Professional Documents
Culture Documents
MS1525:2007
Clause 5 : BUILDING ENVELOPE
25 July 2009 Penang
GREEN BUILDING INDEX BUILDING ENVELOPE the external portions of a building through which thermal energy is transferred and this thermal transfer is the major factor affecting interior comfort level and energy usage.
MS1525:2007
GREENBUILDINGINDEX SDN BHD | www.greenbuildingindex.org
MS1525:2007
1.
KEY ISSUES
MS1525:2007 is a Code of Practice (CP), and is intended to be incorporated into UBBL, hence a CP becomes part of a By-law. a) Applies to non-residential, air-conditioned buildings, > 4,000 sq m. Architects and Engineers must submit OTTV & RTTV calculations. Requirement for Energy Management Control system is under Clause 9.
GREENBUILDINGINDEX SDN BHD | www.greenbuildingindex.org
b) c)
MS1525:2007
2.
KEY ISSUES
MS1525:2007 provides the baseline minimum standard for the GBI rating tools for energy efficient design. a) If design falls below the requirements of MS1525:2007, it is unlikely to be rated. Reward for designs that are better than the baseline minimum requirements of MS1525:2007. GBI (Residential) adopts same methods of measurement found in MS1525:2007.
GREENBUILDINGINDEX SDN BHD | www.greenbuildingindex.org
b)
c)
BUILDING ENVELOPE
MS1525:2007 Clause 5
5.1 5.2 5.3 5.4 5.5 5.6 5.7 5.8 5.9 General Requirement Concept Of OTTV Shading Coefficient Daylighting Roofs Roofs With Skylights, RTTV Daylight Credit Submission Procedure Air Leakage
GREENBUILDINGINDEX SDN BHD | www.greenbuildingindex.org
BUILDING ENVELOPE
THERMAL RESISTANCE
Heat energy flows from a hot object to a cooler object. Whenever there is a temperature gradient, heat transfer will always occur. It can never be stopped, and it can only be slowed.
GREENBUILDINGINDEX SDN BHD | www.greenbuildingindex.org
THERMAL RESISTANCE
Relationships between thermal resistance, thermal conductivity and U-value 1. 2. In heat transfer, the Thermal Conductivity, k of a material is its ability to conduct heat. Generally, thermal conductivity approx tracks electrical conductivity, as moving electrons transfer not only electric current, but also heat energy. Therefore, heat conductivity through layers of materials in a composite wall construction is analogous to adding up the resistance in an electric circuit connected in series.
GREENBUILDINGINDEX SDN BHD | www.greenbuildingindex.org
3.
THERMAL RESISTANCE
Relationships between thermal resistance, thermal conductivity and U-value 4. Thermal Resistance, R of each material is R = (material thickness) (thermal conductivity, k) 5. 6. 7. Increasing the thickness of the material will increase its thermal resistance. In a composite wall construction, the total R is Rtotal = R1 + R2 + R3 +...+ Rn. Therefore, Rtotal is the sum of the thermal resistance of all the respective materials making up the composite wall.
GREENBUILDINGINDEX SDN BHD | www.greenbuildingindex.org
THERMAL RESISTANCE
Relationships between thermal resistance, thermal conductivity and U-value 8. U-value of the wall is the heat transmission value of the composite wall in W/m2K, and is inversely proportional to the total R, ie, U = 1 / Rtotal. 9. The higher the R, the lower the U, the better.
THERMAL RESISTANCE
Examples of thermal conductivity, k Material Mineral wool insulation Mineral fibreboard Plasterboard Common clay brick Glass 3mm thick Concrete k (in W/mK) 0.039 0.053 0.160 0.950 1.050 2.160
THERMAL RESISTANCE
Roof thermal resistance is one of the most important design decisions for energy efficient designs The roof plane receives the most Solar Radiation and for the longest period through the day >75% of the Solar Gain by a typical Intermediate single storey terraced house is through its Roof >50% of the Solar Gain by a typical Intermediate double storey terraced house is through its Roof >40% of the Solar Gain by a typical 5 storey block of flats is through its Roof
GREENBUILDINGINDEX SDN BHD | www.greenbuildingindex.org
THERMAL RESISTANCE
Roof Thermal Resistance and SRI
THERMAL RESISTANCE
Solar Reflectance Index (SRI) 1. SRI is a measure of a roofing materials ability to reflect solar heat, and hence, reduce heat absorption; Standard black is 0, standard white is 1; Materials with the highest SRI values are the best (and coolest!) choices for roofing.
2. 3.
THERMAL RESISTANCE
Albedo and SRI The albedo of an object or a surface is the extent to which it reflects light from the Sun. Generally, a light coloured surface has a higher albedo. It is shown as SRI, and ranges from 0 to 1. Eg Material Black acrylic paint Bare soil New asphalt New concrete Concrete w Portland cement White acrylic paint SRI 0.05 0.17 0.40 0.40 - 0.50 0.70 - 0.80 0.80
BUILDING ENVELOPE
MS1525:2007 Clause 5
5.1 5.2 5.3 5.4 5.5 5.6 5.7 5.8 5.9 General Requirement Concept Of OTTV Shading Coefficient Daylighting Roofs Roofs With Skylights, RTTV Daylight Credit Submission Procedure Air Leakage
GREENBUILDINGINDEX SDN BHD | www.greenbuildingindex.org
CONCEPT OF OTTV
OTTV FORMULA
A OTTV =
o1
x OTTV + A
1
o2
x OTTV ...... + A
2 o2 on
on
x OTTV
o1
+ A ...... + A
where A1 is the gross exterior wall area for orientation 1; OTTV1 is the OTTV value for orientation 1; and OTTV for the whole building < 50 W/m2
GREENBUILDINGINDEX SDN BHD | www.greenbuildingindex.org
OTTV FORMULA
OTTV FORMULA
OTTV =
OTTV FORMULA
OTTV =
OTTV FORMULA
OTTV =
OTTV FORMULA
OTTV =
OTTV FORMULA
OTTV =
0.2% to 5%
10% to 20%
70% to 85%
15(1-WWR)Uw +
Heat Conduction through Walls
6(WWR)Uf + 194xCFxWWRxSC
Heat Conduction through Windows Solar Heat Gain through Windows
< 50W/m2
0.2% to 5%
< 50W/m2
15(1-WWR)Uw +
+ 194xCFxWWRxSC
U-values
5.7 to 6.2 4.5 to 5.5 2.6 to 2.9
< 50W/m2
15(1-WWR)Uw +
6(WWR)Uf
+ 194xCFxWWRxSC
70% to 85%
VISIBLE : visible to the human eye; wavelength between 390 and 750 nanometers.
transmitted
Low-E coating
INSIDE
U-values
5.7 to 6.2 4.0 to 4.4 4.5 to 5.5 4.2 to 5.3 2.6 to 2.9 1.2 to 1.8
SHADING COEFFICIENT
SHADING COEFFICIENT
Sunshades
SHADING COEFFICIENT
Sunshades
SHADING COEFFICIENT
Sunshades
SHADING COEFFICIENT
External Shading Devices are more effective than Internal Blinds. External Shading Devices block out Direct Sunlight.
SHADING COEFFICIENT
Sunshades
X=
y=
GREENBUILDINGINDEX SDN BHD | www.greenbuildingindex.org
SHADING COEFFICIENT - R1
MS1525:2007 Table 5
SHADING COEFFICIENT - R1
SHADING COEFFICIENT - R2
MS1525:2007 Table 6
SHADING COEFFICIENT - R2
SHADING COEFFICIENT
MS1525:2007 Table 7
SHADING COEFFICIENT
OTTV CALCULATIONS
SAMPLE BUILDING
MENARA UAC
OTTV CALCULATIONS
MENARA UAC
OTTV CALCULATIONS
MENARA UAC
MENARA UAC
OTTV CALCULATIONS
MENARA UAC HEAT CONDUCTION THROUGH WALLS 15(1-WWR)Uw +
Heat Conduction through Walls
6(WWR)Uf + 194xCFxWWRxSC
Heat Conduction through Windows Solar Heat Gain through Windows
< 50W/m2
0.2% to 5%
OTTV CALCULATIONS
MENARA UAC Heat Conduction through Walls
OTTV CALCULATIONS
MENARA UAC HEAT CONDUCTION THROUGH WINDOWS 15(1-WWR)Uw +
Heat Conduction through Walls
6(WWR)Uf + 194xCFxWWRxSC
Heat Conduction through Windows Solar Heat Gain through Windows
< 50W/m2
10% to 20%
OTTV CALCULATIONS
MENARA UAC Heat Conduction through Windows
OTTV CALCULATIONS
MENARA UAC HEAT CONDUCTION THROUGH WALLS 15(1-WWR)Uw +
Heat Conduction through Walls
6(WWR)Uf + 194xCFxWWRxSC
Heat Conduction through Windows Solar Heat Gain through Windows
< 50W/m2
70% to 85%
OTTV CALCULATIONS
MENARA UAC Solar Heat Gain through Windows
OTTV CALCULATIONS
MENARA UAC 15(1-WWR)Uw +
Heat Conduction through Walls
6(WWR)Uf + 194xCFxWWRxSC
Heat Conduction through Windows Solar Heat Gain through Windows
< 50W/m2
0.2% to 5%
10% to 20%
70% to 85%
OTTV CALCULATIONS
OTTV
For circular or symmetrical floor plates, divide into 8 zones N NW W SW S
GREENBUILDINGINDEX SDN BHD | www.greenbuildingindex.org
NE
E SE
OTTV
OTTV
OTTV
OTTV
North
38m glazing, 10m solid wall Total perimeter = 48+48+34+34 = 164m aircond
West
16m/18m
34m
East
14m/20m
OTTV
ROOF U-value
ROOF U-value
U-value OF ROOFS U-values are worked out from the Thermal Resistance of the respective materials making up the Roof. U-value is the heat transmission value of the composite roof in W/m2K, and is inversely proportional to R, ie, U = 1 / Rtotal The higher the R, the lower the U, the better.
GREENBUILDINGINDEX SDN BHD | www.greenbuildingindex.org
ROOF U-value
0.4
ROOF U-value
ROOF WITH INSULATION 1. 2. 3. 4. Concrete tiled roofs (light weight) with NO INSULATION will have a U-value of 0.7 W/m2K With 50mm fiberglass, the U-value will be about 0.35 W/m2K 100mm Concrete roof slab (heavy weight) will have a U-value of 2.762 W/m2K With 60mm polystyrene foam, the U-value can be brought down to 0.537 W/m2K
GREENBUILDINGINDEX SDN BHD | www.greenbuildingindex.org
ROOF U-value
MULTIPLE ROOFS 1. 2. If more than one type of roof is used, refer to Clause 5.5.2 for equations for U-value. If roof area is shaded from direct sun by a ventilated external shading device, such as a double roof, the permissible U-value (Table 9) may be increased by 50%. If roof surface treatment is used where SRI > 0.7, the permissible U-value (Table 9) may be increased by 50%.
GREENBUILDINGINDEX SDN BHD | www.greenbuildingindex.org
3.
SUMMARY
MS1525:2007 Clause 5.2
OTTV applies to building envelope, where OTTV < 50 W/m2
SUBMISSION PROCEDURE
Information to be submitted by a Professional Engineer or Professional Architect: a drawing showing the cross-sections of typical parts of the roof construction, giving details of the type and thickness of basic construction materials, insulation and air space; the U-value of the roof assembly; the OTTV calculation; and the RTTV of the roof assembly, if provided with skylights.
DAYLIGHTING
DF (%)
>6 3-6 1-3 0-1
Distribution
Thermal and glare problems Good Fair Poor
Based on Malaysian data, the average Daylight level between 10am and 4pm is 32,000 lux. Thus, a suggested DF of 1.5 = 480 lux (Fair); a DF of 4.5 = 1,440 lux (Good)!
GREENBUILDINGINDEX SDN BHD | www.greenbuildingindex.org
DAYLIGHTING STRATEGIES
1 2
1. 2.
3 4
3. 4.
Locate a continuous strip of narrow windows up high. Add a few view windows for visual connection to the outside. These have a low visible transmittance (VLT 0.2 to 0.3), to balance the luminance of the walls with the luminance of the outside. Every work place in the building should have view windows. Introduce light eggshell white color in the upper part of the room to bounce the light across the room. Add mid-to-light colors in the lower part of the room.
GREENBUILDINGINDEX SDN BHD | www.greenbuildingindex.org
DAYLIGHTING
Spectrally Selective Glazing lets in daylight, but blocks out the heat Tinted Glazing
Heat Light
DAYLIGHTING
CHOOSE SPECTRALLY SELECTIVE GLAZING
ideal window transmittance
solar spectrum
500
1000
1500 Wavelength,
2000 nm
2500
3000
390nm
visible
750nm
DAYLIGHTING
North 34% of NLA with DF = 1.0% to 3.0% Assuming average 32,000 lux, 1.0% DF = 320 lux 3.0% DF = 960 lux
5m
South
GREENBUILDINGINDEX SDN BHD | www.greenbuildingindex.org
DAYLIGHTING
OUTSIDE
INSIDE
OUTSIDE
INSIDE
A. No lightshelf
and no louvres
B. External lightshelf
and no louvres
DAYLIGHTING
OUTSIDE
INSIDE
OUTSIDE
INSIDE
C. With lightshelf
and louvres
DAYLIGHTING
OUTSIDE
INSIDE
OUTSIDE
INSIDE
internal lightshelves
5.7 4.8 3.7 4.9 5.0 3.9 Based on DF of 1.5%, ie approx 150 lux
0 A B C D E F
Glare risk
Glare risk
DAYLIGHTING
DAYLIGHT FACTOR STUDY
DAYLIGHTING
External Views (Open Plan Office)
BUILDING ENVELOPE
BUILDING ENVELOPE
BUILDING ENVELOPE
BUILDING ENVELOPE
Curtain Wall Tests
THANK YOU