TESTING OF RELZ 100 RELAY WITH F6150 & F6TEST SOFTWARE


KAMIN DAVE (RELAY APPLICATION ENGINEER)

DOBLE ENGINEERING PVT LTD

India

Knowledge Is Power SM
Apparatus Maintenance and Power

Management For Energy Delivery

RELAY INFORMATION: Features: Simultaneous phase-phase and phase- earth loop impedance measurement, with individual numerical measuring elements for each type of fault and each distance zone, ensures fast and reliable fault detection. Minimum operating time: 13 ms Typical operating time of impedance measuring function: 28 ms. Multiprocessor design guarantees high availability together with excellent possibilies for combining optional functions. Numerical filtering and measuring technique ensure correct performance during CT saturation and CVT transients. Versatile local human machine communication (HMC) from the relay front panel together with two optional serial ports brings REL 100 close to the any user wherever they may be located (in the substation, in the control centre or in the office). Basic version of REL 100 includes: three forward and one reverse distance zones with individual setting of reach in reactive and resistive direction as well setting of earth return compensating factor. switch onto fault protection. three-phase tripping.

DOBLE ENGINEERING PVT LTD

India

Knowledge Is Power SM
Apparatus Maintenance and Power

Management For Energy Delivery

Distance Protection:
------------Typical Operating Time = 28ms Minimum Operating current = 0.2*Ir Reset Time: Forward = 40ms Reverse = 60ms Tripping mode: Three Phase / Single Phase tripping Number of Zones: 3-forward / 1-reverse Impedance Setting Range at Ir = 1.0A Reactive reach = (0.1 150)Ohms/Phase Resistive reach: - Phase Phase = (0.1 150)Ohms/Phase - Phase Loop = (0.1 150)Ohms/Phase Setting range of Timer = (0 10)s Power Swing detection element: (0.1 150)Ohms

-------------

---------

DOBLE ENGINEERING PVT LTD

India

Knowledge Is Power SM
Apparatus Maintenance and Power

Management For Energy Delivery

RELAY SETTINGS:
CLIENT: RELIANCE ENERGY LTD-DAHANU SERVICE SETTING: ZONE:-1- EARTH FAULT UNIT: R1 = 15.02 OHM X1 = 15.99 OHM KN = 0.59 t1 = 0ms PHASE FAULT UNIT: R1 = 3.85 OHM X1 = 15.99 OHM t1 = 0ms ZONE:-2 - EARTH FAULT UNIT: R2 = 20.4 OHM X2 = 22.41 OHM KN = 1.12 t2 = 400ms PHASE UNIT: R2 = 4.8 OHM X2 = 22.41 OHM t2 = 400ms ZONE:-3 - EARTH FAULT UNIT: R3 = 23.81 OHM X3 = 43.97 OHM KN = 0.59 t3 = 750ms PHASE UNIT: R3 = 7.97 OHM X3 = 43.97 OHM t3 = 750ms

DOBLE ENGINEERING PVT LTD

India

Knowledge Is Power SM
Apparatus Maintenance and Power

Management For Energy Delivery

STEP:-1
SELECT DATABASE OF RELZ100

DOUBLE CLICK ON RELZ100

DOBLE ENGINEERING PVT LTD

India

Knowledge Is Power SM
Apparatus Maintenance and Power

Management For Energy Delivery

STEP:-2
HOW TO SET RELAY CHARACTERISTIC FOR TEST? SINGLE CLICK ON RELAY PARAMETERS

DOBLE ENGINEERING PVT LTD

India

Knowledge Is Power SM
Apparatus Maintenance and Power

Management For Energy Delivery

STEP:-3
OPEN EXISTING DATABASE

DOBLE ENGINEERING PVT LTD

India

Knowledge Is Power SM
Apparatus Maintenance and Power

Management For Energy Delivery

STEP:-4 Modify your settings in Existing database

Select zone & Press Modify button


SELECT GENERAL & ENTER KN VALUE

DOBLE ENGINEERING PVT LTD

India

Knowledge Is Power SM
Apparatus Maintenance and Power

Management For Energy Delivery STEP:-5 READY MADE SHAPES ARE OPEN

DOBLE ENGINEERING PVT LTD

India

Knowledge Is Power SM
Apparatus Maintenance and Power

Management For Energy Delivery

STEP:-6
SINGLE CLICK ON QUAD 2 SHAPE & ENTER RELAY PARAMETERS

ENTER R VALUE

ENTER X VALUE & PUT ANGLE = 90 DEG. ENTER VALUES OF DIRECTIONAL LINES PRESS OK BUTTON & SAVE IT.

DOBLE ENGINEERING PVT LTD

India

Knowledge Is Power SM
Apparatus Maintenance and Power

Management For Energy Delivery STEP:-7

ENTER TOLERANCES & CLOSE WINDOW

DOBLE ENGINEERING PVT LTD

India

Knowledge Is Power SM
Apparatus Maintenance and Power

Management For Energy Delivery HOW TO ENTER IN TESTPLAN FOR TEST? STEP:-1 SINGLE CLICK ON TESTPLAN TAB

DOUBLE CLICK ON TEST PLAN

DOBLE ENGINEERING PVT LTD

India

Knowledge Is Power SM
Apparatus Maintenance and Power

Management For Energy Delivery STEP:-2 NOW, TEST PLAN IS OPEN

SELECT Z-CHAR MODULE

DOBLE ENGINEERING PVT LTD

India

Knowledge Is Power SM
Apparatus Maintenance and Power

Management For Energy Delivery STEP:-3 SINGLE CLICK ON TEST ELEMENTS

SELECT FUNCTION NAME

DOBLE ENGINEERING PVT LTD

India

Knowledge Is Power SM
Apparatus Maintenance and Power

Management For Energy Delivery STEP:-4

SELECT TEST METHOD CONSTANT-I, V or Z

DOBLE ENGINEERING PVT LTD

India

Knowledge Is Power SM
Apparatus Maintenance and Power

Management For Energy Delivery STEP:-5 SELECT TRIGGER

SELECT TRIGGER (Say, Open to Close)

DOBLE ENGINEERING PVT LTD

India

Knowledge Is Power SM
Apparatus Maintenance and Power

Management For Energy Delivery STEP:-6 SINGLE CLICK ON TEST LINES

SELECT ANY ONE OPTION FOR TEST; 1) RADIAL LINES 2) User Drawn Lines

ENTER ANGLE BOUNDARY WITH DELTA STEP

DOBLE ENGINEERING PVT LTD

India

Knowledge Is Power SM
Apparatus Maintenance and Power

Management For Energy Delivery

STEP:-7
SINGLE CLICK ON TEST TAB

SELECT FAULT TYPE

RIGHT CLICK IN BOX; IT SHOWS ONLINE VECTOR & MEASUREMENT NOW, APPLY RUN COMMAND FOR TEST.

DOBLE ENGINEERING PVT LTD

India

Knowledge Is Power SM
Apparatus Maintenance and Power

Management For Energy Delivery

TESTED CHARACTERISTIC ON AB FAULT

BLUE COLOR SHOWS EXPECTED CHARACTERISTIC

RED & GREEN POINT SHOWS; ACTUAL OPERATING POINTS Dotted line shows tolerances

DOBLE ENGINEERING PVT LTD

India

Knowledge Is Power SM
Apparatus Maintenance and Power

Management For Energy Delivery TEST RESULTS OF AB FAULT

TEST VOLTAGE & CURRENT

DOBLE ENGINEERING PVT LTD

India

Knowledge Is Power SM
Apparatus Maintenance and Power

Management For Energy Delivery

SELECT BC FAULT FOR TEST

SELECT BC FAULT

DOBLE ENGINEERING PVT LTD

India

Knowledge Is Power SM
Apparatus Maintenance and Power

Management For Energy Delivery

TESTED CHARACTERISTIC ON BC FAULT

DOBLE ENGINEERING PVT LTD

India

Knowledge Is Power SM
Apparatus Maintenance and Power

Management For Energy Delivery

TEST RESULTS OF BC FAULT

DOBLE ENGINEERING PVT LTD

India

Knowledge Is Power SM
Apparatus Maintenance and Power

Management For Energy Delivery SELECT AN FAULT

SELECT AN FAULT

DOBLE ENGINEERING PVT LTD

India

Knowledge Is Power SM
Apparatus Maintenance and Power

Management For Energy Delivery TESTED CHARACTERISTIC OF AN FAULTS

DOBLE ENGINEERING PVT LTD

India

Knowledge Is Power SM
Apparatus Maintenance and Power

Management For Energy Delivery

TEST RESULTS OF AN FAULT

DOBLE ENGINEERING PVT LTD

India

Knowledge Is Power SM
Apparatus Maintenance and Power

Management For Energy Delivery

(B) TIME TEST: STEP:-1


SELECT Z-TIME MODULE & DOUBLE CLICK ON TIMER TEST

DOBLE ENGINEERING PVT LTD

India

Knowledge Is Power SM
Apparatus Maintenance and Power

Management For Energy Delivery

STEP:-2 SINGLE CLICK ON TEST POINTS

ADD POINT TO LIST BY MOUSE CLICKING ON R-X PLANE SELECT FAULT TYPE

DOBLE ENGINEERING PVT LTD

India

Knowledge Is Power SM
Apparatus Maintenance and Power

Management For Energy Delivery

STEP:-3 SELECT FAULT TYPE (Say, AB)

SELECT FAULT TYPE

SELECT OPTION R-X PLANE

DOBLE ENGINEERING PVT LTD

India

Knowledge Is Power SM
Apparatus Maintenance and Power

Management For Energy Delivery

SAME RESULT IN Z-T PLANE

SELECT Z-T PLANE

DOBLE ENGINEERING PVT LTD

India

Knowledge Is Power SM
Apparatus Maintenance and Power

Management For Energy Delivery

THANK YOU DOBLE ENGINEERING PVT LTD 305-SAKAR OLD PADRA ROAD VADODARA-390 015 INDIA PH: (+91) (265) 555 77 15 FAX: (+91) (265) 235 62 85 EMAIL: kdave@doble.com