Marib Power Project 2nd Stage Tenderer:

Lot 2b, 132 kV Substations - Back-bone Unit Data


Connection

Technical Data required offered

B1.3.1: 132 kV Switchyards

132 kV Disconnector with Earthing Switch


manufacturer
applicable standard IEC 62271-102
type outdoor type
type of operation center break
highest system voltage kV 145
rated normal current A 1250
rated lightning impulse withstand voltage kVpeak 650
rated power frequency withstand voltage kVrms 275
rated frequency Hz 50
number of phases 3
rated short time current (1s) kA 31,5
rated short-circuit making current kApeak 80
power supply V 110 DC/230 AC
minimum creepage distance mm 6525

132 kV Busbar Disconnector


applicable standard IEC 62271-102
type outdoor type
type of operation two column
rotary
highest system voltage kV 145
rated normal current A 1250
rated lightning impulse withstand voltage kVpeak 650
rated power frequency withstand voltage kVrms 275
rated frequency Hz 50
number of phases 3
rated short time current (1s) kA 31,5
rated short-circuit making current kApeak 80
power supply V 110 DC/230 AC

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 1


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.1: 132 kV Switchyards

132 kV Circuit Breaker


manufacturer
applicable standard IEC 62271
type of circuit breaker outdoor type
type of arc quenching medium SF6
highest system voltage kV 145
rated lightning impulse withstand voltage kVpeak 650
rated power frequency withstand voltage kVrms 275
rated frequency Hz 50
number of phases 3
rated normal current A A 1250
rated short-circuit breaking current kA 31.5
rated peak withstand current kApeak 80
number of tripping coils 2
number of closing coils 1
rated operating sequence (three phase auto reclosing) 0 - 0.3 s – CO -
1 min – CO
maximum breaking time msec. 60
minimum creepage distance mm 6525
power supply V 110 DC/230 AC
first-pole-to-clear factor 1.3
drive - 1 pole
type of drive - spring type

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 2


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.1: 132 kV Switchyards

132 kV Current Transformer


manufacturer
applicable standard IEC 60044-1
type
highest system voltage kV 145
rated short time current (1s) kA 31,5
rated primary currents:
for line feeders A 600/1200
for 45 MVA transformer feeders A 100/200
number of cores
for measuring purpose 1
for protection purposes 3
rated secondary currents:
for measuring A 1
for protection A 1/1/1
rated burden 30
for measuring core VA 15
for protection core VA 60
accuracy class
for measuring - 0.5 M 5
for protection - 5 P 20
minimum creepage distance mm 6525

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 3


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.1: 132 kV Switchyards

132 kV Capacitive Voltage Transformer


manufacturer
applicable standard IEC 60 044-5
type Outdoor type
rated primary voltage kV 132/√3
rated secondary voltages (independent)
kV 0.11/√3
kV 0.11/3
rated output VA/VA 150/150
accuracy class:
for measuring 0.5
for protection 5P
minimum creepage distance mm 6525

132 kV Gapless Zinc-Oxide Lightning Arrester


manufacturer
applicable standard IEC 600 99/4
type Outdoor type
rated continuous voltage kV rms 120
rated discharge current kA 10
rated frequency Hz 50
arrester classification heavy duty
minimum creepage distance mm 6525

Lightning Arrester Discharge Counter


type Outdoor type
counter indication Digital
protection class IP54
number per 3 arresters 1

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 4


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.1: 132 kV Switchyards

Busbar Conductors
type / material 2 x AAAC 400
rated current (with max. allowed 30 K temperature rise A 1250
above max. ambient temperature)
branch connections 1 x AAAC 400

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 5


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.2 132 gas insulated switchgear

Electrical Characteristic
type -
nominal voltage kV 132
rated voltage kV 145
rated frequency Hz 50
Basic Data
manufacturer -

place of manufacture -

manufacturer reference/designation -

lightning impulse withstand voltage kV(peak) 650


power frequency withstand voltage kV(rms) 275
peak withstand current kA(peak) 80
short time withstand current (1sec) kA(rms) 31.5
total thermal losses at full load kW
maximum guaranteed gas loss from any compartment % per <1
annum
protection class of switchgear cubicles - IP 52
safety requirements as per 1.5.3 of B1 - Yes
single-phase enclosure as per 1.5.7 of B1 - Yes
material of encapsulation: - yes
aluminum alloy - Yes/no
or
stainless steel - Yes/no
Manufacture and tests shall comply with but shall be not
limited to the following IEC standards as well as
provisions in sections A7 and B1 of this tender:

bus bars IEC 60517, 60094 - Yes


circuit breakers IEC 62271-100 - Yes
current transformers IEC 60044-1 - Yes
voltage transformers IEC 60044-2 - Yes
surge arrestors IEC 60099-4, 99-1, 99-3 - Yes

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 6


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.2 132 gas insulated switchgear


Main dimensions (per feeder)
manufacturer -

place of manufacture -

manufacturer reference/designation -

height x width x depth m


weight of feeder t
weight of heaviest single part t

Busbars
manufacturer -

place of manufacture -

manufacturer reference/designation -

rated current A 2000


2
cross-section of busbar conductor mm
busbar material - aluminum
single-phase enclosure -
material of encapsulation - yes
aluminum alloy Yes/no
or
stainless steel Yes/no
diameter of busbar duct housing mm
rated pressure of SF6 gas at 40°C Kpa
maximum and minimum admissible pressure of SF6 gas Kpa
at 40°C
volume of largest busbar compartment m3
puncturing time msec 500
configuration - single bus
(with bus
coupler)

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 7


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.2 132 gas insulated switchgear

Feeders (outgoing, incoming)


manufacturer -

place of manufacture -

manufacturer reference/designation -
rated current A
cross-section of bus-duct conductor mm2
volume of largest feeder compartment m3

Circuit Breakers
manufacturer -

place of manufacture -

manufacturer reference/designation -

type -
single-phase enclosure -
material of encapsulation: - Yes
aluminum alloy - Yes/no
or
stainless steel - Yes/no
rated voltage kV
rated breaker current:
transformer feeder A 1250
line feeder A 1250
coupling feeder A 2000
rated short-circuit breaking current (1 sec) kA 31.5
peak making current kA 80
rated cable charging breaking current A
rated small inductive breaking currents A
rated lightning impulse
withstand voltage phase to earth kV(peak)
across isolating distance kV(peak)

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 8


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.2 132 gas insulated switchgear


rated switching impulse
withstand voltage phase to earth kV(peak)
across isolating kV(peak)
distance
rated power frequency
withstand voltage phase to earth kV(rms)
across isolating kV(rms)
distance
rated
total breaking time Msec ′50
total making time Msec ′80
volume of breaker compartment M3
rated pressure of SF6 gas at 40°C Kpa
maximum and minimum admissible pressure of SF6 gas Kpa
at 40°C
rated operating sequence for OHL feeder - 0-0.3s-CO-
1min-CO
first pole to clear factor - 1.5
auto reclosing facilities for line feeder bays - Single and 3
phase

Driving Mechanism
manufacturer -

place of manufacture -

manufacturer reference/designation -

type
spring - Yes/no
or
hydraulic - Yes/no
rating of drive motor W
auto-reclose, single-phase/three-phase -
auto-reclose sequence -

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 9


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.2 132 gas insulated switchgear


Compressor or Oil Pump
manufacturer -

place of manufacture -

manufacturer reference/designation -

type -
rated pressure bar
rated flow 1/min
rated power kW

Disconnector
manufacturer -

place of manufacture -

manufacturer reference/designation -
standard - IEC 62271,
60265 part 2,
IEC 60517
type -
rated current A 1250
(full load transfer capability from one bus to another
without load reduction or interruption)

rated lightning impulse


withstand voltage phase to earth kV(peak) 650
across isolating kV(peak) 750
distance
rated switching impulse
withstand voltage phase to earth kV(peak)
across isolating kV(peak)
distance
rated power frequency
withstand voltage phase to earth kV(rms)
across isolating kV(rms)
distance
rating of drive motor W
motor drive supply (AC or DC) -
closing/opening time sec / sec

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 10


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.2 132 gas insulated switchgear


Maintenance Earthing Switch
manufacturer -

place of manufacture -

manufacturer reference/designation -
standard - IEC 62271-102,
60517
type -
driving mechanism -
motor drive supply (AC or DC) -
short time current withstand (1 sec) kA (sec) 31.5
peak current withstand kA
closing / opening time sec/sec

High Speed Earthing Switch


manufacturer -

place of manufacture -

manufacturer reference/designation -

standard - IEC 62271-102,


60517
type -
driving mechanism -
motor drive supply (AC or DC) -
rated peak current withstand kA
rated short time withstand current (1 sec) kA (sec) 31.5
closing / opening time sec/sec

Current Transformer
manufacturer -

place of manufacture -

manufacturer reference/designation -

type - Toroidal, GIS


enclosed
rated primary current A Single line
diagram
number of primary windings n 2/1

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 11


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.2 132 gas insulated switchgear


rated secondary current A 1
number of secondary windings
for measuring n 1
for protection n 5
accuracy class for metering and billing - 0.2
accuracy class for protection - 5P20, class X
Ratio

Cable Bay
power rating (min. burden) (to be justified by successful VA 30
tenderer)
Ratings:
measuring: core 4 A 1000-500/1
protection: core 1 A 1000-500/1
core 2 A 1000-500/1
core 3 A 1000-500/1
core 5 A 2000/1
core 6 A 2000/1
Accuracy Class:
protection 1 Cl X
protection 2 Cl X
protection 3 Cl 5P20
measuring 4 / billing Cl 0.2
protection 5 Cl X
protection 6 Cl X

Rated Output:
protection 1 VA
protection 2 VA
protection 3 VA
measuring 4 / billing VA
protection 5 VA
protection 6 VA
Saturation Factor:
protection 1 n
protection 2 n
protection 3 n
measuring 4 / billing n
protection 5 n
protection 6 n
dynamic current x IN
thermal current x IN

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 12


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.2 132 gas insulated switchgear

Ratings:

Transformer Bay

measuring: core 3 A 400-200/1


protection: core 1 A 400-200/1
core 2 A 400-200/1
core 4 A 400-200/1
core 5 A 2000/1
core 6 A 2000/1
Accuracy Class:
protection 1 Cl X
protection 2 Cl X
protection 3 Cl 5P20
measuring 4 / billing Cl 0.2
protection 5 Cl X
protection 6 Cl X

Rated Output:
protection 1 VA
protection 2 VA
protection 3 VA
measuring 4 / billing VA
protection 5 VA
protection 6 VA
Saturation Factor:
protection 1 n
protection 2 n
protection 3 n
measuring 4 / billing n
protection 5 n
protection 6 n
dynamic current x IN
thermal current x IN

Transformer Bay Outgoing Feeder


HV Neutral CT:
protection: core 1 A 400-200/1
core 2 A 400-200/1

Accuracy Class:
protection 1 Cl 5P20
protection 2 Cl X

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 13


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.2 132 gas insulated switchgear


Rated Output:
protection 1 VA
protection 2 VA
Saturation Factor:
protection 1 n
protection 2 n
dynamic current x IN
thermal current x IN

LV Neutral CT:
protection: core 1 A 1600-800/1
core 2 A 1600-800/1

Accuracy Class:
protection 1 Cl 5P15
protection 2 Cl X

Rated Output:
protection 1 VA
protection 2 VA
Saturation Factor:
protection 1 n
protection 2 n
dynamic current x IN
thermal current x IN

Bus Section CT No. 1:

Protection: core 1 A 2000/1


core 2 A 2000-1000/1
Accuracy Class:
protection 1 Cl X
protection 2 Cl 5P20

Rated Output:
measuring 1 VA
protection 2 VA

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 14


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.2 132 gas insulated switchgear

Bus Section CT No. 2:


protection: core 1 A 2000/1
Accuracy Class:
protection 1 Cl X

Rated Output:
protection 2 VA

Voltage Transformer
manufacturer -

place of manufacture -

manufacturer reference/designation -

type - Inductive, SF6


gas insulated,
enclosed
burden (min) VA
rated primary voltage kV 132
3
rated secondary voltage kV 0.110 0.110
&
3 3
measuring V
protection V
Accuracy Class
measuring / billing Cl 0.2
protection Cl 3P
Rated Output:
measuring VA
protection VA

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 15


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.3: 33 kV Indoor switchgear

33 kV Indoor Switchgear
manufacturer
type - Metalclad
insulation SF6
enclosure - triple pole
primary
application standard IEC 60298
nominal system voltage kV 33
highest value of system operating voltage kV 36
range of highest voltage for equipment (IEC 60071-1)) - A
rated frequency Hz 50
rated short-circuit current, 1 sec. kArms 31,5
rated lightning impulse withstand voltage kVpeak 170
rated power frequency short duration withstand voltage kVrms 70
symmetrical breaking current kA 25
short circuit making current kApeak 80
rated current
busbar and bus coupler
- for Dhamar,Haouban, Sheban A 1250
- for Al Arish, Mansoura A 2500
outgoing feeders
- for Dhamar,Haouban, Sheban A 630
- for Al Arish, Mansoura A 1600
incoming feeder from transformer
- for Dhamar,Haouban, Sheban A 1250
- for Al Arish, Mansoura A 2500
protection class – high voltage live parts - IP 65
- low voltage compartment - IP 41
circuit breaker type - Vacuum or SF6
rated operating cycle of circuit breaker - 0-0.3 s-C0-1
min.-C0

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 16


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.3: 33 kV Indoor switchgear

rated short-circuit current, 1 sec of circuit breaker kA rms 31,5


rated peak withstand current kA peak 63
rated voltage of cb drive V 110 DC
type of earthing switch - positively
making type
type of current transformers - inductive, cast-
resin insulated
ratings primary winding:
- for , Haouban, Sheban
for line bays A 400/200
for transformer bays 45 MVA A 800/400
For transformer incomer 60MVA A 1200/600
- for Al Arish, Mansoura
for line bays A 1600/800
for transformer bays 90 MVA A 1600/800
ratings secondary winding A
- for Dhamar, Haouban, Sheban
for measuring A 1
for protection A 1/1
- for Al Arish, Mansoura
for measuring A 1
for protection A 1/1
accuracy class
- for Dhamar,Haouban, Sheban
for measuring - 0.5 M 5
for protection - 5 P 20
- for Al Arish, Mansoura
for measuring - 0.2
for protection - 5 P 20
burden VA 30
type of voltage transformers - cast-resin
insulated

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 17


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

rated primary voltage kV 33/√3

B1.3.3: 33 kV Indoor switchgear

rated secondary voltages (independent)


V 110/√3
V 110/3
rated output VA/VA 100/100
accuracy class:
- for Dhamar,Haouban, Sheban
for measuring 1.0 M
for protection 5P
- for Al Arish, Mansoura
for measuring 0.2
for protection 3P

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 18


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.4: Power and station service transformers

A. 132/33 kV Power transformers for Haouban


and Sheban Substation
manufacturer
type - 3-phase oil
immersed
applicable standards - IEC 60076,
60354
rated power
for ONAN operation
for Sheban MVA 45
for Haouban MVA 60
rated voltage kV/kV 132/33
highest system voltage kV/kV 145/36
rated frequency Hz 50
rated power frequency withstand voltage
for primary kVrms 275
for secondary kVrms 70
rated lightning impulse withstand voltage
for primary kVpeak 650
for secondary kVpeak 170
vector group - YnD1
impedance voltage at principal tapping % 9.5
voltage regulation - on-load tap
changer
tap positions - +4/-12
range of voltage regulation % +5/- 15
type of cooling - ONAN/ONAF
max. noise level (acc. to. IEC 60551) dB (A) 55
max. no-load current % In 0.2
max. ambient temperature °C 50

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 19


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.4: Power and station service transformers

temperature rise at rated power over 50°C maximum


ambient temperature
oil (upper level) °K 45
winding (average) °K 50
power supply V 110 DC/230 AC

Bushings
insulation - graded/not
graded
terminal arrangement
for primary outdoor
condenser
bushings
for secondary Air filled cable
connection box
with outdoor
bushings
rated creepage distance of bushings
for HV mm 6525
for LV mm 1620
approximate total weight to
approximate transport weight to

On-load Tap Changer


manufacturer
type - resistor
rated current A 350
rated short-time current ( 1 sec) kA 31.5
installation mode - HV side
rated operations duty (min.) No. 200.000

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 20


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.4: Power and station service transformers

Guarantee Values for 132/33 kV, 45MVA


Transformers
no load losses kW --
load losses at principal tap kW
losses of auxiliaries (fans, pumps, etc.) kW

Guarantee Values for 132/33 kV, 60 MVA


Transformers
no load losses kW --
load losses at principal tap kW
losses of auxiliaries (fans, pumps, etc.) kW

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 21


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.4: Power and station service transformers

B. 33/0.4 kV Station Earthing and Auxiliary


Transformers
manufacturer
type - 3-phase
hermetically
sealed
applicable standard - IEC 60076
rated apparent power kVA 400
rated voltage HV/LV kV 33/0.4
rated frequency Hz 50
vector group Znyn 11
impedance voltage % 6
off-load tap changer regulation - +/- 2x2,5%
type of cooling - ONAN
rated power frequency withstand voltage kV 70
rated lightning impulse withstand voltage kVpeak 170
max. noise level (acc. to. IEC 60551) dB (A) 55
max. ambient temperature °C 50
temperature rise at rated power over 50°C maximum
ambient temperature
oil (upper level) °K 45
winding (average) °K 50
power supply V 110 DC/230 AC
approximate weight kg

Guarantee values for 33/0.4 kV station auxiliary


transformers
no load losses
load losses at principal tap

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 22


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.4: Power and station service transformers

C. 132/33/11 kV Power Transformers for Al Arish


and Mansoura Substation
manufacturer
type - 3-phase oil
immersed
applicable standards - IEC 60076,
60354
rated power maximum continuous ONAF operation MVA 90
rated power minimum continuous ONAN operation MVA 63
rated voltage kV/kV 132/33/11
highest system voltage kV/kV 145/36/12
rated frequency Hz 50
rated power frequency withstand voltage
for primary kVrms 275
for secondary kVrms 70
rated lightning impulse withstand voltage
for primary kVpeak 650
for secondary kVpeak 170
vector group - Ynyn0d11
impedance voltage at principal tapping % 10
voltage regulation - on-load tap
changer
tap positions - +4/-12
range of voltage regulation % +5/- 15
type of cooling - ONAN/ONAF
max. noise level (acc. to. IEC 60551) ONAN / ONAF dB (A) 55 / 65
max. no-load current % In 0.2
max. ambient temperature °C 50
temperature rise at rated power over 50°C maximum
ambient temperature

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 23


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.4: Power and station service transformers

oil (upper level) °K 45


winding (average) °K 50
power supply V 110 DC/230 AC
Bushings
insulation - graded/not
graded
terminal arrangement
for primary outdoor
condenser
bushings
for secondary Air filled cable
connection box
with outdoor
bushings
rated creepage distance of bushings
for HV mm 6525
for LV mm 1620
approximate total weight to
approximate transport weight to

On-load Tap Changer


manufacturer
type - resistor
rated current A 400
rated short-time current (1 sec) kA 31.5
installation mode - HV side
rated operations duty (min.) No. 200.000

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 24


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.4: Power and station service transformers

Guarantee Values for 132/33/11 kV, 90MVA


Transformer
no load losses kW --
load losses at principal tap
ONAN operation kW --
ONAF operation kW --
losses of auxiliaries (fans, pumps, etc.)
ONAN operation kW --
ONAF operation kW --

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 25


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.4: Power and station service transformers

D. 33/11 kV Distribution Transformers for Al Arish


Substation
manufacturer
type - 3-phase oil
immersed
applicable standards - IEC 60076,
60354
rated power maximum continuous ONAF operation MVA 20
rated power minimum continuous ONAN operation MVA 15
rated voltage kV/kV 33/11
highest system voltage kV/kV 36/12
rated frequency Hz 50
rated power frequency withstand voltage
for primary kVrms 70
for secondary kVrms 28
rated lightning impulse withstand voltage
for primary kVpeak 170
for secondary kVpeak 95
vector group - DYN11
impedance voltage at principal tapping % 11.7
voltage regulation - on-load tap
changer
tap positions - +8/-8
range of voltage regulation % +10/-10
type of cooling - ONAN/ONAF
max. noise level (acc. to. IEC 60551) ONAN / ONAF dB (A) 55 / 65
max. no-load current % In 0.2
max. ambient temperature °C 50
temperature rise at rated power over 50°C maximum
ambient temperature

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 26


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.4: Power and station service transformers

oil (upper level) °K 45


winding (average) °K 50
power supply V 110 DC/230 AC
Bushings
insulation - graded/not
graded
terminal arrangement
for primary Air filled cable
connection box
with outdoor
bushings
for secondary Air filled cable
connection box
with outdoor
bushings
rated creepage distance of bushings
for HV mm 1620
for LV mm 540
approximate total weight to
approximate transport weight to

On-load tap changer


manufacturer
type - resistor
rated current A 350
rated short-time current (1 sec) kA 31.5
installation mode - HV side
rated operations duty (min.) No. 200.000

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 27


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.4: Power and station service transformers

Guarantee Values for 33/11 kV Distribution


Transformers for Al Arish Substation
no load losses kW --
load losses at principal tap
ONAN operation kW --
ONAF operation kW --
losses of auxiliaries (fans, pumps, etc.)
ONAN operation kW --
ONAF operation kW --

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 28


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.4: Power and station service transformers

E. 11/0.4 kV Station Auxiliary Transformer


manufacturer
type - 3-phase
hermetically
sealed
applicable standard - IEC 60076
rated apparent power kVA 400
rated voltage HV/LV kV 11/0.4
rated frequency Hz 50
vector group Znyn 11
impedance voltage % 6
off-load tap changer regulation - +/- 2x2,5%
type of cooling - ONAN
rated power frequency withstand voltage kV 28
rated lightning impulse withstand voltage kVpeak 95
max. noise level (acc. to. IEC 60551) dB (A) 55
max. ambient temperature °C 50
temperature rise at rated power over 50°C maximum
ambient temperature
oil (upper level) °K 45
winding (average) °K 50
power supply V 110 DC/230 AC
approximate weight kg

Guarantee values for 11/0.4 kV station auxiliary


transformers
no load losses
load losses at principal tap

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 29


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.5: 33 kV Capacitor banks

manufacturer
type -
standards IEC 60871-1
kind of installation - indoor
protection degree IP 00
rated voltage kV 36
rating Mvar 25
steps -
insulation level
- lightning impulse kV 170
- power frequency withstand voltage kV 70
temperature class (1h) °C 50
connection - YY
with diff. relay
in each phase
number of elements connected in series and/or parallel -
per unit capacitor
number of unit capacitor connected per bank -
rated power of unit capacitor kVar
rated voltage of unit capacitor kV
nominal capacitance and max. permitted tolerance for µF/%
each unit capacitor
impregnating medium
- type - non PCB
- specification reference -
total weight of complete unit capacitor incl. all fitting and kg
impregnating medium
total losses per kVar
overall dimensions of unit
- height mm
- depth mm
- width mm

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 30


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.5: 33 kV Capacitor banks

overall dimensions of bank


- height mm
- depth mm
- width mm
number of terminals of each unit capacitor -
creepage distance mm/kV 31
discharge time of capacitor unit from rated voltage to 75 min max. 10
V
material of capacitor unit container - Stainless steel

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 31


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.6: 132 kV and 33 kV Power cables and terminations

132 kV Power Cables, Single-Core


manufacturer
applicable standards IEC 60840
type - XLPE
specified voltage U0/U kV 76/132
highest system voltage kV 145
rated frequency Hz 50
power frequency withstand voltage kV 275
impulse withstand voltage kV 650
conductor cross section mm² 1000
conductor material - annealed
copper
rated short circuit current (1 sec.)
conductor kA 143.0
screen kA 33.0
current carrying capacity
buried in soil at 40°C ground temperature A
laid in concrete channel at 54°C A
Conductor to screen capacitance µF/km
Charging current A/km
reference diameter of cable mm 83
cross-section of screen (copper screen wire) mm² 225
min. thickness of insulation mm 15
thickness of outer sheath mm
weight of cable per m kg 13.7
bending radius (single core cables) mm approx. 15 x d
132 kV Sealing Ends
manufacturer
material of insulator Composite
type test acc. to IEC 60840
rated power frequency withstand voltage (1 min/20°C) kV 275

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 32


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.6: 132 kV and 33 kV Power cables and terminations

impulse withstand voltage kV 650


minimum creepage distance mm 6600
132 kV Sealing Ends for GIS- Termination
manufacturer -
type test acc. to IEC 60840
rated power frequency withstand voltage (1 min/20°C) kV 275
impulse withstand voltage kV 650
type of termination - Dry type
dimension acc. to. - IEC 60859

33 kV Power Cables, Single-Core


manufacturer
applicable standards IEC 60502
type - XLPE
specified voltage U0/U kV 19/33
highest system voltage kV 36
rated frequency Hz 50
power frequency withstand voltage kV 70
impulse withstand voltage kV 170
conductor cross section mm² 630
mm² 95
conductor material - annealed
copper
rated short circuit current (1 sec.)
conductor
for 630 mm² kA 90.0
for 95 mm² kA 13.6
screen
for 630 mm² kA 10.2
for 95 mm² kA 10.2
current carrying capacity

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 33


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.6: 132 kV and 33 kV Power cables and terminations

buried in soil at 40°C ground temperature


for 630 mm² A
for 95 mm² A
laid in concrete channel at 54°C
for 630 mm² A
for 95 mm² A
reference diameter of cable
for 630 mm² mm 58
cross-section of screen
for 630 mm² mm² 35
for 95 mm² mm² 25
min. thickness of insulation mm 8
thickness of outer sheath mm
weight of cable per m
for 630 mm² kg 8.0
for 95 mm² kg 2.0
bending radius (single core cables) mm approx. 15 x d

33 kV Sealing Ends
manufacturer
material of insulator polymeric
type test carried out yes/no
rated power frequency withstand voltage kV 70
impulse withstand voltage kV 170
minimum creepage distance mm 1650

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 34


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.7: Protection equipment

1. Distance protection for 132 kV OHL feeder


(incl. fault locator function)
manufacturer
type
ratings
rating CT secondary A
rating VT secondary Hz
overcurrent capacity
permanent X IN
10 sec XI N
1 sec XI N
burdens (per phase)
current circuit VA
voltage circuit
ambient temperature
within specified accuracy °C
within operation capacity
DC supply
rated voltage V
main burden W
energizing circuit
minimum actuating impedance Ohm
number of actuating elements
range of actuating impedance
forwards direction Ohm/
reverse direction phase
range of actuating current (3 x I0) X IN
accuracy %
resetting ration

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 35


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.7: Protection equipment

Distance measuring circuit


type of measuring
umber of measuring elements
impedance range
a) resistance - min. Ohm/Ph
- max. Ohm/Ph
b) impedance -min. Ohm/Ph
- max. Ohm/Ph
directional sensitivity for
asymmetrical faults mV
triple-pole faults mV
tripping times
min. ms
max. ms
setting range of earth impedance/zero sequence line
impedance
amplitude
angle
accuracy
setting range
basic step
2nd step
3rd step
4th step
reversal of direction
Ancillaries
single multi-phase automatic reclosing capability
PLC interfaces
power swing blocking
switch-on to fault
fuse failure supervising device

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 36


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.7: Protection equipment

Output Contacts
for indication
V DC
• max. service voltage
A
• max. making current (1 s)
A
• continuous current W
• making power at 110 V DC

for tripping
• number
• max. service voltage V DC

• max. making current A

• continuous current A

• making power at 110 V DC W

• rupture power at 110 V DC L/R < 40 ms W

Constructional Features
protection class
mounting mode

Main Characteristics of Fault Locating Function


setting range (secondary ohms)
accuracy of measurement for fault currents with &
without DC transient (% of line length)
variation of accuracy with resistance of point of fault
minimum time between start of fault locator & fault
extinction to achieve accuracy in 1.2 & 1.3 above
state method of rendout
state data storage time if applicable (hours)
References

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 37


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.7: Protection equipment

2. Back-up Protection for 132 kV OHL Feeder –


Overcurrent Protection Relay (50, 51)
manufacturer
type -
ratings -
current A
DC voltage V
main characteristics
current setting range (from-to) X IN
measuring accuracy %
reset ratio
pick-up time (from-to) ms
time error
3. Back-up Protection for 132 kV OHL Feeder –
Directional Sensitive Earthfault Relay (67 N)
manufacturer
type

Ratings
current A
voltage V
frequency Hz
DC voltage V

Main Characteristics
current setting range (earth fault) X IN
measuring accuracy %
reset ratio
pick-up time ms

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 38


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.7: Protection equipment

directional element
measuring angle
angle error
sensitivity
pick-up time
time-lag characteristics
time error

4. Autoreclosing Relay for 132 kV & 33 kV OHLs


(79)
manufacturer
type
main characteristics
number of shots
one-phase cycle
three-phase cycle
dead time for 3-phase cycle sec.
reclaim time sec.
5. Overcurrent Protection (50, 51, 50N, 51N) for OHL
manufacturer
relay type
tripping current range from - to xIIn
tripping time range from - to msec
6. Overvoltage Protection (59)
manufacturer
relay type
setting range undervoltage stage 1 V
setting range undervoltage stage 2 V
setting range time delay stage 1 S
setting range time delay stage 2 S
tolerances %

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 39


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.7: Protection equipment

7. Undervoltage Protection (27)


manufacturer
relay type
setting range undervoltage stage 1 v

setting range undervoltage stage 2 v

setting range time delay stage 1 s

setting range time delay stage 2 s

tolerances

8. Synchrocheck Relay (25)


manufacturer
relay type
operation modes
voltages

∆U measurement

∆φ measurement

9. Load Unbalance Protection


manufacturer
relay type
setting range current stage 1 v
setting range current stage 2 v
setting range time delay stage 1 s
setting range time delay stage 2 S

10. Transformer Differential Protection (87) for Two-


and Three-Winding Transformers
manufacturer
type

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 40


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.7: Protection equipment

Ratings
secondary current A

rated frequency Hz

DC supply V

Main Characteristics
range of operating coil settings % of C.T.
rating
range of bias coil settings
recommended operating coil setting
recommended bias coil setting
number of bias coils
minimum sensitivity
earth faults % of C.T.
rating
phase faults % of C.T.
rating
maximum trough fault at which the protective
equipment is stable with recommended settings:
earth faults % of C.T.
rating
phase faults % of C.T.
rating
maximum time delay between initiation of fault and 3 x IN
10xIN
energizing of breaker trip circuit
(ms)

11. Transformer Overcurrent Protection (50/51, 51N)


for Two-and Three-Winding Transformers
manufacturer
relay type
tripping current range from - to x IN
tripping time range from - to msec

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 41


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.7: Protection equipment

12. Transformer Restricted Earth Fault Protection


(87N) for Two-and Three-Winding Transformers
manufacturer
relay type
tripping current range from – to X IN
tripping time range from – to msec

14. Busbar Protection


manufacturer
type
Ratings
AC current A

frequency Hz

AC supply V

DC supply VDC

Settings
CT supervision
operating time ms

Scheme burdens
DC burden W

AC burden Ohm

Contact rating
make and carry for 0.2 sec. VA

break

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 42


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.8: Substation control and monitoring system

1. Substation Digital Control System


automatic time synchronization at all nodes of the Yes
network
fault indication LEDs on modules and alarm messages Yes
on monitors
basic functions: logic, sequence control, data Yes
processing, including code conversion, text and alarm
signal editing and function units for binary processes
cycle times, selectable (for each control module) ms <10
programming language: elements for logic, control Yes
loops, arithmetic
minimum number of I/0 channels per computer (see rel.
(analogue in/digital in/digital out) chapter )
spare % 25
LCU Processing Unit
manufacturer
type
microprocessing with 32 bit Yes
system software in PROM Yes
application software in battery-buffered RAM or Yes
EPROM/Flash-PROM

LAN
type
protocol
transmission medium
transmission rate MBit/s

Printers (Color)
number of printers
manufacturer/type
noise dB (A)

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 43


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.8: Substation control and monitoring system

resolution dpi
• format DIN
• pages/min.

Printers (Laser, b/w)

• number of printers

• manufacturer/type
• noise dB (A)
• resolution dpi 600 x 600
• format DIN
• pages/min. ≥ 12

Operator workstation

• redundant configuration no

• hardware

• manufacturer
• type
• CPU
• data word
• coprocessor
• working memory MB

• hard disk

• type
• capacity MB

• external memory

• type
• capacity MB

• access ms

• data rate MB/s

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 44


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.8: Substation control and monitoring system



• noise dB (A)

• mouse, type
• monitors

• manufacturer/type
• number of monitors
• TFT screen size inch 19

• pixels x 1280 x 1024

• refresh rate Hz

• TCO standard
• noise dB (A)

4. Service and analysis station


• hardware

• manufacturer
• type
• CPU
• data word
• coprocessor
• working memory MB

• hard disk

• type
• capacity MB


• external memory

• type
• capacity MB

• access ms

• data rate MB/s

• noise dB (A)

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 45


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.8: Substation control and monitoring system


• mouse, type
• monitors

• manufacturer/type
• number of monitors
• TFT screen size inch 19

• pixels x 1280 x 1024

• refresh rate Hz

• TCO standard
• noise dB (A)

Service Aid Laptop


manufacturer
type
processor type
performance MHz
RAM Mbyte
hard disk drive GByte

5. Clock System

manufacturer
synchronization source
synchronization interval

6. Metering Equipment
V-meter
manufacturer -
type -
size mm x mm

scale degree
accuracy class -

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 46


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.8: Substation control and monitoring system

power consumption kO/V


operating principle kOhm/V
electro-mechanical -
electronic -

A-meter
manufacturer -
type -
size mm x
mm
scale degree
accuracy class -
power consumption kO/V
operating principle kOhm/V
electro-mechanical -
electronic -

W-meter
manufacturer -
type -
size -
scale degree
accuracy class -
power consumption mV
operating principle -
electro-mechanical -
electronic -

VAR-meter
manufacturer -

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 47


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.8: Substation control and monitoring system

type -

size mm x mm

scale degree
accuracy class -
power consumption mV
operating principle -
electro-mechanical -
electronic -

Wh-meter
manufacturer -
type -
size -
accuracy class -
power consumption VA
operating principle -
electro-mechanical -
electronic

VARh-meter
manufacturer -
type -
size mm x mm

accuracy class -
power consumption VA
operating principle -
electro-mechanical -
electronic -

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 48


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.9: Telecommunications and telephone systems

Optical Line terminal (OLT/STM-1)


ITU-T Rec.
- functions
G.783
ITU-T Rec.
- PDH to SDH electrical interface
G.703
ITU-T Rec.
- mux structure
G.707
ITU-T Rec.
- timing, synchronisation G.783, G.811,
G.812, G.813
ITU-T Rec.
- jitter and wander for SDH mux
G.783
ITU-T Rec.
- jitter and wander for SDH line
G.958

ITU-T Rec.
- craft interface
G.773
ITU-T Rec.
- optical safety
G.958
- min receive power @ BER 10-10

power supply: rated V DC 48

range V DC 40 - 60

Primary Multiplexer
- comply with ITU-T Rec. G.737
kbps 64 or multiple
- add/drop
of 2.4 kbps
kbps 2048 +/- 50
- Bit rate
ppm
ITU-T Rec.
- PCM requirements
G.711
ITU-T
- frame structure
Rec.G.732
ITU-T Rec.
- encoding law
G.711
ITU-T Rec.
- performance at voice frequencies
G.714

alarms
- power failure
- loss of incoming signals 2048 kbps

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 49


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.9: Telecommunications and telephone systems

- loss of frame alignment


- alarm indication from remote mux

Optical Fibre Underground Cable (OPUG)

manufacturer
type

mm /
stainless steel tube
mm
steel stranding N x mm
steel section mmsp

cross section St mm2


cross section ACS mm2
cross section AA mm2

overall diameter mm
calculated breaking load kN
nominal weight kg/km
kN /
modulus of elasticity
sqmm
load bearing cross section mmsq
10E-
coefficient of thermal exp.
6/K
creep yeald promille
ultimate Tensil strength kN
rated Tensil strength kN
everyday stress N/mm2

short circuit capacity I2t kA2S


Ohms/
DC resistance
km
weight of OPGW kg / km

number of fibres No 24

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 50


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.9: Telecommunications and telephone systems

fibre excess length promille

9.0 to 11.5
core diameter µm
3% tolerance
mode field diameter
@ 1310 nm µm 8 – 9.5
@ 1550 nm µm 9.5 – 11.5

optical cladding diameter µm 125 +/- 2

core clad concentricity <2%

coating diameter µm 250 +/- 15

coating concentricity < 0.7 %

cable attenuation @ 1310 nm dB/km <= 0.35

cable attenuation @ 1550 nm dB/km <= 0.25

splice attenuation @ 1310 nm dB <= 0.15


splice attenuation @ 1550 nm dB <= 0.25

ps/
total dispersion @ 1310 nm 3.5
km.nm
ps/
total dispersion @ 1550 nm 18.0
km.nm

core numerical aperture <= 0.23

life span year > = 30

PLC Terminal Equipment (digital and analogue)


manufacturer
type

number of speech channels per link (analogue) min. 1

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 51


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.9: Telecommunications and telephone systems

“ “ ditto (analogue, for 8 kHz bandwidth) min. 3

“ “ ditto (digital) min. 8


number of data channels per link (analogue) min. 4
“ “ ditto (digital) min. 8

compatibility with existing analogue PLC equipment yes


S/N ratio for complete link (without compandors) dB >35
line attenuation dB

carrier frequency range kHz 40 - 500


gross channel bandwidth kHz 4/8
usable AF bandwidth Hz 300 - 3600
max. usable data transmission rate kBit/s 76.8
RF output power W PEP
spurious emission suppression dB
selectivity of receiver dB
automatic gain control yes
RF level range dB

number of teleprotection commands


protection class of equipment racks, cubicles

EMC standards:

• EN 50081-2, class A yes

• EN 50082-2

Power supply:

• Supply voltage VDC 48 ± 20%

• Power consumption W

Ambient conditions: yes

(according to IEC 721-3)

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 52


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.9: Telecommunications and telephone systems

PLC Teleprotection Equipment


For digital signals:
manufacturer
type

number of simultaneous commands 4


command initiated by potential-free contact yes
test voltages according to IEC 255-4

• isolation kV/DC 0.5 2 /1 min.


• pulse 1.2/50 µsec. kV 1

For analogue signals:


manufacturer
type
test voltages according to IEC 255-4

• isolation (0.5 J, 1 min) kV/DC 2

• pulse 1.2/50 µsec. kV 1

Fibre Equipment Teleprotection Interface


electromagnetic compatibility
test voltages according to IEC 255-4
• isolation (0.5 J, 1 min.) kV/DC 2

• pulse 1.2/50 µsec. kV 1


no. of simultaneous commands

no. of analogue signals

Line Matching Units

manufacturer - -

equipment type - -

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 53


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.9: Telecommunications and telephone systems

equipment site impedance Ω

line site impedance Ω

nominal peak envelope power W

Line Traps 132 kV

manufacturer -

type -

rated inductance mH 0.5/0.315/0.2

power frequency inductance mH

rated continuous current A 1250

rated short time current kA 31.5

• duration s 1

Telephone Set
manufacturer
type
no. of standard sets

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 54


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.10: 0.4 kV AC Installations

0.4 kV AC Installations
applicable standards IEC 60439,
60947
type - fixed units
rated voltage V 400
frequency Hz 50
rated short-circuit current for 1 second kA 25
test voltage V 2500
type of circuit breaker driving mechanism - hand-operated
secondary current of current transformer A 5
protection class - IP 41

400 V Main Switchgear


manufacturer -
type of switchgear -
rated voltage kV
rated current of busbar (45 °C ambient) A
rated frequency Hz
rest voltage V
max. asym. 3-phase short circuit withstand current kApeak
short-time current (1 sec) kA
overall dimensions (H x W x D) mm
weight kg

Circuit Breaker
type -
rated current A
rated short circuit breaking current kA
short-time current (1 sec) kA

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 55


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.10: 0.4 kV AC Installations

max. asym. 3-phase short-circuit withstand current kApeak


total opening time ms

Current Transformer
type -
current ratio A
dynamic current x IN

400 V Sub-distribution
manufacturer -

type of switchgear -
rated voltage kV
rated current of busbar (45°C ambient) A
rated frequency Hz
test voltage V
max. asym. 3-phase short circuit withstand current Apeak
short-time current (1 sec) kA

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 56


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.11: Direct current installations

110 V DC Equipment
applicable standards IEC 60439,
60947
type of distribution board fix mounted
components
busbar P and N insulated
rated voltage DC V 110
test voltage V 1500
type of load break switch/circuit breaker - hand-operated
protection class - IP 41
min. insulation resistance kΩ 110

battery type - NiCd


nominal voltage per cell V 1.2
number of cells - 92
applicable standard IEC 60623
rated voltage V 110
type of operation parallel stand-
by
rated capacity (for 10 hours discharge time) Ah 400
battery charger type - thyristor
controlled
input voltage (three-phase) V 400 ± 10%
frequency Hz 50 ± 2%
rated DC voltage V 110
maximum DC voltage V 132
residual ripple % <5
type of cooling - self-ventilating
protection class of cubicle - IP 41

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 57


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.11: Direct current installations

110 V DC Distribution
manufacturer -
type -
dimensions (height x width x depth) mm
metal cabinets with single busbar system and fixed -
equipment
rated current A
short-circuit withstand current A
busbar cross-section mm²

Circuit Breaker
type -

rated current DC A

Fuse -

type -
rated current DC A
rated breaking current DC A
110 V Battery Charger
manufacturer -
type -
mounted in metal cabinet -
rated voltage DC V
rated current DC A
rated capacity kVA
rated input voltage V
rated current consumption A
efficiency -
charging characteristics -
constant voltage range from - to V
continuous charging voltage per cell and tolerance V+%

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 58


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.12: LV Power and control cables

0.4 kV Power Cables, Four-Core


manufacturer -
cable type -
rated voltage kV
test voltage kV
conductor material - annealed
copper
insulation material -

110 and 48 V DC Cables


manufacturer -
cable type -
rated voltage kV
test voltage kV
conductor material - annealed
copper
insulation material -

Control Cables
manufacturer -
cable type -
rated voltage kV
test voltage kV
conductor material - annealed
copper
insulation material -
type of screen -

Instrument Cables
manufacturer -
cable type -

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 59


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.12: LV Power and control cables

rated voltage kV
test voltage kV
conductor material - annealed
copper
insulation material -
type of screen -

Signaling Cables
manufacturer -
cable type -
rated voltage kV
test voltage kV
conductor material - annealed
copper
type of screen -

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 60


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.13: Earthing system, power and lighting installations

1. Earthing and Lightning Protection System

applicable standards - IEEE 80, IEC


60621/61024
VDE0185:
manufacturer

type
size of standard copper conductor mm2 70
mode of connection - by compression
diameter of round copper rods for lightning protection mm 8
size of stranded copper for earthing conductors mm2
diameter of round copper for lightning protection mm
conductors
diameter of reinforcement bar (round iron) mm
material of conductor supports of lightning protection -
system
material of nuts and bolts on points for remain -
detachment
mode of connection of copper conductors in ground -
and PVC single-core cable to the reinforcement bar in
concrete

2. Power and Lighting Installation

0.4 kV Sub-distributions Boards


manufacturer -
type of switchgear - fixed
plug-in units/fixed units -

rated voltage V 400/250


rated frequency - 50
test voltage V 2500

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 61


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.13: Earthing system, power and lighting installations

rated current of busbar (45°C ambient) A


max. asym. 3-phase short circuit withstand current kApeak
short-time current (1 sec.) kA
degree of protection IP41/IP54

Lighting
manufacturer -
indoor lighting (type) -
outdoor lighting (type) -

Lighting Fixtures
indoor fluorescent W 1 x 58/2 x 58
indoor halogen W 1 x 250/1 x 400
outdoor high-pressure mercury W 400

Power and Domestic Sockets


manufacturer -
power sockets (type) -
domestic sockets (type) -

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 62


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.16: Overhead cranes

Manufacturer -
Place of manufacture -
Manufacturer reference / designation -
Test load for the crane and lifting gears in % of the
% 125
nominal carrying capacity
Carrying capacity, approx. (to be adapted by the
t
Bidder, according to the heaviest part to be lifted)
Weight of the heaviest part to be lifted t
Lifting height, approx. m
Hoisting speed, fast/creep approx. m/min. 4/0.4

Crab traversing speed, fast/creep approx. m/min. 20/5


Crane bridge traveling speed m/min. 20/5
Fast/creep approx.

Span approx. m
Length of runway – full building length m yes
Standards for design and calculation of the crane - yes/no

BS 466,2373 class 2
Or equivalent standard applied -

General Guarantees
The Contractor shall guarantee the following values
and characteristics of the crane.
Faultless operation of the crane installation
Travel and lifting speeds including the inching speed % ±15
with a tolerance of each nominal speed at nominal
load.
The lifting capacity with a permitted overload capacity % 25
(test load) of at least nominal lifting capacity.
Max. deflecting of the crane bridge of span at nominal - 1/800
load

Special Guarantees
Lifting capacity t
Deflecting of crane girder at nominal load and with mm
crab in center position

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 63


Marib Power Project 2nd Stage Tenderer:
Lot 2b, 132 kV Substations - Back-bone Unit Data
Connection

Technical Data required offered

B1.3.16: Overhead cranes

Traveling speeds fast/creep m/min.

Hoisting speeds fast/creep m/min.


Max. power demand kW

6721A17/0.580/Tender Documents/Lot 2b/B1 data sheets B1.4/DS - 64