You are on page 1of 3

Protect

Circuit protection

C60L circuit-breakers

B, C, K and Z curves
IEC 60947-2: 25 kA (y 25 A),
20 kA (32-40 A), 15 kA (50-63 A)
Function

b The circuit-breakers combine the following functions:


v protection of circuits against short-circuit currents
v protection of circuits against overload currents
v control
v isolation
v protection of persons against indirect contact with TN and IT neutral systems.
C60L circuit-breakers are used in the tertiary and industrial sectors.

Tripping curves
25399

B curve

When the short-circuit currents are weak (generators, long cables).


b Power circuit:
v ratings: 6 to 63 A set at 40 C
v tripping curve: the magnetic trip units operate between 3.2 and 4.8 In.

C curve

Cables feeding conventional loads.


b Power circuit:
v ratings: 0.5 to 63 A set at 40 C
v tripping curve: the magnetic trip units operate between 7 and 10 In.
25426

K curve

Loads with a high inrush current (motors, transformers).


b Power circuit:
v rating: 1 to 63 A set at 40 C
v tripping curve: the magnetic trip units operate between 10 and 14 In.

Z curve

Protection of electronic circuits.


b Power circuit:
v rating: 1 to 40 A set at 40 C
v tripping curve: the magnetic trip units operate between 2.4 and 3.6 In.

Technical data according to IEC 60947-2

25439

b
v
v
v
v
-

Power circuit:
voltage rating (Ue): 440 V AC
impulse voltage (Uimp): 6 kV
insulation voltage (Ui): 500 V AC
breaking capacity:
according to IEC 60947-2, Icu ultimate breaking capacity (O-CO cycle) :

Rating (A)

25452

Breaking capacity
Icu (kA)
0,5...25
1P
230...240
25
400...415
6 (1)
2P, 3P, 4P
230...240
50
400...415
25
440
20
32...40
1P
230...240
20
400...415
5 (1)
2P, 3P, 4P
230...240
40
400...415
20
440
15
50...63
1P
230...240
15
400...415
4 (1)
2P, 3P, 4P
230...240
30
400...415
15
440
10
(1) breaking capacity under 1 pole with IT isolated neutral system (case of double fault).

version: 4.1

Type

Voltage (V)

90120E.indd

Protect
Circuit protection

C60L circuit-breakers

B, C, K and Z curves
IEC 60947-2: 25 kA (y 25 A),
20 kA (32-40 A), 15 kA (50-63 A)
Generals technical data

b Fast closing: allows the high inrush currents of some loads to be better held.
b Isolation with positive break indication: opening is indicated by a green strip on the
device operating handle. This indicator shows opening contacts of all the poles.
b Number of cycles (O-C): 20,000.
b Environment:
v tropicalisation: treatment 2 (relative humidity: 95 % at 55 C) according to
IEC 60068-1
v weight (g):
Type

1P
120

2P
240

3P
360

4P
480

b Connection: tunnel terminals for the following cables:


v 16 mm2 flexible or 25 mm2 rigid up to 25 A ratings
v 25 mm2 flexible or 35 mm2 rigid for 32 to 63 A ratings.

Rfrences
Type

1P

2P

3P

90120E.indd

version: 4.1

Rating
(A)

Width
in mod.
of 9 mm

Catalogue
number
B curve

C curve

K curve

Z curve

0.5
1
1.6
2
3
4
6
10
16
20
25
32
40
50
63

2
2
2
2
2
2
2
2
2
2
2
2
2
2
2

25331
25332
25333
25334
25335
25336
25337
25338
25339

25406
25392
25393
25394
25395
25396
25397
25398
25399
25400
25401
25402
25403
25404

25460
25461
25462
25463
25464
25465
25467
25468
25469
25470
25471
25472
25473
25474

26133
26134
26135
26136
26137
26139
26141
26142
26143
26145
26146
26147
-

0.5
1
1.6
2
3
4
6
10
16
20
25
32
40
50
63

4
4
4
4
4
4
4
4
4
4
4
4
4
4
4

25357
25358
25359
25360
25361
25362
25363
25364
25365

25407
25418
25419
25420
25421
25422
25423
25424
25425
25426
25427
25428
25429
25430

25478
25479
25480
25481
25482
25483
25485
25486
25487
25488
25489
25490
25491
25492

26154
26155
26157
26158
26159
26161
26163
26164
26165
26166
26167
-

0.5
1
1.6
2
3
4
6
10
16
20
25
32
40
50
63

6
6
6
6
6
6
6
6
6
6
6
6
6
6
6

25370
25371
25372
25373
25374
25375
25376
25377
25378

25408
25431
25432
25433
25434
25435
25436
25437
25438
25439
25440
25441
25442
25443

25496
25497
25498
25499
25500
25501
25503
25504
25505
25506
25507
25508
25509
25510

26174
26176
26177
26178
26180
26182
26184
26185
26224
26225
26226
-

Protect
Circuit protection

C60L circuit-breakers

B, C, K and Z curves
IEC 60947-2: 25 kA (y 25 A),
20 kA (32-40 A), 15 kA (50-63 A)
Rfrences
Type

Rating
(A)

4P

0.5
1
1.6
2
3
4
6
10
16
20
25
32
40
50
63

Width
in mod.
of 9 mm
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8

Catalogue
number
B curve

C curve

K curve

Z curve

25383
25384
25385
25386
25387
25388
25389
25390
25391

25409
25444
25445
25446
25447
25448
25449
25450
25451
25452
25453
25454
25455
25456

25514
25515
25516
25517
25518
25519
25521
25522
25523
25524
25525
25526
25527
25528

26232
26234
26236
26237
26239
26241
26242
26243
26244
26245
26246
-

Connection
1

1P

2P

3P

4P

Additional information
Vigi modules: page 90116
Electrical auxiliaries: page 90142
Accessories: page 91903
Dimensions: page 90148
Curves: page 90180


version: 4.1

90120E.indd