Electric Utility Grade

PACSclad Metalclad.

Distribution Switchgear
4160 Volts to 27 kV
Drawout Switchgear To 6,000 Amperes

60 kV BIL 95 kV BIL 110 kV BIL 125 kV BIL


For: Electric Utilities Wind Generation Industrials Distribution Marine ...etc.

Including

PACSafe

Arc Resistant Switchgear

Standard & Custom

Since 1972

The Experienced Company

61 Steamboat Road, Great Neck, New York 11024 U.S.A. Tel: 516-829-9060 Fax: 516-829-9557 E-mail: sales@pacsindustries.com

Web: pacsindustries.com

IEC

50 Hertz or 60 Hertz
ISO 9001-2000

ANSI

Facilities in Great Neck, New York and Mount Vernon, Ohio

About PACS
PACS Industries, Inc., has been in business since 1972, and has concentrated on the manufacture of Medium Voltage Metalclad Switchgear in the range of 2400 Volts, to 41 kV, and to Standards of IEEE C37.20.2 and IEC 298. Our 170,000 square foot factory is in Mount Vernon, Ohio. In the range of 2400 Volts to 15 kV (17.5 kV IEC), PACS will use circuit breaker elements manufactured by G.E., Cutler-Hammer, Siemens, or other reputable companies. For 27 kV Class circuit breakers, PACS manufactures a proprietary series of drawout circuit breakers, utilizing Vacuum Interrupters , or SF6 Interrupters . Circuit breaker trucks and cells are built to the standards of IEEE C37.20.2, and include all required ANSI C37.20.2 features such as metal shutters, automatic secondary plugs, automatic trip upon breaker movement in the cell, etc. Type Test data is available to the standards of IEEE C37.20.04, 06, 09 for circuit breakers, to C37.20.2 for distribution switchgear, C37.013 for generator Switchgear, and to C37.20.07 for Arc Resistant switchgear (as well as relevant I.E.C. Standards). Short circuit Type Tests are usually performed at KEMA. The PACS Laboratory includes a 230 kV BIL Impulse generator, a 9,000 Amp Heat run facility, Partial Discharge Test Equipment, Hi-pots, Meggers, etc. Switchgear available as PACSafe Arc Resistant switchgear. Ground switches are available. PACS can provide streaming video services of switchgear being manufactured or tested, as an option.

This catalog has combined in one issue, drawout metalclad switchgear from the operating ranges of 2400 Volts, through 27kV. Although the dielectric characteristics of these ratings vary between the voltage classes (5 kV, 8.25 kv, 15 kV & 27 kV), the dimensions, features and operation have sufficient in common, to list them together. Switchgear is available in two high (circuit breaker) construction to 2000 Amps. Above 2000 Amps, there should be only one circuit breaker per vertical cell. Drawout potential transformers can be installed over a circuit breaker only up to 2000 Amps.

Generator Circuit Breakers Available To IEEE C37.013

Why Specify PACS Switchgear?


As an independent company, we respond much faster to your requests for proposal, service, information, design assistance and delivery. We at PACS Industries, Inc., are proud to be able to design standard and special switchgear to suit a customers requirements. We provide designs and manufacturing methods that reflect the highest Electric Utility Grade switchgear. Change orders are pleasantly and efficiently handled, and are usually integrated into production, without extending the promised delivery date. During all phases of the order, you can directly contact the PACS engineering department to discuss various issues. After-order service is as important to PACS personnel, as is before-order promises. We at PACS continually ask ourselves, Why should a customer purchase PACS products?...and we are continuously striving to develop new reasons for you, our customer, to do so. Contact us for international sales and service support

Tel: 516-829-9060

Fax: 516-829-9557

e-mail: sales@pacsindustries.com

web: pacsindustries.com

Standards & Specifications


Description of

PACSclad Metalclad Switchgear


D G C E F

This class of switchgear is used to control discreet increments of electric power, generally at operating voltages of 2400 Volts, through 26 kV. 50 or 60 Hertz. A typical lineup would include circuit breaker cubicles, and required auxiliary cubicles. Arranged for indoor or outdoor service. Each vertical cubicle is segregated from its adjoining vertical cubicle by 11 gauge sheet steel (3.0 mm) , and within vertical cubicles, each compartment is further segregated by 11 gauge sheet steel partitions. All exterior surfaces are safe-touch, dead front. Standards: All ANSI switchgear conforms to IEEE C37.20.2, and circuit breakers conform to IEEE C37,20, 04, 06, & 09. IEC switchgear conforms to the standards of IEC 298 and IEC 56.

Metalclad switchgear (see Fig 1) consists of segregated :

A. Circuit breaker compartments. B. Drawout circuit breakers. C. Potential transformer drawout compartments. D. Front door(s) containing required protective relays, meters, and control switches. E. Main bus bar duct within the switchgear. F. Rear connection cable or bus duct compartments. G. Required auxiliary cubicles. H. Optional Grounding (Earthing) Switches.

PACS Universal IEEE & IEC Switchgear


Fig 1. Typical cross section of circuit breaker cubicle, with P.T compartment on top. Includes optional Grounding Switch, as required by I.E.C. standards.

Metalclad switchgear is further characterized by the following: All live parts are enclosed within grounded metal compartments. The circuit breaker compartment includes grounded metal shutters in front of the primary (high voltage) plug-in connection bushings. The shutter position is automatically operated by circuit breaker movement. The circuit breaker is mounted on a truck that is drawout. The truck may be connected or disconnected through closed front doors, via a racking mechanism. Available are remote racking motors for operator safety. Stored energy operation. Interlocks are provided to insure safe circuit breaker operation, such as discharging all springs when the breaker is moved within the cell, preventing a closed breaker from being moved into or within the cell, etc. All bus bars are insulated. Copper, with silvered connection pads. The circuit breaker control circuit (secondary), is automatically connected or disconnected, depending upon the circuit breaker position. Control circuits are segregated from high voltage circuits by metallic barriers, (except for short lengths of certain devices, as permitted in IEEE standards). Every circuit breaker has Disconnect, Test, and Connect positions, with visible indication. The control cubicle includes all necessary relays, terminal blocks, etc.. Current transformers include shorting terminal blocks. Control conductors are SIS type switchgear wire. Circuit breaker automatically grounded when racked into position.

Altitude Correction Factors


Altitude To 1000 m 1800m 3000m Altitude 3300 ft 6000 ft 10000 ft
B.I.L. & P.F Correction Current Correction

1.00 0.92 0.80

1.00 0.99 0.96

Correction factors may be interpolated linearly

Ambient Temperature Correction


Maximum Ambient 55 50 40 30 15 (ISO) Correction Factor 0.88 0.92 1.00 1.07 1.18

Background & Services:

PACS Industries, Inc., was founded in 1972, and since then has enjoyed growth commensurate with its service to large industrials , Gas Turbine OEM manufacturers, Contractors & Electric Utility companies. In addition to domestic business, PACS has a significant foreign business especially in the Middle East, and the Pacific Rim. Our customer engineering and administrative offices are in Great Neck, NY. Our 170,000 square foot factory is in Mount Vernon, Ohio. It is a vertically integrated factory, including a metal fabricating shop, a Powder Coat paint facility, and ample indoor assembly space Our test laboratory includes an Impulse Generator to 250 kV BIL, a heat run facility to 9000 Amps, Partial Discharge testing facilities, etc. PACS field supervision services are available as contracted for. All drawings and documentation are by AutoCad and Promis-e programs. PACS drawings, bills-of-material, and instruction manuals constitute a complete record of equipment we build.

Tel: 516-829-9060

Fax: 516-829-9557

e-mail: sales@pacsindustries.com

web: pacsindustries.com

to 15 kV Switchgear Details
Due to many similar physical construction features between 15 kV Class & 27 kV Class switchgear, we have identified certain details that are available for all voltage classes in this bulletin with the mark 15 & 27 kV

PACSclad metalclad switchgear utilizes components such as potential transformers, current transformers, etc., of the highest quality, conforming to the customers requirements. Circuit breakers are provided with 4 Normally Open and 4 Normally Closed auxiliary contacts as standard (MOC). Additional contacts available. DC ratings are 10 Amps @ 125 VDC. Cell contacts (TOC) are available as well. DC ratings are 10 Amps @ 125 VDC. All circuit breakers are furnished with Through-Door (closed door) racking provisions from Disconnect to Connect positions. Remote motorized racking is available. Manual trip provisions are available on closed door. Interior cell lights and convenience receptacles are available.
Following are recommendations regarding the selection of different BIL levels. 95 kV BIL. Ideal for indoor, clean atmospheres. 110 kV BIL. Ideal for outdoor use. Ideal for altitudes over 1000 meters (3300 feet) in order to maintain the same BIL level as at lower altitudes. Also ideal for environmentally challenging atmospheres, or where customer wishes to maintain the 110 kV BIL requirements of outdoor transformer & substations. Ideal for desert areas (as in the Middle East) with high salt atmosphere and high ambient temperatures.

Typical 13.8 kV switchgear with two-high circuit breaker construction.

15 & 27 kV

Remote Control Operators Available For Insertion and Withdrawal of Circuit Breakers.

Bottom breakers are available with either roll-in installation, or lift truck.

Top located circuit breakers are installed via a lift truck.

Grounding & Testing Accessories


15 & 27 kV Grounding (earthing) fault-make switches. Manual or Electrical Interlocked.

Electrical or Manual Ground & Test trucks.

Typical Vacuum Circuit Breakers. To 15 kV. To 3500 Amps, 63 kA


PACS utilizes multifunction relays & controls manufactured by GE Multilin, ABB, Basler, Areva, Schweitzer, Siemens, etc. As required by customer. SCADA provisions or systems available.

A 1/4 x 2 Copper Grounding Bus is carried through each cubicle. Ground Studs & Cables Available as Specified

Tel: 516-829-9060

Fax: 516-829-9557

e-mail: sales@pacsindustries.com

web: pacsindustries.com

to 15 kV Switchgear Details

Arc Resistant Switchgear


15 & 27 kV

Bus Duct Entry

OPEN
Fault-closing Grounding Switch interlocked with circuit breaker in disconnect position.
15 & 27 kV kV kV

Negative Sequence Current Transformer. Typical Drawout Potential Transformer Drawers.

Typical Views of 15 kV Vacuum Drawout Metalclad Switchgear.


SF6 Circuit Breakers Available

GROUNDED

Rear View 2 High

View of Insulated Bus Bars 15 & 27 kV

Front View. Breaker Top, PTs Bottom

Tel: 516-829-9060

Fax: 516-829-9557

e-mail: sales@pacsindustries.com

web: pacsindustries.com

Vacuum Circuit Breaker Data


IEEE/ANSI C37.20.06 (2000) (I.E.C. Data) 5 kV to 15 kV Class. KA Rated Symmetrical Basis. (IEEE standards changed from MVA to KA . K factor is now 1.0 )
Continuous Current Amps (RMS) 1200 Amps 2000 Amps 3000 Amps 1200 Amps 2000 Amps 3000 Amps 1200 Amps 2000 Amps 3000 Amps Maximum Voltage Operating Voltage Obsolete MVA Ratings K Factor Symmetrical Interrupting Rating kA RMS 36 (10 kV) 50 Momentary Close & Latch kA Peak 97 BIL Crest Power Frequency Withstand kV 19 % DC Interrupting Current kA 50 Rated Interrupting Time Cy / ms 3 / 50 5 / 87 3 / 50 5 / 87 3 / 50 5 / 87 Short Time Current Withstand 3 Sec 36

V (kV)

V (kV) 2400V To 4160V 2400V To 4160V 2400V To 4160V

MVA 250 1.0

kV 60 (40 kV) 60

4760 V (3300V) 4760 V 4760 V

350

1.0

135

19

50

50

500

1.0

63

170

60

19

50

63

Numbers in (RED PARENTHESIS) are IEC 56 ratings. IEC are 50 Hz.


1200 Amps 2000 Amps 3000 Amps 1200 Amps 2000 Amps 3000 Amps 1200 Amps 2000 Amps 3000 Amps 1200 Amps 2000 Amps 3000 Amps

8250 V

To 7200 V

500

1.0

41

115

95 kV

95

50

5/87

41

15.0 kV (17.5 kV) 15.0 kV (17.5 kV) 15.0 kV (17.5 kV)

To 13.8 kV To 13.8 kV To 13.8 kV

500

1.0

25

97

95 kV Or 110 kV 95 kV Or 110 kV 95 kV Or 110 kV

36 ANSI (38 IEC) 36 ANSI (38 IEC) 36 ANSI (38 IEC)

50

3 / 50 5 / 87 3 / 50 5 / 87 3 / 50 5 / 87

25

750

1.0

36

135

50

36

1000 1500

1.0

50 63

135 170

50

50 63

HIGH CURRENT VACUUM CIRCUIT BREAKERS


3500 Amps Convection 4000 Amps Fan Cooled 4000 Amps Convection 5000 Amps Convection 5600 Amps Conv/Fan 6000 Amps Conv/Fan

15.0 kV (17.5 kV) 15.0 kV (17.5 kV) 15.0 kV (17.5 kV) 15.0 kV (17.5 kV) 15.0 kV (17.5 kV) 15.0 kV (17.5 kV)

To 13.8 kV To 13.8 kV To 13.8 kV To 13.8 kV To 13.8 kV To 13.8 kV

1.0 1.0 1.0

36-63 kA 36-63 kA

82-160 kA 82-160 kA

95 kV 95 kV

36 ANSI (38 IEC) 36 ANSI (38 IEC)

50 50

3 / 50 5 / 87 3 / 50 5 / 87

50-63 kA 50-63 kA

1.0 1.0 1.0

40 kA 50 kA 63 kA

108 kA 132 kA 160kA

95 kV 110 kV

IEEE 36 kV (IEC 38 kV)

50

5/87

IEEE 36 kV (IEC 38 kV)

Normal width of all cubicles is 36 inches (914 mm), except for 4000 Amp Convection, 5000 Amp Convection & 6000 Amp Fan Cooled. Fan Cooled models utilize 2 sets of fans (one redundant) if requested. Interrupting current rating constant for all voltages less than the maximum voltage. MVA levels therefore decrease (MVA=A x V x 1.73). 3 Cycle or 5 Cycle interrupting circuit breakers available. Contact us for back-to-back capacitor ratings. Maximum tripping delay is 2 seconds for all circuit breakers per IEEE/ANSI standards. Convection Cooling is natural cooling. Fan is forced cooling.

Tel: 516-829-9060

Fax: 516-829-9557

e-mail: sales@pacsindustries.com

web: pacsindustries.com

Dimensions & Data


High Voltage Cables Top Compartment. 2 High. Auxiliary, PTs or Circuit Breaker

Top View Front View


Circuit Breaker

Sectional View
To 15 kV also in 26 95kV BIL 15 kV Width 36 110 kV BIL 15 kV Width 36 125 kV BIL 27 kV Width 36 For width see data to the left. HEIGHT: 95 kV BIL . 95 110 kV BIL. 95 125 kV BIL 95 DEPTH 95 kV BIL 95 110 kV BIL 95 125 kV BIL 110

Dimensions are for estimating purposes only. See PACS for actual dimensions of your requirements.

Estimated Heat Loss per Cubicle Main Bus & 1 Breaker Per Cubicle.
1200 Amp C.B. & Main Bus 2000 Amp C.B. & Main Bus 2500 Amp C.B. & Main Bus 3000 Amp C.B. & Main Bus 4000 Amp C.B. & Main Bus 650 Watts 850 Watts 1100 Watts 1800 Watts 2200 Watts

A)

Sheetmetal Finish Specifications

Data For Estimating Purposes And Subject To Project Requirements Bus Bar Size & Capacity. Based upon 65 deg C Heat Rise Over a 40 deg C Ambient.

1200 Amps 2000 Amps 2500 & 3000 Amps 4000 Amps

1 each 1/4 x 4 Copper per ph. 1 each 1/2 x 6 Copper per ph. 2 each 1/2 x 6 Copper per ph. Based upon arrangement

Interior switchgear sheet metal may be finished either in a galvanized finish, or a coated finish as described below. PACS utilizes a Powder Coat finish to coat sheet metal. This is a heat cured process, utilizing a Polyester powder that is sprayed on, and then is cured at a high temperature to create a virtually indestructible finish, that has been tested to exceed 1000 hours of salt spray. Following is a brief procedure summary: A) Sheetmetal is cleaned and blemishes are removed. B) An Alkaline caustic cleaner is used to treat the metal, prior to preparing the Powder Coat process. C) The metal panels are preheated to a temperature of 450 degrees F. D) The metal panel passes by conveyor to the Polyester powder spray-on area. E) The coated metal is conveyed to a curing oven at 450 degrees F, and then to a cool-down area. F) Standard paint colors are ANSI 61 (grey) and Desert Tan. Other colors are available. G) Sheetmetal available in steel, aluminum, or stainless.

Tel: 516-829-9060

Fax: 516-829-9557

e-mail: sales@pacsindustries.com

web: pacsindustries.com

27 kV Switchgear Details

Typical 27 kV Drawout Circuit Breaker. Includes Automatically coupled Primary (M.V.) and Secondary connections

27 kV Drawout cell with shutters in closed position. Shutters automatically open as circuit breaker is inserted. Can be padlocked.

View of same cell on left, with shutters opened, revealing current transformers installed over primary bushings.

Rear view of assembled 27 kV circuit breaker. Note that primary (MV) connections are round tulips .

Drawout Potential Transformers over circuit breaker.

15 kV and 27 kV circuit breaker racked through available closed door.

View of 27 kV primary bushings and current transformers.

Due to many similar physical construction features between 15 kV Class & 27 kV Class switchgear, we have identified 15 & & kV 15 27 kV certain details marked 15 &V27 27 kV are available for both ratings.

27 kv Class. 125 kV BIL (See our 38 kV bulletin for 150 kV to 200 kV BIL)
Continuous Current Amps (RMS) 1200 Amps 2000 Amps 3000 Amps 1200 Amps 2000 Amps 3000 Amps 1200 Amps 2000 Amps 3000 Amps Maximum Voltage Operating Voltage K Factor Symmetrical Interrupting Rating kA RMS Momentary Close & Latch kA Peak BIL Crest Power Frequency Withstand kV % DC Interrupting Current Rated Interrupting Time Cy / ms Short Time Current Withstand 3 Sec

kV kV kV kV

V (kV)

V (kV)

kV

27 kV 27 kV 27 kV

24 kV

1.0

25

68

125

50

50

5 / 87

25

24 kV

1.0

31.5

85

125

50

50

5 / 87

31.5

24 kV

1.0

40

108

125

50

50

5 / 87

40

Tel: 516-829-9060

Fax: 516-829-9557

e-mail: sales@pacsindustries.com

web: pacsindustries.com

27 kV Switchgear Details

NEMA 3R Non-Walk-In

Lineup in construction

Typical Views of 27 kV Switchgear. Available with Vacuum or SF6 Circuit Breakers.

Protective Relay Panels


Protective Relay Panels for Switchgear or Substation service. Available in various enclosures such as Simplex, Duplex, Walk-in, & buildings. Protective Relay brands of customers choice. SCADA & PLCs available.
Tel: 516-829-9060 Fax: 516-829-9557 e-mail: sales@pacsindustries.com web: pacsindustries.com

Power & Control Centers


Power & Control Center Summary
PACS manufactures all Power & Control Centers (PCC) in our 170,000 Square Foot factory. As such, we can integrate all PACSclad switchgear into the required PCC, under one roof. The PACS assembly areas can accommodate over 30 - 36 x 12 buildings simultaneously. For larger switchgear buildings, we have accommodated 100 x 30 buildings with ease. Buildings can be equipped with climate systems, can be pressurized, and can include ancillary rooms for batteries, controls, etc. Buildings that need to be split for over-the-road transport, are first assembled completely, prior to disassembly for shipment. Customers are welcome to observe.

Views of Outdoor Switchgear

The PACS manufacturing process includes: Structural Underframes: The PACS structural welding shop includes 140 of

44 Feet x 30 Feet

welding jigs. Underframe skids are welded on these jigs by certified welders. Average beam size would be 10 to 15 depending on application. A steel plate floor is then welded to the skid. After welding is complete, the skid is moved to an adjacent sand blasting room, then to an undercoating room, and then to the shop floor.

Wall & Roof Types:

PACS manufactures different wall & roof types to accommodate various PCC applications. Interlocking Panel walls utilize 16 to 18 gauge exterior walls, and 16 to 18 gauge interior walls. Generally freestanding, self-framing, and thermally insulated. Shelter-Clad type, is like the traditional switchgear buildings, fabricated of 11 gauge metal pans. May be thermally insulated or not. Integrated with switchgear cubicles. Monobloc panels are of molded sandwich formed construction, outer & inner surfaces are of 22 gauge to 26 gauge painted metal . The interior of the panel is a minimum of 3 of structural foam bonded to the metal surfaces. The thermal insulating qualities are superior. Various wall & roof types can be combined as required. Steel, aluminum, and stainless cladding available. Accessories: Rear removable panels, or doors as required. All required & exterior lighting, convenience outlets, etc. Required building utility step-down transformers, and circuit breaker panels. Required air conditioning, heating, ventilating, and pressurization systems..etc. 34.5kV

Interior View

80 Feet x 30 Feet In Production

13.8 kV

Combined 13.8 kV & 34.5 kV Building

108 Feet x 34 Feet

Tel: 516-829-9060

Fax: 516-829-9557

e-mail: sales@pacsindustries.com

web: pacsindustries.com

Special Switchgear High Current Drawout Switchgear. 4,000 to 6,000 Amperes

4,000 to 6,000 Ampere Vacuum Circuit Breaker. Drawout, to 63 kA S.C.

4,000 to Circuit Breaker can Circuit Breaker Vacuum 6,000 Amp Vacuum be easily moved moved by use of a fifth wheel accessory. by use of a fifth wheel accessory

Upper photo of cell with closed shutters. Lower photo shutters open , and current transformers.

PACS Industries are theis the leading manufacIndustries, inc., leading manufacturer of turer to 6,000 Ampere Ampere Vacuum Circuit 4,000of 4,000 to 6,000 Vacuum Circuit Breakers Breakers and drawout switchgear, at 13.8 at and drawout metalclad metalclad switchgear, kV 13.8 kV voltage, voltage, for or Generator operating operating for DistributionDistribution or Generator switchgear, switchgear, Generator Circuit Breakers have been Type Tested to IEEE C37.013 requirements. Over 250 are in use with throughout USAUSA and overthroughout the the and overseas. Available to 63 to Interrupting & 3 & 3 second seas. Available kA 63 kA Interruptingsecond S.C., 160 160 kA Momentary. Available at 95 kV & S.C.,kA Momentary. Available at 95 kV & 110 kV BIL. 110 kV BIL.

Typical 4000-6000 Amp Outdoor

Special Switchgear Construction


A.C . Railway Switchgear. 25 or 60 Hz
Trolley switchgear to 52 kV, 250 KV BIL. Fixed station class or drawout construction. One or two pole.

( We can build what other companies ignore..try us)

Drawout traction breaker.

Typical trackside switchgear. Also available in single station class cubicles.

Iso-Phase Switchgear
Accessory switchgear for Isolated-Phase bus duct systems, such as P.T. cubicles, Auxiliary Transformer cubicles, etc.

Generator & Paralleling Switchgear To C37.013 Standards 1200 Amps through 6000 Amps PACS manufactures generator switchgear that includes circuit breakers to the IEEE C37.013 Standard. This Standard will now cover small generators up to 100 MVA, as well as larger generators. Contact us for appropriate bulletins.

Arc Furnace Switchgear for Steel Mills. Through 40.5 kV

comPACSwgr
Compact switchgear 26 wide. Including 2 high circuit breakers. 3 high switchgear to 15 kV. Front-Access-Only metalclad switchgear that can mount against a wall.

Tel: 516-829-9060

Fax: 516-829-9557

e-mail: sales@pacsindustries.com

web: pacsindustries.com

Arc-Flash Avoidance PACSafe

Avoid Arc-Flash
The best way to avoid a destructive electrical ArcFault blast is through preventive means. PACSafe continuously monitors live bus bars for corona and voltage, and detects deteriorating insulation systems. Level adjustments include warning or shutdown setpoints, allowing repairs, avoiding Arc-Flash explosions. Can be fed to a computer for long time analysis & event recording.

Failures

PARTIAL DISCHARGE ANALYZERS:

For retrofit of existing switchgear, or new switchgear.

Request PACSafe Catalog

ARC-MITIGATION SYSTEM:
In the event that an Arc-Flash does occur in switchgear, it is imperative that the fault source be disconnected as quickly as possible, to avoid or mitigate damage to equipment or personnel. The PACSafe Type Arc Detection system, immediately senses a light flash in a switchgear cubicle when an Arc-Flash occurs, and simultaneously senses for Rate-of-Rise of current. A signal is sent to targeted breaker trip coils, bypassing Protective relays, tripping in as low as 57ms, mitigating Arc-Fault damage. This compares to over 300 ms trip time in Selective Coordination relay systems. Damage to the switchgear is proportional to the time duration of the Arc-Fault. The shorter the duration, the less damage will occur.

For retrofit of existing switchgear, or new switchgear.

Request PACSafe Catalog

ARC-RESISTANT SWITCHGEAR:
PACSafe Arc-resistant switchgear is available, designed and tested in accordance with IEEE C37.20.7 standards. PACS has successfully tested single high and 2 high switchgear. IEEE Types 1, 2, 1C & 2C, at the KEMA laboratories. The PACSafe Arc-Resistant designs include available top mounted Collector Plenums, to safely duct the Arc-Fault flames, heat, pressure, smoke & debris out of the switchgear room, into a safe disposal area.

For new & replacement applications.

Request PACSafe Catalog

Additional Products Available From PACS



W Rev 0

See our web. pacsindustries.com Outdoor Structural Substations to 230 kV. Arc-Furnace circuit breakers & switchgear. Railway catenary circuit breakers & switchgear. Single phase. 4,000 to 6,000 Amp Generator Switchgear per IEEE C37.013. Drawout Metalclad switchgear through 40.5 kV.

Switchyards

Station Class CB

6000 A Breakers

Tel: 516-829-9060

Fax: 516-829-9557

e-mail: sales@pacsindustries.com

web: pacsindustries.com