You are on page 1of 17

BUILDINGASSESSMENTREPORT

311WestMainStreet,Lansdale,PA

Presentedby:
ChristopherJ.Fazio,P.E. BoroughEngineer GeorgeLocke BuildingCodeOfficial

August2011

BUILDINGASSESSMENTREPORT 311WestMainStreet,Lansdale,PA REMINGTON,VERNICK&BEACHENGINEERS

PURPOSE
TheBoroughofLansdaledesiredtohaveacertified BuildingCodeOfficialreviewthepropertylocatedat311 WestMainStreetforthepurposeofdeterminingcode compliance. Twomainquestionstobeanswered:
Canandshouldthebuildingbeopentopublicuse? Arethereanysignificantissueswithregardstolifeandsafety?

BUILDINGASSESSMENTREPORT
311WestMainStreet,Lansdale,PA

BUILDINGREVIEWPARAMETERS
Reviewofthebuildingconstructiontodeterminecode compliancewith:
The2003InternationalBuildingCode(includingtheICC/ANSI A117.1 1998),whichwastheadoptedcodeatthetimethat renovationsweredonetothebuilding. The2009InternationalBuildingCode(includingtheICC/ANSI A117.1 2003).

BUILDINGASSESSMENTREPORT
311WestMainStreet,Lansdale,PA

BUILDINGASSESSMENTTEAM
StateCertifiedBuildingCodeOfficials PALicensedProfessionalElectricalEngineers PALicensedProfessionalMechanicalEngineers PALicensedProfessionalStructuralEngineers

BUILDINGASSESSMENTREPORT
311WestMainStreet,Lansdale,PA

RECORDS&AVAILABILITYOFINFORMATION
Unlimitedaccesstoallavailablerecordsonfileatthe Borough. Interviewmembersofthecurrentstafftoassemblea timeline. Fieldreviewandinspectionofthestructureitself. InternalinspectionswereperformedonDecember1, 2010,December17,2010,andDecember26,2010.

BUILDINGASSESSMENTREPORT
311WestMainStreet,Lansdale,PA

HISTORYOFTHEBUILDING
Thebuildinglocatedat311313W.MainStreet,Lansdale Borough,PAwithapresentuseastheLansdaleCenter forthePerformingArts. SeveralCommercialareasarealsoincludedalongthe frontofthebuilding. Thebuildingisathreestorymasonrystructurewitha stonefaade;grossbuildingareaof28,319squarefeet. ThebuildingwasoriginallyconstructedasaMasonic Templein1929.

BUILDINGASSESSMENTREPORT
311WestMainStreet,Lansdale,PA

OBSERVATIONSFROMTHEFILEANALYSIS
SignedArchitecturalplansandanapplicationforabuildingpermit weresubmittedtotheBoroughofLansdaleonMay16,2008to renovatetheexistingbuilding. AbuildingpermitwasissuedbytheBoroughofLansdaleonAugust 7,2008. ConstructionrenovationsbeginningonoraboutAugust14,2007 andendingonNovember3,2008. NofinalCertificatesofOccupancywereissuedforthebuilding. MultipleinspectionswereperformedbytheProjectArchitect, DirectorofCodeEnforcementandThirdPartyBuildingCodeOfficial duringallaspectsoftheconstruction.

BUILDINGASSESSMENTREPORT
311WestMainStreet,Lansdale,PA

REPORTFINDINGS
Totalof38Codeviolationswerefoundinthebuildingsas follows:
Accessibility FireRatedConstruction ElectricalSystems MechanicalSystems Structural 14violations 10violations 7violations 2violations 5violations

BUILDINGASSESSMENTREPORT
311WestMainStreet,Lansdale,PA

ACCESSIBILITYCODEVIOLATIONS
Lackofahandicappedaccessibleentrance. Lackofhandicappedaccessibleparkingstallsincludingvan accessiblestalls. Sidewalkscrossslopesthataretoosteepandseverefor accessibility. Lackofaflatproperlysizedlandingareaforwheelchair maneuverability. Bathroomsarenothandicappedaccessiblecomplaint. Thechairliftprovidingaccessibilitytotheassemblyareadoes not appeartohavetherequiredmaneuveringclearance. Theproximityoftheadjacentbuildingandtheslopeandlengthof theegresspathmakethisnoncodecompliant. Theexistingretailspacesareeachrequiredtohavepublic restrooms.
BUILDINGASSESSMENTREPORT
311WestMainStreet,Lansdale,PA

FIRERATEDCONSTRUCTIONCODEVIOLATIONS
Theexitdooronthemainfloorlevelleadstoanarrowdeadend passagewaybetweentheCulturalArtsBuildingandanadjacent building. Theexteriorwalloftheadjacentbuildingisnotafirerated assembly. Lackoftwohourratedfirewallsbetweenthevariousmixedusesin thebuildings. Theshaftenclosure/smokebarrierbetweenthebasementleveland firstfloorlevelisincompleteandlacksaonehourfirerating. Foamusedforsomeofthesealingpenetrations,draftstoppingand fireblockingappearedtobeflammablewhenintroducedtoaflame source.

BUILDINGASSESSMENTREPORT
311WestMainStreet,Lansdale,PA

FIRERATEDCONSTRUCTIONCODEVIOLATIONS
Theexitpassagewayintheassemblyoccupancyisnoncompliant andnotfirerated. Theglasswallallowingaviewintothebasementisrequiredtohave atwohourratinganddoesnot. Questionablewaterpressureandlackofaboosterpump. Updateoftheexistingfiresuppressionsystemelementstobring it intocurrentcompliance.

BUILDINGASSESSMENTREPORT
311WestMainStreet,Lansdale,PA

ELECTRICALSYSTEMCODEVIOLATIONS
Temporarywiringhadbeeninstalledthroughoutthe entireportionofthebuildingandmustbereplaced. Nonmetallicconductorswereinstalledthroughoutthe mercantileoccupancieswithinthedropped/suspended ceiling.Theseconductorsmustberemovedandreplaced withtypessuitableforthatapplication. Severaljunctionboxesandconduitboxesthatwerenot enclosedwithcovers. Severalconductorswereincontactwiththemetallic sprinklerpiping.

BUILDINGASSESSMENTREPORT
311WestMainStreet,Lansdale,PA

MECHANCIALSYSTEMCODEVIOLATIONS
Thereisnoheatorventilationprovidedtotheunfinished portionofthebuilding. Portableheaterscannotbeusedtomeetthese requirements.

BUILDINGASSESSMENTREPORT
311WestMainStreet,Lansdale,PA

STRUCTURALCODEVIOLATIONS
Theexistingcommercialwaterproofingcompoundisnot fullyprotectingthebasementfromwaterintrusion Thesumppumpshouldhaveabatterybackupand alarminstalled. Theexistinginternalstairsrequirerepairandmustbe securedtotheadjacentwall

BUILDINGASSESSMENTREPORT
311WestMainStreet,Lansdale,PA

COSTSTOBRINGTHEBUILDING INTOCODECOMPLIANCE
BaseEstimatedCosts
Construction ProjectBiddingand ConstructionManagement TotalEstimatedProjectCosts TotalEstimatedProjectCosts TOTALPROJECTCOSTS $208,692.00 $31,303.80 $239,995.80 $145,200.00 $385,195.80

AlternateCost GlassWallReplacement

Whatdoesthisinclude?

BUILDINGASSESSMENTREPORT
311WestMainStreet,Lansdale,PA

RECOMMENDATIONS
Correcttheinternalissueswiththebuildingpermitapprovalprocess DONE!
FollowtheUCCprocessimplicitlyforplanapprovalsandconstruction InhouseBuildingCodeOfficialsforefficiency Accuraterecordkeepingofcertifiedplansandinspectionreports

Donotallowaccesstothebuildinguntilallcoderelateditems arerectified. Restarttheprocess:


Reviewthebuildingarchitecturally Acquirenewprofessionallygeneratedcodecompliantarchitecturalplansto bringthebuildingintocompliance HaveaUCCCertifiedPlanExaminerreviewandultimatelyapprove the submittedarchitecturalplans Approveformalbuildingpermitsfortheconstruction.Thisshouldbedoneby thedesignatedBuildingCodeOfficialfortheBorough. Engageacontractorthroughapublicbiddingprocesstoconstructtheprojectin compliancewiththeCertifiedPlansandunderthesupervisionof acompetent ConstructionManagerassignedbytheBorough. HavetheBoroughBuildingCodeOfficialinvolvedduringallaspectsof constructionandissueafinalcertificateofoccupancyuponcompletionofALL constructionactivities.
BUILDINGASSESSMENTREPORT
311WestMainStreet,Lansdale,PA

922FayetteStreet Conshohocken,PA19428 (610)9401050 www.rve.com