Architects and Consultants Specification Guide

For Otis Gen2 Gearless Traction Elevators

Prepared according to Construction Specifications Institute (CSI)

ELEVATORS 14210 Guide Specifications for Gen2 Gearless Traction Elevator SECTION 14210 Electric Traction Elevators PART 1 - GENERAL 1.01 SUMMARY A. B. This Section specifies electric traction elevators. Work Required: 1. The work required under this section consists of all labor, materials and services required for the complete installation (including operational verification) of all the equipment required for the elevator(s) as herein specified. 2. All work shall be performed in a first class, safe and workmanlike manner. 3. In all cases where a device or part of the equipment is herein referred to in the singular, it is intended that such reference shall apply to as many of such devices or parts as are required to make complete installation. C. Related work not specified herein: The following sections contain requirements that relate to this section and are performed by trades other than the elevator manufacturer/installer. 1. Section 01500 - Construction Facilities and Temporary Controls: protection of floor openings and personnel barriers; temporary power and lighting. 2. Section 02200 - Earthwork: excavation for elevator pit. 3. Section 03300 - Cast-In-Place Concrete: elevator pit, and elevator machine foundation. 4. Section 04200 - Unit Masonry: masonry hoistway enclosure, building-in and grouting hoistway doorframes, and grouting of sills. 5. Section 05500 - Metal Fabrications: pit ladder, divider beams, and supports for entrances, rails and hoisting beam at top of elevator machine room. 6. Section 07145 - Cementitious Waterproofing: waterproofing of elevator pit. 7. Section 15500 - Heating, Ventilating, and Air Conditioning: ventilation and temperature control of elevator equipment areas. 8. Section 16100 - Electrical: a. Main disconnects for each elevator. b. Electrical power for elevator installation and testing. c. Disconnecting device to elevator equipment prior to activation of sprinkler system. d. The installation of dedicated GFCI receptacles in the pit and overhead (with Machine room-less). e. Lighting in controller area, machine area and pit. f. Wiring for telephone service to controller. 9. Section 16610 Emergency (Standby) Power Supply Systems: emergency generator for elevator operation. 10. Section 16720 - Fire Alarm Systems: The installation of fire and smoke detectors at required locations and interconnecting devices; fire alarm signal lines to contacts in the machine room. 11. Section 16740 - Telephone Systems: ADAAG-required emergency communications equipment. D. Applicable Codes: Comply with applicable building codes and elevator codes at the project site, including but not limited to the following: 1. ANSI A117.1, Buildings and Facilities, Providing Accessibility and Usability for Physically Handicapped People. 2. ADAAG, Americans with Disabilities Act Accessibility Guidelines.

14210- 2

Gen2 Gearless Traction Elevator

ELEVATORS 14210 Guide Specifications for Gen2 Gearless Traction Elevator 3. ANSI/NFPA 70, National Electrical Code. 4. ANSI/NFPA 80, Fire Doors and Windows. 5. ASME/ANSI A17.1, Safety Code for Elevators and Escalators. 6. ANSI/UL 10B, Fire Tests of Door Assemblies. 7. CAN/CSA C22.1, Canadian Electrical Code. 8. CAN/CSA-B44, Safety Code for Elevators and Escalators. 9. EN 12016 (May 1998): EMC Product Family Standards for lifts, escalators, and passenger conveyors Part 2 immunity 10. Model & Local Building Codes. 11. All other local applicable codes. [NOTE: EDIT ITEMS SHOWN IN [BOLD] TEXT] 1.2 SYSTEM DESCRIPTION

Note: Create separate sections, each containing the following parameters, if a group contains more than one system configuration. A. B. C. D. E. F. G. Equipment Description: Gen2 gearless traction elevator with [Select One] Machine Room or Machine Room-less (not available at 450 fpm or 500 fpm) application. Equipment Control: Elevonic Control System. Quantity of Elevators: [Enter appropriate number, 8 max] Elevator Stop Designations: [Enter Appropriate elevator designations] Stops (maximum): [200 fpm] 21 or [350 fpm] [400 fpm] [450 fpm] [500 fpm]36 Openings: [Select one] In line or Front & rear openings. Travel (maximum): [200 fpm] 196 ft (60 m) or [350 fpm] [400 fpm] [450 fpm] [500 fpm] 300 ft. (92 m) H. I. J. Rated Capacity: [Select one] 2500 lb., 3000 lb., 3500 lb. 4000 lb., 4500 lb. 5000 lb. Rated Speed: [Select one] 200 fpm or 350 fpm, 400 fpm, 450 fpm, 500 fpm Platform Size: [2500] 6 9-1/2 W x 4 3-3/4 D [3000] 6 9-1/2 W x 4 9-9/16 D [3500] 6 9-2/2 W x 5 5-9/16 D [4000] 7 9-1/2 W x 5 5-9/16 D [4000H] 5 9-1/2 W x 7 5-5/8 D [4500H] 5 9-1/2 W x 7 11-9/16 D [5000H AIA] 5 9-1/2 W x 9 0-9/16 D [5000H] 6 0-1/2 W x 8 6-9/16 D Clear Inside Dimensions: [2500 lb.] 6 8-5/16 W x 4 3-5/32 D [3000] 6 8-5/16 W x 4 9 D [3500] 6 8-5/16 W x 5 5 D [4000] 7 8-5/16 W x 5 5 D [4000H] 5 8-5/16 W x 7 5-1/16 D [4500H] 5 8-5/16 W x 7 11 D [5000H AIA] 5 8-5/16 W x 9 0 D [5000H] 5 11-5/16 W x 8 6 D Cab Height: [Select one] 8 0 or 9 7

K.

L.

14210- 3

Gen2 Gearless Traction Elevator

ELEVATORS 14210 Guide Specifications for Gen2 Gearless Traction Elevator M. N. Clear height under suspended ceiling: [8 0] 7 4-3/4 (2246 mm) [9 7] 8 11-3/4 (2813mm) Entrance Type and Width: [2500] Single-Slide Door 3 6 (1067 mm) [2500] Center-Open Doors 3 6 (1067 mm) [3000] Single-Slide Doors 3 6 (1067 mm) [3000] Center-Open Doors 3 6 (1067 mm) [3500] Single-Slide Doors 3 6 (1067 mm) [3500] Center-Open Doors 3 6 (1067 mm) [4000] Center-Open Doors 4 0 (1219 mm) [4000H] Two-Speed Doors 4 0 (1219 mm) [4500H] Two-Speed Doors 4 0 (1219 mm) [5000H] Two-Speed Doors 4 6 (1372 mm) [5000H AIA] Two-Speed Doors 4 0 (1219 mm) O. P. Q. R. S. T. Entrance Height: [Select one] 7 0 (2134 mm) or 8 0 (2438mm) Main Power Supply: [Select one] 208, 240, 440, 480 or 600 Volts + or - 5% of normal, threePhase, with a separate equipment grounding conductor. Car Lighting Power Supply: 120 Volts, Single-phase, 15 Amp, 60 Hz. Machine Location: [Machine Room-Less] Inside the hoistway at the top or [Machine Room] Inside machine room above hoistway. Signal Fixtures: Manufacturers standard. Controller Location: [Machine Room-Less] Controller(s) shall be located adjacent to the hoistway at the top landing in a [select one <controller space.> or <control room.> or < remote controller space.> or < remote control room.>] [OR] [Machine Room] Controller(s) shall be located above the hoistway in a machine room. Performance: 1. Car Speed: + 3 % of contract speed under any loading condition or direction of travel. 2. Car Capacity: Safely lower, stop and hold up to 125% of rated load. (code required). V. Ride Quality: 1. 2. 3. 4. 5. 6. 7. W. Vertical Vibration (maximum): 12 17 milli-g Horizontal Vibration (maximum): 10 15 milli-g Vertical Jerk (maximum): 4.6 1.0 ft./ sec3 (1.4 0.3 m/ sec3) Acceleration/Deceleration (maximum): 2.6 .33 ft./ sec2 (0.8 0.13 m/ sec2) In Car Noise: 50 55 dB(A) Stopping Accuracy: 0.2 in. ( 5 mm) Re-leveling Distance: 0.4 in. ( 10 mm)

U.

Operation: [Simplex] Simplex Collective Operation: Using a microprocessor-based controller, operation shall be automatic by means of the car and hall buttons. If all calls in the system have been answered, the car shall park at the last landing served. [OR] [Duplex] Duplex Collective Operation: Using a microprocessor-based controller, the operation shall be automatic by means of the car and hall buttons. In the absence of system activity, one car can be made to park at the pre-selected main landing. The other (free) car shall remain at the

14210- 4

Gen2 Gearless Traction Elevator

ELEVATORS 14210 Guide Specifications for Gen2 Gearless Traction Elevator last landing served. Only one car shall respond to a hall call. If either car is removed from service, the other car shall immediately answer all hall calls, as well as its own car calls. [OR] [Multi-car] Multi-Car (3 to 4 cars) Operation: Using a microprocessor-based controller, the operation shall be automatic by means of the car and hall buttons. In the absence of system activity, one car can be made to park at the pre-selected main landing. The other (free) cars shall park in multiple zones, changing their location with traffic demands. X. Operating Features Standard 1. Full Collective Operation 2. Anti-nuisance. 3. Fan and Light Protection. 4. Load Weighing Bypass. 5. Independent Service. 6. Full Collective Operation. 7. Firefighters' Service Phase I and Phase II (USA only); or Special Emergency Service Phase I and II Emergency Recall and In-Car Emergency Operation (Canada only). 8. Top of Car Inspection. [Include the following operations for duplex or multi-car Operation, delete for Simplex.] 9. Zoned Car Parking. 10. Relative System Response Dispatching. 11. MRO Manual Rescue Operation Y. Operation Features Optional [Include the following options as required. Renumber accordingly.] 1. Car to Lobby Operation. 2. Zoned Access at Bottom Landing. 3. Zoned Access at Upper Landing. 4. Car Secure Access. 5. Provision for Card Reader in Car (Card Reader provided and Installed by others). 6. Express Priority Service with key-switch(es) at [enter landing designation(s)] 7. Second Riser of Hall Buttons. 8. Emergency Hospital Service. 9. Automatic Standby Power Operation with Manual Override. This operation shall return each car automatically to a designated landing when the system is initially switched to standby power. One or more cars are returned at a time. Preference is given to loaded cars over empty cars in order to reduce passenger wait times. A car must respond by beginning to move toward the designated landing within a pre-determined time. If a car does not respond, it is automatically placed in a "Not Available" mode while other cars are moved. If a car was not returned to the designated landing on the first try, a second attempt is made. If the second attempt is not successful, the car will remain in a "Not Available" mode and can only be moved by manual means. Once each car has returned to the designated landing, the doors will remain open for a predetermined amount of time. When all cars have successfully returned to the designated landing or have attempted to move twice, automatic selection of the car(s) to run on normal operation will occur. If for any reason a car selected for normal operation under standby power is delayed for 60 seconds, the car will be placed in a "Not Available" mode and another car will be selected for normal operation based on the priorities listed above.

14210- 5

Gen2 Gearless Traction Elevator

ELEVATORS 14210 Guide Specifications for Gen2 Gearless Traction Elevator

Manual Override of Standby Power Operation is achieved by a manual input for each car via a strip switch. A manually selected car may be run either in a return operation to a designated landing or in normal operation under standby power. If a manually selected car has not yet returned to the designated landing, it will perform this operation first then immediately go into normal operation. If a manually selected car is delayed, no other car can be selected in the group unless it is manually selected. If car selection is changed by Manual Override while a car is running in return or normal operation under standby power, the newly selected car will not be permitted to run until the car that had been running has stopped, opened its doors, and gone into the Standby Power Wait state. Z. Door Control Features: 1. Door control to open doors automatically when car arrives at a landing in response to a normal hall or car call. 2. Elevator doors shall be provided with a reopening device that will stop and reopen the car door(s) and hoistway door(s) automatically should the door(s) become obstructed by an object or person. Primary door protection shall consist of a two dimensional, multi-beam array projecting across the car door opening. Under normal operation and for any door position, the system shall detect as a blockage an opaque object that is equal to or greater than 1.3 inches (33 mm) in diameter when inserted between the car doors at vertical positions from within 1 inch (25 mm) above the sill to 71 inches (1800 mm) above the sill. Under degraded conditions (one or more blocked or failed beams), the primary protection shall detect opaque objects that are equal to or greater than 4 (100 mm) in diameter for the same vertical coverage. If the system performance is degraded to the point that the 4 object cannot be detected, the system shall maintain the doors open or permit closing only under nudging force conditions. The door reopening device shall also include a secondary, three dimensional, triangular infrared multi-beam array projecting across the door opening and extending into the hoistway door zone. The door opening device will cause the doors to reopen when it detects a person(s) or object(s) entering or exiting the car in the area between the hoistway doors or the entryway area adjacent to the hoistway doors. The size of the secondary protection zone shall vary as the door positions vary during opening and closing. The width of the zone shall be approximately one-third the size of the separation between the doors (or door and strike plate for single-slide doors) and shall be approximately centered in the door separation. In order to minimize detection of hallway passers-by who are not entering the elevator, the maximum zone penetration into the entryway shall not exceed 20 for any door separation. Normal penetration depth into the entryway from the car doors shall be ~14 for a door separation of 42. The penetration shall reduce proportionally as the doors close. At door separations of 18 or less the secondary protection system may cease its normal operation since the depth of the zone recedes to where it is inside the hoistway doors. The vertical coverage of the secondary protection shall be ~19 (480 mm) above the sill to ~55 (1400 mm) above the sill (mid-thigh to shoulder of a typical adult). The secondary protection shall have an anti-nuisance feature that will ignore detection in the secondary zone after continual detection occurs for a significant time period in the secondary zone without corresponding detection in the primary protection zone; i.e. a person/object is in

14210- 6

Gen2 Gearless Traction Elevator

ELEVATORS 14210 Guide Specifications for Gen2 Gearless Traction Elevator the entryway but does not enter. Normal secondary protection shall be re-enabled whenever detection occurs in the primary zone. The reaction time of the door detector sub-system shall not exceed 60 milliseconds when both primary and secondary protection capabilities are active; nor 40 milliseconds when the secondary protection is disabled. 3. Door nudging operation to occur if doors are prevented from closing for an adjustable period of time. AA. 1.03 Provide equipment according to seismic zone: [Enter appropriate zone for project: 0, 1, 2, 3, 4, California Title 24]

SUBMITTALS A. Product Data: Submit manufacturers product data for each system proposed for use. Include the following: 1. Signal and operating fixtures, operating panels and indicators. 2. Cab design, dimensions and layout. 3. Hoistway-door and frame details. 4. Electrical characteristics and connection requirements. 5. Expected heat dissipation of elevator equipment in control room space and machine space (BTU). 6. Color selection chart for Cab and Entrances. B. Shop Drawings: Submit approval layout drawings. Include the following: 1. 2. 3. 4. 5. 6. C. Car, guide rails, buffers and other components in hoistway. Maximum rail bracket spacing. Maximum loads imposed on guide rails requiring load transfer to building structure. Clearances and travel of car. Clear inside hoistway and pit dimensions. Location and sizes of access doors, hoistway entrances and frames.

Operations and Maintenance Manuals: Provide manufacturer's standard operations and maintenance manual.

1.04

QUALITY ASSURANCE A. B. C. Manufacturer: Elevator manufacturer shall be ISO 9001 certified. Installer: Elevators shall be installed by the manufacturer. Permits, Inspections and Certificates: The Elevator Contractor shall obtain and pay for necessary Municipal or State Inspection and permit as required by the elevator inspection authority, and make such tests as are called for by the regulations or such authorities. These tests shall be made in the presence of such authorities or their authorized representatives.

1.05

DELIVERY, STORAGE AND HANDLING A. Should the building or the site not be prepared to receive the elevator equipment at the agreed upon date, the General Contractor will be responsible to provide a proper and suitable storage area on or off the premises.

14210- 7

Gen2 Gearless Traction Elevator

ELEVATORS 14210 Guide Specifications for Gen2 Gearless Traction Elevator Should the storage area be off-site and the equipment not yet delivered, then the elevator contractor, upon notification from the General Contractor, will divert the elevator equipment to the storage area. If the equipment has already been delivered to the site, then the General Contractor shall transport the elevator equipment to the storage area. The cost of elevator equipment taken to storage by either party, storage, and redeliver to the job site shall not be at the expense of the elevator contractor. 1.06 WARRANTY A. The elevator contractors acceptance is conditional on the understanding that their warranty covers defective material and workmanship. The guarantee period shall not extend longer than one (1) year from the date of completion or acceptance thereof by beneficial use, whichever is earlier, of each elevator. The guarantee excludes: ordinary wear and tear or improper use, vandalism, abuse, misuse, or neglect or any other causes beyond the control of the elevator contractor and this express warranty is in lieu of all other warranties, express or implied, including any warranty of merchantability or fitness for a particular purpose.

1.07

MAINTENANCE and SERVICE A. Maintenance service consisting of regular examinations and adjustments of the elevator equipment shall be provided by the elevator contractor for a period of [Select the appropriate new installation maintenance period: <three (3)> <six (6)> <nine (9)> <twelve (12)>] months after the elevator has been turned over for the customers use. This service shall not be subcontracted but shall be performed by the elevator contractor. All work shall be performed by competent employees during regular working hours of regular working days and shall include emergency 24hour callback service. This service shall not cover adjustments, repairs or replacement of parts due to negligence, misuse, abuse or accidents caused by persons other than the elevator contractor. Only genuine parts and supplies as used in the manufacture and installation of the original equipment shall be provided. B. The periodic lubrication of elevator components shall not be required, including: Sheaves, Rails, Belts, Ropes, Car and CWT guides, etc. C. The elevator control system must: 1) Provide in the controller the necessary devices to run the elevator in inspection operation. 2) Provide on top of the car the necessary devices to run the elevator in inspection operation. 3) Provide in the controller an emergency stop switch. This emergency stop switch when opened disconnects power from the brake and prevents the motor from running. 4) Provide in the event of a power outage, means from the controller to electrically lift and control the elevator brake to safely bring the elevator to the nearest available landing. 5) Provide the means from the controller to reset the governor over speed switch and also trip the governor. 6) Provide the means from the controller to reset the emergency brake when set because of an unintended car movement or ascending car over speed. 7) [Optional] Provide the means from the controller to reset elevator earthquake operation.

PART 2 - PRODUCTS 2.01 DESIGN AND SPECIFICATIONS A. Provide [Select One] <machine room-less> or <machine room> Gen2 traction passenger elevators from Otis Elevator Company. The control system and car design based on materials and systems manufactured by Otis Elevator Company. Specifically, the system shall consist of the following components:

14210- 8

Gen2 Gearless Traction Elevator

ELEVATORS 14210 Guide Specifications for Gen2 Gearless Traction Elevator

1. An AC gearless machine using embedded permanent magnets mounted [Machine RoomLess] at the top of the hoistway or [Machine Room] in machine room above the hoistway. 2. Polyurethane Coated Steel Belts (CSBs) for elevator hoisting purposes. B. 2.02 Approved Installer: Otis Elevator

EQUIPMENT: CONTROL ROOM COMPONENTS

A. Controller: A microcomputer based control system shall be provided to perform all of the functions of safe elevator operation. The system shall also perform car and group operational control. 1. All high voltage (110V or above) contact points inside the controller cabinet shall be protected from accidental contact in a situation where the controller doors are open. 2. Controller shall be separated into two distinct halves; Motor Drive side and Control side. High voltage motor power conductors shall be routed so as to be physically segregated from the rest of the controller. 3. Field conductor terminations points shall be segregated; high voltage (>30 volts DC and 110 VAC,) and low voltage (< 30 volts DC) 4. Controllers shall be designed and tested for Electromagnetic Interference (EMI) immunity according to the EN 12016 (May 1998): EMC Product Family Standards for lifts, escalators, and passenger conveyors Part 2 immunity B. Drive: A Variable Voltage Variable Frequency AC regenerative drive system shall be provided. The drive shall be set up for regeneration of AC power back to the building grid. C. [Optional] Control space barrier: Provide control space barrier consisting of a bi-folding barrier system that can be opened out of the room to provide protection during service. 2.03 EQUIPMENT: MACHINE AND GOVERNOR

A. Machine: [Machine Room-Less] <AC gearless machine, with a synchronous permanent-magnet motor, dual solenoid service and emergency disc brakes, mounted at the top of the hoistway.> [OR] [Machine Room] <AC gearless machine, with a synchronous permanent-magnet motor, dual solenoid service and emergency disc brakes, mounted in the machine room above the hoistway.> B. Governor: [Machine Room-Less] <The governor shall be a tension type governor.> [OR] [Machine Room]< ? > Buffers, Car and Counterweight:[Select one] [200 fpm] Compression spring type buffers shall be used. [350 fpm] Oil type buffers shall be used. [400 fpm] Oil type buffers shall be used. [450 fpm] Oil type buffers shall be used. [500 fpm] Oil type buffers shall be used. E. Hoistway Operating Devices: 1. Emergency stop switch in the pit 2. Terminal stopping switches.

D.

14210- 9

Gen2 Gearless Traction Elevator

ELEVATORS 14210 Guide Specifications for Gen2 Gearless Traction Elevator F. Positioning System: Consists of an encoder, reader box, and door zone vanes.

G. Guide Rails and Attachments: Guide rails shall be Tee-section steel rails with brackets and fasteners. Side counterweight arrangements shall have a dual-purpose bracket that combines both counterweight guide rails, and one of the car guide rails to building fastening. H. Coated Steel Belts: Polyurethane coated belts with high-tensile-grade, zinc-plated steel cords.

I. Governor Rope: Governor rope shall be steel and shall consist of at least eight strands wound about a sisal core center. J. K. Fascia: Galvanized sheet steel shall be provided at the front of the hoistway. Hoistway Entrances: 1. Frames: Entrance frames shall be of bolted construction for complete one-piece unit assembly. All frames shall be securely fastened to fixing angles mounted in the hoistway and shall be of UL fire rated steel. 2. 3. 4. 5. Sills shall be extruded [Select: <aluminum> or <bronze> or <nickel silver>.] Doors: Entrance doors shall be of metal construction with vertical channel reinforcements. Fire Rating: Entrance and doors shall have a UL 1-1/2 hour fire protection rating. Entrance Finish: [This paragraph may be written as needed to indicate specific entrance finishes by the opening. Clearly indicate landing/opening designations for each finish. For example: Lobby - satin finish stainless steel, floors 2 through 8 with white baked enamel. Frame & Door finish can be independent.] [Select finish: satin stainless steel> or <satin bronze> or <mirror stainless steel> or <mirror bronze> or < white prime> or <powder coated finish.> Color to be selected from the manufacturer's standard color chart.] Entrance marking plates: Entrance jambs shall be marked with 4 x 4 (102 mm x 102 mm) plates having raised floor markings with Braille located [select one] [< adjacent to >] or [California only < underneath >] the floor marking. Marking plates shall be provided on both sides of the entrance. Sight Guards: Black sight guards will be furnished.

6.

7. L. 2.04

[Optional] Counterweight Safeties: Counterweight safeties shall be applied to the counterweight frame, and shall be either a type D or E, flexible guide clamp type.

EQUIPMENT: CAR COMPONENTS A. Carframe and Safety: A carframe fabricated from formed or structural steel members shall be provided with adequate bracing to support the platform and car enclosures. The car safety shall be integral to the carframe and shall be Type "B", flexible guide clamp type. B. Steel Cab [Select one] [Series 4 cab] with [Select finish: <brushed stainless steel> or <rigid stainless steel> metal finish or <painted finish from standard manufacturers catalog of choices>].

14210- 10

Gen2 Gearless Traction Elevator

ELEVATORS 14210 Guide Specifications for Gen2 Gearless Traction Elevator [OR] [Series 5 cab] with attached vertical non-removable panels, plastic laminate selected from standard manufacturers catalog of choices. Aluminum trim and base plate with a [Select finish] <mirror stainless > or <mirror gold> finish. C. Car Front Finish: [Select finish: <satin stainless steel> or <satin bronze> or <mirror stainless steel> or <mirror bronze>] D. Car Door Finish: Select finish: <satin stainless steel> or <satin bronze> or <mirror stainless steel> or <mirror bronze>. E. Car Top: shall be of (12.7 mm) thick structural wood material clad on both sides with a 1/32 (0.79 mm) natural finish aluminum panel. F. Ceiling Type: [Select one] Lexan [DC22L Ceiling] suspended ceiling shall consist of white translucent polycarbonate diffusers set in frame of extruded [Select: <aluminum> or <aluminum w/gold-tone-paint>] with fluorescent lighting fixtures. [OR] Aluminum Egg crate [DC22E Ceiling] suspended ceiling shall consist of aluminum egg crate diffusers set in frame of extruded [Select: <aluminum> or <aluminum w/gold-tone-paint>] with fluorescent lighting fixtures. [OR] Downlight [DC23 Ceiling] suspended ceiling will have panels laminated with [Select: <natural mirror finish> or <natural satin finish> or <bronze satin finish> or <bronze mirror finish> or <plastic laminate (Color to be selected from the manufacturer's standard color chart).>] Set with incandescent down lights, one per panel (120 volts). [OR] Ceiling by Others [DC29] Unfinished car top with exposed hardware. No suspended ceiling with fluorescent lighting mounted to the canopy. Canopy to be natural aluminum. Others supply code compliant suspended ceiling locally. G. Emergency Car Lighting: An emergency power unit employing a 6-volt sealed rechargeable battery and totally static circuits shall be provided to illuminate the elevator car and provide current to the alarm bell in the event of building power failure. H. Emergency Pulsating Siren: Siren mounted on top of the car that is activated when the Alarm button in the car operating panel is engaged. Siren shall have a rated sound pressure level of 80 dB(A) at a distance of 3.0 m from the device. Siren shall respond with a delay of not more than 1 second after the switch or push button has been pressed. I. Fan: [Select one] [2000 - 3000 Duty] A two-speed 120 VAC fan will be mounted to the structural ceiling to facilitate in-car air circulation, meeting A17.1 code requirements. This two-speed fan produces airflow rates of 5.8 and 7.4 m3/min on low and high setting respectively. The fan shall be rubber mounted to prevent the transmission of structural vibration and will include a baffle to diffuse audible noise. A switch shall be provided in the car-operating panel to control the fan.

14210- 11

Gen2 Gearless Traction Elevator

ELEVATORS 14210 Guide Specifications for Gen2 Gearless Traction Elevator

[OR] [3500 - 5000 Duty] A two-speed 120 VAC fan will be mounted to the structural ceiling to facilitate in-car air circulation, meeting A17.1 code requirements. This two-speed fan produces airflow rates of 7.2 and 9.2 m3/min on low and high setting respectively. The fan shall be rubber mounted to prevent the transmission of structural vibration and will include a baffle to diffuse audible noise. A switch shall be provided in the car-operating panel to control the fan. J. Handrail: [Select one] [DH-50] Handrails shall be provided on the [Select one <side walls> or <rear wall> or <side and rear walls>] of the car enclosure. Handrails shall be 1/2 x 1-1/2 (13mm x 38mm) flat tubular handrail with a Select finish: <satin stainless steel> or <mirror stainless steel> or <satin bronze> or <mirror bronze> finish. [OR] Round Tubular Metal [DH154 Handrails] 1-1/2 (38 mm) or 2(51 mm) [Select: <satin> or <mirror>] finish [Select <stainless steel> or <bronze>] provided on the [Select location(s)<rear> or <sides> or <sides and rear>] of the car enclosure. [OR] Flat Solid Metal [DH51 Handrails] 1/4 (6 mm) x 8 (203 mm) [Select: <satin> or <mirror>] finish [Select <stainless steel> or <bronze>] provided on the [Select location(s)<rear> or <sides> or <sides and rear>] of the car enclosure. K. Threshold: [Select: < aluminum> or <bronze> or <nickel silver>.] L. Emergency Exit Contact: An electrical contact shall be provided on the car-top exit. M. Roller Guides: Rubber roller guides shall be mounted on the top and the bottom of the car and counterweight. Car roller guides shall be 3 (76mm) [Optional] <6-1/4 (160mm)> at the top of the car, and 6-1/4 (160mm) at the bottom. The counterweight roller guides shall be 3 (76mm) at the top and the bottom. [OR] [400fpm] [450fpm] [500fpm] Rubber roller guides shall be mounted on the top and the bottom of the car and counterweight. <Car roller guides shall be 6-1/4 (160mm) at the top of the car, and 61/4 (160mm) at the bottom.> [Optional] <Car roller guides shall be 7-7/8 (200mm) at the top of the car, and 7-7/8 (200mm) at the bottom.> The counterweight roller guides shall be 3 (76mm) at the top and the bottom. N. Platform: The car platform shall be constructed of 2 layers of plywood and 2 layers of .032 (.81mm) thick aluminum laminate for a total thickness of 1-1/2 (38mm). Load weighing device shall be mounted under the platform. O. [Optional] Certificate frame: Provide a Certificate frame with a [Select finish: <satin stainless steel> or <satin bronze> or <mirror stainless steel> or <mirror bronze>.] finish. P. [Optional] Glass rear cab wall - [Select thickness: <1/4> or <9/16>] laminated safety glass per ANSI code. If exposed to direct sun light then a variable speed fan will be necessary. Aluminum tube frame painted black. Two piece design with handrail space between the top and bottom pieces of glass. No shrouding at the top or bottom of car.

14210- 12

Gen2 Gearless Traction Elevator

ELEVATORS 14210 Guide Specifications for Gen2 Gearless Traction Elevator

2.05 A.

EQUIPMENT: SIGNAL DEVICES AND FIXTURES Car Operating Panel: A car operating panel shall be provided which contains all push buttons, key switches, and message indicators for elevator operation. The car operating panel shall have a [Select finish: <satin stainless steel> or <satin bronze> or <mirror stainless steel> or <mirror bronze>.] finish. [Select One] 1. [Select for Series 2 Fixtures] Applied car operating panel shall be furnished. It shall contain a bank of round metal (plastic when required by some local California codes) mechanical illuminated buttons. Flush mounted to the panel and marked to correspond to the landings served, an emergency call button, door open and door close buttons, and switches for lights, inspection and the exhaust fan. The emergency call button shall be connected to a bell that serves as an emergency signal. All buttons to have raised numerals and Braille markings. Red LED halo illumination with [Select: <Flat Flush> or <1/8 projecting> targets.] Target finishes: [Select finish: <satin stainless steel> or <satin bronze> or <mirror stainless steel> or <mirror bronze.>] 1. [Select for Series 2 Vandal- Resistant Fixtures] Applied car operating panel shall be furnished. It shall contain a bank of round metal (plastic when required by some local California codes) mechanical illuminated buttons. Flush mounted to the panel and marked to correspond to the landings served, an emergency call button, door open and door close buttons, and switches for lights, inspection and the exhaust fan. The emergency call button shall be connected to a bell that serves as an emergency signal. All buttons to have raised numerals and Braille markings. Red LED in center of button for illumination with [Select: <Flat Flush> or <1/8 projecting> targets.] Target finishes: [Select finish: <satin stainless steel> or <satin bronze> or <mirror stainless steel> or <mirror bronze.>] [OR] 1. [Select for Series 4 Fixtures] Hinged swing car operating panel shall be furnished. It shall contain a bank of round metal (plastic when required by some local California codes) mechanical illuminated buttons. Flush mounted to the panel and marked to correspond to the landings served, an emergency call button, door open and door close buttons, and switches for lights, inspection and the exhaust fan. The emergency call button shall be connected to a bell that serves as an emergency signal. All buttons to have raised numerals and Braille markings. LED [Select: <green> or <red>] halo illumination with [Select: <Flat Flush> or <1/8 projecting> targets.] Target finishes : [Select finish: <satin stainless steel> or <satin bronze> or <mirror stainless steel> or <mirror bronze.>

[OR] 1. [Select for Series 4 Vandal- Resistant Fixtures] Hinged swing car operating panel shall be furnished. It shall contain a bank of round metal (plastic when required by some local California codes) mechanical illuminated buttons. Flush mounted to the panel and marked to correspond to the landings served, an emergency call button, door open and door close buttons, and switches for lights, inspection and the exhaust fan. The emergency call button shall be connected to a bell that serves as an emergency signal. All buttons to have raised numerals and Braille markings. LED red halo illumination with [Select: <Flat Flush> or <1/8 projecting> targets.] Target finish is satin stainless steel.

14210- 13

Gen2 Gearless Traction Elevator

ELEVATORS 14210 Guide Specifications for Gen2 Gearless Traction Elevator

The car operating panel shall be equipped with the following features: Standard: 1) Raised markings and Braille shall be provided to the left hand side of each push-button. 2) Car Position Indicator at the top of and integral to the car operating panel. 3) Door open and door close buttons. 4) Light key-switch. 5) Fan key-switch. 6) Inspection key-switch. 7) Elevator Data Plate marked with elevator capacity and car number. 8) Illuminated alarm button with raised markings. Standard for USA, Optional in Canada 10) In car stop switch (toggle or key unless local code prohibits use) 11) Firefighters hat (standard USA) 12) Firefighters Phase II Key-switch (standard USA) 13) Call Cancel Button (standard USA) Optional 1) Help Button The help button shall initiate two-way communication between the car and a location inside the building, switching over to another location if the call is unanswered, where personnel are available who can take the appropriate action. Visual indicators are provided for call initiation and call acknowledgement. 2) Firefighters Phase II emergency in-car operating instructions, worded according to A17.1 2000, Article 2.27.7.2. 3) Landing Passing Signal: A chime bell shall sound in the car to signal that the car is either stopping at or passing a floor served by the elevator. 4) Please exit symbol, provided with emergency hospital service, Seismic Zones 2 or express priority in the hall. B. [Select for Series 4 ]Car Position Indicator: A 16-segment, digital, vacuum fluorescent car position indicator shall be integral to the car operating panel. Hall Fixtures: Hall fixtures shall be provided with necessary push buttons and key switches for elevator operation. Hall fixtures shall have a [This paragraph may be written as needed to indicate specific fixture finishes by opening. Clearly indicate landing/opening designations for each finish [Select One] 1. [Select for Series 5 Fixtures] Hall fixtures shall feature round mechanical buttons marked to correspond to the landings, in raised fixture housings. Buttons shall be [Select one] <flat flush> or <1/8 projecting> in vertically mounted fixture. Hall Lanterns and Position indicators shall be illuminated by means of LED. Fixture shall be [Select finish: <satin stainless steel> or <satin bronze> or <mirror stainless steel> or <mirror bronze>] finish. [OR] 1. [Select for Series 2 Fixtures] Hall fixtures shall feature round mechanical buttons in flush mount face frame. Buttons shall be [Select one] <flat flush> or <1/8 projecting> in vertically mounted fixture. Hall lanterns and position indicators shall be illuminated by means of LED. Fixture shall be [Select finish: <satin stainless steel> or <satin bronze> or <mirror stainless steel> or <mirror bronze>] finish.

C.

14210- 14

Gen2 Gearless Traction Elevator

ELEVATORS 14210 Guide Specifications for Gen2 Gearless Traction Elevator

[OR] 1. [Select for Series 2 Vandal Resistant Fixtures] Hall fixtures shall feature round mechanical buttons in flush mount face frame with vandal resistant buttons. Buttons shall be [Select one] <flat flush> or <1/8 projecting> in vertically mounted fixture. Hall lanterns and position indicators shall be illuminated by means of LED. Fixture shall be satin stainless steel finish. [Select one or both] Car Lantern and Chime: A directional lantern visible from the corridor shall be provided in the car entrance. When the car stops and the doors are opening, the lantern shall indicate the direction in which the car is to travel and a chime will sound. Or/And Hall Lanterns and Chime: A directional lantern visible from the corridor shall be provided at each hall entrance. When the car stops and the doors are opening, the lantern shall indicate the direction in which the car is to travel and a chime will sound. [Include the following options as required. Re-letter accordingly] E. [Optional] Hall Position Indicator centered above the entrance at [enter landing designation(s), maximum two landings.] [Optional] Telephone Cabinet: A telephone compartment shall be furnished in the return panel below the car operating panel. Necessary wires for the telephone shall be included in the compartment and connected to the car traveling cable. The telephone instrument shall be furnished by others. [Optional] Combination Hall Position Indicator and Hall Lantern at [enter landing designation(s), maximum two.] [Optional] Hall call cutout key-switches to disable activation of hall buttons [enter landing designation(s)]. [Optional] Key-switch Operation in lieu of hall buttons [enter landing designation(s).] [Optional] Access key-switch at top floor in entrance jamb. [Optional] Access key-switch at lowest floor in entrance jamb. [Optional] Coaxial cable (RG6) in traveling cable. [Optional] Card reader provisions, 4 twisted shielded pairs in traveling cable. [Optional, Duplex only] Emergency (standby) Power key-switch: Manual selection of each elevator in normal operation after automatic return in standby power operation has been initiated. [Optional, available with 3 to 4 car groups] Emergency (standby) Power Cabinet: Manual selection of each elevator in normal operation after automatic return in standby power operation has been initiated. This is achieved via a strip switch inside the standby-power cabinet.

D.

F.

G.

H.

I. J. K. L. M. N.

O.

PART 3 - EXECUTION 3.01 PREPARATION

14210- 15

Gen2 Gearless Traction Elevator

ELEVATORS 14210 Guide Specifications for Gen2 Gearless Traction Elevator

A.

Take field dimensions and examine conditions of substrates, supports, and other conditions under which this work is to be performed. Do not proceed with work until unsatisfactory conditions are corrected.

3.02

INSTALLATION A. Installation of all elevator components except as specifically provided for elsewhere by others.

3.03

DEMONSTRATION A. The elevator contractor shall make a final check of each elevator operation with the Owner or Owners representative present prior to turning each elevator over for use. The elevator contractor shall determine that control systems and operating devices are functioning properly.

Notice to the user: Permission is granted to use this material for only the purpose for which Otis supplies it. Copyright 2003 by Otis Elevator Co. All rights reserved. REV 11/04/09