FACILITY DESIGN STANDARDS APPENDIX D Page 1

APPENDIX D CAD DRAWING STANDARDS


1.1 Purpose The purpose of this appendix is to provide the standards and specifications necessary to create construction and as-built CAD drawings in a manner that produces a consistent and uniform set of drawings. Additionally it facilitates the future modification of these same drawings and minimizes the integration effort required to incorporate these drawings into the Lockheed Martin Space System Facilities master as-built drawing databases. The goal of Lockheed Martin Space System (LMSS) Facility Technology Resource Management (TRM) group (see section 1.8) is to ensure that submitted drawings by LMSS contractors and by LMSS Facilities Engineering groups adhere to these standards. LMSS Contractors and LMSS Facilities Engineering groups are required to create CAD drawings according to the following guidelines and those provided in Section 11 of the Design Standards. CAD System The preferred CAD system is AutoCAD. Contact the TRM group for information on the acceptable releases of AutoCAD. All LMSS Facility Engineers will utilize the AutoCAD application provided and configured by TRM group to create drawings. LMSS Contractors may generate drawings in other CAD systems; however, submittals of construction and as-built drawings to LMSS shall be in AutoCAD format. All CAD files of as-built drawings must conform to the file set-up and layering conventions discussed throughout the following sections. CAD files of Issued For Construction (IFC) drawings do not need to comply with these standards but the files need to be readable and in AutoCAD format. CAD File IDs and Drawing Numbers A. CAD file IDs shall be according to Section 2.10, CAD File Naming Convention. B. Drawing numbers shall conform to Figure 1.1, Title Block Drawing Number Convention. C. Drawings such as Issued for Construction, demolition, reference sheets, etc. do not require standard drawing numbers. Use a temporary drawing number that may conform to Figure 1.1. Symbols and Cross Referencing in as-built Drawings A. Use LMSS standard drawing-symbols and legends, Figures 11.10 through 11.17 of the Design Standards. AutoCAD blocks of these symbols can be obtained when available by contacting the TRM group. B. When cross referencing on drawings such as plan drawings to non-plan drawings such as details, sections and others, use the 5 character sequence number of the drawing numbers (i.e. 001AM). Do not use Temp IDs for referencing purposes. This section applies to as-built drawings only. Construction drawings may be treated as seen fit by the creator of the drawings. However, keep in mind that drawings qualified to become the as-built set must comply with these requirements. Ownership of Electronic Drawing Files and Hard Copy Drawings All drawing in electronic or hardcopy format, existing and new, shall remain or become the property of LMSS. Any copies retained shall not be reproduced or released to persons outside LMSS without the written authorization of LMSS. In support of this statement, all drawings shall use the latest LMSS Facilitys Drawing Title block, which contains the latest modifications to the revision blocks proprietary data. Required Drawings A. Construction Drawings Submit a soft copy set of the latest revision of the Issued for Construction drawings, in their original issued condition. These drawing do not need to comply with Appendix D standards however they shall be in a readable and workable condition. External references, if used, must remain intact and all references must be included in the submittal. All third party fonts and other electronic resources such as referenced drawings used to generate these drawings shall be included Revised May, 2005 Lockheed Martin Space Systems

1.2

1.3

1.4

1.5

1.6

FACILITY DESIGN STANDARDS APPENDIX D Page 2 in the submittal, as well. AutoCADs Pack&Go option is a preferable method of collecting and submitting these drawings to LMSS. B. As-Built Drawings Submit a complete set of as-built drawings with all field as-built red-lines incorporated. These drawings shall be in compliance with Section 11 and Appendix D of the Design Standards. Refer to section 11 of the Design Standards for the project categories, description and requirements. 1.7 Submittal Process CAD files shall be submitted to the LMSS Facility Project Scheduler. Do not submit as-built CAD files directly to TRM group or the LMSS project manager. CAD files shall be submitted only when LMSS Facility Engineering review of the plots is complete and plots have been approved. CAD files must include all changes made to the drawings from the results of the engineering review. TRM Group Technology Resource Management group is a team within LMSS Facility Planning and Asset Management, Organization EH-13. Any questions regarding the content of Appendix D shall be forwarded to one of the following members of this team. Any requests for drawings shall be forwarded via phone or email to Dave Kaeini. Requests will be scheduled to the next available member of the TRM group. The list is sorted by contact order. David Kaeini Bert Palmon Michelle Cabreros Emma Forlanda Nancy Neilsen (408) 756-1625 Dave.Kaeini@lmco.com (408) 756-1059 Bert.Palmon@lmco.com (408) 756-1068 Michelle.K.Cabreros@lmco.com (408) 756-1267 Emma.Forlanda@lmco.com (408) 756-1598 Nancy.Neilsen@lmco.com

1.8

Revised May, 2005 Lockheed Martin Space Systems

FACILITY DESIGN STANDARDS APPENDIX D Page 3

TITL E B LOC K D R A WI NG N U M B E R
CAD FILE # FOR CAD FILE NUMBER SEE SECTION2.10 DWG. NO. REV

SH 2 OF 5

1 5 6 -8 -3 0 5 E P -0 2 3 -2

3
DESIGNATES REVIS ION NUMBE R TO CAD MASTER FILE OR PROJE CT DWG. USE ALPHA FOR INT ERNAL (L MMS & DURING DESIGN). RELEASE (I.E., A, B) USE NUMERIC FOR E X TE RNAL (LMMS & ISSUED FOR BID) RELEASE (I.E., 04_, 05_) OR CONTRACT RELE AS E /IS SUE D FOR BID (REV. 0)

DES IGNATE S BUILDING NUMBER. US E LE TT ER F OR BLDGS . WITH AN ALP HA (I.E ., 1 95D) FOR CIV IL DRAWINGS , US E PL 1 FOR PL ANT1, PL2 F OR P LANT 2 AND PL 5 FOR PL ANT 5.

DESIGNATES CAD SYSTEM USED. USE "9" FOR CADAM, "8" FOR AUTOCAD AND "1" FOR VELLUM.

IF MORE THAN ONE SHEE T OF TH E S A ME TYPE OF DRAWING WAS CREAT ED , U S E A N U MBER IN THIS FIELD TO REFLECT T H E S H EE T NU MBER.

PLAN DWGS - THE FIRS T NUMBER DE SIGNAT ES F LOOR L E VEL (I.E., LE VEL 3) NOTE : A MEZZ ANINE IS CONSIDE RE D A LE VE L. A "9" WILL DE SIGNAT E THE ROOF L EV EL . THE NE XT TWO NUMBE RS DE SIGNATE THE AREA WITHIN THE BUILDING. (I.E., ARE A 05). "0 0" DES IGNAT E S E NTIRE LE V EL (I.E ., 100 = 1st F L R.) "X X " DE S IGNATE S MULT I ARE A (COMPOS IT E) DRAWINGS . "X 1" DE S IGNAT E S MORE THAN ONE SHEE T . I.E ., 156-9-3X 1EP -023 156-9-3X 2E P-02 3 FOR P ROJECT DRAWINGS ONL Y . NOT PRACT ICE D F OR AS-BUIL T RECORD DRAWINGS . NON P L AN DWGS - THE SE THREE NUMBE RS DE S IGNATE T HE SE QUE NCE OF A NON P L AN DRAWING.

DESIGNATES ASSIGNED CONTROL NUMBE R. SEE PROJECT MANAGER (PM) FOR CONTROL NUMBER. A NUMBERS ARE ASSIGNED BY BUIL DING AND CROSS REFERENCED TO THE ER NUMBE R ON T HE MASTER LOG. THIS NUMBER STAYS WIT H THE PROJECT THROUGHOUT THE LIFE OF THE DE SIGN (I.E., REQUIREMENTS THRU DESIGN). "000" DESIGNATES A FACILITY RE CORD DRAWING.

DESIGNATES DRAWING NAME FOR PRINTING AND SORTING. FIRST CHARACTER DESIGNATES DISCIPLINE. I.E., A = ARCHITECTURAL S = STRUCTURAL G = CIVIL I = INDUSTRIAL ENG. ETC.

SECOND CHARACTER DESIGNATES DRAWING T YP E .


I. E . ,

0 = BASE LINE FLOOR PLAN P = ELECTRICAL POWER PL AN C = ELECT. COMMUNICATION P LAN Q = EQUIPMENT AND FURNIT URE PL AN M = MISC (NON PLAN DRAWINGS)

A THIRD CHARACTER MAY BE USED TO DES IGNAT E DEMOLITION DRAWINGS. I.E., 156-8-305EPD-023

FIGURE 1.1 Revised May, 2005 Lockheed Martin Space Systems

FACILITY DESIGN STANDARDS APPENDIX D Page 4 2.1 As-Built CAD File Submittal Requirements A. CAD files of all approved as-built drawings shall be submitted on one of the following media: 3 floppies, CDs or ZIP disks. Each media shall be readable by a Windows based PC. Macintosh and Unix media will not be accepted. At the time of release of these standards, email submittals are not permitted. Label each media with the Building Number, Project ER Number and Project Title. (Example: B152, ER C44622, Major Modifications) For projects with multiple building sites, group files onto separate media for each building and label each media accordingly. The contents of drawings shall comply with the most recent edition of the Facility Engineering Design Standards, Section 11, Drawing Procedures. AutoCAD Blocks shall be created in Layer 0 (zero) and names shall be descriptive so that they can be easily identified and re-used. Avoid the use of symbols such as (*,<>?;:@%&$!{ } / \) in block names. Block names for the title blocks (borders) and standard symbol blocks must remain as is when obtained from LMSS TRM group. Do not explode or rename these blocks. CAD file layering convention (Names and Contents) shall adhere to Section 5.0, CAD Layering Standards. Since the AIA CAD layering system is used, to the extent of compatibility with the LMSS facilities CAD database, any additional required layer shall be selected from the AIA CAD layering guidelines and approved by TRM group prior to use on as-built drawings. External referencing and the use of paper space environment are prohibited in as-built drawings but acceptable in construction drawings. All AutoCAD files shall be saved with AutoCAD's original ACAD.MNU. Third party fonts shall not be used on submitted as-built drawing files. Avoid the use of symbol characters, such as the ones shown in section 2.2.E above, in naming of text and dimension styles. Use the underscore character if a space is needed in style names for the purpose of clarity.

B. C. D. E.

F.

G. H. I. J.

2.2

Issued For Construction CAD File Submittal Requirements A. CAD files of all Issued For Construction drawings shall be submitted on one of the following media: 3 floppies, CDs or ZIP disks. Each media shall be readable by a Windows based PC. Macintosh and Unix media will not be accepted. B. Label each media with the Building Number, Project ER Number and Project Title. (Example: B152, ER C44622, Major Modifications) C. For projects with multiple building sites, group files onto separate media for each building and label each media accordingly. D. CAD files may contain XREFs and other referenced material such as bitmaps and such, in this case all reference materials shall be submitted along with the actual issued for construction drawings. The users have the option of using AutoCADs XREF-Bind and manually copying other files onto the media or AutoCADs Pack&Go commands to satisfy this requirement. E. All submittals shall contain a project cover sheet that shows an accurate list of all drawings in the package by ID, Title and Revision number. This cover sheet will be used to insure that all drawings are accounted for. Drawing Number All drawing numbers shall be according to Figure 1.1, Title Block Drawing Number. Units Architectural units shall be used for all drawings except for the civil plans.

2.3 2.4

Revised May, 2005 Lockheed Martin Space Systems

FACILITY DESIGN STANDARDS APPENDIX D Page 5 2.5 Area Size This section does not apply to construction drawings. A floor plan shall cover the size of an area of a building that is shown on the building key plan. Exceptions to this case would be the floor plan drawings of Mechanical Controls and ACAS and roof plan drawings of all disciplines. A building with multiple areas require a key plan on all plan drawings. Use of Revision Clouds Use revision clouds on all as-built drawings. A revision cloud must be drawn around the area of work and all the associated as-built notes and objects elsewhere on the drawing. Revision Numbers As-built drawings contain a revision history. Revision number shall be 0 for all new drawings. Revision number on drawings obtained from TRM that have existing revision numbers shall be the next available number. Do not delete the previous revision numbers and project information from the revision block. Building Start Points All building floor plan CAD files have a set insertion point. This insertion point is 0,0,0 at the crossing of the grid line to the most left and the grid line at the most bottom part of the building structure.

2.6

2.7

2.8

102
START POINT OF BLDG 0,0

101 103

104

POSSIBLE OUTSIDE SHACK


An exception is made for the Architectural roof plans of certain buildings in Plant 2 (Palo Alto). These CAD files have been spatially located with special coordinates to allow creation of a composite plant 2 site plan. Buildings 201, 202 and 220 are spatially located to each other. Buildings 204, 205 and 206 are spatially located to each other. All other buildings in Palo Alto are spatially located to the 0,0,0 as described in early part of this section. 2.9 Drawing Insertion Points for Individual Areas. All floor plan CAD files of individual areas shall be spatially located to the buildings start point of 0,0,0. An overall column grid system, referred to as Building Locator, shall be used to spatially locate these individual drawings. The column numbers/grids of an individual area shall overlay the matching column numbers/grids of the building locator. Building Locator CAD files may be obtained by contacting TRM. CAD File ID Naming Convention for plan drawings A. Floor Plan Drawings: The following is the standard naming convention for an as-built floor plan drawing.

2.10

195D101AR01-000-R10.dwg
This CAD file ID represents a revision 10 of the first sheet of Architectural Reflected Ceiling plan drawing for Area 01 on the First Floor of building 195D. The 000 denotes that drawing to be an as-built drawing. Revised May, 2005 Lockheed Martin Space Systems

FACILITY DESIGN STANDARDS APPENDIX D Page 6

The first four characters, 195D Represent the building number. Use PL1 on drawings representing civil and utility site plans of Sunnyvale Plant 1 (on Architectural site plans, use the building number). Use PL5 on drawings representing civil and utility site plans of Sunnyvale and other Santa Clara County plants covering leased buildings outside of the main plant 1. Use PL2 on drawings representing civil and utility site plans of Palo Alto. The fifth character, 1 Represents the building floor/level number. Because of intermediate floors, some level numbers will not correspond to the floor numbers. Use B for basement level and 9 for roof level. All other levels in between B and 9 will use number 1 through 8. Each level will receive a number regardless of the size or usage of the level. A Mezzanine level between 1st and 2nd floor of a two story building will actually be called the 2nd level. Thus, the actual 2nd floor of the building will be referred to as the 3rd level. For building 156G Hi-Bay section, use I-J-K&L for 9th, 10th and the 11and the Catwalk levels. The sixth and the seventh characters, 01 Represent the area number (area numbers are taken from the key plan of the building. If a building is not broken up into areas, the area number shall be 00) The eighth character, A Represents the discipline group to which this drawing belongs. Refer to section 3.0 for a complete listing of discipline codes and definitions. The ninth character, R Represents the drawing type in the discipline group that this drawing was created for. Refer to section 4.0 for a complete listing of drawing type codes and descriptions. The tenth, eleventh characters, 01 Represent the sheet number. At times, it is possible for a drawing to be broken up into multiple sheets due to the amount of data shown on it. For clarity purposes it is allowable for a drawing to be represented by multiple sheets. This option shall only be considered with prior approval from the LMSS Facility Engineering and TRM group. The twelfth, thirteenth & fourteenth characters, 000 Represent the drawings CAD Control Number(CCN). Master as-built drawings in TRMs database have 000 as their CCN. As-built drawings not yet entered into TRMs Master database have a non-000 CCN in this field. CCNs are assigned by TRM. These numbers, if other than 000, are associated with the project FMR or ER numbers. The remaining characters, R10 Represent the revision number of the file. A revision history is kept in the revision block of each drawing. Refer to sections 2.6 and 2.7 for more information.

Revised May, 2005 Lockheed Martin Space Systems

FACILITY DESIGN STANDARDS APPENDIX D Page 7 2.11 Line Weights for AutoCAD Objects

Color Red Yello w Green Cya n Blue Ma g enta White

Pen # Pen 1 Pen 2 Pen 3 Pen 4 Pen 5 Pen 6 Pen 7

Inches .05 .1 .15 .2 .25 .3 .35

2.12

Text Styles AutoCAD's STANDARD text style shall be set to ROMANS for all notes. When a bolder text style is needed, use ROMANC. Text Sizes For plan drawings, regardless of the scale of the plotted drawing, the text size shall be 5 in Architectural units. For non-plan drawings, the 5 text requirement is not enforced. The user may use any text size appropriate based on the scale of the details, sections, elevations so long as the text sizes are consistent on the plotted drawings.

Revised May, 2005 Lockheed Martin Space Systems

FACILITY DESIGN STANDARDS APPENDIX D Page 8 3.0 DISCIPLINE Designation ID

LETTER DESIGNATION A B C E F G H I M P Q S T U V Z

DESCRIPTION Architectural ACAS Controls (mechanical) Electrical Fire Protection Civil Engineering Topo Plans Occupational Health & Safety Industrial Engineering / Space Allocation Reports (SAR) Mechanical Piping - Plumbing / Process Piping Equipment Engineering Structural Project Cover Sheet Underground Utilities Building Evacuation Site Master Planning

Revised May, 2005 Lockheed Martin Space Systems

FACILITY DESIGN STANDARDS APPENDIX D Page 9 4.0 DRAWING TYPE Designation ID LETTER DESIGNATION 0 (ZERO) DESCRIPTION Primary floor plan: for all disciplines. Structural: Roof Framing Plan 1 Line Diagram: Primarily used within Electrical discipline to represent the master building single line diagram drawing. This type of drawing requires a non-plan drawing number Electrical: Alarms and Emergency Notification System (ENS) Controls: Analog Elements Architectural: Site Plan ACAS: ACAS Coverage Above Ceiling Controls: Block & Logical Diagram Structural: Bottom Chord Plan ACAS: ACAS Coverage Below Ceiling Electrical: Communications/Voice & Data Controls: Communication Trunk-Local Area Network ACAS: Public Address System Demolition / Removal: for all disciplines Elevation: for all disciplines Control: Emergency Process Alarm ACAS: ACAS Circuit Numbers Below Ceiling Architectural: Exterior Elevations Evacuation: Exiting Plan Structural: Foundation ACAS: Fences Access Control Industrial Engineering: Interior Finishes Electrical: Grounding Controls: Digital Elementary ACAS: ACAS Coverage Below Floor Industrial Engineering: Partitions Structural: Intermediate Framing Architectural: Interstitial Plans Electrical: Interstitial Plans Mechanical: Interstitial Plans Industrial Engineering: Office Accessories ACAS: Manual Fire Alarm Signaling System Plan Electrical: Sound Masking ACAS: ACAS Details Electrical: Lighting ACAS: Manual Fire Alarm Signaling System Riser Diagram Architectural: Interior Elevations Revised May, 2005 Lockheed Martin Space Systems

D E

H I

FACILITY DESIGN STANDARDS APPENDIX D Page 10

Misc./Details/Diagrams/Enlarged Plans: for all disciplines ACAS: Manual Fire Alarm Signaling System Details Information Systems: IWC Jack Layout ACAS: Sound Masking System Not used Electrical: Power Piping: Instrumentation Process Piping-HVAC Chilled water piping Controls: Point to Point Wiring Schematics and Panel Layout Details ACAS: Closed Circuit Television System Industrial Engineering: Furniture and Equipment ACAS: Closed Circuit Television Details Architectural: Reflected Ceiling Controls: Ladder/Riser Diagram ACAS: Roof coverage

O P

Schedules: for all disciplines ACAS: Public Address Details Title Sheet: for all disciplines not used Electrical: Audio / Visual not used Sections, Interior/Exterior: for all disciplines not used Electrical: Secure / Classified Voice & Data

T U V W X Y Z

This area intentionally left blank.

Revised May, 2005 Lockheed Martin Space Systems

FACILITY DESIGN STANDARDS APPENDIX D Page 11

5.0

CAD Layering Standards All as-built CAD files submitted by LMSS contractors for projects of Category 1 and 2 shall comply with this section. Issued for Construction drawings are not required to comply with this section. Layer Names are chosen from the CAD Layer Guidelines established by AIA. The layer names are limited to nine characters subdivided into three sections: Major, Minor and Modifier (as shown below in section 5.2). Common Rules A. Layer 0 (zero) shall remain empty at all times. This layer is used for creating blocks and is not intended to have permanent geometry stored in it. B. All layer colors must be according to the layer guideline tables beginning with Section 5.3. C. Layer 0-TBLK contains: 1. Border lines of the drawing. 2. Title block and all its information. 3. Revision block and all its information. 4. North arrow, key plan, graphic scale. D. As-built drawings submitted by contractors shall not have XREF links. Therefore all layers are active layers of the same drawings. E. Graphic indicators for text and notes (e.g., header line and arrowheads for a note) must be located on the same layer as the corresponding text. F. Additional layer names, other than shown in the schedules below, can be used once a request has been submitted to TRM group for approval. Layer Name Structure Nine Character Layer Name Major Group Minor Group Modifier

5.1

5.2

X - XXXX - XXXX

Major Group headings define the layers discipline. Refer to section 3.0 for a listing of the disciplines and designated letters. Minor Group headings define assemblies or construction systems such as walls, doors, ceilings or electrical power. Refer to sections 5.3.1 through 5.3.21. Modifier headings further define the Minor Group headings such as DEMO, CONS, etc.

Revised May, 2005 Lockheed Martin Space Systems

FACILITY DESIGN STANDARDS APPENDIX D Page 12

5.3.1 GENERAL LAYERS These layers shall be created in all drawings as general layers of those drawings Layer Description Color Linetype 0-COL Column bubbles and numbers/letters Grey #8 Continuous 0-DIMS Dimensions Red Continuous 0-GRID Column Grid line only Grey #8 Center 0-HTCH Hatchings and Patterns Varies Continuous 0-IMAG Imported Images/Pictures 0-NOTE Notes and Call-outs directly associated to an Red Continuous object including Symbols, Targets and Titles 0-TEXT General Notes, Specifications & header text Red Continuous 0-TBLK Sheet Titles and Title Borders Green Continuous 0-VPRT Viewports created in Paper Space White Continuous 0-REVS Revision clouds and triangles for rev Cyan Continuous numbers 0-XREF Contains Xrefed drawings White Continuous Elevation, Section, Detail and Schedule Layers [* is replaced by the discipline code letter] Layer Description Color Linetype Elevations *-ELEV-FRAM Penetrations and changes in plane of the Green Continuous elevation, outline of objects beyond *-ELEV-OTLN Building outline and ground line (use thick Blue Continuous pline for ground line) *-ELEV-SURF Surface features, joints Yellow Continuous *-ELEV-HIDN Hidden lines Red Dashed Sections *-SECT-MBND Material beyond section cut Green Continuous *-SECT-MCUT Material cut by section Blue Continuous *-SECT-PATT Textures and hatch patterns Varies Details *-DETL-MBND Material beyond section cut Green Continuous *-DETL-MCUT Material cut by section Blue Continuous *-DETL-PATT Textures and hatch patterns Varies Schedules *-SCHD-BLOK Schedule blocks Red Continuous *-SCHD-TEXT Text placed inside the schedule blocks Red *-SCHD-PATT Textures and hatch patterns Red Diagrams *-DIAG-LINE Components and connecting lines Green Varies *-DIAG-TEXT Text associated with components Red *-DIAG-PATT Texture and hatch patterns Red

Revised May, 2005 Lockheed Martin Space Systems

FACILITY DESIGN STANDARDS APPENDIX D Page 13

5.3.2 ARCHITECTURAL FLOOR PLAN A0: Layer Description A-WALL-FULL Walls to ceiling or structure above A-WALL-PRHT Walls that do not go the ceiling A-WALL-IDEN Wall type symbol. Hatching & patterns within walls to graphically indicate basic wall type. A-DOOR Standard height man doors and roll-up doors A-DOOR-IDEN Door schedule symbols A-GLAZ Windows A-GLAZ-IDEN Window schedule symbols A-FLOR-STRS Stairs, ramps, escalators, ladders, handrails and guardrails A-FLOR-RAIS Raised floors A-FLOR-EVTR Elevators cars and equipment A-FLOR-TPTN Toilet Partitions A-FLOR-TRNC Floor Trenches A-FLOR-FIXT Plumbing fixtures A-FLOR-FENC Fences installed within the building A-FLOR-WDWK Built-in counters and casework A-FLOR-PATT Paving, tile, carpet, aisle way tape patterns A-FLOR-IDEN Room names and numbers A-EQPM-FIXD Fixed building equipment including wall mounted panels such as electrical, fire and alarm 5.3.3 ARCHITECTURAL ROOF PLAN A0: Layer Description A-ROOF Ridge lines, crickets, drains, etc. A-ROOF-OTLN Face of parapet, penthouse, screens A-ROOF-LEVL Level changes, back of parapet and screens A-ROOF-STRS Stairs and ladders A-ROOF-PNTR Hatches, skylights, ventilators M-HVAC HVAC equipment ductwork and piping

Color White Blue Red

Linetype continuous Continuous Continuous

Green Red Green Red Green Red Green Yellow #8 Yellow Red Yellow Red Red Red

Continuous Continuous Continuous Continuous Continuous Continuous Continuous Continuous Dashed Continuous FENC Continuous ------------Continuous Continuous

Color Red White Blue Green Cyan Yellow

Linetype Continuous Continuous Continuous Continuous Continuous Continuous

5.3.4 ARCHITECTURAL REFLECTED CEILING PLAN AR: (Use Architectural floor plan, Mechanical floor plan and Electrical Lighting plan as reference) Layer Description Color Linetype A-WALL-DHED Door headers Green Continuous A-WALL-WHED Window headers Green Continuous A-CLNG-BRAC Ceiling seismic bracing Cyan Continuous A-CLNG-GRID Ceiling grid Green Continuous A-CLNG-OPEN Ceiling penetration Green Continuous A-CLNG-SUSP Ceiling suspended elements Yellow Continuous Revised May, 2005 Lockheed Martin Space Systems

FACILITY DESIGN STANDARDS APPENDIX D Page 14

5.3.4 ACAS COVERAGE ABOVE CEILING BA: (Use Architectural floor plan as reference) Layer Description Color Linetype B-ALRM-COMP Alarm components. Duct traps, and area Green Continuous termination cabinets. B-ALRM-NOTE General notes Red Continuous B-ALRM-ZONE Zones and area designations. Green Continuous B-ALRM-WIRE Wire and conduit requirements. Yellow Continuous B-ALRM-CIRC Circuit numbers above ceiling Yellow Continuous 5.3.5 ACAS COVERAGE BELOW CEILING- BB: (Use Architectural floor plan as reference) Layer Description Color Linetype B-ALRM-COMP Alarm components. Duct traps, and area Green Continuous termination cabinets. B-ALRM-NOTE General notes Red Continuous B-ALRM-ZONE Zones and area designations. Green Continuous B-ALRM-WIRE Wire and conduit requirements. Yellow Continuous B-ALRM-CIRC Circuit numbers above ceiling Yellow Continuous 5.3.6 ACAS COVERAGE ON ROOF BR: (Use Architectural floor plan as reference) Layer Description Color Linetype B-ALRM-COMP Alarm components. Duct traps, and area Green Continuous termination cabinets. B-ALRM-NOTE General notes Red Continuous B-ALRM-ZONE Zones and area designations. Green Continuous B-ALRM-WIRE Wire and conduit requirements. Yellow Continuous B-ALRM-CIRC Circuit numbers above ceiling Yellow Continuous 5.3.7 ACAS COVERAGE BELOW FLOOR BG: (Use Architectural floor plan as reference) Layer Description Color Linetype B-ALRM-COMP Alarm components. Duct traps, and area Green Continuous termination cabinets. B-ALRM-NOTE General notes Red Continuous B-ALRM-ZONE Zones and area designations. Green Continuous B-ALRM-WIRE Wire and conduit requirements. Yellow Continuous B-ALRM-CIRC Circuit numbers above ceiling Yellow Continuous 5.3.8 ACAS DETAILS - BK: Layer Description B-ALRM-DETL Specific component details and related notes B-ALRM-LINE Component one line diagram and related notes B-ALRM-DIAG Component wiring diagram and related notes

Color Green Blue Magenta

Linetype Continuous Continuous Continuous

Revised May, 2005 Lockheed Martin Space Systems

FACILITY DESIGN STANDARDS APPENDIX D Page 15

5.3.9 MANUAL FIRE ALARM SIGNALING SYSTEM - BJ: (Use Architectural floor plan as reference) Layer Description Color Linetype B-FIRE-COMP Components Green Continuous B-FIRE-NOTE General notes Red Continuous B-FIRE-ZONE Zones and area designations. Green Continuous B-FIRE-WIRE Wire and conduit requirements. Yellow Continuous B-FIRE-CIRC Circuit numbers above ceiling Yellow Continuous 5.3.10 MANUAL FIRE ALARM SIGNALING SYSTEM RISER DIAGRAM BL: Layer Description Color Linetype B-FIRE-LINE Component one line diagram and related Green Continuous notes B-FIRE-RISR System risers and related notes Blue Continuous B-FIRE-DIAG Component wiring diagram and related notes Magenta Continuous 5.3.11 MANUAL FIRE ALARM SIGNALING SYSTEM DETAILS BM: Layer Description Color B-FIRE-DETL System specific details and related notes Green

Linetype Continuous

5.3.12 SOUND MASKING SYSTEM - BN: (Use Architectural floor plan as reference) Layer Description Color Linetype B-MASK-COMP Components Green Continuous B-MASK-NOTE General notes Red Continuous B-MASK-ZONE Zones and area designations. Green Continuous B-MASK-WIRE Wire and conduit requirements. Yellow Continuous B-MASK-CIRC Circuit numbers above ceiling Yellow Continuous 5.3.13 CLOSED CIRCUIT TELEVISION SYSTEM - BP:(Use Architectural floor plan as reference) Layer Description Color Linetype B-CCTS-COMP Components Green Continuous B-CCTS-NOTE General notes Red Continuous B-CCTS-ZONE Zones and area designations. Green Continuous B-CCTS-WIRE Wire and conduit requirements. Yellow Continuous B-CCTS-CIRC Circuit numbers above ceiling Yellow Continuous 5.3.14 CLOSED CIRCUIT TELEVISION SYSTEM DETAILS BQ: Layer Description Color B-CCTS-DETL System specific details and related notes Green

Linetype Continuous

5.3.15 PUBLIC ADDRESS SYSTEM BC: (Use Architectural floor plan as reference) Layer Description Color Linetype Revised May, 2005 Lockheed Martin Space Systems

FACILITY DESIGN STANDARDS APPENDIX D Page 16

B-PAS-COMP B-PAS-NOTE B-PAS-ZONE B-PAS-WIRE B-PAS-CIRC

Components General notes Zones and area designations. Wire and conduit requirements. Circuit numbers above ceiling

Green Red Green Yellow Yellow

Continuous Continuous Continuous Continuous Continuous

5.3.16 PUBLIC ADDRESS SYSTEM DETAILS BS: Layer Description B-PAS-DETL System specific details and related notes

Color Green

Linetype Continuous

5.3.17 FENCES ACCESS CONTROL SYSTEM BF: (Use Architectural floor plan as reference) Layer Description Color Linetype B-FENC-COMP Components Green Continuous B-FENC-NOTE General notes Red Continuous B-FENC-ZONE Zones and area designations. Green Continuous B-FENC-WIRE Wire and conduit requirements. Yellow Continuous B-FENC-CIRC Circuit numbers above ceiling Yellow Continuous 5.3.18 SITE CIVIL PLAN-G0 (these layers are also used in Architectural building site plans) Layer Description Color Linetype G-BLDG Footprint of Buildings / overhangs (dashed) White Continuous G-PKNG-STRP Parking lot striping, handicapped symbol, Yellow Continuous wheel stops G-PKNG-NOTE Parking lot notes Red Continuous G-ROAD-CNTR Roads center lines Red Center G-ROAD-CURB Face of curb, Green Continuous G-ROAD-PAVE Back of curb, line of gutter, G-ROAD-NOTE Road and street notes and names Red Continuous G-RAMP All Ramps including handicap and docking White Continuous areas G-STRM-CULV Culverts headwalls, drainage inlets Red Continuous G-STRM-IDEN Storm sewer system annotation Red Continuous G-STRM-DTCH Drainage ditches Green Dashed G-STRM-FIXT Storm drainage surface Features (catch Green Continuous basins, manholes) G-TOPO Contour Lines, Elevations and associated #8 Phantom notes G-PROP Property Lines including bearing, distance 12 Phantom and associated notes Site communication/telephone poles, boxes, G-COMM Red Continuous
towers

G-WATR G-FIRE G-NGAS G-SSWR

Domestic water-manholes, pumping stations, storage tanks and associated notes Fire protection-hydrants, connections and associated notes Natural gas-manholes, meters, storage tanks and associated notes Sanitary sewer-manholes, pumping stations and associated notes

Green Green Green Green

Continuous Continuous Continuous Continuous

Revised May, 2005 Lockheed Martin Space Systems

FACILITY DESIGN STANDARDS APPENDIX D Page 17

G-FENC G-DECK G-WALL G-WATR G-WALK G-ELEC-FIXT

Fencing Decks Walls Site water features, rivers, streams, ponds, Bay coastlines and associated notes Edge of concrete walks, steps Parking lot light poles, outside generators and similar objects

Red Green Blue Red Green White

Fenceline 2 Continuous Continuous Continuous Continuous Continuous

5.3.19 Electrical Communication plan-EC: (Use Architectural floor plan as reference) Layer Description Color Linetype E-COMM-**** Telephone and communication outlets Green Continuous E-DATA-**** Data outlets Green Continuous E-SOUN-**** Sound and PA systems Green Continuous E-CCTV-**** Closed circuit TV Green Continuous

**** = Modifiers used from the list below


Modifiers for the above Layer Description E-****-CIRC Circuit information E-****-IDEN Identification text E-****-EQPM Equipment and devices E-****-NUMB Numbers for systems Color Red Yellow Blue Yellow Linetype Continuous Continuous Continuous Continuous

5.3.20 ELECTRICAL LIGHTING PLAN EL: (Use Architectural floor plan as reference) Layer Description Color Linetype E-LITE-SPCL Special Lighting Green Continuous E-LITE-EMER Emergency Lighting Blue Continuous E-LITE-CLNG Ceiling-mounted Lighting Green Continuous E-LITE-FLOR Floor-mounted Lighting Blue Continuous E-LITE-WALL Wall-mounted Lighting Cyan Continuous E-LITE-SWCH Lighting Switches Green Continuous E-LITE-EXIT Exit Lighting Red Continuous E-LITE-NUMB Lighting Circuit Numbers Red Continuous E-LITE-WIRE Lighting wiring and conduit Red Center 5.3.21 ELECTRICAL POWER PLAN EP: (Use Architectural floor plan as reference) Layer Description Color Linetype E-POWR-WALL Power wall Receptacles Green Continuous E-POWR-CLNG Power Ceiling Receptacles and Devices Blue Continuous E-POWR-PANL Power Panels Blue Continuous E-POWR-EQPM Power Equipment-includes outlines of Green Continuous equipment shown in other disciplines E-POWR-WIRE Power wiring and conduit Red Center

Revised May, 2005 Lockheed Martin Space Systems

FACILITY DESIGN STANDARDS APPENDIX D Page 18

E-POWR-MISC

E-POWR-NUMB

Power Switchboards, Raceways, Cable Trays, Feeders and Bus-ways, transformers, equipment disconnect switches Power Circuit Numbers

Green

Continuous

Red

Continuous

5.3.22 ELECTRICAL GROUNDING PLAN EG: (Use Architectural floor plan as reference) Layer Description Color Linetype E-GRND-CIRC Ground system circuits Blue Continuous E-GRND-REFR Reference ground system Blue Continuous E-GRND-EQUI Equipment ground system Blue Continuous E-GRND-DIAG Ground system diagram Green Continuous

5.3.23 FIRE PROTECTION PLAN F0 (Use Architectural floor plan as reference) Layer Description Color Linetype F-HALN-PIPE Halon System Piping and associated notes Green Continuous F-HALN-EQPM Halon Equipment and associated notes Cyan Continuous F-HALN-SPHD Halon Spray Heads and associated notes Red Continuous F-PROT-EQPM Fire System Equipment (Fire Hose Cabinet, Green Continuous Extinguishers) and associated notes F-PROT-ALRM Fire Alarm and associated notes Green Continuous F-PROT-SMOK Smoke Detectors or Heat Sensors and Red Continuous associated notes F-SPRN-SPHD Fire Protection Sprinkler Head Green Continuous F-SPRN-PIPE Fire Protection Sprinkler Piping and Green Continuous associated notes F-STAN-PIPE Fire Protection Standpipe Piping and Cyan Continuous associated notes F-STAN-EQPM Fire Protection Standpipe Equipment and Green Continuous associated notes 5.3.24 HAZARDOUS MATERIAL MANAGEMENT PLANS H0 (Use Architectural floor plan as reference) Layer Description Color Linetype H-HMMP-SYMB Hazmat symbols Green Continuous H-HMMP-TEXT Hazmat associated text Red Continuous 5.3.25 MECHANICAL CONTROLS C0 (Use Mechanical floor plan as reference) Layer Description Color Linetype C-CONT-THER Controls-thermostats and associated notes Magenta Continuous C-CONT-WIRE Controls-low voltage wiring and associated Magenta Continuous notes
This drawing references the Architectural floor plan and the Mechanical HVAC plan drawings (layer colors shall be color number 8)

5.3.26 MECHANICAL HVAC PLAN M0 (Use Architectural floor plan as reference) Layer Description Color Linetype M-DUCT-SUPL HVAC system supply ductwork and Green Continuous associated notes Revised May, 2005 Lockheed Martin Space Systems

FACILITY DESIGN STANDARDS APPENDIX D Page 19

M-DUCT-RTRN M-DUCT-EXHS M-DUCT-OTHR M-EXHS-EQPM M-HVAC-SDFF M-HVAC-RDFF M-HVAC-EQPM

HVAC system return ductwork and associated notes HVAC system exhaust ductwork and associated notes HVAC system other ductwork and associated notes Exhaust system equipment and associated notes Supply diffusers and associated notes Return diffusers and associated notes HVAC equipment and associated notes

Red Cyan Yellow Red Blue Blue Cyan

Continuous Continuous Continuous Various Continuous Continuous Various

5.3.27 MECHANICAL PIPING PLAN MP: (Use Architectural floor plan as reference) Layer Description Color Linetype M-CWTR-EQPM Chilled water equipment and associated notes Blue Continuous M-CWTR-SUPL Cold water supply lines and associated notes Cyan Continuous M-CWTR-RTRN Cold water return lines and associated notes Cyan Continuous M-HWTR-EQPM Hot water equipment and associated notes Green Continuous M-HWTR-SUPL Hot water supply lines and associated notes Red Continuous HWTR-RTRN Hot water return lines and associated notes Red Continuous

5.3.28 PLUMBING PLAN P0: (Use Architectural floor plan as reference) Layer Description Color Linetype P-ACID-PIPE Acid, Alkaline and Oil Waste piping and Green Continuous associated notes P-DOMW-EQPM Domestic Hot and Cold Water equipment and Blue Various associated notes P-DOMW-HPIP Domestic hot water piping and associated Green Continuous notes P-DOMW-CPIP Domestic cold water piping and associated Green Continuous notes P-DOMW-RISR Domestic hot and cold water risers and Green Continuous associated notes P-SANR-PIPE Sanitary piping and associated notes Cyan Continuous P-SANR-FIXT Plumbing fixtures and associated notes Yellow Continuous P-SANR-FLDR Floor drains and associated notes Green Continuous P-SANR-RISR Sanitary risers and associated notes Red Continuous P-STRM-PIPE Storm drain piping and associated notes Red Continuous P-STRM-RFDR Roof drains and associated notes Magenta Continuous 5.3.29 PROCESS PIPING PLAN PP: (Use Architectural floor plan as reference) Layer Description Color Linetype M-BRIN-EQPM Brine system equipment and associated notes Green Continuous M-BRIN-PIPE Brine system piping and associated notes Green Continuous M-CMPA-CEQP Compressed air equipment and associated Cyan Continuous notes M-CMPA-CPIP Compressed air piping and associated notes Cyan Continuous M-CMPA-PEQP Process air equipment and associated notes Cyan Continuous Revised May, 2005 Lockheed Martin Space Systems

FACILITY DESIGN STANDARDS APPENDIX D Page 20

M-CMPA-PPIP M-FUEL-GPRP M-FUEL-GGEP M-FUEL-OPRP M-FUEL-OGEP M-MDGS-EQPM M-MDGS-PIPE M-LGAS-EQPM M-LGAS-PIPE M-NGAS-EQPM M-NGAS-PIPE M-PROC-EQPM M-PROC-PIPE M-REFG-EQPM M-REFG-PIPE M-SPEC-EQPM M-SPEC-PIPE M-STEM-CONP M-STEM-EQPM M-STEM-LPIP M-STEM-HPIP M-STEM-MPIP M-TEST-EQPM

Process air piping and associated notes Fuel gas process piping and associated notes Fuel gas general piping and associated notes Fuel oil process piping and associated notes Fuel oil general piping and associated notes Medical gas equipment and associated notes Medical gas piping and associated notes Laboratory gas equipment and associated notes Laboratory gas piping and associated notes Natural gas equipment and associated notes Natural gas piping and associated notes Process equipment and associated notes Process piping and associated notes Refrigeration equipment and associated notes Refrigeration piping and associated notes Special system equipment and associated notes Special system piping and associated notes Steam systems condensate piping and associated notes Steam systems equipment and associated notes Low pressure steam piping and associated notes High pressure steam piping and associated notes Medium pressure steam piping and associated notes Test Equipment and associated notes

Cyan Yellow Yellow Yellow Yellow Magenta Magenta Red Red Blue Blue 41 41 241 241 110 110 54 54 54 54 54 181

Continuous Continuous Continuous Continuous Continuous Continuous Continuous Continuous Continuous Continuous Continuous Continuous Continuous Continuous Continuous Continuous Continuous Continuous Continuous Continuous Continuous Continuous Continuous

5.3.30 EQUIPMENT PLAN Q0: (Use Architectural floor plan as reference) Layer Description Color Linetype Q-QTLN Equipment outline and associated notes Blue Continuous Q-POWR Power information and associated notes Cyan Continuous Q-PIPE Piping information and associated notes Cyan Continuous 5.3.31 SITE UTILITIES PLAN - U0 (uses the Site topo plan as reference) Layer Description Color U-STRM Storm drain pipes and all related notes Red U-WATR Domestic water pipes and all related notes Yellow U-FIRE Fire protection pipes and all related notes Green U-NGAS Natural gas pipes and all related notes Cyan U-SSWR Sanitary sewer pipes and all related notes Blue U-ELEC Electricity lines and all related notes White U-CWTR Chilled water lines and all related notes U-COMM Telephone communication lines and all Blue related notes Revised May, 2005 Lockheed Martin Space Systems

Linetype Dashed Continuous Continuous Continuous Continuous Fenceline 2 Continuous Continuous

FACILITY DESIGN STANDARDS APPENDIX D Page 21

U-STDR U-IRRG

Storm drain pipes and all related notes Irrigation pipes, sprinkler and all related notes

Blue 41

Continuous Continuous

5.3.32 STRUCTURAL PLAN S0,SF Layer Description S-FNDN-PILE Piles, drilled piers S-FNDN-RBAR Foundation reinforcement S-SLAB-EDGE Edge of slab S-SLAB-RBAR Slab reinforcement S-SLAB-JOIN Slab control joints S-ABLT Anchor bolts S-COLS Columns S-WALL Structural bearing or shear walls S-METL Miscellaneous metal S-BEAM Beams S-JOIS Joists S-DECK Structural floor deck

Color Blue Blue Blue Green Red Blue Green Cyan Green Green Yellow Yellow

Linetype Continuous Continuous Continuous Continuous Continuous Continuous Continuous Continuous Continuous Continuous Continuous Continuous

5.3.33 FURNITURE PLAN IQ: (Use Architectural floor plan as reference) Layer Description Color Linetype I-EQPM-MOVE Moveable equipment Blue Continuous I-EQPM-IDEN Equipment identification numbers and notes Red Continuous I-FURN-FREE Freestanding furniture (desks, credenzas, etc) Yellow Continuous I-FURN-IDEN Furniture identification numbers and notes Red Continuous I-PART-MOVE Moveable partitions (Haworth, RJ, etc.) Green Continuous I-PART-IDEN Partition size symbols Red Continuous

5.3.34 AREA Space Allocation Reports(SAR) - IS: (Use Architectural floor plan as reference) Layer Description Color Linetype Varies All layers are assigned by the SAR Vaires Varies Application. 5.3.35 EVACUATION PLAN V0: (Use Architectural floor plan as reference) Layer Description Color Linetype V-EVAC-SYMB Evacuation symbols Green Continuous V-EVAC-PATT Evacuation patterns Varies Continuous V-EVAC-TEXT Evacuation associated text Red Continuous

END