Digital V, A Meters
QUICK START GUIDE
Need to know about Refer
List of safety symbols used 1.1
Safety first 1.2
Box contents 2.1
Electrical & Mechanical installations 2.2
Mechanical dimensions & Panel cut-out 2.3
Wiring diagrams 2.4
Intuitive Dual function key 3.1
Menu Hierarchy 3.2

Setup Menu - Editing CT/PT ratio 3.3 This document is applicable for DM3110 & DM3210 meters
ISO 14001:2004 Certified
ISO 9001:2000 Certified
www.conzerv.com

Caution, Risk of danger – Documentation should be consulted


wherever the symbol is used.

Caution, Risk of electric shock which can cause severe injury or


invoice death.

User accessible area is protected through out by DOUBLE


INSULATION

Measurement category III

+
Intended use: DM3000 series meters are designed for use in Industrial
& Commercial Installations, not for domestic use.
+
Building installation shall be included with a disconnecting device like
switch or circuit breaker, with clear ON/OFF markings and within close
proximity to equipment and the reach of operator, to cut-off the supply
mains in case of any hazardous voltages.
+
The protection provided by the manufacturer will be impaired, if the
equipment is not used in the specified manner.
+
Only qualified and trained personnel should carry out
+ Installation & wiring
+ Disconnection & removal of the meter
+
De-energize the connected circuits before meter installation or
Disconnection.
+
Always use a properly rated voltage sensing device to confirm that all
power is off.
+
Before performing Dielectric (Hi-Pot) or Megger testing on any equipment
in which the DM3000 series meter is installed, disconnect all input and
output wires to the meter. High voltage testing may damage electronic
components contained in the DM3000 series meter.
+
During normal operation of this meter, hazardous voltages might be
present at the rear terminals, which can cause severe injury or death.
+
High voltages are likely to be present inside even after the meter
has been switched off.
+
Do not open the cover of the meter – there are no user serviceable
parts inside.
+
Contact your nearest authorized Schneider Electric Conzerv service
center for all your servicing requirements.

Page 1 of 2
2.1 Box contents 3.1 Intuitive Dual function key
+
V, A meter: One number Duration of press Output
+
Quick start guide (QSG): One number Five seconds Setup entry
+
Test and calibration certificate for the meter: One number
Long press - Digit/Value selection to edit in setup
2.2
+
Electrical & Mechanical installations
Connecting cable recommendations
Two seconds
+
Scroll down through the display pages
Short press -
Insulation Rating Current Rating Simple one touch +
Digit/Value editing in setup

Voltage Circuit > 480 VAC > 0.1 A 3.2 Menu Hierarchy
Current Circuit > 480 VAC > 7.5 A DM3110 DM3210
Or 2.5 mm2 minimum A1 V1

+
Tools & Equipments V2
A2

V3
A3

V12

V23
< 5 mm. Diameter = 5 mm or more will get stuck in the safety
cover V31

Tightening Torque: (2.5 to 6) N.m


Loosening Torque: (5.5 to 6) N.m 3.3 Setup Menu - Editing CT/PT ratio V02.01
Torque greater than 6 N.m may strip the screw or break the To edit CT ratio
safety cover.
The following example explains how to set the CT ratio 2500/5 i.e. 0500 in
DM3110 Ammeter.
CT ratio
Schneider Electric Conzerv recommends the use of insulated
sleeved U lugs (2.5 mm2) for wiring terminals. Don’t use pin Run mode 0100 0 100 0 1 00
lugs which may reduce the safety isolation
Short press
continuously until

2.3 Mechanical dimensions & recommended panel cut-out 0 5 00 0500

- Key Long press - Digit/Value selection


- Key Short press 1 - Digit/Value 1 is selected PASS

1. From Run mode, press for five seconds.


2. The meter flashes CTr and shows the default value 0100 indicating the
successful entry to setup mode.
3. Long press .
4. The display shows 0100 with 0 blinking.
5. Long press .
6. The display shows 0100 with 1 blinking.
7. Short press four times.
Not to scale 8. The display shows 0500 with 5 blinking.
All dimensions in mm 9. To accept the new value, long press .
10.The new value is accepted.
2.4 Wiring diagrams 11.To save the new value, short press .
12.The display flashes PASS and come out of the setup mode.
DM3110 - 3 f
Ammeter CT
Line Load
L1 To edit PT ratio
S1 S2
L2 S1 S2 The following example explains how to set the PT ratio 11kV/110 i.e. 100 in
L3
S1 S2 DM3210 Voltmeter.

* * * * other meter in series

50mA to 6A
S/N:xxxxxx/xxxxxx-xxxx Acc Cl: x.x

VER:xx.xx.xx
9 0 t o 300 Vac 50/60 Hz

Fuse
0.25 A - Key Long press - Digit/Value selection
- Key Short press 1 - Digit/Value 1 is selected

Aux supply (Control power)


90 to 300 VAC
DM3210 - 3 f
Voltmeter
Line Load 1. From Run mode, press for five seconds.
L1
L2 2. The meter flashes PTr and shows the default value 1.000 indicating the
L3 successful entry to setup mode.
N
3. Long press four times.
4. The display shows 1.000 with last digit/value 0 blinking.
5. Long press .
S/N:xxxxxx/xxxxxx-xxxx Acc Cl: x.x
6. The display shows 1.000 with “.” blinking.
VER:xx.xx.xx
80 to 480 Vac(LL) 9 0 t o 300 Vac 50/60 Hz 7. Short press twice to shift the decimal point.
8. The display shows 100.0 with “.” blinking.
9. To accept the new value, long press .
SEC/DM3000/0610/V2

Fuse Fuse
0.25 A 0.25 A Use PT, if VLL > 480V
10.The new value is accepted.
11.To save the new value, short press .
Aux supply (control power) 12.The display flashes PASS and come out of the setup mode.
90 to 300 VAC
NOTE:
1. The maximum value for PTr and CTr setting is 9999.
2. To edit the CTr/PTr values again, long press and repeat the above steps.