You are on page 1of 29

APPENDIX - 1

RELAY SETTINGS TABLES


PLANT ELECTRICAL SYSTEM

NOTES :
1. This document lists the recommended settings for various protections as per requirement. However, in Siemens relays all other functions such as monitoring and measurement
shall be set at site. Further, address details of each function shall be site verified as per relay manual.
2. Settings for relays in DG Breaker panel and DG Controller PCC 3100 shall be done by DG vendor M/s Powerica.

04

03
Aker Powergas Pvt. Ltd.
02

01 CLIENT : HINDUSTAN TITLE : PROTECTION


UNILEVER LTD. SETTINGS CALCULATIONS
SPA NEJ 00
11/11/09 11/11/09 ISSUED FOR ENGINEERING DOC NO.1607/4000/CAL007
MADE CHECKED REV SHT 1 OF 7 REV
BY & DATE BY & DATE STATUS 00
JOB NO : 2090/1607
Aker Powergas Pvt. Ltd. RELAY SETTINGS TABLE CLIENT : HINDUSTAN UNILEVER LTD.
PCC - CLS PLANT UNIT-8 : P05 DOC NO : 1607/4000/CAL006
REV NO : 00 DATE : 11/11/09
Feeder Relay / Relay /
Breaker Feeder Setting Recommended
(breaker) Panel No CT Ratio Release Release Setting Function Range Available Remarks
No. Nos Parameter Settings
Rating Make Type
400A O/G P05 11F3, - Merlin STR53UE
Feeder 12F3, Gerin I0 0.5, 0.63, 0.7, 0.8,
0.8 In
13F3, 0.9, 1 times In
14F3,
1F3, 0.8, 0.85, 0.88, 0.9,
2F3, L
Ir 0.93, 0.95, 0.98, 1 1 Io
4F3, times Io
5F3
tr @ 6 Ir 0.4, 2, 4, 8, 16 sec 2 sec

Isd 1.5, 2, 3, 4, 5, 6, 7,
6 In
8, 9, 10 times Ir
S

tsd I2 t function is turned


0, 0.1, 0.2, 0.3 sec 0.1 sec
off
1.5, 2, 3, 4, 6, 8,
I Ii 10 In No time delay
10, 11 times In
Ig 0.2, 0.3, 0.4, 0.6,
0.3 In
0.8, 1 times In
G
tg 0.1, 0.2, 0.3, 0.4
0.1 sec
sec

Page 2 of 29
JOB NO : 2090/1607
Aker Powergas Pvt. Ltd. RELAY SETTINGS TABLE CLIENT : HINDUSTAN UNILEVER LTD.
PCC - CLS PLANT UNIT-8 : P05 DOC NO : 1607/4000/CAL006
REV NO : 00 DATE : 11/11/09
Feeder Relay / Relay /
Breaker Feeder Setting Recommended
(breaker) Panel No CT Ratio Release Release Setting Function Range Available Remarks
No. Nos Parameter Settings
Rating Make Type
630A O/G P05 8F1, - Merlin STR53UE
Feeder 8F2, Gerin I0 0.5, 0.63, 0.7, 0.8,
0.8 In
9F1, 0.9, 1 times In
9F2,
11F1,
11F2, L 0.8, 0.85, 0.88, 0.9,
12F1, Ir 0.93, 0.95, 0.98, 1 1 Io
12F2, times Io
13F1,
13F2, tr @ 6 Ir 0.4, 2, 4, 8, 16 sec 2 sec
14F1,
14F2, 1.5, 2, 3, 4, 5, 6, 7,
1F1, Isd 6 In
8, 9, 10 times Ir
1F2, S
2F1, tsd I2 t function is turned
0, 0.1, 0.2, 0.3 sec 0.1 sec
2F2, off
4F1, 1.5, 2, 3, 4, 6, 8,
4F2, I Ii 10 In No time delay
10, 11 times In
5F1,
5F2 Ig 0.2, 0.3, 0.4, 0.6,
0.3 In
0.8, 1 times In
G
tg 0.1, 0.2, 0.3, 0.4
0.1 sec
sec

Page 3 of 29
JOB NO : 2090/1607
Aker Powergas Pvt. Ltd. RELAY SETTINGS TABLE CLIENT : HINDUSTAN UNILEVER LTD.
PCC - CLS PLANT UNIT-8 : P05 DOC NO : 1607/4000/CAL006
REV NO : 00 DATE : 11/11/09
Feeder Relay / Relay /
Breaker Feeder Setting Recommended
(breaker) Panel No CT Ratio Release Release Setting Function Range Available Remarks
No. Nos Parameter Settings
Rating Make Type
1250A O/G P05 7F1, - Siemens ETU27B IR 0.4 - 1.0 In 0.55 In
Feeder 7F2 L
tR 10 sec @ 6 IR 10 sec @ 6 IR
Isd 1.25 - 12 In 1.25 In
S
tsd 0 - 0.4 sec 0.3 sec
I Ii 20 In (fixed) 20 In (fixed)
A-100A, B-300A,
Ig Trip : C - 600 A
C-600A, D-
G Alarm : B - 300 A
900A, E-1200A
tg 0.1 - 0.5 sec 0.1 sec

Page 4 of 29
JOB NO : 2090/1607
Aker Powergas Pvt. Ltd. RELAY SETTINGS TABLE CLIENT : HINDUSTAN UNILEVER LTD.
PCC - CLS PLANT UNIT-8 : P05 DOC NO : 1607/4000/CAL006
REV NO : 00 DATE : 11/11/09
Feeder Relay / Relay /
Breaker Feeder Setting Recommended
(breaker) Panel No CT Ratio Release Release Setting Function Range Available Remarks
No. Nos Parameter Settings
Rating Make Type
3200A P05 3200/1A Siemens 7SJ600 Rated current IN 1 or 5A 1A
Incomer BUS-A 11F1 Rated frequency fN 50 or 60Hz 50Hz
BUS-B 3F1 I> 0.1 to 25 IN 2.5

Definite Time T I> 0 to 60 sec 0.25


Overcurrent Phase I>> 0.1 to 25 IN Blocked
Protection - 50 T I>> 0 to 60 sec Blocked
I>>> Blocked

O/C Pickup- Ip 0.1 to 4 IN 1 IN


Inverse Time
Overcurrent Phase Characteristics IEC or ANSI IEC-Very Inverse
Protection - 51
TMS - Tp 0.05 to 3.2 sec 0.25
IE> 0.05 to 25 IN 0.15
T IE> 0 to 60 sec 0.2
Definite Time
Overcurrent Earth IE>> 0.05 to 25 IN Blocked
Protection - 50N T IE>> 0 to 60 sec Blocked
IE>>> Blocked

O/C Pickup- Ip 0.05 to 4 IN 0.1 IN


Inverse Time
Overcurrent Earth
Characteristics IEC or ANSI IEC-Normal Inverse
Protection - 51N
TMS - Tp 0.05 to 3.2 sec 0.3

Page 5 of 29
JOB NO : 2090/1607
Aker Powergas Pvt. Ltd. RELAY SETTINGS TABLE CLIENT : HINDUSTAN UNILEVER LTD.
PCC - CLS PLANT UNIT-8 : P05 DOC NO : 1607/4000/CAL006
REV NO : 00 DATE : 11/11/09
Feeder Relay / Relay /
Breaker Feeder Setting Recommended
(breaker) Panel No CT Ratio Release Release Setting Function Range Available Remarks
No. Nos Parameter Settings
Rating Make Type

Page 6 of 29
JOB NO : 2090/1607
Aker Powergas Pvt. Ltd. RELAY SETTINGS TABLE CLIENT : HINDUSTAN UNILEVER LTD.
PCC - CLS PLANT UNIT-8 : P05 DOC NO : 1607/4000/CAL006
REV NO : 00 DATE : 11/11/09
Feeder Relay / Relay /
Breaker Feeder Setting Recommended
(breaker) Panel No CT Ratio Release Release Setting Function Range Available Remarks
No. Nos Parameter Settings
Rating Make Type
3200A P05 3200/1A Areva CAG-14 REF Protection Pickup Current 10 to 40% 10%
Incomer BUS-A 11F1 Stab Resi 0 to 1000 ohm 740 ohms
BUS-B 3F1 3200/5A Areva CDG-11 SBEF Protection Current setting 10 to 40% 40%
TMS 0.1 to 1.0 0.4

110V Ph-Ph Areva VAGM22 U/V Protection

Rated voltage Vn 110V


U/V setting Vs 40% to 80% 80%
Areva VTT11 Time Delay for U/V
Timer Td 0.5 to 5 sec 5 seconds

Page 7 of 29
JOB NO : 2090/1607
Aker Powergas Pvt. Ltd. RELAY SETTINGS TABLE CLIENT : HINDUSTAN UNILEVER LTD.
PCC - CLS PLANT UNIT-8 : P05 DOC NO : 1607/4000/CAL006
REV NO : 00 DATE : 11/11/09
Relay / Relay /
Feeder Feeder Feeder CT Setting Recommended
Panel No Release Release Setting Function Range Available Remarks
Description Rating Nos Ratio Parameter Settings
Make Type

MCC404-A1 630A O/G P05 20F1 - SIEMENS ETU42 Ir 0.4 - 1.0 In 0.4 In
L
MCC404-A2 Feeder 19F1 tr @ 6 Ir 2.5 to 30 sec 2.5 sec

MCC404-A8 17F1 Isd 1.5 - 10 Ir 1.5 Ir


S I2 t function is turned
tsd 0 to 0.5 sec 0.2 sec
off
I Ii 1.25 - 11 In 1.25 In No time delay

Method-1

I∆n 0.4 - 1.0 In NA

G Method-2
Ig 0.4 - 1.0 In 0.4 In
tg 0.1 to 0.5 sec 0.1 sec

MCC404-A7 630A O/G P05 18F1 - SIEMENS ETU42 Ir 0.4 - 1.0 In 0.5 In
L
Feeder tr @ 6 Ir 2.5 to 30 sec 2.5 sec
Isd 1.5 - 10 Ir 1.5 Ir
S I2 t function is turned
tsd 0 to 0.5 sec 0.2 sec
off
I Ii 1.25 - 11 In 1.25 In No time delay
JOB NO : 2090/1607
Aker Powergas Pvt. Ltd. RELAY SETTINGS TABLE CLIENT : HINDUSTAN UNILEVER LTD.
PCC - CLS PLANT UNIT-8 : P05 DOC NO : 1607/4000/CAL006
REV NO : 00 DATE : 11/11/09
Relay / Relay /
Feeder Feeder Feeder CT Setting Recommended
Panel No Release Release Setting Function Range Available Remarks
Description Rating Nos Ratio Parameter Settings
Make Type

Method-1

I∆n 0.4 - 1.0 In NA

G Method-2
Ig 0.4 - 1.0 In 0.4 In
tg 0.1 to 0.5 sec 0.1 sec

8-X-902 630A O/G P05 14F2 - SIEMENS ETU42 Ir 0.4 - 1.0 In 0.85 In
L
8-X-904 Feeder 16F1 tr @ 6 Ir 2.5 to 30 sec 2.5 sec
Isd 1.5 - 10 Ir 1.5 Ir
S I2 t function is turned
tsd 0 to 0.5 sec 0.2 sec
off
I Ii 1.25 - 11 In 1.5 In No time delay

Method-1

I∆n 0.4 - 1.0 In NA

G Method-2
Ig 0.4 - 1.0 In 0.4 In
tg 0.1 to 0.5 sec 0.1 sec
JOB NO : 2090/1607
Aker Powergas Pvt. Ltd. RELAY SETTINGS TABLE CLIENT : HINDUSTAN UNILEVER LTD.
PCC - CLS PLANT UNIT-8 : P05 DOC NO : 1607/4000/CAL006
REV NO : 00 DATE : 11/11/09
Relay / Relay /
Feeder Feeder Feeder CT Setting Recommended
Panel No Release Release Setting Function Range Available Remarks
Description Rating Nos Ratio Parameter Settings
Make Type

8-X-903B 630A O/G P05 15F1 - SIEMENS ETU42 Ir 0.4 - 1.0 In 0.8 In
L
Feeder tr @ 6 Ir 2.5 to 30 sec 2.5 sec
Isd 1.5 - 10 Ir 1.5 Ir
S I2 t function is turned
tsd 0 to 0.5 sec 0.2 sec
off
I Ii 1.25 - 11 In 1.5 In No time delay

Method-1

I∆n 0.4 - 1.0 In NA

G Method-2
Ig 0.4 - 1.0 In 0.4 In
tg 0.1 to 0.5 sec 0.1 sec

8-X-905A 630A O/G P05 14F1 - SIEMENS ETU42 Ir 0.4 - 1.0 In 1 In


L
Feeder tr @ 6 Ir 2.5 to 30 sec 2.5 sec
Isd 1.5 - 10 Ir 1.5 Ir
S I2 t function is turned
tsd 0 to 0.5 sec 0.2 sec
off
JOB NO : 2090/1607
Aker Powergas Pvt. Ltd. RELAY SETTINGS TABLE CLIENT : HINDUSTAN UNILEVER LTD.
PCC - CLS PLANT UNIT-8 : P05 DOC NO : 1607/4000/CAL006
REV NO : 00 DATE : 11/11/09
Relay / Relay /
Feeder Feeder Feeder CT Setting Recommended
Panel No Release Release Setting Function Range Available Remarks
Description Rating Nos Ratio Parameter Settings
Make Type

I Ii 1.25 - 11 In 1.6 In No time delay

Method-1

I∆n 0.4 - 1.0 In NA

G Method-2
Ig 0.4 - 1.0 In 0.4 In
tg 0.1 to 0.5 sec 0.1 sec

MCC404-A5 400A O/G P05 18F2 - SIEMENS ETU42 Ir 0.4 - 1.0 In 0.6 In
L
Feeder tr @ 6 Ir 2.5 to 30 sec 2.5 sec
Isd 1.5 - 10 Ir 1.5 Ir
S I2 t function is turned
tsd 0 to 0.5 sec 0.2 sec
off
I Ii 1.25 - 11 In 1.25 In No time delay

Method-1

I∆n 0.4 - 1.0 In NA

G Method-2
Ig 0.4 - 1.0 In 0.4 In
tg 0.1 to 0.5 sec 0.1 sec
JOB NO : 2090/1607
Aker Powergas Pvt. Ltd. RELAY SETTINGS TABLE CLIENT : HINDUSTAN UNILEVER LTD.
PCC - CLS PLANT UNIT-8 : P05 DOC NO : 1607/4000/CAL006
REV NO : 00 DATE : 11/11/09
Relay / Relay /
Feeder Feeder Feeder CT Setting Recommended
Panel No Release Release Setting Function Range Available Remarks
Description Rating Nos Ratio Parameter Settings
Make Type

MCC404-A9 400A O/G P05 16F2 - SIEMENS ETU42 Ir 0.4 - 1.0 In 0.6 In
8-AHU-1 & 8- Feeder L
17F2 tr @ 6 Ir 2.5 to 30 sec 2.5 sec
AHU-2
Isd 1.5 - 10 Ir 1.5 Ir
S I2 t function is turned
tsd 0 to 0.5 sec 0.2 sec
off
I Ii 1.25 - 11 In 1.75 In No time delay

Method-1

I∆n 0.4 - 1.0 In NA

G Method-2
Ig 0.4 - 1.0 In 0.4 In
tg 0.1 to 0.5 sec 0.1 sec

MCC404-A3 250A O/G P05 20F2 - SIEMENS ETU42 Ir 0.4 - 1.0 In 0.4 In
L
Feeder tr @ 6 Ir 2.5 to 30 sec 2.5 sec
Isd 1.5 - 10 Ir 2 Ir
S
JOB NO : 2090/1607
Aker Powergas Pvt. Ltd. RELAY SETTINGS TABLE CLIENT : HINDUSTAN UNILEVER LTD.
PCC - CLS PLANT UNIT-8 : P05 DOC NO : 1607/4000/CAL006
REV NO : 00 DATE : 11/11/09
Relay / Relay /
Feeder Feeder Feeder CT Setting Recommended
Panel No Release Release Setting Function Range Available Remarks
Description Rating Nos Ratio Parameter Settings
Make Type
S I2 t function is turned
tsd 0 to 0.5 sec 0.2 sec
off
I Ii 1.25 - 11 In 1.25 In No time delay

Method-1

I∆n 0.4 - 1.0 In NA

G Method-2
Ig 0.4 - 1.0 In 0.4 In
tg 0.1 to 0.5 sec 0.1 sec

MCC404-A4 250A O/G P05 20F3 - SIEMENS ETU42 Ir 0.4 - 1.0 In 0.4 In
L
Feeder tr @ 6 Ir 2.5 to 30 sec 2.5 sec
Isd 1.5 - 10 Ir 1.5 Ir
S I2 t function is turned
tsd 0 to 0.5 sec 0.2 sec
off
I Ii 1.25 - 11 In 1.25 In No time delay

Method-1

I∆n 0.4 - 1.0 In NA

G Method-2
JOB NO : 2090/1607
Aker Powergas Pvt. Ltd. RELAY SETTINGS TABLE CLIENT : HINDUSTAN UNILEVER LTD.
PCC - CLS PLANT UNIT-8 : P05 DOC NO : 1607/4000/CAL006
REV NO : 00 DATE : 11/11/09
Relay / Relay /
Feeder Feeder Feeder CT Setting Recommended
Panel No Release Release Setting Function Range Available Remarks
Description Rating Nos Ratio Parameter Settings
Make Type G
Ig 0.4 - 1.0 In 0.4 In
tg 0.1 to 0.5 sec 0.1 sec

MCC404-A6 250A O/G P05 19F2 - SIEMENS ETU42 Ir 0.4 - 1.0 In 0.45 In
L
Feeder tr @ 6 Ir 2.5 to 30 sec 2.5 sec
Isd 1.5 - 10 Ir 2 Ir
S I2 t function is turned
tsd 0 to 0.5 sec 0.2 sec
off
I Ii 1.25 - 11 In 1.25 In No time delay

Method-1

I∆n 0.4 - 1.0 In NA

G Method-2
Ig 0.4 - 1.0 In 0.4 In
tg 0.1 to 0.5 sec 0.1 sec

LTG-TR-01 250A O/G P05 19F3 - SIEMENS ETU42 Ir 0.4 - 1.0 In 0.75 In
L
Feeder tr @ 6 Ir 2.5 to 30 sec 2.5 sec
JOB NO : 2090/1607
Aker Powergas Pvt. Ltd. RELAY SETTINGS TABLE CLIENT : HINDUSTAN UNILEVER LTD.
PCC - CLS PLANT UNIT-8 : P05 DOC NO : 1607/4000/CAL006
REV NO : 00 DATE : 11/11/09
Relay / Relay /
Feeder Feeder Feeder CT Setting Recommended
Panel No Release Release Setting Function Range Available Remarks
Description Rating Nos Ratio Parameter Settings
Make Type
Isd 1.5 - 10 Ir 2 Ir
S I2 t function is turned
tsd 0 to 0.5 sec 0.2 sec
off
I Ii 1.25 - 11 In 3.5 In No time delay

Method-1

I∆n 0.4 - 1.0 In NA

G Method-2
Ig 0.4 - 1.0 In 0.4 In
tg 0.1 to 0.5 sec 0.1 sec

VFD-U-1 250A O/G P05 15F3 - SIEMENS ETU42 Ir 0.4 - 1.0 In 0.6 In
L
VFD-U-3 Feeder 14F3 tr @ 6 Ir 2.5 to 30 sec 2.5 sec
Isd 1.5 - 10 Ir 1.5 Ir
S I2 t function is turned
tsd 0 to 0.5 sec 0.2 sec
off
I Ii 1.25 - 11 In 1.75 In No time delay

Method-1

G
JOB NO : 2090/1607
Aker Powergas Pvt. Ltd. RELAY SETTINGS TABLE CLIENT : HINDUSTAN UNILEVER LTD.
PCC - CLS PLANT UNIT-8 : P05 DOC NO : 1607/4000/CAL006
REV NO : 00 DATE : 11/11/09
Relay / Relay /
Feeder Feeder Feeder CT Setting Recommended
Panel No Release Release Setting Function Range Available Remarks
Description Rating Nos Ratio Parameter Settings
Make Type

I∆n 0.4 - 1.0 In NA

G Method-2
Ig 0.4 - 1.0 In 0.4 In
tg 0.1 to 0.5 sec 0.1 sec

MCC404-B1 630A O/G P05 7F1 - SIEMENS ETU42 Ir 0.4 - 1.0 In 0.4 In
L
MCC404-B10 Feeder 1F1 tr @ 6 Ir 2.5 to 30 sec 2.5 sec
Isd 1.5 - 10 Ir 1.5 Ir
S I2 t function is turned
tsd 0 to 0.5 sec 0.2 sec
off
I Ii 1.25 - 11 In 1.25 In No time delay
Method-1
I∆n 0.4 - 1.0 In NA
G Method-2
Ig 0.4 - 1.0 In 0.4 In
tg 0.1 to 0.5 sec 0.1 sec
JOB NO : 2090/1607
Aker Powergas Pvt. Ltd. RELAY SETTINGS TABLE CLIENT : HINDUSTAN UNILEVER LTD.
PCC - CLS PLANT UNIT-8 : P05 DOC NO : 1607/4000/CAL006
REV NO : 00 DATE : 11/11/09
Relay / Relay /
Feeder Feeder Feeder CT Setting Recommended
Panel No Release Release Setting Function Range Available Remarks
Description Rating Nos Ratio Parameter Settings
Make Type
MCC404-B2 630A O/G P05 7F2 - SIEMENS ETU42 Ir 0.4 - 1.0 In 0.5 In
L
Feeder tr @ 6 Ir 2.5 to 30 sec 2.5 sec
Isd 1.5 - 10 Ir 1.5 Ir
S I2 t function is turned
tsd 0 to 0.5 sec 0.2 sec
off
I Ii 1.25 - 11 In 1.25 In No time delay
Method-1
I∆n 0.4 - 1.0 In NA
G Method-2
Ig 0.4 - 1.0 In 0.4 In
tg 0.1 to 0.5 sec 0.1 sec

MCC404-B7 630A O/G P05 8F1 - SIEMENS ETU42 Ir 0.4 - 1.0 In 0.6 In
L
Feeder tr @ 6 Ir 2.5 to 30 sec 2.5 sec
Isd 1.5 - 10 Ir 1.5 Ir
S I2 t function is turned
tsd 0 to 0.5 sec 0.2 sec
off
I Ii 1.25 - 11 In 1.5 In No time delay
Method-1
I∆n 0.4 - 1.0 In NA
G Method-2
Ig 0.4 - 1.0 In 0.4 In
JOB NO : 2090/1607
Aker Powergas Pvt. Ltd. RELAY SETTINGS TABLE CLIENT : HINDUSTAN UNILEVER LTD.
PCC - CLS PLANT UNIT-8 : P05 DOC NO : 1607/4000/CAL006
REV NO : 00 DATE : 11/11/09
Relay / Relay /
Feeder Feeder Feeder CT Setting Recommended
Panel No Release Release Setting G
Function Range Available Remarks
Description Rating Nos Ratio Parameter Settings
Make Type
tg 0.1 to 0.5 sec 0.1 sec

8-X-903A 630A O/G P05 6F1 - SIEMENS ETU42 Ir 0.4 - 1.0 In 0.85 In
L
Feeder tr @ 6 Ir 2.5 to 30 sec 2.5 sec
Isd 1.5 - 10 Ir 1.5 Ir
S I2 t function is turned
tsd 0 to 0.5 sec 0.2 sec
off
I Ii 1.25 - 11 In 1.5 In No time delay
Method-1
I∆n 0.4 - 1.0 In NA
G Method-2
Ig 0.4 - 1.0 In 0.4 In
tg 0.1 to 0.5 sec 0.1 sec

8-X-905B 630A O/G P05 5F1 - SIEMENS ETU42 Ir 0.4 - 1.0 In 1 In


L
8-X-905C Feeder 2F1 tr @ 6 Ir 2.5 to 30 sec 2.5 sec
Isd 1.5 - 10 Ir 1.5 Ir
S I2 t function is turned
tsd 0 to 0.5 sec 0.2 sec
off
I Ii 1.25 - 11 In 1.6 In No time delay
Method-1

G
JOB NO : 2090/1607
Aker Powergas Pvt. Ltd. RELAY SETTINGS TABLE CLIENT : HINDUSTAN UNILEVER LTD.
PCC - CLS PLANT UNIT-8 : P05 DOC NO : 1607/4000/CAL006
REV NO : 00 DATE : 11/11/09
Relay / Relay /
Feeder Feeder Feeder CT Setting Recommended
Panel No Release Release Setting Function Range Available Remarks
Description Rating Nos Ratio Parameter Settings
Make Type
I∆n 0.4 - 1.0 In NA
G Method-2
Ig 0.4 - 1.0 In 0.4 In
tg 0.1 to 0.5 sec 0.1 sec

MCC404-B6 400A O/G P05 5F2 - SIEMENS ETU42 Ir 0.4 - 1.0 In 0.4 In
L
Feeder tr @ 6 Ir 2.5 to 30 sec 2.5 sec
Isd 1.5 - 10 Ir 1.5 Ir
S I2 t function is turned
tsd 0 to 0.5 sec 0.2 sec
off
I Ii 1.25 - 11 In 1.25 In No time delay

Method-1

I∆n 0.4 - 1.0 In NA

G Method-2
Ig 0.4 - 1.0 In 0.4 In
tg 0.1 to 0.5 sec 0.1 sec

MCC404-B8 400A O/G P05 2F2 - SIEMENS ETU42 Ir 0.4 - 1.0 In 0.7 In
L
JOB NO : 2090/1607
Aker Powergas Pvt. Ltd. RELAY SETTINGS TABLE CLIENT : HINDUSTAN UNILEVER LTD.
PCC - CLS PLANT UNIT-8 : P05 DOC NO : 1607/4000/CAL006
REV NO : 00 DATE : 11/11/09
Relay / Relay /
Feeder Feeder Feeder CT Setting Recommended
Panel No Release Release Setting Function Range Available Remarks
Description Rating Nos Ratio Parameter Settings
Make Type
L
Feeder tr @ 6 Ir 2.5 to 30 sec 2.5 sec
Isd 1.5 - 10 Ir 1.5 Ir
S I2 t function is turned
tsd 0 to 0.5 sec 0.2 sec
off
I Ii 1.25 - 11 In 1.5 In No time delay

Method-1

I∆n 0.4 - 1.0 In NA

G Method-2
Ig 0.4 - 1.0 In 0.4 In
tg 0.1 to 0.5 sec 0.1 sec

8-AHU-3 & 8- - SIEMENS ETU42 Ir


400A O/G P05 6F2 0.4 - 1.0 In 0.6 In
AHU-4 L
Feeder tr @ 6 Ir 2.5 to 30 sec 2.5 sec
Isd 1.5 - 10 Ir 1.5 Ir
S I2 t function is turned
tsd 0 to 0.5 sec 0.2 sec
off
I Ii 1.25 - 11 In 1.75 In No time delay

Method-1

G
JOB NO : 2090/1607
Aker Powergas Pvt. Ltd. RELAY SETTINGS TABLE CLIENT : HINDUSTAN UNILEVER LTD.
PCC - CLS PLANT UNIT-8 : P05 DOC NO : 1607/4000/CAL006
REV NO : 00 DATE : 11/11/09
Relay / Relay /
Feeder Feeder Feeder CT Setting Recommended
Panel No Release Release Setting Function Range Available Remarks
Description Rating Nos Ratio Parameter Settings
Make Type

I∆n 0.4 - 1.0 In NA

G Method-2
Ig 0.4 - 1.0 In 0.4 In
tg 0.1 to 0.5 sec 0.1 sec

MCC404-B3 250A O/G P05 7F3 - SIEMENS ETU42 Ir 0.4 - 1.0 In 0.4 In
L
MCC404-B5 Feeder 8F3 tr @ 6 Ir 2.5 to 30 sec 2.5 sec
Isd 1.5 - 10 Ir 2 Ir
S I2 t function is turned
tsd 0 to 0.5 sec 0.2 sec
off
I Ii 1.25 - 11 In 1.25 In No time delay

Method-1

I∆n 0.4 - 1.0 In NA

G Method-2
Ig 0.4 - 1.0 In 0.4 In
tg 0.1 to 0.5 sec 0.1 sec
JOB NO : 2090/1607
Aker Powergas Pvt. Ltd. RELAY SETTINGS TABLE CLIENT : HINDUSTAN UNILEVER LTD.
PCC - CLS PLANT UNIT-8 : P05 DOC NO : 1607/4000/CAL006
REV NO : 00 DATE : 11/11/09
Relay / Relay /
Feeder Feeder Feeder CT Setting Recommended
Panel No Release Release Setting Function Range Available Remarks
Description Rating Nos Ratio Parameter Settings
Make Type

MCC404-B4 250A O/G P05 6F3 - SIEMENS ETU42 Ir 0.4 - 1.0 In 0.4 In
L
Feeder tr @ 6 Ir 2.5 to 30 sec 2.5 sec
Isd 1.5 - 10 Ir 1.5 Ir
S I2 t function is turned
tsd 0 to 0.5 sec 0.2 sec
off
I Ii 1.25 - 11 In 1.25 In No time delay

Method-1

I∆n 0.4 - 1.0 In NA

G Method-2
Ig 0.4 - 1.0 In 0.4 In
tg 0.1 to 0.5 sec 0.1 sec

MCC404-B9 250A O/G P05 5F3 - SIEMENS ETU42 Ir 0.4 - 1.0 In 0.75 In
L
Feeder tr @ 6 Ir 2.5 to 30 sec 2.5 sec
Isd 1.5 - 10 Ir 1.75 Ir
S I2 t function is turned
tsd 0 to 0.5 sec 0.2 sec
off
I Ii 1.25 - 11 In 2.25 In No time delay
JOB NO : 2090/1607
Aker Powergas Pvt. Ltd. RELAY SETTINGS TABLE CLIENT : HINDUSTAN UNILEVER LTD.
PCC - CLS PLANT UNIT-8 : P05 DOC NO : 1607/4000/CAL006
REV NO : 00 DATE : 11/11/09
Relay / Relay /
Feeder Feeder Feeder CT Setting Recommended
Panel No Release Release Setting Function Range Available Remarks
Description Rating Nos Ratio Parameter Settings
Make Type

Method-1

I∆n 0.4 - 1.0 In NA

G Method-2
Ig 0.4 - 1.0 In 0.4 In
tg 0.1 to 0.5 sec 0.1 sec

VFD-U-2 250A O/G P05 1F2 - SIEMENS ETU42 Ir 0.4 - 1.0 In 0.6 In
L
Feeder tr @ 6 Ir 2.5 to 30 sec 2.5 sec
Isd 1.5 - 10 Ir 1.5 Ir
S I2 t function is turned
tsd 0 to 0.5 sec 0.2 sec
off
I Ii 1.25 - 11 In 1.75 In No time delay

Method-1

I∆n 0.4 - 1.0 In NA

G Method-2
Ig 0.4 - 1.0 In 0.4 In
tg 0.1 to 0.5 sec 0.1 sec
JOB NO : 2090/1607
Aker Powergas Pvt. Ltd. RELAY SETTINGS TABLE CLIENT : HINDUSTAN UNILEVER LTD.
PCC - CLS PLANT UNIT-8 : P05 DOC NO : 1607/4000/CAL006
REV NO : 00 DATE : 11/11/09
Relay / Relay /
Feeder Feeder Feeder CT Setting Recommended
Panel No Release Release Setting Function Range Available Remarks
Description Rating Nos Ratio Parameter Settings
Make Type

LTG-TR-02 250A O/G P05 2F3 - SIEMENS ETU42 Ir 0.4 - 1.0 In 0.75 In
L
Feeder tr @ 6 Ir 2.5 to 30 sec 2.5 sec
Isd 1.5 - 10 Ir 2 Ir
S I2 t function is turned
tsd 0 to 0.5 sec 0.2 sec
off
I Ii 1.25 - 11 In 3.5 In No time delay

Method-1

I∆n 0.4 - 1.0 In NA

G Method-2
Ig 0.4 - 1.0 In 0.4 In
tg 0.1 to 0.5 sec 0.1 sec

8-BCP-1 125A O/G P05 9F2 - SIEMENS ETU42 Ir 0.4 - 1.0 In 0.25 In
L
Feeder tr @ 6 Ir 2.5 to 30 sec 2.5 sec
Isd 1.5 - 10 Ir 2 Ir
S I2 t function is turned
tsd 0 to 0.5 sec 0.2 sec
off
JOB NO : 2090/1607
Aker Powergas Pvt. Ltd. RELAY SETTINGS TABLE CLIENT : HINDUSTAN UNILEVER LTD.
PCC - CLS PLANT UNIT-8 : P05 DOC NO : 1607/4000/CAL006
REV NO : 00 DATE : 11/11/09
Relay / Relay /
Feeder Feeder Feeder CT Setting Recommended
Panel No Release Release Setting Function Range Available Remarks
Description Rating Nos Ratio Parameter Settings
Make Type

I Ii 1.25 - 11 In 3.5 In No time delay

Method-1

I∆n 0.4 - 1.0 In NA

G Method-2
Ig 0.4 - 1.0 In 0.4 In
tg 0.1 to 0.5 sec 0.1 sec

412-CAP PNL- 1250A P05 Ir


9F1 - SIEMENS ETU42 0.4 - 1.0 In 0.9 In
02 O/G
Feeder L
412-CAP PNL- tr @ 6 Ir
13F1 2.5 to 30 sec 2.5 sec
01
Isd 1.5 - 10 Ir 1.5 Ir
S I2 t function is turned
tsd 0 to 0.5 sec 0.2 sec
off
I Ii 1.25 - 11 In 1.6 In No time delay

Method-1

I∆n 0.4 - 1.0 In NA


G
Method-2
Ig 0.4 - 1.0 In 0.4 In
JOB NO : 2090/1607
Aker Powergas Pvt. Ltd. RELAY SETTINGS TABLE CLIENT : HINDUSTAN UNILEVER LTD.
PCC - CLS PLANT UNIT-8 : P05 DOC NO : 1607/4000/CAL006
REV NO : 00 DATE : 11/11/09
Relay / Relay / G
Feeder Feeder Feeder CT Setting Recommended
Panel No Release Release Setting Function Range Available Remarks
Description Rating Nos Ratio Parameter Settings
Make Type
tg 0.1 to 0.5 sec 0.1 sec
JOB NO : 2090/1607
Aker Powergas Pvt. Ltd. RELAY SETTINGS TABLE CLIENT : HINDUSTAN UNILEVER LTD.
PCC - CLS PLANT UNIT-8 : P05 DOC NO : 1607/4000/CAL006
REV NO : 00 DATE : 11/11/09
Feeder Relay / Relay /
Feeder CT Setting Recommended
(breaker) Swbd No. Release Release Setting Function Range Available Remarks
Nos Ratio Parameter Settings
Rating Make Type
1250A 33kV O/G Siemens 7SJ600 Rated current IN 1 or 5A 5A Back-up O/C & E/F
50/5A
Feeder to Rated frequency fN 50 or 60Hz 50Hz
Tr-05 1 I> 0.1 to 25 IN 11.5 IN
Tr-06 3 Definite Time T I> 0 to 60 sec 0 sec
Overcurrent 0.1 to 25 IN
I>> Blocked
Phase Protection -
50 T I>> 0 to 60 sec Blocked
I>>> Blocked
O/C Pickup- Ip 0.1 to 4 IN 0.9 IN
Inverse Time
Overcurrent Characteristics IEC or ANSI IEC-Very Inverse
Phase Protection -
51 TMS - Tp 0.05 to 3.2 sec 0.4
IE> 0.05 to 25 IN 0.8 IN
T IE> 0 to 60 sec 0.1 sec
Definite Time
Overcurrent Earth IE>> 0.05 to 25 IN 6 IN
Protection - 50N T IE>> 0 to 60 sec 0 sec
IE>>> Blocked
O/C Pickup- Ip 0.05 to 4 IN 0.1 IN
Inverse Time IEC-Standard
Overcurrent Earth Characteristics IEC or ANSI
(Normal) Inverse
Protection - 51N
TMS - Tp 0.05 to 3.2 sec 0.15

Page 27 of 29
JOB NO : 2090/1607
Aker Powergas Pvt. Ltd. RELAY SETTINGS TABLE CLIENT : HINDUSTAN UNILEVER LTD.
PCC - CLS PLANT UNIT-8 : P05 DOC NO : 1607/4000/CAL006
REV NO : 00 DATE : 11/11/09
Feeder Relay / Relay /
Feeder CT Setting Recommended
(breaker) Swbd No. Release Release Setting Function Range Available Remarks
Nos Ratio Parameter Settings
Rating Make Type

1250A 33kV I/C 2 Siemens 7SJ680 Rated current IN 1 or 5A 5A Back-up O/C & E/F
100/5A
Feeder Rated frequency fN 50 or 60Hz 50Hz
I> 0.5 to 175 IN Blocked
Definite Time T I> 0 to 60 sec Blocked
Overcurrent 0.5 to 175 IN
I>> Blocked
Phase Protection -
50 T I>> 0 to 60 sec Blocked
I>>> Blocked
O/C Pickup- Ip 0.5 to 20 IN 4 IN
Inverse Time
Overcurrent Characteristics IEC or ANSI IEC-Very Inverse
Phase Protection -
51 TMS - Tp 0.05 to 3.2 sec 0.3
IE> 0.25 to 175 IN 0.8 IN
T IE> 0 to 60 sec 0.2 sec
Definite Time
Overcurrent Earth IE>> 0.25 to 175 IN 6 IN
Protection - 50N T IE>> 0 to 60 sec 0 sec
IE>>> Blocked
O/C Pickup- Ip 0.25 to 20 IN 0.4 IN
Inverse Time IEC-Standard
Overcurrent Earth Characteristics IEC or ANSI
(Normal) Inverse
Protection - 51N
TMS - Tp 0.05 to 3.2 sec 0.3
Rated voltage
110V 110V
Vn
U/V Protection - U/V setting
40% to 80% 0.8
27 Vs
Time Delay for
U/V 'Td'
Page 28 of 29
JOB NO : 2090/1607
Aker Powergas Pvt. Ltd. RELAY SETTINGS TABLE CLIENT : HINDUSTAN UNILEVER LTD.
OTI AND WTI SETTINGS FOR 2 MVA TRANSFORMER DOC NO : 1607/4000/CAL006
REV NO : 00 DATE : 11/11/09
Feeder Relay / Relay /
Setting Range
(breaker) CT Ratio Release Release Setting Title Recommended Settings Remarks
Parameter Available
Rating Make Type
WTI Alarm - - 850C
WTI Trip - - 900C
These seetings are recommended by transformer manufacturer, Voltamp considering 50% to 60% loading of transformer.

Page 29 of 29