You are on page 1of 2

SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - August 2004)

SAIC NUMBER DATE APPROVED QR NUMBER


SAUDI ARAMCO INSPECTION CHECKLIST
Structural Steel - Foundation or Connection Point Inspection SAIC-M-1024 18-May-05 CIVIL-
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.

LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.

SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?

SAUDI ARAMCO INSPECTION LEVEL CONTRACTOR INSPECTION LEVEL

ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.

Before erecting steel, the erector shall check foundations and other
connection points to confirm their location, orientation, elevation, and
12-SAMSS-008
1 condition (readiness, anchor bolts, curing, clean, etc.).
Sec. III.B
(PIP STS05130, Erection of Structural and Miscellaneous Steel
Specification, Sec. 6.2.1.10)

SAES-Q-005
2 The top of concrete shall be a minimum of 150mm above finished grade.
Sec. 4.3.2.a

The design concrete compressive strength of concrete shall be 27.6MPa


SAES-Q-005
3 (4000psi) at 28 days. Concrete shall be cured before release for
Sec. 4.3.2.b
structural installation.

Base Plates shall be grouted per SAES-Q-010 as shown on the IFC


12-SAMSS-008
4 drawings to the levels indicated. (PIP STS05130, Erection of Structural
Sec. III.B.
and Miscellaneous Steel Specification, Sec. 6.4.2)

SAES-Q-005
5 The minimum thickness of grout shall be 25mm.
Sec. 4.3.2.c

Threaded Anchor Bolts shall be ASTM A36 / ASTM A36M or ASTM 12-SAMSS-007
6
F1554, Grade 36. Sec. 4.8

Headed Bolts shall be ASTM A307 Grade A with "Hex" sizes from 1/2" to 12-SAMSS-007
7
1-1/2" diameter and Heavy Hex over 1-1/2" diameter. Sec. 4.8

12-SAMSS-007
8 Anchor Bolt Washers shall be ASTM F436 or ASTM F436M.
Sec. 4.8

12-SAMSS-007
9 Anchor Bolt Plate Washers shall be ASTM A36 / ASTM A36M material.
Sec. 4.8

Anchor Bolt Nuts shall be ASTM A563 Grade A (Hex sizes 1/2" - 1-1/2" 12-SAMSS-007
10
diameter; Heavy Hex Sizes over 1-1/2" diameter) or ASTM A563M. Sec. 4.8

High Strength Anchor Bolts shall conform to ASTM A193 / ASTM A193M 12-SAMSS-007
11
Grade B7 or ASTM F1554, Grade 105. Sec. 4.9

High Strength Heavy Hex Nuts shall conform to ASTM A194 / ASTM 12-SAMSS-007
12
A194M or ASTM A563 DH. Sec. 4.9

High Strength Anchor Bolt Washers shall conform to ASTM F436 / 12-SAMSS-007
13
ASTM F436M. Sec. 4.9

12-SAMSS-007
14 High Strength Plate Washers shall conform to ASTM A36 / ASTM A36M.
Sec. 4.9

All Column Base Plates shall be designed with a minimum of 4 anchor SAES-M-001
15
bolts except for posts under 300lbs (136kg). Sec. 7.1.6

Page 1 of 2
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - August 2004)
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Structural Steel - Foundation or Connection Point Inspection SAIC-M-1024 18-May-05 Civil
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.

The erector shall clean the top of bearing surfaces and the bottom of
base plates and shall set and shim column base plates to correct
12-SAMSS-008
16 positions, elevations, and locations as shown on the erection drawings.
Sec. III.B
(PIP STS05130, Erection of Structural and Miscellaneous Steel
Specification, Sec. 6.4.1)

If a filler plate is used in spaces between members to be bolted, it may


not exceed 3mm (1/8") thickness. Saudi Aramco's approval shall be 12-SAMSS-008
17
required for filler plates greater than 3mm's (1/8"). (PIP STS05130, Sec. III.B.
Erection of Structural and Miscellaneous Steel Specification, Sec. 6.7.5)

REMARKS:

REFERENCE DOCUMENTS:
1- SAES-M-001, "Structural Design Criteria for Non-Building Structures" Issued 30 June 2004
2- SAES-Q-005, "Concrete Foundations" Issued 07 August 2004
3- 12-SAMSS-008, "Erection of Structural and Miscellaneous Steel" Issued 28 January 2004
4- 12-SAMSS-007, "Fabrication of Structural and Miscellaneous Steel" Issued 28 April 2004

Contractor / Third-Party Saudi Aramco


Construction Representative* PMT Representative
Work is Complete and Ready for Inspection: T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date:

QC Inspector PID Representative


Performed Inspection Work / Rework May Proceed T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date:

QC Supervisor Proponent and Others


Quality Record Approved: T&I Witnessed QC Record Reviewed Work Verified
Name, Organization,
Name, Sign and Date:
Initials and Date:

*Person Responsible for Completion of Quality Work / Test Y = YES N = NO F = FAILED

Page 2 of 2