You are on page 1of 24

n° 172

earthing systems
in LV

Bernard Lacroix Roland Calvas

An ESPCI 74 engineering graduate An ENSERG 1964 engineering


(from the Ecole Supérieure de graduate (from the Ecole Nationale
Physique et Chimie Industrielle de Supérieure d'Electronique et
Paris), he then worked 5 years for Radioélectricité de Grenoble) and an
Jeumont Schneider, where his Institut d'Administration des
activities included development of Entreprises graduate, he joined
the TGV chopper. Merlin Gerin in 1966.
After joining Merlin Gerin in 1981, he During his professional career, he
was then in turn Sales Engineer for has been sales manager and then
UPS and sales manager for marketing manager for protection of
protection of persons. persons. He is currently in charge of
Since 1991 he is in charge of technical communication for the
prescription for LV power groupe Schneider.
distribution.

E/CT 172, first issued September 1995


glossary

Electric Shock Application of a voltage between two parts of the body


Electrocution Electric Shock resulting in death
EMC Electro Magnetic Compatibility
I∆n Operating threshold of a RCD
IMD Insulation Monitoring Device
GFLD Insulation Fault Location Device
MV/HV Medium Voltage: 1 to 35 kV as in CENELEC (circular of the 27.07.92)
High Voltage: 1 to 50 kV as in french standard (14.11.88)
RCD Residual Current Device
SCPD Short-Circuit Protection Device (circuit-breakers or fuses)
STD Short Time Delay protection (protection against short-circuit overcurrents by circuit-breaker with rapid
trip release)
TBM Technical Building Management
TEM Technical Electrical Power Distribution Management
UL Conventional limit voltage (maximum acceptable contact voltage) known as the «safety» voltage

Cahier Technique Merlin Gerin n° 172 / p.2


This «Cahier Technique» reviews the
earthing systems in LV hazards that insulation faults represent
for safety of persons and propery. It
emphasises the influence of earthing
systems and the availability of electrical
power.
It presents the three earthing systems
defined in standard IEC 364 and used
to varying degrees in all countries.
Each earthing system is looked at in
content terms of dependability (safety,
maintenability and availability).
There is no such thing as a bad
1. Introduction Evolution of needs p. 4 earthing system; they all ensure safety
Causes of insulation faults p. 4 of persons. Each system has its own
advantages and disadvantages and the
Hazards linked to insulation faults p. 4 user must therefore be guided
2. Earthing systems and protection of persons p. 7 according to his needs, with the
TN system p. 8 exception, however, of prescription or
TT system p. 9 of standard or legislative bans.
IT system p. 9 Readers interested in the practices of
various countries and in evolution of
3. Earthing systems confronted with Fire p. 12
earthing systems should read «Cahier
fire and electrical power unavailabiliy Electrical power unavailability p. 12 Technique» n° 173.
hazards
4. Influences of MV on BV, according to Lighning p. 14
the earthing systems Operating overvoltages p. 14
MV-frame disruptive breakdown p. 14
of the transformer
MV-LV disruptive breakdown p. 15
inside the transformer
5. Switchgear linked to choice of TN system p. 17
earthing system TT system p. 17
IT system p. 18
Neutral protection according to p. 19
the earthing system
6. Choice of eathing system Methods for choosing the p. 21
and conclusion earthing system
Conclusion p. 21
7. Bibliography p. 22

Cahier Technique Merlin Gerin n° 172 / p.3


1. introduction

evolution of needs c use of insulating materials; It is normally a combination of these


Today the 3 earthing systems such as c distancing, which calls for clearances primary causes which results in the
defined in IEC 364 and French in gases (e.g. in air) and creepage insulation fault. The latter is:
standard NF C 15-100, are: distances (concerning switchgear, e.g. c either of differential mode (between
c exposed-conductive parts connected an insulator flash over path). live conductors) and becomes a
to neutral -TN-; Insulation is characterised by specified short-circuit;
c earthed neutral -TT-; voltages which, in accordance with c or of common mode (between live
c unearthed (or impedance-earthed) standards, are applied to new products conductors and frame or earth), a fault
neutral -IT-. and equipment: current -said to be common mode or
The purpose of these three systems is c insulating voltage (highest network zero sequence (MV)- then flows in the
identical as regards protection of voltage); protective conductor (PE) and/or in the
persons and property: mastery of c lightning impulse withstand voltage earth.
insulation fault effects. They are (1.2; 50 µs wave); LV earthing systems are mainly
considered to be equivalent with c power frequency withstand voltage concerned by common mode faults
respect to safety of persons against (2 U + 1,000 V/1mn). which mainly occur in loads and cables.
indirect contacts. Example for a LV PRISMA type
However, the same is not necessarily switchboard:
true for dependability of the c insulating voltage: 1,000 V;
hazards linked to
LV electrical installation with respect to: c impulse voltage: 12 kV. insulation faults
c electrical power availability; An insulation fault, irrespective of its
When a new installation is
c installation maintenance. cause, presents hazards for:
commissioned, produced as per
These quantities, which can be proper practices with products c human life;
calculated, are subjected to manufactured as in standards, c preservation of property;
increasingly exacting requirements in the risk of insulation faults is extremely c availability of electrical power;
factories and tertiary buildings. small; as the installation ages, the above all depending on
Moreover, the control and monitoring dependability.
however, this risk increases.
systems of buildings -TBM- and
electrical power distribution In point of fact, the installation is Electric Shock of persons
management systems -TEM- play an subject to various aggressions which A person (or animal) subjected to
increasingly important role in give rise to insulation faults, for an electrical voltage is electrified.
management and dependability. example: According to the gravity of the Electric
c during installation: Shock, this person may experience:
This evolution in dependability
requirements therefore affects the v mechanical damage to a cable c discomfort;
choice of earthing system. insulator; c a muscular contraction;
c during operation: c a burn;
It should be borne in mind that the
v conductive dust, c cardiac arrest (this is Electrocution)
concern with continuity of service
v thermal ageing of insulators due to (see fig. 1).
(keeping a sound network in public
excessive temperature caused by: Since protection of persons against the
distribution by disconnecting
consumers with insulation faults) played - climate, dangerous effects of electric current
a role when earthing systems first - too many cables in a duct, takes priority, Electric Shock is thus the
emerged. - a poorly ventilated cubicle, first hazard to be considered.
- harmonics, The current strength I -in value and
- overcurrents, etc, time-, passing through the human body
causes of insulation faults v the electrodynamic forces developed (in particular the heart) is the
In order to ensure protection of persons during a short-circuit which may dangerous aspect. In LV, the
and continuity of service, conductors damage a cable or reduce a clearance, impedance value of the body (an
and live parts of electrical installations v the operating and lightning important aspect of which is skin
are «insulated» from the frames overvoltages, resistance) virtually changes only
connected to the earth. v the 50 Hz return overvoltages, according to environment (dry and wet
Insulation is achieved by: resulting from an insulation fault in MV. premises and damp premises).

Cahier Technique Merlin Gerin n° 172 / p.4


In each case, a safety voltage
(maximum acceptable contact voltage time during which the human body is exposed
for at least 5 s) has been defined: it is
ms
known as the conventional limit voltage
UL in IEC 479. 10,000
a b c1 c2 c3
IEC 364 paragraph 413.1.1.1 and 5,000
NF C 15-100 state that if there is a risk
of contact voltage Uc exceeding 2,000
voltage UL, the application time of the 1,000
fault voltage must be limited by the use
500
of protection devices (see fig. 2).
1 2 3 4
Fire 200
This hazard, when it occurs, can have
100
dramatic consequences for both
persons and property. A large number 50
of fires are caused by important and
localised temperature rises or an 20
mA
electric arc generated by an insulation 10
fault. The hazard increases as the fault 0.1 0.2 0.5 1 2 5 10 20 50 100 200 500 1,000 2,000 5,000 10,000
current rises, and also depends on the current passing through the human body
risk of fire or explosion occurring in the
premises. zone 1: perception
zone 2: considerable discomfort
Unavailability of electrical power zone 3: muscular contractions
It is increasingly vital to master this zone 4: risk of ventricular fibrillation (cardiac arrest)
hazard. In actual fact if the faulty part is c1: likelihood 5 %
automatically disconnected to eliminate c3: likelihood > 50 %
the fault, the result is:
fig. 1: time/current zones of AC current effects (15 Hz to 100 Hz) on persons as in IEC 479-1.
c a risk for persons, for example:
v sudden absence of lighting,
v placing out of operation of equipment c dry or wet premises and places: UL i 50 V
required for safety purposes; presumed contact voltage (V) maximum breaking time of the protection
c an economic risk due to production device (s)
loss. This risk must be mastered in AC DC
particular in process industries, which < 50 5 5
are lengthy and costly to restart. 50 5 5
75 0.60 5
Moreover, if the fault current is high: 90 0.45 5
c damage, in the installation or the 120 0.34 5
loads, may be considerable and 150 0.27 1
increase repair costs and times; 220 0.17 0.40
c circulation of high fault currents in the 280 0.12 0.30
common mode (between network and 350 0.08 0.20
earth) may also disturb sensitive 500 0.04 0.10
equipment, in particular if these are part
of a «low current» system c damp premises and places: UL i 25 V
geographically distributed with galvanic presumed contact voltage (V) maximum breaking time of the protection
links. device (s)
Finally, on de-energising, the AC (a) DC (b)
25 5 5
occurrence of overvoltages and/or
50 0.48 5
electromagnetic radiation phenomena
75 0.30 2
may lead to malfunctioning or even 90 0.25 0.80
damage of sensitive equipment. 110 0.18 0.50
Direct and indirect contacts 150 0.10 0.25
Before beginning to study the earthing 220 0.05 0.06
systems, a review of Electric Shock by 280 0.02 0.02
direct and indirect contacts will certainly fig. 2: maximum time for maintenance of contact voltage as in standard IEC 364.
be useful.

Cahier Technique Merlin Gerin n° 172 / p.5


c direct contact and protection The protection measures against
measures indirect contacts are based on three a) direct contact
This is accidental contact of persons basic principles:
ph
with a live conductor (phase or neutral) c earthing of the frames of loads
or a normally live conductive element and electrical equipment to
(see fig. 3a). prevent an insulation fault from
In cases where the risk is very great, resulting in the equivalent of a direct
the common solution consists in contact; Uc
distributing electricity using a non- c equipotentiality of simultaneously
dangerous voltage, i.e. less than or accessible frames
equal to safety voltage. This is Interconnection of these frames
safety by extra-low voltage (SELV b) indirect contact
considerably helps to reduce contact
or PELV), in LV (230/400 V). voltage. It is performed by the
3
Protection measures consist in placing protective conductor (PE) which
these live parts out of reach or in connects the frames of electrical
insulating them by means of insulators, equipment for entire buildings,
enclosures or barriers. A complemen- completed if required by
tary measure against direct contacts additional equipotential links Id Uc
consists in using instantaneous (see fig. 4).
i 30 mA High Sensitivity Residual Reminder: equipotentiality cannot
Current Devices known as HS-RCDs. fig. 3: direct and indirect contacts.
be complete in all points (in particular
Note: this measure is necesssary in all in single level premises). Consequently,
circuit supply cases where for the study of earthing systems
implementation of the earthing system and their associated protection
downstream is not mastered. devices, the hypothesis chosen by
Consequently, some countries make standard makers Uc = Ud is applied
this measure a requirement: since Uc is at the most equal to Ud. individual
v for sockets of rating i 32 A, v Ud = «fault» voltage, with respect to protective
v in some types of installations the deep earth, of the frame of an conductors
(temporary, worksite, etc.). (PE)
electrical device with an insulation
Treatment of protection against direct reinforcement
fault,
meshing
contacts is completely independent v Uc = contact voltage depending on main
from the earthing system. the potential Uc and the potential protective
c indirect contact, protection and reference of the person exposed to conductor
prevention measures the hazard, generally the ground.
Contact of a person with c managing the electrical hazard
accidentally energised metal frames v this management is optimised by water
is known as indirect contact prevention. For example, by gas
(see fig. 3b). measuring insulation of a device before heating
This accidental energising is the result energising it, or by fault prediction
of an insulation fault. A fault current based on live monitoring of insulation
flows and creates a potential rise evolution of an unearthed installation
between the frame and the earth, thus (IT system),
causing a fault voltage to appear which v if an insulation fault occurs, measuring
is dangerous if it exceeds voltage UL. generating a dangerous fault strip
As regards this hazard, the installation voltage, it must be eliminated by
standards (IEC 364 at international automatically disconnecting the
level) have given official status to three part of the installation where this earthing
earthing systems and defined the fault occurred. How the hazard is ditch bottom loop conductor
corresponding installation and removed then depends on the earthing fig. 4: equipotentiality in a building.
protection rules. system.

Cahier Technique Merlin Gerin n° 172 / p.6


2. earthing systems and protection
of persons

This section defines the Electric Shock however several earthing systems may in MV, the LV earthing system is
and Electrocution hazards for the be included in the same installation, expressed by an additional letter
various earthing systems, such as see figure 6 as an example. according to interconnection of
specified by the International Note 3: the various earth connections
Electrotechnical Committee in standard In France, as in standard NF C 13-100 (see fig. 7).
IEC 364. The LV earthing system concerning delivery substations, in Let us now see how to protect persons
characterises the earthing mode of the order to prevent hazards originating in each case.
secondary of the MV/LV transformer
and the means of earthing the
installation frames. 3 3
Identification of the system types is N
thus defined by means of 2 letters: N
c the first one for transformer neutral
connection (2 possibilities):
v T for «connected» to the earth, T
v I for «isolated» from the earth; T
c the second one for the type
of application frame connection 3 3
(2 possibilities):
v T for «directly connected» to the N N
earth,
N
v N for «connected to the neutral» at I
the origin of the installation, which is
connected to the earth (see fig. 5).
Combination of these two letters gives fig. 5: connection mode of the neutral at the origin of the installation and of the frames of the
three possible configurations: electrical loads.
transformer frame
neutral 3
c if T → T or N;
c if I → T; N
i.e. TT, TN and IT. PEN N N
Note 1: PE PE PE
The TN system, as in IEC 364 includes
several sub-systems:
c TN-C; if the N and PE neutral TN-C TN-S TT IT
conductors are one and the
same (PEN);
c TN-S: if the N and PE neutral fig. 6: example of the various earthing systems included in the same installation.
conductors are separate;
c TN-C-S: use of a TN-S downstream additional earthing of the earthing of the earthing of the
from a TN-C (the opposite is forbidden). letter MV/LV substation LV neutral LV application
Note that the TN-S is compulsory for R (connected) c c c
networks with conductors of a cross- N (of neutral) c c v
section i 10 mm2 Cu. S (separated) v v v
Note 2: (c = interconnected, v = separate)
Each earthing system can be applied to fig. 7: linking of LV earth connections with that of the MV/LV substation.
an entire LV electrical installation;

Cahier Technique Merlin Gerin n° 172 / p.7


TN system calculation. Certain country standards For the protection device to perform
When an insulating fault is present, the
recommend this. its function properly, Ia must be less
To guarantee this condition, another than Id, hence the expression
fault current Id is only limited by the
. approach consists in imposing a of Lmax, the maximum length
impedance of the fault loop cables
maximum impedance value on the authorised by the protection device with
(see fig. 8):
fault loops according to the type and a threshold Ia:
Uo rating of the SCPDs chosen (see
Id = . 0.8 Uo Sph
Rph1 + Rd + RPE British standard BS 7671). This Lmax =
ρ (1 + m) Ia
For a feeder and as soon as Rd ≈ 0: approach may result in increasing the
cross-section of the live and/or c Lmax: maximum length in m;
0.8 Uo
Id = . protective conductors. c Uo: phase-to-neutral voltage 230 V
Rph1 + RPE Another means of checking that the for a three-phase 400 V network;
In point of fact, when a short-circuit device will ensure protection of c ρ: resistivity to normal operating
occurs, it is accepted that the persons is to calculate the maximum temperature;
impedances upstream from the relevant length not to be exceeded by each c Ia: automatic breaking current:
feeder cause a voltage drop of feeder for a given protection v for a circuit-breaker Ia = Im (Im
around 20 % on phase-to-neutral threshold Ia. operating current of the magnetic or
voltage Uo, which is the nominal To calculate Id and Lmax, short time delay trip release),
voltage between phase and earth. three simple methods can be used v for a fuse, current such that
Id thus induces a fault voltage with (see «Cahier Technique» n° 158): total breaking time of the fuse
respect to earth: c the impedance method; (prearcing time + arcing time) complies
Ud = RPE Id c the composition method; with the standard (see fig. 9),
i.e.: c the conventional method. Sph
The latter gives the following c m = .
RPE SPE
Ud = 0.8 Uo
Rph1 + RPE . equation:
If the line is longer than Lmax, either
0.8 Uo 0.8 Uo
For 230/400 V networks, this voltage of Id = = conductor cross-section must be
around Uo/2 (if RPE = Rph) is Z Rph + RPE increased or it must be protected
dangerous since it exceeds the limit 0.8 Uo Sph using a Residual Current Device
=
safety voltage, even in dry ρ (1 + m) L (RCD).
atmospheres (UL = 50 V). The
installation or part of the installation
must then be automatically and
A Id
promptly de-energised (see fig. 9).
As the insulation fault resembles a
phase-neutral short-circuit, breaking is N
achieved by the Short-Circuit Protection D
Device (SCPD) with a maximum
PE
specified breaking time depending
on UL.
Implementation C B
To be sure that the protection device
really is activated, the current Id must Rd
be greater than the operating threshold
of the protection device Ia (Id > Ia) Ud
irrespective of where the fault occurs.
This condition must be verified at the
installation design stage by calculating
the fault currents for all the distribution
circuits. Uo 0.8 Uo
Ud ≈
0.8 Uo
if RPE = Rph and Rd = 0 Id = ⇒
If the same path is taken by the 2 RAB + Rd + RCD Rph + RPE
protective conductor - PE- and the live fig. 8: fault current and voltage in TN system.
conductors, this will simplify the

Cahier Technique Merlin Gerin n° 172 / p.8


TT system dangerous. The part of the installation increased to 5 s if Ra and Rb are
affected by the fault must therefore be interconnected).
When an insulation fault occurs, the
automatically disconnected Note that protection by RCD:
fault current Id (see fig. 10) is mainly
(see fig. 11). c does not depend on cable length;
limited by the earth resistances (if the
Implementation c authorises several separate Ra earth
earth connection of the frames and the
As the fault current beyond which a risk connections (an unsuitable measure
earth connection of the neutral are not
since the PE is no longer a unique
associated). UL
is present ( Id0 = ) is far lower potential reference for the entire
Still assuming that Rd = 0, the fault
Ra installation).
current is:
than the settings of the overcurrent «Cahier Technique» n° 114 gives a
Uo protection devices, at least one RCD detailed description of RCD technology
Id ≈
Ra + Rb must be fitted at the supply end of the and use.
This fault current induces a fault installation. In order to increase
voltage in the earth resistance of the availability of electrical power, use of IT system
applications: several RCDs ensures time and current The neutral is unearthed, i.e. not
discrimination on tripping. connected to the earth.
Uo Ra
Ud = Ra Id, or Ud = All these RCDs will have a nominal The earth connections of the frames
Ra + Rb current threshold I∆n less than Id0. are normally interconnected (just like
As earth resistances are normally low The standard stipulates that the TN and TT earthing systems).
and of the same magnitude (≈ 10 Ω), de-energising by the RCDs must occur
this voltage of the order of Uo/2 is in less than 1 s (this time may be c in normal operation (without
insulation fault), the network is earthed
by the network leakage impedance.
We remind you that natural earth
Uo (volts) breaking time breaking time
leakage impedance of a three-phase
phase/neutral voltage (seconds) UL = 50 V (seconds) UL = 25 V
1 km long cable is characterised by the
127 0.8 0.35
standard values:
230 0.4 0.2 v C = 1 µF / km,
400 0.2 0.05 v R = 1 MΩ / km,

> 400 0.1 0.02 which give (in 50 Hz):
fig. 9: breaking time in TN system (taken from IEC 364 tables 41 and 48A). v Zcf = 1 / j C ω = 3,200 Ω,
v Zrf = Rf = 1 MΩ,
therefore Zf ≈ Zcf = 3,200 Ω.
Id In order to properly set the potential of
a network in IT with respect to the
earth, we advise that you place an
N impedance (Zn ≈ 1,500 Ω) between
transformer neutral and the earth.... this
is the IT impedance-earthed system.
PE

UL maximum resistance of earth


I∆n i connection
Ra
UL 50 V 25 V
Ud 3A 16 Ω 8Ω
1A 50 Ω 25 Ω
500 mA 100 Ω 50 Ω
300 mA 166 Ω 83 Ω
Rb Ra
30 mA 1,660 Ω 833 Ω
fig. 11: upper limit of the resistance of the
Uo Ra
Id ≈ Ud = Uo frame earth connection not to be exceeded
Ra + Rb Ra + Rb according to RCD sensitivity and
fig. 10: fault current and voltage in TT system. limit voltage UL [I∆n = F (Ra)].

Cahier Technique Merlin Gerin n° 172 / p.9


c behaviour on the first fault
v unearthed neutral: If
The fault current is formed as follows
(maximum value in the case of a full 3
2
fault and neutral not distributed) 1
N
If = Ic1 + Ic2, where: N
Ic1 = j Cf ω V1 3 and PE
Ic2 = j Cf ω V2 3, where:
Id = Uo 3 Cf ω. insulation surge
If If
monitoring limiter
For 1 km of 230/400V network, the fault Cf Cf Cf Cf
device
voltage will be equal to:
Uc = Rb Id, i.e. 0.7 V if Rb = 10 Ω.
This voltage is not dangerous and the IcN Ic1 Ic2
installation can thus be kept in
Ud
operation.
If the neutral is distributed, the shift of
neutral potential with respect to the Rb
earth adds a current Icn = Uo Cf ω and If
Id = Uo 4 Cf ω (see fig. 12).
v impedance-earthed neutral:
First fault current: Ic2
V1 V2
U
Id = where
Zeq
1 1 If IcN
= + 3j Cf ω
Zeq Zn V1 3 V2 3
Ic1
The corresponding fault voltage is still
low and not dangerous; the installation
can be kept in operation. Ud ≈ Rb If
V3
Although risk-free continuity of service
is a great advantage, it is necessary:
- to know that there is a fault, fig. 12: first insulation fault current in IT system.
- to track it and eliminate it promptly,
before a second fault occurs.
To meet this need: 0,8 Uo
- the fault information is provided by an
Insulation Monitoring Device (IMD) Id
monitoring all live conductors, including 3
2
the neutral, 1
N
- locating is performed by means of N
fault trackers. PE
c behaviour on the second fault Id
When a second fault occurs and the
first fault has not yet been eliminated, RPE Rph RPE Rph
there are three possibilities:
v the fault concerns the same live
conductor: nothing happens and
operation can continue, Ud Ud
v the fault concerns two different live
conductors: if all the frames are inter-
connected, the double fault is a short- Rb
circuit (via the PE). The Electric Shock
hazard is similar to that encountered
with the TN system. The most
0.8 Uo
unfavourable conditions for the SCPDs Id ≈ Ud ≈
0.8 Uo
(smallest Id) are obtained when both 2 (RPE + Rph)
4
faults occur on feeders with the same fig. 13: 2nd insulation fault current in IT system (distributed neutral) and relevant feeders with
characteristics (cross-sections and the same cross-section and length.
lengths) (see fig. 13).

Cahier Technique Merlin Gerin n° 172 / p.10


The SCPDs have to comply with the - non-distributed neutral: Note that in view of the times specified
following relationships: by the standard, horizontal time
- if the neutral is distributed and 3 0.8 Uo Sph . discrimination can be achieved to give
Lmax =
one of the two faulty conductors is 2 ρ (1 + m) Ia priority to continuity of service on
the neutra: This is provided that the neutral is certain feeders.
0.8 Uo protected and its cross-section equal to Note: in order to protect LV unearthed
Ia i , phase cross-section... This is the main networks (IT) against voltage
2Z reason why certain country standards rises (arcing in the MV/LV
- or if the neutral is not distributed: advise against distributing the neutral. transformer, accidental contact
0.8 Uo 3 v case where all frames are not with a network of higher voltage,
Ia i . interconnected. lightning on the MV network),
2Z
For frames earthed individually or in French standard NF C 15-100
Note that if one of the two faults is groups, each circuit or group of circuits stipulates that a surge limiter must
on the neutral, the fault current and must be protected by a RCD. be installed between the neutral
fault voltage are twice as low as In point of fact, should an insulation fault point of the MV/LV transformer and the
in the TN system. This has resulted occur in groups connected to two different earth (Rb).
in standard makers authorising earth connections, the earthing system's Readers wishing to study the IT
longer SCPD operating times reaction to the insulation fault (Id, Ud) is earthing systems in greater detail
(see fig. 14). similar to that of a TT system (the fault should read «Cahier Technique»
Just as in the TN earthing system, current flows through the earth). n° 178.
protection by SCPD only applies to Protection of persons against
maximum cable lengths: indirect contacts is thus ensured So as to obtain a concise overview of
- distributed neutral: the quantities characterising the various
UL earthing systems, as regards protection
in the same manner I∆n i
1 0.8 Uo Sph Ra of persons, the main formulas are listed
Lmax = ,
2 ρ (1 + m) Ia (see table in fig. 11). in the table in figure 15.

Uo/U (volts) UL = 50 V UL = 25 V
Uo: phase/neutral voltage breaking time (seconds) breaking time (seconds)
U: phase to phase voltage neutral not distributed neutral distributed neutral not distributed neutral distributed
127/220 0.8 5 0.4 1.00
230/400 0.4 0.8 0.2 0.5
400/690 0.2 0.4 0.06 0.2
580/1 000 0.1 0.2 0.02 0.08

fig. 14: maximum breaking times specified in IT system (as in IEC 364 tables 41B and 48A).

Id Ud Lmax continuity of service


TN 0.8 Uo Sph 0.8 Uo 0.8 Uo Sph vertical discrimination
ρ (1 + m) L 1+ m ρ (1 + m) Ia
TT Uo Uo Ra no constraint vertical discrimination
Ra + Rb Ra + Rb
IT 1st fault <1A << UL no tripping
double fault 1 0.8 Uo Sph m 0.8 Uo 1 0.8 Uo Sph vertical discrimination
i i
with neutral 2 ρ (1 + m) L 2 1+ m 2 ρ (1 + m) Ia and possibility of
double fault horizontal discrimination
between phases 3 0.8 Uo Sph m 3 0.8 Uo 3 0.8 Uo Sph to the advantage of hich
i i
2 ρ (1 + m) L 2 1+ m 2 ρ (1 + m) Ia current feeders

Remember that:
c ρ = 22 10-6 Ω/mm2/m for Cu (36 for Al); c PE cross-section, normally equal to phase cross-section, can be equal
to half of phase cross-section when the latter exceeds 35 mm2.... thus
Sph increasing Ud in TN and IT.
cm = ;
SPE

fig. 15: characteristic quantities of earthing systems.

Cahier Technique Merlin Gerin n° 172 / p.11


3. earthing systems confronted with fire and
electrical power unavailability hazards

fire and/or explosion is present: as the c reference time equal to the time
PE and neutral conductors are «mains present + mains absent».
It has been proved, then accepted
one and the same, RCDs cannot be Mean Up Time (MUT) depends on the
by standard makers, that contact used.
between a conductor and a metal overall condition of network insulation.
part can cause fire to break out, in However, insulation deteriorates with
particularly vulnerable premises, electrical power time as a result of thermal aggressions
when the fault current exceeds and electrodynamic forces due in
unavailability particular to fault currents.
500 mA.
This hazard is a major one for Mean Down Time (MDT) also depends
To give an example: operators, since it results in on the fault current and in particular on
c premises particularly at risk: non-production and repair costs which its strength which, according to its
petrochemical factories, farms; can be high. value, may cause:
c premises averagely at risks, but It varies according to the earthing c damage of varying degrees to loads,
where consequences may be very system chosen. cables...;
serious: very high buildings receiving We remind you that availability (D) is a c fires;
the general public... statistical quantity (see fig. 16) equal to c malfunctionings on the low current
In the unearthed neutral system, the the ratio between two periods of time: control and monitoring equipment.
risk of «fire»: c time during which the mains is Each earthing system must therefore
c is very small on the first fault; present; be examined as regards availability of
c is as important as in TN on the
second fault.
For the TT and TN earthing systems,
the fault current is dangerous given the
power developed (P = Rd I2): MDT MUT MDT MUT MDT
c in TT = 5A < Id < 50 A;
c in TN = 1 kA < Id < 100 kA.
The power present where the fault has
occurred is considerable, particularly in
the TN system, and prompt action is
vital as from the lowest current levels in
order to limit the dissipated energy
(∫ Rd i2 dt).
This protection, specified by the IEC time
and a requirement of French standards
de-energising de-energising de-energising
(NF C 15-100, paragraph 482-2-10) is
on fault on fault on fault
provided by an instantaneous RCD with restoration restoration restoration
threshold i 500 mA, regardless of the of voltage of voltage of voltage
earthing system.
When risk of fire is especially high failure status operating status
(manufacture/storage of inflammable
materials....) it is necessary and
indeed compulsory to use an earthing
system with earthed frames which D = availability of a system MDT = Mean Down Time MUT
D =
naturally minimises this hazard MUT = Mean Up Time (detection + repair + MDT + MUT
(TT or IT). Mean failure free time resumption of operation)
Note that the TN-C is banned in fig. 16: availability of electrical power.
certain countries when a risk of fire

Cahier Technique Merlin Gerin n° 172 / p.12


electrical power, with special emphasis of certain motors before startup. earthing systems can be listed in the
on the IT earthing system since it is the Bear in mind that 20 % of motor following order of preference: IT,
only one that authorises non-tripping in failures are due to an insulation fault TT, TN.
the presence of a fault. which occurs on energising. In point
Note:
c the IT earthing system of fact, an insulation loss, even small,
If, to ensure continuity of service,
In order to retain the advantage of this on a hot motor cooling down in a
system, i.e. not interrupting electrical the installation is fitted with a
damp atmosphere (condensation)
distribution on the first fault, the second generator set or a UPS
degenerates into a full fault on
fault must be prevented, since this then (Uninterruptible Power Supply)
restarting, causing both considerable
presents the same high risks as the TN damage to windings and production in «off line», there is a risk of failure to
system. The first fault must therefore be loss and even major risks if the motor operate or of delayed operation of the
eliminated before a second fault has a safety function (drainage, fire, SCPDs (the short-circuit current is
occurs. The use of efficient detection lower) on changeover to the
fan pump motor, etc.).
and locating methods and the presence replacement source (lowest Isc -
This type of incident can be prevented,
of a reactive maintenance team see fig.17).
considerably reduces the likelihood of whatever the earthing system, by an
the «double fault». Insulation Monitoring Device In TN and IT, for safety of persons
Moreover, monitoring devices are monitoring the load with power off. If a and property, it is thus vital to check
currently available which monitor in fault occurs, startup is then prevented. that the protection conditions are
time the evolution in insulation of the To round off this section on «the always met (operating time and
various feeders, perform fault prediction hazard presented by electrical power threshold), especially for very long
and thus anticipate maintenance of the unavailability» it is clear that, regarding feeders. If this is not so, then RCDs
first fault. proper electrical power availability, the must be used.
This ensures maximum availability with
the IT earthing system.
c the TN and TT earthing systems
These systems use discrimination on I rms subtranscient transcient
tripping. state state
In TN, this is acquired with short-circuit
protection devices if the installation
protection plan has been properly generator with compound
designed (current discrimination). ≈ 3 In excitation or overexcitation
In TT, it is easy to implement thanks to
the RCDs which ensure current and
time discrimination. In generator with serial
Remember that, in TN system, repair
≈ 0.3 In excitation
time according to ∫ i2 dt, may be longer
than in TT system, wich also affects
availability. occurence 10 to 0.1 to
c for all the earthing systems of fault 20 ms 0.3 s
It is always useful to anticipate fig. 17: making a short-circuit in a network supplied by a diesel standby generator.
insulation faults and in particular those

Cahier Technique Merlin Gerin n° 172 / p.13


4. influences of MV on LV, according to
the earthing systems

LV networks, unless a replacement advisable to install surge limiters transmitted to the LV network by
uninterruptible power supply (with (lightning arresters) at the origin of the capacitive and magnetic coupling.
galvanic insulation) or a LV/LV LV network, whatever earthing system Just like all differential mode
transformer is used, are influenced is used (see fig. 18). phenomena, operating overvoltages do
by MV. Likewise, to prevent coupling by not interfere, or only very slightly, with
This influence takes the form of: common impedance, it is wise never to any of the earthing systems.
c capacitive coupling: transmission of connect the following to the earth
overvoltage from MV windings to LV connection of the LV neutral:
windings; c MV lightning arresters; MV-frame disruptive
c galvanic coupling, should disruptive c lightning rods placed on the roof of breakdown of the
breakdown occur between the MV and buildings.
LV windings;
transformer
In point of fact, the lightning current
c common impedance, if the various would cause a rise in potential of the On MV-frame disruptive breakdown
earth connections are connected and a PE and/or the LV neutral (risk of inside the transformer and when the
MV current flows off to earth. disruptive breakdown by return) and transformer frame and LV installation
This results in LV disturbances, often loss of earth connection effectiveness neutral are connected to the same
overvoltages, whose generating by vitrification. earth connection, a MV «zero
phenomena are MV incidents: sequence» currrent (whose strength
c lightning; depends on the MV earthing system)
c operating overvoltages; operating overvoltages can raise the frame of the transformer
c MV-frame disruptive breakdown Some MV switchgear (e.g. vacuum and neutral of the LV installation to a
inside the transformer; circuit-breakers) cause considerable dangerous potential.
c MV-LV disruptive breakdown inside overvoltages when operated In point of fact, the value of the
the transformer. (see «Cahier Technique» n° 143). transformer earth connection directly
Their most common consequence is Unlike lightning which is a common conditions the contact voltage in the
destruction of LV insulators with the mode disturbance (between network substation Ut i Rp IhMV and the
resulting risks of Electric Shock of and earth), these overvoltages are, dielectric withstand voltage of
persons and destruction of equipment. in LV, differential mode disturbances the LV equipment in the substation
(between live conductors) and are Utp = Rp IhMV (if the LV neutral earth is
lighning
If the MV network is an overhead one,
the distributor installs ZnO lightning i 125 kV i 10 kV
arresters to limit the effects of a direct
or an indirect lightning stroke. 3
Placed on the last pylon before
the MV/LV substation, these lightning N
arresters limit overvoltage and cause
lightning current to flow off to earth short
(see «Cahiers Techniques» n° 151 connections
and 168). 3
A lightning wave, however, is 3
transmitted by capacitive effect
between the transformer windings, to
the LV live conductors and can reach
10 kV peak. Although it is progressively fig. 18: limitation and transmission of lighting overvoltages (whether or not the neutral is
weakened by the stray capacities of the earthed, there are common mode overvoltages on phases).
network with respect to earth, it is

Cahier Technique Merlin Gerin n° 172 / p.14


separate from the substation one). The c in TT or RB: there is a risk of disruptive
earth connections of the substation and Whereas the load frames are at the breakdown «by return» of loads
of the LV neutral are not generally potential of the deep earth, the entire if the voltage developed in RPB or RB
connected. If however they are, a limit LV network is subjected to IhMV RPB exceeds their dielectric withstand.
is given to the common earth
connection value to prevent a rise in
potential of the LV network compared
diagrams (1) maximum resistance of the earth
with the deep earth. Figure 19 gives the
connection of substation frames Rp (Ω)
common earth connection values for
the IhMV values of French public no value stipulated but the following values
networks. Readers interested in this prevent potential rise of the assembly
can consult standard IEC 364-4-442
which explains the risks according to IhMV (A) RPAB (Ω)
LV earthing systems.
300 3 to 20
Still for public networks (except for
Australia and the USA where the fault 1,000 1 to 10
Z
current can be very high), values
encountered range from 10 A in Ireland
(an impedance compensates the
capacitive current) to 1,000 A in France TNR or ITR RPAB
(underground networks) and in
Great Britain. IhMV (A) RPB (Ω)
MV industrial networks are normally run 300 3
in impedance-earthed IT and have a
1,000 1
zero sequence current IhMV of a few
dozens of amps (see «Cahier
Technique» n° 62).
Z
The maximum value authorised for the
earth connection depends on the
equipotentiality conditions of the frames
of the LV network, i.e. on its earthing
TTN or ITN RPB RA
system.

Utp (kV) 2 4 10
MV-LV disruptive IhMV (A) RP (Ω)
breakdown inside 300 4 8 20
1,000 1 3 10
the transformer
To prevent potential with respect to Z
the earth of the LV network from
rising to the phase-to-neutral voltage of
the MV network on MV-LV disruptive
breakdown inside the transformer, the RP RB TTS or ITS RA
LV network must be earthed.
The consequences of this fault are:
Z: direct earthing in TN and TT
c in TN impedance-earthed or unearthed in IT with presence of a discharger.
The entire LV network, including the IhMV: maximum strength of the first earth single-phase fault current of the high voltage network
PE, is subjected to voltage IhMV RPAB supplying the substation.
or RAB. Utp: power frequency withstand voltage of the low voltage equipment of the substation.
If this overvoltage exceeds the (1) the third letter of the earthing systems means:
dielectric withstand of the LV network c all the frames are linked R;
(in practice of the order of 1,500 V), c the substation frame is connected to the Neutral frame: N;
LV disruptive breakdowns are possible c the earth connections are Separated S.
if the equipotentiality of all the frames, fig. 19: maximum resistance of the earth connection of the substation frames according to
electrical or not, of the building is not network earthing system.
complete.

Cahier Technique Merlin Gerin n° 172 / p.15


c in IT consult IEC 364 which explains risks This section has described the
Operation of a discharger/short-circuiter according to the earthing systems. influence of the MV network. Its
(known as a surge limiter in France), The example of overhead public conclusions are:
which short-circuits itself as soon as its distribution in France provides a c the value of using lightning arresters at
arcing voltage is reached, then brings solution to a situation where risks of the origin of the LV installation, whatever
the problem to the level of the TN lightning, operating overvoltage and the earthing system type, if the MV and
network one (or TT if there are several transformer frame-MV and particularly the LV supply is overhead;
application earth connections). MV-LV disruptive breakdown are c connection of the earth connection
In all cases, MV/LV disruptive present (see fig. 20). It shows that of the substation with the earth
breakdowns give rise to constraints equipotentiality of the entire connection of the LV neutral or with
which can be severe, both for the distribution (all MV frames, neutrals those of the application frames,
LV installation and loads, if the value of and application frames connected) is imposes variable constraints on
the LV neutral earth connection is not not vital: each risk is dealt with the LV network according to
controlled. Interested readers can separately. the MV earthing system (value of Ih).

Ih i 300 A 3

N
metering

lightning
arrester
u 30 m RCD

u8m u8m
PE
earth trip

Rp < 50 Ω RB < 4 Ω RA < 100 Ω


fig. 20: rural overhead public distribution in France.

Cahier Technique Merlin Gerin n° 172 / p.16


5. switchgear linked to choice of
earthing system

Choice of earthing system affects not 0.8 Uo persons against indirect contacts.
only dependability (in the largest I∆n < RCDs (see fig. 23) need to be used,
Rph + RPE associated with circuit-breakers or
sense) but also installation, in particular
with respect to the switchgear to be Use of a RCD has the advantage of switches (see IEC 364 - paragraph
implemented. making loop impedance checking 413.1.4.2).
unnecessary, a fact which is of These devices must meet the following
particular value when the installation is standards in particular:
TN system modified or extended. c IEC 755: general rules;
In this system the SCPDs (circuit- This solution is clearly not applicable c IEC 1008: «household» residual
breaker or fuses) generally provide with a TN-C type earthing system (the current switches;
protection against insulation faults, with protective conductor being the same as c IEC 1009: «household» residual
automatic tripping according to a the neutral one). current SCPDs;
specified maximum breaking time c with fuses c IEC 947-2: «industrial» residual
(depending on phase-to-neutral voltage The fuses used for short-circuit current circuit-breakers.
Uo: see fig. 9). protection are of the gG type and their Their implementation must meet the
c with circuit-breaker time/current characteristics (see fig. 22) objectives for:
As soon as the fault current exceeds are defined by standards (household c protection of persons, i.e.:
the threshold of the short-circuit fuses: IEC 241, industrial fuses: v threshold I∆n i UL/RA,
protection trip release (generally IEC 269). Checking suitability with the v breaking time i 1s;
«instantaneous»), opening occurs in a maximum specified breaking time c continuity of service with thresholds
time far shorter than specified therefore calls for individual validation and time delays enabling current and
maximum breaking time, for example of the ratings provided for each time discrimination;
5 s for distribution circuits and 0.4 s for protection device. If they are not c fire protection with I∆n i 500 mA.
terminal circuits (see fig. 21). suitable, either fault loop impedance
must be reduced (increased cross-
When impedance of the source and
sections) or the fuse must be replaced
cables is high, either low threshold trip
by a low threshold or a residual current
releases must be used or RCDs
circuit-breaker.
associated with the SCPDs. These
RCDs may be separate residual current
devices or be combined with TT system
circuit-breakers (residual current With this system, the small value of the
circuit-breakers) of low sensitivity. Their fault currents (see previous section)
threshold must be: does not allow the SCPDs to protect

trip release type operating threshold


household B 3 In i Ia i 5 In fig. 23: Vigi module of a Compact NS.
(EN 60898) C 5 In i Ia i 10 In
D 10 In i Ia i 20 In
industrial G (low threshold) 2 In i Ia i 5 In
(IEC 947-2) D 5 In i Ia i 10 In
MA (for motor starter) 6.3 In i Ia i 12.5 In output
fig. 21: tripping current (magnetic or short time delay) of LV circuit-breakers.
time delay

In gG (A) Imin. 10 s Imax. 5 s Imin. 0.1 s Imax. 0.1 s threshold


63 160 320 450 820
80 215 425 610 110
shaping
100 290 580 820 1,450
ΣI≠0
fig. 22: example of fuse operating threshold limits (as in IEC 269 paragraph 5-6-3). fig. 24: fonctional diagram of a RCD.

Cahier Technique Merlin Gerin n° 172 / p.17


IT system In France, the IMDs and GFLDs have v then locating of this fault (GFLD) to
to comply with manufacturing standard put it right (curative maintenance)
Remember that in the event of a double
UTE 63080. (see fig. 27),
fault, safety of persons is provided by v and knowledge of insulation evolution
the SCPDs. When the first insulation The purpose of the IMDs is thus to
in time, feeder by feeder, to take
fault occurs, the calculation proved monitor the value of this resistance.
action on feeders with abnormal insula-
there was no risk (contact voltage They normally work by injecting an AC
tion drops (predictive maintenance);
lower than limit safety voltage). or DC current between the network and
the earth and by measuring the value of c surge limiters: these are connected
Automatic de-energising is therefore between a live conductor (neutral or
not compulsory: this is the main this current (see fig. 25).
phase) of the installation and the earth.
advantage of this system. Injection of a DC current ensures Their arcing voltage Ue must therefore
To retain this advantage, standards continuous knowledge of network be adapted to the assembly planned:
recommend (IEC 364 - paragraph insulation resistance. If this resistance thus there are two models for a 50 Hz
413.1.5.4) or stipulate (NF C 15-100) drops below a pre-set threshold, then 230/400 V network:
the use of an Insulation Monitoring the IMD reports the fault. v 250 V for connection to the neutral
Device (IMD) and locating of the first Injection of low frequency AC current (400 V < Ue i 750 V),
fault. In point of fact, if a second fault (F ≈ a few hertz) monitors fault v 400 V, for connection to a phase
occurs, automatic breaking is vital due resistance but with a distorsion due to (700 V < Ue i 1,100 V).
to the Electric Shock risk: this is then the presence of network leakage Their purpose is twofold:
the role of the SCPDs backed up by the capacitites. This minor drawback v limit voltage on the LV network on
RCDs if required. compared with injection frequency, is MV/LV disruptive breakdown in the
made up for by an advantage in first distribution transformer. In this case,
Locating the first fault for repairs the limiter must flow off to earth the
(curative maintenance) is considerably fault locating (one single injection
«residual» current of the MV network,
simplified by the use of a Ground Fault device).
v limit lightning overvoltages.
Location Device (GFLD). LF current injection devices are now This accounts for their characteristics,
Predictive maintenance, based on the available which can separately give the for example for the 250 V model:
monitoring (recording) of variations in network’s insulation resistance and - rate voltage: 250 V,
insulation impedance of each circuit, is reactance. Moreover, they enable
also possible. locating of the first fault without circuit
LV networks, using the IT system, opening and without the problems due
which take their origin at a MV/LV to highly capacitive feeders.
transformer, must be protected against c operating principle of the GFLDs N insulation measuring
risks of insulation faults between MV The most common solution is to current (Rd)
and LV by a «surge limiter». inject an identifiable current (with a
impedance
Finally, to fix the potential of the LV frequency other than network one).
Z (≈100 kΩ at 50 Hz ;
network with respect to the earth The generator can be the IMD. Then, low in LF)
(short network supplied by a MV/LV by means of magnetic Current Sensors
transformer) and avoid the risk of (toroid transformers and/or clamp-on threshold → time delay
ferromagnetic resonance, an probe) associated with an amplifier → alarm
impedance can be installed between tuned to the injected current frequency,
the transformer neutral and the earth. to trace its path up to the fault
measuring
Its value in 50 Hz, of the order of (see fig. 26).
1,500 Ω, is very high in DC and in very Finally, another solution is also used,
low frequency so as not to obstruct which consists in comparing, constantly LF current
insulation measurement and fault a generator
and for each feeder, the value of its
locating. resistance with a pre-defined or
c operating principle of the IMDs PE
programmable threshold value.
A fault on a circuit results in a drop in This solution, computerised, enables
insulation, or more precisely in the following actions, both locally and fig. 25: functional diagram of an Insulation
resistance of the network compared remotely: Monitoring Device (IMD).
with earth. v reporting of the first fault (IMD),

Cahier Technique Merlin Gerin n° 172 / p.18


- disruptive breakdown voltage at earth connection must be provided for which earthing system. Note that TT
50 Hz: min 400 V, max 750 V, each zone/consumer. and TN can use the same devices (with
- disruptive breakdown voltage Figure 28, page 20, shows which types an additional residual current module
according to the 1.2/50 µ wave: of circuit-breaker should be used for in TT).
û < 1,570 V,
- î lightning: 20 times 2,500 A (8/20 ms
wave): without short-circuiting,
- î 50 Hz: 20,000 A / 0.2s,
5,000 A / 5 s,
1,200 A / 2 mn.
This î 50 Hz: peak current withstand is far
greater than the value of the «residual»
current of the MV network since a
limiter which has been «arced» during a
very high overvoltage may continue to
be short-circuited and must therefore a LF generator
be still able to withstand a LV
short-circuit current resulting from a first PE
insulation fault in the protected
LV network. PE
The limiters marketed under the
Merlin Gerin brand can withstand
40 kA/0.2 s.
fig. 26: locating insulation faults by tracing the path of a low frequency current injected at the
neutral protection origin of the installation.
according to the earthing
system
The neutral must be broken by a multi-
pole device:
c in TT and TN, if neutral cross-section
is less than phase cross-section;
c in terminal distribution in view of the
Neutral/Phase reversal risk.
The neutral must be protected and
broken:
a
c in IT for intervention of the protection
device on the double fault, with PE
one of the faults possibly on the neutral;
c in TT and TN-S if neutral cross-section PE
is less than phase cross-section;
c for all earthing systems if the
installation generates harmonic
currents of rank 3 and multiples
(especially if neutral cross-section is "locating voltage" bus
reduced).
In TN-C the neutral, which is also The locating current flowing in the conductors is detected by Current Sensor s (CS). Each load
the PE, cannot be broken which is comprising a discriminating amplifier (set to the frequency and phase of the locating current)
dangerous as a result of its potential calculates the resistance and capacity of the circuit (with the voltage and phase whose
variations, due to load currents and reference it obtains via a bus) and indicates the presence of the fault.
insulation fault currents. To prevent fig. 27: operating principle of an GFLD with LF impedance measurement.
risks, a local equipotentiality and an

Cahier Technique Merlin Gerin n° 172 / p.19


circuits diagrams
TN-C TN-S TT IT
single phase circuits
single phase circuits with one protected pole no yes yes no
two-pole
I> circuit-breaker
N (1 protected pole,
2 de-energized poles)
phase to neutral circuits with two protected poles no yes yes yes
two-pole
I> circuit-breaker
N I> (with 2 protected poles)

three-phase circuits without neutral


with two-pole protection yes yes yes yes
1 I>
three-pole
2 I> circuit-breaker
3 I>
three-phase circuits with neutral
without overcurrent detection on neutral no yes yes no
1 I>
four-pole
2 I> circuit-breaker
3 I> with three
protected poles
N

yes yes yes no


1 I>
2 I> three-pole
3 I> circuit-breaker

N
with overcurrent detection on neutral no yes yes yes
1 I>
four-pole
2 I> circuit-breaker
3 I> with four
protected poles
N I>

fig. 28: examples of circuit-breakers according to earthing systems

Cahier Technique Merlin Gerin n° 172 / p.20


6. choice of earthing system and conclusion

The three earthing systems v whether or not there is a v loads with low natural insulation
internationally used and standardised maintenance service, (furnaces) or with large HF
by IEC 364 have as their common v fire hazard. filter (large computers):
objective the quest for optimum Generally: prefer the TN-S,
dependability. v continuity of service and v supply of control and monitoring
As regards protection of persons, the maintenance service: the IT will be systems: perfer the IT (continuity of
3 systems are equivalent if all installa- chosen, service) or the TT (enhanced
tion and operating rules are complied v continuity of service and no equipotentiality of communicating
with. In view of the characteristics maintenance service: no fully devices).
specific to each system, no one system satisfactory solution: prefer the TT
can be preferred over another. whose discrimination on tripping is
Rather, choice of earthing system must easier to implement and which conclusion
result from a concertation between the minimises damage with respect to As there is no ideal choice with a single
network user and designer (engineering the TN, earthing system, it is thus advisable, in
firm, contractor, etc.) on: The installation of additionnal output is many cases, to implement several
c installation characteristics; easily achieved without the necessity of earthing systems in the same
further calculations. installation.
c operating conditions and
v continuity of service not essential and
requirements. As a rule, a radial network installation,
compent maintenance service: prefer
with a clear distinction between priority
the TN-S (rapid repairs and extensions
and non-priority circuits and using
methods for choosing the performed according to rules),
v continuity of service not essential standby sources or uninterruptible
earthing system and no maintenance service: prefer power supplies, is preferable to an
c firstly do not forget that the three the TT, arborescent monolithic installation.
earthing systems can all be included v fire hazard: IT if maintenance service The purpose of this «Cahier
in the same electrical installation: this and use of 0.5 A RCD or TT. Technique» was to perfect your
guarantees the best possible answer to c allow for the special features of knowledge of earthing systems;
safety and availability needs; network and loads: we hope it will enable you to
c then check that the choice is not v very long network or, even more optimise the dependability of your
specified or stipulated by standards important, leakage current: prefer the installations.
or legislation (decrees, ministerial TN-S, «Cahier Technique» n° 173 which
decisions); v use of replacement or standby power provides an insight into use of earthing
c then dialogue with the user to get to supplies: prefer the TT, systems worldwide and their evolution
know his requirements and resources: v loads sensitive to high fault currents will usefully complete this first
v need for continuity of service, (motors): prefer the TT or IT, document.

Cahier Technique Merlin Gerin n° 172 / p.21


7. bibliography

Standards Merlin Gerin's Cahiers Techniques Other publications


c IEC 241: Fuses for domestic and c Earthing of the neutral in a HV c Guide de l’installation electrique
similar purposes. industrial network Ed. France Impression Conseil 1991.
c IEC 269: Low voltage fuses. Cahier Technique n° 62, c Guide de l’ingénierie électrique
F. SAUTRIAU Ed. ELECTRA 1986.
c IEC 364: Electrical installation of
buildings. c Residual current devices c Electrical Review
Cahier Technique n° 114, Nov. 1991 - Oct. 1992.
c IEC 479: Effects of currents flowing
R. CALVAS
through the human body. c La protection différentielle
c Protections des personnes et Cahier Technique J3E - 02/90.
c IEC 755: General rules for residual
alimentations statiques sans coupure,
current devices
Cahier Technique n° 129,
c IEC 947-2: Low voltage switchgear - J.-N. FIORINA
2nd part: circuit-breakers.
c Les perturbations électriques en BT,
c IEC 1008: Residual current operated Cahier Technique n° 141
circuit-breakers without integral R. CALVAS
overcurrent protection for household
c Introduction to dependability design
and similar uses (RCCB's)
Cahier Technique n° 144,
c IEC 1009: Residual current operated P. BONNEFOI
circuit-breakers with integral
c EMC: Electromagnetic compatibility
overcurrent protection for household
Cahier Technique n° 149,
and similar uses (RCBO's)
F. VAILLANT
c NF C 15-100: Installations électriques
c Overvoltages and insulation
à basse tension.
coordination in MV and HV
French decree of the 14.11.88. Cahier Technique n° 151,
D. FULCHIRON
c Lightning and HV electrical
installations
Cahier Technique n° 168,
B. DE METZ NOBLAT
c Earthing systems worldwide
and evolutions
Cahier Technique n° 173,
B. LACROIX and R. CALVAS
c Connaissances et emploi du SLT
neutre isolé,
Cahier Technique n° 178,
E. TISON et I. HERITIER
(available: end of 1995)

Cahier Technique Merlin Gerin n° 172 / p.22


Cahier Technique Merlin Gerin n° 172 / p.23
Real.: Illustration Technique - Lyon
Edition: DTE - Grenoble
09-95 - 2500 - Printing: Clerc
Cahier Technique Merlin Gerin n° 172 / p.24 Printed in France

You might also like