INTEGRATED TELECOM POWER UNIT

ITPU 2008A Integrated Telecom Power Unit is an all-in-one power solution for Mobile Telecom Operators. It houses all required power and control equipments except Diesel Generators and Batteries in one 19 Inch Rack. The basic building block used is 25 Amp SMPS Rectifier as per latest TEC specifications. These rectifier modules have been designed to work in Indian electric and climatic environment and provide full power over applicable voltage and temperature range without any degradation in performance.

The system gets electric power from two sources, a three phase commercial electricity

connection and a single phase or three phase Diesel Generator. Using intelligent phase selection and distribution techniques, adequate numbers of Rectifier Modules are powered for providing DC power up to 3 BTS and for charging the back-up battery. DG is put ON automatically in case no good phase of

Mains Power is available and installed battery has discharged to the programmed threshold. The SMPS Rectifiers operate over a wide voltage range (90-300V Single Phase) eliminating the need of any additional Line Conditioning Unit (LCU), SVR or Servo Stabilizer for powering the BTS.

Provision is made for metering the energy consumed by each BTS. Required measurements, controls and alarm processing are done through Micro-processor based Control Modules. All required equipments including rectifiers for ultimate capacity of

300A are accommodated in a 19 Rack of height 1660 mm.

Salient Features
No need of using any SVR (LCU) or Servo Stabiliser improving system efficiency resulting in low operating cost and heat dissipation. Power Plant capable of giving full power over wide voltage range (90-300V) and temperature range (0-50 degree C) without any degradation. Protection against lightening and voltage surges Intelligent phase selection Up to 3 BTS powered as long as any single phase 90V is available. DG to run only if no good phase (90 V) is available and battery discharged to programmed threshold. Capacity field expandable from 25A to 300A using plug-in modules. Active current sharing among rectifiers in parallel Priority of critical load over non-critical load in case of battery discharge. Energy metering for individual Operators Climatic control of Indoor Shelter by minimum use of Air Conditioners Low Capital and Operating cost compared to conventional PIU and SMPS solutions Custom built AC Distribution Board (ACDB), DC Distribution Board DCDB) Optional IP 55 Cabinet Provision of Remote Monitoring and Control

Technical Specifications
AMF Function
Capacity Mechanical Time Event Logs Rated input voltage range 300A at 48V DC 19 Rack, Maximum size 600x500x2200 Real time & date-programmable Last 500 events 90 - 300V LN (R, Y, B).

Protections
Input Voltage protection at incoming power input Lightening protection MCB (TPN) Suitable for Capacity a) High Voltage Disconnect (HVD) b) Low Voltage Disconnect (LVD) The input shall be protected from multi -strike lightening 10/350 micro seconds, 50KA, as per IEC 61312-3 ( Optional)

DG Protection system
LLOP Low Fuel Over load Voltage Protection HCT / HWT Essential Critical Adjustable HVD & LVD- +-5V above/below the range Individual

Delays
DG on load Blackout delay DG cooling time DG start attempts DG Lock time Stop Command duration After DG starts and supply is healthy 10 seconds between mains and DG contactor changeover. 5 minutes Three attempts with delay between attempts (40 -40 -40 sec ) After three very short mains restoration 10-10-20 minutes. Settable from 0 to 30 Seconds Automatic DG battery, SMPS charger with boost/trickle charging & with constant current charging facility (12V) Charger suitable for charging the SMF/Conventional battery of 150AH. Generator controller with start, stop relays & other monitoring & control features Complete shutoff during fire/smoke Provision of Auto manual mode selection

Battery charger & DG controller unit

AC Distribution
Surge arrester-Class B+C Auto Phase selector Set point-for high temperature and Battery Voltage

As per customer requirement Optional Optional AS per Customer requirement Mains/DG status DG accumulated hours DG voltage

DG set measurements

Mains measurements LED / LCD Indications

Input Voltage (Individually for all three phases and DG ) Mains ON, Load on Mains, Load on DG, Smoke/ Fire Alarm, Over Load, LCU fail, Fuel Low, DG fail to start, DG fail to stop, Alternator fail, LLOP, System battery low, DG battery low, HCT/HWT, DG Manual, High shelter temperature Mains fail, Shelter Door open/ Intruder, Low fuel level, Common DG fault -- LLOP/Alt fault/HCT/HWT/V belt/Dg fail to start/DG fail to stop Smoke/Fire, Load on DG, DG on, DG Fail to stop, DG Fail to start, DG over load, High Room Temperature, Site on battery Default as per customer Through Keys ( Optional) Through Laptop ( Optional) Remote Control ( Optional)

Potential Free Contacts

Setting Programmable Parameters

SMR Function
Power factor Current harmonic distortion Efficiency Ripple & noise Acoustic noise Transient response Protections Indications Environmental Cooling DC Distribution LVD Disconnect Voltage Temp. Compensation Metering 0.99 at full load and Nominal input (>0.95 in other working conditions) Less than 10% for load 50 to 100% 90% (typical) at full load and Nominal input 100mV peak-to-peak & less than 2mv Sophomoric Less than 45dBA. Limited to 5% & recovery within 10mSec Galvanic Isolation (Input out of range), Over voltage, over load, short circuit. AC on, AC abnormal, under voltage, over voltage, Over load, Fan Fail, Fuse Fail, Rectifier Fail, Communication Fail Conforming to QM333 category B2 of QA Wing of BSNL. Forced Cooling. Custom configurable as per requirement. Single, Two Stage (Optional) 44.4V, reconnect 51.5V (settable) 3mV / degree Centigrade / cell. AC Input Voltage System, Load & Battery Current System, Load & Battery Voltage Individual Module Current

Alarms (Audio/Visual)

AC Input Abnormal Load Over/Under Voltage Rectifier Fail Mains on Battery Discharge System Overload Temp. Compensation Fail Battery Fail/ No battery/ Isolated from load Lightning & surge protection element fail

Status

AC Available System OK LVD System on Float Mode System on Charge Mode

Environment Specification
Operating Temperature Storage Temperature Humidity 0 50 C. -100C to + 600 C. 95% Max.

EXICOM TELE-SYSTEMS LTD.