You are on page 1of 76

CI/SfB

(47) Nh2
Nov 2002

Approved Construction Details


for Part L2 (England and Wales) and Part J (Scotland)
Building Regulations & Standards for Conservation of Fuel & Power (Non-Domestic Buildings)

Insurer Approved
Systems
2

Contents Building Regulations Com

Building Regulations Compliance in 7 steps 2 Part L2: 2002 Conservation of Energy includes four major
changes to traditional insulated metal roofing and cladding.
a. Reduced heat loss by improved U-values and
Parts L2 and J Project Design, 4
limits on thermal bridging.
Specification, Construct ion, b. Limit on air leakage for building envelope.
Testing & Handover Compliance Checklist c. Measures to quantify the risk of condensation.
d. Certificate or declaration by a suitably qualified
competent person(s) that the as-built roof and walls
Building Regulations 2000 Part L2 6
comply with the requirements of Part L2.
Conservation of Fuel & Power (England & Wales)
Architects and designers now need to take an integrated
and holistic design approach to achieve regulatory
Building Regulations 2000 Part L2 7 compliance.

Elemental Method Kingspan Roof & Wall Solutions


STEP 1 - DESIGN
Building Standards 1990 Part J 8 The design will need to be based on a complete integrated system
solution for roof and/or wall cladding. Kingspan can provide
6th Amendments: Conservation of Fuel & Power (Scotland)
construction solutions and details to achieve regulatory compliance
with U-values, thermal bridging, air leakage and insulation continuity
Building Standards 1990 Part J 9 to the approved standard suitable for the intended use of the
building e.g. industrial, office, swimming pool, etc.
Elemental Method Kingspan Roof & Wall Solutions

Building Heating Loss through 10


Thermal Bridging

Thermal Bridging & Heat Loss 12


Calculation Example

Air Leakage Risk Areas 14

Standard Construction Details 16


STEP 2 - BUILDING
CONTROL APPLICATIONS
Enhanced Construction Details 50
Architects or designers have to calculate the a-value (alpha)
for the building envelope to achieve compliance of a equal to
or less than 0.10 or demonstrate compliance via the alternative
Two sets of details have been produced to trade off route. In order to make the a calculation, the
give the Building Designer flexibility within the architects or designers as competent person(s) will most likely
calculation for the total building heat loss. need the assistance of the envelope system manufacturer to
provide f and Y values for the roof and wall cladding design.
The decision on the choice of standard or Any changes to specification of the cladding after the a-value
enhanced details is taken by the Building is calculated will mean that the value has to be recalculated.
Designer and is determined from the total If the a-value is too high the design and/or products will have
building heat loss methodology demonstrated on to be amended to achieve compliance.
pages 10 & 11 of this guide.
A mixture of both standard and enhanced
STEP 3 - TENDER
details maybe required for some projects. The architects or designers have to specify roof and wall
cladding systems which can achieve compliance with the
requirement to minimise heat loss at all junctions or thermal
bridges.
Detailed drawings should be provided for each part of the roof
and wall system, including all junctions, penetrations,
abutments, internal gutters, smoke vents, louvres, soakers,
doors, windows, rooflights, curtain walling, brickwork and floor
slab edge etc.
Kingspan as a roof and wall system manufacturer provide a
comprehensive package of details for which the f, Y and air
leakage seals have been optimised for differing building uses.
3

pliance in 7 Steps

STEP 4 - CONSTRUCTION STEP 7 - CONTINUITY


The duties of competent person(s) may be carried out by the
OF INSULATION
developer/main contractor from step 4 onwards. The Provide a declaration that appropriate design and installation
competent person(s) will be responsible for ensuring that the has been carried out to achieve reasonable conformity.
approved design is built and that workmanship quality also Alternatively carry out a thermographic survey by competent
achieves compliance. Should alternative roof and wall systems person to demonstrate that the insulation is reasonably
or products be substituted to that specified it is necessary that continuous over the visible envelope of the building and that
they are fully regulatory compliant. excessive thermal bridging is avoided.
Kingspan’s construction details have been designed to be
Note: Building Control should be asked to confirm in advance who they
installer friendly and robust so that a high level of workmanship consider is competent to complete the various declarations required before
quality can be achieved combined with fast installation speed. the completion certificate is issued.

Failure to achieve regulatory compliance will result in project


handover delays and subsequent rectification costs.

KINGSPAN PARTS L2 & J


SERVICE AND TOOLKIT
Construction Solutions Service
• Industry awareness and education programme
for property investors, agents/advisers, design
teams, constructors, installers and building control.
• Project specific roof and wall system solutions and
construction details for designers, contractors and
installers.
• Contractor and site installer training programme.
STEP 5 - INSPECTION & TESTING • Specialist site service support.
• Independent design - construction,
Materials being installed and workmanship quality will need to air leakage testing and infra-red
be checked during construction so that the competent service available through alliance
person(s) can provide the required certificate or declaration with Building Sciences Ltd.
following air pressurisation testing and thermographic
inspection survey.
Toolkit

STEP 6 - AIR TIGHTNESS TESTING


On buildings of any size, an air leakage test has to be carried
out to provide a declaration from a competent person(s) that
the test result demonstrates regulatory compliance.
Alternatively for buildings of less than 1000m2 floor area a
declaration that appropriate design and installation has been
carried out to achieve conformity to specification for regulatory For further information contact our
compliance. Technical Services Department on:
Hotline: 01352 716101
or Email: info@kingspanpanels.com

All construction details are available in AutoCAD and


DXF format from the Kingspan website.

www.kingspanpanels.com
4

Parts L2 and J Project Design, Specification, Construct

PARTS L2 & J ELEMENTAL PRE-TENDER


DESIGN
METHOD REQUIREMENTS SPECIFICATION

U-Value Requirements (W/m2K) 1 Calculation by Elemental method. 1 Specify selected roof and wall system
Part L2 Part J
(England & Wales) (Scotland) • Roof products
2 Select type of roof and wall systems. - Type and reference.
Roofs 0.25 0.25
Walls 0.35 0.30 3 Select U-Value requirements. • Wall products
Rooflights - Type and reference.
Max 20% Area 2.20 2.20 4 Determine insulation continuity integrity. • U-Value requirements.
Max 12% Area* 3.00 3.00
* Rooflights may be permitted up to 12% of roof area
5 Determine solar gain and rooflight • Thermal and insulation continuity
at 3.0W/m2K however, there is significant risk of
condensation. requirements. requirements.
Part L2 Additional Calculation Requirements • Solar gain and rooflight
• Calculation to assess risk of surface 6 Determine cold bridges and heat loss requirements.
mould growth and condensation risk areas.
introduced - • Air tightness requirement
Surface Temperature f-factor. 7 Determine airtightness standard (Part (Part L2 only).
Internal humidity classes and the L2 only).
minimum temperature factor necessary 2 Specify ancillary components i.e.
to prevent condensation. 8 Develop compliant designs and details doors, windows, rooflights, gutters,
for envelope joints, junctions, internal smoke vents, louvres and soakers etc.
Table A
Humidity Minimum gutters, penetrations, rooflights and
Class Building Type f value abutment details. 3 Specify f-factor and Y-values for all
1 Storage areas 0.30 junctions, penetrations, abutments,
2 Offices & shops 0.50 internal gutters and provide project
3 Dwellings with low occupancy 0.65 9 Calculate f-factor value for intended
4 Dwellings with high occupancy, 0.80 building use (see Table A) and details specific design solutions, construction
sports halls, kitchens, canteens; indicated in 8 above. details and specifications.
buildings heated with un-flued
gas heaters
5 Special buildings, e.g. laundries 0.90
10 Calculate Y-values for envelope system 4 Indicate whole building’s a-value for
breweries, swimming pools and details indicated in 8 above. specified envelope system.
The BS EN 13788 methodology leads to the temperature factors
necessary to avoid condensation shown in the table above. 11 Calculate whole building’s a-value and 5 Specify lifecycle durability
• Calculation to establish extent of heat check this is within the limits for requirements.
losses through thermal bridges at details building use (see Table B).
- Y Value (psi). 6 Agree with building control body that
• Calculation to assess total heat loss 12 Determine lifecycle durability the design and specification complies
through all thermal bridges a-value must warranties. with Part L2 or J requirements and that
not exceed limits stated in BRE • U-Value and insulant integrity the person providing certificates or
Information Paper 17/01. declarations for insulation
• Airtightness level
Table B • External coatings standards/continuity, air tightness and
a-value must be less than or equal to: • Structural performance testing is suitably qualified and
0.16 domestic buildings competent.
0.10 non-domestic buildings
13 Determine design parameters for
Part L2 Completed Building heating, ventilation and HVAC system 7 Incorporate compliant design(s) and
Compliance Testing specification(s) into employer’s tender
and subsequent energy usage levels
Air Leakage Testing Requirements package.
and operating costs.
• Maximum air leakage rate up to
30 September 2003 is 11.5m3/hr/m2 @ 50PA
• Maximum air leakage rate from
1 October 2003 is 10m3/hr/m2 @ 50PA
Infra-Red Thermographic Surveys
• Infra-red thermographic report confirming
that insulation “is reasonably
continuous over the whole visible
envelope”. where required.
5

ion, Testing & Handover Compliance Checklist

MAIN OR DESIGN - BUILD ROOFING & CLADDING PROJECT APPROVAL,


CONTRACTORS CONTRACTORS TESTING & HANDOVER

1 Obtain from employer or employer 1 Obtain from employer or employer 1 All Buildings
agent(s) project specific Part L2 or J agent(s) Part L2 or J compliant design Suitably qualified competent person(s)
envelope compliant pre-tender and envelope specification package to prepare written report confirming
package which includes: including: design, specification and site
• U-values, insulation continuity integrity, • Roof products workmanship quality compliance with
cold bridges and heat loss solutions. - Type and reference. regard to U-Values, insulation continuity,
limiting thermal bridges and air leakage.
• Airtightness standard (Part L2 only). • Wall products
- Type and reference. 2 Buildings larger than 1,000m2 floor area
• Solar gain and rooflight requirements.
Airtightness test (Part L2 only) in
• Calculated f-factor and Y-values for • U-values. accordance with CIBSE TM 23, the
all junctions, penetrations, abutments, • Insulation/thermal continuity solutions. whole building envelope has a maximum
internal gutters and approved design • Solar gain and rooflight requirements. air leakage rate of 10m3/hr/m2 @ 50 Pa.
and construction details (Part L2 only). Note: Until 30 September 2003 reasonable provision in
• Airtightness requirement the event that initial airtightness test results are
• Calculated whole building’s a-value (Part L2 only) and sealing methods. unsatisfactory would be the results of further tests
(Part L2 only). carried out after appropriate remedial work showing:-
• f-factor and Y-values for junctions, an improvement of 75% of the difference between the
• Parts L2 or J compliant solutions for penetrations, abutments, internal initial test result and the target standard of 10m3/hr/m2
doors, windows, rooflights, smoke gutters, smoke vents, louvres and @ 50 Pa; or, if less demanding a performance no
vents, louvres, soakers, brickwork, worse than 11.5m3/hr/m2 @ 50 Pa.
soakers etc.
curtain walling, floor slab and other 3 A suitably qualified person(s) to issue a
elements. • Whole building’s envelope a-value.
certificate or declaration that appropriate
• Windows, doors and other openings • Specified doors, windows, rooflights, design details and building techniques have
maybe treated as adiabatic junctions. internal gutters, smoke vents, been used and that the work has been
penetrations, soakers, curtain carried out in ways that can be expected to
2 Plan airtightness testing (Part L2 only). walling, brickwork and floor slab achieve reasonable conformity with the
3 No infra-red thermographic testing is edge systems/solutions and details. specifications that have been approved for
required with Kingspan roof and wall the purpose of compliance with Part L2.
2 Any change to selected or specified
systems as insulation continuity is Alternatively an infra-red thermographic survey of
system or product will alter system completed building envelope to show that the insulation
guaranteed within the panels. compliance. Assess and verify is reasonably continuous over the whole building
alternative systems/solutions for envelope by a competent person in accordance with
4 Agree with building control body prior BRE Report 176 and BS EN 13187.
to work starting suitably qualified compliance.
4 CDM - Health and Safety File for the
competent person(s) who can audit 3 Agree method of compliance with suitably
building including COSHH data sheets
and verify design, sub-contractor’s qualified competent person(s) appointed
for products incorporated in building
workmanship quality and give by main contractor. Obtain details of
and copies of maintenance
certificates or declarations for airtightness testing (Part L2 only), insulation
recommendations plus guarantee
insulation/thermal continuity and continuity and infra-red thermographic
certificates.
airtightness testing (Part L2 only). surveys where appropriate.
5 Written report on commissioning of all
5 Select tender list from suitably qualified 4 Agree lifecycle durability warranty HVAC plant and controls by a suitably
roofing and cladding contractor’s . package. qualified competent person(s).
5 Provide site installation team(s) with 6 Building log-book - the owner and/or
6 Audit returned bids for Parts L2 or J
project specific construction assembly occupier of the building to be provided
compliance prior to contract award.
specifications, details and instructions/ with a log-book giving details of the
7 Alternatively training to achieve Parts L2 and J installed building services plant and
Establish own project specific Part L2 compliant site workmanship quality controls, their method of operation and
or J compliant design and standards. maintenance and other details that
specification pre-tender package in 6 Agree site supervision and workmanship collectively enable energy consumption
conjunction with a suitably qualified quality control audit requirements. to be monitored and controlled.
competent person(s).
7 Alternatively 7 Buildings less than 1,000m2 floor area
Establish own project specific Part L2 Air leakage testing is not compulsory on
or J compliant design and buildings below 1000m2 floor area
specification pre-tender package in provided that a suitably qualified
conjunction with a suitably qualified competent person(s) issues the required
competent person(s). certificates or declarations.
6

Building Regulations 2000 Part L2


Conservation of Fuel & Power (England & Wales)

Part L2 Compliance Requirements Effective from 1st April 2002


Standard U-Values of Construction Elements (U-Value W/m2K)

• Flat roof (not exceeding 10˚) or roof with integral insulation 0.25

• Walls, including basement walls 0.35

• Floors, including ground floors and basement floors 0.25

• Windows, roof windows and personnel doors (area weighted average 2.20
for the whole building), glazing in metal frames 3

• Windows, roof windows and personnel doors (area weighted average 2.00
for the whole building), glazing in wood or PVC frames3

• Rooflights 4,5
2.20

• Vehicle and similar large doors 0.70

Notes to table:
1. Any part of a roof having a pitch greater or equal to 70° can be considered as a wall.
2. For the sloping parts of a room-in-the-roof constructed as a material alteration, a U-value of 0.30W/m2K
would be reasonable.
3. Display windows, shop entrance doors and similar glazing are not required to meet the standard given in
this table.
4. This standard applies only to the performance of the unit excluding any upstand. Reasonable provision
would be to insulate any upstand, or otherwise isolate it from the internal environment.
5. For the purposes of Approved Document L2, a roof window may be considered as a rooflight.

Standard U-Values (W/m2K) for Insulated Metal Roof & Wall Cladding Systems –
Elemental Method Part L2

Boundary Wall Rooflights Roofs


& Valley Gutters 2.20d 0.25
0.25
(For pre melt
c
applications 0.35)
Overhanging Eaves
External or Soffits
Side Walls 0.35
0.35 (When soffits are
part of a floor 0.25)

Windows & Personnel Doors Floors Vehicle - Large Doors


2.00a/2.20b 0.25 0.70

Notes:
a. If windows have wood or PVC frames.
b. If windows have metal frames.
c. For pre melt gutter specifications obtain building control approval at design stage.
d. Rooflights may be permitted up to 12% of roof area at 3.0W/m2K by using the ‘Whole building’ or
‘Carbon emission’ method of calculation, however, there is a significant risk of condensation.
7

Elemental Method - Kingspan Roof & Wall Solutions

Approved Document L2 Compliance – Kingspan Roof and Wall Systems – CFC Free

Roof Systems – U-Values Product Thickness Air Leakage*


Flat roof or roof with integral KS1000 RW - TS 80mm (0.25 W/m K)
2
5m3/h/m2
insulation 0.25 W/m2K KS1000 LP - CR 80mm (0.25 W/m2K) 5m3/h/m2
KS500/1000 ZIP Kingzip 90mm (0.25 W/m K)
2
5m3/h/m2

Rooflights 2.20 W/m2K 5m3/h/m2

Wall Systems – U-Values Product Thickness Air Leakage*


0.35 W/m K 2
KS600/900/1000 - MR/EB/FL-S/WV/CX/MM 70mm (0.35 W/m K)2
5m3/h/m2
0.35 W/m2K KS900/1000 Optimo 70mm (0.35 W/m2K) 5m3/h/m2
0.35 W/m2K KS1000 RW 60mm (0.35 W/m2K) 5m3/h/m2

Notes: *To achieve a building air leakage performance of 10m3/h/m2 @ 50 Pa, the air leakage performance of the
roof/wall system has to be lower to allow for leakage at openings/junctions.
Air leakage solutions are available for 2m3/h/m2, consult Kingspan Technical Services Department.
8

Building Standards 1990 Part J


6th Amendments: Conservation of Fuel & Power (Scotland)

Part J Compliance Requirements Effective from 4th March 2002


Maximum U-Values of Exposed Building Elements when using the Elemental Method (Note1)

Exposed Building Element Maximum U-Value (W/m2K)

• Roof (all roof slopes) 0.25

• External Wall (Note 2) 0.30

• Floor 0.25

• Windows, personnel doors and rooflights (area weighted 2.20


average for the whole building) (Note 3), glazing in metal frames (Note 4)

• Windows, personnel doors and rooflights (area weighted 2.00


average for the whole building) (Note 3), glazing in wood or PVC frames

• Vehicle access and similar large doors (Note 5) 0.70

Notes to table:
1. When an element is exposed to the outside via an unheated space, the unheated space may be
disregarded or the U-value of the element calculated using BS EN ISO 13789: 1999.
2. Solid area of element only (i.e. excluding windows, doors and rooflights).
3. For method of calculation, see Appendix E.
4. Metal framed windows have slimmer frames and therefore provide a passive solar benefit, justifying a less
onerous U-value standard.
5. No requirement where for operational reasons doors have to be left open when building is in use.

Standard U-Values (W/m2K) for Insulated Metal Roof & Wall Cladding Systems –
Elemental Method Part J

Boundary Wall Rooflights Roofs


& Valley Gutters 2.20d 0.25
0.25
(For pre melt
c
applications 0.35)
Overhanging Eaves
or Soffits
External 0.30
Side Walls
(When soffits are
0.30 part of a floor 0.25)

Windows & Personnel Doors Floors Vehicle - Large Doors


2.00a/2.20b 0.25 0.70

Notes:
a. Windows, personnel doors and rooflights (area weighted average for the whole building), glazing in wood
or PVC frames.
b. Windows, personnel doors and rooflights (area weighted average for the whole building), glazing in
metal frames.
c. For pre melt gutter specifications obtain building control approval at design stage.
d. Rooflights may be permitted up to 12% of roof area at 3.0W/m2K, by using the ‘Whole building’ or
‘Carbon emission’ method of calculation, however, there is a significant risk of condensation.
9

Elemental Method - Kingspan Roof & Wall Solutions

Part J Standards Compliance – Kingspan Roof and Wall Systems – CFC Free

Roof Systems – U-Values Product Thickness


2
0.25 W/m K KS1000 RW - TS 80mm (0.25 W/m2K)
KS1000 LP - CR 80mm (0.25 W/m2K)
KS500/1000 ZIP Kingzip 90mm (0.25 W/m2K)

Rooflights 2.20 W/m2K

Wall Systems – U-Values Product Thickness


2
0.30 W/m K KS600/900/1000 - MR/EB/FL-S/WV/CX/MM 80mm (0.30 W/m2K)
0.30 W/m2K KS900/1000 Optimo 80mm (0.30 W/m2K)
0.30 W/m2K KS1000 RW 70mm (0.30 W/m2K)
10

Building Heating Loss through Thermal Bridging

Introduction
STEP 2
The Amendments to Part L2 of the Building
Regulations 2000 came into force on 1st April 2002. The linear meterage of thermal bridge junctions within
The amendments require that thermal bridges at the external envelope of the building is then
junctions and around openings be minimised (Items measured/calculated. These junctions include
1.9). Two means of meeting this requirement are window/door jambs, eaves details, corner details, cill
described. The first (Item 1.10) requires the use of details etc. The linear meterage of each junction is
standard robust “details and practices independently then multiplied by a calculated Y value (measurement
demonstrated as being satisfactory.” This option of linear thermal transmittance) for that specific
primarily applies to domestic type constructions. The junction. This provides the total heat loss through
second option (Item 1.11) is to prove compliance by each junction type for the building. The losses for
calculation in accordance with BRE Information Paper each junction are then added together to give the
IP 17/01 for which MCRMA Technical Report No 14 total heat loss through thermal bridge junctions within
provides specific guidance for profiled metal roofing the building (Total B).
and cladding.
Length Y-value Heat
Detail Junction
Means of Proving Compliance (m) (W/mK) Loss
A methodology for proving that an acceptable level of A Ridge 120.00 0.01 1.20
B Eaves 120.00 0.31 37.20
heat loss through thermal bridging in buildings has
C Verge 80.00 1.01 80.80
been achieved is contained within MCRMA Technical D Valley Gutter 60.00 1.38 82.80
Paper 14. The methodology is based upon BRE E1 Cladding Drip 195.00 0.86 167.70
Information Paper IP 17/01 – Assessing the Effects of E2 Ground Floor 195.00 0.16 31.20
F Corner 24.00 0.18 4.32
Thermal Bridges at Junctions and Around Openings.
G1 Cladding Window or personnel door head 34.00 0.97 32.98
The basic procedure for proving compliance is best G2 Window Frame Head 30.00 0.04 1.20
shown using a typical worked example: G3 Personnel Door Head 4.00 0.04 0.16
H1 Cladding Window Sill 30.00 0.48 14.40
H2 Window Frame Sill 30.00 0.04 1.20
I1 Window & Personnel Door Jambs 20.00 0.80 16.00
I2 Window Frame Jambs 4.00 0.04 0.16
I3 Personnel Door Jambs 16.00 0.04 0.64
6m J1 Cladding Head to Vehicle Bay Door 4.00 0.68 2.72
J2 Vehicle Unloading Bay Door Head 4.00 0.04 0.16
60m K1 Cladding Jamb to Vehicle Bay Door 8.00 1.70 13.60
40m
K2 Vehicle Unloading Bay Door Jambs 8.00 0.04 0.32
Total Heat Loss (B) = 488.76
The calculation process which should be followed is
as follows: STEP 3
STEP 1 To achieve compliance, the total heat loss for the
thermal bridge junctions (Total B) should be equal to
The total heat loss through each plane element in the or less than 10% of the total heat loss through the
external envelope (including the floor) of the building is plane elements of the building (Total A).
calculated by multiplying the U-value of each element
i.e
by the total square meterage (m2) of that element
within the building. Heat loss through
thermal bridging (Total B)
The heat loss for each element is then added = must be less than 0.1
Heat loss through the
together to provide the total heat loss for the plane plane elements (Total A)
elements of the building (Total A).
For the example above:
Example Building Area U-value Heat
Element (m2) (W/m2K) Loss
488.76 (Total B)
= 0.22
Total Roof Area 2647.00 - -
2224.8 (Total A)
Roof 2382.30 0.25 595.58
Therefore the example building has failed to comply
Rooflights (10%) 264.70 2.20 582.34
Total Wall Area 1194.80 - - through this route as the total heat loss through the
Exposed Walls 1164.80 0.35 407.68 thermal bridges equals 22% of the total heat loss
Windows & Personnel Doors 14.00 2.00 28.00 through the plain elements. If a building fails to comply
Vehicle Unloading Bay Doors 16.00 0.70 11.20 two options exist:
Ground Floor 2400.00 0.25 600.00
Total Heat Loss (A) = 2224.80
11

Building Heating Loss through Thermal Bridging

1. Improvements can be made to the junction details For the example building:
to reduce the levels of heat losses until the 10% Notional Building Area U-value Heat
threshold is achieved. In some instances it may not Element (m2) (W/m2K) Loss
be possible or economically viable to minimise the Total Roof Area 2647.00 - -
total additional heat losses through the thermal Roof 2117.60 0.25 529.40
bridges to this level. This may be particularly true with Rooflights (20%) 529.40 2.20 1164.68
some specific building uses (e.g. Warehouses or Total Wall Area 1194.80 - -
Exposed Walls 999.58 0.35 349.85
Industrial Units) and/or junction detail configurations.
Windows & Personnel Doors (15%) 179.22 2.00 358.44
2. Follow the alternative permitted means of Vehicle Unloading Bay Doors 16.00 0.70 11.20
compliance outlined below. Ground Floor 2400.00 0.25 600.00
Total Heat Loss (C) = 3013.57
Alternative Means of Proving Compliance
BRE Information Paper 17/01 permits compliance to
be proven via a trade off calculation (paragraph 5.4). STEP 5
This methodology can provide a significantly easier The total plane element heat loss in the notional
route to compliance for many buildings. building (Total C) is then multiplied by 1.1. This allows
If the building in question does not contain the full for the 10% additional heat loss permitted at thermal
allowable percentage of rooflights (20%) and bridge junctions and provides the total allowable heat
windows/personnel doors (15% in industrial/storage losses for the notional building (Total D).
buildings or 40% in places of assembly/offices/
For the example building:
shops) and these allowances have not been traded
off elsewhere, then they can be used as a trade off Total Allowable Notional Losses (D)
against heat losses at thermal bridge junctions to = 3013.57 x 1.1 = 3314.93
prove overall compliance. Additional improved
thermal standards of envelope plane elements can STEP 6
also be traded off in this manner.
As the Total B is greater than 10% of Total A in the The total heat losses for the actual building are
example building, then the trade off route should be obtained by adding the heat loss through the plane
followed. The means of proving compliance via this elements (Total A) and the thermal bridge junctions
route is as follows: (Total B). If A + B (total heat losses for the actual
building) is less than Total D (allowable heat losses for
STEP 4 the notional building) then compliance is proven.

A further calculation for the plane element heat losses For the example building:
should be undertaken for a “notional building” of As the total heat losses for the actual building [(A+B)
identical size and form but which contains the = 2713.36] are less than the total allowable losses for
maximum permissible areas of windows/personnel notional building [(D) = 3314.93], the building has
doors and rooflights. The areas of opaque roof and complied with the requirements of IP 17/01 and Part
wall elements require to be reduced to allow for the L2 of the Building Regulations.
additional rooflight and window/personnel door areas Conclusion
within the notional building. In many industrial and commercial buildings, the
e.g. If the actual building has a total roof area of thermal bridging at junctions will not require any
1000m2 with 10% rooflights it would break down into significant level of improvement over existing practice
plane elemental areas of: in order to prove compliance with IP17/01. This will
be particularly true where the areas of rooflights and
900m2 of roof @ U value of 0.25 personnel doors/windows are below the maximum
100m2 of rooflights @ U value of 2.2 permitted areas within the regulations.
Total roof area = 1000m2 The risk of condensation formation at thermal bridges
is potentially of greater importance and must be
With the notional building, the areas of rooflights can considered. The risk of condensation formation is
be the maximum permitted 20%. related to the building use and the internal surface
Therefore the revised elemental areas would be: temperatures at details. The minimum surface
800m2 of roof @ U value of 0.25 temperatures at details are defined as ‘f’ factors.
Generic building types have minimum ‘f’ factor
200m2 of rooflights @ U value of 2.2
requirements which are laid down in IP17/01 (See
Total roof area = 1000m2 Table A, page 4). Care must be taken to ensure that
A similar trade off would be undertaken for windows the degree of thermal bridging present at a detail
and personnel doors within the wall areas. The total does not lead to an unacceptable ‘f’ factor for the
heat losses for each element are then calculated and building use.
added together to provide the total plane element
losses for the notional building. (Total C).
12

Thermal Bridging & Heat Loss Calculation Example

Parts L2 & J Part L2


To illustrate the relative effect of different components, • Assess condensation and mould growth risk
junctions and air leakage loss the following has to be (surface temperature f-factor).
considered at design stage: • Assess impact of thermal bridging throughout
• Provide continuity of insulation at junctions, joints, the building envelope, calculate linear thermal
penetrations and abutment interfaces. transmissions - Y-value and calculation of whole
building’s a-value).
• Prevent missing insulation or gaps.
• Minimise thermal or cold bridges.
Parts L2 Whole Building a (alpha) Value - Case Study

A
D
6m
B
E

60
m G
H J
C K
m
I 40
G
F

Standard Details - Specification: Roof KS1000 RW 80mm - Walls KS1000 MR 70mm


Actual Building - U-values Actual Building - Y Values
Area U-value A.U Length Y Value L.Y
Object Name
Element (m2) (W/m2K) (W/K) (m) (W/mK) (W/K)
Total Roof Area 2647.00 - - A Ridge 120.00 0.01 1.20
Roof 2382.30 0.25 595.58 B Eaves 120.00 0.31 37.20
Rooflights (10%) 264.70 2.20 582.34 C Verge 80.00 1.01 80.80
Total Wall Area 1194.80 - - D Valley Gutter 0.35 U-Value (2mm Galv. Steel) 60.00 1.38 82.80
Exposed Walls 1164.80 0.35 407.68 E1 Cladding Drip 195.00 0.86 167.70
Windows & Personnel Doors 14.00 2.00 28.00 E2 Ground Floor* 195.00 0.16 31.20
Vehicle Unloading Bay Doors 16.00 0.70 11.20 F Corner 24.00 0.18 4.32
Ground Floor 2400.00 0.25 600.00 G1 Cladding Window or Personnel Door Head 34.00 0.97 32.98
Actual SA.U = 2224.80 G2 Window Frame Head* 30.00 0.04 1.20
Total Heat Loss for Actual Building 2713.36 G3 Personnel Door Head* 4.00 0.04 0.16
H1 Cladding Window Sill 30.00 0.48 14.40
Notional Building - U-values H2 Window Frame Sill* 30.00 0.04 1.20
Area U-value A.U I1 Window & Personnel Door Jambs 20.00 0.80 16.00
Element (m2) (W/m2K) (W/K) I2 Window Frame Jambs* 4.00 0.04 0.16
Total Roof Area 2647.00 - - I3 Personnel Door Jambs* 16.00 0.04 0.64
Roof 2117.60 0.25 529.40 J1 Cladding Head to Vehicle Bay Door 4.00 0.68 2.72
Rooflights (20%) 529.40 2.20 1164.68 J2 Vehicle Unloading Bay Door Head* 4.00 0.04 0.16
Total Wall Area 1194.80 - - K1 Cladding Jamb to Vehicle Bay Door 8.00 1.70 13.60
Exposed Walls 999.58 0.35 349.85 K2 Vehicle Unloading Bay Door Jambs 8.00 0.04 0.32
Windows & Personnel Doors (15%) 179.22 2.00 358.44 * Assumed value SL.Y = 488.76
Vehicle Unloading Bay Doors 16.00 0.70 11.20 Alpha Value SL..Y/Actual SA.U = 0.22
Ground Floor 2400.00 0.25 600.00
Notional SA.U = 3013.57 Vertical panel joints for KS 1000 MR
Notional Total Heat Loss inc. 10% = 3314.93 are included within U-Value for the panel

Total Heat Loss Compliance with MCRMA Technical Paper No. 14 = FAILS
Notional Building Heat Loss 3314.93 carry out calculation against notional building
Actual Building Heat Loss 2713.36 Compliance (Actual Heat Loss < Notional Building) = complies
Approved Document L2
13

Thermal Bridging & Heat Loss Calculation Example

A
D
6m
B
E

60
m G
H J
C K
I m
40
G F

Enhanced Details - Specification: Roof KS1000 RW 80mm - Walls KS1000 MR 70mm


Actual Building - U-values Actual Building - Y Values
Area U-value A.U Length Y Value L.Y
Object Name
Element (m2) (W/m2K) (W/K) (m) (W/mK) (W/K)
Total Roof Area 2647.00 - - A Ridge 120.00 0.004 0.48
Roof 2382.30 0.25 595.58 B Eaves 120.00 0.10 12.00
Rooflights (10%) 264.70 2.20 582.34 C Verge 80.00 0.01 0.80
Total Wall Area 1194.80 - - D Valley Gutter* 60.00 0.83 49.80
Exposed Walls 1164.80 0.35 407.68 E1 Cladding Drip 195.00 0.60 117.00
Windows & Personnel Doors 14.00 2.00 28.00 E2 Ground Floor* 195.00 0.16 31.20
Vehicle Unloading Bay Doors 16.00 0.70 11.20 F Corner 24.00 0.01 0.24
Ground Floor 2400.00 0.25 600.00 G1 Cladding Window or Personnel Door Head 34.00 0.62 21.08
Actual SA.U = 2224.80 G2 Window Frame Head* 30.00 0.04 1.20
Total Heat Loss for Actual Building 2474.00 G3 Personnel Door Head* 4.00 0.04 0.16
H1 Cladding Window Sill 30.00 0.10 3.00
Notional Building - U-values H2 Window Frame Sill* 30.00 0.04 1.20
Area U-value A.U I1 Window & Personnel Door Jambs 20.00 0.08 1.60
Element (m2) (W/m2K) (W/K) I2 Window Frame Jambs* 4.00 0.04 0.16
Total Roof Area 2647.00 - - I3 Personnel Door Jambs* 16.00 0.04 0.64
Roof 2117.60 0.25 529.40 J1 Cladding Head to Vehicle Bay Door 4.00 0.62 2.48
Rooflights (20%) 529.40 2.20 1164.68 J2 Vehicle Unloading Bay Door Head* 4.00 0.04 0.16
Total Wall Area 1194.80 - - K1 Cladding Jamb to Vehicle Bay Door 8.00 0.71 5.68
Exposed Walls 999.58 0.35 349.85 K2 Vehicle Unloading Bay Door Jambs 8.00 0.04 0.32
Windows & Personnel Doors (15%) 179.22 2.00 358.44 * Assumed value SL.Y = 249.24
Vehicle Unloading Bay Doors 16.00 0.70 11.20 Alpha Value SL..Y/Actual SA.U = 0.11
Ground Floor 2400.00 0.25 600.00
Notional SA.U = 3016.57
Notional Total Heat Loss inc. 10% = 3314.93

Total Heat Loss Compliance with MCRMA Technical Paper No. 14 = FAILS
Notional Building Heat Loss 3314.93 carry out calculation against notional building
Actual Building Heat Loss 2474.00 Compliance (Actual Heat Loss < Notional Building) = complies
Approved Document L2
14

Air Leakage Risk Areas

Parts L2 & J
• Roof and wall cladding air leakage will be required
To illustrate the relative effect of different components, to be less than that indicated in Part L2 as the
junctions and air leakage loss the following has to be regulations refers to the whole building air leakage
considered at design stage: level. i.e. including doors, windows, dado walls and
• Limit air leakage loss within the envelope fabric floor slab junctions.
and at junctions, joints, penetrations and abutment
• The air leakage performance of Kingspan’s roof
interfaces to comply with regulatory requirements. and wall panels is 5m3/hr/m2 when installed to
specification.

A
D
6m
B
E

60
m G
H J
C K
I m
40
G F

The red lines highlight the air leakage risk


areas where air seals are required
15

STANDARD CONSTUCTION DETAILS


16
STANDARD

KS1000 RW Roof Systems

Two sets of details have been produced to give the Building Designer flexibility within the calculation for
the total building heat loss.
The decision on the choice of standard or enhanced details is taken by the Building Designer and is determined
from the total building heat loss methodology demonstrated on pages 10 & 11 of this guide.
A mixture of both standard and enhanced details maybe required for some projects.

KS1000 RW Roof Systems Standard Details


Panel End Lap Detail 17
Ridge Detail 17
Parapet Details - Boundary Wall Gutter 18-19
Eaves Details - External Gutter 20
Verge Details - Wall Cladding 21-22
Valley Gutter Detail 23
Valley Hip Detail 24
Hip Detail 24
End Lap Detail (Panel to GRP Rooflight) 25
End Lap Detail (GRP Rooflight to Panel) 25
Rooflight Intermediate Detail 26
Rooflight Side Lap - Fastener Location Detail 26

KS1000 LP Roof Systems Standard Details


Panel End Lap Detail 27
Ridge Detail 27
Parapet Details - Boundary Wall Gutter 28-29
Eaves Details - External Gutter 30
Valley Gutter Detail 31
Valley Hip Detail 32
Hip Detail 32
Verge Details - Wall Cladding 33-34
Barrel Vault End Lap Details 35
Barrel Vault Side Lap Detail 36
End Lap Detail (Panel to GRP Rooflight) 37
End Lap Detail (GRP Rooflight to Panel) 37
Rooflight Intermediate Detail 38
Rooflight Side Lap - Fastener Location Detail 38

KS1000 RW Wall (Vertically Laid) Systems Standard Details


Drip Detail 39
External Corner Detail 39
Window Head and Cill Detail 40
Window Jamb Detail & Alternative Option Detail 40
Personnel Door Detail (Door head panel site cut) 41
Door Jamb & Door Head Detail 41
Up and Over Door Head Detail 42
Door Jamb Detail 42

KS1000 MR/EB/FL-S/MM/CX/WV Wall (Horizontally Laid) Systems Standard Details


External Corner Detail 43
Vertical Joint Details 44
Window Head and Cill Detail 45
Window Jamb Detail 45
Personnel Door Detail - (Door head panel site cut) 46
Door Jamb & Door Head Detail 46
Drip Detail - Above Floor Level & Below Floor Level 47
Up and Over Door Head Detail 48
Door Jamb Detail 48
17
STANDARD

KS1000 RW Roof Systems

PANEL END LAP DETAIL

Fixing screw

KS1000 RW/LPCB roof panel

150mm

m 50mm
Nominal 10m
Max. 20mm
3 runs of 4mm Ø butyl rubber
sealant (Site applied)

Min. 10mm

Purlin

RIDGE DETAIL
Mineral fibre insulation site applied
Ridge flashing with 150mm KS1000 RW/LPCB
sealed butt straps insulated roof panel

Profiled filler sealed top and Profiled filler set back 80


bottom with gun-grade sealant to 100mm to prevent
bird attack

Max.
50mm

Air seal - 8mm Ø butyl Internal ridge flashing


rubber sealant with 150mm overlap
sealed with air seal,
Vapourflex or gun-grade
Purlin
sealant

Building Regulations Part L2 Thermal Data


fmin = 0.97 Y = 0.01 W/mK
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.
18
STANDARD

KS1000 RW Roof Systems

PARAPET DETAIL - BOUNDARY WALL GUTTER

Parapet flashing with 150mm sealed butt straps

Mineral fibre insulation site applied

Butyl rubber sealant

Air seal - 6mm Ø butyl rubber sealant

Profiled filler sealed top and bottom with gun-grade sealant


Parapet rail with air seal, Vapourflex tape to rail joints

Profiled filler Sheeting rail


sealed top
and bottom Air seal - 6mm Ø butyl rubber sealant
with gun-
grade sealant Mineral fibre insulation site applied
KS1000 RW/LPCB
insulated roof panel
KS1000 RW/
LPCB wall panel
vertically laid
Air seal - 8mm Ø
butyl rubber sealant
2mm external non-thermally
broken factory made gutter
35mm
Min

with PIR insulation to 0.25


or 0.35 W/m2K U-value
60mm

Purlin

Gutter outlet

Eaves beam gutter support

Building Regulations Part L2 Thermal Data


0.25 W/m2K gutter fmin = 0.48 Y = 1.63 W/mK
0.35 W/m2K gutter fmin = 0.48 Y = 1.72 W/mK
0.35 sole width 300mm and depth 150mm, values for other widths available
on request. The above values are only applicable to the components on this
detail. Changes to the components will have an effect on the given values.
19
STANDARD

KS1000 RW Roof Systems

PARAPET DETAIL - BOUNDARY WALL GUTTER

Parapet flashing with 150mm sealed butt straps

Mineral fibre insulation site applied

Butyl rubber sealant

Air seal - 6mm Ø bead of gun-grade sealant


Air seal - 6mm Ø butyl rubber sealant

Profiled filler sealed top and bottom with gun-grade sealant


Parapet rail with air seal, Vapourflex tape to rail joints

Sheeting rail
KS1000 MR/
LPCB wall panel Air seal - 6mm Ø butyl rubber sealant
horizontally laid
Mineral fibre insulation site applied
KS1000 RW/LPCB
insulated roof panel
KS1000 RW/
LPCB wall panel
vertically laid
Air seal - 8mm Ø
butyl rubber sealant
2mm external non-thermally
broken factory made gutter
35mm
Min

with PIR insulation to 0.25


or 0.35 W/m2K U-value
60mm

Purlin

Gutter outlet

Eaves beam gutter support

Building Regulations Part L2 Thermal Data


0.25 W/m2K gutter fmin = 0.48 Y = 1.63 W/mK
0.35 W/m2K gutter fmin = 0.48 Y = 1.72 W/mK
0.35 sole width 300mm and depth 150mm, values for other widths available
on request. The above values are only applicable to the components on this
detail. Changes to the components will have an effect on the given values.
20
STANDARD

KS1000 RW Roof Systems

EAVES DETAIL - EXTERNAL GUTTER


Gutter support 0.7mm thick doubled
sided plastisol coated
ing centres
200mm fix
centres
200mm fixing
75mm
Approx

9mm x 3mm butyl


rubber sealant
Air seal - 8mm Ø butyl
rubber sealant
Air seal - 6mm Ø butyl
rubber sealant
Mineral fibre insulation
site applied

Double sided
Plastisol
“Highline”
type gutter 20 35 20
*
mm mm mm

Eaves beam

Building Regulations Part L2 Thermal Data


fmin = 0.92 Y = 0.27 W/mK
The above values are only applicable to the components on this detail.
* Air seal - Vapourflex sealant is to be applied over any breaks in
supporting secondary steelwork to give a continuous bearing face.
Changes to the components will have an effect on the given values.

EAVES DETAIL - EXTERNAL GUTTER


Gutter support 0.7mm thick doubled
sided plastisol coated
centres
200mm fixing
centres
200mm fixing
75mm
Approx

9mm x 3mm butyl


rubber sealant
Air seal - 8mm Ø butyl
rubber sealant
Air seal - 6mm Ø bead of
gun-grade sealant
Mineral fibre insulation
site applied

Double sided
Plastisol
“Highline”
type gutter 20 35 20
*
mm mm mm

Eaves beam

Building Regulations Part L2 Thermal Data


fmin = 0.91 Y = 0.31 W/mK
The above values are only applicable to the components on this detail.
* Air seal - Vapourflex sealant is to be applied over any breaks in
supporting secondary steelwork to give a continuous bearing face.
Changes to the components will have an effect on the given values.
21
STANDARD

KS1000 RW Roof Systems

VERGE DETAIL - WALL CLADDING (END OF ROOF SHEETING)


Verge flashing with 150mm sealed butt straps
Mineral fibre insulation site applied
9mm x 3mm butyl rubber sealant
Verge zed support with 150mm sealed overlaps

Cleader angle by steel sub-contractor with


air seal - Vapourflex sealant applied at joints
Direction of Lay
Air seal - 8mm Ø butyl rubber sealant

Purlin
Air seal - 6mm Ø butyl rubber sealant
Profiled filler sealed top and bottom
with gun-grade sealant
Building Regulations Part L2 Thermal Data
fmin = 0.91 Y = 1.01 W/mK
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.
22
STANDARD

KS1000 RW Roof Systems

VERGE DETAIL - WALL CLADDING (START OF ROOF SHEETING)


Verge flashing with 150mm sealed butt straps
Mineral fibre insulation site applied
9mm x 3mm butyl rubber sealant
Verge zed support with 150mm sealed overlaps
Direction of Lay
Cleader angle by steel sub-contractor with
air seal - Vapourflex sealant applied at joints
Air seal - 8mm Ø butyl rubber sealant

KS1000 MR/
LPCB wall panel
horizontally laid

4mm Ø butyl
sealant

Purlin
Building Regulations Part L2 Thermal Data
Air seal - 6mm Ø bead of gun-grade sealant
fmin = 0.91 Y = 1.01 W/mK
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.

VERGE DETAIL - WALL CLADDING (END OF ROOF SHEETING)


Verge flashing with 150mm sealed butt straps
Mineral fibre insulation site applied

Site cut panel to suit


Verge zed support with 150mm sealed overlaps
9mm x 3mm butyl rubber sealant
Direction of Lay
Cleader angle by steel sub-contractor with
air seal - Vapourflex sealant applied at joints
Air seal - 8mm Ø butyl rubber sealant

4mm Ø butyl
sealant
KS1000 MR/
Purlin LPCB wall panel
Air seal - 6mm Ø bead of gun-grade sealant horizontally laid

Building Regulations Part L2 Thermal Data


fmin = 0.91 Y = 1.01 W/mK
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.
23
STANDARD

KS1000 RW Roof Systems

VALLEY GUTTER DETAIL

KS1000 RW/LPCB
insulated roof panel

2mm external non-thermally broken


factory made galvanised sheet
Air seal - 8mm gutter with PIR board insulation to Air seal - 8mm
Ø butyl rubber 0.25 or 0.35 W/m2K U-value Ø butyl rubber
sealant sealant
Gutter outlet offset to miss
Purlin
Stanchion head tie stanchion head tie
if necessary as
steelwork design

Building Regulations Part L2 Thermal Data


0.25 W/m2K gutter fmin = 0.74 Y = 1.07 W/mK
0.35 W/m2K gutter fmin = 0.71 Y = 1.38 W/mK
0.35 sole width 600mm and depth 150mm, values for other widths available
on request. The above values are only applicable to the components on this
detail. Changes to the components will have an effect on the given values.
24
STANDARD

KS1000 RW Roof Systems

VALLEY HIP DETAIL


KS1000 RW/LPCB
Double sided Plastisol coated flashing insulated roof panel

Air seal - 8mm Ø


butyl rubber sealant

Air seal - 8mm Ø butyl


rubber sealant
Edge protection lacquer applied to all
panels cut on site to suit rake angle

Cleader angle by steel


sub-contractor

2mm external non-thermally broken


factory made galvanised sheet gutter
with PIR board insulation to 0.25 or
0.35 W/m2K U-value

Hip rafter Purlin

Building Regulations Part L2 Thermal Data


fmin = 0.85 Y = 0.41 W/mK
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.

HIP DETAIL
Internal ridge flashing with 150mm overlap
sealed with Vapourflex or gun-grade sealant Mineral fibre insulation site applied
Panels site cut to suit rake angle

Hip flashing with 150mm KS1000 RW/LPCB insulated


sealed butt straps Max. 50mm roof panel
Rake cut profiled filler sealed top and Profiled filler set back 80 to
bottom with gun-grade sealant 100mm to prevent bird attack
Cleader angle by steel
sub-contractor Air seal - 8mm Ø butyl
rubber sealant

Hip rafter Purlin

Building Regulations Part L2 Thermal Data


fmin = 0.97 Y = 0.01 W/mK
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.
25
STANDARD

KS1000 RW Roof Systems

END LAP DETAIL - (PANEL TO GRP ROOFLIGHT)

. end lap
150mm Min

Position of 6 No. main fixings with


29mm Ø washers at end laps

9mm x 3mm sealant strip or


bead either side of fixing
KS1000 RW/LPCB roof panel
Silicone or mastic sealant
strip at bottom of lap

Sealant

Triple skin GRP integral


5mm expansion gap
rooflight system

Support bearing plate (Ref: LP2)

END LAP DETAIL - (GRP ROOFLIGHT TO PANEL)

. end lap
150mm Min

Position of 6 No. main fixings with


29mm Ø washers at end laps

9mm x 3mm sealant strip or


bead either side of fixing
Silicone or mastic sealant
strip at bottom of lap Triple skin GRP integral
rooflight system

Sealant

5mm expansion gap

KS1000 RW/LPCB roof panel

Support bearing plate (Ref: LP2)


26
STANDARD

KS1000 RW Roof Systems

ROOFLIGHT INTERMEDIATE DETAIL

Galvanised steel plate at filler positions


for high thread fixing

High density filler

Triple skin GRP integral rooflight system

Position of 6 No. main fixings with


29mm Ø washers

Purlin

ROOFLIGHT SIDE LAP - FASTENER LOCATION DETAIL

Direction of Prevailing Wind Direction of Lay

4mm Ø butyl rubber sealant

Position of main fixings 6 No. with 29mm Ø washers at: 4mm Ø butyl rubber sealant
i) Ridge
ii) Intermediate
iii) End laps Aluminium strip in underlap

KS1000 RW/LPCB roof panel Triple skin GRP Stitcher screw into aluminium 3mm Ø
rooflight system hole to be drilled prior to fixing/p side
lap fixings at 300mm centres

Note: The GRP translucent rooflight illustrated above is generic in detail.


Kingspan GRP rooflight details to comply with Part L2 and Part J
will be made available later.
These details DO NOT represent our product.
27
STANDARD

KS1000 LP Roof Systems

END LAP DETAIL

panel
m between
Min. of 300m ver cap end lap
co
end lap and

Cover cap complete with


joggle factory applied
Continuous run of non-setting
gun-grade sealant

End lap stitching plate

18mm x 4mm ‘U’ shaped


butyl sealant

RIDGE DETAIL

Ridge flashing with 150mm


sealed butt straps Outer sheet turned up with roof slopes below 4˚

Cover cap Mineral fibre insulation site applied


Profiled filler set back 80 to Apex dam (Ref: LP1)
100mm to prevent bird attack
20mm x 3mm butyl
rubber sealant

Max.
50mm
Profiled filler sealed
top and bottom with Air seal - 8mm Ø
gun-grade sealant 2 No. runs
silicone sealant butyl rubber sealant
KS1000 LP/LPCB
insulated roof panel

Internal ridge flashing


Purlin
with 150mm overlap
sealed with Vapourflex
or gun-grade sealant

Building Regulations Part L2 Thermal Data


fmin = 0.97 Y = 0.01 W/mK
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.
28
STANDARD

KS1000 LP Roof Systems

PARAPET DETAIL - BOUNDARY WALL GUTTER

Parapet flashing with 150mm sealed butt straps

Mineral fibre insulation site applied

Butyl rubber sealant

Parapet rail with air seal - Vapourflex tape to rail joints

Air seal - 6mm Ø butyl rubber sealant

Profiled filler sealed top and bottom with gun-grade sealant

Air seal - 6mm Ø bead of gun-grade sealant

Air seal - 6mm Ø butyl rubber sealant

4mm Ø butyl
rubber sealant

KS1000 LP/LPCB
KS1000 MR/ insulated roof panel
LPCB wall panel 75mm
horizontally laid Top sheet turned
down on site with
KS1000 RW/ roof pitches below 4˚
LPCB wall panel
vertically laid Gun-grade seal at
panel joints inline
with 8mm butyl
Sheeting rail Air seal - 8mm Ø butyl
35mm

rubber sealant
Min

2mm external non-thermally


broken factory made gutter
60mm with PIR insulation to 0.25
Mineral fibre
insulation or 0.35 W/m2K U-value
site applied
Purlin
Direction of Lay

Gutter outlet

Eaves beam gutter support

Building Regulations Part L2 Thermal Data


0.25 W/m2K gutter fmin = 0.48 Y = 1.63 W/mK
0.35 W/m2K gutter fmin = 0.48 Y = 1.72 W/mK
0.35 sole width 300mm and depth 150mm, values for other widths available
on request. The above values are only applicable to the components on this
detail. Changes to the components will have an effect on the given values.
29
STANDARD

KS1000 LP Roof Systems

PARAPET DETAIL - BOUNDARY WALL GUTTER

Parapet flashing with 150mm sealed butt straps

Mineral fibre insulation site applied

Butyl rubber sealant

Parapet rail with air seal - Vapourflex tape to rail joints

Air seal - 6mm Ø butyl rubber sealant

Profiled filler sealed top and bottom with gun-grade sealant

Air seal - 6mm Ø bead of gun-grade sealant

Air seal - 6mm Ø butyl rubber sealant

4mm Ø butyl
rubber sealant

KS1000 LP/LPCB
KS1000 RW/ insulated roof panel
LPCB wall panel 75mm
vertically laid Top sheet turned
down on site with
KS1000 RW/ roof pitches below 4˚
LPCB wall panel
vertically laid Gun-grade seal at
panel joints inline
with 8mm butyl
Sheeting rail Air seal - 8mm Ø butyl
35mm

rubber sealant
Min

2mm external non-thermally


broken factory made gutter
60mm with PIR insulation to 0.25
Mineral fibre
insulation or 0.35 W/m2K U-value
site applied
Purlin
Direction of Lay

Gutter outlet

Eaves beam gutter support

Building Regulations Part L2 Thermal Data


0.25 W/m2K gutter fmin = 0.48 Y = 1.63 W/mK
0.35 W/m2K gutter fmin = 0.48 Y = 1.72 W/mK
0.35 sole width 300mm and depth 150mm, values for other widths available
on request. The above values are only applicable to the components on this
detail. Changes to the components will have an effect on the given values.
30
STANDARD

KS1000 LP Roof Systems

EAVES DETAIL - EXTERNAL GUTTER


Gutter support 0.7mm thick double sided plastisol coated

Top sheet turned down on site with roof pitches below 4˚

9mm x 3mm butyl rubber sealant


Stitching screw fixings
for gutter brackets
g centres
200mm fixin
g centres
200mm fixin
75mm
Approx

KS1000 LP/LPCB insulated roof panel


Gun-grade seal at panel joints inline with 8mm butyl
Air seal - 8mm Ø butyl rubber sealant
Air seal - 6mm Ø
bead of gun-grade sealant
Mineral fibre
insulation site applied

Double sided
*
plastisol Highline
type gutter 20 35 20
mm mm mm
Eaves beam
* Air seal - Vapourflex
sealant is to be applied
KS1000 MR/LPCB wall over any breaks in Building Regulations Part L2 Thermal Data
panel horizontally laid supporting secondary
steelwork to give a fmin = 0.91 Y = 0.31 W/mK
The above values are only applicable to the components on this detail.
continuous bearing Changes to the components will have an effect on the given values.
face.

EAVES DETAIL - EXTERNAL GUTTER


Gutter support 0.7mm thick double sided plastisol coated

Top sheet turned down on site with roof pitches below 4˚

9mm x 3mm butyl rubber sealant


Stitching screw fixings
for gutter brackets
g centres
200mm fixin
g centres
200mm fixin
75mm
Approx

KS1000 LP/LPCB insulated roof panel


Gun-grade seal at panel joints inline with 8mm butyl
Air seal - 8mm Ø butyl rubber sealant
Air seal - 6mm
Ø butyl rubber sealant
Mineral fibre
insulation site applied

Double sided
*
plastisol Highline
type gutter 20 35 20
mm mm mm
Eaves beam
* Air seal - Vapourflex
sealant is to be applied
KS1000 RW/ LPCB wall over any breaks in Building Regulations Part L2 Thermal Data
panel vertically laid supporting secondary
steelwork to give a fmin = 0.92 Y = 0.27 W/mK
The above values are only applicable to the components on this detail.
continuous bearing Changes to the components will have an effect on the given values.
face.
31
STANDARD

KS1000 LP Roof Systems

VALLEY GUTTER DETAIL


Gun-grade seal at panel
Cover cap joints inline with 8mm butyl
75mm

Top sheet turned down on site


with roof pitches below 4˚

2mm external non-thermally


broken factory made gutter
Air seal - 8mm with PIR insulation to 0.25 or
Ø butyl rubber 0.35 W/m2K U-value
sealant
Gutter outlet offset to miss
Stanchion head stanchion head tie Air seal - 8mm Ø
tie if necessary butyl rubber sealant
as steelwork
design Purlin

Building Regulations Part L2 Thermal Data


0.25 W/m2K gutter fmin = 0.74 Y = 1.07 W/mK
0.35 W/m2K gutter fmin = 0.71 Y = 1.38 W/mK
0.35 sole width 600mm and depth 150mm, values for other widths available
on request. The above values are only applicable to the components on this
detail. Changes to the components will have an effect on the given values.
32
STANDARD

KS1000 LP Roof Systems

VALLEY HIP DETAIL


Double sided plastisol
coated flashing
Cover cap Gun-grade seal at
KS1000 LP/LPCB panel joints inline with
insulated roof panel 8mm butyl

Edge protection lacquer applied to all


panels cut on site to suit rake angle

Air seal - 8mm Ø butyl rubber sealant

Cleader angle by steelwork contractors

2mm external non-thermally broken


factory made gutter with PIR insulation
to 0.25 W/m2K U-value

Building Regulations Part L2 Thermal Data Hip rafter Purlin


fmin = 0.85 Y = 0.41 W/mK
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.

HIP DETAIL
Hip flashing with 150mm Mineral fibre insulation site applied
sealed butt straps
Panels site cut to suit rake angle Outer sheet turned up on
site with roof pitches below 4˚
Apex dam (Ref: LP1/A)
Rake cut profiled filler sealed top Cover cap
and bottom with gun-grade sealant
20mm x 3mm butyl rubber sealant
KS1000 LP/LPCB
2 No. runs of silicone sealant
insulated roof panel

Air seal - 8mm Ø


butyl rubber sealant Purlin
Internal ridge flashing with 150mm overlap Cleader angle by steelwork
sealed with Vapourflex or gun-grade sealant contractor

Building Regulations Part L2 Thermal Data Hip rafter


fmin = 0.97 Y = 0.01 W/mK
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.
33
STANDARD

KS1000 LP Roof Systems

VERGE DETAIL - WALL CLADDING (START OF ROOF SHEETING)


Verge flashing with 150mm sealed butt straps
Direction of Lay Mineral fibre insulation site applied

20mm x 3mm butyl rubber sealant


Cleader angle by steel sub-contractor with air seal Vapourflex sealant applied at joints
KS1000 LP/LPCB insulated roof panel

Purlin
Air seal - 8mm Ø butyl rubber sealant
Air seal - 6mm Ø bead of gun-grade sealant
Gable rafter
KS1000 MR/LPCB insulated wall
panel horizontally laid
4mm Ø butyl rubber sealant
Building Regulations Part L2 Thermal Data
fmin = 0.96 Y = 0.18 W/mK
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.

VERGE DETAIL - WALL CLADDING (START OF ROOF SHEETING)


Verge flashing with 150mm sealed butt straps
Direction of Lay Mineral fibre insulation site applied

20mm x 3mm butyl rubber sealant


Cleader angle by steel sub-contractor with air seal Vapourflex sealant applied at joints
KS1000 LP/LPCB insulated roof panel

Purlin
Air seal - 8mm Ø butyl rubber sealant
Air seal - 6mm Ø butyl rubber sealant
Gable rafter
KS1000 RW/LPCB insulated wall
panel vertically laid
Profiled filler sealed top & bottom
Building Regulations Part L2 Thermal Data
with gun grade sealant
fmin = 0.96 Y = 0.18 W/mK
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.
34
STANDARD

KS1000 LP Roof Systems

VERGE DETAIL - WALL CLADDING (END OF ROOF SHEETING)


Verge flashing with 150mm sealed butt straps
Mineral fibre insulation site applied
Direction of Lay
20mm x 3mm butyl rubber sealant
Cleader angle by steel sub-contractor with air seal Vapourflex sealant applied at joints
KS1000 LP/LPCB insulated roof panel

Purlin
Air seal - 8mm Ø butyl rubber sealant
Air seal - 6mm Ø bead of gun-grade sealant
Gable rafter
KS1000 MR/LPCB insulated wall
panel horizontally laid
4mm Ø butyl rubber sealant
Building Regulations Part L2 Thermal Data
fmin = 0.96 Y = 0.18 W/mK
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.

VERGE DETAIL - WALL CLADDING (END OF ROOF SHEETING)


Verge flashing with 150mm sealed butt straps
Mineral fibre insulation site applied
Direction of Lay
20mm x 3mm butyl rubber sealant
Cleader angle by steel sub-contractor with air seal Vapourflex sealant applied at joints
KS1000 LP/LPCB insulated roof panel

Purlin
Air seal - 8mm Ø butyl rubber sealant
Air seal - 6mm Ø butyl rubber sealant
Gable rafter
KS1000 RW/LPCB insulated wall
panel vertically laid
Profiled filler sealed top & bottom
with gun grade sealant Building Regulations Part L2 Thermal Data
fmin = 0.96 Y = 0.18 W/mK
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.
35
STANDARD

KS1000 LP Roof Systems

BARREL VAULT END LAP DETAIL

9mm x 3mm butyl rubber sealant

GRP barrel vault rooflight system fixed


at 225mm centres with 30mm Ø sealed Single skin GRP barrel vault
washers rooflight system
lap
Apex dam (Ref: LP1) 75mm end
Double skin GRP
rooflight system
20mm x 3mm butyl
rubber sealant
Cover cap

5mm expansion gap

Position of 4 no. main fixings with


2 No. runs silicone
29mm Ø washers at end lap
sealant
Main panel fixing at side profile joint
KS1000 LP/LPCB insulated
roof panel

Support bearing plate (Ref: LP2)

BARREL VAULT END LAP DETAIL


GRP barrel vault rooflight system fixed at
225mm centres with 30mm Ø sealed
washers
Single skin GRP barrel
vault rooflight system In-situ GRP weather seal

GRP site applied water deflector

Cover cap over


lap GRP weather seal
75mm end

9mm x 3mm butyl


rubber sealant

External closure flashing

Main panel fixing at side profile joint

Double skin GRP 5mm expansion gap


rooflight system
Position of 4 no. main fixings with
Support bearing plate 29mm Ø washers at end lap
(Ref: LP2)
36
STANDARD

KS1000 LP Roof Systems

BARREL VAULT SIDE LAP DETAIL

Single skin GRP barrel vault rooflight

Self tap screw with 30mm Ø washers


at 255mm centres, stitched to galv.
support angle.
Continuous 1.6mm thick galv.
steel zed support for rooflight
20mm x 3mm butyl rubber sealant fixings stitched to panel at
200mm centres
2 runs of 20mm x 3mm butyl rubber sealant
Continuous 1.6mm thick
between top & bottom galv. support
galv steel angle for rooflight
fixings bulb type rivets at Double skin GRP rooflight system
300mm centres

1000mm
KS1000 LP/LPCB roof panel

Main fixing at purlin locations


37
STANDARD

KS1000 LP Roof Systems

END LAP DETAIL (PANEL TO GRP ROOFLIGHT)

lap
75mm end 5mm expansion gap

9mm x 3mm butyl rubber sealant

Triple skin GRP


integral rooflight system

Cover cap

KS1000 LP/LPCB
roof panel
High density filler
Support bearing plate
(Ref: LP2)
Position of 4 No. main fixings with Main panel fixings at
29mm Ø washers at end laps side profile joint

END LAP DETAIL (GRP ROOFLIGHT TO PANEL)

75mm end lap


Cover cap
9mm x 3mm butyl rubber sealant

KS1000 LP/LPCB
roof panel

Triple skin GRP integral


rooflight system

Position of 4 No. main


Main panel fixings at
fixings with 29mm Ø
side profile joint
washers at end laps
Support bearing plate (Ref: LP2)
5mm expansion gap
38
STANDARD

KS1000 LP Roof Systems

ROOFLIGHT INTERMEDIATE DETAIL

Triple skin GRP


rooflight system

High density filler


Position of 4 No. main fixings
with 29mm Ø washers

ROOFLIGHT SIDE LAP - FASTENER LOCATION DETAIL

1000mm Cover caps

KS1000 LP/LPCB Cover cap snaps on without external fixings Triple skin GRP rooflight
roof panel Note: Position cap on rooflight side first system
39
STANDARD

KS1000 RW Wall Systems


Vertically laid

DRIP DETAIL

KS1000 RW/LPCB vertically laid

Air seal - 6mm Ø butyl


rubber sealant

Air seal - continuous bead of gun-grade


sealant required at angle edge

Internal closure flashing

Mineral fibre insulation site applied

Alfas C foam seal

Galvanised ledger angle

Drip flashing

Building Regulations Part L2 Thermal Data


fmin = 0.52 Y = 0.60 W/mK
The appropriate Y value for the brickwork, blocks or concrete must be added
to the above Y value to obtain the total loss through this junction detail.
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.

EXTERNAL CORNER DETAIL

Corner column

Sheeting rail

KS1000 RW/LPCB insulated wall panel vertically laid

Air seal - 6mm Ø butyl rubber sealant

Internal cleader angle by steel sub-contractor with


air seal Vapourflex sealant applied at joints

Zed support lapped 100mm at joints

Site cut vertical sheeting

Mineral fibre insulation site applied

External corner flashing with 100mm sealed overlaps

Direction of Lay
9mm x 3mm butyl rubber sealant

KS1000 RW/LPCB insulated wall panel vertically laid

Building Regulations Part L2 Thermal Data


fmin = 0.95 Y = 0.02 W/mK
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.
40
STANDARD

KS1000 RW Wall Systems


Vertically laid
WINDOW HEAD AND CILL DETAIL

Building Regulations Part L2 Thermal Data Air seal - 6mm Ø butyl rubber sealant

fmin = 0.44 Y = 1.01 W/mK Optional internal head flashing


The appropriate Y value for the window system must be added to the
above Y value to obtain the total heat loss through this junction detail.
The above values are only applicable to the components on this detail. Mineral fibre insulation
Changes to the components will have an effect on the given values.
site applied

Window support rail


Head flashing

9mm x 3mm butyl rubber sealant

External soffit flashing with no


connection to internal

Window depth to suit panel module


Polyethylene backing rod with silicone sealant
by window installer

Window unit by others

Window cill flashing with 3° slope to facilitate


drainage (no connection to internal)

Profiled filler sealed top and bottom


with gun-grade sealant
Mineral fibre insulation
site applied
Building Regulations Part L2 Thermal Data
Air seal - 6mm Ø butyl
fmin = 0.52 Y = 0.83 W/mK rubber sealant
The appropriate Y value for the window system must be added to the
above Y value to obtain the total heat loss through this junction detail. Internal cill flashing
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.

WINDOW JAMB DETAIL OPTION 1 WINDOW JAMB DETAIL OPTION 2

Window width

Mineral fibre insulation


site applied
Jamb steelwork

Window unit
by others

Polyethylene backing
rod with silicone sealant
Air seal - 6mm Ø butyl
rubber sealant
External jamb flashing
with no connection to
internal
Site cut panel
Building Regulations Part L2 Thermal Data
9mm x 3mm butyl rubber sealant
fmin = 0.59 Y = 0.53 W/mK
The appropriate Y value for the window system must be added to the
above Y value to obtain the total heat loss through this junction detail.
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.
41
STANDARD

KS1000 RW Wall Systems


Vertically laid

PERSONNEL DOOR DETAIL (DOOR HEAD PANEL SITE CUT)

+2100mm

B
A A

Door frame by others

Pressed metal base channel Expanding type anchor


or RSA by others fixing by others

F.F.L. 0.00mm
900mm

DOOR JAMB DETAIL A-A DOOR HEAD DETAIL B-B


Galvanised door post by
steel sub-contractor with
Vapourflex sealant Air seal - 6mm Ø
applied to joints butyl rubber sealant

Polyethylene backing Internal head


rod with silicone sealant Mineral fibre insulation flashing (optional)
by door installer site applied

Galvanised
door head

Mineral fibre insulation


site applied
Door & frame by
others fixed to steel
Site cut panel support frame
External soffit flashing
with no connection to
Air seal - 6mm Ø butyl internal
rubber sealant
9mm x 3mm butyl
rubber sealant
External jamb flashing with no 9mm x 3mm butyl
rubber sealant Door head flashing
connection to internal
Note: For opening outward door ensure
drip flashing is clear top of door

Building Regulations Part L2 Thermal Data Building Regulations Part L2 Thermal Data
fmin = 0.59 Y = 0.53 W/mK fmin = 0.44 Y = 1.01 W/mK
The appropriate Y value for the door system must be added to the above The appropriate Y value for the door system must be added to the above
Y value to obtain the total heat loss through this junction detail. Y value to obtain the total heat loss through this junction detail.
The above values are only applicable to the components on this detail. The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values. Changes to the components will have an effect on the given values.
42
STANDARD

KS1000 RW Wall Systems


Vertically laid

UP AND OVER DOOR HEAD DETAIL

See door manufacturers details for height required


Drum

Optional internal closure flashing

Air seal - 6mm Ø butyl


rubber sealant pe
slo
riable
Mineral fibre insulation Va
site applied

9mm x 3mm butyl rubber sealant

Roller guide supported


Head flashing from main structure
Clear door height

External soffit flashing


RSC door post

Building Regulations Part L2 Thermal Data


fmin = 0.30 Y = 0.66 W/mK
The appropriate Y value for the door system must be added to the above
Y value to obtain the total heat loss through this junction detail.
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.
DOOR JAMB DETAIL
Door guide by others

Door by others

Air seal

RSC door post

Mineral fibre insulation site applied

Sheeting rail

Internal cleader angle by steel


sub-contractor with Vapourflex
seal applied to joints
Air seal - 6mm Ø butyl
rubber sealant
Site cut panel

Door jamb flashing

9mm x 3mm butyl 9mm x 3mm butyl


Clear door width
rubber sealant rubber sealant

Note: Roller shutter doors to be well insulated and Building Regulations Part L2 Thermal Data
have sealed joints, head, jamb and at floor.
fmin = 0.37 Y = 1.33 W/mK
The appropriate Y value for the door system must be added to the above
Y value to obtain the total heat loss through this junction detail.
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.
43
STANDARD

KS1000 MR/EB/FL-S/MM/CX/WV Wall Systems


Horizontally laid

EXTERNAL CORNER DETAIL

KS1000 MR/LPCB Air seal - 4mm Ø bead of gun-grade sealant


horizontally Laid

Corner column

Air seal - 4mm Ø bead


of gun-grade sealant
Air seal - gun-grade
sealant to male joint
Internal cleader angle by Vertical sheeting rail
steel sub-contractor
with air seal - Vapourflex
sealant applied at joints

AWP joint filler and


silicone sealant

Mineral fibre insulation


site applied

External corner flashing 4mm Ø butyl rubber sealant KS1000 MR/LPCB horizontally laid
with 100mm overlaps

Building Regulations Part L2 Thermal Data


fmin = 0.91 Y = 0.18 W/mK
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.
44
STANDARD

KS1000 MR/EB/FL-S/MM/CX/WV Wall Systems


Horizontally laid

VERTICAL JOINT DETAILS


VERTICAL JOINT Min. Steel bearing face 130mm
Mineral fibre insulation site applied
OPTION A

Air seal - EPDM bubble gasket 35mm 40mm 35mm Air seal - gun-grade sealant to male joint
95x10mm. Kingspan (Ref: VJ2)
“Snap on” cover flashing
AWP joint filler and
gun-grade sealant OPTION A
RECESSED

30mm
15
KS1000 MR/LPCB insulated 15
wall panel horizontally laid 35mm 30mm 35mm
15mm recess to“Snap
“Snap on” receiver on” cover flashing
flashing (30mm deep)
Building Regulations Part L2 Thermal Data
4mm Ø butyl rubber
sealant site applied fmin = 0.97 Y = 0.03 W/mK
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.
For joint spacings of 1000mm or more, the above Y value is included
within the U value of the insulated panel.

VERTICAL JOINT
Min. Steel bearing face 130mm
OPTION B Mineral fibre insulation site applied

Air seal - EPDM bubble gasket


95x10mm. Kingspan (Ref: VJ2)
35mm 35mm 35mm
AWP joint filler and Air seal - gun-grade sealant to male joint
gun-grade sealant

30mm

KS1000 MR/LPCB insulated


wall panel horizontally laid Building Regulations Part L2 Thermal Data
35mm 30mm 35mm
“Snap on” receiver flashing (30mm deep) fmin = 0.97 Y = 0.03 W/mK
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.
4mm Ø butyl rubber sealant site applied For joint spacings of 1000mm or more, the above Y value is included
within the U value of the insulated panel.

VERTICAL JOINT
OPTION F Min. Steel bearing face 130mm

Air seal - EPDM bubble gasket Mineral fibre insulation site applied
95x10mm. Kingspan (Ref: VJ2)
35mm 35mm 35mm

AWP joint filler and Air seal - gun-grade sealant to male joint
gun-grade sealant

25mm

KS1000 MR/LPCB insulated


Optional push in MG02 or snap in MXS02
wall panel horizontally laid
28mm 19mm 28mm
Building Regulations Part L2 Thermal Data
9mm x 4mm PVC sealant (site applied)
fmin = 0.96 Y = 0.03 W/mK
TH25 extruded aluminium top hat The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.
section (25mm deep) For joint spacings of 1000mm or more, the above Y value is included
within the U value of the insulated panel.
45
STANDARD

KS1000 MR/EB/FL-S/MM/CX/WV Wall Systems


Horizontally laid

WINDOW HEAD AND CILL DETAIL

Building Regulations Part L2 Thermal Data Air seal - 6mm bead of gun-grade sealant
fmin = 0.49 Y = 0.97 W/mK
The appropriate Y value for the window system must be added to the Optional internal head flashing
above Y value to obtain the total heat loss through this junction detail.
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values. Mineral fibre insulation
site applied
Panel bearer at 1500mm centres
Window support rail
Head flashing

4mm Ø butyl rubber sealant

External soffit flashing with no connection

Window depth to suit panel module


to internal

Polyethylene backing rod with silicone


sealant by window installer

Window unit by others

Mineral fibre insulation


Window cill flashing with 3° slope to facilitate site applied
drainage (no connection to internal)

Air seal - 6mm bead of


gun-grade sealant
Building Regulations Part L2 Thermal Data
Internal cill flashing
fmin = 0.67 Y = 0.48 W/mK
The appropriate Y value for the window system must be added to the
above Y value to obtain the total heat loss through this junction detail.
The above values are only applicable to the components on this detail. 4mm Ø butyl rubber sealant
Changes to the components will have an effect on the given values.

WINDOW JAMB DETAIL

Window opening

Jamb steelwork

Mineral fibre insulation site applied

Polyethylene backing rod with silicone


sealant by window installer

Window unit by others


External jamb flashing with no connection to internal

Air seal - 6mm bead of gun-grade sealant

Site cut panel


Air seal - Gun-grade sealant to male joint

AWP joint filler and gun-grade sealant

4mm Ø Butyl rubber sealant


Building Regulations Part L2 Thermal Data
fmin = 0.62 Y = 0.67 W/mK
The appropriate Y value for the window system must be added to the
above Y value to obtain the total heat loss through this junction detail.
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.
46
STANDARD

KS1000 MR/EB/FL-S/MM/CX/WV Wall Systems


Horizontally laid

PERSONNEL DOOR DETAIL - DOOR JAMB DETAIL A-A


(DOOR HEAD PANEL SITE CUT)

Galvanised door post by steel


sub-contractor with Vapourflex Mineral fibre insulation
sealant applied to joints site applied
B
+2100mm

A A
Polyethylene backing rod with
silicone sealant by door installer
External jamb flashing with no
Door frame connection to internal
by others
Air seal - 6mm Ø bead
of gun-grade sealant 4mm Ø butyl
AWP joint filler and rubber sealant
Pressed metal gun-grade sealant
base channel or
RSA by others Building Regulations Part L2 Thermal Data
fmin = 0.60 Y = 0.80 W/mK
The appropriate Y value for the door system must be added to the above
F.F.L. Y value to obtain the total heat loss through this junction detail.
Expanding type The above values are only applicable to the components on this detail.
0.00mm
anchor fixing Changes to the components will have an effect on the given values.

900mm DOOR HEAD DETAIL B-B

Air seal - 6mm bead


of gun-grade sealant
Optional internal
head flashing

Mineral fibre
insulation
site applied
Galvanised
door head

Door & frame by


others fixed to steel
support frame

External soffit flashing


with no connection to
internal
Note: For opening
outward door ensure 4mm Ø butyl
door head flashing is rubber sealant
sufficiently high
enough to clear Door head flashing
top of door
Building Regulations Part L2 Thermal Data
fmin = 0.44 Y = 0.91 W/mk
The appropriate Y value for the door system must be added to the above
Y value to obtain the total heat loss through this junction detail.
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.
47
STANDARD

KS1000 MR/EB/FL-S/MM/CX/WV Wall Systems


Horizontally laid

DRIP DETAIL - ABOVE FLOOR LEVEL

Column face

Vertical rail

KS1000 MR/LPCB insulated wall


panel horizontally laid

Optional internal closure flashing


to mask insulation from view
Galvanised drip support angle

Mineral fibre insulation site applied

Air seal - 6mm bead of gun-grade sealant

Panel bearer at ends of panel &


max. 1500mm centres between

Drip flashing
Building Regulations Part L2 Thermal Data
fmin = 0.50 Y = 0.86 W/mK Air seal - continuous bead of gun-grade sealant
The appropriate Y value for the brickwork, blockwork or concrete must be added
to the above Y value to obtain the total heat loss through this junction detail.
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.

DRIP DETAIL - BELOW FLOOR LEVEL

Column face

Vertical rail

KS1000 MR/LPCB insulated wall


panel horizontally laid

Optional internal closure flashing


to mask insulation from view
Air seal - 6mm bead of gun-grade sealant

Galvanised drip support angle

Air seal - continuous bead of gun-grade sealant

Both support angles fixed together


prior to placing
Mineral fibre insulation site applied

Galvanised drip support angle

Building Regulations Part L2 Thermal Data Panel bearer at ends of panel &
max. 1500mm centres between
fmin = 0.58 Y = 1.12 W/mK
The appropriate Y value for the brickwork, blockwork or concrete must be added Drip flashing
to the above Y value to obtain the total heat loss through this junction detail.
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.
Alfas C foam seal
48
STANDARD

KS1000 MR/EB/FL-S/MM/CX/WV Wall Systems


Horizontally laid

UP AND OVER DOOR HEAD DETAIL

See door manufacturers details for height required


Drum

Optional internal closure flashing

Air seal - 6mm Ø bead e


lop
of gun-grade sealant le s
ariab
V
Mineral fibre insulation
site applied

4mm Ø butyl rubber sealant

Roller guide supported


Head flashing from main structure
Clear door height

External soffit flashing


RSC door post

Building Regulations Part L2 Thermal Data


fmin = 0.30 Y = 0.68 W/mK
The appropriate Y value for the door system must be added to the above
Y value to obtain the total heat loss through this junction detail.
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.
DOOR JAMB DETAIL
Door guide by others

Door by others

Air seal

RSC door post

Mineral fibre insulation site applied

Sheeting rail

Internal cleader angle by steel


sub-contractor with Vapourflex
seal applied to joints

Air seal - 6mm Ø butyl


rubber sealant

Site cut panel

Door jamb flashing


9mm x 3mm butyl AWP joint filler and
rubber sealant Clear door width gun-grade sealant

Note: Roller shutter doors to be well insulated and Building Regulations Part L2 Thermal Data
have sealed joints, head, jamb and at floor.
fmin = 0.37 Y = 1.70 W/mK
The appropriate Y value for the door system must be added to the above
Y value to obtain the total heat loss through this junction detail.
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.
49

ENHANCED CONSTUCTION DETAILS


50
ENHANCED

Construction Details Contents

This paragraph of text should explain that the remaining pages contain enhanced details.

KS1000 RW Roof Systems Enhanced Details


Ridge Detail 51
Eaves Detail - External Gutter 51
Parapet Detail - Boundary Wall Gutter 52
Verge Detail - Wall Cladding (End of roof sheeting) 53
Valley Gutter Detail 53
Valley Hip Gutter Detail 54
Hip Detail 54

KS1000 LP Roof Systems Enhanced Details


Ridge Detail 55
Parapet Details - Boundary Wall Gutter 56-57
Eaves Details - External Gutter 58
Valley Gutter Detail 59
Verge Details - Wall Cladding 60-61
Valley Hip Detail 62
Hip Detail 62

KS1000 RW Wall (Vertically Laid) Systems Enhanced Details


Drip Detail 63
External Corner Detail 63
Window Head and Cill Detail 64
Window Jamb Detail & Alternative Option Detail 64
Personnel Door Detail (Door head panel site cut) 65
Door Jamb & Door Head Detail 65
Up and Over Door Head Detail 66
Door Jamb Detail 66

KS1000 MR/EB/FL-S/MM/CX/WV Wall (Horizontally Laid) Systems Enhanced Details


Parapet Detail - Boundary Wall Gutter 67
Eaves Details - External Gutter 68
Verge Details - Wall Cladding 69
External Corner Detail 70
Pre-formed External Corner Detail 70
Vertical Joint Details 71
Window Head and Cill Detail 72
Window Jamb Detail 72
Personnel Door Detail - (Door head panel site cut) 73
Door Jamb & Door Head Detail 73
Drip Detail - Above Floor Level & Below Floor Level 74
Up and Over Door Head Detail 75
Door Jamb Detail 75
51
ENHANCED

KS1000 RW Roof Systems

RIDGE DETAIL Site applied Alfasbond fire


rated (FR) canister insulation
Ridge flashing with 150mm KS1000 RW/LPCB
sealed butt straps insulated roof panel

Profiled filler sealed top and Profiled filler set back 80


bottom with gun-grade sealant to 100mm to prevent
bird attack

Air seal - 8mm Ø butyl Internal ridge flashing


rubber sealant with 150mm overlap
sealed with air seal,
Purlin Vapourflex or gun-grade
sealant

Building Regulations Part L2 Thermal Data


fmin = 0.97 Y = 0.004 W/mK
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.

EAVES DETAIL - EXTERNAL GUTTER


Gutter support 0.7mm thick doubled
sided plastisol coated
0mm fixing centres
20
centres
200mm fixing
75mm
Approx

9mm x 3mm butyl


rubber sealant
Air seal - 8mm Ø butyl
rubber sealant
Air seal - 6mm Ø butyl
rubber sealant
Site applied Alfasbond fire
rated (FR) canister insulation

Double sided
Plastisol
“Highline”
type gutter 20 35 20
*
mm mm mm

Eaves beam

Building Regulations Part L2 Thermal Data


fmin = 0.92 Y = 0.27 W/mK * Air seal - Vapourflex sealant is to be applied over any breaks in
supporting secondary steelwork to give a continuous bearing face.
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.
52
ENHANCED

KS1000 RW Roof Systems

PARAPET DETAIL - BOUNDARY WALL GUTTER

Parapet flashing with 150mm sealed butt straps

Site applied PIR board insulation

Site applied Alfasbond fire rated


(FR) canister insulation

Air seal - 6mm Ø butyl rubber sealant

Profiled filler sealed top and bottom with gun-grade sealant


Parapet rail with air seal, Vapourflex tape to rail joints

Profiled filler Sheeting rail


sealed top
and bottom Air seal - 6mm Ø butyl rubber sealant
with gun- Site applied Alfasbond fire
grade sealant rated (FR) canister insulation
KS1000 RW/LPCB
insulated roof panel
KS1000 RW/
LPCB wall panel
vertically laid
Air seal - 8mm Ø
butyl rubber sealant

Factory made thermally broken


membrane lined gutter with PIR
35mm
Min

board insulation to 0.25 or


0.35 W/m2K U-value
60mm

Purlin

Gutter outlet

Eaves beam gutter support

Building Regulations Part L2 Thermal Data


0.25 W/m2K gutter fmin = 0.90 Y = 0.13 W/mK
0.35 W/m2K gutter fmin = 0.90 Y = 0.21 W/mK
0.35 sole width 300mm and depth 150mm, values for other widths available
on request. The above values are only applicable to the components on this
detail. Changes to the components will have an effect on the given values.
53
ENHANCED

KS1000 RW Roof Systems

VERGE DETAIL - WALL CLADDING (END OF ROOF SHEETING)


Verge flashing with 150mm sealed butt straps
PIR board insulation with site applied Alfasbond
fire rated (FR) canister insulation to fill any gaps if
required to maintain continuity of insulation
9mm x 3mm butyl rubber sealant
Verge zed support with 150mm sealed overlaps

Cleader angle by steel sub-contractor with


air seal - Vapourflex sealant applied at joints
Direction of Lay
Air seal - 8mm Ø butyl rubber sealant

Purlin
Air seal - 6mm Ø butyl rubber sealant
Profiled filler sealed top and bottom
with gun-grade sealant
Building Regulations Part L2 Thermal Data
fmin = 0.96 Y = 0.01 W/mK
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.

VALLEY GUTTER DETAIL

KS1000 RW/LPCB
insulated roof panel

Factory made thermally broken membrane


Air seal - 8mm lined gutter with PIR board insulation to Air seal - 8mm
Ø butyl rubber 0.25 or 0.35 W/m2K U-value Ø butyl rubber
sealant sealant
Gutter outlet offset to miss
Purlin
Stanchion head tie stanchion head tie
if necessary as
steelwork design

Building Regulations Part L2 Thermal Data


0.25 W/m2K gutter fmin = 0.94 Y = 0.27 W/mK
0.35 W/m2K gutter fmin = 0.93 Y = 0.43 W/mK
0.35 sole width 600mm and depth 150mm, values for other widths available
on request. The above values are only applicable to the components on this
detail. Changes to the components will have an effect on the given values.
54
ENHANCED

KS1000 RW Roof Systems

VALLEY HIP DETAIL


KS1000 RW/LPCB
Double sided Plastisol coated flashing insulated roof panel

Air seal - 8mm Ø


butyl rubber sealant

Air seal - 8mm Ø butyl


rubber sealant
Edge protection lacquer applied to all
panels cut on site to suit rake angle

Cleader angle by steel


sub-contractor

Factory made thermally broken


membrane lined gutter with PIR
board insulation to 0.25 or 0.35
W/m2K U-value

Hip rafter Purlin

Building Regulations Part L2 Thermal Data


fmin = 0.94 Y = 0.29 W/mK
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.

HIP DETAIL

Panels site cut to suit rake angle


Site applied Alfasbond fire rated
Internal ridge flashing with 150mm overlap (FR) canister insulation
sealed with Vapourflex or gun-grade sealant
Hip flashing with 150mm KS1000 RW/LPCB insulated
sealed butt straps roof panel
Rake cut profiled filler sealed top and Profiled filler set back 80 to
bottom with gun-grade sealant 100mm to prevent bird attack
Cleader angle by steel
sub-contractor Air seal - 8mm Ø butyl
rubber sealant

Hip rafter Purlin

Building Regulations Part L2 Thermal Data


fmin = 0.97 Y = 0.004 W/mK
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.
55
ENHANCED

KS1000 LP Roof Systems

RIDGE DETAIL

Ridge flashing with 150mm


sealed butt straps Outer sheet turned up with roof slopes below 4˚
Site applied Alfasbond
Cover cap fire rated (FR) canister insulation
Profiled filler set back 80 to Apex dam (Ref: LP1)
100mm to prevent bird attack
20mm x 3mm butyl
rubber sealant

Profiled filler sealed


top and bottom with Air seal - 8mm Ø
gun-grade sealant 2 No. runs
silicone sealant butyl rubber sealant
KS1000 LP/LPCB
insulated roof panel

Internal ridge flashing


Purlin
with 150mm overlap
sealed with Vapourflex
or gun-grade sealant

Building Regulations Part L2 Thermal Data


fmin = 0.97 Y = 0.004 W/mK
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.
56
ENHANCED

KS1000 LP Roof Systems

PARAPET DETAIL - BOUNDARY WALL GUTTER

Parapet flashing with 150mm sealed butt straps

Site applied PIR board insulation

Site applied Alfasbond fire rated


(FR) canister insulation

Air seal - 6mm Ø butyl rubber sealant

Profiled filler sealed top and bottom with gun-grade sealant

Sheeting rail
Profiled filler
sealed top Air seal - 6mm Ø butyl rubber sealant
and bottom
with gun- Site applied Alfasbond fire rated (FR) canister insulation
grade sealant
KS1000 LP/LPCB
75mm insulated roof panel
Parapet rail
with air seal
Vapourflex Top sheet turned
tape to rail down on site with
joints roof pitches below 4˚
Profiled filler sealed top
and bottom with gun-grade
Air seal - 8mm Ø butyl
rubber sealant
35mm
Min

KS1000 RW/
Factory made thermally
LPCB wall broken membrane lined
panel gutter with PIR board
vertically laid 60mm insulation to 0.25 or 0.35
W/m2K U-value

Purlin

Gutter outlet

Eaves beam gutter support

Building Regulations Part L2 Thermal Data


0.25 W/m2K gutter fmin = 0.90 Y = 0.13
0.35 W/m2K gutter fmin = 0.90 Y = 0.21
0.35 sole width 300mm and depth 150mm, values for other widths available
on request. The above values are only applicable to the components on this
detail. Changes to the components will have an effect on the given values.
57
ENHANCED

KS1000 LP Roof Systems

PARAPET DETAIL - BOUNDARY WALL GUTTER

Parapet flashing with 150mm sealed butt straps

Site applied PIR board insulation

Site applied Alfasbond fire rated


(FR) canister insulation
Parapet rail with air seal - Vapourflex tape to rail joints

Air seal - 6mm Ø butyl rubber sealant

Profiled filler sealed top and bottom with gun-grade sealant

Air seal - 6mm Ø bead of gun-grade sealant

Sheeting rail
4mm Ø butyl Air seal - 6mm Ø butyl rubber sealant
rubber sealant
Site applied Alfasbond fire rated (FR) canister insulation
KS1000 LP/LPCB
KS1000 MR/
75mm insulated roof panel
LPCB wall panel
horizontally laid
Top sheet turned
KS1000 RW/
down on site with
LPCB wall panel roof pitches below 4˚
vertically laid
Gun-grade seal at panel
joints inline with 8mm butyl
Air seal - 8mm Ø butyl
rubber sealant
35mm
Min

Factory made thermally


broken membrane lined
gutter with PIR board
60mm insulation to 0.25 or 0.35
W/m2K U-value

Purlin
Direction of Lay

Gutter outlet

Eaves beam gutter support

Building Regulations Part L2 Thermal Data


0.25 W/m2K gutter fmin = 0.90 Y = 0.13 W/mK
0.35 W/m2K gutter fmin = 0.90 Y = 0.21 W/mK
0.35 sole width 300mm and depth 150mm, values for other widths available
on request. The above values are only applicable to the components on this
detail. Changes to the components will have an effect on the given values.
58
ENHANCED

KS1000 LP Roof Systems

EAVES DETAIL - EXTERNAL GUTTER


Gutter support 0.7mm thick double sided plastisol coated
Top sheet turned down on site with roof pitches below 4˚

9mm x 3mm butyl rubber sealant


Stitching screw fixings
for gutter brackets
g centres
200mm fixin
g centres
200mm fixin
75mm

KS1000 LP/LPCB insulated roof panel


Gun-grade seal at panel joints inline with 8mm butyl
Air seal - 8mm Ø butyl rubber sealant

Air seal - 6mm Ø butyl rubber sealant


Site applied Alfasbond fire
rated (FR) canister insulation

Double sided
*
plastisol Highline
type gutter 20 35 20
mm mm mm
Eaves beam
* Air seal - Vapourflex
sealant is to be applied
KS1000 RW/LPCB wall over any breaks in Building Regulations Part L2 Thermal Data
panel vertically laid supporting secondary
steelwork to give a fmin = 0.92 Y = 0.27 W/mK
continuous bearing The above values are only applicable to the components on this detail.
face. Changes to the components will have an effect on the given values.

EAVES DETAIL - EXTERNAL GUTTER


Gutter support 0.7mm thick double sided plastisol coated

Top sheet turned down on site with roof pitches below 4˚

9mm x 3mm butyl rubber sealant


Stitching screw fixings
for gutter brackets
g centres
200mm fixin
g centres
200mm fixin
75mm
Approx

KS1000 LP/LPCB insulated roof panel


Gun-grade seal at panel joints inline with 8mm butyl
Air seal - 8mm Ø butyl rubber sealant
Air seal - 6mm Ø
bead of gun-grade sealant
Site applied Alfasbond fire
rated (FR) canister insulation

Double sided
*
plastisol Highline
type gutter 20 35 20
mm mm mm
Eaves beam
* Air seal - Vapourflex
sealant is to be applied
KS1000 MR/LPCB wall over any breaks in Building Regulations Part L2 Thermal Data
panel horizontally laid supporting secondary
steelwork to give a fmin = 0.95 Y = 0.13 W/mK
The above values are only applicable to the components on this detail.
continuous bearing Changes to the components will have an effect on the given values.
face.
59
ENHANCED

KS1000 LP Roof Systems

VALLEY GUTTER DETAIL


Gun-grade seal at panel
Cover cap joints inline with 8mm butyl
75mm

Top sheet turned down on site


with roof pitches below 4˚

Factory made thermally broken membrane


Air seal - 8mm lined gutter with PIR board insulation to
Ø butyl rubber 0.25 or 0.35 W/m2K U-value
sealant
Gutter outlet offset to miss
Stanchion head stanchion head tie Air seal - 8mm Ø
tie if necessary butyl rubber sealant
as steelwork
design Purlin

Building Regulations Part L2 Thermal Data


0.25 W/m2K gutter fmin = 0.96 Y = 0.13 W/mK
0.35 W/m2K gutter fmin = 0.96 Y = 0.25 W/mK
0.35 sole width 600mm and depth 150mm, values for other widths available
on request. The above values are only applicable to the components on this
detail. Changes to the components will have an effect on the given values.
60
ENHANCED

KS1000 LP Roof Systems

VERGE DETAIL - WALL CLADDING (START OF ROOF SHEETING)


Verge flashing with 150mm sealed butt straps
PIR board insulation with site applied Alfasbond fire rated (FR) canister
Direction of Lay
insulation to fill any gaps if required to maintain continuity of insulation
20mm x 3mm butyl rubber sealant
Cleader angle by steel sub-contractor with air seal
Vapourflex sealant applied at joints
KS1000 LP/LPCB insulated roof panel

Purlin
Air seal - 8mm Ø butyl rubber sealant
Air seal - 6mm Ø butyl rubber sealant
Gable rafter
KS1000 RW/LPCB insulated
wall panel horizontally laid
Building Regulations Part L2 Thermal Data 4mm Ø butyl rubber sealant
fmin = 0.96 Y = 0.01 W/mK
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.

VERGE DETAIL - WALL CLADDING (START OF ROOF SHEETING)


Verge flashing with 150mm sealed butt straps
Direction of Lay PIR board insulation with site applied Alfasbond fire rated (FR) canister insulation to
fill any gaps if required to maintain continuity of insulation
20mm x 3mm butyl rubber sealant
Cleader angle by steel sub-contractor with air seal Vapourflex sealant applied at joints
KS1000 LP/LPCB insulated roof panel

Purlin
Air seal - 8mm Ø butyl rubber sealant
Air seal - 6mm Ø bead of gun-grade sealant
Gable rafter
KS1000 MR/LPCB insulated wall
panel horizontally laid
4mm Ø butyl rubber sealant
Building Regulations Part L2 Thermal Data
fmin = 0.96 Y = 0.01 W/mK
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.
61
ENHANCED

KS1000 LP Roof Systems

VERGE DETAIL - WALL CLADDING (END OF ROOF SHEETING)

Verge flashing with 150mm sealed butt straps


PIR board insulation with site applied Alfasbond fire rated (FR) canister insulation to Direction of Lay
fill any gaps if required to maintain continuity of insulation
20mm x 3mm butyl rubber sealant
Cleader angle by steel sub-contractor with air seal Vapourflex sealant
applied at joints
KS1000 LP/LPCB insulated roof panel

Purlin
Air seal - 8mm Ø butyl rubber sealant

Air seal - 6mm Ø butyl rubber sealant


Gable rafter
KS1000 RW/LPCB insulated
wall panel vertically laid Building Regulations Part L2 Thermal Data
Profiled filler sealed top and bottom
with gun-grade sealant
fmin = 0.96 Y = 0.01 W/mK
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.

VERGE DETAIL - WALL CLADDING (END OF ROOF SHEETING)


Verge flashing with 150mm sealed butt straps
PIR board insulation with site applied Alfasbond fire rated (FR) canister insulation to
Direction of Lay
fill any gaps if required to maintain continuity of insulation
20mm x 3mm butyl rubber sealant
Cleader angle by steel sub-contractor with
air seal Vapourflex sealant applied at joints
KS1000 LP/LPCB insulated roof panel

Purlin
Air seal - 8mm Ø butyl rubber sealant

Air seal - 6mm Ø bead of gun-grade sealant


Gable rafter
KS1000 MR/LPCB insulated
wall panel horizontally laid Building Regulations Part L2 Thermal Data
4mm Ø butyl rubber sealant
fmin = 0.96 Y = 0.01 W/mK
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.
62
ENHANCED

KS1000 LP Roof Systems

VALLEY HIP DETAIL


Double sided plastisol
coated flashing
Cover cap Gun-grade seal at
KS1000 LP/LPCB panel joints inline with
insulated roof panel 8mm butyl

Edge protection lacquer applied to all


panels cut on site to suit rake angle

Air seal - 8mm Ø butyl rubber sealant

Cleader angle by steelwork contractors

Factory made thermally broken membrane


lined gutter with PIR board insulation to
0.25 or 0.35 W/m2K U-value

Building Regulations Part L2 Thermal Data Hip rafter Purlin


fmin = 0.94 Y = 0.29 W/mK
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.

HIP DETAIL
Hip flashing with 150mm Site applied Alfasbond fire rated
sealed butt straps (FR) canister insulation
Panels site cut to suit rake angle Outer sheet turned up on
site with roof pitches below 4˚
Apex dam (Ref: LP1/A)
Rake cut profiled filler sealed top Cover cap
and bottom with gun-grade sealant
20mm x 3mm butyl rubber sealant
KS1000 LP/LPCB
2 No. runs of silicone sealant
insulated roof panel

Air seal - 8mm Ø


butyl rubber sealant Purlin
Internal ridge flashing with 150mm overlap Cleader angle by steelwork
sealed with Vapourflex or gun-grade sealant contractor

Building Regulations Part L2 Thermal Data Hip rafter


fmin = 0.97 Y = 0.004 W/mK
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.
63
ENHANCED

KS1000 RW Wall Systems


Vertically laid

DRIP DETAIL

Stanchion
Optional internal closure flashing to
mask insulation from view
Sheeting rail

Air seal - 6mm Ø butyl


rubber sealant

PIR board insulation with Alfasbond


(FR) canister applied insulation to fill
any gaps if required to maintain
continuity of insulation

100mm min. 35mm


lap over wall min
Panels specified with flush
ends will have a minimum
cut back of 10mm

Drip flashing

Air seal - continuous bead of gun-grade sealant

Building Regulations Part L2 Thermal Data


fmin = 0.64 Y = 0.54 W/mK
The appropriate Y value for the brickwork, blocks or concrete must be added
to the above Y value to obtain the total loss through this junction detail.
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.

EXTERNAL CORNER DETAIL

Corner column

Sheeting rail

KS1000 RW/LPCB insulated wall panel vertically laid

Air seal - 6mm Ø butyl rubber sealant

Internal cleader angle by steel sub-contractor with


air seal Vapourflex sealant applied at joints

Zed support lapped 100mm at joints

Site cut vertical sheeting

PIR board insulation with site applied air seal Alfasbond


fire rated (FR) canister insulation to fill any gaps if
required to maintain continuity of insulation

External corner flashing with 100mm sealed overlaps

On site remove overlap leg from panel

9mm x 3mm butyl rubber sealant Direction of Lay

KS1000 RW/LPCB insulated wall panel vertically laid

Building Regulations Part L2 Thermal Data


fmin = 0.95 Y = 0.01 W/mK
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.
64
ENHANCED

KS1000 RW Wall Systems


Vertically laid

WINDOW HEAD AND CILL DETAIL

Building Regulations Part L2 Thermal Data Air seal - 6mm Ø butyl rubber sealant

fmin = 0.50 Y = 0.61 W/mK PIR board insulation


The appropriate Y value for the window system must be added to the
above Y value to obtain the total heat loss through this junction detail.
The above values are only applicable to the components on this detail. Optional internal head flashing
Changes to the components will have an effect on the given values.

Window support rail


Head flashing

Internal head flashing


9mm x 3mm butyl rubber sealant (optional) with no connection
to external soffit flashing

25mm thick PIR board insulation

Window depth to suit panel module


External soffit flashing with no
connection to internal flashing

Polyethylene backing rod with silicone sealant


by window installer

Window unit by others

Site applied Alfasbond fire rated


(FR) canister insulation

Window cill flashing with 3° slope to facilitate


drainage (no connection to internal flashing)

Profiled filler sealed top and bottom


with gun-grade sealant
Ferrules used to fix windows
Building Regulations Part L2 Thermal Data
Air seal - 6mm Ø butyl
fmin = 0.95 Y = 0.07 W/mK rubber sealant
The appropriate Y value for the window system must be added to the
above Y value to obtain the total heat loss through this junction detail.
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.

WINDOW JAMB DETAIL OPTION 1 WINDOW JAMB DETAIL OPTION 2

Window width
Internal jamb flashing with no
connection to external flashing

25mm thick PIR


board insulation
Jamb steelwork

Window unit
by others

Polyethylene backing
rod with silicone sealant
Air seal - 6mm Ø butyl
rubber sealant
External jamb flashing
with no connection to
internal flashing
Site cut panel
Building Regulations Part L2 Thermal Data
9mm x 3mm butyl rubber sealant
fmin = 0.96 Y = 0.08 W/mK
The appropriate Y value for the window system must be added to the
above Y value to obtain the total heat loss through this junction detail.
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.
65
ENHANCED

KS1000 RW Wall Systems


Vertically laid

PERSONNEL DOOR DETAIL (DOOR HEAD PANEL SITE CUT)

+2100mm

B
A A

Door frame by others

Pressed metal base channel Expanding type anchor


or RSA by others fixing by others

F.F.L. 0.00mm
900mm

DOOR JAMB DETAIL A-A DOOR HEAD DETAIL B-B


Galvanised door post by Air seal - 6mm Ø
steel sub-contractor with butyl rubber sealant
Vapourflex sealant
applied to joints Internal jamb flashing PIR board
with no connection to insulation
external flashing
25mm thick PIR Optional internal
board insulation head flashing

Ferrules used Galvanised


to fix doors door head

25mm thick PIR


board insulation
Internal head flashing
(optional) with no
connection to
external soffit flashing
Door & frame by
Polyethylene backing rod others fixed to steel
with silicone sealant support frame
External soffit flashing
with no connection to
Air seal - 6mm Ø butyl internal flashing
rubber sealant 9mm x 3mm butyl
rubber sealant
9mm x 3mm butyl
rubber sealant Door head flashing
External jamb flashing with no
connection to internal flashing Note: For opening outward door ensure
drip flashing is clear top of door

Building Regulations Part L2 Thermal Data Building Regulations Part L2 Thermal Data
fmin = 0.96 Y = 0.08 W/mK fmin = 0.50 Y = 0.61 W/mK
The appropriate Y value for the door system must be added to the above The appropriate Y value for the door system must be added to the above
Y value to obtain the total heat loss through this junction detail. Y value to obtain the total heat loss through this junction detail.
The above values are only applicable to the components on this detail. The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values. Changes to the components will have an effect on the given values.
66
ENHANCED

KS1000 RW Wall Systems


Vertically laid

UP AND OVER DOOR HEAD DETAIL

See door manufacturers details for height required


Drum

Optional closure flashing

e
lop
Air seal - 6mm Ø butyl le s
rubber sealant ariab
V
PIR board insulation

Head flashing

Roller guide supported


from main structure
9mm x 3mm butyl rubber sealant
Clear door height

60mm return to soffit flashing


70mm thick PIR
board insulation External soffit flashing

RSC door post

Building Regulations Part L2 Thermal Data


fmin = 0.51 Y = 0.62 W/mK
The appropriate Y value for the door system must be added to the above
Y value to obtain the total heat loss through this junction detail.
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.
DOOR JAMB DETAIL
Door guide by others

Door by others

Air seal

RSC door post

Sheeting rail

70mm thick PIR board insulation


with site applied Alfasbond fire
rated (FR) canister insulation filling
gaps

Internal cleader angle by steel


sub-contractor with Vapourflex
seal applied to joints
Air seal - 6mm Ø butyl
rubber sealant
Site cut panel

Door jamb flashing

9mm x 3mm butyl 9mm x 3mm butyl


Clear door width
rubber sealant rubber sealant

Note: Roller shutter doors to be well insulated and Building Regulations Part L2 Thermal Data
have sealed joints, head, jamb and at floor.
fmin = 0.76 Y = 0.81 W/mK
The appropriate Y value for the door system must be added to the above
Y value to obtain the total heat loss through this junction detail.
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.
67
ENHANCED

KS1000 MR/EB/FL-S/MM/CX/WV Wall Systems


Horizontally laid

PARAPET DETAIL - BOUNDARY WALL GUTTER


Parapet fixing with 150mm sealed butt straps

80mm PIR approved insulation board

Site applied Alfasbond fire rated (FR) canister insulation

Parapet rail air seal Vapourflex tape to rail joints

Air seal - 6mm Ø butyl rubber sealant

Profiled filler sealed top and bottom


with gun-grade sealant

Air seal - 6mm Ø bead of gun-grade sealant

4mm Ø butyl Air seal - 6mm Ø butyl rubber sealant


rubber sealant
Site applied Alfasbond fire rated (FR)
KS1000 canister insulation as panel is placed
MR/LPCB
insulated wall
panel KS1000 RW/LPCB insulated
horizontally laid roof panel
KS1000
RW/LPCB
insulated roof
panel vertically
laid

Factory made membrane


35mm
Min

lined gutter with PIR Air seal - 8mm


board insulation 0.25 or Ø butyl rubber
60mm 0.35 W/m2K U value sealant

Purlin

Direction
of Lay

Gutter outlet

Eaves beam gutter support with


expandable seal

Building Regulations Part L2 Thermal Data


0.25 W/m2K gutter fmin = 0.90 Y = 0.13 W/mK
0.35 W/m2K gutter fmin = 0.90 Y = 0.21 W/mK
0.35 sole width 300mm and depth 150mm, values for other widths available
on request. The above values are only applicable to the components on this
detail. Changes to the components will have an effect on the given values.
68
ENHANCED

KS1000 MR/EB/FL-S/MM/CX/WV Wall Systems


Horizontally laid

EAVES DETAIL - EXTERNAL GUTTER

Gutter support 0.7mm thick double sided plastisol coated

centres 9mm x 3mm butyl rubber sealant


0mm fixing
m fixing centres 20
200m
75mm
Approx

KS1000 RW/LPCB
insulated roof panel
Air seal - 8mm Ø butyl rubber sealant

Double sided
Plastisol “High

*
line” type gutter 20 35 20
mm mm mm

Eaves beam

Site applied Alfasbond fire rated


(FR) canister insulation

Air seal - 6mm Ø bead of gun-grade sealant


KS1000 MR/LPCB insulated
wall panel horizontally laid

Building Regulations Part L2 Thermal Data

Direction
fmin = 0.95 Y = 0.13 W/mK
The above values are only applicable to the components on this detail.
of Lay Changes to the components will have an effect on the given values.

* Air seal - Vapourflex sealant is to be applied over any breaks in


supporting secondary steelwork to give a continuous bearing face.
69
ENHANCED

KS1000 MR/EB/FL-S/MM/CX/WV Wall Systems


Horizontally laid

VERGE DETAIL - WALL CLADDING (START OF ROOF SHEETING)


Verge flashing with 150mm sealed butt straps

PIR board insulation with fire rated Alfasbond (FR) canister insulation
to fill any gaps if required to maintain continuity of insulation
Verge zed support lapped 150mm at joints

Cleader angle by steel sub-contractor with


Direction of Lay air seal Vapourflex sealant applied to joints
KS1000 RW/LPCB insulated roof panel

9mm x 3mm butyl


rubber sealant

4mm Ø butyl
rubber sealant

KS1000 MR/LPCB insulated


wall panel horizontally laid
Air seal - 8mm Ø butyl rubber sealant
Air seal - 6mm Ø bead of gun-grade sealant
Purlin
Gable rafter

Direction of Lay Vertical sheeting rail

Building Regulations Part L2 Thermal Data


fmin = 0.96 Y = 0.01 W/mK
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.

VERGE DETAIL - WALL CLADDING (END OF ROOF SHEETING)


Verge flashing with 150mm sealed butt straps

PIR board insulation with fire rated Alfasbond (FR) canister insulation
to fill any gaps if required to maintain continuity of insulation
Verge zed support lapped 150mm at joints
Cleader angle by steel sub-contractor with
Vapourflex sealant applied to joints
Site cut KS1000 RW/LPCB
insulated roof panel to suit Direction of Lay

9mm x 3mm butyl


rubber sealant

4mm Ø butyl
rubber sealant

KS1000 MR/LPCB insulated


Air seal - 8mm Ø bead of gun-grade sealant wall panel horizontally laid

Air seal - 6mm Ø bead of gun-grade sealant


Purlin
Gable rafter

Vertical sheeting rail Direction of Lay

Building Regulations Part L2 Thermal Data


fmin = 0.96 Y = 0.01 W/mK
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.
70
ENHANCED

KS1000 MR/EB/FL-S/MM/CX/WV Wall Systems


Horizontally laid

EXTERNAL CORNER DETAIL

KS1000 MR/LPCB Air seal - 4mm Ø bead of gun-grade sealant


horizontally Laid

Corner column

Air seal - 4mm Ø bead


of gun-grade sealant
Air seal - gun-grade
sealant to male joint
Internal cleader angle by Vertical sheeting rail
steel sub-contractor
with air seal - Vapourflex
sealant applied at joints

AWP joint filler and


silicone sealant

PIR board insulation with


Alfasbond FR canister
applied insulation to fill any
gaps if required to maintain
continuity of insulation

External corner flashing 4mm Ø butyl rubber sealant KS1000 MR/LPCB horizontally laid
with 100mm overlaps

Building Regulations Part L2 Thermal Data


fmin = 0.96 Y = 0.01 W/mK
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.

EXTERNAL PRE-FORMED CORNER DETAIL

For vertical joint details see page 71

KS1000 MR/LPCB
horizontally laid pre-formed
insulated corner panel

Pre-formed panel maximum


unsupported length 1000mm.
For longer panels additional
steelwork is required.

Building Regulations Part L2 Thermal Data


fmin = 0.96 Y = 0.01 W/mK
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.
71
ENHANCED

KS1000 MR/EB/FL-S/MM/CX/WV Wall Systems


Horizontally laid

VERTICAL JOINT DETAILS


PIR board insulation with fire rated Alfasbond
VERTICAL JOINT Min. Steel bearing face 130mm
(FR) canister insulation to fill any gaps if required
OPTION A to maintain continuity of insulation

Air seal - EPDM bubble gasket 35mm 40mm 35mm Air seal - gun-grade sealant to male joint
95x10mm. Kingspan (Ref: VJ2)
“Snap on” cover flashing
AWP joint filler and
gun-grade sealant OPTION A
RECESSED

30mm
15
KS1000 MR/LPCB insulated 15
wall panel horizontally laid 35mm 30mm 35mm
15mm recess to“Snap
“Snap on” receiver on” cover flashing
flashing (30mm deep)
Building Regulations Part L2 Thermal Data
4mm Ø butyl rubber
sealant site applied fmin = 0.96 Y = 0.01 W/mK
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.
For joint spacings of 1000mm or more, the above Y value is included
within the U value of the insulated panel.

PIR board insulation with fire rated Alfasbond


VERTICAL JOINT Min. Steel bearing face 130mm
(FR) canister insulation to fill any gaps if required
OPTION B to maintain continuity of insulation
Air seal - EPDM bubble gasket
95x10mm. Kingspan (Ref: VJ2)
35mm 35mm 35mm
AWP joint filler and Air seal - gun-grade sealant to male joint
gun-grade sealant

30mm

KS1000 MR/LPCB insulated


wall panel horizontally laid Building Regulations Part L2 Thermal Data
35mm 30mm 35mm
“Snap on” receiver flashing (30mm deep) fmin = 0.96 Y = 0.01
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.
4mm Ø butyl rubber sealant site applied For joint spacings of 1000mm or more, the above Y value is included
within the U value of the insulated panel.

OPTION F Min. Steel bearing face 130mm


PIR board insulation with fire rated Alfasbond
Air seal - EPDM bubble gasket (FR) canister insulation to fill any gaps if required
95x10mm. Kingspan (Ref: VJ2) to maintain continuity of insulation
35mm 35mm 35mm

AWP joint filler and Air seal - gun-grade sealant to male joint
gun-grade sealant

25mm

KS1000 MR/LPCB insulated


Optional push in MG02 or snap in MXS02
wall panel horizontally laid
28mm 19mm 28mm
Building Regulations Part L2 Thermal Data
9mm x 4mm PVC sealant (site applied)
fmin = 0.96 Y = 0.01
TH25 extruded aluminium top hat The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.
section (25mm deep) For joint spacings of 1000mm or more, the above Y value is included
within the U value of the insulated panel.
72
ENHANCED

KS1000 MR/EB/FL-S/MM/CX/WV Wall Systems


Horizontally laid

WINDOW HEAD AND CILL DETAIL

Building Regulations Part L2 Thermal Data Air seal - 6mm bead of gun-grade sealant
fmin = 0.34 Y = 0.83 W/mK
The appropriate Y value for the window system must be added to the PIR board insulation
above Y value to obtain the total heat loss through this junction detail.
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values. Optional internal head flashing

Panel bearer at 1500mm centres


Window support rail
Head flashing
Internal head flashing (optional)
4mm Ø butyl rubber sealant with no connection to external
soffit flashing

25mm thick PIR board insulation

Window depth to suit panel module


External soffit flashing with no connection
to internal flashing

Polyethylene backing rod with silicone


sealant by window installer

Window unit by others

Site applied Alfasbond fire rated (FR)


canister insulation Ferrules used to
fix window
Window cill flashing with 3° slope to facilitate
drainage (no connection to internal flashing)

Air seal - 6mm bead of


gun-grade sealant
Building Regulations Part L2 Thermal Data
fmin = 0.93 Y = 0.10 W/mK 4mm Ø butyl rubber sealant
The appropriate Y value for the window system must be added to the
above Y value to obtain the total heat loss through this junction detail.
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.

WINDOW JAMB DETAIL


Window opening

Jamb steelwork
Internal jamb flashing with no connection to external flashing

Site applied 25mm thick PIR board insulation with Alfasbond


fire rated (FR) canister insulation filling gaps
to maintain insulation prior to placing board

Polyethylene backing rod with silicone


sealant by window installer

Window unit by others


External jamb flashing with no connection to internal flashing

Air seal - 6mm bead of gun-grade sealant

Site cut panel


Air seal - Gun-grade sealant to male joint

AWP joint filler and gun-grade sealant


4mm Ø Butyl rubber sealant
Building Regulations Part L2 Thermal Data
fmin = 0.96 Y = 0.08 W/mK
The appropriate Y value for the window system must be added to the
above Y value to obtain the total heat loss through this junction detail.
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.
73
ENHANCED

KS1000 MR/EB/FL-S/MM/CX/WV Wall Systems


Horizontally laid

PERSONNEL DOOR DETAIL - DOOR JAMB DETAIL A-A


(DOOR HEAD PANEL SITE CUT)
Galvanised door post by steel 25mm thick PIR board
sub-contractor with Vapourflex insulation with site applied
sealant applied to joints Alfasbond fire rated (FR)
canister insulation filling
Internal jamb flashing with no gaps to maintain insulation
connection to external flashing prior to placing board

B
+2100mm Ferrules used to fix doors

A A
Polyethylene backing rod with
silicone sealant by door installer

External jamb flashing with no


Door frame connection to internal flashing
by others
Air seal - 6mm Ø bead
of gun-grade sealant 4mm Ø butyl
AWP joint filler and rubber sealant
Pressed metal gun-grade sealant
base channel or
RSA by others Building Regulations Part L2 Thermal Data
fmin = 0.96 Y = 0.08 W/mK
The appropriate Y value for the door system must be added to the above
F.F.L. Y value to obtain the total heat loss through this junction detail.
Expanding type The above values are only applicable to the components on this detail.
0.00mm
anchor fixing Changes to the components will have an effect on the given values.

900mm DOOR HEAD DETAIL B-B

Optional internal
head flashing
Air seal - 6mm bead
of gun-grade sealant

PIR board insulation

Galvanised door head

25mm thick PIR


board insulation
Optional internal
head flashing
with no connection
to external soffit
flashing
Door & frame by
others fixed to steel
support frame
External soffit flashing
with no connection to
internal flashing
Note: For opening 4mm Ø butyl
outward door ensure rubber sealant
door head flashing is
sufficiently high Door head flashing
enough to clear
top of door
Building Regulations Part L2 Thermal Data
fmin = 0.51 Y = 0.62 W/mK
The appropriate Y value for the door system must be added to the above
Y value to obtain the total heat loss through this junction detail.
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.
74
ENHANCED

KS1000 MR/EB/FL-S/MM/CX/WV Wall Systems


Horizontally laid

DRIP DETAIL - ABOVE FLOOR LEVEL

Column face

Vertical rail

KS1000 MR/LPCB insulated wall


panel horizontally laid

Optional internal closure flashing


to mask insulation from view
Galvanised drip support angle

80mm thick PIR board insulation with


Alfasbond FR canister applied
insulation used to fill gap, if required

Air seal - 6mm bead of gun-grade sealant

Panel bearer at ends of panel &


max. 1500mm centres between

Drip flashing
Building Regulations Part L2 Thermal Data
fmin = 0.33 Y = 0.60 W/mK Air seal - continuous bead of gun-grade sealant
The appropriate Y value for the brickwork, blockwork or concrete must be added
to the above Y value to obtain the total heat loss through this junction detail.
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.

DRIP DETAIL - BELOW FLOOR LEVEL

Column face

Vertical rail

KS1000 MR/LPCB insulated wall panel


horizontally laid

Optional internal closure flashing


to mask insulation from view
Air seal - 6mm bead of gun-grade sealant

Galvanised drip support angle

80mm thick PIR board insulation with


Alfasbond FR canister applied
insulation used to fill gap, if required

Air seal - continuous bead of gun-grade sealant

Both support angles fixed together


prior to placing
Galvanised drip support angle

Building Regulations Part L2 Thermal Data Panel bearer at ends of panel &
max. 1500mm centres between
fmin = 0.60 Y = 0.35 W/mK
The appropriate Y value for the brickwork, blockwork or concrete must be added Drip flashing
to the above Y value to obtain the total heat loss through this junction detail.
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.
75
ENHANCED

KS1000 MR/EB/FL-S/MM/CX/WV Wall Systems


Horizontally laid

UP AND OVER DOOR HEAD DETAIL

Drum
See door manufacturers details for height required

Air seal - 6mm bead Internal door head


of gun-grade sealant flashing - optional

e
PIR board insulation lop
le s
ariab
V

Head flashing

Roller guide supported


from main structure
60mm return to soffit flashing.
4mm Ø butyl sealant
Clear door height

Door guide with air seal


70mm thick PIR
board insulation
External soffit flashing

RSC door post

Building Regulations Part L2 Thermal Data


fmin = 0.51 Y = 0.63 W/mK
The appropriate Y value for the door system must be added to the above
Y value to obtain the total heat loss through this junction detail.
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.

DOOR JAMB DETAIL

Door guide with air seals

70mm thick PIR board insulation


with Alfasbond fire rated (FR)
Site cut panel canister insulation filling gaps to Air seal - 6mm bead of
maintain insulation prior to gun-grade sealant
Air seal - 6mm placing board
Bridging seal to
bead of gun- male joint
grade sealant
RSC door posts by steel sub-
contractor with Vapourflex
sealant applied at joints

Door jamb flashing

4mm Ø butyl AWP joint filler and gun-


rubber sealant Clear door width grade sealant

Building Regulations Part L2 Thermal Data


Note: Roller shutter doors to be well insulated and
fmin = 0.74 Y = 0.71 W/mK have sealed joints, head, jamb and at floor.
The appropriate Y value for the door system must be added to the above
Y value to obtain the total heat loss through this junction detail.
The above values are only applicable to the components on this detail.
Changes to the components will have an effect on the given values.
Kingspan Insulated Roof & Wall Systems
Roof Systems
KS1000 RW KS1000 TS KS1000 KS1000 LP KS1000 CR
Trapezoidal Tile Support Kingzip Low Pitched Curved

Available Q1 2003

Wall Systems
KS600, 900 KS600, 900 KS600, 900 KS600, 900
& 1000 & 1000 MR & 1000 EB & 1000 FL-S
Optimo Micro-Rib Euro-Box Flat (Stucco)

KS600, 900 KS600, 900 KS600, 900 KS1000 RW


& 1000 MM & 1000 CX & 1000 WV Trapezoidal
Mini-Micro Convex Wave

Insulated Temperature Control Systems


KS1200 CS

Telephone: +44 (0) 1352 716110, Fax: +44 (0) 1352 716161, Email: info@kingspanpanels.com
www.kingspanpanels.com

You might also like