You are on page 1of 45

SUBHEAD-I: POINT WIRING & SUBMAIN WIRING

UNIT RATE AMOUNT


Sl. No. DESCRIPTION OF ITEM UNIT QTY.
In Fig. (Rs.) In Words (Rs.)
1.1 Wiring for light Point/ fan point/ exhaust fan point/ call bell point with 1.5 Sq. mm FRLS
PVC insulated copper conductor single core cable in surface/ recessed Steel conduit,
with modular switch, modular plate, suitable size GI box and earthing the point with 1.5
sq.mm FRLS PVC insulated copper conductor single core cable etc as required.
Point 7277
1.2 Wiring for twin control light Point with 1.5 Sq. mm FRLS PVC insulated copper
conductor single core cable in surface/ recessed Steel conduit, 2 way modular switch,
modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC
insulated copper conductor single core cable etc as required. Point 10
1.3 Wiring for submain wiring/ circuit wiring along with earth wire with the following sizes of
PVC insulated copper conductor, single core cable in surface/ recessed Steel conduits
as required.
a) 2 x 2.5 Sq. mm + 1 x 2.5 Sq. mm earth wire. Mtrs. 23145
b) 2 x 4 Sq. mm + 1 x 4 Sq. mm earth wire. Mtrs. 13010
c) 2 x 6 Sq. mm + 1 x 6 Sq. mm earth wire. Mtrs. 200
d) 4 x 2.5 Sq. mm + 2 x 2.5 sq.mm earth wire Mtrs. 100
e) 4 x 4 Sq. mm + 2 x 4 sq.mm earth wire Mtrs. 4800
f) 4 x 6 Sq. mm + 2 x 6 sq.mm earth wire Mtrs. 200
g) 4 x 10 Sq. mm + 2 x 10sq.mm earth wire Mtrs. 250
h) 4 x 16 Sq. mm + 2 x 16sq.mm earth wire Mtrs. 200
1.4 Supplying and drawing co-axial TV cable RG-6 grade, 0.7 mm solid copper conductor
PE insulated, shielded with fine tinned copper braid and protected with PVC sheath in
the existing surface/ recessed steel/ PVC conduits as required. Metre 1360
1.5 Supplying and fixing of following sizes of Steel conduit along with accessories in surface/
recess including cutting the wall and making good the same in case of recessed conduit
as required.
a) 25 mm Metre 1360
b) 32 mm Metre 100
c) 40 mm Metre 200
1.6 Supplying and fixing following modular switch/ socket on existing modular plate & switch
box including connections but excluding modular plate etc. as required.
TV antenna socket outlet Each 34
1.7 Supplying and fixing stepped type electronic fan regulator on the existing modular plate
switch box including connections but excluding modular plate etc. as required.
Each 632
1.8 Supplying and fixing modular blanking plate on the existing modular plate switch box
including connections but excluding modular plate etc. as required. Each 200

Ru-Tech Services Inc. Page-1 Electrical BOQ.xls


SUBHEAD-I: POINT WIRING & SUBMAIN WIRING

UNIT RATE AMOUNT


Sl. No. DESCRIPTION OF ITEM UNIT QTY.
In Fig. (Rs.) In Words (Rs.)
1.9 Supplying and fixing of metal box of GI box with modular plate and cover in front on
surface or in recess, including providing and fixing of 3 pin 5/6 amps. modular socket
outlet and 5/6 amps. modular switch, connections, painting etc. as required. (For light
plugs). Each 682
2.0 Supplying and fixing of metal box of GI box with modular plate and cover in front on
surface or in recess, including providing and fixing of 6 pin 15/16 & 5/6 amps modular
socket outlet and 15/16 amps. modular switch, connections, painting etc. as required.
(For power plugs). Each 768
2.1 Supplying and fixing of metal box of GI box with modular plate and cover in front on
surface or in recess , including providing and fixing of 3 Nos 3 pin 5/6 amps modular
socket outlet and 15/16 amps. modular switch, connections, painting etc. as required.
(For computer plugs). Each 657
2.2 Supplying and fixing of 3 pin, 5 Amp. ceiling rose on the existing junction box/ wooden
block including connection etc. as required. (For power plugs). Each 143
2.3 Supplying and fixing 20 amps, 240 volts, SPN industrial type, socket outlet, with 2 pole
and earth, metal enclosed plug top alongwith 20 amps. 'C'-series, SP, MCB, in sheet
steel enclosure, on surface or in recess, with chained metal cover for the socket outlet
and complete with connections, testing and commissioning etc. as required.
Each 90
2.4 Supplying and fixing 30 amps, 240 volts, TPN industrial type socket outlet, with 4 pole
and earth metal enclosed plug top alongwith 30 amps. 'C'-series, TPMCB, in sheet steel
enclosure, on surface or in recess, with chained metal cover for the socket outlet, and
complete with connections, testing and commissioning etc. as required.
Each 117

TOTAL OF SUBHEAD I CARRIED OVER TO SUMMARY OF ELECTRICAL WORKS

Ru-Tech Services Inc. Page-2 Electrical BOQ.xls


SUBHEAD-II: FANS & FITTINGS

Sl. UNIT RATE AMOUNT


DESCRIPTION OF ITEM UNIT QTY.
No. In Fig.(Rs.) In Words(Rs.)
Supplying, installation, testing and commissioning of the following
luminaries mounting on surface / recess required for the internal wiring of
the building along with suitable hangers and lamps.
1 Surface mounted Industrial Box type 4 X 14W T-5 fixtures with HF ballast
(Philips Cat No. TPS 814/414 D8 HF/ Equivalent ) complete in everyway
with accessories & lamps. Each 721
2 Recessed mounted in modular cielings with 4 X 14W T-5 fixtures with HF
ballast (Philips Cat No. TBS 869/414 D8 HF/ Equivalent ) complete in
everyway with accessories & lamps. Each 800
3 Recessed mounted low glare luminair with 3 X PL-L36W (Philips Cat No.
FBS 300/336 P5 HF/ Equivalent ) complete in everyway with accessories
& lamps. Each 1134
4 Recessed mounted low glare luminair with 2 X PL-L36W (Philips Cat No.
FBS 570/236 FNC D6 MM HPF/ Equivalent ) complete in everyway with
accessories & lamps. Each 270
5 Recessed mounted downlighter 2 X PL-C 26W (Philips Cat No. FBH
225/226 ALR/ Equivalent ) complete in everyway with accessories &
lamps. Each 55
6 Surface mounted rectangular luminaire with 2 X 28W T-5 fixtures with HF
ballast (Philips Cat No. TPS 814/228 D8 HF/ Equivalent ) complete in
everyway with accessories & lamps. Each 100
7 Recessed mounted rectangular luminaire with 2 X 28W T-5 fixtures with
HF ballast(Philips Cat No. TBS 869/228 D8 HF/ Equivalent ) complete in
everyway with accessories & lamps. Each 47
8 Industrial Batton suitable for 1 X 28W T-5 fixtures with HF ballast (Philips
Cat No. TMS 122/128 HF/ Equivalent ) complete in everyway with
accessories & lamps. Each 10
9 Indoor decorative surface mounted suitable for 1 X 28W T-5 fixtures with
HF ballast (Philips Cat No. TWG 128 / 2005 HF/ Equivalent ) complete in
everyway with accessories & lamps. Each 93
10 Surface mounted suitable for 1 X PL-S 9 W fixtures with HF ballast
(Philips Cat No. FCS 518/209 / Equivalent ) complete in everyway with
accessories & lamps. Each 2

Ru-Tech Services Inc. Page-1 Electrical BOQ.xls


SUBHEAD-II: FANS & FITTINGS

Sl. UNIT RATE AMOUNT


DESCRIPTION OF ITEM UNIT QTY.
No. In Fig.(Rs.) In Words(Rs.)
11 Wall recess step light luminaire die cast housing suitable for 2 X PL-C 18
W fixtures with HF ballast (Philips Cat No. DBP701/ 2x PLC18W/ Similar
specifications of other approved makes) complete in everyway with
accessories & lamps. Each 11
12 Surface mounted suitable for 2 X PL-S 18 W fixtures with HF ballast
(Philips Cat No. FCS 518/218 / Equivalent ) complete in everyway with
accessories & lamps. Each 734
13 Recessed down lighter suitable for 1 X PL-C 13W fixtures (Philips Cat
No. FBH 145 /113 L / Equivalent ) complete in everyway with accessories
& lamps. Each 184
14 Recessed down lighter suitable for 1 X PL-C 18W fixtures (Philips Cat
No. FBH 145 /118 L / Equivalent ) complete in everyway with accessories
& lamps. Each 2
15 Recessed down lighter suitable for 2 X PL-C 18W fixtures (Philips Cat
No. FBH 145 /218 L/ Equivalent ) complete in everyway with accessories
& lamps. Each 1000
16 Surface mounted down lighter suitable for 1 X 70W (Philips Cat No.
MBS205 / 1 X 70W MHN-TD / Equivalent ) complete in everyway with
accessories & lamps. Each 80
17 Scrabble with adjustable Lamp position 1X70W CDMT 3000 Deg.K
(Havells Cat No. LHOH80150399 / Equivalent ) complete in everyway
with accessories & lamps. Each 117
18 Scrabble with adjustable Lamp position 1X35W CDMT 3000 Deg.K
(Havells Cat No. LHOH80150399 / Equivalent ) complete in everyway
with accessories & lamps. Each 25
19 Scrabble with adjustable Lamp position 2X70W CDMT 3000 Deg.K
(Havells Cat No. LHOH80250399 / Equivalent ) complete in everyway
with accessories & lamps. Each 51
20 Decorative non-integral medium bay luminaire with prismatic diffusers
suitable for 1 X CDM-TT 150W fixtures (Philips Cat No. HPK 205 /CDM-
TT 150W PR / Equivalent ) complete in everyway with accessories &
lamps. Each 302

Ru-Tech Services Inc. Page-2 Electrical BOQ.xls


SUBHEAD-II: FANS & FITTINGS

Sl. UNIT RATE AMOUNT


DESCRIPTION OF ITEM UNIT QTY.
No. In Fig.(Rs.) In Words(Rs.)
21 Wall mounted mirror luminaire suitable for 1 X PL-5 11W fixtures (Philips
Cat No. FMS 200/111 / Equivalent ) complete in everyway with
accessories & lamps. Each 134
22 Bulkhead luminaire fitting suitable for 18 W CFL (Philips Cat No. FXC
101/ Equivalent ) complete in everyway with accessories & lamps
Each 45
23 Decorative moulded body ceiling mounted fixture suitable for 2 X 9W CFL
(Havells Cat. No. LHDC27209024 / Equivalent ) complete in everyway
with accessories & lamps. Each 10
24 Wall Bracket Lighting fixture suitable for 2 X 9W CFL (Havells Cat. No.
LHDC01209017 / Equivalent ) complete in everyway with accessories &
lamps. Each 97
25 Supplying of 1200mm A.C Ceiling fan sweep complete (Havells Cat. No.
LHDC27209024 / Equivalent ) (But without regulator) Each 632
26 Supplying of wall mounted Turbo Force Air Circulators 450 MM Wall TF
of Havells Cat. / Equivalent ) (But without regulator) Each 439
27 Supplying of Heavy Duty Exhaust Fan complete with louvers / shutter of
following sizes
a) 300 MM x 1400 RPM Single phase Nos 30
b) 380 MM x 1400 RPM Single phase Nos 113

TOTAL OF SUBHEAD II CARRIED OVER TO SUMMARY OF


ELECTRICAL WORKS

Ru-Tech Services Inc. Page-3 Electrical BOQ.xls


SUBHEAD-III: DISTRIBUTION BOARDS

UNIT RATES (Rs.) AMOUNT


Sl. No DESCRIPTION OF ITEM UNIT QTY.
In Fig. (Rs.) In Words(Rs.)
DISTRIBUTION BOARDS
1.1 Supplying and fixing following way, single pole and neutral, prewired, sheet
steel, MCB distribution board, 240 volts, on surface/ recess, complete with
loose wire box, terminal box, duly prewired with suitable size FRLS PVC
insulated copper conductor upto terminal blocks, tinned copper busbar,
neutral links, earthbar, dinbar, detachable gland plate, interconnections,
phosphatized and powder painted including earthing etc. as required (But
without MCB/ RCCB/ Isolator)
2+4, Double door Each 10
1.2 Supplying, installation, testing and commissioning of surface/ recess
mounting, vertical type, 415 volts, prewired, TPN MCB distribution board of
sheet steel, dust protected, duly phosphatized and powder painted, inclusive
of 200 amps tinned copper busbars, common neutral link, earth bar, din bar
for mounting MCB's, detachable gland/ knock out plate, and with built in loose
wire box, and superior make terminal connectors for all incoming and
outgoing circuits, duly prewired with adequate size of FRLS PVC insulated
copper conductor upto the terminal connector/ neutral link and ready for
installation of following ways (but without MCB's and incomer) as required.

a) 4 way (4+12), Double door Each 51


b) 6 way (4+18), Double door Each 83
c) 8 way (4+24), Double door Each 81
d) 12 way (4+36), Double door Each 31
1.3 Supplying and fixing 5 amps to 32 amps rating, 240 volts, 'B' series ,
miniature circuit breaker suitable for lighting and other loads of following poles
in the existing MCB DB complete with connections, testing and commissioning
etc. as required.
a) Single Pole, 10/16/20/32 Amps Nos 2629
b) Triple Pole, 16/20/32 Amps Nos 117
1.4 Supplying and fixing following rating, double pole, (single phase and neutral),
240 volts, residual current circuit breaker (RCCB), having a sensitivity current
upto 300 milliamperes in the existing MCB DB complete with connections,
testing and commissioning etc. as required.
40 Amps Each 10

Ru-Tech Services Inc. Page-1 Electrical BOQ.xls


SUBHEAD-III: DISTRIBUTION BOARDS

UNIT RATES (Rs.) AMOUNT


Sl. No DESCRIPTION OF ITEM UNIT QTY.
In Fig. (Rs.) In Words(Rs.)
1.5 Supplying and fixing following rating, foure pole, (three phase and neutral),
415 volts, residual current circuit breaker (RCCB), having a sensitivity current
upto 300 milliamperes in the existing MCB DB complete with connections,
testing and commissioning etc. as required.
a) 25 Amps Each 142
b) 40 Amps Each 20
c) 63 Amps Each 52

1.6 Providing and fixing following rating and breaking capacity MCCB in existing
cubicle panel board incuding drilling holes in cubicle panel, making
connections, etc. as required.
100 Amp, 16kA Each 32

TOTAL OF SUBHEAD III CARRIED OVER TO SUMMARY OF ELECTRICAL


WORKS

Ru-Tech Services Inc. Page-2 Electrical BOQ.xls


SUBHEAD-IV: TELEPHONE CONDUITING & WIRING

Sl. No. DESCRIPTION OF ITEM UNIT QTY. UNIT RATE AMOUNT


In Fig. (Rs.) In Words (Rs.)
1 Supplying and fixing cat 5e Information outlet for telephone sockets
housed in GI boxes recessed in walls/ partitions/ panelling for
telephone outlets Nos. 361

a) Single surface mount/recessed box within jacks (RJ-45) I/O (Cat-6) Nos 361

2 Fish wire of 5 SWG, fixing hardware etc., including cutting,chasing


the walls/floor and filling the chased portion and making good the
damages etc. complete as required
a) 25 mm dia RM 1000

3 Supplying and drawing the following sizes of anealed tinned


electrolytic copper conductor PVC insulated unshielded twisted wires
in eisting conduitand making connection on both the ends.
a) Cat -5 cable RM 15000

4 Supply, installation, testing, and commissioning of 24 port Jack Panel


Cat 5e cable management system with all material as required.
Nos 28
5 Supplying and fixing the telephone tag blocks housed in MS boxes
(with hinged cover and duly painted) recessed in wall with adequate
knockouts including chase cutting and making the surface good and
making connections complete as required
a) 10 pair Nos 200
b) 20 pair Nos 1000
c) 50 pair Nos 1000

TOTAL OF SUBHEAD IV CARRIED OVER TO SUMMARY OF


ELECTRICAL WORKS

Ru-Tech Services Inc. Page-1 Electrical BOQ.xls


SUBHEAD V: DATA NETWORKING

Sl. No. DESCRIPTION OF ITEM UNIT QTY. UNIT RATES AMOUNT


In Fig. (Rs.) In Words (Rs.)
1 Supply, installation, testing and commissioning of category 6 flush
mounted information outlets wired according to T568B standard with
a faceplate. The plastic shall be high impact, flame retardent & UL-
rated thermoplastic with minimum insulation resistance of 500 M
Ohm Nos. 657
2 Single surface mount/recessed box withn jacks (RJ-45) I/O (Cat-6)
Nos 657
3 fish wire of 6 SWG, fixing hardware etc., including cutting,chasing
the walls/floor and filling the chased portion ande making good the
damages etc. complete as required
a) 25 mm dia RM 4000

4 Supplying and drawing the following sizes of anealed tinned


electrolytic copper conductor PCV insulated unshielded twisted wires
in eisting conduitand making connection on both the ends.
a) Cat - 6 cable RM 26280

5 Supply, installation, testing, and commissioning of 24 port Jack Panel


Cat 6 cable management system with all material as required.
Nos 22

6 Supply, installation, testing, and commissioning of 24 port switch with


all meterial as required Nos 22

7 Supply, installation, testing, and commissioning of 12U rack with all


meterial as required Nos 2

8 Supply, installation, testing, and commissioning of 12 port 1000


MBPS core switch with all materials as required . Nos 4

9 Supply, installation, testing, and commissioning of rack server 42U


with all meterial as required Nos 3

10 Supply, installation, testing, and commissioning of patch cord 2


meter with all meterial as required Nos 657

Ru-Tech Services Inc. Page 1 Electrical BOQ.xls


SUBHEAD V: DATA NETWORKING

Sl. No. DESCRIPTION OF ITEM UNIT QTY. UNIT RATES AMOUNT


In Fig. (Rs.) In Words (Rs.)
11 Supply, installation, testing, and commissioning of patch cord 5
meter (1 side R445 another side Unterminated)with all meterial as
required Nos 657

12 Supply, installation, testing, and commissioning of information


outlet(WI-FY)with all material as required Nos 20

13 Supply, installation, testing, and commissioning of UPS system with


following features 1. High
freq. PWM inverter using IGBT 2.
Manual bypass switch 3.
Inbuilt Static Switch 4.
80 Character Alpha Numeric LCD display with
5. SMF batteries to provide approx. 2 hours backup time on IT load
alongwith battery rack.
a. 8 KVA True on-line, Nos 2
b. 20 KVA True on-line, Nos 2
c. 25 KVA True on-line, Nos 1
d. 40 KVA True on-line, Nos 1

TOTAL OF SUBHEAD V CARRIED OVER TO SUMMARY OF


ELECTRICAL WORKS

Ru-Tech Services Inc. Page 2 Electrical BOQ.xls


SUBHEAD VI: LT CABLES & TERMINATIONS, CABLE TRAYS etc.

UNIT RATES AMOUNT


Sl . No. DESCRIPTION OF ITEM UNIT QTY.
In Fig. (Rs.) In Words (Rs.)
1.1 Supply and laying in cable Tray/clamped to wall with suitable clamps
saddles and fixing bolts/ in ground including the cost of digging and back
filling with sand and brick protection as required and including testing and
commissioning of the following sizes of 1.1KV grade multicore aluminium
conductor XLPE insulated and PVC sheathed armoured cable conforming
to IS : 7098 (Part-I). The costs shall include for all cables to be provided
with a 1D gap and shall be properly clamped with cable clamps and ties.
Identification tags shall be provided for all cables and route markers for
cables in ground as per specifications and as per instructions of Engineer-
in-charge.
a) 3.5 core, 185 Sq.mm. Meter 160
b) 3.5 core, 150 Sq.mm. Meter 20
c) 3.5 core, 120 Sq.mm. Meter 210
d) 3.5 core, 70 Sq.mm. Meter 460
e) 3.5 core, 50 Sq.mm. Meter 120
f) 3.5 core, 35 Sq.mm. Meter 95
g) 3.5 core, 25 Sq.mm. Meter 465

1.2 Supply and laying in cable Tray/clamped to wall with suitable clamps
saddles and fixing bolts/ in ground including the cost of digging and back
filling with sand and brick protection as required and including testing and
commissioning of the following sizes of 1.1KV grade multicore aluminium
conductor PVC insulated and PVC sheathed armoured cable conforming to
IS : 1554 (Part-I). Identification tags shall be provided for all cables and
route markers for cables in ground as per specifications and as per
instructions of Engineer-in-charge.
a) 4 core, 16 Sq.mm. Meter 2505
b) 4 core, 10 Sq.mm. Meter 1580
c) 4 core, 6 Sq.mm. Meter 1810
d) 4 core, 4 Sq.mm. Meter 4770

Ru-Tech Services Inc. Page-1 Electrical BOQ.xls


SUBHEAD VI: LT CABLES & TERMINATIONS, CABLE TRAYS etc.

UNIT RATES AMOUNT


Sl . No. DESCRIPTION OF ITEM UNIT QTY.
In Fig. (Rs.) In Words (Rs.)
1.3 Supply and laying in cable Tray/clamped to wall with suitable clamps
saddles and fixing bolts/ in ground as required and including testing and
commissioning of the following sizes of 1.1KV grade multicore copper
conductor PVC insulated and PVC sheathed un-armoured cable
conforming to IS : 1554 (Part-I). Identification tags shall be provided for all
cables and route markers for cables in ground as per specifications and as
per instructions of Engineer-in-charge.
a) 4 core, 25 Sq.mm. Meter 190
b) 4 core, 16 Sq.mm. Meter 240
c) 4 core, 10 Sq.mm. Meter 380
d) 4 core, 6 Sq.mm. Meter 450
e) 4 core, 4 Sq.mm. Meter 3540
f) 4 core, 2.5 Sq.mm. Meter 1310

1.4 Supplying and making end termination with brass compression gland and
aluminium lugs for following size of PVC insulated and PVC sheathed/
XLPE aluminium conductor cable of 1.1 KV grade as required.

a) 3.5 core, 185 Sq.mm. Set 6


b) 3.5 core, 150 Sq.mm. Set 2
c) 3.5 core, 120 Sq.mm. Set 10
d) 3.5 core, 70 Sq.mm. Set 19
e) 3.5 core, 50 Sq.mm. Set 4
f) 3.5 core, 35 Sq.mm. Set 4
g) 3.5 core, 25 Sq.mm. Set 18
h) 4 core, 16 Sq.mm. Set 102
i) 4 core, 10 Sq.mm. Set 64
j) 4 core, 6 Sq.mm. Set 72
k) 4 core, 4 Sq.mm. Set 258
l) 4 core, 2.5 Sq.mm. Set 46

Ru-Tech Services Inc. Page-2 Electrical BOQ.xls


SUBHEAD VI: LT CABLES & TERMINATIONS, CABLE TRAYS etc.

UNIT RATES AMOUNT


Sl . No. DESCRIPTION OF ITEM UNIT QTY.
In Fig. (Rs.) In Words (Rs.)
1.5 Fabrication and installing following size of perforated M.S. cable trays
including horizontal and vertical bends, reducers, tees, cross members and
other accessories as required and duly suspended from the ceiling with
M.S. suspenders and including painting with powder coating etc. as
required.
a) 375 mm width x 50 mm depth x 2.0 mm thickness Meter 1250
b) 150 mm width x 50 mm depth x 1.6 mm thickness Meter 300
c) 100 mm width x 50 mm depth x 1.6 mm thickness Meter 350

1.6 Providing & laying in position hume pipes of the following sizes in road
crossings, paved areas etc., including collars, joints filled with cement
mortar 1:4 (1 Cement :4 Coarse sand ) finished complete as required.

a) 100mm dia Meter 150


b) 250mm dia Meter 100

TOTAL OF SUBHEAD VI CARRIED OVER TO SUMMARY OF


ELECTRICAL WORKS

Ru-Tech Services Inc. Page-3 Electrical BOQ.xls


SUBHEAD VII: EARTHING

Sl. DESCRIPTION OF ITEM UNIT QTY. UNIT RATES AMOUNT


No. In Fig. (Rs.) In Words (Rs.)
1 Earthing with G.I. earth pipe 4.5 mtr long, 40 mm dia including accessories, and Set 36
providing masonry enclosure with cover plate having locking arrangement and
watering pipe etc. (but without charcoal or coke and salt) as required.

2 Extra for using salt and charcoal for pipe earth electrode as required. Set 36

3 Supplying and laying 25 mm X 5 mm thick G.I. Strip at 0.5 meters below ground Metre 2350
as strip earth electrod including soldering etc. as required.

4 Providing and Fixing 25mm x 5mm GI strip in 40 mm dia G.I. Pipe from earth Metre 1800
electrode, as required.

5 Providing and fixing earth bus of 50 mm X 5 mm copper strip on surface for Metre 90
connections etc. as required.

TOTAL OF SUBHEAD VII CARRIED OVER TO SUMMARY OF ELECTRICAL


WORKS

Ru-Tech Services Inc. Page-1 Electrical BOQ.xls


SUBHEAD VIII: LIGHTENING

Sl. No. DESCRIPTION OF ITEM UNIT QTY. UNIT RATES AMOUNT


In Fig. (Rs.) In Words ( Rs.)
1 Supply, installation tested and commissioning of Early streamer Emission based
advance Lightning Arrestor System made of 304 L stainless steel including supply
and fixing of 1 no. support Mast on top of Mumti complete as required.
Each 6
2 Supply and fixing GI strip 25 mm x 3 mm along outside wall / columns as vertical
conductors fixing, saddles, screws complete as required. Each 240
3 Supply and laying in ground with GI strip 25 mm x 3 mm including the cost of digging
and back filling complete as required for earth pits interconnection complete as
required. Each 120
4 Providing and making maintenance free earthpits including the cost of 3 nos 16 mm
dia 1.2 m long MS earth rods molecularly bonded with 250 micron copper and
treated with 10 kGs ground enhancing back filled chemical TEREC+, all earth work,
masonary enclosure with bituminized CI pit cover and frame as per IS 3043: 1987.
Metre 12

TOTAL OF SUBHEAD VIII CARRIED OVER TO SUMMARY OF ELECTRICAL


WORKS

Ru-Tech Services Inc. Page 1 Electrical BOQ.xls


SUBHEAD IX: DISTRIBUTION LT PANELS

UNIT RATES AMOUNT


Sl. No. DESCRIPTION OF ITEM UNIT QTY. In Words
In Fig. (Rs.)
(Rs.)
1.0 GUEST HOUSE MAIN LT PANEL
Supply, erection, testing and commissioning of LT panel fully compartmentalized (bolted type design)
metal clad, floor mounted, both side extensible type switchboard made of 2 mm CRCA sheet suitable for
415 V, 3 phase 4 wire 50 Hz system, consisting of 3.5 strips Aluminum busbars complete with following
accessories. Set 1
Incoming :
1 no. 200A FP MCCB Ics=35kA with TMD release.
1 No. Multifunction meter with control MCBs.
2 Nos. ON/OFF indicating Lamp
3 Nos. phase indication lamps with control fuses.
Busbar :
250A TPN Al busbar. Busbar shall be insulated with heat shrinkable sleeves and shall be color coded.

Outgoings :
2 Nos. 100 A TP MCCB (Ics=25 kA)
6 Nos. 63 A TP MCCB (Ics=25 kA)
All the O/G shall have with ON/OFF indication lamp

1.1 GUEST HOUSE SMB-GF,F/F,S/F,T/F


Supply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,
AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thick
CRCA sheet complete with busbars, meters, indicating lamps, protection fuses, interconnections and
having following incoming and outgoing as per the SLD and specifications . Set 4
Incoming
1 No. 63 Amp FP MCB(10kA)
1 No. Ammeter with control MCBs.
3 Nos. phase indication lamps with control fuses.
Busbars
TP+N AL Busbar shall be suitable to carry 100A continuous current.
Outgoing
1Nos. 25 Amp TP MCB
2 Nos. 63 Amp TP MCB

1.2 GUEST HOUSE UPS DB


Supply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,
AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thick
CRCA sheet complete with busbars, meters, relays, indicating lamps, protection fuses, interconnections
and having following incoming and outgoing as per the SLD and specifications. Set 1

Ru-Tech Services Inc. Page-1 Electrical BOQ.xls


SUBHEAD IX: DISTRIBUTION LT PANELS

UNIT RATES AMOUNT


Sl. No. DESCRIPTION OF ITEM UNIT QTY. In Words
In Fig. (Rs.)
(Rs.)
Incoming
1 No. 63 Amp FP MCB(10kA)
1 No. Ammeter with control MCBs.
3 Nos. phase indication lamps with control fuses.
Busbars
TP+2N Busbar(Aluminium) shall be suitable to carry 100A continuous current.
Outgoing
5 Nos. 25 Amp TP MCB(10kA)

1.3 GUEST HOUSE AC DISTRIBUTION PANEL


Supply, erection, testing and commissioning of AC Distribution panel fully compartmentalized (bolted type
design) metal clad, floor mounted, both side extensible type switchboard made of 2 mm CRCA sheet
suitable for 415 V, 3 phase 4 wire 50 Hz system, consisting of 3.5 strips Aluminium busbars complete
with following accessories. Set 1
Incoming :
1 No. 200A FP MCCB (Ics=35kA) with TMD release.
1 No. Volt meter with Selector switch.
1 No. Ammeter with Selector switch.
2 Nos. ON/OFF indicating Lamp.
3 Nos. phase indication lamps with control fuses.
Busbar :
300A TPN Al busbar. Busbar shall be insulated with heat shrinkable sleeves and shall be color coded.

Outgoings :
2 Nos. 100 A TP MCCB (Ics=25 kA)
1 Nos. 63 A TP MCB (Ics=10kA)
All the O/G shall have with ON/OFF indication lamp.

2.0 COMMON ACTIVITY MAIN LT PANEL


Supply, erection, testing and commissioning of LT panel fully compartmentalized (bolted type design)
metal clad, floor mounted, both side extensible type switchboard made of 2 mm CRCA sheet suitable for
415 V, 3 phase 4 wire 50 Hz system, consisting of 3.5 strips Aluminum busbars complete with following
accessories. Set 1
Incoming :
1 no. 250A FP MCCB Ics=35kA with Electronic release.
1 No. Multifunction meter with control MCBs.
2 Nos. ON/OFF indicating Lamp
3 Nos. phase indication lamps with control fuses.

Ru-Tech Services Inc. Page-2 Electrical BOQ.xls


SUBHEAD IX: DISTRIBUTION LT PANELS

UNIT RATES AMOUNT


Sl. No. DESCRIPTION OF ITEM UNIT QTY. In Words
In Fig. (Rs.)
(Rs.)
Busbar :
300A TPN Al busbar. Busbar shall be insulated with heat shrinkable sleeves and shall be color coded.

Outgoings :
4 Nos. 100 A TP MCCB (Ics=25 kA)
5 Nos. 63 A TP MCCB (Ics=25 kA)
All the O/G shall have with ON/OFF indication lamp

2.1 COMMON ACTIVITY SMB-GF


Supply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,
AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thick
CRCA sheet complete with busbars, meters, indicating lamps, protection fuses, interconnections and
having following incoming and outgoing as per the SLD and specifications . Set 1
Incoming
1 No. 100 Amp FP MCCB(25kA) with TMD release
1 No. Ammeter with control MCBs.
3 Nos. phase indication lamps with control fuses.
Busbars
TP+N AL Busbar shall be suitable to carry 125A continuous current.
Outgoing
2 Nos. 25 Amp TP MCB(10kA)
3 Nos. 63 Amp TP MCB(10kA)

2.2 COMMON ACTIVITY SMB-F/F,T/F


Supply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,
AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thick
CRCA sheet complete with busbars, meters, indicating lamps, protection fuses, interconnections and
having following incoming and outgoing as per the SLD and specifications . Set 2
Incoming
1 No. 63 Amp FP MCB(10kA)
1 No. Ammeter with control MCBs.
3 Nos. phase indication lamps with control fuses.
Busbars
TP+N AL Busbar shall be suitable to carry 100A continuous current.
Outgoing
2 Nos. 25 Amp TP MCB(10kA)
3 Nos. 40 Amp TP MCB(10kA)

Ru-Tech Services Inc. Page-3 Electrical BOQ.xls


SUBHEAD IX: DISTRIBUTION LT PANELS

UNIT RATES AMOUNT


Sl. No. DESCRIPTION OF ITEM UNIT QTY. In Words
In Fig. (Rs.)
(Rs.)
2.3 COMMON ACTIVITY UPS DB
Supply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,
AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thick
CRCA sheet complete with busbars, meters, relays, indicating lamps, protection fuses, interconnections
and having following incoming and outgoing as per the SLD and specifications. Set 1
Incoming
1 No. 63 Amp FP MCB(10kA)
1 No. Ammeter with control MCBs.
3 Nos. phase indication lamps with control fuses.
Busbars
TP+2N Busbar(Aluminium) shall be suitable to carry 100A continuous current.
Outgoing
3 Nos. 25 Amp TP MCB(10kA)

2.4 COMMON ACTIVITY SOLAR DB


Supply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,
AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thick
CRCA sheet complete with busbars, meters, relays, indicating lamps, protection fuses, interconnections
and having following incoming and outgoing as per the SLD and specifications. Set 1
Incoming
1 No. 63A Automatic transfer switch
1 No. 63 Amp FP MCB(10kA)
1 No. Ammeter with control MCBs.
3 Nos. phase indication lamps with control fuses.
Busbars
TPN Busbar(Aluminium) shall be suitable to carry 100A continuous current.
Outgoing
4 Nos. 25 Amp TP MCB(10kA)

2.5 COMMON ACTIVITY AC DISTRIBUTION PANEL


Supply, erection, testing and commissioning of AC Distribution panel fully compartmentalized (bolted type
design) metal clad, floor mounted, both side extensible type switchboard made of 2 mm CRCA sheet
suitable for 415 V, 3 phase 4 wire 50 Hz system, consisting of 3.5 strips Aluminium busbars complete
with following accessories. Set 1
Incoming :
1No. 300A FP MCCB (Ics=35kA) with TMD release.
1 No. Volt meter with Selector switch.
1 No. Ammeter with Selector switch.

Ru-Tech Services Inc. Page-4 Electrical BOQ.xls


SUBHEAD IX: DISTRIBUTION LT PANELS

UNIT RATES AMOUNT


Sl. No. DESCRIPTION OF ITEM UNIT QTY. In Words
In Fig. (Rs.)
(Rs.)
2 Nos. ON/OFF indicating Lamp.
3 Nos. phase indication lamps with control fuses.
Busbar :
350A TPN Al Busbar. Busbar shall be insulated with heat shrinkable sleeves and shall be color coded.

Outgoings :
3 Nos. 100 A TP MCCB (Ics=25 kA)
1 Nos. 63 A TP MCB (Ics=10 kA)
All the O/G shall have with ON/OFF indication lamp.

3.0 FILM &TV MAIN LT PANEL


Supply, erection, testing and commissioning of LT panel fully compartmentalized (bolted type design)
metal clad, floor mounted, both side extensible type switchboard made of 2 mm CRCA sheet suitable for
415 V, 3 phase 4 wire 50 Hz system, consisting of 3.5 strips Aluminum busbars complete with following
accessories. Set 1
Incoming :
1 no. 1000A FP MDO ACB with microprocessor based O/L & S/C Protection
1 No. Multifunction meter with control MCBs.
2 Nos. ON/OFF indicating Lamp
3 Nos. phase indication lamps with control fuses.
Busbar :
1250A TPN Al busbar. Busbar shall be insulated with heat shrinkable sleeves and shall be color coded.

Outgoings :
3 Nos. 200 A TP MCCB (Ics=25 kA)
3 Nos. 315 A TP MCCB (Ics=25 kA)
3 Nos. 100 A TP MCCB (Ics=25 kA)
All the O/G shall have with ON/OFF indication lamp

3.1 FILM & TV SMB- 2 GF


Supply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,
AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thick
CRCA sheet complete with busbars, meters, indicating lamps, protection fuses, interconnections and
having following incoming and outgoing as per the SLD and specifications . Set 1
Incoming
1 No. 315 Amp FP MCCB(35kA)
1 No. Ammeter with control MCBs.
3 Nos. phase indication lamps with control fuses.

Ru-Tech Services Inc. Page-5 Electrical BOQ.xls


SUBHEAD IX: DISTRIBUTION LT PANELS

UNIT RATES AMOUNT


Sl. No. DESCRIPTION OF ITEM UNIT QTY. In Words
In Fig. (Rs.)
(Rs.)
Busbars
TP+N AL Busbar shall be suitable to carry 400A continuous current.
Outgoing
5 Nos. 25 Amp TP MCB(10kA)
1 Nos. 40 Amp TP MCB(10kA)
6 Nos. 63 Amp TP MCB(10kA)

3.2 FILM & TV SMB- 1 GF


Supply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,
AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thick
CRCA sheet complete with busbars, meters, indicating lamps, protection fuses, interconnections and
having following incoming and outgoing as per the SLD and specifications . Set 1
Incoming
1 No. 315 Amp FP MCCB(35kA)
1 No. Ammeter with control MCBs.
3 Nos. phase indication lamps with control fuses.
Busbars
TP+N AL Busbar shall be suitable to carry 350A continuous current.
Outgoing
6 Nos. 25 Amp TP MCB(10kA)
6 Nos. 63 Amp TP MCB(10kA)

3.3 FILM & TV SMB- FF


Supply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,
AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thick
CRCA sheet complete with busbars, meters, indicating lamps, protection fuses, interconnections and
having following incoming and outgoing as per the SLD and specifications . Set 1

Ru-Tech Services Inc. Page-6 Electrical BOQ.xls


SUBHEAD IX: DISTRIBUTION LT PANELS

UNIT RATES AMOUNT


Sl. No. DESCRIPTION OF ITEM UNIT QTY. In Words
In Fig. (Rs.)
(Rs.)
Incoming
1 No. 200 Amp FP MCCB(25kA)
1 No. Ammeter with control MCBs.
3 Nos. phase indication lamps with control fuses.
Busbars
TP+N AL Busbar shall be suitable to carry 250A continuous current.
Outgoing
2 Nos. 25 Amp TP MCB(10kA)
3 Nos. 63 Amp TP MCB(10kA)

3.4 FILM & TV SMB- SF


Supply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,
AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thick
CRCA sheet complete with busbars, meters, indicating lamps, protection fuses, interconnections and
having following incoming and outgoing as per the SLD and specifications . Set 1
Incoming
1 No. 200 Amp FP MCCB(25kA)
1 No. Ammeter with control MCBs.
3 Nos. phase indication lamps with control fuses.
Busbars
TP+N AL Busbar shall be suitable to carry 250A continuous current.
Outgoing
6 Nos. 25 Amp TP MCB(10kA)
5 Nos. 63 Amp TP MCB(10kA)

3.5 FILM & TV UPS DB


Supply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,
AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thick
CRCA sheet complete with busbars, meters, relays, indicating lamps, protection fuses, interconnections
and having following incoming and outgoing as per the SLD and specifications. Set 1
Incoming
1 No. 100Amp FP MCCB(Ics=25kA)
1 No. Ammeter with control MCBs.
3 Nos. phase indication lamps with control fuses.
Busbars
TP+2N Busbar(Aluminium) shall be suitable to carry 125A continuous current.
Outgoing
5 Nos. 40 Amp TP MCB(10kA)

Ru-Tech Services Inc. Page-7 Electrical BOQ.xls


SUBHEAD IX: DISTRIBUTION LT PANELS

UNIT RATES AMOUNT


Sl. No. DESCRIPTION OF ITEM UNIT QTY. In Words
In Fig. (Rs.)
(Rs.)

Ru-Tech Services Inc. Page-8 Electrical BOQ.xls


SUBHEAD IX: DISTRIBUTION LT PANELS

UNIT RATES AMOUNT


Sl. No. DESCRIPTION OF ITEM UNIT QTY. In Words
In Fig. (Rs.)
(Rs.)
3.6 FILM & TV UPS SUB-DB-1,
Supply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,
AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thick
CRCA sheet complete with busbars, meters, relays, indicating lamps, protection fuses, interconnections
and having following incoming and outgoing as per the SLD and specifications. Set 1
Incoming
1 No. 40Amp FP MCB(10kA)
1 No. Ammeter with control MCBs.
3 Nos. phase indication lamps with control fuses.
Busbars
TP+2N Busbar(Aluminium) shall be suitable to carry 63A continuous current.
Outgoing
6 Nos. 20 Amp TP MCB(10kA)

3.7 FILM & TV UPS SUB-DB-2 , 3


Supply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,
AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thick
CRCA sheet complete with busbars, meters, relays, indicating lamps, protection fuses, interconnections
and having following incoming and outgoing as per the SLD and specifications. Set 2
Incoming
1 No. 40Amp FP MCB(10kA)
1 No. Ammeter with control MCBs.
3 Nos. phase indication lamps with control fuses.
Busbars
TP+2N Busbar(Aluminium) shall be suitable to carry 63A continuous current.
Outgoing
3 Nos. 20 Amp TP MCB(10kA)

3.8 FILM & TV SOLAR DB


Supply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,
AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thick
CRCA sheet complete with busbars, meters, relays, indicating lamps, protection fuses, interconnections
and having following incoming and outgoing as per the SLD and specifications. Set 1
Incoming
1 No. 100A Automatic transfer switch
1 No. 100 Amp FP MCCB(25kA)
1 No. Ammeter with control MCBs.
3 Nos. phase indication lamps with control fuses.

Ru-Tech Services Inc. Page-9 Electrical BOQ.xls


SUBHEAD IX: DISTRIBUTION LT PANELS

UNIT RATES AMOUNT


Sl. No. DESCRIPTION OF ITEM UNIT QTY. In Words
In Fig. (Rs.)
(Rs.)
Busbars
TPN Busbar(Aluminium) shall be suitable to carry 125A continuous current.
Outgoing
5 Nos. 25 Amp TP MCB(10kA)

3.9 FILM &TV AC DISTRIBUTION PANEL


Supply, erection, testing and commissioning of AC Distribution panel fully compartmentalized (bolted type
design) metal clad, floor mounted, both side extensible type switchboard made of 2 mm CRCA sheet
suitable for 415 V, 3 phase 4 wire 50 Hz system, consisting of 3.5 strips Aluminium busbars complete
with following accessories. Set 1
Incoming :
1 No. 800A FP MDO ACB with microprocessor based O/L & S/C Protection.
1 No. Volt meter with Selector switch.
1 No. Ammeter with Selector switch.
2 Nos. ON/OFF indicating Lamp.
3 Nos. phase indication lamps with control fuses.
Busbar :
1000A TPN Al Busbar. Busbar shall be insulated with heat shrinkable sleeves and shall be color coded.

Outgoings :
7 Nos. 100 A TP MCCB (Ics=25 kA)
6 Nos. 63 A TP MCB (Ics=10 kA)
All the O/G shall have with ON/OFF indication lamp

4.0 PROFESSIONAL STUDIES MAIN LT PANEL


Supply, erection, testing and commissioning of LT panel fully compartmentalized (bolted type design)
metal clad, floor mounted, both side extensible type switchboard made of 2 mm CRCA sheet suitable for
415 V, 3 phase 4 wire 50 Hz system, consisting of 3.5 strips Aluminum busbars complete with following
accessories. Set 1
Incoming :
1 no. 630A FP MCCB Ics=35kA with Electronic release.
1 No. Multifunction meter with control MCBs.
2 Nos. ON/OFF indicating Lamp
3 Nos. phase indication lamps with control fuses.
Busbar :
800A TPN Al busbar. Busbar shall be insulated with heat shrinkable sleeves and shall be color coded.
Outgoings :
2 Nos. 200 A TP MCCB (Ics=25 kA)

Ru-Tech Services Inc. Page-10 Electrical BOQ.xls


SUBHEAD IX: DISTRIBUTION LT PANELS

UNIT RATES AMOUNT


Sl. No. DESCRIPTION OF ITEM UNIT QTY. In Words
In Fig. (Rs.)
(Rs.)
2 Nos. 150 A TP MCCB (Ics=25 kA)
1 No. 125 A TP MCCB (Ics=25 kA)
2 Nos. 100 A TP MCCB (Ics=25 kA)

Ru-Tech Services Inc. Page-11 Electrical BOQ.xls


SUBHEAD IX: DISTRIBUTION LT PANELS

UNIT RATES AMOUNT


Sl. No. DESCRIPTION OF ITEM UNIT QTY. In Words
In Fig. (Rs.)
(Rs.)
1 No. 63 A TP MCCB (Ics=25 kA)
All the O/G shall have with ON/OFF indication lamp

4.1 PROFESSIONAL STUDIES SMB-GF


Supply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,
AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thick
CRCA sheet complete with busbars, meters, indicating lamps, protection fuses, interconnections and
having following incoming and outgoing as per the SLD and specifications . Set 1
Incoming
1 No. 200 Amp FP MCCB(25kA) with TMD release
1 No. Ammeter with control MCBs.
3 Nos. phase indication lamps with control fuses.
Busbars
TP+N AL Busbar shall be suitable to carry 250A continuous current.
Outgoing
5 Nos. 25 Amp TP MCB(10kA)
1 No. 40 Amp TP MCB(10kA)
4 Nos. 63 Amp TP MCB(10kA)

4.2 PROFESSIONAL STUDIES SMB-F/F


Supply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,
AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thick
CRCA sheet complete with busbars, meters, indicating lamps, protection fuses, interconnections and
having following incoming and outgoing as per the SLD and specifications . Set 1
Incoming
1 No. 150 Amp FP MCCB(25kA) with TMD release
1 No. Ammeter with control MCBs.
3 Nos. phase indication lamps with control fuses.
Busbars
TP+N AL Busbar shall be suitable to carry 200A continuous current.
Outgoing
5 Nos. 25 Amp TP MCB(10kA)
1 No. 40 Amp TP MCB(10kA)
4 Nos. 63 Amp TP MCB(10kA)

Ru-Tech Services Inc. Page-12 Electrical BOQ.xls


SUBHEAD IX: DISTRIBUTION LT PANELS

UNIT RATES AMOUNT


Sl. No. DESCRIPTION OF ITEM UNIT QTY. In Words
In Fig. (Rs.)
(Rs.)
4.3 PROFESSIONAL STUDIES SMB-S-T/F
Supply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,
AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thick
CRCA sheet complete with busbars, meters, indicating lamps, protection fuses, interconnections and
having following incoming and outgoing as per the SLD and specifications . Set 1
Incoming
1 No. 125 Amp FP MCCB(25kA) with TMD release
1 No. Ammeter with control MCBs.
3 Nos. phase indication lamps with control fuses.
Busbars
TP+N AL Busbar shall be suitable to carry 160A continuous current.
Outgoing
5 Nos. 25 Amp TP MCB(10kA)
1 No. 40 Amp TP MCB(10kA)
3 Nos. 63 Amp TP MCB(10kA)

4.4 PROFESSIONAL STUDIES UPS DB


Supply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,
AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thick
CRCA sheet complete with busbars, meters, relays, indicating lamps, protection fuses, interconnections
and having following incoming and outgoing as per the SLD and specifications. Set 1
Incoming
1 No. 100 Amp FP MCCB(25kA)
1 No. Ammeter with control MCBs.
3 Nos. phase indication lamps with control fuses.
Busbars
TP+2N Busbar(Aluminium) shall be suitable to carry 150A continuous current.
Outgoing
5 Nos. 63 Amp TP MCB(10kA)

4.5 PROFESSIONAL STUDIES UPS SUB-DB-1,2,3


Supply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,
AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thick
CRCA sheet complete with busbars, meters, relays, indicating lamps, protection fuses, interconnections
and having following incoming and outgoing as per the SLD and specifications. Set 3
Incoming
1 No. 63Amp FP MCB(10kA)
1 No. Ammeter with control MCBs.

Ru-Tech Services Inc. Page-13 Electrical BOQ.xls


SUBHEAD IX: DISTRIBUTION LT PANELS

UNIT RATES AMOUNT


Sl. No. DESCRIPTION OF ITEM UNIT QTY. In Words
In Fig. (Rs.)
(Rs.)
3 Nos. phase indication lamps with control fuses.
Busbars
TP+2N Busbar(Aluminium) shall be suitable to carry 100A continuous current.
Outgoing
4 Nos. 25 Amp TP MCB(10kA)

4.6 PROFESSIONAL STUDIES SOLAR DB


Supply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,
AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thick
CRCA sheet complete with busbars, meters, relays, indicating lamps, protection fuses, interconnections
and having following incoming and outgoing as per the SLD and specifications. Set 1
Incoming
1 No. 63A Automatic transfer switch
1 No. 63 Amp FP MCB(10kA)
1 No. Ammeter with control MCBs.
3 Nos. phase indication lamps with control fuses.
Busbars
TPN Busbar(Aluminium) shall be suitable to carry 100A continuous current.
Outgoing
9 Nos. 25 Amp TP MCB(10kA)

4.7 PROFFESSIONAL STUDY AC DISTRIBUTION PANEL


Supply, erection, testing and commissioning of AC Distribution panel fully compartmentalized (bolted type
design) metal clad, floor mounted, both side extensible type switchboard made of 2 mm CRCA sheet
suitable for 415 V, 3 phase 4 wire 50 Hz system, consisting of 3.5 strips Aluminium busbars complete
with following accessories. Set 1
Incoming :
1 No. 250A FP MCCB (Ics =35 kA ) with TMD release.
1 No. Volt meter with Selector switch.
1 No. Ammeter with Selector switch.
2 Nos. ON/OFF indicating Lamp.
3 Nos. phase indication lamps with control fuses.
Busbar :
300A TPN Al Busbar. Busbar shall be insulated with heat shrinkable sleeves and shall be color coded.

Outgoings :
3 Nos. 100 A TP MCCB (Ics=25 kA)
1 Nos. 63 A TP MCB (Ics=10 kA)

Ru-Tech Services Inc. Page-14 Electrical BOQ.xls


SUBHEAD IX: DISTRIBUTION LT PANELS

UNIT RATES AMOUNT


Sl. No. DESCRIPTION OF ITEM UNIT QTY. In Words
In Fig. (Rs.)
(Rs.)
All the O/G shall have with ON/OFF indication lamp.

5.0 FINE ARTS MAIN LT PANEL


Supply, erection, testing and commissioning of LT panel fully compartmentalized (bolted type design)
metal clad, floor mounted, both side extensible type switchboard made of 2 mm CRCA sheet suitable for
415 V, 3 phase 4 wire 50 Hz system, consisting of 3.5 strips Aluminum busbars complete with following
accessories. Set 1
Incoming :
1 no. 800A FP MDO ACB with microprocessor based O/L & S/C Protection
1 No. Multifunction meter with control MCBs.
2 Nos. ON/OFF indicating Lamp
3 Nos. phase indication lamps with control fuses.
Busbar :
1000A TPN Al busbar. Busbar shall be insulated with heat shrinkable sleeves and shall be color coded.

Outgoings :
3 Nos. 200 A TP MCCB (Ics=25 kA)
3 Nos.160 A TP MCCB (Ics=25 kA)
4 Nos. 100 A TP MCCB (Ics=25 kA)
All the O/G shall have with ON/OFF indication lamp

5.1 FINE ARTS SMB- 2 GF


Supply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,
AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thick
CRCA sheet complete with busbars, meters, indicating lamps, protection fuses, interconnections and
having following incoming and outgoing as per the SLD and specifications . Set 1
Incoming
1 No. 200 Amp FP MCCB(25kA)
1 No. Ammeter with control MCBs.
3 Nos. phase indication lamps with control fuses.
Busbars
TP+N AL Busbar shall be suitable to carry 250A continuous current.
Outgoing
8 Nos. 63 Amp TP MCB(10kA)

5.2 FINE ARTS SMB- 1 GF

Ru-Tech Services Inc. Page-15 Electrical BOQ.xls


SUBHEAD IX: DISTRIBUTION LT PANELS

UNIT RATES AMOUNT


Sl. No. DESCRIPTION OF ITEM UNIT QTY. In Words
In Fig. (Rs.)
(Rs.)
Supply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,
AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thick
CRCA sheet complete with busbars, meters, indicating lamps, protection fuses, interconnections and
having following incoming and outgoing as per the SLD and specifications . Set 1
Incoming
1 No. 200 Amp FP MCCB(25kA)
1 No. Ammeter with control MCBs.
3 Nos. phase indication lamps with control fuses.
Busbars
TP+N AL Busbar shall be suitable to carry 250A continuous current.
Outgoing
4 Nos. 25 Amp TP MCB(10kA)
4 Nos. 63 Amp TP MCB(10kA)

5.3 FINE ARTS SMB- FF , SF


Supply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,
AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thick
CRCA sheet complete with busbars, meters, indicating lamps, protection fuses, interconnections and
having following incoming and outgoing as per the SLD and specifications . Set 2
Incoming
1 No. 160 Amp FP MCCB(25kA)
1 No. Ammeter with control MCBs.
3 Nos. phase indication lamps with control fuses.
Busbars
TP+N AL Busbar shall be suitable to carry 200A continuous current.
Outgoing
4 Nos. 25 Amp TP MCB(10kA)
4 Nos. 63 Amp TP MCB(10kA)

5.4 FINE ARTS SMB- TF


Supply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,
AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thick
CRCA sheet complete with busbars, meters, indicating lamps, protection fuses, interconnections and
having following incoming and outgoing as per the SLD and specifications . Set 1
Incoming
1 No. 100 Amp FP MCCB(25kA)
1 No. Ammeter with control MCBs.
3 Nos. phase indication lamps with control fuses.

Ru-Tech Services Inc. Page-16 Electrical BOQ.xls


SUBHEAD IX: DISTRIBUTION LT PANELS

UNIT RATES AMOUNT


Sl. No. DESCRIPTION OF ITEM UNIT QTY. In Words
In Fig. (Rs.)
(Rs.)
Busbars
TP+N AL Busbar shall be suitable to carry 125A continuous current.
Outgoing
4 Nos. 25 Amp TP MCB(10kA)
4 Nos. 63 Amp TP MCB(10kA)

Ru-Tech Services Inc. Page-17 Electrical BOQ.xls


SUBHEAD IX: DISTRIBUTION LT PANELS

UNIT RATES AMOUNT


Sl. No. DESCRIPTION OF ITEM UNIT QTY. In Words
In Fig. (Rs.)
(Rs.)
5.5 FINE ARTS UPS DB
Supply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,
AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thick
CRCA sheet complete with busbars, meters, relays, indicating lamps, protection fuses, interconnections
and having following incoming and outgoing as per the SLD and specifications. Set 1
Incoming
1 No. 100Amp FP MCCB(Ics=25kA)
1 No. Ammeter with control MCBs.
3 Nos. phase indication lamps with control fuses.
Busbars
TP+2N Busbar(Aluminium) shall be suitable to carry 125A continuous current.
Outgoing
10 Nos. 25 Amp TP MCB(10kA)

5.6 FINE ARTS SOLAR DB


Supply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,
AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thick
CRCA sheet complete with busbars, meters, relays, indicating lamps, protection fuses, interconnections
and having following incoming and outgoing as per the SLD and specifications. Set 1
Incoming
1 No. 100A Automatic transfer switch
1 No. 100 Amp FP MCCB(25kA)
1 No. Ammeter with control MCBs.
3 Nos. phase indication lamps with control fuses.
Busbars
TPN Busbar(Aluminium) shall be suitable to carry 125A continuous current.
Outgoing
10 Nos. 25 Amp TP MCB(10kA)

5.7 FINE ARTS AC DISTRIBUTION PANEL


Supply, erection, testing and commissioning of AC Distribution panel fully compartmentalized (bolted type
design) metal clad, floor mounted, both side extensible type switchboard made of 2 mm CRCA sheet
suitable for 415 V, 3 phase 4 wire 50 Hz system, consisting of 3.5 strips Aluminium busbars complete
with following accessories. Set 1
Incoming :
1 No. 500 A FP MCCB (Ics= 35 kA ) with TMD release.
1 No. Volt meter with Selector switch.
1 No. Ammeter with Selector switch.

Ru-Tech Services Inc. Page-18 Electrical BOQ.xls


SUBHEAD IX: DISTRIBUTION LT PANELS

UNIT RATES AMOUNT


Sl. No. DESCRIPTION OF ITEM UNIT QTY. In Words
In Fig. (Rs.)
(Rs.)
2 Nos. ON/OFF indicating Lamp.
3 Nos. phase indication lamps with control fuses.
Busbar :
630 A TPN Al Busbar. Busbar shall be insulated with heat shrinkable sleeves and shall be color coded.

Outgoings :
4 Nos. 100 A TP MCCB (Ics=25 kA)
5 Nos. 63 A TP MCB (Ics=10kA)
All the O/G shall have with ON/OFF indication lamp

6.0 FASHION DESIGN MAIN LT PANEL


Supply, erection, testing and commissioning of LT panel fully compartmentalized (bolted type design)
metal clad, floor mounted, both side extensible type switchboard made of 2 mm CRCA sheet suitable for
415 V, 3 phase 4 wire 50 Hz system, consisting of 3.5 strips Aluminum busbars complete with following
accessories. Set 1
Incoming :
1 no. 1000A FP MDO ACB with microprocessor based O/L & S/C Protection
1 No. Multifunction meter with control MCBs.
2 Nos. ON/OFF indicating Lamp
3 Nos. phase indication lamps with control fuses.
Busbar :
1250A TPN Al busbar. Busbar shall be insulated with heat shrinkable sleeves and shall be color coded.

Outgoings :
1 Nos. 125 A TP MCCB (Ics=25 kA)
3 Nos. 315 A TP MCCB (Ics=25 kA)
4 Nos. 200 A TP MCCB (Ics=25 kA)
2 Nos. 160 A TP MCCB (Ics=25 kA)
1 Nos. 100 A TP MCCB (Ics=25 kA)
All the O/G shall have with ON/OFF indication lamp

6.1 FASHION DESIGN SMB-1 SF


Supply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,
AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thick
CRCA sheet complete with busbars, meters, indicating lamps, protection fuses, interconnections and
having following incoming and outgoing as per the SLD and specifications . Set 1
Incoming
1 No. 315 Amp FP MCCB(35kA)

Ru-Tech Services Inc. Page-19 Electrical BOQ.xls


SUBHEAD IX: DISTRIBUTION LT PANELS

UNIT RATES AMOUNT


Sl. No. DESCRIPTION OF ITEM UNIT QTY. In Words
In Fig. (Rs.)
(Rs.)
1 No. Ammeter with control MCBs.
3 Nos. phase indication lamps with control fuses.
Busbars
TP+N AL Busbar shall be suitable to carry 400A continuous current.
Outgoing
7 Nos. 25 Amp TP MCB(10kA)
5 Nos. 40 Amp TP MCB(10kA)
3 Nos. 63 Amp TP MCB(10kA)

6.2 FASHION DESIGN SMB-1 GF


Supply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,
AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thick
CRCA sheet complete with busbars, meters, indicating lamps, protection fuses, interconnections and
having following incoming and outgoing as per the SLD and specifications . Set 1
Incoming
1 No. 300 Amp FP MCCB(35kA)
1 No. Ammeter with control MCBs.
3 Nos. phase indication lamps with control fuses.
Busbars
TP+N AL Busbar shall be suitable to carry 400A continuous current.
Outgoing
7 Nos. 25 Amp TP MCB(10kA)
6 Nos. 40 Amp TP MCB(10kA)
2 Nos. 63 Amp TP MCB(10kA)

6.3 FASHION DESIGN SMB-2 GF


Supply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,
AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thick
CRCA sheet complete with busbars, meters, indicating lamps, protection fuses, interconnections and
having following incoming and outgoing as per the SLD and specifications . Set 1
Incoming
1 No. 200 Amp FP MCCB(25kA)
1 No. Ammeter with control MCBs.
3 Nos. phase indication lamps with control fuses.
Busbars
TP+N AL Busbar shall be suitable to carry 250A continuous current.
Outgoing
4 Nos. 25 Amp TP MCB(10kA)

Ru-Tech Services Inc. Page-20 Electrical BOQ.xls


SUBHEAD IX: DISTRIBUTION LT PANELS

UNIT RATES AMOUNT


Sl. No. DESCRIPTION OF ITEM UNIT QTY. In Words
In Fig. (Rs.)
(Rs.)
6 Nos. 63 Amp TP MCB(10kA)

Ru-Tech Services Inc. Page-21 Electrical BOQ.xls


SUBHEAD IX: DISTRIBUTION LT PANELS

UNIT RATES AMOUNT


Sl. No. DESCRIPTION OF ITEM UNIT QTY. In Words
In Fig. (Rs.)
(Rs.)
6.4 FASHION DESIGN SMB-FF
Supply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,
AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thick
CRCA sheet complete with busbars, meters, indicating lamps, protection fuses, interconnections and
having following incoming and outgoing as per the SLD and specifications . Set 1
Incoming
1 No. 200 Amp FP MCCB(25kA)
1 No. Ammeter with control MCBs.
3 Nos. phase indication lamps with control fuses.
Busbars
TP+N AL Busbar shall be suitable to carry 250A continuous current.
Outgoing
5 Nos. 25 Amp TP MCB(10kA)
5 Nos. 63 Amp TP MCB(10kA)

6.5 FASHION DESIGN SMB-2 SF


Supply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,
AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thick
CRCA sheet complete with busbars, meters, indicating lamps, protection fuses, interconnections and
having following incoming and outgoing as per the SLD and specifications . Set 1
Incoming
1 No. 160 Amp FP MCCB(25kA)
1 No. Ammeter with control MCBs.
3 Nos. phase indication lamps with control fuses.
Busbars
TP+N AL Busbar shall be suitable to carry 200A continuous current.
Outgoing
4 Nos. 25 Amp TP MCB(10kA)
4 Nos. 63 Amp TP MCB(10kA)

6.6 FASHION DESIGN SMB-TF


Supply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,
AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thick
CRCA sheet complete with busbars, meters, indicating lamps, protection fuses, interconnections and
having following incoming and outgoing as per the SLD and specifications . Set 1
Incoming
1 No. 160 Amp FP MCCB(25kA)
1 No. Ammeter with control MCBs.

Ru-Tech Services Inc. Page-22 Electrical BOQ.xls


SUBHEAD IX: DISTRIBUTION LT PANELS

UNIT RATES AMOUNT


Sl. No. DESCRIPTION OF ITEM UNIT QTY. In Words
In Fig. (Rs.)
(Rs.)
3 Nos. phase indication lamps with control fuses.
Busbars
TP+N AL Busbar shall be suitable to carry 200A continuous current.
Outgoing
4 Nos. 25 Amp TP MCB(10kA)
3 Nos. 63 Amp TP MCB(10kA)
1 Nos. 40 Amp TP MCB(10kA)

6.7 FASHION DESIGN UPS DB


Supply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,
AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thick
CRCA sheet complete with busbars, meters, relays, indicating lamps, protection fuses, interconnections
and having following incoming and outgoing as per the SLD and specifications. Set 1
Incoming
1 No. 200Amp FP MCCB(Ics=25kA)
1 No. Ammeter with control MCBs.
3 Nos. phase indication lamps with control fuses.
Busbars
TP+2N Busbar(Aluminium) shall be suitable to carry 250A continuous current.
Outgoing
5 Nos. 63 Amp TP MCB(10kA)

6.8 FASHION DESIGN UPS SUB-DB-1,2


Supply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,
AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thick
CRCA sheet complete with busbars, meters, relays, indicating lamps, protection fuses, interconnections
and having following incoming and outgoing as per the SLD and specifications. Set 2
Incoming
1 No. 63Amp FP MCB(10kA)
1 No. Ammeter with control MCBs.
3 Nos. phase indication lamps with control fuses.
Busbars
TP+2N Busbar(Aluminium) shall be suitable to carry 100A continuous current.
Outgoing
6 Nos. 25 Amp TP MCB(10kA)

6.9 FASHION DESIGN UPS SUB-DB-3

Ru-Tech Services Inc. Page-23 Electrical BOQ.xls


SUBHEAD IX: DISTRIBUTION LT PANELS

UNIT RATES AMOUNT


Sl. No. DESCRIPTION OF ITEM UNIT QTY. In Words
In Fig. (Rs.)
(Rs.)
Supply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,
AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thick
CRCA sheet complete with busbars, meters, relays, indicating lamps, protection fuses, interconnections
and having following incoming and outgoing as per the SLD and specifications. Set 1

Ru-Tech Services Inc. Page-24 Electrical BOQ.xls


SUBHEAD IX: DISTRIBUTION LT PANELS

UNIT RATES AMOUNT


Sl. No. DESCRIPTION OF ITEM UNIT QTY. In Words
In Fig. (Rs.)
(Rs.)
Incoming
1 No. 63Amp FP MCB(10kA)
1 No. Ammeter with control MCBs.
3 Nos. phase indication lamps with control fuses.
Busbars
TP+2N Busbar(Aluminium) shall be suitable to carry 100A continuous current.
Outgoing
9 Nos. 25 Amp TP MCB(10kA)

6.10 FASHION DESIGN SOLAR DB


Supply, installation, testing & commissioning of LT Panel for 415 volts (nominal) 3 phase 4 wire, 50 Hz,
AC, totally enclosed type, wall mounted dust and vermin proof indoor type fabricated from 2mm thick
CRCA sheet complete with busbars, meters, relays, indicating lamps, protection fuses, interconnections
and having following incoming and outgoing as per the SLD and specifications. Set 1
Incoming
1 No. 125A Automatic transfer switch
1 No. 125 Amp FP MCCB(25kA)
1 No. Ammeter with control MCBs.
3 Nos. phase indication lamps with control fuses.
Busbars
TPN Busbar(Aluminium) shall be suitable to carry 150A continuous current.
Outgoing
10 Nos. 25 Amp TP MCB(10kA)

6.11 FASHION DESIGN AC DISTRIBUTION PANEL


Supply, erection, testing and commissioning of AC Distribution panel fully compartmentalized (bolted type
design) metal clad, floor mounted, both side extensible type switchboard made of 2 mm CRCA sheet
suitable for 415 V, 3 phase 4 wire 50 Hz system, consisting of 3.5 strips Aluminium busbars complete
with following accessories. Set 1
Incoming :
1 No. 1000A FP MDO ACB with microprocessor based O/L & S/C Protection.
1 No. Volt meter with Selector switch.
1 No. Ammeter with Selector switch.
2 Nos. ON/OFF indicating Lamp.

Ru-Tech Services Inc. Page-25 Electrical BOQ.xls


SUBHEAD IX: DISTRIBUTION LT PANELS

UNIT RATES AMOUNT


Sl. No. DESCRIPTION OF ITEM UNIT QTY. In Words
In Fig. (Rs.)
(Rs.)
3 Nos. phase indication lamps with control fuses.
Busbar :
1000A TPN Al busbar. Busbar shall be insulated with heat shrinkable sleeves and shall be color coded.

Outgoings :
7 Nos. 100 A TP MCCB (Ics=25 kA)
8 Nos. 63 A TP MCB (Ics=10 kA)
All the O/G shall have with ON/OFF indication lamp

TOTAL OF SUBHEAD IX CARRIED OVER TO SUMMARY OF ELECTRICAL WORKS

Ru-Tech Services Inc. Page-26 Electrical BOQ.xls


SUB-HEAD X: FIRE DETECTION AND ALARM

Sl. No. DESCRIPTION OF ITEM UNIT QTY. UNIT RATES AMOUNT


In Fig. (Rs.) In Words (Rs.)

1 Supply, Installation, Testing & Commissioning of Microprocessor


based addressable Fire Alarm Control Panel with with built-in Battery
Back-up for identification of the fire location and fire alarm system
control( each Loop consists of 199 devices and 199 detector). The
panel shall have 240 volts AC power supply, automatic battery Nos 6
charger, 24 volts, sealed lead acid maintenance free batteries
sufficient for 24 hours normal working and then be capable of
operating the system for 30 minutes during emergency condition as
detailled.
2 Supply installation testing and commossioning of Repeater panel
with LCD display with battery & battery charger completed as per
specification as required. No 26
3 Supply, Installation, Testing & Commissioning of addressable Multi-
criteria photo thermal smoke detector including the cost of base plate Nos 204
mounting accessories as per detailed.
4 Supply, Installation, Testing & Commissioning of plug-in type
addressable (ROR + Fixed temp) heat detectors including the cost Nos 773
of base plate mounting accessories as per detailed.
5 Supply, Installation, Testing & Commissioning of Addressable type
Nos 2
Duct Detector complete as per detailed.
6 Supply, Installation, Testing & Commissioning of Control Modules for
trip off of (AHU+Fire Damper etc) and as required. The control
Nos 4
module should have 2 independent outputs including the cost of
mounting accessories complete as per detailed.
7 Supply, Installation, Testing & Commissioning of Addressable
Manual Call Point break glass type with Alarm LED and mounting Nos 60
accessories complete as per detailed.
8 Supply, Installation, Testing & Commissioning of Monitor Module with
minimum of 2 monitoring inputs for various applications complete as Nos. 15
per detailed.

Ru-Tech Services Inc. Page-1 Electrical BOQ.xls


SUB-HEAD X: FIRE DETECTION AND ALARM

Sl. No. DESCRIPTION OF ITEM UNIT QTY. UNIT RATES AMOUNT


In Fig. (Rs.) In Words (Rs.)

9 Supply, Installation, Testing & Commissioning of Hooter including the


Nos 63
cost of mounting complete as per detailed.
10 Supply, Installation, Testing & Commissioning of Response indicator
Nos 210
complete as per detailed.
11 Supply,Installation ,Testing & Commissioning of Fire exit sign
(Illuminated) made from etched sheet with LED illumination and all
Nos 88
electrical accessories including battery and battery charger etc. as
per detailled.
12 Supplying and fixing of 2X 1.5 sq. mm PVC insulated Copper
RM 14655
conductor wire.
13 Supplying and fixing of 4X 1.5 sq. mm PVC insulated Copper
RM 3690
conductor wire.
14 Supplying and fixing of following sizes of MS conduit along with the
accessories in surface/ recess including cutting the wall and making
good the same in case of recessed conduit as required.
a) 25 mm Metre 12842

TOTAL OF SUBHEAD XI OF ELECTRICAL WORKS

Ru-Tech Services Inc. Page-2 Electrical BOQ.xls


LIST OF APPROVED MANUFACTURERS
S.NO. Brief Description of Material Name of Approved Makes

1 11 KV VCB PANEL BOARD. SIEMENS / AREVA / ABB / CROMPTON GREAVES /


KIRLOSKAR

2 XLPE 11 KV CABLE CCI / UNIVERSAL / NICCO / POLYCAB / HAVELLS

3 HT TERMINATIONS CAB SEAL / RAYCHEM / YAMUNA GAS

4 OIL TYPE TRANSFORMERS CROMPTON GREAVES / EMCO / KIRLOSKAR / ECE /


AREVA

5 OLTC OLG / CTR / CROMPTON

6 DIESEL ENGINE CATERPILLAR / CUMMINS / KOHLER / MTU / PERKINS

7 ALTERNATOR STAMFORD / CATERPILLAR / LEROY SOMER & CONTROL

8 BATTERY CHARGER EXPO-FYN / AMAR RAJA / CHHABI ELECTRICALS /


VOLSTAT

9 BATTERIES EXCIDE / AMARA RAJA / STANDARD FARRUKAWA /


OKAYA

10 CAPACITORS L & T / GE / ABB / EPCOS

11 APFCR L & T / SYSTEM SENSOR / ABB / SIEMENS

12 PROTECTION RELAY SIEMENS / EASUN / ABB / L & T ( PNB - Gold Series)

13 DIGITAL/ MICROPROCESSOR ABB / L & T / NEPTUNE / SECURE / ENERCON / FPI


BASED ENERGY METERS

14 LT CABLES HAVELLS / TECHNOCARE / NICCO / FINOLEX / POLYCAB /


ECHO / SKYTONE / LAPP CABLE

15 PVC INSULATED WIRES HAVELLS / TECHNOCARE / NICCO / FINOLEX / POLYCAB /


ECHO / SKYTONE / LAPP CABLE

16 CAT - 6 CABLES AWAYA / LAPPCABLE

17 RG - 6 / RG - 11 COMSOB / SKYLINE / PLYCAB

18 TELEPHONE TAG BLOCKS MK / L K FUGA / CLIPSAL / LEGRAND / KRON

19 CABLE TRAY PILCO / UBITECH / RICO STEEL / STEELCO


LIST OF APPROVED MANUFACTURERS
S.NO. Brief Description of Material Name of Approved Makes
20 CABLE COMPRESSION GLANDS COMET / PEECO / RAYCHEM

21 CABLE LUGS DOWELS / RAYCHEM

22 MODULAR RANGE OF HONEY WELL / CLIPSAL / LEGRAND / CRABTREE /


SWITCHES, SOCKET HAVELLS

23 INDUSTRIAL SOCKET & PLUGS INDO ASIAN / SIEMENS / SCHNEIDER / CROMPTON /


LEGRAND/ BCH / HAGGER

24 STEEL CONDUIT BEC / AKG / STEEL KRAFT

25 LIGHT FIXTURES PHILIPS / BAJAJ / CROMPTON / HAVELLS / THORN

26 CEILING FANS CROMPTON GREAVES / HAVELLS / USHA / KHAITAN

27 EXHAUST FAN CROMPTON GREAVES / USHA / KHAITAN / HAVELLS

28 MV PANELS TRICOLITE / MILESTONE SWITCHGEARS /


MADHUELECTRICALS/ UBITECH / CONTROLS &
SWITCHGEARS

29 BUSDUCTS / RISING MAIN TRICOLITE / MILESTONE SWITCHGEARS /


MADHUELECTRICALS/ UBITECH / CONTROLS &
SWITCHGEARS / ZETA

30 AIR CIRCUIT BREAKER L & T (U Power ) / SIEMENS / ABB / SCHNEIDER(


MASTERPACK)

31 MCCB SCHNEIDER (COMPAC) / SIEMENS / HAGGER / ABB /


LEGRAND

32 MCB-DB's, MCB, ELCB MCB-Isolator


SCHNEIDER
etc. (COMPAC) / SIEMENS / L & T / ABB /
LEGRAND / INDOASIAN / HAVELLS / MK

33 FSU/SDFU/SFU L & T/ ABB / SIEMENS / HAVELLS / C & S

34 Power Contactors L & T/ ABB / SIEMENS / SCHNEIDER / C & S

35 Measuring Instruments AE / MECO / Rishline (L & T) / RAAS Controls


NOTE:
1. Above makes of materials are approved subject to their meeting the tender specifications
& requirements. Contractor however shall seek approval of specific make from the engineer
incharge before commencement the work. The final choice of make to be used in the work
will rest with RITES and the decision of the Engineer -in-charge shall be final & binding on
the contractor.
2. For any item not covered in the above list, the contractor shall get the make & sample
approved from the Engineer-in-charge before procurement. The final choice of make to be
used in the work will rest with RITES and the decision of the engineer -in-charge shall be
final & binding on the contractor in this respect.