POWER GRID CORPORATION OF INDIA LTD.

DATA, DESIGNS, CALCULATIONS AND DRAWINGS TO BE FURNISHED BY OWNER 1.


OVERHEAD LINE CROSSING : a) DATA AND DESIGNS:

1.

Location of the proposed crossing, the names of railway stations on either side of the crossing, the distance of the crossing from the nearest railway station, the painted numbers of Telegraph Poles and or traction mast or structures between which the crossing is proposed to be located and the exact location to such poles or masts or structures:- Please refer our Drawing No. 09031-T-TLOS-MS-0002 Rev B for Railway crossing detail. Particulars of the Overhead line are as below: Name of transmission line : 765 kV S/C Agra Jattikalan TL. Voltages : 765 kV Frequency : 50Hz No. of Phases : 3 (Three) Size of Conductor : ACSR (Bersimis), Overall Dia., 35.05 mm2 Earthing Type : Pipe type (Each Tower is earthed Individually at two diagonally Opposite legs). WIND PRESSURE ADOPTED :Wind Zone = 4 Wind Velocity = 47 m/sec. Terrain category = 1 & Reliability level = 1 & Hence Basic wind Pressure = 83Kg/mtr2. TEMPERATURE DATA ADOPTED :
Material Conductor Maximum Temp 85 C
0

2.

1.

2.
Sl No 1

Minimum Temp 0 C
0

Average Temp 32 0C

Page 1 of 4

Earthwire

53 0C

0 0C

32 0C

3. Particulars of Ice/Snow loading, if any, adopted: - There is no ice or snow loading. 4. Factors of safety adopted in the designs
Sl No 1 2 Material Conductor Earthwire At temperature 32 C 32 C
0 0

At Wind Load Full Wind Load Full Wind Load

F.O.S. 2.04 2.075

And Tower structures are designed as per IS : 2062 & IS 8500 & Ultimate Loads are considered in design & hence F.O.S. is considered as per above mentioned IS code.

5.

Design calculations of structures and foundations for the crossing span, communication lines or guarding, if any. (Copy enclosed).

Note: - If the structures and foundations are of standard type used for the transmission/distribution line concerned, the detailed design calculations shall be furnished.

6.

Calculations leading to the minimum values under worst conditions of the following :i) Vertical clearance between the lowest crossing conductor, communication lines and guarding different railway tracks in the crossing span: 24.7 Meters ii) Vertical clearance between the lowest crossing conductor, communication lines and / or Guarding and railways conductors of the traction system or other conductors : 18.0 Meters iii) Horizontal clearance to railway mast/structure/building, if any: N/A Note: - Full particulars of the number, size, material and characteristics of various wires and conductors shall be furnished. CONDUCTOR & EARTHWIRE PROPERTIES :Sl No 1 2 Decription Type Stranding & wire Diameter Alluminium Steel Conductor Per Phase Overall Diameter (mm) Total Cross Sectional Area (Sqmm) Unit Mass (kg/km) Conductor ACSR "BERSIMIS" Conductor 42/4.57 7/2.54 4 35.05 725 2181 Earthwire 7/3.66mm GS Earthwire 7/3.66 NA 10.98 73.65 583

3 4 5 6

Page 2 of 4

7 8 9 10

Minimum UTS (KN) Ruling Design Span (Metres) Modulus of Elasticity (Kg/Sqmm) Co-efficient of Linear Expansion

154 400 6322 0.0000212

68.4 400 19361 0.0000115

7. PARTICULARS OF INSULATORS, BRIDLING OF THE CONDUCTORS:TYPE OF STRING SIZE OF DISC INSULATOR (MM) 280x170 MINIMUM CREEPAGE DISTANCE OF EACH DISC. (MM) 370 NO. OF STD. DISC ELECTROMECHANICAL STRENGTH OF EACH INSULATOR IN THE STRING IN KN 210

Quadruple Tension String

4X35

8.

Details of guarding size of guard and cross wires & their characteristics. A detailed drawing showing the guarding arrangement, if provided, shall be given: N/A

9. Size and characteristics of guy wire, if provided, and the number of supports: N/A 10. Details of earthing indicating the earth electrode, size of earthing connection, method of connection to the support and the method of artificial soil treatment if proposed. Details of pipe type earthing, if contemplated, shall be furnished: Drawing No. 09031-T-TL-OS-MS-0002 Rev B enclosed. 11. Details of protection against moving road vehicles: N/A 12. Particulars of anti-climbing devices, if provided, & warning and caution notices:Drawings No 09031-T-TL-OS-MS-0002 Rev B 13. Detailed scheme of protection for the transmission / distribution line including particulars, of relays, operating times etc. and particulars of circuit breakers, if any. Main line protection shall be used as per existing practice of 765 KV lines. Particulars of Relay: Distance protection 7 SA 523, Instantaneous Type (Less than 100 ms) Circuit Breaker: SF6 type. 14. Layout and site plan of the proposed crossing indication railways boundaries:Please refer our Drawing No. 09031-T-TL-OS-MS-0002 Rev B

Page 3 of 4

15. Longitudinal elevation of the crossing. The drawing shall indicate full particulars of one span on either side of the crossing span with various clearances with respect to the Railway Tracks, The drawing shall show the cross section of Railway formation and tracks: - Drawing No. 09031-T-TL-OS-MS-0002 Rev B enclosed. 16. Drawing for warning and caution notices: - Drawing No. 09031-T-TL-OS-MS-0002 Rev B enclosed.

Page 4 of 4