You are on page 1of 23

COBRATHERM

random
polypropylene tubes
and pipe fittings

Technical and practical manual which is necessary


to use COBRATHERM system in the field
of waterworks and sanitary facilities.
1. Introduction

This technical manual, which is addressed


to the professionals who are working in
hydrothermosanitary field, results from the
development strategy which has been
adopted in the last few years. TIEMME
Raccorderie firm has been investing its
capital in high technology and human
resources since it was incorporated in
Lumezzane Gnutti Group. Thanks to
these actions, the traditional range of
products was renewed, including a wider
range of articles in order to comply with
customers’ requests and meet their needs.

The TIEMME general catalogue, not only


includes traditional pipe fittings, but also
the following new products which are
already available on the market:

• Ball valves
• Brass bibcock
• Compression fittings for copper pipes
• Compression fittings for multilayer pipes
• Compression fittings for Cobra-Pex
pipes
• Compression fittings with O-Ring The TIEMME System Quality organisation To meet these needs, TIEMME firm shows
for polyethylene pipes has been amplified, achieving the ISO a series of technical and practical manuals
• Brass generic fittings 9002 certification with KIWA, the primary which are necessary to use our products
• Press fittings for multilayer pipes certification Authority in the water field in according to the system concept, also
• Copper and bronze soldering fittings Europe, in May, 1999. mentioning dimensioning methods.
• Soldering fittings As in addition to the numerous and
• Copper and bronze press fittings authoritative written articles published in Wishing You a good and profitable work
• Polypropylene pipes and fittings specialised stamp, the company’s certification and hoping that You will appreciate this
• Cross linked polyethylene and multilayer is the guarantee that the products are useful manual, we remain with our best
pipes projected, constructed and tested to in regards.
• Manifolds order to satisfy the users demands.
• Radiator valves and lockshield
The updating of certificates and other TIEMME Raccorderie S.p.a.
detail information are at the customer’s
As it can be seen, TIEMME firm made a disposal at the TIEMME Commercial The Chairman
great effort, as it not only offers single Offices.
products, but also a wide range of products
which are similar and compatible one with Moreover, after having invested its capital
the other, forming a “system”. in high technologies and human resources,
This manual, just like those which are our firm also intends to concentrate its
related to other firm products, aims at attention on communication and information
emphasising this new concept of “system”, field in order to give its commercial
also providing all information which are partners and installers all advice and
necessary to easily and correctly use technical information which are necessary
various components. to correctly use our products.

According to our firm, it is necessary to


guarantee product certification in order to
meet customer’s needs, as the customer
himself will have to issue a Conformity
Declaration with system rules, thus assuming
precise responsibility.

1
2. Generalities
As it was previously mentioned in the
introduction, these manuals aims at better
explaining how to use our product systems.
In order to reach this target, systems must be
divided into different groups and after having
divided them into the two traditional fields of
water systems and sanitary facilities and
air-conditioning units, it is necessary to
subdivide them into other groups. These
groups must be split up starting from the
system which is included in the group in
question.
For example, air conditioning units include
manifold, single-tube, radiant panel systems
and so on.

Considering COBRATHERM system-product


purposes, this manual only deals with and
analyses those systems which are compatible
with them.
It will be possible to provide useful
information which are necessary to use
various system products and guarantee
system dimensioning according to existing
specific rules. picture 1
In case of those systems whose dimensioning
is calculated following complex procedures, it
will only be possible to give general instructions,
referring the reader to the specific regulations
on the subject.
(*)
160
This manual thoroughly examines traditional
supply systems (with series-connected
sanitary facilities ) – see picture 1 and picture 2.
The sizes which are shown in the pictures at
the right side of the page are indicated in
[mm] and they refer to most common sanitary
facility installation.
These values are checked according to the
kind of sanitary facilities which are used and 160 220
building obligations.
(*) This value is suitable for outer supply tubes. picture 2
COBRATHERM tubes and pipe fittings can
be used for the construction of any supply
system of fluids which are chemically and Regression curves graphically show the As regards chemical compatibility between
physically compatible with the material and connection between these three parameters. the material and carrier fluids, see material
lowest and highest temperatures and pressure Consequently, in short, PP-R tube and pipe list which is shown in 4.4 paragraph on
values which are allowed by the system. fitting duration strictly depends on system page 4.
Concerning this, see regression curves highest working temperature and pressure
which are shown in the diagram on page 5. values. The manual includes an appendix concer-
As in the case of all plastic pipes, Tube and pipe fitting duration also depends ning all specifications which are commonly
COBRATHERM tube and pipe fitting duration on other aspects, such as for example, the and frequently used, hoping that they can be
depends on the following parameters: chemical compatibility with carrier fluid, ther- rapidly and easily consulted by technicians
mal expansions which are not well compen- and installers.
• Mechanical stress = pressure sated, etc.
• Thermal shock = temperature
• Stress duration = time

2
3. PP-R polypropylene – type 3
COBRATHERM system tubes and pipe RANDOM POLYPROPYLENE – TYPE 3 SPECIFICATIONTABLE
fittings are manufactured by using BEC 6006
random copolymer polypropylene type 3 which
SPECIFICATIONS REGULATION/TEST MEASUREMENT VALUE
is specially produced by PCD Polymere for UNIT
the construction of fluid supply systems. Fluidity index – MFI 230/2, 16 ISO 1133 / Proced. 12 g/10 min 0,25
The Table I on the right side of the page DIN 53735 / Code M g/10 min 0,25
shows all material specifications, reference
regulations and regulations which are related Density at 23 °C ISO R1183 / DIN 53479 g/cm3 0,90÷0,91
to endurance tests.
BEC 6006 random copolymer polypropylene Yield stress ISO R527 / DIN 53455 N/mm2 27
type 3 is not only manufactured according to E modulus traction ISO R527 / DIN 53457 % 900
the regulations which are shown in the table, Breaking strain ISO R527 - Velocità D % >800
but it also complies with national laws which Brinell hardness test ISO 2039 (H358/30) N/mm2 49
are in force concerning the materials which
are used for the construction of foodstuff Resilience (Charpy) at: 23 °C ISO 179/2D / DIN 53479 KJ/m2 It does not
supply pipes (further details will be provided -30 °C ISO 179/2D / norm. scale KJ/m2 40
upon demand). Resilience at : 23 °C ISO 179/1eA KJ/m2 31
The material which is used for the construction -20 °C ISO 179/1eA KJ/m2 2,2
of COBRATHERM system is also:
• Suitable for the construction of tubes and VICAT A/C° melting point ISO 306 / DIN 53460 °C 140÷150
pipe fittings which are used for drinking Dimensional stability maximum temperature ISO 75/B / DIN 53461 °C 75
water supply. Linear thermal conductivity DIN 52612 W/mK 0,22
• It is complies with DIN8078 and DIN 16887 Thermal expansion coefficient VIDE 0304 (1-4) mm/m°C 0,15
regulations concerning the lowest long-lasting Specific heat at 20 °C Adiabatic calorimetry KJ/KgK 2,0
hydrostatic force.
Dielectric constant DIN 53483 --- 2,3
Dielectric rigidity DIN 53481 KV/mm 75
Table I

4. COBRATHERMsystem
The system is characterised by plastic 4.1 Dielectric properties 4.2 Low thermal conductivity
components which are subject to polyfusion The raw material which is used for the Thermal conductivity value of these pipes,
welding. construction of COBRATHERM system has which is equal to 0,22 W/mK and heat loss per
This technology was successfully put on the a very high volume and surface resistivity. linear metre are lower than those of metal
market according to two concepts which are Thanks to this characteristic, random tubes.
necessary for most installers: guarantee polypropylene type 3 is one of the best A lower heat loss which passes through pipe
working schedule by using innovative materials electrically insulated materials. walls also determines a lower condenser water
which offer great technical and economic Consequently, supply systems which are formation in special outer thermo-hygrometric
advantages. manufactured will never be subject to electro- conditions.
TIEMME COBRATHERM system reaches erosion phenomena, unlike metal tubes which Condenser water formation is obviously due to
both goals, offering the following advantages: are subject to stray currents, battery ignition carrier fluid temperature, ambient temperature,
effect which is due to the combination of relative humidity value and the diameter of the
• High dielectric properties non-homogeneous materials such as copper tube in question.
• Low thermal conductivity and steel, etc. The experimental data which are collected
• Soundproofing properties; plastic material According to the values which are shown in thanks to a direct observation with the help of
damps sound-wave propagation. Table I, this material is also characterised by a practical tests are available upon demand.
• Non-toxicity; it can be used for foodstuff very low dielectric constant value and a reduced In any case, if COBRATHERM system is used
supply (see chemical compatibility table) pressure loss factor, becoming totally insensitive for hot or refrigerated fluid supply, it is necessary
• Very good mechanical and functional to the magnetic field action of any frequency, to follow the thermal insulation regulations
characteristics (duration, pressure, consequently COBRATHERM systems can which are in force.
temperature, expansions, never generate electro-magnetic interference,
applications, etc.) unlike metal tube systems. 4.3 Sound-proofing properties
• Lower pressure loss thanks to its smooth Nowadays, buildings are characterised by Random copolymer polypropylene type 3,
inner coating. management, check and measurement thanks to its very good mechanical and dynamic
• Very good behaviour in the presence of computerised systems, reception and data properties, is able to absorb mechanical stresses,
deposits and abrasion phenomena. transmission systems, therefore water systems such as vibrations or small water hammers which
• Lightness during transport, movement and with above-mentioned characteristics are always take place in the system, highly reducing
installation. considered as a great technological step forward. their sound diffusion along the supply system.
• It can be easily installed

3
4.4 Non-toxicity Chemical endurance of the pipe when it is not subjected to mechanical stress
Copolymer polypropylene type 3 is a
material which is insensitive to the chemical
agents which are in contact with it. Conc. T.(°C) Conc. T.(°C)
The material which is used for the construction Substance / Fluido (%) 20 60 Substance / Fluido (%) 20 60
of COBRATHERM system is stable even in
Commonly used anti-freeze - l l Margarine - l l
the presence of water or other foodstuffs.
Chromium-plating baths - l l Jam - l l
Thanks to this characteristic, it is non-toxic
Benzene 100 l l Menthol - l
and it can be used for fluid, powder or
Ethyl-benzene 100 l l Methanol 100 l l
gelatine supply in the field of food industry.
As COBRATHERM system can also be used
Sodium bicarbonate sat. sol. l l Methyl ethyl ketone 100 l l
Beer - l l Mercury 100 l l
for the construction of industrial processing Liquid bromine 100 l Diesel oil 100 l
plants, chemical compatibility of commonly Butane (gas) 100 l Naphthalene 100 l
used substances is indicated below. Butyl alcohol 100 l Potassium nitrate sat. sol. l l
Butyl acetate 100 l Sodium nitrate sat. sol. l l
Soluble cocoa - l l Copper nitrate 30 l l
Limestone - l l Nitrobenzene 100 l l
Bleach 12,5% of chlorine l l Oleum all l l
Potassium carbonate sat. sol. l l Peanut-oil - l l
Sodium carbonate sat. sol. l l Animal oil - l l
Wax - l l Camphor oil 98 l l
Cyclohexane 100 l Fuel oil - l l
Cyclohexanol 100 l l Coconut oil - l l
Potassium chlorate sat. sol. l l Almond oil - l l
l Very good resistance Sodium chlorate 25 l l Cod-liver-oil - l
l Good resistance Sodium chlorite 5 l Motor oil - l l
l Quite resistant Liquid chlorine 100 l l Corn oil - l l
l Unresisting Chlorine (dry gas) 100 l l Linseed oil - l l
Chlorine (wet gas) 100 l l Olive-oil - l l
Conc. T.(°C) Chloroform 10 l l Silicone oil - l l
Substance / Fluido (%) 20 60 Calcium chloride sat. sol. l l Turpentine oil - l l
Ethyl chloride 100 l Paraffin oil 98 l l
Vinegar - l Methyl chloride 100 l Octane - l l
Acetone 100 l l Potassium chloride sat. sol. l l Ozone <0,5 ppm l l
Acetic acid 100 l l Sodium chloride sat. sol. l l Liquid cream - l
Benzoic acid 100 l l Coke - l Paraffin 100 l l
Boric acid 100 l l Potassium chromate sat. sol. l l Petroleum 100 l l
Hydrochloric acid all l l Toothpaste - l l Perborax sat. sol. l l
Chromic acid - l l Liquid detergent - l l Potassium permanganate sat. sol. l l
Phosphoric acid sat. sol. l l Diethyl ether 100 l Potassium persulphate sat. sol. l
Formic acid - l Dimethyl-formamide 100 l Propane gas 100 l l
Photographic acid - l l Dioxan 100 l l Liquid soap 10 l l
Glycolic acid 100 l l Hexane 100 l l Mustard - l l
Lactic acid - l l Heptane 100 l l Caustic soda 100 l l
Muriatic acid 10 l l Ethyl acetate 100 l l Sodium sulphate sat. sol. l l
Nitric acid >40 l l Ethyl hexane 100 l Sodium sulphite sat. sol. l l
Oleic acid 100 l Petroleum ether 100 l l Apple juice - l l
Accumulator acid - l l Flour - l Orange juice - l l
Sulphuric acid 98 l l Phenol sat. sol. l l Lemon juice - l l
Chlorine water sat. sol. l l Sodium phosphate sat. sol. l l Fruit juice - l l
Distilled water 100 l l Formaldehyde 40 l l Tea - l l
Drinking water - l l Glycerine 100 l l Sodium thiosulphate sat. sol. l l
Sea-water - l l Liquid glycerine low l l Carbon tetrachloride 100 l l
Soda-water - l Gas oil - l l Tetrachloroethylene 100 l l
Boric acid solution sat. sol. l l Glucose - l l Thiophene 100 l l
Hydrogen peroxide 10 l l Sodium hypochlorite 5 l l Turpentine 100 l
Aqua regia - l l Potassium iodide sat. sol. l l Trichloro-ethylene 100 l l
Ethyl alcohol 100 l Iso-octane 100 l l Urea sat. sol. l l
Starch al l l Wool-fat - l l Vanilla - l l
Ammonia gas 100 l l Milk - l l Vaseline - l l
Liquid ammonia conc. l l Liquor all l Wine - l l
Aniline 100 l l Lemonades - l Xylene 100 l l

4
4.5 Mechanical characteristics
In order to determine COBRATHERM tube
Regression curve diagram
and component mechanical characteristics, it is
necessary to analyse the following parameters:
pressure, temperature, duration, thermal
expansions etc.
Thanks to the regression curves which are
shown in the diagram on the right side of the
page, it is possible to determine PP-R pipe
characteristics.
The curves resulted from accelerated tests

EQUIVALENT STRESSES [N/mm]


concerning pressure and working temperatures
which were conducted according DIN 8078
regulation in order to calculate PP-R pipe
lowest life cycle.
Regression curve diagram is commonly used
to determine PP-R pipe system life cycle,
considering pressure and working temperature
values.
It is also possible to determine system duration
and highest working pressure in the period in
question.
The various parameters are calculated thanks
to the following equation:

σ = (P/2s)•(d e - s) • f [1]

and:
σ = stands for mechanical stress indicated in
[N/mm2] which is exerted on pipe walls
because of pressure.
P = stands for the highest working pressure
indicated in [N/mm2]
d e = indicates pipe outer diameter [mm]
s = indicates pipe wall thickness [mm] HOURS
f = stands for safety factor; according to
accelerated ageing tests, the experiment
and the applications in the field of
waterworks and sanitary facilities, it is it is possible to achieve the following equation: 4.5.1. Thermal expansions
generally equal to 1,5. COBRATHERM system is characterised by a
σ = (1/2•3,4) • (20 - 3,4) • 1,5 = 3,66 thermal expansion coefficient which is higher
After having determined system life cycle, it is than that of metals and commonly used
possible to calculate the equivalent highest After having calculated mechanical stress, building materials, but system components
working pressure value thanks to the following draw a line which is parallel to abscissa axis are easily installed underground.
equation: (red broken line) which starts from [s] value This is due to supply system route deviations,
and reaches working temperature curve in thus favouring expansion absorption.
P [bar] = A•s•(σ/f)/(d e - s) [2] question (which, according to the example, is Even if all this does not happen, or
equal to 60°C). COBRATHERM tubes are under-floor,
and: The point which is determined and which is expansions can be absorbed by random
A = indicates system yearly life cycle shown on abscissa axis, indicates pipe copolymer polypropylene type 3 thanks to its
duration; according to the example, it is deformation properties which are due to its
Above-mentioned equations can be better equal to 5 x 105 hours, which correspond low elasticity coefficient.
explained thanks to the following example. with more than 50 years. In order to prove that underground installation
N° [1] formula is commonly used to determine Similarly, thanks to [2] equation, it is possible does not generally cause any problem,
supply system duration, considering pressure to determine highest working pressure value thanks to the presence of insulating sheaths,
and working temperature values. [P]. which are required for the construction of hot
Considering the following data: For example, it is possible to calculate [P] value and cold water supply system having a
• tube outer diameter – de = 20 mm of a tube with 20 x 3,4 mm diameter throughout thickness which ranges from 9 to 20 mm, it is
• tube wall thickness – s = 3, 4 mm a period of 20 years at a temperature of possible to compensate the stresses which
• highest working p.(*) – P = 10 bar = 1 N/mm2 80°C, thanks to [2] equation: are caused by thermal expansions.
• highest working temperature – T = 60 °C
• safety factor – f = 1,5 P = 20•3,4•(2,5/1,5) / (20-3,4) = 6,8 bar

5
On the contrary, in case of exposed supply LINEAR EXPANSION TABLE [mm] While positioning fixed points, it is
systems, thermal expansions cause circuit necessary to use, if possible, supply system
length twisting and bending which, besides
Length Δt [°K] course deviations to compensate thermal
being unaesthetic, can exert undesired L [m] 10 20 30 40 50 60 expansions.
stresses on some system components such 1,0 1,50 3,00 4,50 6,00 7,50 9,00 System and tap rigid pipe fittings will act as
as elbow joints, tees, curves, etc. 2,0 3,00 6,00 9,00 12,0 15,0 18,0 fixed points.
In these cases, it is necessary to use 3,0 4,50 9,00 13,5 18,0 22,5 27,0 Sliding supports will be installed between
special pipe clamps and create a supply 4,0 6,00 12,0 18,0 24,0 30,0 36,0 two fixed points according to pipe length,
system which is able to compensate 5,0 7,50 15,0 22,5 30,0 37,5 45,0 supporting pipes and favouring expansion
thermal expansions. 6,0 9,00 18,0 27,0 36,0 45,0 54,0 and shrinkage phenomena.
Type 3 copolymer polypropylene pipe 7,0 10,5 21,0 31,5 42,0 52,5 63,0 Supports will be fitted at the distance which
thermal expansion linear coefficient is equal 8,0 12,0 24,0 36,0 48,0 60,0 72,0 is shown in Table III, according to tube
to the following value:
9,0 13,5 27,0 40,5 54,0 67,5 81,0
diameter and working temperature.

α = 0,15 mm/m°C
10,0 15,0 30,0 45,0 60,0 75,0 90,0
Table II
this means that if every pipe length indicated SUPPORT DISTANCE TABLE [cm]
in linear metres is subject to a temperature Ø Temperature [°C]
rise which is equal to Dt = 1K, linear Tube 20 40 60 80
expansion value will be equal to 0,15 mm 4.5.3. Expansion joint calculation 20x3,4 80 70 65 60
and, consequently, it is very easy to calculate In order to create an expansion joint forming
system length total expansion value, which one or more curves, the minimum length 25x4,2 85 85 75 70
is the following: of the arm [Bd] to be achieved must be 32x5,4 100 90 80 70
calculated as follows: 40x6,7 110 105 100 90
ΔL = L • α • [3] 50x8,4 125 115 105 100
BD = k • √ de• ΔL [4] 63x10,5 140 130 120 110
and: and: Table III
ΔL = stands for total expansion value [mm] k = stands for material constant = 30
α = indicates linear expansion coefficient de = indicates the outer diameter of the
Δt = indicates the thermal head the tube is tube which is used
Fixed points
subject to [K] ΔL = indicates thermal expansion to be
compensated (PF)
For designer and installer’s convenience,
the Table II on the right side of the page Considering, for example, the following
shows linear expansion values related to data:
some system lengths and commonly used • ø 20 mm tube which is used

Bar or roll length (m)


thermal head values. • 10 metre long system part
• Thermal head Dt = 40 K (10 ‹ 50°C)
4.5.2. Expansion compensation
ΔL

Pipe linear expansion which is caused by calculation is solved as follows:


temperature rise and shrinkage which is Arm
due to refrigerated water supply can generate ΔL = 10 • 0,15 • 40 = 60 mm [BD]
tensions which act on some supply system
points and, above all, on pipe fittings. When BD = 30 • √ 20 • 60 = 1040 mm
expansions or shrinkage reach values
which cannot be compensated by supply Even in this case, to facilitate technician Picture 3
system development and natural form, it is and installer’s work, all calculations have
necessary to use appropriate anchoring been converted into a graphic form and
points (PF), sliding supports (PS) and thanks to the nomogram which is shown in
expansion arms (BD). picture 5, it is possible to rapidly calculate TO BE NOTICED:
The procedures and calculations which are expansion arms. Pipe length [L] which is necessary
indicated below are necessary to solve the to calculate expansion coefficient
problem of thermal shrinkage and expansion [ΔL] always corresponds with
absorption of COBRATHERM tubes. Fixed points Sliding support system parts which are measured
(PF) (PS) between two fixed supports
Arm [BD]

– see the diagrams which are


shown in picture 3 and 4.

ΔL ΔL Picture 4
Pipe length [m]

6
Nomogram which is used to calculate expansion arm 4.5.4. Fields of application
Considering above mentioned COBRATHERM
tube and pipe fitting specifications, it is
possible to determine this technological
system application fields.
According to the highest temperature and
pressure values related to a system duration
which is equal to 50 years, this system can be
used both in civil and industrial field.
Civil systems includes hot and cold water supply
systems for sanitary use, low temperature
heating plants, garden irrigation systems, air
conditioning unit condenser water drain pipes,
EXPANSION ARM LOWEST LENGTH [mm]

etc.
The applications in the industrial field include,
besides above-mentioned systems, compressed
air supply systems, purifying systems which
are used for the supply of processing fluids or
fluids which are used in food industry (after
having previously checked their chemical
compatibility with carrier fluid), farm supply
systems, etc.
COBRATHERM system, thanks to its technical
characteristics such as salt-water and vibration
resistance, its soundproofing properties,
lightness, non toxicity, etc. is used for the
construction of boat and ship technological
systems.
This manual makes a calculation example
related to commonly used water systems and
sanitary facilities.

4.6 Continuous and local pressure losses


Random polypropylene pipes type 3 are
subject to pressure losses which are lower
than those of other kinds of pipes.
Thanks to material malleability, pipes with a
SYSTEM LENGTH [m] very smooth inner coating are subject to
extrusion.
Thanks to the diagram which is shown in
picture 6 of the following page, it is possible to
TEMPERATURE VARIATION [ΔT ° C]

determine [R] unit pressure loss values which


are indicated in c.a. mm and [v] speed values
indicated in m/s, considering [Q] flow indicated
in l/s.
Consequently, considering [L] pipe length
which is indicated in metres or in equivalent
metres, it is very easy to calculate the total
pressure loss of a straight or presumably
straight system length.
The paragraph 4.6.1. shows how it is possible
to define a straight “equivalent” pipe length
every local pressure loss point.
LENGTH VARIATION ΔL [mm] The diagram which is shown in picture 6, on the
contrary, refers to water flows at a temperature
Picture 5 of 10°C; in case of different temperature
values, collected data must be updated and
multiplied by correction factor [fc] which is indi-
cated in the diagram of picture 7.

7
Considering, for example, a system which
supplies 0,25 l/s of water at 60 °C., according
COBRATHERM tube pressure loss diagram
to the diagram which is shown in picture 6, it
results that R value is equal to 80 mm of c.a.
/m, while flow speed is equal to 0,88
m/s.Before calculating system length, it is
necessary to update [R] value at a fluid
temperature of 60 °C.
Thanks to the diagram which is shown in
picture 7, it is possible to determine fc
correction factor which is equal to 0,848, FLOW [l/s]
according to the following equation:

R = 80 • 0,848 = 68 mm di c.a./m
Correction factor [fc]

PRESSURE LOSS [mm c.a./m] Picture 6

and 4.6.1.2. Equivalent metre method


ζ indicates local drag coefficient Thanks to equivalent metre method, it is
v stands for fluid speed possible to calculate local pressure losses
considering system [Le] fictitious length
Fluid temperature [°C]
Picture 7 γ ndicates fluid specific weight [Kg/m3]
g stands for gravity acceleration [m/s2] values which are shown in table IV.
[ζ] values related to any kind of pipe fitting These lengths are added to real system
are indicated in table IV, while, thanks to the development indicated in metres, thus
4.6.1. Local pressure losses nomogram which is shown in picture 8, it is achieving a total fictitious length which will be
Besides continuous pressure losses which possible to rapidly calculate [H] value used to calculate continuous pressure losses
are due to the resistance caused by the fric- according to [v] speed and [ζ] drag coefficient thanks to traditional method.
tion which is exerted along pipe walls, it is value. This calculation can be easily and rapidly
necessary to mention local pressure losses made.
which are caused by the presence of nodes, Picture 8
branches, pipe fittings, etc. Speed [m/s]
Any jet disturbance causes a local pressure 4.6.1.3. Comparison of the two methods
loss whose extent depends on the kind and Considering that the two methods are
consequence of the disturbance. equivalent, [Le] equivalent length could be
The following methods are commonly used calculated as follows:
to calculate local pressure losses: the direct
method and equivalent metre method. R = ζ • (v2/2g) = λ • (v2/2g) • (Le/D)
The direct method is based on the specific
Pressure loss [c.a. m]

calculation of each pressure gradient which thus achieving the following equation:
is due to fluid flow stoppage.
According to the equivalent metre method, Le = (ζ/λ) • D
on the contrary, each obstacle must be repla-
ced by a fictitious system length which deter- According to this relation, [Le] value
mines the same pressure loss. depends on [λ] friction coefficient, therefore
local pressure losses are not only due to
speed as it is stated by direct method.
Recent experiments seem to confirm this
4.6.1.1. Direct method theory, but even if [ζ] local drag coefficient
[H] local pressure loss can be calculated can be affected by Reynolds number, its
thanks to the following expression: variation not always corresponds with that of
[λ] friction coefficient.
H = ∑ζ • v2 • γ / 2g [5] Drag coefficient [ζ]

8
Table which is used to calculate local pressure losses 4.7. Deposits, abrasion and corrosion
COBRATHERM system components are
Equivalent metres [eq. m] resistant to the elements which are commonly
present in hydrothermosanitary facility water
and they are also characterised by a very
Kind of pipe fitting Ø 20 Ø 25 Ø 32 Ø 40 Ø 50 Ø 63
[ζ] di 13,2 di 16,6 di 21,2 di 26,6 di 33,2 di 42
smooth surface.
For this reason, it is possible to avoid all
problems which are due to tube corrosion
Coupling 0,25 0,20 0,25 0,30 0,35 0,40 0,45 and those which are due to deposit formation,
thus preventing rusty particles, limestone or
galvanic treatment chips from detaching from
90° elbow joint 2,00 0,90 1,10 1,40 1,70 2,00 2,80 pipe walls.
Thanks to random polypropylene pipe thermal
45° elbow joint 0,60 0,40 0,50 0,60 0,70 0,80 1,00 expansion coefficient, which is higher than
that of calcareous deposits, it is possible to
avoid the latter phenomenon.
Tee 1,80 0,80 1,00 1,30 1,60 2,00 2,50 Thanks to tube expansion and shrinkage,
which are higher than those of calcareous
deposits, the latter are detached from the
Reduced tee 3,60 1,60 2,00 2,50 3,20 4,00 5,00
walls and removed.
It is well-known that random polypropylene
Tee 1,30 0,60 0,80 1,00 1,20 1,40 1,80 type 3 is highly abrasion-resistant, even if
water contains suspended impurities and at
an high flow speed.
Reduced tee 2,60 1,10 1,40 1,80 2,30 2,90 3,60
4.8. Lightness
Tee 4,20 1,70 2,20 3,00 3,70 4,60 5,90
COBRATHERM system tubes and pipe
fittings, besides offering all above-mentioned
advantages, are also very light and consequently,
Reduced tee 9,00 3,60 4,60 6,20 8,00 10,0 12,6 they can be easily carried.
Thanks to this characteristic, which can
seem to be obvious and relatively important,
Tee 2,20 0,90 1,20 1,60 2,00 2,40 3,10 it is possible to avoid down times.

Reduced tee 5,00 2,00 2,60 3,50 4,40 5,50 7,00 4.9. Easy installation
Even if COBRATHERM system is manufactured
by using an high technology raw material, it
Male tee 0,80 0,40 0,50 0,60 0,70 0,90 1,20 can be achieved according to the same
installation procedures which are followed in
case of traditional steel pipes.
Reducer <2d 0,55 0,30 0,40 0,50 0,60 0,70 0,80 As it is shown in the diagram of picture 2,
bathroom hydrosanitary supply system
Reducer 3d 0,85 0,40 0,50 0,70 0,80 1,00 1,20 development is unchanged both in case
of galvanised steel tubes and random
polypropylene tubes.
Male nipples 0,40 0,30 0,40 0,50 0,60 0,70 0,80 Thanks to this characteristic, the installer is
not obliged to carry out unfamiliar operations.
Polyfusion procedure which is necessary for
Reduced Nipples M. 0,85 0,40 0,50 0,70 0,80 1,00 1,30
part connection can be easily and rapidly
followed (see Sect. 6).
Male elbow joint 2,20 0,90 1,20 1,60 2,00 2,40 3,10

Reduced elbow joint M. 3,50 1,40 1,80 2,40 3,10 3,90 4,90

Table IV

9
5. Warning and precautions
5.1. Transport and movement 5.3. Exposure to UV rays 5.5. Connection with other pipe fittings
Products must be handled with care in order Tubes and pipe fittings which are used for The connection between COBRATHERM
to avoid undesired shocks, deformations, the construction of a supply system are system female pipe fittings and other kinds of
scratches or incisions. generally located far from sun rays. male pipe fittings must take place according
Tubes and pipe fittings which are faulty as It must be reminded that COBRATHERM to the following procedures:
they are incautiously carried or those which system components must not be installed or • do not use, if possible, male pipe fittings
are subject to building damages must not be stored in places which are exposed to direct with conic thread.
used. sun light for more than 6 months (after this • use sealing material such as PTFE (Teflon‚)
During the installation of under-floor tube and period, special stabiliser no longer has its tape or paste.
pipe fittings, make sure that they are not effects). • do not use, if possible, hemp as a sealing
crushed by people, wheelbarrows etc. The exposure to sun rays also implies the material; in any case do not use a large quantity
Similarly, in case of underground components, direct exposure to UV ultraviolet rays. of it in order to avoid buckling stresses which act
make sure that sharp parts such as brick or UV ray prolonged action causes material on female pipe fittings during part welding.
concrete pieces do not damage tubes or pipe early ageing. • if male conic nipples are inevitably used,
fittings, by cutting them. Because of this ageing, product loses its besides following the above-mentioned
While sticking insulating sheath parts, starting physical and chemical properties. instructions, do not to tighten pipe fittings too
check if the kind of glue which is used much, by forcing them, without causing
contains substances which are chemically female pipe fitting deformation.
incompatible with COBRATHERM system
tubes and pipe fittings (see the table on
page 4).
During COBRATHERM tube storage before
their installation, keep them in their original
packaging in order to protect them from dirt,
such as dust, oils, fats etc.

5.2 Low temperatures


When installation takes place in cold winter
periods at temperatures which are up to 0
°C, COBRATHERM system components
must be handled with care in order not to Picture 10 Picture 12
damage them.
As random polypropylene is very rigid at 5.4. Pipe continuous bending
above-mentioned temperatures, it is necessary In case of very large radiuses, cold-bending 5.6. Contact with sharp parts
to avoid dynamic stresses such as, for exam- takes place. Tube surface must not be in contact with
ple, bar shaking, hammer blows, pipe length In these cases, it is necessary to use lowest sharp edges or other sharp parts, such as,
fall from a framework, etc. bending radiuses which are 8 times as higher for example, in case of underground pipes
In order to create a supply system at maximum than pipe outer diameter, such as, for example: (see also at 5.1).
temperatures, it is also necessary to pay • ø 20 mm tube ‹ 160 mm lowest radius Tube outer surface cutting can cause break
attention to future thermal expansions • ø 25 mm tube ‹ 200 mm lowest radius propagation phenomenon which is due to
which will take place until usual ambient • ø 32 mm tube ‹ 256 mm lowest radius cutting.
temperature is reached and to following If, on the contrary, bending radiuses are 8
expansions which are due to carrier fluid times as lower than pipe diameter, it is
temperature. necessary to heat the tube by using an hot
It is necessary to remove ice deposits from air jet which acts on the part which is subject
the systems order to prevent them from to bending.
causing breaks or cracks.
During pipe heating,
do not use direct flames.

Picture 9 Picture 11

10
6. Installation
In order to achieve a perfect installation, ∏ After pipe cutting, remove the burr of the ª In order to achieve system part welding,
besides following above-mentioned instructions two terminals to be welded by using special insert at the same time the tube and pipe
and suggestions, it is necessary to carry out boring gauges, a simple fine with fine fitting into the corresponding polyfuser
the simple and necessary operations which teeth or a blade – see picture 15. dies.
are indicated below:

∂ First fit the dies having the diameter of the


pipes which must be used on polyfuser
plate.
While fitting the dies, insert those with lower
diameter in outer connection and those with
higher diameter in inner connection – see
picture 13.
The, start polyfuser in order to pre-heat
the equipment; this phase can last from Figura 17
10 to 30 minutes according to ambient
temperature.
Polyfuser is provided with a pre-calibrated Picture 15 A perfect welding is achieved under working
thermostat according to the kind of material conditions which are indicated in Table V.
to be welded (BEC 6006) and a special
warning light switches off when correct plate π make sure that terminals to be welded are
and die working temperature is reached Heating Interval Cooling
perfectly clean ( without dust, fat, oil or Ø [mm]
(250 ÷ 260 °C). [sec.] [sec.] [min]
other substances which are usually present
in the builder’s yard); if necessary, clean
20 5 4 2
them with alcohol. 25 7 4 3
32 8 6 4
∫ by using a common pencil, draw tube fit 40 12 6 4
height on pipe fitting welding bell – see 50 18 6 4
picture 16. 63 24 8 6
Table V

ø 20 mm tubes L = 16 mm
ø 25 mm tubes L = 18 mm After above-mentioned heating time, remove
ø 32 mm tubes L = 20 mm the tube and the pipe fitting from dies and
ø 40 mm tubes L = 22 mm rapidly connect the two parts without rotating
Picture 13 ø 50 mm tubes L = 25 mm them – see picture 18.
ø 63 mm tubes L = 29 mm Insert the tube into pipe fitting bell in order to
reach fit depth which is shown in picture 16
∑ Then, cut the tube to the desired size by and determined by the action of polyfuser
using special shears, making sure that die. Parts must be perfectly connected within
pipe cutting is perpendicular to tube axis the time interval indicated in Table V; during
– see picture 14. this phase, it is still possible to correct tube
and pipe fitting alignment.
After this working phase, corrections are no
longer allowed.
The presence of an irregular bead shows
that tube and pipe fitting are not correctly
aligned.
Picture 16 The joint which is achieved must be cooled
according to the minimum time interval which
[L] height corresponds with pipe fitting is indicated in the above-mentioned table
welding bell depth and indicates welding before being subject to any kind of stress.
area length. Higher heights cause the
formation of a large bead which is located in
and outside the tube, thus narrowing fluid
passing area.

After having carried out these preliminary


operations and having started polyfuser,
weld various parts together.

Figua 14 Picture 18

11
7. System testing and washing
The joint must be slowly air-cooled – see 7.1. Pressure testing times as higher than highest working pressure
picture 19.A sudden cooling process would Supply systems are subject to a pressurisation and this value must be reached within 30
generate great inner stresses which act on test in order to check if leaks are present. minutes during the two following tests, with a
welding area. In fact, in most cases, random polypropylene 10 minute interval between the two tests.
tube and pipe fitting supply systems are laid After a further period when pressure value is
underground, “covered” with the structures reached within 30 minutes, final pressure
and hidden. value must not fall below 0,6 bar (60 KPa).
Consequently, before including these During this first check, water leaks must not
systems in building structure, they must be be present along the system.
necessarily subject to pressure testing in The main check lasts 2 hours using a pressure
order to check if leaks are present along the value which corresponds with that which was
whole system. achieved during preliminary test.
However, the rules which regulate waterworks After the check, the pressure value which is
testing standards (according to UNI 9182 – achieved must not be lower than 0,2 bar (20
Picture 19 DIN 1988 regulation), not only include this KPa) compared to initial value.
test, but also other important tests such as Finally, the last test phase is characterised
contemporary highest flow test and loudness by two system pressurisation alternating
º If the tube is accidentally perforated by a test which concern designing and dimensioning cycles at a pressure of 10 bar (100 KPa) and
nail or a drill bit, it is possible to repair it by aspect (see Section 8)and not installation 1 bar (10 KPa) with a 5 minute interval
using special dies – see picture 20. merely “mechanical” aspect. between one cycle and another.
While fitting dies on polyfuser, it is necessary Therefore, this section only deals with After all test phases, water leaks must not be
to use welding plate connection . technical regulations concerning system present along the supply system.
Repair the tube following the instructions pressurisation test, while the following section
indicated below: deals with calculation procedures.
- carefully clean and dry the tube length to According to UNI 9182 regulation – Sect. 5 – 7.2. Supply system washing
be repaired. Par. 27.2 – Clause 27.2.1.”Cold hydraulic Hot and cold water supply system for sanitary
- insert mending die and male terminal into tests”: use at man’s disposal must be subject to a
the hole to be repaired. “Tests are conducted on the whole hot and preliminary washing operation in order to
- insert at the same time [A] mending trunk cold water supply system before fitting taps remove all working and installation residues
into female mending die. and closing holes, inner courtyards, double which are potentially unhealthy.
- both tube and mending trunk must ceilings etc., while pipes are subject to a Thanks to COBRATHERM system component
simultaneously reach melting point; see more than four consecutive hour exposure to characteristics, it is only necessary to wash
heating times indicated in Table V. a pressure value which is 1,5 times as higher the system with water in order to guarantee
- insert mending trunk into the hole within than highest working pressure with at least its inner cleaning.
throughput time which is shown in Table V. 600 KPa. In fact, apart from dust or building loam,
- after welding, wait until the joint is totally Tests are passed if, after this period, the PP-R tubes are installed without using glues,
cooled, then cut tube shank. manometer shows that pressure initial value solvents or other noxious substances.
has a tolerance which is equal to 30 KPa. Tube and pipe fitting packing and product
If the hole of the tube to be repaired has a It is possible to carry out separate tests non-toxic properties guarantee fluid sliding
diameter which is higher than that of the according to different systems”. inner surface good conditions.
die or if it is a passing hole, tube can be Even if the regulation in question is related to Make sure that oils and fats do not filter
repaired by cutting it and using a normal high density PE-X pipes, it is not referred to through the system whether accidentally
coupling. PP-R systems, therefore it is necessary to whether through operator’s negligence, thus
make some considerations. compromising system cleaning.
Thanks to random polypropylene characteristics, If supply system lengths are unfinished at the
when pipes are exposed to a pressure end of the day, it is highly recommended to
value which is 1,5 times as higher than cover open terminals with a clean cloth or
highest working pressure, they are subject to other suitable waterproofing protections.
expansion.
Moreover, in case of PP-R systems, pressure
test must take place at a steady temperature
throughout test period.
Thanks to thermal expansion characteristics
of these pipes, a temperature variation of
10°C can also determine a pressure variation
which ranges between 0,3 and 0,8 bar
(30 ÷ 80 KPa).
As regards DIN 1988 regulation, pressure
testing is divided into three phases: the
pre-check, the main check and the final check.
Each phase is characterised by a specific
pressure and test duration.
Picture 20 During pre-check phase, test pressure is 1,5

12
8. Sanitary facilities
8.1. Introduction
This chapter analyses the procedures and
calculation methods which are necessary
to dimension water system and sanitary
facilities of two bathrooms and a kitchen for
domestic use.
As this manual is not specifically used to cal-
culate sanitary facility dimensioning, it is not
possible to consider every single case.
Therefore, the case in question represents
almost all kinds of sanitary facilities,
considering that bathrooms which are present
both in civil or industrial buildings and in
barracks are dimensioned following the
same procedures.
The calculation example which will be made is
related to hot and cold water supply system Picture 21
for sanitary use, considering the installation
of COBRATHERM random polypropylene
tube and its relative welding pipe fittings.
Calculation example refers to series-connected
sanitary facilities, as it is shown in Picture 21. The house which was taken as a calculation
example and which is shown in Picture 22 is
8.2. General calculation method made up of two bathrooms (a main bathroom
Contemporaneity factor was previously used and a service one with washing machine) Load unit
to dimension water systems and sanitary and a kitchen.
Kind of sani- flow cold hot
facilities.
In other terms, thanks to this method, it was
According to present standard current
meters which are installed in civil and not
tary facility [l/s] water water
possible to determine how many sanitary luxury houses, it is not allowed to use was- Sink 0,15 1,50 1,50
facilities which were connected to a certain hing machines and dishwashers at the same Washbasin 0,10 0,75 0,75
circuit or part of it could be used at the same time, therefore the case in question is not Bidet 0,10 0,75 0,75
time, thus determining the highest supply considered. WC 0,10 3,00 ---
flow during peak periods. Domestic sanitary facilities have the follo- Bathtub/Shower 0,20 1,50 1,50
This effective and tested method was replaced wing general characteristics: Washing machine 0,15 2,00
by UNI 9182 regulation which is based on Dishwasher 0,15 2,00
the concept of “load units” and system
dimensioning is calculated according to this Table VI
parameter.
Calculation examples which are shown on
the following pages are made according to
this method.

8.3. General specifications


In order to make real technical dimensioning
calculations, it is necessary to consider a
standard house which is part of a residential
complex which is made up of 86 apartments
and which is located in the outskirts of a
famous town. As it often happened in the
last few years, it will be possible to install
independent heating systems and hot water
supply systems for sanitary use.
Consequently, main cold water supply
system will be connected to single wall
boilers and bathrooms.
From wall boilers, hot water supply horizontal
system will be connected to every single
domestic sanitary facility.
Considering the kind of generator and the
small horizontal system, it is not possible
to install hot water circulation systems for
Picture 22
sanitary use.

13
8.4 Series-connected sanitary facility supply picture 23, cold water [lu] value is equal to 4,5 and, This problem can be solved in two different
system according to the values indicated in Table F.4.1.1. ways: the first method consists in evaluating
Considering the specifications which are indicated and in UNI 9182 regulation F.4.1.3. diagram, this real system part length, calculating pressure
in previous paragraph, it is possible to calculate load unit value corresponds with a contemporary losses and adding them by using coefficient
the flows which are necessary for every single highest flow value which is equal to 0,30 l/s. method [ζζ].
sanitary facility or supply point. Análogamente y con el idéntico razonamiento, The second easier procedure is based on
It is now necessary to determine contemporary para el agua caliente se conseguirá un valor “equivalent metre” method; this means that
highest flow value which is achieved by a group total de unidad de carga igual a 2,25 con, pressure losses are calculated considering a
of sanitary facilities. consecuentemente, un caudal máximo contem- system fictitious length which determines the
Considering the main bathroom which is made poráneo de 0,25 l/s. same resistance value.
up of a washbasin, bidet , WC and bathtub, it is Following the same calculation procedures, hot water This more practical and rapid method will be
possible to start dimensioning cold water supply system will reach a load unit total value which is used to make calculation examples, as it is
system which will be fed by [A] riser. equal to 2,25 and, consequently, a contemporary shown in Table IV on page 9.
If all sanitary facilities were used at the same highest flow value which is equal to 0,25 l/s. Then, it is necessary to calculate [1] system
time, contemporary highest flow value would be Now, it is possible to start dimensioning branch, considering the following values:
equal to supply point whole flow, that is to say it bathroom hot and cold water supply system.
would be equal to 0,5 l/s (see Table VI). First, it is necessary to number every single • real length: for example 2 metres
As it is not possible to consider the case in system part as indicated in picture 23, then it is • under-sink pipe fitting: 0,9 eq. metres
question, it is necessary to determine which possible to make analytic calculations by using • 2 90° curves: 1,8 eq. metres
sanitary facilities can be used or not at the calculation form which is shown on page 15.
same time. It is necessary to start calculation procedure Adding all these values, it is possible to obtain
According to the traditional method of from the sanitary fitting which is in the most a length which is equal to 4,7 eq. m.
“contemporaneity factor”, the above-mentioned unfavourable condition up to supply riser shaft, Consequently, the whole system length [1] up
sanitary facilities would reach a highest flow value thus determining separating pressure value. to [x] node is characterised by a pressure loss
which is equal to 0,29 l/s (contemporaneity As regards cold water supply system, first which is equal to:
factor is equal to 57%). consider system length which is connected to
On the contrary, UNI 9182 regulation is based the washbasin and which is indicated by n° [1]. Δp1 = 4,7 [m eq] • 0,005 [bar/m] = 0,023 [bar]
on load unit method [lu] and, considering the As this system length is connected to a single
data indicated in the table F.2.1. of the sanitary facility, it must be dimensioned according As in the case of length [1], n° [2] branch
regulation itself, according to the kind and num- to sanitary facility highest flow value, which, in pressure loss will be calculated achieving the
ber of main bathroom sanitary facilities, calcu- this case, is equal to 0,10 l/s. following results:
lation would be the following (see l.u. values According to COBRATHERM tube pressure
indicated in Table VI ): loss diagram which is indicated on the right side • sanitary facility flow: 0,10 [l/s]
of the page and considering the flow value in • branch length: 3,6 [eq. m] and:
• cold water: 3,0 lu question, it is possible to use a pipe having a • real length = 0,9 [m]
• hot water: 6,0 lu diameter of Δ 20 x 3,4 mm and, consequently, a under-bidet pipe fitting = 0,9 [eq. m]
unit pressure loss value which is equal to 0,005 2 90° curves = 1,8 [eq. m]
However, in the presence of several sanitary bar per linear metre. • COBRATHERM tube: ø 20 x 3,4 mm
facilities in the same bathroom, it is possible to Then, in order to determine [1] system length • unit pressure loss: 0,005 [bar/m]
calculate [lu] value of all sanitary facilities (see pressure loss from sanitary facility to [x] node, it
regulation F.2.2 table). is necessary to define system length and pressure consequently:
As regards bathroom sanitary facilities in losses which are due to the presence of pipe
question, whose supply diagram is indicated in fittings, curves etc. Δp2 = 3,6 [m eq] • 0,005 [bar/m] = 0,018 [bar]

Picture 23

14
[1] and [2] branches come from [x] node and, • max. contemporary flow : 0,15 [l/s] As in the case of previous [x] node, comparing
as it was previously seen, they have two • COBRATHERM tube: ø 20 x 3,4 mm. [y] node resistance values, it results that Δp4
different pressure loss values. • branch length: 3,9 [eq. m] value is lower than P(y) value, therefore the latter
In order to calculate system dimensioning real length: 2,3 [m] value will be used to make following calculations.
and above all to determine the lowest tee = 1,6 [eq. m] N° [5] system length will be connected to
pressure value which must be guaranteed • unit pressure loss: 0,009 [bar/m] three sanitary facilities, whose total load unit
when separating from [A] riser, Δp1 higher value is equal to lu = 3, consequently, flow
value will be considered. consequently: value is equal to about 0,25 l/c.
This value will be added to the residual Considering, for example, 4,0 [eq. m] n° [5]
lowest pressure value which must be Δp3 = 3,9 [m eq] • 0,009 [bar/m] = 0,035 [bar] system length and using ø 20 x 3,4 mm
achieved by water supply tube after COBRATHERM tube, [z] node lowest pressure
having neutralised continuous and local After having calculated Δp3 value and value will be equal to:
system resistance. having added it to Δp1 value, it is possible to
This pressure value is generally equal to 0,5 determine the following [y] node system P(Z) = Δp + P(y) = (4,0•0,022) + 0,56 = 0,65[bar]
5
[bar] and this means that [x] node lowest lowest working pressure:
pressure value must be equal to: N° [6] branch will be calculated according to
P(y) = Δp + Δp = 0,523 + 0,035 = 0,56 [bar] the following procedures, as in the case of
P(X) = Δp + 0,5 = 0,523 [bar]
3 1

1 previous branches:
As in the case of previous system lengths, n° • sanitary facility flow: 0,10 [l/s]
[x] node calculation procedures must be [4] branch pressure loss will be calculated • branch length: 4,2 [eq. m]
followed to calculate all other node values. achieving the following results: real length = 1,5 [m]
It is now possible to calculate n° [3] length, elbow joint = 0,9 [eq. m]
considering that system length contemporary • sanitary facility flow : 0,20 [l/s] 2 90° curves = 1,8 [eq. m]
highest flow value can be equal to the whole • branch length: 3,0 [eq. m] • COBRATHERM tube: Δ 20 x 3,4 mm
water flow which is sent to the bidet and real length = 1,2 [m] • unit pressure loss: 0,005 [bar/m]
washbasin, which is equal to 0,20 l/s. male elbow joint = 0,9 [eq. m]
According to the previous contemporaneity 1 90° curve = 0,9 [eq. m] and, consequently:
factor method, flow value would have been • COBRATHERM tube: ø 20 x 3,4 mm
equal to 0,15 l/s, which corresponds with • unit pressure loss: 0,016 [bar/m] Δp6 = 4,2 [m eq] • 0,005 [bar/m] = 0,021[bar]
75% of total value.
As the two sanitary facilities in question consequently: Adding this value to the residual supply
cannot be used at the same time, calculation lowest pressure value, it is possible to obtain
will be made considering length [3] lower Δp4 = 3,0 [m eq] • 0,016 [bar/m] = 0,048[bar] the value which is indicated in Table VII –
flow, thus obtaining the following data: column 9.

COLD WATER SUPPLY SYSTEM CALCULATION


Δp
Length [n°] of sanitary
facil. which l.u. Max. contem. Branch
length
Pipe Unit pressure
diameter loss
Δp
length
Δp total supply
length + Min. p. system
n° are conn. to
thesystem flow [l/s] [eq. m.] ø [mm] [bar/m] [bar] (*)[bar] [bar]
1 1 0,75 0,10 4,7 20 x 3,4 0,005 0,023 0,523 0,53 (x)
2 1 0,75 0,10 3,6 20 x 3,4 0,005 0,018 0,518 ---
3 2 1,50 0,15 3,9 20 x 3,4 0,009 0,035 --- 0,56 (y)
4 1 1,50 0,20 3,0 20 x 3,4 0,016 0,048 0,548 ---
5 3 3,00 0,25 4,0 20 x 3,4 0,022 0,088 --- 0,65 (z)
6 1 0,75 1,10 4,2 20 x 3,4 0,005 0,021 0,521 ---
7 4 4,50 0,30 4,0 20 x 3,4 0,031 0,124+0,025 --- 0,80
(*) – Min. P. = water supply tube residual lowest pressure value (which is generally equal to 0,5 bar) Table VII

HOT WATER SUPPLY SYSTEM CALCULATION Table VIII


Δp
Length [n°] of sanitary
facil. which l.u. Max. contem. Branch
length
Pipe Unit pressure
diameter loss
Δp
length
Δp total supply
length + Min. p. system
n° are conn. to
thesystem flow [l/s] [eq. m.] ø [mm] [bar/m] [bar] (**)[bar] [bar]
1 1 1,50 0,20 4,7 20 x 3,4 0,014 0,066 0,566 0,57 (k)
2 1 0,75 0,10 3,6 20 x 3,4 0,004 0,015 0,515 ---
3 2 1,50 0,20 3,9 20 x 3,4 0,014 0,055 --- 0,63 (w)
4 1 0,75 0,10 3,0 20 x 3,4 0,004 0,012 0,512 ---
5 3 3,00 0,25 6,5 20 x 3,4 0,019 0,123+0,018 --- 0,75(Q)
(*) Corrected values related to fc = 0,848 – see nomogram which is shown in Picture 7 on Page 8. (**) – Min. P. = water supply tube residual lowest pressure value (which is generally equal to 0,5 bar)

15
Now, it is necessary to calculate n° [7] length
until it is separated from the riser.
System length load units are achieved by all
bathroom cold water supply system sanitary
facilities in question, and, as it is shown by
UNI 9182 regulation, they are equal to 4,5 [lu]
having a flow value which is equal to 0,3 [l/s] -
see Table VII – column 3 and 4.
Calculation procedure is unchanged, but it is Boiler
necessary to consider system cut-off cock.
As the latter can be available in various
versions and models, it is not possible to
indicate its approximate resistance value in
terms of equivalent metres.
The pressure gradient which is caused by
cut-off cock will be calculated according to a Picture 24
traditional pressure loss diagram which is
provided by the manufacturer or, in the absence
of this diagram, by using its [Kv] value
according to the following formula: supply system and [B1] bathroom supply and, considering 5 [eq.m] length, Δp total
system have the same values, [Q] node must value will be equal to:
Δpv = (Q / Kv) 2
supply 4,5 load units (even in this case, in
fact, 3 sanitary facilities have the same flow). Δptot = Δp(J) + (5 • 0,01) = 0,90 [bar]
indicating “Q” value in [m3/h] and Δpv value in According to curve 1 indicated in table F.4.1.3.,
[bar]. this [lu] value has a highest contemporary flow The value which is determined whose pressure
In the case in question, cut-off cock, having which is equal to 0,3 l/s. loss is generated by the boiler and relative
for example a Kv value which is equal to 6,8 R unit drag coefficient [bar/m] is subject to fittings is the lowest pressure value which
and a 0,3 l/s contemporary highest flow, has a [fc] correction factor which corresponds must be guaranteed during separation from
the following pressure loss: with a water temperature which is equal to [A1] riser in order to guarantee correct domestic
60 °C (see Pict. 7 on page 8). sanitary facility hot water supply, considering
Δpv = (3,6 • 0,3) / 6,8) = 0,025 [bar]
2
Consequently, pipe length will have 25 x 4,2 that water supply tube has a residual pressure
mm diameter until it is separated from value which is equal to 0,5 [bar].
In conclusion, [7] pipe length total pressure kitchen washbasin, having a pressure Then, main supply system dimensioning
loss is equal to: gradient which is equal to 0,01 [bar/m], which, calculation must be made following UNI 9182
considering a 10 [eq.m] length, is equal to regulation specifications.
Δp7 = 4,0 [m eq] • 0,031 [bar/m] = 0,124 [bar] 0,10 [bar].
Adding this value to the lowest pressure value 8.5. Practical considerations
Adding above-mentioned value to cut-off cock which is necessary for [Q] node bathroom Picture 24 shows hot and cold water supply
pressure loss, it is possible to obtain the supply system, it is possible to determine the systems.
following equation: pressure value which must be guaranteed As it can be noticed, [B1] and [B2] bathrooms
until pipe length is separated from kitchen are different one from the other: [B1] bathroom
Δp7 = 0,124 [bar] • 0,025 [bar] = 0,149 [bar] washbasin. is characterised by traditional under-floor
Considering [B1] bathroom [Q] node pressure water systems, while [B2] bathroom is charac-
Indicating this value in column 8 of Table VII value, it is possible to achieve the following terised by wall water systems (as it is shown
and adding it to [z] node lowest pressure equation: in picture 21).
value, it will be possible to achieve the Wall water systems less interfere with waste
following pressure value which must be reached P(J) = P(Q) + Δp(Q-J) = 0,85 [bar] pipes using fewer connections, therefore they
while separating from [A] riser in order to are more rapidly installed.
guarantee the correct [B1] main bathroom Then, it is necessary to calculate last length From the analysis of Table VII and VIII, it
sanitary facility cold water supply system. up to the boiler in order to determine [A1] riser results that various system lengths are achieved
hot water supply system lowest pressure by using standard diameter tubes.
ΔpB1 = Δp(Z) [bar] + Δp7 [bar] = 0,80 [bar] value. Standard tubes are generally suitable for all
Adding [Q] node load units (which are equal sanitary facilities, thus standardising all
As regards hot water supply system for sanitary to 4,5) to kitchen washbasin load units components, facilitating builder’s yard organi-
use, calculation procedure is unchanged and (which are equal to 1,5), it results that final sation and speeding up pipe laying.
results related to [B1] bathroom are indicated system length up to the boiler must be The standard tube which is commonly used
in Table VIII. dimensioned by 6 [lu], thus achieving a for the construction of the whole domestic
As it can be noticed, in this case lowest contemporary highest flow value which is supply system has 20 x 3,4 mm diameter.
pressure final value is referred to [Q] node – always equal to 0,3 l/s (UNI 9182 regulation This method causes sanitary facility over-
see picture 24 – and two bathroom supply – Table F.4.1.3). dimensioning, but it guarantees successful
systems start from this point. Consequently, as in case of previous length, supply system performances; on the contrary,
tube will have 25 x 4,2 mm diameter, unit tubes having a lower diameter could have a
Considering that [B2] bathroom hot water pressure loss will be equal to 0,011 [bar/m] lower flow and be noisy.

16
9. Range and dimensions
Art. R100 - M. F welding nipple
Codice dxG E L L1 Lt Conf.
R100B2004 20 x 1/2” 29 16 15 59 10/130
R100B2005 20 x 3/4” 36,5 16 15 63 5/80
R100B2504 25 x 1/2” 36,5 19 15 63 10/120
R100B2505 25 x 3/4” 36,5 194 15 63 5/80
R100B3206 32 x 1” 45 24 17 73,2 5/50
R100B4007 40 x 1”1/4 57 23 18 81 1/30
R100B5008 50 x 1”1/2 70 27 19 81 1/20
R100B6309 63 x 2” 88 30 19 89 1/18

Art. R101 - F.F. welding coupling


Codice dxG E E1 L L1 Lt Conf.
R101B2020 20 x 20 29 29 16 16 34 10/250
R101B2520 25 x 20 36,5 36,5 19 19 41 10/150
R101B2525 25 x 25 36,5 36,5 19 19 41 10/150
R101B3220 32 x 20 45 36,5 24 19 46,5 10/100
R101B3225 32 x 25 45 36,5 24 19 46,5 5/90
R101B3232 32 x 32 45 45 24 24 52 5/70
R101B4040 40 x 40 56,5 56,5 22 22 50 1/55
R101B5050 50 x 50 70 70 27 27 60 1/30
R101B6363 63 x 63 88 88 29 29 64 1/20

Art. R102 - F. F welding nipple


Codice dxG E L Lt Conf.
R102B2004 20 x 1/2” 29 16 44 5/140
R102B2005 20 x 3/4” 36,5 16 48 5/100
R102B2504 25 x 1/2” 36,5 19 48 5/100
R102B2505 25 x 3/4” 36,5 19 48 5/100
R102B3205 32 x 3/4” 45 24 56,5 5/60
R102B3206 32 x 1” 45 24 56,5 5/60
R102B4007 40 x 1”1/4 56 23 63 1/35
R102B5008 50 x 1”1/2 70 27 63 1/20
R102B6309 63 x 2” 88 30 70 1/20

Art. R103 - F.F. welding curve


Codice d x d1 E L Z Conf.
R103B2020 20 x 20 29 16 28 10/180
R103B2525 25 x 25 36,5 19 33 5/90
R103B3232 32 x 32 45 24 42 5/50
R103B4040 40 x 40 56 22 44 1/25
R103B5050 50 x 50 70 27 53 1/15
R103B6363 63 x 63 88 28,5 61,5 1/8

17
Art. R104 - M. threaded F welding curve
Codice dxG E L L1 Z Z1 Conf.
R104B2004 20 x 1/2” 29 16 15 28 57 5/100
R104B2504 25 x 1/2” 36,5 19 15 33 59 5/60
R104B2505 25 x 3/4” 36,5 19 15 33 59 5/60
R104B3205 32 x 3/4” 45 24 15 42 67 5/35
R104B3206 32 x 1” 45 24 17 42 69 5/35

Art. R105 - F. threaded F welding curve


Codice dxG E L Z Z1 Conf.
R105B2004 20 x 1/2” 29 16 28 41 5/100
R105B2504 25 x 1/2” 36,5 19 33 44 5/70
R105B2505 25 x 3/4” 36,5 19 33 44 5/70
R105B3205 32 x 3/4” 45 24 42 52 5/40
R105B3206 32 x 1” 45 24 42 52 5/40

Art. R106 - F. threaded F welding curve with 2 hole supporting flange


Codice dxG A E L Z Z1 Conf.
R106B2004 20 x 1/2” 50 29 16 28 41 5/60
R106B2504 25 x 1/2” 50 36,5 19 33 41 5/60

Art. R107 - Tee with F. welding connections


Codice d x d1 x d E E1 L L1 Z Z1 Conf.
R107B202020 20 x 20 x 20 29 29 16 16 28 28 5/120
R107B252525 25 x 25 x 25 36,5 36,5 19 19 33 33 5/70
R107B323232 32 x 32 x 32 45 45 24 24 42 42 5/40
R107B404040 40 x 40 x 40 56 56 22 22 44 44 1/20
R107B505050 50 x 50 x 50 70 70 27 27 53 53 1/15
R107B636363 63 x 63 x 63 88 88 28,5 28,5 61,5 61,5 1/8
R107B252025 25 x 20 x 25 36,5 36,5 19 16 33 33 5/70
R107B322032 32 x 20 x 32 45 36,5 24 16 42 37 5/50
R107B322532 32 x 25 x 32 45 36,5 24 19 42 37 5/40
R107B402040 40 x 20 x 40 56 36,5 22 16 44 41 1/25
R107B402540 40 x 25 x 40 56 36,5 22 19 44 41 1/25
R107B403240 40 x 32 x 40 56,5 45 22 21 44 41 1/25
R107B503250 50 x 32 x 50 70 45 26 21 53 50 1/15
R107B504050 50 x 40 x 50 70 56 26 22 53 50 1/15
R107B633263 63 x 32 x 63 88 45 29 21 62 67 1/9
R107B634063 63 x 40 x 63 88 56 29 22 62 60 1/9
R107B635063 63 x 50 x 63 88 70 29 27 62 60 1/9

18
Art. R108 - M. threaded F. welding tee
Codice d x d1 x d E L L1 Z Z1 Conf.
R108B200420 20 x 1/2” x 20 29 16 15 28 56 5/80
R108B250425 25 x 1/2” x 25 36,5 19 15 33 59 5/50
R108B250525 25 x 3/4” x 25 36,5 19 15 33 59 5/50
R108B320532 32 x 3/4” x 32 45 24 15 42 67 5/30
R108B320632 32 x 1” x 32 45 24 17 42 69 5/30

Art. R109 - F. threaded F. welding tee


Codice dxGxd E L L1 Z Z1 Conf.
R109B200420 20 x 1/2” x 20 29 16 28 41 5/100
R109B250425 25 x 1/2” x 25 36,5 19 33 44 5/60
R109B250525 25 x 3/4” x 25 36,5 19 33 44 5/60
R109B320532 32 x 3/4” x 32 45 24 42 52 5/35
R109B320632 32 x 1” x 32 45 24 42 52 5/35

Art. R111 - M.F. welding curve


Codice d x d1 E L Z Z1 Conf.
R111B2020 20 x 20 29 16 28 35 5/180
R111B2525 25 x 25 36,5 19 33 41 5/100
R111B3232 32 x 32 45 21 38 47 5/50

Art. R112 - F.F. 45° welding curve


Codice d x d1 E L Z Conf.
R112B2020 20 x 20 29 16 22 10/200
R112B2525 25 x 25 36,5 19 26 10/120
R112B3232 32 x 32 45 24 33 5/60
R112B4040 40 x 40 56 22 31,5 1/40
R112B5050 50 x 50 70 26 40 1/20
R112B6363 63 x 63 88 29 44 1/10

Art. R113 - By-pass curve with M. welding terminals


Codice d L Z Conf.
R113B2020 Ø 20 150 35 1/100
R113B2520 Ø 25 180 37 1/60
R113B3232 Ø 32 200 42 1/40

Art. R114 - Inset cut-off cock with F.F. welding connections


Codice d x d1 E L Z Z1 Conf.
R114B2020 20 x 20 36,5 16 46 80 1/20
R114B2525 25 x 25 36,5 19 46 80 1/20

19
Art. R115 - M.F. welding reducer
Codice d x d1 E L L1 Lt Conf.
R115B2520 25 x 20 29 16 17 34 10/250
R115B3220 32 x 20 36,5 16 20 41 10/150
R115B3225 32 x 25 36,5 19 20 41 10/150
R115B4020 40 x 20 29 16 25 42 1/160
R115B4025 40 x 25 36,5 19 25 43 1/140
R115B4032 40 x 32 45 19 22 47 1/120
R115B5025 50 x 25 36,5 19 30 50 1/80
R115B5032 50 x 32 45 20 30 52 1/70
R115B5040 50 x 40 52 23 28 52 1/60
R115B6332 63 x 32 45 20 30 55 1/45
R115B6340 63 x 40 56 22 30 55 1/40
R115B6350 63 x 50 70 25,5 30 60 1/30

Art. R117 - Straight pipe fitting with flat seat pipe union
Codice dxG E L Lt Ch Conf.
R117B2005 20 x 3/4” 29 16 58 30 5/120
R117B2506 25 x 1” 36,5 19 64 37 5/80
R117B3207 32 x 1”1/4 45 24 75,5 47 1/40

Art. R118 - Elbow joint with flat seat pipe union


Codice dxG E L Z Z1 Ch Conf.
R118B2005 20 x 3/4” 29 16 28 55 30 5/100
R118B2506 25 x 1” 36,5 19 33 60 37 5/50
R118B3207 32 x 1”1/4 45 24 42 71 47 1/30

Art. R135 - Welding female cap


Codice d E L Lt Conf.
R135B20 20 29 16 22 10/350
R135B25 25 36,5 19 27 10/260
R135B32 32 45 24 33 10/130
R135B40 40 56 22 37 1/90
R135B50 50 70 28 45 1/40
R135B63 63 88 30 45 1/30

Art. R400 - PP-R random polypropylene tubes which are available in bars
Codice d Sp L Conf.
R400B20 20 3,4 4 mt 100 mt
R400B25 25 4,2 4 mt 100 mt
R400B32 32 5,4 4 mt 10/160
R400B40 40 6,7 4 mt 60 mt
R400B50 50 8,4 4 mt 20 mt
R400B63 63 10,5 4 mt 16 mt

20
Castegnato, September 23 1998

CONFORMITY DECLARATION
TIEMME RACCORDERIE S.p.A. firm, which has its head office in Via Cavallera 6/A – 25045
– Castegnato (Bs), and manufactures hydrothermosanitary system parts, according to the
regulations which are in force and in particular:

• 46/90 Law – Art. 7 – “System safety rules”


• P.D. n° 477 of December 6 1991 – Art. 5 – “46/90 Law enforcement regulations”

DECLARES
• that COBRATHERM tubes and pipe fittings are manufactured by using random copolymer
Polypropylene of type 3 – BEC 6006 – according to national laws which are in force concerning
the materials which are used for the construction of pipes which convey foodstuffs.

• that PP-R material which is used is suitable for the construction of drinking water supply
tubes and pipe fittings, according to ONORM B5014 regulation.

• that PP-R material which is used complies with DIN 8078 – ONORM B5174 and
BGA KTW regulations.

• that, according to DIBT, PP-R material which is used is a suitable raw material.

• that COBRATHERM tubes are dimensioned according to DIN 8077 regulation.

• that quality control tests are conducted according to the following product regulations which
are in force:
- ISO (1133 – R1183 – R527 – 2039 – 179/2D – 179/1eA – 306 – 75/B)
- DIN (53735 – 53479 – 53455 – 53457 – 53479 – 53460 – 53461 – 52612 – 53483 – 53481)
- VDE 0304 (1-4)

TIEMME S.p.A.
Technical Manager

21
E mail: info@tiemme.com
Tel. ++39 030 2142211 r.a. - Telefax ++39 030 2142206
Via Cavallera 6/A (Loc.Barco) - 25045 Castegnato (BS) - Italy
E’ vietata la riproduzione totale o parziale del presente catalogo, senza preventiva autorizzazione scritta. 9999C0003GB
I dati tecnici e descrittivi potranno essere variati senza alcun obbligo di avviso preventivo - Release 1/98

You might also like