LABOUR RATE

BUILDIN ITEM
S.No ITEM DESCRIPTION Qty Unit Rate Amount G NAME CODE

b) MEDIA CENTRE 2
1.00 SUB STATION SAFETY EQUIPMENT : MC 2 MISC
Supplying and fixing 1000 mm x 900 mm wide checkered
1.10 rubber matting conforming to IS 15652-2006 complete as MC 2 MISC
required.
MC 2 MISC
a) 1100 V grade size 1000 x 900 x 15 mm thick 15 Nos. MC 2 MISC
Supplying & fixing standard shock treatment charts in English
1.20 & Hindi / (Local Language) duly framed and covered with 1 No. MC 2 MISC
glass.
Providing & fixing HT danger notice plate 200 mm x 150 mm
made of mild steel atleast 2mm thick & vitreous enameled
1.30 ur Nos. MC 2 MISC
white on both sides and with inscription in signal red colour
with skull & bone on front side as required.
1.40 Providing first aid box as per IS:13115. 1 Set MC 2 MISC
TOTAL OF SUB STATION SAFETY EQUIPMENT CARRIED
MC 2 MISC
OVER TO SUMMARY
MC 2 BBT
2.0 BUS DUCT/BUS BAR TRUNKING SYSTEM : MC 2 BBT
MC 2 BBT
2.1 Bus Duct : MC 2 BBT
MC 2 BBT
Design, manufacturing, supply, installation, testing &
commissioning (at site) of sheet steel enclosed 3 phase &
neutral, 400V, 50 Hz., 50 KA copper conductor bus duct with
insulation of thermal rating confirming to class 'H' including
bends, transposition piece, expansion joint, Tees, End MC 2 BBT
termination units, Feeder units, tap off unit etc. with all flexible
connections as per specifications and drawings with all
accessories, supports and termination of bus duct to
switchgear/transformer.
MC 2 BBT
a) 3000A, 50kA @ 1 Sec., TP+N, Bus Duct (IP.55) with 8 Nos.
of Terminations and all other accessories as required as per MC 2 BBT
specifications, and approved Shop Drawings. ur RM
MC 2 BBT
b) 2000A, 50kA @ 1 Sec., TP+N, Bus Duct (IP.55) with 4 Nos.
of Terminations and all other accessories as required as per MC 2 BBT
specifications, and approved Shop Drawings. ur RM
MC 2 BBT
c) 2500A, 50kA @ 1 Sec., TP+N, Bus Duct (IP.55) with 4 Nos.
of Terminations and all other accessories as required as per MC 2 BBT
specifications, and approved Shop Drawings. ur RM
MC 2 BBT
2.2 Bus Bar Trunking (BBT) : MC 2 BBT
MC 2 BBT
2.2.1 Design, manufacture, assembly, supply, installation, testing
and commissioning (at site) of following capacity compact,
Copper Conductor, Bus Bar Trunking System including
Bends, Tees, Expansion Joints, Feeder Units, Tap off Units,
Transposition pieces, Flexible Connections etc. with all other MC 2 BBT
Hardware/accessories required for installation of Bus Bar
Trunking as per Specifications, approved Shop Drawings and
instruction of Engineer-in-charge.
MC 2 BBT

VOLTEC ENERGY SYSTEMS Page 1


LABOUR RATE
Shutter type spring loaded arrangements shall be provided
for tap off system. The shutter shall get closed when tap off
MC 2 BBT
box is taken out. Tap off facilities shall be there at every 500
mm interval as per standard.
MC 2 BBT
i) 1500A, TPN+E, 400 Volt, 40 KA, compact, copper conductor
MC 2 BBT
BBT. ur RM
MC 2 BBT
ii) 1250 A, TPN+E, 400 Volt, 40 KA, compact, copper Conductor
MC 2 BBT
BBT. ur RM
MC 2 BBT
iii) 1200 A, TPN+E, 400 Volt, 40 KA, compact, copper Conductor
MC 2 BBT
BBT. ur RM
MC 2 BBT
iv) 1000 A, TPN+E, 400 Volt, 40 KA, compact, copper Conductor
MC 2 BBT
BBT. ur RM
MC 2 BBT
v) 800 A, TPN+E, 400 Volt, 40 KA, compact, copper Conductor
MC 2 BBT
BBT. ur RM
vi) 630 A, TPN+E, 400 Volt, 40 KA, compact, copper Conductor
MC 2 BBT
BBT. ur RM
MC 2 BBT
vii) 400 A, TPN+E, 400 Volt, 40 KA, compact, copper Conductor
MC 2 BBT
BBT. ur RM
MC 2 BBT
viii) 250 A, TPN+E, 400 Volt, 40 KA, compact, copper Conductor
MC 2 BBT
BBT. ur RM
MC 2 BBT
ix) 200 A, TPN+E, 400 Volt, 40 KA, compact, copper Conductor
MC 2 BBT
BBT. ur RM
MC 2 BBT
Notes: MC 2 BBT
MC 2 BBT
a) The quantity mentioned above is approximate. Bidder to
procure /manufacture the items as per actual site MC 2 BBT
measurement & approved Shop drawings.
MC 2 BBT
b) Rates shall be inclusive of all accessories & fittings. MC 2 BBT
MC 2 BBT
2.2.2 Design, manufacture, assembly, supply, installation, testing
and commissioning of plug-in type TPN tap off box of
following capacity on the existing Bus Bar Trunking and
MC 2 BBT
complete with TPN MCCBs, links, interconnections, earthing
etc. as required, as per specifications and as per approved
Shop drawings.
MC 2 BBT
i) 250A, TPN MCCB Tap off box. ur No. MC 2 BBT
MC 2 BBT
ii) 125A TPN MCCB Tap off box. ur Nos. MC 2 BBT
MC 2 BBT
iii) 100A TPN MCCB Tap off box. ur Nos. MC 2 BBT
MC 2 BBT
iv) 80A TPN MCCB Tap off box. ur Nos. MC 2 BBT
MC 2 BBT
v) 63A TPN MCCB Tap off box. ur Nos. MC 2 BBT
MC 2 BBT

VOLTEC ENERGY SYSTEMS Page 2


LABOUR RATE
vi) 40A TPN MCCB Tap off box. ur Nos. MC 2 BBT
MC 2 BBT
vii) 32A TPN MCCB Tap off box. ur Nos. MC 2 BBT
MC 2 BBT
2.2.3 Design, Manufacture, Supply, installation, testing and
commissioning of End Feed Box/Bus Bar Trunking Adapter
Box, of following ratings with Digital Voltmeter & Ammeter
(ELF 3259 of Conzerv or Equivalent) complete with 5VA, MC 2 BBT
class 1.0 CTs of required ratio and one set of phase
indication lamps and back-up SPMCBs, as per approved
drawing and specifications.
MC 2 BBT
a) 1500 Amp with 1600 Amp, TPN, 40 KA, MDO ACB. ur Nos. MC 2 BBT
MC 2 BBT
b) 1250 Amp with 1250 Amp, TPN, 40 KA, MDO ACB. ur Nos. MC 2 BBT
MC 2 BBT
c) 1200 Amp with 1200 Amp, TPN, 40 KA, MDO ACB. ur Nos. MC 2 BBT
MC 2 BBT
d) 1000 Amp with 1000 Amp, TPN, 40 KA, MDO ACB. ur Nos. MC 2 BBT
MC 2 BBT
e) 800 Amp with 800 Amp, TPN, 40 KA, MDO ACB. ur Nos. MC 2 BBT
MC 2 BBT
f) 630 Amp with 630 Amp, TPN, 40 KA, MCCB. ur Nos. MC 2 BBT
g) 400 Amp with 400 Amp, TPN, 40 KA, MCCB. ur Nos. MC 2 BBT
MC 2 BBT
h) 250 Amp with 250 Amp, TPN, 40 KA, MCCB. ur Nos. MC 2 BBT
MC 2 BBT
MC 2 BBT
Design, Manufacturing, Supply, installation, testing and
2.2.4 commissioning of Bus Coupler panels with ACB/MCCB of MC 2 PANEL
following ratings for Bus Duct/Bus Bar Trunking System.
The Bus Coupler panel shall consist of 400V, 40 KA@ 1 Sec,
4 pole, Draw out type, Electrically operated, ACB/MCCB
- complete with under voltage and shunt trip release, MC 2 PANEL
antipumping protection, ON/OFF indication lamps etc. as
required, as per specifications and approved Shop drawings.

MC 2 PANEL
Bus Couper Panel shall be suitable for Termination of
- Compact Bus Bar Trunking from Top/Bottom as per approved MC 2 PANEL
shop drawing.
Bus Coupler Breaker shall have suitable No. of NO/NC
- contacts for required interlocking with the Breakers of End MC 2 PANEL
feed units of Bus Bar Trunking.
MC 2 PANEL
Bus Coupler Panel with 1000 Amp, 400V, 40 KA @ 1 Sec, 4
a) ur Nos. MC 2 PANEL
Pole, EDO ACB
MC 2 PANEL
Bus Coupler Panel with 800 Amp, 400V, 40 KA @ 1 Sec, 4
b) ur Nos. MC 2 PANEL
Pole, EDO ACB
MC 2 PANEL
Bus Coupler Panel with 630 Amp, 400V, 40 KA @ 1 Sec, 4
c) ur Nos. MC 2 PANEL
Pole, Motorised MCCB
MC 2 PANEL
Notes: MC 2 PANEL
MC 2 PANEL

VOLTEC ENERGY SYSTEMS Page 3


LABOUR RATE
The fabrication of bus duct/Bus Bar Trunking shall be taken
up only after actual measurement and site routing. Necessary
i) bends/transposition pieces/ expansion joints etc. shall be MC 2 PANEL
estimated & included. Payment will be made on running
meter basis.
MC 2 PANEL
The supply and fabrication & installation of structural steel for
ii) bus duct/Bus Bar Trunking support is included in the above MC 2 PANEL
items.
MC 2 PANEL
TOTAL OF BUS DUCT/BUS BAR TRUNKING SYSTEM
MC 2 PANEL
CARRIED OVER TO SUMMARY
3.00 LV SWITCHGEAR PANELS & DISTRIBUTION BOARDS: MC 2 PANEL
MC 2 PANEL
LV SWITCHGEAR PANELS : MC 2 PANEL
MC 2 PANEL

Design, manufacture, supply, unloading, receiving, storing,


handling, installation, testing and commissioning of following
LV panels suitable for 400 V, 3 phase, 4 wire, 50 Hz power
distribution system. The panel shall be Indoor, free standing,
floor mounting, sheet metal clad, cubicle, dead front, dust and
vermin proof type compartmentalised design fabricated out of
14 SWG CRCA sheet steel, complete with colour coded, heat
shrinkable PVC insulated, Copper bus bars and separate
earth bus bar of adequate cross section through out the . MC 2 PANEL
length of the panel. The incoming and outgoing feeders shall
be accommodated in a fully segregated, modular multitier
arrangement with adequate size and distinct cable alley, bus
bar alley/chamber. The panel shall be complete with name
plate, earthing, numbering, danger plate etc. as required and
as per specifications and drawings. The panel shall withstand
the fault level of as indicated elsewhere or shown in Single
Line Diagrams.

MC 2 PANEL
Important Notes: Common for all Switchboard: MC 2 PANEL
MC 2 PANEL
The BOQ shall be read inconjunction with general notes,
specification and Single Line Diagrams. Incase of any
discrepancy between specification, BOQ and SLD, the same
1.00 MC 2 PANEL
shall be brought to the notice of Employer before quoting the
rates, otherwise stringent condition shall be deemed to have
been considered.
MC 2 PANEL
2.00 Fault current wherever mentioned shall be Ics value. MC 2 PANEL
MC 2 PANEL

All MCCB shall be provided with door interlocked rotary


handle with ON/OFF/TRIP position indicator, microprocessor
3.00 based releases for over current, selectable short circuit and MC 2 PANEL
instentaneous short circuit protection (settable at site). I/C
MCCB shall be provided with E/F release/ protection also.

MC 2 PANEL
4.00 All feeder doors shall have pad locking arrangement. MC 2 PANEL
MC 2 PANEL
5.00 All TP feeders shall have solid isolable neutral link. MC 2 PANEL
MC 2 PANEL
All MCCB used in starter feeder shall be suitable for motor
6.00 MC 2 PANEL
duty application.

VOLTEC ENERGY SYSTEMS Page 4


LABOUR RATE
MC 2 PANEL
7.00 All power contactors including NIC shall be of AC3 duty. MC 2 PANEL
MC 2 PANEL
All ACB's shall be with micro processor based O/C and S/C
releases and Breaker Control Switch (BCS) having lost
8.00 MC 2 PANEL
motion device. I/C ACBs shall be provided with E/F release
also. Bus coupler shall be provided without releases.
MC 2 PANEL
Spare contacts of ACB/Relays/Contactor etc. shall be wired
9.00 MC 2 PANEL
upto terminal block.
All switchgear used in starter feeder shall be type-2 co-
10.00 ordinated. Manufacturer is required to submit manufacturers MC 2 PANEL
type-2 co-ordination chart for the make used.

MC 2 PANEL
11.00 Capacitor shall be super heavy duty type (MPP technology). MC 2 PANEL
MC 2 PANEL
All outgoing terminals (power and control) shall be brought
12.00 MC 2 PANEL
upto cable alley. 10% extra terminals shall be provided.
MC 2 PANEL
10% extra indicating lamp in loose shall be supplied along
13.00 MC 2 PANEL
with panel.
MC 2 PANEL
Removable lifting hook shall be provided in all transportation
14.00 MC 2 PANEL
section.
MC 2 PANEL
15.00 All CT, PT shall be epoxy resin cast. MC 2 PANEL
MC 2 PANEL
16.00 All meters are digital type. MC 2 PANEL
MC 2 PANEL
Panel shall be powder coated of approved shade with
17.00 MC 2 PANEL
minimum 60 micron thickness.
MC 2 PANEL
ACB's/MCCB's in one particular panel shall be of one similar
18.00 MC 2 PANEL
make.
MC 2 PANEL
Size of Voltmeter / Ammeter for incomer also, 96mm x 96mm
19.00 flush mounted with shrouded terminal shall be used in the MC 2 PANEL
panel.
MC 2 PANEL
20.00 Bus bar chamber shall be kept at top of the all panels. MC 2 PANEL
MC 2 PANEL
All bus bar shall be insulated with coloured PVC Sleeve
21.00 MC 2 PANEL
i.e.RYB,BK as per colour code.
MC 2 PANEL
Internal wiring of panel shall be with size 2.5sqmm Flexible
22.00 Copper Conductor for CT circuit and control wiring with 1.5 MC 2 PANEL
sqmm.
MC 2 PANEL
23.00 All indicating light shall be LED type . MC 2 PANEL
MC 2 PANEL
Each vertical section of floor mounted panel shall have
24.00 independent base frame (75mm x 40mm) size made out of 3 MC 2 PANEL
mm sheet steel (LT Panel & DG Panel).
MC 2 PANEL

VOLTEC ENERGY SYSTEMS Page 5


LABOUR RATE
All the makes shall be as per Employer's approved make list
25.00 MC 2 PANEL
only.
MC 2 PANEL
Wherever only voltmeter & ammeter are required, the same
26.00 may be provided in combined meter suitable for both MC 2 PANEL
parameter.
3.10 SMDB-EE-ME2.00-E2-01 : MC 2 PANEL
Location: Ground Floor : MC 2 PANEL
MC 2 PANEL
SMDB shall Comprise of the following: MC 2 PANEL
MC 2 PANEL
a) Incomings: MC 2 PANEL
MC 2 PANEL

One (1) No. 400 Amps, 400 V, 40kA TPN MCCB with
ON/OFF/TRIP indication lamp and TNC control switch, under
voltage & shunt trip release, microprocessor based O/C, S/C MC 2 PANEL
& E/F protection etc. complete as required for Incomming
Supply Feeder as per SLD, (E/SP/ME2 5.S.01.01, Rev. A).

MC 2 PANEL
b) Metering & indication for incoming breaker: MC 2 PANEL
MC 2 PANEL
Incoming breaker shall be provided with MC 2 PANEL
MC 2 PANEL
One (1) No. Digital Multifunction meter with RS-485 port
i) suitable for measurement of voltage, currents and Frequency MC 2 PANEL
(ELF3259 of 'Conzerv' make or equivalent).
MC 2 PANEL
One (1) set 3 Nos. CTs of ratio 400/5A,15VA, Class 1.0 as
ii) MC 2 PANEL
required.
MC 2 PANEL
iii) One set (3 Nos) phase indication lamp with backup SP MCB. MC 2 PANEL
MC 2 PANEL
Notes : MC 2 PANEL
MC 2 PANEL
Sufficient No. of contacts terminals shall be provided in the
1.00 panel as required for necessary remote operation and MC 2 PANEL
indications etc.
MC 2 PANEL
Operation interlocks as per specification & drawings
indicating sufficient nos. of potential free contacts for
2.00 MC 2 PANEL
interlocking/ indication annunciation/ control etc shall be
provided by the bidder as required.
MC 2 PANEL
c) BUS BARS: MC 2 PANEL
MC 2 PANEL
One (1) Sets of 500Amp., 40kA, TPN+E, Copper Bus bar with
colour coded, heat shrinkable sleeves (with 100% neutral). MC 2 PANEL
Copper Earth Bus of 40 x 6 mm.
MC 2 PANEL
d) Outgoing: MC 2 PANEL
MC 2 PANEL
Outgoing feeders, supplying to the pumps shall be provided
with Earth leakage relay with CBCT as required and as per MC 2 PANEL
SLD (E/SP/ME2 5.S.01.01, Rev. A) and specifications.

VOLTEC ENERGY SYSTEMS Page 6


LABOUR RATE
MC 2 PANEL
i) Two (2) Nos. 100 A, 40 KA, TPN MCCB. MC 2 PANEL
MC 2 PANEL
ii) One (1) No. 80 A, 40 KA, TPN MCCB. MC 2 PANEL
MC 2 PANEL
iii) Four (4) Nos. 63 A, 40 KA, TPN MCCB. MC 2 PANEL
MC 2 PANEL
iv) Three (3) Nos. 40 A, 40 KA, TPN MCCB. MC 2 PANEL
SMDB-EE-ME2.00-E2-01 described as above (from a to d)
1 Set MC 2 PANEL
and as per Specifications and SLD.
3.20 FINAL DISTRIBUTION BOARDS : MC 2 PANEL
MC 2 PANEL
Design, manufacture, supply, installation (recessed/ surface),
testing and commissioning of following switch fuse Unit/
MCCB/MCB type distribution boards as per drawings &
MC 2 PANEL
specifications. The surface distribution boards shall be
mounted as required and as per specifications and relevant
approved shop drawings.
MC 2 PANEL
3.2.1 DB-EE-ME2.00-E2-01 : MC 2 PANEL
MC 2 PANEL
Incomer: MC 2 PANEL
MC 2 PANEL
- 100A TP MCB Isolator. MC 2 PANEL
MC 2 PANEL
Busbar : MC 2 PANEL
MC 2 PANEL
- 150A 4P Cu. busbar MC 2 PANEL
MC 2 PANEL
Outgoing – (10KA) comprising MC 2 PANEL
MC 2 PANEL
Section-1 MC 2 PANEL
MC 2 PANEL
- One (1) no. 16A 3 phase, RCD (100 mA). MC 2 PANEL
MC 2 PANEL
- Fifteen (15) nos. 10A SP MCB. MC 2 PANEL
MC 2 PANEL
Section-2 MC 2 PANEL
MC 2 PANEL
- One (1) no. 63A 3 Phase RCD (30 mA). MC 2 PANEL
MC 2 PANEL
- Twenty One (21) nos. 20A SP MCB. MC 2 PANEL
MC 2 PANEL
DB-EE-ME2.00-E2-01 as described above and as per DB
- 1 Set MC 2 PANEL
chart.
MC 2 PANEL
3.2.2 DB-EE-ME2.00-E2-02 : MC 2 PANEL
MC 2 PANEL
Incomer: MC 2 PANEL
MC 2 PANEL
- 63A TP MCB Isolator. MC 2 PANEL
MC 2 PANEL

VOLTEC ENERGY SYSTEMS Page 7


LABOUR RATE
Busbar : MC 2 PANEL
MC 2 PANEL
- 100A 4P Cu. busbar MC 2 PANEL
MC 2 PANEL
Outgoing – (10KA) comprising MC 2 PANEL
MC 2 PANEL
Section-1 MC 2 PANEL
MC 2 PANEL
- One (1) no. 16A, 3 Phase RCD (100 mA). MC 2 PANEL
MC 2 PANEL
- Nine (9) nos. 10A SP MCB. MC 2 PANEL
MC 2 PANEL
Section-2 MC 2 PANEL
MC 2 PANEL
- One (1) no. 32A, 3 Phase RCD (30 mA). MC 2 PANEL
MC 2 PANEL
- Twelve (12) nos. 20A SP MCB. MC 2 PANEL
MC 2 PANEL
DB-EE-ME2.00-E2-02 as described above and as per DB
- 1 Set MC 2 PANEL
chart.
3.2.3 DB-EE-ME2.10-D2-03 : MC 2 PANEL
MC 2 PANEL
Incomer: MC 2 PANEL
MC 2 PANEL
- 63A TP MCB Isolator. MC 2 PANEL
MC 2 PANEL
Busbar : MC 2 PANEL
MC 2 PANEL
- 100A 4P Cu. busbar MC 2 PANEL
MC 2 PANEL
Outgoing – (10KA) comprising MC 2 PANEL
MC 2 PANEL
Section-1 MC 2 PANEL
MC 2 PANEL
- One (1) no. 20A 3 Phase RCD (100 mA). MC 2 PANEL
MC 2 PANEL
- Twelve (12) nos. 10A SP MCB. MC 2 PANEL
MC 2 PANEL
Section-2 MC 2 PANEL
MC 2 PANEL
- One (1) no. 32A 3 Phase RCD (30 mA). MC 2 PANEL
MC 2 PANEL
- Twenty One (21) nos. 20A, SP MCB. MC 2 PANEL
MC 2 PANEL
DB-EE-ME2.10-D2-03 as described above and as per DB
- 1 Set MC 2 PANEL
chart
MC 2 PANEL
3.2.4 DB-EE-ME2.10-D2-04 : MC 2 PANEL
MC 2 PANEL
Incomer: MC 2 PANEL
MC 2 PANEL

VOLTEC ENERGY SYSTEMS Page 8


LABOUR RATE
- 100A TP MCB Isolator. MC 2 PANEL
MC 2 PANEL
Busbar : MC 2 PANEL
MC 2 PANEL
- 150A 4P Cu. busbar MC 2 PANEL
MC 2 PANEL
Outgoing – (10KA) comprising MC 2 PANEL
MC 2 PANEL
Section-1 MC 2 PANEL
MC 2 PANEL
- One (1) no. 63A 3 Phase RCD (30 mA). MC 2 PANEL
MC 2 PANEL
- Twenty One (21) nos. 20A SP MCB. MC 2 PANEL
MC 2 PANEL
Section-2 MC 2 PANEL
MC 2 PANEL
- One (1) no. 63A 3 Phase RCD (30 mA). MC 2 PANEL
MC 2 PANEL
- Twenty Four (24) nos. 20A SP MCB. MC 2 PANEL
MC 2 PANEL
DB-EE-ME2.10-D2-04 as described above and as per DB
- 1 Set MC 2 PANEL
chart.
MC 2 PANEL
Design, Manufacturing, Supply, installation, Testing and
Commissioning of Auto Transfer Switch Panel (ATS Panels)
3.30 MC 2 PANEL
of following ratings as per specifications, SLD and approved
Shop drawing :-
MC 2 PANEL
a) 250 Amp, 4 pole, 400V, 40 KA @ 1 Sec. ur Nos. MC 2 PANEL
MC 2 PANEL
b) 200 Amp, 4 pole, 400V, 40 KA @ 1 Sec. ur Nos. MC 2 PANEL
MC 2 PANEL
c) 100 Amp, 4 pole, 400V, 40 KA @ 1 Sec. ur Nos. MC 2 PANEL
MC 2 PANEL
d) 63 Amp, 4 pole, 400V, 40 KA @ 1 Sec. ur Nos. MC 2 PANEL
MC 2 PANEL
e) 40 Amp, 4 pole, 400V, 40 KA @ 1 Sec. 1 No. MC 2 PANEL
MC 2 PANEL
f) 32 Amp, 4 pole, 400V, 40 KA @ 1 Sec. ur Nos. MC 2 PANEL
MC 2 PANEL
TOTAL OF LV SWITCHGEAR PANELS & DISTRIBUTION
MC 2 PANEL
BOARDS CARRIED OVER TO SUMMARY
4.00 CABLES, SUB MAINS & CABLE TRAYS : MC 2 CAB
MC 2 CAB
4.10 Cables in Under Ground Installations : MC 2 CAB
MC 2 CAB
Supply, installation, testing and commissioning of following
sizes of PVC sheathed, XLPE insulated copper conductor
power/multicore control, armoured, Multi-strand cable of 1.1
KV grade in ground including digging the trench, laying the MC 2 CAB
cable with sand and brick covering, back filling reaming etc
as required, as per specfications and as per directions of
Engineer-in-charge.

VOLTEC ENERGY SYSTEMS Page 9


LABOUR RATE
MC 2 CAB
Copper Conductor, Armoured XLPE Cables
4.1.1 MC 2 CAB
(PVC/SWA/XLPE) :
MC 2 CAB
a) 4 core 400 Sqmm 10 RM MC 2 CAB
b) 4 core 300 Sqmm 10 RM MC 2 CAB
c) 4 core 240 Sqmm 200 RM MC 2 CAB
d) 4 core 185 sqmm 10 RM MC 2 CAB
e) 4 core 150 sqmm 10 RM MC 2 CAB
f) 4 core 120 sqmm 10 RM MC 2 CAB
g) 4 core 95 sqmm 10 RM MC 2 CAB
h) 4 core 70 sqmm 20 RM MC 2 CAB
i) 4 core 50 sqmm 10 RM MC 2 CAB
j) 4 core 35 sqmm 50 RM MC 2 CAB
k) 4 core 25 sqmm 50 RM MC 2 CAB
l) 4 core 16 sqmm 20 RM MC 2 CAB
m) 4 core 10 sqmm 10 RM MC 2 CAB
n) 4 core 6 sqmm 10 RM MC 2 CAB
o) 4 core 4 sqmm 10 RM MC 2 CAB
p) 3 core 25 sqmm 10 RM MC 2 CAB
q) 3 core 16 sqmm 10 RM MC 2 CAB
r) 3 core 10 sqmm 10 RM MC 2 CAB
s) 3 core 6 sqmm 10 RM MC 2 CAB
t) 3 core 4 sqmm 10 RM MC 2 CAB
u) 2 core 6 sqmm 10 RM MC 2 CAB
v) 2 core 4 sqmm 10 RM MC 2 CAB
MC 2 CAB
4.20 Cables on Racks / Pipes / Ducts / Wireways/Cable Trays : MC 2 CAB
MC 2 CAB
Supply, installation, testing and commissioning of following
sizes of PVC sheathed, XLPE insulated, copper conductor,
power/multicore, control, armoured, Multi-stranded cable of
1.1 KV grade on surface of wall or in existing cable tray MC 2 CAB
/masonary ducts/hume pipe with fixing hardware etc as
required, as per specifications and as per direction of
Engineer-in-charge.
MC 2 CAB
4.2.1 Copper Conductor Armoured Cables : MC 2 CAB
MC 2 CAB
a) 4 core 400 Sqmm 10 RM MC 2 CAB
b) 4 core 300 Sqmm 10 RM MC 2 CAB
c) 4 core 240 Sqmm 100 RM MC 2 CAB
d) 4 core 185 sqmm 10 RM MC 2 CAB
e) 4 core 150 sqmm 10 RM MC 2 CAB
f) 4 core 120 sqmm 10 RM MC 2 CAB
g) 4 core 95 sqmm 10 RM MC 2 CAB
h) 4 core 70 sqmm 10 RM MC 2 CAB
i) 4 core 50 sqmm 10 RM MC 2 CAB
j) 4 core 35 sqmm 10 RM MC 2 CAB
k) 4 core 25 sqmm 200 RM MC 2 CAB
l) 4 core 16 sqmm 200 RM MC 2 CAB
m) 4 core 10 sqmm 100 RM MC 2 CAB

VOLTEC ENERGY SYSTEMS Page 10


LABOUR RATE
n) 4 core 6 sqmm 100 RM MC 2 CAB
o) 4 core 4 sqmm 100 RM MC 2 CAB
p) 3 core 25 sqmm 10 RM MC 2 CAB
q) 3 core 16 sqmm 10 RM MC 2 CAB
r) 3 core 10 sqmm 10 RM MC 2 CAB
s) 3 core 6 sqmm 10 RM MC 2 CAB
t) 3 core 4 sqmm 100 RM MC 2 CAB
u) 2 core 6 sqmm 10 RM MC 2 CAB
v) 2 core 4 sqmm 10 RM MC 2 CAB
MC 2 CAB
4.2.2 Copper Conductor Armoured Control Cables : MC 2 CAB
MC 2 CAB
a) 14 C 1.5 Sqmm PVC cable 10 RM MC 2 CAB
b) 10 C 1.5 Sqmm PVC cable 10 RM MC 2 CAB
c) 9 C 1.5 Sqmm PVC cable 10 RM MC 2 CAB
d) 7 C 1.5 Sqmm PVC cable 10 RM MC 2 CAB
e) 5 C 1.5 Sqmm PVC cable 100 RM MC 2 CAB
f) 3 C 1.5 Sqmm PVC cable 100 RM MC 2 CAB
MC 2 CAB
4.30 Cable Termination : MC 2 TERM
MC 2 TERM
Supply and making end termination with brass double
compression glands for the following XLPE insulated PVC
sheathed, 1100 V grade, Multi-strand copper conductor cable
including cost of crimping lugs/ferrules, double compression MC 2 TERM
glands, solder, cable sockets, insulation tap etc complete as
required, as per specifications and as per direction of
Engineer-in-charge.
MC 2 TERM
4.3.1 Copper conductor armoured cables : MC 2 TERM
MC 2 TERM
a) 4 core 400 Sqmm 2 Nos. MC 2 TERM
b) 4 core 300 Sqmm 2 Nos. MC 2 TERM
c) 4 core 240 Sqmm 2 Nos. MC 2 TERM
d) 4 core 185 sqmm 2 Nos. MC 2 TERM
e) 4 core 150 sqmm 2 Nos. MC 2 TERM
f) 4 core 120 sqmm 2 Nos. MC 2 TERM
g) 4 core 95 sqmm 2 Nos. MC 2 TERM
h) 4 core 70 sqmm 2 Nos. MC 2 TERM
i) 4 core 50 sqmm 2 Nos. MC 2 TERM
j) 4 core 35 sqmm 2 Nos. MC 2 TERM
k) 4 core 25 sqmm 10 Nos. MC 2 TERM
l) 4 core 16 sqmm 8 Nos. MC 2 TERM
m) 4 core 10 sqmm 4 Nos. MC 2 TERM
n) 4 core 6 sqmm 2 Nos. MC 2 TERM
o) 4 core 4 sqmm 2 Nos. MC 2 TERM
p) 3 core 25 sqmm 2 Nos. MC 2 TERM
q) 3 core 16 sqmm 2 Nos. MC 2 TERM
r) 3 core 10 sqmm 2 Nos. MC 2 TERM
s) 3 core 6 sqmm 2 Nos. MC 2 TERM
t) 3 core 4 sqmm 2 Nos. MC 2 TERM

VOLTEC ENERGY SYSTEMS Page 11


LABOUR RATE
u) 2 core 6 sqmm 2 Nos. MC 2 TERM
v) 2 core 4 sqmm 2 Nos. MC 2 TERM
4.3.2 Copper Conductor PVC Insulated Armoured Control Cables : MC 2 TERM
(Single Compression Glands suitable for following armoured
MC 2 TERM
cables)
MC 2 TERM
a) 14 C x 1.5 Sqmm 2 Nos. MC 2 TERM
b) 10 C x 1.5 Sqmm 2 Nos. MC 2 TERM
c) 9 C x 1.5 Sqmm 2 Nos. MC 2 TERM
d) 7 C x 1.5 Sqmm 2 Nos. MC 2 TERM
e) 5 C x 1.5 Sqmm 4 Nos. MC 2 TERM
f) 3 C x 1.5 Sqmm 4 Nos. MC 2 TERM
MC 2 TERM

The cable quantities given are approximate and to cover


various sizes. The contractor shall measure the cables
Notes : MC 2 TERM
required and procurement order shall be placed accordingly.
The quantities shall be confirmed before start of work.

MC 2 TERM
Supply, installation, testing and commissioning of 1.1 KV
grade, Multicore, copper conductor, LSZH outer sheathed,
CWZ fire resistant cable (in compliance with BS:6387) of
4.40 following sizes on surfae of wall/existing cable MC 2 CAB
trays/Mesonary Hume pipe/Duct/Trenches etc., with fixing
hardware etc. as required as per specifications and as per
direction of Engineer-in-charge.
MC 2 CAB
a) 4 C x 185 Sqm, CWZ Cable 10 RM MC 2 CAB
b) 4 C x 150 Sqm, CWZ Cable 10 RM MC 2 CAB
c) 4 C x 120 Sqm, CWZ Cable 10 RM MC 2 CAB
d) 4 C x 95 Sqm, CWZ Cable 10 RM MC 2 CAB
e) 4 C x 70 Sqm, CWZ Cable 10 RM MC 2 CAB
f) 4 C x 50 Sqm, CWZ Cable 10 RM MC 2 CAB
g) 4 C x 35 Sqm, CWZ Cable 10 RM MC 2 CAB
h) 4 C x 25 Sqm, CWZ Cable 10 RM MC 2 CAB
i) 4 C x 16 Sqm, CWZ Cable 200 RM MC 2 CAB
j) 4 C x 10 Sqm, CWZ Cable 10 RM MC 2 CAB
k) 4 C x 6 Sqm, CWZ Cable 10 RM MC 2 CAB
l) 4 C x 4 Sqm, CWZ Cable 10 RM MC 2 CAB
m) 4 C x 2.5 Sqm, CWZ Cable 10 RM MC 2 CAB
MC 2 CAB
4.50 Cable Trays : MC 2 TRAY
MC 2 TRAY

Supply and installation of ladder type/perforated type cable


trays of the following sizes fabricated out of perforated hot dip
galvanised MS sheets of minimum 2.0 mm thick to be
installed horizontally or vertically. The cable tray shall be
complete including cost of supporting Steel/Hangers, bends, MC 2 TRAY
elbows, cross, tees, reducers etc as per drawings/site
condition and rate shall include cost of anchor fasteners,
screws, nuts, bolts and misc. other fixing hardware etc as
required, as per specifications and approved Shop drawings.

MC 2 TRAY

VOLTEC ENERGY SYSTEMS Page 12


LABOUR RATE
The cable tray shall be factory built. Bidder shall include in his
price, required numbers of Tees, Crosses, Bends, Elbows etc
Notes : MC 2 TRAY
as required as per actual site conditions. Bidder may refer to
the drawings for estimation purpose.
MC 2 TRAY
4.5.1 Ladder Type Cable tray : MC 2 TRAY
MC 2 TRAY
a) 900 mm x 75 mm x 2.0 mm 10 RM MC 2 TRAY
b) 750 mm x 75 mm x 2.0 mm 10 RM MC 2 TRAY
c) 600 mm x 75 mm x 2.0 mm 10 RM MC 2 TRAY
d) 450 mm x 75 mm x 2.0 mm 10 RM MC 2 TRAY
e) 300 mm x 75 mm x 2.0 mm 10 RM MC 2 TRAY
f) 225 mm x 75 mm x 2.0 mm 10 RM MC 2 TRAY
g) 100 mm x 75 mm x 2.0 mm 10 RM MC 2 TRAY
MC 2 TRAY
4.5.2 Perforated Type Cable Tray : MC 2 TRAY
MC 2 TRAY
a) 900 mm x 75 mm x 2.0 mm 10 RM MC 2 TRAY
b) 750 mm x 75 mm x 2.0 mm 10 RM MC 2 TRAY
c) 600 mm x 75 mm x 2.0 mm 10 RM MC 2 TRAY
d) 400 mm x 75 mm x 2.0 mm 50 RM MC 2 TRAY
e) 300 mm x 50 mm x 2.0 mm 50 RM MC 2 TRAY
f) 250 mm x 50 mm x 2.0 mm 10 RM MC 2 TRAY
g) 200 mm x 75 mm x 2.0 mm 10 RM MC 2 TRAY
h) 150 mm x 75 mm x 2.0 mm 10 RM MC 2 TRAY
i) 100 mm x 75 mm x 2.0 mm 50 RM MC 2 TRAY
MC 2 TRAY
4.5.3 Fibreglass Ladder Type Cable Tray : MC 2 TRAY
MC 2 TRAY
Supply & Installation of Ladder type Cable tray of following
sizes. The Cable Tray shall be complete including the cost of
MC 2 TRAY
Anchor fasteners, Hardware, supporting structure etc. as
required and as per specifications and approved drawing :
a) 600 mm wide 10 RM MC 2 TRAY
b) 450 mm wide 10 RM MC 2 TRAY
c) 300 mm wide 10 RM MC 2 TRAY
d) 225 mm wide 10 RM MC 2 TRAY
e) 100 mm wide 10 RM MC 2 TRAY
MC 2 TRAY
4.60 Misc. Works Relating to Cabling: MC 2 PIPE
MC 2 PIPE
4.6.1 GI Pipe Installation : MC 2 PIPE
MC 2 PIPE
Supply and installation of following sizes of `A' class GI pipe
for cable sleeves in recess/ on surface/Ground complete with
all accessories pull boxes where ever required, G.I. fish wire,
fixing hardware etc. including the chasing of wall/floor, and MC 2 PIPE
plastering the chased portion, digging the trench and back
filling, making good the damages, sealing of pipe entry etc as
required.
MC 2 PIPE
a) 25 mm dia 10 RM MC 2 PIPE
b) 32 mm dia 10 RM MC 2 PIPE

VOLTEC ENERGY SYSTEMS Page 13


LABOUR RATE
c) 40 mm dia 10 RM MC 2 PIPE
d) 50 mm dia 10 RM MC 2 PIPE
e) 80 mm dia 10 RM MC 2 PIPE
f) 100 mm dia 10 RM MC 2 PIPE
g) 150 mm dia 10 RM MC 2 PIPE
MC 2 PIPE
4.6.2 Flexible Conduits Installation : MC 2 PW
MC 2 PW
Supply and installation of following sizes of GI flexible
conduits with all accessories including fixing nipples,
MC 2 PW
couplings and fixing hardware etc as required and as per
specifications.
MC 2 PW
4.6.2.1 GI flexible conduits : MC 2 PW
MC 2 PW
a) 20 mm dia 100 RM MC 2 PW
b) 25 mm dia 200 RM MC 2 PW
c) 40 mm dia 50 RM MC 2 PW
d) 50 mm dia 50 RM MC 2 PW
TOTAL OF CABLES, SUB MAINS, CABLE TRAYS
MC 2 PW
CARRIED OVER TO SUMMARY
5.00 WIRING : MC 2 PW
MC 2 PW
5.10 Point Wiring : MC 2 PW
MC 2 PW
The rates for point wiring shall include the circuit wiring. MC 2 PW
MC 2 PW
Circuit wiring means the wiring from DB / Dimmer panel to the
MC 2 PW
first point of circuit through control switch.
MC 2 PW
Circuit wiring and subsequent looping shall be done with 2.5
MC 2 PW
Sqmm, 1100V grade LSZH insulated stranded, copper wires.
MC 2 PW
The rates of point wiring shall include supply, installation,
testing & commissioning of MS conduit with accessories, GI
Boxes and required GI flexible conduits with accessories up
to the Point, LSZH insulated, stranded, Cu. Wire, switches MC 2 PW
and sockets (as approved by Engineer-in-charge) etc. as
required and as per specification and direction of Engineer-in-
charge.
MC 2 PW
Where the light points are directly controlled from DB (without
any local control switches), the quoted rates shall not include MC 2 PW
the cost of MCBs etc. in the point wiring.
MC 2 PW
The rates of point wiring shall include earthing of each light,
fan, switches, switch plates, boxes and other non current
MC 2 PW
carrying metallic part with 2.5Sqm. Stranded copper, LSZH
insulated, stranded, copper wire.
MC 2 PW
5.1.1 Light Points controlled by switch : MC 2 PW
MC 2 PW
a) Single/ First light point con-trolled by a 5Amps switch. 29 Nos. MC 2 PW
MC 2 PW

VOLTEC ENERGY SYSTEMS Page 14


LABOUR RATE
b) Same as above but loop point 151 Nos. MC 2 PW
MC 2 PW
5.1.2 Light Points controlled directly from DB . MC 2 PW
MC 2 PW
i. Single/ First Point Controlled directly by MCB in DB 6 Nos. MC 2 PW
MC 2 PW
ii. Same as above but loop point. 50 Nos. MC 2 PW
MC 2 PW
5.1.3 Two way points : MC 2 PW
MC 2 PW
a) Light points controlled by 2 Nos 2 way switch. MC 2 PW
MC 2 PW
One / first light point controlled by two nos. two way 5 Amps.
i) 1 No. MC 2 PW
switch.
MC 2 PW
ii) Same as above but loop point. 1 No. MC 2 PW
MC 2 PW
5.1.4 Presence Sensor : MC 2 PW
MC 2 PW
Wiring from Presence Sensor to the DB/SwitchBoard/Light
fixtures, including providing Presence Sensor as required and
a) as per approved shop drawing (wiring from DB to light points 5 Nos. MC 2 PW
has already been included in subheads 1.1,1.2,1.3 above and
not to be considered here).
5.1.5 6A Socket Points : MC 2 PW
MC 2 PW
Wiring for 6A, BS, switched socket outlet including providing
a) 6A, BS, switched, socket outlet as per specification and 23 Point MC 2 PW
approved shop drawing.
MC 2 PW
5.20 Power Socket Wiring : MC 2 PW
MC 2 PW

Power Socket Wiring shall include supply, installation, testing


and commissioning of wiring of following points, including,
providing conduits of suitable size, its accessories/Hardware,
MC 2 PW
Junction Boxes, LSZH wires, termination of wires, switches,
socket outlets, Plug tops etc. as required, as per specification
and as approved by Engineer-in-charge.

MC 2 PW
Wiring for 1 No. BS, 16A, switched socket outlet with 4 Sqmm
LSZH insulated stranded copper conductor wires in
recessed/surface black enameled MS conduit including
cutting/filling chases, providing conduit with conduit
5.2.1 accessories, saddles, supply and fixing of 1 No. BS, 16A, 4 Point MC 2 PW
switched outlet with internal wiring in G.I. box, earthing of 3rd
pin with LSZH insulated, green colour 2.5 Sq.mm copper
wire, complete with all accessories as required and as per
approved shop drawing.
MC 2 PW

VOLTEC ENERGY SYSTEMS Page 15


LABOUR RATE
Wiring for 2 Nos. BS, 16A, switched outlet with 4 Sqmm
LSZH insulated stranded copper conductor wires in
recessed/surface black enameled MS conduit including
cutting/filling chases, providing conduit with conduit
5.2.2 accessories, saddles, supply and fixing of 2 Nos.BS, 16A, 10 Point MC 2 PW
switched outlet with internal wiring in G.I. box, earthing of 3rd
pin with LSZH insulated, green colour 2.5 Sq.mm copper
wire, complete with all accessories as required and as per
approved shop drawing.
MC 2 PW
Wiring for 3 Nos. BS, 16A, switched outlet with 4 Sqmm
LSZH insulated stranded copper conductor wires in
recessed/surface black enameled MS conduit including
cutting/filling chases, providing conduit with conduit
5.2.3 accessories, saddles, supply and fixing of 3 Nos.BS outlet 3 Point MC 2 PW
16A switched with internal wiring in G.I. box, earthing of 3rd
pin with LSZH insulated, green colour 2.5 Sq.mm copper
wire, complete with all accessories as required and as per
approved shop drawing.
MC 2 PW
Wiring for 4 Nos. BS, 16A, switched outlet with 4 Sqmm
LSZH insulated stranded copper conductor wires in
recessed/surface black enameled MS conduit including
cutting/filling chases, providing conduit with conduit
5.2.4 accessories, saddles, supply and fixing of 4 Nos.BS, 16A, 2 Point MC 2 PW
switched outlet with internal wiring in G.I. box, earthing of 3rd
pin with LSZH insulated, green colour 2.5 Sq.mm copper
wire, complete with all accessories as required and as per
approved shop drawing.
Wiring for 1 No. BS, 16A, switched outlet in IP-65 enclosure
with 4 Sqmm LSZH insulated stranded copper conductor
wires in recessed/surface black enameled MS conduit
including cutting/filling chases, providing conduit with conduit
5.2.5 accessories, saddles, supply and fixing of 1 No. BS, 16A, 5 Point MC 2 PW
switched outlet in IP-65 enclosure with internal wiring,
earthing of 3rd pin with LSZH insulated, green colour 2.5
Sq.mm copper wire, complete with all accessories as required
and as per approved shop drawing.
MC 2 PW

Wiring for 2 Nos. BS, 16A, switched outlet in IP-65 enclosure


with 4 Sqmm LSZH insulated stranded copper conductor
wires in recessed/surface black enameled MS conduit
including cutting/filling chases, providing conduit with conduit
5.2.6 accessories, saddles, supply and fixing of 2 Nos. BS, 16A, 1 Point MC 2 PW
switched outlet in IP-65 enclosure with internal wiring,
earthing of 3rd pin with LSZH insulated, green colour 2.5
Sq.mm copper wire, complete with all accessories as required
and as per approved shop drawing.

MC 2 PW

Wiring for 3 Nos. BS, 16A, switched outlet in IP-65 enclosure


with 4 Sqmm LSZH insulated stranded copper conductor
wires in recessed/surface black enameled MS conduit
including cutting/filling chases, providing conduit with conduit
5.2.7 accessories, saddles, supply and fixing of 3 Nos. BS, 16A, 2 Point MC 2 PW
switched outlet in IP-65 enclosure with internal wiring,
earthing of 3rd pin with LSZH insulated, green colour 2.5
Sq.mm copper wire, complete with all accessories as required
and as per approved shop drawing.

MC 2 PW

VOLTEC ENERGY SYSTEMS Page 16


LABOUR RATE
Wiring for 1 No. BS, 16A, switched outlet & 1 No. IP-65 BS
outlet 16A switched with 4 Sqmm LSZH insulated stranded
copper conductor wires in recessed/surface black enameled
MS conduit including cutting/filling chases, providing conduit
with conduit accessories, saddles, supply and fixing of 1 No.
5.2.8 1 Point MC 2 PW
BS, 16A, switched outlet & 1 No. IP-65 BS, 16A, switched
outlet with internal wiring in G.I. box, earthing of 3rd pin with
LSZH insulated, green colour 2.5 Sq.mm copper wire,
complete with all accessories as required and as per
approved shop drawing.
MC 2 PW
Wiring for 1 No. BS, 16A, switched outlet (Spur Outlet) with 4
Sqmm LSZH insulated stranded copper conductor wires in
recessed/surface black enameled MS conduit including
cutting/filling chases, providing conduit with conduit
5.2.9 accessories, saddles, supply and fixing of 1 No. BS, 16A, 6 Point MC 2 PW
switched outlet (Spur Outlet) with internal wiring in G.I. box,
earthing of 3rd pin with LSZH insulated, green colour 2.5
Sq.mm copper wire, complete with all accessories as required
and as per approved shop drawing.
MC 2 PW

Wiring for 1 No. BS, 32A, switched outlet in IP-65 enclosure


for Water Heater with 4 Sqmm LSZH insulated stranded
copper conductor wires in recessed/surface black enameled
MS conduit including cutting/filling chases, providing conduit
5.2.10 with conduit accessories, saddles, supply and fixing of 1 No. 1 Point MC 2 PW
BS, 32A, switched outlet in IP-65 enclosure with internal
wiring, earthing of 3rd pin with LSZH insulated, green colour
2.5 Sq.mm copper wire, complete with all accessories as
required and as per approved shop drawing.

MC 2 PW

Wiring for 2 Nos. Power & Data Pillar (type-1), each


consisting of 2 Nos. 6A BS socket, 1 No. 15A Switch and 1
No. RJ-45 Data Outlets in IP-65 enclosure, with 4 Sqmm
LSZH insulated stranded copper conductor wires in
recessed/surface black enameled MS conduit including
cutting/filling chases, providing conduit with conduit
5.2.11 6 Point MC 2 PW
accessories, saddles, supply and fixing of 2 Nos. Power &
Data Pillar (type-1), each consisting of 2 Nos. 6A BS socket
with 1 No. 15A Switch and 1 No. RJ-45 Data Outlets in IP-65
enclosure, with internal wiring, earthing with LSZH insulated,
green colour 2.5 Sq.mm copper wire, complete with all
accessories as required and as per approved shop drawing.

MC 2 PW
Wiring for 4 Nos. Power & Data Pillar (type-1), each
consisting of 2 Nos. 6A BS socket with 1 No. 15A Switch and
1 No. RJ-45 Data outlet in IP-65 enclosure, with 4 Sqmm
LSZH insulated stranded copper conductor wires in
recessed/surface black enameled MS conduit including
cutting/filling chases, providing conduit with conduit
5.2.12 42 Point MC 2 PW
accessories, saddles, supply and fixing of 4 Nos. Power &
Data Pillar (type-1), each consisting of 2 Nos. 6A BS socket
with 1 No. 15A Switch and 1 No. RJ-45 Data outlet in IP-65
enclosure, with internal wiring, earthing with LSZH insulated,
green colour 2.5 Sq.mm copper wire, complete with all
accessories as required.
MC 2 PW

VOLTEC ENERGY SYSTEMS Page 17


LABOUR RATE

Wiring for 2 Nos. Power & Data Pillar (type-2), each


consisting of 1 No. 6A BS switched socket and 1 No. RJ-45
Data outlets in IP-65 enclosure, with 4 Sqmm LSZH insulated
stranded copper conductor wires in recessed/surface black
enameled MS conduit including cutting/filling chases,
5.2.13 providing conduit with conduit accessories, saddles, supply 5 Point MC 2 PW
and fixing of 2 Nos. Power & Data Pillar (type-2), each
consisting of 1 No. 6A BS switched socket and 1 No. RJ-45
Data outlets in IP-65 enclosure, with internal wiring, earthing
with LSZH insulated, green colour 2.5 Sq.mm copper wire,
complete with all accessories as required.

MC 2 PW

Wiring for 1 No. Floor LV tank consisting of 4 Nos. 6A BS


switched socket and 2 Nos. RJ-45 Data Outlets in IP-65
enclosure, with 4 Sqmm LSZH insulated stranded copper
conductor wires in recessed/surface black enameled MS
conduit including cutting/filling chases, providing conduit with
5.2.14 4 Nos. MC 2 PW
conduit accessories, saddles, supply and fixing of 1 No. Floor
LV tank consisting of 4 Nos. 6A BS switched socket and 2
Nos. RJ-45 Data outlets in IP-65 enclosure, with internal
wiring, earthing with LSZH insulated, green colour 2.5 Sq.mm
copper wire, complete with all accessories as required.

MC 2 PW
5.30 CEE INDUSTRIAL SWITCHED SOCKETS MC 2 PW
MC 2 PW
Supply, installation, testing and commissioning of single
phase/three phase, CEE, switched, industrial type plug and
socket outlet in IP-65 enclosure including termination,
5.3.1 earthing etc. in surface/recessed mounting as required, as MC 2 PW
per specifications and approved shop drawings
(Cabling/Conduiting & wiring shall be paid separately under
different items).
MC 2 PW
a) 16A, 2P+E, CEE, switched socket outlet with plug top (IP-44) 8 Nos. MC 2 PW
16A, 3P+N+E, CEE, switched socket outlet with plug top (IP-
b) 1 No. MC 2 PW
44)
16A, 3P+N+E, CEE, switched socket outlet with plug top (IP-
c) 1 No. MC 2 PW
65) for water heaters.
MC 2 PW
5.40 ISOLATORS MC 2 DB
MC 2 DB
Supply, installation, testing and commissioning of isolators in
IP-65 enclosures complete with termination in MC 2 DB
surface/recessed mounting as required.
MC 2 DB
a) 16A Double pole isolator 1 No. MC 2 DB
MC 2 DB
b) 16A Four pole isolator 1 No. MC 2 DB
MC 2 DB
c) 40A Four pole isolator 4 Nos. MC 2 DB
MC 2 DB
d) 63A Four pole isolator 1 No. MC 2 DB
MC 2 DB
5.50 M.S. Black Conduits : MC 2 PW
MC 2 PW

VOLTEC ENERGY SYSTEMS Page 18


LABOUR RATE
Supply and installation of following size of MS conduit pipe in
recess or on surface including all accessories MS/CI
pull/junction boxes, GI fish wire, fixing hardware etc
MC 2 PW
including chasing the walls/floor and plastering the chased
portion and making good the damages etc, complete as
required and as per specifications.
MC 2 PW
a) 20 mm dia 20 RM MC 2 PW
b) 25 mm dia 20 RM MC 2 PW
c) 32 mm dia 20 RM MC 2 PW
d) 40 mm dia 20 RM MC 2 PW
e) 50 mm dia 20 RM MC 2 PW
MC 2 PW
5.60 Sub-mains Wiring : MC 2 PW
MC 2 PW
Supply and drawing of following sizes of LSZH insulated,
stranded, copper conductor wires of 650/1100 Volts grade in
MC 2 PW
existing conduit pipe /wire ways including connection
/terminations etc as required.
MC 2 PW
a) 2 x 1.5 Sqmm + 1 No. 1.5 Sqmm Copper earth wire 20 RM MC 2 PW
b) 2 x 2.5 Sqmm + 1 No. 1.5 Sqmm Copper earth wire 20 RM MC 2 PW
c) 2 x 4.0 Sqmm + 1 No. 2.5 Sqmm Copper earth wire. 20 RM MC 2 PW
d) 2 x 6.0 Sqmm + 1 No. 2.5 Sqmm Copper earth wire 20 RM MC 2 PW
e) 4 x 4.0 Sqmm + 1 No. 2.5 Sqmm Copper earth wire 20 RM MC 2 PW
f) 4 x 6.0 Sqmm + 1 No. 2.5 Sqmm Copper earth wire 20 RM MC 2 PW
g) 2 x 10.0 Sqmm + 1 No. 6.0 Sqmm Copper earth wire 20 RM MC 2 PW
h) 4 x 10.0 Sqmm + 2 Nos. 6.0 Sqmm Copper earth wire 20 RM MC 2 PW
i) 4 x 16.0 Sqmm + 2 Nos. 10.0 Sqmm Copper earth wire 20 RM MC 2 PW
j) 4 x 25.0 Sqmm + 2 Nos. 16.0 Sqmm Copper earth wire 20 RM MC 2 PW
MC 2 PW
Note: MC 2 PW
MC 2 PW
In false ceiling areas the work is to be co-ordinated with
respect to interior work and rate for point wiring shall include
1) MC 2 PW
flexible conduit/fixing nipples/couplers etc from the junction
box up to the fitting.
MC 2 PW
All wires used for circuit / point wiring shall be Low Smoke
2) MC 2 PW
Zero Halogen (LSZH) wires.
MC 2 PW
TOTAL OF WIRING CARRIED OVER TO SUMMARY MC 2 PW
6.00 LIGHTING FIXTURES : MC 2 LIGHT
MC 2 LIGHT
Inspection, receiving, storing, handling, assembling,
installation, testing and commissioning of wall /ceiling,
surface/ recessed, suspended from down rod, in furniture,
fluorescent / incandescent / Halogen lamp fixtures including
making connections with PVC insulated stranded copper
conductor wires complete including steel supports, MC 2 LIGHT
suspenders, fixing screws, turn buckles, bolts, nuts (down
rods ball and socket arrangement and special channel
mounting for industrial fitting/chandelier) etc, as required. The
mounting arrangement of lighting fixture shall be as indicated
in the approved drawings.
MC 2 LIGHT

VOLTEC ENERGY SYSTEMS Page 19


LABOUR RATE
Recessed Downlight 1 x 26 W (Thorn Chalice C 190H 1 X 26
i) 45 Nos. MC 2 LIGHT
W or Equivalent) (T13)
MC 2 LIGHT
Recessed Downlight 1 x 26 W (Thorn Chalice C 190H 1 X 26
ii) W or Equivalent) (T13) complete with Emergency Lighting 14 Nos. MC 2 LIGHT
Units.
MC 2 LIGHT
Wall mounted Luminaire with 1 x 28W Fluorescent T5 Lamp
iii) water proof IP44 (SITECO Europlex 24W IP44 or Equivalent) 4 Nos. MC 2 LIGHT
(T8)
MC 2 LIGHT
Recessed Luminaire with 4 x 18W T5 Lamps with Parabolic
iv) 47 Nos. MC 2 LIGHT
Louvre (Thorn Omega BS/SB 4 x 18W or Equivalent) (T14)
MC 2 LIGHT
Recessed Luminaire with 4 x 18W T5 Lamps with Parabolic
v) Louvre (Thorn Omega BS/SB 4 x 18W or Equivalent) (T14) 19 Nos. MC 2 LIGHT
complete with Emergency Lighting Units.
MC 2 LIGHT
Recessed outside Downlight IP54 (Trilux Downlight IP54 or
vi) 6 Nos. MC 2 LIGHT
Equivalent) (T21)
MC 2 LIGHT
Wall mounted Luminaire with 2 x 35W Fluorescent T5 Lamps
vii) with Prismatic Diffuser (Thorn Prisma C 2 x 35 T16CL or 2 Nos. MC 2 LIGHT
Equivalent) (T19)
MC 2 LIGHT

Wall mounted Luminaire with 2 x 35W Fluorescent T5 Lamps


viii) with Prismatic Diffuser (Thorn Prisma C 2 x 35 T16CL or 3 Nos. MC 2 LIGHT
Equivalent) (T19) complete with Emergency Lighting Units.

MC 2 LIGHT
Recessed Outside Downlight IP44 (Thorn Chalice or
ix) 21 Nos. MC 2 LIGHT
Equivalent) (T22)
MC 2 LIGHT
Recessed Outside Downlight IP44 (C190H 1 x 26W IP44 or
x) 9 Nos. MC 2 LIGHT
Equivalent) (T22) complete with Emergency Lighting Units.
MC 2 LIGHT
Bulk Head Light Wall Mounted with 2 x 28W TC-DEL Lamp
xi) 18 Nos. MC 2 LIGHT
IP-65 (Thorn Dunube 2 x 28W IP65 or Equivalent) (T11)
MC 2 LIGHT
Surface mounted Industrial Luminaire with 2 x 36W
xii) Fluorescent T5 Lamps (Thorn Indus RD 2 x 58W TW or 4 Nos. MC 2 LIGHT
Equivalent) (T6)
Surface mounted Industrial Luminaire with 2 x 36W
xiii) Fluorescent T5 Lamps (Thorn Indus RD 2 x 58W TW or 4 Nos. MC 2 LIGHT
Equivalent) (T6) complete with Emergency Lighting Units.
MC 2 LIGHT
CL 90 Bollard 18/24W IP65 Single-S (Siteco DL 102 Bollard
xiv) 4 Nos. MC 2 LIGHT
Luminaire TC-L 1x18/24W IP67 or equivalent) (T28)
MC 2 LIGHT
Emergency Exit down Fixture complete with Emergency
xv) 5 Nos. MC 2 LIGHT
Lighting Units (Cooper/Crompton or Approved Equivalent).
MC 2 LIGHT
Emergency Exit Up Fixture complete with Emergency Lighting
xvi) 1 No. MC 2 LIGHT
Units (Cooper/Crompton or Approved Equivalent).
MC 2 LIGHT
TOTAL OF LIGHTING FIXTURES CARRIED OVER TO
MC 2 LIGHT
SUMMARY
7.00 EARTHING & LIGHTNING PROTECTION SYSTEM : MC 2 EARTH

VOLTEC ENERGY SYSTEMS Page 20


LABOUR RATE
7.10 Earthing System: MC 2 EARTH

Supply, installation, testing and commissioning of copper


plate earthing stations making earth pits, earthing with copper
earth plate 600 mm x 600 mm x 3.15 mm thick including
funnel, charcoal/coke, salt, all earth work. Providing masonry
7.1.1 4 Nos. MC 2 EARTH
enclosure with 10 mm thick C.I. cover plate having locking
arrangement and watering pipe, disconnecting/ testing links
etc as per IS –3043 complete as required, as per
specifications, drawings and direction of Engineer-in-charge.

MC 2 EARTH
Supply, installation, testing and commissioning of GI plate
earthing stations making earth pits, earthing with GI earth
plate 600 mm x 600 mm x 6.30 mm thick including funnel,
charcoal/coke, salt, all earth work. Providing masonry
7.1.2 ur Nos. MC 2 EARTH
enclosure with 10 mm thick C.I. cover plate having locking
arrangement and watering pipe, disconnecting/ testing links
etc as per IS–3043 complete as required, as per
specifications, drawing and direction of Engineer-in-charge.
MC 2 EARTH
Supply, installation, testing and commissioning of GI Pipe
earthing stations making earth pits, earthing with GI pipe
4500 mm x 40 mm Dia including funnel, charcoal/coke, salt,
all earth work. Providing masonry enclosure with 10 mm thick
7.1.3 ur Nos. MC 2 EARTH
C.I. cover plate having locking arrangement and watering
pipe, disconnecting/ testing links etc as per IS–3043 complete
as required as per specifications, drawing and direction of
Engineer-in-charge.
MC 2 EARTH
7.1.4 Earthing Strip/Tape/Cables : MC 2 EARTH
MC 2 EARTH
Supply, installation, testing and commissioning of following
sizes of GI/Tinned Copper strip/tape clamped to walls, cable
trays, bus ducts, recess in Ground or surface etc for
equipment/ System earthing complete as required including
MC 2 EARTH
inter connection between length at joints, all fixing
accessories saddles, clamps etc and other fixing hardware
material as required, as per specifications, detail drawings
shall be included for proper installation.
MC 2 EARTH
7.1.4.1 G.I. Earthing strip/tape : MC 2 EARTH
MC 2 EARTH
a 50 x 8 mm strip 5 RM MC 2 EARTH
b 50 x 6 mm strip 5 RM MC 2 EARTH
c 40 x 6 mm strip 5 RM MC 2 EARTH
d 32 x 6 mm strip 5 RM MC 2 EARTH
e 25 x 6 mm strip 5 RM MC 2 EARTH
f 25 x 3 mm strip 5 RM MC 2 EARTH
MC 2 EARTH
7.1.4.2 Tinned Copper earthing strip/tape : MC 2 EARTH
MC 2 EARTH
a) 50 x 6 mm 500 RM MC 2 EARTH
b) 32 x 6 mm 100 RM MC 2 EARTH
c) 25 x 6 mm 10 RM MC 2 EARTH
d) 25 x 3 mm 500 RM MC 2 EARTH

VOLTEC ENERGY SYSTEMS Page 21


LABOUR RATE
Supply, installation, Termination, testing and commissioning
of PVC insulated, stranded copper conductor cable, laid on
7.1.5 surface/cable tray/duct/undger ground/Trench etc. as MC 2 CAB
required, as per approved shop drawing, site conditions and
as directed by Engineer-in-charge.
MC 2 CAB
a) 1C x 185 Sqm 100 RM MC 2 CAB
MC 2 CAB
b) 1C x 90 Sqm 5 RM MC 2 CAB
MC 2 CAB
c) 1C x 50 Sqm 5 RM MC 2 CAB
MC 2 CAB
d) 1C x 35 Sqm 5 RM MC 2 CAB
MC 2 CAB
e) 1C x 25 Sqm 5 RM MC 2 CAB
MC 2 CAB
Supply, installation, Termination, testing and Commissioning
of following sizes Tinned Copper Earth Bars including its
7.1.6 MC 2 EARTH
supporting/fixing hardware, as per drawings, specifications
and as directed by Engineer-in-charge.
MC 2 EARTH
7.1.6.1 75 x 6 mm tinned, Copper, Earth Bars. MC 2 EARTH
MC 2 EARTH
a) 300 mm 1 No. MC 2 EARTH
b) 500 mm 1 No. MC 2 EARTH
c) 750 mm 1 No. MC 2 EARTH
d) 1000 mm 1 No. MC 2 EARTH
MC 2 EARTH
7.1.6.2 50 x 6 mm tinned, Copper, Earth Bars. MC 2 EARTH
MC 2 EARTH
a) 300 mm 5 Nos. MC 2 EARTH
b) 500 mm 5 Nos. MC 2 EARTH
c) 750 mm 2 Nos. MC 2 EARTH
d) 1000 mm 1 No. MC 2 EARTH
MC 2 EARTH
7.20 Lightning Protection System: MC 2 EARTH
MC 2 EARTH

Supply, installation, testing and commissioning of copper


plate earthing stations making earth pits, earthing with copper
earth plate 600 mm x 600 mm x 3.15 mm thick including
funnel, charcoal/coke, salt, all earth work. Providing masonry
7.2.1 4 Nos. MC 2 EARTH
enclosure with 10 mm thick C.I. cover plate having locking
arrangement and watering pipe, disconnecting/ testing links
etc as per IS –3043 complete as required, as per drawings,
specifications and direction of Engineer-in-charge.

MC 2 EARTH
Supply, installation, testing and commissioning of GI Pipe
earthing stations making earth pits, earthing with GI pipe
4500 mm x 40 mm Dia including funnel, charcoal/coke, salt,
all earth work. Providing masonry enclosure with 10 mm thick
7.2.2 6 Nos. MC 2 EARTH
C.I. cover plate having locking arrangement and watering
pipe, disconnecting/ testing links etc as per IS–3043 complete
as required, as per drawings, specifications and direction of
Engineer-in-charge.
MC 2 EARTH

VOLTEC ENERGY SYSTEMS Page 22


LABOUR RATE
7.2.3 Earthing Strip/Wires : MC 2 EARTH
MC 2 EARTH

Supply, installation, testing and commissioning of following


sizes of GI strip/wire clamped to walls, Ductwork, pipe work,
Structural steel work, cladding work etc. in recess, in Ground
or surface etc for Lightning Protection System complete as
required including inter connection, terminations, between
0.00 length at joints, all fixing accessories saddles, plastic isolator MC 2 EARTH
mounting (of 50mmx80mm approx.), Sealing Collars, Sealing
Strip, Squared Timber Block (80mmx100mm approx.),
clamps, Lugs etc and other fixing hardware material as
required for proper installation as per detail drawings,
specifications and direction of Engineer-in-charge.

MC 2 EARTH
a) 25 x 3 mm strip 500 RM MC 2 EARTH
MC 2 EARTH
b) 25 x 6 mm strip 100 RM MC 2 EARTH
MC 2 EARTH
c) 32 x 6 mm strip 10 RM MC 2 EARTH
MC 2 EARTH
Supply, installation, Termination, testing and Commissioning
of following sizes GI Earth Bars including in supporting/fixing
7.2.4 MC 2 EARTH
hardware, as per drawings, specifications and as directed by
Engineer-in-charge.
MC 2 EARTH
7.2.4.1 75 x 6 mm GI Earth Bars. MC 2 EARTH
MC 2 EARTH
a) 300 mm 2 Nos. MC 2 EARTH
b) 500 mm 2 Nos. MC 2 EARTH
c) 750 mm 2 Nos. MC 2 EARTH
d) 1000 mm 2 Nos. MC 2 EARTH
MC 2 EARTH
7.2.4.2 50 x 6 mm GI Earth Bars. MC 2 EARTH
MC 2 EARTH
a) 300 mm 2 Nos. MC 2 EARTH
b) 500 mm 2 Nos. MC 2 EARTH
c) 750 mm 2 Nos. MC 2 EARTH
d) 1000 mm 2 Nos. MC 2 EARTH
MC 2 EARTH
Supply and fixing of Lightning Arrestor Rod/Lightning
Conductor finial made of 25 mm dia, 2.0 mm thick & 300 mm
Long GI Tube having single prong at top with 75 mm dia, 6
7.2.5 20 Nos. MC 2 EARTH
mm thick Base plate, including connections with roof parapit
Lightning protection Conductors, as per detailed drawings
and as per direction of Engineer-in-charge.
MC 2 EARTH
Supply and fixing of "Earth Test Joints" encased in 200 mm
(H) x 150 mm (W) x 100 mm (D) recessed in concrete with
7.2.6 6 Nos. MC 2 EARTH
removable cover plate as per detailed drawing and as per
direction of Engineer-in-charge.
MC 2 EARTH
TOTAL OF EARTHING & LIGHTNING PROTECTION
MC 2 EARTH
SYSTEM CARRIED OVER TO SUMMARY
TEAM BUILDING TB
1.00 LV SWITCHGEAR PANELS & DISTRIBUTION BOARDS: TB PANEL

VOLTEC ENERGY SYSTEMS Page 23


LABOUR RATE
TB PANEL
LV SWITCHGEAR PANELS : TB PANEL
TB PANEL

Design, manufacture, supply, unloading, receiving, storing,


handling, installation, testing and commissioning of following
LV panels suitable for 400 V, 3 phase, 4 wire, 50 Hz power
distribution system. The panel shall be Indoor, free standing,
floor mounting, sheet metal clad, cubicle, dead front, dust and
vermin proof type compartmentalised design fabricated out of
14 SWG CRCA sheet steel, complete with colour coded, heat
shrinkable PVC insulated, Copper bus bars and separate
earth bus bar of adequate cross section through out the TB PANEL
length of the panel. The incoming and outgoing feeders shall
be accommodated in a fully segregated, modular multitier
arrangement with adequate size and distinct cable alley, bus
bar alley/chamber. The panel shall be complete with name
plate, earthing, numbering, danger plate etc. as required and
as per specifications and drawings. The panel shall withstand
the fault level of as indicated elsewhere or shown in Single
Line Diagram.

TB PANEL
Important Notes: Common for all Switchboard: TB PANEL
TB PANEL
The BOQ shall be read inconjunction with general notes,
specification and Single Line Diagram. Incase of any
discrepancy between specification, BOQ and SLD, the same
1.00 TB PANEL
shall be brought to the notice of Employer before quoting the
rates, otherwise stringent condition shall be deemed to have
been considered.
TB PANEL
2.00 Fault current wherever mentioned shall be Ics value. TB PANEL
TB PANEL
All MCCB shall be provided with door interlocked rotary
handle with ON/OFF/Trip position indicator, microprocessor
3.00 based releases for over current, selectable short circuit and TB PANEL
instentaneous short circuit protection (settable at site). I/C
MCCB shall be provided with E/F release/ protection also.
TB PANEL
4.00 All feeder doors shall have pad locking arrangement. TB PANEL
TB PANEL
5.00 All TP feeders shall have solid isolable neutral link. TB PANEL
TB PANEL
All MCCB used in starter feeder shall be suitable for motor
6.00 TB PANEL
duty application.
TB PANEL
7.00 All power contactors including NIC shall be of AC3 duty. TB PANEL
TB PANEL
All ACB's shall be with micro processor based O/C and S/C
releases and Breaker Control Switch (BCS) having lost
8.00 TB PANEL
motion device. I/C ACBs shall be provided with E/F release
also. Bus coupler shall be provided without releases.
Spare contacts of ACB/Relays/Contactor etc. shall be wired
9.00 TB PANEL
upto terminal block.
TB PANEL

All switchgear used in starter feeder shall be type-2 co-


10.00 ordinated. Manufacturer is required to submit manufacturers TB PANEL
type-2 co-ordination chart for the make used.

VOLTEC ENERGY SYSTEMS Page 24


LABOUR RATE
TB PANEL
11.00 Capacitor shall be super heavy duty type (MPP technology). TB PANEL
TB PANEL
All outgoing terminals (power and control) shall be brought
12.00 TB PANEL
upto cable alley. 10% extra terminals shall be provided.
TB PANEL
10% extra indicating lamp in loose shall be supplied along
13.00 TB PANEL
with panel.
TB PANEL
Removable lifting hook shall be provided in all transportation
14.00 TB PANEL
section.
TB PANEL
15.00 All CT, PT shall be cast resin. TB PANEL
TB PANEL
16.00 All meters are digital type. TB PANEL
TB PANEL
Panel shall be powder coated of approved shade with
17.00 TB PANEL
minimum 60 micron thickness.
TB PANEL
ACB's/MCCB's in one particular panel shall be of one similar
18.00 TB PANEL
make.
TB PANEL
Size of Voltmeter / Ammeter for incomer also, 96mm x 96mm
19.00 flush mounted with shrouded terminal shall be used in the TB PANEL
panel.
TB PANEL
20.00 Bus bar chamber shall be kept at top of the all panels. TB PANEL
TB PANEL
All bus bar shall be insulated with coloured PVC Sleeve
21.00 TB PANEL
i.e.RYB,BK as per colour code.
TB PANEL
Internal wiring of panel shall be with size 2.5sqmm Flexible
22.00 Copper Conductor for CT circuit and control wiring with 1.5 TB PANEL
sqmm.
TB PANEL
23.00 All indicating light shall be LED type . TB PANEL
TB PANEL
Each vertical section of floor mounted panel shall have
24.00 independent base frame (75mm x 40mm) size made out of 3 TB PANEL
mm sheet steel (LT Panel & DG Panel).
TB PANEL
All the makes shall be as per Employer's approved make list
25.00 TB PANEL
only.
TB PANEL
Wherever only voltmeter & ammeter are required, the same
26.00 may be provided in combined meter suitable for both TB PANEL
parameter.
TB PANEL
SDB-EE-TB-03-J06, SDB-EE-TB-04-H09, SDB-EE-TB-08-
1.10 J19, SDB-EE-TB-09-H21, SDB-EE-TB10-H23, SDB-EE- TB PANEL
TB11-J27, SDB-EE-TB15-H36, SDB-EE-TB16-J39
TB PANEL
Comprisising of the following: TB PANEL
TB PANEL
a) Incomings: TB PANEL

VOLTEC ENERGY SYSTEMS Page 25


LABOUR RATE
TB PANEL
One (1) No.160Amps, 400 V, 36kA TPN MCCB, with
ON/OFF/TRIP/ indication lamp and TNC control switch,
under voltage & shunt trip release with microprocessor based TB PANEL
O/C, S/C & E/F protection etc. complete as required and as
per SLD.
TB PANEL
b) Metering & indication for incoming breakers: TB PANEL
TB PANEL
Incoming breaker shall be provided with TB PANEL
TB PANEL
One (1) No. Digital Multifunction meter with RS-485 port
i) suitable for measurement of voltage, currents and Frequency TB PANEL
(ELF 3259 of 'Conzerv' make or equivalent).
TB PANEL
One (1) set 3 Nos. CTs of ratio 150/5A,15VA, Class 1.0 as
ii) TB PANEL
required.
TB PANEL
iii) One set (3 Nos) phase indication lamp with backup SP MCB. TB PANEL
TB PANEL
Sufficient No. of contacts terminals shall be provided in the
Note: panel as required for necessary remote operation and TB PANEL
indications etc.
TB PANEL
c) BUS BARS: TB PANEL
TB PANEL
200Amp., 36kA, TPN+E, Copper Bus bar with colour coded,
heat shrinkable sleeves (with 100% neutral). Earth Bus shall TB PANEL
be of 32 x 6 mm copper.
TB PANEL
d) Outgoing: TB PANEL
TB PANEL
i) Three (3) Nos. 100 A, 36 KA, TPN MCCB. TB PANEL
TB PANEL
SDB-EE-TB-03-J06, SDB-EE-TB-04-H09, SDB-EE-TB-08-
J19, SDB-EE-TB-09-H21, SDB-EE-TB10-H23, SDB-EE-
8 Set TB PANEL
TB11-J27, SDB-EE-TB15-H36, SDB-EE-TB16-J39 described
as above (from a to d) and as per SLD
TB PANEL
SDB-EE-TB-01-H01, SDB-EE-TB-02-G04, SDB-EE-TB-05-
G13, SDB-EE-TB-06-J13, SDB-EE-TB07-G16, SDB-EE-
1.20 TB PANEL
TB12-G29, SDB-EE-TB13-J32, SDB-EE-TB14-G32, SDB-EE-
TB17-G41, SDB-EE-TB18-G44
TB PANEL
Comprisising of the following: TB PANEL
TB PANEL
a) Incomings: TB PANEL
TB PANEL
One (1) No.100Amps, 400 V, 36kA TPN MCCB, with
ON/OFF/TRIP/ indication lamp and TNC control switch,
under voltage & shunt trip release with microprocessor based TB PANEL
O/C, S/C & E/F protection etc. complete as required and as
per SLD.
TB PANEL
b) Metering & indication for incoming breakers: TB PANEL

VOLTEC ENERGY SYSTEMS Page 26


LABOUR RATE
TB PANEL
Incoming breaker shall be provided with TB PANEL
TB PANEL
One (1) No. Digital Multifunction meter with RS-485 port
i) suitable for measurement of voltage, currents and Frequency TB PANEL
(ELF 3259 of 'Conzerv' make or equivalent).
TB PANEL
One (1) set 3 Nos. CTs of ratio 100/5A,15VA, Class 1.0 as
ii) TB PANEL
required.
TB PANEL
iii) One set (3 Nos) phase indication lamp with backup SP MCB. TB PANEL
TB PANEL
Sufficient No. of contacts terminals shall be provided in the
Note: panel as required for necessary remote operation and TB PANEL
indications etc.
TB PANEL
c) BUS BARS: TB PANEL
TB PANEL
200Amp., 36kA, TPN+E, Copper Bus bar with colour coded,
heat shrinkable sleeves (with 100% neutral). Earth Bus shall TB PANEL
be of 32 x 6 mm copper.
TB PANEL
d) Outgoing: TB PANEL
TB PANEL
i) Three (3) Nos. 100 A, 36 KA, TPN MCCB. TB PANEL
TB PANEL
SDB-EE-TB-01-H01, SDB-EE-TB-02-G04, SDB-EE-TB-05-
G13, SDB-EE-TB-06-J13, SDB-EE-TB07-G16, SDB-EE-
TB12-G29, SDB-EE-TB13-J32, SDB-EE-TB14-G32, SDB-EE- 10 Set TB PANEL
TB17-G41, SDB-EE-TB18-G44 described as above (from a to
d) and as per SLD
TB PANEL
1.30 FINAL DISTRIBUTION BOARDS TB PANEL
TB PANEL
Design, manufacture, supply, installation (recessed/ surface),
testing and commissioning of following switch fuse Unit/
MCCB/MCB type distribution boards as per drawings &
specifications fabricated out of 14 SWG, CRCA sheet steel in
compartmentalised design as per specification and drawings. TB PANEL
The surface distribution boards shall be mounted on 50 x 50 x
6 MS angle frame work grounted to floor/ walls. The rate
includes the angle iron frame, support, painting, numbering,
earthing etc as required.
TB PANEL
1.3.1 DB-EE-TB01-G01, DB-EE-TB18-G44 : TB PANEL
TB PANEL
Incomer: TB PANEL
- 125A TPN MCCB. TB PANEL
TB PANEL
Busbar : TB PANEL
- 150A 4P Cu. Busbar TB PANEL
TB PANEL
Outgoing – (10KA) comprising TB PANEL
TB PANEL

VOLTEC ENERGY SYSTEMS Page 27


LABOUR RATE
Section-1 TB PANEL
- One (1) no. 32A 3 Phase RCD (100 mA). TB PANEL
TB PANEL
- Twenty Four (24) nos. 10A SP MCB. TB PANEL
TB PANEL
Section-2 Part-1 TB PANEL
TB PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). TB PANEL
TB PANEL
- Four (4) nos. 6A SP MCB. TB PANEL
TB PANEL
- Eight (8) nos. 16A SP MCB. TB PANEL
TB PANEL
- Three (3) nos. 16A TPN MCB. TB PANEL
TB PANEL
- One (1) nos. 32A TPN MCB. TB PANEL
TB PANEL
Section-2 Part-2 TB PANEL
TB PANEL
- One (1) no. 32A, 3 Phase, RCD (30 mA). TB PANEL
TB PANEL
- Nine (9) nos. 6A SP MCB. TB PANEL
TB PANEL
- Six (6) nos. 16A SP MCB. TB PANEL
TB PANEL
- Two (2) nos. 16A TPN MCB. TB PANEL
TB PANEL
- One (1) nos. 32A TPN MCB. TB PANEL
TB PANEL
DB-EE-TB01-G01, DB-EE-TB18-G44 as described above
- 2 Set TB PANEL
and as per DB chart.
DB-EE-TB02-G05, DB-EE-TB07-G17, DB-EE-TB12-G28,
TB PANEL
DB-EE-TB17-G40 :
TB PANEL
Incomer: TB PANEL
- 125A TPN MCCB. TB PANEL
TB PANEL
Busbar : TB PANEL
- 150A 4P Cu. Busbar TB PANEL
TB PANEL
Outgoing – (10KA) comprising TB PANEL
TB PANEL
Section-1 TB PANEL
- One (1) no. 32A 3 Phase RCD (100 mA). TB PANEL
TB PANEL
- Twenty Four (24) nos. 10A SP MCB. TB PANEL
TB PANEL
Section-2 Part-1 TB PANEL
TB PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). TB PANEL
TB PANEL

VOLTEC ENERGY SYSTEMS Page 28


LABOUR RATE
- Four (4) nos. 6A SP MCB. TB PANEL
TB PANEL
- Eight (8) nos. 16A SP MCB. TB PANEL
TB PANEL
- Three (3) nos. 16A TPN MCB. TB PANEL
TB PANEL
- One (1) no. 32A TPN MCB. TB PANEL
TB PANEL
Section-2 Part-2 TB PANEL
TB PANEL
- One (1) no. 32A, 3 Phase, RCD (30 mA). TB PANEL
TB PANEL
- Eight (8) nos. 6A SP MCB. TB PANEL
TB PANEL
- Seven (7) nos. 16A SP MCB. TB PANEL
TB PANEL
- Two (2) nos. 16A TPN MCB. TB PANEL
TB PANEL
- One (1) no. 32A TPN MCB. TB PANEL
TB PANEL
DB-EE-TB02-G05, DB-EE-TB07-G17, DB-EE-TB12-G28,
- 4 Set TB PANEL
DB-EE-TB17-G40 as described above and as per DB chart.
TB PANEL
1.3.3 DB-EE-TB03-J07 : TB PANEL
TB PANEL
Incomer: TB PANEL
TB PANEL
- 125A TPN MCCB. TB PANEL
TB PANEL
Busbar : TB PANEL
TB PANEL
- 150A 4P Cu. Busbar TB PANEL
TB PANEL
Outgoing – (10KA) comprising TB PANEL
TB PANEL
Section-1 TB PANEL
TB PANEL
- One (1) no. 32A 3 Phase RCD (100 mA). TB PANEL
TB PANEL
- Twenty Four (24) nos. 10A SP MCB. TB PANEL
TB PANEL
Section-2 Part-1 TB PANEL
TB PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). TB PANEL
TB PANEL
- Five (5) nos. 6A SP MCB. TB PANEL
TB PANEL
- Seven (7) nos. 16A SP MCB. TB PANEL
TB PANEL
- Three (3) nos. 16A TPN MCB. TB PANEL

VOLTEC ENERGY SYSTEMS Page 29


LABOUR RATE
TB PANEL
- One (1) no. 32A TPN MCB. TB PANEL
TB PANEL
Section-2 Part-2 TB PANEL
TB PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). TB PANEL
TB PANEL
- Eleven (11) nos. 6A SP MCB. TB PANEL
TB PANEL
- Thirteen (13) nos. 16A SP MCB. TB PANEL
TB PANEL
- Two (2) nos. 16A TPN MCB. TB PANEL
TB PANEL
- One (1) no. 32A TPN MCB. TB PANEL
TB PANEL
- DB-EE-TB03-J07 as described above and as per DB chart. 1 Set TB PANEL
TB PANEL
1.3.4 DB-EE-TB04-H10, DB-EE-TB015-H35 : TB PANEL
TB PANEL
Incomer: TB PANEL
TB PANEL
- 125A TPN MCB. TB PANEL
TB PANEL
Busbar : TB PANEL
TB PANEL
- 150A 4P Cu. Busbar TB PANEL
TB PANEL
Outgoing – (10KA) comprising TB PANEL
TB PANEL
Section-1 TB PANEL
TB PANEL
- One (1) no. 32A 3 Phase RCD (100 mA). TB PANEL
TB PANEL
- Twenty Four (24) nos. 10A SP MCB. TB PANEL
TB PANEL
Section-2 Part-1 TB PANEL
TB PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). TB PANEL
TB PANEL
- Three (3) nos. 6A SP MCB. TB PANEL
TB PANEL
- Nine (9) nos. 16A SP MCB. TB PANEL
TB PANEL
- Three (3) nos. 16A TPN MCB. TB PANEL
TB PANEL
- One (1) no. 32A TPN MCB. TB PANEL
TB PANEL
Section-2 Part-2 TB PANEL
TB PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). TB PANEL

VOLTEC ENERGY SYSTEMS Page 30


LABOUR RATE
TB PANEL
- Thirteen (13) nos. 6A SP MCB. TB PANEL
TB PANEL
- Fourteen (14) nos. 16A SP MCB. TB PANEL
TB PANEL
- Two (2) nos. 16A TPN MCB. TB PANEL
TB PANEL
- One (1) no. 32A TPN MCB. TB PANEL
TB PANEL
DB-EE-TB04-H10, DB-EE-TB015-H35 as described above
- 2 Set TB PANEL
and as per DB chart.
TB PANEL
1.3.5 DB-EE-TB05-G12, DB-EE-TB14-G33 : TB PANEL
TB PANEL
Incomer: TB PANEL
TB PANEL
- 125A TP MCCB. TB PANEL
TB PANEL
Busbar : TB PANEL
TB PANEL
- 150A 4P Cu. Busbar TB PANEL
TB PANEL
Outgoing – (10KA) comprising TB PANEL
TB PANEL
Section-1 TB PANEL
TB PANEL
- One (1) no. 32A 3 Phase RCD (100 mA). TB PANEL
TB PANEL
- Twenty Four (24) nos. 10A SP MCB. TB PANEL
TB PANEL
Section-2 Part-1 TB PANEL
TB PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). TB PANEL
TB PANEL
- Four (4) nos. 6A SP MCB. TB PANEL
TB PANEL
- Eight (8) nos. 16A SP MCB. TB PANEL
TB PANEL
- Three (3) nos. 16A TPN MCB. TB PANEL
TB PANEL
- One (1) no. 32A TPN MCB. TB PANEL
TB PANEL
Section-2 Part-2 TB PANEL
TB PANEL
- One (1) no. 32A, 3 Phase, RCD (30 mA). TB PANEL
TB PANEL
- Four (4) nos. 6A SP MCB. TB PANEL
TB PANEL
- Seven (7) nos. 16A SP MCB. TB PANEL
TB PANEL

VOLTEC ENERGY SYSTEMS Page 31


LABOUR RATE
- One (1) no. 16A TPN MCB. TB PANEL
TB PANEL
- One (1) no. 32A TPN MCB. TB PANEL
TB PANEL
DB-EE-TB05-G12, DB-EE-TB14-G33 as described above
- 2 Set TB PANEL
and as per DB chart.
TB PANEL
1.3.6 DB-EE-TB06-J14, DB-EE-TB13-J31 : TB PANEL
TB PANEL
Incomer: TB PANEL
TB PANEL
- 125A TPN MCCB. TB PANEL
TB PANEL
Busbar : TB PANEL
TB PANEL
- 150A 4P Cu. Busbar TB PANEL
TB PANEL
Outgoing – (10KA) comprising TB PANEL
TB PANEL
Section-1 TB PANEL
TB PANEL
- One (1) no. 32A 3 Phase RCD (100 mA). TB PANEL
TB PANEL
- Twenty Seven (27) nos. 10A SP MCB. TB PANEL
TB PANEL
Section-2 Part-1 TB PANEL
TB PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). TB PANEL
TB PANEL
- Four (4) nos. 6A SP MCB. TB PANEL
TB PANEL
- Eight (8) nos. 16A SP MCB. TB PANEL
TB PANEL
- Four (4) nos. 16A TPN MCB. TB PANEL
TB PANEL
Section-2 Part-2 TB PANEL
TB PANEL
- One (1) no. 40A, 3 Phase, RCD (30 mA). TB PANEL
TB PANEL
- Eleven (11) nos. 6A SP MCB. TB PANEL
TB PANEL
- Seven (7) nos. 16A SP MCB. TB PANEL
TB PANEL
Two (2) nos. 32A TPN MCB. TB PANEL
TB PANEL
DB-EE-TB06-J14, DB-EE-TB13-J31 as described above and
- 2 Set TB PANEL
as per DB chart.
1.3.7 DB-EE-TB08-J18, DB-EE-TB11-J27, DB-EE-TB16-J38 : TB PANEL
TB PANEL
Incomer: TB PANEL
- 160A TPN MCCB. TB PANEL

VOLTEC ENERGY SYSTEMS Page 32


LABOUR RATE
TB PANEL
Busbar : TB PANEL
- 200A 4P Cu. Busbar TB PANEL
TB PANEL
Outgoing – (10KA) comprising TB PANEL
TB PANEL
Section-1 TB PANEL
- One (1) no. 32A 3 Phase RCD (100 mA). TB PANEL
TB PANEL
- Twenty Four (24) nos. 10A SP MCB. TB PANEL
TB PANEL
Section-2 Part-1 TB PANEL
TB PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). TB PANEL
TB PANEL
- Five (5) nos. 6A SP MCB. TB PANEL
TB PANEL
- Seven (7) nos. 16A SP MCB. TB PANEL
TB PANEL
- Three (3) nos. 16A TPN MCB. TB PANEL
TB PANEL
- One (1) nos. 32A TPN MCB. TB PANEL
TB PANEL
Section-2 Part-2 TB PANEL
TB PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). TB PANEL
TB PANEL
- Eleven (11) nos. 6A SP MCB. TB PANEL
TB PANEL
- Thirteen (13) nos. 16A SP MCB. TB PANEL
TB PANEL
- Two (2) nos. 16A TPN MCB. TB PANEL
TB PANEL
- One (1) nos. 32A TPN MCB. TB PANEL
TB PANEL
DB-EE-TB08-J18, DB-EE-TB11-J27, DB-EE-TB16-J38 as
- 3 Set TB PANEL
described above and as per DB chart.
TB PANEL
1.3.8 DB-EE-TB09-H22, DB-EE-TB10-H23, DB-EE-TB12-G28 : TB PANEL
TB PANEL
Incomer: TB PANEL
- 125A TPN MCCB. TB PANEL
TB PANEL
Busbar : TB PANEL
- 150A 4P Cu. Busbar TB PANEL
TB PANEL
Outgoing – (10KA) comprising TB PANEL
TB PANEL
Section-1 TB PANEL
- One (1) no. 32A 3 Phase RCD (100 mA). TB PANEL

VOLTEC ENERGY SYSTEMS Page 33


LABOUR RATE
TB PANEL
- Twenty Four (24) nos. 10A SP MCB. TB PANEL
TB PANEL
Section-2 Part-1 TB PANEL
TB PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). TB PANEL
TB PANEL
- Three (3) nos. 6A SP MCB. TB PANEL
TB PANEL
- Nine (9) nos. 16A SP MCB. TB PANEL
TB PANEL
- Three (3) nos. 16A TPN MCB. TB PANEL
TB PANEL
- One (1) no. 32A TPN MCB. TB PANEL
TB PANEL
Section-2 Part-2 TB PANEL
TB PANEL
- Twelve (12) nos. 6A SP MCB. TB PANEL
TB PANEL
- Twelve (12) nos. 16A SP MCB. TB PANEL
TB PANEL
- Two (2) nos. 16A TPN MCB. TB PANEL
TB PANEL
- One (1) no. 32A TPN MCB. TB PANEL
TB PANEL
DB-EE-TB09-H22, DB-EE-TB10-H23, DB-EE-TB12-G28 as
- 3 Set TB PANEL
described above and as per DB chart.
TB PANEL
TOTAL OF LV SWITCHGEAR PANELS & DISTRIBUTION
TB PANEL
BOARDS CARRIED OVER TO SUMMARY
2.00 CABLES, SUB MAINS & CABLE TRAYS : TB CAB
TB CAB
2.10 Cables in Under Ground Installations : TB CAB
TB CAB
Supply, installation, testing and commissioning of following
sizes of PVC sheathed, XLPE insulated copper conductor
power/multicore control, armoured, Multi-strand cable of 1.1
KV grade in ground including digging the trench, laying the TB CAB
cable with sand and brick covering, back filling reaming etc
as required, as per specfications and as per directions of
Engineer-in-charge.
TB CAB
Copper Conductor, Armoured XLPE Cables
2.1.1 TB CAB
(PVC/SWA/XLPE) :
TB CAB
a) 4 core 150 sqmm 10 RM TB CAB
b) 4 core 120 sqmm 10 RM TB CAB
c) 4 core 95 sqmm 10 RM TB CAB
d) 4 core 70 sqmm 10 RM TB CAB
e) 4 core 50 sqmm 10 RM TB CAB
f) 4 core 35 sqmm 10 RM TB CAB
g) 4 core 25 sqmm 10 RM TB CAB

VOLTEC ENERGY SYSTEMS Page 34


LABOUR RATE
TB CAB
2.20 Cables on Racks / Pipes / Ducts / Wireways/Cable Trays : TB CAB
TB CAB
Supply, installation, testing and commissioning of following
sizes of PVC sheathed, XLPE insulated, copper conductor,
power/multicore, control, armoured, Multi-stranded cable of
1.1 KV grade on surface of wall or in existing cable tray TB CAB
/masonary ducts/hume pipe with fixing hardware etc as
required, as per specifications and as per direction of
Engineer-in-charge.
TB CAB
2.2.1 Copper Conductor Armoured Cables : TB CAB
TB CAB
a) 4 core 150 sqmm 10 RM TB CAB
b) 4 core 120 sqmm 50 RM TB CAB
c) 4 core 95 sqmm 10 RM TB CAB
d) 4 core 70 sqmm 10 RM TB CAB
e) 4 core 50 sqmm 10 RM TB CAB
f) 4 core 35 sqmm 10 RM TB CAB
g) 4 core 25 sqmm 100 RM TB CAB
h) 4 core 16 sqmm 250 RM TB CAB
i) 4 core 10 sqmm 900 RM TB CAB
j) 4 core 6 sqmm 450 RM TB CAB
k) 4 core 4 sqmm 1,600 RM TB CAB
l) 3 core 25 sqmm 10 RM TB CAB
m) 3 core 16 sqmm 10 RM TB CAB
n) 3 core 10 sqmm 10 RM TB CAB
o) 3 core 6 sqmm 10 RM TB CAB
p) 3 core 4 sqmm 10 RM TB CAB
q) 2 core 6 sqmm 10 RM TB CAB
r) 2 core 4 sqmm 10 RM TB CAB
2.2.2 Copper Conductor Armoured Control Cables : TB CAB
TB CAB
a) 14 C 1.5 Sqmm PVC cable 10 RM TB CAB
b) 10 C 1.5 Sqmm PVC cable 10 RM TB CAB
c) 9 C 1.5 Sqmm PVC cable 10 RM TB CAB
d) 7 C 1.5 Sqmm PVC cable 10 RM TB CAB
e) 5 C 1.5 Sqmm PVC cable 10 RM TB CAB
f) 3 C 1.5 Sqmm PVC cable 10 RM TB CAB
TB CAB
2.30 Cable Termination : TB TERM
TB TERM
Supply and making end termination with brass double
compression glands for the following XLPE insulated PVC
sheathed, 1100 V grade, Multi-strand copper conductor cable
including cost of crimping lugs/ferrules, double compression TB TERM
glands, solder, cable sockets, insulation tap etc complete as
required, as per specifications and as per direction of
Engineer-in-charge.
TB TERM
2.3.1 Copper conductor armoured cables : TB TERM
TB TERM
a) 4 core 150 sqmm 2 Nos. TB TERM

VOLTEC ENERGY SYSTEMS Page 35


LABOUR RATE
b) 4 core 120 sqmm 2 Nos. TB TERM
c) 4 core 95 sqmm 2 Nos. TB TERM
d) 4 core 70 sqmm 2 Nos. TB TERM
e) 4 core 50 sqmm 2 Nos. TB TERM
f) 4 core 35 sqmm 2 Nos. TB TERM
g) 4 core 25 sqmm 6 Nos. TB TERM
h) 4 core 16 sqmm 30 Nos. TB TERM
i) 4 core 10 sqmm 84 Nos. TB TERM
j) 4 core 6 sqmm 60 Nos. TB TERM
k) 4 core 4 sqmm 156 Nos. TB TERM
l) 3 core 25 sqmm 2 Nos. TB TERM
m) 3 core 16 sqmm 2 Nos. TB TERM
n) 3 core 10 sqmm 2 Nos. TB TERM
o) 3 core 6 sqmm 2 Nos. TB TERM
p) 3 core 4 sqmm 2 Nos. TB TERM
q) 2 core 6 sqmm 2 Nos. TB TERM
r) 2 core 4 sqmm 2 Nos. TB TERM
TB TERM
2.3.2 Copper Conductor PVC Insulated Armoured Control Cables : TB TERM
(Single Compression Glands suitable for following armoured
TB TERM
cables)
TB TERM
a) 14 C x 1.5 Sqmm 2 Nos. TB TERM
b) 10 C x 1.5 Sqmm 2 Nos. TB TERM
c) 9 C x 1.5 Sqmm 2 Nos. TB TERM
d) 7 C x 1.5 Sqmm 2 Nos. TB TERM
e) 5 C x 1.5 Sqmm 2 Nos. TB TERM
f) 3 C x 1.5 Sqmm 2 Nos. TB TERM
TB TERM

The cable quantities given are approximate and to cover


various sizes. The contractor shall measure the cables
Notes: TB TERM
required and procurement order shall be placed accordingly.
The quantities shall be confirmed before start of work.

TB CAB
Supply, installation, testing and commissioning of 1.1 KV
grade, Multicore, copper conductor, LSZH outer sheathed,
CWZ fire resistant cable (in compliance with BS : 6387) of
2.40 following sizes on surfae of wall/existing cable TB CAB
trays/Mesonary Hume pipe/Duct/Trenches etc., with fixing
hardware etc. as required as per specifications and as per
direction of Engineer-in-charge.
TB CAB
a) 4 C x 185 Sqm, CWZ Cable 5 RM TB CAB
b) 4 C x 150 Sqm, CWZ Cable 5 RM TB CAB
c) 4 C x 120 Sqm, CWZ Cable 5 RM TB CAB
d) 4 C x 95 Sqm, CWZ Cable 5 RM TB CAB
e) 4 C x 70 Sqm, CWZ Cable 5 RM TB CAB
f) 4 C x 50 Sqm, CWZ Cable 5 RM TB CAB
g) 4 C x 35 Sqm, CWZ Cable 5 RM TB CAB
h) 4 C x 25 Sqm, CWZ Cable 5 RM TB CAB
i) 4 C x 16 Sqm, CWZ Cable 5 RM TB CAB

VOLTEC ENERGY SYSTEMS Page 36


LABOUR RATE
j) 4 C x 10 Sqm, CWZ Cable 5 RM TB CAB
k) 4 C x 6 Sqm, CWZ Cable 5 RM TB CAB
l) 4 C x 4 Sqm, CWZ Cable 5 RM TB CAB
m) 4 C x 2.5 Sqm, CWZ Cable 5 RM TB CAB
TB CAB
2.50 Cable Trays : TB TRAY
TB TRAY

Supply and installation of ladder type/perforated type cable


trays of the following sizes fabricated out of perforated hot dip
galvanised MS sheets of minimum 2.0 mm thick to be
installed horizontally or vertically. The cable tray shall be
complete including cost of supporting Steel/Hangers, bends, TB TRAY
elbows, cross, tees, reducers etc as per drawings/site
condition and rate shall include cost of anchor fasteners,
screws, nuts, bolts and misc. other fixing hardware etc as
required, as per specifications and approved Shop drawings.

TB TRAY
The cable tray shall be factory built. Bidder shall include in his
price, required numbers of Tees, Crosses, Bends, Elbows etc
Notes: TB TRAY
as required as per actual site conditions. Bidder may refer to
the drawings for estimation purpose.
TB TRAY
2.5.1 Ladder Type Cable tray : TB TRAY
TB TRAY
a) 900 mm x 75 mm x 2.0 mm 5 RM TB TRAY
b) 750 mm x 75 mm x 2.0 mm 5 RM TB TRAY
c) 600 mm x 75 mm x 2.0 mm 5 RM TB TRAY
d) 450 mm x 75 mm x 2.0 mm 5 RM TB TRAY
e) 300 mm x 75 mm x 2.0 mm 5 RM TB TRAY
f) 225 mm x 75 mm x 2.0 mm 5 RM TB TRAY
g) 100 mm x 75 mm x 2.0 mm 5 RM TB TRAY
TB TRAY
2.5.2 Perforated Type Cable Tray : TB TRAY
TB TRAY
a) 750 mm x 75 mm x 2.0 mm 10 RM TB TRAY
b) 600 mm x 75 mm x 2.0 mm 10 RM TB TRAY
c) 500 mm x 75 mm x 2.0 mm 10 RM TB TRAY
d) 400 mm x 75 mm x 2.0 mm 10 RM TB TRAY
e) 300 mm x 50 mm x 2.0 mm 10 RM TB TRAY
f) 250 mm x 50 mm x 2.0 mm 10 RM TB TRAY
g) 200 mm x 75 mm x 2.0 mm 800 RM TB TRAY
h) 150 mm x 75 mm x 2.0 mm 10 RM TB TRAY
i) 100 mm x 75 mm x 2.0 mm 10 RM TB TRAY
TB TRAY
2.5.3 Fibreglass Ladder Type Cable Tray : TB TRAY
TB TRAY
Supply & Installation of Ladder type Cable tray of following
sizes. The Cable Tray shall be complete including the cost of
TB TRAY
Anchor fasteners, Hardware, supporting structure etc. as
required and as per specifications and approved drawing :
a) 600 mm wide 5 RM TB TRAY
b) 450 mm wide 5 RM TB TRAY
c) 300 mm wide 5 RM TB TRAY

VOLTEC ENERGY SYSTEMS Page 37


LABOUR RATE
d) 225 mm wide 5 RM TB TRAY
e) 100 mm wide 5 RM TB TRAY
TB TRAY
2.60 Misc. Works Relating to Cabling: TB PIPE
TB PIPE
2.6.1 GI Pipe Installation : TB PIPE
TB PIPE
Supply and installation of following sizes of `A' class GI pipe
for cable sleeves in recess/ on surface/Ground complete with
all accessories pull boxes where ever required, G.I. fish wire,
fixing hardware etc. including the chasing of wall/floor, and TB PIPE
plastering the chased portion, digging the trench and back
filling, making good the damages, sealing of pipe entry etc as
required.
TB PIPE
a) 25 mm dia 10 RM TB PIPE
b) 32 mm dia 10 RM TB PIPE
c) 40 mm dia 10 RM TB PIPE
d) 50 mm dia 10 RM TB PIPE
e) 80 mm dia 10 RM TB PIPE
f) 100 mm dia 10 RM TB PIPE
g) 150 mm dia 10 RM TB PIPE
TB PIPE
2.6.2 Flexible Conduits Installation : TB PW
TB PW
Supply and installation of following sizes of GI flexible
conduits with all accessories including fixing nipples,
TB PW
couplings and fixing hardware etc as required and as per
specifications.
TB PW
2.6.2.1
GI flexible conduits : TB PW
a) 20 mm dia 100 RM TB PW
b) 25 mm dia 100 RM TB PW
c) 40 mm dia 100 RM TB PW
d) 50 mm dia 100 RM TB PW
TOTAL OF CABLES, SUB MAINS, CABLE TRAYS
TB PW
CARRIED OVER TO SUMMARY
3.00 WIRING : TB PW
TB PW
3.10 Point Wiring : TB PW
TB PW
The rates for point wiring shall include the circuit wiring. TB PW
TB PW
Circuit wiring means the wiring from DB / Dimmer panel to the
TB PW
first point of circuit through control switch.
TB PW
Circuit wiring and subsequent looping shall be done with 2.5
TB PW
Sqmm, 1100V grade LSZH insulated stranded, copper wires.
TB PW

VOLTEC ENERGY SYSTEMS Page 38


LABOUR RATE
The rates of point wiring shall include supply, installation,
testing & commissioning of MS conduit with accessories, GI
Boxes and required GI flexible conduits with accessories up
TB PW
to the Point, LSZH insulated, stranded, Cu. Wire etc. as
required and as per specification, Tender Drawing and
direction of Engineer-in-charge.
TB PW
Where the light points are directly controlled from DB (without
any local control switches), the quoted rates shall not include TB PW
the cost of MCBs etc. in the point wiring.
TB PW
The rates of point wiring shall include earthing of each light,
fan, switches, switch plates, boxes and other non current
TB PW
carrying metallic part with 2.5 Sqm. Stranded copper, LSZH
insulated, stranded, copper wire.
TB PW
3.1.1 Light Points controlled by switch : TB PW
TB PW
a) Single/ First light point con-trolled by a 5Amps switch. 341 No. TB PW
TB PW
b) Same as above but loop point 979 No. TB PW
TB PW
3.1.2 Light Points controlled directly from DB TB PW
TB PW
i. Single/ First Point Controlled directly by MCB in DB 4 Nos. TB PW
TB PW
ii. Same as above but loop point. 35 Nos. TB PW
TB PW
3.1.3 Light points controlled by Two Way Switch : TB PW
TB PW
One / first light point controlled by two nos. two way 5 Amps.
i) 86 Nos. TB PW
switch.
TB PW
ii) Same as above but loop point. 277 Nos. TB PW
TB PW
3.1.4 Light points controlled by Twilight Switch : TB PW
TB PW
i) One / first light point controlled by Twilight switch. 18 Nos. TB PW
TB PW
ii) Same as above but loop point. 154 Nos. TB PW
TB PW
3.1.5 Light points controlled by Push Buttons : TB PW
TB PW
i) Three light points controlled by One Push Button. 1 Nos. TB PW
TB PW
ii) Four light points controlled by One Push Button. 2 Nos. TB PW
TB PW
iii) Five light points controlled by One Push Button. 2 Nos. TB PW
TB PW
iv) Six light points controlled by One Push Button. 6 Nos. TB PW
TB PW
v) Eight light points controlled by One Push Button. 4 Nos. TB PW
TB PW

VOLTEC ENERGY SYSTEMS Page 39


LABOUR RATE
vi) Five light points controlled by Two Push Buttons. 3 Nos. TB PW
TB PW
vii) Five light points controlled by Three Push Buttons. 4 Nos. TB PW
TB PW
viii) Fifteen light points controlled by Three Push Buttons. 4 Nos. TB PW
TB PW
ix) Sixteen light points controlled by Three Push Buttons. 4 Nos. TB PW
TB PW
ix) Twenty light points controlled by Three Push Buttons. 4 Nos. TB PW
TB PW
3.1.6 Presence Sensor : TB PW
TB PW
Wiring from Presence Sensor to the DB/SwitchBoard/Light
fixtures, including providing Presence Sensor as required and
a) as per approved shop drawing (wiring from DB to light points 4 Nos. TB PW
has already been included in subheads 8.1.1, 8.1.2, 8.1.3,
8.1.4, 8.1.5 above and not to be considered here).
TB PW
3.1.7 6A Socket Points : TB PW
TB PW
Wiring for 6A, BS, switched socket outlet including providing
a) 6A, BS, switched, socket outlet as per specification and 323 Point TB PW
approved shop drawing.
TB PW
3.1.8 FCU Points controlled by 6A Switch : TB PW
TB PW
One / first light point controlled by 6A, BS, switched socket
i) 94 Nos. TB PW
outlet including providing 6A, BS, switched, socket outlet.
TB PW
ii) Same as above but loop point. 50 Nos. TB PW
TB PW
3.20 Power Socket Wiring : TB PW
TB PW
Power Socket Wiring shall include supply, installation, testing
and commissioning of wiring of following points, including,
providing conduits of suitable size, its accessories/Hardware,
0.00 TB PW
Junction Boxes, LSZH wires, termination of wires, switches,
socket outlets, Plug tops etc. as required and as per
specification.
TB PW
Wiring for 1 No. BS, 16A, switched socket outlet with 4.0
Sqmm LSZH insulated stranded copper conductor wires in
recessed/surface black enameled MS conduit including
cutting/filling chases, providing conduit with conduit
3.2.1 accessories, saddles, supply and fixing of 1 No. BS, 16A, 1 Point TB PW
switched outlet with internal wiring in G.I. box, earthing of 3rd
pin with LSZH insulated, green colour 2.5 Sq.mm copper
wire, complete with all accessories as required and as per
approved shop drawing.
TB PW

VOLTEC ENERGY SYSTEMS Page 40


LABOUR RATE
Wiring for 2 Nos. BS, 16A, switched outlet with 4.0 Sqmm
LSZH insulated stranded copper conductor wires in
recessed/surface black enameled MS conduit including
cutting/filling chases, providing conduit with conduit
3.2.2 accessories, saddles, supply and fixing of 2 Nos. BS, 16A, 6 Point TB PW
switched outlet with internal wiring in G.I. box, earthing of 3rd
pin with LSZH insulated, green colour 2.5 Sq.mm copper
wire, complete with all accessories as required and as per
approved shop drawing.
Wiring for 4 Nos. BS, 16A, switched outlet with 4.0 Sqmm
LSZH insulated stranded copper conductor wires in
recessed/surface black enameled MS conduit including
cutting/filling chases, providing conduit with conduit
3.2.3 accessories, saddles, supply and fixing of 4 Nos. BS, 16A, 83 Point TB PW
switched outlet with internal wiring in G.I. box, earthing of 3rd
pin with LSZH insulated, green colour 2.5 Sq.mm copper
wire, complete with all accessories as required and as per
approved shop drawing.
TB PW
Wiring for 5 Nos. BS, 16A, switched outlet with 4.0 Sqmm
LSZH insulated stranded copper conductor wires in
recessed/surface black enameled MS conduit including
cutting/filling chases, providing conduit with conduit
3.2.4 accessories, saddles, supply and fixing of 5 Nos. BS, 16A, 11 Point TB PW
switched outlet with internal wiring in G.I. box, earthing of 3rd
pin with LSZH insulated, green colour 2.5 Sq.mm copper
wire, complete with all accessories as required and as per
approved shop drawing.
TB PW

Wiring for 2 Nos. BS, 16A, switched outlets and 1 No. 16A
DP Isolators in IP-65 enclosure with 4.0 Sqmm LSZH
insulated stranded copper conductor wires in
recessed/surface black enameled MS conduit including
cutting/filling chases, providing conduit with conduit
3.2.5 1 Point TB PW
accessories, saddles, supply and fixing of 2 No. BS, 16A,
switched outlets and 1 No. 16A DP Isolator in IP-65 enclosure
with internal wiring, earthing of 3rd pin with LSZH insulated,
green colour 2.5 Sq.mm copper wire, complete with all
accessories as required and as per approved shop drawing.

TB PW
Wiring for 2 Nos. BS, 16A, switched outlets and 2 Nos. 16A
DP Isolators in IP-65 enclosure with 4.0 Sqmm LSZH
insulated stranded copper conductor wires in
recessed/surface black enameled MS conduit including
cutting/filling chases, providing conduit with conduit
3.2.6 accessories, saddles, supply and fixing of 2 Nos. BS, 16A, 5 Point TB PW
switched outlets and 2 Nos. 16A DP Isolators in IP-65
enclosure with internal wiring, earthing of 3rd pin with LSZH
insulated, green colour 2.5 Sq.mm copper wire, complete with
all accessories as required and as per approved shop
drawing.
TB PW

VOLTEC ENERGY SYSTEMS Page 41


LABOUR RATE

Wiring for 4 Nos. BS, 16A, switched outlets and 1 No. 16A
DP Isolator in IP-65 enclosure with 4.0 Sqmm LSZH insulated
stranded copper conductor wires in recessed/surface black
enameled MS conduit including cutting/filling chases,
providing conduit with conduit accessories, saddles, supply
3.2.7 5 Point TB PW
and fixing of 4 Nos. BS, 16A, switched outlets and 1 No. 16A
DP Isolator in IP-65 enclosure with internal wiring, earthing of
3rd pin with LSZH insulated, green colour 2.5 Sq.mm copper
wire, complete with all accessories as required and as per
approved shop drawing.

TB PW
Wiring for 2 Nos. 16A DP Isolators in IP-65 enclosure with 4.0
Sqmm LSZH insulated stranded copper conductor wires in
recessed/surface black enameled MS conduit including
cutting/filling chases, providing conduit with conduit
3.2.8 accessories, saddles, supply and fixing of 2 Nos. 16A DP 18 Point TB PW
Isolator in IP-65 enclosure with internal wiring, earthing with
LSZH insulated, green colour 2.5 Sq.mm copper wire,
complete with all accessories as required and as per
approved shop drawing.
TB PW
Wiring for 3 Nos. 16A DP Isolators in IP-65 enclosure with 4.0
Sqmm LSZH insulated stranded copper conductor wires in
recessed/surface black enameled MS conduit including
cutting/filling chases, providing conduit with conduit
3.2.9 accessories, saddles, supply and fixing of 3 Nos. 16A DP 20 Point TB PW
Isolator in IP-65 enclosure with internal wiring, earthing with
LSZH insulated, green colour 2.5 Sq.mm copper wire,
complete with all accessories as required and as per
approved shop drawing.
TB PW
Wiring for 5 Nos. 16A DP Isolators in IP-65 enclosure with 4.0
Sqmm LSZH insulated stranded copper conductor wires in
recessed/surface black enameled MS conduit including
cutting/filling chases, providing conduit with conduit
3.2.10 accessories, saddles, supply and fixing of 5 Nos. 16A DP 4 Point TB PW
Isolator in IP-65 enclosure with internal wiring, earthing with
LSZH insulated, green colour 2.5 Sq.mm copper wire,
complete with all accessories as required and as per
approved shop drawing.
TB PW
Wiring for 1 No. Power & Data Pillar (consisting of 1 No. 6A
BS socket with 1 No. 6A Switch and 1 No. RJ-45 Data outlet
in IP-65 enclosure) and 1 No. Power & TV Pillar (consisting of
1 No. 6A BS socket with 1 No. 6A Switch and 1 No. RJ-11 TV
outlet in IP-65 enclosure) with 2.5 Sqmm LSZH insulated
stranded copper conductor wires in recessed/surface black
enameled MS conduit including cutting/filling chases,
3.2.11 providing conduit with conduit accessories, saddles, supply 14 Point TB PW
and fixing of 1 No. 6A BS socket with 1 No. 6A Switch and 1
No. RJ-45 Data outlet in IP-65 enclosure and 1 No. Power &
TV Pillar, consisting of 1 No. 6A BS socket with 1 No. 6A
Switch and 1 No. RJ-11 TV outlet in IP-65 enclosure, with
internal wiring, earthing with LSZH insulated, green colour 2.5
Sq.mm copper wire, complete with all accessories as
required.
TB PW

VOLTEC ENERGY SYSTEMS Page 42


LABOUR RATE

Wiring for 1 No. Floor LV tank consisting of 4 Nos. 6A BS


switched socket and 2 Nos. RJ-45 Data Outlets in IP-65
enclosure, with 2.5 Sqmm LSZH insulated stranded copper
conductor wires in recessed/surface black enameled MS
conduit including cutting/filling chases, providing conduit with
3.2.12 206 Nos. TB PW
conduit accessories, saddles, supply and fixing of 1 No. Floor
LV tank consisting of 4 Nos. 6A BS switched socket and 2
Nos. RJ-45 Data outlets in IP-65 enclosure, with internal
wiring, earthing with LSZH insulated, green colour 2.5 Sq.mm
copper wire, complete with all accessories as required.

3.30 CEE INDUSTRIAL SWITCHED SOCKETS TB PW


TB PW
Supply, installation, testing and commissioning of single
phase/three phase, CEE, switched, industrial type plug and
socket outlet in IP-44 enclosure including termination,
3.3.1 earthing etc. in surface/recessed mounting as required, as TB PW
per specifications and approved shop drawings
(Cabling/Conduiting & wiring shall be paid separately under
different items).
TB PW
32A, 3P+N+E, CEE, switched socket outlet with plug top (IP-
a) 18 No. TB PW
44).
TB PW
3.40 ISOLATORS TB DB
TB DB
Supply, installation, testing and commissioning of isolators in
IP-65 enclosures complete with termination in TB DB
surface/recessed mounting as required.
TB DB
a) 16A Four pole isolator 78 Nos. TB DB
TB DB
b) 32A Four pole isolator 18 Nos. TB DB
TB DB
3.50 M.S. Black Conduits : TB PW
TB PW
Supply and installation of following size of MS conduit pipe in
recess or on surface including all accessories MS/CI
pull/junction boxes, GI fish wire, fixing hardware etc
. TB PW
including chasing the walls/floor and plastering the chased
portion and making good the damages etc, complete as
required and as per specifications.
TB PW
a) 20 mm dia 20 RM TB PW
b) 25 mm dia 20 RM TB PW
c) 32 mm dia 20 RM TB PW
d) 40 mm dia 20 RM TB PW
e) 50 mm dia 20 RM TB PW
TB PW
3.60 Sub-mains Wiring : TB PW
TB PW
Supply and drawing of following sizes of LSZH insulated,
stranded, copper conductor wires of 650/1100 Volts grade in
TB PW
existing conduit pipe /wire ways including connection
/terminations etc as required.
TB PW
a) 2 x 1.5 Sqmm + 1 No. 1.5 Sqmm Copper earth wire 20 RM TB PW

VOLTEC ENERGY SYSTEMS Page 43


LABOUR RATE
b) 2 x 2.5 Sqmm + 1 No. 1.5 Sqmm Copper earth wire 20 RM TB PW
c) 2 x 4.0 Sqmm + 1 No. 2.5 Sqmm Copper earth wire. 20 RM TB PW
d) 2 x 6.0 Sqmm + 1 No. 2.5 Sqmm Copper earth wire 20 RM TB PW
e) 4 x 4.0 Sqmm + 1 No. 2.5 Sqmm Copper earth wire 20 RM TB PW
f) 4 x 6.0 Sqmm + 1 No. 2.5 Sqmm Copper earth wire 20 RM TB PW
g) 2 x 10.0 Sqmm + 1 No. 6.0 Sqmm Copper earth wire 20 RM TB PW
h) 4 x 10.0 Sqmm + 2 Nos. 6.0 Sqmm Copper earth wire 20 RM TB PW
i) 4 x 16.0 Sqmm + 2 Nos. 10.0 Sqmm Copper earth wire 20 RM TB PW
j) 4 x 25.0 Sqmm + 2 Nos. 16.0 Sqmm Copper earth wire 20 RM TB PW
Note: TB PW
TB PW
In false ceiling areas the work is to be co-ordinated with
respect to interior work and rate for point wiring shall include
1) TB PW
flexible conduit/fixing nipples/couplers etc from the junction
box up to the fitting.
TB PW
All wires used for circuit / point wiring shall be Low Smoke
2) TB PW
Zero Halogen (LSZH) wires.
TB PW
TOTAL OF WIRING CARRIED OVER TO SUMMARY TB PW
4.00 LIGHTING FIXTURES : TB LIGHT
TB LIGHT
Inspection, receiving, storing, handling, assembling,
installation, testing and commissioning of wall /ceiling,
surface/ recessed, suspended from down rod, in furniture,
fluorescent / incandescent / Halogen lamp fixtures including
making connections with PVC insulated stranded copper
conductor wires complete including steel supports, TB LIGHT
suspenders, fixing screws, turn buckles, bolts, nuts (down
rods ball and socket arrangement and special channel
mounting for industrial fitting/chandelier) etc, as required. The
mounting arrangement of lighting fixture shall be as indicated
in the approved drawings.
TB LIGHT
Surface mounted Industrial Luminaire with 1x36W
1.00 Fluorescent T5 Lamps (Thorn Indus RD 1x36W TW or 87 Set TB LIGHT
Equivalent) (T5).
TB LIGHT
Surface mounted Industrial Luminaire with 1x36W
2.00 Fluorescent T5 Lamps (Thorn Indus RD 1x36W TW or 19 Set TB LIGHT
Equivalent) (T5) complete with emergency lighting units.
TB LIGHT
Surface mounted Industrial Luminaire with 2x36W
3.00 Fluorescent T5 Lamps (Thorn Indus RD 2x36W TW or ur Set TB LIGHT
Equivalent) (T6).
TB LIGHT
Surface mounted Industrial Luminaire with 2x36W
4.00 Fluorescent T5 Lamps (Thorn Indus RD 2x36W TW or 6 Set TB LIGHT
Equivalent) (T6) complete with emergency lighting units.
TB LIGHT
Wall mounted Luminaire with 1 x 28W Fluorescent T5 Lamp
5.00 waterproof IP44 (Siteco Europlex 24W IP44 or Equivalent) 88 Set TB LIGHT
(T8).
TB LIGHT
Wall mounted Luminaire with 1 x 28W Fluorescent T5 Lamp
6.00 waterproof IP44 (Siteco Europlex 24W IP44 or Equivalent) 8 Set TB LIGHT
(T8) complete with emergency lighting units.

VOLTEC ENERGY SYSTEMS Page 44


LABOUR RATE
TB LIGHT
Recessed Downlight 1x26W (Thorn Chalice C 190H 1x26W
7.00 860 Set TB LIGHT
or Equivalent) (T13)
TB LIGHT
Recessed Downlight 1x26W (Thorn Chalice C 190H 1x26W
8.00 226 Set TB LIGHT
or Equivalent) (T13) complete with emergency lighting units.
TB LIGHT
Recessed Luminaire with 4 x 18W T5 Lamps with Parabolic
9.00 416 Set TB LIGHT
Louvre (Thorn Omega BS/SB 4 x 18W or Equivalent) (T14)
TB LIGHT
Recessed Luminaire with 4 x 18W T5 Lamps with Parabolic
10.00 Louvre (Thorn Omega BS/SB 4 x 18W or Equivalent) (T14) 70 Set TB LIGHT
complete with emergency lighting units.
TB LIGHT
Recessed outside Downlight IP54 (Trilux Downlight IP54 or
11.00 226 Set TB LIGHT
Equivalent) (T21)
TB LIGHT
Recessed outside Downlight IP54 (Trilux Downlight IP54 or
12.00 33 Set TB LIGHT
Equivalent) (T21) complete with emergency lighting units.
TB LIGHT
Recessed Luminaire 2 x 58W IP65 (Thorn Duopre 2 x 58W
13.00 96 Set TB LIGHT
T26 H2F or Equivalent) (T23).
TB LIGHT
Recessed Luminaire 2 x 58W IP65 (Thorn Duopre 2 x 58W
14.00 T26 H2F or Equivalent) (T23) complete with emergency 22 Set TB LIGHT
lighting units.
TB LIGHT
Emergency Exit Up Fixture (Cooper/Crompton or Equivalent)
15.00 29 Set TB LIGHT
complete with emergency lighting units.
TB LIGHT
Emergency Exit Down Fixture (Cooper/Crompton or
16.00 47 Set TB LIGHT
Equivalent) complete with emergency lighting units.
TB LIGHT
Emergency Exit Left Fixture (Cooper/Crompton or Equivalent)
17.00 9 Set TB LIGHT
complete with emergency lighting units.
TB LIGHT
Emergency Exit Right Fixture (Cooper/Crompton or
18.00 9 Set TB LIGHT
Equivalent) complete with emergency lighting units.
TB LIGHT
TOTAL OF LIGHTING FIXTURES CARRIED OVER TO
TB LIGHT
SUMMARY
5.00 EARTHING & LIGHTNING PROTECTION SYSTEM : TB EARTH
TB EARTH
5.10 Earthing System: TB EARTH
TB EARTH

Supply, installation, testing and commissioning of copper


plate earthing stations making earth pits, earthing with copper
earth plate 600 mm x 600 mm x 3.15 mm thick including
funnel, charcoal/coke, salt, all earth work. Providing masonry
5.1.1 2 Nos. TB EARTH
enclosure with 10 mm thick C.I. cover plate having locking
arrangement and watering pipe, disconnecting/ testing links
etc as per IS –3043 complete as required, as per
specifications, drawings and direction of Engineer-in-charge.

TB EARTH

VOLTEC ENERGY SYSTEMS Page 45


LABOUR RATE
Supply, installation, testing and commissioning of GI plate
earthing stations making earth pits, earthing with GI earth
plate 600 mm x 600 mm x 6.30 mm thick including funnel,
charcoal/coke, salt, all earth work. Providing masonry
5.1.2 42 Nos. TB EARTH
enclosure with 10 mm thick C.I. cover plate having locking
arrangement and watering pipe, disconnecting/ testing links
etc as per IS–3043 complete as required, as per
specifications, drawing and direction of Engineer-in-charge.
TB EARTH
Supply, installation, testing and commissioning of GI Pipe
earthing stations making earth pits, earthing with GI pipe
4500 mm x 40 mm Dia including funnel, charcoal/coke, salt,
all earth work. Providing masonry enclosure with 10 mm thick
5.1.3 2 Nos. TB EARTH
C.I. cover plate having locking arrangement and watering
pipe, disconnecting/ testing links etc as per IS–3043 complete
as required as per specifications, drawing and direction of
Engineer-in-charge.
TB EARTH
5.1.4 Earthing Strip/Tape/Cables : TB EARTH
TB EARTH
Supply, installation, testing and commissioning of following
sizes of GI/Tinned Copper strip/tape clamped to walls, cable
trays, bus ducts, recess in Ground or surface etc for
equipment/ System earthing complete as required including
0.00 TB EARTH
inter connection between length at joints, all fixing
accessories saddles, clamps etc and other fixing hardware
material as required, as per specifications, detail drawings
shall be included for proper installation.
TB EARTH
5.1.4.1 G.I. Earthing strip/tape : TB EARTH
TB EARTH
a 75 x 6 mm strip 10 RM TB EARTH
b 50 x 6 mm strip 10 RM TB EARTH
c 40 x 6 mm strip 100 RM TB EARTH
d 32 x 6 mm strip 100 RM TB EARTH
e 25 x 6 mm strip 100 RM TB EARTH
f 25 x 3 mm strip 1,500 RM TB EARTH
TB EARTH
5.1.4.2 Tinned Copper earthing strip/tape : TB EARTH
TB EARTH
a) 50 x 6 mm 10 RM TB EARTH
b) 32 x 6 mm 10 RM TB EARTH
c) 25 x 6 mm 10 RM TB EARTH
d) 25 x 3 mm 10 RM TB EARTH
TB EARTH
Supply, installation, Termination, testing and commissioning
of PVC insulated, stranded copper conductor cable, laid on
5.1.5 surface/cable tray/duct/undger ground/Trench etc. as TB CAB
required, as per approved shop drawing, site conditions and
as directed by Engineer-in-charge.
TB CAB
a) 1C x 240 Sqm 10 RM TB CAB
TB CAB
b) 1C x 185 Sqm 10 RM TB CAB
TB CAB
c) 1C x 90 Sqm 100 RM TB CAB

VOLTEC ENERGY SYSTEMS Page 46


LABOUR RATE
TB CAB
d) 1C x 50 Sqm 100 RM TB CAB
TB CAB
Supply, installation, Termination, testing and Commissioning
of following sizes GI Earth Bars including its supporting/fixing
5.1.6 TB EARTH
hardware, as per drawings, specifications and as directed by
Engineer-in-charge.
TB EARTH
5.1.6.1 75 x 6 mm GI Earth Bars. TB EARTH
TB EARTH
a) 300 mm 1 No. TB EARTH
b) 500 mm 1 Nos. TB EARTH
c) 750 mm 1 Nos. TB EARTH
d) 1000 mm 1 No. TB EARTH
TB EARTH
5.1.6.2 50 x 6 mm GI Earth Bars. TB EARTH
TB EARTH
a) 300 mm 2 Nos. TB EARTH
b) 500 mm 7 Nos. TB EARTH
c) 750 mm 7 Nos. TB EARTH
d) 1000 mm 2 Nos. TB EARTH
TB EARTH
5.20 Lightning Protection System: TB EARTH
TB EARTH

Supply, installation, testing and commissioning of copper


plate earthing stations making earth pits, earthing with copper
earth plate 600 mm x 600 mm x 3.15 mm thick including
funnel, charcoal/coke, salt, all earth work. Providing masonry
5.2.1 2 Nos. TB EARTH
enclosure with 10 mm thick C.I. cover plate having locking
arrangement and watering pipe, disconnecting/ testing links
etc as per IS –3043 complete as required, as per drawings,
specifications and direction of Engineer-in-charge.

TB EARTH
Supply, installation, testing and commissioning of GI Pipe
earthing stations making earth pits, earthing with GI pipe
4500 mm x 40 mm Dia including funnel, charcoal/coke, salt,
all earth work. Providing masonry enclosure with 10 mm thick
5.2.2 110 Nos. TB EARTH
C.I. cover plate having locking arrangement and watering
pipe, disconnecting/ testing links etc as per IS–3043 complete
as required, as per drawings, specifications and direction of
Engineer-in-charge.
TB EARTH
5.2.3 Earthing Strip/Wires : TB EARTH
TB EARTH

Supply, installation, testing and commissioning of following


sizes of GI strip/wire clamped to walls, Ductwork, pipe work,
Structural steel work, cladding work etc. in recess, in Ground
or surface etc for Lightning Protection System complete as
required including inter connection, terminations, between
length at joints, all fixing accessories saddles, plastic isolator TB EARTH
mounting (of 50mmx80mm approx.), Sealing Collars, Sealing
Strip, Squared Timber Block (80mmx100mm approx.),
clamps, Lugs etc and other fixing hardware material as
required for proper installation as per detail drawings,
specifications and direction of Engineer-in-charge.

VOLTEC ENERGY SYSTEMS Page 47


LABOUR RATE
TB EARTH
a) 25 x 3 mm strip 2,400 RM TB EARTH
TB EARTH
b) 25 x 6 mm strip 1,000 RM TB EARTH
TB EARTH
c) 32 x 6 mm strip 10 RM TB EARTH
TB EARTH
Supply, installation, Termination, testing and Commissioning
of following sizes GI Earth Bars including in supporting/fixing
5.2.4 TB EARTH
hardware, as per drawings, specifications and as directed by
Engineer-in-charge.
TB EARTH
5.2.4.1 75 x 6 mm GI Earth Bars. TB EARTH
TB EARTH
a) 300 mm 2 Nos. TB EARTH
b) 500 mm 2 Nos. TB EARTH
c) 750 mm 2 Nos. TB EARTH
d) 1000 mm 2 Nos. TB EARTH
TB EARTH
5.2.4.2 50 x 6 mm GI Earth Bars. TB EARTH
TB EARTH
a) 300 mm 2 Nos. TB EARTH
b) 500 mm 2 Nos. TB EARTH
c) 750 mm 2 Nos. TB EARTH
d) 1000 mm 2 Nos. TB EARTH
TB EARTH
Supply and fixing of Lightning Arrestor Rod/Lightning
Conductor finial made of 25 mm dia, 2.0 mm thick & 300 mm
Long GI Tube having single prong at top with 75 mm dia, 6
5.2.5 110 Nos. TB EARTH
mm thick Base plate, including connections with roof parapit
Lightning protection Conductors, as per detailed drawings
and as per direction of Engineer-in-charge.
TB EARTH
Supply and fixing of "Earth Test Joints" encased in 200 mm
(H) x 150 mm (W) x 100 mm (D) recessed in concrete with
5.2.6 110 Nos. TB EARTH
removable cover plate as per detailed drawing and as per
direction of Engineer-in-charge.
TB EARTH
TOTAL OF EARTHING & LIGHTNING PROTECTION
TB EARTH
SYSTEM CARRIED OVER TO SUMMARY
MEDICAL CENTER MC
1.00 FINAL DISTRIBUTION BOARDS MC PANEL
MC PANEL
Design, manufacture, supply, installation (recessed/ surface),
testing and commissioning of following switch fuse Unit/
MCCB/MCB type distribution boards as per drawings &
specifications fabricated out of 14 SWG, CRCA sheet steel in
compartmentalised design as per specification and drawings. MC PANEL
The surface distribution boards shall be mounted on 50 x 50 x
6 MS angle frame work grounted to floor/ walls. The rate
includes the angle iron frame, support, painting, numbering,
earthing etc as required.
MC PANEL
1.10 SDB-MC00-D01 : MC PANEL
MC PANEL

VOLTEC ENERGY SYSTEMS Page 48


LABOUR RATE
Incomer: MC PANEL
MC PANEL
- 100A TPN MCB Isolator. MC PANEL
MC PANEL
Busbar : MC PANEL
MC PANEL
- 150A 4P Cu. Busbar MC PANEL
MC PANEL
Outgoing – (10KA) comprising MC PANEL
MC PANEL
Section-1 MC PANEL
MC PANEL
- One (1) no. 32A 3 Phase RCD (100 mA). MC PANEL
MC PANEL
- Twelve (12) nos. 10A SP MCB. MC PANEL
MC PANEL
Section-2 MC PANEL
MC PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). MC PANEL
MC PANEL
- Three (3) nos. 16A SP MCB. MC PANEL
MC PANEL
- Thirteen (13) nos. 16A TPN MCB. MC PANEL
MC PANEL
- Six (6) nos. 32A TPN MCB. MC PANEL
MC PANEL
SDB-MC00-D01 as described above and as per DB chart. 1 Set MC PANEL
MC PANEL
1.20 DB-EE-MC00-B04 : MC PANEL
MC PANEL
Incomer: MC PANEL
MC PANEL
- 100A TPN MCB Isolator. MC PANEL
MC PANEL
Busbar : MC PANEL
MC PANEL
- 150A 4P Cu. Busbar MC PANEL
MC PANEL
Outgoing – (10KA) comprising MC PANEL
MC PANEL
Section-1 MC PANEL
MC PANEL
- One (1) no. 32A 3 Phase RCD (100 mA). MC PANEL
MC PANEL
- Eighteen (18) nos. 10A SP MCB. MC PANEL
MC PANEL
- Space for installation of three(3) Nos. SP MCB MC PANEL
MC PANEL
Section-2 MC PANEL
MC PANEL

VOLTEC ENERGY SYSTEMS Page 49


LABOUR RATE
- One (1) no. 63A, 3 Phase, RCD (30 mA). MC PANEL
MC PANEL
- Thirteen (13) nos. 16A SP MCB. MC PANEL
MC PANEL
- Two (2) nos. 16A TPN MCB. MC PANEL
MC PANEL
- Space for installation of eight (8) Nos. SP MCB MC PANEL
MC PANEL
DB-EE-MC00-B04 as described above and as per DB chart. 1 Set MC PANEL
MC PANEL
TOTAL OF FINAL DISTRIBUTION BOARDS CARRIED
MC PANEL
OVER TO SUMMARY
2.00 CABLES, SUB MAINS & CABLE TRAYS : MC CAB
MC CAB
2.10 Cables in Under Ground Installations : MC CAB
MC CAB
Supply, installation, testing and commissioning of following
sizes of PVC sheathed, XLPE insulated copper conductor
power/multicore control, armoured, Multi-strand cable of 1.1
KV grade in ground including digging the trench, laying the MC CAB
cable with sand and brick covering, back filling reaming etc
as required, as per specfications and as per directions of
Engineer-in-charge.
MC CAB
Copper Conductor, Armoured XLPE Cables
2.1.1 MC CAB
(PVC/SWA/XLPE) :
MC CAB
a) 4 core 150 sqmm 10 RM MC CAB
b) 4 core 120 sqmm 10 RM MC CAB
c) 4 core 95 sqmm 10 RM MC CAB
d) 4 core 70 sqmm 10 RM MC CAB
e) 4 core 50 sqmm 10 RM MC CAB
f) 4 core 35 sqmm 10 RM MC CAB
g) 4 core 25 sqmm 10 RM MC CAB
MC CAB
2.20 Cables on Racks / Pipes / Ducts / Wireways/Cable Trays : MC CAB
MC CAB
Supply, installation, testing and commissioning of following
sizes of PVC sheathed, XLPE insulated, copper conductor,
power/multicore, control, armoured, Multi-stranded cable of
1.1 KV grade on surface of wall or in existing cable tray MC CAB
/masonary ducts/hume pipe with fixing hardware etc as
required, as per specifications and as per direction of
Engineer-in-charge.
MC CAB
2.2.1 Copper Conductor Armoured Cables : MC CAB
MC CAB
a) 3.5 core 50 sqmm 10 RM MC CAB
b) 3.5 core 35 sqmm 10 RM MC CAB
c) 4 core 25 sqmm 10 RM MC CAB
d) 4 core 16 sqmm 10 RM MC CAB
e) 4 core 10 sqmm 50 RM MC CAB
f) 4 core 6 sqmm 50 RM MC CAB
g) 4 core 4 sqmm 600 RM MC CAB

VOLTEC ENERGY SYSTEMS Page 50


LABOUR RATE
h) 3 core 25 sqmm 10 RM MC CAB
i) 3 core 16 sqmm 10 RM MC CAB
j) 3 core 10 sqmm 10 RM MC CAB
k) 3 core 6 sqmm 10 RM MC CAB
l) 3 core 4 sqmm 300 RM MC CAB
m) 2 core 6 sqmm 10 RM MC CAB
n) 2 core 4 sqmm 10 RM MC CAB
MC CAB
2.2.2 Copper Conductor Armoured Control Cables : MC CAB
MC CAB
a) 14 C 1.5 Sqmm PVC cable 10 RM MC CAB
b) 10 C 1.5 Sqmm PVC cable 10 RM MC CAB
c) 9 C 1.5 Sqmm PVC cable 10 RM MC CAB
d) 7 C 1.5 Sqmm PVC cable 10 RM MC CAB
e) 5 C 1.5 Sqmm PVC cable 10 RM MC CAB
f) 3 C 1.5 Sqmm PVC cable 10 RM MC CAB
MC CAB
2.30 Cable Termination : MC TERM
MC TERM
Supply and making end termination with brass double
compression glands for the following XLPE insulated PVC
sheathed, 1100 V grade, Multi-strand copper conductor cable
including cost of crimping lugs/ferrules, double compression MC TERM
glands, solder, cable sockets, insulation tap etc complete as
required, as per specifications and as per direction of
Engineer-in-charge.
MC TERM
2.3.1 Copper conductor armoured cables : MC TERM
MC TERM
a) 3.5 core 50 sqmm 2 Nos. MC TERM
b) 3.5 core 35 sqmm 2 Nos. MC TERM
c) 4 core 25 sqmm 2 Nos. MC TERM
d) 4 core 16 sqmm 2 Nos. MC TERM
e) 4 core 10 sqmm 4 Nos. MC TERM
f) 4 core 6 sqmm 4 Nos. MC TERM
g) 4 core 4 sqmm 42 Nos. MC TERM
h) 3 core 25 sqmm 2 Nos. MC TERM
i) 3 core 16 sqmm 2 Nos. MC TERM
j) 3 core 10 sqmm 2 Nos. MC TERM
k) 3 core 6 sqmm 2 Nos. MC TERM
l) 3 core 4 sqmm 20 Nos. MC TERM
m) 2 core 6 sqmm 2 Nos. MC TERM
n) 2 core 4 sqmm 2 Nos. MC TERM
MC TERM
2.3.2 Copper Conductor PVC Insulated Armoured Control Cables : MC TERM
(Single Compression Glands suitable for following armoured
MC TERM
cables)
MC TERM
a) 14 C x 1.5 Sqmm 2 Nos. MC TERM
b) 10 C x 1.5 Sqmm 2 Nos. MC TERM
c) 9 C x 1.5 Sqmm 2 Nos. MC TERM

VOLTEC ENERGY SYSTEMS Page 51


LABOUR RATE
d) 7 C x 1.5 Sqmm 2 Nos. MC TERM
e) 5 C x 1.5 Sqmm 2 Nos. MC TERM
f) 3 C x 1.5 Sqmm 2 Nos. MC TERM
MC TERM

The cable quantities given are approximate and to cover


various sizes. The contractor shall measure the cables
Notes: MC TERM
required and procurement order shall be placed accordingly.
The quantities shall be confirmed before start of work.

MC TERM
Supply, installation, testing and commissioning of 1.1 KV
grade, Multicore, copper conductor, LSZH outer sheathed,
CWZ fire resistant cable (in compliance with BS : 6387) of
2.40 following sizes on surfae of wall/existing cable MC CAB
trays/Mesonary Hume pipe/Duct/Trenches etc., with fixing
hardware etc. as required as per specifications and as per
direction of Engineer-in-charge.
MC CAB
a) 4 C x 185 Sqm, CWZ Cable 5 RM MC CAB
b) 4 C x 150 Sqm, CWZ Cable 5 RM MC CAB
c) 4 C x 120 Sqm, CWZ Cable 5 RM MC CAB
d) 4 C x 95 Sqm, CWZ Cable 5 RM MC CAB
e) 4 C x 70 Sqm, CWZ Cable 5 RM MC CAB
f) 4 C x 50 Sqm, CWZ Cable 5 RM MC CAB
g) 4 C x 35 Sqm, CWZ Cable 5 RM MC CAB
h) 4 C x 25 Sqm, CWZ Cable 5 RM MC CAB
i) 4 C x 16 Sqm, CWZ Cable 5 RM MC CAB
j) 4 C x 10 Sqm, CWZ Cable 5 RM MC CAB
k) 4 C x 6 Sqm, CWZ Cable 5 RM MC CAB
l) 4 C x 4 Sqm, CWZ Cable 5 RM MC CAB
m) 4 C x 2.5 Sqm, CWZ Cable 5 RM MC CAB
MC CAB
2.50 Cable Trays : MC TRAY
MC TRAY

Supply and installation of ladder type/perforated type cable


trays of the following sizes fabricated out of perforated hot dip
galvanised MS sheets of minimum 2.0 mm thick to be
installed horizontally or vertically. The cable tray shall be
complete including cost of supporting Steel/Hangers, bends, MC TRAY
elbows, cross, tees, reducers etc as per drawings/site
condition and rate shall include cost of anchor fasteners,
screws, nuts, bolts and misc. other fixing hardware etc as
required, as per specifications and approved Shop drawings.

MC TRAY
The cable tray shall be factory built. Bidder shall include in his
price, required numbers of Tees, Crosses, Bends, Elbows etc
Notes: MC TRAY
as required as per actual site conditions. Bidder may refer to
the drawings for estimation purpose.
MC TRAY
2.5.1 Ladder Type Cable tray : MC TRAY
MC TRAY
a) 900 mm x 75 mm x 2.0 mm 5 RM MC TRAY
b) 750 mm x 75 mm x 2.0 mm 5 RM MC TRAY
c) 600 mm x 75 mm x 2.0 mm 5 RM MC TRAY

VOLTEC ENERGY SYSTEMS Page 52


LABOUR RATE
d) 450 mm x 75 mm x 2.0 mm 5 RM MC TRAY
e) 300 mm x 75 mm x 2.0 mm 5 RM MC TRAY
f) 250 mm x 75 mm x 2.0 mm 5 RM MC TRAY
g) 200 mm x 75 mm x 2.0 mm 5 RM MC TRAY
g) 150 mm x 75 mm x 2.0 mm 5 RM MC TRAY
g) 100 mm x 75 mm x 2.0 mm 5 RM MC TRAY
MC TRAY
2.52 Perforated Type Cable Tray : MC TRAY
MC TRAY
a) 750 mm x 75 mm x 2.0 mm 10 RM MC TRAY
b) 600 mm x 75 mm x 2.0 mm 10 RM MC TRAY
c) 450 mm x 75 mm x 2.0 mm 10 RM MC TRAY
d) 300 mm x 50 mm x 2.0 mm 10 RM MC TRAY
e) 200 mm x 75 mm x 2.0 mm 100 RM MC TRAY
f) 150 mm x 75 mm x 2.0 mm 10 RM MC TRAY
g) 100 mm x 75 mm x 2.0 mm 10 RM MC TRAY
MC TRAY
2.5.3 Fibreglass Ladder Type Cable Tray : MC TRAY
MC TRAY
Supply & Installation of Ladder type Cable tray of following
sizes. The Cable Tray shall be complete including the cost of
MC TRAY
Anchor fasteners, Hardware, supporting structure etc. as
required and as per specifications and approved drawing :
MC TRAY
a) 600 mm wide 5 RM MC TRAY
b) 450 mm wide 5 RM MC TRAY
c) 300 mm wide 5 RM MC TRAY
d) 225 mm wide 5 RM MC TRAY
e) 100 mm wide 5 RM MC TRAY
MC TRAY
2.60 Misc. Works Relating to Cabling: MC PIPE
MC PIPE
2.6.1 GI Pipe Installation : MC PIPE
MC PIPE
Supply and installation of following sizes of `A' class GI pipe
for cable sleeves in recess/ on surface/Ground complete with
all accessories pull boxes where ever required, G.I. fish wire,
fixing hardware etc. including the chasing of wall/floor, and MC PIPE
plastering the chased portion, digging the trench and back
filling, making good the damages, sealing of pipe entry etc as
required.
MC PIPE
a) 25 mm dia 10 RM MC PIPE
b) 32 mm dia 10 RM MC PIPE
c) 40 mm dia 10 RM MC PIPE
d) 50 mm dia 10 RM MC PIPE
e) 80 mm dia 10 RM MC PIPE
f) 100 mm dia 10 RM MC PIPE
g) 150 mm dia 10 RM MC PIPE
MC PIPE
2.6.2 Flexible Conduits Installation : MC PW
MC PW

VOLTEC ENERGY SYSTEMS Page 53


LABOUR RATE
Supply and installation of following sizes of GI flexible
conduits with all accessories including fixing nipples,
MC PW
couplings and fixing hardware etc as required and as per
specifications.
2.6.2.1 GI flexible conduits : MC PW
MC PW
a) 20 mm dia 50 RM MC PW
b) 25 mm dia 50 RM MC PW
c) 40 mm dia 10 RM MC PW
d) 50 mm dia 10 RM MC PW
MC PW
TOTAL OF CABLES, SUB MAINS, CABLE TRAYS
MC PW
CARRIED OVER TO SUMMARY
3.00 WIRING : MC PW
MC PW
3.10 Point Wiring : MC PW
MC PW
The rates for point wiring shall include the circuit wiring. MC PW
MC PW
Circuit wiring means the wiring from DB / Dimmer panel to the
MC PW
first point of circuit through control switch.
MC PW
Circuit wiring and subsequent looping shall be done with 2.5
MC PW
Sqmm, 1100V grade LSZH insulated stranded, copper wires.
MC PW
The rates of point wiring shall include supply, installation,
testing & commissioning of MS conduit with accessories, GI
Boxes and required GI flexible conduits with accessories up
MC PW
to the Point, LSZH insulated, stranded, Cu. Wire etc. as
required and as per specification, Tender Drawing and
direction of Engineer-in-charge.
MC PW
Where the light points are directly controlled from DB (without
any local control switches), the quoted rates shall not include MC PW
the cost of MCBs etc. in the point wiring.
MC PW
The rates of point wiring shall include earthing of each light,
fan, switches, switch plates, boxes and other non current
MC PW
carrying metallic part with 2.5 Sqm. Stranded copper, LSZH
insulated, stranded, copper wire.
MC PW
3.1.1 Light Points controlled by switch : MC PW
MC PW
i. Single/ First light point con-trolled by a 5Amps switch. 24 Nos. MC PW
MC PW
ii. Same as above but loop point 44 Nos. MC PW
MC PW
3.1.2 Light Points controlled directly from DB . MC PW
MC PW
i. Single/ First Point Controlled directly by MCB in DB 1 Nos. MC PW
MC PW
ii. Same as above but loop point. 5 Nos. MC PW
MC PW
3.1.3 Light points controlled by Two Way Switch : MC PW

VOLTEC ENERGY SYSTEMS Page 54


LABOUR RATE
MC PW
One / first light point controlled by two nos. two way 5 Amps.
i) 2 Nos. MC PW
switch.
MC PW
ii) Same as above but loop point. 9 Nos. MC PW
MC PW
3.1.4 Light Points controlled by Twilight switch : MC PW
MC PW
i. Single/ First light point con-trolled by a Twilight switch. 24 Nos. MC PW
MC PW
ii. Same as above but loop point 44 Nos. MC PW
MC PW
3.1.5 Light points controlled by Push Buttons : MC PW
MC PW
i) Five light points controlled by Two Push Buttons. 1 Nos. MC PW
MC PW
ii) Eleven light points controlled by Two Push Buttons. 1 Nos. MC PW
MC PW
iii) Ten light points controlled by Four Push Buttons. 1 Nos. MC PW
MC PW
iv) Twelve light points controlled by Four Push Buttons. 1 Nos. MC PW
MC PW
v) Ten light points controlled by Six Push Buttons. 1 Nos. MC PW
MC PW
3.1.6 Presence Sensor : MC PW
MC PW
Wiring from Presence Sensor to the DB/SwitchBoard/Light
fixtures, including providing Presence Sensor as required and
a) as per approved shop drawing (wiring from DB to light points 1 Nos. MC PW
has already been included in subheads 3.1.1, 3.1.2, 3.1.3,
3.1.4, 3.1.5 above and not to be considered here).
MC PW
3.1.7 6A Socket Points : MC PW
MC PW
Wiring for 6A, BS, switched socket outlet including providing
a) 6A, BS, switched, socket outlet as per specification and 12 Point MC PW
approved shop drawing.
MC PW
3.1.8 FCU Points controlled by 6A Switch : MC PW
MC PW
One / first light point controlled by 6A, BS, switched socket
i) 2 Nos. MC PW
outlet including providing 6A, BS, switched, socket outlet.
MC PW
ii) Same as above but loop point. 9 Nos. MC PW
MC PW
3.20 Power Socket Wiring : MC PW
MC PW
Power Socket Wiring shall include supply, installation, testing
and commissioning of wiring of following points, including,
providing conduits of suitable size, its accessories/Hardware,
MC PW
Junction Boxes, LSZH wires, termination of wires, switches,
socket outlets, Plug tops etc. as required and as per
specification.
MC PW

VOLTEC ENERGY SYSTEMS Page 55


LABOUR RATE
Wiring for 1 No. BS, 16A, switched socket outlet with 4 Sqmm
LSZH insulated stranded copper conductor wires in
recessed/surface black enameled MS conduit including
cutting/filling chases, providing conduit with conduit
3.2.1 accessories, saddles, supply and fixing of 1 No. BS, 16A, 4 Point MC PW
switched outlet with internal wiring in G.I. box, earthing of 3rd
pin with LSZH insulated, green colour 2.5 Sq.mm copper
wire, complete with all accessories as required and as per
approved shop drawing.
MC PW
Wiring for 2 Nos. BS, 16A, switched outlet with 4 Sqmm
LSZH insulated stranded copper conductor wires in
recessed/surface black enameled MS conduit including
cutting/filling chases, providing conduit with conduit
3.2.2 accessories, saddles, supply and fixing of 2 Nos. BS, 16A, 1 Point MC PW
switched outlet with internal wiring in G.I. box, earthing of 3rd
pin with LSZH insulated, green colour 2.5 Sq.mm copper
wire, complete with all accessories as required and as per
approved shop drawing.
MC PW
Wiring for 3 Nos. BS, 16A, switched outlet with 4 Sqmm
LSZH insulated stranded copper conductor wires in
recessed/surface black enameled MS conduit including
cutting/filling chases, providing conduit with conduit
3.2.3 accessories, saddles, supply and fixing of 3 Nos. BS, 16A, 7 Point MC PW
switched outlet with internal wiring in G.I. box, earthing of 3rd
pin with LSZH insulated, green colour 2.5 Sq.mm copper
wire, complete with all accessories as required and as per
approved shop drawing.
MC PW
Wiring for 4 Nos. BS, 16A, switched outlet with 4 Sqmm
LSZH insulated stranded copper conductor wires in
recessed/surface black enameled MS conduit including
cutting/filling chases, providing conduit with conduit
3.2.4 accessories, saddles, supply and fixing of 4 Nos. BS, 16A, 10 Point MC PW
switched outlet with internal wiring in G.I. box, earthing of 3rd
pin with LSZH insulated, green colour 2.5 Sq.mm copper
wire, complete with all accessories as required and as per
approved shop drawing.
MC PW
Wiring for 1 No. BS, 16A, switched outlet in IP-65 enclosure
with 4 Sqmm LSZH insulated stranded copper conductor
wires in recessed/surface black enameled MS conduit
including cutting/filling chases, providing conduit with conduit
3.2.5 accessories, saddles, supply and fixing of 1 No. BS, 16A, 1 Point MC PW
switched outlet in IP-65 enclosure with internal wiring,
earthing of 3rd pin with LSZH insulated, green colour 2.5
Sq.mm copper wire, complete with all accessories as required
and as per approved shop drawing.
MC PW
Wiring for 3 Nos. BS, 16A, switched outlets and 1 No. 16A DP
Isolator in IP-65 enclosure with 4 Sqmm LSZH insulated
stranded copper conductor wires in recessed/surface black
enameled MS conduit including cutting/filling chases,
providing conduit with conduit accessories, saddles, supply
3.2.6 1 Point MC PW
and fixing of 3 Nos. BS, 16A, switched outlets and 1 No. 16A
DP Isolator in IP-65 enclosure with internal wiring, earthing of
3rd pin with LSZH insulated, green colour 2.5 Sq.mm copper
wire, complete with all accessories as required and as per
approved shop drawing.
MC PW

VOLTEC ENERGY SYSTEMS Page 56


LABOUR RATE
Wiring for 1 No. 16A DP Isolators in IP-65 enclosure with 4
Sqmm LSZH insulated stranded copper conductor wires in
recessed/surface black enameled MS conduit including
cutting/filling chases, providing conduit with conduit
3.2.7 accessories, saddles, supply and fixing of 1 No. 16A DP 1 Point MC PW
Isolator in IP-65 enclosure with internal wiring, earthing with
LSZH insulated, green colour 2.5 Sq.mm copper wire,
complete with all accessories as required and as per
approved shop drawing.
MC PW
Wiring for 1 No. Disabled Alarm Device with 4 Sqmm LSZH
insulated stranded copper conductor wires in
recessed/surface black enameled MS conduit including
cutting/filling chases, providing conduit with conduit
accessories, saddles, supply and fixing of 1 No. Disabled
3.2.8 1 Point MC PW
Alarm Device, Single phase motor of required capacity (As
approved by the Engineer-in-charge) with internal wiring in
G.I. box, earthing with LSZH insulated, green colour 2.5
Sq.mm copper wire, complete with all accessories as required
and as per approved shop drawing.
MC PW
3.30 CEE INDUSTRIAL SWITCHED SOCKETS MC PW
MC PW
Supply, installation, testing and commissioning of single
phase/three phase, CEE, switched, industrial type plug and
socket outlet in IP-44 enclosure including termination,
3.3.1 earthing etc. in surface/recessed mounting as required, as MC PW
per specifications and approved shop drawings
(Cabling/Conduiting & wiring shall be paid separately under
different items).
MC PW
a) 16A, 2P+E, CEE, switched socket outlet with plug top (IP-44) 1 Nos. MC PW
MC PW
32A, 2P+E, CEE, switched socket outlet with plug top (IP-44)
b) 8 Nos. MC PW
(for single phase motors)
MC PW
16A, 3P+N+E, CEE, switched socket outlet with plug top (IP-
c) 4 No. MC PW
44)
MC PW
32A, 3P+N+E, CEE, switched socket outlet with plug top (IP-
d) 3 No. MC PW
44).
MC PW
16A, 3P+N+E, CEE, switched socket outlet with plug top (IP-
e) 1 No. MC PW
65) for water heaters.
MC PW
32A, 3P+N+E, CEE, switched socket outlet with plug top (IP-
b) 2 Nos. MC PW
44) (for three phase motors)
MC PW
3.40 ISOLATORS MC DB
MC DB
Supply, installation, testing and commissioning of isolators in
IP-65 enclosures complete with termination in MC DB
surface/recessed mounting as required.
MC DB
a) 16A Double pole isolator 10 Nos. MC DB
MC DB
b) 16A Four pole isolator 2 Nos. MC DB

VOLTEC ENERGY SYSTEMS Page 57


LABOUR RATE
MC DB
c) 32A Four pole isolator 1 Nos. MC DB
MC DB
3.50 M.S. Black Conduits : MC PW
MC PW
Supply and installation of following size of MS conduit pipe in
recess or on surface including all accessories MS/CI
pull/junction boxes, GI fish wire, fixing hardware etc
MC PW
including chasing the walls/floor and plastering the chased
portion and making good the damages etc, complete as
required and as per specifications.
MC PW
a) 20 mm dia 20 RM MC PW
MC PW
b) 25 mm dia 20 RM MC PW
MC PW
c) 32 mm dia 20 RM MC PW
MC PW
d) 40 mm dia 20 RM MC PW
MC PW
e) 50 mm dia 20 RM MC PW
MC PW
3.60 Sub-mains Wiring : MC PW
MC PW
Supply and drawing of following sizes of LSZH insulated,
stranded, copper conductor wires of 650/1100 Volts grade in
MC PW
existing conduit pipe /wire ways including connection
/terminations etc as required.
MC PW
a) 2 x 1.5 Sqmm + 1 No. 1.5 Sqmm Copper earth wire 20 RM MC PW
MC PW
b) 2 x 2.5 Sqmm + 1 No. 1.5 Sqmm Copper earth wire 20 RM MC PW
MC PW
c) 2 x 4.0 Sqmm + 1 No. 2.5 Sqmm Copper earth wire. 20 RM MC PW
MC PW
d) 2 x 6.0 Sqmm + 1 No. 2.5 Sqmm Copper earth wire 20 RM MC PW
MC PW
e) 4 x 4.0 Sqmm + 1 No. 2.5 Sqmm Copper earth wire 20 RM MC PW
MC PW
f) 4 x 6.0 Sqmm + 1 No. 2.5 Sqmm Copper earth wire 20 RM MC PW
MC PW
g) 2 x 10.0 Sqmm + 1 No. 6.0 Sqmm Copper earth wire 20 RM MC PW
MC PW
h) 4 x 10.0 Sqmm + 2 Nos. 6.0 Sqmm Copper earth wire 20 RM MC PW
MC PW
i) 4 x 16.0 Sqmm + 2 Nos. 10.0 Sqmm Copper earth wire 20 RM MC PW
MC PW
j) 4 x 25.0 Sqmm + 2 Nos. 16.0 Sqmm Copper earth wire 20 RM MC PW
MC PW
Note: MC PW
MC PW

VOLTEC ENERGY SYSTEMS Page 58


LABOUR RATE
In false ceiling areas the work is to be co-ordinated with
respect to interior work and rate for point wiring shall include
1) MC PW
flexible conduit/fixing nipples/couplers etc from the junction
box up to the fitting.
MC PW
All wires used for circuit / point wiring shall be Low Smoke
2) MC PW
Zero Halogen (LSZH) wires.
MC PW
TOTAL OF WIRING CARRIED OVER TO SUMMARY MC PW
4.00 LIGHTING FIXTURES : MC LIGHT
MC LIGHT
Inspection, receiving, storing, handling, assembling,
installation, testing and commissioning of wall /ceiling,
surface/ recessed, suspended from down rod, in furniture,
fluorescent / incandescent / Halogen lamp fixtures including
making connections with PVC insulated stranded copper
conductor wires complete including steel supports, MC LIGHT
suspenders, fixing screws, turn buckles, bolts, nuts (down
rods ball and socket arrangement and special channel
mounting for industrial fitting/chandelier) etc, as required. The
mounting arrangement of lighting fixture shall be as indicated
in the approved drawings.
MC LIGHT
Recessed Grid Luminaire 2x36W (Thorn Specalph BS/SB
1.00 2 Set MC LIGHT
2x36W or Equivalent) (T2).
MC LIGHT
Recessed Grid Luminaire 2x36W (Thorn Specalph BS/SB
2.00 2x36W or Equivalent) (T2) complete with emergency lighting 2 Set MC LIGHT
units.
MC LIGHT
Recessed Grid Luminaire 2x58W (Thorn Specalph BS/SB
3.00 10 Set MC LIGHT
2x58W or Equivalent) (T4).
MC LIGHT
Recessed Grid Luminaire 2x58W (Thorn Specalph BS/SB
4.00 2x58W or Equivalent) (T4) complete with emergency lighting 6 Set MC LIGHT
units.
MC LIGHT
Surface mounted Industrial Luminaire with 1x36W
5.00 Fluorescent T5 Lamps (Thorn Indus RD 1x36W TW or 24 Set MC LIGHT
Equivalent) (T5).
MC LIGHT
Surface mounted Industrial Luminaire with 1x36W
6.00 Fluorescent T5 Lamps (Thorn Indus RD 1x36W TW or 5 Set MC LIGHT
Equivalent) (T5) complete with emergency lighting units.
MC LIGHT
Surface mounted Industrial Luminaire with 2x36W
7.00 Fluorescent T5 Lamps (Thorn Indus RD 2x36W TW or 11 Set MC LIGHT
Equivalent) (T6).
MC LIGHT
Surface mounted Industrial Luminaire with 2x36W
8.00 Fluorescent T5 Lamps (Thorn Indus RD 2x36W TW or 3 Set MC LIGHT
Equivalent) (T6) complete with emergency lighting units.
MC LIGHT
Wall mounted Luminaire with 1 x 28W Fluorescent T5 Lamp
9.00 waterproof IP44 (Siteco Europlex 24W IP44 or Equivalent) 9 Set MC LIGHT
(T8).
MC LIGHT
Surfaced Luminaire 2x58W IP65 (Thorn AQUAF2 2x58W
10.00 1 Set MC LIGHT
IP65 or Equivalent) (T9)

VOLTEC ENERGY SYSTEMS Page 59


LABOUR RATE
MC LIGHT
Surfaced Luminaire 2x58W IP65 (Thorn AQUAF2 2x58W
11.00 IP65 or Equivalent) (T9) complete with emergency lighting 1 Set MC LIGHT
units.
MC LIGHT
Bulk Head Light Wall Mounted with 2 x 28W TC-DEL Lamp IP
12.00 8 Set MC LIGHT
65 (Thorn Danube 2x28W IP65 or Equivalent) (T11).
MC LIGHT
Recessed Downlight 1x26W (Thorn Chalice C 190H 1x26W
13.00 14 Set MC LIGHT
or Equivalent) (T13)
MC LIGHT
Recessed Downlight 1x26W (Thorn Chalice C 190H 1x26W
14.00 7 Set MC LIGHT
or Equivalent) (T13) complete with emergency lighting units.
MC LIGHT
Recessed Quad 2 x 18W (Thorn Matrix 300 2 x 18W or
15.00 20 Set MC LIGHT
Equivalent) (T15)
MC LIGHT
Recessed Quad 2 x 18W (Thorn Matrix 300 2 x 18W or
16.00 4 Set MC LIGHT
Equivalent) (T15) complete with emergency lighting units.
MC LIGHT
Recessed outside Downlight IP54 (Trilux Downlight IP54 or
17.00 5 Set MC LIGHT
Equivalent) (T21)
MC LIGHT
Emergency Exit Up Fixture (Cooper/Crompton or Equivalent)
18.00 10 Set MC LIGHT
complete with emergency lighting units.
MC LIGHT
Emergency Exit Down Fixture (Cooper/Crompton or
19.00 4 Set MC LIGHT
Equivalent) complete with emergency lighting units.
MC LIGHT
Emergency Exit Left & Right Fixture (Cooper/Crompton or
20.00 3 Set MC LIGHT
Equivalent) complete with emergency lighting units.
MC LIGHT
TOTAL OF LIGHTING FIXTURES CARRIED OVER TO
MC LIGHT
SUMMARY
5.00 EARTHING & LIGHTNING PROTECTION SYSTEM : MC EARTH
MC EARTH
5.10 Earthing System: MC EARTH
MC EARTH

Supply, installation, testing and commissioning of copper


plate earthing stations making earth pits, earthing with copper
earth plate 600 mm x 600 mm x 3.15 mm thick including
funnel, charcoal/coke, salt, all earth work. Providing masonry
5.1.1 5 Nos. MC EARTH
enclosure with 10 mm thick C.I. cover plate having locking
arrangement and watering pipe, disconnecting/ testing links
etc as per IS –3043 complete as required, as per
specifications, drawings and direction of Engineer-in-charge.

MC EARTH
Supply, installation, testing and commissioning of GI plate
earthing stations making earth pits, earthing with GI earth
plate 600 mm x 600 mm x 6.30 mm thick including funnel,
charcoal/coke, salt, all earth work. Providing masonry
5.1.2 5 Nos. MC EARTH
enclosure with 10 mm thick C.I. cover plate having locking
arrangement and watering pipe, disconnecting/ testing links
etc as per IS–3043 complete as required, as per
specifications, drawing and direction of Engineer-in-charge.
MC EARTH

VOLTEC ENERGY SYSTEMS Page 60


LABOUR RATE
Supply, installation, testing and commissioning of GI Pipe
earthing stations making earth pits, earthing with GI pipe
4500 mm x 40 mm Dia including funnel, charcoal/coke, salt,
all earth work. Providing masonry enclosure with 10 mm thick
5.1.3 1 Nos. MC EARTH
C.I. cover plate having locking arrangement and watering
pipe, disconnecting/ testing links etc as per IS–3043 complete
as required as per specifications, drawing and direction of
Engineer-in-charge.
MC EARTH
5.1.4 Earthing Strip/Tape/Cables : MC EARTH
MC EARTH
Supply, installation, testing and commissioning of following
sizes of GI/Tinned Copper strip/tape clamped to walls, cable
trays, bus ducts, recess in Ground or surface etc for
equipment/ System earthing complete as required including
MC EARTH
inter connection between length at joints, all fixing
accessories saddles, clamps etc and other fixing hardware
material as required, as per specifications, detail drawings
shall be included for proper installation.
MC EARTH
5.1.4.1 G.I. Earthing strip/tape : MC EARTH
MC EARTH
a 75 x 8 mm strip 10 RM MC EARTH
b 75 x 6 mm strip 10 RM MC EARTH
c 50 x 6 mm strip 10 RM MC EARTH
d 40 x 6 mm strip 10 RM MC EARTH
e 32 x 6 mm strip 10 RM MC EARTH
f 25 x 6 mm strip 10 RM MC EARTH
g 25 x 3 mm strip 250 RM MC EARTH
MC EARTH
5.1.4.2 Tinned Copper earthing strip/tape : MC EARTH
MC EARTH
a) 50 x 6 mm 10 RM MC EARTH
b) 32 x 6 mm 10 RM MC EARTH
c) 25 x 6 mm 10 RM MC EARTH
d) 25 x 3 mm 10 RM MC EARTH
MC EARTH
Supply, installation, Termination, testing and commissioning
of PVC insulated, stranded copper conductor cable, laid on
5.1.5 surface/cable tray/duct/undger ground/Trench etc. as MC CAB
required, as per approved shop drawing, site conditions and
as directed by Engineer-in-charge.
MC CAB
a) 1C x 240 Sqm 100 RM MC CAB
MC CAB
b) 1C x 185 Sqm 100 RM MC CAB
MC CAB
c) 1C x 90 Sqm 10 RM MC CAB
MC CAB
d) 1C x 50 Sqm 10 RM MC CAB
MC CAB
Supply, installation, Termination, testing and Commissioning
of following sizes tinned Cu/GI Earth Bars including its
5.1.6 MC EARTH
supporting/fixing hardware, as per drawings, specifications
and as directed by Engineer-in-charge.

VOLTEC ENERGY SYSTEMS Page 61


LABOUR RATE
MC EARTH
5.1.6.1 75 x 6 mm GI Earth Bars. MC EARTH
MC EARTH
a) 300 mm 1 No. MC EARTH
b) 500 mm 1 Nos. MC EARTH
c) 750 mm 1 Nos. MC EARTH
d) 1000 mm 1 No. MC EARTH
MC EARTH
5.1.6.2 50 x 6 mm GI Earth Bars. MC EARTH
MC EARTH
a) 300 mm 1 Nos. MC EARTH
b) 500 mm 1 Nos. MC EARTH
c) 750 mm 1 Nos. MC EARTH
d) 1000 mm 1 Nos. MC EARTH
MC EARTH
5.1.6.3 75 x 6 mm tinnned Cu Earth Bars. MC EARTH
MC EARTH
a) 300 mm 1 No. MC EARTH
b) 500 mm 2 Nos. MC EARTH
c) 750 mm 1 Nos. MC EARTH
d) 1000 mm 1 No. MC EARTH
MC EARTH
5.1.6.4 50 x 6 mm tinned Cu Earth Bars. MC EARTH
MC EARTH
a) 300 mm 1 Nos. MC EARTH
b) 500 mm 1 Nos. MC EARTH
c) 750 mm 1 Nos. MC EARTH
d) 1000 mm 1 Nos. MC EARTH
5.20 Lightning Protection System: MC EARTH
MC EARTH

Supply, installation, testing and commissioning of copper


plate earthing stations making earth pits, earthing with copper
earth plate 600 mm x 600 mm x 3.15 mm thick including
funnel, charcoal/coke, salt, all earth work. Providing masonry
5.2.1 1 Nos. MC EARTH
enclosure with 10 mm thick C.I. cover plate having locking
arrangement and watering pipe, disconnecting/ testing links
etc as per IS–3043 complete as required, as per drawings,
specifications and direction of Engineer-in-charge.

MC EARTH
Supply, installation, testing and commissioning of GI Pipe
earthing stations making earth pits, earthing with GI pipe
4500 mm x 40 mm Dia including funnel, charcoal/coke, salt,
all earth work. Providing masonry enclosure with 10 mm thick
5.2.2 6 Nos. MC EARTH
C.I. cover plate having locking arrangement and watering
pipe, disconnecting/ testing links etc as per IS–3043 complete
as required, as per drawings, specifications and direction of
Engineer-in-charge.
MC EARTH
5.2.3 Earthing Strip/Wires : MC EARTH
MC EARTH

VOLTEC ENERGY SYSTEMS Page 62


LABOUR RATE

Supply, installation, testing and commissioning of following


sizes of GI strip/wire clamped to walls, Ductwork, pipe work,
Structural steel work, cladding work etc. in recess or surface
etc for Lightning Protection System complete as required
including inter connection, terminations, between length at
joints, all fixing accessories saddles, plastic isolator mounting MC EARTH
(of 50mmx80mm approx.), Sealing Collars, Sealing Strip,
Squared Timber Block (80mmx100mm approx.), clamps,
Lugs etc and other fixing hardware material as required for
proper installation as per detail drawings, specifications and
direction of Engineer-in-charge.

MC EARTH
a) 25 x 3 mm strip 250 RM MC EARTH
MC EARTH
b) 25 x 6 mm strip 100 RM MC EARTH
MC EARTH
Supply, installation, Termination, testing and Commissioning
of following sizes GI Earth Bars including in supporting/fixing
5.2.4 MC EARTH
hardware, as per drawings, specifications and as directed by
Engineer-in-charge.
MC EARTH
5.2.4.1 75 x 6 mm GI Earth Bars. MC EARTH
MC EARTH
a) 300 mm 1 Nos. MC EARTH
b) 500 mm 1 Nos. MC EARTH
c) 750 mm 1 Nos. MC EARTH
d) 1000 mm 1 Nos. MC EARTH
MC EARTH
5.2.4.2 50 x 6 mm GI Earth Bars. MC EARTH
MC EARTH
a) 300 mm 1 Nos. MC EARTH
b) 500 mm 1 Nos. MC EARTH
c) 750 mm 1 Nos. MC EARTH
d) 1000 mm 1 Nos. MC EARTH
Supply and fixing of Lightning Arrestor Rod/Lightning
Conductor finial made of 25 mm dia, 2.0 mm thick & 300 mm
Long GI Tube having single prong at top with 75 mm dia, 6
10.2.5 15 Nos. MC EARTH
mm thick Base plate, including connections with roof parapit
Lightning protection Conductors, as per detailed drawings
and as per direction of Engineer-in-charge.
MC EARTH
Supply and fixing of "Earth Test Joints" encased in 200 mm
(H) x 150 mm (W) x 100 mm (D) recessed in concrete with
10.2.6 6 Nos. MC EARTH
removable cover plate as per detailed drawing and as per
direction of Engineer-in-charge.
MC EARTH
TOTAL OF EARTHING & LIGHTNING PROTECTION
MC EARTH
SYSTEM CARRIED OVER TO SUMMARY
PIT BUILDING PB HTO
PB HTO
1.00 11 KV, GAS INSULATED, RING MAIN UNITS: PB HTO
PB HTO
Unloading,Receiving, storing, checking, handling, installation,
testing and commissioning of 350 MVA, 11 KV indoor 4 way,
1.10 PB HTO
SF6 insulated, Extensible Ring Main Breaker Unit consisting
of following :-

VOLTEC ENERGY SYSTEMS Page 63


LABOUR RATE
PB HTO
Two (2) Nos. 630 Amp, TP VCB with disconnector and Earth
a) Switch as Incommers, with required Indication, Metering and PB HTO
Protection System.
PB HTO
Two (2) Nos. 630 Amp, TP VCB with disconnector and Earth
b) Switch as Outgoings, with required Indication, Metering & 2 Set PB HTO
Protection System.
PB HTO
Notes : PB HTO
PB HTO
Installation shall include supply of all Hardware material
i) (excluding civil work) as required and as per Approved Shop PB HTO
Drawings.
PB HTO
Necessary Co-ordination with client and manufacturer to be
ii) done by the contractor for successful installation, Testing and PB HTO
Commissioning.
PB HTO
1.30 Battery & Battery Charger : PB BATT
PB BATT
Supply, installation, testing & commissioning of 200 AH
capacity, Ni-Cd maintenance free batteries, duly charged,
complete with seasoned teak wood stand, connecting lead
a) PB BATT
as required for 11 KV RMU boards and some other control
loads. (AH calculation to be submitted by successful bidder in
co-ordination with the client and 11 KV, RMU Vendor).
PB BATT
i) for 24V DC System ur Set PB BATT
PB BATT
ii) for 110V DC System 2 Set PB BATT
PB BATT
Supply, installation, testing & commissioning of suitable float
cum boost battery charger and necessary distribution board
with 12 Nos. 16A outgoing feeders, instrument panel, Amp,
b) PB BATT
Volts meter, interconnections etc. power supply 240 V, 1
phase, 50 Hz ± 10%. Charger trouble annunciation shall be
provided through potential free contacts.
PB BATT
i) for 24V DC System ur Set PB BATT
PB BATT
ii) for 110V DC System 2 Set PB BATT
PB BATT
TOTAL OF 11 KV, GAS INSULATED, RING MAIN UNITS
PB BATT
CARRIED OVER TO SUMMARY
2.00 H T CABLING : PB CAB
PB CAB
2.10 11kV Cable laying : PB CAB
PB CAB
Supplying, laying, testing and commissioning of 11 KV grade
copper conductor, cross linked polyethylene (XLPE)
insulated, individual core screened, extruded inner sheath,
PB CAB
flat steel/strip armoured PVC sheathed cable and suitable for
(E) system complete as required and as per specification, as
follows:
PB CAB

VOLTEC ENERGY SYSTEMS Page 64


LABOUR RATE
2.1.1 Underground: PB CAB
PB CAB
Supply and laying of following size of 11 KV cables in earth
as per drawing, specifications and direction of engineer in PB CAB
charge.
PB CAB
a) 3C x 400 Sqmm, 11KV XLPE 10 Mtr PB CAB
PB CAB
b) 3C x 300 Sqmm, 11KV XLPE 10 Mtr PB CAB
PB CAB
c) 3C x 240 Sqmm, 11KV XLPE 10 Mtr PB CAB
PB CAB
2.1.2 In hume pipe/trays/trenches : PB CAB
PB CAB
Supply and laying of following sizes of 11 KV cables on
already laid trays/hume pipes/walls/ trench etc, as required,
PB CAB
as per drawing, specifications and direction of Engineer-in-
charge.
PB CAB
a) 3C x 400 Sqmm, 11KV XLPE 20 Mtr. PB CAB
PB CAB
b) 3C x 300 Sqmm, 11KV XLPE 20 Mtr PB CAB
PB CAB
c) 3C x 240 Sqmm, 11KV XLPE 100 Mtr PB CAB
PB CAB
2.20 End Termination (HT) : PB TERM
PB TERM
Supply, installation, testing and commissioning of Cable joints
of 11 KV grade, XLPE insulated, armoured, Copper
Conductor cable with suitable cable termination KITS
PB TERM
including all accessories i.e. Sockets, lugs, gland etc as
required, as per drawings, specifications and direction of
Engineer-in-charge.
PB TERM
a) 3C x 400 Sqmm, 11KV XLPE 1 Set PB TERM
PB TERM
b) 3C x 300 Sqmm, 11KV XLPE 1 Set PB TERM
PB TERM
c) 3C x 240 Sqmm, 11KV XLPE 8 Set PB TERM
PB TERM
2.30 End Termination (HT) : PB TERM
PB TERM
Cable jointing of 11 KV grade, XLPE insulated, armoured,
Aluminium Conductor cable with suitable cable termination
KITS including all accessories i.e. Sockets, lugs, gland etc as PB TERM
required, as per drawings, specifications and direction of
Engineer-in-charge.
PB TERM
a) 3C x 400 Sqmm, 11KV XLPE 4 Set PB TERM
PB TERM
b) 3C x 300 Sqmm, 11KV XLPE 1 Set PB TERM
PB TERM
c) 3C x 240 Sqmm, 11KV XLPE 1 Set PB TERM
PB TERM

VOLTEC ENERGY SYSTEMS Page 65


LABOUR RATE
Notes : PB TERM
PB TERM
The cable and cable terminations quantities given above, are
approximate. The contractor shall measure the cables
1.00 PB TERM
required at site and procurement order shall be place
accrodingly.
PB TERM
Wherever copper cable to be connected to Aluminium Bus
2.00 PB TERM
Bar or vis-à-vis., Bimetalic lugs to be used for terminations.
PB TERM
TOTAL OF H.T CABLING CARRIED OVER TO SUMMARY PB TERM
3.00 SUB STATION SAFETY EQUIPMENT : PB MISC
PB MISC
Supplying and fixing 1000 mm x 900 mm wide checkered
3.10 rubber matting conforming to IS 15652-2006 complete as PB MISC
required.
PB MISC
a) 11 KV grade size 1000 x 900 mm of suitable thickness 12 Nos. PB MISC
PB MISC
b) 1100 V grade size 1000 x 900 mm of suitable thickness 40 Nos. PB MISC
PB MISC
Supplying & fixing standard shock treatment charts in English
3.20 & Hindi / (Local Language) duly framed and covered with 3 Nos. PB MISC
glass.
PB MISC
Providing & fixing HT danger notice plate 200 mm x 150 mm
made of mild steel atleast 2mm thick & vitreous enameled
3.30 4 Nos. PB MISC
white on both sides and with inscription in signal red colour
with skull & bone on front side as required.
PB MISC
3.40 Providing 11 KV tested hand gloves. 2 Pair PB MISC
PB MISC
3.50 Providing 11 KV insulated grounding rod. 2 Nos. PB MISC
PB MISC
3.60 Providing first aid box as per IS:13115. 2 Set PB MISC
PB MISC
TOTAL OF SUB STATION SAFETY EQUIPMENT CARRIED
PB MISC
OVER TO SUMMARY
4.00 TRANSFORMER: PB TRAFO
PB TRAFO
Unloading,Receiving, storing, handling, installation, testing
and commissioning of 11 kV/ 400V (terminal voltage), 3
phase, 50 Hz delta/star connected, copper winding. indoor
type, natural air cooled, dry type, cast resin transformer of
following ratings, complete with all fittings such as
thermometer, off circuit tap changer with + 5 % to –15%, PB TRAFO
tapping at the step of 2.5% bi-directional roller, diagrams &
rating plate & Winding temperature indicator, lifting lugs, H. T.
cable box/ LT Terminal Box suitable for bus duct / Cable
termination etc. complete as per relevant specifications,
drawings and direction of Engineer-in-charge.
PB TRAFO
a) 1600 KVA 4 Set PB TRAFO
PB TRAFO
PB TRAFO
Notes : PB TRAFO

VOLTEC ENERGY SYSTEMS Page 66


LABOUR RATE
PB TRAFO
Installation rate shall include unloading, receiving including
storage at site,assembly, erection, testing and commissioning
i) PB TRAFO
etc. as required, as per approved Shop Drawing and as per
direction of Engineer-in-charge..
PB TRAFO
Necessary co-ordination with the manufacturer and client
ii) PB TRAFO
shall be done by the contractor without extra cost.
PB TRAFO
TOTAL OF TRANSFORMER CARRIED OVER TO
PB TRAFO
SUMMARY
PB BBT
5.0 BUS DUCT/BUS BAR TRUNKING SYSTEM : PB BBT
PB BBT
5.1 Bus Duct : PB BBT
PB BBT
Design, manufacturing, supply, installation, testing &
commissioning (at site) of sheet steel enclosed 3 phase &
neutral (100% neutral), 400V, 50 Hz., 65 KA copper
conductor bus duct with insulation of thermal rating confirming
to class 'F', including bends, transposition piece, expansion PB BBT
joint, Tees, End termination units, Feeder units, tap off unit
etc. with all flexible connections as per specifications and
drawings with all accessories, supports and termination of
bus duct to switchgear/transformer.
PB BBT
a) 2500A, 65kA @ 1 Sec., TP+N, Bus Duct (IP.55) with 4 Nos.
of Terminations and all other accessories as required as per PB BBT
specifications, and approved Shop Drawings. 80 RM
PB BBT
b) 2500A, 65kA @ 1 Sec., TP+N, Bus Duct (IP.68) with 4 Nos.
of Terminations and all other accessories as required as per PB BBT
specifications, and approved Shop Drawings. 120 RM
PB BBT
5.2 Bus Bar Trunking (BBT) : PB BBT
PB BBT
5.2.1 Design, manufacture, assembly, supply, installation, testing
and commissioning (at site) of following capacity compact,
Copper Conductor, Bus Bar Trunking System including
Bends, Tees, Expansion Joints, Feeder Units, Tap off Units,
Transposition pieces, Flexible Connections etc. with all other PB BBT
Hardware/accessories required for installation of Bus Bar
Trunking as per Specifications, approved Shop Drawings and
instruction of Engineer-in-charge.
PB BBT
Shutter type spring loaded arrangements shall be provided
for tap off system. The shutter shall get closed when tap off
PB BBT
box is taken out. Tap off facilities shall be there at every 500
mm interval as per standard.
PB BBT
i) 1600A, TPN+E, 400 Volt, 65 KA, compact, copper conductor
PB BBT
BBT. 40 RM
PB BBT
ii) 1250 A, TPN+E, 400 Volt, 65 KA, compact, copper Conductor
PB BBT
BBT. 180 RM
PB BBT
iii) 1000 A, TPN+E, 400 Volt, 65 KA, compact, copper Conductor
PB BBT
BBT. 565 RM

VOLTEC ENERGY SYSTEMS Page 67


LABOUR RATE
PB BBT
iv) 800 A, TPN+E, 400 Volt, 65 KA, compact, copper Conductor
PB BBT
BBT. ur RM
PB BBT
v) 630 A, TPN+E, 400 Volt, 65 KA, compact, copper Conductor
PB BBT
BBT. 15 RM
PB BBT
vi) 400 A, TPN+E, 400 Volt, 65 KA, compact, copper Conductor
PB BBT
BBT. ur RM
PB BBT
vii) 250 A, TPN+E, 400 Volt, 65 KA, compact, copper Conductor
PB BBT
BBT. ur RM
PB BBT
Notes: PB BBT
PB BBT
a) The quantity mentioned above is approximate. Bidder to
procure /manufacture the items as per actual site PB BBT
measurement & approved Shop drawings.
PB BBT
b) Rates shall be inclusive of all accessories & fittings. PB BBT
PB BBT
5.2.2 Design, manufacture, assembly, supply, installation, testing
and commissioning of plug-in type TPN tap off box of
following capacity on the existing Bus Bar Trunking and
PB BBT
complete with TPN MCCBs, links, interconnections, earthing
etc. as required, as per specifications and as per approved
Shop drawings.
PB BBT
i) 630A, TPN MCCB, 65 kA Tap off box. 1 No. PB BBT
PB BBT
ii) 400A TPN MCCB, 65 kA Tap off box. 2 Nos. PB BBT
PB BBT
iii) 315A TPN MCCB, 65 kA Tap off box. 4 Nos. PB BBT
PB BBT
iv) 250A TPN MCCB, 65 kA Tap off box. 1 Nos. PB BBT
PB BBT
v) 160A TPN MCCB, 65 kA Tap off box. 40 Nos. PB BBT
PB BBT
vi) 100A TPN MCCB, 65 kA Tap off box. 2 Nos. PB BBT
PB BBT
vii) 63A TPN MCCB, 65 kA Tap off box. 2 Nos. PB BBT
PB BBT
vi) 50A TPN MCCB, 65 kA Tap off box. 2 Nos. PB BBT
PB BBT
5.2.3 Design, Manufacture, Supply, installation, testing and
commissioning of End Feed Box/Bus Bar Trunking Adapter
Box, of following ratings with Digital Voltmeter & Ammeter
(ELF 3259 of Conzerv or Equivalent) complete with 5VA, PB BBT
class 1.0 CTs of required ratio and one set of phase
indication lamps and back-up SPMCBs, as per approved
drawing and specifications.
PB BBT
a) 1600 Amp with 1600 Amp, TPN, 65 kA, MDO ACB. 1 Nos. PB BBT
PB BBT
b) 1250 Amp with 1250 Amp, TPN, 65 kA, MDO ACB. 1 Nos. PB BBT

VOLTEC ENERGY SYSTEMS Page 68


LABOUR RATE
PB BBT
c) 1000 Amp with 1000 Amp, TPN, 65 kA, MDO ACB. 3 Nos. PB BBT
PB BBT
d) 800 Amp with 800 Amp, TPN, 65 kA, MDO ACB. ur Nos. PB BBT
PB BBT
e) 630 Amp with 630 Amp, TPN, 65 kA, MCCB. 1 Nos. PB BBT
PB BBT
f) 400 Amp with 400 Amp, TPN, 65 kA, MCCB. ur Nos. PB BBT
PB BBT
g) 250 Amp with 250 Amp, TPN, 65 kA, MCCB. ur No. PB BBT
PB BBT
PB BBT
Design, Manufacturing, Supply, installation, testing and
5.2.4 commissioning of Bus Coupler panels with ACB/MCCB of PB PANEL
following ratings for Bus Duct/Bus Bar Trunking System.
PB PANEL

The Bus Coupler panel shall consist of 400V, 65 KA@ 1 Sec,


4 pole, Draw out type, Electrically operated, ACB/MCCB
- complete with under voltage and shunt trip release, PB PANEL
antipumping protection, ON/OFF indication lamps etc. as
required, as per specifications and approved Shop drawings.
Bus Couper Panel shall be suitable for Termination of
- Compact Bus Bar Trunking from Top/Bottom as per approved PB PANEL
shop drawing.
PB PANEL
Bus Coupler Breaker shall have suitable No. of NO/NC
- contacts for required interlocking with the Breakers of End PB PANEL
feed units of Bus Bar Trunking.
PB PANEL
Bus Coupler Panel with 1600 Amp, 400V, 65 kA @ 1 Sec, 4
a) ur Nos. PB PANEL
Pole, EDO ACB
PB PANEL
Bus Coupler Panel with 1250 Amp, 400V, 65 kA @ 1 Sec, 4
b) ur Nos. PB PANEL
Pole, EDO ACB
PB PANEL
Bus Coupler Panel with 1000 Amp, 400V, 65 kA @ 1 Sec, 4
c) ur Nos. PB PANEL
Pole, MCCB
PB PANEL
Notes: PB PANEL
PB PANEL
The fabrication of bus duct/Bus Bar Trunking shall be taken
up only after actual measurement and site routing. Necessary
i) bends/transposition pieces/ expansion joints etc. shall be PB PANEL
estimated & included. Payment will be made on running
meter basis.
PB PANEL
The supply and fabrication & installation of structural steel for
ii) bus duct/Bus Bar Trunking support is included in the above PB PANEL
items.
PB PANEL
TOTAL OF BUS DUCT/BUS BAR TRUNKING SYSTEM
PB PANEL
CARRIED OVER TO SUMMARY
6.00 LV SWITCHGEAR PANELS & DISTRIBUTION BOARDS: PB PANEL
PB PANEL
LV SWITCHGEAR PANELS : PB PANEL

VOLTEC ENERGY SYSTEMS Page 69


LABOUR RATE
PB PANEL

Design, manufacture, supply, unloading, receiving, storing,


handling, installation, testing and commissioning of following
LV panels suitable for 400 V, 3 phase, 4 wire, 50 Hz power
distribution system. The panel shall be Indoor, free standing,
floor mounting, sheet metal clad, cubicle, dead front, dust and
vermin proof type compartmentalised design fabricated out of
14 SWG CRCA sheet steel, complete with colour coded, heat
shrinkable PVC insulated, Copper bus bars and separate
earth bus bar of adequate cross section through out the PB PANEL
length of the panel. The incoming and outgoing feeders shall
be accommodated in a fully segregated, modular multitier
arrangement with adequate size and distinct cable alley, bus
bar alley/chamber. The panel shall be complete with name
plate, earthing, numbering, danger plate etc. as required and
as per specifications and drawings. The panel shall withstand
the fault level of as indicated elsewhere or shown in Single
Line Diagram.

PB PANEL
Important Notes: Common for all Switchboard: PB PANEL
PB PANEL
The BOQ shall be read inconjunction with general notes,
specification and Single Line Diagram. Incase of any
discrepancy between specification, BOQ and SLD, the same
1.00 PB PANEL
shall be brought to the notice of Employer before quoting the
rates, otherwise stringent condition shall be deemed to have
been considered.
PB PANEL
2.00 Fault current wherever mentioned shall be Ics value. PB PANEL
PB PANEL
All MCCB shall be provided with door interlocked rotary
handle with ON/OFF/Trip position indicator, microprocessor
3.00 based releases for over current, selectable short circuit and PB PANEL
instentaneous short circuit protection (settable at site). I/C
MCCB shall be provided with E/F release/ protection also.
PB PANEL
4.00 All feeder doors shall have pad locking arrangement. PB PANEL
PB PANEL
5.00 All TP feeders shall have solid isolable neutral link. PB PANEL
PB PANEL
All MCCB used in starter feeder shall be suitable for motor
6.00 PB PANEL
duty application.
PB PANEL
7.00 All power contactors including NIC shall be of AC3 duty. PB PANEL
PB PANEL
All ACB's shall be with micro processor based O/C and S/C
releases and Breaker Control Switch (BCS) having lost
8.00 PB PANEL
motion device. I/C ACBs shall be provided with E/F release
also. Bus coupler shall be provided without releases.
PB PANEL
Spare contacts of ACB/Relays/Contactor etc. shall be wired
9.00 PB PANEL
upto terminal block.
PB PANEL

All switchgear used in starter feeder shall be type-2 co-


10.00 ordinated. Manufacturer is required to submit manufacturers PB PANEL
type-2 co-ordination chart for the make used.
11.00 Capacitor shall be super heavy duty type (MPP technology). PB PANEL

VOLTEC ENERGY SYSTEMS Page 70


LABOUR RATE
PB PANEL
All outgoing terminals (power and control) shall be brought
12.00 PB PANEL
upto cable alley. 10% extra terminals shall be provided.
PB PANEL
10% extra indicating lamp in loose shall be supplied along
13.00 PB PANEL
with panel.
PB PANEL
Removable lifting hook shall be provided in all transportation
14.00 PB PANEL
section.
PB PANEL
15.00 All CT, PT shall be cast resin. PB PANEL
PB PANEL
16.00 All meters are digital type. PB PANEL
PB PANEL
Panel shall be powder coated of approved shade with
17.00 PB PANEL
minimum 60 micron thickness.
PB PANEL
ACB's/MCCB's in one particular panel shall be of one similar
18.00 PB PANEL
make.
PB PANEL
Size of Voltmeter / Ammeter for incomer also, 96mm x 96mm
19.00 flush mounted with shrouded terminal shall be used in the PB PANEL
panel.
PB PANEL
20.00 Bus bar chamber shall be kept at top of the all panels. PB PANEL
PB PANEL
All bus bar shall be insulated with coloured PVC Sleeve
21.00 PB PANEL
i.e.RYB,BK as per colour code.
PB PANEL
Internal wiring of panel shall be with size 2.5sqmm Flexible
22.00 Copper Conductor for CT circuit and control wiring with 1.5 PB PANEL
sqmm.
PB PANEL
23.00 All indicating light shall be LED type . PB PANEL
PB PANEL
Each vertical section of floor mounted panel shall have
24.00 independent base frame (75mm x 40mm) size made out of 3 PB PANEL
mm sheet steel (LT Panel & DG Panel).
PB PANEL
All the makes shall be as per Employer's approved make list
25.00 PB PANEL
only.
PB PANEL
Wherever only voltmeter & ammeter are required, the same
26.00 may be provided in combined meter suitable for both PB PANEL
parameter.
PB PANEL
6.10 MDB-EE-PB00-C3 : PB PANEL
Location: Ground Floor Electrical Room : PB PANEL
PB PANEL
MDB-EE-PB00-C3 shall Comprise of the following: PB PANEL
PB PANEL
a) Incomings: PB PANEL
PB PANEL

VOLTEC ENERGY SYSTEMS Page 71


LABOUR RATE
Two (2) Nos. 2500 Amps, 400 V, 65kA, TPN draw out,
Electrically operated ACB, with ON/OFF/TRIP/Trip circuit
healthy indication lamp and TNC control switch, under
PB PANEL
voltage & shunt trip release, anti pumping protection
microprocessor based O/C, S/C & E/F protection etc.
complete as required for Transformer Supply Feeder.
One (1) no. 1600 Amps, 400 V, 50KA, four pole EDO ACB
Bus coupler breaker complete with under voltage and shunt
trip release, anti pumping protection, ON/OFF/ indication etc.
to be Electrically and mechanically interlocked with the PB PANEL
incommers so that necessary interlocking can be achieved as
per approved SLD, (E/MP/PB
5.S.02.01A,02A,03A,04A,05A,06A).
PB PANEL
Metering & indication for Transformer Supply incoming
b) PB PANEL
breakers:
PB PANEL
Each incoming breaker shall be provided with PB PANEL
PB PANEL
One (1) No. Digital Multifunction meter with RS-485 port
suitable for measurement of voltage, currents, Power Factor,
i) PB PANEL
Frequency,Power , Energy, harmonics and hours run
(EM6400 of 'Conzerv' make or equivalent).
PB PANEL
One (1) set 3 Nos. CTs of ratio 2500/5A,15VA, Class 1.0 as
ii) PB PANEL
required.
PB PANEL
iii) One (1) set of 2500/5 A, C.L 1.0 CTs for input to APFC relay. PB PANEL
PB PANEL
iv) One set (3 Nos) phase indication lamp with backup SP MCB. PB PANEL
PB PANEL
One (1) No. 4 Window Audi/visual annunciator system
v) complete with hooter, Ack, test & reset PBs for annunciation PB PANEL
of Alarm and Trip for following :-
PB PANEL
1.00 WTI Alarm PB PANEL
2.00 WTI Trip PB PANEL
3.00 REF Trip PB PANEL
4.00 HT Breaker Trip PB PANEL
PB PANEL
c) Protection Relays for Transformer Supply incoming breakers: PB PANEL
PB PANEL
Each Transformer breaker to be provided with : PB PANEL
PB PANEL
One (1) no. SIPROTEC compact 7SJ80 Multifunction
i) PB PANEL
Protection Relay of Siemens make or equivalent.
PB PANEL
One(1) set of CTs of ratio 2500/5A with core for protection of
ii) PB PANEL
5VA and class 5P10.
PB PANEL
One (1) Set, 4 Nos. CTs of ratio 2500/1A, Class PS shall be
iii) PB PANEL
provided for REF Protection.
PB PANEL
Notes : PB PANEL

VOLTEC ENERGY SYSTEMS Page 72


LABOUR RATE
PB PANEL
Sufficient No. of contacts terminals shall be provided in the
1.00 panel as required for necessary remote operation and PB PANEL
indications etc.
PB PANEL
Operation interlocks as per specification & drawings
indicating sufficient nos. of potential free contacts for
2.00 PB PANEL
interlocking/ indication annunciation/control etc shall be
provided by the bidder as required.
d) BUS BARS: PB PANEL
PB PANEL
Two (2) Sets of 3000Amp.,65kA, TPN+E, Copper Bus bar
with colour coded, heat shrinkable sleeves (with 100%
PB PANEL
neutral). Seperate Earth Bus Bar of Copper Conductor of 65 x
6 mm.
PB PANEL
e) Outgoing: PB PANEL
PB PANEL
Section-1 PB PANEL
PB PANEL
i) One (1) No. 1250A, 65 KA, 4P ACB. PB PANEL
PB PANEL
ii) One (1) No. 630 A, 36 KA, TPN MCCB. PB PANEL
PB PANEL
iii) One (1) No. 400 A, 36 KA, TPN MCCB. PB PANEL
PB PANEL
Section-2 PB PANEL
PB PANEL
i) One (1) No. 1000A, 65 KA, TPN ACB. PB PANEL
PB PANEL
ii) Four (4) Nos. 400 A, 36 KA, TPN MCCB. PB PANEL
PB PANEL
iii) Two (2) Nos. 100A, 36 KA, TPN MCCB. PB PANEL
PB PANEL
MDB-EE-PB00-C3 described as above (from a to e) and as
1 Set PB PANEL
per Specifications and SLD.
PB PANEL
6.20 MDB-EE-PB10-D51 : PB PANEL
Location: Ground Floor Electrical Room : PB PANEL
PB PANEL
MDB-EE-PB10-D51 shall Comprise of the following: PB PANEL
PB PANEL
a) Incomings: PB PANEL
PB PANEL
Two (2) Nos. 2500 Amps, 400 V, 65kA, TPN draw out,
Electrically operated ACB, with ON/OFF/TRIP/Trip circuit
healthy indication lamp and TNC control switch, under
PB PANEL
voltage & shunt trip release, anti pumping protection
microprocessor based O/C, S/C & E/F protection etc.
complete as required for Transformer Supply Feeder.
PB PANEL

VOLTEC ENERGY SYSTEMS Page 73


LABOUR RATE
One (1) no. 1600 Amps, 400 V, 50KA, four pole EDO ACB
Bus coupler breaker complete with under voltage and shunt
trip release, anti pumping protection, ON/OFF/ indication etc.
PB PANEL
to be Electrically and mechanically interlocked with the
incommers so that necessary interlocking can be achieved as
per approved SLD.
PB PANEL
Metering & indication for Transformer Supply incoming
b) PB PANEL
breakers:
PB PANEL
Each incoming breaker shall be provided with PB PANEL
PB PANEL
One (1) No. Digital Multifunction meter with RS-485 port
suitable for measurement of voltage, currents, Power Factor,
i) PB PANEL
Frequency, Power, Energy, harmonics and hours run
(EM6400 of 'Conzerv' make or equivalent).
PB PANEL
One (1) set 3 Nos. CTs of ratio 2500/5A,15VA, Class 1.0 as
ii) PB PANEL
required.
PB PANEL
iii) One (1) set of 2500/5 A, C.L 1.0 CTs for input to APFC relay. PB PANEL

iv) One set (3 Nos) phase indication lamp with backup SP MCB. PB PANEL
PB PANEL
One (1) No. 4 Window Audi/visual annunciator system
v) complete with hooter, Ack, test & reset PBs for annunciation PB PANEL
of Alarm and Trip for following :-
PB PANEL
1.00 WTI Alarm PB PANEL
2.00 WTI Trip PB PANEL
3.00 REF Trip PB PANEL
4.00 HT Breaker Trip PB PANEL
PB PANEL
c) Protection Relays for Transformer Supply incoming breakers: PB PANEL
PB PANEL
Each Transformer breaker to be provided with : PB PANEL
PB PANEL
One (1) no. SIPROTEC compact 7SJ80 Multifunction
i) PB PANEL
Protection Relay of Siemens make or equivalent.
PB PANEL
One(1) set of CTs of ratio 2500/5A with core for protection of
ii) PB PANEL
5VA and class 5P10.
PB PANEL
One (1) Set, 4 Nos. CTs of ratio 2500/1A, Class PS shall be
iii) PB PANEL
provided for REF Protection.
PB PANEL
Notes : PB PANEL
PB PANEL
Sufficient No. of contacts terminals shall be provided in the
1.00 panel as required for necessary remote operation and PB PANEL
indications etc.
PB PANEL

VOLTEC ENERGY SYSTEMS Page 74


LABOUR RATE
Operation interlocks as per specification & drawings
indicating sufficient nos. of potential free contacts for
2.00 PB PANEL
interlocking/ indication annunciation/control etc shall be
provided by the bidder as required.
PB PANEL
d) BUS BARS: PB PANEL
PB PANEL
Two (2) Sets of 3000Amp.,65kA, TPN+E, Copper Bus bar
with colour coded, heat shrinkable sleeves (with 100%
PB PANEL
neutral). Seperate Earth Bus Bar of Copper Conductor of 65 x
6 mm.
PB PANEL
e) Outgoing: PB PANEL
PB PANEL
Section-1 PB PANEL
PB PANEL
i) One (1) No. 1600A, 65 KA, TPN ACB. PB PANEL
PB PANEL
One (1) No. 1000A, 65 KA, TPN ACB. PB PANEL
PB PANEL
ii) One (1) No. 400 A, 36 KA, TPN MCCB. PB PANEL
PB PANEL
iii) One (1) No. 250A, 36 KA, TPN MCCB. PB PANEL
PB PANEL
Section-2 PB PANEL
PB PANEL
i) One (1) No. 1000A, 65 KA, TPN ACB. PB PANEL
PB PANEL
ii) One (1) No. 630 A, 36 KA, TPN MCCB. PB PANEL
PB PANEL
iii) Five (5) Nos. 400 A, 36 KA, TPN MCCB. PB PANEL
PB PANEL
iv) Two (2) Nos. 250A, 36 KA, TPN MCCB. PB PANEL
PB PANEL
MDB-EE-PB10-D51 described as above (from a to e) and as
1 Set PB PANEL
per Specifications and SLD.
6.30 CAPACITOR PANELS (250 kVAR) : PB PANEL
PB PANEL
a) Incoming : PB PANEL
PB PANEL
One (1) No. 400A, 36KA, TPN MCCB, incomer with 10 step
APFC relay with Auto/Manual selector switch, timer, aux. PB PANEL
Contactor, louvers, Exhaust fan etc.
PB PANEL
b) Metering, Indication and Protection : PB PANEL
PB PANEL
One (1) No. digital multifunction meter for measurement of
- voltage and currents with selector push buttons and one set PB PANEL
of CTs of ratio 400A /5A, CL 1.0, 15 VA.
PB PANEL
One (1) set of RYB phase indication lamps with control SP
- PB PANEL
MCB.
PB PANEL

VOLTEC ENERGY SYSTEMS Page 75


LABOUR RATE
c) Busbar : PB PANEL
PB PANEL
500A TPN+E, Cu. Busbar insulated with heat shrinkable
- sleeves and shall be color coded. Copper Earth Bus of 50 x 6 PB PANEL
mm.
PB PANEL
d) Outgoings : PB PANEL
PB PANEL
250 KVAR Capacitor Panel in steps of 10 Nos. of 1 x 25
- 4 Set PB PANEL
kVAR banks.
PB PANEL
Notes: PB PANEL
PB PANEL

Each capacitor bank should have its individual MCCB &


1.00 Contactor suitable for capacitor duty including fuses for each PB PANEL
capacitor unit as per specifications and approved SLD.

PB PANEL
Enclosure of capacitor panel shall be liberally designed to
take care of internal heat emission by capacitor unit without
2.00 forced cooling and to limit the temperature rise with in PB PANEL
permissible limit. However, louvers are allowed to facilitate
extra cooling.
PB PANEL
Enclosure of capacitor panel shall be designed so that
3.00 detuned reactors can be installed in the same panel for PB PANEL
harmonics reduction, in future.
PB PANEL
6.40 SDB-EE-PB00-D24 PB PANEL
PB PANEL
SDB-EE-PB00-D24 shall Comprise of the following: PB PANEL
PB PANEL
a) Incomings: PB PANEL
PB PANEL
One (1) No. 400Amps, 400 V, 36kA TPN MCCB, with
ON/OFF/TRIP/ indication lamp and TNC control switch,
under voltage & shunt trip release with microprocessor based PB PANEL
O/C, S/C & E/F protection etc. complete as required and as
per SLD.
PB PANEL
b) Metering & indication for incoming breakers: PB PANEL
PB PANEL
Incoming breaker shall be provided with PB PANEL
PB PANEL
One (1) No. Digital Multifunction meter with RS-485 port
i) suitable for measurement of voltage, currents and Frequency PB PANEL
(ELF 3259 of 'Conzerv' make or equivalent).
One (1) set 3 Nos. CTs of ratio 400/5A,15VA, Class 1.0 as
ii) PB PANEL
required.
PB PANEL
iii) One set (3 Nos) phase indication lamp with backup SP MCB. PB PANEL
PB PANEL
Sufficient No. of contacts terminals shall be provided in the
Note: panel as required for necessary remote operation and PB PANEL
indications etc.

VOLTEC ENERGY SYSTEMS Page 76


LABOUR RATE
PB PANEL
c) BUS BARS: PB PANEL
PB PANEL
500Amp., 36kA, TPN+E, Copper Bus bar with colour coded,
heat shrinkable sleeves (with 100% neutral). Earth Bus shall PB PANEL
be of 32 x 6 mm copper.
PB PANEL
d) Outgoing: PB PANEL
PB PANEL
i) One (1) No. 250 A, 36 KA, TPN MCCB. PB PANEL
PB PANEL
ii) One (1) No. 100 A, 36 KA, TPN MCCB. PB PANEL
PB PANEL
SDB-EE-PB00-D24 described as above (from a to d) and as
1 Set PB PANEL
per SLD
PB PANEL
6.50 SDB-EE-PB10-D2 PB PANEL
PB PANEL
SDB-EE-PB00-D24 shall Comprise of the following: PB PANEL
PB PANEL
a) Incomings: PB PANEL
PB PANEL
One (1) No. 250Amps, 400 V, 36kA TPN MCCB, with
ON/OFF/TRIP indication lamp and TNC control switch, under
voltage & shunt trip release with microprocessor based O/C, PB PANEL
S/C & E/F protection etc. complete as required and as per
SLD.
PB PANEL
b) Metering & indication for incoming breakers: PB PANEL
PB PANEL
Incoming breaker shall be provided with PB PANEL
PB PANEL
One (1) No. Digital Multifunction meter with RS-485 port
i) suitable for measurement of voltage, currents and Frequency PB PANEL
(ELF 3259 of 'Conzerv' make or equivalent).
PB PANEL
One (1) set 3 Nos. CTs of ratio 250/5A,15VA, Class 1.0 as
ii) PB PANEL
required.
PB PANEL
iii) One set (3 Nos) phase indication lamp with backup SP MCB. PB PANEL
PB PANEL
Sufficient No. of contacts terminals shall be provided in the
Note: panel as required for necessary remote operation and PB PANEL
indications etc.
PB PANEL
c) BUS BARS: PB PANEL
300Amp., 36kA, TPN+E, Copper Bus bar with colour coded,
heat shrinkable sleeves (with 100% neutral). Earth Bus shall PB PANEL
be of 32 x 6 mm copper.
PB PANEL
d) Outgoing: PB PANEL
i) One (1) No. 250 A, 36 KA, TPN MCCB. PB PANEL
ii) One (1) No. 100 A, 36 KA, TPN MCCB. PB PANEL

VOLTEC ENERGY SYSTEMS Page 77


LABOUR RATE
PB PANEL
SDB-EE-PB10-D24 described as above (from a to d) and as
1 Set PB PANEL
per SLD
SDB-EE-PB20-E8, SDB-EE-PB10-E15, SDB-EE-PB10-E22,
6.60 PB PANEL
SDB-EE-PB50-E47, SDB-EE-PB10-E47
PB PANEL
SDB-EE-PB20-E8, SDB-EE-PB10-E15, SDB-EE-PB10-E22,
SDB-EE-PB50-E47, SDB-EE-PB10-E47 shall Comprise of PB PANEL
the following:
PB PANEL
a) Incomings: PB PANEL
PB PANEL
One (1) No. 400Amps, 400 V, 36kA TPN MCCB, with
ON/OFF/TRIP indication lamp and TNC control switch, under
voltage & shunt trip release with microprocessor based O/C, PB PANEL
S/C & E/F protection etc. complete as required and as per
SLD.
PB PANEL
b) Metering & indication for incoming breakers: PB PANEL
PB PANEL
Incoming breaker shall be provided with PB PANEL
PB PANEL
One (1) No. Digital Multifunction meter with RS-485 port
i) suitable for measurement of voltage, currents and Frequency PB PANEL
(ELF 3259 of 'Conzerv' make or equivalent).
PB PANEL
One (1) set 3 Nos. CTs of ratio 400/5A,15VA, Class 1.0 as
ii) PB PANEL
required.
PB PANEL
iii) One set (3 Nos) phase indication lamp with backup SP MCB. PB PANEL
PB PANEL
Sufficient No. of contacts terminals shall be provided in the
Note: panel as required for necessary remote operation and PB PANEL
indications etc.
PB PANEL
c) BUS BARS: PB PANEL
PB PANEL
500Amp., 36kA, TPN+E, Copper Bus bar with colour coded,
heat shrinkable sleeves (with 100% neutral). Earth Bus shall PB PANEL
be of 32 x 6 mm copper.
PB PANEL
d) Outgoing: PB PANEL
PB PANEL
i) Two (2) Nos. 100 A, 36 KA, TPN MCCB. PB PANEL
PB PANEL
ii) Three (3) Nos. 100 A, 25 KA, TPN MCCB. PB PANEL
PB PANEL
SDB-EE-PB20-E8, SDB-EE-PB10-E15, SDB-EE-PB10-E22,
SDB-EE-PB50-E47, SDB-EE-PB10-E47 described as above 5 Set PB PANEL
(from a to d) and as per SLD
PB PANEL
6.70 SDB-EE-PB10-E08 PB PANEL
PB PANEL
SDB-EE-PB10-E08 shall Comprise of the following: PB PANEL

VOLTEC ENERGY SYSTEMS Page 78


LABOUR RATE
PB PANEL
a) Incomings: PB PANEL
PB PANEL
One (1) No. 400Amps, 400 V, 36kA TPN MCCB, with
ON/OFF/TRIP indication lamp and TNC control switch, under
voltage & shunt trip release with microprocessor based O/C, PB PANEL
S/C & E/F protection etc. complete as required and as per
SLD.
PB PANEL
b) Metering & indication for incoming breakers: PB PANEL
PB PANEL
Incoming breaker shall be provided with PB PANEL
PB PANEL
One (1) No. Digital Multifunction meter with RS-485 port
i) suitable for measurement of voltage, currents and Frequency PB PANEL
(ELF 3259 of 'Conzerv' make or equivalent).
PB PANEL
One (1) set 3 Nos. CTs of ratio 400/5A,15VA, Class 1.0 as
ii) PB PANEL
required.
PB PANEL
iii) One set (3 Nos) phase indication lamp with backup SP MCB. PB PANEL
PB PANEL
Sufficient No. of contacts terminals shall be provided in the
Note: panel as required for necessary remote operation and PB PANEL
indications etc.
PB PANEL
c) BUS BARS: PB PANEL
PB PANEL
500Amp., 36kA, TPN+E, Copper Bus bar with colour coded,
heat shrinkable sleeves (with 100% neutral). Earth Bus shall PB PANEL
be of 32 x 6 mm copper.
PB PANEL
d) Outgoing: PB PANEL
PB PANEL
i) One (1) No. 160 A, 36 KA, TPN MCCB. PB PANEL
PB PANEL
ii) Two (2) Nos. 100 A, 36 KA, TPN MCCB. PB PANEL
PB PANEL
ii) Three (3) Nos. 100 A, 25 KA, TPN MCCB. PB PANEL
PB PANEL
SDB-EE-PB10-E08 described as above (from a to d) and as
1 Set PB PANEL
per SLD
PB PANEL
6.80 SDB-EE-PB20-E47, SDB-EE-PB30-E47 PB PANEL
PB PANEL
SDB-EE-PB20-E47, SDB-EE-PB30-E47 shall Comprise of
PB PANEL
the following:
PB PANEL
a) Incomings: PB PANEL
PB PANEL

VOLTEC ENERGY SYSTEMS Page 79


LABOUR RATE
One (1) No. 400Amps, 400 V, 36kA TPN MCCB, with
ON/OFF/TRIP indication lamp and TNC control switch, under
voltage & shunt trip release with microprocessor based O/C, PB PANEL
S/C & E/F protection etc. complete as required and as per
SLD.
PB PANEL
b) Metering & indication for incoming breakers: PB PANEL
PB PANEL
Incoming breaker shall be provided with PB PANEL
PB PANEL
One (1) No. Digital Multifunction meter with RS-485 port
i) suitable for measurement of voltage, currents and Frequency PB PANEL
(ELF 3259 of 'Conzerv' make or equivalent).
PB PANEL
One (1) set 3 Nos. CTs of ratio 400/5A,15VA, Class 1.0 as
ii) PB PANEL
required.
PB PANEL
iii) One set (3 Nos) phase indication lamp with backup SP MCB. PB PANEL
PB PANEL
Sufficient No. of contacts terminals shall be provided in the
Note: panel as required for necessary remote operation and PB PANEL
indications etc.
c) BUS BARS: PB PANEL
PB PANEL
500Amp., 36kA, TPN+E, Copper Bus bar with colour coded,
heat shrinkable sleeves (with 100% neutral). Earth Bus shall PB PANEL
be of 32 x 6 mm copper.
PB PANEL
d) Outgoing: PB PANEL
PB PANEL
i) One (1) No. 100 A, 36 KA, TPN MCCB. PB PANEL
PB PANEL
ii) Three (3) Nos. 100 A, 25 KA, TPN MCCB. PB PANEL
PB PANEL
SDB-EE-PB20-E47, SDB-EE-PB30-E47 described as above
2 Set PB PANEL
(from a to d) and as per SLD
PB PANEL
6.90 SDB-EE-PB50-D54 PB PANEL
PB PANEL
SDB-EE-PB50-D54 shall Comprise of the following: PB PANEL
PB PANEL
a) Incomings: PB PANEL
PB PANEL
One (1) No. 630Amps, 400 V, 36kA TPN MCCB, with
ON/OFF/TRIP indication lamp and TNC control switch, under
voltage & shunt trip release with microprocessor based O/C, PB PANEL
S/C & E/F protection etc. complete as required and as per
SLD.
PB PANEL
b) Metering & indication for incoming breakers: PB PANEL
PB PANEL
Incoming breaker shall be provided with PB PANEL
PB PANEL

VOLTEC ENERGY SYSTEMS Page 80


LABOUR RATE
One (1) No. Digital Multifunction meter with RS-485 port
i) suitable for measurement of voltage, currents and Frequency PB PANEL
(ELF 3259 of 'Conzerv' make or equivalent).
PB PANEL
One (1) set 3 Nos. CTs of ratio 600/5A,15VA, Class 1.0 as
ii) PB PANEL
required.
PB PANEL
iii) One set (3 Nos) phase indication lamp with backup SP MCB. PB PANEL
PB PANEL
Sufficient No. of contacts terminals shall be provided in the
Note: panel as required for necessary remote operation and PB PANEL
indications etc.
PB PANEL
c) BUS BARS: PB PANEL
PB PANEL
700Amp., 36kA, TPN+E, Copper Bus bar with colour coded,
heat shrinkable sleeves (with 100% neutral). Earth Bus shall PB PANEL
be of 32 x 6 mm copper.
PB PANEL
d) Outgoing: PB PANEL
PB PANEL
i) One (1) No. 250 A, 36 KA, TPN MCCB. PB PANEL
PB PANEL
ii) Three (3) Nos. 100 A, 36 KA, TPN MCCB. PB PANEL
PB PANEL
SDB-EE-PB50-D54 described as above (from a to d) and as
1 Set PB PANEL
per SLD
6.10 SDB-EE-PB2M-D54 PB PANEL
PB PANEL
SDB-EE-PB2M-D54 shall Comprise of the following: PB PANEL
PB PANEL
a) Incomings: PB PANEL
PB PANEL
One (1) No. 100Amps, 400 V, 36kA TPN MCCB, with
ON/OFF/TRIP indication lamp and TNC control switch, under
voltage & shunt trip release with microprocessor based O/C, PB PANEL
S/C & E/F protection etc. complete as required and as per
SLD.
PB PANEL
b) Metering & indication for incoming breakers: PB PANEL
PB PANEL
Incoming breaker shall be provided with PB PANEL
PB PANEL
One (1) No. Digital Multifunction meter with RS-485 port
i) suitable for measurement of voltage, currents and Frequency PB PANEL
(ELF 3259 of 'Conzerv' make or equivalent).
PB PANEL
One (1) set 3 Nos. CTs of ratio 100/5A,15VA, Class 1.0 as
ii) PB PANEL
required.
PB PANEL
iii) One set (3 Nos) phase indication lamp with backup SP MCB. PB PANEL
PB PANEL

VOLTEC ENERGY SYSTEMS Page 81


LABOUR RATE
Sufficient No. of contacts terminals shall be provided in the
Note: panel as required for necessary remote operation and PB PANEL
indications etc.
PB PANEL
c) BUS BARS: PB PANEL
PB PANEL
150Amp., 36kA, TPN+E, Copper Bus bar with colour coded,
heat shrinkable sleeves (with 100% neutral). Earth Bus shall PB PANEL
be of 32 x 6 mm copper.
PB PANEL
d) Outgoing: PB PANEL
PB PANEL
i) Two (2) Nos. 100 A, 36 KA, TPN MCCB. PB PANEL
PB PANEL
SDB-EE-PB2M-D54 described as above (from a to d) and as
1 Set PB PANEL
per SLD
PB PANEL
6.11 SDB-EE-PB40-E47, SDB-EE-PB10-E26 PB PANEL
PB PANEL
SDB-EE-PB40-E47, SDB-EE-PB10-E26 shall Comprise of
PB PANEL
the following:
PB PANEL
a) Incomings: PB PANEL
PB PANEL
One (1) No. 400Amps, 400 V, 36kA TPN MCCB, with
ON/OFF/TRIP indication lamp and TNC control switch, under
voltage & shunt trip release with microprocessor based O/C, PB PANEL
S/C & E/F protection etc. complete as required and as per
SLD.
PB PANEL
b) Metering & indication for incoming breakers: PB PANEL
PB PANEL
Incoming breaker shall be provided with PB PANEL
PB PANEL
One (1) No. Digital Multifunction meter with RS-485 port
i) suitable for measurement of voltage, currents and Frequency PB PANEL
(ELF 3259 of 'Conzerv' make or equivalent).
PB PANEL
One (1) set 3 Nos. CTs of ratio 400/5A,15VA, Class 1.0 as
ii) PB PANEL
required.
iii) One set (3 Nos) phase indication lamp with backup SP MCB. PB PANEL
PB PANEL
Sufficient No. of contacts terminals shall be provided in the
Note: panel as required for necessary remote operation and PB PANEL
indications etc.
PB PANEL
c) BUS BARS: PB PANEL
PB PANEL
500Amp., 36kA, TPN+E, Copper Bus bar with colour coded,
heat shrinkable sleeves (with 100% neutral). Earth Bus shall PB PANEL
be of 32 x 6 mm copper.
PB PANEL
d) Outgoing: PB PANEL
PB PANEL

VOLTEC ENERGY SYSTEMS Page 82


LABOUR RATE
i) Three (3) Nos. 100 A, 36 KA, TPN MCCB. PB PANEL
PB PANEL
ii) Three (3) Nos. 100 A, 25 KA, TPN MCCB. PB PANEL
PB PANEL
SDB-EE-PB40-E47, SDB-EE-PB10-E26 described as above
2 Set PB PANEL
(from a to d) and as per SLD
PB PANEL
6.12 SDB-EE-PB10-E33 PB PANEL
PB PANEL
SDB-EE-PB10-E33 shall Comprise of the following: PB PANEL
PB PANEL
a) Incomings: PB PANEL
PB PANEL
One (1) No. 400Amps, 400 V, 36kA TPN MCCB, with
ON/OFF/TRIP indication lamp and TNC control switch, under
voltage & shunt trip release with microprocessor based O/C, PB PANEL
S/C & E/F protection etc. complete as required and as per
SLD.
PB PANEL
b) Metering & indication for incoming breakers: PB PANEL
PB PANEL
Incoming breaker shall be provided with PB PANEL
PB PANEL
One (1) No. Digital Multifunction meter with RS-485 port
i) suitable for measurement of voltage, currents and Frequency PB PANEL
(ELF 3259 of 'Conzerv' make or equivalent).
PB PANEL
One (1) set 3 Nos. CTs of ratio 400/5A,15VA, Class 1.0 as
ii) PB PANEL
required.
PB PANEL
iii) One set (3 Nos) phase indication lamp with backup SP MCB. PB PANEL
PB PANEL
Sufficient No. of contacts terminals shall be provided in the
Note: panel as required for necessary remote operation and PB PANEL
indications etc.
PB PANEL
c) BUS BARS: PB PANEL
PB PANEL
500Amp., 36kA, TPN+E, Copper Bus bar with colour coded,
heat shrinkable sleeves (with 100% neutral). Earth Bus shall PB PANEL
be of 32 x 6 mm copper.
PB PANEL
d) Outgoing: PB PANEL
PB PANEL
i) One (1) No. 160 A, 36 KA, TPN MCCB. PB PANEL
PB PANEL
ii) One (1) No. 100 A, 36 KA, TPN MCCB. PB PANEL
PB PANEL
ii) Three (3) Nos. 100 A, 25 KA, TPN MCCB. PB PANEL
PB PANEL
SDB-EE-PB10-E33 described as above (from a to d) and as
1 Set PB PANEL
per SLD
6.13 SDB-EE-PB10-E40 PB PANEL

VOLTEC ENERGY SYSTEMS Page 83


LABOUR RATE
PB PANEL
SDB-EE-PB10-E40 shall Comprise of the following: PB PANEL
PB PANEL
a) Incomings: PB PANEL
PB PANEL
One (1) No. 630Amps, 400 V, 36kA TPN MCCB, with
ON/OFF/TRIP indication lamp and TNC control switch, under
voltage & shunt trip release with microprocessor based O/C, PB PANEL
S/C & E/F protection etc. complete as required and as per
SLD.
PB PANEL
b) Metering & indication for incoming breakers: PB PANEL
PB PANEL
Incoming breaker shall be provided with PB PANEL
PB PANEL
One (1) No. Digital Multifunction meter with RS-485 port
i) suitable for measurement of voltage, currents and Frequency PB PANEL
(ELF 3259 of 'Conzerv' make or equivalent).
PB PANEL
One (1) set 3 Nos. CTs of ratio 600/5A,15VA, Class 1.0 as
ii) PB PANEL
required.
PB PANEL
iii) One set (3 Nos) phase indication lamp with backup SP MCB. PB PANEL
PB PANEL
Sufficient No. of contacts terminals shall be provided in the
Note: panel as required for necessary remote operation and PB PANEL
indications etc.
PB PANEL
c) BUS BARS: PB PANEL
PB PANEL
700Amp., 36kA, TPN+E, Copper Bus bar with colour coded,
heat shrinkable sleeves (with 100% neutral). Earth Bus shall PB PANEL
be of 32 x 6 mm copper.
PB PANEL
d) Outgoing: PB PANEL
PB PANEL
i) One (1) No. 160 A, 36 KA, TPN MCCB. PB PANEL
PB PANEL
ii) Three (3) Nos. 100 A, 36 KA, TPN MCCB. PB PANEL
PB PANEL
ii) Three (3) Nos. 100 A, 25 KA, TPN MCCB. PB PANEL
PB PANEL
SDB-EE-PB10-E40 described as above (from a to d) and as
1 Set PB PANEL
per SLD
PB PANEL
6.13 SDB-EE-PB10-D52 PB PANEL
PB PANEL
SDB-EE-PB10-D52 shall Comprise of the following: PB PANEL
PB PANEL
a) Incomings: PB PANEL
PB PANEL

VOLTEC ENERGY SYSTEMS Page 84


LABOUR RATE
One (1) No. 400Amps, 400 V, 36kA TPN MCCB, with
ON/OFF/TRIP indication lamp and TNC control switch, under
voltage & shunt trip release with microprocessor based O/C, PB PANEL
S/C & E/F protection etc. complete as required and as per
SLD.
PB PANEL
b) Metering & indication for incoming breakers: PB PANEL
PB PANEL
Incoming breaker shall be provided with PB PANEL
PB PANEL
One (1) No. Digital Multifunction meter with RS-485 port
i) suitable for measurement of voltage, currents and Frequency PB PANEL
(ELF 3259 of 'Conzerv' make or equivalent).
One (1) set 3 Nos. CTs of ratio 400/5A,15VA, Class 1.0 as
ii) PB PANEL
required.
PB PANEL
iii) One set (3 Nos) phase indication lamp with backup SP MCB. PB PANEL
PB PANEL
Sufficient No. of contacts terminals shall be provided in the
Note: panel as required for necessary remote operation and PB PANEL
indications etc.
PB PANEL
c) BUS BARS: PB PANEL
PB PANEL
500Amp., 36kA, TPN+E, Copper Bus bar with colour coded,
heat shrinkable sleeves (with 100% neutral). Earth Bus shall PB PANEL
be of 32 x 6 mm copper.
PB PANEL
d) Outgoing: PB PANEL
PB PANEL
i) One (1) No. 160 A, 36 KA, TPN MCCB. PB PANEL
PB PANEL
ii) Six (6) Nos. 100 A, 36 KA, TPN MCCB. PB PANEL
PB PANEL
SDB-EE-PB10-D52 described as above (from a to d) and as
1 Set PB PANEL
per SLD
PB PANEL
6.60 FINAL DISTRIBUTION BOARDS PB PANEL
PB PANEL
Design, manufacture, supply, installation (recessed/ surface),
testing and commissioning of following switch fuse Unit/
MCCB/MCB type distribution boards as per drawings &
specifications fabricated out of 14 SWG, CRCA sheet steel in
compartmentalised design as per specification and drawings. PB PANEL
The surface distribution boards shall be mounted on 50 x 50 x
6 MS angle frame work grounted to floor/ walls. The rate
includes the angle iron frame, support, painting, numbering,
earthing etc as required.
PB PANEL
6.6.1 DB-EE-PB00-D10 : PB PANEL
PB PANEL
Incomer: PB PANEL
PB PANEL
- 100A TP MCB Isolator. PB PANEL
PB PANEL

VOLTEC ENERGY SYSTEMS Page 85


LABOUR RATE
Busbar : PB PANEL
PB PANEL
- 150A 4P Cu. Busbar PB PANEL
PB PANEL
Outgoing – (10KA) comprising PB PANEL
PB PANEL
Section-1 PB PANEL
PB PANEL
- One (1) no. 32A 3 Phase RCD (100 mA). PB PANEL
PB PANEL
- Nine (9) nos. 10A SP MCB. PB PANEL
PB PANEL
- Six (6) nos. 16A SP MCB. PB PANEL
PB PANEL
- Three (3) nos. 32A TPN MCB. PB PANEL
PB PANEL
Section-2 PB PANEL
PB PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). PB PANEL
PB PANEL
- Twenty Two (22) nos. 16A SP MCB. PB PANEL
PB PANEL
- Space for installation of five (5) Nos. SP MCB PB PANEL
PB PANEL
DB-EE-PB00-D10 as described above and as per DB chart. 1 Set PB PANEL
6.6.2 DB-EE-PB00-D16 : PB PANEL
PB PANEL
Incomer: PB PANEL
PB PANEL
- 100A TP MCB Isolator. PB PANEL
PB PANEL
Busbar : PB PANEL
PB PANEL
- 150A 4P Cu. Busbar PB PANEL
PB PANEL
Outgoing – (10KA) comprising PB PANEL
PB PANEL
Section-1 PB PANEL
PB PANEL
- One (1) no. 32A 3 Phase RCD (100 mA). PB PANEL
PB PANEL
- Nine (9) nos. 10A SP MCB. PB PANEL
PB PANEL
- Nine (9) nos. 16A SP MCB. PB PANEL
PB PANEL
- Two (2) nos. 32A TPN MCB. PB PANEL
PB PANEL
Section-2 PB PANEL
PB PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). PB PANEL

VOLTEC ENERGY SYSTEMS Page 86


LABOUR RATE
PB PANEL
- Twenty Two (22) nos. 16A SP MCB. PB PANEL
PB PANEL
- Space for installation of five (5) Nos. SP MCB PB PANEL
PB PANEL
DB-EE-PB00-D16 as described above and as per DB chart. 1 Set PB PANEL
PB PANEL
6.6.3 DB-EE-PB00-D31 : PB PANEL
PB PANEL
Incomer: PB PANEL
PB PANEL
- 100A TP MCB Isolator. PB PANEL
PB PANEL
Busbar : PB PANEL
PB PANEL
- 150A 4P Cu. Busbar PB PANEL
PB PANEL
Outgoing – (10KA) comprising PB PANEL
PB PANEL
Section-1 PB PANEL
PB PANEL
- One (1) no. 32A 3 Phase RCD (100 mA). PB PANEL
PB PANEL
- Twenty One (21) nos. 10A SP MCB. PB PANEL
PB PANEL
- One (1) no. 32A TPN MCB. PB PANEL
PB PANEL
Section-2 PB PANEL
PB PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). PB PANEL
PB PANEL
- Three (3) nos. 10A SP MCB. PB PANEL
PB PANEL
- Nineteen (19) nos. 16A SP MCB. PB PANEL
PB PANEL
- Space for installation of five (5) Nos. SP MCB PB PANEL
PB PANEL
DB-EE-PB00-D31 as described above and as per DB chart. 1 Set PB PANEL
PB PANEL
6.6.4 DB-EE-PB00-D39 : PB PANEL
PB PANEL
Incomer: PB PANEL
PB PANEL
- 100A TP MCB Isolator. PB PANEL
PB PANEL
Busbar : PB PANEL
PB PANEL
- 150A 4P Cu. Busbar PB PANEL
Outgoing – (10KA) comprising PB PANEL
PB PANEL

VOLTEC ENERGY SYSTEMS Page 87


LABOUR RATE
Section-1 PB PANEL
PB PANEL
- One (1) no. 32A 3 Phase RCD (100 mA). PB PANEL
PB PANEL
- Six (6) nos. 10A SP MCB. PB PANEL
PB PANEL
- Fifteen (15) nos. 16A SP MCB. PB PANEL
PB PANEL
One (1) no. 32A TPN MCB. PB PANEL
PB PANEL
- Section-2 PB PANEL
PB PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). PB PANEL
PB PANEL
- Twenty Two (22) nos. 16A SP MCB. PB PANEL
PB PANEL
- Space for installation of five (5) Nos. SP MCB PB PANEL
PB PANEL
DB-EE-PB00-D39 as described above and as per DB chart. 1 Set PB PANEL
PB PANEL
6.6.5 DB-EE-PB00-D46 : PB PANEL
PB PANEL
Incomer: PB PANEL
PB PANEL
- 100A TP MCB Isolator. PB PANEL
PB PANEL
Busbar : PB PANEL
PB PANEL
- 150A 4P Cu. Busbar PB PANEL
PB PANEL
Outgoing – (10KA) comprising PB PANEL
PB PANEL
Section-1 PB PANEL
PB PANEL
- One (1) no. 32A 3 Phase RCD (100 mA). PB PANEL
PB PANEL
- Six (6) nos. 10A SP MCB. PB PANEL
PB PANEL
- Six (6) nos. 16A SP MCB. PB PANEL
PB PANEL
- One (1) no. 32A TPN MCB. PB PANEL
PB PANEL
- Space for installation of Nine (9) Nos. SP MCB PB PANEL
PB PANEL
- Section-2 PB PANEL
PB PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). PB PANEL
PB PANEL
- Twenty Two (22) nos. 16A SP MCB. PB PANEL
PB PANEL

VOLTEC ENERGY SYSTEMS Page 88


LABOUR RATE
- Space for installation of five (5) Nos. SP MCB PB PANEL
PB PANEL
DB-EE-PB00-D46 as described above and as per DB chart. 1 Set PB PANEL
PB PANEL
6.6.6 DB-EE-PB00-D52 : PB PANEL
PB PANEL
Incomer: PB PANEL
PB PANEL
- 100A TP MCB Isolator. PB PANEL
PB PANEL
Busbar : PB PANEL
PB PANEL
- 150A 4P Cu. Busbar PB PANEL
PB PANEL
Outgoing – (10KA) comprising PB PANEL
PB PANEL
Section-1 PB PANEL
PB PANEL
- One (1) no. 32A 3 Phase RCD (100 mA). PB PANEL
PB PANEL
- One (1) no. 6A SP MCB. PB PANEL
- Eighteen (18) nos. 10A SP MCB. PB PANEL
PB PANEL
- Five (5) nos. 16A SP MCB. PB PANEL
PB PANEL
- One (1) no. 16A TPN MCB. PB PANEL
PB PANEL
- One (1) no. 32A TPN MCB. PB PANEL
PB PANEL
Section-2 PB PANEL
PB PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). PB PANEL
PB PANEL
- Three (3) nos. 6A SP MCB. PB PANEL
PB PANEL
- Nineteen (19) nos. 16A SP MCB. PB PANEL
PB PANEL
- Space for installation of five (5) Nos. SP MCB PB PANEL
PB PANEL
DB-EE-PB00-D52 as described above and as per DB chart. 1 Set PB PANEL
PB PANEL
6.6.7 DB-EE-PB00-D54 : PB PANEL
PB PANEL
Incomer: PB PANEL
PB PANEL
- 100A TP MCB Isolator. PB PANEL
PB PANEL
Busbar : PB PANEL
PB PANEL
- 150A 4P Cu. Busbar PB PANEL

VOLTEC ENERGY SYSTEMS Page 89


LABOUR RATE
PB PANEL
Outgoing – (10KA) comprising PB PANEL
PB PANEL
Section-1 PB PANEL
PB PANEL
- One (1) no. 32A 3 Phase RCD (100 mA). PB PANEL
PB PANEL
- Five (5) nos. 6A SP MCB. PB PANEL
PB PANEL
- Twelve (12) nos. 10A SP MCB. PB PANEL
PB PANEL
- Four (4) nos. 16A SP MCB. PB PANEL
PB PANEL
Section-2 PB PANEL
PB PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). PB PANEL
PB PANEL
- One (1) no. 6A SP MCB. PB PANEL
PB PANEL
- Fifteen (15) nos. 16A SP MCB. PB PANEL
PB PANEL
- Two (2) nos. 32A TPN MCB. PB PANEL
PB PANEL
- Space for installation of five (5) Nos. SP MCB PB PANEL
PB PANEL
DB-EE-PB00-D54 as described above and as per DB chart. 1 Set PB PANEL
PB PANEL
6.6.8 DB-EE-PB20-E8 : PB PANEL
PB PANEL
Incomer: PB PANEL
PB PANEL
- 100A TP MCB Isolator. PB PANEL
PB PANEL
Busbar : PB PANEL
PB PANEL
- 150A 4P Cu. Busbar PB PANEL
PB PANEL
Outgoing – (10KA) comprising PB PANEL
PB PANEL
Section-1 PB PANEL
PB PANEL
- One (1) no. 32A 3 Phase RCD (100 mA). PB PANEL
- Thirty (30) nos. 10A SP MCB. PB PANEL
PB PANEL
Section-2 PB PANEL
PB PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). PB PANEL
PB PANEL
- Nine (9) nos. 16A SP MCB. PB PANEL
PB PANEL

VOLTEC ENERGY SYSTEMS Page 90


LABOUR RATE
- One (1) no. 32A TPN MCB. PB PANEL
PB PANEL
DB-EE-PB20-E8 as described above and as per DB chart. 1 Set PB PANEL
PB PANEL
6.6.9 DB-EE-PB20-E47 : PB PANEL
PB PANEL
Incomer: PB PANEL
PB PANEL
- 100A TP MCB Isolator. PB PANEL
PB PANEL
Busbar : PB PANEL
PB PANEL
- 150A 4P Cu. Busbar PB PANEL
PB PANEL
Outgoing – (10KA) comprising PB PANEL
PB PANEL
Section-1 PB PANEL
PB PANEL
- One (1) no. 32A 3 Phase RCD (100 mA). PB PANEL
PB PANEL
- Twelve (12) nos. 10A SP MCB. PB PANEL
PB PANEL
Section-2 PB PANEL
PB PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). PB PANEL
PB PANEL
- Five (5) nos. 16A SP MCB. PB PANEL
PB PANEL
- One (1) no. 32A TPN MCB. PB PANEL
PB PANEL
DB-EE-PB20-E47 as described above and as per DB chart. 1 Set PB PANEL
PB PANEL
6.6.10 DB-EE-PB2M-D54 : PB PANEL
PB PANEL
Incomer: PB PANEL
PB PANEL
- 100A TP MCB Isolator. PB PANEL
PB PANEL
Busbar : PB PANEL
PB PANEL
- 150A 4P Cu. Busbar PB PANEL
PB PANEL
Outgoing – (10KA) comprising PB PANEL
PB PANEL
Section-1 PB PANEL
PB PANEL
- One (1) no. 32A 3 Phase RCD (100 mA). PB PANEL
PB PANEL
- Thirty Three (23) nos. 10A SP MCB. PB PANEL
PB PANEL

VOLTEC ENERGY SYSTEMS Page 91


LABOUR RATE
Section-2 PB PANEL
PB PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). PB PANEL
PB PANEL
- Twenty Seven (27) nos. 16A SP MCB. PB PANEL
PB PANEL
- Four (4) nos. 32A TPN MCB. PB PANEL
PB PANEL
DB-EE-PB2M-D54 as described above and as per DB chart. 1 Set PB PANEL
6.6.11 DB-EE-PB3M-D2 : PB PANEL
PB PANEL
Incomer: PB PANEL
PB PANEL
- 100A TP MCB Isolator. PB PANEL
PB PANEL
Busbar : PB PANEL
PB PANEL
- 150A 4P Cu. Busbar PB PANEL
PB PANEL
Outgoing – (10KA) comprising PB PANEL
PB PANEL
Section-1 PB PANEL
PB PANEL
- One (1) no. 32A 3 Phase RCD (100 mA). PB PANEL
PB PANEL
- Twenty One (21) nos. 10A SP MCB. PB PANEL
PB PANEL
Section-2 PB PANEL
PB PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). PB PANEL
PB PANEL
- Sixteen (16) nos. 16A SP MCB. PB PANEL
PB PANEL
- Two (2) nos. 32A TPN MCB. PB PANEL
PB PANEL
DB-EE-PB3M-D2 as described above and as per DB chart. 1 Set PB PANEL
PB PANEL
6.6.12 DB-EE-PB30-E8 : PB PANEL
PB PANEL
Incomer: PB PANEL
PB PANEL
- 100A TP MCB Isolator. PB PANEL
PB PANEL
Busbar : PB PANEL
PB PANEL
- 150A 4P Cu. Busbar PB PANEL
PB PANEL
Outgoing – (10KA) comprising PB PANEL
PB PANEL
Section-1 PB PANEL

VOLTEC ENERGY SYSTEMS Page 92


LABOUR RATE
PB PANEL
- One (1) no. 32A 3 Phase RCD (100 mA). PB PANEL
PB PANEL
- Fourty Five (45) nos. 10A SP MCB. PB PANEL
PB PANEL
Section-2 PB PANEL
PB PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). PB PANEL
PB PANEL
- Fifteen (15) nos. 16A SP MCB. PB PANEL
PB PANEL
- One (1) no. 32A TPN MCB. PB PANEL
PB PANEL
DB-EE-PB30-E8 as described above and as per DB chart. 1 Set PB PANEL
PB PANEL
6.6.13 DB-EE-PB30-E47 : PB PANEL
PB PANEL
Incomer: PB PANEL
PB PANEL
- 100A TP MCB Isolator. PB PANEL
PB PANEL
Busbar : PB PANEL
PB PANEL
- 150A 4P Cu. Busbar PB PANEL
PB PANEL
Outgoing – (10KA) comprising PB PANEL
PB PANEL
Section-1 PB PANEL
- One (1) no. 32A 3 Phase RCD (100 mA). PB PANEL
- Fourty Two (42) nos. 10A SP MCB. PB PANEL
PB PANEL
Section-2 PB PANEL
PB PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). PB PANEL
PB PANEL
- Thirteen (13) nos. 16A SP MCB. PB PANEL
PB PANEL
- One (1) no. 32A TPN MCB. PB PANEL
PB PANEL
DB-EE-PB30-E47 as described above and as per DB chart. 1 Set PB PANEL
PB PANEL
6.6.14 DB-EE-PB40-E47 : PB PANEL
PB PANEL
Incomer: PB PANEL
PB PANEL
- 100A TP MCB Isolator. PB PANEL
PB PANEL
Busbar : PB PANEL
PB PANEL
- 150A 4P Cu. Busbar PB PANEL

VOLTEC ENERGY SYSTEMS Page 93


LABOUR RATE
PB PANEL
Outgoing – (10KA) comprising PB PANEL
PB PANEL
Section-1 PB PANEL
PB PANEL
- One (1) no. 32A 3 Phase RCD (100 mA). PB PANEL
PB PANEL
- Thirty Three (33) nos. 10A SP MCB. PB PANEL
PB PANEL
Section-2 PB PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). PB PANEL
- Twelve (12) nos. 16A SP MCB. PB PANEL
PB PANEL
- One (1) no. 32A TPN MCB. PB PANEL
PB PANEL
DB-EE-PB40-E47 as described above and as per DB chart. 1 Set PB PANEL
PB PANEL
6.6.15 DB-EE-PB50-D54 : PB PANEL
PB PANEL
Incomer: PB PANEL
PB PANEL
- 100A TP MCB Isolator. PB PANEL
PB PANEL
Busbar : PB PANEL
PB PANEL
- 150A 4P Cu. Busbar PB PANEL
PB PANEL
Outgoing – (10KA) comprising PB PANEL
PB PANEL
Section-1 PB PANEL
PB PANEL
- One (1) no. 32A 3 Phase RCD (100 mA). PB PANEL
PB PANEL
- Fifteen (15) nos. 10A SP MCB. PB PANEL
PB PANEL
Section-2 PB PANEL
PB PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). PB PANEL
PB PANEL
- Nine (9) nos. 16A SP MCB. PB PANEL
PB PANEL
- Four (4) nos. 32A TPN MCB. PB PANEL
PB PANEL
DB-EE-PB50-D54 as described above and as per DB chart. 1 Set PB PANEL
TOTAL OF LV SWITCHGEAR PANELS & DISTRIBUTION
PB PANEL
BOARDS CARRIED OVER TO SUMMARY
7.00 CABLES, SUB MAINS & CABLE TRAYS : PB CAB
PB CAB
7.10 Cables in Under Ground Installations : PB CAB
PB CAB

VOLTEC ENERGY SYSTEMS Page 94


LABOUR RATE
Supply, installation, testing and commissioning of following
sizes of PVC sheathed, XLPE insulated copper conductor
power/multicore control, armoured, Multi-strand cable of 1.1
KV grade in ground including digging the trench, laying the PB CAB
cable with sand and brick covering, back filling reaming etc
as required, as per specfications and as per directions of
Engineer-in-charge.
PB CAB
Copper Conductor, Armoured XLPE Cables
7.1.1 PB CAB
(PVC/SWA/XLPE) :
PB CAB
a) 4 core 150 sqmm 10 RM PB CAB
b) 4 core 120 sqmm 10 RM PB CAB
c) 4 core 95 sqmm 10 RM PB CAB
d) 4 core 70 sqmm 10 RM PB CAB
e) 4 core 50 sqmm 10 RM PB CAB
f) 4 core 35 sqmm 10 RM PB CAB
g) 4 core 25 sqmm 10 RM PB CAB
PB CAB
7.20 Cables on Racks / Pipes / Ducts / Wireways/Cable Trays : PB CAB
PB CAB
Supply, installation, testing and commissioning of following
sizes of PVC sheathed, XLPE insulated, copper conductor,
power/multicore, control, armoured, Multi-stranded cable of
1.1 KV grade on surface of wall or in existing cable tray PB CAB
/masonary ducts/hume pipe with fixing hardware etc as
required, as per specifications and as per direction of
Engineer-in-charge.
PB CAB
7.2.1 Copper Conductor Armoured Cables : PB CAB
PB CAB
a) 3.5 core 300 sqmm 50 RM PB CAB
b) 3.5 core 240 sqmm 200 RM PB CAB
c) 3.5 core 185 sqmm 50 RM PB CAB
d) 3.5 core 150 sqmm 370 RM PB CAB
e) 3.5 core 120 sqmm 10 RM PB CAB
f) 3.5 core 95 sqmm 160 RM PB CAB
g) 3.5 core 70 sqmm 50 RM PB CAB
h) 3.5 core 50 sqmm 680 RM PB CAB
i) 3.5 core 35 sqmm 650 RM PB CAB
j) 4 core 25 sqmm 1250 RM PB CAB
k) 4 core 16 sqmm 900 RM PB CAB
l) 4 core 10 sqmm 2900 RM PB CAB
m) 4 core 6 sqmm 40 RM PB CAB
n) 4 core 4 sqmm 10 RM PB CAB
o) 3 core 25 sqmm 10 RM PB CAB
p) 3 core 16 sqmm 10 RM PB CAB
q) 3 core 10 sqmm 10 RM PB CAB
r) 3 core 6 sqmm 10 RM PB CAB
s) 3 core 4 sqmm 1600 RM PB CAB
t) 2 core 6 sqmm 10 RM PB CAB
u) 2 core 4 sqmm 10 RM PB CAB
PB CAB

VOLTEC ENERGY SYSTEMS Page 95


LABOUR RATE
7.2.2 Copper Conductor Armoured Control Cables : PB CAB
PB CAB
a) 14 C 1.5 Sqmm PVC cable 10 RM PB CAB
b) 10 C 1.5 Sqmm PVC cable 10 RM PB CAB
c) 9 C 1.5 Sqmm PVC cable 10 RM PB CAB
d) 7 C 1.5 Sqmm PVC cable 10 RM PB CAB
e) 5 C 1.5 Sqmm PVC cable 10 RM PB CAB
f) 3 C 1.5 Sqmm PVC cable 10 RM PB CAB
PB CAB
7.30 Cable Termination : PB TERM
PB TERM
Supply and making end termination with brass double
compression glands for the following XLPE insulated PVC
sheathed, 1100 V grade, Multi-strand copper conductor cable
including cost of crimping lugs/ferrules, double compression PB TERM
glands, solder, cable sockets, insulation tap etc complete as
required, as per specifications and as per direction of
Engineer-in-charge.
PB TERM
7.3.1 Copper conductor armoured cables : PB TERM
PB TERM
a) 3.5 core 300 sqmm 2 Nos. PB TERM
b) 3.5 core 240 sqmm 12 Nos. PB TERM
c) 3.5 core 185 sqmm 4 Nos. PB TERM
d) 3.5 core 150 sqmm 16 Nos. PB TERM
e) 3.5 core 120 sqmm 2 Nos. PB TERM
f) 3.5 core 95 sqmm 16 Nos. PB TERM
g) 3.5 core 70 sqmm 20 Nos. PB TERM
h) 3.5 core 50 sqmm 46 Nos. PB TERM
i) 3.5 core 35 sqmm 44 Nos. PB TERM
j) 4 core 25 sqmm 92 Nos. PB TERM
k) 4 core 16 sqmm 46 Nos. PB TERM
l) 4 core 10 sqmm 268 Nos. PB TERM
m) 4 core 6 sqmm 4 Nos. PB TERM
n) 4 core 4 sqmm 2 Nos. PB TERM
o) 3 core 25 sqmm 2 Nos. PB TERM
p) 3 core 16 sqmm 2 Nos. PB TERM
q) 3 core 10 sqmm 2 Nos. PB TERM
r) 3 core 6 sqmm 2 Nos. PB TERM
s) 3 core 4 sqmm 164 Nos. PB TERM
t) 2 core 6 sqmm 2 Nos. PB TERM
u) 2 core 4 sqmm 2 Nos. PB TERM
PB TERM
7.3.2 Copper Conductor PVC Insulated Armoured Control Cables : PB TERM
(Single Compression Glands suitable for following armoured
PB TERM
cables)
PB TERM
a) 14 C x 1.5 Sqmm 2 Nos. PB TERM
b) 10 C x 1.5 Sqmm 2 Nos. PB TERM
c) 9 C x 1.5 Sqmm 2 Nos. PB TERM
d) 7 C x 1.5 Sqmm 2 Nos. PB TERM

VOLTEC ENERGY SYSTEMS Page 96


LABOUR RATE
e) 5 C x 1.5 Sqmm 2 Nos. PB TERM
f) 3 C x 1.5 Sqmm 2 Nos. PB TERM
PB TERM

The cable quantities given are approximate and to cover


various sizes. The contractor shall measure the cables
Notes: PB TERM
required and procurement order shall be placed accordingly.
The quantities shall be confirmed before start of work.

PB TERM
Supply, installation, testing and commissioning of 1.1 KV
grade, Multicore, copper conductor, LSZH outer sheathed,
CWZ fire resistant cable (in compliance with BS : 6387) of
7.40 following sizes on surfae of wall/existing cable PB CAB
trays/Mesonary Hume pipe/Duct/Trenches etc., with fixing
hardware etc. as required as per specifications and as per
direction of Engineer-in-charge.
PB CAB
a) 4 C x 185 Sqm, CWZ Cable 5 RM PB CAB
b) 4 C x 150 Sqm, CWZ Cable 5 RM PB CAB
c) 4 C x 120 Sqm, CWZ Cable 5 RM PB CAB
d) 4 C x 95 Sqm, CWZ Cable 5 RM PB CAB
e) 4 C x 70 Sqm, CWZ Cable 5 RM PB CAB
f) 4 C x 50 Sqm, CWZ Cable 5 RM PB CAB
g) 4 C x 35 Sqm, CWZ Cable 5 RM PB CAB
h) 4 C x 25 Sqm, CWZ Cable 5 RM PB CAB
i) 4 C x 16 Sqm, CWZ Cable 5 RM PB CAB
j) 4 C x 10 Sqm, CWZ Cable 5 RM PB CAB
k) 4 C x 6 Sqm, CWZ Cable 5 RM PB CAB
l) 4 C x 4 Sqm, CWZ Cable 5 RM PB CAB
m) 4 C x 2.5 Sqm, CWZ Cable 5 RM PB CAB
PB CAB
7.50 Cable Trays : PB TRAY
PB TRAY

Supply and installation of ladder type/perforated type cable


trays of the following sizes fabricated out of perforated hot dip
galvanised MS sheets of minimum 2.0 mm thick to be
installed horizontally or vertically. The cable tray shall be
complete including cost of supporting Steel/Hangers, bends, PB TRAY
elbows, cross, tees, reducers etc as per drawings/site
condition and rate shall include cost of anchor fasteners,
screws, nuts, bolts and misc. other fixing hardware etc as
required, as per specifications and approved Shop drawings.

PB TRAY
The cable tray shall be factory built. Bidder shall include in his
price, required numbers of Tees, Crosses, Bends, Elbows etc
Notes: PB TRAY
as required as per actual site conditions. Bidder may refer to
the drawings for estimation purpose.
PB TRAY
7.5.1 Ladder Type Cable tray : PB TRAY
PB TRAY
a) 900 mm x 75 mm x 2.0 mm 5 RM PB TRAY
b) 750 mm x 75 mm x 2.0 mm 5 RM PB TRAY
c) 600 mm x 75 mm x 2.0 mm 5 RM PB TRAY
d) 450 mm x 75 mm x 2.0 mm 5 RM PB TRAY

VOLTEC ENERGY SYSTEMS Page 97


LABOUR RATE
e) 300 mm x 75 mm x 2.0 mm 5 RM PB TRAY
f) 250 mm x 75 mm x 2.0 mm 5 RM PB TRAY
g) 200 mm x 75 mm x 2.0 mm 5 RM PB TRAY
g) 150 mm x 75 mm x 2.0 mm 5 RM PB TRAY
g) 100 mm x 75 mm x 2.0 mm 5 RM PB TRAY
PB TRAY
7.5.2 Perforated Type Cable Tray : PB TRAY
PB TRAY
a) 750 mm x 75 mm x 2.0 mm 10 RM PB TRAY
b) 600 mm x 75 mm x 2.0 mm 10 RM PB TRAY
c) 500 mm x 75 mm x 2.0 mm 10 RM PB TRAY
d) 400 mm x 75 mm x 2.0 mm 10 RM PB TRAY
e) 300 mm x 50 mm x 2.0 mm 50 RM PB TRAY
f) 250 mm x 50 mm x 2.0 mm 970 RM PB TRAY
g) 200 mm x 75 mm x 2.0 mm 610 RM PB TRAY
h) 150 mm x 75 mm x 2.0 mm 1590 RM PB TRAY
i) 100 mm x 75 mm x 2.0 mm 350 RM PB TRAY
PB TRAY
7.5.3 Fibreglass Ladder Type Cable Tray : PB TRAY
PB TRAY
Supply & Installation of Ladder type Cable tray of following
sizes. The Cable Tray shall be complete including the cost of
PB TRAY
Anchor fasteners, Hardware, supporting structure etc. as
required and as per specifications and approved drawing :
PB TRAY
a) 600 mm wide 5 RM PB TRAY
b) 450 mm wide 5 RM PB TRAY
c) 300 mm wide 5 RM PB TRAY
d) 225 mm wide 5 RM PB TRAY
e) 100 mm wide 5 RM PB TRAY
PB TRAY
7.60 Misc. Works Relating to Cabling: PB PIPE
PB PIPE
7.6.1 GI Pipe Installation : PB PIPE
PB PIPE
Supply and installation of following sizes of `A' class GI pipe
for cable sleeves in recess/ on surface/Ground complete with
all accessories pull boxes where ever required, G.I. fish wire,
fixing hardware etc. including the chasing of wall/floor, and PB PIPE
plastering the chased portion, digging the trench and back
filling, making good the damages, sealing of pipe entry etc as
required.
PB PIPE
a) 25 mm dia 10 RM PB PIPE
b) 32 mm dia 10 RM PB PIPE
c) 40 mm dia 10 RM PB PIPE
d) 50 mm dia 10 RM PB PIPE
e) 80 mm dia 10 RM PB PIPE
f) 100 mm dia 10 RM PB PIPE
g) 150 mm dia 10 RM PB PIPE
7.6.2 Flexible Conduits Installation : PB PW
PB PW

VOLTEC ENERGY SYSTEMS Page 98


LABOUR RATE
Supply and installation of following sizes of GI flexible
conduits with all accessories including fixing nipples,
PB PW
couplings and fixing hardware etc as required and as per
specifications.
7.6.2.1 GI flexible conduits : PB PW
PB PW
a) 20 mm dia 100 RM PB PW
b) 25 mm dia 100 RM PB PW
c) 40 mm dia 100 RM PB PW
d) 50 mm dia 100 RM PB PW
PB PW
TOTAL OF CABLES, SUB MAINS, CABLE TRAYS
PB PW
CARRIED OVER TO SUMMARY
8.00 WIRING : PB PW
PB PW
8.10 Point Wiring : PB PW
PB PW
The rates for point wiring shall include the circuit wiring. PB PW
PB PW
Circuit wiring means the wiring from DB / Dimmer panel to the
PB PW
first point of circuit through control switch.
PB PW
Circuit wiring and subsequent looping shall be done with 2.5
PB PW
Sqmm, 1100V grade LSZH insulated stranded, copper wires.
PB PW
The rates of point wiring shall include supply, installation,
testing & commissioning of MS conduit with accessories, GI
Boxes and required GI flexible conduits with accessories up
PB PW
to the Point, LSZH insulated, stranded, Cu. Wire etc. as
required and as per specification, Tender Drawing and
direction of Engineer-in-charge.
PB PW
Where the light points are directly controlled from DB (without
any local control switches), the quoted rates shall not include PB PW
the cost of MCBs etc. in the point wiring.
PB PW
The rates of point wiring shall include earthing of each light,
fan, switches, switch plates, boxes and other non current
PB PW
carrying metallic part with 2.5 Sqm. Stranded copper, LSZH
insulated, stranded, copper wire.
PB PW
8.1.1 Light Points controlled by switch : PB PW
PB PW
a) Single/ First light point con-trolled by a 5Amps switch. 103 No. PB PW
PB PW
b) Same as above but loop point 322 No. PB PW
PB PW
8.1.2 Light Points controlled directly from DB . PB PW
PB PW
i. Single/ First Point Controlled directly by MCB in DB 419 Nos. PB PW
PB PW
ii. Same as above but loop point. 3780 Nos. PB PW
PB PW
8.1.3 Light points controlled by Two Way Switch : PB PW

VOLTEC ENERGY SYSTEMS Page 99


LABOUR RATE
PB PW
One / first light point controlled by two nos. two way 5 Amps.
i) 41 Nos. PB PW
switch.
PB PW
ii) Same as above but loop point. 256 Nos. PB PW
PB PW
8.1.5 Light points controlled by Push Buttons : PB PW
PB PW
i) One light points controlled by One Push Button. 1 Nos. PB PW
PB PW
ii) Two light points controlled by One Push Button. 41 Nos. PB PW
PB PW
iii) Three light points controlled by One Push Button. 45 Nos. PB PW
PB PW
iv) Six light points controlled by Two Push Buttons. 39 Nos. PB PW
PB PW
v) Seven light points controlled by Two Push Buttons. 39 Nos. PB PW
PB PW
vi) Nine light points controlled by Two Push Buttons. 1 Nos. PB PW
8.1.6 Presence Sensor : PB PW
PB PW
Wiring from Presence Sensor to the DB/SwitchBoard/Light
fixtures, including providing Presence Sensor as required and
a) as per approved shop drawing (wiring from DB to light points 208 Nos. PB PW
has already been included in subheads 8.1.1, 8.1.2, 8.1.3,
8.1.4, 8.1.5 above and not to be considered here).
PB PW
8.1.7 6A Socket Points : PB PW
PB PW
Wiring for 6A, BS, switched socket outlet including providing
a) 6A, BS, switched, socket outlet as per specification and 215 Point PB PW
approved shop drawing.
PB PW
8.1.8 FCU Points controlled by 6A Switch : PB PW
PB PW
One / first light point controlled by 6A, BS, switched socket
i) 21 Nos. PB PW
outlet including providing 6A, BS, switched, socket outlet.
PB PW
ii) Same as above but loop point. 38 Nos. PB PW
PB PW
8.20 Power Socket Wiring : PB PW
PB PW
Power Socket Wiring shall include supply, installation, testing
and commissioning of wiring of following points, including,
providing conduits of suitable size, its accessories/Hardware,
PB PW
Junction Boxes, LSZH wires, termination of wires, switches,
socket outlets, Plug tops etc. as required and as per
specification.
PB PW

VOLTEC ENERGY SYSTEMS Page 100


LABOUR RATE
Wiring for 1 No. BS, 16A, switched socket outlet with 4 Sqmm
LSZH insulated stranded copper conductor wires in
recessed/surface black enameled MS conduit including
cutting/filling chases, providing conduit with conduit
8.2.1 accessories, saddles, supply and fixing of 1 No. BS, 16A, 43 Point PB PW
switched outlet with internal wiring in G.I. box, earthing of 3rd
pin with LSZH insulated, green colour 2.5 Sq.mm copper
wire, complete with all accessories as required and as per
approved shop drawing.
PB PW
Wiring for 2 Nos. BS, 16A, switched outlet with 4 Sqmm
LSZH insulated stranded copper conductor wires in
recessed/surface black enameled MS conduit including
cutting/filling chases, providing conduit with conduit
8.2.2 accessories, saddles, supply and fixing of 2 Nos. BS, 16A, 10 Point PB PW
switched outlet with internal wiring in G.I. box, earthing of 3rd
pin with LSZH insulated, green colour 2.5 Sq.mm copper
wire, complete with all accessories as required and as per
approved shop drawing.
PB PW
Wiring for 3 Nos. BS, 16A, switched outlet with 4 Sqmm
LSZH insulated stranded copper conductor wires in
recessed/surface black enameled MS conduit including
cutting/filling chases, providing conduit with conduit
8.2.3 accessories, saddles, supply and fixing of 3 Nos. BS, 16A, 26 Point PB PW
switched outlet with internal wiring in G.I. box, earthing of 3rd
pin with LSZH insulated, green colour 2.5 Sq.mm copper
wire, complete with all accessories as required and as per
approved shop drawing.
Wiring for 4 Nos. BS, 16A, switched outlet with 4 Sqmm
LSZH insulated stranded copper conductor wires in
recessed/surface black enameled MS conduit including
cutting/filling chases, providing conduit with conduit
8.2.4 accessories, saddles, supply and fixing of 4 Nos. BS, 16A, 77 Point PB PW
switched outlet with internal wiring in G.I. box, earthing of 3rd
pin with LSZH insulated, green colour 2.5 Sq.mm copper
wire, complete with all accessories as required and as per
approved shop drawing.
PB PW
Wiring for 5 Nos. BS, 16A, switched outlet with 4 Sqmm
LSZH insulated stranded copper conductor wires in
recessed/surface black enameled MS conduit including
cutting/filling chases, providing conduit with conduit
8.2.5 accessories, saddles, supply and fixing of 5 Nos. BS, 16A, 29 Point PB PW
switched outlet with internal wiring in G.I. box, earthing of 3rd
pin with LSZH insulated, green colour 2.5 Sq.mm copper
wire, complete with all accessories as required and as per
approved shop drawing.
PB PW
Wiring for 6 Nos. BS, 16A, switched outlet with 4 Sqmm
LSZH insulated stranded copper conductor wires in
recessed/surface black enameled MS conduit including
cutting/filling chases, providing conduit with conduit
8.2.6 accessories, saddles, supply and fixing of 6 Nos. BS, 16A, 19 Point PB PW
switched outlet with internal wiring in G.I. box, earthing of 3rd
pin with LSZH insulated, green colour 2.5 Sq.mm copper
wire, complete with all accessories as required and as per
approved shop drawing.
PB PW

VOLTEC ENERGY SYSTEMS Page 101


LABOUR RATE
Wiring for 7 Nos. BS, 16A, switched outlet with 4 Sqmm
LSZH insulated stranded copper conductor wires in
recessed/surface black enameled MS conduit including
cutting/filling chases, providing conduit with conduit
8.2.7 accessories, saddles, supply and fixing of 7 Nos. BS, 16A, 12 Point PB PW
switched outlet with internal wiring in G.I. box, earthing of 3rd
pin with LSZH insulated, green colour 2.5 Sq.mm copper
wire, complete with all accessories as required and as per
approved shop drawing.
PB PW
Wiring for 3 Nos. BS, 16A, switched outlet & 2 Nos. BS 16A
switched outlet in IP-65 enclosure with 4 Sqmm LSZH
insulated stranded copper conductor wires in
recessed/surface black enameled MS conduit including
cutting/filling chases, providing conduit with conduit
8.2.8 accessories, saddles, supply and fixing of Wiring for 3 Nos. 1 Point PB PW
BS, 16A, switched outlet & 2 Nos. BS 16A switched outlet in
IP-65 enclosure with internal wiring in G.I. box, earthing of 3rd
pin with LSZH insulated, green colour 2.5 Sq.mm copper
wire, complete with all accessories as required and as per
approved shop drawing.
Wiring for 2 Nos. BS, 16A, switched outlets in IP-65
enclosure with 4 Sqmm LSZH insulated stranded copper
conductor wires in recessed/surface black enameled MS
conduit including cutting/filling chases, providing conduit with
8.2.9 conduit accessories, saddles, supply and fixing of 2 No. BS, 41 Point PB PW
16A, switched outlets in IP-65 enclosure with internal wiring,
earthing of 3rd pin with LSZH insulated, green colour 2.5
Sq.mm copper wire, complete with all accessories as required
and as per approved shop drawing.
PB PW

Wiring for 2 Nos. BS, 16A, switched outlets and 1 No. 16A
DP Isolators in IP-65 enclosure with 4 Sqmm LSZH insulated
stranded copper conductor wires in recessed/surface black
enameled MS conduit including cutting/filling chases,
providing conduit with conduit accessories, saddles, supply
8.2.10 1 Point PB PW
and fixing of 2 No. BS, 16A, switched outlets and 1 No. 16A
DP Isolator in IP-65 enclosure with internal wiring, earthing of
3rd pin with LSZH insulated, green colour 2.5 Sq.mm copper
wire, complete with all accessories as required and as per
approved shop drawing.

PB PW
Wiring for 3 Nos. BS, 16A, switched outlets and 1 No. 16A DP
Isolator in IP-65 enclosure with 4 Sqmm LSZH insulated
stranded copper conductor wires in recessed/surface black
enameled MS conduit including cutting/filling chases,
providing conduit with conduit accessories, saddles, supply
8.2.11 2 Point PB PW
and fixing of 3 Nos. BS, 16A, switched outlets and 1 No. 16A
DP Isolator in IP-65 enclosure with internal wiring, earthing of
3rd pin with LSZH insulated, green colour 2.5 Sq.mm copper
wire, complete with all accessories as required and as per
approved shop drawing.
PB PW

VOLTEC ENERGY SYSTEMS Page 102


LABOUR RATE

Wiring for 1 No. BS, 16A, switched outlet (Spur Outlet) for
Hand Dryer with 4 Sqmm LSZH insulated stranded copper
conductor wires in recessed/surface black enameled MS
conduit including cutting/filling chases, providing conduit with
8.2.12 conduit accessories, saddles, supply and fixing of 1 No. BS, 43 Point PB PW
16A, switched outlet (Spur Outlet) with internal wiring in G.I.
box, earthing of 3rd pin with LSZH insulated, green colour 2.5
Sq.mm copper wire, complete with all accessories as required
and as per approved shop drawing.

PB PW
Wiring for 1 No. Disabled Alarm Device with 4 Sqmm LSZH
insulated stranded copper conductor wires in
recessed/surface black enameled MS conduit including
cutting/filling chases, providing conduit with conduit
accessories, saddles, supply and fixing of 1 No. Disabled
8.2.13 12 Point PB PW
Alarm Device, Single phase motor of required capacity (As
approved by the Engineer-in-charge) with internal wiring in
G.I. box, earthing with LSZH insulated, green colour 2.5
Sq.mm copper wire, complete with all accessories as required
and as per approved shop drawing.
Wiring for 1 No. 16A DP Isolators in IP-65 enclosure with 4
Sqmm LSZH insulated stranded copper conductor wires in
recessed/surface black enameled MS conduit including
cutting/filling chases, providing conduit with conduit
8.2.14 accessories, saddles, supply and fixing of 1 No. 16A DP 20 Point PB PW
Isolator in IP-65 enclosure with internal wiring, earthing with
LSZH insulated, green colour 2.5 Sq.mm copper wire,
complete with all accessories as required and as per
approved shop drawing.
PB PW

Wiring for 1 No. Floor LV tank consisting of 4 Nos. 6A BS


switched socket and 2 Nos. RJ-45 Data Outlets in IP-65
enclosure, with 4 Sqmm LSZH insulated stranded copper
conductor wires in recessed/surface black enameled MS
conduit including cutting/filling chases, providing conduit with
8.2.15 7 Nos. PB PW
conduit accessories, saddles, supply and fixing of 1 No. Floor
LV tank consisting of 4 Nos. 6A BS switched socket and 2
Nos. RJ-45 Data outlets in IP-65 enclosure, with internal
wiring, earthing with LSZH insulated, green colour 2.5 Sq.mm
copper wire, complete with all accessories as required.

PB PW
Wiring for 2 Nos. 16A 2P+E CEE, switched, industrial type
plug and socket outlet in IP-44 enclosure with 4 Sqmm LSZH
insulated stranded copper conductor wires in
recessed/surface black enameled MS conduit including
cutting/filling chases, providing conduit with conduit
8.2.2 accessories, saddles, supply and fixing of 2 Nos. 16A 2P+E 41 Point PB PW
CEE, switched, industrial type plug and socket outlet in IP-44
enclosure with internal wiring in G.I. box, earthing of 3rd pin
with LSZH insulated, green colour 2.5 Sq.mm copper wire,
complete with all accessories as required and as per
approved shop drawing.
PB PW
8.30 CEE INDUSTRIAL SWITCHED SOCKETS PB PW
PB PW

VOLTEC ENERGY SYSTEMS Page 103


LABOUR RATE
Supply, installation, testing and commissioning of single
phase/three phase, CEE, switched, industrial type plug and
socket outlet in IP-44 enclosure including termination,
8.3.1 earthing etc. in surface/recessed mounting as required, as PB PW
per specifications and approved shop drawings
(Cabling/Conduiting & wiring shall be paid separately under
different items).
PB PW
a) 16A, 2P+E, CEE, switched socket outlet with plug top (IP-44) 82 Nos. PB PW
PB PW
16A, 3P+N+E, CEE, switched socket outlet with plug top (IP-
b) 1 No. PB PW
44)
PB PW
32A, 3P+N+E, CEE, switched socket outlet with plug top (IP-
c) 40 No. PB PW
44).
PB PW
16A, 3P+N+E, CEE, switched socket outlet with plug top (IP-
d) 4 No. PB PW
65) for water heaters.
PB PW
125A, 3P+N+E, CEE, switched socket outlet with plug top (IP-
d) 36 No. PB PW
44)
8.3.2 Socket Combination A PB PW
PB PW
Supply, installation, testing and commissioning of following
Single Phase/3 phase, CEE, switched, Industrial type Plug
and socket Combination Outlet in single enclosure (IP-44)
PB PW
including termination, Earthing etc. in surface/recess
mounting as required. (Conduiting/wiring/cabling for the same
shall be paid seperately under different item).
PB PW
One no. 16A, 2P+E, CEE, switched socket outlets with plug
- PB PW
(IP-44) with 16A TPN MCB,10kA.
PB PW
One no. 16A, 3P+N+E, CEE, switched socket outlets with
- PB PW
plug (IP-44) with 16A TPN MCB,10kA.
PB PW
One no. 32A, 3P+N+E, CEE, switched socket outlets with
- PB PW
plug (IP-44) with 32A TPN MCB,10kA.
PB PW
- One no. 13A, BS switched socket outlet 39 Set PB PW
PB PW
8.3.3 Socket Combination B PB PW
PB PW
Supply, installation, testing and commissioning of following
Single Phase/3 phase, CEE, switched, Industrial type Plug
and socket Combination Outlet in single enclosure (IP-44)
PB PW
including termination, Earthing etc. in surface/recess
mounting as required. (Conduiting/wiring/cabling for the same
shall be paid seperately under different item).
PB PW
Two nos. 16A, 2P+E, CEE, switched socket outlets with plug
- PB PW
(IP-44) with 16A TPN MCB,10kA.
PB PW
One no. 16A, 3P+N+E, CEE, switched socket outlets with
- PB PW
plug (IP-44) with 16A TPN MCB,10kA.
PB PW

VOLTEC ENERGY SYSTEMS Page 104


LABOUR RATE
One no. 32A, 3P+N+E, CEE, switched socket outlets with
- PB PW
plug (IP-44) with 32A TPN MCB,10kA.
PB PW
- Two nos. 13A, BS switched socket outlet 122 Set PB PW
PB PW
8.3.4 Socket Combination C PB PW
PB PW
Supply, installation, testing and commissioning of following
Single Phase/3 phase, CEE, switched, Industrial type Plug
and socket Combination Outlet in single enclosure (IP-44)
PB PW
including termination, Earthing etc. in surface/recess
mounting as required. (Conduiting/wiring/cabling for the same
shall be paid seperately under different item).
PB PW
One no. 16A, 2P+E, CEE, switched socket outlets with plug
- PB PW
(IP-44) with 16A TPN MCB,10kA.
PB PW
One no. 16A, 3P+N+E, CEE, switched socket outlets with
- PB PW
plug (IP-44) with 16A TPN MCB,10kA.
PB PW
One no. 32A, 3P+N+E, CEE, switched socket outlets with
- PB PW
plug (IP-44) with 32A TPN MCB,10kA.
PB PW
One no. 63A, 3P+N+E, CEE, switched socket outlets with
- PB PW
plug (IP-44) with 63A TPN MCB,10kA.
PB PW
- One no. 13A, BS switched socket outlet 1 Set PB PW
8.40 ISOLATORS PB PW
PB PW
Supply, installation, testing and commissioning of isolators in
IP-65 enclosures complete with termination in PB PW
surface/recessed mounting as required.
PB PW
a) 16A Four pole isolator 3 Nos. PB PW
PB PW
b) 63A Four pole isolator 19 Nos. PB PW
PB PW
c) 125A Four pole isolator 2 Nos. PB PW
PB PW
8.50 M.S. Black Conduits : PB PW
PB PW
Supply and installation of following size of MS conduit pipe in
recess or on surface including all accessories MS/CI
pull/junction boxes, GI fish wire, fixing hardware etc
PB PW
including chasing the walls/floor and plastering the chased
portion and making good the damages etc, complete as
required and as per specifications.
PB PW
a) 20 mm dia 20 RM PB PW
b) 25 mm dia 20 RM PB PW
c) 32 mm dia 20 RM PB PW
d) 40 mm dia 20 RM PB PW
e) 50 mm dia 20 RM PB PW
PB PW
8.60 Sub-mains Wiring : PB PW

VOLTEC ENERGY SYSTEMS Page 105


LABOUR RATE
PB PW
Supply and drawing of following sizes of LSZH insulated,
stranded, copper conductor wires of 650/1100 Volts grade in
PB PW
existing conduit pipe /wire ways including connection
/terminations etc as required.
PB PW
a) 2 x 1.5 Sqmm + 1 No. 1.5 Sqmm Copper earth wire 20 RM PB PW
b) 2 x 2.5 Sqmm + 1 No. 1.5 Sqmm Copper earth wire 20 RM PB PW
c) 2 x 4.0 Sqmm + 1 No. 2.5 Sqmm Copper earth wire. 20 RM PB PW
d) 2 x 6.0 Sqmm + 1 No. 2.5 Sqmm Copper earth wire 20 RM PB PW
e) 4 x 4.0 Sqmm + 1 No. 2.5 Sqmm Copper earth wire 20 RM PB PW
f) 4 x 6.0 Sqmm + 1 No. 2.5 Sqmm Copper earth wire 20 RM PB PW
g) 2 x 10.0 Sqmm + 1 No. 6.0 Sqmm Copper earth wire 20 RM PB PW
h) 4 x 10.0 Sqmm + 2 Nos. 6.0 Sqmm Copper earth wire 20 RM PB PW
i) 4 x 16.0 Sqmm + 2 Nos. 10.0 Sqmm Copper earth wire 20 RM PB PW
j) 4 x 25.0 Sqmm + 2 Nos. 16.0 Sqmm Copper earth wire 20 RM PB PW
PB PW
Note: PB PW
PB PW
In false ceiling areas the work is to be co-ordinated with
respect to interior work and rate for point wiring shall include
1) PB PW
flexible conduit/fixing nipples/couplers etc from the junction
box up to the fitting.
PB PW
All wires used for circuit / point wiring shall be Low Smoke
2) PB PW
Zero Halogen (LSZH) wires.
PB PW
TOTAL OF WIRING CARRIED OVER TO SUMMARY PB PW
9.00 LIGHTING FIXTURES : PB LIGHT
PB LIGHT
Inspection, receiving, storing, handling, assembling,
installation, testing and commissioning of wall /ceiling,
surface/ recessed, suspended from down rod, in furniture,
fluorescent / incandescent / Halogen lamp fixtures including
making connections with PVC insulated stranded copper
conductor wires complete including steel supports, PB LIGHT
suspenders, fixing screws, turn buckles, bolts, nuts (down
rods ball and socket arrangement and special channel
mounting for industrial fitting/chandelier) etc, as required. The
mounting arrangement of lighting fixture shall be as indicated
in the approved drawings.
PB LIGHT
Recessed Grid Luminaire 1x36W (Thorn Specalph BS/SB
1.00 87 Set PB LIGHT
1x36W or Equivalent) (T1).
PB LIGHT
Recessed Grid Luminaire 1x36W (Thorn Specalph BS/SB
2.00 1x36W or Equivalent) (T1) complete with emergency lighting 25 Set PB LIGHT
units.
PB LIGHT
Recessed Grid Luminaire 2x36W (Thorn Specalph BS/SB
3.00 2 Set PB LIGHT
2x36W or Equivalent) (T2).
PB LIGHT
Recessed Grid Luminaire 2x36W (Thorn Specalph BS/SB
4.00 2x36W or Equivalent) (T2) complete with emergency lighting 2 Set PB LIGHT
units.
PB LIGHT

VOLTEC ENERGY SYSTEMS Page 106


LABOUR RATE
Recessed Grid Luminaire 1x58W (Thorn Specalph BS/SB
5.00 5 Set PB LIGHT
1x58W or Equivalent) (T3).
PB LIGHT
Recessed Grid Luminaire 1x58W (Thorn Specalph BS/SB
6.00 1x58W or Equivalent) (T3) complete with emergency lighting 1 Set PB LIGHT
units.
PB LIGHT
Surface mounted Industrial Luminaire with 1x36W
7.00 Fluorescent T5 Lamps (Thorn Indus RD 1x36W TW or 154 Set PB LIGHT
Equivalent) (T5).
PB LIGHT
Surface mounted Industrial Luminaire with 1x36W
8.00 Fluorescent T5 Lamps (Thorn Indus RD 1x36W TW or 46 Set PB LIGHT
Equivalent) (T5) complete with emergency lighting units.
PB LIGHT
Surface mounted Industrial Luminaire with 2x36W
9.00 Fluorescent T5 Lamps (Thorn Indus RD 2x36W TW or 92 Set PB LIGHT
Equivalent) (T6).
PB LIGHT
Surface mounted Industrial Luminaire with 2x36W
10.00 Fluorescent T5 Lamps (Thorn Indus RD 2x36W TW or 15 Set PB LIGHT
Equivalent) (T6) complete with emergency lighting units.
PB LIGHT
Surface mounted Industrial Luminaire with 2x58W
11.00 Fluorescent T5 Lamps (Thorn Indus RD 2x58W TW or 441 Set PB LIGHT
Equivalent) (T7).
PB LIGHT
Surface mounted Industrial Luminaire with 2x58W
12.00 Fluorescent T5 Lamps (Thorn Indus RD 2x58W TW or 39 Set PB LIGHT
Equivalent) (T7) complete with emergency lighting units.
PB LIGHT
Wall mounted Luminaire with 1 x 28W Fluorescent T5 Lamp
13.00 waterproof IP44 (Siteco Europlex 24W IP44 or Equivalent) 184 Set PB LIGHT
(T8).
PB LIGHT
Floodlight 400W (Siteco A2 Midi 400W IP65 asym or
14.00 30 Set PB LIGHT
Equivalent) (T10)
PB LIGHT
Bulk Head Light Wall Mounted with 2 x 28W TC-DEL Lamp IP
15.00 165 Set PB LIGHT
65 (Thorn Danube 2x28W IP65 or Equivalent) (T11).
PB LIGHT
Bulk Head Light Wall Mounted with 2 x 28W TC-DEL Lamp IP
16.00 65 (Thorn Danube 2x28W IP65 or Equivalent) (T11) complete 60 Set PB LIGHT
with emergency lighting units.
PB LIGHT
Recessed Downlight 1x26W (Thorn Chalice C 190H 1x26W
17.00 2524 Set PB LIGHT
or Equivalent) (T13)
PB LIGHT
Recessed Downlight 1x26W (Thorn Chalice C 190H 1x26W
18.00 234 Set PB LIGHT
or Equivalent) (T13) complete with emergency lighting units.
PB LIGHT
Recessed Luminaire with 4 x 18W T5 Lamps with Parabolic
19.00 96 Set PB LIGHT
Louvre (Thorn Omega BS/SB 4 x 18W or Equivalent) (T14)
PB LIGHT
Recessed Luminaire with 4 x 18W T5 Lamps with Parabolic
20.00 Louvre (Thorn Omega BS/SB 4 x 18W or Equivalent) (T14) 10 Set PB LIGHT
complete with emergency lighting units.

VOLTEC ENERGY SYSTEMS Page 107


LABOUR RATE
PB LIGHT
Recessed Quad 2 x 18W (Thorn Matrix 300 2 x 18W or
21.00 35 Set PB LIGHT
Equivalent) (T15)
PB LIGHT
Recessed Quad 2 x 18W (Thorn Matrix 300 2 x 18W or
22.00 3 Set PB LIGHT
Equivalent) (T15) complete with emergency lighting units.
PB LIGHT
Recessed outside Downlight IP54 (Trilux Downlight IP54 or
23.00 760 Set PB LIGHT
Equivalent) (T21)
PB LIGHT
Recessed outside Downlight IP54 (Trilux Downlight IP54 or
24.00 36 Set PB LIGHT
Equivalent) (T21) complete with emergency lighting units.
PB LIGHT
Recessed Luminaire 2 x 58W IP65 (Thorn Duopre 2 x 58W
25.00 311 Set PB LIGHT
T26 H2F or Equivalent) (T23).
PB LIGHT
Recessed Luminaire 2 x 58W IP65 (Thorn Duopre 2 x 58W
26.00 T26 H2F or Equivalent) (T23) complete with emergency 9 Set PB LIGHT
lighting units.
PB LIGHT
Wall Luminaire 2x36W IP44 (Bega 4422-2 TC-L 2x36W IP44
27.00 29 Set PB LIGHT
or Equivalent) (T30)
PB LIGHT
Emergency Exit Up Fixture (Cooper/Crompton or Equivalent)
28.00 200 Set PB LIGHT
complete with emergency lighting units.
PB LIGHT
Emergency Exit Down Fixture (Cooper/Crompton or
29.00 58 Set PB LIGHT
Equivalent) complete with emergency lighting units.
PB LIGHT
Emergency Exit Left Fixture (Cooper/Crompton or Equivalent)
30.00 46 Set PB LIGHT
complete with emergency lighting units.
PB LIGHT
Emergency Exit Right Fixture (Cooper/Crompton or
31.00 22 Set PB LIGHT
Equivalent) complete with emergency lighting units.
PB LIGHT
TOTAL OF LIGHTING FIXTURES CARRIED OVER TO
PB LIGHT
SUMMARY
10.00 EARTHING & LIGHTNING PROTECTION SYSTEM : PB EARTH
PB EARTH
10.10 Earthing System: PB EARTH
PB EARTH

Supply, installation, testing and commissioning of copper


plate earthing stations making earth pits, earthing with copper
earth plate 600 mm x 600 mm x 3.15 mm thick including
funnel, charcoal/coke, salt, all earth work. Providing masonry
10.1.1 8 Nos. PB EARTH
enclosure with 10 mm thick C.I. cover plate having locking
arrangement and watering pipe, disconnecting/ testing links
etc as per IS –3043 complete as required, as per
specifications, drawings and direction of Engineer-in-charge.

PB EARTH

VOLTEC ENERGY SYSTEMS Page 108


LABOUR RATE
Supply, installation, testing and commissioning of GI plate
earthing stations making earth pits, earthing with GI earth
plate 600 mm x 600 mm x 6.30 mm thick including funnel,
charcoal/coke, salt, all earth work. Providing masonry
10.1.2 21 Nos. PB EARTH
enclosure with 10 mm thick C.I. cover plate having locking
arrangement and watering pipe, disconnecting/ testing links
etc as per IS–3043 complete as required, as per
specifications, drawing and direction of Engineer-in-charge.
PB EARTH
Supply, installation, testing and commissioning of GI Pipe
earthing stations making earth pits, earthing with GI pipe
4500 mm x 40 mm Dia including funnel, charcoal/coke, salt,
all earth work. Providing masonry enclosure with 10 mm thick
10.1.3 2 Nos. PB EARTH
C.I. cover plate having locking arrangement and watering
pipe, disconnecting/ testing links etc as per IS–3043 complete
as required as per specifications, drawing and direction of
Engineer-in-charge.
PB EARTH
10.1.4 Earthing Strip/Tape/Cables : PB EARTH
PB EARTH
Supply, installation, testing and commissioning of following
sizes of GI/Tinned Copper strip/tape clamped to walls, cable
trays, bus ducts, recess in Ground or surface etc for
equipment/ System earthing complete as required including
PB EARTH
inter connection between length at joints, all fixing
accessories saddles, clamps etc and other fixing hardware
material as required, as per specifications, detail drawings
shall be included for proper installation.
PB EARTH
10.1.4.
G.I. Earthing strip/tape : PB EARTH
1
PB EARTH
a 75 x 8 mm strip 50 RM PB EARTH
b 75 x 6 mm strip 50 RM PB EARTH
c 50 x 6 mm strip 10 RM PB EARTH
d 40 x 6 mm strip 50 RM PB EARTH
e 32 x 6 mm strip 10 RM PB EARTH
f 25 x 6 mm strip 50 RM PB EARTH
g 25 x 3 mm strip 1100 RM PB EARTH
PB EARTH
10.1.4.
Tinned Copper earthing strip/tape : PB EARTH
2
PB EARTH
a) 50 x 6 mm 10 RM PB EARTH
b) 32 x 6 mm 10 RM PB EARTH
c) 25 x 6 mm 10 RM PB EARTH
d) 25 x 3 mm 10 RM PB EARTH
PB EARTH
Supply, installation, Termination, testing and commissioning
of PVC insulated, stranded copper conductor cable, laid on
10.1.5 surface/cable tray/duct/undger ground/Trench etc. as PB CAB
required, as per approved shop drawing, site conditions and
as directed by Engineer-in-charge.
PB CAB
a) 1C x 240 Sqm 200 RM PB CAB
PB CAB
b) 1C x 185 Sqm 300 RM PB CAB

VOLTEC ENERGY SYSTEMS Page 109


LABOUR RATE
PB CAB
c) 1C x 90 Sqm 500 RM PB CAB
PB CAB
d) 1C x 50 Sqm 2000 RM PB CAB
PB CAB
Supply, installation, Termination, testing and Commissioning
of following sizes tinned Cu/GI Earth Bars including its
10.1.6 PB EARTH
supporting/fixing hardware, as per drawings, specifications
and as directed by Engineer-in-charge.
PB EARTH
10.1.6.
75 x 6 mm GI Earth Bars. PB EARTH
1
PB EARTH
a) 300 mm 1 No. PB EARTH
b) 500 mm 1 Nos. PB EARTH
c) 750 mm 1 Nos. PB EARTH
d) 1000 mm 1 No. PB EARTH
PB EARTH
10.1.6.
50 x 6 mm GI Earth Bars. PB EARTH
2
PB EARTH
a) 300 mm 1 Nos. PB EARTH
b) 500 mm 1 Nos. PB EARTH
c) 750 mm 1 Nos. PB EARTH
d) 1000 mm 1 Nos. PB EARTH
PB EARTH
10.1.6.
75 x 6 mm tinnned Cu Earth Bars. PB EARTH
3
PB EARTH
a) 300 mm 1 No. PB EARTH
b) 500 mm 3 Nos. PB EARTH
c) 750 mm 3 Nos. PB EARTH
d) 1000 mm 1 No. PB EARTH
PB EARTH
10.1.6.
50 x 6 mm tinned Cu Earth Bars. PB EARTH
4
PB EARTH
a) 300 mm 25 Nos. PB EARTH
b) 500 mm 30 Nos. PB EARTH
c) 750 mm 30 Nos. PB EARTH
d) 1000 mm 10 Nos. PB EARTH
10.20 Lightning Protection System: PB EARTH
PB EARTH

Supply, installation, testing and commissioning of copper


plate earthing stations making earth pits, earthing with copper
earth plate 600 mm x 600 mm x 3.15 mm thick including
funnel, charcoal/coke, salt, all earth work. Providing masonry
10.2.1 2 Nos. PB EARTH
enclosure with 10 mm thick C.I. cover plate having locking
arrangement and watering pipe, disconnecting/ testing links
etc as per IS –3043 complete as required, as per drawings,
specifications and direction of Engineer-in-charge.

PB EARTH

VOLTEC ENERGY SYSTEMS Page 110


LABOUR RATE
Supply, installation, testing and commissioning of GI Pipe
earthing stations making earth pits, earthing with GI pipe
4500 mm x 40 mm Dia including funnel, charcoal/coke, salt,
all earth work. Providing masonry enclosure with 10 mm thick
10.2.2 44 Nos. PB EARTH
C.I. cover plate having locking arrangement and watering
pipe, disconnecting/ testing links etc as per IS–3043 complete
as required, as per drawings, specifications and direction of
Engineer-in-charge.
PB EARTH
10.2.3 Earthing Strip/Wires : PB EARTH
PB EARTH

Supply, installation, testing and commissioning of following


sizes of GI strip/wire clamped to walls, Ductwork, pipe work,
Structural steel work, cladding work etc. in recess or surface
etc for Lightning Protection System complete as required
including inter connection, terminations, between length at
joints, all fixing accessories saddles, plastic isolator mounting PB EARTH
(of 50mmx80mm approx.), Sealing Collars, Sealing Strip,
Squared Timber Block (80mmx100mm approx.), clamps,
Lugs etc and other fixing hardware material as required for
proper installation as per detail drawings, specifications and
direction of Engineer-in-charge.

PB EARTH
a) 25 x 3 mm strip 1100 RM PB EARTH
PB EARTH
b) 25 x 6 mm strip 2400 RM PB EARTH
PB EARTH
Supply, installation, Termination, testing and Commissioning
of following sizes GI Earth Bars including in supporting/fixing
10.2.4 PB EARTH
hardware, as per drawings, specifications and as directed by
Engineer-in-charge.
PB EARTH
10.2.4.
75 x 6 mm GI Earth Bars. PB EARTH
1
PB EARTH
a) 300 mm 2 Nos. PB EARTH
b) 500 mm 2 Nos. PB EARTH
c) 750 mm 2 Nos. PB EARTH
d) 1000 mm 2 Nos. PB EARTH
PB EARTH
10.2.4.
50 x 6 mm GI Earth Bars. PB EARTH
2
PB EARTH
a) 300 mm 2 Nos. PB EARTH
b) 500 mm 2 Nos. PB EARTH
c) 750 mm 2 Nos. PB EARTH
d) 1000 mm 2 Nos. PB EARTH
Supply and fixing of Lightning Arrestor Rod/Lightning
Conductor finial made of 25 mm dia, 2.0 mm thick & 300 mm
Long GI Tube having single prong at top with 75 mm dia, 6
10.2.5 130 Nos. PB EARTH
mm thick Base plate, including connections with roof parapit
Lightning protection Conductors, as per detailed drawings
and as per direction of Engineer-in-charge.
PB EARTH

VOLTEC ENERGY SYSTEMS Page 111


LABOUR RATE
Supply and fixing of "Earth Test Joints" encased in 200 mm
(H) x 150 mm (W) x 100 mm (D) recessed in concrete with
10.2.6 44 Nos. PB EARTH
removable cover plate as per detailed drawing and as per
direction of Engineer-in-charge.
PB EARTH
TOTAL OF EARTHING & LIGHTNING PROTECTION
PB EARTH
SYSTEM CARRIED OVER TO SUMMARY
MC-1 EARTH
MC-1 MC-1 EARTH
1.00 11 KV, GAS INSULATED, RING MAIN UNITS: MC-1 HTO
MC-1 HTO
Safe Unloading, Receiving, storing, checking, handling,
installation, testing and commissioning of 350 MVA, 11 KV
1.10 MC-1 HTO
indoor 4 way, SF6 insulated, Extensible Ring Main Breaker
Unit consisting of following :-
MC-1 HTO
Two (2) Nos. 630 Amp, TP VCB with disconnector and Earth
a) Switch as Incommers, with required Indication, Metering and MC-1 HTO
Protection System.
MC-1 HTO
Two (2) Nos. 630 Amp, TP VCB with disconnector and Earth
b) Switch as Outgoings, with required Indication, Metering & 1 Set MC-1 HTO
Protection System.
MC-1 HTO
Notes : MC-1 HTO
MC-1 HTO
Installation shall include supply of all Hardware material
i) (excluding civil work) as required and as per Approved Shop MC-1 HTO
Drawings.
MC-1 HTO
Necessary Co-ordination with client and manufacturer to be
ii) done by the contractor for successful installation, Testing and MC-1 HTO
Commissioning.
MC-1 HTO
1.20 Battery & Battery Charger : MC-1 BATT
MC-1 BATT
Supply, installation, testing & commissioning of 200 AH
capacity, Ni-cd maintenance free batteries, duly charged,
complete with seasoned teak wood stand, connecting lead
a) MC-1 BATT
as required for 11 KV RMU boards and some other control
loads. (AH calculation to be submitted by successful bidder in
co-ordination with the client and 11 KV, RMU Vendor).
MC-1 BATT
i) for 24V DC System ur Set MC-1 BATT
MC-1 BATT
ii) for 110V DC System 1 Set MC-1 BATT
MC-1 BATT
Supply, installation, testing & commissioning of suitable float
cum boost battery charger and necessary distribution board
with 12 Nos. 16A outgoing feeders, instrument panel, Amp,
b) MC-1 BATT
Volts meter, interconnections etc. power supply 240 V, 1
phase, 50 Hz ± 10%. Charger trouble annunciation shall be
provided through potential free contacts.
MC-1 BATT
i) for 24V DC System ur Set MC-1 BATT
MC-1 BATT
ii) for 110V DC System 1 Set MC-1 BATT

VOLTEC ENERGY SYSTEMS Page 112


LABOUR RATE
TOTAL OF 11 KV, GAS INSULATED, RING MAIN UNITS
MC-1 BATT
CARRIED OVER TO SUMMARY
2.00 H T CABLING : MC-1 CAB
MC-1 CAB
2.10 11kV Cable laying : MC-1 CAB
MC-1 CAB

Supplying, laying, testing and commissioning of 11 KV grade


copper conductor, cross linked polyethylene (XLPE) insulated
individual core screened extruded inner sheath, flat steel/strip MC-1 CAB
armoured PVC sheathed cable and suitable for (E) system
complete as required and as per specification, as follows:

MC-1 CAB
2.1.1 Underground: MC-1 CAB
MC-1 CAB
Supply and laying of following size of 11 KV cables in earth
as per drawing, specifications and direction of engineer in MC-1 CAB
charge.
MC-1 CAB
a) 3C x 400 Sqmm, 11KV XLPE 10 Mtr MC-1 CAB
MC-1 CAB
b) 3C x 300 Sqmm, 11KV XLPE 10 Mtr MC-1 CAB
MC-1 CAB
c) 3C x 240 Sqmm, 11KV XLPE 10 Mtr MC-1 CAB
MC-1 CAB
d) 3C x 185 Sqmm, 11KV XLPE 10 Mtr MC-1 CAB
MC-1 CAB
e) 3C x 150 Sqmm, 11KV XLPE 10 Mtr MC-1 CAB
MC-1 CAB
f) 3C x 120 Sqmm, 11KV XLPE 10 Mtr MC-1 CAB
MC-1 CAB
g) 3C x 95 Sqmm, 11KV XLPE 10 Mtr MC-1 CAB
MC-1 CAB
h) 3C x 70 Sqmm, 11KV XLPE 10 Mtr MC-1 CAB
MC-1 CAB
i) 3C x 50 Sqmm, 11KV XLPE 10 Mtr MC-1 CAB
MC-1 CAB
2.1.2 In hume pipe/trays/trenches : MC-1 CAB
MC-1 CAB
Supply and laying of following sizes of 11KV cables on
already laid trays/hume pipes/walls/ trench etc, as required,
MC-1 CAB
as per drawing, specifications and direction of Engineer-in-
charge..
MC-1 CAB
a) 3C x 400 Sqmm, 11KV XLPE 10 Mtr. MC-1 CAB
MC-1 CAB
b) 3C x 300 Sqmm, 11KV XLPE 10 Mtr MC-1 CAB
MC-1 CAB
c) 3C x 240 Sqmm, 11KV XLPE 50 Mtr MC-1 CAB
MC-1 CAB
d) 3C x 185 Sqmm, 11KV XLPE 10 Mtr MC-1 CAB
MC-1 CAB
e) 3C x 150 Sqmm, 11KV XLPE 10 Mtr MC-1 CAB

VOLTEC ENERGY SYSTEMS Page 113


LABOUR RATE
MC-1 CAB
f) 3C x 120 Sqmm, 11KV XLPE 10 Mtr MC-1 CAB
MC-1 CAB
g) 3C x 95 Sqmm, 11KV XLPE 10 Mtr MC-1 CAB
MC-1 CAB
h) 3C x 70 Sqmm, 11KV XLPE 10 Mtr MC-1 CAB
MC-1 CAB
i) 3C x 50 Sqmm, 11KV XLPE 10 Mtr MC-1 CAB
MC-1 CAB
2.20 End Termination (HT) : MC-1 TERM
MC-1 TERM
Cable jointing of 11 KV grade, XLPE insulated, armoured,
Copper Conductor cable with suitable cable termination KITS
including all accessories i.e. Sockets, lugs, gland etc as MC-1 TERM
required, as per drawings, specifications and direction of
Engineer-in-charge.
MC-1 TERM
a) 3C x 400 Sqmm, 11KV XLPE 1 Set MC-1 TERM
MC-1 TERM
b) 3C x 300 Sqmm, 11KV XLPE 1 Set MC-1 TERM
MC-1 TERM
c) 3C x 240 Sqmm, 11KV XLPE 4 Set MC-1 TERM
MC-1 TERM
d) 3C x 185 Sqmm, 11KV XLPE 1 Set MC-1 TERM
MC-1 TERM
e) 3C x 150 Sqmm, 11KV XLPE 1 Set MC-1 TERM
MC-1 TERM
f) 3C x 120 Sqmm, 11KV XLPE 1 Set MC-1 TERM
MC-1 TERM
g) 3C x 95 Sqmm, 11KV XLPE 1 Set MC-1 TERM
MC-1 TERM
h) 3C x 70 Sqmm, 11KV XLPE 1 Set MC-1 TERM
MC-1 TERM
i) 3C x 50 Sqmm, 11KV XLPE 1 Set MC-1 TERM
MC-1 TERM
2.30 End Termination (HT) : MC-1 TERM
MC-1 TERM
Cable jointing of 11 KV grade, XLPE insulated, armoured,
Aluminium Conductor cable with suitable cable termination
KITS including all accessories i.e. Sockets, lugs, gland etc as MC-1 TERM
required, as per drawings, specifications and direction of
Engineer-in-charge.
MC-1 TERM
a) 3C x 400 Sqmm, 11KV XLPE 1 Set MC-1 TERM
MC-1 TERM
b) 3C x 300 Sqmm, 11KV XLPE 2 Set MC-1 TERM
MC-1 TERM
c) 3C x 240 Sqmm, 11KV XLPE 2 Set MC-1 TERM
MC-1 TERM
d) 3C x 185 Sqmm, 11KV XLPE 1 Set MC-1 TERM
MC-1 TERM
e) 3C x 150 Sqmm, 11KV XLPE 1 Set MC-1 TERM

VOLTEC ENERGY SYSTEMS Page 114


LABOUR RATE
MC-1 TERM
f) 3C x 120 Sqmm, 11KV XLPE 1 Set MC-1 TERM
MC-1 TERM
g) 3C x 95 Sqmm, 11KV XLPE 1 Set MC-1 TERM
MC-1 TERM
h) 3C x 70 Sqmm, 11KV XLPE 1 Set MC-1 TERM
MC-1 TERM
i) 3C x 50 Sqmm, 11KV XLPE 1 Set MC-1 TERM
MC-1 TERM
Notes : MC-1 TERM
MC-1 TERM
The cable and cable terminations quantities given above, are
approximate. The contractor shall measure the cables
1.00 MC-1 TERM
required at site and procurement order shall be place
accrodingly.
MC-1 TERM
Wherever copper cable to be connected to Aluminium Bus
2.00 MC-1 TERM
Bar or vis-à-vis., Bimetalic lugs to be used for terminations.
MC-1 TERM
TOTAL OF H.T CABLING CARRIED OVER TO SUMMARY MC-1 TERM
3.00 SUB STATION SAFETY EQUIPMENT : MC-1 MISC
MC-1 MISC
Supplying and fixing 1000 mm x 900 mm wide checkered
3.10 rubber matting conforming to IS 15652-2006 complete as MC-1 MISC
required.
MC-1 MISC
a) 11 KV grade size 1000 x 900 x 25 mm thick 5 Nos. MC-1 MISC
MC-1 MISC
b) 1100 V grade size 1000 x 900 x 15 mm thick 5 Nos. MC-1 MISC
MC-1 MISC
Supplying & fixing standard shock treatment charts in English
3.20 & Hindi / (Local Language) duly framed and covered with 1 No. MC-1 MISC
glass.
MC-1 MISC
Providing & fixing HT danger notice plate 200 mm x 150 mm
made of mild steel atleast 2mm thick & vitreous enameled
3.30 5 Nos. MC-1 MISC
white on both sides and with inscription in signal red colour
with skull & bone on front side as required.
MC-1 MISC
3.40 Providing 11 KV tested hand gloves. 1 Pair MC-1 MISC
MC-1 MISC
3.50 Providing 11 KV insulated grounding rod. 1 No. MC-1 MISC
MC-1 MISC
3.60 Providing first aid box as per IS:13115. 1 Set MC-1 MISC
MC-1 MISC
TOTAL OF SUB STATION SAFETY EQUIPMENT CARRIED
MC-1 MISC
OVER TO SUMMARY
4.00 TRANSFORMER: MC-1 TRAFO
MC-1 TRAFO

VOLTEC ENERGY SYSTEMS Page 115


LABOUR RATE
Unloading,Receiving, storing, handling, installation, testing
and commissioning of 11 kV/ 400V (terminal voltage), 3
phase, 50 Hz delta/star connected, copper winding. indoor
type, natural air cooled, dry type, cast resin transformer of
following ratings, complete with all fittings such as
thermometer, off circuit tap changer with + 5 % to –15%, MC-1 TRAFO
tapping at the step of 2.5% bi-directional roller, diagrams &
rating plate & Winding temperature indicator, lifting lugs, H. T.
cable box/ LT Terminal Box suitable for bus duct / Cable
termination etc. complete as per relevant specifications,
drawings and direction of Engineer-in-charge.
MC-1 TRAFO
a) 2000 KVA ur Set MC-1 TRAFO
b) 1600 KVA 2 Set MC-1 TRAFO
c) 1250 KVA ur Set MC-1 TRAFO
d) 1000 KVA ur Set MC-1 TRAFO
e) 800 KVA ur Set MC-1 TRAFO
f) 630 KVA ur Set MC-1 TRAFO
g) 500 KVA ur Set MC-1 TRAFO
h) 315 KVA ur Set MC-1 TRAFO
MC-1 TRAFO
Notes : MC-1 TRAFO
MC-1 TRAFO
Installation rate shall include unloading, receiving including
storage at site,assembly, erection, testing and commissioning
i) MC-1 TRAFO
etc. as required, as per approved Shop Drawing and as per
direction of Engineer-in-charge..
MC-1 TRAFO
Necessary co-ordination with the manufacturer and client
ii) MC-1 TRAFO
shall be done by the contractor without extra cost.
MC-1 TRAFO
TOTAL OF TRANSFORMER CARRIED OVER TO
MC-1 TRAFO
SUMMARY
MC-1 BBT
5.0 BUS DUCT/BUS BAR TRUNKING SYSTEM : MC-1 BBT
MC-1 BBT
5.1 Bus Duct : MC-1 BBT
MC-1 BBT
Design, manufacturing, supply, installation, testing &
commissioning (at site) of sheet steel enclosed 3 phase &
neutral, 400V, 50 Hz., 50 KA copper conductor bus duct with
insulation of thermal rating confirming to class 'H' including
bends, transposition piece, expansion joint, Tees, End MC-1 BBT
termination units, Feeder units, tap off unit etc. with all flexible
connections as per specifications and drawings with all
accessories, supports and termination of bus duct to
switchgear/transformer.
MC-1 BBT
a) 3000A, 50kA @ 1 Sec., TP+N, Bus Duct (IP.55) with 8 Nos.
of Terminations and all other accessories as required as per MC-1 BBT
specifications, and approved Shop Drawings. RM R.O.
MC-1 BBT
b) 2000A, 50kA @ 1 Sec., TP+N, Bus Duct (IP.55) with 4 Nos.
of Terminations and all other accessories as required as per MC-1 BBT
specifications, and approved Shop Drawings. RM R.O.
MC-1 BBT

VOLTEC ENERGY SYSTEMS Page 116


LABOUR RATE
c) 2500A, 50kA @ 1 Sec., TP+N, Bus Duct (IP.55) with 4 Nos.
of Terminations and all other accessories as required as per MC-1 BBT
specifications, and approved Shop Drawings. RM 55
MC-1 BBT
5.2 Bus Bar Trunking (BBT) : MC-1 BBT
MC-1 BBT
5.2.1 Design, manufacture, assembly, supply, installation, testing
and commissioning (at site) of following capacity compact,
Copper Conductor, Bus Bar Trunking System including
Bends, Tees, Expansion Joints, Feeder Units, Tap off Units,
Transposition pieces, Flexible Connections etc. with all other MC-1 BBT
Hardware/accessories required for installation of Bus Bar
Trunking as per Specifications, approved Shop Drawings and
instruction of Engineer-in-charge.
MC-1 BBT
Shutter type spring loaded arrangements shall be provided
for tap off system. The shutter shall get closed when tap off
MC-1 BBT
box is taken out. Tap off facilities shall be there at every 500
mm interval as per standard.
MC-1 BBT
i) 1500A, TPN+E, 400 Volt, 40 KA, compact, copper conductor
MC-1 BBT
BBT. RM R.O.
MC-1 BBT
ii) 1250 A, TPN+E, 400 Volt, 40 KA, compact, copper Conductor
MC-1 BBT
BBT. RM R.O.
MC-1 BBT
iii) 1200 A, TPN+E, 400 Volt, 40 KA, compact, copper Conductor
MC-1 BBT
BBT. RM R.O.
MC-1 BBT
iv) 1000 A, TPN+E, 400 Volt, 40 KA, compact, copper Conductor
MC-1 BBT
BBT. RM R.O.
MC-1 BBT
v) 800 A, TPN+E, 400 Volt, 40 KA, compact, copper Conductor
MC-1 BBT
BBT. RM R.O.
vi) 630 A, TPN+E, 400 Volt, 40 KA, compact, copper Conductor
MC-1 BBT
BBT. RM 10
MC-1 BBT
vii) 400 A, TPN+E, 400 Volt, 40 KA, compact, copper Conductor
MC-1 BBT
BBT. RM 10
MC-1 BBT
viii) 250 A, TPN+E, 400 Volt, 40 KA, compact, copper Conductor
MC-1 BBT
BBT. RM 10
MC-1 BBT
ix) 200 A, TPN+E, 400 Volt, 40 KA, compact, copper Conductor
MC-1 BBT
BBT. RM 10
MC-1 BBT
Notes: MC-1 BBT
MC-1 BBT
a) The quantity mentioned above is approximate. Bidder to
procure /manufacture the items as per actual site MC-1 BBT
measurement & approved Shop drawings.
MC-1 BBT
b) Rates shall be inclusive of all accessories & fittings. MC-1 BBT
MC-1 BBT

VOLTEC ENERGY SYSTEMS Page 117


LABOUR RATE
5.2.2 Design, manufacture, assembly, supply, installation, testing
and commissioning of plug-in type TPN tap off box of
following capacity on the existing Bus Bar Trunking and
MC-1 BBT
complete with TPN MCCBs, links, interconnections, earthing
etc. as required, as per specifications and as per approved
Shop drawings.
MC-1 BBT
i) 250A, TPN MCCB Tap off box. No. 1 MC-1 BBT
MC-1 BBT
ii) 125A TPN MCCB Tap off box. No. 1 MC-1 BBT
MC-1 BBT
iii) 100A TPN MCCB Tap off box. No. 1 MC-1 BBT
MC-1 BBT
iv) 80A TPN MCCB Tap off box. No. 1 MC-1 BBT
MC-1 BBT
v) 63A TPN MCCB Tap off box. No. 1 MC-1 BBT
MC-1 BBT
vi) 40A TPN MCCB Tap off box. No. 1 MC-1 BBT
MC-1 BBT
vii) 32A TPN MCCB Tap off box. No. 1 MC-1 BBT
MC-1 BBT
5.2.3 Design, Manufacture, Supply, installation, testing and
commissioning of End Feed Box/Bus Bar Trunking Adapter
Box, of following ratings with Digital Voltmeter & Ammeter
(ELF 3259 of Conzerv or Equivalent) complete with 5VA, MC-1 BBT
class 1.0 CTs of required ratio and one set of phase
indication lamps and back-up SPMCBs, as per approved
drawing and specifications.
MC-1 BBT
a) 1500 Amp with 1600 Amp, TPN, 40 KA, MDO ACB. Nos. R.O. MC-1 BBT
MC-1 BBT
b) 1250 Amp with 1250 Amp, TPN, 40 KA, MDO ACB. Nos. R.O. MC-1 BBT
MC-1 BBT
c) 1200 Amp with 1200 Amp, TPN, 40 KA, MDO ACB. Nos. R.O. MC-1 BBT
MC-1 BBT
d) 1000 Amp with 1000 Amp, TPN, 40 KA, MDO ACB. Nos. R.O. MC-1 BBT
MC-1 BBT
e) 800 Amp with 800 Amp, TPN, 40 KA, MDO ACB. No. 1 MC-1 BBT
MC-1 BBT
f) 630 Amp with 630 Amp, TPN, 40 KA, MCCB. No. 1 MC-1 BBT
g) 400 Amp with 400 Amp, TPN, 40 KA, MCCB. No. 1 MC-1 BBT
MC-1 BBT
h) 250 Amp with 250 Amp, TPN, 40 KA, MCCB. No. 1 MC-1 BBT
MC-1 BBT
MC-1 BBT
Design, Manufacturing, Supply, installation, testing and
5.2.4 commissioning of Bus Coupler panels with ACB/MCCB of MC-1 PANEL
following ratings for Bus Duct/Bus Bar Trunking System.
MC-1 PANEL

The Bus Coupler panel shall consist of 400V, 40 KA@ 1 Sec,


4 pole, Draw out type, Electrically operated, ACB/MCCB
- complete with under voltage and shunt trip release, MC-1 PANEL
antipumping protection, ON/OFF indication lamps etc. as
required, as per specifications and approved Shop drawings.

VOLTEC ENERGY SYSTEMS Page 118


LABOUR RATE
MC-1 PANEL
Bus Couper Panel shall be suitable for Termination of
- Compact Bus Bar Trunking from Top/Bottom as per approved MC-1 PANEL
shop drawing.
MC-1 PANEL
Bus Coupler Breaker shall have suitable No. of NO/NC
- contacts for required interlocking with the Breakers of End MC-1 PANEL
feed units of Bus Bar Trunking.
MC-1 PANEL
Bus Coupler Panel with 1000 Amp, 400V, 40 KA @ 1 Sec, 4
a) ur Nos. MC-1 PANEL
Pole, EDO ACB
MC-1 PANEL
Bus Coupler Panel with 800 Amp, 400V, 40 KA @ 1 Sec, 4
b) ur Nos. MC-1 PANEL
Pole, EDO ACB
MC-1 PANEL
Bus Coupler Panel with 630 Amp, 400V, 40 KA @ 1 Sec, 4
c) ur Nos. MC-1 PANEL
Pole, Motorised MCCB
MC-1 PANEL
Notes: MC-1 PANEL
MC-1 PANEL
The fabrication of bus duct/Bus Bar Trunking shall be taken
up only after actual measurement and site routing. Necessary
i) bends/transposition pieces/ expansion joints etc. shall be MC-1 PANEL
estimated & included. Payment will be made on running
meter basis.
MC-1 PANEL
The supply and fabrication & installation of structural steel for
ii) bus duct/Bus Bar Trunking support is included in the above MC-1 PANEL
items.
MC-1 PANEL
TOTAL OF BUS DUCT/BUS BAR TRUNKING SYSTEM
MC-1 PANEL
CARRIED OVER TO SUMMARY
6.000 LV SWITCHGEAR PANELS & DISTRIBUTION BOARDS: MC-1 PANEL
MC-1 PANEL
LV SWITCHGEAR PANELS : MC-1 PANEL
MC-1 PANEL

Design, manufacture, supply, unloading, receiving, storing,


handling, installation, testing and commissioning of following
LV panels suitable for 400 V, 3 phase, 4 wire, 50 Hz power
distribution system. The panel shall be Indoor, free standing,
floor mounting, sheet metal clad, cubicle, dead front, dust and
vermin proof type compartmentalised design fabricated out of
14 SWG CRCA sheet steel, complete with colour coded, heat
shrinkable PVC insulated, Copper bus bars and separate
earth bus bar of adequate cross section through out the MC-1 PANEL
length of the panel. The incoming and outgoing feeders shall
be accommodated in a fully segregated, modular multitier
arrangement with adequate size and distinct cable alley, bus
bar alley/chamber. The panel shall be complete with name
plate, earthing, numbering, danger plate etc. as required and
as per specifications and drawings. The panel shall withstand
the fault level of as indicated elsewhere or shown in Single
Line Diagram (Dwg No. E/SP/ME1 5.S.01.01.REV. B).

MC-1 PANEL
Important Notes: Common for all Switchboard: MC-1 PANEL
MC-1 PANEL

VOLTEC ENERGY SYSTEMS Page 119


LABOUR RATE

The BOQ shall be read inconjunction with general notes,


specification and Single Line Diagram (Dwg. No. E/SP/ME1
5.S.01.01.REV B). Incase of any discrepancy between
1.000 MC-1 PANEL
specification, BOQ and SLD, the same shall be brought to the
notice of Employer before quoting the rates, otherwise
stringent condition shall be deemed to have been considered.

MC-1 PANEL
2.000 Fault current wherever mentioned shall be Ics value. MC-1 PANEL
MC-1 PANEL
All MCCB shall be provided with door interlocked rotary
handle with ON/OFF/Trip position indicator, microprocessor
3.000 based releases for over current, selectable short circuit and MC-1 PANEL
instentaneous short circuit protection (settable at site). I/C
MCCB shall be provided with E/F release/ protection also.
MC-1 PANEL
4.000 All feeder doors shall have pad locking arrangement. MC-1 PANEL
MC-1 PANEL
5.000 All TP feeders shall have solid isolable neutral link. MC-1 PANEL
MC-1 PANEL
All MCCB used in starter feeder shall be suitable for motor
6.000 MC-1 PANEL
duty application.
MC-1 PANEL
7.000 All power contactors including NIC shall be of AC3 duty. MC-1 PANEL
MC-1 PANEL
All ACB's shall be with micro processor based O/C and S/C
releases and Breaker Control Switch (BCS) having lost
8.000 MC-1 PANEL
motion device. I/C ACBs shall be provided with E/F release
also. Bus coupler shall be provided without releases.
MC-1 PANEL
Spare contacts of ACB/Relays/Contactor etc. shall be wired
9.000 MC-1 PANEL
upto terminal block.
All switchgear used in starter feeder shall be type-2 co-
10.000 ordinated. Manufacturer is required to submit manufacturers MC-1 PANEL
type-2 co-ordination chart for the make used.

MC-1 PANEL
11.000 Capacitor shall be super heavy duty type (MPP technology). MC-1 PANEL
MC-1 PANEL
All outgoing terminals (power and control) shall be brought
12.000 MC-1 PANEL
upto cable alley. 10% extra terminals shall be provided.
MC-1 PANEL
10% extra indicating lamp in loose shall be supplied along
13.000 MC-1 PANEL
with panel.
MC-1 PANEL
Removable lifting hook shall be provided in all transportation
14.000 MC-1 PANEL
section.
MC-1 PANEL
15.000 All CT, PT shall be epoxy resin cast. MC-1 PANEL
MC-1 PANEL
16.000 All meters are digital type. MC-1 PANEL
MC-1 PANEL
Panel shall be powder coated of approved shade with
17.000 MC-1 PANEL
minimum 60 micron thickness.
MC-1 PANEL
ACB's/MCCB's in one particular panel shall be of one similar
18.000 MC-1 PANEL
make.

VOLTEC ENERGY SYSTEMS Page 120


LABOUR RATE
MC-1 PANEL
Size of Voltmeter / Ammeter for incomer also, 96mm x 96mm
19.000 flush mounted with shrouded terminal shall be used in the MC-1 PANEL
panel.
MC-1 PANEL
20.000 Bus bar chamber shall be kept at top of the all panels. MC-1 PANEL
MC-1 PANEL
All bus bar shall be insulated with coloured PVC Sleeve
21.000 MC-1 PANEL
i.e.RYB,BK as per colour code.
MC-1 PANEL
Internal wiring of panel shall be with size 2.5sqmm Flexible
22.000 Copper Conductor for CT circuit and control wiring with 1.5 MC-1 PANEL
sqmm.
MC-1 PANEL
23.000 All indicating light shall be LED type . MC-1 PANEL
MC-1 PANEL
Each vertical section of floor mounted panel shall have
24.000 independent base frame (75mm x 40mm) size made out of 3 MC-1 PANEL
mm sheet steel (LT Panel & DG Panel).
MC-1 PANEL
All the makes shall be as per Employer's approved make list
25.000 MC-1 PANEL
only.
MC-1 PANEL
Wherever only voltmeter & ammeter are required, the same
26.000 may be provided in combined meter suitable for both MC-1 PANEL
parameter.
MC-1 PANEL
6.100 LV PANEL 1 & 2. MC-1 PANEL
Location: Ground Floor MC-1 PANEL
MC-1 PANEL
LV PANEL 1 & 2 shall Comprise of the following: MC-1 PANEL
MC-1 PANEL
a) Incomings: MC-1 PANEL
MC-1 PANEL
Two (2) Nos. 2500 Amps, 400 V, 50kA TPN draw out,
Electrically operated ACB, with ON/OFF/TRIP/Trip circuit
healthy indication lamp and TNC control switch, under
voltage & shunt trip release, anti pumping protection MC-1 PANEL
microprocessor based O/C, S/C & E/F protection etc.
complete as required and as per SLD for Transformer Supply
Feeder.
One (1) no. 3000 Amps, 400 V, 50KA four pole EDO ACB
Bus coupler breaker complete with under voltage and shunt
trip release, anti pumping protection, ON/OFF/ indication etc.
MC-1 PANEL
to be electrically and mechanically interlocked with the
incommers so that necessary interlocking can be achieved as
per approved SLD.
MC-1 PANEL
Metering & indication for Transformer Supply incoming
b) MC-1 PANEL
breakers:
MC-1 PANEL
Each incoming breaker shall be provided with MC-1 PANEL
MC-1 PANEL
One (1) No. Digital Multifunction meter with RS-485 port
suitable for measurement of voltage, currents, Power Factor,
i) MC-1 PANEL
Frequency,Power , Energy, harmonics and hours run
(EM6400 of 'Conzerv' make or equivalent).

VOLTEC ENERGY SYSTEMS Page 121


LABOUR RATE
MC-1 PANEL
One (1) set 3 Nos. CTs of ratio 2500/5A,15VA, Class 1.0 as
ii) MC-1 PANEL
required.
MC-1 PANEL
iii) One (1) set of 2500/5 A, C.L 1.0 CTs for input to APFC relay. MC-1 PANEL
MC-1 PANEL
iv) One set (3 Nos) phase indication lamp with backup SP MCB. MC-1 PANEL
MC-1 PANEL
One (1) No. 4 Window Audi/visual annunciator system
v) complete with hooter, Ack, test & reset PBs for annunciation MC-1 PANEL
of Alarm and Trip for following :-
MC-1 PANEL
1.000 WTI Alarm MC-1 PANEL
2.000 WTI Trip MC-1 PANEL
3.000 REF Trip MC-1 PANEL
4.000 HT Breaker Trip MC-1 PANEL
MC-1 PANEL
c) Protection Relays for Transformer Supply incoming breakers: MC-1 PANEL
MC-1 PANEL
Each Transformer breaker to be provided with : MC-1 PANEL
MC-1 PANEL
One (1) no. SIPROTEC compact 7SJ80 Multifunction
i) MC-1 PANEL
Protection Relay of Siemens make or equivalent.
MC-1 PANEL
One(1) set of CTs of ratio 2500/5A with core for protection of
ii) MC-1 PANEL
5VA and class 5P10.
MC-1 PANEL
One (1) Set, 4 Nos. CTs of ratio 2500/1A, Class PS shall be
iii) MC-1 PANEL
provided for REF Protection.
MC-1 PANEL
Notes : MC-1 PANEL
MC-1 PANEL
Sufficient No. of contacts terminals shall be provided in the
1.000 panel as required for necessary remote operation and MC-1 PANEL
indications etc.
MC-1 PANEL
Operation interlocks as per specification & drawings
indicating sufficient nos. of potential free contacts for
2.000 MC-1 PANEL
interlocking/ indication annunciation/ control etc shall be
provided by the bidder as required.
MC-1 PANEL
d) BUS BARS: MC-1 PANEL
MC-1 PANEL
Two (2) Sets of 3000Amp.,50kA, TPN+E, Copper Bus bar
with colour coded, heat shrinkable sleeves (with 100% MC-1 PANEL
neutral). Earth Bus shall be of 50 x 6 mm copper.
MC-1 PANEL
e) Outgoing: MC-1 PANEL
MC-1 PANEL
Some of the outgoing feeders shall be provided with earth
leakage relays with CBCT of suitable size as per SLD, MC-1 PANEL
(E/SP/ME1 5.S.01.01 Rev. B).
Section-1 MC-1 PANEL

VOLTEC ENERGY SYSTEMS Page 122


LABOUR RATE
MC-1 PANEL
i) Two (2) Nos. 800 A, 50 KA, TPN MDO ACB. MC-1 PANEL
MC-1 PANEL
ii) One (1) No. 630 A, 50 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
iii) One (1) No. 400 A, 50 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
iv) Two (2) Nos. 200 A, 50 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
v) Five (5) Nos. 100 A, 50 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
vi) Five (5) Nos. 63 A, 50 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
vii) Eight (8) Nos. 40 A, 50 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
viii) Four (4) Nos. 32 A, 50 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
Section-2 MC-1 PANEL
MC-1 PANEL
i) One (1) No. 800 A, 50 KA, TP MDO ACB. MC-1 PANEL
MC-1 PANEL
ii) One (1) No. 400 A, 50 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
iii) Six (6) Nos. 250 A, 50 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
iv) One (1) No. 200 A, 50 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
v) Two (2) Nos. 160 A, 50 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
vi) Six (6) Nos. 125 A, 50 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
vii) One (1) No. 100 A, 50 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
viii) Two (2) Nos. 63 A, 50 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
LV Panel 1 & 2 described as above (from a to e) and as per
1 Set MC-1 PANEL
SLD
MC-1 PANEL
6.200 Capacitor Panels (400 kVAR) MC-1 PANEL
MC-1 PANEL
a) Incoming : MC-1 PANEL
MC-1 PANEL
One (1) No. 800A, 50KA, TPN MDO ACB, incomer with 10
step APFC relay with Auto/Manual selector switch, timer, aux. MC-1 PANEL
Contactor, louvers, Exhaust fan etc.
MC-1 PANEL
b) Metering, Indication and Protection : MC-1 PANEL
MC-1 PANEL
One (1) No. digital multifunction meter for measurement of
- voltage and currents with selector push buttons and one set MC-1 PANEL
of CTs of ratio 800A /5A, CL 1.0, 15 VA.

VOLTEC ENERGY SYSTEMS Page 123


LABOUR RATE
MC-1 PANEL
One (1) set of RYB phase indication lamps with control SP
- MC-1 PANEL
MCB.
MC-1 PANEL
c) Busbar : MC-1 PANEL
MC-1 PANEL
1000A, TPN+E, Cu. Busbar insulated with heat shrinkable
- sleeves and shall be color coded. Earth Bus of 50 x 6 mm MC-1 PANEL
copper shall be provided.
MC-1 PANEL
d) Outgoings : MC-1 PANEL
400 KVAR Capacitor Panel in steps of 6 nos. of 2 x 25 kVAR
- 2 Set MC-1 PANEL
banks, 4 Nos. of 1 x 25 kVAR banks.
MC-1 PANEL
Notes: MC-1 PANEL
MC-1 PANEL

Each capacitor bank should have its individual MCCB &


1.000 Contactor suitable for capacitor duty including fuses for each MC-1 PANEL
capacitor unit as per specifications and approved SLD.
Enclosure of capacitor panel shall be liberally designed to
take care of internal heat emission by capacitor unit without
2.000 forced cooling and to limit the temperature rise with in MC-1 PANEL
permissible limit. However, louvers are allowed to facilitate
extra cooling.
MC-1 PANEL
Enclosure of capacitor panel shall be designed so that
3.000 detuned reactors can be installed in the same panel for MC-1 PANEL
harmonics reduction, in future.
MC-1 PANEL
6.300 GENERATOR PANEL MC-1 PANEL
MC-1 PANEL
Generator Panel shall Comprise of the following: MC-1 PANEL
MC-1 PANEL
a) Incomings: MC-1 PANEL
MC-1 PANEL
One (1) No. 630 Amps, 400 V, 40kA TPN MCCB, with
ON/OFF/TRIP and TNC control switch, under voltage &
shunt trip release, microprocessor based O/C, S/C & E/F MC-1 PANEL
protection releases etc. complete as required for DG Supply
Feeder.
MC-1 PANEL
b) Metering & indication for incoming breakers: MC-1 PANEL
MC-1 PANEL
Incoming breaker shall be provided with MC-1 PANEL
MC-1 PANEL
One (1) No. Digital Multifunction meter with RS-485 port
suitable for measurement of voltage, currents, Power Factor,
i) MC-1 PANEL
Frequency,Power, Energy, harmonics and hours run
(EM6400 of 'Conzerv' make or equivalent).
MC-1 PANEL
One (1) set 3 Nos. CTs of ratio 600/5A,15VA, Class 1.0 as
ii) MC-1 PANEL
required.
MC-1 PANEL
iii) One set (3 Nos) phase indication lamp with backup SP MCB. MC-1 PANEL

VOLTEC ENERGY SYSTEMS Page 124


LABOUR RATE
MC-1 PANEL
Sufficient No. of contacts terminals shall be provided in the
Note: panel as required for necessary remote operation and MC-1 PANEL
indications etc.
MC-1 PANEL
c) BUS BARS: MC-1 PANEL
MC-1 PANEL
800Amp., 40kA, TPN+E, Copper Bus bar with colour coded,
heat shrinkable sleeves (with 100% neutral). Earth Bus Bar of MC-1 PANEL
40 x 6 mm Copper shall be provided.
MC-1 PANEL
d) Outgoing: MC-1 PANEL
MC-1 PANEL
Each outgoing feeder shall be provided with Earth leakage
relay and CBCT of suitable size as per SLD (E/SP/ME1 MC-1 PANEL
5.S.01.01, Rev. B)
MC-1 PANEL
i) One (1) No. 630 A, 40 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
ii) Two (2) Nos. 100 A, 40 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
iii) Two (2) Nos. 63 A, 40 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
iv) One (1) No. 40 A, 40 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
v) One (1) No. 32 A, 40 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
Generator Panel described as above (from a to d) and as per
1 Set MC-1 PANEL
SLD (E/SP/ME1 5.S.01.01 Rev. B)
6.400 SMDB-EE-ME1.30-C8-TR1.01 MC-1 PANEL
MC-1 PANEL
SMDB shall Comprise of the following: MC-1 PANEL
MC-1 PANEL
a) Incomings: MC-1 PANEL
MC-1 PANEL
One (1) No. 800 Amps, 400 V, 40kA TPN draw out,
Electrically operated ACB, with ON/OFF/TRIP/Trip circuit
healthy indication lamp and TNC control switch, under
MC-1 PANEL
voltage & shunt trip release, anti pumping protection
microprocessor based O/C, S/C & E/F protection etc.
complete as required.
MC-1 PANEL
b) Metering & indication for incoming breakers: MC-1 PANEL
MC-1 PANEL
Incoming breaker shall be provided with MC-1 PANEL
MC-1 PANEL
One (1) No. Digital Multifunction meter with RS-485 port
i) suitable for measurement of voltage, currents and Frequency MC-1 PANEL
(ELF 3259 of 'Conzerv' make or equivalent).
MC-1 PANEL
One (1) set 3 Nos. CTs of ratio 800/5A,15VA, Class 1.0 as
ii) MC-1 PANEL
required.
MC-1 PANEL
iii) One set (3 Nos) phase indication lamp with backup SP MCB. MC-1 PANEL

VOLTEC ENERGY SYSTEMS Page 125


LABOUR RATE
MC-1 PANEL
Sufficient No. of contacts terminals shall be provided in the
Note: panel as required for necessary remote operation and MC-1 PANEL
indications etc.
MC-1 PANEL
c) BUS BARS: MC-1 PANEL
MC-1 PANEL
1000Amp., 40kA, TPN+E, Copper Bus bar with colour coded,
heat shrinkable sleeves (with 100% neutral). Earth Bus shall MC-1 PANEL
be of 40 x 6 mm copper.
MC-1 PANEL
d) Outgoing: MC-1 PANEL
MC-1 PANEL
Some of the outgoing feeders shall be provided with Earth
leakage relay with CBCT of suitable size as per SLD MC-1 PANEL
(E/SP/ME1 5.S.01.01, Rev. B).
MC-1 PANEL
i) Twelve (12) Nos. 100 A, 40 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
ii) One (1) No. 80 A, 40 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
iii) Six (6) Nos. 63 A, 40 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
iv) Two (2) Nos. 40 A, 40 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
v) Five (5) Nos. 32 A, 40 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
vi) Three (3) Nos. 16 A, 40 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
SMDB-EE-ME1.30-C8-TR1.01 described as above (from a to
1 Set MC-1 PANEL
d) and as per SLD
MC-1 PANEL
6.500 SMDB-EE-ME1-OM-C4-TR1.01 MC-1 PANEL
MC-1 PANEL
SMDB shall Comprise of the following: MC-1 PANEL
MC-1 PANEL
a) Incomings: MC-1 PANEL
MC-1 PANEL
One (1) No. 400 Amps, 400 V, 40kA TPN MCCB, with
ON/OFF/TRIP indication lamp and TNC control switch, under
voltage & shunt trip release with microprocessor based O/C, MC-1 PANEL
S/C & E/F protection etc. complete as required and as per
SLD (E/SP/ME1 5.S.01.01 Rev. B).
MC-1 PANEL
b) Metering & indication for incoming breakers: MC-1 PANEL
MC-1 PANEL
Incoming breaker shall be provided with MC-1 PANEL
MC-1 PANEL
One (1) No. Digital Multifunction meter with RS-485 port
i) suitable for measurement of voltage, currents and Frequency MC-1 PANEL
(ELF 3259 of 'Conzerv' make or equivalent).
MC-1 PANEL
One (1) set 3 Nos. CTs of ratio 400/5A,15VA, Class 1.0 as
ii) MC-1 PANEL
required.

VOLTEC ENERGY SYSTEMS Page 126


LABOUR RATE
MC-1 PANEL
iii) One set (3 Nos) phase indication lamp with backup SP MCB. MC-1 PANEL
MC-1 PANEL
Sufficient No. of contacts terminals shall be provided in the
Note: panel as required for necessary remote operation and MC-1 PANEL
indications etc.
MC-1 PANEL
c) BUS BARS: MC-1 PANEL
MC-1 PANEL
500Amp., 40kA, TPN+E, Copper Bus bar with colour coded,
heat shrinkable sleeves (with 100% neutral). Earth Bus shall MC-1 PANEL
be of 40 x 6 mm copper.
MC-1 PANEL
d) Outgoing: MC-1 PANEL
MC-1 PANEL
i) Three (3) Nos. 100 A, 40 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
ii) Two (2) Nos. 63 A, 40 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
iii) Two (2) Nos. 40 A, 40 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
iv) Four (4) Nos. 16 A, 40 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
SMDB-EE-ME1,OM-C4-TR1.01 described as above (from a
1 Set MC-1 PANEL
to d) and as per SLD
MC-1 PANEL
6.600 SMDB-EE-ME1.O1-E1-TR1.01 MC-1 PANEL
MC-1 PANEL
SMDB shall Comprise of the following: MC-1 PANEL
MC-1 PANEL
a) Incomings: MC-1 PANEL
MC-1 PANEL
One (1) No. 630Amps, 400 V, 40kA TPN MCCB, with
ON/OFF/TRIP/ indication lamp and TNC control switch,
under voltage & shunt trip release with microprocessor based MC-1 PANEL
O/C, S/C & E/F protection etc. complete as required and as
per SLD (E/SP/ME1 5.S.01.01, Rev. B).
MC-1 PANEL
b) Metering & indication for incoming breaker: MC-1 PANEL
MC-1 PANEL
Incoming breaker shall be provided with MC-1 PANEL
MC-1 PANEL
One (1) No. Digital Multifunction meter with RS-485 port
i) suitable for measurement of voltage, currents and Frequency MC-1 PANEL
(ELF 3259 of 'Conzerv' make or equivalent).
MC-1 PANEL
One (1) set 3 Nos. CTs of ratio 600/5A,15VA, Class 1.0 as
ii) MC-1 PANEL
required.
MC-1 PANEL
iii) One set (3 Nos) phase indication lamp with backup SP MCB. MC-1 PANEL
MC-1 PANEL

VOLTEC ENERGY SYSTEMS Page 127


LABOUR RATE
Sufficient No. of contacts terminals shall be provided in the
Note: panel as required for necessary remote operation and MC-1 PANEL
indications etc.
MC-1 PANEL
c) BUS BARS: MC-1 PANEL
MC-1 PANEL
800Amp., 40kA, TPN+E, Copper Bus bar with colour coded,
heat shrinkable sleeves (with 100% neutral). Earth Bus shall MC-1 PANEL
be of 40 x 6 copper.
MC-1 PANEL
d) Outgoing: MC-1 PANEL
MC-1 PANEL
Each outgoing feeder shall be provided with earth leakage
relay with CBCT of suitable size as per SLD (E/SP/ME1 MC-1 PANEL
5.S.01.01, Rev. B).
MC-1 PANEL
i) Three (3) Nos. 250 A, 40 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
ii) Two (2) Nos. 32 A, 40 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
SMDB-EE-ME1.01-E1-TR1.01 described as above (from a to
1 Set MC-1 PANEL
e) and as per SLD
MC-1 PANEL
6.700 FINAL DISTRIBUTION BOARDS MC-1 PANEL
MC-1 PANEL
Design, manufacture, supply, installation (recessed/ surface),
testing and commissioning of following switch fuse Unit/
MCCB/MCB type distribution boards as per drawings &
specifications. The surface distribution boards shall be MC-1 PANEL
mounted on 50 x 50 x 6 MS angle frame work grounted to
floor/ walls. The rate includes the angle iron frame, support,
painting, numbering, earthing etc as required.
MC-1 PANEL
6.7.1 DB-EE-ME1.00-E2-TR1.01 MC-1 PANEL
MC-1 PANEL
Incomer: MC-1 PANEL
MC-1 PANEL
- 100A TP MCB Isolator. MC-1 PANEL
MC-1 PANEL
Busbar : MC-1 PANEL
MC-1 PANEL
- 150A 4P Cu. busbar MC-1 PANEL
MC-1 PANEL
Outgoing – (10KA) comprising MC-1 PANEL
MC-1 PANEL
Section-1 MC-1 PANEL
MC-1 PANEL
- One (1) no. 16A 3 Phase RCD (100 mA). MC-1 PANEL
MC-1 PANEL
- Six (6) nos. 10A SP MCB. MC-1 PANEL
Section-2 MC-1 PANEL
MC-1 PANEL
- One (1) no. 63A 3 Phase RCD (30 mA). MC-1 PANEL
MC-1 PANEL

VOLTEC ENERGY SYSTEMS Page 128


LABOUR RATE
- Three (3) nos. 20A SP MCB. MC-1 PANEL
MC-1 PANEL
- One (1) no. 20A TP MCB. MC-1 PANEL
MC-1 PANEL
Section-3 MC-1 PANEL
MC-1 PANEL
- One (1) no. 63A, 3 Phase RCD (30 mA). MC-1 PANEL
MC-1 PANEL
- Six (6) nos. 20A, SP MCB. MC-1 PANEL
MC-1 PANEL
- Two (2) nos. 20A, TP MCB. MC-1 PANEL
MC-1 PANEL
DB-EE-ME1.00-E2-TR1.01 as described above and as per
- 1 Set MC-1 PANEL
DB chart
MC-1 PANEL
6.7.2 DB-EE-ME1.00-D1TR1.02 MC-1 PANEL
MC-1 PANEL
Incomer: MC-1 PANEL
MC-1 PANEL
- 63A TP MCB Isolator. MC-1 PANEL
MC-1 PANEL
Busbar : MC-1 PANEL
MC-1 PANEL
- 100A 4P Cu. busbar MC-1 PANEL
MC-1 PANEL
Outgoing – (10KA) comprising MC-1 PANEL
MC-1 PANEL
Section-1 MC-1 PANEL
MC-1 PANEL
- One (1) no. 32A, 3 Phase RCD (100 mA). MC-1 PANEL
MC-1 PANEL
- Twenty One (21) Nos. 10A SP MCB. MC-1 PANEL
MC-1 PANEL
Section-2 MC-1 PANEL
MC-1 PANEL
- One (1) no. 40A, 3 Phase RCD (30 mA). MC-1 PANEL
MC-1 PANEL
- Six (6) nos. 20A SP MCB. MC-1 PANEL
MC-1 PANEL
- Two (2) nos. 20A TP MCB. MC-1 PANEL
MC-1 PANEL
DB-EE-ME1.00-D1TR1.02 as described above and as per DB
- 1 Set MC-1 PANEL
chart.
MC-1 PANEL
6.7.3 ME1.00-E2-TR1.03 MC-1 PANEL
MC-1 PANEL
Incomer: MC-1 PANEL
MC-1 PANEL
- 100A TP MCB Isolator. MC-1 PANEL
MC-1 PANEL
Busbar : MC-1 PANEL

VOLTEC ENERGY SYSTEMS Page 129


LABOUR RATE
MC-1 PANEL
- 150A 4P Cu. busbar MC-1 PANEL
MC-1 PANEL
Outgoing – (10KA) comprising MC-1 PANEL
MC-1 PANEL
Section-1 MC-1 PANEL
MC-1 PANEL
- One (1) no. 63A 3 Phase RCD (30 mA). MC-1 PANEL
MC-1 PANEL
- Twenty One (21) nos. 20A SP MCB. MC-1 PANEL
MC-1 PANEL
Section-2 MC-1 PANEL
MC-1 PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). MC-1 PANEL
MC-1 PANEL
- Twenty Seven (27) nos. 20A SP MCB. MC-1 PANEL
MC-1 PANEL
- ME1.00-E2-TR1.03 as described above and as per DB chart 1 Set MC-1 PANEL
MC-1 PANEL
6.7.4 DB-EE-ME1.00-E2-TR1.04 MC-1 PANEL
MC-1 PANEL
Incomer: MC-1 PANEL
MC-1 PANEL
- 40A TP MCB Isolator. MC-1 PANEL
MC-1 PANEL
Busbar : MC-1 PANEL
MC-1 PANEL
- 100A 4P Cu. busbar MC-1 PANEL
MC-1 PANEL
Outgoing – (10KA) comprising MC-1 PANEL
MC-1 PANEL
Section-1 MC-1 PANEL
MC-1 PANEL
- One (1) no. 32A, 3 Phase, RCD (100 mA). MC-1 PANEL
MC-1 PANEL
- Eighteen (18) nos. 10A, SP MCB. MC-1 PANEL
MC-1 PANEL
DB-EE-ME1.00-E2-TR1.04 as described above and as per
- 1 Set MC-1 PANEL
DB chart
MC-1 PANEL
6.7.5 DB-EE-ME1.00-D2-TR1.05 MC-1 PANEL
MC-1 PANEL
Incomer: MC-1 PANEL
MC-1 PANEL
- 100A TP MCB Isolator. MC-1 PANEL
MC-1 PANEL
Busbar : MC-1 PANEL
MC-1 PANEL
- 150A 4P Cu. busbar MC-1 PANEL
MC-1 PANEL

VOLTEC ENERGY SYSTEMS Page 130


LABOUR RATE
Outgoing – (10KA) comprising MC-1 PANEL
MC-1 PANEL
Section-1 MC-1 PANEL
MC-1 PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). MC-1 PANEL
MC-1 PANEL
- Twenty One (21) nos. 20A, SP MCB. MC-1 PANEL
MC-1 PANEL
Section-2 MC-1 PANEL
MC-1 PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). MC-1 PANEL
MC-1 PANEL
- Twenty Seven (27) no. 20A SP MCB. MC-1 PANEL
MC-1 PANEL
DB-EE-ME1.00-D2-TR1.05 as described above and as per
- 1 Set MC-1 PANEL
DB chart
MC-1 PANEL
6.7.6 DB-EE-ME1.00-D2-TR1.06 MC-1 PANEL
MC-1 PANEL
Incomer: MC-1 PANEL
MC-1 PANEL
- 40A TP MCB Isolator. MC-1 PANEL
MC-1 PANEL
Busbar : MC-1 PANEL
MC-1 PANEL
- 100A 4P Cu. busbar MC-1 PANEL
MC-1 PANEL
Outgoing – (10KA) comprising MC-1 PANEL
MC-1 PANEL
Section-1 MC-1 PANEL
MC-1 PANEL
- One (1) no. 32A, 3 Phase, RCD (100 mA). MC-1 PANEL
MC-1 PANEL
- Eighteen (18) nos. 10A, SP MCB. MC-1 PANEL
MC-1 PANEL
DB-EE-ME1.00-D2-TR1.06 as described above and as per
- 1 Set MC-1 PANEL
DB chart
6.7.7 DB-EE-ME1.00-B2-TR1.07 MC-1 PANEL
MC-1 PANEL
Incomer: MC-1 PANEL
MC-1 PANEL
- 100A TP MCB Isolator. MC-1 PANEL
MC-1 PANEL
Busbar : MC-1 PANEL
MC-1 PANEL
- 150A 4P Cu. busbar MC-1 PANEL
MC-1 PANEL
Outgoing – (10KA) comprising MC-1 PANEL
MC-1 PANEL
Section-1 MC-1 PANEL
MC-1 PANEL

VOLTEC ENERGY SYSTEMS Page 131


LABOUR RATE
- One (1) no. 63A, 3 Phase, RCD (30 mA). MC-1 PANEL
MC-1 PANEL
- Twenty One (21) nos. 20A, SP MCB. MC-1 PANEL
MC-1 PANEL
Section-2 MC-1 PANEL
MC-1 PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). MC-1 PANEL
MC-1 PANEL
- Twenty Seven (27) nos. 20A, SP MCB. MC-1 PANEL
MC-1 PANEL
DB-EE-ME1.00-B2-TR1.07 as described above and as per
- 1 Set MC-1 PANEL
DB chart
MC-1 PANEL
6.7.8 DB-EE-ME1.00-B2-TR1.08 MC-1 PANEL
MC-1 PANEL
Incomer: MC-1 PANEL
- 40A TP MCB Isolator. MC-1 PANEL
MC-1 PANEL
Busbar : MC-1 PANEL
- 100A 4P Cu. busbar MC-1 PANEL
MC-1 PANEL
Outgoing – (10KA) comprising MC-1 PANEL
MC-1 PANEL
Section-1 MC-1 PANEL
- One (1) no. 32A, 3 Phase, RCD (100 mA). MC-1 PANEL
MC-1 PANEL
- Eighteen (18) nos. 10A, SP MCB. MC-1 PANEL
MC-1 PANEL
DB-EE-ME1.00-B2-TR1.08 as described above and as per
- 1 Set MC-1 PANEL
DB chart
MC-1 PANEL
6.7.9 DB-EE-ME1.00-E4-TR1.09 MC-1 PANEL
MC-1 PANEL
Incomer: MC-1 PANEL
- 100A TP MCB Isolator. MC-1 PANEL
MC-1 PANEL
Busbar : MC-1 PANEL
- 150A 4P Cu. busbar MC-1 PANEL
MC-1 PANEL
Outgoing – (10KA) comprising MC-1 PANEL
MC-1 PANEL
Section-1 MC-1 PANEL
- One (1) no. 32A, 3 Phase, RCD (100 mA). MC-1 PANEL
MC-1 PANEL
- Twelve (12) nos. 10A, SP MCB. MC-1 PANEL
MC-1 PANEL
Section-2 MC-1 PANEL
- One (1) no. 63A, 3 Phase RCD (30 mA). MC-1 PANEL
MC-1 PANEL
- Thirty (30) nos. 20A SP MCB. MC-1 PANEL
MC-1 PANEL

VOLTEC ENERGY SYSTEMS Page 132


LABOUR RATE
DB-EE-ME1.00-E4-TR1.09 as described above and as per
- 1 Set MC-1 PANEL
DB chart
6.7.10 DB-EE-ME1.00-D4-TR1.10 MC-1 PANEL
MC-1 PANEL
Incomer: MC-1 PANEL
MC-1 PANEL
- 100A TP MCB Isolator. MC-1 PANEL
MC-1 PANEL
Busbar : MC-1 PANEL
MC-1 PANEL
- 100A 4P Cu. busbar MC-1 PANEL
MC-1 PANEL
Outgoing – (10KA) comprising MC-1 PANEL
MC-1 PANEL
Section-1 MC-1 PANEL
MC-1 PANEL
- One (1) no. 40A 3 Phase RCD (100 mA). MC-1 PANEL
MC-1 PANEL
- Twenty Seven (27) nos. 10A SP MCB. MC-1 PANEL
MC-1 PANEL
Section-2 MC-1 PANEL
MC-1 PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). MC-1 PANEL
MC-1 PANEL
- Seventeen (17) nos. 20A SP MCB. MC-1 PANEL
MC-1 PANEL
- One (1) no. 20A TP MCB. MC-1 PANEL
MC-1 PANEL
Section-3 MC-1 PANEL
MC-1 PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). MC-1 PANEL
MC-1 PANEL
- Fourteen (14) nos. 20A SP MCB. MC-1 PANEL
MC-1 PANEL
- One (1) no. 20A TP MCB. MC-1 PANEL
MC-1 PANEL
DB-EE-ME1.00-D4-TR1.10 as described above and as per
- 1 Set MC-1 PANEL
DB chart
MC-1 PANEL
6.7.11 DB-EE-ME1.0M-E2-TR1.01 MC-1 PANEL
MC-1 PANEL
Incomer: MC-1 PANEL
MC-1 PANEL
- 63A TP MCB Isolator. MC-1 PANEL
MC-1 PANEL
Busbar : MC-1 PANEL
MC-1 PANEL
- 100A 4P Cu. busbar MC-1 PANEL
MC-1 PANEL
Outgoing – (10KA) comprising MC-1 PANEL
MC-1 PANEL

VOLTEC ENERGY SYSTEMS Page 133


LABOUR RATE
Section-1 MC-1 PANEL
MC-1 PANEL
- One (1) no. 16A, 3 Phase, RCD (100 mA). MC-1 PANEL
MC-1 PANEL
- Nine (9) nos. 10A SP MCB. MC-1 PANEL
MC-1 PANEL
Section-2 MC-1 PANEL
MC-1 PANEL
- One (1) no. 40A, 3 Phase, RCD (30 mA). MC-1 PANEL
MC-1 PANEL
- Six (6) nos. 20A SP MCB. MC-1 PANEL
MC-1 PANEL
- Two (2) nos. 20A TP MCB. MC-1 PANEL
MC-1 PANEL
DB-EE-ME1.0M-E2-TR1.01 as described above and as per
- 1 Set MC-1 PANEL
DB chart
6.7.12 DB-EE-ME1.10-D3-TR1.01 MC-1 PANEL
MC-1 PANEL
Incomer: MC-1 PANEL
- 40A TP MCB Isolator. MC-1 PANEL
MC-1 PANEL
Busbar : MC-1 PANEL
- 100A 4P Cu. busbar MC-1 PANEL
Outgoing – (10KA) comprising MC-1 PANEL
MC-1 PANEL
Section-1 MC-1 PANEL
- One (1) no. 32A 3 Phase RCD (100 mA). MC-1 PANEL
MC-1 PANEL
- Nine (9) nos. 10A SP MCB. MC-1 PANEL
MC-1 PANEL
Section-2 MC-1 PANEL
- One (1) no. 32A 3 Phase RCD (30 mA). MC-1 PANEL
MC-1 PANEL
- Twelve (12) nos. 20A SP MCB. MC-1 PANEL
MC-1 PANEL
DB-EE-ME1.10-D3-TR1.01 as described above and as per
- 1 Set MC-1 PANEL
DB chart
MC-1 PANEL
6.7.13 DB-EE-ME1.10-D3-TR1.02 MC-1 PANEL
Incomer: MC-1 PANEL
- 40A TP MCB Isolator. MC-1 PANEL
MC-1 PANEL
Busbar : MC-1 PANEL
- 100A 4P Cu. busbar MC-1 PANEL
Outgoing – (10KA) comprising MC-1 PANEL
Section-1 MC-1 PANEL
- One (1) no. 32A 3 Phase RCD (30 mA). MC-1 PANEL
MC-1 PANEL
- Twenty One (21) nos. 20A SP MCB. MC-1 PANEL
MC-1 PANEL

VOLTEC ENERGY SYSTEMS Page 134


LABOUR RATE
DB-EE-ME1.10-D3-TR1.02 as described above and as per
- 1 Set MC-1 PANEL
DB chart
MC-1 PANEL
6.7.14 DB-EE-ME1.20-C4-TR2.01 MC-1 PANEL
MC-1 PANEL
Incomer: MC-1 PANEL
- 63A TP MCB Isolator. MC-1 PANEL
MC-1 PANEL
Busbar : MC-1 PANEL
- 100A 4P Cu. busbar MC-1 PANEL
Outgoing – (10KA) comprising MC-1 PANEL
Section-1 MC-1 PANEL
- One (1) no. 32A 3 Phase RCD (100 mA). MC-1 PANEL
- Twenty One (21) nos. 10A SP MCB. MC-1 PANEL
MC-1 PANEL
Section-2 MC-1 PANEL
- One (1) no. 40A 3 Phase RCD (30 mA). MC-1 PANEL
- Fifteen (15) nos. 20A SP MCB. MC-1 PANEL
Section-3 MC-1 PANEL
- One (1) no. 32A 3 Phase RCD (100 mA). MC-1 PANEL
- Twelve (12) nos. 10A SP MCB. MC-1 PANEL
Section-4 MC-1 PANEL
- One (1) no. 32A 3 Phase RCD (100 mA). MC-1 PANEL
- Six (6) nos. 20A SP MCB. MC-1 PANEL
DB-EE-ME1.20-C4-TR2.01 as described above and as per
- 1 Set MC-1 PANEL
DB chart
6.7.16 DB-EE-ME1.20-C5-TR2.02 MC-1 PANEL
MC-1 PANEL
Incomer: MC-1 PANEL
- 100A TP MCB Isolator. MC-1 PANEL
MC-1 PANEL
Busbar : MC-1 PANEL
- 150A 4P Cu. busbar MC-1 PANEL
MC-1 PANEL
Outgoing – (10KA) comprising MC-1 PANEL
MC-1 PANEL
Section-1 MC-1 PANEL
MC-1 PANEL
- One (1) no. 16A 3 Phase RCD (100 mA). MC-1 PANEL
MC-1 PANEL
- Six (6) nos. 10A SP MCB. MC-1 PANEL
MC-1 PANEL
Section-2 MC-1 PANEL
MC-1 PANEL
- One (1) no. 63A 3 Phase RCD (30 mA). MC-1 PANEL
MC-1 PANEL
- Six (6) nos. 20A SP MCB. MC-1 PANEL
MC-1 PANEL
- One (1) no. 20A TP MCB. MC-1 PANEL
MC-1 PANEL
Section-3 MC-1 PANEL

VOLTEC ENERGY SYSTEMS Page 135


LABOUR RATE
MC-1 PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). MC-1 PANEL
MC-1 PANEL
- Nine (9) nos. 20A, SP MCB. MC-1 PANEL
MC-1 PANEL
- One (1) no. 20A, TP MCB. MC-1 PANEL
MC-1 PANEL
DB-EE-ME1.20-C5-TR2.02 as described above and as per
- 1 Set MC-1 PANEL
DB chart
MC-1 PANEL
6.7.17 DB-EE-ME1.20-C8-TR2.03 MC-1 PANEL
MC-1 PANEL
Incomer: MC-1 PANEL
- 100A TP MCB Isolator. MC-1 PANEL
Busbar : MC-1 PANEL
- 150A 4P Cu. busbar MC-1 PANEL
MC-1 PANEL
Outgoing – (10KA) comprising MC-1 PANEL
MC-1 PANEL
Section-1 MC-1 PANEL
- One (1) no. 16A, 3 Phase, RCD (100 mA). MC-1 PANEL
MC-1 PANEL
- Twenty One (21) nos. 10A SP MCB. MC-1 PANEL
MC-1 PANEL
Section-2 MC-1 PANEL
- One (1) no. 40A, 3 Phase, RCD (30 mA). MC-1 PANEL
MC-1 PANEL
- Nine (9) nos. 20A, SP MCB. MC-1 PANEL
MC-1 PANEL
Section-3 MC-1 PANEL
- One (1) no. 40A, 3 Phase, RCD (30 mA). MC-1 PANEL
MC-1 PANEL
- Twelve (12) nos. 10A SP MCB. MC-1 PANEL
MC-1 PANEL
Section-4 MC-1 PANEL
- One (1) no. 32A, 3 Phase, RCD (100 mA). MC-1 PANEL
MC-1 PANEL
- Twelve (12) nos. 10A SP MCB. MC-1 PANEL
MC-1 PANEL
Section-5 MC-1 PANEL
- One (1) no. 32A, 3 Phase, RCD (100 mA). MC-1 PANEL
MC-1 PANEL
- Six (6) nos. 20A SP MCB. MC-1 PANEL
MC-1 PANEL
DB-EE-ME1.20-C8-TR2.03 as described above and as per
- 1 Set MC-1 PANEL
DB chart
6.7.18 DB-EE-ME1.30-C8-TR2.01 MC-1 PANEL
MC-1 PANEL
Incomer: MC-1 PANEL
MC-1 PANEL
- 63A TP MCB Isolator. MC-1 PANEL

VOLTEC ENERGY SYSTEMS Page 136


LABOUR RATE
MC-1 PANEL
Busbar : MC-1 PANEL
MC-1 PANEL
- 100A 4P Cu. busbar MC-1 PANEL
MC-1 PANEL
Outgoing – (10KA) comprising MC-1 PANEL
MC-1 PANEL
Section-1 MC-1 PANEL
MC-1 PANEL
- One (1) no. 32A, 3 Phase, RCD (100 mA). MC-1 PANEL
MC-1 PANEL
- Nine (9) nos. 10A SP MCB. MC-1 PANEL
MC-1 PANEL
Section-2 MC-1 PANEL
MC-1 PANEL
- One (1) no. 40A, 3 Phase, RCD (30 mA). MC-1 PANEL
MC-1 PANEL
- Fifteen (15) nos. 20A SP MCB. MC-1 PANEL
MC-1 PANEL
DB-EE-ME1.30-C8-TR2.01 as described above and as per
- 1 Set MC-1 PANEL
DB chart
MC-1 PANEL
6.7.19 DB-EE-ME1.01-F1-TR1.01 MC-1 PANEL
MC-1 PANEL
Incomer: MC-1 PANEL
- 63A TP MCB Isolator. MC-1 PANEL
MC-1 PANEL
Busbar : MC-1 PANEL
100A 4P Cu. busbar MC-1 PANEL
MC-1 PANEL
Outgoing – (10KA) comprising MC-1 PANEL
MC-1 PANEL
Section-1 MC-1 PANEL
- MC-1 PANEL
One (1) no. 16A, 3 Phase, RCD (100 mA). MC-1 PANEL
- MC-1 PANEL
Six (6) nos. 10A SP MCB. MC-1 PANEL
MC-1 PANEL
Section-2 MC-1 PANEL
- MC-1 PANEL
One (1) no. 40A, 3 Phase, RCD (30 mA). MC-1 PANEL
- MC-1 PANEL
Six (6) nos. 20A SP MCB. MC-1 PANEL
- MC-1 PANEL
DB-EE-ME1.01-F1-TR1.01 as described above and as per
1 Set MC-1 PANEL
DB chart
MC-1 PANEL
Design, Manufacturing, Supply, installation, Testing and
Commissioning of Auto Transfer Switch Panel (ATS Panels)
6.800 MC-1 PANEL
of following ratings as per specifications, SLD and approved
Shop drawing :-

VOLTEC ENERGY SYSTEMS Page 137


LABOUR RATE
MC-1 PANEL
a) 630 Amp, 4 pole, 400V, 40 KA @ 1 Sec. 1 No. MC-1 PANEL
b) 250 Amp, 4 pole, 400V, 40 KA @ 1 Sec. 1 No. MC-1 PANEL
c) 200 Amp, 4 pole, 400V, 40 KA @ 1 Sec. ur Nos. MC-1 PANEL
d) 100 Amp, 4 pole, 400V, 40 KA @ 1 Sec. 1 No. MC-1 PANEL
e) 63 Amp, 4 pole, 400V, 40 KA @ 1 Sec. 1 No. MC-1 PANEL
f) 40 Amp, 4 pole, 400V, 40 KA @ 1 Sec. 1 No. MC-1 PANEL
g) 32 Amp, 4 pole, 400V, 40 KA @ 1 Sec. 1 No. MC-1 PANEL
TOTAL OF LV SWITCHGEAR PANELS & DISTRIBUTION
MC-1 PANEL
BOARDS CARRIED OVER TO SUMMARY
7.00 CABLES, SUB MAINS & CABLE TRAYS : MC-1 CAB
MC-1 CAB
7.10 Cables in Under Ground Installations : MC-1 CAB
MC-1 CAB
Supply, installation, testing and commissioning of following
sizes of PVC sheathed, XLPE insulated copper conductor
power/multicore control, armoured, Multi-strand cable of 1.1
KV grade in ground including digging the trench, laying the MC-1 CAB
cable with sand and brick covering, back filling reaming etc
as required, as per specfications and as per directions of
Engineer-in-charge.
MC-1 CAB
Copper Conductor, Armoured XLPE Cables
7.1.1 MC-1 CAB
(PVC/SWA/XLPE) :
MC-1 CAB
a) 4 core 400 Sqmm 10 RM MC-1 CAB
b) 4 core 300 Sqmm 10 RM MC-1 CAB
c) 4 core 240 Sqmm 10 RM MC-1 CAB
d) 4 core 185 sqmm 10 RM MC-1 CAB
e) 4 core 150 sqmm 100 RM MC-1 CAB
f) 4 core 120 sqmm 10 RM MC-1 CAB
g) 4 core 95 sqmm 50 RM MC-1 CAB
h) 4 core 70 sqmm 100 RM MC-1 CAB
i) 4 core 50 sqmm 100 RM MC-1 CAB
j) 4 core 35 sqmm 500 RM MC-1 CAB
k) 4 core 25 sqmm 500 RM MC-1 CAB
l) 4 core 16 sqmm 100 RM MC-1 CAB
m) 4 core 10 sqmm 10 RM MC-1 CAB
n) 4 core 6 sqmm 10 RM MC-1 CAB
o) 4 core 4 sqmm 10 RM MC-1 CAB
p) 3 core 25 sqmm 10 RM MC-1 CAB
q) 3 core 16 sqmm 10 RM MC-1 CAB
r) 3 core 10 sqmm 10 RM MC-1 CAB
s) 3 core 6 sqmm 10 RM MC-1 CAB
t) 3 core 4 sqmm 10 RM MC-1 CAB
u) 2 core 6 sqmm 10 RM MC-1 CAB
v) 2 core 4 sqmm 10 RM MC-1 CAB
MC-1 CAB
7.20 Cables on Racks / Pipes / Ducts / Wireways/Cable Trays : MC-1 CAB
MC-1 CAB

VOLTEC ENERGY SYSTEMS Page 138


LABOUR RATE
Supply, installation, testing and commissioning of following
sizes of PVC sheathed, XLPE insulated, copper conductor,
power/multicore, control, armoured, Multi-stranded cable of
1.1 KV grade on surface of wall or in existing cable tray MC-1 CAB
/masonary ducts/hume pipe with fixing hardware etc as
required, as per specifications and as per direction of
Engineer-in-charge.
MC-1 CAB
7.2.1 Copper Conductor Armoured Cables : MC-1 CAB
MC-1 CAB
a) 4 core 400 Sqmm 100 RM MC-1 CAB
b) 4 core 300 Sqmm 400 RM MC-1 CAB
c) 4 core 240 Sqmm 300 RM MC-1 CAB
d) 4 core 185 sqmm 150 RM MC-1 CAB
e) 4 core 150 sqmm 300 RM MC-1 CAB
f) 4 core 120 sqmm 1700 RM MC-1 CAB
g) 4 core 95 sqmm 10 RM MC-1 CAB
h) 4 core 70 sqmm 10 RM MC-1 CAB
i) 4 core 50 sqmm 1500 RM MC-1 CAB
j) 4 core 35 sqmm 200 RM MC-1 CAB
k) 4 core 25 sqmm 700 RM MC-1 CAB
l) 4 core 16 sqmm 600 RM MC-1 CAB
m) 4 core 10 sqmm 700 RM MC-1 CAB
n) 4 core 6 sqmm 1500 RM MC-1 CAB
o) 4 core 4 sqmm 1200 RM MC-1 CAB
p) 3 core 25 sqmm 10 RM MC-1 CAB
q) 3 core 16 sqmm 10 RM MC-1 CAB
r) 3 core 10 sqmm 10 RM MC-1 CAB
s) 3 core 6 sqmm 10 RM MC-1 CAB
t) 3 core 4 sqmm 1700 RM MC-1 CAB
u) 2 core 6 sqmm 300 RM MC-1 CAB
v) 2 core 4 sqmm 10 RM MC-1 CAB
MC-1 CAB
7.2.2 Copper Conductor Armoured Control Cables : MC-1 CAB
MC-1 CAB
a) 14 C 1.5 Sqmm PVC cable 50 RM MC-1 CAB
b) 10 C 1.5 Sqmm PVC cable 50 RM MC-1 CAB
c) 9 C 1.5 Sqmm PVC cable 100 RM MC-1 CAB
d) 7 C 1.5 Sqmm PVC cable 200 RM MC-1 CAB
e) 5 C 1.5 Sqmm PVC cable 200 RM MC-1 CAB
f) 3 C 1.5 Sqmm PVC cable 200 RM MC-1 CAB
MC-1 CAB
7.30 Cable Termination : MC-1 TERM
MC-1 TERM
Supply and making end termination with brass double
compression glands for the following XLPE insulated PVC
sheathed, 1100 V grade, Multi-strand copper conductor cable
including cost of crimping lugs/ferrules, double compression MC-1 TERM
glands, solder, cable sockets, insulation tap etc complete as
required, as per specifications and as per direction of
Engineer-in-charge.
MC-1 TERM
7.3.1 Copper conductor armoured cables : MC-1 TERM

VOLTEC ENERGY SYSTEMS Page 139


LABOUR RATE
MC-1 TERM
a) 4 core 400 Sqmm 2 Nos. MC-1 TERM
b) 4 core 300 Sqmm 8 Nos. MC-1 TERM
c) 4 core 240 Sqmm 4 Nos. MC-1 TERM
d) 4 core 185 sqmm 12 Nos. MC-1 TERM
e) 4 core 150 sqmm 20 Nos. MC-1 TERM
f) 4 core 120 sqmm 20 Nos. MC-1 TERM
g) 4 core 95 sqmm 2 Nos. MC-1 TERM
h) 4 core 70 sqmm 2 Nos. MC-1 TERM
i) 4 core 50 sqmm 16 Nos. MC-1 TERM
j) 4 core 35 sqmm 10 Nos. MC-1 TERM
k) 4 core 25 sqmm 42 Nos. MC-1 TERM
l) 4 core 16 sqmm 30 Nos. MC-1 TERM
m) 4 core 10 sqmm 26 Nos. MC-1 TERM
n) 4 core 6 sqmm 44 Nos. MC-1 TERM
o) 4 core 4 sqmm 100 Nos. MC-1 TERM
p) 3 core 25 sqmm 2 Nos. MC-1 TERM
q) 3 core 16 sqmm 2 Nos. MC-1 TERM
r) 3 core 10 sqmm 2 Nos. MC-1 TERM
s) 3 core 6 sqmm 2 Nos. MC-1 TERM
t) 3 core 4 sqmm 114 Nos. MC-1 TERM
u) 2 core 6 sqmm 2 Nos. MC-1 TERM
v) 2 core 4 sqmm 2 Nos. MC-1 TERM
MC-1 TERM
7.3.2 Copper Conductor PVC Insulated Armoured Control Cables : MC-1 TERM
(Single Compression Glands suitable for following armoured
MC-1 TERM
cables)
MC-1 TERM
a) 14 C x 1.5 Sqmm 2 Nos. MC-1 TERM
b) 10 C x 1.5 Sqmm 2 Nos. MC-1 TERM
c) 9 C x 1.5 Sqmm 2 Nos. MC-1 TERM
d) 7 C x 1.5 Sqmm 4 Nos. MC-1 TERM
e) 5 C x 1.5 Sqmm 4 Nos. MC-1 TERM
f) 3 C x 1.5 Sqmm 2 Nos. MC-1 TERM
MC-1 TERM

The cable quantities given are approximate and to cover


various sizes. The contractor shall measure the cables
Notes : MC-1 TERM
required and procurement order shall be placed accordingly.
The quantities shall be confirmed before start of work.

MC-1 TERM
Supply, installation, testing and commissioning of 1.1 KV
grade, Multicore, copper conductor, LSZH outer sheathed,
CWZ fire resistant cable (in compliance with BS : 6387) of
7.40 following sizes on surfae of wall/existing cable MC-1 cab
trays/Mesonary Hume pipe/Duct/Trenches etc., with fixing
hardware etc. as required as per specifications and as per
direction of Engineer-in-charge.
MC-1 cab
a) 4 C x 185 Sqm, CWZ Cable 150 RM MC-1 cab
b) 4 C x 150 Sqm, CWZ Cable 10 RM MC-1 cab
c) 4 C x 120 Sqm, CWZ Cable 10 RM MC-1 cab

VOLTEC ENERGY SYSTEMS Page 140


LABOUR RATE
d) 4 C x 95 Sqm, CWZ Cable 10 RM MC-1 cab
e) 4 C x 70 Sqm, CWZ Cable 10 RM MC-1 cab
f) 4 C x 50 Sqm, CWZ Cable 10 RM MC-1 cab
g) 4 C x 35 Sqm, CWZ Cable 10 RM MC-1 cab
h) 4 C x 25 Sqm, CWZ Cable 400 RM MC-1 cab
i) 4 C x 16 Sqm, CWZ Cable 250 RM MC-1 cab
j) 4 C x 10 Sqm, CWZ Cable 200 RM MC-1 cab
k) 4 C x 6 Sqm, CWZ Cable 10 RM MC-1 cab
l) 4 C x 4 Sqm, CWZ Cable 10 RM MC-1 cab
m) 4 C x 2.5 Sqm, CWZ Cable 10 RM MC-1 cab
MC-1 cab
7.50 Cable Trays : MC-1 tray
MC-1 tray

Supply and installation of ladder type/perforated type cable


trays of the following sizes fabricated out of perforated hot dip
galvanised MS sheets of minimum 2.0 mm thick to be
installed horizontally or vertically. The cable tray shall be
complete including cost of supporting Steel/Hangers, bends, MC-1 tray
elbows, cross, tees, reducers etc as per drawings/site
condition and rate shall include cost of anchor fasteners,
screws, nuts, bolts and misc. other fixing hardware etc as
required, as per specifications and approved Shop drawings.

MC-1 tray
The cable tray shall be factory built. Bidder shall include in his
price, required numbers of Tees, Crosses, Bends, Elbows etc
Notes : MC-1 tray
as required as per actual site conditions. Bidder may refer to
the drawings for estimation purpose.
MC-1 tray
7.5.1 Ladder Type Cable tray : MC-1 tray
MC-1 tray
a) 900 mm x 75 mm x 2.0 mm 10 RM MC-1 tray
b) 750 mm x 75 mm x 2.0 mm 10 RM MC-1 tray
c) 600 mm x 75 mm x 2.0 mm 10 RM MC-1 tray
d) 450 mm x 75 mm x 2.0 mm 10 RM MC-1 tray
e) 300 mm x 75 mm x 2.0 mm 10 RM MC-1 tray
f) 225 mm x 75 mm x 2.0 mm 10 RM MC-1 tray
g) 100 mm x 75 mm x 2.0 mm 10 RM MC-1 tray
MC-1 tray
7.5.2 Perforated Type Cable Tray : MC-1 tray
MC-1 tray
a) 750 mm x 75 mm x 2.0 mm 10 RM MC-1 tray
b) 600 mm x 75 mm x 2.0 mm 50 RM MC-1 tray
c) 500 mm x 75 mm x 2.0 mm 300 RM MC-1 tray
d) 400 mm x 75 mm x 2.0 mm 100 RM MC-1 tray
e) 300 mm x 50 mm x 2.0 mm 300 RM MC-1 tray
f) 250 mm x 50 mm x 2.0 mm 100 RM MC-1 tray
g) 200 mm x 75 mm x 2.0 mm 200 RM MC-1 tray
h) 150 mm x 75 mm x 2.0 mm 500 RM MC-1 tray
i) 100 mm x 75 mm x 2.0 mm 150 RM MC-1 tray
MC-1 tray
7.5.3 Fibreglass Ladder Type Cable Tray : MC-1 tray
MC-1 tray

VOLTEC ENERGY SYSTEMS Page 141


LABOUR RATE
Supply & Installation of Ladder type Cable tray of following
sizes. The Cable Tray shall be complete including the cost of
MC-1 tray
Anchor fasteners, Hardware, supporting structure etc. as
required and as per specifications and approved drawing :
a) 600 mm wide 10 RM MC-1 tray
b) 450 mm wide 10 RM MC-1 tray
c) 300 mm wide 10 RM MC-1 tray
d) 225 mm wide 10 RM MC-1 tray
e) 100 mm wide 10 RM MC-1 tray
MC-1 tray
7.60 Misc. Works Relating to Cabling: MC-1 pipe
MC-1 pipe
7.6.1 GI Pipe Installation : MC-1 pipe
MC-1 pipe
Supply and installation of following sizes of `A' class GI pipe
for cable sleeves in recess/ on surface/Ground complete with
all accessories pull boxes where ever required, G.I. fish wire,
fixing hardware etc. including the chasing of wall/floor, and MC-1 pipe
plastering the chased portion, digging the trench and back
filling, making good the damages, sealing of pipe entry etc as
required.
MC-1 pipe
a) 25 mm dia 10 RM MC-1 pipe
b) 32 mm dia 10 RM MC-1 pipe
c) 40 mm dia 10 RM MC-1 pipe
d) 50 mm dia 10 RM MC-1 pipe
e) 80 mm dia 10 RM MC-1 pipe
f) 100 mm dia 10 RM MC-1 pipe
g) 150 mm dia 10 RM MC-1 pipe
MC-1 pipe
7.6.2 Flexible Conduits Installation : MC-1 pw
MC-1 pw
Supply and installation of following sizes of GI flexible
conduits with all accessories including fixing nipples,
MC-1 pw
couplings and fixing hardware etc as required and as per
specifications.
7.6.2.1 GI flexible conduits : MC-1 pw
MC-1 pw
a) 20 mm dia 200 RM MC-1 pw
b) 25 mm dia 100 RM MC-1 pw
c) 40 mm dia 100 RM MC-1 pw
d) 50 mm dia 100 RM MC-1 pw
TOTAL OF CABLES, SUB MAINS, CABLE TRAYS
MC-1 pw
CARRIED OVER TO SUMMARY
8.00 WIRING : MC-1 pw
MC-1 pw
8.10 Point Wiring : MC-1 pw
MC-1 pw
The rates for point wiring shall include the circuit wiring. MC-1 pw
MC-1 pw
Circuit wiring means the wiring from DB / Dimmer panel to the
MC-1 pw
first point of circuit through control switch.
MC-1 pw

VOLTEC ENERGY SYSTEMS Page 142


LABOUR RATE

Circuit wiring and subsequent looping shall be done with 2.5


MC-1 pw
Sqmm, 1100V grade LSZH insulated stranded, copper wires.
MC-1 pw
The rates of point wiring shall include supply, installation,
testing & commissioning of MS conduit with accessories, GI
Boxes and required GI flexible conduits with accessories up
to the Point, LSZH insulated, stranded, Cu. Wire, switches MC-1 pw
and sockets (as approved by Engineer-in-charge) etc. as
required and as per specification and direction of Engineer-in-
charge.
MC-1 pw
Where the light points are directly controlled from DB (without
any local control switches), the quoted rates shall not include MC-1 pw
the cost of MCBs etc. in the point wiring.
MC-1 pw
The rates of point wiring shall include earthing of each light,
fan, switches, switch plates, boxes and other non current
MC-1 pw
carrying metallic part with 2.5Sqm. Stranded copper, LSZH
insulated, stranded, copper wire.
MC-1 pw
8.1.1 Light Points controlled by switch : MC-1 pw
MC-1 pw
a) Single/ First light point con-trolled by a 5Amps switch. 52 Nos. MC-1 pw
MC-1 pw
b) Same as above but loop point 172 Nos. MC-1 pw
MC-1 pw
8.1.2 Light Points controlled directly from DB . MC-1 pw
MC-1 pw
i. Single/ First Point Controlled directly by MCB in DB 108 Nos. MC-1 pw
MC-1 pw
ii. Same as above but loop point. 699 Nos. MC-1 pw
MC-1 pw
8.1.3 Two way points : MC-1 pw
MC-1 pw
a) Light points controlled by 2 Nos 2 way switch. MC-1 pw
MC-1 pw
One / first light point controlled by two nos. two way 5 Amps.
i) 2 Nos. MC-1 pw
switch.
MC-1 pw
ii) Same as above but loop point. 11 Nos. MC-1 pw
MC-1 pw
8.1.4 Presence Sensor : MC-1 pw
MC-1 pw
Wiring from Presence Sensor to the DB/SwitchBoard/Light
fixtures, including providing Presence Sensor as required and
a) as per approved shop drawing (wiring from DB to light points 25 Nos. MC-1 pw
has already been included in subheads 1.1,1.2,1.3 above and
not to be considered here).
MC-1 pw
8.1.5 6A Socket Points : MC-1 pw
MC-1 pw
Wiring for 6A, BS, switched socket outlet including providing
a) 6A, BS, switched, socket outlet as per specification and 40 Point MC-1 pw
approved shop drawing.

VOLTEC ENERGY SYSTEMS Page 143


LABOUR RATE
8.20 Power Socket Wiring : MC-1 pw
MC-1 pw

Power Socket Wiring shall include supply, installation, testing


and commissioning of wiring of following points, including,
providing conduits of suitable size, its accessories/Hardware,
MC-1 pw
Junction Boxes, LSZH wires, termination of wires, switches,
socket outlets, Plug tops etc. as required, as per specification
and as approved by Engineer-in-charge.

MC-1 pw
Wiring for 1 No. BS, 16A, switched socket outlet with 4 Sqmm
LSZH insulated stranded copper conductor wires in
recessed/surface black enameled MS conduit including
cutting/filling chases, providing conduit with conduit
8.2.1 accessories, saddles, supply and fixing of 1 No. BS, 16A, 11 Point MC-1 pw
switched outlet with internal wiring in G.I. box, earthing of 3rd
pin with LSZH insulated, green colour 2.5 Sq.mm copper
wire, complete with all accessories as required and as per
approved shop drawing.
MC-1 pw
Wiring for 2 Nos. BS, 16A, switched outlet with 4 Sqmm
LSZH insulated stranded copper conductor wires in
recessed/surface black enameled MS conduit including
cutting/filling chases, providing conduit with conduit
8.2.2 accessories, saddles, supply and fixing of 2 Nos.BS, 16A, 15 Point MC-1 pw
switched outlet with internal wiring in G.I. box, earthing of 3rd
pin with LSZH insulated, green colour 2.5 Sq.mm copper
wire, complete with all accessories as required and as per
approved shop drawing.
MC-1 pw
Wiring for 3 Nos. BS, 16A, switched outlet with 4 Sqmm
LSZH insulated stranded copper conductor wires in
recessed/surface black enameled MS conduit including
cutting/filling chases, providing conduit with conduit
8.2.3 accessories, saddles, supply and fixing of 3 Nos.BS outlet 7 Point MC-1 pw
16A switched with internal wiring in G.I. box, earthing of 3rd
pin with LSZH insulated, green colour 2.5 Sq.mm copper
wire, complete with all accessories as required and as per
approved shop drawing.
MC-1 pw
Wiring for 4 Nos. BS, 16A, switched outlet with 4 Sqmm
LSZH insulated stranded copper conductor wires in
recessed/surface black enameled MS conduit including
cutting/filling chases, providing conduit with conduit
8.2.4 accessories, saddles, supply and fixing of 4 Nos.BS, 16A, 9 Point MC-1 pw
switched outlet with internal wiring in G.I. box, earthing of 3rd
pin with LSZH insulated, green colour 2.5 Sq.mm copper
wire, complete with all accessories as required and as per
approved shop drawing.
MC-1 pw
Wiring for 1 No. BS, 16A, switched outlet in IP-65 enclosure
with 4 Sqmm LSZH insulated stranded copper conductor
wires in recessed/surface black enameled MS conduit
including cutting/filling chases, providing conduit with conduit
8.2.5 accessories, saddles, supply and fixing of 1 No. BS, 16A, 1 Point MC-1 pw
switched outlet in IP-65 enclosure with internal wiring,
earthing of 3rd pin with LSZH insulated, green colour 2.5
Sq.mm copper wire, complete with all accessories as required
and as per approved shop drawing.
MC-1 pw

VOLTEC ENERGY SYSTEMS Page 144


LABOUR RATE

Wiring for 2 Nos. BS, 16A, switched outlet in IP-65 enclosure


with 4 Sqmm LSZH insulated stranded copper conductor
wires in recessed/surface black enameled MS conduit
including cutting/filling chases, providing conduit with conduit
8.2.6 accessories, saddles, supply and fixing of 2 Nos. BS, 16A, 10 Point MC-1 pw
switched outlet in IP-65 enclosure with internal wiring,
earthing of 3rd pin with LSZH insulated, green colour 2.5
Sq.mm copper wire, complete with all accessories as required
and as per approved shop drawing.

MC-1 pw
Wiring for 1 No. BS, 16A, switched outlet & 1 No. BS 16A
switched outlet in IP-65 enclosure with 4 Sqmm LSZH
insulated stranded copper conductor wires in
recessed/surface black enameled MS conduit including
cutting/filling chases, providing conduit with conduit
8.2.7 accessories, saddles, supply and fixing of 1 No. BS, 16A, 1 Point MC-1 pw
switched outlet & 1 No. IP-65 BS, 16A, switched outlet with
internal wiring in G.I. box, earthing of 3rd pin with LSZH
insulated, green colour 2.5 Sq.mm copper wire, complete with
all accessories as required and as per approved shop
drawing.
MC-1 pw
Wiring for 1 No. BS, 16A, switched outlet (Spur Outlet) with 4
Sqmm LSZH insulated stranded copper conductor wires in
recessed/surface black enameled MS conduit including
cutting/filling chases, providing conduit with conduit
8.2.8 accessories, saddles, supply and fixing of 1 No. BS, 16A, 40 Point MC-1 pw
switched outlet (Spur Outlet) with internal wiring in G.I. box,
earthing of 3rd pin with LSZH insulated, green colour 2.5
Sq.mm copper wire, complete with all accessories as required
and as per approved shop drawing.
MC-1 pw

Wiring for 1 No. BS, 32A, switched outlet in IP-65 enclosure


for Water Heater with 4 Sqmm LSZH insulated stranded
copper conductor wires in recessed/surface black enameled
MS conduit including cutting/filling chases, providing conduit
8.2.9 with conduit accessories, saddles, supply and fixing of 1 No. 4 Point MC-1 pw
BS, 32A, switched outlet in IP-65 enclosure with internal
wiring, earthing of 3rd pin with LSZH insulated, green colour
2.5 Sq.mm copper wire, complete with all accessories as
required and as per approved shop drawing.

MC-1 pw

Wiring for 1 No. Disabled Alarm Device with 4 Sqmm LSZH


insulated stranded copper conductor wires in
recessed/surface black enameled MS conduit including
cutting/filling chases, providing conduit with conduit
8.2.10 accessories, saddles, supply and fixing of 1 No. Disabled 3 Point MC-1 pw
Alarm Device (As approved by the Engineer-in-charge) with
internal wiring in G.I. box, earthing with LSZH insulated,
green colour 2.5 Sq.mm copper wire, complete with all
accessories as required and as per approved shop drawing.

MC-1 pw

VOLTEC ENERGY SYSTEMS Page 145


LABOUR RATE
Wiring for 2 Nos. Power & Data Pillar, each consisting of 2
Nos. 6A BS socket, 1 No. 15A Switch and 1 No. RJ-45 Data
Outlets in IP-65 enclosure, with 4 Sqmm LSZH insulated
stranded copper conductor wires in recessed/surface black
enameled MS conduit including cutting/filling chases,
providing conduit with conduit accessories, saddles, supply
8.2.11 2 Point MC-1 pw
and fixing of 2 Nos. Power & Data Pillar, each consisting of 2
Nos. 6A BS socket with 1 No. 15A Switch and 1 No. RJ-45
Data Outlets in IP-65 enclosure, with internal wiring, earthing
with LSZH insulated, green colour 2.5 Sq.mm copper wire,
complete with all accessories as required and as per
approved shop drawing.
MC-1 pw
Wiring for 3 Nos. Power & Data Pillar, each consisting of 2
Nos. 6A BS socket with 1 No. 15A Switch and 1 No. RJ-45
Data outlet in IP-65 enclosure, with 4 Sqmm LSZH insulated
stranded copper conductor wires in recessed/surface black
enameled MS conduit including cutting/filling chases,
8.2.12 providing conduit with conduit accessories, saddles, supply 2 Point MC-1 pw
and fixing of 3 Nos. Power & Data Pillar, each consisting of 2
Nos. 6A BS socket with 1 No. 15A Switch and 1 No. RJ-45
Data outlet in IP-65 enclosure, with internal wiring, earthing
with LSZH insulated, green colour 2.5 Sq.mm copper wire,
complete with all accessories as required.
MC-1 pw

Wiring for 4 Nos. Power & Data Pillar, each consisting of 2


Nos. 6A BS socket with 1 No. 15A Switch and 1 No. RJ-45
Data outlets in IP-65 enclosure, with 4 Sqmm LSZH insulated
stranded copper conductor wires in recessed/surface black
enameled MS conduit including cutting/filling chases,
8.2.13 providing conduit with conduit accessories, saddles, supply 120 Point MC-1 pw
and fixing of 4 Nos. Power & Data Pillar, each consisting of 2
Nos. 6A BS socket with 1 No. 15A Switch and 1 No. RJ-45
Data outlets in IP-65 enclosure, with internal wiring, earthing
with LSZH insulated, green colour 2.5 Sq.mm copper wire,
complete with all accessories as required.

MC-1 pw
8.30 CEE INDUSTRIAL SWITCHED SOCKETS MC-1 pw
MC-1 pw
Supply, installation, testing and commissioning of single
phase/three phase, CEE, switched, industrial type plug and
socket outlet in IP-65 enclosure including termination,
8.3.1 earthing etc. in surface/recessed mounting as required, as MC-1 pw
per specifications and approved shop drawings
(Cabling/Conduiting & wiring shall be paid separately under
different items).
MC-1 pw
a) 16A, 2P+E, CEE, switched socket outlet with plug top (IP-44) 47 Nos. MC-1 pw
16A, 3P+N+E, CEE, switched socket outlet with plug top (IP-
b) 15 Nos. MC-1 pw
44)
16A, 3P+N+E, CEE, switched socket outlet with plug top (IP-
c) 4 Nos. MC-1 pw
65) for water heaters.
MC-1 pw
Supply, installation, testing and commissioning of following
BS switched socket outlets including termination, earthing etc.
8.3.2 in surface/recessed mounting as required. MC-1 pw
(Cabling/conduiting & wiring shall be paid seperately under
different item).
MC-1 pw

VOLTEC ENERGY SYSTEMS Page 146


LABOUR RATE
a) 16A BS switched socket outlet. 12 Nos. MC-1 pw
MC-1 pw
16A weatherproof BS switched socket outlet in IP-65
b) 15 Nos. MC-1 pw
enclosure.
MC-1 pw
Supply, installation, testing and commissioning of following
Single Phase/3 phase, CEE, switched, Industrial type Plug
and socket Combination Outlet in single enclosure (IP-65)
8.3.3 consisting of including termination, Earthing etc. in MC-1 pw
surface/recess mounting as required.
(Conduiting/wiring/cabling for the same shall be paid
seperately under different item).
MC-1 pw
16A, 3P+N+E, CEE, switched socket outlets with plug (IP-44)
- MC-1 pw
with 16A TPN MCB,10kA.
MC-1 pw
32A, 3P+N+E, CEE, switched socket outlets with plug (IP-44)
- MC-1 pw
with 32A TPN MCB,10kA.
MC-1 pw
63A, 3P+N+E, CEE, switched socket outlets with plug (IP-44)
- 7 Nos. MC-1 pw
with 63A TPN MCB,10kA.
MC-1 pw
8.40 ISOLATORS MC-1 pw
MC-1 db
Supply, installation, testing and commissioning of isolators in
IP-65 enclosures complete with termination in MC-1 db
surface/recessed mounting as required.
MC-1 db
a) 16A Four pole isolator 7 Nos. MC-1 db
MC-1 db
b) 32A Four pole isolator 6 Nos. MC-1 db
MC-1 db
c) 63A Four pole isolator 2 Nos. MC-1 db
MC-1 db
d) 100A Four pole isolator 2 Nos. MC-1 db
MC-1 db
e) 200A Four pole isolator 1 No. MC-1 db
MC-1 db
f) 250A Four pole isolator 2 Nos. MC-1 db
MC-1 db
8.50 M.S. Black Conduits : MC-1 pw
MC-1 pw
Supply and installation of following size of MS conduit pipe in
recess or on surface including all accessories MS/CI
pull/junction boxes, GI fish wire, fixing hardware etc
. MC-1 pw
including chasing the walls/floor and plastering the chased
portion and making good the damages etc, complete as
required and as per specifications.
MC-1 pw
a) 20 mm dia 20 RM MC-1 pw
b) 25 mm dia 20 RM MC-1 pw
c) 32 mm dia 20 RM MC-1 pw
d) 40 mm dia 20 RM MC-1 pw
e) 50 mm dia 20 RM MC-1 pw
8.60 Sub-mains Wiring : MC-1 pw

VOLTEC ENERGY SYSTEMS Page 147


LABOUR RATE
MC-1 pw
Supply and drawing of following sizes of LSZH insulated,
stranded, copper conductor wires of 650/1100 Volts grade in
MC-1 pw
existing conduit pipe /wire ways including connection
/terminations etc as required.
MC-1 pw
a) 2 x 1.5 Sqmm + 1 No. 1.5 Sqmm Copper earth wire 20 RM MC-1 pw
b) 2 x 2.5 Sqmm + 1 No. 1.5 Sqmm Copper earth wire 20 RM MC-1 pw
c) 2 x 4.0 Sqmm + 1 No. 2.5 Sqmm Copper earth wire. 20 RM MC-1 pw
d) 2 x 6.0 Sqmm + 1 No. 2.5 Sqmm Copper earth wire 20 RM MC-1 pw
e) 4 x 4.0 Sqmm + 1 No. 2.5 Sqmm Copper earth wire 20 RM MC-1 pw
f) 4 x 6.0 Sqmm + 1 No. 2.5 Sqmm Copper earth wire 20 RM MC-1 pw
g) 2 x 10.0 Sqmm + 1 No. 6.0 Sqmm Copper earth wire 20 RM MC-1 pw
h) 4 x 10.0 Sqmm + 2 Nos. 6.0 Sqmm Copper earth wire 20 RM MC-1 pw
i) 4 x 16.0 Sqmm + 2 Nos. 10.0 Sqmm Copper earth wire 20 RM MC-1 pw
j) 4 x 25.0 Sqmm + 2 Nos. 16.0 Sqmm Copper earth wire 20 RM MC-1 pw
MC-1 pw
Note: MC-1 pw
MC-1 pw
In false ceiling areas the work is to be co-ordinated with
respect to interior work and rate for point wiring shall include
1) MC-1 pw
flexible conduit/fixing nipples/couplers etc from the junction
box up to the fitting.
MC-1 pw
All wires used for circuit / point wiring shall be Low Smoke
2) MC-1 pw
Zero Halogen (LSZH) wires.
MC-1 pw
TOTAL OF WIRING CARRIED OVER TO SUMMARY MC-1 pw
9.00 LIGHTING FIXTURES : MC-1 light
MC-1 light
Inspection, receiving, storing, handling, assembling,
installation, testing and commissioning of wall /ceiling,
surface/ recessed, suspended from down rod, in furniture,
fluorescent / incandescent / Halogen lamp fixtures including
making connections with PVC insulated stranded copper
conductor wires complete including steel supports, MC-1 light
suspenders, fixing screws, turn buckles, bolts, nuts (down
rods ball and socket arrangement and special channel
mounting for industrial fitting/chandelier) etc, as required. The
mounting arrangement of lighting fixture shall be as indicated
in the approved drawings.
MC-1 light
Pole Light with 70W Lamp, Pole Height 4.2 m (SIMES
i) 21 Nos. MC-1 light
Minislot Disk S.3982 with S.2846 Pole or Equivalent) (F11)
MC-1 light
Surfaced Downlight 1 x 26 W (Thorn Chalice C 190H 1 X 26
ii) 7 Nos. MC-1 light
W or Equivalent) (T12)
MC-1 light
Surfaced Downlight 1 x 26 W (Thorn Chalice C 190H 1 X 26
iii) W or Equivalent) (T2) complete with Emergency Lighting 3 Nos. MC-1 light
Units.
MC-1 light
Recessed Downlight 1 x 26W (Thorn Chalice C 190H 1 x
iv) 303 Nos. MC-1 light
26W or Equivalent) (T13)
MC-1 light

VOLTEC ENERGY SYSTEMS Page 148


LABOUR RATE
Recessed Downlight 1 x 26W (Thorn Chalice C 190H 1 x
v) 26W or Equivalent) (T13) complete with Emergency Lighting 84 Nos. MC-1 light
Units.
MC-1 light
Wall mounted Luminaire with 1 x 28W Fluorescent T5 Lamp
vi) water proof IP44 (SITECO Europlex 24W IP44 or Equivalent) 45 Nos. MC-1 light
(T8)
MC-1 light
Recessed Quad 2 x 18W (Thorn Matrix 300 2 x 18W or
vii) 22 Nos. MC-1 light
Equivalent) (T15)
MC-1 light
Recessed Quad 2 x 18W (Thorn Matrix 300 2 x 18W or
viii) 7 Nos. MC-1 light
Equivalent) (T15) complete with Emergency Lighting Units.
MC-1 light
Recessed Luminaire with 4 x 18W T5 Lamps with Parabolic
ix) 162 Nos. MC-1 light
Louvre (Thorn Omega BS/SB 4 x 18W or Equivalent) (T14)
MC-1 light
Recessed Luminaire with 4 x 18W T5 Lamps with Parabolic
x) Louvre (Thorn Omega BS/SB 4 x 18W or Equivalent) (T14) 34 Nos. MC-1 light
complete with Emergency Lighting Units.
MC-1 light
Recessed Luminaire 2 x 58W IP65 (Thorn Duopre 2 x 58W
xi) 13 Nos. MC-1 light
T26 H2F or Equivalent) (T23).
MC-1 light
Recessed Luminaire 2 x 58W IP65 (Thorn Duopre 2 x 58W
xii) T26 H2F or Equivalent) (T23) complete with Emergency 5 Nos. MC-1 light
Lighting Units.
MC-1 light
Recessed outside Downlight IP54 (Trilux Downlight IP54 or
xiii) 8 Nos. MC-1 light
Equivalent) (T21)
MC-1 light
Recessed outside Downlight IP54 (Trilux Downlight IP54 or
xiv) 5 Nos. MC-1 light
Equivalent) (T21) complete with Emergency Lighting Units.
MC-1 light

Step Light recessed in stairs with 11W LED Lamp diffusers


xv) with pressure formed glass IP64 (Bega Step Light TC-S 2191 156 Nos. MC-1 light
or Iguzzini Step Light Vision SP50 or Equivalent) (T26).

MC-1 light
Wall mounted Luminaire with 2 x 35W Fluorescent T5 Lamps
xvi) with Prismatic Diffuser (Thorn Prisma C 2 x 35 T16CL or 29 Nos. MC-1 light
Equivalent) (T19)
MC-1 light

Wall mounted Luminaire with 2 x 35W Fluorescent T5 Lamps


xvii) with Prismatic Diffuser (Thorn Prisma C 2 x 35 T16CL or 10 Nos. MC-1 light
Equivalent) (T19) complete with Emergency Lighting Units.

MC-1 light
Recessed Outside Downlight IP44 (Thorn Chalice C 190H 1 x
xviii) 4 Nos. MC-1 light
26W IP44) (T22)
MC-1 light
Bulk Head Light Wall Mounted with 2 x 28W TC-DEL Lamp
xix) 40 Nos. MC-1 light
IP-65 (Thorn Dunube 1 x 28W IP65 or Equivalent) (T11)
MC-1 light
Bulk Head Light Wall Mounted with 2 x 28W TC-DEL Lamp
xx) IP-65 (Thorn Dunube 1 x 28W IP65 or Equivalent) (T11) 4 Nos. MC-1 light
complete with Emergency Lighting Units.
MC-1 light

VOLTEC ENERGY SYSTEMS Page 149


LABOUR RATE
Surface mounted Industrial Luminaire with 2 x 36W
xxi) Fluorescent T5 Lamps (Thorn Indus RD 2 x 58W TW or 75 Nos. MC-1 light
Equivalent) (T6)
MC-1 light
Surface mounted Industrial Luminaire with 2 x 36W
xxii) Fluorescent T5 Lamps (Thorn Indus RD 2 x 58W TW or 32 Nos. MC-1 light
Equivalent) (T6) complete with Emergency Lighting Units.
MC-1 light
Emergency Exit Up Fixture complete with Emergency Lighting
xxiii) 9 Nos. MC-1 light
Unit (Cooper/Crompton or Approved Equivalent).
MC-1 light
Emergency Exit Down Fixture complete with Emergency
xxiv) 11 Nos. MC-1 light
Lighting Unit (Cooper/Crompton or Approved Equivalent).
MC-1 light
Emergency Exit Right Fixture complete with Emergency
xxv) 1 No. MC-1 light
Lighting Units (Cooper/Crompton or Approved Equivalent).
MC-1 light
TOTAL OF LIGHTING FIXTURES CARRIED OVER TO
MC-1 light
SUMMARY
10.00 EARTHING & LIGHTNING PROTECTION SYSTEM : MC-1 earth
MC-1 earth
10.10 Earthing System: MC-1 earth
MC-1 earth

Supply, installation, testing and commissioning of copper


plate earthing stations making earth pits, earthing with copper
earth plate 600 mm x 600 mm x 3.15 mm thick including
funnel, charcoal/coke, salt, all earth work. Providing masonry
10.1.1 14 Nos. MC-1 earth
enclosure with 10 mm thick C.I. cover plate having locking
arrangement and watering pipe, disconnecting/ testing links
etc as per IS –3043 complete as required, as per
specifications, drawings and direction of Engineer-in-charge.

MC-1 earth
Supply, installation, testing and commissioning of GI plate
earthing stations making earth pits, earthing with GI earth
plate 600 mm x 600 mm x 6.30 mm thick including funnel,
charcoal/coke, salt, all earth work. Providing masonry
10.1.2 2 Nos. MC-1 earth
enclosure with 10 mm thick C.I. cover plate having locking
arrangement and watering pipe, disconnecting/ testing links
etc as per IS–3043 complete as required, as per
specifications, drawing and direction of Engineer-in-charge.
MC-1 earth
Supply, installation, testing and commissioning of GI Pipe
earthing stations making earth pits, earthing with GI pipe
4500 mm x 40 mm Dia including funnel, charcoal/coke, salt,
all earth work. Providing masonry enclosure with 10 mm thick
10.1.3 2 Nos. MC-1 earth
C.I. cover plate having locking arrangement and watering
pipe, disconnecting/ testing links etc as per IS–3043 complete
as required as per specifications, drawing and direction of
Engineer-in-charge.
MC-1 earth
10.1.4 Earthing Strip/Tape/Cables : MC-1 earth
MC-1 earth

VOLTEC ENERGY SYSTEMS Page 150


LABOUR RATE
Supply, installation, testing and commissioning of following
sizes of GI/Tinned Copper strip/tape clamped to walls, cable
trays, bus ducts, recess in Ground or surface etc for
equipment/ System earthing complete as required including
MC-1 earth
inter connection between length at joints, all fixing
accessories saddles, clamps etc and other fixing hardware
material as required, as per specifications, detail drawings
shall be included for proper installation.
MC-1 earth
10.1.4.
G.I. Earthing strip/tape : MC-1 earth
1
MC-1 earth
a 50 x 8 mm strip 10 RM MC-1 earth
b 50 x 6 mm strip 10 RM MC-1 earth
c 40 x 6 mm strip 10 RM MC-1 earth
d 32 x 6 mm strip 10 RM MC-1 earth
e 25 x 6 mm strip 10 RM MC-1 earth
f 25 x 3 mm strip 10 RM MC-1 earth
MC-1 earth
10.1.4.
Tinned Copper earthing strip/tape : MC-1 earth
2
MC-1 earth
a) 50 x 6 mm 100 RM MC-1 earth
b) 32 x 6 mm 50 RM MC-1 earth
c) 25 x 6 mm 10 RM MC-1 earth
d) 25 x 3 mm 2100 RM MC-1 earth
Supply, installation, Termination, testing and commissioning
of PVC insulated, stranded copper conductor cable, laid on
10.1.5 surface/cable tray/duct/undger ground/Trench etc. as MC-1 cab
required, as per approved shop drawing, site conditions and
as directed by Engineer-in-charge.
MC-1 cab
a) 1C x 185 Sqm 400 RM MC-1 cab
MC-1 cab
b) 1C x 90 Sqm 10 RM MC-1 cab
MC-1 cab
c) 1C x 50 Sqm 10 RM MC-1 cab
MC-1 cab
d) 1C x 35 Sqm 10 RM MC-1 cab
MC-1 cab
e) 1C x 25 Sqm 10 RM MC-1 cab
MC-1 cab
Supply, installation, Termination, testing and Commissioning
of following sizes Tinned Copper Earth Bars including its
10.1.6 MC-1 earth
supporting/fixing hardware, as per drawings, specifications
and as directed by Engineer-in-charge.
MC-1 earth
10.1.6.
75 x 6 mm tinned, Copper, Earth Bars. MC-1 earth
1
MC-1 earth
a) 300 mm 1 No. MC-1 earth
b) 500 mm 2 Nos. MC-1 earth
c) 750 mm 3 Nos. MC-1 earth
d) 1000 mm 1 No. MC-1 earth
MC-1 earth

VOLTEC ENERGY SYSTEMS Page 151


LABOUR RATE
10.1.6.
50 x 6 mm tinned, Copper, Earth Bars. MC-1 earth
2
MC-1 earth
a) 300 mm 5 Nos. MC-1 earth
b) 500 mm 5 Nos. MC-1 earth
c) 750 mm 10 Nos. MC-1 earth
d) 1000 mm 5 Nos. MC-1 earth
MC-1 earth
10.20 Lightning Protection System: MC-1 earth
MC-1 earth

Supply, installation, testing and commissioning of copper


plate earthing stations making earth pits, earthing with copper
earth plate 600 mm x 600 mm x 3.15 mm thick including
funnel, charcoal/coke, salt, all earth work. Providing masonry
10.2.1 2 Nos. MC-1 earth
enclosure with 10 mm thick C.I. cover plate having locking
arrangement and watering pipe, disconnecting/ testing links
etc as per IS –3043 complete as required, as per drawings,
specifications and direction of Engineer-in-charge.

MC-1 earth
Supply, installation, testing and commissioning of GI Pipe
earthing stations making earth pits, earthing with GI pipe
4500 mm x 40 mm Dia including funnel, charcoal/coke, salt,
all earth work. Providing masonry enclosure with 10 mm thick
10.2.2 10 Nos. MC-1 earth
C.I. cover plate having locking arrangement and watering
pipe, disconnecting/ testing links etc as per IS–3043 complete
as required, as per drawings, specifications and direction of
Engineer-in-charge.
MC-1 earth
10.2.3 Earthing Strip/Wires : MC-1 earth
MC-1 earth

Supply, installation, testing and commissioning of following


sizes of GI strip/wire clamped to walls, Ductwork, pipe work,
Structural steel work, cladding work etc. in recess, in Ground
or surface etc for Lightning Protection System complete as
required including inter connection, terminations, between
length at joints, all fixing accessories saddles, plastic isolator MC-1 earth
mounting (of 50mmx80mm approx.), Sealing Collars, Sealing
Strip, Squared Timber Block (80mmx100mm approx.),
clamps, Lugs etc and other fixing hardware material as
required for proper installation as per detail drawings,
specifications and direction of Engineer-in-charge.

MC-1 earth
a) 25 x 3 mm strip 500 RM MC-1 earth
MC-1 earth
b) 25 x 6 mm strip 200 RM MC-1 earth
MC-1 earth
c) 32 x 6 mm strip 10 RM MC-1 earth
MC-1 earth
Supply, installation, Termination, testing and Commissioning
of following sizes GI Earth Bars including in supporting/fixing
10.2.4 MC-1 earth
hardware, as per drawings, specifications and as directed by
Engineer-in-charge.
MC-1 earth
10.2.4.
75 x 6 mm GI Earth Bars. MC-1 earth
1
MC-1 earth

VOLTEC ENERGY SYSTEMS Page 152


LABOUR RATE
a) 300 mm 2 Nos. MC-1 earth
b) 500 mm 2 Nos. MC-1 earth
c) 750 mm 2 Nos. MC-1 earth
d) 1000 mm 2 Nos. MC-1 earth
MC-1 earth
10.2.4.
50 x 6 mm GI Earth Bars. MC-1 earth
2
MC-1 earth
a) 300 mm 2 Nos. MC-1 earth
b) 500 mm 2 Nos. MC-1 earth
c) 750 mm 2 Nos. MC-1 earth
d) 1000 mm 2 Nos. MC-1 earth
MC-1 earth
Supply and fixing of Lightning Arrestor Rod/Lightning
Conductor finial made of 25 mm dia, 2.0 mm thick & 300 mm
Long GI Tube having single prong at top with 75 mm dia, 6
10.2.5 40 Nos. MC-1 earth
mm thick Base plate, including connections with roof parapit
Lightning protection Conductors, as per detailed drawings
and as per direction of Engineer-in-charge.
MC-1 earth
Supply and fixing of "Earth Test Joints" encased in 200 mm
(H) x 150 mm (W) x 100 mm (D) recessed in concrete with
10.2.6 10 Nos. MC-1 earth
removable cover plate as per detailed drawing and as per
direction of Engineer-in-charge.
MC-1 earth
TOTAL OF EARTHING & LIGHTNING PROTECTION
MC-1 earth
SYSTEM CARRIED OVER TO SUMMARY
MC-1 earth
GRAND TOTAL