Medium voltage products

Vmax Medium voltage vacuum circuit-breakers IEC: ... 17.5 kV; ... 1250 A; ... 31.5 kA ANSI: ... 15 kV; ... 1200 A; ... 31.5 kA

Contents

2 10 24 28 33

1. 2. 3. 4. 5.

Description Selection and ordering Specific product characteristics Overall dimensions Electric circuit diagram

1. Description

Vacuum breaking technique Contacts in a vacuum protected against oxidation and contamination Operation under different climatic conditions Limited switching energy Stored energy operating mechanism with anti-pumping device supplied as standard Simple customization with a complete range of accessories Fixed and withdrawable version Compact dimensions Sealed-for-life vacuum interrupters Sturdiness and reliability 10,000 operations with regular maintenance Circuit-breaker racking-in and racking-out with the door closed Incorrect and hazardous operations prevented thanks to special locks in the operating mechanism and in the truck

General information
The new Vmax circuit-breakers are the synthesis of ABBs affirmed technology in designing and constructing vacuum interrupters and their excellence in design, engineering and production of circuit-breakers. The Vmax medium voltage circuit-breakers consist of an insulating monobloc in which three vacuum interrupters are housed. The monobloc and operating mechanism are fixed to a frame. The vacuum interrupter houses the contacts and makes up the interrupting chamber.

Current breaking in vacuum


The vacuum circuit-breaker does not require an interrupting and insulating medium. In fact, the interrupter does not contain ionizable material. In any case, on separation of the contacts an electric arc is generated, made up exclusively of melted and vaporised contact material. The electric arc only remains supported by the external energy until the current is cancelled by passing through natural zero. At that instant, the rapid reduction in the load density carried and fast condensation of the metallic vapor, leads to extremely rapid recovery of the dielectric properties. The vacuum interrupter therefore recovers the insulating capacity and the capacity to withstand the transient recovery voltage, definitively extinguishing the arc. Since high dielectric strength can be reached in the vacuum, even with minimum distances, circuit breaking is also guaranteed when separation of the contacts takes place a few milliseconds before passage of the current through natural zero.

Push-buttons and mechanical indicators for IEC versions

Vmax/L according to IEC STDs

Push-buttons and mechanical indicators for ANSI versions

The special geometry of the contacts and the material used, together with the limited duration and low voltage of the arc guarantee minimum contact wear and long life. Furthermore, the vacuum prevents their oxidation and contamination.

Structure
The operating mechanism, monobloc and interrupters are fixed to a metal frame which is also the support for the fixed version of the circuit-breaker. The compact structure ensures sturdiness and mechanical reliability. Apart from the isolating contacts and the cord with plug for connection of the auxiliary circuits, the withdrawable version is completed with the truck for racking it into and out of the switchgear with the door closed.

EL type operating mechanism


The low speed of the contacts, together with the reduced run, and the mass contained, limit the energy required for the operation and therefore guarantee extremely limited wear of the system. This means the circuit-breaker requires limited maintenance. The Vmax circuit-breakers use a mechanical operating mechanism, with stored energy and free release. These characteristics allow opening and closing operations independent of the operator. The mechanical operating mechanism is of simple concept and use and can be customized with a wide range of easily and rapidly installed accessories. This simplicity translates into greater reliability of the apparatus.

Versions available
Vmax circuit-breakers are available in the fixed and withdrawable version with front operating mechanism. The withdrawable version is available for UniGear ZS1 switchgear with 550 mm width, and for PowerCube modules with 600 mm width. A specific fixed version is available for UniGear 500R switchgear. Note: all the above mentioned switchgear only complies with IEC Standards.

1. Description

Breaking principle of ABB interrupters


In a vacuum interrupter, the electric arc starts at the instant of separation of the contacts, is maintained until the next current through zero and can be influenced by the magnetic field. Diffuse or contracted vacuum arcs Following contact separation, single melting points form on the surface of the cathode, producing metal vapors which support the arc. The diffuse vacuum arc is characterized by expansion over the contact surface and by an even distribution of the thermal stress. At the rated current of the vacuum interrupter, the electric arc is always of the diffuse type. Contact erosion is very limited, and the number of interruptions very high.

As the interrupted current value increases (above the rated value), the electric arc tends to be transformed from the diffuse into the contracted type, due to the Hall effect. Starting at the anode, the arc contracts and as the current rises further it tends to concentrate. In the area involved there is an increase in temperature with consequent thermal stress on the contact. To prevent overheating and erosion of the contacts, the arc is kept rotating. With arc rotation it becomes similar to a moving conductor which the current passes through. Spiral geometry of ABB vacuum interrupter contacts The special spiral geometry of the contacts generates a radial magnetic field in all areas of the arc column, concentrated over the circumferences of the contacts.

Diffuse arc

Contraction over the anode

Contraction over the anode and cathode

Schematic diagram of the transition from a diffuse to a contracted arc in a vacuum interrupter.

Radial magnetic field contact pattern with an arc rotating in a vacuum.

An electromagnetic force is self-generated and acts tangentially, causing rapid arc rotation around the contact axis. This means the arc is forced to rotate and to involve a wider surface than that of a fixed contracted arc. Apart from minimizing thermal stress on the contacts, all this makes contact erosion negligible and, above all, allows the breaking process to be controlled even with very high shortcircuit currents. ABB vacuum interrupters are zero-current interrupters and are free of any re-striking. Rapid reduction in the current charge and rapid condensation of the metal vapors simultaneously with the zero current, means maximum dielectric strength can be restored between the interrupter contacts within microseconds.

1 2 3 4 5

6 7 8 9

Short-circuit current Current, Voltage Arc voltage System voltage Short-circuit current breaking

10

Time Contact separation Recovery voltage (system frequency) Transient recovery (TRV) (high frequency)

1 2 3 4 5 6 7 8 9 10

Terminal Twist protection Metal bellows Interrupter housing Shield Ceramic insulator Shield Contacts Terminal Interrupter housing

Development of current and voltage trends during a single-phase vacuum breaking process.

Vacuum interrupter

1. Description

Fields of application
Vmax circuit-breakers are used in electrical distribution to protect cables, distribution and transformer substations, motors, transformers, generators and capacitor banks.

Standards and approvals


Vmax circuit-breakers comply with the IEC 62271-100, CEI-EN 62271 (file 7642), ANSI/IEEE C37.54-C37.09C37.04-C37.55 Standards and with those of the major industrialized countries. The Vmax circuit-breakershave undergone the tests indicated below and guarantee safety and reliability of apparatus in service in all installations. Type tests: heating, insulation withstand at power frequency, atmospheric impulse withstand insulation, shorttime and peak withstand current, mechanical life, making capacity and breaking capacity. Individual tests: insulation of main circuits with voltage at power frequency, auxiliary and control circuit insulation, measurement of main circuit resistance, mechanical and electrical operation.

Service safety
Thanks to the complete range of mechanical and electrical locks (available on request), safe distribution switchgear can be built with Vmax circuit-breakers. The locking devices have been studied to prevent incorrect operations and to carry out inspection of the installations, ensuring maximum operator safety. Key locks or padlock devices enable opening and closing operations and/or racking in and racking out. The racking-out device with the door closed only allows the circuit-breaker to be racked into or out of the switchgear with the door closed. Anti-racking-in locks prevent circuit-breakers with different rated currents from being racked in, and the racking-in operation with the circuit-breaker closed.

Accessories
The Vmax circuit-breakers have a complete range of accessories to satisfy all installation requirements. The operating mechanism has a standardized range of accessories and spare parts which are easy to identify and order. The accessories are installed conveniently from the front of the circuit-breaker. Electrical connection is carried out with plug-socket connectors. Use, maintenance and service of the apparatus are simple and require limited use of resources.

Operating mechanism
The operating mechanism of Vmax circuit-breakers is of simple concept and use and can be customized with a wide range of easily and rapidly installed accessories. This simplicity translates into greater reliability of the apparatus. The operating mechanism is of the stored energy type with the anti-pumping device mounted as standard and it is fitted with suitable locks to prevent incorrect operations. Each operation sequence is only enabled if all the conditions ensuring it will be carried out correctly are respected. The accessories are the same for all the types of Vmax circuit-breakers. To facilitate assembly and replacement of accessories, assembly seats with special fixed references are provided.

1. Description

Highly reliable operating mechanisms thanks to a low number of components Extremely limited and simple maintenance The accessories are common to the whole range The electrical accessories can be easily and rapidly installed or replaced thanks to the wiring already prepared with its own plug-socket connectors

Mechanical anti-pumping device is standard Built-in closing spring charging lever Key lock with circuit-breaker open Protective cover over the opening and closing pushbuttons for operation using a special tool Padlock on the operating pushbuttons

Circuit-breaker operating mechanism (pushbutton and mechanical indicators according to IEC STDs) F

M N A

L I H G

C D

B E

A B C D E F G

Open/closed auxiliary contacts Geared motor for closing spring charging Built-in closing spring charging lever Mechanical signaling device for circuit-breaker open/closed Mechanical operation counter Plug-socket connectors of electrical accessories Signaling device for closing springs charged/discharged

H Service releases (shunt opening release, shunt closing release, undervoltage release) I Closing pushbutton L Opening pushbutton M Additional shunt opening release N Locking magnet on the operating mechanism O Contact for signaling closing spring charged/discharged

Technical documentation
To go into technical and application aspects of the Vmax circuit-breakers in depth, please ask for the following publications: UniGear ZS1 type switchgear code 1VCP000138 REF542plus unit code 1VTA100001 PowerCube code 1VCP000091

Quality Assurance System


This complies with the ISO 9001Standards, certified by an independent external organization.

Test laboratory
This complies with the UNI CEI EN ISO/IEC 17025 Standards, accredited by an independent external organization.

Environmental Management System


This complies with the ISO 14001 Standards, certified by an independent external organization.

Health and Safety Management System


This complies with the OHSAS 18001 Standards, certified by an independent external organization.

2. Selection and ordering

General characteristics of fixed circuit-breakers for:


free-standing installation ABB UniGear 500R switchgear

Circuit-breaker Fixed version Fixed version for ABB UniGear 500R panel IEC 62271-100 Standards CEI EN62271-100 (file 7642) C37.54 - C37.09 - C37.04 - C37.55 UL Recognized Component Mark Rated voltage Rated insulation voltage Withstand voltage at 50 Hz Impulse withstand voltage Rated frequency Rated normal current (40 C) Rated breaking capacity (rated symmetrical short-circuit current) Ur [kV] Us [kV] Ud (1 min) [kV] Up [kV] fr [Hz] Ir [A]

Isc [kA]

Rated-short time withstand current (3s)

Ik [kA]

Standard fittings for fixed circuit-breaker series ( )


1

The basic versions of the fixed circuit-breakers are three-pole and fitted with: EL type manual operating mechanism mechanical signaling device for closing springs charged/ discharged mechanical signaling device for circuit-breaker open/closed closing pushbutton opening pushbutton operation counter set of ten circuit-breaker open/closed auxiliary contacts (2) lever for manually charging the closing springs auxiliary circuit support terminal board.

Making capacity

Ip [kA]

Operation sequence Opening time Arc duration Total breaking time Closing time
I I

[O - 0.3 - CO - 15 - CO] [O - 0.3 - CO - 3 - CO] [ms] [ms] [ms] [ms] H [mm/in] W [mm/in] D [mm/in]
W D

Maximum overall dimensions Weight

Pole centre I [mm/in] [kg/lb] 1VCD [C] IEC: 60068-2-30, 60721-2-1 IEC 62271-1

Standardized table of dimensions Operating temperature Tropicalization Electromagnetic compatibility


(*) this version cannot be sold loose; this version can only be supplied together ABB UniGear 500R switchgear

(1) Refer to the UniGear 500R catalogue for the standard equipment of the Vmax/F circuit-breaker. (2) Application of the shunt opening release and/or the supplementary shunt opening release foresees the use of one and/or two auxiliary make contacts (normally open), thereby reducing the number of available auxiliary contacts.

10

Vmax 12 12 12 28 75 50-60 630 16 20 25 31.5 16 20 25 31.5 40 50 63 80 33.5 ... 60 10 ... 15 43.5 ... 75 45 ... 80 496 416 421 133 77 003279 -5 ... +40 1250 16 20 25 31.5 16 20 25 31.5 40 50 63 80 630 16 20 25

Vmax 17 17.5 17.5 38 95 50-60 1250 16 20 25 31.5 16 20 25 31.5 40 50 63 80 630 25 31.5 25 31.5 63 80

Vmax/F 12 (*) 12 12 28 75 50-60 1250 25 31.5 25 31.5 63 80 2000 25 31.5 25 31.5 63 80 630 25 31.5 25 31.5 63 80

Vmax/F 17 (*) 17.5 17.5 38 95 50-60 1250 25 31.5 25 31.5 63 80 33.5 ... 60 10 ... 15 43.5 ... 75 45 ... 80 543 516 562 133 80 003558 543 416 461 133 77 003516 -5 ... +40 543 516 562 133 80 003558 2000 25 31.5 25 31.5 63 80

Vmax 15 15 15 36 (at 60 Hz) 95 60 1200 25 (3 cycles) 31.5 (3 cycles) 25 (2s) 31.5 (2s) 65 82 27 ... 32.5 10 ... 17.5 <50 45 ... 80 534/21.02 416/16.38 456/17.95 133/5.24 77/169.40 003279 -30 ... +40 -

31.5 16 20 25 31.5 40 50 63 80 -

33.5 ... 60 10 ... 15 43.5 ... 75 45 ... 80 534 416 456 133 77 003279 -5 ... +40

33.5 ... 60 10 ... 15 43.5 ... 75 45 ... 80 543 416 461 133 77 003516 -5 ... +40

11

2. Selection and ordering

General characteristics of withdrawable circuit-breakers for:


UniGear switchgear (550 mm width) PowerCube PB1 modules (600 mm width)

Circuit-breaker Use in switchgear/enclosure IEC 62271-100 Standards CEI EN62271-100 (file 7642) C37.54 - C37.09 - C37.04 - C37.55 UL Listed Rated voltage Rated insulation voltage Withstand voltage at 50 Hz Impulse withstand voltage Rated frequency Rated normal current (40 C) Rated breaking capacity (rated symmetrical short-circuit current) Ur [kV] Us [kV] Ud (1 min) [kV] Up [kV] fr [Hz] Ir [A]

Isc [kA]

Rated short-time withstand current (3s)

Ik [kA]

Standard fittings for withdrawable circuit-breaker series The basic versions of the withdrawable circuit-breakers are three-pole and fitted with: EL type manual operating mechanism mechanical signaling device for closing springs charged/ discharged mechanical signaling device for circuit-breaker open/closed closing pushbutton opening pushbutton operation counter set of ten circuit-breaker open/closed auxiliary contacts (1) lever for manually charging the closing springs isolating contacts cord with connector (plug only) for auxiliary circuits, with striker pin which does not allow the plug to be inserted into the socket if the rated current of the circuit-breaker is different from the rated current of the panel racking-in/out lever (the quantity must be defined according to the number of pieces of apparatus ordered) locking electromagnet in the truck (-RL2). This prevents the circuit-breaker being racked into the panel with the auxiliary circuits disconnected (plug not inserted in the socket).

Making capacity

Ip [kA]

Operation sequence Opening time Arc duration Total breaking time Closing time
I I

[O - 0.3" - CO - 15" - CO] [O - 0.3" - CO - 3' - CO] [ms] [ms] [ms] [ms] H [mm/in] W [mm/in] D [mm/in]
W D

Maximum overall dimensions Weight

Pole centre I [mm/in] [kg/lb] 1VCD [C] IEC: 60068-2-30, 60721-2-1 IEC 62271-1

Standardized table of dimensions Operating temperature Tropicalization Electromagnetic compatibility

(1) Application of the shunt opening release and/or the supplementary shunt opening release foresees the use of one and/or two auxiliary make contacts (normally open), thereby reducing the number of available auxiliary contacts.

12

Vmax/L 12 UniGear 550 12 12 28 75 50-60 630 16 20 25 31.5 16 20 25 31.5 40 50 63 80 33.5 ... 60 10 ... 15 43.5 ... 75 45 ... 80 665 461 665 150 98 003334 -5 ... +40 665 461 665 150 98 665 461 665 150 98 1250 16 20 25 31.5 16 20 25 31.5 40 50 63 80 630 16 20 25 31.5 16 20 25 31.5 40 50 63 80

Vmax/L 17 UniGear 550 17.5 17.5 38 95 50-60 1250 16 20 25 31.5 16 20 25 31.5 40 50 63 80 33.5 ... 60 10 ... 15 43.5 ... 75 45 ... 80 665 461 665 150 98 003334 -5 ... +40 665 503 662 150 98 630 16 20 25 31.5 16 20 25 31.5 40 50 63 80

Vmax/W 12 PowerCube 12 12 28 75 50-60 1250 16 20 25 31.5 16 20 25 31.5 40 50 63 80 33.5 ... 60 10 ... 15 10 ... 17.5 45 ... 80 665 503 662 150 98 003280 -5 ... +40 665 503 662 150 98 630 16 20 25 31.5 16 20 25 31.5 40 50 63 80

Vmax/W 17 PowerCube 17.5 17.5 38 95 50-60 1250 16 20 25 31.5 16 20 25 31.5 40 50 63 80 33.5 ... 60 10 ... 15 43.5 ... 75 45 ... 80 665 503 662 150 98 003280 -5 ... +40

Vmax/W 15 PowerCube (on request) 15 15 36 (at 60 Hz) 95 60 1200 25 (3 cycles) 31.5 (3 cycles) 25 (2s) 31.5 (2s) 65 82 27 ... 32.5 10 ... 17.5 <50 45 ... 80 665/26.18 503/19.80 662/26.06 150/5.91 98/215.60 003280 -30 ... +40 -

13

2. Selection and ordering


Optional accessories
The accessories identified with the same number are alternative to each other (pictures refer to service releases of IEC version) 1 Shunt opening release (-MO1) 2 Additional shunt opening release (-MO2)

This allows remote opening control of the apparatus. The release can operate both in direct and alternating current. This release is suitable for both instantaneous and permanent service. In the case of instantaneous service, the minimum current impulse time must be 150 ms.
Table 1 Un Operating limits MO1-MO2-MC MU RL1 MO1-MO2 (1) Opening time MO1-MO2 ( 2) MC MU Power on inrush (Ps) Inrush duration Continuous power (Pc) Insulation voltage 24 - 30 - 48 - 60 - 110 - 132 - 220 - 250 V DC-AC (50-60 Hz) 65 120% Un 35 85% Un 85 110% Un 33.5...60 ms 27...32.5 ms 45...80 ms 60...60 ms < 150 W 150 ms 3W 2000 V 50/60 Hz (for 1 min)

Like the shunt opening release described above, this allows remote opening control of the apparatus and can be supplied by a circuit completely separate from the -MO1 release. The electrical and operating characteristics are identical to those of the shunt opening release -MO1 (see Table 1).

(1) All versions except Vmax 15 kV and Vmax/W 15 kV. (2) Vmax 15 kV and Vmax/W 15 kV only.

14

3 Undervoltage release (-MU)

The undervoltage release makes circuit-breaker open in the case of notable lowering or lack of its power supply. It can be used for remote release (by means of a normally closed type of pushbutton), lock on closing or to control the voltage in the auxiliary circuits. Circuit-breaker closing is only allowed with the release supplied (the lock on closing is made mechanically). In particular, when the undervoltage release is: de-energized (not supplied): it prevents circuit-breaker closing (if the circuit-breaker is open) and makes the circuitbreaker open (if the circuit-breaker is closed) energized (supplied): it allows circuit-breaker closing (if the circuit-breaker is open) and does not make the circuitbreaker open (if the circuit-breaker is closed). The undervoltage release can be provided for power supply with voltage derived on the supply side of the circuit-breaker (therefore independent of the state the circuit-breaker fitted with undervoltage release is in) or from an independent source.

Should the shunt closing (-MC) and undervoltage (-MU) releases have the same power supply and you want automatic self-closing of the circuit-breaker on return of the auxiliary power supply, to prevent missed closing, it is necessary to introduce a delay of 50 ms between the instant of consent to the undervoltage release and energization of the shunt closing release. When the power supply network of the undervoltage release can be subject to short interruptions or drops in voltage, to avoid undesired trips it is possible to delay the undervoltage release trip by fitting it with an electronic delay device (see the accessory described in the next point). Should the undervoltage release not be supplied, circuitbreaker closing is prevented mechanically and the circuitbreaker remains permanently in the open state. The circuitbreaker can only be operated again if the undervoltage release is de-activated mechanically by means of the undervoltage override (see the accessory described further on).

15

2. Selection and ordering


Optional accessories
The accessories identified with the same number are alternative to each other (pictures refer to IEC version service releases) 4 Shunt closing release (-MC) 5 Electronic time-delay device (-KT)

This allows remote closing control of the apparatus. The release can operate both in direct and alternating current. This release is suitable both for instantaneous and permanent service. In the case of instantaneous service, the minimum current impulse time must be 150 ms. The permanently supplied release carries out the electrical anti-pumping function. The electrical and operating characteristics are identical to those of the shunt opening release -MO1 (for the characteristics see table 1 - page 14).

The electronic time delay device must be mounted externally to the circuit-breaker. It allows release trip with established and adjustable times. The use of the delayed undervoltage release is recommended in order to prevent trips when the power supply network of the release may be subject to cuts or voltage drops of short duration. If it is not energized, circuit-breaker closing is prevented. The time-delay device must be combined with an undervoltage release with the same voltage as the delay device.
Characteristics of the time-delay device

Un
Un

24...30 - 48 - 60 - 110...127 - 220...250 V


48 - 60 - 110...127 - 220...240 - V ~ 50/60 Hz

Adjustable opening time (release + time-delay device): 0.5-1-1.5-2-3 s

16

6 Undervoltage release mechanical override

The mechanical override of the undervoltage release is a mechanical device allowing deactivation of the undervoltage release functionality. Should this accessory by required, specify the request at the time of ordering because subsequent application by the customer is not possible. Deactivation of the undervoltage release takes place by means of a special two-position selector located on the front of the circuit-breaker operating mechanism. The override remains in the selected position until the selector is moved manually from undervoltage deactivated to undervoltage activated (and vice versa). With the override set to undervoltage deactivated the circuit-breaker behaves as if it were without the undervoltage release. This means it is possible to close the circuit-breaker even without power supply to the release.

With the circuit-breaker closed, if you move the selector to the undervoltage activated position, the following occurs: the circuit-breaker remains in the closed state if the undervoltage release is energized (supplied) the circuit-breaker opens immediately if the undervoltage release is de-energized (not supplied). The undervoltage circuit-breaker override is particularly required when: the circuit-breaker controls/protects a MV/LV transformer and the undervoltage release receives the power supply from the LV side and therefore only with the circuit-breaker closed (without the undervoltage override it would never be possible to close the circuit-breaker and therefore to supply the undervoltage release) should it be desired to carry out manual opening and closing operations of a circuit-breaker fitted with undervoltage, in the withdrawn position and/or with auxiliary circuits not supplied. The undervoltage mechanical override with manual resetting is always fitted with an auxiliary contact for electrical signaling of undervoltage release deactivated (-BB6). Note: the mechanical override with manual resetting cannot be supplied on the Italian market for the delivery point of power to the user connected in medium voltage. The CEI 0-16 Standard does, in fact, prohibit permanent deactivation of the undervoltage release when it is used by the General Protection to control opening of the General Device.

17

2. Selection and ordering


Optional accessories
The accessories identified with the same number are alternative to each other (pictures refer to IEC version service releases) 7 Circuit-breaker auxiliary contacts (-BB1; -BB2; -BB3)

General characteristics Insulation voltage according to VDE 0110 standard. Group C Rated voltage Test voltage Rated overcurrent Number of contacts Contact run Activation force Resistance Storage temperature Operating temperature Contact overtemperature Number of cycles 660 V AC 800 V DC 24 V ... 660 V 2.2 kV 10 A 5 6 mm ... 7 mm 26 N 3 m 20 C ... +120 C 20 C ... +70 C 20 K 30,000

It is possible to have electrical signaling of circuit-breaker open/closed with a group of 15 auxiliary contacts as an alternative to the 10 provided as standard. Note Application of the shunt opening release and/or the supplementary shunt opening release foresees the use of one and/or two auxiliary make contacts (normally open), thereby reducing the number of available auxiliary contacts.

Unlimited breaking capacity if used with 10 A fuse in series Electrical characteristics Un 220 V AC 380 V AC 500 V AC 660 V AC Cos = 0,7 Cos = 0,7 Cos = 0,7 Cos = 0,7 Time constant 1 ms 24 V DC 15 ms 50 ms 200 ms 1 ms 60 V DC 15 ms 50 ms 200 ms 1 ms 110 V DC 15 ms 50 ms 200 ms 1 ms 220 V DC 15 ms 50 ms 200 ms 10 A 10 A 8A 6A 8A 6A 5A 4A 6A 4A 2A 1A 1.5 A 1A 0.75 A 0.5 A 12 A 12 A 10 A 7.7 A 10 A 8A 6A 5.4 A 8A 5A 4.6 A 2.2 A 2A 1.4 A 1.2 A 1A Rated current 2.5 A 1.5 A 1.5 A 1.2 A Breaking capacity 25 A 15 A 15 A 12 A

18

8 Transmitted contacts in the truck (-BT1; -BT2)

9 Position contact (-BT3)

Transmitted contacts of the withdrawable circuit-breaker (installed in the circuit-breaker truck). These contacts are either in addition or as an alternative to the position contacts (for signaling circuit-breaker racked out) located in the unit. They also carry out the function of the position contact (-BT3).

This is used, together with the locking magnet of the operating mechanism (-RL1) to prevent remote closing during racking into the cubicle. It is supplied for Vmax/W and Vmax/L withdrawable circuitbreakers. It is not supplied when the transmitted contacts in the truck are required (-BT1; -BT2).

19

2. Selection and ordering


Optional accessories
The accessories identified with the same number are alternative to each other (pictures refer to IEC version service releases) 10 Motor operator (-MS) 11 Contact for signaling closing spring charged/discharged (-BS2)

This carries out automatic charging of the circuit-breaker operating mechanism closing springs. After circuit-breaker closing, the geared motor immediately recharges the closing springs. In the case of a power cut or during maintenance work, the closing springs can be charged manually in any case (by means of the special crank handle incorporated in the operating mechanism).
Characteristics
Un Un Operating limits Power on inrush (Ps) Rated power (Pn) Inrush duration Charging time Insulation voltage 24...30 - 48...60 - 110...130 - 220...250 V 100...130 - 220...250 V ~ 50/60 Hz 85 110 % Un DC = 600 W; AC = 600 VA DC = 200 W; AC = 200 VA 0,2 s 6-7 s 2000 V 50 Hz (for 1 min)

This consists of a microswitch which allows remote signaling of the state of the circuit-breaker operating mechanism closing spring. The contact is available in the following versions: contact open: signaling spring charged contact closed: signaling spring discharged.

20

Protections and locks


Various mechanical and electromechanical locking and protection devices are available. 12 Opening and closing pushbutton protection 14 Key lock in open position

The protection allows the opening and closing pushbuttons to be operated using a special tool only.

The lock is activated by a special circular lock. Different keys (for a single circuit-breaker) are available, or the same keys (for several circuit-breakers).

13 Opening and closing pushbutton padlock

The device allows the opening and closing pushbuttons to be locked using a maximum of three padlocks (not supplied): 4 mm.

21

2. Selection and ordering


Protections and locks
Various mechanical and electromechanical locking and protection devices are available. 15 Locking magnet on the truck (-RL2) 16 Locking magnet on the operating mechanism (-RL1)

Accessory for the withdrawable version to prevent circuitbreaker racking into the switchgear with the auxiliary circuit plug disconnected. The plug makes the anti racking-in lock for different rated current (by means of special pins). This accessory is compulsory for Vmax/L in UniGear 550 switchgear and is optional for Vmax/W in the PowerCube enclosure.
Characteristics Un: 24 - 30 - 48 - 60 - 110 - 125 - 127 - 132 - 220 - 240 V Un: 24 - 30 - 48 - 60 - 110 - 125 - 127 - 220 - 230...240 V~ 50/60 Hz Operating limits: Power on inrush (Ps): Continuous power (Pc): Inrush duration: 85 110% Un DC 250 W; AC = 250 VA DC = 5 W; AC = 5 VA 150 ms

This allows activation of the operating mechanism when the lock is energized only (for the characteristics see table 1 page 14).

22

17 Opening solenoid (-MO3)

18 Mechanical racking-in/racking-out interlock

The opening solenoid (-MO3) is a special release with demagnetization. It is located in the operating mechanism (in the left side piece) and is not alternative to the additional shunt opening release (-MO2). Use of this special release with overcurrent protection devices, differing from PR521 and PR512, must first be tested.

This device allows the racking-in and racking-out lock to be made for circuit-breakers which have been converted into the withdrawable version using a fixed circuit-breaker. The lock consists of two devices which carry out the following functions respectively: lock on circuit-breaker closing during racking in and racking out (installed in the front part of the circuit-breaker) lock on racking in and racking out with the circuit-breaker (installed in the rear part of the circuit-breaker). Compulsory device for Vmax/W and Vmax/L circuit-breakers.

23

3. Specific product characteristics

Resistance to vibrations

Altitude

The Vmax circuit-breakers are unaffected by mechanically generated vibrations. Please contact us for the versions approved by the shipping registers.

Tropicalization

The insulating property of air decreases as the altitude increases, therefore this phenomenon must be taken into account for external insulation of the apparatus (the internal insulation of the interrupters does not undergo any variations as it is guaranteed by the vacuum). The phenomenon must always be taken into account during the design stage of the insulating components of apparatus to be installed over 1000 m / 3300 ft above sea level. In this case an ACF (Altitude Correction Factor) must be considered, which can be taken from the graph on the following page, built up on the basis of the indications in the IEC 62271-1 Standards or by Table 8 of ANSI/IEEE C37.20.2 1999. The following example is a clear interpretation of the indications given above according IEC Standards.

The Vmax circuit-breakers are manufactured in compliance with the strictest regulations for use in hot-humid-saline climates. All the most important metal components are treated against corrosive factors according to EN12500 Standards environmental class C and to ANSI/IEEE C37.20.2. Galvanization is carried out in accordance with UNI ISO 2081 Standards, classification code Fe/Zn 12, with a thickness of 12x10-6 m, protected by a conversion layer mainly consisting of chromates in compliance with the UNI ISO 4520 Standards. These construction characteristics mean that all the Vmax series of apparatus and their accessories comply to IEC/TS 62271-304 Standards environmental class 2.
24

Graph for determining the Ka correction factor according to IEC 62271-1 standards. Example Installation altitude: 2000 m Rated service voltage of 12 kV Industrial frequency withstand voltage: 28 kV rms Impulse withstand voltage: 75 kVp Ka factor, which can be taken from the graph = 1.13. Considering the above parameters, the apparatus must withstand (on test at zero altitude, i.e. at sea level): power frequency withstand voltage: 28 x 1.13 = 31.6 kVrms impulse withstand voltage: 75 x 1.13 = 84.7 kVp. From the above, it can be deduced that for installations at an altitude of 2000 m above sea level, with 12 kV service voltage, the apparatus must be provided with 17.5 kV rated voltage, characterized by insulation levels at industrial frequency of 38 kVrms with 95 kVp impulse withstand voltage.
H = altitude in meters; m = value referred to power frequency and to the lightning impulse withstand and between phase voltages.
ka 1,50

m=1 1,40

Ka = e m (H 1000)/8150

1,30

1,20

1,10

1,00 1000 1500 2000 2500 3000 3500 4000 H

From the above, it can be deduced that for installations at an altitude of 2000 m above sea level, with 12 kV service voltage, the apparatus must be provided with 17.5 kV rated voltage, characterized by insulation levels at industrial frequency of 38 kVrms with 95 kVp impulse withstand voltage.

25

3. Specific product characteristics

Anti-pumping device

Environmental protection program


The Vmax circuit-breakers are manufactured in accordance with the ISO 14000 Standards (Guidelines for environmental management). The production processes are carried out in compliance with the Standards for environmental protection in terms of reduction in energy consumption as well as in raw materials and production of waste materials. All this is thanks to the medium voltage apparatus manufacturing facility environmental management system. Assessment of the environmental impact of the life cycle of the product, obtained by minimizing energy consumption and overall raw materials of the product, became a concrete matter during the design stage by means of targeted selection of the materials, processes and packing. This is to allow maximum recycling at the end of the useful life cycle of the apparatus.

The EL operating mechanism of Vmax circuit-breakers (in all versions) is fitted with a mechanical anti-pumping device which prevents re-closing due to either electrical or mechanical commands. Should both the closing command and any one of the opening commands (local or remote) be active at the same time, there would be a continuous succession of opening and closing operations. The anti-pumping device avoids this situation, ensuring that each closing operation is only followed by a single opening operation and that there is no closing operation after this. To obtain a further closing operation, the closing command must be released and then re-launched. Furthermore, the anti-pumping device only allows circuitbreaker closure if the following conditions are present at the same time: operating mechanism springs fully charged opening pushbutton and/or opening release (-MO1/-MO2) not enabled circuit-breaker open.

26

Spare parts (*)


Shunt opening release Supplementary shunt opening release Undervoltage release Time delay device for undervoltage release Undervoltage release override Shunt closing release Spring charging geared motor with electrical signaling of springs charged Contact signaling closing springs charged/discharged Circuit-breaker auxiliary contacts Locking electromagnet on the operating mechanism Position contact of the withdrawable truck Contacts signaling connected/isolated Key lock in open position Isolation interlock with the door Protection for opening pushbutton Protection for closing pushbutton Locking electromagnet on the withdrawable truck Set of six isolating contacts

Ordering
For availability and to order spare parts, please contact our Service department, specifying the circuit-breaker serial number.

(*) Replacement with spare parts as well as maintenance operations must be carried-out by ABB personnel or by skilled and specially trained personnel with in-depth knowledge of the apparatus.

27

4. Overall dimensions

Vmax - Fixed circuit-breaker IEC: 12...17.5 kV - 630...1250 A - 16...31.5 kA ANSI: 15 kV - 1200 A - 25...31.5 kA
1VCD003279_V3198

32 1,26

416 16,37 291 11,46

421 16,57 364 14,33

35 1,38

133 5,24

133 5,24

534 21,02

10 0,39

496 19,53

16 0,61

240 1 9,45 0,04 221 1 8,7 0,04

30 1,16

29 1,12 188 7,39 49 1,93 48 1,89 320 12,6

104,5 4,11

176 6,93

57 2,22

29 1,12 48 1,89

336 13,23

28 1,1 75 2,95

8 0,31

8 0,31

2-10

40 1,56

1-8-10

11,9 0,47

22 0,87 17 0,67 39 1,54 10 0,39

12 11 266 10,47

4x

8,5 [0,33] 80 3,15 17 0,67 17 0,67

Dimensions are in mm and in inches.

28

Vmax/F - Fixed circuit-breakers for UniGear 500R IEC: 12...17.5 kV - 630 A - 25...31.5 kA
1VCD003516_E0771

Dimensions are in mm. 29

4. Overall dimensions

Vmax/F - Fixed circuit-breakers for UniGear 500R IEC: 12...17.5 kV - 2000 A - 25...31.5 kA
1VCD003558_V2315

79,5 59 51,5 61

150 133

150 133

108

30

18XM10 17

240 1

200

28

94

12 543

R47 29,5 40 58,5 80

155,5 189 48 320

20 49

105

173

218

336

28 81

66

416

SEZIONE A-A

SEC. A-A
426,5

75 16

266

26,5

86,5

243
47

17

LV BT

11,5

133

133

9,5

16

562

Dimensions are in mm. 30

112,7

135,5

218

240

Vmax/W - Withdrawable circuit-breakers for PowerCube IEC: 12...17.5 kV - 630...1250 A - 16...31.5 kA ANSI: 15 kV - 1200 A - 25...31.5 kA
1VCD003280_V2856

492 19,37 234 9,19 42,5 1,67 15,5 0,61 123,5 4,86

1-8-10 2-10 31 1,22 4 16 0,61 662,2 26,07

10 0,39

79 3,11

35 1,38

629,5 24,78

619,5 24,39

625,5 24,63

39 1,53

52 2,05

56,5 2,22

228,5 9

19 0,75

21,5 0,85

19,5 0,77

28 1,09 28 1,09 = 503 19,8 531 20,91

49 1,93

320 12,6 370 14,58 416 16,38 438 17,23 662 26,05

76 2,99

28 1,09

25 0,98

150 5,91

154 6,06

456 17,95

260 10,24 501 19,72

68 2,68 124 4,88

Dimensions are in mm and in inches.

150 5,91

598 23,54

36 1,42

205 8,07

31

4. Overall dimensions

Vmax/L - Withdrawable circuit-breakers for UniGear 550 switchgear IEC: 12...17.5 kV - 630...1250 A - 16...31.5 kA
1VCD003334_V2296

Dimensions are in mm only.

32

5. Electric circuit diagram

Circuit-diagram of Vmax circuit-breaker in withdrawable version for PowerCube and UniGear 550, with EL operating mechanism. For other circuit-breakers, please consult us. The diagram indicates the following conditions: circuit-breaker off and connected circuits de-energized closing springs discharged

Graphical symbols for electrical diagrams (617 IEC Standards)


Thermal effect Frame Capacitor (general symbol) Passing make contact closing momentarily when its operating device is released Position switch (limit switch) make contact

Electromagnetic effect

Conductors in screened cable (two conductors shown)

Motor (general symbol)

Delay

Connection of conductors

Rectifier in full wave connection (bridge)

Position switch (limit switch) brake contact

Pushbutton control

Terminal or clamp

Make contact

Circuit-breaker with automatic release

Key control

Socket and plug (female and male)

Break contact

Operating device (general symbol)

Earth (general symbol)

Resistor (general symbol)

Change-over break before make contact

Lamp (general symbol)

33

5. Electric circuit diagram

34

35

5. Electric circuit diagram

36

37

5. Electric circuit diagram

Caption = Reference number of diagram figure. * -QB -BM = See note indicated by the letter. = Circuit-breaker accessories. = Device for the supervision of shunt opening release and shunt closing release coil continuity (see note D). = Motor for the closing springs charging (see note C).

Description of figures Fig. 1 Fig. 2 Fig. 3 = Spring charging-motor circuit (see note C). = Shunt closing release (anti-pumping is achieved mechanically). = Locking magnet. If de-energized it prevents the circuit-breaker closing mechanically (this fig. must be given when -RL1 is requested and fig. 31 or 32 is selected). (It is possible to limit its consumption by connecting a delay pushbutton in series to enable the operation). = Locking magnet. If de-energized it prevents the circuit-breaker closing mechanically (this fig. must be given when -RL1 is requested and fig. 33 or 34 is selected). (It is possible to limit its consumption by connecting a delay pushbutton in series to enable the operation). = Instantaneous undervoltage release (see note B). = First shunt opening release circuit with possibility of permanent supervision of coil continuity (see note D). = Locking magnet. If de-energized it prevents the circuit-breaker racking-in and rackingout mechanically (it is possible to limit its consumption by connecting a delay pushbutton in series to enable the operation). = Second shunt opening release circuit with possibility of permanent supervision of coil continuity (see note D). = Opening solenoid for release outside the circuitbreaker. = Contact signaling closing spring charged and discharged (see note H). = Contacts signaling circuit-breaker in the connected and isolated positions located on the circuit-breaker (obligatory when fig. 31 or 32 is requested). = Contacts signaling circuit-breaker in the connected and isolated positions located on the circuit-breaker (optional when fig. 33 or 34 is requested). = Contact signaling undervoltage release deactivated.

-MS

-BB1..2-3 = Circuit-breaker auxiliary contacts. -BS1 -BS2 -BD -BT1 -BT2 -BT3 -SC -SO -XB -XB2..9 -XB1 -RL1 = Limit switches of the spring-charging motor. = Limit switches signaling closing spring charged or discharged. = Position contact of the enclosure door. = Contacts signaling circuit-breaker in the connected position (see note E). = Contacts signaling circuit-breaker in the removed position (see note E). = Circuit-breaker position contact. It is open during the travel of the breaker (see note H). = Pushbutton or contact for the circuit-breaker closing. = Pushbutton or contact for the circuit-breaker opening. = Connector for the circuit-breaker circuits. = Connectors of accessories. = Switchboard terminal board (mounted outside the circuit-breaker). = Locking magnet. If de-energized it prevents circuit-breaker closing mechanically (it is possible to limit its consumption by connecting a delay pushbutton in series to enable the operation). = Locking magnet. If de-energized it prevents the circuit-breaker racking-in and rackingout mechanically (it is possible to limit its consumption by connecting a delay pushbutton in series to enable the operation). = Shunt closing release (see note D). = First shunt opening release (see note D). = Second shunt opening release (see note D) = Opening solenoid for release outside the circuitbreaker. = Undervoltage release (see note B).

Fig. 4

Fig. 5 Fig. 7

Fig. 8

Fig. 9

Fig. 10 Fig. 26

Fig. 31-32-33-34 =Circuit-breaker available auxiliary contacts. Fig. 51

-RL2

Fig. 52

-MC -MO1 -MO2 -MO3 -MU

Fig. 60

38

Incompatibility The combinations of circuits given in the figures below are not possible on the same circuit-breaker: 3-4 3-33-34 33-34-51 31-31-33-34 51-52 4-31-32 31-32-52

Notes A) The circuit-breaker is delivered complete with the accessories listed in the ABB order acknowledgement only. To draw up the order, consult this catalogue. B) The undervoltage release is available in the version suitable for circuit-breaker supply side feeding or for feeding from an independent source. The circuit-breaker can only be closed if the undervoltage release is energized (lock on closing is achieved mechanically). When there is the same voltage supply for the closing and undervoltage releases and automatic closing of the circuit-breaker is required when the auxiliary voltage supply returns, a delay of 50 ms must be provided between energization of the closing release and the instant of consent to the undervoltage release. C) The circuit for supervision of the shunt opening release coil continuity must only be used for this function. D) The circuit for supervision of the shunt opening release coil continuity must only be used for this function. E) Contacts signaling circuit-breaker in the connected and isolated positions (-BT1 and -BT2) given in fig. 51 or 52 are located on the circuit-breaker (moving part) and are available on request. F) Fig. 3 is given when fig. 31 or 32 is required, fig. 4 when fig. 33 or 34 is required (in this case -BT3 is obligatory). G) When fig. 10 is required, contact -BB3 31-32 given in fig. 32-34 is not available. When fig. 30 is requested contact -BB3 53-54 given in fig. 32-34 is not available. When fig. 9 is required, contact -BB1 43-44 given in fig. 31-32-34-34 is not available. H) Both limit switch contacts must be operating at the same supply voltage

39

Notes

40

41

Contact us

Your sales contact: www.abb.com/contacts More product information: www.abb.com/productguide


The data and illustrations are not binding. We reserve the right to make changes without notice in the course of technical development of the product. Copyright 2011 ABB. All rights reserved.

1VCP000408 - Rev. -, en - Technical catalogue - 2011.02 (Vmax) (gs)