You are on page 1of 2

IBM System X –

PDU Solutions for EMEA


Front
Follow these 4 easy steps to choose the right PDU
Back 1. First, determine what power is available on site (Example: 16A, 1Ph = 16 Amp, 1 Phase)
2. Determine the load, required in Watts or Amps
DPI PDI+ PN 39M2818

3. Choose your PDUs based on the number of total outlets required


(see next page for help, may may need to have a combination of the below)

4. Follow the chart looking at the plug type you required


(C13 for x366, x336 & ……………C19 for BladeCenter)

PDI PDU+ PN 39M2816


C13 Plug Type C19 Plug Type

1Ph/ Max Load Power Power


Outlets PDU Part No. Outlets PDU Part No.
3Ph Watts/Amps Cord Cord

230V supplied
16A DPI Universal Rack PDU no solution available for C19
<3,450W 7 with
1 Ph (choose part code from Table A) see 7,360 watt options and above
<16A PDU

IBM DPI PDU+ IBM DPI PDU+


12 40k9612 6 40K9612
P/N 39M2816 P/N 39M2818
230V
DPI Enterprise PDU PN with line cord attached PN 39Y8923, 39Y8948

32A
<7,360W One DPI Front End PDU
1 Ph supplied
<32A P/N 39Y8934 DPI Front-end PDU supplied
21 with 3

DPI High Density PDU PN 39Y8999


and three DPI Universal Rack PDU P/N 39Y8934 with PDU
PDUs
(choose part code from Table A)

One DPI Front End PDU


230V supplied
63A P/N 39Y8935 DPI PDU
<10,350**W 21 with 3 40K9613
1 Ph and three DPI Universal Rack PDUs P/N 39Y8935
<63A PDUs
(choose part code from Table A)

230V
63A IBM Enterprise PDU DPI PDU+
<14,490W 12* 40K9613 6 40K9613
1 Ph P/N 39Y8941 P/N 39M2818
<63A

DPI PDU+
6 40K9611
230V P/N 39M2818
32A DPI PDU+
<22,080W 12* 40K9611
3 Ph P/N 39M2816 DPI High Density
<32A supplied
12 PDU
with PDU
P/N 39Y8999
* Can get up to 24 recepticles when using the 2.8M rack power cable (IBM P/N 25R5785)
**The wattage is limited by the Front End PDU

DPI Rack PDU PN 39Y8951 to 39Y8962


Table A
Test Drive the new DPI+ PDU @
DPI PDU is supplied with country specific
DPI Front End PDU PN

http://192.104.67.81
39Y8934, 39Y8935

connections, choose yours


DPI Enterprise PDU with Line Cord attached PN 39Y8941

PDU & Euro line cord 39Y8952 user name and password : ibm
PDU & Denmark line cord 39Y8953
PDU & Israel line cord 39Y8954
Y o u r E a t o n A c c o u n t M a n a g e r i s :
PDU & Italy line cord 39Y8955 Note: We offer on site training on
PDU & South Africa line cord 39Y8956 PDUs, to set this up, contact:
Fiona Carlton-Shields
PDU & UK line cord 39Y8957 Ph: +44 (0) 1753 608913
Note: Rack PDU is supplied with IEC C19 to IEC M o b : + 4 4 ( 0 ) 7 7 6 8 7 0 6 1 6 7
C20 power cord fionacarlton-shields@eaton.com

DPI Rack & Front End DPI Enterprise PDU New DPI PDU+
DPI High Density PDU
Feature (FE) PDU 39Y8923, 39Y8941 & 39M2816 to
39Y8999
39Y8905 to 39Y8962 39Y8948 39M2819
Type of PDU Good Better Better Best
DPI Nema PDU PN 39Y8905

Qty 5 - 15 outlets 6 (Nema) none none none


Qty C13 (10A) outlets 7 (Rack) none 12 12
Qty C19 (16A) outlets 3 (FE) 12 6 6+3/C13
Size ½ width Full width Full width Full width
Connection Sides 2 2 1 1 or 2
Overload protection Fuse* Fuse* Breaker Breaker
Maximum Operating Temp 40C 40C 40C 60C
Inout Voltage (Phases) 1Ph & 3Ph 3Ph 1Ph & 3Ph 1Ph & 3Ph
Monitoring none none none Ethernet Remote
*Unit replacement is required to change the fuse
Web sites IBM: http://www- 1.ibm.com/servers/eserver/xseries/storage/rack.html
Page 1
Eaton: http://www.oem.powerware.com/ibm -ups/Products/9910solutions/systemx.asp PDU EMEA Handout v6e 14 Aug 2006
IBM System X PDU Solutions for EMEA

Rack Device PDU Solutions


Amps Amps Amps
16A 32A 63A
.
[32A 3 phase]
39Y8935
.
40K9613
Up to 7 . .
39M2819, 39Y8923,
73P5847
outlets . .
Up to 12* Up to 12*
outlets outlets
39Y8952, 39Y8953
39Y8954, 39Y8955
39Y8934 39Y8956, 39Y8957 39M2816 or 39Y8941 + 40K9613 39M2816 + 40K9612 39Y8958
Note: PDU supplied with 39Y8941 + 40K9612
40K9612
country specific cable. 39M2816 or 39Y8941 + [40K9611]
See Table A
*Up to 24 when using 2.8M rack power Y cable.

BladeCenter PDU Solutions


40K9614 39Y8951
Amps Amps Amps
32A 63A 32A 3 phase
Redundant
PDU

39Y8952
39Y8957

39Y8934 (3) 39Y8948 + 40K9613 (6) 39Y8948 + 40K9611 (6)


39M2818 + 40K9612 (6) 39M2818 + 40K9613 (6) 39M2818 + 40K9611 (6)
39Y8999 (12)
39Y8999
40K9611
BladeCenter with 2,000W power supplies. (Qty C19 outlets). Redundant PDU. 39Y8956

BladeCenter H PDU Solutions Amps


If 3 phase, balance
63A or [32A 3 phase]
Phase A: 16A (PS) Select IBM P/N 25R5785
Phase B: 16A (PS)
to connect BC-H to PDU
Phase C: 5A (blower)
total: 37A Power supply (PS) (sold with BladeCenter) Triple IEC C19 Cable Set

40K9615
Amps Amps 39Y8955

63A 32A 3 phase


NOTE: 32A 1-phase
will not support BC-H

39Y8954
39Y8953

39Y8935 (3) 39Y8948 + 40K9611 (6) 39M2818 & 40K9612 (6)


39M2818 + 40K9612 (6) 39M2818 + 40K9611 (6) [39Y8948 + 40K9611 (6)]
39Y8999 (12) [39M2818 + 40K9611 (6)]
[39Y8999 (12)]
C13/14 C19/20
Some PDUs may have more outlets than shown, (Qty C19 outlets). Redundant PDU.

You might also like