You are on page 1of 13

Measuring earth resistance 1.

5 Avoiding hazards
and measuring errors
The process of measurement and any accom-
E. Hering, Dresden (Germany) panying procedures (e.g. breaking standard
connections and making non-standard con-
Earth resistance is a key parameter in determining the efficiency of earthing nections) must not pose a safety hazard ([3],
systems. In this article we look at the measurement of earth resistance. sec. 61.1.3). The magnitude of the test volta-
ge or the test current must be limited (see secti-
ons 3.1 and 4.1). Before breaking a connecti-
on that is required for electric shock prevention,
tems in low-voltage installations ([1], sec- the entire power installation must be discon-
tions 411.5 and 411.6; [2]); nected from the supply and locked out to pre-
1 A few fundamentals • Joint earthing system for high-voltage pro- vent it being switched on again.
tective earthing and functional earthing in Any measurement that involves breaking con-
1.1 Earth resistance and transformer substations; nections (e.g. opening the inspection joint of a
earth impedance • Earthing system for the neutral earthing reac- lightning protection system) must never be car-
The efficiency of an earthing system is princi- tor of a medium-voltage distribution system. ried out during a storm or whenever a storm
pally determined by its impedance ZE. As can In the case of lightning protection systems, could be expected. Failure to comply could be
be seen from figure ➊, the earth impedance earthing measurements must be made even hazardous, particularly for the person perfor-
can be expressed as in equation (1): when there is no requirement to comply with a ming the operation. After the measurement has
specific value. The results of repeat tests must been completed, any connections that were
Z E = RE2 + X E2 (1) be compared with those of earlier measure- broken must be properly restored.
ments. If the test current is split so that part of it runs
RE = RD + RM + RC (2) parallel to the earth electrode being measured,
1.3 Standards for the earth resistance displayed by the meter will
As shown in equation (2), the earth resistance measuring instruments be too small. The person conducting the mea-
RE is the sum of the dissipation resistance RD, The standards contain the requirements that surement must therefore be aware of everything
the resistance of the metal conductor that ser- have to be met by the manufacturers of mea- that is connected to the earth electrode under
ves as the earth electrode RM and the resistance suring equipment. For users, these standards test [8]. Measurements must only be carried
of the earthing conductor RC, which runs be- serve only informational purposes. out by competent persons.
tween the main earthing busbar and the earth In low-voltage systems earthing measurements
electrode. The dissipation resistance RD is the must be made using equipment that complies 1.6 Taking the effects of
resistance between the earth electrode and the with the VDE 0413 standards (VDE: Verband weather into account
surrounding soil. The reactance of the earthing der Elektrotechnik Elektronik Informationstech- The specific resistance of soil decreases with in-
system XE can be expressed as: nik e.V./ engl.: Association for Electrical, Elect- creasing temperature and increasing soil mois-
ronic & Information Technologies) (see [3], ture levels. Whereas these effects are of minor
UM
RE = (3) sec. 61.1). All equipment must comply with consequence for foundation earth electrodes in
I the specifications in IEC 61557-1:2007 [4]. In buildings with a basement or for long (vertical)
with addition, equipment must also comply with the rod electrodes, they have to be taken into ac-
XM reactance of the metallic earth electrode following standards depending on the type of count in the case of horizontal surface earth
XC reactance of the earthing conductor. device or measuring method for which it is used: electrodes.
• IEC 61557-5:2007 Equipment for measu- Measurements made during cold, dry weather
For AC supply current the reactance of the earth- ring resistance to earth [5] remain unaffected, but measurement data re-
ing conductor is only significant in the case of • IEC 61557-6:2007 Equipment for testing, corded in warm weather or after a rain shower
extended horizontal earthing strips or long earth measuring or monitoring protective measures have to be adjusted upward.
rods. In all other cases, the difference between involving residual current devices [6]
earth impedance and earth resistance is so • IEC 61557-10:2007 Combined measuring
small that frequently no distinction is made be- equipment [7].
tween these two quantities. The relevant indus- Equipment manufactured in accordance with ZE
XM XC
XE

trial standards also treat earth impedance and earlier editions of the VDE 0413 series of stan-
ϕ
earth resistance as identical. dards can of course also be used.
As earthing measurements are carried out using RD RM RC
an AC supply, it is actually the earth impedan- 1.4 Selecting the right RE
ce that is measured. If the measurement fre- measuring equipment
quency is greater than 50 Hz, a slightly larger It is not enough for users to simply follow the
earth impedance is displayed. However, over- (frequently unclear) instructions provided by ➊ Vector diagram of impedance in an
estimating the earth impedance is not a pro- the manufacturer, they need to be aware of and earthing system
blem, as it errs on the side of safety. understand the measuring method they want Rd dissipation resistance; RE resistance of
to apply. Measuring instruments that do not the earthing system (earth resistance);
1.2 Requirements for make it clear which measuring method is being RM resistance of the metal conductor that
acts as the earth electrode; RC resistance of
earthing measurements applied should not be used.
the earthing conductor (e.g. connection lug,
Earthing measurements are necessary when- Before purchasing equipment, users should re-
cable); XE reactance of the earthing system;
ever compliance with a specified earth resis- quest technical descriptions of the devices of in- XM reactance of the metal conductor that
tance or a particular earth impedance is requi- terest as well as their performance data and, if acts as the earth electrode; XC reactance of
red, as is the case in the following earthing sys- possible, instruction manuals, and should as- the earthing conductor; ZE earth impedance;
tems: sess the equipment on the basis of this docu- ϕ impedance angle.
• Protective earth for TT and IT earthing sys- mentation.

1
1.7 Assessing systems [9]. In general, the results from all the the instrument are shown in red in the dia-
measurement results tests are contained in a single test report. The grams.
Earth resistance meters are not error free. Mea- measurements performed and any accompany- Known measurement methods are listed in
surement errors can occur even if the conditi- ing action that is taken must be described pre- table ➊. The underlying circuit principles are
ons specified in the relevant standards and in- cisely so that they can be reproduced at a later shown in figures À to Õ. The unusually long
strument instruction manuals are complied date. Information that must be provided inclu- names given here to the various methods ensu-
with and even in the absence of interference ef- des: re that the methods can be distinguished unam-
fects. The magnitude of an instrument’s opera- • the measurement method used biguously.
ting error is listed on its technical specification • the type of measuring instrument used Although there are clear differences between
sheet or in its instruction manual. In those me- • the positions of any selector switches, if the individual measurement methods, no one
thods of measuring earth resistance that draw relevant particular method can be said to be ideal. Each
current directly from the power source (see • details of any connections that were broken method has its own particular disadvantages
sections 2.4 and 4), additional measurement or made for the purposes of the measure- such as limited applicability, electric shock ha-
uncertainty can be caused by random current ment. zard, larger measurement errors or requiring
and voltage fluctuations in the supply during The results of the measurement must be stated greater time and effort to complete. The vario-
the measurement. clearly and unambiguously. This also applies to us advantages and disadvantages of the indivi-
Examples of possible operator errors include: any weather-related adjustments of the results dual measurement techniques are described in
• failure to take account of connections detri- that may have been made. more detail in sections 3 and 4. All of the me-
mental to the measurement process The test report is required by thods discussed must only be carried out by
• connecting the instrument leads incorrectly • [3], section 61.1.6 concerning earthing sys- competent persons exercising due care and at-
or selecting the wrong setting on the selector tems in low-voltage networks tention.
switch of the instrument • [10], annex E, section E.7.2.5 concerning In those methods that do not draw current
• inserting the auxiliary earth electrode or lightning protection systems directly from the supply (columns  1 to 6 in
probe in the wrong location • both standards apply if the earthing system table  ➊), the measurement frequency used
• meter reading errors serves both purposes. will be at least 5 Hz above or below the fre-
• failure to implement measures to reduce sys- quencies 16.7 Hz, 50 Hz and integer multi-
tematic measurement errors. ples thereof. This prevents interference from
Results from first-time measurements should supply frequency currents (‘interference cur-
be compared with the project specifications, re- Overview of measurement rents’) that can falsify measurement results.
sults of repeat tests should be compared with
those of earlier measurements. If significant dif-
2 methods for RE In those methods that do draw current directly
from the supply (columns 7 to 9 in table ➊),
ferences are apparent, the possible causes of 2.1 Principles it is of course essential that the supply frequen-
the discrepancy should be determined. The in- There is a wide degree of variation in the inter- cy and measuring frequency are identical. This
fluence of weather on the measurement results nal circuitry of the measuring instruments used means that the interference effects mentioned
and how this can be taken into account is dis- and the layout and arrangement of the external above cannot be ruled out when such methods
cussed in section 1.6. measuring circuits. However, a common featu- are used. However, these methods are simpler
re of all the methods is that they determine the to perform and offer advantages in terms of their
1.8 Test report earth impedance by measuring the voltage applicability.
Measuring earth resistance is only one of seve- across the earthing system for a known test cur-
ral tests that have to be performed on earthing rent. Leads that carry the test current outside of

Table ➊ Overview of earth resistance measuring methods


1 2 3 4 5 6 7 8 9
Designation based on internal circuitry
Balanced-bridge methods Current-voltage methods
Distinction based on whether method draws current directly from supplyv)
yes no
Distinction based on use of probe and/or auxiliary electrodew)
probe and probe, no no probe, no probe and probe, no no probe, no probe PEN or neutral no probex)
auxiliary auxiliary auxiliary auxiliary auxiliary auxiliary conductor in-
electrode electrode electrodex) electrode electrode electrodex), y) stead of probe
(‘stakeless
method’)
Figure
2 3b)z) 3c) 3a) 3b) 3c) 4a) 4b) 4c)
Detailed description in section
2.2 3.2 3.3 3.4 4.3 4.4 4.5
Detailed schematic of measurement method
5 6 7 11 12 13
v) For current-voltage techniques, this distiction is included in the method name.
w) All methods include this distinction as part of the method name.
x) Measures resistance of conductor loop via earth return path.
y) An earth resistance meter does not need to be inserted into the earthing conductor if a clamp-on resistance meter is placed around the earthing
conductor.
z) In the case of balance-bridge methods, figure only applies to the exterior circuit.

2
L1 L1
L2 L2
L3 L3
Earth resistance meter
UM PEN PEN
RE = –––
I

Earth resistance meter REC REC REC


∼ ∼ ∼
PSAC PSAC PSAC
tr = I2 : I1 = 0.1; 1; 10; 100
I UM I UM I UM
I1 A V A V A V
I2 R2
E ES S H E ES S H E ES S H
CT
U2 N

REC UM
∼ RE RF RE RE = ––– RF RE RE < Rloop
REC I
PSAC UM
Rloop = –––
U1 I
I1 Probe
I3 = 0 Probe Functional Earth Functional Earth
I3 = 0 I1 Earth Auxiliary earth electrode earth electrode
E electrode earth electrode electrode
ES S H electrode
a) b) c)

RE
à Current-voltage methods that do not draw current directly from the power supply
a) with probe and auxiliary electrode; b) with probe, but without an auxiliary electrode;
c) no probe, no auxiliary electrode (measures resistance of conductor loop via earth return path).
Earth Auxiliary I test current; Rloop loop resistance; UM test voltage.
electrode Probe earth
electrode

À The balanced-bridge method


REC rectifier; I1 test (or measuring) current; L1
I2 Reference current; I3 current whose mag- L2
L3
nitude is zero when bridge is balanced;
PEN
C capacitor; N null detector; RE earth resis- UM or N
tance being measured; R2 reference resis- RE = ––– UM UM
I RE = ––– RE = –––
tance; CT current transformer; U1 Voltage Earth I I
across earth electrode under test; U2 refe- resistance
rence voltage; tr transformation ratio of the meter
CT; PSAC AC power supply.
L L L

2.2 The balanced-bridge method UM


The balanced-bridge method as described by
Behrend is one of the techniques for measuring
earth resistance that does not involve drawing U0
current directly from supply. Earth resistance UM I UM I UM I
meters based on this method are no longer ma- V A V A V A
nufactured, as other more user-friendly instru-
ments have now been developed for the same S E S E S E
sorts of applications. These new meters use the
so-called current-voltage method, which also
UE
does not involve current being drawn from the
RF RE RF RE RF RE
supply. Nevertheless the balanced-bridge me-
thod is described here because it is of funda-
mental importance to the development of earth
resistance measurement techniques and be- Probe Earth Functional Earth Functional Earth
cause meters based on this method are still in Functional electrode earth electrode earth electrode
use. earth electrode electrode
electrode U0 – UM
The measurement circuit for the balanced- Rloop < ––––––––
a) b) c) I
bridge method is shown in figure À. The me- RE < Rloop
thod involves driving an auxiliary earth elec- UE < U0 – UM
trode1) and a probe2) temporarily into the soil.
When the earth meter is in its balanced state,
there is no current flowing in the probe. The re- Õ Current-voltage methods that draw current directly from the power supply
sistance to earth of the probe has therefore no a) with probe; b) using PEN conductor or neutral conductor instead of probe;
influence on the measurement result; it simply c) no probe (measures resistance of conductor loop via earth return path);
lowers measurement sensitivity. Information on U0 conductor-to-earth voltage
the alignment and separation of the auxiliary

3
earth electrode and the probe is provided in constant-current generator, the earth resistance
section 3. can be displayed directly on the voltage meter.
The AC power source PSAC is located between When the balanced-bridge method was first de- UM
RE = –––
the connection point for the earth electrode un- veloped, the only exterior circuit known was I
that shown in figures À and Ãa). It was the-
Earth resistance meter
der test (socket  E) and that for the auxiliary
earth electrode (socket H). The AC source is refore usual to consider the circuitry inside the
connected in series with the primary winding of meter and the exterior circuit as a single entity. REC

a current transformer CT. Connected to the se- However, as indicated in columns 2 and 3 in
condary winding of the current transformer is a table À, the same meter can be used for mea- PSAC
variable voltage divider. The setting chosen for surements with the exterior circuits shown in fi- I UM
the left part of the divider R2 (‘reference resis- gures Ãb) and Ãc). Equally, the earth resis- A V
tance’) is displayed on the scale on the voltage tance meters used for the current-voltage me-
divider’s control unit. A null detector N with a thods that do not draw current directly from the E ES S H Auxiliary
rectifier REC in series is located between the va- supply can be used like the meters designed Earth earth
riable tap point of the voltage divider and the with the balanced-bridge circuit. The internal electrode Probe electrode
connection point for the probe (socket S). The circuits can therefore be freely combined with
rectifier is driven by the AC power source. A ca- the exterior circuits.
pacitor C prevents any DC current from flowing RE
across the probe. One end of the voltage divider 2.4 Measurement methods with
is connected to the earth electrode being mea- current from the supply
sured via the instrument sockets ES and E. The These methods can only be used in networks
transformation ratio tr of the current transfor- with a direct connection to earth. As shown in 0.2 s 0.2 s
mer can be switched to achieve the required figure  Õ, the measurement involves drawing s
measurement range. the test current from the phase conductor of the
RE'
When balanced, the current I3 in the probe is supply system. The meters used in this type of approximately
zero. The same current I1 therefore flows in the measurement are primarily designed for testing flat section
auxiliary earth electrode and in the earth elec- electrical safety systems involving residual cur-
trode under test. Additionally, the voltages U2

RE'1

RE'2
rent devices. The meters are generally con-

RE'
(‘reference voltage’) and U1 are of the same nected to the supply via a flexible power lead
size. The voltage U1 corresponds to the earth and an earthed safety plug. Distance
electrode voltage that drives the test current I1
in the earth resistance RE of the test object E,
whereas U2 is the voltage drop that maintains Current-voltage method that ΠCurrent-voltage methods that do not
the current I2 (‘reference current’) in the refe-
rence resistor R2. The potential drops obey
3 draws no supply current draw current directly from the power sup-
ply and that use a probe and an auxiliary
Ohm’s law as expressed by the equations 3.1 Earth resistance meters earth electrode
U1 = I1 · RE and U2 = I2 · R2. If the transforma- The four connection sockets are labelled as I test current; RE earth resistance being
tion ratio of the current transformer tr = 1:1, shown in figure Œ. Sockets for the supply measured; RE´ measured earth resistance;
then I2 = I1 and the value of the earth resis- current path and for current measurement: UM test voltage
tance RE is equal to the selected reference re- • E – Earth electrode (test object)
sistance R2. The earth resistance can therefore • H – Auxiliary earth electrode1)
be read off the voltage divider scale mentioned Sockets for the voltage measurement path: To protect against electric shocks, the open-cir-
above. If another transformation ratio is used, • ES – Earth electrode (or the probe located cuit test voltage generated by the meter must
this must be multiplied by the value of the re- close to the earth electrode when measuring not exceed 50 V (r.m.s.) and 70 V (peak). In
ference resistance R2, i. e. RE = tr · R2. the soil resistivity) the case of earth resistance meters used on
• S – Probe2) agricultural sites, these values must be halved.
2.3 Other measurement methods Normally when measuring the resistance to Alternatively, the short-circuit current must not
without supply current earth, the sockets E and ES are connected to exceed 3.5 mA r.m.s. and a peak value of
Another group of methods for measuring earth one another via a removable link or via a con- 5  mA (see [5], sec. 4.5). If neither of these
resistance that do not draw current directly tact strip within the meter’s selector switch as conditions are met, the meter must switch off
from the supply are the so-called current-volta- this ensures that the earth electrode under test automatically.
ge techniques illustrated in figure Ã. The earth is connected to both the current and voltage The meter is powered either by a battery, a
resistance RE is determined from the voltage measurement paths. If, in addition, a jumper is group of primary cells or a hand-driven genera-
UM that appears across the earth electrode and placed between sockets H and S, the earth re- tor, though the latter method is now rare. The
across the sockets ES and S, and the measu- sistance meter can be used as a simple ohm- meter must indicate whether the end-point vol-
red current I. meter. tage of the power supply is sufficient to main-
The frequency of the AC supply PSAC is at tain proper instrument function (see [4],
UM least 5  Hz above or below the frequencies sec. 4.3).
RE = (4) 16.7 Hz and 50 Hz and any integer multiples When earth resistance is measured by a me-
I
thereof. Typically, the supply frequency is in the thod that does not involve current being drawn
Figure à simply illustrates the principle of the range 41–140 Hz, though in some meters a directly from the supply, the earth resistance RE
measurement and shows only a small part of higher frequency is used. Some earth resistance is computed as the quotient of the measured
the complex circuitry within the earth resis- meters also offer the option of selecting the fre- voltage UM that appears across the earth elect-
tance meter. Usually, the voltage UM and cur- quency. A number of meters with automatic fre- rode (and across the meter sockets ES and S)
rent I are not shown separately and the meter quency control (AFC) automatically switch to and the measured current I (that flows through
only displays a digital reading of the earth re- that frequency offering the lowest level of inter- sockets E and H). Figure Œ only indicates the
sistance RE. If the AC supply source PSAC is a ference. basic principle of the complex circuitry within

4
the meter. Usually, the voltage UM and current measuring lead can of course be measured and flatter. If the distance between the earth elect-
I are not shown separately and the meter only this value subtracted from the value displayed rode and the auxiliary electrode is large enough,
displays a digital reading of the earth resistance by the earth resistance meter. If the effect of the the curve will have an approximately horizontal
RE. If the AC supply source is a constant-cur- measuring lead’s resistance is to be avoided at central section in which the measured resis-
rent generator, there is no need to measure the all costs, the jumper linking sockets E and the tance to earth is essentially independent of
current and calculate the quotient. In this case ES must be removed and each socket con- electrode separation.
a voltage meter can be calibrated to display the nected to the earthing system by its own mea- This central section must be determined by at
earth resistance directly. suring lead. least three measurements. The midpoint of the
Most meters are equipped with a switch for se- The earth electrode under test must not be con- central section is not midway between the earth
lecting the type of measuring circuit, the mea- nected to any other earth electrodes as this electrode and the auxiliary earth electrode, but
surement frequency and/or the measurement would falsify the result of the measurement. In lies closer to the auxiliary earth electrode as the
range, and for switching the power on and off. the TN earthing systems found in consumer in- spatial extent of the spheres of influence asso-
Most meters also have a button that is used to stallations, the earthing conductor must be dis- ciated with the two earth electrodes differ. In
initiate measurement. The earth resistance me- connected from the main earthing busbar as the general, the optimum separation between the
ter must also indicate that the resistance of latter is connected to the PEN conductor of the earth electrode and the probe is about two
the auxiliary earth electrode and the probe are supply network. This is not required in TT sys- thirds of the distance between the earth elec-
within the specified limits (see [5], sec. 4.4). tems as the main earthing busbar is not con- trode and the auxiliary earth electrode3).
However, it is not advisable to rely too heavily nected to the neutral conductor of the power
on a warning signal, because by the time a supply network. If, nevertheless, the earthing 3.2.5 Limitations of method
warning signal has been issued, the limit may conductor is disconnected, the entire system If no portion of the resistance vs. distance cur-
have been exceeded by a significant amount. must be de-energized beforehand and locked ve is approximately horizontal, then the dis-
User-friendly devices offer additional functions out to prevent it being switched on again. tance between the earth electrode under test
such as: and the auxiliary earth electrode is too small.
• warning signal or automatic cut-out if too 3.2.3 Auxiliary electrode1) If the curve exhibits an unusual profile, buried
great an interference voltage is detected The auxiliary earth electrode should be positio- metal installations (e. g. water pipes) are very
• warning signal or disabling of measurement ned as far away as possible from the earth elect- probably influencing the measurement. In
function if test current is too small rode under test, so as to minimize the degree of such conditions it is not possible to achieve
• display of test current (for monitoring purpo- overlap between the potential gradient areas usable results from the measurement. Measu-
ses only when measurements made with a (‘spheres of influence’) surrounding the two rement may be possible if the electrodes can
constant-current generator) electrodes. The larger the electrodes, the farther be laid out perpendicular to their original di-
• automatic measurement range selection apart they must be. As a rough guide, the mi- rection or perpendicular to the longitudinal
• display hold function nimum distance apart can be taken to be three axis of the buried metal installation or so that
• data storage for transmitting or printing mea- times the depth of a rod earth electrode or the they run away from and not above the buried
surement results. average diameter of a ring earth electrode. The metal installation.
figure of 40 m that is found in the documenta- It is also not possible to achieve reliable results
3.2 Methods using a probe and an tion provided by some manufacturers can only if the earth electrode under test is surrounded
auxiliary earth electrode be considered to be a rough average value. by other earth electrodes, for example in areas
Whether the chosen distance is appropriate will with a high density of buildings. Furthermore
3.2.1 Principle be shown when the correct alignment and po- measurement is impossible whenever the au-
As shown in figure Œ, the earth electrode un- sitioning of the electrodes is carried out (see xiliary earth electrode and the probe cannot
der test, an auxiliary earth electrode and the sec. 3.2.4). be positioned in the right locations. In all such
probe are connected to the earth resistance me- The greater the resistivity of the soil, the longer cases, another measurement technique must
ter. The test current I flows through the earth the auxiliary electrode needs to be and the dee- be selected.
electrode, the soil and the auxiliary earth elect- per it needs to be driven into the ground. If the
rode. The voltage UM that appears across the resistance of the auxiliary earth electrode is too 3.3 Method using a probe but no
earth resistance RE also appears across the me- large, measurement errors can arise, because, auxiliary earth electrode
ter sockets ES and S. The earth resistance is for example, the constant current normally ge-
displayed as the value of UM divided by I. nerated by the AC supply cannot then flow. In 3.3.1 Principle
such cases, it can prove useful to saturate the As shown in figure œ, the functional earth of
3.2.2 Earth electrode (test object) area of ground being used for the measurement the supply network acts as a replacement for
If socket E is connected to the beginning of the with water. the auxiliary earth electrode. It is extremely
earthing conductor (at the main earthing termi-
nal), the earthing conductor will be included in 3.2.4 Probe2) 1) In some publications the auxiliary electrode is
the measurement of the earth resistance. If, on As the internal resistance of the voltage measu- also referred to as the outer test electrode, or cur-
the other hand, socket E is connected directly rement path is very large, the resistance of the rent test stake.
to the earth electrode, the resistance of the eart- probe and therefore the size of the probe is of 2) In some publications the probe is also referred to
as the inner test electrode, or voltage test stake.
hing conductor will not be included in the mea- minor importance. The preferred location of the 3) Some manufacturers state that the distance be-
surement. The difference, however, is usually probe is on the straight line between the earth tween the earth electrode and the probe should
slight. electrode and the auxiliary earth electrode at a be half the distance between the earth electrode
The resistance of the measuring leads will be in- position where it has minimum interaction with and the auxiliary earth electrode. That is incorrect.
Other companies recommend placing the probe at
cluded in the measurement. This will result in the spheres of influence of the two electrodes a distance from the earth electrode that is always
an overestimation of the earth resistance and (see diagram in figure Œ). 62 % of the separation between the earth and
thus yield a value that errs on the side of safety. If one were to carry out a series of measure- the auxiliary earth electrode. This method is thus
To reduce the magnitude of the error, it is ex- ments with different distances between the sometimes referred to as the 62 % method. The
62 % mark generally gives a good approximation
pedient to position the earth resistance meter earth electrode and the probe the results would of the correct location. But the optimum position
close to the point of connection and to use a form a curve whose ends are relatively steep must always be determined by moving the probe
short measuring lead. The resistance of the while the intermediate section of the curve is to neighbouring positions.

5
important to ensure that the connection is not
accidentally made to one of the phase con-
ductors. L1 L1
L2 L2
In a TN system, the H socket of the meter has L3 L3
to be connected (for instance, via the earthing PEN PEN
contact of a plug) to the protective earth (PE) PEN PEN
conductor, which itself has been branched off
MEB PE N MEB PE N
the PEN conductor. The meter socket E is con-
nected to the earthing conductor, which has to Earth resistance meter Earth resistance meter
be disconnected from the main earthing busbar.
Supply networks configured with the TT earth- REC REC
ing system have a neutral conductor instead of ∼ ∼
the PEN conductor. This has to be treated as a PSAC PSAC
live conductor even though it is connected to a I I
UM UM
functional earth. Applying this method of mea-
A V A V
suring earth resistance to a TT system would
therefore involve connecting the earth resis-
tance meter to the neutral conductor. The me- E ES S H E ES S H
thod is therefore not approved for use with TT
systems.
EC EC
3.3.2 Problems in the TN system UM
Rloop < RE
The method does not function in a TN system RF RE RE = ––– RF RE UM
I Rloop = –––
if the electrode being measured is strongly cou- I
pled or if it is connected via a metal conductor
to another earth electrode that itself is con- Functional Earth Probe Functional Earth
nected to the PEN conductor. This would result earth electrode earth electrode
electrode electrode
in the test current flowing in the wrong path so
that the display on the earth resistance meter
would be smaller than the true value of the re- œ Current-voltage methods that do not – Current-voltage methods that do not
sistance to earth. This is discussed in more de- draw current directly from the power sup- draw current directly from the power
tail in section 3.4.2. ply and that use a probe but no auxiliary supply and that use neither a probe nor
earth electrode an auxiliary earth electrode (resistance
3.4 Method without a probe and EC earthing conductor; MEB main earthing of conductor loop via earth return path)
an auxiliary earth electrode busbar; RB resistance to earth of the functio- Rloop loop resistance.
(‘stakeless method’) nal earth electrode

3.4.1 Principle
This method (illustrated in figure –) is an 3.4.2 Problems in TN systems inducing clamp, VIC) and a current transformer
earth-loop resistance measurement because it The problem mentioned earlier in secton 3.3.2 (a current measuring clamp CMC). Models
involves measuring the resistance of a con- can also arise when measuring earth resistance available include:
ductor loop via an earth return path. The S and without an auxiliary earth electrode and without • Chauvin Arnoux Earth Clamps C.A  6410,
H sockets of the earth resistance meter are con- a probe. Some examples of configurations whe- C.A 6412 or C.A 64154);
nected together. The advantage of this method re problems can arise are shown in figure —. • Fluke Earth Ground Clamp Meter 16305).
is that neither an auxiliary earth electrode nor a Temporary remedial measures include: The meter displays the resistance calculated as
probe need to be used. • Disconnecting the metal connection between the quotient of the voltage induced by the VIC
In a TN system the earthing conductor (EC) is the earth electrodes as shown in figure —b). in the earthing conductor and the resulting test
disconnected from the main earthing busbar • Disconnecting the second earth electrode current registered by the CMC. In this case the
(MEB) and the earth resistance meter is inser- from the PEN conductor, if permitted by the resistance is the loop resistance Rloop, or more
ted between them. This method is not suitable owner. The residual influence of the second precisely the loop impedance (see section 
for measurements on a consumer installations earth electrode on the earth resistance mea- 3.4.1).
with a TT earthing system. surement is not a disadvantage, as it acts to Another solution (no separate diagram provi-
The resistance measurement displayed on the improve the performance of the first earth ded) involves clamping two split-core current
meter includes the resistance to earth of the electrode. transformers around the earthing conductor,
functional earth and the resistance of the More details can be found in reference [8]. one of which functions like the voltage-inducing
PEN conductor. If they were accurately known, clamp VIC while the other corresponds to the
these values could be subtracted from the re- 3.5 Stakeless methods (no probe, current measuring clamp CMC that measures
sistance displayed on the meter. However, they no auxiliary earth electrode)
are difficult to determine, because the functio- using a clamp-on ohmmeter
nal earth in a TN system comprises not only the This is a variation on the measurement method 4) Induced voltage: approx. 60 mV; frequency:
functional earth electrode shown in figure –,
2403 Hz; inner diameter of clamp jaw: 32 mm.
described in section 3.4. This technique differs Data provided without warranty.
it is also connected to numerous earths in the from that shown in figure – in that instead of 5) Induced voltage: approx.  30 mV; frequency:
consumer installations of neighbouring buil- inserting an earth resistance meter into the eart- 1667 Hz; inner diameter of clamp jaw: 23 mm.
dings. The error that is introduced by measu- hing conductor, a clamp-on ohmmeter (COM) Data provided without warranty.
6) On its own, the expression ‘selective earth mea-
ring these additional resistances results in an is placed around the earthing conductor (see fi-
surement’ is ambiguous, as other earth resistance
overestimation of the earth resistance, yielding gure “). The clamp-on ohmmeter contains measurement techniques are also selective, e.g.
a value that errs on the side of safety. both a current-to-voltage transformer (a voltage those presented in sections  3.4, 3.5 and 4.6.

6
L1 L1 L1
L2 L2 L2
L3 L3 L3
PEN PEN PEN
PEN

MEB
E ES S H E ES S H PE N
EC
IV IV
I
I = IE1 + Icpl I = IE1 + Icpl CMC COM
IE1 < Icpl IE1 < 0 for
I RM < RE1 I Icpl < I UM VIC Rloop
RM ⪡ RE1

Icpl EC

Icpl E2 E2
RF RE RE < Rloop
Rcpl

RE1 RE1
RE2 RE2
IE1 Functional Earth
IE2 IE12 = 0 IE2 = 0
earth electrode
electrode

— Cases involving a TN system in which the method shown in fig. – is not suitable “ Method as in figure  – but with a
a) Small distance and therefore small coupling resistance Rcpl between the earth electrode under clamp-on ohmmeter rather than an
test E1 and a second earth electrode E2 that is connected to the PEN conductor. b) Metallic earth resistance meter
connection to a second earth electrode that is itself connected to the PEN conductor. EC earthing conductor; VIC voltage-induc-
Icpl current causing measurement error; RE1 earth resistance being measured; RM earth resis- ing clamp; CMC current measuring clamp;
tance displayed on meter. COM clamp-on ohmmeter.

the test current. The clamps are connected to a


special earth resistance meter (Fluke Earth
Ground Tester 1623 or 1625). Depending on Earth resistance meter Earth resistance meter Earthed conductor
e. g. counterpoise
which of the Fluke meters is used, either EI- E ES S H UM E ES S H
RE = –––
1623 or EI-1625 ‘selective/stakeless clamp I
set’ is required. The advantage in both cases is UM
RE1 = –––
that the earthing conductor does not need to be I IE1
I
disconnected, making measurement safer and
Other earth
quicker. The problem discussed in section electrodes
IP
3.4.2 can also arise in these cases. I
I
If this method is used to make measurements IP
on consumer installations, they must be desig- IE Lattice-type EC IE
ned with a TN earthing system. The method is CMC pylon
suitable for measuring the resistance to earth of
EC SCT IE1 IE2 IE3 IE4
a pylon in an overhead power transmission line
if the clamps can be fitted around the earthing
conductor. RE RE1 RE2 RE3 RE4

3.6 Selective earth resistance


measurements using a probe, Auxiliary Auxiliary
an auxiliary earth electrode Test Other Probe earth Test object Probe earth
and a clamp-on ohmmeter object earth electrode (pyton stubs) electrode
The earth resistance measurement described in a) electrodes b)
this section6) is used if the earth electrode un-
der test cannot or should not be disconnected
from other earth electrodes to which it is wired ” Selective earth resistance measurements using a probe, an auxiliary earth
in parallel. This method is based on the techni- electrode and split-core current transformers
que using a probe and auxiliary earth electrode a) Test object whose earthing conductor can be clamped by a split-core current transformer;
that is discussed in section 3.2, but in this va- b) Pylon whose legs can be clamped by a split-core current transformer near the foundation
riant (see figure ”a)) a special earth resistance of the pylon
meter (Fluke 1623 or 1625) and an additional IE part of test current flowing through the earth electrode under test to the auxiliary earth
electrode; IE1 to IE4 parts of IE flowing in the pylon legs and stubs; IP portion of the test
clamp-on current transformer (CMC) are requi-
current flowing to the auxiliary earth electrode via the other parallel earth electrodes (current
red. The current measuring clamp CMC is clam- path through soil not shown in part b) of figure).
ped around the earthing conductor EC con-

7
L1 L1
L2 L2
L3 L3
PEN N
RCD
UM UM
RE = ––– RE = ––– PE
I N PE I N
nected to the earth electrode under test and
MEB MEB
connected to a multi-pole socket on the earth Earth Earth
resistance meter. When the meter is connected resistance resistance
in this way and the rotary selector switch has meter meter
been set appropriately, IP, the portion of the test L L
current I flowing via the other parallel earth
electrodes, has no effect on measurement result
so that the branch current IE recorded by cur-
rent measuring clamp CMC is solely responsi-
ble for determining the resistance to earth RE
displayed by the meter.
Figure  ”b) shows the measurement circuit
UM I UM I
V A V A
used when dealing with a steel-lattice electrici- EC
ty pylon that cannot be electrically discon- S E S E
nected from the earthed conductor (e. g. coun-
terpoise, PEN conductor or neutral conductor).
EC
As the pylon structure serves as the earthing
RF RE RF RE
conductor EC, it is clearly not possible to clamp
a CMC around the earthing conductor as in fi-
gure ”a). In this case, measurements are ma-
Functional Probe Earth Functional Probe Earth
de by consecutively clamping a splitcore trans- earth electrode earth electrode
former SCT (Fluke EI-162BN7)) around the four a) electrode b) electrode
pylon legs that are connected to the four pylon
stubs that act as earth electrodes. The earth re-
sistance meter displays the resistances RE1 to Current-voltage methods that draw current directly from the power supply and
RE4 consecutively. The resulting earth resis- that use a probe
tance RE of the four mast feet, which are con- a) Installation with TN system; b) Installation with TT system
nected to one another through the steel lattice EC earthing conductor; RCD residual current device; I test current; MEB Main earthing busbar;
structure, can be calculated by equation (5): RF resistance of functional earth; RE earth resistance being measured; UM test voltage

1
RE =
1 1 1 1 (5)
+ + +
RE1 RE2 RE3 RE4 L1 L1
L2 L2
L3 L3
PEN N
Measurement methods that
4 draw current from supply UM
RE = –––
UM
RE = –––
I
RCD

I N PE N PE
4.1 Measuring equipment MEB MEB
The meters used for this type of measurement Earth Earth
resistance resistance
are designed primarily for testing electrical meter meter
safety systems that make use of residual cur-
L L
rent devices. To ensure the simplest and safest
connection to the power supply, the meters are
typically equipped with a flexible power cable
and an earthed safety plug. The meters also
have a socket S for the probe (see figures 
EC
and 13 ). The socket E is used to connect
the meter to the earth electrode under test un- UM I UM I
less one of the cores (protective earth core) of V A V A
the flexible power cable and the earth contacts
S E E
on the plug are used for this purpose. As the test S
meters are classified as Class II equipment (see
ref.  [4], sec.  4.5), the core and the plug’s EC
earth contact do not serve as protection against
shock hazards. RF RE RF RE

The meters do not have their own power sour-


ce unless this is needed for some other type of
Functional Earth Functional Earth
measurement. Some meters may have an addi- earth electrode earth electrode
tional connector socket for a current measuring a) electrode b) electrode
clamp.

12 Current-voltage methods that draw current directly from the power supply and
that use the PEN or neutral conductor instead of a probe
a) Installation with TN system;
7) The jaws of the split-core transformer are dimen-
sioned for large rectangular-section conductors b) Installation with TT system
such as the legs of high-voltage pylons.

8
L1 L1
L2 L2
L3 L3
PEN N
U0 – UM U0 – UM
Rloop < –––––––– Rloop < –––––––– RCD
I I
RE < Rloop RE < Rloop
N PE N PE Figures  to 14 show the basic principles of the
UE < U0 – UM UE < U0 – UM
MEB complicated circuitry inside these meters. In
Earth L Earth most of these meters, the actual measurement
resistance resistance
meter meter
process (including any gradual increase in the
MEB test current that may be involved) is carried out
L L automatically. Rather than displaying the mea-
UM UM
sured voltage and current separately, the resis-
tance to earth is computed and displayed digi-
tally on the meter.
U0 U0
A selector switch enables the type of measure-
EC ment, measurement technique, measurement
UM I UM I circuit, parameter range and/or measurement
V A V A sequence to be chosen. Most meters are fitted
with a ‘START’ button to initiate the measure-
E E
S S ment process. User-friendly devices offer addi-
tional functions such as:
EC UE UE • Multiple measurements with display of ave-
RF RE RF RE rage result
• Smoothing function
• Display hold function
Functional Earth Functional Earth • Data storage for transmitting or printing mea-
earth electrode earth electrode
a) electrode b) electrode surement results.
To provide protection against electric shock, the
meter must switch off automatically as soon as
13 Current-voltage methods that draw current directly from the power supply and it causes a fault voltage greater than 50 V in
that do not use a probe the earthing system being measured. If a varia-
a) Installation with TN system; b) Installation with TT system ble resistor is used to increase the test current,
Rloop loop resistance; U0 conductor-to-earth voltage; UE voltage across tested earth electrode the current must not exceed 3.5 mA at the be-
ginning of the measurement (see ref.  [6],
L1 L1
sec. 4.7). Measurements in which the test cur-
L2 L2 rent is increased gradually and measurements
L3 L3 in which the current is only allowed to flow at
N N
maximum strength for a short period are both
UM RCD
UM RE = ––– common.
RE = ––– I
I UE = UM The difficulty associated with drawing current
N N PE
MEB directly from the power supply is that the mea-
Earth Earth surement is made at the supply frequency and
resistance resistance
meter meter interference currents that originate in the power
supply or that are carried via earth can easily in-
L L MEB
troduce measurement errors. The larger the test
current, the less effect these sources of interfe-
rence will have. It is therefore expedient to work
with a large test current. However, a large test
current can itself be problematic when the me-
ter is connected behind a residual current devi-
UM UM
V I V I ce, as it can cause the RCD to trigger. This can
E E
be avoided by using one of the following proce-
A A dures:
• Ensuring that the magnitude of the test cur-
S E S E rent is only half that of the rated residual cur-
rent IΔN of the RCD.
I IP I IP
• Connecting the meter in front of the RCD or
IE IE to a circuit that is not equipped with an RCD.
CMC CMC
EC EC
• According to the manufacturer Chauvin
Arnoux the patented ‘ALT system’ used in its
RF RE RF RE
C.A 6115 N and C.A 6456 Earth Clamps
enables these devices to make earth resis-
tance measurements using a larger test cur-
Functional Probe Earth Other Functional Probe Earth Other rent even if connected behind a 30 mA RCD.
earth electrode earth earth electrode earth Whenever interference effects may play a role,
electrode electrodes electrode electrodes
several measurements should be conducted
and the results compared with one another.
14 Selective earth resistance measurement methods that draw current directly from
the power supply and that use a probe and a clamp-on ammeter 4.2 Connections to power supply
a) Installation with TN system; b) Installation with TT system and earth electrode
IE portion of test current flowing to the earth electrode under test; IF portion of test current The meter is typically connected to the power
flowing to the other earth electrodes; CMC current measuring clamp supply via its earthed safety plug. If the plug is

9
inserted incorrectly, no hazard arises but no achievable using the method described in References
measurement is possible. Although not shown section 4.3. [1] IEC 60364-4-41:205 Erection of power installa-
tions with nominal voltages up to 1000 V – Part
in the figures, the internal circuitry of most of 4-41: Protection for safety – Protection against
the meters only functions if the meter is con- 4.5 Method without a probe electric shock.
nected to the phase conductor and to the neu- This method (illustrated schematically in fig- [2] Hering, E.: Schutzerder des TT-Systems (engl.:
tral conductor. ure ) involves measuring the resistance of a Protective earthing in the TT system). Elektro-
praktiker, Berlin 59 (2005) 5, p. 370-373.
The test current can induce accidental trigger- conductor loop via an earth return path. In this [3] IEC 60364-6:2006-02 Low-voltage electrical in-
ing of an upstream RCD. This may need to be method, the voltage across the test object (UE) stallations – Part 6: Verification.
taken into account when connecting the meter is not measured directly. It is determined as the [4] IEC 61557-1:2007 Equipment for testing, mea-
(see discussion in section 4.1 above). difference between the potential drop between suring or monitoring of protective measures –
Part 1: General requirements.
Depending on the type of meter used, the earth the phase conductor and earth when the test re-
[5] IEC 61557-5:2007 Equipment for testing, mea-
electrode to be measured is sistance is switched off (U0) and that when the suring or monitoring of protective measures –
• either connected directly to socket E of the test current I is flowing (UM). The resistance val- Part 5: Resistance to earth.
meter (see fig. Õ in section 2) ue measured includes the resistances of the [6] IEC 61557-6:2007 Equipment for testing, mea-
• or (in most cases) is connected to the meter functional earth, the transformer and the phase suring or monitoring of protective measures –
Part 6: Effectiveness of residual current devices
via the plug’s earth contact as shown in fig- conductor. This will result in an overestimation (RCD) in TT, TN and IT systems.
ures  to 14 . of the earth resistance and thus yield a value [7] IEC 61557-10:2000 Equipment for testing,
Connections between the earth electrode that errs on the side of safety. measuring or monitoring of protective measures
under test and other earth electrodes would This method is particularly attractive as it can – Part 10: Combined measuring equipment for
testing, measuring or monitoring of protective
yield erroneous results. It is for this reason that be performed with a minimum of effort. But it measures.
when measurements are made on consumer in- suffers from the weakness that supply load fluc- [8] Hering, E.: Probleme mit einem der Erdungs-
stallations with a TN earthing system, the earth- tuations that happen to occur simultaneously meßverfahren beim TN-System (engl.: Problems
ing conductor EC has to be separated from the while the measurement is being made will with an earth resistance measurement technique
in a TN system). Elektropraktiker, Berlin 53
main earthing busbar MEB (see figures a) to cause significant additional measurement er- (1999) 9, p. 820-822.
14 a)) as the latter is connected via the PEN rors. To limit these errors, it is therefore expe- [9] Hering, E.: Durchgangsprüfungen an Erdungsan-
conductor of the service cable and the supply dient to work with a large test current. It is also lagen [Continuity testing in earthing systems].
network to other earth electrodes. Disconnec- advisable to perform numerous measurements, Elektropraktiker, Berlin 59 (2005) 11, p. 888-
891 und in diesem Sonderdruck.
tion is not required in a TT system as the main to reject any extreme values recorded and to
[10]DIN EN 62305-3 (VDE 0185-305-3):2006-10:
earthing busbar is not linked to the neutral line compute the mean value from the remaining Protection against lightning – Part 3: Physical da-
of the supply network and the connection can measurement data. mage to structures and life hazard.
be made as shown in figures  b) to 14 b).
4.6 Selective earth resistance
4.3 Methods using a probe measurements using a probe
This method is the most accurate of the tech- and a clamp-on ammeter
niques that draw current directly from the sup- The method selective earth resistance meas-
ply provided that the probe can be inserted in- urement8) is used if, for the purposes of the
to the soil at a suitable location. A schematic of measurement, the earth electrode under test
the measurement set-up is shown in figure  . cannot or should not be disconnected from oth-
The probe has to be located so that it is outside er earth electrodes to which it is wired in paral-
the sphere of influence of the earth electrode. lel. It is based on the method using a probe dis-
The voltage UM between the sockets E and S cussed in section 4.3, but in this variant (see
generates the test current I in the earth elec- figure 14 ) a special earth resistance meter
trode. (Chauvin Arnoux C.A. 6115N or C.A. 6456)
and an additional current measuring clamp
4.4 Method using the PEN con- CMC are required. The current measuring
ductor or neutral conductor clamp is connected to a multipole socket on the
instead of a probe meter and the clamp jaws are placed around
This measuring techniques can be used when- the earthing conductor EC connected to the
ever it is not possible to insert a probe into the earth electrode under test.
ground at the right location. In this method (see If the meter is connected in this way and if the
figure 12 ) the probe is replaced by connecting rotary selector switch set appropriately, IP, the
socket S of the meter to the PEN or PE con- portion of the measuring current I flowing via
ductor in a TN system or to the neutral con- the other parallel earth electrodes, has no effect
ductor in a TT system. Caution! The neutral on measurement result so that the branch cur-
conductor must be treated as if it is live, even rent IE recorded by the current measuring clamp
though it is earthed. CMC is solely responsible for determining the
The value displayed by the meter includes the resistance to earth RE displayed by the meter.
resistance to earth of the functional earth elec-
trode. This will overestimate the resistance of
the earth electrode and thus yield a value that
errs on the side of safety.
The voltages generated by operating currents
and by fault currents in the functional earth or
in the PEN conductor or neutral conductor of
the power supply system can result in erro- 8) On its own, the expression ‘selective earth mea-
surement’ is ambiguous, as other earth resistance
neous measurement results. The accuracy of measurement techniques are also selective, e. g.
this technique is therefore lower than that those presented in sections  3.4, 3.5 and 3.6.

10
Continuity testing earthing of a TT or IT earthing system as detai-
led in [1], its connection to the MEB may only

in earthing systems
be broken if the electrical installation has been
disconnected from the power source or power
generator.
E. Hering, Dresden (Germany) Tests that involve breaking connections (e.g.
opening the inspection joint of a lightning pro-
Continuity tests are carried out to verify that conductors, in this case metal tection system) must never be carried out du-
conductors, are unbroken. This article describes the extent to which continuity ring a storm or whenever a storm could ex-
pected. Failure to comply could be hazardous,
testing in earthing systems is required and possible and also discusses the test
particularly for the person doing the testing.
equipment that can be used. In terms of continuity there is no significant diffe- For safety reasons, the use of voltages greater
rence between the initial test and repeat tests, despite the fact that they are than 25 V should be avoided. Small voltages
treated separately in the relevant standards. are anyway advisable for continuity testing (see
[6], sec. 612.2). The testing and measuring
equipment used must comply with the specifi-
cations in the relevant standard (see ref. [7]).
Reasons for and limits of two soil entry points, while a foundation earth Resistance measurements are typically carried
1 continuity testing
electrode must be equipped with at least two
connection points. The more of these hook-up
out using equipment that conforms with the
specifications in reference [8]. However, earth
1.1 Earthing conductor and points there are available, the easier it is to car- resistance meters that meet the requirements in
main earthing busbar ry out continuity testing. reference [9] can also be used.
The earthing system must be connected to the In reinforced concrete foundations, it is not pos-
main earthing busbar (MEB) of the electrical in- sible to detect a break in the ring of the foun-
stallation. This is necessary dation earth electrode. This is not dangerous,
a) to provide protection against electric shock
([1], sec. 441.3.1; [2], sec. 542.1.2)
however, as the break is effectively bridged by
the steel reinforcing bars within the foundation.
3 Test methods
b) to provide a connection to earth for overvol- In this case, continuity testing can only serve to 3.1 Principles
tage protection devices even if the building is verify that the connection between the con- The person carrying out the test must be
not equipped with a lightning protection sys- nection points and the ring is intact. aware of all connections between the earthing
tem ([3], figures A.1 to A.5) system and other electrical and non-electrical
c) in buildings with a lightning protection sys- 1.3 Linear earth electrodes installations. Examples of the latter include
tem ([4], sections 5.4.1, 6.2.1, 6.2.5 and Continuity testing is not possible with vertical pipe systems or metallic structural components
E.6.2) earth rods and elongated horizontal earth elect- of a building. An unknown connection can fal-
d) in buildings with an antenna requiring light- rodes (star or crow’s foot configurations) as the- sify the test results. The continuity test can be
ning protection se electrodes only have a single soil entry point. carried out most simply if the conductor under
e) for foundation earth electrodes ([5], secti- If there is a break in the earth electrode near to test can be disconnected at least on one side.
ons 4 and 5.4). where it enters the soil, this may be detectable This assumes, however, that the broken con-
The conductor between the main earthing as increased earth resistance. nection can be reliably re-stored after testing.
busbar and the earthing system is an earthing To facilitate continuity testing on lightning pro-
conductor and/or an equipotential bonding con- tection systems, it is normal to open the in-
ductor (protective bonding conductor and/or spection joints at the soil entry points or con-
lightning protection bonding conductor).
The continuity of this conductor must be tested
2 Hazard avoidance nection terminals.
Figure  ➊ illustrates test circuits that can be
([6], section 612.2; [4], section E.7.2.4; [5], The process of measurement and any accom- used when no other conductor is connected in
section 7). panying procedures (e.g. breaking standard parallel to the test object. The continuity tester
connections and making non-standard con- shown in figure ➊a) consists of at least a power
1.2 Ring earth electrodes nections) must not pose a safety hazard. If the source and an indicator, e.g. a lamp. To in-
Continuity testing on ring earth electrodes is ad- earth electrode also functions as the protective crease the test current, a resistance can be con-
visable for the following reasons:
a) Earth resistance measurements, which are
required by the applicable standards but are
not dealt with in this article, are unable to de-
tect any break in the ring. While any discon-
tinuity will not lead to an increase in the re-
sistance to earth, it can have a significant de-
trimental effect on the efficiency of the
voltage protection, as the surge currents are
forced to flow via another path.
b) Repeated continuity testing on older ring
earth electrodes can, if carried out in the form
of resistance measurements, identify reducti-
ons in the conductor cross-section (as a re-
sult of corrosion) by registering an increased
resistance.
In order for continuity testing to be possible, a
buried ring earth electrode must have at least

11
PS PS
1 2 1 2 1 2 1 2
G G CA2
CA1
PLC PLC CAM2 G G
3 CT 3 CT 3 PS 3 PS
TC TC

CAM CAM a) b)
a) b)

a) b) mV VM I2 I2 – I3 = I4 – I1
1 2
CA2 CA4 I3
CA1
G CA3
À Continuity testing circuits that mea- CT
I1 I
PS I4 4 3
sure the current in a conductor that has
another conductor connected to it in c) c)
parallel
a) Without determining the resistance of the
conductor à Examples of continuity tests when ring Õ Examples of continuity tests when ring
b) Resistance of conductor determined by earth electrode is open earth electrode has not been opened
making an additional voltage measurement a) Testing connections 1 and 3 and the left secti- a) Analogous to fig. Ãa);
PLC conductor connected in parallel (can on of the ring b) Analogous to fig. Ãb);
also be a second test conductor) b) Testing connections 2 and 3 and the right c) Four tests on a foundation earth electrode
VM low-voltage voltmeter section of the ring with a cross connector and four connection
CAM position of clamp-on ammeter c) Testing the entire ring earth electrode points
CAM2 second position of clamp-on ammeter I measured current; I1 to I4 partial currents;
when PLC is a second test conductor CA1 to CA4 positions of clamp-on ammeter

nected in parallel to the indicator. According to a current is detected by a clamp-on ammeter Figure Ã shows the ring opened for testing. In
the recommendation in reference  [6], sec- that is clamped around the conductor under the test circuits shown in figure Õ continuity
tion 612.2, the power source should generate test TC. If, as shown in figure Àb), a voltmeter is verified by detecting current in the relevant
an open circuit voltage of between 4 and 24 V for measuring small voltages is connected parts of the ring by means of a clamp-on am-
and the test current should be at least 0.2 A. across the conductor under test, the resistance meter at the bridging strip or the underfloor in-
Some continuity testers produce an acoustic of the conductor can be determined by dividing spection joint. In the test scenario shown in fig-
signal if the resistance measured exceeds a the measured voltage by the measured current. ure Œ, the resistance of the ring is measured
user-adjustable limit. Continuity testing is carried out preferentially at the bridging strip or the underfloor inspection
In figure  ➊b) the resistance is determined with alternating current, e.g. from a transformer joint using a clamp-on ohmmeter (see ‘Earth
using a milliohmmeter. The advantage of the or from an earth resistance meter. If a DC Clamp’ in section 3.1).
four-wire connection shown is that the result of source is used, then a special type of clamp-on
the measurement is not affected by the resis- ammeter is required that contains a current 3.3 Continuity testing in ring
tances of the measuring leads. If a bridge is in- sensor based on the Hall effect instead of a cur- earth systems that cannot be
stalled between the connection sockets 1 and rent transformer. opened
2 or between sockets 3 and 4 or if the meter If the ring earth electrode has at least four con-
only has two sockets and only two measuring 3.2 Continuity testing in ring earth nection points, a break in ring continuity can be
leads are used, the resistances of the leads electrodes that can be opened identified by sequentially measuring the resist-
must be subtracted from the resistance value This section describes examples of continuity ance between two neighbouring connection
displayed by the meter. In order to measure the tests performed on ring-shaped foundation points. The small resistances of the conductors
resistance of the leads their ends are connected earth electrodes. Many of these tests can also that run between the point of connection of the
together. Instead of using a milliohmmeter an be carried out in the same way on buried ring meter leads and the ring have to be subtracted
earth resistance meter can be used as shown in earth electrodes. from the resistance displayed on the ohmmeter.
figure ➊c) provided that the meter has a resis- As already mentioned in section 1.2, the ease Although the soil and, in the case of a founda-
tance measuring range down to 0.1 Ω, or low- of performing a continuity test and the reliabil- tion earth electrode, also the concrete are con-
er if possible. The remarks made about the me- ity of the results obtained depends on the num- nected in parallel to the metal conductor, they
ter connections in figure ➊b) apply here anal- ber and arrangement of connection points or have no significant effect on the measurement
ogously. soil entry points. Being able to open the ring result because their resistivity is very much
As indicated in figure ➊d), the resistance can earth electrode considerably simplifies continu- greater than that of steel.
also be measured by means of a clamp-on ohm- ity testing. These factors should be taken into If the ring is uninterrupted, the resistance mea-
meter such as the Earth Clamp1) C.A 6410 account when planning the earthing system. sured is that of a parallel circuit comprising the
manufactured by Chauvin Arnoux. The resist- The test circuits shown in figures à to Œ can
ance of the measuring lead needed to close the only be used if the ring can be opened at least
1) The semicircular jaws of the clamp contain two
circuit must be subtracted from the resistance one location. Foundation earth electrodes can
transformers. The purpose of one is to induce a
value displayed by the meter. If one or more be opened when there are two adjacent, flush- voltage in the conductor, the other measures the
conductors are connected in parallel to the test floor connection points that are linked conduc- resulting current. The clamp is closed when the
object, the same procedures discussed with re- tively to one another via a bridging strip that jaws have been placed around the conductor. The
gard to figure À can be used. A power source closes the ring. Buried ring earth electrodes display on the clamp meter displays a resistance
value computed by dividing the value of the indu-
is connected to the ends of the conductor under may have an inspection joint located in an un- ced voltage by the current flowing in the con-
test. In figure Àa) continuity is verified when derfloor inspection box. ductor.

12
If the ring is unbroken, the resistance measured References
across any pair of neighbouring connection [1] IEC 60364-4-41:2005 Erection of power instal-
lations with nominal voltages up to 1000 V – Part
points is expressed by equation (4): 4-41: Protection for safety – Protection against
COM
Ro = RP
(3 R ) = 3 R
P (4)
electric shock.
[2] DIN VDE 0100-540 (VDE 0100-540):2007-06
(4 R ) 4
P
P
– Low-voltage electrical installations – Part 5-54:
Selection and erection of electrical equipment –
Earthing arrangements, protective conductors and
If the ring is broken (i.e. open), the resistance protective bonding conductors.
RC measured across the two connection points [3] Prestandard DIN V VDE V 0100-534 (VDE V
enclosing the break will be: 0100-534):1999-04 Electrical installations of
ΠContinuity testing using a clamp-on buildings РPart 5-34: Selection and erection of
equipment – Devices for protection against over-
ohmmeter positioned at the point COM RC = 3 RP (5) voltages.
[4] EN 62305-3:2006 Protection against lightning –
Part 3: Physical damage to structures and life ha-
Rc = 3 (43)R o= 4Ro (6) zard (IEC 62305-3:2006).
[5] DIN 18014:2007-09 Foundation earth electro-
mΩ OM des.
If the measurement is therefore made across [6] IEC 60364-6:2006-02 Low-voltage electrical in-
those connection points enclosing the disconti- stallations – Part 6: Verification.
nuity, the resistance measured will be three [7] EN 61557-1:2007 Equipment for testing, mea-
Discontinuity suring or monitoring of protective measures – Part
times the resistance of the partial resistance RP 1: General requirements (equivalent to IEC
and four times the resistance that would be 61557-1).
measured if the ring were unbroken. [8] EN 61557-4:2007 Equipment for testing, mea-
œ Verifying a discontinuity as an in- If the number of connection points is greater suring or monitoring of protective measures – Part
4: Resistance of earth connection and equipoten-
creased resistance resulting from the than four, the same computational methodolo- tial bonding (equivalent to IEC 61557-4).
longer current path gy can be used with the exception that equa- [9] EN 61557-5:2007 Equipment for testing, mea-
tions (1) and (2) would then contain addition- suring or monitoring of protective measures – Part
al terms for the additional sections of the ring, 5: Resistance to earth (equivalent to IEC 61557-
5).
and the factors in equations (4) and (5) would
section of the earth ring enclosed by the mea- be larger.
suring leads and the series circuit that makes If the earth ring electrode has only two connec-
up the remaining part of the ring. If the earth tion points, it may be possible to carry out test-
ring electrode is broken at some point between ing in accordance with figure  Àb) (see sec-
the measuring leads (see figure œ), the resis- tion 3.1). However, this would require being
tance measured is that of the remaining part of able to clamp a clamp-on ammeter around the
the ring. If the measurement is made on one two parts of the ring that are connected in par-
part of the ring, the resistance of that part alone allel to the power source. If this is to be at-
is measured. tempted on a buried ring earth electrode, the
clamp can, for instance, be located on each
Example calculation 1 side of a soil entry point. If the measurement is
The ring earth electrode has four connection an initial measurement, then the earthing chan-
points. Those parts of the ring located between nel in the relevant areas must not be backfilled
the connection points have the resistances until the measurement has been made. If the
R1…R4. If the ring is unbroken, the resistance measurement is a repeat measurement, it can
RO (‘O’ is used here to symbolize the intact be carried out, for example, when material has
earth ring electrode) measured across the two to be removed from the earthing channel in or-
connection points that enclose the part of the der to check on the state of corrosion of the
ring with the resistance R1 is given by: earth electrode.
1
RE =
1 1 1 1 (1)
+ + +
RE1 RE2 RE3 RE4

However, if the part of the ring with the resist-


4 Test report
ance R1 is broken, the resistance RC measured Continuity testing is only one of several tests
across those same connection points (‘C’ is that have to be performed on earthing systems.
used here to symbolize a ring with a continuity In general, the results from all the tests are con-
break) will now be given by equation (2). tained in a single test report.
The tests performed and any accompanying ac-
RC = R2 + R3 + R4 (2) tion that is taken must be described precisely
so that they can be reproduced at a later date.
All test and measurement results must be stat-
Example calculation 2 ed clearly and precisely. If the earth electrode
Situation as in example calculation 1 but each serves as a lightning protection earth electrode,
of the four sections of the ring has the same re- the test report must comply with the specifica-
sistance RP. tions in reference [4], sec. E.7.2.5.

RP = R1 = R2 = R3 = R4 (3)

13

You might also like