Ground Fault Relay ( GFR ) and SEF In Is I Prim t / td Inst (A) I Prim (A) Kar Type Blocked Blocked SI SI SI SI NI Def SI SI SI LTI SI SI SI SI SI OFF Blocked DATA SETTING DIFFERENTIAL RELAY MERK GEC TYPE MBCH GARDU INDUK PADANG SIDIMPUAN No Bay No. Seri Ratio CT (A
Ground Fault Relay ( GFR ) and SEF In Is I Prim t / td Inst (A) I Prim (A) Kar Type Blocked Blocked SI SI SI SI NI Def SI SI SI LTI SI SI SI SI SI OFF Blocked DATA SETTING DIFFERENTIAL RELAY MERK GEC TYPE MBCH GARDU INDUK PADANG SIDIMPUAN No Bay No. Seri Ratio CT (A
Copyright:
Attribution Non-Commercial (BY-NC)
Available Formats
Download as XLSX, PDF, TXT or read online from Scribd
Ground Fault Relay ( GFR ) and SEF In Is I Prim t / td Inst (A) I Prim (A) Kar Type Blocked Blocked SI SI SI SI NI Def SI SI SI LTI SI SI SI SI SI OFF Blocked DATA SETTING DIFFERENTIAL RELAY MERK GEC TYPE MBCH GARDU INDUK PADANG SIDIMPUAN No Bay No. Seri Ratio CT (A
Copyright:
Attribution Non-Commercial (BY-NC)
Available Formats
Download as XLSX, PDF, TXT or read online from Scribd
PLN (Persero) PENYALURAN DAN PUSAT PENGATUR BEBAN SUMATERA UNIT PELAYANAN TRANSMISI PEMATANG SIANTAR
DATA SETTING OVER CURRENT / GROUNT FAULT RELAY & SEF
GARDU INDUK PADANG SIDIMPUAN
Kedudukan Setting NGR
Over Current Relay ( OCR ) Ground Fault Relay ( GFR ) & SEF Ratio No Lokasi Keterangan Ratio CT In Is I Prim t/td Inst I Prim In Is I Prim t/td Inst I Prim Arus R (Ω) Merk Type Kar Type Kar (A) (A) (A) (A) (sec) (A) (A) (A) (A) (A) (sec) (A) (A) (A) I. Trafo Daya 1 ( Pauwel 31,5 MVA ) 1 Sisi 150 kv GEC MCGG 52 150/1 1 0.85 127.5 0.4 Blocked - SI MCGG 52 1 0.3 45 0.6 Blocked - SI 2 Inc 20 kv GEC MCGG 62 1000/5 5 4.75 950 0.3 Blocked - SI N/A 3 SEF 20 kv GEC MCGG 22 5 0.75 45 0.35 Blocked - LTI 300/5 40 300 A : 30 s 4 PD - 1 GEC MCGG 52 400/5 5 5 400 0.2 15 1200 SI MCGG 52 5 0.5 40 0.1 1.5 120 SI 5 PD - 2 GEC MCGG 52 400/5 5 5 400 0.2 15 1200 SI MCGG 52 5 0.5 40 0.15 1.5 120 SI 6 PD - 7 MICOM P123 600/5 5 3.25 390 0.1 15 1800 SI P123 5 0.35 42 0.15 1.3 160 SI 7 Bustie GE MIF II 1000/5 5 3.75 750 0.6 Blocked - MI Disable OFF II. Trafo Daya 2 ( Energoinvest 30 MVA ) 1 Sisi 150 kv GEC MCGG 52 150/1 1 0.85 127.5 0.4 Blocked - SI MCGG 52 1 0.4 60 0.65 Blocked - SI 2 Inc 20 kv GEC MCGG 62 1000/5 5 4.75 950 0.3 Blocked - SI 3 SEF 20 kv GEC MCGG 22 5 0.75 45 0.3 Blocked - LTI 300/5 40 300 A : 30 s 4 PD - 3 GEC MCGG 52 400/5 5 5 400 0.2 15 1200 SI MCGG 52 5 0.5 40 0.15 1.5 120 SI 5 PD - 4 GEC MCGG 52 400/5 5 5 400 0.2 15 1200 SI MCGG 52 5 0.5 40 0.15 1.5 120 SI 6 PD - 5 GEC MCGG 62 500/5 5 5 500 0.1 15 1500 SI MCGG 62 5 0.25 25 0.15 1 100 SI B=C:C=N 7 PD - 6 GEC MCGG 62 500/5 5 5 500 0.1 15 1500 SI MCGG 62 5 0.25 25 0.15 1 100 SI B=C:C=N 8 Capacitor GEC MCGG 52 OFF III. Transmisi Line 150 KV 1 RTPAT 1 GEC MCGG 52 500/1 1 0.8 400 0.2 Blocked - SI MCGG 52 1 0.2 100 0.3 Blocked - SI 2 RTPAT 2 GEC MCGG 52 500/1 1 0.8 400 0.2 Blocked - SI MCGG 52 1 0.2 100 0.3 Blocked - SI 3 SBLGA 1 GEC MCGG 52 500/1 1 1 500 0.2 Blocked - SI MCGG 52 1 0.2 100 0.35 Blocked - SI 4 SBLGA 2 ABB SPAJ 140C 500/1 1 1 500 0.2 Blocked - NI SPAJ 140C 1 0.2 100 0.35 Blocked - NI 5 Bus Coupler GEC MCGG 52 1000/1 1 0.5 500 2 Blocked - Def MCGG 52 1 0.2 200 2 Blocked - Def
Padang Sidimpuan, 15 April 2011
diketahui oleh, DIPERIKSA OLEH, dibuat oleh, MANAGER ASMAN OPHAR PH. Supv. Har Relay, Meter & Scadatel
dto dto
EDYANSYAH SARIAH BANGUN PURBA AGUSRIANTO
PT. PLN (Persero) PENYALURAN DAN PUSAT PENGATUR BEBAN SUMATERA UNIT PELAYANAN TRANSMISI PEMATANG SIANTAR
DATA SETTING DIFFERENTIAL RELAY
MERK GEC TYPE MBCH GARDU INDUK PADANG SIDIMPUAN
Ratio CT (A) Setting
No Bay No. Seri Keterangan Primer Sekunder In (A) Min. Op. Current (A) Trafo Daya 1 1 517987B / 517984B / 518007B 150/1 1000/5 1 0.2 (Pauwel 31,5 MVA) Trafo Daya 2 2 518005B / 518004B / 518009B 150/1 1000/1 1 0.2 (Energoinvest 30MVA)
Pematang Siantar, 22 September 2010
diketahui oleh, DIPERIKSA OLEH, dibuat oleh, MANAGER ASMAN OPHAR PH. Supv. Har Relay, Meter & Scadatel