GIS Equipment For reconstruction/new building Quantity Delivery dates Object address End user Customer Executor

TECHNICAL REQUIREMENTS

GIS . kV

1. 2. 3. 3.1. 3.2. 3.3. 3.4.

Technical characteristics (parameter description) Manufacturer Type (model) BASIC TECHNICAL CHARACTERISTICS Rated voltage, kV Maximal operated voltage, kV Rated frequency, Hz

Parameter value * *

HHI*

HHIs technical characteristics HYUNDAI

Nominal current, A, not less than


a) of bus bars b) of connection

5.1. 5.2. 5.3. 5.4. 5.5.

CB rated breaking current, kA Thermal capability current, kA Electrodinamic capability current, kA Time of short circuit current running, sec Allowable overheating of bodies, accepted value of bodies overheating, which can be touched, , not more than Requirements to insulation of GIS main circuits Testing full storm impulse voltage, kV, not less than a) regarding the earth and between CB contacts b) between contacts of disconnectors
1

6. 6.1.

6.2.

One-minute testing voltage of industrial frequency, kV, not less than a) GIS to earth and between CB contacts

b) measuring transformers and bushings c) between contacts of disconnectors


8.1. 8.2.

Partial discharge level at voltage 1,1 U../3, not more than, pC AC line frequency voltage, which can be hold by the CB insulation to earth without excessive pressure of SF6 during 1 hour, kV, not less than Insulation of control circuits, auxiliary GIS circuits and secondary windings of measuring transformers INSTALLATION AND OPERATION CONDITIONS Category of placement and climatic modification Indoor or outdoor installation Type of building new/old Building equipment Heating Ventilation Air drying .

8.3.

9. 9.1. 9.2. 9.3. 9.4.

12.1.

GIS operating temperature in building, 0 Climatic modification and stability to climate factors acc. to GOST 15150-69 and GOST 15543.1-89 and for bushings and overvoltage limiters Category of placement and climate resolution Ambient temperature,

13. 13.1.

13.2.

max operative temperature min operative temperature

13.3. 13.4. 14. 14.1. 14.2.

Allowable altitude above sea level, m Seismic stability, points according to MSK scale CB (CIRCUIT BREAKERS) Number of gaps per pole Parameters of short circuit through current
2

14.2.1. 14.2.2. 14.2.3. 14.2.4.

Current max peak of electrodynamic stability, kA, not less than Start active value of periodical component, kA, not less than Mean square value of current during its running time (current of thermal stability), kA Running time of thermal stability current, sec

14.3. Latching current parameters 14.3.1.

Start active value of periodical component, kA

14.3.2. Max peak, kA 14.4.

Parameters of breaking current:

14.4.1. Normal content of the inperiodical component,% 14.4.2. Coefficient of the first dampen pole, , 14.4.3. Rated breaking current in phases error conditions, kA 14.4.4. Characteristics of the own transitional restore voltage according to

GOST 687 -78 p.3.6.3 (yes, no)


14.4.5. Capacity current off-load lines, interrupting without repeated

breakdowns, A, not less than


14.4.6. Allowable interrupting current of off-load cable, A, not less than 14.4.7. Commutation stability operating life for each pole, not less than

number of operations Open, (Close) with latching (interrupting) current ranging 0,61,0 I0nom number of operations Open, (Close) at latching (interrupting) of rated current
14.5. 14.5.1. 14.5.2.

Requirements to mechanical characteristics: Excessive pressure of SF6 at +20, MPa Possibility of realization of normalized commutation cycles during operation with reclosing according to GOST 687-78 p.3.6.1.5 Way of the CB control Line bus-couplers transformers *

14.5.3.

14.5.4. 14.5.5. 14.5.6. 14.5.7.

No-current condition at HS reclosing , sec Opening time, sec, not more than Total breaking time, sec Closing time, sec, not more than
3

14.5.8. 14.5.9.

Time difference in closing of poles, sec, not more than Time difference in opening of poles, sec, not more than

14.6. 14.6.1.

Technical characteristics of the drive: Drive type (spring-motor type, hydraulic)

14.6.2. 14.6.3. 14.6.4.

Drives power, kJ AC voltage of electromotor drive, V Absorbes current of electric motor for closing springs wind-up device, A

steady-state current starting current, A 14.6.5. Number of shutoff electromagnets, pcs


14.6.6. 14.6.7. 14.6.8.

* *

Number of shut on electromagnets, pcs DC rated voltage of control electromagnets , V Operating voltage range of electric magnets of control from the rated value, % of shut on electric magnets of shutoff electric magnets

14.6.9.

: Absorbed current of shut on/shutoff electric magnets , A steady-state current, A starting current, A * * *

14.6.1 Time of switching springs wind-up process, sec, not more than 0. 14.6.11. Presence of manual device for wind-up of switching springs (yes,

no)
14.6.12. Indicator of springs active state (yes, no) readiness to operation 14.7. 14.7.1. 14.7.2.

Requirements to reliability Lifetime before the mid-life repair, years Mechanical stability lifetime, - number of cycles Closing- t -Opening, not less than *

14.7.3.

Experience of trouble-free running with the specified drive type in Russia, years, not less than

14.8. Equipment and service devices 4

14.8.1. 14.8.2.

Counters (meter) of number of CB responses (yes, no) Counter of the rest commutation resource (yes, no)

14.8.3. 15. 15.1. 15.2.

Mechanical gauge of the switch state (close/open) (yes, no) Disconnectors and technological earthing devices Construction- line acting contact (yes, no) Drive type for the main circuit for the earthing circuit

15.3. 15.4. 15.5. 15.6. 15.7. 15.8. 15.9. 16. 16.1. 16.2. 16.3. 16.4. 17. 17.1.

Number of drives for 3 poles Mechanical blocking of disconnector and earthing switch (yes, no) AC rated voltage of electric drive feeding, V Current consumed by the poles drive, A, not more than Possibility of disconnector manual operation (yes, no) Resource of mechanical stability, cycles closing - opening, not less than Windows for observation (yes, no) Quick earthing devices Construction high speed switching (spring), slow disconnection (yes, no) Type of the drive Number of drives for 3 poles Insulated earthing device (yes, no) Current transformers For lines rated primary current, A rated secondary current, A number of secondary windings Winding 1 (energy accounting) Winding 2 Technological process automatic control system Winding 3 (relay protection) 6 (relay protection) Accuracy class Secondary load, VA Accuracy class Secondary load, VA Accuracy class Secondary load, VA

Allowable primary current overload at which the specified class of precision of measuring windings is retained, ambient air temperature +40 0 , % Rated limit ratio of secondary windings for protection, not less than Coefficient of measuring winding devices protection
29.1.

For CB of transformers and bus couplers switches rated primary current, A rated secondary current, A Number of secondary windings: Winding 1 Technological Accuracy class process automatic control Secondary load, VA system Winding 2 (relay protection) Accuracy class Secondary load, VA 6 (relay protection) Allowable primary current overload at which the specified accuracy class of measuring windings is retained, ambient air temperature +40 0 , % Rated limit ratio of secondary windings for protection, not less than Coefficient of measuring winding devices protection

40. 40.1. 40.2. 40.3.

Electromagnetic voltage transformers on the collecting buses Primary voltage, kV Number of secondary windings Winding 1-main Secondary voltage, kV Accuracy class, % Nominal load, VA

40.4.

Winding 2-additional Secondary voltage, kV Accuracy class, % Nominal load, VA

40.5.

Winding 3- energy accounting Secondary voltage, kV Accuracy class, % Nominal load, VA


6

41. 41.1. 41.2.

Electromagnetic voltage transformers in bays Primary voltage, kV Number of secondary windings Winding 1-main Secondary voltage, kV

41.3.

Accuracy class, % Nominal load, VA

41.4.

Winding 2-additional Secondary voltage, kV Accuracy class, % Nominal load, VA

41.5.

Winding 3- energy accounting Secondary voltage, kV Accuracy class, % Nominal load, VA

42. 42.1. 42.2. 43. 43.1. 43.2. 43.3. 43.4. 43.5. 43.6. 43.7.

Light arresters in the GIS Number Main characteristics BushingsSF6 gas-air Construction of bushings composite, dry bushing with graded insulation (yes, no) Quantity Temperature of exploitation Heating (yes, no) Angle of installation from the horizontal line Requirements to bushings insulation acc. to GOST 1516.3-96 Specific length of the leakage path of the external insulation acc. to GOST 9920-89, sm/kV, not less than Allowable horizontal load on the bushing, N, not less than Experience of bushings/operation of the specified type and climatic modification, years *
7

43.8. 43.9.

44.

Bushings SF6 gas- cable terminal box Construction of bushings composite, dry bushing with graded insulation (yes, no) Quantity Temperature of exploitation Heating (yes, no) Angle of installation from the horizontal line Requirements to bushings insulation acc. to GOST 1516.3-96 Experience of bushings exploitation of the specified type and climatic implementation, years Technical requirements to the construction, manufacturing and materials Q-ty and location of gas-barrier insulator should ensure max durability of the GIS without its switching-off in case of repair of its components Barrier and support insulators Bodies of the barrier and rigid insulators should not be located between flanges of neighboring sections of GIS in order to exclude mechanical action on the insulators body during flanges squeezing. Mechanical loads should be transferred to the outer metallic ring of the insulator Outer SF6 gas and other connection tubes including connection of neighboring electric gas sections of 3 phases (yes, no) Welding of components of GIS and support structure on the place of installation Sealing system at flanges Compensators of the mechanical movements and extensions are placed where it is required for ensuring of mechanical flexibility of GIS Fixation of GIS support structure. It is not allowed to use the same bolts and pins for connection of neighboring flanges and fixation of support structures (to avoid creation of additional mechanical loads because of thermal extension and squeezing) Embedded detail for GIS installation GIS maintenance Excessive pressure of SF6 gas at temperature +20 * * * *

44.1. 44.2. 44.3. 44.4. 44.5. 44.6. 44.7.

45. 45.1.

45.2.

45.3.

45.4.

45.5. 45.6.

45.7.

45.8. 45.9. 45.10.

In the CB bay, MPa In the voltage transformer, MPa

* *
8

In the collecting buses, MPa In the tap-offs, MPa In the over-light arrester, MPa
49.1. 49.2. 49.3.

* * *

Allowable level of SF6 gas leakage, % a year Max capacity of one SF6 gas section Gauges of gas density temperature-compensating on each gas section, with 2 alarm devices (yes, no) combination of sections in a group with one gauge

50.1.

Gauges of partial charges for tests after the installation of GIS (yes, no) in the process of operation (yes, no) gauges layout

52.1.

Control boxes (cabinets) should have a micro-processor system of bays control and operational equipment (yes, no) Control and alarm cabinets should be zinced or made of stainless materials with protection degree IP-54 acc. to GOST 14254-96 (yes, no) Control cables copper, multicore in a metal hose, cross section mm2

52.2.

52.3.

from the current transformers from the control devices


52.4.

Motors Power supply voltage Heating circuits Control circuits

55. 55.1.

Durability requirements , Lifetime before the mid life repair, years Lifetime, years, not less than Periodicity and size of servicing Lifetime of the complete bay, years Period of trouble-free operation in the lifetime period Specific cost of after-warranty service of the GIS module bay by the manufacturer, rubles/year * * * *
9

55.2. 55.3. 55.4. 55.5. 55.6.

56. 56.1. 56.2.

Manufacturers warranty Warranty period of exploitation, months, not less than Other on desire of Supplier *

57. 57.1.

Ecological requirements Radio interference voltage from bushings air-SF6 gas, measured at 1.1 U, mkV, not more than Safety requirements Safety certificates (No and date of issuing) Complete set includes GIS shall be supplied in accordance with single-line diagram and layout Manometer gauge of gas density with temperature compensation and block-contacts for signaling about pressure reduction and prohibition of CB operation (yes, no) Gauges of partial charges (yes, no) Gas-technological service truck (yes, no) ) SF6 gas for initial filling (yes, no) Set of spare parts tools and accessories (yes, no) Exploitation documentation (Technical passport, Test protocols, operation manuals, technical descriptions) in Russian, copies Marking, packing, transportation, storage Marking, packing, transportation, utilization according to GOST 11677-85 or IEC (yes, no) Transportation conditions * Customs clearance and delivery to the site Shock-indicators for transportation conditions control (yes, no) Storage conditions, period of storage for separate parts, completing units, spare parts tools and accessories * Installation and tests of the GIS shall be carried out in the presence of Suppliers supervisor (yes, no) Requirements to certification: Number and date of issuing of Technical conditions approved by RAO UES of Russia or JSC UES FGC (yes, no) Number and date of issuing of Expert certificate according to
10

58. 58.1. 59. 59.1.

59.2.

59.3. 59.4. 59.5.

59.6. 59.7.

60. 60.1.

60.2. 60.3. 60.4. 60.5.

60.6.

61. 61.1.

61.2.

Article on attestation of equipment, technologies and materials, introduced by order of JSC UES FGC 334 21.12.2005 (yes, no)

Notes: 1. The column HHIs technical characteristics is pointed by the manufacturer 2. These parameters marked by * should be pointed by the manufacturer 3. In all other not mentioned cases autotransformers should be manufactured in accordance with IEC 60517