KEY BENEFITS
Q Low priced scalable options – event reports, waveform capture, Q Two settings groups
reclosure, breaker fail Q Password protection for local operation
Q Reduce troubleshooting and maintenance cost – Event Q Automatic display of last fault information
reports, waveform capture
Q AC/DC power supply
Q Design flexibility – Easy to use programming logic
Q Improved user interface
Q Asset monitoring – Breaker health, and breaker failure
Q Access via front panel keypad or communication links
protection
Q EnerVista compatible
Q Access to information – Modbus RTU communications
Q Isolated front RS232 serial port
Q Configurable logic, curves, I/Os and LEDs
Q Flash memory for field upgrades

APPLICATIONS
Q Primary circuit protection on distribution networks at any Q Backup/auxiliary protection for transformers, generators
voltage level and motors

FEATURES
Protection and Control Monitoring and Metering
Q Phase and ground TOC and IOC Q 32-event record
Q Thermal image protection Q Analog/digital oscillography
Q Option “N” for single phase or ground applications Q KI2 counter for breaker maintenance
Q IAC time-current curves Q Per phase current metering
Q EPTAR-C time-current curves Q Monitoring of the last 5 trips information from the display
Q Circuit breaker control (open and close) User Interface
Q Four shot autorecloser Q EnerVista for setting and monitoring
Q Cold load pickup element Q 2x16 character LCD display
Q Configurable breaker failure to open Q 6 LED indicators, 4 configurable in function and colour.
Q Configurable I/O Q Front RS232 and rear RS485 ports using ModBus®RTU
Q 6 outputs: trip, service required, 4 auxiliary protocol up to 19,200 bps

183
MIF II Feeder Protection System MIF II Feeder Protection System

MIF II Technical Specifications


PROTECTION INPUTS ENVIRONMENTAL
Description or fiber optic port (plastic or glass fiber Phase TOC (51P) PHASE / GROUND TIME OVERCURRENT (51P, 51G)
Current: Fundamental
AC CURRENT
Secondary Rated Current:
Temperature:
Storage: -40ºC to +80ºC
optics) by means of using an external The TOC protection can be set from 0.1 to Pickup Level: 0.1 – 2.4 times In (rated current) in steps 1m 5 A depending on the selected Operation: -20ºC to +60ºC
The MIF II is a member of the M II Family of of 0.01 x In (51P & 51N if 1/5 A ground model, or 50 mA for sensitive ground Humidity: Up to 95% without condensing
converter, such as GE Multilin DAC300 or 2.4 times In. Four standard TOC curves can models)
models Pollution Degree: 2
protection relays. This relay is used to Dropout Level: 97% (typical) of Pickup
F485. Windows® based EnerVista software be selected in addition to a user config- Level Accuracy: ±1% of injected current at rated current Frequency: 50 / 60 Hz ±3 Hz (The unit can be set to
±3% in the complete range 50 or 60 Hz)
perform primary circuit protection on is provided free of charge with the relay to Curve Shapes: IEC (B.S.) A/B/C Relay Burden: < 0.2 VA @ In = 5A secondary
PACKAGING

distribution networks at any voltage level, urable curve. Each curve can be set with Level: ±1% at the rated current < 0.08 VA @ In = 1A secondary Approximate Weight:
allow setup and configuration of MIF units. customized time multipliers to coordinate ANSI Inverse, Very Inverse < 0.08 VA @ In = 1A sensitive ground, Net: 8.8 lbs (4 kgs)
or Extremely Inverse Ship: 9.9 lbs (4.5 kgs)
and backup/auxiliary protection for IAC Inverse, Very Inverse, Extremely
secondary
The MIF II can be accessed with a PC using with equipment. Inverse, Inverse Short or Inverse Long
Current Withstand:
transformers, generators and motors. Time delayed (0.00 to 600.00 sec. in 4 x In continuously TYPE TESTS
the M II EnerVista Setup Software via the steps of 0.01 sec. 100 x In for 1 sec. Test Standard Class
Basic protection features include time Time Dial: 0.05 to 2 in steps of 0.01 for IEC curves DIGITAL INPUTS InsulationTest Voltage:
RS232 communication port located in the Ground TOC (51G) 0.5 to 20 in steps of 0.1 for ANSI curves Voltage Level: 300 Vdc maximum
delayed overcurrent, instantaneous over- 0.5 to 10 in steps of 0.1 for IAC curves Recognition Time: < 4 ms
IEC 60255-5 2kV, 50/60 Hz 1 min
relay front panel. Use EnerVista to view or Reset Type: Instantaneous
Surge Test Voltage:
current (two levels), and thermal image This element has the same curve selection Timing Accuracy:
IEC 60255-5 5 kV, 0.5 J.
modify settings and relay configuration POWER SUPPLY (3 positive pulses
protection. Overcurrent elements can be choices and settings as the phase time ± 3% of set time for I > 1.50 times the
LOW RANGE
and 3 negative.)
(inputs, outputs, LEDs and configurable Actual Pickup Level for IEC/ANSI/ 1 MHz Interference:
three-phase and ground or single phase, overcurrent element. The ground signal is definite time curves Rated DC Voltage: 24 to 48 Vdc IEC 60255-22-1 III
logic), as well as to display metering ± 6% of set time for I > 1.50 times the Min./Max. DC Voltage: 19 / 58 Vdc Electrostatic Discharge:
depending on the selected model. normally derived as the residual sum of Actual Pickup for IAC curves
8 information, and real time status. If the Type/measure time: HIGH RANGE IEC 60255-22-2
EN 61000-4-2
IV
8 kV in contact,
8
An optional protection offering is also pro- the three-phase CTs eliminating the need DFT of 1 cycle Rated DC Voltage: 110 to 250 Vdc 15 kV through air
relay was furnished with the appropriate PHASE / GROUND INSTANTANEOUS OVERCURRENT Min./Max. DC Voltage: 88 / 300 Vdc
vided for cold load pickup, breaker failure for an additional ground sensor. For more (50P1, 50P2, 50G1, 50G2) Rated AC Voltage: 110 to 230 Vac @ 50 – 60 Hz
Radiointerference:
option, use EnerVista to display last fault Current: Fundamental Min./Max. AV Voltage: 88 / 264 Vac @ 50 – 60 Hz
IEC 60255-22-3: III
protection, breaker health, configurable sensitive detection, an additional core Pickup Level: 0.1 to 30.0 times In (rated current) in 40 MHz,
information such as event reports and an steps of 0.1 x In. (50P1/P2 & 50G1/G2 151 MHz,
logic, and autorecloser. balance (zero sequence) ground sensor for 1/5 A ground models)
Power Consumption: Max. = 10 W 450 MHz and
oscillography records. The MIF has a 0.005 to 0.12 A (50G1/G2 for sensitive Backup time: (date, time and log memory) cellular phone.
Each protection element can be selectively encircling the three-phase conductors can ground models) without power supply voltage Radiated Electromagnetic
drawout construction in 1/4 of a 19'' rack Dropout Level: 97% (typical) of Pickup > 1 week fields with amplitude
enabled either via the front panel or via be used. Overreach: < 2% modulation:
case. OUTPUTS ENV 50140 10 V/m
communications. Flexible settings, and Time Delay: 0.00 to 600.00 sec. in steps of 0.01 s
OUTPUT RELAYS Radiated Electromagnetic
selectable models for ANSI, IEC, IAC or Instantaneous Overcurrent (50) Reset Type: Instantaneous
Configuration: 6 Electro-Mechanical Form C fields with amplitude
Operate Time: Between 20 and 30 ms for I> 1.5 x Contact Material: Silver alloy suited for inductive modulation. Common mode.
EPTAR-C curves enable accurate coordina- Protection The MIF II includes two separately Timing Accuracy:
Actual Pickup loads
Maximum Operating Voltage:
ENV 50141
Radiated Electromagnetic
10 V/m

tion with other devices. adjustable IOC elements, each of which ± 3% of settled time for I > 1.5 times 400 Vac fields with frequency
The MIF II provides primary circuit the Actual Pickup Continuous Mode Current: modulation.
The basic MIF II has two fixed digital inputs can be independently enabled. MIF II Type/measure time: 16 A at 250 Vac. ENV 50204 10 V/m
protection for distribution networks of any DFT of 1 cycle
general purpose Fast Transients:
and six fixed digital outputs. An option is models provide two three-phase IOC THERMAL IMAGE ELEMENT (49) ¾ HP, 124 Vac ANSI/IEEE C37.90.1 IV
voltage, and backup/auxiliary protection Current: Fundamental IEC 60255-22-4 IV
elements and two ground IOC elements. 1-1/2 HP, 250 Vac
provided allowing the two inputs and four BS EN 61000-4-4 IV
for transformers, generators and motors. Pickup Level: 0.10 to 2.40 In in steps of 0.01 x In 10A, 250 Vac, 0.4 PF,
Magnetic fields at industrial
of the outputs to be user configurable. The pickup setpoint can be set from 0.1 to Dropout Level: Between 97% typical of Pickup Level B300 pilot duty
frequency:
As part of the M II Family, the MIF II Level Accuracy: ±1% at In
Make and Carry: 30 A
EN 61000-4-8 30 AV/m
30 times In and a time delay from 0 to 600 Breaking: 4000 VA
The basic MIF II has six fixed status LEDs. provides advanced digital protection ±3% in the complete range RELAY CONTACTS
Power Supply interruptions:
seconds. Heating Constant T1: Max rating for 10,000 operations
IEC 60255-11
An option is provided allowing four of these which includes: Temperature: IEC 57 (CO) 22
From 3 to 600 min in steps of 1 min. Voltage Make M&C Break Max RF Emission: EN 55011 B
LEDs to be user configurable. The front Cooling Constant T2: &Carry CONT. 0.2 seg Load Sinusoidal Vibration:
Thermal Image Unit (49) From 1 to 6 times ?1 in steps of 1. DC Resist 24 Vdc 16A 48A 16A 384W IEC 60255-21-1 II
panel also features a 5-button keypad and Overcurrent Protection Thermal Image Alarm: 48 Vdc 16A 48A 2.6A 125W Shock: IEC 60255-21-2 I
A thermal image element protects equip- From 70% to 100%Ipickup in steps 125 Vdc 16A 48A 0.6A 75W Insulation Test:
a 16x2 LCD display that provides an easy A variety of time curves are provided, of 1% 250 Vdc 16A 48A 0.5A 125W IEC255-5
ment against overheating due to excessive (Tested on CTs,
to use user interface. depending on model. It includes GE IAC, Timing Accuracy: AC Resist 120Vdc 16A 48A 16A 1920VA Power Supply
load. Several operating curves can be set 5% for operate times greater than 250 Vdc 16A 48A 16A 4000VA terminals,
The front keypad allows the user to set the ANSI, IEC, EPTAR-C (for resistive earths), 2 sec. Inductive 250 Vdc 10A 30A 10A 1000VA Contact Inputs
as a function of heating time constant T1 (PF=0.4) and Contact
baud rate and relay address for communi- definite time and user-programmable METERING Outputs)
(adjustable between 3 and 600 minutes). MECHANICAL CHARACTERISTICS
cation. curves. See ordering code for details. The FUNDAMENTAL CURRENT
APPROVALS
Cool down time constant T2 is adjustable Accuracy: ±1% at In • Metallic package in 1/4 19'' rack and 4 units high
A front RS232 and a rear RS485 communi- GE-IAC curves inverse, very inverse, ±3% in the complete range • Protection class IP52 (according to IEC 529) UL: UL listed
from one to six times the heating time CE: Conforms to EN/IEC 60255
cation port are provided for computer extremely inverse, short and long inverse ISO: Manufactured to an ISO9001 registered program
constant. MONITORING * Specifications subject to change without notice

access using ModBus®RTU protocol. The allow retrofit of most popular electro- OSCILLOGRAPHY
mechanical IAC relays. Records: 1 x 24 cycles
rear RS485 can be converted to an RS232 Sampling rate: 8 samples per power frequency cycle
Triggers: Any element pickup or operation
Ordering
Digital input configured as MIF II * * * * * * * * 00
Functional Block Diagram oscillography trigger
Communications command
P
N
3 phase + ground relay
Single phase or ground relay
Information: AC input channels
Digital input/output channels
A ANSI curves
Self-test events I IEC curves
EVENT RECORDER U IAC curves
52 Capacity: 32 events C EPTAR-C curves (only for single phase model)
Time-tag: To 1 millisecond 0 MIF II N models
Triggers: Any element pickup, operation or reset. 1 MIF II P models: Phase CT in = 1 A
79 Digital input/output change of state 5 MIF II P models: Phase CT in = 5 A
Self-test events
CLOSE TRIP 1 Ground CT In = 1 A
5 Ground CT In = 5 A
METERING
COMMUNICATIONS N Sensitive ground: CT In = 1 A
Local Communication: 2x16 LCD Display L Very sensitive ground: CT In = 1 A
Monitoring 5 button frontal keypad E English language
BREAKER HEALTH
Remote Communication: F French language
BREAKER FAILURE TO OPEN
(local or remote PC and communications net): 0 MIF II Basic Model
OSCILLOGRAPHY Mode: ModBus® RTU 1 MIF II Option 1 *
EVENT RECORDING Baud rate: 300 to 19200 bps 2 MIF II Option 2 **
COLD LOAD PICKUP
CONFIGURABLE I/O AND LEDS
DB9 connector for RS232 ports on the front (1) and 0 Without recloser
RS485 on the rear
CONFIGURABLE LOGIC
R With recloser (not available in the Basic Model)
1 50G-1 50G-2 51G 49 LO 24-48 VDC (Range: 19~58 Vdc) Power Supply
Accessories HI 110-250 VDC (Range: 88~300 Vdc) Power Supply
B1315P1 Depth reducing collar. Reduces the 110-230 VAC (Range: 88~264 Vac) Power Supply
MIF II N mounting depth by 2.45 inches. * Configurable I/O/LEDs, event recording, oscillography
EN MIFII N BLOCK ** Option 1 + cold load pickup, breaker failure to open, breaker health, configurable logic
B1343P1 S1/S2 case adapting collar for retrofit
installations

www.GEMultilin.com www.GEMultilin.com
184 189
MIF II Feeder Protection System MIF II Feeder Protection System

Typical Wiring CAUTION: FORK OR RING TERMINALS MUST


BE USED ON THE TERMINAL BLOCK Inputs and Outputs Option 1 Features
NOTES: The basic unit of MIF II incorporates two
SUITABLE DISCONNECT DEVICES RECOMMENDED
ALTERNATIVE CT WIRING FOR
RESIDUAL GROUND SENSING MIF II OPTION 1 units include all the
LOCATED NEAR THE RELAY inputs programmed as Disable 50P and
20 A MAX CIRCUIT BREAKER functions described above plus the follow-
Disable 50G, and 6 outputs, programmed
PHASE A CT
OVERVOLTAGE CATEGORY: II LOCATED BEFORE
POWER INPUT A ing features.
ZERO SEQUENCE
GROUND SENSING CONNECTION
PHASE B CT
as Service Required, Trip, Phase Trip,
B
NOTE: 14 AWG wiring PHASE C CT
Ground Trip, 50 Trip and 49 Alarm.
PHASE A CT ZERO SEQUENCE
GROUND CT
recommended
C Event Recording
A AC
The factory configuration of MIF II inputs
Events consist of a broad range of change
PHASE B CT OR
DC
LINE B and outputs can be easily modified using
PHASE C CT
of state occurrences, including pickups,
C EnerVista software in relays with OPTION 1
trips, contact operations, alarms and self
or OPTION 2.
C1 C2 C3 C4 C5 C6 C7 C8 test status. The MIF II stores up to 32 events
IA N IB N IC N IG N time tagged to the nearest millisecond. This Inputs, outputs and LEDs can be easily
A1 A2
C1 C2 C3 C4 C5 C6 C7 C8
Multiple Setting Groups provides the information needed to
conf igured using EnerVista
IA N IB N IC N IG N +/L -/N
8
CIRCUIT
BREAKER
POWER CURRENT INPUTS
Two separate settings groups are stored in determine sequence of events which Option 2 Features 8
INTERNALLY FUSED nonvolatile memory, with only one group facilitates diagnosis of relay operation.
1A / 250V FAST BLOW MIF II OPTION 2 units include all the
CURRENT INPUTS active at a given time. Switching between Each event is individually maskable in functions described above plus the
setting groups 1 and 2 can be done by order to avoid the generation of undesired
52a 52a SDA B12(*) A following features.

g
means of a setting, a communication

RS485
TRIP COIL -
TRIP
COIL Multilin MIF II SDB A12(*)
events, and includes the values of currents
A5 B
TRIP command or contact input activation.
CONTROL Feeder Protection System
and status of all the protection elements at
POWER + A6 GND B11 (*) GROUND Cold Load Pickup
Settings classified into two categories, the moment of the event.
This feature adapts the pickup of the
READY

main and advanced settings. This allows

COM OUT4 OUT3 OUT1/2 OUT1


B5 INPUT
B7
overcurrent elements to override higher

DIGITAL OUTPUTS (**)


B6 users to have access to main relay Oscillography
overload currents resulting from re-ener-
PROGRAMMABLE functionalities in an extremely simple, MIF II captures current waveforms and
INPUTS (**)

A8 CC1 B8 CONTROLLER gization.


user-friendly way by entering only main
DIGITAL

JX digital channels at 8 samples per cycle.


A9 CC2 settings. Access to complete functionality One oscillography record with a maximum
A10 COM
B9
for more complex use is available through Breaker Failure Protection
WARNING: length of 24 cycles is stored in memory.
GROUND PC TO RELAY GROUND. advanced settings. Oscillography is triggered either by internal A simple “breaker has not opened” feature
OTHERWISE USE UNGROUNDED PC RS232 B10
signals or an external contact. is standard. A complex breaker failure
SAFETY
scheme can be easily implemented
Metering
GND GROUND A7 INPUT
through a digital input and configurable
Configurable I/O and LEDs
GROUND BUS
(*) Terminals B12, A12 and B11 must be connected to SELV (safety extra-low MIF II provides metering values for phase output logic (logic gates and timers).
In MIF II OPTION 1 and OPTION 2 models,
voltage) parts (on the PLC). They are not to be tested for hipot test under and ground currents. The accuracy is 3% in
any circumstance the two digital inputs are user config-
the complete range, and 1% at the rated Breaker Health
urable. Out of the six digital outputs
(**) In the basic model, inputs and outputs are configured as follows: current. The breaker health threshold is set by the
incorporated, two have a fixed function
INPUTS OUTPUTS (trip and service required), while the other user to achieve “just in time” maintenance.
CC1: Disable 50P Function OUT1: Phase Trip Primary or Secondary Metering When the cumulative I2 value exceeds the
OUT2: Ground Trip
four are user programmable. Those config-
CC2: Disable 50G Function threshold, an alarm is issued.
OUT3: 50 Trip The MIF II can monitor both the primary urable outputs can be assigned either to a
OUT4: 49 Alarm and secondary current metering values, by set of pre-configured values, or an OR/NOT
previously setting the corresponding CT combination of the same values. Each Configurable Logic
ratio. configurable output can be independently Up to a maximum of 4 configurable logic
Dimensions latched, and individually selected as NO or schemes can be implemented into the MIF II
6.243 10.472 5.35(136) NC by means of a jumper. by means of using a set of 4 pre-configured
( 158,6 ) (266)
4.33(110) Outputs 1 and 2 can be isolated from logic gates and timer cells. A graphical user
O0
.27
(0 outputs 2 and 3 by removing jumber JX. interface is provided for configuration of
.7)
MIF II logic. The inputs of the MIF II config-
Optional depth Four of the 6 LED indicators can also be
reducing collar
urable logic can be assigned to contact
programmed by the user. The first LED has
outputs and/or LEDs.
4.0 (101.6)

a fixed assignment (relay in service), the


7.0 (178)

ESC

7.131 ENTER second is fixed for trip, and the remaining


(181,1) MENU

four LEDs are configurable in function, Circuit Breaker Control


memory and color(red or green). The MIF II permits operation of the circuit
g Use the oscillography feature as an accurate
M II Digital Protection System

troubleshooting and diagnostics tool breaker. Breaker opening and closing


operations can be carried out by program-
EN MIFII DIM C ming specific outputs, and digital inputs
6.819
(173) can be used for verifying the success of the
9.276
(235,5) operation.

FRONT SIDE CUTOUT


* Note: Dimensions in inches (mm)

www.GEMultilin.com www.GEMultilin.com
188 185
MIF II Feeder Protection System MIF II Feeder Protection System

User Interface Q Converts Modbus RTU over RS485 into relevant data and options for the relay it is the industry experience of GE, all in one
Modbus TCP/IP over Ethernet communicating with. This eliminates very cost-effective package.
Q Supports both 10BaseT and 10BaseF having to manually configure the relay Unlike complicated tools consisting of mul-
DISPLAY fiber connections within the software and provides a simple tiple applications, EnerVista VIEWPOINT
16x2 characters LCD display for
viewing setpoints, actual value Q Connect up to 32 RS485 serial devices to and easy to use operator user interface. offers a truly simplified user interface.
messages, and fault reports
an Ethernet network Creating a site diagram is as easy as drag-
Q Modbus TCP/IP provides multiple SCADA ging and dropping icons for analog and
STATUS INDICATION LEDs
Four of six status LEDs are masters allowing simultaneous commu- digital values. Monitored quantities are
user programmable in function nications to the same IED presented in familiar formats like gauges
and color
Q Flexible mounting options allow retro- fit and dials. You can also choose an annunci-
CONTROL AND to existing devices ator panel view that provides a virtual front
PROGRAMMING KEYS
Escape, Reset, Enter, Menu Up, Q Industrially hardened for utility and panel for your equipment complete with
and Menu Down keys for complete industrial applications alarm and alert notification.
access to settings and information
without a computer Q Simple “plug & play” device setup with
8 EnerVista software 8

EnerVista setup software, an intuitive easy to use


man machine interface

All M II Family products are supplied with


Windows® based EnerVista M II Setup
PROGRAMMING PORT
RS232 Communications Port Software. EnerVista is an easy to use tool
for connection to a computer that allows the communication with M II
Family relays for monitoring, setting
changes, and configuration. EnerVista
software may be run on a PC with any
Autorecloser Four additional LEDs are programmable in Self Test Diagnostics Connect up to 32 ModBus devices to your ethernet Windows® based operating system. The EnerVista Viewpoint, a plug-and-play tool for real-
function and color. The factory default network including M II devices
Comprehensive self-test diagnostics occur program may be used locally on the RS232 time monitoring and troubleshooting the power
The automatic recloser is intended for use functions of the programmable LEDs are: front port or remotely on the RS485 port. It system
at power up and continuously during relay MultiNet gives you the ability to connect M
in three-pole tripping schemes and single Phase Trip, Ground Trip, 50 Trip, and provides full access to the relay data with
operation. Any problem found by self-tests II serial devices to new or existing Ethernet EnerVista VIEWPOINT works seamlessly
breaker applications. Up to four reclosing Pickup, while the color is set to RED, and the following features:
causes an alarm and an event is logged. networks. It has a 10Base-F fiber optic with the entire family of GE Multilin protec-
"shots" are possible prior to locking out. the status memory as self-resetting. The
interface that provides high EMI/RFI Q View relay status and actual values tion, control and communications devices,
Each shot has an independently program- user may change the function and status
mable dead time. Communication Ports immunity and inherent electrical isolation Q View/edit settings on-line/off-line including M II relays. The software also
memory through the use of the EnerVista includes a custom device editor that allows
A front mounted RS232 and a rear RS485 over long cable runs. MultiNet setup is View event recorder for trouble-shoot-
The autoreclosure scheme provides outputs software. Q
you to connect to virtually any generic
port allow easy user interface via a PC. simple, with a Windows®based EnerVista ing
that can be used to modify circuit protection The LED color can be modified using the Modbus compliant Intelligent Electronic
ModBus® RTU protocol is used for all ports. software program for installing and Configure inputs, outputs and LEDs
settings between shots. relay keypad. The status memory may be
Q
Device (IED) by creating a custom memory
The relay supports baud rates from 300 to configuring the communication drivers. through configurable logic
programmed either self-resetting or 19,200 bps. Up to 32 GE Multilin devices map.
Q Utilize a configurable protection curve
User Interfaces latching. If programmed as self-resetting, can be addressed on a single communica- EnerVista Software
Relay firmware programming for
when the associated function drops out Q

Display the corresponding LEDs turn off. If


tions channel. A unique address must be upgrades MIF II Guideform
assigned to each relay via a setting when
Measurement data (actual values), fault
programmed as latched, the LED will multiple relays are connected.
In addition, all status information such as Specifications
remain "ON" until the ESC/RESET key is target messages and digital input/output
reports for the last five trips, and settings For an electronic version of the MIF II
pressed for three seconds to reset the states may be viewed with EnerVista M II
are shown on the 16x2 characters LCD GE MultiNet™ compatible Setup Software. guideform specifications, please visit:
relay.
display. MultiNet is a communications module that www.GEMultilin.com/specs, fax your
In order to test LEDs, pressing the request to 905-201-2098 or email to
provides GE Multilin serial ModBus IEDs EnerVista VIEWPOINT
Status LEDs ESC/RESET key for three seconds will turn literature.multilin@ge.com.
with ModBus TCP/IP communications over
"ON" all LEDs. When the key is released, the Introducing EnerVista VIEWPOINT soft-
The MIF II incorporates 6 LED indicators in Ethernet, allowing connection to fiber optic
LEDs will turn off (except if the function ware, the simplest way to monitor and
the front plate. The first one is a green LED LAN and WAN network systems.
identified as "READY", used to indicate the
pickups are still active). This allows easy
MultiNet has the capability to connect up
EnerVista MII setup software is a common interface control your site-based equipment using Accessorize your MIF II
testing of the equipment. tool for the entire MII Family of products any Windows®based PC. With EnerVista
status of the protection elements. When to 32 serial ModBus devices eliminating
A single PC setup software package is VIEWPOINT you can easily create detailed
"ON" it means the relay is energized and complex wiring and additional communi-
Keypad required to access, configure, and monitor graphical representations of your entire
ready to protect, and at least one protection cations converters, and providing a
all the relays in the M II family, regardless site, connect onscreen icons to your equip-
element has been enabled. A five-button keypad allows user access streamlined and economical Ethernet hub.
of their model, application, or available ment and start managing in minutes.
for easy relay interrogation and change of Unlike most communications converters
The second one is a red LED used for TRIP options. The EnerVista M II Setup Software www.GEMultilin.com
settings. As part of the EnerVista suite of products
indication. It will be "ON" when a fault that are designed for commercial use,
extracts the model number, version, and and services EnerVista VIEWPOINT
occurs and the relay energizes the trip Access to events and oscillography MultiNet is environmentally hardened to
configuration parameters from the combines the power to easily monitor and
outputs. Once energized, it will remain records, and unit configuration is possible withstand severe utility and industrial
connected relay to display only the control your site-based equipment with
latched until the ESC/RESET key is pressed only through PC communication. conditions.
for three seconds to RESET the relay.

www.GEMultilin.com www.GEMultilin.com
186 187