You are on page 1of 124

Comprehensive Catalogue

2010

Air Circuit Breakers


Super Solution

ACB
LS Industrial Systems Made It!

Susol Air Circuit Breakers

Super Solution

Overview External configuration Internal configuration Ordering Ratings Trip relays Accessories Electrical diagram Dimensions Technical information

4 14 16 18 22 26 52 80 82 104 105 106 108 113 114 117

Contents

UInsulation voltage UTemperature derating UOperating conditions UProtective coordination

Standards & Approval Time chart Ordering sheet

Premium Susol ACB meets your demands for high breaking capacity, fully line-up, and optimized panel size. Various accessories and connection methods realize user-friendly handling. Susol ACB provides you with total solutions with an advanced trip relay for measurement, diagnosis, analysis, and communication as well as protective functions for absolute protective coordination and electric power monitoring system.

LS Industrial System

Super Solution series

Susol series circuit breakers are suitable for


Protection of power distribution Protection of motor & its control device Controlling and disconnecting circuits

Optimum technical support for


(Cascading, Discrimination, Type 2 coordination) Selecting economical protection system Quarantee safety of the installation Reducing the stress on components and damage Guarantee service continuity

Susol Manual Motor Starters

Susol Air Circuit Breakers

Susol Molded Circuit Breakers

Susol Magnetic Contactors & Overload Relays

Full line-up & Compact


Up to 6300A, Susol ACB provides fully lined-up 3 frame. For each frame, there is just one size, which is smaller and more compact. It makes it possible for you to design the optimized volume panel.

H = 430mm

W = 334mm

W = 412mm

85kA
AH-06~20D
06 08 10 13 16 20 630AF 800AF 1000AF 1250AF 1600AF 2000AF Icu=Ics=85kA/500Vac W=334(3p), 419(4p)mm

100kA
AH-06~40E
06 08 10 13 16 630AF 800AF 1000AF 1250AF 1600AF 20 25 32 40 2000AF 2500AF 3200AF 4000AF Icu=Ics=100kA/500Vac W=412(3p), 527(4p)mm

37

5m

W = 785mm

150kA
T The highest breaking capacity: 150kA (6300AF at 500Vac) 3 3 ampere frame sizes: 2000/4000/6300AF N N phase current conducting capacity: 100%

AH-40~63G
40 50 63 4000AF 5000AF 6300AF

Icu=Ics=150kA/500Vac W=785(3p), 1015(4p)mm

Trip Relay
(OCR)

Trip relays are classified according to function.


Trip relays are classified according to their usages and functions to maximize customers satisfaction. Classified trip relays and easy installation.
Protection: overload, short current, ground fault, earth leakage, under voltage, over voltage, under frequency, over frequency, reverse power, unbalance, etc Measurement: voltage, ampere, power, energy, frequency, power factor, Harmonics, etc. Event & fault recording: Max. 256 events & faults Communication: Modbus/RS-485, Profibus-DP

Susol ACB Trip Relay functioning world-best protection can be interlocked with mechanism. It makes the breaking capacity of ACB improved and ACBs life enhanced, and provides advanced functions - measurement, diagnosis, analysis, and communication.

Susol ACB Trip relay


N type A type P/S type

L/S/I/G/Thermal Self Power RTC Timer mounted Fault information (LED)

L/S/I/G/Thermal ZSI Remote Reset Modbus/RS-485 Profibus-DP Self Power AC/DC 100~250V DC 24~60V RTC Timer mounted Fault Recording (10EA)

L/S/ I/G/Thermal(Continuous) UV/OV/OF/UF/rP/Vun/Iun Measurement: V/A/W/Wh/F/PF Harmonics (63th), Waveform (S Type) ZSI Remote Reset Modbus/RS-485 Profibus-DP AC/DC 100~250V DC 24~60V RTC Timer mounted Event Recording (256EA) Fault Recording (256EA) Fault Wave (S Type)

Trip relays series


N type

N Type (Normal)

Self-power + Current protection

P type

P Type (Power Meter) A type + Power Meter +


Voltage / Frequency / Unbalance protection

A type

A Type (Ammeter) Current Meter + Current protection +


DO control + Communication

S type

S Type (Supreme) P type + Harmonics analysis (63 th) +


Fault wave recording

Accessories

ACB
Trip Relay (OCR) Motor (M) Closing Coil (CC) Shunt Coil (SHT) Under Voltage Trip Device (UVT) Door Interlock (DI) MOC (Mechanically Operated Cell Switch) Mechanical Interlock (MI) Auxiliary Switch (AX) Key Lock (K1), Double Key Lock (K3) Counter (C) On/Off Button Lock (B) Miss Insertion Preventing Device (MIP) Automatically Discharge Mechanism (ADM) Manual Reset Button (MRB)

Cradle
Safety Shutter (ST) Manual Connector Zero Arc Space (ZAS) Insulation Barrier (IB) Cell Switch (CEL) Door Interlock (DI) MOC (Mechanical Operated Cell switch) Mechanical Interlock (MI) Body Supporter (BSP) Shorting "b" Contact (SBC) Safety Control Cover (SC) Automatically Discharge Mechanism.(ADM) Racking Interlock (RI) Safety Shutter Lock (STL)

Other
Condenser Trip Device (CTD) Dust Cover (DC) OCR Tester (OT) ATS Controller (ATS) Lifting Hook (LH) Dummy ACB UVT Time Delay Controller (UDC) Profibus-DP Communication module Remote I/O Temperature Alarm Miss Insertion Prevent Device (MIP) Door Frame (DF)

Connection and Installation

Diverisified terminal connection methods of the ACB main circuit for users.

Multiple connections
Various installation methods
Standard connection

Horizontal type

Vertical type

Front type

Mixed connection

Horizontal / Vertical type

Vertical / Horizontal type

Horizontal / Front type

Vertical / Front type

Front / Horizontal type

Front / Vertical type

F Front connection type is available to be connected regardless of the depth of main circuit terminal, and it is suited for the panel required for limited installation space. T The vertical and horizontal type terminal are module types which can easily compose the vertical and horizontal terminals by rotating 90 Vertical and horizontal terninals are different each other for over 3200AF ACBs
Please refer to the rating lists (Page 22~25) because the installation method is various according to the rated current.

External configuration
Fixed type ACB

Terms
Trip relay

Counter ON button OFF button Series name Charge handle Rated name plate Charge/Discharge indicator ON/OFF indicator Corporation logo Arc cover Terminal cover Cradle Draw-out handle Position indicator Handle storage space Pad lock button Arc chute Control cover Fixed type bracket

Draw-out ACB (Cradle)

14

Cradle (Internal)

Cradle (Rear)

Terms
Terminal cover of control circuit Cradle finger (Line side) Cradle finger (Load side) Draw-out handle Position indicator Handle storage space Pad lock button Connecting conductor (Line side) Connecting conductor (Load side)

Main nameplate
[Acronym explanation] [Secondary nameplate] Explanation of terminologies Motor charge Control power and Closing coil terminal No. Shunt tripping coil Auxiliary switches: Contact specification and terminal No. Under voltage trip: UVT terminal No. OCR control source: Trip relay control power Alarm switch: Alarm and terminal No. Digital trip relay: Switching diagram Z.S.I: Input/Output terminal No. Reset: LED/LCD reset Communication: Communication and terminal No. Voltage module: Phase voltage and symbol Earth/Leakage: Ground fault / Earth leakage input terminal No.

Ui: Rated insulation voltage Uimp: Impulse withstand voltage Ue: Rated operational voltage (AC base) Icu: Ultimate breaking capacity Ics: Service breaking capacity Icw: Short time withstand current MFG. Date: Manufacturing date

15

Internal configuration

Terms

Arc chute Aux. switch control terminal Control power supply terminal

Trip relay control terminal Carrying grip Trip coil or UVT coil Mechanism Main body Counter Trip coil Closing coil Motor Assy Aux. switch

ON button OFF button MTD base Trip relay Front cover

16

Terms

Control circuit terminal block Control terminal Auxiliary switches Closing, Trip, UVT coil Trip relay Front cover Mechanism Charge handle Trip spring Closing spring

Draw-in/out device Arc extinguishing part Moving contact Fixed contact Conductor on line side

Cradle finger Cradle Connecting conductor Power supply CT Conductor on load side

17

Ordering
ACB & Accessories
AH

10
Ampere frame 06 -

D
Frame sizes & phase array 3P/4P

10

Type AH AS AN

No. of pole 00 02 3 3P(D) 04 06 04 06 08 10 4 4P(D, W) 13 16 20

Rated current (CT Spec.) Without OCR & CT 200A 400A 630A 400A 630A 800A 1000A 1250A 1600A 2000A N P M H V J A

Connections Draw-out type Manual connection Automatic connection Fixed type Horizontal type Vertical type Mixed type Line: Horizontal Load: Vertical Mixed type Line: Vertical Load: Horizontal Front type

630AF

Standard type RST(N)

AH

AN

08 10 13 16

800AF 4P 1000AF 1250AF 1600AF 2000AF W Reverse phase type NRST

AS

20

3P/4P E 20 AH AS 4P 25 32 40 2500AF 3200AF 4000AF X Reverse phase type NRST 4 4P(E, X) 2000AF Standard type RST(N) 3 3P(E)

06 08 10 13 16 20 25 32 40

630A 800A 1000A 1250A 1600A 2000A 2500A 3200A 4000A

3P/4P 40 AS 50 5000AF Y 4000AF F Standard type RST(N) 4P Reverse phase type NRST 4 4P(F, Y) 50 5000A 3 3P(F) 40 4000A

40 AH AS 50 63

4000AF 5000AF 6300AF

3P/4P G Standard type RST(N) 4P Reverse Z phase type NRST 4 4P(G, Z) 3 3P(G)

40 50 63

4000A 5000A 6300A

18

M1

D1

D1

AX

NG0

U1

AL

Motor rated voltage MA M1 M2 M3 M4 M5 M6 M7 M8 Without Motor AC/DC 100V~130V AC/DC 200V~250V DC 125V DC 24V~30V DC 48V~60V AC 380V~415V AC 440V~480V AC 48V

Shunt coil rated voltage D0 D1 D2 D3 D4 D5 D6 D7 Without Shunt coil AC/DC 100V~130V AC/DC 200V~250V DC 125V DC 24V~30V DC 48V~60V AC 380V~480V AC 48V

Trip relay Refer to 26page

Closing coil rated voltage D0 D1 D2 D3 D4 D5 D6 D7 Without Closing coil AC/DC 100V~130V AC/DC 200V~250V DC 125V DC 24V~30V DC 48V~60V AC 380V~480V AC 48V
3)

Aux.contact & charging types AX AC BX BC HX HC CC JC Standard OFF-Charge 3a3b Standard ON-Charge 3a3b Standard OFF-Charge 5a5b Standard ON-Charge 5a5b High capacity OFF-Charge 5a5b High capacity ON-Charge 5a5b Standard ON-Charge 6a6b High capacity ON-Charge 6a6b

UVT coil rated voltage U0 U1 U2 U3 U4 U5 U6 U7 Without UVT coil AC/DC 100V~130V AC/DC 200V~250V DC 125V DC 24V~30V DC 48V~60V AC 380V~480V AC 48V

* UVT Delay module is available over AC / DC 48V

Option AL A1 A2 A3 A4 A5 A6 A7 A8 A9 C S 2) B M

Type name AL1+MRB AL1+MRB+RES (AC110~130V) AL1+AL2+MRB AL1+MRB+RES (DC110~125V) AL1+MRB+RES (AC200~250V)

Option D DI or MOC K1 K2 K3 RCS TM

Type name Door Interlock or MOC (Mechanism operated cell switch) Key lock Key Interlock set Key lock double Ready to close switch Temperature monitoring AC/DC 100~130V AC/DC 200~250V DC 125V Double shunt coil DC 24~30V **At using UVT, not applied DC 48~60V AC 380~480V AC 48V

*AC private use

*DC private use *AC private use

AL1+MRB+Auto reset AL1+AL2+MRB+Auto reset AL1+MRB+RES (DC110~125V)+Auto reset *DC private use AL1+MRB+RES (AC200~250V)+Auto reset *AC private use AL1+MRB+RES (AC110~130V)+Auto reset *AC private use C Counter CS2 Charge switch communication B On/Off Button lock MI Mechanical interlock **AN typenot applied

K K2 K3 R 2) T 3) H1 H2 H3 H4 H5 H6 H7

1)

SHT2

Note) 1. UVT and SHT2 are alternative. 2. CS2 and RCS are alternative. 3. TM and CC/JC(6a6b) are alternative. 4. Other accessories should be ordered seperately.

19

Ordering
Cradle
AL

N16D

LS ACB cradle

Rated current & frame N16D S20D S32E S40E S50F S50G S63G H16D H20D H32E H40E H50G H63G AN-06~16D AS-20D

No. of pole 3 4 3P 4P H V

Connections Horizontal type (20D inapplicable) Vertical type Mixed type

Safety shutter E F Without safety shutter With safety shutter

AS-20~32E AS-40E AS-40~50F AS-40~50G AS-63G AH-06~16D AH-20D AH-20~32E AH-40E AH-40~50G AH-63G P J A Terminal connections Manual connection Automatic Connection N Line: Horizontal Load: Vertical (20D inapplicable) Mixed type Line: Vertical Load: Horizontal (20D inapplicable) Front type (20D, 40E, 50FG, 63G inapplicable)

Arc cover N S Without Arc cover With Arc cover

20

Trip relay
N G 0

Trip relay type 000 Without trip relay N N Normal G

Communication & protection

Control voltage & frequency

G Without comm. + L/S/I/G 0 5


* L/S/I/G configuration as standard -with LED indicators -without output contacts * Ground fault system by vector sum

0 Self-Power, 60Hz Self-Power, 50Hz

A A Ammeter G Z E C K X Without comm.

G 0 1 2 5 6 7 Without comm. + Earth leakage Without comm. + Earth leakage Comm. Comm. + Earth leakage Comm. + Earth leakage

0 Self-Power, 60Hz AC/DC 100V~250V, 60Hz DC 24V~60V, 60Hz Self-Power, 50Hz AC/DC 100V~250V, 50Hz DC 24V~60V, 50Hz

* L/S/I/G configuration as standard * Ground fault system by vector sum(G,C) * Earth leakage system - Z,K: External CT - LS ZCT applied(fault current 0.5~30A, 1600AF) - E,X: External CT - Private ZCT applied(faullt current >30A) * Comm. and output contacts DO NOT work under self-power condition.

P P Power meter C K X A Comm. Comm. + Earth leakage Comm. + Earth leakage Comm. + Pre-trip alarm

C 1 2 6 7

1 AC/DC 100V~250V, 60Hz DC 24V~60V, 60Hz AC/DC 100V~250V, 50Hz DC 24V~60V, 50Hz

* L/S/I/G configuration as standard * Ground fault system by vector sum * Earth leakage system - K: External CT - LS ZCT applied(fault current 0.5~30A, 1600AF) - X: External CT - Private ZCT applied(faullt current >30A) * Applicable to generator protection purpose

S S Supreme meter C K X A Comm. Comm. + Earth leakage Comm. + Earth leakage Comm. + Pre-trip alarm

C 1 2 6 7

1 AC/DC 100V~250V, 60Hz DC 24V~60V, 60Hz AC/DC 100V~250V, 50Hz DC 24V~60V, 50Hz

* L/S/I/G configuration as standard * Ground fault system by vector sum * Earth leakage system - K: External CT - LS ZCT applied(fault current 0.5~30A, 1600AF) - X: External CT - Private ZCT applied(faullt current >30A) * Applicable to generator protection purpose

Note) 1. L/S/I/G configuration as standard 2. Ground fault, earth leakage and pre-trip alarm functions are alternative. 3. The functions like Metering, Communication, ZSI, Remote reset and Digital output are NOT available only under Self-power condition. 4. Voltage module should be required for P and S types(supplied seperately)

21

Ratings

Type Ampere frame Rated current(A) Setting current (A) * Rated current of neutral pole (A) (AF) (In max) at 40

Control trip relay ( ... In max)

Rated insulation voltage(V) (Ui) Rated operating voltage(V) (Ue) Rated impulse withstand voltage (kV)(Uimp) Frequency(Hz) Number of poles (P) Rated breaking capacity (kA sym) 220V/230V/380V/415V IEC 60947-2 AC 50/60Hz (Icu) 460V/480V/500V KS C 4620 550V/600V/690V Rated service breaking capacity (kA) (Ics) ... %Icu Rated making capacity (kA peak) 220V/230V/380V/415V IEC 60947-2 AC 50/60Hz (Icm) 460V/480V/500V KS C 4620 550V/600V/690V Rated short-time 1sec withstand current (kA) (Icw) 2 sec 3 sec Operating time (ms) Maximum total breaking time Maximum closing time Life cycle (time) Mechanical Without maintenance With maintenance Electrical Without maintenance With maintenance Connections ** Draw-out / Fixed Horizontal connection Vertical connection Front connection Mixed connection Weight (kg) Draw-out type Main body Motor charging type (3P/4P) (With cradle) Manual charging type Cradle only Fixed type Motor charging type Manual charging type External dimensions (mm) Draw-out 3P (HWD) type 4P H Fixed type 3P D W 4P Trip relay Certificate & Approval Marine clasiflcation
* Refer to trip relay specification. ** : Standard, : Option

AH-06D AH-08D AH-10D AH-13D AH-16D AH-20D 630 800 1000 1250 1600 2000 200 400 400 630 1000 1250 1600 2000 630 800 (0.4 ~ 1.0) In max 400 400 630 1000 1250 1600 2000 630 800 1000 690 12 50/60 3/4 85 85 65 100% 187 187 143 65 60 50 40 80 20,000 30,000 5,000 10,000 63/74 70/85 61/72 68/83 29/32 33/40 34/44 38/47 32/42 36/45 430334375 430419375 300300295 300385295 N, A, P, S type KS / KEMA / KERI / GOST LR, ABS, DNV, KR, BV, GL, RINA, NK

22

AH-06E 630 630

AH-08E 800 800

AH-10E 1000 1000

AH-13E 1250 1250

AH-16E 1600 1600

AH-20E 2000 2000

AH-25E 2500 2500

AH-32E 3200 3200

AH-40E 4000 4000

AH-40G 4000 4000

AH-50G 5000 5000 (0.4 ~ 1.0) In max

AH-63G 6300 6300

(0.4 ~ 1.0) In max 630 800 1000 1250 1600 1,000 690 12 50/60 3/4 100 100 85 100% 220 220 187 85 75 65 40 80 15,000 20,000 5,000 10,000 87/103 85/101 44/55 44/55 42/53 430412375 430527375 300378295 300493295 N, A, P, S type KS / KEMA / KERI / GOST LR, ABS, DNV, KR, BV, GL, RINA, NK 107/139 102/145 65/85 61/81 60/80 2000 2500 3200 4000 4000

5000

6300

1,000 690 12 50/60 3/4 150 150 100 100% 330 330 220 100 100 100 40 80 10,000 15,000 2,000 5,000 181/223 186/230 179/221 184/228 97/117 102/124 98/123 103/130 96/121 101/128 460785375 4601015375 300751295 300981295 N, A, P, S type KS / KEMA / KERI / GOST LR, ABS, DNV, KR, BV, GL, RINA, NK

23

Ratings

Type Ampere frame Rated current(A) Setting current (A) * Rated current of neutral pole (A) (AF) (In max) at 40

Control trip relay ( ... In max)

Rated insulation voltage(V) (Ui) Rated operating voltage(V) (Ue) Rated impulse withstand voltage (kV)(Uimp) Frequency (Hz) Number of poles (P) Rated breaking capacity (kA sym) 220V/230V/380V/415V IEC 60947-2 AC 50/60Hz (Icu) 460V/480V/500V KS C 4620 550V/600V/690V Rated service breaking capacity (kA) (Ics) ... %Icu Rated making capacity (kA peak) 220V/230V/380V/415V IEC 60947-2 AC 50/60Hz (Icm) 460V/480V/500V KS C 4620 550V/600V/690V Rated short-time 1 sec withstand current (kA) (Icw) 2 sec 3 sec Operating time (ms) Maximum total breaking time Maximum closing time Life cycle (time) Mechanical Without maintenance With maintenance Electrical Without maintenance With maintenance Connections ** Draw-out / Fixed Horizontal connection Vertical connection Front connection Mixed connection Weight (kg) Draw-out type Main body Motor charging type (3P/4P) (With cradle) Manual charging type Cradle only Fixed type Motor charging type Manual charging type External dimensions (mm) Draw-out 3P (HWD) type 4P H Fixed type 3P D W 4P Trip relay Certificate & Approval Marine clasiflcation
* Refer to trip relay specification. ** : Standard, : Option

AN-06D AN-08D AN-10D AN-13D AN-16D AS-20D 630 800 1000 1250 1600 2000 200 400 400 630 1000 1250 1600 2000 630 800 (0.4 ~ 1.0) In max 400 400 630 1000 1250 1600 2000 630 800 1000 690 12 50/60 3/4 65 70 65 70 50 65 100% 100% 143 154 143 154 105 143 50 65 42 55 36 50 40 80 20,000 30,000 5,000 10,000 63/74 70/85 61/72 68/83 29/32 33/40 34/44 38/47 32/42 36/45 430334375 430419375 300300295 300385295 N, A, P type KS / KEMA / KERI / GOST LR, ABS, DNV, KR, BV, GL, RINA, NK

24

AS-20E 2000 630, 800 1000, 1250 1600, 2000 630, 800 1000, 1250 1600, 2000

AS-25E 2500 2500

AS-32E 3200 3200

AS-40E 4000 4000

AS-50F 4000 4000 5000 5000

AS-40G 4000 4000

AS-50G 5000 5000

AS-63G 6300 6300

(0.4 ~ 1.0) In max 2500 1,000 690 12 50/60 3/4 85 85 85 100% 187 187 187 85 75 65 40 80 15,000 20,000 5,000 10,000 87/103 104/147 85/101 102/145 44/50 58/70 44/55 63/100 42/53 61/98 430412375 430527375 300378295 300493295 N, A, P type KS / KEMA / KERI / GOST LR, ABS, DNV, KR, BV, GL, RINA, NK 3200 4000

(0.4 ~ 1.0) In max 4000 5000 4000

(0.4 ~ 1.0) In max 5000 6300

1000 690 12 50/60 3/4 100 100 85 100% 220 220 187 85 75 65 40 80 10,000 15,000 2,000 5,000 107/139 102/145 65/85 61/81 60/80 460629375 460799375 300597295 300767295 N, A, P type KS / KEMA / KERI / GOST LR, ABS, DNV, KR, BV, GL, RINA, NK

1,000 690 12 50/60 3/4 120 120 100 100% 264 264 220 100 90 85 40 80 10,000 15,000 2,000 5,000 181/223 186/230 179/221 184/228 97/117 102/124 98/123 103/130 96/121 101/128 460785375 4601015375 300751295 300981295 N, A, P type KS / KEMA / KERI / GOST LR, ABS, DNV, KR, BV, GL, RINA, NK

25

Trip relay(OCR)
The trip relay of Susol ACB provides the additional protection functions for voltage, frequency, unbalance, and others in addition to main protection functions for over current, short-circuit, ground fault. It supports the advanced measurement functions for voltage, current, power, electric energy, harmonics, communication function, and others. Analog trip function interlocked with mechanism enhanced a durability of devices as well as the breaking capacity of ACB. Zone selective interlocking function makes the protective coordination more simple and thermal memory can be applied to various loads.

Contents
Trip relay types N type: Normal type A type: Ammeter type P type: Power meter type S type: Supreme meter type Operation characteristic Measurement function Man machine interface Protection element setting Measurement element display Characteristic curves ZSI - Zone Selective Interlocking Remote reset and digital I/O Communication Event & fault recording System information System block diagram 27 28 30 32 34 36 38 39 40 41 42 45 46 47 48 48 49

Trip relays
Trip relay types
Classification N type A type P type S type

Externals

Current protection

L / S / I / G / Thermal

L / S / I / G / Thermal ZSI(Protective coordination) Earth leakage (Option)

Other protection

Current (R / S / T / N)

Measurement function

L / S / I / G / Thermal(Continuous) ZSI(Protective coordination) Earth leakage(Option) Over/Under current Over/Under frequency Unbalance(Voltage/Current) Reverse power 3 Phase Voltage/Current RMS/Vector Power(P, Q, S), PF(3-Phase) Energy(Positive/Negative) Frequency, Demand

P type P type

Fine adjustment

Pre Trip Alarm

Digital Output IDMTL setting Communication

Self Power -Power source works over 20% of load current.

3DO (Fixed) L, S/I, G Alarm Modbus/RS-485 Profibus-DP Self Power - Power source works over 20% of load current. - External power source are required for comm. AC/DC 100~250V DC 24~60V Available N type

Fine adjustment for long/short time delay/instantaneous/ ground Overload protection relays : DO (Alarm) (Ground fault is not available when using Pre trip alarm) 3DO (Programmable) Trip, Alarm, General Compliance with IEC60255-3 SIT, VIT, EIT, DT Modbus / RS-485 Profibus-DP AC/DC 100~250V DC 24~60V

3 Phase Voltage/Current RMS/Vector Power(P, Q, S), PF(3-Phase) Energy(Positive/Negative) Frequency, Demand Voltage/Current harmonics (1st~63th) 3 Phase Waveforms THD, TDD, K-Factor P type P type

P type P type Modbus / RS-485 Profibus-DP AC/DC 100~250V DC 24~60V

Power supply

Basic protection function(L / S / I / G) is still under normal operation without control power. Available N type Available N type

RTC timer LED for trip info.

Available Long time delay Short time delay/Instantaneous Ground fault -

Fault recording

10 records (Fault/Current/Date and Time) Reset, Menu Up/Down, Left/Right, Enter

Event recording Operating Reset button button

256 records Last fault wave recording (3 Phase) 256 records(Content, Status, Date) P type A type A type

256 records (Fault/Current/Date and Time)

27

Trip relays
N type: Normal type
Optimized protection function OCR, OCGR function according IEC60947-2 Overload protection -Long-time delay -Thermal Short-circuit protection -Short-time delay / Instantaneous -I2t On/Off optional (for short-time delay) Ground fault protection -I2t On/Off optional Self-Power

LED: Indication of trip info. and overload state


Isd Ii

Alarm SP

Ir

Ig

Ig: LED indicating ground-fault Isd/Ii: LED indicating short-time or instantaneous tripping Ir: LED indicating long-time delay SP: Self-protection and battery test LED Alarm: LED indicating an overload (Turn on above 90%, Blink above 105%)

Reset Key: Fault reset or battery check Iu, Ir: Long-time current setting, tr: Long-time tripping delay setting Isd: Short-time current setting, tsd: Short-time tripping delay setting Ii: Instantaneous current setting

Ig: Ground fault current setting, tg: Ground fault tripping delay setting Test terminal: OCR test terminal (Connected with OCR tester)

28

Protection
t Ir

Long time Current setting (A)


tr lsd tsd Ii I

Iu = In... Ir = Iu... tr@(1.5lr) tr@(6.0lr) tr@(7.2lr)

0.5 0.8 0.5

0.6

0.7 50 2

0.8 100 4

0.9 200 8 5.5

1.0 0.93 0.95 0.98 300 12 8.3 400 16 11 500 20 13.8 1.0 Off Off Off

0.83 0.85 0.88 0.9 1

Time delay (s) Accuracy: 15% or below 100ms Short time Current setting (A) Accuracy: 10% Time delay (s) @ 10Ir

12.5 25

0.34 0.69 1.38 2.7

Isd = Ir... tsd I2t Off I2t On Min. Trip (I2t Off) Time(ms) Max. Trip Time(ms)

1.5

3 0.2 0.2 160 240

4 0.3 0.3 260 340

5 0.4 0.4 360 440

10

Off

0.05 0.1 0.1 20 80 80 140

Instantaneous Current setting (A) Tripping time


t

Ii = In...

10

12

15

Off

below 50ms

Ground fault Pick-up (A) Accuracy: 10%(Ig0.4In)


Ig

Ig = In... I2t Off I2t On Min. Trip (I2t Off) Time(ms) Max. Trip Time(ms)

0.2

0.3

0.4 0.2 0.2 160 240

0.5 0.3 0.3 260 340

0.6 0.4 0.4 360 440

0.7

0.8

1.0

Off

20%(Ig0.4In)
tg

tg
I

0.05 0.1 0.1 20 80 80 140

Time delay (s) @ 1In

29

Trip relays
A type: Ammeter type
Overload protection -Long-time delay -Thermal Short-circuit protection -Short-time delay / Instantaneous -I2t On/Off optional (for short-time delay) Ground fault protection -I2t On/Off optional Realization of protective coordination by ZSI (Zone Selective Interlocking) High-performance and high-speed MCU built-in -Accurate measurement with tolerance of 1.0% Fault recording -Records Max. up to 10 fault information about fault type, fault phase, fault data, occurrence time of fault SBO (Select Before Operation) -High reliability for control and setting change method 3 DO(Digital Output) -Fixed Communication -Modbus/RS485 -Profibus-DP

LCD: Indication of measurement and information LED: Indication of trip info. and overload state
Isd Ii

Alarm SP

Ir

Ig

Comm

Ig: LED indicating ground-fault Isd/Ii: LED indicating short-time or instantaneous tripping Ir: LED indicating long-time delay SP: Self-protection and battery test LED Alarm: LED indicating an overload (Turn on above 90%, Blink above 105%) Key: Move to menu or reset
Reset Esc

Reset/ESC: Fault reset or ESC from menu Enter: Enter into secondary menu or setting input Up/Down: Move the cursor up/down on screen or increase/decrease a setting value Right/Left: Move the cursor or setting right/left on screen (Rotation) Menu: Menu display Measurement display

Iu, Ir: Long-time current setting, tr: Long-time tripping delay setting Isd: Short-time current setting, tsd: Short-time tripping delay setting Ii: Instantaneous current setting Ig: Ground fault current setting, tg: Ground fault tripping delay setting Test terminal: OCR test terminal (Connected with OCR tester)

30

Protection
t Ir

Long time Current setting (A)


tr lsd tsd Ii I

Iu = In... Ir = Iu... tr@(1.5lr) tr@(6.0lr) tr@(7.2lr)

0.5 0.8 0.5

0.6

0.7 50 2

0.8 100 4

0.9 200 8 5.5

1.0 0.93 0.95 0.98 300 12 8.3 400 16 11 500 20 13.8 1.0 Off Off Off

0.83 0.85 0.88 0.9 1

Time delay (s) Accuracy: 15% or below 100ms Short time Current setting (A) Accuracy: 10% Time delay (s) @ 10Ir

12.5 25

0.34 0.69 1.38 2.7

Isd = Ir... tsd I2t Off I2t On Min. Trip (I2t Off) Time(ms) Max. Trip Time(ms)

1.5

3 0.2 0.2 160 240

4 0.3 0.3 260 340

5 0.4 0.4 360 440

10

Off

0.05 0.1 0.1 20 80 80 140

Instantaneous Current setting (A) Tripping time


t

Ii = In...

10

12

15

Off

below 50ms

Ground fault Pick-up (A) Accuracy: 10%(Ig0.4In)


Ig

Ig = In... I2t Off I2t On Min. Trip (I2t Off) Time(ms) Max. Trip Time(ms)

0.2

0.3

0.4 0.2 0.2 160 240

0.5 0.3 0.3 260 340

0.6 0.4 0.4 360 440

0.7

0.8

1.0

Off

20%(Ig0.4In)
tg

tg
I

0.05 0.1 0.1 20 80 80 140

Time delay (s) @ 1In

Earth leakage (Option) Current setting (A) Time delay (ms)


I n

In Alarm
t

0.5 Time(ms) Trip Time(ms) 140 140

1 230 230

2 350 350

3 800 800

5 950

10

20

30

Off

Accuracy: 15%
t

Note) Earth leakage function is available with ZCT or external CT

31

Trip relays
P type: Power meter type
Overload protection -Long-time delay -Thermal Short-circuit protection -Short-time delay / Instantaneous -I2t On/Off optional (for short-time delay) Ground fault protection -I2t On/Off optional Protection for Over voltage/Under voltage/Over frequency/Under frequency/Unbalance/Reverse power Realization of protective coordination by ZSI (Zone Selective Interlocking) The fine-adjustable setting by knob and Key IDMTL setting (SIT, VIT, EIT, DT curve) - Basic setting : None. Thermal curve. Measurement and Display Function -High detailed measurement for 3 phase current/Voltage/Power/Energy/Phase angle/Frequency/PF/Demand -128 x 128 Graphic LCD -Indicates current/voltage Vector Diagram and Waveform Fault recording -Records Max. up to 256 fault information about fault type, fault phase, fault value, occurrence time of fault Event recording -Records events of device related to setting change, operation and state change. (Max. up to 256) SBO (Select Before Operation) -High reliability for control and setting change method 3 DO(Digital output) -Programmable for alarm, trip and general DO Communication -Modbus/RS485 -Profibus-DP

Graphic LCD: Indication of measurement and information LED: Indication of trip info. and overload state
Isd Ii

Alarm SP

Ir

Ig

Comm

Comm: LED indicating comm. state (Blink when running) Ig: LED indicating ground-fault Isd/Ii: LED indicating short-time or instantaneous tripping Ir: LED indicating long-time delay SP: Self-protection and battery test LED Alarm: LED indicating an overload (Turn on above 90%, Blink above 105%) Key: Move to menu or reset
Reset Esc

Reset/ESC: Fault reset or ESC from menu Enter: Enter into secondary menu or setting input Up/Down: Move the cursor up/down on screen or increase/decrease a setting value Right/Left: Move the cursor or setting right/left on screen (Rotation) Menu: Menu display Measurement display

Ir: Long-time current setting, tr: Long-time tripping delay setting Isd: Short-time current setting, tsd: Short-time tripping delay setting Ii: Instantaneous current setting Ig: Ground fault current setting, tg: Ground fault tripping delay setting Test terminal: OCR test terminal (Connected with OCR tester)

32

Protection
t Ir

tr lsd tsd Ii I

Long time Current setting (A) Time delay (s) Accuracy: 15% or below 100ms Short time Current setting (A) Accuracy: 10% Time delay (s) @ 10Ir

Ir = In... tr@(1.5lr) tr@(6.0lr) tr@(7.2lr)

0.4 12.5 0.5 0.34

0.5 25 1 0.69

0.6 50 2 1.38

0.7 100 4 2.7

0.8 200 8 5.5

0.9 300 12 8.3

1.0 400 16 11

500 20 13.8

Off Off Off

Isd = Ir... tsd

1.5

3 0.2 0.2 160 240

4 0.3 0.3 260 340

5 0.4 0.4 360 440

10

Off

(I2t Off)

I2t Off 0.05 0.1 I2t On 0.1 Min. Trip 20 80 Time(ms) Max. Trip 80 140 Time(ms)

Ig

Instantaneous Current setting (A) Tripping time Ground fault Pick-up (A) Accuracy: 10%(Ig0.4In) 20%(Ig0.4In)
tg

Ii = In...

2 3 4 below 50ms

10

12

15

Off

Ig = In...

0.2

0.3

0.4 0.2 0.2 160 240

0.5 0.3 0.3 260 340

0.6 0.4 0.4 360 440

0.7

0.8

1.0

Off

tg Time delay (s) @ 1In

(I2t Off)

0.05 0.1 I2t Off I2t On 0.1 Min. Trip 20 80 Time(ms) Max. Trip 80 140 Time(ms)

I n

Earth leakage (Option) Current setting (A) Time delay (ms) Accuracy: 15%
t

In

0.5 Alarm 140 Time(ms) Trip 140 Time(ms)

1 230 230

2 350 350

3 800 800

5 950

10

20

30

Off

Note) Earth leakage function is available with ZCT or external CT I

PTA(Pre Trip Alarm) Current setting (A) Time delay (s) Accuracy: 15%

Ip = Ir x tp@(1.2Ip)

0.6 1

0.65 0.7 5 10

0.75 0.8 15 20

0.85 0.9 25 30

0.95 35

1 Off

Other protection Under voltage Over voltage Voltage unbalance Reverse power Over power Current unbalance Over 60Hz frequency 50Hz Under 60Hz frequency 50Hz

Setting range 80V ~ 0V_Pick-up UV_Pick-up ~ 980V 6% ~ 99% 10~500 kW 500~5000 kW 6% ~ 99% UF_Pick-up ~ 65 UF_Pick-up ~ 55 55Hz ~ OF_Pick-up 45Hz ~ OF_Pick-up

Pick-up Step 1V 1V 1% 1kW 1kW 1% 1Hz 1Hz 1Hz 1Hz

Accuracy 5% 5% 2.5% or (*10%) 10% 10% 2.5% or (*10%) 0.1Hz 0.1Hz 0.1Hz 0.1Hz

Time delay(s) Setting range Step Accuracy 1.2~40sec

0.2~40sec 0.1sec 0.1sec

1.2~40sec

33

Trip relays
S type: Supreme meter type
Overload protection -Long-time delay -Thermal Short-circuit protection -Short-time delay / Instantaneous -I2t On/Off optional (for short-time delay) Ground fault protection -I2t On/Off optional Protection for Over voltage/Under voltage/Over frequency/Under frequency/Unbalance/Reverse power Realization of protective coordination by ZSI (Zone Selective Interlocking) The fine-adjustable setting by knob and Key IDMTL setting (SIT, VIT, EIT, DT curve) - Basic setting : None. Thermal curve. Measurement and Display Function -High detailed measurement for 3 phase current/Voltage/Power/Energy/ Phase angle/Frequency/PF/Demand -128 x 128 Graphic LCD -Indicates current/voltage Vector Diagram and Waveform Fault recording -Records Max. up to 256 fault information about fault type, fault phase, fault value, occurrence time of fault -Fault wave recording: records the latest fault wave Event recording -Records events of device related to setting change, operation and state change. (Max. up to 256) SBO (Select Before Operation) -High reliability for control and setting change method Power quality analysis -Measurement for 1st~63th harmonics -THD, TDD, k-Factor -Voltage/current waveform capture 3 DO(Digital output) -Programmable for alarm, trip and general DO Communication -Modbus/RS485 -Profibus-DP

Graphic LCD: Indication of measurement and information LED: Indication of trip info. and overload state
Isd Ii

Alarm SP

Ir

Ig

Comm

Comm: LED indicating comm. state (Blink when running) Ig: LED indicating ground-fault Isd/Ii: LED indicating short-time or instantaneous tripping Ir: LED indicating long-time delay SP: Self-protection LED and battery test LED Alarm: LED indicating an overload (Turn on above 90%, Blink above 105%) Key: Move to menu or reset
Reset Esc

Reset/ESC: Fault reset or ESC from menu Enter: Enter into secondary menu or setting input Up/Down: Move the cursor up/down on screen or increase/decrease a setting value Right/Left: Move the cursor or setting right/left on screen (Rotation) Menu: Menu display Measurement display

Ir: Long-time current setting, tr: Long-time tripping delay setting Isd: Short-time current setting, tsd: Short-time tripping delay setting Ii: Instantaneous current setting Ig: Ground fault current setting, tg: Ground fault tripping delay setting Test terminal: OCR test terminal (Connected with OCR tester)

34

Protection
t Ir

tr lsd tsd Ii I

Long time Current setting (A) Time delay (s) Accuracy: 15% or below 100ms Short time Current setting (A) Accuracy: 10% Time delay (s) @ 10Ir

Iu = In... tr@(1.5lr) tr@(6.0lr) tr@(7.2lr)

0.4 12.5 0.5 0.34

0.5 25 1 0.69

0.6 50 2 1.38

0.7 100 4 2.7

0.8 200 6 5.5

0.9 300 12 8.3

1.0 400 16 11

500 20 13.8

Off Off Off

Isd = Ir... tsd

1.5

3 0.2 0.2 160 240

4 0.3 0.3 260 340

5 0.4 0.4 360 440

10

Off

(I2t Off)

I2t Off 0.05 0.1 I2t On 0.1 Min. Trip 20 80 Time(ms) Max. Trip 80 140 Time(ms)

Ig

Instantaneous Current setting (A) Tripping time Ground fault Pick-up (A) Accuracy: 10%(Ig0.4In) 20%(Ig0.4In)
tg

Ii = In...

2 3 4 below 50ms

10

12

15

Off

Ig = In...

0.2

0.3

0.4 0.2 0.2 160 240

0.5 0.3 0.3 260 340

0.6 0.4 0.4 360 440

0.7

0.8

1.0

Off

tg Time delay (s) @ 1In

(I2t Off)

I2t Off 0.05 0.1 I2t On 0.1 Min. Trip 20 80 Time(ms) Max. Trip 80 140 Time(ms)

I n

Earth leakage (Option) Current setting (A) Time delay (ms) Accuracy: 15%
t

In

0.5 Alarm 140 Time(ms) Trip 140 Time(ms)

1 230 230

2 350 350

3 800 800

5 950

10

20

30

Off

Note) Earth leakage function is available with ZCT or external CT I

PTA(Pre Trip Alarm) Current setting (A) Time delay (s) Accuracy: 15%

Ip = Ir x tp@(1.2Ip)

0.6 1

0.65 0.7 5 10

0.75 0.8 15 20

0.85 0.9 25 30

0.95 35

1 Off

Other protection Under voltage Over voltage Voltage unbalance Reverse power Over power Current unbalance Over 60Hz frequency 50Hz Under 60Hz frequency 50Hz

Setting range 80V ~ 0V_Pick-up UV_Pick-up ~ 980V 6% ~ 99% 10~500 kW 500~5000 kW 6% ~ 99% UF_Pick-up ~ 65 UF_Pick-up ~ 55 55Hz ~ OF_Pick-up 45Hz ~ OF_Pick-up

Pick-up Step 1V 1V 1% 1kW 1kW 1% 1Hz 1Hz 1Hz 1Hz

Accuracy 5% 5% 2.5% or (*10%) 10% 10% 2.5% or (*10%) 0.1Hz 0.1Hz 0.1Hz 0.1Hz

Time delay(s) Setting range Step Accuracy 1.2~40sec

0.2~40sec 0.1sec 0.1sec

1.2~40sec

35

Trip relays
Operation characteristic
Long-time delay (L)
N, A type
Iu
.7 .6 .5
In

.8

.9

Ir
1

.88

.9

tr
.93 .95 .98 2 1

The function for overload protection which has time delayed


12 16 20

.85 .83
Iong time

characteristic in inverse ratio to fault current.


1. Standard current setting knob: Ir 1) Setting range in P type and S type: (0.4-0.5-0.6-0.7-0.8-0.9-1.0)In 2) Setting range in N type and A type: (0.4 ~1.0)In - Iu: (0.5-0.6-0.7-0.8-0.9-1.0)In - Ir: (0.8-0.83-0.85-0.88-0.9-0.93-0.95-0.98-1.0)Iu 2. Time delay setting knob: tr - Standard operating time is based on the time of 6Ir - Setting range: 0.5-1-2-4-8-12-16-20-Off sec (9 modes) 3. Relay pick-up current - When current over (1.15)Ir flows in, relay is picked up. 4. Relay operates basing on the largest load current among R/S/T/N phase.

.8
Iu

.5
@6 Ir

off

P, S type
t Ir

Ir
.6 .5

.7

.8

tr
.9 1
(S)

12 16 20

2 1

.4
In

Iong time

.5
@6 Ir

off

tr

Short-time delay (S)


The function for fault current (over current) protection which has definite
Isd
3 2 1.5
Ir

tsd
6 8 10
(S)

.4

.4

time characteristic and time delayed in inverse ratio to fault current.


.3 .2 .1 .05

.3 .2

off .1 short time


I t

on 2 off

Isd tsd

1. Standard current setting knob: Isd - Setting range: (1.5-2-3-4-5-6-8-10-Off)Ir 2. Time delay setting knob: tsd - Standard operating time is based on the time of 10Ir. - Inverse time (I2t On ): 0.1-0.2-0.3-0.4 sec - Definite time (I2t Off): 0.05-0.1-0.2-0.3-0.4 sec 3. Relay operates basing on the largest load current among R/S/T/N phase. 4. When ZSI function was set, the protection operation will take place instantaneously with input absence by downstream devices. It is advised to disable its ZSI function on the last downstream device.

Instantaneous (I)
The function for breaking fault current above the setting value within
Ii
4 3 6 8

the shortest time to protect the circuit from short-circuit.


10 12 15

2 off instantaneous In

1. Standard current setting knob: Ii - Setting range: (2-3-4-6-8-10-12-15-Off)In 2. Relay operates basing on the largest load current among R/S/T/N phase. 3. Total breaking time is below 50ms.

Ii

36

Ground Fault (G)


The function for breaking ground fault current above setting value
Ig
.4 .3 .2
In

.5

.6

tg
.7 .8 1
(S)

.4

.4

.3 .2 .1 .05

after time-delay to protect the circuit from ground fault.


1. Standard setting current knob: Ig - Setting range: (0.2-0.3-0.4-0.5-0.6-0.7-0.8-1.0-Off)In 2. Time delay setting knob: tg - Inverse time (I2t On): 0.1-0.2-0.3-0.4 sec - Definite time (I2t Off): 0.05-0.1-0.2-0.3-0.4 sec 3. Ground fault current is vector sum of each phase current. Therefore, 3Pole products may operate under its phase-unbalance including ground fault situations.(R+S+T+(N) Phase) 4. When ZSI function was set, the protection operation will take place instantaneously with input absence by downstream devices. It is advised to disable its ZSI function on the last downstream device. 5. Ground-fault functions are basically provided with products equipped with a trip relay through its internal CT that is embedded in each phase.(But, it cant be used with earth-leakage protection function at the same time)

.3 .2

off .1 ground fault


I t

on 2 off

Ig

tg

Earth Leakage (G) - Option


The function for breaking earth leakage current above setting value after
I n
2 1 0.5 3 4 5 10 20
(ms)

800

900

800 350 230

time delay to protect the circuit from earth leakage. (A, P, S type)
1. Standard setting current knob: In - Setting range: 0.5-1-2-3-4-5-10-20-30-Off (A) 2. Time delay setting knob: t - Trip time: 140-230-350-800 ms - Alarm time: 140-230-350-800-950 ms 3. Settings within its alarm range will prevent its breaker from tripping but activating its alarm. 4. This function is enabled and can be used only with standard ZCT provided by LS or private external CT(secondary output 5A) selected by customers. 5. When ZSI function was set, the protection operation will take place instantaneously with input absence by downstream devices. It is advised to disable its ZSI function on the last downstream device.

350 230

140 30 140 Earth Leakage trip alarm

I n

R S T N
ZCT or External CT

Use cautions with earth-leakage current settings


- When using a standard ZCT provided by LS, the setting range is from 0.5 to 30A which is based on its primary current. But ACB installed like A type (displayed on the left side) should only be cable-connected and its rated current should be less than 1600A. - When using other CT selected by customers, the setting range is from 0.5 to 5A based on its secondary current.(Secondary output rating : 5A) Hence, under 100:5A CT, if trip relay is set to 0.5A, earth-leakage exceeding 10A will activate its operation (0.5A20 = 10A)

Guideline for the external CT usage


- Earth-leakage protection characteristics using the standard CT which is installed inside of ACB can protect currents from 20 to 100% range on its rated current. - As rated currents on ACB increases, current that is covered by its standard CT increase as well. This can not protect against small leakage currents. ex) 400A ACB Min. Earth-leakage current 400A20% =80A 4000A ACB Min. Earth-leakage current 4000A20% =800A - Therefore, customers are advised to install an external CT in accordance with its rated currents within its systems. And choose trip relay(E, X type) which is required with external CT usage in order to provide earth-leakage functions.

ZCT or External CT

37

Trip relays
Measurement function

Class.
A type

Measurement element Line current Normal current Reverse current Line voltage Phase voltage Normal voltage Reverse voltage Line-to-line Line-to-current Phase-to-phase Phase-to-current Active power I1 I2

Detailed element Ia,Ib,Ic

Unit

Display range

Accuracy 3%

Current

80A~65,535A 1%

Vab,Vbc,Vca Va,Vb,Vc V1 V2 VabIa, VabIb, VabIc, VabVbc, VabVca VaVb,VaVc VaIa, VbIb, VcIc Pa(ab), Pb(bc), Pc(ca), P Qa(ab), Qb(bc), Qc(ca), Q Sa(ab), Sb(bc), Sc(ca), S WHa(ab), WHb(bc), WHc(ca), WH VARHa(ab), VARHb(bc), VARHc(ca), VARH rWHa(ab), rWHb(bc), rWHc(ca), rWH F PFa(ab), PFb(bc), PFc(ca), PF Iunalance, Vunbalance Peak demand Peak demand 1st~63th harmonics of Va(ab),Vb(bc),Vc(ca) 1st~63th harmonics of Ia,Ib,Ic % kW A V A % kW kVar kVA kWh MWh kVarh Mvarh kWh MWh Hz 1kW~99,999kW 1kVar~99,999kVar 1kVA~99,999kVA 1kWh~9999.99MWh 1kVarh~9999.99MVarh 1kWh ~9999.99MWh 45~65Hz +: Lead, -: Lag 0.0~100.0 1kW~99999kW 80A~65,535A 60~690V 80A~65,535A 0.0~100.0 0.0~100.0 0~360 V 60~690V

Voltage

1%

1 1 1 3% 3% 3% 3% 3% 3%

Angle

Power
P type

Reactive power Apparent power Active energy

Energy

Reactive energy Reverse active energy

Freq. Power factor Unbalance Demand

Frequency Power factor(PF) Unbalance rate Active power demand Current demand Voltage harmonics

S type

Harmonics

Current harmonics THD, TDD K-Factor

Voltage module
For P and S type Trip relay, separate voltage module is necessary to measure other element besides current (Seperate purchase is needed) - Voltage input range: AC 60~690V

Vr Vs Vt Vn
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

Vr Vs Vt V1 V2 V3 Vn
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

V1 V2 V3 Vn

Voltage module

Voltage module

3P4W wiring

3P3W wiring

38

Man machine interface

1000 A
R
100%

Initial display

Measurement display

M
Setting display

50%

1. H/W set
Initial display
1. Wiring 2. Comm 3. Password 4. Time-RTC 5. Demand 6. Data Rst Max Power Demand Energy CB Count Run Time 7. DO Setup

2. Relay set
1. OCR 2. OCGR 3. OVR/UVR 4. Unbal 5. rPower 6. OFR/UFR

3. Events
1. Event 2. Clear All 3. Fault 4. Clear All

4. Sys info

5. L/R (L)

An example of graphic LCD display

1000 A
R
100%

1000 A
R
100%

Ir
.6 .5

.7

.8

.9 1

Ir =

50%

.4
50%

In

1000 A
Displayed screen when changing Ir value into 1.0 (After 3 sec, return to initial display)

Ir adjustment knob Initial display

tg
(S)

.4

.4

.3 .2 .1

Tg = 200 ms [I2T Off]

.3 .2 .1
I t

.05
on 2 off

tg adjustment knob Displayed screen when changing tg value into 0.2 (After 3sec, return to initial display)

39

Trip relays
Protection element setting
Initial display Setting display

1000 A
R
100%

50%

1.H/W Set 2.Relay Set 3.Events 4.Sys Info 5.L/R [L]

1.H/W Set 2.Relay Set 3.Events 4.Sys Info 5.L/R [L]

PASSWORD

XXXX
Password input

1.OCR 2.OCGR 3.OVR/UVR 4.Unbal 5.rP/OPR


Relay setting display

Find adjustment of protection setting current


OCR and OCGR's current setting is basically controlled by knob's setting values. The fine current that cannot be controlled by knob is adjustable by using , key. Fine adjustment is only adjustable in the present knob and next knob's setting range, when moving knob, the adjusted data becomes reset state.

OCRL, S, I
800 A EIT 6400 A 15000 A

Find adjustment of long-time delay Select one IDTM characteristic curve among DT, SIT, VIT and EIT Find adjustment of short-time delay Find adjustment of Instantaneous

I2T [Off]

OCRL, S, I
800 A EIT 6400 A 15000 A

OCRL, S, I
800 A EIT 6400 A 15000 A

OCRL, S, I
800 A EIT 6401 A 15000 A

The setting method of OCGR is same with OCR's, fine adjustment is available.

I2T [Off]

I2T [Off]

I2T [Off]

1.OCR 2.OCGR 3.OVR/UVR 4.Unbal 5.rP/OPR

OVR/UVR Set
Pick Up Delay Action Pick Up Delay Action : 724 V : 1.2 s : None : 150 V : 1.2 s : D01

1.OCR 2.OCGR 3.OVR/UVR 4.Unbal 5.rP/OPR


Relay setting display

Unbal V/I
Pick Up Delay Action Pick Up Delay Action : 6% : 10.0 s : D02 : 12 % : 10.0 s : D03

Protection setting display

OVR/UVR setting

Unbalance setting

1.OCR 2.OCGR 3.OVR/UVR 4.Unbal 5.rP/OPR

rPower
Pick Up Delay Action Pick Up Delay Action :100 kW : 10.0 s : D02 : 2400 kW : 0.2 s : TRIP

6.OFR/UFR

OFR/UFR Set
Pick Up Delay Action Pick Up Delay Action : 65 Hz : 10.0 s : D01 : 55 Hz : 10.0 s : None

Relay setting display Reverse power setting

Relay setting display

Frequency setting

40

Measurement element display


Load current

1000 A
R
100%

50%

Measurement overview
Metering Overview VR 220 IR P Q 1000 986 589 V0.0 A330.0 kW kVar kWh kVarh Demand Current [A] R : S : T : 1000 1000 1000 Max Power [kW] 987 2007/05/14 10:00:00

PF 0.866 F 60.0 EP 56 EQ 32

Max Demand [kW] 986 2007/05/14 11:15:00

Voltage/Current vector diagram


Vector Diagram
Vt It

VOLTGAE [V] VR : 220 0.0 VS : 220240.0 VT : 220120.0 CURRENT [A] IR : 1000330.0 IS : 1000210.0 IT : 1000 90.0 IN : 0

V unbal 3Phase Vpos : 220 V Vneg : Unbal : 0 0.0 V % A A %

Vr Is Ir Vs

I unbal 3Phase Ipos : 1000 Ineg : Unbal : 0 0.0

Power and power factor


Power Diagram
P=986 Q=589

Active Power [kW] R : S : T : 328 328 328 189 189 189 Total 589 Total 986

Apparent [kVA] R : S : T : R : S : T : 379 379 379 0.87 0.87 0.87 Total 0.866 Total 1139

kW

Reactive [kVar] R :
1000

Power Factor

S : T :

kVar 2000

Energy
Forward Energy
P+ Q+

Forward P [kWh] R : S : T : R : S : T : 360 360 Total 1080

Reverse P [kWh] R : S : T : 0 0 Total 0

1051 kWh 607 kVarh

Reverse Energy
PQ-

360 Forward Q [kVarh] 210 210 210 Total 630

0 Reverse Q [kVarh] R : S : T : 0 0 0 Total 0

0 kWh 0 kVarh

Voltage/Current harmonics (S type)


I R S

Volt Wave & FFT [%]


THD[S] : 25.0

S Volt Harmonics [V] H1 H2 H3 H4 H5 H6 H7 220 H8 0 H9 55 H10 0 H11 0 H12 0 H13 0 H14 0 0 0 0 0 0 0

S Volt Harmonics [V] H15 H16 H17 H18 H19 H20 H21 0 H22 0 H23 55 H24 0 H25 0 H26 0 H27 0 H28 0 0 0 0 0 0 0

S Volt Harmonics [V] H57 H58 H59 H60 H61 H62 H63 0 0 0 0 0 0 0

Curr Wave & FFT [%]


THD[R] : 3.0

R Curr Harmonics [A] H1 1000 H8 H2 H3 H4 H5 H6 H7 0 H9 15 H10 0 H11 20 H12 0 H13 0 H14 0 3 0 1 0 1 0

R Curr Harmonics [A] H15 H16 H17 H18 H19 H20 H21 1 H22 0 H23 1 H24 0 H25 1 H26 0 H27 1 H28 0 1 0 1 0 1 0

R Curr Harmonics [A] H57 H58 H59 H60 H61 H62 H63 0 0 0 0 0 0 0

TDD 3Phase R : S : T : R : S : T : 0.1 % 0.1 % 0.1 % 1.2 1.2 1.3

T R S

Current K - Factor

41

Trip relays
Characteristic curves

Long-time delay (L)

5000 2000 1000 500 Ir = 0.4...1 In

200

100 50 40 30 20 20 12 10 8 4 2 1 1 0.5 0.4 0.3 0.2

tr = 0.5...20s

t(s)

5 4 3 2

0.1 0.05

0.02 0.01

0.5

0.7

10

Ir

42

20

Short-time delay (S)

5000 2000 1000

500

Isd = 1.5...10 Ir

200 100 50 40 30 20 10

t(s)

5 4 3 2 1

0.4 0.3 0.2 0.1

0.4 0.3 0.2 I2t OFF 0.1

I2t ON

0.4 0.3 0.2 0.1 0.05

0.05

0.02 0.01

0.5

0.7

10

Ir

20

43

Trip relays
Characteristic curves

Instantaneous (I) Ground fault (G)

100

50 40 30 20 Ig = 0.2...1 In 10

5 4 3 2

t(s)

1 I2t ON

0.4 0.3 0.2

0.4 0.3 0.2 I2t OFF 0.1

0.4 0.3 0.2

0.1

0.1

0.05

0.05 Ii = 2...15 In

0.02

0.1

0.2

0.3

0.4 0.5

0.7

4 5

0.05

0.07

In

44

10

0.01

IDMTL

10000

5000

2000 EIT 1000

500 VIT

200

100

t(s)
50

SIT

20 DT 10

0.5

0.7

10

Ir

20

0.05

45

Trip relays
Characteristic curves

Pre Trip Alarm

500

200

100

50 40 30 20

35

15

10 5

5 4 3

t(s)

2 1 1

0.4 0.3 0.2

0.1

0.05

0.02

0.5

0.7

10

20

Ip

46

30

0.01

ZSI - Zone Selective Interlocking (A, P, S type)

Zone-selective interlocking drops delay time that eliminates faults for breakers. It minimizes the shock that all kinds of electric machineries get under fault conditions. 1. In case of that short time-delay or ground fault accident occurs at ZSI built in system, the breaker at accident site sends ZSI signal to halt upstream breakers operation. 2. To eliminate a breakdown, trip relay of ACB at accident site activates trip operation without time delay. 3. The upstream breaker that received ZSI signal adhere to pre-set short time-delay or ground fault time-delay for protective coordination in the system. However upstream breaker that did not receive its signal will trip instantaneously. 4. For ordinary ZSI operation, it should arrange operation time accordingly so that downstream circuit breakers will react before upstream ones under overcurrent/short time delay/ ground fault situations. 5. ZSI connecting line needs to be Max. 3m.

Z4 Z3 Z2 Z1

ZSI input

Fault A

Z4 Z3 Z2 Z1

ZSI output ZSI input

Fault B

Z4 Z3 Z2 Z1

Z4 Z3 Z2 Z1

Z4 Z3 Z2 Z1

1) Occurrence of fault A - Only breaker performs instantaneous trip operation. 2) Occurrence of fault B - Breaker performs instantaneous trip operation, breaker performs trip operation after prearranged delay time - But if breaker did not break the fault normally, breaker performs instantaneous trip operation to protect system.

47

Trip relays
Remote reset and digital I/O (A, P, S type)

In case of that ACB operates due to accidents or over current, Trip relay indicates the information of the accident through the LED and LCD. Trip relay A, P and S type is possible to perform the remote reset by digital input, and have 3 DO(Digital output). 1. Methods to reset Trip relay is to push the Reset button on the frontal side and to use the remote reset. 2. Digital input - [R11-R22] input: Remote reset - [Z1-Z2] Input: ZSI input - [E1-E2] Input: ZCT for earth leakage detection or external CT input All DI are dry contact that has 3.3V of recognition voltage. When inputting close by SSR(Solid State Relay) or open-collector, connect collector(Drain) to R11. 3. Digital output 3a(524, 534, 544-513) - Fault output: Long/Short time delay, Instantaneous, Ground fault, UVR, OVR, UFR, OFR, rPower, Vunbal, Iunbal (Maintains state as Latch form until user pushes reset.) - General DO: when setting L/R as remote, it is available to control close/open remotely by using communication.

ZSI output

Common

ZSI input

Voltage module
ZCT
V1 V2 V3 Vn E1

Reset

Power supply

Z3

Z1

485+

R11

R22

513

R2

R1

Trip relay

Z4

Z2

485-

544

534

524

GTD

Trip Relay

Digital Output

Long Short Instantaneous Ground Overload OVR UVR rPower Vunbal Iunbal OFR UFR OPR Alarm time time Not available

LTD

S/I

Note

DO1(524) P, S DO2(534) type DO3(544) DO1(524) A type DO2(534) DO3(544)

Programmable

Fixed

48

Communication

Modbus/RS-485
Operation mode: Differential Distance: Max. 1.2km Cable : General RS-485 shielded twist 2-pair cable Baud rate : 9600bps, 19200bps, 38400bps Transmission method: Half-Duplex Termination: 150
SCADA system

Modbus/RS-485

Profibus-DP
Profibus-DP module is installed separately (Option) Operation mode: Differential Distance: Max. 1.2km Cable : Profibus-DP shielded twist 2-pair cable Baud rate: 9600bps~12Mbps Transmission method: Half-Duplex Termination: 150 Standard: EN 50170 / DIN 19245
Ethernet/TCP/IP
Area controller

TCP/IP/Ethernet

TCP/IP CNC

Profibus-FMS
PC DCS PLC

Profibus-DP

Profibus-DP communication module (Option)

Profibus-DP communication module (Option)

PLC

Modbus/RS-485

49

Trip relays
Event & fault recording (P, S type)

When there are events such as setting change, Info. change, error of self-diagnose, state change, P and S type record Max. up to 256 information of the events in accordance with time(ms). In addition, they can record Max. up to 256(up to 10 for A type) information of the faults such as fault cause, fault phase, fault value and so on in accordance with time(ms).

Event information display


Initial display Setting display Password input

1000 A
R
100%

50%

1.H/W Set 2.Relay Set 3.Events 4.Sys Info 5.L/R [L]

1.Event 2.Clear All 3.Fault 4.Clear All

1. EventL 2007/05/15 20:29:41 Sta Change


Power On

10. EventL 2007/04/15 10:11:24 Cfg Change


Comm Set up

Fault information display


Initial display Setting display Password input

1000 A
R
100%

50%

1.H/W Set 2.Relay Set 3.Events 4.Sys Info 5.L/R [L]

1.Event 2.Clear All 3.Fault 4.Clear All

1. Trip 2007/04/26 08:35:52 OCR-Short


Phase T 930A

9. Trip 2007/04/11 09:11:32 UVR


Phase R OV

System information

P and S type can indicate information as followings with the information of the ACB. - Present time: year/month/date/hour/minute/ms - ACB current ratings - N-phase current ratings: 100% - Frequency information: 60Hz / 50Hz - Closing numbers of breaker: CB ON numbers - Trip relay operating time: OCR ON time - ON time of breaker: CB ON time - S/W ver. information

System information display


Initial display Setting display Password input

1000 A
R
100%

50%

1.H/W Set 2.Relay Set 3.Events 4.Sys Info 5.L/R [L]

System Info Date Time 2007/05/15 21:23:30 Rating 1000 A Ex-Func 4POCGR Freq 60 Hz CB ON# 23 Ver-Arm 1.41

System Info Date Time 2007/05/15 21:23:30 Rating 1000 A Ex-Func 4POCGR T-OPER 220 h T-CB ON 180 h Ver-Msp 1.01

50

System block diagram

R ACB

N ACB Trip
Vcc/+9V/-9V Vcc +5V +24V

CN2-1 CN2-11 CN2-3 CN2-13

Filter Amp.
Main PCB Assy

CPU Output
Power PCB Assy

Display (LED, LCD)


Main PCB Assy
CN2-6

MTD
Output CN2-8

Signal CT

CN2-5 CN2-15 CN2-7 CN2-16 CN2-14

Setting part
GND 24

CN2-4

Vcc

Self power

RY0 (K1) CN4-2 GTD contact RY1 (K2) CN4-4 STD/INST contact RY2 (K3) CN4-6 LTD contact CN4-8 Common contact

+24V GND+24V

Power CT
Main PCB Assy
CN2-2

+5V -5V

Additional source AC/DC 100~250V DC 24~60V

CN4-9 CN4-10

SMPS
Power PCB Assy

Trip relay

CN1-9 CN1-10

VDM

CN1-11 CN1-12

CN1-1 ZSI output+ terminal CN1-2 ZSI output- terminal CN1-3 ZSI input+ terminal CN1-4 ZSI input- terminal

CN1-7

Earth

CN1-8

CN1-5 Remote reset+ terminal CN1-6 Remote reset- terminal

Input signal(R phase) CN3-2 Input signal(S phase) CN3-4 Input signal(T phase) CN3-6 Input signal(N phase) CN3-8 DC 24V UTXO URXO GND 24V AD GND CN3-5 CN3-1 CN3-3 CN3-7/9 CN3-10

CN1-7 Earth leakage+ terminal CN1-8 Earth leakage- terminal

Test

Main PCB Assy

Comm.
Power PCB Assy

CN4-1 485+ terminal CN4-3 485- terminal

51

Accessories

Mounting

Accessories SHT1 Shunt Coil SHT2 Double Shunt Coil CC M CS1 CS2 Closing Coil Motor Charge Switch Charge Switch Communication Under Voltage Trip Device Trip Alarm Contact

AH

AS

AN

Standard Option Standard Option Standard Option

Remark Page * * * * * * * * * * * * * * * * * * 54 55 56 57 57 57 58 59 59 60 60 67 61 78 62 62 63 63 64 64 65 67 71 66 * *

Internal

UVT AL

MRB Manual Reset Button RES Remote Reset Switch

RCS Ready to Close Switch C AX TM K1 K2 K3 B LH CTD External ATS DC DF OT J A Counter Auxiliary Switch Temperature Alarm Key Lock Key Interlock Set Double Key Lock On/Off Button lock Lifting Hook Condenser Trip Device Automatic Transfer Switch Controller Dust Cover Door Frame OCR Tester Manual Connector Automatic Connector

* Seperate purchasing is not allowed. Each item should be purchased with the main body.

52

Mounting N A Trip relay P S VM

Accessories N type A type P type S type Voltage Module

AH

AS

AN

Standard Option Standard Option Standard Option

Remark Page * * * * ** 28 30 32 34 38

ZCT ZCT for the earth leakage SBC MI ST STL MIP Shorting "b" Contact Mechanical Interlock Safety Shutter Safety Shutter Lock Miss Insertion Prevent Device

73 69 * 70 70 76 68 72 69 * *** * 73 74 74 75 * * 75 71 77

MOC Mechanical Operated Cell Switch CEL Cradle DI ZAS SC BSP RI PL IB Cell Switch Door Interlock Zero Arc Space Safety Control Cover Body Supporter Racking Interlock Pad Lock/ Position Lock Insulation Barrier

UDC UVT Time Delay Controller ADP Compatible Adapter

RPH Reverse Phase ACB DUM Dummy ACB Other VAD Various Connection Type

13 79 49

RCO Remote I/O PC Profibus-DP comm. module

* Seperate purchasing is not allowed. Each item should be purchased with the main body. ** Voltage module should be purchased with P/S type trip relay. *** It is available only when the control block is in the mode of auto-connection.

53

Accessories
Shunt Coil [SHT1]

Shunt coil 1

SHT1 is a control device which trips a circuit breaker from remote place, when applying voltage continuously or instantaneously over 200ms to coil terminals(C1, C2). When UVT coil is installed, its location is changed.

1. Rated voltage and characteristics of Trip coil


Rated voltage [Vn]
Opening order C1

Power consumption (VA or W) Operating voltage range [V] 0.6~1.1 Vn 0.6~1.1 Vn 0.56~1.1 Vn 0.56~1.1 Vn 0.56~1.1 Vn 200 5 Less than 40ms Inrush Steady-state Trip time [ms]

DC [V] 24~30 48~60 100~130 200~250 -

AC [V] 48 100~130 200~250 380~480

SHT1 C2

Note) Operating voltage range is the min. rated voltage standard for each rated voltage(Vn).

The dotted line to * User be made by the Wiring Diagram customer

Wiring Diagram

2. Specification of the wire Refer to the below table regarding the length and specification of wire when using trip coil with DC 24~30[V] or DC/AC 48~60[V] of rated voltage. The maximum wire length
Rated voltage [Vn] DC 24~30 [V] Wire type Operating voltage 100% 85% #14 AWG (2.08mm2) 95.7m 62.5m #16 AWG (1.31mm2) 61m 38.4m DC/AC 48 [V] #14 AWG (2.08mm2) 457.8m 291.7m #16 AWG (1.31mm2) 287.7m 183.2m

54

Double Shunt Coil [SHT2]

Shunt coil 1

Shunt coil 2

SHT2 is a control device which trips a circuit breaker doubly from the outside. When SHT1 doesnt operate normally, it can trip a circuit breaker safely. Shunt coil 1: Install it at existing location. Shunt coil 2: Install it on the right side of the Shunt coil 1 It is not available with UVT coil when installing double shunt coil.

1. Rated voltage and characteristics of Trip coil


Rated voltage [Vn]
Opening order C11

Power consumption (VA or W) Operating voltage range [V] 0.6~1.1 Vn 0.6~1.1 Vn 0.56~1.1 Vn 0.56~1.1 Vn 0.56~1.1 Vn 200 5 Less than 40ms Inrush Steady-state Trip time [ms]

DC [V] 24~30 48~60 100~130 200~250 -

AC [V] 48 100~130 200~250 380~480

SHT2 C12

Note) Operating voltage range is the min. rated voltage standard for each rated voltage(Vn).

* The dotted line to be made by the customer

Wiring Diagram

2. Specification of the wire Refer to the below table regarding the length and specification of wire when using trip coil with DC 24~30[V] or DC/AC 48~60[V] of rated voltage. The maximum wire length
Rated voltage [Vn] DC 24~30 [V] Wire type Operating voltage 100% 85% #14 AWG (2.08mm2) 95.7m 62.5m #16 AWG (1.31mm2) 61m 38.4m DC/AC 48 [V] #14 AWG (2.08mm2) 457.8m 291.7m #16 AWG (1.31mm2) 287.7m 183.2m

55

Accessories
Closing Coil [CC]

Closing coil

It is a control device which closes a circuit breaker, when the voltage is applied continuously or instantaneously over 200ms to the coil terminals (A1, A2).

1. Rated voltage and characteristics of Closing coil


Rated voltage [Vn]
Closing order

Power consumption (VA or W) Operating voltage range [V] 0.75~1.1 Vn 0.75~1.1 Vn 0.75~1.1 Vn 0.75~1.1 Vn 0.75~1.1 Vn 200 5 Inrush Steady-state

Shunt time [ms]

DC [V] 24~30

AC [V] 48 100~130 200~250 380~480

A1

48~60 100~130 200~250 -

Less than 80ms

CC A2

Note) Operating voltage range is the min. rated standard for each rated voltage (Vh).

* The dotted line to be made by the customer

Wiring Diagram

2. Specification of the wire Refer to the below table regarding the length and specification of wire when using trip coil with DC 24~30[V] or DC/AC 48~60[V] of rated voltage. The maximum wire length
Rated voltage [Vn] DC 24~30 [V] Wire type Operating voltage 100% 85% #14 AWG (2.08mm2) 95.7m 62.5m #16 AWG (1.31mm2) 61m 38.4m DC/AC 48 [V] #14 AWG (2.08mm2) 457.8m 291.7m #16 AWG (1.31mm2) 287.7m 183.2m

56

Motor [M]

Motor

Charge the closing spring of a circuit breaker by the external power source. Without the external power source, charge manually.
Gear

Operating voltage range(IEC 60947) 85%~110%Vn

Main axis

Fully charged contact

Charge switch

Input voltage(V) Load current(max.) Starting current(Max.) Load rpm(Motor) Charge time Dielectric strength Using temperature range Using humidity range Endurance Charge switch

DC 24~30V AC/DC 48~60V AC/DC 100~130V AC/DC 200~250V 5A 3A 1A 0.5A 5 times of load current 15000 ~ 19000 rpm Less than 5sec. 2kV/min -20 60 ~

AC 380V 0.3A

AC 440~480V 0.3A

Max. RH 80% (No dew condensation) 15,000 cycle (Load connection, 2 times/min) 10A at 250VAC

Charge Switch [CS1] Charge Switch Communication [CS2]

It is a built-in contact which sends the signal to the outside, when motor charging is completed. (2a) It has a 1a contact for communication and the other 1a contact for complete charging. When using an extra communication module (Remote I/O), the state of contacts can be displayed through the network. 10A at 250VAC

57

Accessories
Under Voltage Trip device [UVT]

UVT coil

Shunt coil

If the voltage of the main or the control power is under voltage, UVT which is installed inside of the breaker breaks the circuit automatically. Please connect with UVT time-delay device in order to present the timedelay function because UVT is technically instantaneous type.
Closing coil

The closing of a circuit breaker is impossible mechanically or electrically if control power not supplied to UVT. To close the circuit breaker, 65~85% of rated voltage should be applied to both terminals of UVT coil (D1, D2). When using UVT coil, the double trip coil can not be used, and the location of trip coil is changed.

1. Rated voltage and characteristics of UVT coil


Rated voltage [Vn] DC [V] 24~30 48~60 100~130 200~250 AC [V] 48 100~130 200~250 380~480 0.65~0.85 Vn 0.4~0.6 Vn 200 5 Less than 50ms Operating voltage range [V] Pick up Drop out Power consumption (VA or W) Inrush Steady-state Trip time [ms]

Note) Operating voltage range is the min. rated standard for each rated voltage (Vh).

2. Specification of the wire Refer to the below table regarding the length and specification of wire when using trip coil with DC 24~30[V] or DC/AC 48~60[V] of rated voltage. The maximum wire length
Rated voltage [Vn] DC 24~30 [V] Wire type Operating voltage 100% 85% #14 AWG (2.08mm2) 48.5m 13.4m #16 AWG (1.31mm2) 30.5m 8.8m DC/AC 48 [V] #14 AWG (2.08mm2) 233.2m 62.5m #16 AWG (1.31mm2) 143.9m 39.3m

Note) In case of using UVT coil, the location of TC coil is changed.

58

Trip Alarm Contact [AL]

AL1, 1a AL2, 1a

When a circuit breaker is tripped by OCR which operates against the fault current (Over Current Relay), Trip Alarm switch provides the information regarding the trip of circuit breaker by sending the electrical signal from the mechanical indicator on main cover of main circuit breaker or internal auxiliary switch. (Installed at the inside of circuit breaker) When a circuit breaker tripped by fault current, a mechanical trip indicator (MRB, Manual Reset Button) pops out from the main cover and the switch (AL) which sends control signal electrically is conducted to output the information occurred from fault circuit breaker. MRB and AL can be operated only when tripping by OCR, but doesnt be operated by Off button and OFF operation of trip coil. To re-close a circuit breaker after a trip, press MRB to reset it for closing. 2pcs of electrical trip switch (AL1, AL2, 1a) are provided (Option) Trip alarm contact and MRB(Manual reset bottom) need to be purchased together. 1. Electrical characteristics of trip alarm contact
Rated voltage [V] 8V DC 30V DC 125V DC 250V DC 250V AC Non-inductive load (A) Resistive load 11 10 0.6 0.3 11 lamp load 3 3 0.1 0.05 1.5 6 6 0.6 0.3 6 Inductive load (A) Inductive load(A) Motor load 3 3 0.1 0.05 2 MAX. 24A Inrush current

Manual Reset Button [MRB]


It is a function which resets a circuit breaker manually when a circuit breaker is tripped by OCR. When a circuit breaker tripped by fault current, a mechanical trip indicator (MRB, Manual Reset Button) pops out from the main cover and the switch(SDE) which sends control signal electrically is conducted to output the information occurred from fault circuit breaker. MRB can be operated only by OCR but not by OFF operation of circuit breaker. To re-close a circuit breaker after a trip, press MRB to reset it for closing.

Manual reset button Manual reset button

MRB reset lever


Note) The manual reset button is protruded in the event of trip.

59

Accessories
Remote Reset Switch [RES]

Following tripping, this function resets the "fault trip" alarm contacts(AL) and the mechanical indicator(MRB) and enables circuit breaker closing. Push button switch : AC 125V 10A, AC 250V 6A, DC 110V 2.2A, DC 220V 1.1A Resistive load In case of auto reset type circuit breaker Following tripping, a reset of Manual Reset Button(MRB) or Remote Reset Switch(RES) is no longer required to enable circuit breaker closing. The mechanical indicator(MRB) and electrical indicator(AL) remain in fault position until the reset button is pressed. AL2 and RES are alternative. 1. Rated voltage and rated current of RES
Rated voltage
Reset order

Operating current(Max.) AC DC AC DC
Connect to inner micro switch

Operating time

Wire spec. #14 AWG (2.08 mm2)

AC/DC 100~130V AC/DC 200~250V

6A 5A 3A 2.5A Less 40ms

183

#16 AWG (1.31 mm2)

RES 184

* The dotted line to be made by the customer

Connect to AL2 / RES

Wiring Diagram

Ready to Close Switch [RCS]


It interlocks with mechanism of circuit breaker. It indicates the status that the circuit breaker is ready to do closing operation.
Ready to close switch

When mechanism is in OFF position or in Charge, contact is output with ON and it indicates that mechanism can be closed.

A contact Contact part

60

Auxiliary switch [AX]

It is a contact used to monitor ON/OFF position of ACB from remote place.

AUX. contact & charging types AX AC BX BC HX HC


Standard High capacity

Standard OFF charge 3a3b Standard ON charge 3a3b Standard OFF charge 5a5b Standard ON charge 5a5b High capacity OFF charge 5a5b High capacity ON charge 5a5b Standard ON charge 6a6b High capacity ON Charge 6a6b

CC JC

Standard classification
Standard 2000, 5000AF 4000, 6300AF High capacity 2000, 5000AF 4000, 6300AF

Classification 490V AC Contact capacity DC 250V 125V 250V 125V 30V AX BX HX No. of Contact that can be used AC BC CC HC JC

Standard Resistive load 5A 10A 10A 0.3A 0.5A 10A 3a3b 5a5b 3a3b 5a5b 6a6b Inductive load 6A 6A 6A 0.3A 0.6A 6A 5A

High capacity Resistive load 10A 10A 3A 10A 10A 5a5b 5a5b 6a6b Inductive load 2.5A 10A 10A 1.5A 6A 10A

Remark

Standard charging type

Rapid autoreclosing charging type

61

Accessories
Key Lock [K1]

It is a device for locking which prevents a certain circuit breaker from being operated by users discretion when two or more circuit breakers are used at the same time. K1: Preventing mechanical closing

K1

Key Interlock Set [K2]


Wiring
3 circuit breakers can be arranged for the continuous power supply to the load side and be interlocked mutually by using Key Lock embedded in each circuit breaker.
ACB-1 ACB-2 ACB-3 Status LOAD1 OFF ON ON ON OFF OFF ON LOAD2 OFF ON ON ON OFF ON OFF

ACB1

ACB2

: Release : Lock

ACB3 Load 1 Load 2

62

Double Key Lock [K3]

When only two keys are released at the same time, circuit breakers operate. Handling method is same as K1.

Key interlock double

ON/OFF Button Lock [B]

It is to prevent manual operation of ACBs closing/tripping button due to users wrong handling. It is not possible to handle ON/OFF operation under the Button lock status.

Note) Padlocks(5 ~ 6) are not supplied.

ON/OFF button lock

63

Accessories
Lifting Hook [LH]

It is a device to make an ACB easy to shift. Please hang it to both handles of the arc cover.

Condenser Trip Device [CTD]


Ratings
It gets a circuit breaker tripped electrically within regular time when control power supply is broken down and is used with Shunt coil, SHT. In case there is no DC power, It can be used as the rectifier which supplies DC power to a circuit breaker by rectifying AC power.
Ratings Model Rated input voltage (V) Frequency () Rated charge voltage (V) Charging time Trip possible time Range of Input voltage (%) Condenser capacity Specification CTD-100 AC 100/110 50/60 140/155 Within 5S Over 3 MIN 85~110 400 CTD-200 AC 200/220 50/60 280/310 Within 5S Over 2 MIN 85~111 160

External dimension
131 118 15 7.5

Circuit diagram

AC input

DC output

Side view

108 75

Rear view

Front view

64

75

Automatic Transfer Switch Controller [ATS]

Ratings
Model type Rated voltage Voltage range Frequency Power consumption (apparent power) 4-location switch (stop, N, R, Auto) Test function Generator control function N power source setting (phase-to-phase/ 3phases) Time setting (T1~T6) Fault function (OCR/Circuit breaker trouble) Output contact (Auto, Load burden) Communication function (RS-485) ATSC-110 AC 110V AC 93.5(5%) ~126.5V(5%) 50Hz/60Hz 15.4W ATSC-220 AC 220V AC 187(5%) ~ 253V(5%)

T1: The delayed time from when UN (power supply of electric company) is tripped to when generator start-up signal contact is closed. (t1: 0.2, 0.5, 1, 2, 4, 8, 15, 30, 40, 50secs) T2: The delayed time from when UN is closed to when ACB2 is tripped. (t2: 0.2, 1, 2, 4, 8, 15, 30, 60, 120, 240secs) T3: The delayed time from when ACB1 is tripped to when ACB2 is closed. (t3: 0.5, 1, 2, 5, 10, 15, 20, 25, 30, 40secs) T4: The delayed time from when ACB2 is tripped to when ACB1 is closed. (t4: 0.5, 1, 2, 5, 10, 15, 20, 25, 30, 40secs) T5: The delayed time when ACB1 is closed to when generator start-up signal contact is opened. (t5: 60, 120, 180, 240, 300, 360, 420, 480, 540, 600secs) Stop-mode: This mode is for compulsory trip of ACB1(electric power company) or ACB2 (power station) when UN (power supply of electric power company) or UR (power supply of power station) is available *UN or UR should be kept in ON position N-mode: This mode is for compulsory closing of ACB1 when UN is available. * it does not matter to be ON or OFF position of UR and if converting to N-mode while using UR, generator start-up signal contact is opened. R-mode: This mode is for compulsory closing of ACB2 during the use of UR regardless of that UN is available or not. Auto-mode: This mode is for transferring a circuit breaker automatically to available power supply of UN or UR. In short, it trips the circuit breaker where power supply is not available and it close the circuit breaker where power supply is available.

65

Accessories
OCR Tester [OT]

It is a device which can test for the operation of Trip Relay under no power condition. 1. Maximum 17 times rated current can be inputted. 2. It is possible to enter the current value and phase on each of R/S/T/N 3. Frequency is adjustable. 4. It is available to test for long time delay/short time delay/instantaneous /ground fault.

OCR tester

Configuration
R S T N
R, S, T, N phase signal input

Increase/Decrease signal input

ENT.

ESC

Signal setting/Delete

START

STOP

Waveform generation/Stop

50Hz 60Hz

Hz

Select frequency

66

Dust Cover [DC]

Attach it to the door frame. It protects the product against the dust (IP5X) which may cause fault operation and enhances the sealing degree by being mounted to protrude type of panel. It is transparent so that the front side of ACB is visible and the Cover can be opened/closed even if ACB is drawn out to until TEST position.

Panel door Dust cover Door frame

Counter [C]

It displays the total number of ON/OFF operation of ACB.

Counter

67

Accessories
Mechanical Operated Cell Switch [MOC]

a1 a2

a3

a4 a5

b1 b2

b3 b4

b5

a1 a2

a3

a4 a5

b1 b2

b3 b4

b5

13 23 14 24

33 34

43 53 44 54

11 21 12 22

31 41 51 32 42 52

13 23 14 24

33 34

43 53 44 54

11 21 12 22

31 41 51 32 42 52

AUX S/W

AUX S/W

It is the contact (10a10b) which displays the ON/OFF condition of ACB. It mechanically operates only when the breaker is CONNECTED position. A standard type and a high capacity type is available. The contact capacity is as same as the ratings of aux. contacts. When MOC link is installed to cradle, MOC can be equipped with the inside of panel.

68

Mechanical Interlock [MI]

It is used to interlock closing and trip between two or three breakers mechanically so as to prevent unintended operation at the same time. Wire type interlock can be applied upto 3 breakers

Door Interlock [DI]

It is a safety device which does not allow the panel door to open when a circuit breaker is in the ON position.

Install on the door of panel

Install on the side plate of ACB cradle

69

Accessories
Safety Shutter [ST]

It is the automatic safety device to protect the connectors of main circuit by cutting off dangerous contact from outside while the breaker is drawn out. When the ACB is drawn in, the shutter is automatically opened. There are 4 types of Safety Shutter and they are divided as shown in figure below.
The types of safety shutter plate 2000/5000AF, 3P 4000/6300AF, 3P

2000/5000AF, 4P

4000/6300AF, 4P

Safety Shutter Lock [STL]

Shutter plate

Guide shutter

It is a locking device which prevents safety shutter from being opened when it is closed. If shutter lock is connected with guide shutter, the guide shutter can not be pushed structurally. Thus, it is not available to open the safety shutter.

Note) Padlocks(5 ~ 6) are not supplied.

Shutter lock

Key lock

70

Door Frame [DF]

When structuring the embedded type of ACB panel, it protects the protrude front of ACB and the cutting side of panel door by attaching it to the panel door.

Door frame

Panel door

Insulation Barrier [IB]

Fixed type

Draw-out type

Insulation barrier prevents the arc which may arise and result in short-circuit between phases in advance As C stands for CRADLE, install the insulation barrier in the direction of C in case of Draw-out type. As A stands for ACB main frame, install the insulation barrier in the direction of A in case of Fixed type.

71

Accessories
Cell Switch [CEL]

It is a contact which indicates the present position of ACB.(CONNECTED, TEST, DISCONNECTED) <Contact configuration> 4C: 1Disconnected +1Test +2Connected 8C: 2Disconnected +2Test +4Connected
Contact configuration can be changeable if necessary.

Cell switch

ACB position Draw-in and draw-out position CL-C (Connected) Contact operation CL-T (Test) CL-D (Disconnected) Voltage(V) 460V Contact capacity DC Contact number AC 250V 125V 250V 125V 30V OFF OFF

DISCONNECTED DISCONNECTED TEST

CONNECTED CONNECTED ON

ON ON OFF Resistive load 5 10 3 10 10 4C Inductive load 2.5 10 1.5 10 10

72

Shorting b Contact [SBC]


It is the contact which keeps the external control circuit in normal by Aux. contact which disconnects Axb when ACB is moved from CONNECTED position to TEST position. The number of shorting b-contact corresponds to the number of Axb (4b)

Shorting b contact

Contact condition (Link between Axb and shorting bcontact)


ACB location Shorting b contact Auxiliary contact (Axb) ACB condition CONNECTED location TEST location CONNECTED location TEST location CLOSE OFF ON OFF OFF OPEN OFF ON ON ON

Zero Arc Space [ZAS]


Arc which may arise while breaking fault current is extinguished first by Arc chute in main body of circuit breaker and then completely extinguished by Arc cover. By preventing arc from exposing to the outside, it protects itself from all kinds of accidents. It is categorized into 8 types by ratings and poles.
Ampere frame 2000AF 3P 2000AF 4P 4000AF 3P 4000AF 4P 5000AF 3P 5000AF 4P 6300AF 3P 6300AF 4P Cover length (mm) 281.4 366.4 359.4 474.4 576.4 746.4 732.4 962.4

Arc cover

73

Accessories
Safety Control Cover [SC]

It protects control terminals which exposes to the outside, and prevents the damages resulted from foreign substances.
Safety control cover

It is categorized into 8 types by ratings and poles.


Ampere frame 2000AF 3P 2000AF 4P 4000AF 3P 4000AF 4P 5000AF 3P 5000AF 4P 6300AF 3P 6300AF 4P Cover length (mm) 334 419 412 527 629 799 785 1015

It is available only when the control block is in the mode of auto-connection.

Body Supporter [BSP]

It interlocks the main body of circuit breaker and cradle mechanically to fix the former in connected position. Therefore, all draw-in/outs are not available.

Body supporter

74

Racking Interlock [RI]

Door plate

Handle inserting hole

Racking interlock

When panel door is opened, Draw in/out handle doesnt be inserted. Thus, panel handle can be inserted only when panel door is closed.

Pad Lock / Position Lock [PL]

Draw-in button

Pad lock

ACB is subject to restriction regarding moving in connected, test, disconnected when drawing in or out. If main body of ACB is placed in 3 positions, it is locked and stopped when drawing in or out. As shown in the figure, if draw-in/out button pops out, it means locking is operating. To continue Draw-in/out operation, release lock by pushing Draw-in/out button In case it is locked as shown in the figure above, main body of ACB can not be drawn in or out into the cradle. For the lock device, user has to purchase it. (5 ~ 6)

75

Accessories
Miss Insertion Prevent Device [MIP]

A C E G B D F

2 4 6

1 3 5 7

Cradle

ACB body

When the main body of ACB is inserted to the cradle, if the ratings of ACB does not match with cradle, it mechanically prevents ACB from being inserted into cradle of ACB. The installation method is variable according to ratings.
Cradle ABCD ABCE ABCF ABCG ABDE ABDF ABDG ABEF ACB 567 467 457 456 367 357 356 347 Cradle ADEF ADEG ADFG AEFG BCDE BCDF BCDG BCEF ACB 237 236 235 234 167 157 156 147 Cradle ABEG ABFG ACDE ACDF ACDG ACEF ACEG ACFG ACB 346 345 267 257 256 247 246 245 Cradle BCEG BDEF BDEG BDFG CDEF CDEG CEFG DEFG ACB 146 137 136 135 127 126 124 123

76

UVT Time Delay Controller [UDC]

UVT is a device which makes ACB tripped automatically to prevent the accident on load side due to under voltage or power breakdown. There are two types, Instantaneous type and time delay type. It can be installed on the rail or to the cradle. Instantaneous type: only available with UVT coil. Time delay type: available by connecting UVT coil and UVT time delay controller. Common use for the all types.
UVT time delay controller

1. The rated voltage and characteristic of UVT time delay controller


Rated voltage [Vn] DC [V] 48~60 100~130 200~250 AC [V] 48 100~130 200~250 380~480 0.65~0.85 Vn 0.4~0.6 5Vn 200 5 0.5, 1, 1.5, 3 Operating voltage range [V] Pick up Drop out Power consumption (VA or W) Inrush Steady-state Trip time[s]

Note) Operating voltage range is the min. rated standard for each rated voltage (Vh).

2. Wiring
14 16

Rating voltage Delay trip Command


1 1.5 3

UVT
18 19 20 a c b Signal for tripping DC48~60V AC48 5 7 0.5

[sec] UVT Time Delay Controller 14 Instaneous trip command D1 D2 UVT Rating voltage 16

Time Delay for UVT

77

Accessories
Temperature Alarm [TM]

Temperature alarm

Temperature Alarm Unit is a device to show the temperature through a sensor inside of ACB. The temperature sensor can be installed up to 4 and the output is connected to control terminal blocks. It displays the maximum temperature of them and transmits through a network. If the temperature is higher than a standard, an alarm can occur. Temperature alarm unit communicates with Modbus / RS-485 basically, Profibus-DP need to be purchased separately. Temperature alarm unit is installed on the cradle or the inside of panel.

Control power AC/DC 110/220V

1 2

Power

24V 24V GND 5V 5V GND

13 14 15 16

3 4

Temperature alarm

5 6 7

Relay 3 DO control

17 18

Temperature Alarm(+) Temperature Alarm(-)

Temp. Sensor input 1 Temp. Sensor input 2 Temp. Sensor input 3 Temp. Sensor input 4 Temp_COM

8 9

RS-485(-) RS-485(+)

19

10 11 12

20

RS-485

MODBUS Profibus-DP

*In case of using Profibus-DP communication, it needs to communicate with ACB trip relay.

Temperature LED(): 10 ~150, Warning (Indicates the maximum value)

78

Remote I/O Unit [RCO]

Control Power AC/DC 110/220V

Power
2 3 4 5 6 7

24V 24V GND 5V 5V GND

Relay 0 CB close

13 14

CB ON(+) CB ON(-) CB OFF(+)

CB ON

Relay 1 CB open

15

Remote I/O Unit

CB OFF General DI 1 General DI 2 DI_COM

16

CB OFF(-)

RS-485(-)
9

19

RS-485(+)
10 11

20

RS-485
12

MODBUS Profibus-DP

*In case of using Profibus-DP communication, it needs to communicate with ACB trip relay.

Classification CB control Alarm Contact switching capacity Max. switching capacity Contact switching capacity Max. switching capacity

Applied range AC230V 16A / DC30V 16A 3680VA, 480W AC230V 6A / DC25V 6A 1880VA, 150W

Remarks

Induction load (cos=0.4, L/R=7ms)

Remote I/O unit has the I/O contact which can trip or close the ACB from the remote site by communication. For the General DO, the output of DI1 or DI2 is selectable. Remote I/O Unit communicates with Modbus / RS-485 communication basically, Profibus-DP need to be purchased separately. It supports SBO (Select Before Operation) function and guarantees the control reliability. Remote I/O Unit can be installed on the cradle of ACB or the inside of panel.
- Baud rate setting - Comm. address setting - Temperature setting

LED 1 2 3 4 5 6 7 8 DI1 DI2 DO ON DO OFF CB ON CB OFF RUN LED CB ERROR

Status Indicates digital Input #1condition Indicates digital Input #2condition Indicates temperature alarm output is ON Indicates temperature alarm output is OFF Indicates circuit break close condition Indicates circuit break open condition Indicates unit run condition Indicates circuit break terminal Disconnection / control Err condition

79

Electrical diagram
This diagram is based on CONNECTED position of a circuit breaker and Opening, Motor charging, Releasing of locking plate should be normal condition.

ZSI Output

Voltage module
ZCT V1 V2 V3 VN E1

ZSI Input

Common

Power supply

Reset

OFF

OFF
C1 C2

Z3

Z1

485+

R11

R22

513

R2

R1

251

83

183 /RES(+)

D1

C11

Trip relay

UVT SHT2 SHT1 or

E2

Z4

Z2

485-

544

534

524

252

84

184 /RES(-)

D2

C12

STD/Inst

GTD

LTD

Main circuit

Digital trip relay

Fault trip UVT

Electric operation circuit Secondary trip coil

Ready to close

Terminal code description


13 11 14 ~ 63 12 ~ 61 64 62

Auxiliary switch a Auxiliary switch b Charged signal Charged signal communication Motor charging Closing coil Shunt trip 2nd shunt trip

D1 83

D2 84

Voltage input terminal of UVT Alarm1 a Alarm2 a Ready to close switch Control power Alarm contact Alarm reset (Trip cause LED, Alarm contact) RS-485 communication

413 414 423 424 U1 A1 C1 U2 A2 C2

183 184 251 252 R1 R2

513 ~ 544 R11 R22 485+ 485-

C11 C12

Note) 1. The diagram is shown with circuits de-energized, all devices open, connected and charged and relays in normal position 2. Relay is normal condition and charging type is "OFF-Charging" 3. The standard of auxiliary contact is 3a3b. The auxiliary switch in above diagram is composed of 5a5b. See 48 page for more detail on auxiliary switches. 4. Option - Ready to close contact, Trip alarm contact, UVT coil, Fully charged contact, secondary trip coil - Cell switch, Temperature module, Voltage module, Remote close-open module, ZCT, ZSI 5. Please consult us for the use of ZSI (Zone selective Interlocking). 6. Refer to the page 33 for the connection of Trip relay and the page 43 for UVT. 7. For connecting RS-485 verify if the polarity is correct

80

ON
A1 CC A2

Temperature Module

U1

413

423

51

41

31

21

11

53

43

33

23

13

T1

TC1

T2

TC2

341

331

321

311

Axb

Temperature Sensor-1

Temperature Sensor-2

Axb

Axb

Axb

Axb

Axb

Axa

Axa

Axa

Axa

Axa

CL

CL

CL

U2

414

424

52

42

32

22

12

54

44

34

24

14

342

344

332

334

322

324

312

OFF

Charged

Charged

ON

Charge completion contact

Auxiliary switch

Thermal, communication remote control module

Cell switch

Accessory code description


Z1 Z3 E1 Z2 Z4 E2

ZSI input ZSI output ZCT Voltage module


, T2

Ax LTD STD/Inst GTD CL


M CC SHT1 SHT2 UVT

Auxiliary switch Long time delay trip indicator Short time delay/instantaneous Ground fault trip indicator Cell switch Motor Closing coil Shunt tripping device 1 Shunt tripping device 2 UVT coil

Internal wiring External wiring (by customer) Connector of the control circuit terminal of drawout type

VN ~ V3 TC1 , TC2 ~ T1 311 ~ 344

Temperature module Position switch

CL
314

81

Dimensions
Fixed type 2000AF (630~1600A: AH/AN/AS-06~16D)
Front view
300 280 150 Operating panel center 385 280 150 Operating panel center

300

270

320

300

270 12 250 439 165

35

20

12

165 354

165

12

20

3P

4P

Vertical type
25

85

85 15

85

85

85 15

45

35 12 25 4- 14 Mounting hole 415 439

165

20

4- 14 Mounting hole 330 354

3P
90 (Insulation barrier)

4P

15

30 15 50

270

133

83

42 50 67

2- 13

35

<Conductor>

65

20

165 295

45 32.5

Door Frame: DF (AH/AN/AS-D/E)


Operating panel center 276 10- 5

<Mounting hole>

<Side hole>
Rear panel

25

50

<Panel cutting >


D3 D4 E3 E4 Din. "W" 330 415 408 523

315(Panel cutting size)

Door frame W

120

353(Panel cutting size)

266 388

352

128

20

165

45

320

39 21.5

170

120

278 350

7 10

165 Cradle bottom

165

Cradle bottom

<External size>

82

Note) The dimensions are for drawout type.

11.5

109

304

Horizontal type
25

85

85 50

85

85

85 50

45

25

165

20

4- 14 Mounting hole 330 354

415 439

3P
90 (Insulation barrier)

4P

15

15

30 15

270

118 133

59.5 15

2- 13 67

35

65

20

165 295

45 32.5

<Conductor>

85

85 50 5.5

85

85

85 50 45

20

4- 14 Mounting hole 330 354 415 439

3P

4P

25 19.5 55

15

200

15

25

270

483

2- 13

<Conductor>
35 200

65

20

165 295

45 5.5

108

50

20

165

Front connection type

25

45

165 230

25

25

50

4- 14 Mounting hole

20 4- 14 Mounting hole

165

45

83

Dimensions
Draw-out type 2000AF (630~1600A: AH/AN/AS-06~16D)
Front view
20 394 167 20 20 479 42.5 167 20

2-M12 Tap CMB-U/F

2-M12 Tap CMB-U/F

405 430

260 334

85 419

260

3P

4P

Vertical type
115

85 15

85 15

85

85

85

200

260 334

200

115

85 345

260

3P

4P

50 15

Disconnected & Test Connected 55 ARC Chute surface 90 (Insulation barrier)

35 15 270 50

25

133 350

2- 13 41 18 97

<Conductor>

60 10

200 375 6- 13 Mounting hole

115 38.5

84

50

405 430

Horizontal type
115

85 50

85 50

85

85

85

200

200

115

260 334

85 345

260

3P
Disconnected & Test Connected 50 15 55 ARC Chute surface 90 (Insulation barrier)

4P

35 15

15

270

133

350

2- 13

<Conductor>
41 18 97

60 10

200 375 4- 13 Mounting hole

115 38.5

Front connection type

85

85 50

85

85

25 115 200 260 334 200 115 85 345 260

85 50

3P
Disconnected & Test Connected 50
15

4P
ARC Chute surface 13.5

55

25

200

15

270

483

50

25

41 18

<Conductor>
4- 13 Mounting hole 60 10 200 375 115 11.5 200

78

50 2- 13

85

Dimensions
Fixed type 2000AF (2000A: AH/AS-20D)
Front view
300 280 150 Operating panel center 385 280 150 Operating panel center

300

270

300

270 12 250 439 165

320

35

20

20

12

165 354

165

12

3P

4P

Vertical type
25

85

85 15

85

85

85 15

35 12 25 4- 14 Mounting hole 415 439

45

165

330 354

3P

20

4- 14 Mounting hole

4P

15

90 (Insulation barrier) 30 15 75

270

25

133

58

75

35

67

3- 13

32.5

86

29.5

65

20

165 295

45

<Conductor>

25

75

20

165

45

320

Draw-out type 2000AF (2000A: AH/AS-20D)


Front view
20 394 167 20 20 479 42.5 167 20

2-M12 Tap CMB-U/F

2-M12 Tap CMB-U/F

260 334

405 430

85 419

260

3P

4P

Vertical type
115

85 15

85 15

85

85

85

200

200

115

260 334

85 345

260

3P

4P

50 15

Disconnected & Test Connected 55 ARC Chute surface 90 (Insulation barrier)

35 15

75

25

270

133 350

3- 13 41 18

60 10

200 375 6- 13 Mounting hole

115 38.5

97

<Conductor>

25

75

405 430

87

Dimensions
Fixed type 4000AF (2000~3200A: AH/AN/AS-20~32E)
Front view
378 189 280 Operating panel center 189 304 280 Operating panel center 493 189

270 320

35

20

20

12

204 432

204

12

12

319 547

204

12

3P

4P

Vertical type
25

115

115 20

115

115

115 20

45

165

25

20

4- 14 Mounting hole 408 432 523 547

3P

4P

15

90 (Insulation barrier) 30 15 75

270

25

133

58

75

35

67

3- 13

32.5

88

29.5

65

20

165 295

45

<Conductor>

25

75

20 4- 14 Mounting hole

165

45

35

270 320

300

300

Horizontal type
25

115

115 75

115

115

115 75

45

25

165

20

4- 14 Mounting hole 408 432 523 547

3P
90 (Insulation barrier)

4P

15

30 15 20

270

25

113

133

57 20

35

67

3- 13

65

20

165 295

45 32.5

<Conductor>

Front connection type

5.5

115

115 75

115

115

25

75

115 75 5.5 20 4- 14 Mounting hole 165 45

25

45

408 432

20

165

4- 14 Mounting hole 523 547

3P
25 19.5 55

25

4P

15

212.5

15

270

25

483

3- 13 35 212.5

<Conductor>

65

20

165 295

45 5.5

108

25

75

20 4- 14 Mounting hole

165

45

89

Dimensions
Draw-out type 4000AF (2000~3200A: AH/AN/AS-20~32E)
Front view
20 472 20 206 20 20 587 57.5 20 206

2-M12 Tap CMB-U/F

2-M12 Tap CMB-U/F

405 430

260 412

115 375 527

260

3P

4P

Vertical type
20

115

115 20

115

115

115

200

115

200

115

260 412

115 375

260

3P

4P

50

Disconnected & Test Connected


55

15

ARC Chute surface


90 34 15

(Insulation barrier)

25

270

75

350

133

3- 13

<Conductor>
41 18 97

60 10

200 375

115 38.5

6- 13 Mounting hole

90

25

75

405 430

Horizontal type
115

115 75

115 75

115

115

115

200

260 412

200

115

115 375

260

3P
Disconnected & Test Connected 50 15 55 ARC Chute surface 90 (Insulation barrier)

4P

34 15 20

25 270 133 350 3- 13 41 18 97

<Conductor>
60 10 200 375 6- 13 Mounting hole 115 38.5

115

115 75

Front connection type

115

115

25 115 75 200 115 115 375 260

200

115

260 412

3P
Disconnected & Test Connected 50 15 55 13.5 ARC Chute surface 25

4P

15

212.5

25 483 3- 13

270

<Conductor>
41 18 212.5

60 10

200 375

115 11.5

78

4- 13 Mounting hole

25

75

75

91

Dimensions
Fixed type 4000AF (4000A: AH/AS-40E)
Front view
189 280 Operating panel center 378 189 304 280 Operating panel center 493 189

270 320

35

20

12

204 432

204

12

20

12

319 547

204

12

3P

4P

Vertical type

150 17.5

150 15 10 15

150

150 17.5

150 15 10 15

25

45

25

165

20

408 432

4- 14 Mounting hole

523 547

3P

4P

15

90 (Insulation barrier) 34 15

125

270

125

35

67

165 295

112.5

4.5

65

20

45

5- 13

<Conductor>

92

25

25 25 125

33 158

25

20
4- 14 Mounting hole

165

45

35

270 320

300

300

Horizontal type
25

140

140 100

140

140

140 100

12.5 45 45 25 523 547

20

165

4- 14 Mounting hole 408 432

3P

4P

15

90 (Insulation barrier) 34 15 12.5 55

270

25

55

25

35

65.5

29.5

65

20

165 295

45

4- 13

<Conductor>

12.5

57

10 1010

98 153

100

25

20 4- 14 Mounting hole

165

93

Dimensions
Draw-out type 4000AF (4000A: AH/AS-40E)
Front view
20 472 206 20 20 587 57.5 20 206

2-M12 Tap CMB-U/F

2-M12 Tap CMB-U/F

260 412

115 375 527

260

3P 4P

Vertical type
115

10

150 17.5

150 15 40 10

150 15

150 40

150

200

200

115

260 412

115 375

260

3P

4P

Disconnected & Test Connected 50 15 55

ARC Chute surface 90 (Insulation barrier) 34 15

125

25

15 10 15

125*10t-3ea M12*80L bolt

270

350

125

158

33

41 18

125

25

25

25

84.5

5- 13

10

98.5

94

22

60

200 375 4- 13 Mounting hole

115

<Conductor>

405 430

405 430

Horizontal type
115

140 100 12.5

140 100

140

140

140

200

200

115

260 412

115 375

260

3P

4P

Disconnected & Test Connected 50 15 55 ARC Chute surface 90 (Insulation barrier) 34 15 12.5 55 25 350 153 98 25 55 4- 13 87 41 18 60 10 200 375 6- 13 Mounting hole 115 66.5 6 59.5

<Conductor>

12.5

10 1010

270

100

25

95

Dimensions
Fixed type 5000AF (4000~5000A: AS-40~50F)
Front view
595 280 150 Operating panel center 765 280 150 Operating panel center

270

300

300

380

270
630 819 165

60 35 95

12

460 649

165

12

12

3P

4P

Vertical type

190

190 20 70 20

190

190

190 20 70 20

45

165

4- 14 Mounting hole 625 649 795 819

20

4- 14 Mounting hole

3P

4P

15

90 (Insulation barrier) 34 15

270

125

58 183

39.5 125 102

95

20.5

5- 13

65

20

165 295

45 67.5

<Conductor>

96

25

25 25 125

25

20

165

45

60 35 95
12

80

80

380

Horizontal type

190

190 125

190

190

190 125

45

165

20

625 649

4- 14 Mounting hole

795 819

4- 14 Mounting hole

3P

4P

15

90 (Insulation barrier)

70

20

34 15

270

83 193

20

20

42 20 97

95

18

70

5- 13

65

20

165 295

45 67.5

<Conductor>

Door Frame: DF (AH-G, AS-F)


Operating panel center 276 10- 5

<Mounting hole>

<Side hole>

25

25 25 125

25

<Panel cutting >


Din. "W" 625 795 781 1011

Rear panel 315(Panel cutting size) Door frame W 120

F3 F4 G3 G4

353(Panel cutting size)

266 388

352

128

278 350

39 21.5

7 10

200 120

Cradle bottom

Cradle bottom

<External size>

Note) The dimensions are for drawout type.

11.5

165

165

109

334

20

165

45

97

Dimensions
Draw-out type 5000AF (4000~5000A: AS-40~50F)
Front view
20 689 147.5 20 Operating panel center 20 859 232.5 20 Operating panel center

2-M12 Tap CMB-U/F

2-M12 Tap CMB-U/F

435 460

295 629

260

260

205 799

260

3P

4P

190

190 20 70 20

190

190

190 20 70 20

Vertical type
115

200

200

115

295

260

260

205

260

3P

4P

Disconnected & Test Connected 50 15 55

Arc chute surface 90 (Insulation barrier)

34 15 125

270

39.5 125 102

36 41 18

5- 13

200 10

115 53 .5

<Conductor>

375 6- 13 Mounting hole

98

25

25 25 125

58 183 380

25

435 460

Horizontal type

190

190 125

190

190

190 125

115

200

295

260

200

115

260

205

260

3P

4P

50

Disconnected & Test Connected Arc chute surface 55 90 (Insulation barrier) 20 34 15

15

70 110

270

20 83 193 380

110

36 41 18

5- 13 97

<Conductor>

200 10 375

115 63.5

6- 13 Mounting hole

42

25

25

125

25

25

99

Dimensions
Fixed type 6300AF (4000A~6300A: AH/AS-40~50G)
Front view
751 562 280 Operating panel center 189 792 280 Operating panel center 981 189

300

270

300

270
807 1035 204

380

60 35 95

12

577 805

204

12

12

3P

4P

4000A~5000A
34 15

6300A

34 15

25

25 25 125

25

5- 13

6- 13

<Conductor>

<Conductor>

Vertical type
244 244 20 70 20 244 244 244 20 70 20

45

25

25

25 150

25

25

165

20

781 805

4- 14 Mounting hole

1011 1035

4- 14 Mounting hole

3P

4P

4000A~5000A
90 (Insulation barrier) 15

6300A
90 (Insulation barrier) 15 20

125

270

58 183

270

39.5 125 102

20.5

65

20

165 295

45 67.5

65

20

165 295

45 67.5

100

42 20 97

95

95

18

70

20

83 193

20

70

20

165

45

60 35 95
12

80

80

380

Horizontal type
4000A~5000A
244 244 125 244 244 244 125

45

165

20

781 805

4- 14 Mounting hole

1011 1035

4- 14 Mounting hole

3P

4P

6300A
244 244 150 244 244 244 150

45

165

20

781 805

4- 14 Mounting hole

1011 1035

4- 14 Mounting hole

3P

4P

15

90 (Insulation barrier)

270

65

20

165 295

18

45 67.5

42 20 97

95

70

20

83 193

20

70

20

20

165

45

20

165

45

101

Dimensions
Draw-out type 6300AF (4000A~6300A: AH/AS-40~50G)
Front view
20 845 186.5 Operating panel center 20 20 1075 301.5 Operating panel center 20

2-M12 Tap CMB-U/F

2-M12 Tap CMB-U/F

435 460

260

113 785

260

260

343 1015

260

3P

4P

4000A~5000A
34 15

6300A

34 15

25

25 25 125

25

5- 13

6- 13

<Conductor>

<Conductor>

Vertical type
244 244 20 70 20 244 244 244 20 70 20

115

200

200

115

260

113

260

260

25

25

25 150

25

25

343

260

3P

4P

4000A~5000A
Disconnected & Test Connected 50 15 55 Arc chute surface 90 (Insulation barrier)

6300A
Disconnected & Test Connected 50 55 15 Arc chute surface 90 (Insulation barrier)

125

A
270

A
270

58 183 380

39.5 125 102

36 41 18

36 41 18

150

10

200 375

115 53.5 10

200 375

115 53.5

102

6- 13 Mounting hole

6- 13 Mounting hole

27

102

33 183 380

150

435 460

Horizontal type
4000A~5000A
244 244 125 244 244 244 125

200

115

260

113

260

200

115

260

343

260

3P

4P

6300A

244

244 150 150

244

244

244

115

200

260

113

260

200

115

260

343

260

3P

4P

50

Disconnected & Test Connected 55 Arc chute surface 90 (Insulation barrier)

15

270

20 110
10 200 375 115 63.5 6- 13 Mounting hole

36 41 18

42

97

83 193 380

70 20 110

103

Technical information
Insulation voltage
You should keep the isolation distance between ACB and panel as below table.

B (AH)

OPEN

CLOSE

000001

A Type Fixed Draw out AN/AS AH AN/AS AH A 50 50 50 50

A B 150 150 150 0

Note) When drawing the distribution panel, it is available to use regardless of the distance between ACB and the wall of the panel because Susol ACB(draw-in/out type) extinguishes the arc in the Arc Chute and Arc Cover clearly.

Minimum isolation distance


For the safety, all the electric charging parts need to be installed over minimum isolation distance.

Insulating voltage (Ui) 600V


X

Minimum isolation distance (X min) 8 mm 14 mm

1000V

Bolt
Washers 40-50Nm

Bolt

Washers

Bolt

Nut
Busher 25

Screw type M8 M10 M12

Tightening torque Standard(kgfcm) 135 270 480 Tolerance 16 32 57 Standard(N.m) 13.3 26.5 46.6 Tolerance 1.6 3.2 5.6

104

B (AN, AS)

Temperature derating
The table below indicates the maximum current rating, for each connection type, as a function of the ambient temperature around the circuit breaker and the busbars. Circuit breakers with mixed connections have the same derating as horizontally connected breakers. For ambient temperatures greater than 60C, consult us. Temperature inside the switchboard around the circuit breaker and its connection: Ti(IEC 60947-2)

Frame

Rated current

ACB terminal

Applicable busbar size

Horizontal type 1600AF AN-D AS-D AH-D 200A 400A 630A 800A 1,000A 1,250A 15t501EA 40C 200A 400A 630A 800A 45C 200A 400A 630A 800A 50C 200A 400A 630A 800A 55C 200A 400A 630A 800A 60C 200A 400A 630A 800A 40C 200A 400A 630A 800A

Vertical type 45C 200A 400A 630A 800A 50C 200A 400A 630A 800A 55C 200A 400A 630A 800A 60C 200A 400A 630A 800A

5t501EA 5t502EA 10t601EA 6t502EA 10t601EA 8t502EA 6t752EA 8t602EA 10t502EA 6t753EA 10t602EA 8t603EA 8t753EA 10t1002EA 5t502EA 10t601EA 6t502EA 10t601EA 8t502EA 6t752EA 8t602EA 10t502EA 6t753EA 10t602EA 8t603EA 8t753EA 10t1002EA 10t753EA 8t754EA 10t1003EA 10t754EA 10t1004EA 10t755EA 10t1004EA 10t1254EA 10t1004EA 10t1254EA 10t1504EA

1000A 1000A 1000A 1000A 1000A 1000A 1000A 1000A 1000A 1000A 1250A 1250A 1250A 1250A 1250A 1250A 1250A 1250A 1250A 1250A 1600A 1600A 1580A 1550A 1500A

1,600A 2000AF AS/AH-D 3200AF AN-E AS-E AH-E

1600A 1600A 1520A 1480A 1420A 630A 800A 630A 800A 630A 800A 630A 800A 630A 800A

2,000A 630A 800A 1,000A 1,250A

15t751EA

2000A 2000A 1940A 1860A 1780A 630A 800A 630A 800A 630A 800A 630A 800A 630A 800A

1000A 1000A 1000A 1000A 1000A 1000A 1000A 1000A 1000A 1000A 1250A 1250A 1250A 1250A 1250A 1250A 1250A 1250A 1250A 1250A 1600A 1600A 1600A 1600A 1600A

20t751EA 1,600A

1600A 1600A 1600A 1600A 1600A

2,000A 2,500A 3,200A 4000AF AS/AH-E 5000AF AS-F 6300AF AS-G AH-G 4,000A 4,000A 5,000A 4,000A 5,000A 6,300A 10t1003EA 20t1252EA 20t1252EA 20t1502EA

2000A 2000A 2000A 2000A 2000A 2000A 2000A 2000A 2000A 2000A 2500A 2500A 2500A 2400A 2300A 2500A 2500A 2500A 2500A 2400A 3200A 4000A 4000A 5000A 4000A 5000A 6300A 3200A 4000A 4000A 5000A 4000A 5000A 6300A 3100A 3900A 3920A 4900A 4000A 4900A 6170A 3000A 3800A 3860A 4800A 4000A 4820A 6040A 2900A 3640A 3800A 4700A 4000A 4750A 5900A 3200A 3200A 3120A 3050A 2950A 4000A 4000A 3950A 3800A 3680A 4000A 5000A 4000A 5000A 6300A 4000A 5000A 4000A 5000A 6300A 3960A 4950A 4000A 4950A 6220A 3900A 4900A 4000A 4870A 6160A 3880A 4850A 4000A 4850A 6100A

105

Technical information
Operating conditions
Ambient temperature
ACB devices can operate under the following temperature conditions - The electrical and mechanical characteristics are stipulated for an ambient temperature of -5C to +40C - The average temperature should be within + 35C - Reduce the continuous conducting current when the temperature is over 45C (refer to temperature derating) - Storage condition : -20C to + 60C is recommended.

Altitude
Susol ACB is designed for operation at altitudes under 2000m. At altitudes higher than 2000m, emitting heat is lowered and operating voltage, continuous current capacity, and breaking capacity will be reduced. Durability of the insulation is also reduced according to the atmosphere pressure. According to the below table, change the ratings upon a service condition.
Altitude [m] Item Withstand voltage [V] Average insulating voltage [v] Max. using voltage [V] Current compensation constant 2000m 3500 1000 690 1In 3000m 3150 900 590 0.99In 4000m 2500 700 520 0.96In 5000m 2100 600 460 0.94In

Environment
Under clean air; Maximum temperature + 40C (relative humidity should be under 85%) Maximum temperature + 20C (relative humidity should be under 90%) Do not apply under corrosive or ammonia gas circumstances (H2S 0.01ppm, SO2 0.01ppm, NH3 a few ppm) * Extreme atmosphere conditions Under high temperature and/or high humidity, the insulation durability, electrical and mechanical features could be deteriorated. At this conditions, increasing corrosion-resistant dealing needs. Corrosion-resistant parts need under this conditions.

Internal resistance and power consumption (per pole)


AF Rated current (A) 630 800 1,000 1,250 1,600 630 800 1,000 1,250 1,600 2,000 2,000 2,500 3,200 2,000 2,500 3,200 4,000 4,000 5,000 4,000 5,000 6,300 Fixed type Draw-out type Inner resistance Power consumption Inner resistance Power consumption (W/3Phase) (m) (W/3Phase) (m) 0.02 0.02 0.02 0.02 0.02 0.015 0.015 0.015 0.015 0.015 0.013 0.01 0.01 0.01 0.01 0.01 0.01 0.008 0.008 0.008 0.006 0.006 0.005 24 38 60 94 154 18 29 45 70 115 156 120 188 307 120 188 307 384 384 600 288 450 595 0.04 0.04 0.04 0.04 0.04 0.03 0.03 0.03 0.03 0.03 0.027 0.02 0.02 0.02 0.02 0.02 0.02 0.011 0.011 0.011 0.009 0.009 0.007
3. Power factor = 1.0

AN-16D

AH/AS-20D

AH/AS-32E

AH/AS-40E

AS-50F AH/AS-63G

48 77 120 188 307 36 58 90 141 230 324 240 375 614 240 375 614 528 528 825 432 675 833

106

Note) 1. Above power consumption is whole power consumption for each Rated current, 50/60Hz, 3/4pole. 2. This is inner assistant value per 1 pole.

Installation recommendation
BUS-BAR Connection

Cables connections Make sure that no excessive mechanical force put on the rear terminals for cable connection. Extension terminal is fixed such as B, C and cable is to fixed to the frame such as E

Bus-bar connection For busbar connection, connect access parts with a provided torque and fix with parallel installing the support not to apply terminal weight to circuit breaker. In order to prevent the spread safety or secondary accidents, secure maximum safe distance A (Table 1) from the access area to withstand the electrical force during the short circuit faults.

(Table 1) Maximum safe distance A

Short capacity (kA) Length A (mm)

30 350

50 300

65 250

80 150

100 150

150 150

107

Technical information
Installation recommendation

Protection degree provided by enclosures (IP Code) IEC 60529


IP First characteristic numeral (numerals 0 to 6, or letter ) Second characteristic numeral (numerals 0 to 8, or letter ) Code letters (international Protection)

First characteristic numeral


Degree of protection Brief description 0 1 2 3 4 Non-protected Protected against solid foreign objects of 50mm and greater Protected against solid foreign objects of 12.5mm and greater Protected against solid foreign objects of 2.5mm and greater Protected against solid foreign objects of 1.0mm and greater Dust-protected Dust-tight Definition The object probe sphere of 50mm , shall not fully penetrate The object probe sphere of 12.5mm , shall not fully penetrate The object probe sphere of 2.5mm , shall not penetrate at all The object probe of 1.0mm , shall not penetrate at all Ingress of dust is not totally prevented, but dust shall not penetrate in a quantity to interfere with satisfactory operation of the apparatus or to impair safety No ingress of dust

5 6

Second characteristic numeral


Degree of protection Brief description 0 1 Non-protected Protected against vertically falling water drops Protected against vertically falling water drops when enclosure tilted up to 15 Protected against spraying water Protected against spraying water Protected against spraying jets Protected against powerful water jets Protected against the effects of temporary immersion in water Definition Vertically falling drops shall have no harmful effects Vertically falling drops shall have no harmful effects when the enclosure is tilted at any angle up to 15 on either side of the vertical Water sprayed at an angle up to 60 wither side of on the vertical shall have no harmful effects Water splashed against the enclosure from and direction shall have no harmful effects Water projected in powerful jets against the enclosure from and direction shall have no harmful effects Water projected in powerful jets against the enclosure from any direction shall have no harmful effects Ingress of water in quantities causing harmful effects shall not be possible when the enclosure is temporarily immersed in water under standardized conditions of pressure and time Ingress of water in quantities causing harmful effects shall not be possible when the enclosure is continuously immersed in water under conditions which shall be agreed between manufacturer and used but which are more severs than for numeral 7

3 4 5 6

Protected against the effects of continuous immersion in water

108

Derating table
ambient temperature outside of the switchboard:Ta (IEC 60439-1)

Switchboard compsition (2300800900)


4 3 2 1

Connection type

Model type Busbar dimensions(mm)


Ventilated switchboard(IP31)

Model type AS/AH-06/08E, AN-06/08D 2EA-506 Ta=35 4 3 2 1 Ta=45 4 3 2 1 Ta=55 4 3 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 1000 800 800 800 800 800 800 800 1000 800 800 800 800 2 1 Ta=35 4 3 2 1 Ta=45 4 3 2 1 Ta=55 4 3 2 1 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 1000 1000 1000 1000

AS/AH-10E, AN-10D 2EA-508 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000

Area of outlet vents: 350cm Area of intlet vents: 350cm2

Non Ventilated switchboard(IP41/54)

109

Technical information
Installation recommendation

Derating table
ambient temperature outside of the switchboard:Ta (IEC 60439-1)

Switchboard compsition (2300800900)


4 3 2 1

Connection type

Model type Busbar dimensions(mm)


Ventilated switchboard(IP31)

AS/AH-13E, AN-13D 2EA-756 Ta=35 4 3 2 1 Ta=45 4 3 2 1 Ta=55 4 3 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 2 1 Ta=35 4 3 2 1 Ta=45 4 3 2 1 Ta=55 4 3 2 1 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250

AS/AH-16E, AN-16D 2EA-6010

1600 1600 1600 1600

1600 1600 1600 1600

Area of outlet vents: 350cm Area of intlet vents: 350cm2

1470 1500 1600 1600

Non Ventilated switchboard(IP41/54)

1600 1600 1600 1600

1500 1480 1600 1600

1400 1400 1520 1500

110

ambient temperature outside of the switchboard:Ta (IEC 60439-1)

Switchboard compsition (2300800900)


4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1

Connection type

Model type Busbar dimensions(mm)


Ventilated switchboard(IP31)

AN/AS/AH-20E, 2EA-7510 Ta=35 4 3 2 1 Ta=45 4 3 2 1 Ta=55 4 3 2000 2000 2000 2000 2 1 Ta=35 4 3 2 1 Ta=45 4 3 2 1 Ta=55 4 3 2 1 1800 1920 1780 1920 1900 1960 1900 1960 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000

AN/AS/AH-25E 3EA-7510

AN/AS/AH-32E 4EA-7510

AS/AH-40E 4EA-7510

2400

2500

3100

3200

3400

3750

2300

2400

2900

3100

3200

3550

Area of outlet vents: 350cm Area of intlet vents: 350cm2

2200

2300

2700

2900

3000

3300

Non Ventilated switchboard(IP41/54)

2115

2275

2650

2850

3040

3320

2000

2150

2550

2700

2880

3120

1900

2020

2370

2530

2720

2960

111

Technical information
Installation recommendation

Derating table
ambient temperature outside of the switchboard:Ta (IEC 60439-1)

Switchboard compsition (2300800900)


4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1

Connection type

Model type Busbar dimensions(mm)


Ventilated switchboard(IP31)

AS-40F 4EA-10010 Ta=35 4 3 2 1 Ta=45 4 3 2 1 Ta=55 4 3 2 1 Ta=35 4 3 2 1 Ta=45 4 3 2 1 Ta=55 4 3 2 1 3550 3650 3650 3800 3800 3900 3800 3850 3850 3900 3900 4000

AS-50F 4EA-12510

AS/AH-63G 4EA-10010

AS/AH-50G 4EA-12510

AS/AH-63G 4EA-15010

4750

4800

4000

4000

4750

5000

5850

6300

4350

4650

4000

4000

4450

4850

5670

5850

Area of outlet vents: 500cm Area of intlet vents: 500cm2

4200

4400

4000

4000

4200

4600

5350

5670

Non Ventilated switchboard(IP41/54)

4200

4550

4000

4000

4400

4650

5350

5000

3950

4250

4000

4000

4100

4400

5040

5350

3700

4050

3900

3950

3850

4150

4730

5040

112

AH-D,W

Protective coordination
AC 220/240V

Rated voltage: AC 220/240V Main breaker(Main ACB): Susol ACB Downstream breaker(Downstream MCCB): Susol MCCB TD/TS series Below protective coordination table is based on ACB equipped with OCR under arrangement of short time delay trip current as 10 times of rated current.

Susol MCCB

Susol AH series Upstream breaker Product type AH-06D Rated current [A] Short time delay trip current (Max. 10In) Is [kA] Rated current Ultimate breaking capacity Icu [kA] [A] 100 100 100 160 160 160 100 100 100 160 160 160 250 250 250 400 400 400 630 630 630 800 800 800 85 100 200 85 100 200 100 120 200 100 120 200 100 120 200 100 120 200 100 120 200 100 120 200 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 200 3 400 6 630 9.45 400 6 AH-D,W AH-08D 630 9.45 800 12 AH-10D AH-13D AH-16D AH-20D 1000 15 1250 18.75 1600 24 2000 30

Downstream breaker

Model TD100N TD100H TD100L TD160N TD160H TD160L TS100N TS100H TS100L TS160N TS160H Susol MCCB TS160L TS250N TS250H TS250L TS400N TS400H TS400L TS630N TS630H TS630L TS800N TS800H TS800L

85 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

Note) 1. On table, protective coordination is not available for areas where number is missing. 2. On table, marked number is breaking capacity limit (Unit: kA) for protective coordination. 3. On table, areas that is marked as T are capable of total discrimination up to its Downstream breaker rated short breaking capacity. s

113

Technical information
AH-E,X AH-G,Z

Protective coordination
AC 220/240V

Rated voltage: AC 220/240V Main breaker(Main ACB): Susol ACB Downstream breaker(Downstream MCCB): Susol MCCB TD/TS series Below protective coordination table is based on ACB equipped with OCR under arrangement of short time delay trip current as 10 times of rated current.
Susol AH series Upstream breaker Product type AH-06E Rated current [A] Short time delay trip current (Max. 10In) Is[kA] Rated Ultimate breaking current [A] capacity Icu [kA] 100 100 100 160 160 160 100 100 100 160 160 160 250 250 250 400 400 400 630 630 630 800 800 800 85 100 200 85 100 200 100 120 200 100 120 200 100 120 200 100 120 200 100 120 200 100 120 200 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 400 6 630 9.45 800 12 1000 15 AH-E,X 1250 18.75 1600 24 2000 30

Susol MCCB

AH-G,Z 2500 37.5 3200 48 4000 60 4000 60 5000 75 6300 94.5

AH-08E AH-10E AH-13E AH-16E AH-20E AH-25E AH-32E AH-40E AH-40G AH-50G AH-63G

Downstream breaker

Model TD100N TD100H TD100L TD160N TD160H TD160L TS100N TS100H TS100L TS160N TS160H Susol TS160L MCCB TS250N TS250H TS250L TS400N TS400H TS400L TS630N TS630H TS630L TS800N TS800H TS800L

100 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

150 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

Note) 1. On table, protective coordination is not available for areas where number is missing. 2. On table, marked number is breaking capacity limit (Unit: kA) for protective coordination. 3. On table, areas that is marked as T are capable of total discrimination up to its Downstream breaker rated short breaking capacity. s

114

AH-D,W

AC 380/415V

Rated voltage: AC 380/415V Main breaker(Main ACB): Susol ACB Downstream breaker(Downstream MCCB): Susol MCCB TD/TS series Below protective coordination table is based on ACB equipped with OCR under arrangement of short time delay trip current as 10 times of rated current.

Susol MCCB

Susol AH series Upstream breaker Product type AH-06D Rated current [A] Short time delay trip current (Max. 10In) Is [kA] Rated current Ultimate breaking [A] capacity Icu [kA] 100 100 100 160 160 160 100 100 100 160 160 160 250 250 250 400 400 400 630 630 630 800 800 800 50 85 150 50 85 150 50 85 150 50 85 150 50 85 150 65 85 150 65 85 150 65 100 150 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 200 3 400 6 630 9.45 400 6 AH-D,W AH-08D 630 9.45 800 12 AH-10D AH-13D AH-16D AH-20D 1000 15 1250 18.75 1600 24 2000 30

Downstream breaker

Model TD100N TD100H TD100L TD160N TD160H TD160L TS100N TS100H TS100L TS160N TS160H Susol MCCB TS160L TS250N TS250H TS250L TS400N TS400H TS400L TS630N TS630H TS630L TS800N TS800H TS800L

85 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

Note) 1. On table, protective coordination is not available for areas where number is missing. 2. On table, marked number is breaking capacity limit (Unit: kA) for protective coordination. 3. On table, areas that is marked as T are capable of total discrimination up to its Downstream breaker rated short breaking capacity. s

115

Technical information
AH-E,X AH-G,Z

Protective coordination
AC 380/415V

Rated voltage: AC 380/415V Main breaker(Main ACB): Susol ACB Downstream breaker(Downstream MCCB): Susol MCCB TD/TS series Below protective coordination table is based on ACB equipped with OCR under arrangement of short time delay trip current as 10 times of rated current.
Susol AH series Upstream breaker Product type AH-06E Rated current [A] Short time delay trip current (Max. 10In) Is[kA] Rated Ultimate breaking current [A] capacity Icu [kA] 100 100 100 160 160 160 100 100 100 160 160 160 250 250 250 400 400 400 630 630 630 800 800 800 50 85 150 50 85 150 50 85 150 50 85 150 50 85 150 65 85 150 65 85 150 65 100 150 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 400 6 630 9.45 800 12 1000 15 AH-E,X 1250 18.75 1600 24 2000 30

Susol MCCB

AH-G,Z 2500 37.5 3200 48 4000 60 4000 60 5000 75 6300 94.5

AH-08E AH-10E AH-13E AH-16E AH-20E AH-25E AH-32E AH-40E AH-40G AH-50G AH-63G

Downstream breaker

Model TD100N TD100H TD100L TD160N TD160H TD160L TS100N TS100H TS100L TS160N TS160H Susol TS160L MCCB TS250N TS250H TS250L TS400N TS400H TS400L TS630N TS630H TS630L TS800N TS800H TS800L

100 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

150 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

Note) 1. On table, protective coordination is not available for areas where number is missing. 2. On table, marked number is breaking capacity limit (Unit: kA) for protective coordination. 3. On table, areas that is marked as T are capable of total discrimination up to its Downstream breaker rated short breaking capacity. s

116

AH-D,W

AC 480/500V

Rated voltage: AC 480/500V Main breaker(Main ACB): Susol ACB Downstream breaker(Downstream MCCB): Susol MCCB TD/TS series Below protective coordination table is based on ACB equipped with OCR under arrangement of short time delay trip current as 10 times of rated current.

Susol MCCB

Susol AH series Upstream breaker Product type AH-06D Rated current [A] Short time delay trip current (Max. 10In) Is [kA] Rated current Ultimate breaking [A] capacity Icu [kA] 100 100 100 160 160 160 100 100 100 160 160 160 250 250 250 400 400 400 630 630 630 800 800 800 30 50 65 30 50 65 42 65 85 42 65 85 42 65 85 42 65 85 42 65 85 42 85 100 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 200 3 400 6 630 9.45 400 6 AH-D,W AH-08D 630 9.45 800 12 AH-10D AH-13D AH-16D AH-20D 1000 15 1250 18.75 1600 24 2000 30

Downstream breaker

Model TD100N TD100H TD100L TD160N TD160H TD160L TS100N TS100H TS100L TS160N TS160H Susol MCCB TS160L TS250N TS250H TS250L TS400N TS400H TS400L TS630N TS630H TS630L TS800N TS800H TS800L

85 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

Note) 1. On table, protective coordination is not available for areas where number is missing. 2. On table, marked number is breaking capacity limit (Unit: kA) for protective coordination. 3. On table, areas that is marked as T are capable of total discrimination up to its Downstream breaker rated short breaking capacity. s

117

Technical information
AH-E,X AH-G,Z

Rated voltage: AC 480/500V Main breaker(Main ACB): Susol ACB Downstream breaker(Downstream MCCB): Susol MCCB TD/TS series Below protective coordination table is based on ACB equipped with OCR under arrangement of short time delay trip current as 10 times of rated current.

AC 480/500V

Susol MCCB

Susol AH series Upstream breaker Product type AH-06E Rated current [A] Short time delay trip current (Max. 10In) Is[kA] Rated Ultimate breaking current [A] capacity Icu [kA] 100 100 100 160 160 160 100 100 100 160 160 160 250 250 250 400 400 400 630 630 630 800 800 800 30 50 65 30 50 65 42 65 85 42 65 85 42 65 85 42 65 85 42 65 85 42 85 100 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 400 6 630 9.45 800 12 1000 15 AH-E,X 1250 18.75 1600 24 2000 30 2500 37.5 3200 48 4000 60 4000 60 AH-G,Z 5000 75 6300 94.5 AH-08E AH-10E AH-13E AH-16E AH-20E AH-25E AH-32E AH-40E AH-40G AH-50G AH-63G

Downstream breaker

Model TD100N TD100H TD100L TD160N TD160H TD160L TS100N TS100H TS100L TS160N TS160H Susol TS160L MCCB TS250N TS250H TS250L TS400N TS400H TS400L TS630N TS630H TS630L TS800N TS800H TS800L

100 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

150 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

Note) 1. On table, protective coordination is not available for areas where number is missing. 2. On table, marked number is breaking capacity limit (Unit: kA) for protective coordination. 3. On table, areas that is marked as T are capable of total discrimination up to its Downstream breaker rated short breaking capacity. s

118

Standards & Approval


AH, AS, AN series Air Circuit Breakers comply with the following international standard;
IEC 60947-1 Low-voltage switchgear and controlgear - Part 1: General rules IEC 60947-2 Low-voltage switchgear and controlgear - Part 2: Circuit-breakers The following certificates are available on a request. - CE Declaration of conformity - Certificate of conformance test (CB) - IEC 60947 - Full type test report issued by KEMA - Letter of origin - Taiwan TPC

CE conformity marking
The CE conformity marking shall indicate conformity to all the obligations imposed on the manufacturer, as regards his products, by virtue of the European Community directives providing for the affixing of the CE marking. When the CE marking is affixed on a product, it represents a declaration of the manufacturer or of his authorized representative that the product in question conforms to all the applicable provisions including the conformity assessment procedures. This prevents the Member States from limiting the marketing and putting into service of products bearing the CE marking, unless this measure is justified by the proved non-conformity of the product.

IECEE CB SCHEME
The IECEE CB Scheme is the world's first truly international system for acceptance of test reports dealing with the safety of electrical and electronic products. It is a multilateral agreement among participating countries and certification organizations. A manufacturer utilizing a CB test report issued by one of these organizations can obtain national certification in all other member countries of the CB Scheme. The Scheme is based on the use of international (IEC) Standards. If some members' national standards are not yet completely harmonized with IEC Standards, national differences are permitted if clearly declared to all other members. The CB Scheme utilizes CB Test Certificates to attest that product samples have successfully passed the appropriate tests and are in compliance with the requirements of the relevant IEC Standard and with the declared national differences of various member countries. The main objective of the Scheme, is to facilitate trade by promoting harmonization of the national standards with international Standards and cooperation among product certifiers worldwide in order to bring product manufacturers a step closer to the ideal concept of "one product, one test, one mark, where applicable'. - LR, ABS, DNV, KR, BV, GL, RINA, NK - GOST, TPC

119

Time chart
Long time
tr Ir 1.11 1.15 1.20 1.25 1.30 1.35 1.40 1.45 1.50 1.55 1.60 1.65 1.70 1.75 1.80 1.85 1.90 1.95 2.00 2.05 2.10 2.15 2.20 2.25 2.30 2.35 2.40 2.45 2.50 2.55 2.60 2.65 2.70 2.75 2.80 2.85 2.90 2.95 3.00 3.05 3.10 3.15 3.20 3.25 3.30 3.35 3.40 3.45 3.50 3.55 3.60 3.65 3.70 3.75 3.80 3.85 3.90 0.5 1 2 4 8 12 16 20 58806 117611 235223 470445 940890 1411335 1881780 2352225 36041 72082 144163 288326 576652 864978 1153305 1441631 26827 53654 107308 214615 429231 643846 858461 1073077 21777 43553 87106 174212 348424 522636 696848 871060 18408 36817 73634 147268 294535 441803 589071 736338 15947 31895 63789 127579 255157 382736 510314 637893 14049 28098 56197 112393 224787 337180 449573 561967 12532 25063 50126 100252 200504 300756 401009 501261 11286 22573 45145 90290 180580 270870 361160 451450 10244 20488 40977 81954 163907 245861 327814 409768 9359 18717 37434 74869 149737 224606 299474 374343 8596 17193 34386 68771 137542 206313 275084 343855 7934 15867 31734 63468 126936 190404 253873 317341 7352 14704 29408 58815 117631 176446 235261 294077 6838 13675 27351 54702 109404 164106 218808 273509 6380 12760 25521 51041 102082 153123 204164 255205 5970 11941 23882 47764 95528 143292 191056 238820 5602 11204 22408 44815 89630 134446 179261 224076 5269 10537 21075 42150 84299 126449 168598 210748 4966 9932 19865 39730 79459 119189 158919 198649 4691 9381 18762 37525 75049 112574 150099 187623 4439 8877 17754 35508 71017 106525 142034 177542 4207 8415 16829 33659 67318 100976 134635 168294 3995 7989 15979 31957 63914 95871 127829 159786 3798 7597 15194 30387 60775 91162 121550 151937 3617 7234 14468 28936 57871 86807 115742 144678 3449 6897 13795 27590 55180 82769 110359 137949 3292 6585 13170 26339 52679 79018 105358 131697 3147 6294 12588 25176 50351 75527 100702 125878 3011 6022 12045 24090 48180 72269 96359 120449 2884 5769 11538 23075 46151 69226 92301 115377 2766 5531 11063 22126 44251 66377 88503 110628 2654 5309 10618 21235 42471 63706 84941 106177 2550 5100 10200 20399 40799 61198 81597 101997 2452 4903 9807 19613 39226 58840 78453 98066 2359 4718 9436 18873 37746 56619 75491 94364 2272 4544 9087 18175 36350 54524 72699 90874 2189 4379 8758 17516 35032 52547 70063 87579 2112 4223 8446 16893 33786 50679 67572 84464 2038 4076 8152 16303 32607 48910 65214 81517 1968 3936 7872 15745 31490 47235 62980 78725 1902 3804 7608 15215 30431 45646 60862 76077 1839 3678 7356 14713 29425 44138 58851 73563 1779 3559 7117 14235 28470 42705 56940 71175 1723 3445 6890 13781 27561 41342 55122 68903 1669 3337 6674 13348 26696 40044 53392 66741 1617 3234 6468 12936 25872 38808 51744 64680 1568 3136 6272 12543 25086 37629 50172 62715 1521 3042 6084 12168 24336 36504 48672 60841 1476 2952 5905 11810 23620 35430 47240 59050 1433 2867 5734 11468 22935 34403 45871 57338 1393 2785 5570 11140 22281 33421 44561 55702 1353 2707 5413 10827 21654 32481 43308 54135 1316 2632 5263 10527 21054 31581 42108 52634 1280 2560 5120 10239 20479 30718 40957 51196 1245 2491 4982 9963 19927 29890 39854 49817 1212 2425 4849 9699 19398 29096 38795 48494 tr Ir 3.95 4.00 4.05 4.10 4.15 4.20 4.25 4.30 4.35 4.40 4.45 4.50 4.55 4.60 4.65 4.70 4.75 4.80 4.85 4.90 4.95 5.00 5.05 5.10 5.15 5.20 5.25 5.30 5.35 5.40 5.45 5.50 5.55 5.60 5.65 5.70 5.75 5.80 5.85 5.90 5.95 6.00 6.05 6.10 6.15 6.20 6.25 6.30 6.35 6.40 6.45 6.50 6.55 6.60 6.65 6.70 6.75 0.5 1181 1150 1121 1093 1065 1039 1014 990 966 944 922 901 881 861 842 824 806 789 772 756 741 726 711 697 683 670 657 644 632 620 608 597 586 575 565 555 545 536 526 517 509 500 492 483 476 468 460 453 446 439 432 425 418 412 406 400 394 1 2361 2300 2241 2185 2131 2079 2028 1980 1933 1888 1844 1802 1762 1722 1684 1648 1612 1578 1545 1513 1481 1451 1422 1393 1366 1339 1313 1288 1263 1240 1217 1194 1172 1151 1130 1110 1091 1071 1053 1035 1017 1000 983 967 951 936 920 906 891 877 863 850 837 824 811 799 787 2 4722 4600 4483 4370 4262 4157 4056 3959 3866 3776 3688 3604 3523 3445 3369 3295 3225 3156 3089 3025 2963 2902 2844 2787 2732 2678 2626 2576 2527 2479 2433 2388 2344 2302 2261 2220 2181 2143 2106 2070 2034 2000 1967 1934 1902 1871 1841 1811 1782 1754 1727 1700 1674 1648 1623 1598 1575 4 9445 9201 8966 8740 8523 8314 8113 7919 7731 7551 7377 7209 7046 6889 6738 6591 6449 6312 6179 6050 5925 5804 5687 5574 5463 5356 5252 5152 5054 4959 4866 4776 4689 4604 4521 4441 4362 4286 4212 4139 4069 4000 3933 3868 3804 3742 3682 3622 3565 3508 3453 3400 3347 3296 3246 3197 3149 8 18889 18401 17932 17481 17046 16628 16225 15837 15463 15102 14754 14417 14093 13779 13475 13182 12898 12624 12358 12100 11851 11609 11374 11147 10927 10713 10505 10303 10107 9917 9732 9552 9378 9207 9042 8881 8724 8572 8423 8279 8138 8000 7866 7736 7608 7484 7363 7245 7129 7017 6907 6799 6694 6592 6492 6394 6298 12 28334 27602 26898 26221 25569 24942 24338 23756 23194 22653 22131 21626 21139 20668 20213 19773 19347 18935 18536 18150 17776 17413 17062 16721 16390 16069 15757 15455 15161 14876 14598 14329 14066 13811 13563 13322 13087 12858 12635 12418 12206 12000 11799 11604 11413 11226 11045 10867 10694 10525 10360 10199 10042 9888 9738 9591 9447 16 37779 36802 35864 34961 34092 33256 32451 31674 30926 30204 29507 28835 28185 27557 26951 26364 25796 25247 24715 24200 23701 23218 22749 22294 21853 21425 21010 20607 20215 19834 19464 19105 18755 18415 18084 17762 17449 17144 16847 16557 16275 16000 15733 15471 15217 14968 14726 14490 14259 14034 13814 13599 13389 13184 12984 12788 12597 20 47223 46003 44830 43701 42615 41570 40563 39593 38657 37755 36884 36043 35231 34447 33688 32955 32245 31559 30894 30250 29627 29022 28436 27868 27317 26782 26262 25758 25268 24793 24330 23881 23444 23019 22605 22203 21811 21430 21058 20697 20344 20001 19666 19339 19021 18710 18408 18112 17823 17542 17267 16998 16736 16480 16230 15985 15746

120

tr Ir 6.80 6.85 6.90 6.95 7.00 7.05 7.10 7.15 7.20 7.25 7.30 7.35 7.40 7.45 7.50 7.55 7.60 7.65 7.70 7.75 7.80 7.85 7.90 7.95 8.00 8.05 8.10 8.15 8.20 8.25 8.30 8.35 8.40 8.45 8.50 8.55 8.60 8.65 8.70 8.75 8.80 8.85 8.90 8.95 9.00 9.05 9.10 9.15 9.20 9.25 9.30 9.35 9.40 9.45 9.50 9.55 9.60

0.5 388 382 376 371 366 360 355 350 345 341 336 331 327 322 318 314 310 306 302 298 294 290 286 283 279 276 272 269 266 262 259 256 253 250 247 244 241 238 236 233 230 228 225 223 220 218 215 213 211 208 206 204 202 200 197 195 193

1 776 764 753 742 731 721 711 701 691 681 672 663 654 645 636 628 619 611 603 595 588 580 573 565 558 551 544 538 531 525 518 512 506 500 494 488 482 477 471 466 461 455 450 445 440 435 431 426 421 417 412 408 403 399 395 391 387

2 1551 1528 1506 1484 1463 1442 1421 1401 1382 1362 1344 1325 1307 1289 1272 1255 1239 1222 1206 1191 1175 1160 1145 1131 1117 1103 1089 1076 1062 1049 1037 1024 1012 1000 988 976 965 954 943 932 921 911 901 890 880 871 861 852 842 833 824 815 807 798 790 781 773

4 3102 3057 3012 2968 2925 2884 2843 2803 2763 2725 2687 2650 2614 2579 2544 2510 2477 2444 2412 2381 2350 2320 2291 2262 2233 2205 2178 2151 2125 2099 2073 2048 2024 2000 1976 1953 1930 1908 1886 1864 1843 1822 1801 1781 1761 1741 1722 1703 1685 1666 1648 1631 1613 1596 1579 1563 1546

8 6205 6113 6024 5936 5851 5767 5685 5605 5527 5450 5374 5301 5229 5158 5089 5021 4954 4889 4825 4762 4701 4640 4581 4523 4466 4411 4356 4302 4249 4197 4147 4097 4048 3999 3952 3906 3860 3815 3771 3728 3685 3643 3602 3562 3522 3483 3444 3407 3369 3333 3297 3261 3227 3192 3159 3125 3093

12 9307 9170 9036 8905 8776 8651 8528 8408 8290 8175 8062 7951 7843 7737 7633 7531 7431 7333 7237 7143 7051 6961 6872 6785 6700 6616 6534 6453 6374 6296 6220 6145 6071 5999 5928 5858 5790 5723 5657 5592 5528 5465 5403 5343 5283 5224 5167 5110 5054 4999 4945 4892 4840 4788 4738 4688 4639

16 12410 12227 12048 11873 11702 11534 11371 11210 11053 10899 10749 10601 10457 10316 10177 10041 9908 9778 9650 9524 9401 9281 9163 9047 8933 8821 8712 8604 8498 8395 8293 8193 8095 7999 7904 7811 7720 7630 7542 7455 7370 7287 7204 7123 7044 6966 6889 6813 6739 6666 6594 6523 6453 6384 6317 6251 6185

20 15512 15283 15060 14841 14627 14418 14213 14013 13816 13624 13436 13252 13071 12895 12721 12552 12385 12222 12062 11906 11752 11601 11453 11308 11166 11026 10889 10755 10623 10494 10366 10242 10119 9998 9880 9764 9650 9538 9428 9319 9213 9108 9005 8904 8805 8707 8611 8516 8423 8332 8242 8153 8066 7981 7896 7813 7732

tr Ir 9.65 9.70 9.75 9.80 9.85 9.90 9.95 10.00

0.5 191 189 187 185 184 182 180 178

1 383 379 375 371 367 363 360 356

2 765 757 749 742 734 727 719 712

4 1530 1514 1499 1483 1468 1453 1439 1424

8 3060 3029 2998 2967 2937 2907 2878 2849

12 4591 4543 4496 4450 4405 4360 4316 4273

16 6121 6058 5995 5934 5873 5814 5755 5697

20 7651 7572 7494 7417 7342 7267 7194 7122

Short time
tsd Ir 1.40 1.45 1.50 1.55 1.60 1.65 1.70 1.75 1.80 1.85 1.90 1.95 2.00 2.05 2.10 2.15 2.20 2.25 2.30 2.35 2.40 2.45 2.50 2.55 2.60 2.65 2.70 2.75 2.80 2.85 2.90 2.95 3.00 3.05 3.10 3.15 3.20 3.25 3.30 3.35

0.1

0.2

0.3

0.4

5102 10204 15306 20408 4756 9512 14269 19025 4444 8889 13333 17778 4162 8325 12487 16649 3906 7813 11719 15625 3673 7346 11019 14692 3460 6920 10381 13841 3265 6531 9796 13061 3086 6173 9259 12346 2922 5844 8766 11687 2770 5540 8310 11080 2630 5260 7890 10519 2500 5000 7500 10000 2380 4759 7139 9518 2268 4535 6803 9070 2163 4327 6490 8653 2066 4132 6198 8264 1975 3951 5926 7901 1890 3781 5671 7561 1811 3622 5432 7243 1736 3472 5208 6944 1666 3332 4998 6664 1600 3200 4800 6400 1538 3076 4614 6151 1479 2959 4438 5917 1424 2848 4272 5696 1372 2743 4115 5487 1322 2645 3967 5289 1276 2551 3827 5102 1231 2462 3693 4925 1189 2378 3567 4756 1149 2298 3447 4596 1111 2222 3333 4444 1075 2150 3225 4300 1041 2081 3122 4162 1008 2016 3023 4031 977 1953 2930 3906 947 1893 2840 3787 918 1837 2755 3673 891 1782 2673 3564

tsd Ir 3.40 3.45 3.50 3.55 3.60 3.65 3.70 3.75 3.80 3.85 3.90 3.95 4.00 4.05 4.10 4.15 4.20 4.25 4.30 4.35 4.40 4.45 4.50 4.55 4.60 4.65 4.70 4.75 4.80 4.85 4.90 4.95 5.00 5.05 5.10 5.15 5.20 5.25 5.30 5.35

0.1 865 840 816 793 772 751 730 711 693 675 657 641 625 610 595 581 567 554 541 528 517 505 494 483 473 462 453 443 434 425 416 408 400 392 384 377 370 363 356 349

0.2 1730 1680 1633 1587 1543 1501 1461 1422 1385 1349 1315 1282 1250 1219 1190 1161 1134 1107 1082 1057 1033 1010 988 966 945 925 905 886 868 850 833 816 800 784 769 754 740 726 712 699

0.3 2595 2520 2449 2380 2315 2252 2191 2133 2078 2024 1972 1923 1875 1829 1785 1742 1701 1661 1622 1585 1550 1515 1481 1449 1418 1387 1358 1330 1302 1275 1249 1224 1200 1176 1153 1131 1109 1088 1068 1048

0.4 3460 3361 3265 3174 3086 3002 2922 2844 2770 2699 2630 2564 2500 2439 2380 2323 2268 2215 2163 2114 2066 2020 1975 1932 1890 1850 1811 1773 1736 1700 1666 1632 1600 1568 1538 1508 1479 1451 1424 1398

121

Time chart
Short time
tsd Ir 5.40 5.45 5.50 5.55 5.60 5.65 5.70 5.75 5.80 5.85 5.90 5.95 6.00 6.05 6.10 6.15 6.20 6.25 6.30 6.35 6.40 6.45 6.50 6.55 6.60 6.65 6.70 6.75 6.80 6.85 6.90 6.95 7.00 7.05 7.10 7.15 7.20 7.25 7.30 7.35 7.40 7.45 7.50 7.55 7.60 7.65 7.70 7.75 7.80 7.85 7.90 7.95 8.00 8.05 8.10 8.15 8.20

Ground fault
0.3 1029 1010 992 974 957 940 923 907 892 877 862 847 833 820 806 793 780 768 756 744 732 721 710 699 689 678 668 658 649 639 630 621 612 604 595 587 579 571 563 555 548 541 533 526 519 513 506 499 493 487 481 475 469 463 457 452 446 0.4 1372 1347 1322 1299 1276 1253 1231 1210 1189 1169 1149 1130 1111 1093 1075 1058 1041 1024 1008 992 977 961 947 932 918 905 891 878 865 852 840 828 816 805 793 782 772 761 751 740 730 721 711 702 693 683 675 666 657 649 641 633 625 617 610 602 595
tsd Ir 8.25 8.30 8.35 8.40 8.45 8.50 8.55 8.60 8.65 8.70 8.75 8.80 8.85 8.90 8.95 9.00 9.05 9.10 9.15 9.20 9.25 9.30 9.35 9.40 9.45 9.50 9.55 9.60 9.65 9.70 9.75 9.80 9.85 9.90 9.95 10.00

0.1 343 337 331 325 319 313 308 302 297 292 287 282 278 273 269 264 260 256 252 248 244 240 237 233 230 226 223 219 216 213 210 207 204 201 198 196 193 190 188 185 183 180 178 175 173 171 169 166 164 162 160 158 156 154 152 151 149

0.2 686 673 661 649 638 627 616 605 595 584 575 565 556 546 537 529 520 512 504 496 488 481 473 466 459 452 446 439 433 426 420 414 408 402 397 391 386 380 375 370 365 360 356 351 346 342 337 333 329 325 320 316 312 309 305 301 297

0.1 147 145 143 142 140 138 137 135 134 132 131 129 128 126 125 123 122 121 119 118 117 116 114 113 112 111 110 109 107 106 105 104 103 102 101 100

0.2 294 290 287 283 280 277 274 270 267 264 261 258 255 252 250 247 244 242 239 236 234 231 229 226 224 222 219 217 215 213 210 208 206 204 202 200

0.3 441 435 430 425 420 415 410 406 401 396 392 387 383 379 375 370 366 362 358 354 351 347 343 340 336 332 329 326 322 319 316 312 309 306 303 300

0.4 588 581 574 567 560 554 547 541 535 528 522 517 511 505 499 494 488 483 478 473 467 462 458 453 448 443 439 434 430 425 421 416 412 408 404 400

tg In 0.20 0.21 0.22 0.23 0.24 0.25 0.26 0.27 0.28 0.29 0.30 0.31 0.32 0.33 0.34 0.35 0.36 0.37 0.38 0.39 0.40 0.41 0.42 0.43 0.44 0.45 0.46 0.47 0.48 0.49 0.50 0.51 0.52 0.53 0.54 0.55 0.56 0.57 0.58 0.59 0.60 0.61 0.62 0.63 0.64 0.65 0.66 0.67 0.68 0.69 0.70 0.71 0.72 0.73 0.74 0.75 0.76

0.1 2500 2268 2066 1890 1736 1600 1479 1372 1276 1189 1111 1041 977 918 865 816 772 730 693 657 625 595 567 541 517 494 473 453 434 416 400 384 370 356 343 331 319 308 297 287 278 269 260 252 244 237 230 223 216 210 204 198 193 188 183 178 173

0.2 5000 4535 4132 3781 3472 3200 2959 2743 2551 2378 2222 2081 1953 1837 1730 1633 1543 1461 1385 1315 1250 1190 1134 1082 1033 988 945 905 868 833 800 769 740 712 686 661 638 616 595 575 556 537 520 504 488 473 459 446 433 420 408 397 386 375 365 356 346

0.3 0.4 7500 10000 6803 9070 6198 8264 5671 7561 5208 6944 4800 6400 4438 5917 4115 5487 3827 5102 3567 4756 3333 4444 3122 4162 2930 3906 2755 3673 2595 3460 2449 3265 2315 3086 2191 2922 2078 2770 1972 2630 1875 2500 1785 2380 1701 2268 1622 2163 1550 2066 1481 1975 1418 1890 1358 1811 1302 1736 1249 1666 1200 1600 1153 1538 1109 1479 1068 1424 1029 1372 992 1322 957 1276 923 1231 892 1189 862 1149 833 1111 806 1075 780 1041 756 1008 732 977 710 947 689 918 668 891 649 865 630 840 612 816 595 793 579 772 563 751 548 730 533 711 519 693

tg In 0.77 0.78 0.79 0.80 0.81 0.82 0.83 0.84 0.85 0.86 0.87 0.88 0.89 0.90 0.91 0.92 0.93 0.94 0.95 0.96 0.97 0.98 0.99 1.00

0.1 169 164 160 156 152 149 145 142 138 135 132 129 126 123 121 118 116 113 111 109 106 104 102 100

0.2 337 329 320 313 305 297 290 283 277 270 264 258 252 247 242 236 231 226 222 217 213 208 204 200

0.3 506 493 481 469 457 446 435 425 415 406 396 387 379 370 362 354 347 340 332 326 319 312 306 300

0.4 675 657 641 625 610 595 581 567 554 541 528 517 505 494 483 473 462 453 443 434 425 416 408 400

122

Ordering sheet
For faster quote processing, please use the following request for ordering sheet. For each section, check the applicable box or enter value cerresponding to your choice. Receipt Project Delivery place ACB main body Type of ACB Frame size Ratings Rated current (CT) Trip relay AH AN Note 1) D (630~2000AF) Note 1) LS Industrial System co., Ltd Order date Contractor Delivery date AS E (2000~4000AF) AF A NO YES
Frequency Type 60Hz NGO AGO AG1 AG2 AZ0 AZ1 AZ2 AE0 A Ammeter AE1 AE2 AC1 AC2 AK1 AK2 AX1 AX2 50Hz NG5 AG5 AG6 AG7 AZ5 AZ6 AZ7 AE5 AE6 AE7 AC6 AC7 AK6 AK7 AX6 AX7 Control voltage DC AC/DC No 100~250V 24~60V Comm. Optional function Type 60Hz PC1 PC2 PK1 P Power meter PK2 PX1 PX2 PA1 PA2 SC1 SC2 SK1 S Supreme SK2 meter SX1 SX2 SA1 SA2 Frequency 50Hz PC6 PC7 PK6 PK7 PX6 PX7 PA6 PA7 SC6 SC7 SK6 SK7 SX6 SX7 SA6 SA7 Control voltage Optional function Earth External No Yes leakage CT ground detection fault External Pre-Trip Comm. Earth DC AC/DC leakage CT ground Alarm 100~250V 24~60V fault detection

Distributor name PNL Maker Quantity F (4000~5000AF) G (4000~6300AF)

Normal

Note) - Standard function: Ground fault detection - Communication function is not available under no control voltage - AN, AS type is not available for S Meter - P(Power), S(Supreme) Meter is also available for generator protection - P, S Meter needs the accessory(VDM) for voltage measurement No.of poles Installation type Closing type 3-pole Draw-out type Manual closing Electrical closing Charge method: Charging completion contact(1b) is basically installed 4-pole Fixed type Standard type (R, S, T, N) Reverse phase type (N, R, S, T)

ACB cradle

Closing voltage Trip voltage Cradle type Terminal connection Connections

ACB accessory ACB Main body

Standard accessory

ACB Cradle

Standard accessory

Separate Main body purchase mounting

Cradle mounting

External mounting

Standard type (OFF-Charge method) Rapid auto-reclosing type (ON-Charge method) Motor operating voltage AC/DC 100V~130V DC 125V DC 24V~30V AC 48V~60V AC/DC 200V~250V DC 380V~415V AC 440V~480V AC 48V AC/DC 100V~130V DC 125V AC/DC 200V~250V DC 24V~30V DC 48V~60V AC 380V~480V AC 48V AC/DC 100V~130V DC 125V AC/DC 200V~250V DC 24V~30V DC 48V~60V AC 380V~480V AC 48V No safety shutter (E class) Safety shutter attachment (F class) Manual connection Automatic connection Horizontal Vertical Front connection Line: Horizontal, Load: Vertical Line: Vertical, Load: Horizontal Separate order/ User Installation Aux. contact(AX) Standard type (3a3b, Standard installation) Extended type (5a5b) Note 3) High capacity (5a5b) Note 3) Key Lock(K1, K3) Single key, K1 (ONLock) Double key, K3 (ONLock) Undervoltage trip device (UVT, Instantaneous) AC/DC 100V~130V AC/DC 200V~250V DC 125V DC 24V~30V DC 48V~60V AC/DC 380V~480V AC 48V Mechanical operation contact (MOC), Door Interlock (DI) Non-attachment type Attachment type Mechanical interlock (MI) Non-attachment type Attachment type Counter(C) Note 2) Non-attachment type Attachment type Miss insertion preventive device (MIP) Non-attachment type Attachment type Double shunt coil(SHT2) Non-attachment type Attachment type Ready-to-close switch(RCS) Non-attachment type Attachment type Trip alarm switch, Manual reset button(AL, MRB) Non-attachment type Attachment type Key interlock (K2, ONLock) ON/OFF Button Lock Temperature Alarm Safety shutter lock(STL) Zero arc space(ZAS) Note 2) Insulation barrier(IB) Slow closing lever(SL) Cell switch(CL) 4c 8c Door interlock(DI) Mechanical operation contact (MOC) Standard type (10a10b) High capacity(10a10b) Mechanical Interlock (MI) Wire type (2 terminals) Wire type (3 terminals) Shortening b-contact (SBC, 4b Max) 1b 2b 3b 4b Miss insertion preventive device (MIP) Non-attachment type Attachment type Cradle mounting block(CMB) Safety control cover(SC) Racking interlock(RI) Insulation barrier(IB) Note 2) UVT time delay controller(UDC) AC/DC 100V~130V AC/DC 200V~250V DC 125V DC 48V~60V AC 380V~480V AC 48V Door frame (DF) Condenser trip device (CTD) OCR tester Dust cover(DC) Profibus-DP Comm.(PC) Temperature alarm(TM) Remote I/O(RCO)

Note) 1. In case of D type of Metasol (AN), frame size is in the range of 630~1600AF 2. The standard accessory for Susol (AH). 3. Aux. contact with extended/high capacity type adopts the rapid auto-reclosing method and available up to 6a6b.

S u p e r

S o l u t i o n

HEAD OFFICE
LS Tower 1026-6, Hogye-dong, Dongan-gu Anyang-si, Gyeonggi-do 431-848, Korea Tel. (82-2)2034-4870 Fax. (82-2)2034-4713 http://www.lsis.biz

Cheong-Ju Plant
Cheong-Ju Plant #1, Song Jung Dong, Hung Duk Ku, Cheong Ju, 361-720, Korea Tel. (82-43)261-6001 Fax. (82-43)261-6410
Specifications in this catalog are subject to change without notice due to continuous products development and improvement.
100711 / STAFF
2007.8 LS Industrial Systems Co.,Ltd. All rights reserved.