single-phase static or • Direct control of compressor, defrost heaters, weight 1 Kg
ventilated systems up to 2 HP, off-cycle or evaporator fans, room light with 230Vac contacts Power supply
electrical defrost, direct or pump-down directly connectable to various devices. Voltage 230 V AC ± 10% 50/60 Hz
mode compressor stop together with • Control electronics with large backlit LCD and Max absorbed power
(electronic control)
~ 7 VA
Datalogger function. user-friendly keypad. Ambient conditions
• Control of single-phase evaporating unit • Simultaneous display on LCD of ambient Working temperature 0 - 50 °C
only with freon solenoid enabling or remote temperature, evaporator temperature, calendar Storage temperature -20 ÷ +60°C
motor condenser enabling, together with and system status. Relative humidity < 90% Rh
Datalogger function. • Recording of ambient temperature and relative General characteristics
alarms (up to 1 year) with recorder independent Connectable sensor types NTC 10K Ω
from cold room system control. Resolution 0,1 °C POWER
opTIONS • Secure Digital™ slot built into controller for data Read range -45 ÷ +45 °C
SUPPLY
230 V AC

• SD (Secure Digital™) memory for transfer of downloads. Recording characteristics


temperature recordings onto Personal computer. • Defrosts can be carried out in real time clock mode. Maximum number of readings
1 year (cyclic memory)
without overwrite
• CR version with free-voltage contacts to remotely • RS485 for connection to TeleNET industrial
Output characteristics - max applicable load (230 V AC)
control a power panel. supervision network. Compressor 1500 W (AC3)
• Safety and protection guaranteed and Defrost 3000 W (AC1)
certified thanks to incorporated differential Fans 500 W (AC3)
magnotothermic circuit breaker, which cuts Room light 800 W (AC1)
the power supply. Configurable alarm contact present
• Easy installation and opening thanks to new (voltage-free contact)

SUPERVISION SYSTEM TELENET


hinged cover.
General electric protection
• Auxiliary relay with parameter-configurable
16A Id = 300 mA
activation. Bipolar differential magne-
Switching power 4.5 kA
tothermic circuit breaker
• Registration probe with calibration certificate Id = 30 mA (ON REQUEST)
included. Insulation and mechanical characteristics
• TeleNET SD software to download data on Box Protection rating IP 65

personal computer (provided free of charge Box material self-extinguishing ABS


Type of insulation Class II
with product).
DESIGNATION
STANDARD REFERENCE EN 12830
SUITABILITY S (STORAGE)
LOCATION a
ACCURACY CLASS 1

22 23
ECP300 EXPERT vd Three-phase systems
Expert series
C003.GB.02
ECP300 Expert VD 4 | ECP300 Expert VD 7

A line of power and control panels for refrigeration


systems with three-phase compressor up to 7,5 HP,
for the complete management of cold room.

300
Magnetothermic protection and motor circuit breaker
for the compressor accessible from the front panel
linked to an innovative form makes it a perfect and
functional choice.

400 135

APPLICATIONS MAIN CHARACTERISTICS TECHNICAL CHARACTERISTICS: ECP300 Expert VD 4 ECP300 Expert VD 7

• Control of three-phase refrigeration plant up • Direct control of the compressor, condenser Box dimensions 400 x 300 x 135 mm 400 x 300 x 135 mm
Weight 9 Kg 10 Kg
to 7.5 HP, static or ventilated, with off-cycle or fans, compressor oil heater, defrosting heaters,
Protection rating IP 65 IP 65
electrical defrosting. evaporator fans, solenoid valve, room light and all Power supply 400 V AC ±10% 50/60 Hz 400 V AC ±10% 50/60 Hz
standard-compliant electrical safeguards. Load type Three-phase Three-phase

OPTIONS • General magnetothermic circuit breaker Working temperature -5 ÷ +40°C -5 ÷ +40°C


Storage temperature -25 ÷ +55°C -25 ÷ +55°C
accessible from the front panel, which cuts the
• Hot-gas defrost control. Relative ambient humidity 30% - 90% Rh w/out condensate 30% - 90% Rh w/out condensate
general power supply. range OF READING -45 ÷ +45°C -45 ÷ +45°C
• Adjustable motor circuit breaker for compressor Main switch / general protection 4 poles magnetothermic 16A 4 poles magnetothermic 25A
protection accessible from the front panel. Compressor protection Motor circuit breaker Motor circuit breaker

• Easy wiring on the internal terminal block. Control PEGO PEGO


Defrosting Electrical Electrical
• Selection of functioning mode for the compressor Status indicators LED + Display LED + Display
Connection diagrams (pump-down / thermostat). Alarm signals LED + Buzzer LED + Buzzer
• Auxiliary relay with activation configurable by Inputs

parameter. Ambient probe NTC 10K Ω NTC 10K Ω


Evaporator probe NTC 10K Ω NTC 10K Ω
• Transparent cover for access to magnetothermic
Door switch Present Present
circuit breaker, all with IP 65 protection rating. High/low pressure switch Present Present
• Electronic control with wide LED display and easy Kriwan ® connection Present Present

to use buttons. Compressor functioning


Pump-down / Thermostat Pump-down / Thermostat
mode selection
• Signaling with LED icons of the plant status. Outputs
• RS485 for connection to TeleNET industrial Compressor 370 W ÷ 3000 W (0,5 ÷ 4 HP) 3000 W ÷ 5500 W (4 ÷ 7,5 HP)

supervision network. Condenser fans output 1 800 W (1ph) 800 W (1ph) (1ph)
Condenser fans output 2 (separated) TOTAL (1ph)
Evaporator fans 500 W (1ph) 2000 W (1ph / 3ph)
Defrosting heaters 6000 W (ac1) eq. resistive load 9000 W (ac1) eq. resistive load
Room light 800 W (AC1) resistive load 800 W (AC1) resistive load
Solenoid valve Present Present
Compressor oil heater Present Present
Alarm relay present present
Supervision system TeleNET TeleNET

24 25
ECP300 EXPERT u vd Three-phase Units
Expert series
C004.gb.02
ECP300 Expert U VD 6 | ECP300 Expert U VD 12

A line of power and control panels for refrigeration sy-


stems to control only the three-phase evaporating unit
where units are served by a central refrigerator or remo-

300
te condenser unit.
Magnetothermic and differential protection for room
light accessible from the front panel linked to an innova-
tive form makes it a perfect and functional choice.

400 135

APPLICATIONS MAIN CHARACTERISTICS TECHNICAL CHARACTERISTICS ECP300 Expert U VD 6 ECP300 Expert U VD 12

• Control of evaporating unit with electrical defrost • Enable for motor condenser unit, defrosting Box dimensions 400 x 300 x 135 mm 400 x 300 x 135 mm
Weight 9 Kg 10 Kg
up to 12 kW. elements, evaporator fans, solenoid valve,
Protection rating IP 65 IP 65
room light and all standard-compliant electrical
Power supply 400 V AC ±10% 50/60 Hz 400 V AC ±10% 50/60 Hz
safeguards. Load type Three-phase Three-phase
• Magnetothermic circuit breaker accessible from Working temperature -5 ÷ +40°C -5 ÷ +40°C
the front panel, which cuts the general power Storage temperature -25 ÷ +55 °C -25 ÷ +55 °C

supply. Relative ambient humidity 30% - 90% Rh W/OUT CONDENSATE 30% - 90% Rh W/OUT CONDENSATE
range of reading -45 ÷ +45°C -45 ÷ +45°C
• Differential magnetothermic Id=30mA dedicated
CONNECTION DIAGRAMS to room light accessibile from the front panel (see
Main switch / general protection 4 poles magnetothermic 16A 4 poles magnetothermic 25A
Differential magnetothermic Differential magnetothermic
Room light protection
the table). circuit breaker (optional) circuit breaker
• Easy wiring on the internal terminal block. Control PEGO PEGO
Defrosting Electrical Electrical
• Auxiliary relay with activation configurable by
Status indicators LED + Display LED + Display
parameter. Alarm signals LED + Buzzer LED + Buzzer
• Transparent cover for access to all the Inputs
protections, all with IP 65 protection rating. Ambient probe NTC 10K Ω NTC 10K Ω
• Electronic control with wide LED display and easy Evaporator probe NTC 10K Ω NTC 10K Ω
Door switch Present Present
to use buttons.
Man in cold-room alarm Available Available
• Signaling with LED icons of the plant status.
Outputs
• RS485 for connection to TeleNET industrial Evaporator fans 550 W (1ph) 2000 W (1ph / 3ph)
supervision network. Defrosting heaters 6000 W (ac1) eq. resistive load 12000 W (ac1) eq. resistive load
Room light 800 W (AC1) resistive load 1200 W (AC1) resistive load
Solenoid valve Present Present
Enable condensing unit Present Present
Configurable alarm relay present present
Door heater Present Present
Supervision system TeleNET TeleNET

26 27
Plus300 EXPERT Datalogger Three-phase Systems
Expert Datalogger series
C005.gb.02
Plus 300 Expert VD 4 | Plus 300 Expert VD 7

Control board for complete control of cold rooms with three-


phase compressor up to 7,5 HP and Datalogger function.
A large backlit LCD allows for simultaneous display of ambient
temperature, evaporator temperature, calendar and all other
refrigeration system information. The temperature recorder is
independent from the controller used to manage the refrigera-

300
tion system and can record (for up to 1 year) ambient tempera-
ture and relative alarms through an electronic circuit equipped
with autonomous power and temperature sensor (as per EN
12830). The recorder can be removed or replaced without any
interruption to normal cold room operation. Moreover, defrosts
can be carried out in real time clock mode and it is possible to
connect up to the TeleNET supervision system. Magnetother-
mic protection and motor circuit breaker for the compressor
accessible from the front panel linked to an innovative form
makes it a perfect and functional choice. 400 135

application • Selection of functioning mode for the compressor


TECHNICAL CHARACTERISTICS Plus300 Expert VD 4 plus300 Expert VD 7

Box dimensions 400 x 300 x 135 mm 400 x 300 x 135 mm


• Control of three-phase refrigeration plant up (pump-down / thermostat). Weight 9 Kg 10 Kg
to 7.5 HP, static or ventilated, with off-cycle or • Auxiliary relay with activation configurable by Protection rating IP 65 IP 65

electrical defrosting. parameter. Power supply 400 V AC ±10% 50/60 Hz 400 V AC ±10% 50/60 Hz

• Transparent cover for access to magnetothermic Load type Three-phase Three-phase

circuit breaker, all with IP65 protection rating. Working temperature -5 ÷ +40°C -5 ÷ +40°C

OPTIONS • Control electronics with large backlit LCD and


Storage temperature -25 ÷ +55°C -25 ÷ +55°C
Relative ambient humidity 30% - 90% Rh w/out condensate 30% - 90% Rh w/out condensate
• SD (Secure Digital™)memory for transfer of user-friendly keypad. Main switch / general protection 4 poles magnetothermic 16A 4 poles magnetothermic 25A
temperature recordings onto Personal computer. • Simultaneous display on LCD of ambient Compressor protection Motor circuit breaker Motor circuit breaker

temperature, evaporator temperature, calendar Control PEGO PEGO

and system status. Defrosting Electrical Electrical

MAIN CHARACTERISTICS • Recording of ambient temperature and relative


Status indicators Display LCD Display LCD
Alarm signals Display LCD + Buzzer Display LCD + Buzzer
• Direct control of the compressor, condenser alarms (up to 1 year) with recorder independent inputs

fans, compressor oil heater, defrosting heaters, from cold room system control. Ambient probe NTC 10K Ω NTC 10K Ω

evaporator fans, solenoid valve, room light and • Secure Digital™ slot built into controller for data Evaporator probe NTC 10K Ω NTC 10K Ω
DATALOGGER PROBE NTC 10K Ω NTC 10K Ω
all standard-compliant electrical safeguards. downloads. Door switch Present Present
• General magnetothermic circuit breaker • Defrosts can be carried out in real time clock mode. High/low pressure switch Present Present
accessible from the front panel, which cuts the • RS485 for connection to TeleNET industrial Kriwan ® connection Present Present
general power supply. supervision network. Compressor functioning mode selection Pump-down / Thermostat Pump-down / Thermostat

• Adjustable motor circuit breaker for compressor • TeleNET SD software to download data on outputs

protection accessible from the front panel. personal computer (provided free of charge Compressor 370W÷3000W (0,5-4HP) 3000 W ÷ 5500 W (4 ÷ 7,5 HP)
Condenser fans output 1 800W (1ph) 800 W (1ph)
• Easy wiring on the internal terminal block. with product). Condenser fans output 2 (separated) total (1ph)
Evaporator fans 500W (1ph) 2000W (1ph / 3ph)
Defrosting heaters 6000W (AC1) eq. resistive load 9000W (AC1) eq. resistive load
Room light 800W (AC1) resistive load 800W (AC1) resistive load
Solenoid valve Present Present
CONNECTION DIAGRAMS Compressor oil heater Present Present
Alarm relay Present Present
Supervision system TeleNET TeleNET
datalogger
DATALOGGER INDEPENDENT CIRCUIT INDEPENDENT CIRCUIT
MAX. NUMBER OF READINGS WITHOUT OVERWRITE 1 YEAR (CYCLIC MEMORY) 1 YEAR (CYCLIC MEMORY)
DESIGNATION
STANDARD REFERENCE EN 12830 EN 12830
SUITABILITY S (STORAGE) S (STORAGE)
LOCATION a a
ACCURACY CLASS 1 1

28 29
PLUS300 EXPERT u vd datalogger THREE-PHASE UNITS
EXPERT DATALOGGER SERIES
C006.Gb.02
PLUS 300 Expert U VD 6 | PLUS 300 Expert U VD 12

A line of power and control panels for refrigeration systems to


control only the three-phase evaporating unit where units are
served by a central refrigerator or remote condenser unit and
Datalogger function.
A large backlit LCD allows for simultaneous display of ambient
temperature, evaporator temperature, calendar and all other
refrigeration system information. The temperature recorder is

300
independent from the controller used to manage the refrigera-
tion system and can record (for up to year) ambient tempera-
ture and relative alarms through an electronic circuit equipped
with autonomous power and temperature sensor (as per EN
12830). The recorder can be removed or replaced without any
interruption to normal cold room operation. Moreover, defrosts
can be carried out in real time clock mode and it is possible to
connect up to the TeleNeT supervision system.
Magnetothermic protection and motor circuit breaker for the
compressor accessible from the front panel linked to an inno- 400 135
vative form makes it a perfect and functional choice.

applications MAIN CHARACTERISTICS TECHNICAL CHARACTERISTICS plus300 Expert U VD 6 plus300 Expert U VD 12

Box dimensions 400 x 300 x 135 mm 400 x 300 x 135 mm


• Control of evaporating unit with electrical defrost • Enable for motor condenser unit, defrosting Weight 9 Kg 10 Kg
up to 12 kW. elements, evaporator fans, solenoid valve, Protection rating IP 65 IP 65

room light and all standard-compliant electrical Power supply 400 V AC ±10% 50/60 Hz 400 V AC ±10% 50/60 Hz

safeguards. Load type Three-phase Three-phase

options • Magnetothermic circuit breaker accessible from Working temperature -5 ÷ +40°C -5 ÷ +40°C
Storage temperature -25 ÷ +55 °C -25 ÷ +55 °C
• SD (Secure Digital™) memory for transfer of the front panel, which cuts the general power Relative ambient humidity 30% - 90% Rh W/OUT CONDENSATE 30% - 90% Rh W/OUT CONDENSATE
temperature recordings onto personal computer. supply. range of reading -45 ÷ +45°C -45 ÷ +45°C
• Differential magnetothermic Id=30mA dedicated Main switch / general protection 4 poles magnetothermic 16A 4 poles magnetothermic 25A
to room light accessibile from the front panel Room light protection
Differential magnetothermic Differential magnetothermic
circuit breaker (optional) circuit breaker
(see the table). Control PEGO PEGO
• Easy wiring on the internal terminal block.
CONNECTION DIAGRAMS • Auxiliary relay with activation configurable by
Defrosting
Status indicators
Electrical
Display lcd
Electrical
Display lcd

parameter. Alarm signals Buzzer + Display lcd Buzzer + Display lcd

• Transparent cover for access to all the Ingressi


Ambient probe NTC 10K Ω NTC 10K Ω
protections, all with IP 65 protection rating.
Evaporator probe NTC 10K Ω NTC 10K Ω
• Control electronics with large backlit LCD and DATALOGGER PROBE NTC 10K Ω NTC 10K Ω
user-friendly keypad. Door switch Present Present
• Simultaneous display on LCD of ambient Man in cold-room alarm Available Available

temperature, evaporator temperature, calendar Uscite

and system status. Evaporator fans 550 W (1ph) 2000 W (1ph / 3ph)
Defrosting heaters 6000 W (ac1) eq. resistive load 12000 W (ac1) eq. resistive load
• Recording of ambient temperature and relative
Room light 800 W (AC1) resistive load 1200 W (AC1) resistive load
alarms (up to 1 year) with recorder independent Solenoid valve Present Present
from cold room system control. Enable condensing unit Present Present
• Secure Digital™ slot built into controller for data Configurable alarm relay present present

downloads. Door heater Present Present

• Defrosts can be carried out in real time clock Supervision system TeleNET TeleNET
datalogger
mode. datalogger INDEPENDENT CIRCUIT INDEPENDENT CIRCUIT
• RS485 for connection to TeleNeT industrial MAX. NUMBER OF READINGS
1 YEAR (CYCLIC MEMORY) 1 YEAR (CYCLIC MEMORY)
supervision network. WITHOUT OVERWRITE

• TeleNET SD software to download data on designazione


STANDARD REFERENCE EN 12830 EN 12830
personal computer (provided free of charge SUITABILITY S (STORAGE) S (STORAGE)
with product). LOCATION a A
ACCURACY CLASS 1 1

30 31
ecp 04 condensing units
Single-phase or Three-phase
D001.gb.02
ECP 04 | ECP 04 M

A simple, compact solution for control of the


condensing unit: single-phase up to 2 HP and
three-phase up to 3 HP.

260
The call can be generated by pressure switch
(compressor shutdown in pump-down mode),
thermostat or free-voltage contact.

210 130

APPLICATIONS MAIN CHARACTERISTICS TECHNICAL CHARACTERISTICS ECP 04 M ECP 04

• ECP 04 M Control of condensing unit with • Direct control of compressor, condenser fans and box dimensions 210x260x130 mm 210x260x130 mm

single-phase compressor up to 2 HP. all standard-compliant electrical safeguards. Weight 4 Kg 4 Kg


Protection rating IP 65 IP 65
• ECP 04 Control of condensing unit with • Compressor call by pressure switch, thermostat
Power supply 230 V AC ±10% 50/60 Hz 400 V AC ±10% 50/60 Hz
three-phase compressor up to 3 HP. or free-voltage contact.
Load type Single-phase Three-phase
• Compact unit with self-extinguishing ABS panel Working temperature -5 ÷ +50°C -5 ÷ +50°C
and IP65 protection rating plus circuit breaker on Storage temperature -10 ÷ +70°C -10 ÷ +70°C
front of panel. Relative ambient humidity < 90% Rh < 90% Rh
CONNECTION DIAGRAMS • System status indicated by LED icon. Main switch 16 A 16 A
Overload protection Thermal relay
General protection Fuses Fuses
Control External Pressure switch External Pressure switch
Pump-down stop Present Present
Status indicators LED LED
Inputs
Thermostat or pressure switch Present Present
Outputs
Compressor 1500 W (2 HP) (1 PH) 2200 W (3HP) (3PH)
Condenser fans 800 W (1 ph) 800 W (1PH)

32 33
ecp 07 10 15 condensing units
Three-phase
D002.gb.02
ECP 07 | ECP 10 | ECP 15

A simple, compact solution for control of three-pha-


se condensing units up to 20 HP.
The call can be generated by pressure switch (com-
pressor shutdown in pump-down mode), thermostat

450
or clean contact.

340
290 145 350 160

applications MAIN CHARACTERISTICS TECHNICAL CHARACTERISTICS ECP 07 ECP 10 ECP 15

• ECP 07 Control of condensing unit with three- • Direct control of compressor, condenser fans and Box dimensions 290 x 340 x 145 mm 290 x 340 x 145 mm 350 x 450 x 160 mm

phase compressor up to 7 HP. all standard-compliant electrical safeguards. Weight 4 Kg 6 Kg 7 Kg

• ECP 10 Control of condensing unit with three- • Compressor call by pressure switch, thermostat Protection rating IP 65 IP 65 IP 65

or clean contact. Power supply 400 V AC ±10% 50/60 Hz 400 V AC ±10% 50/60 Hz 400 V AC ±10% 50/60 Hz
phase compressor up to 10 HP.
Load type Three-phase Three-phase Three-phase
• ECP 15 Control of condensing unit with three- • Compact unit with self-extinguishing ABS panel
Working temperature -5 ÷ +50°C -5 ÷ +50°C -5 ÷ +50°C
phase compressor up to 20 HP. and IP65 protection rating plus circuit breaker on
Storage temperature -10 ÷ +70°C -10 ÷ +70°C -10 ÷ +70°C
front of panel.
Relative ambient humidity < 90% Rh < 90% Rh < 90% Rh
• System status indicated by LED icon.
Main switch 32 A 32 A 63 A
Overload protection Thermal relay Thermal relay Thermal relay
General protection Fuses Fuses Fuses
External Pressure External Pressure External Pressure
Control
switch switch switch
Pump-down stop Present Present Present
Insulation transformer Present Present Present
Status indicators LED LED LED
Inputs
Thermostat or pressure switch Present Present Present
CONNECTION DIAGRAMS Oil differential pressure switch Present Present
Kriwan® connection Present Presente Present
Condenser fans regulator
Present Present
press. switch (R.P.S.)
Krivan
Outputs

32 A
Compressor 2200÷5500 W (3÷7 HP) 5500÷7500 W (7÷10 HP) 7500÷15000 W (10÷20 HP)
400 Vac
ECP 07 Condenser fans output 1 (1 ph) 2000 W (1ph/ 3ph) 2000 W (1ph/ 3ph)
800 W (1 ph)
Condenser fans output 2 total (1 ph) 2000 W (1ph/ 3ph) 2000 W (1 ph / 3ph)
(separated)
Compressor oil heater Present Present

34 35
ecp__ VD Three-phase systems
without electronics
E001.gb.02
ECP300 VD | ECP400 VD
ECP750 VD | ECP1000 VD

A line of power boards for refrigeration systems with


three-phase compressors up to 10 HP to be linked
to a thermostat, thermo-regulator or out-of-room
control unit.

450
An electromechanical timer is incorporated for timed

340
defrosts.

290 145 350 160

APPLICATIONS MAIN CHARACTERISTICS TECHNICAL CHARACTERISTICS ECP300 VD ECP400 VD ECP750 VD ECP1000 VD

• Control of three-phase static or ventilated • Direct control of compressor, condenser fans, Box dimensions 290 x 340 x 145 mm 350 x 450 x 160 mm 350 x 450 x 160 mm 350 x 450 x 160 mm

refrigeration units up to 10 HP, with electric compressor oil element, defrost elements, Weight 5 Kg 6 Kg 6 Kg 7 Kg

or off-cycle defrost linked to a thermostat, evaporator fans, solenoid valve and all standard- Protection rating IP 65 IP 65 IP 65 IP 65

compliant electrical safeguards. 400 V AC ±10% 400 V AC ±10% 400 V AC ±10% 400 V AC ±10%
thermo-regulator or out-of-room control unit Power supply
50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz
that issues a cold request. • Compact unit with self-extinguishing ABS Load type Three-phase Three-phase Three-phase Three-phase
housing panel and IP65 protection rating plus Working temperature -5 ÷ +50°C -5 ÷ +50°C -5 ÷ +50°C -5 ÷ +50°C
circuit breaker on front of panel. Storage temperature -10 ÷ +70°C -10 ÷ +70°C -10 ÷ +70°C -10 ÷ +70°C
OPtions • Electromechanical timer for timed defrosts Relative ambient humidity < 90% Rh < 90% Rh < 90% Rh < 90% Rh
• Installation of magnetothermic circuit breakers • System status indicated by LED icon. Main switch 16 A 32 A 32 A 32 A
instead of fuses. • Can be controlled by thermostat, thermo- Overload protection Thermal relay Thermal relay Thermal relay Thermal relay
• Compressor shutdown in pump-down mode. regulator or out-of-room control unit General protection Fuses Fuses Fuses Fuses
• Can house thermo-regulator on front of panel. External ON /OFF External ON /OFF External ON /OFF External ON /OFF
External External External External
Control Thermoregulator Thermoregulator Thermoregulator Thermoregulator
Remote control Remote control Remote control Remote control
panel panel panel panel
Defrosting Electrical Electrical Electrical Electrical
Insulation transformer Present Present Present
Status indicators LED LED LED LED
Alarm signals LED LED LED LED
inputs
Thermostat or pressure switch Present Present Present Present
Oil differential pressure switch Present
High/low pressure switch Present Present Present Present
CONNECTION DIAGRAMS Kriwan® connection Present Present Present
Condenser fans regulator
Present Present Present
press. switch (R.P.S.)
Outputs
Compressor 2200 W (0,5÷3 HP) 2200÷3000 W (3÷4 HP) 3000÷5500W(4÷7,5HP) 5500÷7500 W (7÷10 HP)
Condenser fans output 1 800 W (1 ph) 800 W (1 ph) 800 W (1 ph) 2000 W (1ph/ 3ph)
Condenser fans output 2 (se- (1 ph) (1 ph)
total (1 ph) total (1 ph) 2000 W (1ph / 3ph)
parated)
Evaporator fans 800 W (1 ph) 2000 W (1ph) 2000 W (1ph) 2000 W (1ph/ 3ph)
Defrosting heaters 4000 W (AC1) 7500 W (AC1) 9000 W (AC1) 12000 W (AC1)
Room light Present Present Present Present
Solenoid valve Present Present Present Present
Compressor oil heater Present Present Present

36 37
ecp__ VD cr Examples of out-of-room
Three-phase systems
without electronics for remote control
E002.gb.02
control units to link
ECP300 VD CR | ECP400 VD CR
ECP750 VD CR | ECP1000 VD CR ECP200 Base4

A line of power boards for refrigeration systems with


three-phase compressors up to 10 HP to be linked to
Slim Base4
an out-of-room control unit.
Controls and powers the compressor, condenser

450
fans, evaporator fans, solenoid valve, defrost ele-

340
PLUS 200 EXPERT CR
ments managed by means of cold fans and defrost
call enabling from out-of-room control unit.

ECP__ VD CR

290 145 350 160

APPLICATIONS MAIN CHARACTERISTICS TECHNICAL CHARACTERISTICS ECP300 VD CR ECP400 VD CR ECP750 VD CR ECP1000 VD CR

• Control of three-phase static or ventilated • Direct control of compressor, condenser fans, Box dimensions 290 x 340 x 145 mm 350 x 450 x 160 mm 350 x 450 x 160 mm 350 x 450 x 160 mm
Weight 5 Kg 6 Kg 6 Kg 7 Kg
refrigeration systems up to 10 HP, with electric or off- compressor oil element, defrost elements,
Protection rating IP 65 IP 65 IP 65 IP 65
cycle defrost linked to an out-of-room control unit. evaporator fans, solenoid valve and all standard- 400 V AC ±10% 400 V AC ±10% 400 V AC ±10% 400 V AC ±10%
Power supply
compliant electrical safeguards. 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz

• Compact unit with self-extinguishing ABS Load type Three-phase Three-phase Three-phase Three-phase

OPTIONS housing panel and IP65 protection rating plus


Working temperature -5 ÷ +50°C -5 ÷ +50°C -5 ÷ +50°C -5 ÷ +50°C
Storage temperature -10 ÷ +70°C -10 ÷ +70°C -10 ÷ +70°C -10 ÷ +70°C
• Installation of magnetothermic circuit breakers circuit breaker on front of panel. Relative ambient humidity < 90% Rh < 90% Rh < 90% Rh < 90% Rh
instead of fuses. • Electromechanical timer for timed defrosts. Main switch 16 A 32 A 32 A 32 A
• Compressor shutdown in pump-down mode. • System status indicated by LED icon. Overload protection Thermal relay Thermal relay Thermal relay Thermal relay

• Datalogger function with PLUS200 EXPERT CR • Can be controlled by thermostat, thermo- General protection Fuses Fuses Fuses Fuses

out-of-room controller for temperature and regulator or out-of-room control unit.


Compressor External ON /OFF External ON /OFF External ON /OFF External ON /OFF
Control Defrost External ON /OFF External ON /OFF External ON /OFF External ON /OFF
alarms registration. • Can house thermo-regulator on front of panel. Fans External ON /OFF External ON /OFF External ON /OFF External ON /OFF
Defrosting Electrical Electrical Electrical Electrical
Insulation transformer Present Present Present
Status indicators LED LED LED LED
Alarm signals LED LED LED LED
Inputs
Compressor power Enable only Enable only Enable only Enable only
Defrost Enable only Enable only Enable only Enable only
Evaporator fans Enable only Enable only Enable only Enable only
Oil differential pressure switch Present
High/low pressure switch Present Present Present Present
CONNECTION DIAGRAMS Kriwan ® connection Present Present Present
Condenser fans regulator press.
Present Present Present
switch (R.P.S.)
Outputs
Compressor 2200 W (0,5÷3 HP) 2200÷3000 W (3÷4 HP) 3000÷5500 W (4÷7,5 HP) 5500÷7500 W (7÷10 HP)
Condenser fans output 1 800 W (1 ph) 800 W (1 (1 ph) 800 W (1 (1 ph) 2000 W (1ph/ 3ph)
Condenser fans output 2 ph) ph)
total (1 ph) total (1 ph) 2000 W (1ph / 3ph)
(separated)
Evaporator fans 800 W (1 ph) 2000 W (1ph) 2000 W (1ph) 2000 W (1ph/ 3ph)
Defrosting heaters 4000 W (AC1) 7500 W (AC1) 9000 W (AC1) 12000 W (AC1)
Room light Present Present Present Present
Solenoid valve Present Present Present Present
Compressor oil heater Present Present Present

38 39
ecp2000 VD cr Examples of out-of-room
Three-phase systems
without electronics for remote control
E003.GB.02
ECP1500 VD CR | ECP2000 VD CR control units to link

ECP2500 VD CR ECP200 Base4

A line of power and control panels for refrigeration sys-


tems with three-phase compressor up to 25HP to be
Slim Base4
linked with an out-of-room control unit (i.e. ECP200
Base4 or SLIM Base4).

650
Controls and powers the compressor, condenser fans,
PLUS 200 EXPERT CR
evaporator fans, solenoid valve, defrost elements man-
aged by means of cold, fans and defrost call enabling
from out-of-room control unit.

ECP2000 VD CR

470 210

APPLICATIONS MAIN CHARACTERISTICS TECHNICAL CHARACTERISTICS ECP1500 VD CR ECP2000 VD CR ECP2500 VD CR

• Control of three-phase ventilated refrigeration • Direct control of compressor, condenser fans, Box dimensions 470 x 650 x 210 mm 470 x 650 x 210 mm 470 x 650 x 210 mm
Weight 20 Kg 20 Kg 20 Kg
systems up to 25 HP, with electrical defrost linked compressor oil element, defrost elements,
Protection rating IP 65 IP 65 IP 65
to an out-of-room control unit. evaporator fans, solenoid valve and all standard-
Power supply 400 V AC ±10% 50/60 Hz 400 V AC ±10% 50/60 Hz 400 V AC ±10% 50/60 Hz
compliant electrical safeguards. Load type Three-phase Three-phase Three-phase
• Compact unit with self-extinguishing ABS Working temperature -5 ÷ +50°C -5 ÷ +50°C -5 ÷ +50°C
OPTIONS housing panel and IP65 protection rating plus Storage temperature -10 ÷ +70°C -10 ÷ +70°C -10 ÷ +70°C
• Compressor shutdown in pump-down mode. circuit breaker on front of panel. Relative ambient humidity < 90% Rh < 90% Rh < 90% Rh

• Datalogger function with external control panel • System status indicated by LED icon. Main switch 63 A 63 A 100 A

Plus 200 Expert CR for temperatures and • Alarm signal by voltage-free contact. Overload protection Motor circuit breaker Motor circuit breaker Motor circuit breaker

alarms recording. • Can be controlled by thermostat, thermo- General protection Fuses Fuses Fuses
Compressor External ON /OFF External ON /OFF External ON /OFF
regulator or out-of-room control unit.
Control Defrost External ON /OFF External ON /OFF External ON /OFF
Fans External ON /OFF External ON /OFF External ON /OFF
Defrosting Electrical Electrical Electrical
Insulation transformer Present Present Present
Status indicators LED LED LED
Alarm signals LED LED LED
Inputs
Compressor Enable only Enable only Enable only
Defrosting Enable only Enable only Enable only
Evaporator fans Enable only Enable only Enable only
Oil differential pressure switch Present Present Present
High/low pressure switch Present Present Present
CONNECTION DIAGRAMS Kriwan® connection Present Present Present
Condenser fans regulator press.
Present Present Present
P. P.

P. P.

P. P.

switch (R.P.S.)
Krivan

Krivan

Krivan

Klixon connections for condenser


Present Present Present
/ evaporator fans
Outputs
Compressor 7500÷11250 W (10÷15 HP) 11250÷15000 W (15÷20 HP) 15000÷18750 W (20÷25 HP)
P.D.O.

P.D.O.
P.D.O.

Condenser fans (separated) 2 x 2000 W (1ph / 3ph) 2 x 2000 W (1ph / 3ph) 2 x 2000 W (1ph / 3ph)
Enable only Enable only Enable only
Enable only Enable only Enable only
Enable only Enable only Enable only

ECP1500 VD CR

ECP2000 VD CR

ECP2500 VD CR
Consenso
Consenso

Consenso

Evaporator fans 2 x 2000 W (3ph) 3 x 2000 W (3ph) 3 x 2000 W (3ph)


Consenso

Consenso

Consenso

Defrosting heaters 15000 W (AC1) 20000 W (AC1) 25000 W (AC1)


Solenoid valve Present Present Present
Consenso

Consenso

Consenso

Compressor oil heater Present Present Present


400 Vac 100 A
63 A

63 A

Alarm relay Present Present Present


400 Vac

400 Vac

40 41
QUALITY
All our products are made using high quality materials and
equipments, as well as production process are constantly
verified in compliance with EEC directives and relative
standards currently in force.
ecp__ VD T Three-phase systems
with thermo-regulator
f001.gb.02
ECP300 VD T | ECP400 VD T
ECP750 VD T | ECP1000 VD T

A line of power and control boards for refrigeration


systems with three-phase compressors up to 10 HP
that provide complete cold room management.
Cold room light and system stand-by switches incor-

450
porated on front of panel. Integrated thermo-regula-

340
tor controls compressor, ventilation and defrosting.
The unit also controls the door switch, which auto-
matically turns on the room light, and compressor
and fan shutdown.

290 145 350 160

applications MAIN CHARACTERISTICS TECHNICAL CHARACTERISTICS ECP300 VD T ECP400 VD T ECP750 VD T ECP1000 VD T

• Complete control of three-phase static or • Direct control of compressor, condenser fans, Box dimensions 290 x 340 x 145 mm 350 x 450 x 160 mm 350 x 450 x 160 mm 350 x 450 x 160 mm

ventilated refrigeration systems up to 10 HP, compressor oil element, defrost elements, Weight 5 Kg 6 Kg 6 Kg 7 Kg

with electric or off-cycle defrost. evaporator fans, solenoid valve, room light and all Protection rating IP 55 IP 55 IP 55 IP 55

standard-compliant electrical safeguards. 400 V AC ±10% 400 V AC ±10% 400 V AC ±10% 400 V AC ±10%
Power supply
50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz
• Compact unit with self-extinguishing ABS
OPTIONS housing panel and IP55 protection rating plus
Load type Three-phase Three-phase Three-phase Three-phase
Working temperature -5 ÷ +50°C -5 ÷ +50°C -5 ÷ +50°C -5 ÷ +50°C
• Installation of magnetothermic circuit breakers circuit breaker on front of panel. Storage temperature -10 ÷ +70°C -10 ÷ +70°C -10 ÷ +70°C -10 ÷ +70°C
instead of fuses. • Integrated thermo-regulator: various models Relative ambient humidity < 90% Rh < 90% Rh < 90% Rh < 90% Rh
• Compressor shutdown in pump-down mode. available. Main switch 16 A 32 A 32 A 32 A
• Hot gas defrost control. • System status indicated by LED icon. Overload protection Thermal relay Thermal relay Thermal relay Thermal relay
• Wide range of thermo-regulator models available. • Room light and system stand-by switches on General protection Fuses Fuses Fuses Fuses
front of panel. Control Thermoregulator Thermoregulator Thermoregulator Thermoregulator
Defrosting Electrical Electrical Electrical Electrical
Insulation transformer Present Present Present
Status indicators LED + Display LED + Display LED + Display LED + Display
Alarm signals LED LED LED LED
Inputs
Ambient probe NTC NTC NTC NTC
Evaporator probe NTC NTC NTC NTC
Door switch Present Present Present Present
Oil differential pressure switch Present
High/low pressure switch Present Present Present Present
Kriwan ® connection Present Present Present
CONNECTION DIAGRAMS Condenser fans regulator
Present Present Present
press. switch (R.P.S.)
Outputs
Compressor 2200 W (0,5÷3 HP) 2200÷3000 W (3÷4 HP) 3000÷5500 W (4÷7,5 HP) 5500÷7500 W (7÷10 HP)
Condenser fans output 1 800 W (1 ph) 800 W (1 ph) 800 W (1 ph) 2000 W (1ph/ 3ph)
Condenser fans output 2 (1 ph) (1 ph)
total (1 ph) total (1 ph) 2000 W (1ph / 3ph)
(separated)
Evaporator fans 800 W (1 ph) 2000 W (1ph) 2000 W (1ph) 2000 W (1ph/ 3ph)
Defrosting heaters 4000 W (ac1) 7500 W (ac1) 9000 W (ac1) 12000 W (ac1)
Room light Present Present Present Present
Solenoid valve Present Present Present Present
Compressor oil heater Present Present Present

44 45
ecp__ T U Three-phase units
with thermo-regulator
f002.gb.02
ECP300 T U | ECP400 T U
ECP750 T U | ECP1000 T U

A line of power and electronic control boards for con-


trol of the three-phase evaporating unit only where
devices are served by a compressor rack.
Cold room light and system stand-by switches incor-

450
porated on front of panel.

340
Integrated thermo-regulator controls cold, ventilation
and defrosting calls.
The unit also controls the door switch, which auto-
matically turns on the room light, fan shutdown and
cold call shutdown.

290 145 350 160

APPLICATIONS MAIN CHARACTERISTICS TECHNICAL CHARACTERISTICS ECP300 T U ECP400 T U ECP750 T U ECP1000 T U

• Control of evaporating unit only with • Enabling for motor condenser unit, defrosting Box dimensions 290 x 340 x 145 mm 350 x 450 x 160 mm 350 x 450 x 160 mm 350 x 450 x 160 mm
Weight 5 Kg 6 Kg 6 Kg 7 Kg
electrical defrost up to 12 kW. elements, evaporator fans, solenoid valve, room
Protection rating IP 55 IP 55 IP 55 IP 55
light, door element and all standard-compliant 400 V AC ±10% 400 V AC ±10% 400 V AC ±10% 400 V AC ±10%
Power supply
OPtions electrical safeguards. 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz

• Compact, self-extinguishing ABS housing with Load type Three-phase Three-phase Three-phase Three-phase
• Installation of magnetothermic circuit Working temperature -5 ÷ +50°C -5 ÷ +50°C -5 ÷ +50°C -5 ÷ +50°C
IP55 protection rating and circuit breaker on front
breakers instead of fuses. Storage temperature -10 ÷ +70°C -10 ÷ +70°C -10 ÷ +70°C -10 ÷ +70°C
of panel.
• Wide range of thermo-regulator Relative ambient humidity < 90% Rh < 90% Rh < 90% Rh < 90% Rh
• Integrated thermo-regulator: various models Main switch 16 A 32 A 32 A 32 A
models available.
available. Overload protection Fuses Fuses Fuses Fuses
• System status indicated by LED icon. Control Thermoregulator Thermoregulator Thermoregulator Thermoregulator
Defrosting Electrical Electrical Electrical Electrical
• Room light and system stand-by switches
Insulation transformer Present Present Present
on front of panel. Status indicators LED + Display LED + Display LED + Display LED + Display
Alarm signals LED LED LED LED
Inputs
Ambient probe NTC NTC NTC NTC
Evaporator probe NTC NTC NTC NTC
Door switch Present Present Present Present
Outputs
Evaporator fans 800 W (1 ph) 2000 W (1ph) 2000 W (1ph) 2000 W (1ph/ 3ph)
CONNECTION DIAGRAMS Defrosting heaters 4000 W (ac1) 7500 W (ac1) 9000 W (ac1) 12000 W (ac1)
Room light Present Present Present Present
Solenoid valve Present Present Present Present
Enable condensing unit Present Present Present Present

46 47
plus200 2plt Double System
Single-phase Plus series
g001.gb.02

100MASTER 2PLT
Electronic controller for double system management.
Can manage up to two compressors and two evapo-
rators, operating in call rotation mode (for even utili-

193
sation) or with a double set-point.
Defrosts can be executed in real time clock mode.

114
214 69

203 79

APPLICATIONS TECHNICAL CHARACTERISTICS Plus100 2PLT Plus200 2PLT


Version with 100Master and remote telephone
• Low temperature rooms with double safety lead-connected keyboard/display also available.
Weight 1 Kg 1 Kg
Protection rating IP 65 ( keyboard/display ) IP 65
system.
Power supply 230 V AC ±10% 50/60 Hz 230 V AC ±10% 50/60 Hz
• Room with single motor condenser unit 100MASTER 2PLT Load type Single-phase Single-phase
and double evaporator. Working temperature -5 ÷ +50°C -5 ÷ +50°C
Storage temperature -10 ÷ +70°C -10 ÷ +70°C
MAIN CHARACTERISTICS Relative ambient humidity < 90% Rh < 90% Rh
range of reading -45 ÷ +45°C -45 ÷ +45°C
• Single set-point with 2-system control and delayed
Defrosting Electrical Electrical
start of second system, compressor rotation. Status indicators Display LCD Display LCD
• Double set-point for gradual application of Alarm signals Display + Buzzer Display + Buzzer
plus100 2PLT
refrigeration power. Inputs
• Real time clock defrosts with one or two Ambient probe NTC 10 kΩ NTC 10 kΩ
evaporators, each with end-of-defrost sensor. Evaporator probe 1 NTC 10 kΩ NTC 10 kΩ

• Display of ambient temperature, evaporator Evaporator probe 2 NTC 10 kΩ NTC 10 kΩ


Compressor protection 1 Present Present
temperature, systems status.
Compressor protection 2 Present Present
• The Plus200 2PLT electronic controller allows
Man in cold-room alarm Present Present
complete control of all the units on a double- Door switch Present Present
system refrigeration plant. Outputs
• Control of up to two compressors, double evaporator Compressor 1 1500 W (2 HP) 750 W (1 HP)
(fans and defrost elements) and room light. Compressor 2 750 W (1 HP) 750 W (1 HP)
• Double evaporator control occurs separately with Defrost 1 1500 W (AC1) 1500 W (AC1)

double end-of-defrost sensor. Defrost 2 1500 W (AC1) 1500 W (AC1)


Evaporator fans 1 500 W 500 W
• Safety devices for the two systems are separate
and room light can be controlled by door switch. CONNECTION DIAGRAM Evaporator fans 2 500 W 500 W
Room light 800 W (AC1) 800 W (AC1)
• Alarm relay fitted as standard. Alarm relay /aux
present present
(voltage-free contact)
Supervision system TeleNET TeleNET

48 49
plus100 thr Seasoning
Single-phase Plus series
g002.gb.02

100MASTER thr plus100 thr


Temperature and humidity control complete with
specific seasoning functions.
Flexible programming also makes it ideal for simple
storage purposes.

98 ( x 180 )
114
Programming up to five formula, of seven phases

110
each, settable and customizable.

214 69 210 35

APPLICATIONS THR ELECTRONIC CONTROLLER FUNCTIONS TECHNICAL CHARACTERISTICS Plus100 THR

• Seasoning/drying rooms. • Backlit LCD screen. Weight 1 Kg plus100 THR


Protection rating IP 55 (keyboard/display)
• Germination rooms with day/night cycles. • Clock and calendar.
Power supply 230 V AC ±10% 50/60 Hz
• Storage rooms with or without humidity control. • Manual or automatic mode. Load type Single-phase
• Up to 5 formula completely customazible. Working temperature -5 ÷ +50°C
Automatic management of 7 phases for each Storage temperature -10 ÷ +70°C
formula (dripping first phase, seasoning/ Relative ambient humidity < 90% Rh

conservation last phase). Simple programming range of reading -45 ÷ +45°C


Status indicators Display LCD

Phone lead
CONNECTION DIAGRAM and selection of set formula. Possibility of join
Alarm signals Display + Buzzer
together more formula for exceeding the 7 inputs
phases limit. Ambient probe NTC 10 kΩ
• Heat and humidity can be excluded to manage Evaporator probe NTC 10 kΩ
storage cells with defrost activation. Humidity probe 4 ÷ 20 mA (0 ÷ 100% Rh)
Overload protection Present
• Temperature to one decimal point.
Door switch Present
• Password for keypad lock. outputs
• Day/night cycle for germination systems with Compressor 1500 W (2 HP) 100MASTER THR
double set-point. Evaporator fans 500 W
• Dehumidification program with cold or heat call. Defrosting heaters 1500 W (ac1)
Hot heaters 1500 W
Enable humidifiers 500 W
Enable dehumidifiers 500 W
Air change 500 W
PAUSE 500 W
Room light 800 W (ac1)
Alarm relay present
Supervision system TeleNET

50 51
plus100 ab Quick-refrigeration
Single-phase Plus series
g003.GB.02

100MASTER ab plus100 ab
Electronic control unit for the management of quick-
refrigeration systems and deep freezers.
It is possible to set different timed or product core
temperature-based quick-refrigeration programs, ex-

98 ( x 180 )
114
ecute positive or negative temperature quick-refrig-

110
eration and apply timed or temperature-based deep-
freezing and mixed programs.

214 69 210 35

APPLICATIONS MAIN CHARACTERISTICS TECHNICAL CHARACTERISTICS PLUS100 AB


plus100 ab
• Cabinets and quick-refrigeration rooms • The Plus100 AB electronic controller allows Weight 1 Kg

(positive / negative temperature). complete management of all the components Protection rating IP 55 ( keyboard/display )

• Product deep-freezing. on a refrigeration plant such as the compressor, Power supply 230 V AC ±10% 50/60 Hz
Load type Single-phase
evaporator fans, defrosting elements and room light.
Working temperature -5 ÷ +50°C
• The LCD screen shows cold room and product
FUNCTIONS core temperatures simultaneously.
Storage temperature -10 ÷ +70°C
Relative ambient humidity < 90% Rh
• Timed or temperature-based quick-refrigeration. • Where time-based programs are used the clock
Status indicators Display LCD
• Timed or temperature-based deep-freezing. field shows the remaining time.

Phone lead
Alarm signals Display + Buzzer
• Mixed quick-refrigeration/deep-freezing function. • Compressor control during quick-refrigeration INPUTS
• Storage with electrical defrost. is optimised to ensure that quick-refrigeration Ambient probe NTC 10 kΩ
• Min. and max. temperature limits for the final user. of the product occurs under the best possible Evaporator probe NTC 10 kΩ
• Activation of fans to de-layer the air. conditions. Food probe NTC 10 kΩ
• Defrosts in real time clock mode. Overload protection Present 100MASTER ab
Fans protection Present
Door switch Present
OUTPUTS
Compressor 1500 W (2 HP)
CONNECTION DIAGRAMS Evaporator fans 500 W
Defrosting heaters 1500 W (ac1)
Room light 800 W (ac1)
Alarm relay present
Supervision system TeleNET

52 53
plus100 PAN Pause-leavening
Single-phase Plus series
g004.gb.02

100MASTER PAN plus100 PAN


Electronic controller designed for pause-leavening
rooms. Work cycles easily programmed via user-
friendly interface.
Luminous graphics indicate progress of program be-

98 ( x 180 )
114
ing executed.

110
214 69 210 35

APPLICATIONS MAIN CHARACTERISTICS TECHNICAL CHARACTERISTICS PLUS100 AB

• Cabinets, counters and pause-leavening rooms • The Plus100 PAN electronic controller consists of Weight 1 Kg plus100 PAN

for small and large bakeries and confectionaries. the 100Master PAN unit, on which all the electrical Protection rating IP 55 ( keyboard/display )

• Can replace other pause-leavening controls on connections are made, and the keyboard/display, Power supply 230 V AC ±10% 50/60 Hz
Load type Single-phase
existing plants. which features a large LCD screen providing
Working temperature -5 ÷ +50°C
complete information on room status.
Storage temperature -10 ÷ +70°C
• The overall unit allows control of cold,
FUNCTIONS Relative ambient humidity < 90% Rh
heat, ventilation, room light, humidification,
range OF READING -45 ÷ +45°C
• Neutral-zone temperature and humidity control. dehumidification, defrosting and alarms via

Phone lead
Status indicators Display LCD
• Programming of four work cycles. control of the NTC ambient and evaporator Alarm signals Display + Buzzer
• Double fan speed. sensors and the 4-20 mA humidity sensor inputs. INPUTS
• Hot and cold manual cycles. • Compressor and fan safety devices, door switch, Ambient probe NTC 10 kΩ
• Management of cooling, storage, leavening and humidifier alarm. Evaporator probe NTC 10 kΩ
product-ready settling phases. • Special power boards complete with the Plus100 Humidity probe 4 ÷ 20 mA (0 ÷ 100% Rh)
• Clock and calendar to set product-ready time. PAN controller can be supplied according to Compressors protection Present
• Luminous synoptic display indicating program customer-specified requirements. Fans protection Present
progress. Humidifiers alarm Present
Door switch Present
OUTPUTS
100MASTER PAN
Compressor 1500 W (2 HP)
Condenser fans (double speed) 500 W
CONNECTION DIAGRAM Defrosting heaters 1500 W (AC1)
Hot heaters 1500 W
Enable humidifiers 500 W
Enable dehumidifiers 500 W
Room light 800 W (AC1)
Alarm relay present
Stand-by control 500 W
Supervision system TeleNET

54 55
SC 600 Controllers for compressor racks
g005.gb.02

100MASTER SC 600 SC 600


Electronic controller for compressor rack manage-
ment. Allows control of compressors and conden-
ser fans, adjusted with pressure sensor (high and
low pressure).

98 ( x 180 )
114

110
214 69 210 35

APPLICATIONS MAIN CHARACTERISTICS TECHNICAL CHARACTERISTICS SC 600


SC 600
• Compressor rack. • Pego compressor rack controllers are Weight 0,7 Kg

• Electrical board designed according to customer characterised by simplicity of installation and Protection rating IP 55 ( keyboard/display )

specifications. parameter configuration. Power supply 230 V AC ±10% 50/60 Hz


Load type Single-phase
• The installer can configure the controller and start
Working temperature -5 ÷ +50°C
the rack just by making a few simple settings.
FUNctions Storage temperature -10 ÷ +70°C
• The compressors come on in “neutral zone” mode;
Relative ambient humidity < 90% Rh
• Control of up to 4 compressors and 4 condenser configuration may be with or without rotation.
Control PEGO

Phone lead
fans or 3 capacity-control compressors.
Status indicators Display LCD
• LCD screen simultaneously displays high and
Alarm signals Display + Buzzer
low pressure, output status (on, off, starting or
Inputs
shutting down). HIGH PRESSURE PROBE 4 ÷ 20 mA (0 ÷ 30 bar)
100MASTER SC 600
• Alarm management. LOW PRESSURE PROBE 4 ÷ 20 mA configurable
Compressors protection Present
Condenser fans protection Present
General alarm Present
CONNECTION DIAGRAM Outputs
Relay ( ON/OFF status ) (N°8) 16 Amp AC1
Alarm relay Present
Supervision system TeleNET

56 57
telenet MONITORING AND SUPERVISION SYSTEMS
z001.gb.02
210

TeleNET is an application for the monitoring and su-


pervision of refrigeration and conditioning

200
systems controlled by Pego electronic instrumenta-
tion. The network of instruments channels the data
onto a personal computer where it is possible to dis-
play and print reports, manage alarms, modify operat-
ing parameters and monitor the whole system.

48
APPLICATIONS System requisites TECHNICAL CHARACTERISTICS telenet

• Monitoring and supervision of refrigeration and • Windows XP SP2 or Windows Vista operating dimensions 210 x 200 x 48 mm

conditioning systems. system weight 0,5 Kg

• Automatic control of work cycles. • RAM memory 1 GB (recommended 2 GB) N° of connectable instruments Unlimited *
Alarm relays Richiede TWMA
• Recording of physical parameters (temperature, • Hard disk 10 GB available space
Sampled variables print-out •
humidity, pressure, CO2 etc.). • Min. resolution 1024x768 24 bit
Graphics print-out •
• Industrial cooling, storage, seasoning systems. (recommended 1280x1024 32 bit)
Event history •
• Registration and consultation of data saved on
Sampling interval from 1 min
Secure Digital card (for Pego electrical panel Plus Automatic work cycles •
Expert series). Client/Server • * subject to verification of
available connection line
User management by password
• capacity and hardware
and authorisation levels resources.
MAIN CHARACTERISTICS
• Industrial supervision system for Pego electronic
controls with RS485 output.
• Allows interaction with instruments.
• Suitable for local networks (LAN) in client/server
configuration. TWMT Temperature acquisition module (with NTC probe included) to
• Control of work cycles with automatic be connected to interface module TWRS485.
modification of parameters over time.
• Integrated data backup and restore. TWMP Pressure acquisition module (with 4 – 20 mA probe, not included)
• Remote system control. to be connected to interface module TWRS485.
• Home page can be configured to show selected TWMUR Humidity acquisition module (with 4 – 20 mA probe, not
instrument data. included) to be connected to interface module TWRS485.
• Customised graphics with parameters comparison.
• A differentiated alarm management and TWMIO Digital input status-recognition module with 3 digital inputs and
trasmission of e-mails to mobile phones and relay output.
computers to inform user of alarm activation/
TWMA Alarm module.
deactivation.
• User-friendly programme updating with download
from PEGO website. All TWM modules requires an external 12V power supply.
• No limit to connectable instruments with the
addition of TWRS 485 interfaces (unique interface
available for connection up to 64 instruments).

58 59
ecp ape 03 man in cold room alarm
z002.gb.02

Man in cold room alarm kit: consisting


of control unit with acoustic / visual
warning, comes complete with buffer

193
battery and luminous emergency in-
room pushbutton.

68
68 53

203 79

TECHNICAL CHARACTERISTICS ECP APE 03

weight 2 Kg
Main power supply 230 V AC 50 Hz
Max consumption on main
20 mA
applications Component parts power supply
12 VDC Ni-MH 1300 mAh
• “Man in room” safety system for • Emergency pushbutton to be fitted inside cold Buffer battery
Complete recharge time: 110 H
low-temperature rooms. room. This is a luminous mushroom-shaped • with 230 V AC power OFF
Autonomy (operation with charged buffer battery: about 14 hrs)
pushbutton with a N.C. contact. The pushbutton • with 230 V AC power ON: unlimited.
is illuminated by LEDs, thus making it easy to find External module IP 43 protection rating
SYSTEM DESCRIPTION even in the dark. Working temperature -5 ÷ +45 °C

• Acoustic-visual alarm control unit to be fitted Type: piezoelectric


The man in cold room alarm kit allows a person Acoustic characteristics
Sound power: 95 dB at 1 m
trapped inside the cold room to activate outside the room. Features a siren and a flashing Visual warning Red flashing LED 12 V DC
an acoustic-luminous alarm installed outside the light and a buffer battery to provide power in the In-room emergency pushbutton Red flashing LED 12 V DC
N.C. contact
room and so call for help. The system will work event of a black-out. Also has a clean contact In-room emergency pushbutton
Keyboard with IP 65 Protection rating
even in the event of a temporary power cut (closed when alarm is active) that can be used to Operating temperature: -25 - +70°C

inhibit refrigeration, switch on the interior room Auxiliary relay 8A AC1 (contact closes when alarm is switched on)
thanks to the buffer battery on the external unit.
light or activate other devices such as a dialler for
remote alarm activation.

battery 1 v dC (+)
battery 1 v dC (-)
Common (+) alarm
acoustic-visual alarm control unit Common (-)
fixed alarm output (-)

with
intermittent alarm output (-)
-tone alarm output (-)

power supply

emergency pushbutton
(install inside the cold room)

60 61
Printed in January 2009.

The images and technical characteristics descripted in


this book are purely indicative. Pego is not responsible
for any changes following the pubblication of this volume.