RELAY INFORMATION: Features: Simultaneous phase-phase and phase- earth loop impedance measurement, with individual numerical measuring elements for each type of fault and each distance zone, ensures fast and reliable fault detection. Minimum operating time: 13 ms Typical operating time of impedance measuring function: 28 ms. Multiprocessor design guarantees high availability together with excellent possibilies for combining optional functions. Numerical filtering and measuring technique ensure correct performance during CT saturation and CVT transients. Versatile local human machine communication (HMC) from the relay front panel together with two optional serial ports brings REL 100 close to the any user wherever they may be located (in the substation, in the control centre or in the office). Basic version of REL 100 includes: three forward and one reverse distance zones with individual setting of reach in reactive and resistive direction as well setting of earth return compensating factor. switch onto fault protection. three-phase tripping.
India
Knowledge Is Power SM
Apparatus Maintenance and Power
Distance Protection:
------------Typical Operating Time = 28ms Minimum Operating current = 0.2*Ir Reset Time: Forward = 40ms Reverse = 60ms Tripping mode: Three Phase / Single Phase tripping Number of Zones: 3-forward / 1-reverse Impedance Setting Range at Ir = 1.0A Reactive reach = (0.1 150)Ohms/Phase Resistive reach: - Phase Phase = (0.1 150)Ohms/Phase - Phase Loop = (0.1 150)Ohms/Phase Setting range of Timer = (0 10)s Power Swing detection element: (0.1 150)Ohms
-------------
---------
India
Knowledge Is Power SM
Apparatus Maintenance and Power
RELAY SETTINGS:
CLIENT: RELIANCE ENERGY LTD-DAHANU SERVICE SETTING: ZONE:-1- EARTH FAULT UNIT: R1 = 15.02 OHM X1 = 15.99 OHM KN = 0.59 t1 = 0ms PHASE FAULT UNIT: R1 = 3.85 OHM X1 = 15.99 OHM t1 = 0ms ZONE:-2 - EARTH FAULT UNIT: R2 = 20.4 OHM X2 = 22.41 OHM KN = 1.12 t2 = 400ms PHASE UNIT: R2 = 4.8 OHM X2 = 22.41 OHM t2 = 400ms ZONE:-3 - EARTH FAULT UNIT: R3 = 23.81 OHM X3 = 43.97 OHM KN = 0.59 t3 = 750ms PHASE UNIT: R3 = 7.97 OHM X3 = 43.97 OHM t3 = 750ms
India
Knowledge Is Power SM
Apparatus Maintenance and Power
STEP:-1
SELECT DATABASE OF RELZ100
India
Knowledge Is Power SM
Apparatus Maintenance and Power
STEP:-2
HOW TO SET RELAY CHARACTERISTIC FOR TEST? SINGLE CLICK ON RELAY PARAMETERS
India
Knowledge Is Power SM
Apparatus Maintenance and Power
STEP:-3
OPEN EXISTING DATABASE
India
Knowledge Is Power SM
Apparatus Maintenance and Power
India
Knowledge Is Power SM
Apparatus Maintenance and Power
Management For Energy Delivery STEP:-5 READY MADE SHAPES ARE OPEN
India
Knowledge Is Power SM
Apparatus Maintenance and Power
STEP:-6
SINGLE CLICK ON QUAD 2 SHAPE & ENTER RELAY PARAMETERS
ENTER R VALUE
ENTER X VALUE & PUT ANGLE = 90 DEG. ENTER VALUES OF DIRECTIONAL LINES PRESS OK BUTTON & SAVE IT.
India
Knowledge Is Power SM
Apparatus Maintenance and Power
India
Knowledge Is Power SM
Apparatus Maintenance and Power
Management For Energy Delivery HOW TO ENTER IN TESTPLAN FOR TEST? STEP:-1 SINGLE CLICK ON TESTPLAN TAB
India
Knowledge Is Power SM
Apparatus Maintenance and Power
India
Knowledge Is Power SM
Apparatus Maintenance and Power
India
Knowledge Is Power SM
Apparatus Maintenance and Power
India
Knowledge Is Power SM
Apparatus Maintenance and Power
India
Knowledge Is Power SM
Apparatus Maintenance and Power
SELECT ANY ONE OPTION FOR TEST; 1) RADIAL LINES 2) User Drawn Lines
India
Knowledge Is Power SM
Apparatus Maintenance and Power
STEP:-7
SINGLE CLICK ON TEST TAB
RIGHT CLICK IN BOX; IT SHOWS ONLINE VECTOR & MEASUREMENT NOW, APPLY RUN COMMAND FOR TEST.
India
Knowledge Is Power SM
Apparatus Maintenance and Power
RED & GREEN POINT SHOWS; ACTUAL OPERATING POINTS Dotted line shows tolerances
India
Knowledge Is Power SM
Apparatus Maintenance and Power
India
Knowledge Is Power SM
Apparatus Maintenance and Power
SELECT BC FAULT
India
Knowledge Is Power SM
Apparatus Maintenance and Power
India
Knowledge Is Power SM
Apparatus Maintenance and Power
India
Knowledge Is Power SM
Apparatus Maintenance and Power
SELECT AN FAULT
India
Knowledge Is Power SM
Apparatus Maintenance and Power
India
Knowledge Is Power SM
Apparatus Maintenance and Power
India
Knowledge Is Power SM
Apparatus Maintenance and Power
India
Knowledge Is Power SM
Apparatus Maintenance and Power
ADD POINT TO LIST BY MOUSE CLICKING ON R-X PLANE SELECT FAULT TYPE
India
Knowledge Is Power SM
Apparatus Maintenance and Power
India
Knowledge Is Power SM
Apparatus Maintenance and Power
India
Knowledge Is Power SM
Apparatus Maintenance and Power
THANK YOU DOBLE ENGINEERING PVT LTD 305-SAKAR OLD PADRA ROAD VADODARA-390 015 INDIA PH: (+91) (265) 555 77 15 FAX: (+91) (265) 235 62 85 EMAIL: kdave@doble.com