Safety manual
The manual includes installation, commissioning, operation.The meaning of the mark you must understand clearly blow:
DANGER
It will result in death, serious harm to life or significant property damage,if you do not take preventive measures.
WARNING
It may result death, serious harm to life or significant property damage,if you do not take preventive measures.
CAUTION
It mar result light harm to life or property damage,if you do not preventive measures.
ATTENTION
Attention to the important information of the product and Specific parts.
Qualified staff
Only trained and qualified personnel should be allowed to install and operate the equipment. Qualified personnel must compliance with safety practices and eligible to install, debug, transport, repair, mark for the circuit and equipments.
Correct Application
Notice below:
DANGER
The device and its components can only be used to our product. The product performs their functions correctly and safely only through correct transport, restore, install and running, repairing by our proposed steps.
Safety Notes
Warning
Non-associated ESP staff to prohibit the operation of this equipment
DANGER
Before you start the divice,please make sure there was no peoplein side the ESP body , HV switchgear and transformer and related system was on the correct stations,and the staff of power supply were evacuated Safety.
WARNING
Forbidding operating the main breaker after starting the device
DANGER
Please cut off power supply before Commissioning.
ATTENTION
Read the instruction manual before installation, commissioning, operation, repairing, and understand every part of the information.
Solemnly Declare
We have checked this with the contents of the manual referred to in line with the hardware and software, but mistakes do happen and can not guarantee exactly the same. The manual will be reviewed on a regular basis and in the next edition of the amendment, welcome to suggest improvements.
WARNING
Not to read and understand the information provided in this statement may cause personal injury, product damage or bad operations. To start with, or any steps before the operation, please read the complete chapter, and make sure to understand each chapter and section of the information.
II
Foreword
The purpose
This manual is designed to provide GGAJ02-JHB ESP high-voltage rectifier equipment included H.V control cabinets, rectifier transformers, high voltage switchgear separation of functions and instructions. In the appendix gives the wiring-related equipment, size, electrical schematics.
The readers
This manual written for the operation and design staff of ESP device is applied to have the necessary basic knowledge of electrical system or learn more about ESP knowledge of the following persons: ESP installation, commissioning, maintenance, operation and maintenance personnel. In the field of management, sales staff.
Attention
In the appendix of the chart gives only part of the specifications of the equipment size and technical parameters For other specifications of the technical information, please contact our company. Address: Zip Code: Phone: Fax: Web: E-mail: No.41 torch road, High-tech zone, Dalian City 116023 0411-84799990 0411-84795956 http://www.jiahegy.com jiahe@jiahegy.com
III
Contents
1 OVERVIEW .............................................................................................................................1 1.1 1.2 1.3 1.4 1.5 PRODUCT FEATURES ..........................................................................................................1 THE MAIN PURPOSE ............................................................................................................2 THE SCOPE OF APPLICATION................................................................................................2 PRODUCT MODEL ...............................................................................................................3 PRODUCT SPECIFICATIONS ..................................................................................................3
1.5.1 60KV and 66KV device capability .................................................................................4 1.5.2 72KV and 80KV device capability .................................................................................5 1.5.3 90KV and 100KV device capability ...............................................................................6 1.6 1.7 2 WRKING ENVIRONMENT ......................................................................................................7 WORKING CONDITIONS .......................................................................................................7
STRUCTURE AND WORKING PRINCIPLE ...........................................................................8 2.1 2.2 THE WHOLE STRUCTURE AND WORKING PRINCIPLE ...............................................................8 H.V CONTROL CABINET STRUCTURE AND WORKING PRINCIPLE ..............................................9
2.2.1 main loop ....................................................................................................................10 2.2.2 Control loop ................................................................................................................10 3 TECHNICAL CHARACTERISTICS.......................................................................................16 3.1 MAIN CHARACTERISTICS ...................................................................................................16
3.1.1 Control method ...........................................................................................................16 3.1.2 Equipment soft start function ......................................................................................17 3.1.3 Current limit control.....................................................................................................17 3.1.4 High-impedance transformer ......................................................................................17 3.1.5 LCD display ................................................................................................................17 3.1.6 History fault information query ....................................................................................18 3.1.7 Communication Network.............................................................................................18 3.1.8 Analog output .............................................................................................................18 3.1.9 Reliability design.........................................................................................................18 3.2 4 MAIN PARAMETERS ...........................................................................................................19
4.1.1 GGAJ02-JHB-2...........................................................................................................21 4.1.2 GGAJ02-JHB-D ..........................................................................................................22 4.2 H.V. RECTIFIER TRANSFORMER .........................................................................................22
IV
JHB ESP H.V rectifier device use manual 4.2.1 Outdoors kind .............................................................................................................23 4.2.2 Indoor kind ..................................................................................................................25 4.3 4.4 5 H.V. ISOLATION SWITCH CABINET .......................................................................................27 CONNECTION BETWEEN TRANSFORMER AND H.V. ISOLATION SWITCH CABINET .....................28
INSTALLATION AND DEBUGGING .....................................................................................29 5.1 5.2 5.3 5.4 5.5 INSTALLATION CONDITION AND TECHNICAL REQUIRMENT ......................................................29 INSTALLATION METHOD .....................................................................................................29 INSTALLATION CHECKING ...................................................................................................30 DEBUGGING EQUIPMENT...................................................................................................32 OPERATING EQUIPMENT ...................................................................................................32
5.5.1 Debugging of Dummy Load ........................................................................................32 5.5.2 Debugging of Electric Field.........................................................................................33 5.5.3 Power supply in parallel of two high voltage units.......................................................33 5.5.4 Debugging for transformers tap .................................................................................34 6 USE AND OPERATION ........................................................................................................35 6.1 6.2 READY FOR USE AND SECURITY .........................................................................................35 OPERATE EQUIPMENT .......................................................................................................35
6.2.1 Startup and stop..........................................................................................................35 6.2.2 CON panel ..................................................................................................................36 6.2.3 Management purview is divided into three grades......................................................38 6.2.4 Equipment common fault ............................................................................................39 6.3 7 8 EQUIPMENT MONITOR AND RECORD ...................................................................................39
FAILURE ANALYSIS AND TROUBLESHOOTING ..............................................................40 EQUIPMENT MAINTENANCE AND LIFTING ......................................................................41 8.1 8.2 8.3 8.4 MAINTENANCE OF UNIT .....................................................................................................41 REPAIR OF UNIT ................................................................................................................41 PROCEDURES FOR HANGING CORE OF OUTDOOR TRANSFORMER ........................................42 LIFTING EQUIPMENT .........................................................................................................42
ORDER NOTICE...................................................................................................................43 9.1 9.2 9.3 UNIT CAPACITY, SPECIFICATIONS AND MODEL ......................................................................43 INLET AND OUTLET DIRECTIONS OF HIGH-VOLTAGE ISOLATION SWITCH CABINET ...................43 OTHER SPECIAL REQUIREMENTS.......................................................................................43
10 ANNEX A ..............................................................................................................................44
1 Overview
With modern industrial development, increasing environmental pollution, environmental protection is receiving increasing attention from all sectors of society and the importance of industrial gas pollution is a major source of environmental pollution, ESP as the prevention of industrial pollution in an effective way to Industrial emissions, through the provision of H.V electrostatic precipitator body, making the body through the flue gas ionization occurred, and charged dust in force under the electric field to a collecting campaign to re-use device for collecting dust. The collection has been widely used in electric power, metallurgy, building materials industries. ESP usually include ontology and control equipment consists of two parts, the ontology is the closed room for Industrial emissions dust through,it is a workplace for ESP, anode and cathode-ray board is an important part of the body, when the HV power supply to the anode and cathode-ray, there will be an Electric field between the Anode and cathode-ray, it makes the flue dust ionizate,the ionizating dust will moving to collecting board (cathode-ray board). The H.V control device suplly H.V DC power and such control for ESP. The H.V control device usually include H.V control cabinet and L.V control cabinet, H.V control by H.V rectifier device, include H.V control cabinet, H.V rectifier transformer, H.V switchgear, it responsible for ontology with power suplly, L.Vcontrol device incude L.V control cabinet and related executing agency, it responsible for ontology bolew: cathode rapping, anode rapping, porcelain axis heating, porcelain set heating, de-dust control etc. GGAJ02-JHBreferred to as JHBESP H.V rectifier control device was developed on the base of WA and JHA product, it has greatly improved in the real-time control, communicate, human-operation.
current/voltage.
1
JHB ESP H.V rectifier device use manual Use watchdog design, to protect the CPU beyond death at any situation. All I / O ports, communications ports are over-current, over-voltage protection. With the calendar clock. Power isolation design, enhance system reliability. Current and voltege signal use high-speed sampling after isolation, wave clearly, spark detecyion and control in a timely manner. Main loop, safety lock, run/stop, trigger power locked by hardware and software, to ensure the mistake does not trigger the SCR trigger. Synchronous signal detection has anti-jamming design and phase compensation by hardware and software, to ensure the accuracy of detection. Hardware over current detection and software voer current detection are independent of each other, to ensure reliable detection of over-current. Use high impedance transformer, to improve the output voltage waveform, to avoid short-circuit load, the spark breakdown at the time of the impact of over-current. Soft start design, to avoid rapid step-up equipment on the impact. Support automatic / manual mode step-up, in auto mode, set the Current primary, the voltage secondary, the turn-on angle setting, turn-on angle to limit the maximum value at the same time to participate in the four control, with a current limit control features. Secondary current display, real-time secondary voltage curve display, V-I sampling curve display. Failures history inquiry, include the type of fault and Failure happened time. Data history inquiry, include primary current, primary voltage, secondary current, secondary voltage.
JHB ESP H.V rectifier device use manual removal and recycling of raw materials. The chemical industry demist, dedust and recycling the useful components of the Industrial emissions dust. Petrochemical industry: separate the salt, water or other impurities from crude oil. Textile industry: recycling the alkali in the proccing of textile production and dedust. Paper-making industry: recycling the alkali in the proccing of paper-making production and dedust. Other Industry: clean air.
DANGER
Forbid to use this product other than the ESP system.
GGAJ02XX A / XX KVJHB2DHWN
The product composition and significance as follows: G G AJ 02XX A / XX KVJHB2DH WN W: Outdoor Transformer N : Indoor Transformer Syncytial Transformer H.V cabinet hight 2: Hight: 2000mm D: Hight: 2200mm Product design code Rating voltage, unit: kV Rating current, unit: A SCR regulate voltage Cooling by oil inside For the H.V occasion Diode rectifier current
JHB ESP H.V rectifier device use manual Rating secondary current is 1.0A
capability Unit:A A 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0 23 46 69 92 115 138 161 184 207 230 260.8 276 308.2 322 345 368 403 414 450.5 460
KVA 8.7 17.5 26.2 35 43.7 52.4 61.2 69.9 78.7 87.4 99.1 104.9 117.1 122.4 131.1 139.8 153.1 157.3 171.2 174.8
mm 216 216 225 235 250 270 295 2120 2120 2250 2270 2270 2295 2295 2295 2295 2 2120 2 2120 2 2150 2 2150
A 25.3 50.6 75.9 101 126 152 177 202 227 253 286.9 304 339 355 380 405 443.3 456 495.5 506
KVA 9.6 19.2 28.8 38.4 47.9 57.8 67.3 76.8 86.3 96.1 109 115.5 128.8 134.9 144.4 153.9 168.5 173.3 188.3 192.3
mm2 216 225 235 250 270 295 295 2120 2250 2270 2270 2295 2295 2295 2 2120 2 2120 2 2150 2 2150 2 2185 2 2185 (A) A-X3 54
H.V rectifier transformer: below +40, not less then the condensate temperature of tranformer oiliness. 3 Relative humidity: 85%. 4 Altitude: 2000m
ATTENTION
If you want the product works in the special environment, please order with manufacturer links.
3 Anti-vibration and tilt: No strong vibration and shock, the vertical gradient is less than 5 4 The H.V control cabinet, H.V rectifier transformer, HV Switchgear need reliable ground, in any climate, the grounding resistance must below 2.
ATTENTION
If you want the product works in the special conditiont, please order with manufacturer links.
Picture 1 JHB H.V rectifier device working princple After the power (AC 380V) through the main breaker (QF1) of the H.V control cabinet, it had been regulated voltage by anti-parallel SCR (V1, V2), re-export to the high-voltage rectifier transformer primary ciol, through the high-voltage transformer rectifier boost, after transform rectifier, a negative high-voltage output in the secondary, and then through the high-voltage switchgear and isolation body connected to the body in order to supply the electric field. The H.V control cabinet control the trigger of SCR (V1 and V2), and then control the input voltege of tranformer, tranformer suplly ontology changes of the voltage.
28 12 31
36 30 16 29 17 1 18 32 14 33 34 23 5 13
38 6 7 22 8
19 20 9 2 21 3 11 10
35
a.
b. front inside
c. Main loop unit 2. Input copper row 5. SCR models 8. SCR heat sink 11.heat sink fan 13.Signal and trigger unit 16.Fuse 19. 24V power supply 22.voltage sampling TR 25. Primary voltage meter 28. Failure light 31. Start button 34.Grounding row
9
d.
back
e. back inside
Picture 2 H.V control cabinet Structure 1. Main loop unit 4. Main breaker QF1 7. RC absorption Capacitance 10. Output protect device 12. CON 15.Control loop breaker QF2 18.TR.TC2220:15 21. Current transformer 24. Primary ammeter 27. Secondary voltage meter 30. Alarm 33. Local / manual switch 3. Ouput copper row 6. RC absorption resistance 9. Input protect device
14.Relay unit 17.TR.TC1380:220 20.Control power box 23.Secondary sampling unit 26.Secondary ammeter 29.main loop power on light 32. Stop button 35.Grounding pole
JHB ESP H.V rectifier device use manual 36. Lighting 37. Overhaul power socket 38.Dust defend cover
then the capability is bolew 0.5A, it used to maintain a fixed current for SCR. Heat sink and fan for cooling SCR.
JHB ESP H.V rectifier device use manual Signal conditioning and trigger unit receive two groups trigger signal form CON unit, after pulse transformer isolation, driver the SCR V1 and V2, controlled the output voltage.
8 CON unit
CON is the control core of the H.V control cabinet, when the control loop power is on, CON analog circuits produces phase and synchronous signal, and sends it to the CON digital circuit, CPU of the CON digital circuit sampling the primary current, primary voltage ,secondary current secondary voltage signal by A/D converter at the same time.and then press start button,the H.V control cabinet start, CON according to the pre-set parameters and feedback signals, closed loop feedback-controll, CPU calculates the trigger turn-on angle next cycle wave, timings the trigger
11
JHB ESP H.V rectifier device use manual angle and to control the SCR trigger signal, and then control the output voltage of SCR. CON can detectes the spark happened in the ontology field by feedback signal, when the spark happening, the programme get into spark closed loop feedback-controll. CON includes 5 ports, analog circuits part, digtal part, trigger part, communicate and D/A output part, switch I/O signal part, all of the parts using isolation design, CON working princple is shown in picture 6. 1) Analog circuits part
Primary current, primary voltage, secondary current, secondary voltage, turbidity sampling signals deal with input filtering and amplification RMS filter, for AD conversion, in order to calculation of RMS and turbidity control, at the same time, primary current, secondary sampling signal had been amplified and filtered before linear optocoupler, the signal ouput of linear optocoupler connect to the control CPU, using the CPU high-speed AD conversion to converse primary current, secondary voltage, control CPU use the data of the result to detect spark. Besides, phase and synchronous signal also comes from the power analog circuits. 2) Digital ciicuit part
CON use double 32-bit ARM CPU, LPC2132 and LPC2129,both main frequence is 44MHz, 22ns command speed, LPC2132 used to control voltage output ,LPC2129 used to control LCD, key, communicate networks and HMI, as well as historical data storage, calendar clock count. LPC2132 control spark by the signal of primary current and secondary voltage sampling,support spark rate set.support manual/automatic control model, at automatic model, control with the value primary current set, secondary voltage set, trigger angle set,max trigger angel set at same time, has current limit control. CPU and detect H.V rectifier transformer faut, ontology field faut, device faut and also can protect the system by cutoff the related power, fault for exampleontology field open circuit, short circuit, abnormal excitation, oil temperature high, oil Limits temperature, limits gas, light gas, oil serface has safety lock function, in order to ensure personal safety.when the fault happend, there will generate a report to store. LPC2129 control a 5.7-inch LCD, LPC2132 and the LCD communicate data, LCD display the running data, support history fault Query and history data store, 32K primary current /voltage, secondary current/voltage data store space. 3) Trigger unit
The trigger unit of CON power supply seperate, LPC2132 send trigger pulse signal to isolation Optocoupler, the output signal of isolation optocoupler into MC1413, and then into signal conditioning and trigger unit, then through pulse transformer the signal get into SCR finally, two loops trigger output have over-voltage protect.
12
JHB ESP H.V rectifier device use manual 4) Communicate and D/A unit
Support CAN bus and RS485 communication, the highest rates of CAN bus is 500Kbps, the highest rates of RS485 is 115.2Kbps, support the standard communication protocol Modbus ASCII/RTU, have 2 loops Isolated analog output, output 4~20mA signal, the signal can choose primary current /voltage, secondary current/voltage.
13
Digital part
Filtering enlarge Filtering enlarge Filtering enlarge Filtering enlarge Filtering enlarge
AD
converters
Optocoupler
Communication and DA
High-speed Optocoupler
Key
CPU LPC2129
High-speed Optocoupler
Linear
Optocoupler
Toggle switch
CPU LPC2132
Toggle switch
Output drive
Spark +3.3V Precision power SPX1117-3.3V Digital power voltage +5V regulator +1.8V Precision power SPX1117-1.8V +5V voltage Analog power -5V regulator DA and COM +5V power Digital output +24V power voltage regulator voltage regulator
DA output1 DA output2
Output filtering
Optocoupler
TR.
12V input
Commnucition and DA
picture 6 CON working princple
AC220V input
14
JHB ESP H.V rectifier device use manual 5) Switch I/O signal unit
The signal of this unit includes H.V rectifier transformer fault, start/stop input etc, and alarm, control output etc. DI has a hardware filter can effectively prevent the jitter signal. The control output and alarm output are perfect over-current over-voltage protection.
9 Relay unit
This unit has a number of relay, include ready, alarm output, over-curent, start, stop etc, it makes the wiring inside cabinet easy.
10 Auxiliary circuit
This part incudes cooling fan M1 and M2, coil excitation of main breaker, lighting, AC220V power outlet, lighting and overhaul outlet power supplied by L>V control cabinet.
15
3 Technical characteristics
3.1 Main characteristics 3.1.1 Control method
CON support Sparks track, spark rate track, turbidity feedback, reduce-voltage rapping control model etc. 1) Sparks track model
When ontology field produce spark breakdown, in order to avoid short-current, cutoff the SCR, quickly restored to 90% of the original breakdown voltage at several cycle-wave, and then approach the original breakdown voltage slowly, the characteristics are called second-line spark track, this model of control is a very good approach to the restoration of media curve, and also guarantes the maximum output power. 2) Sparks rate track model
H.V control cabinet and L.V control cabinet works together, when rapping, the PLC cabinet(L.V control cabinet) sends a signal to H.V control cabinet, if the CON of H.V control cabinet detects the signal of rapping, it reduces the output voltage by controlling SCR, and when the rapping over, it restorate voltage to original value. 4) Turbidity feedback control
In order to achieve the concentration of gas emissions required by environmental protection departments of the concentration of dust emission standards, and also can reduce power consumption as much as possible, CON with the dust concentration monitor support for achieving the concentration of dust on the closed-loop control. 5) Fualt running
Debugging equipment, by setting the master switch with dial code, the device can run a short period of time with the fault which includes open-circuit running and short-current runnig. When open-circuit, equipment detects open-circuit failure, only the alarm, non-stop machine. When short-current, equipment detects short-current failure, only the alarm, non-stop machine. At the same time equipment allow running at short-current and open-circuit, but in any case, rquipment will detect over-current, if over-current, alarm, stop equipment immediately, and drive coil excitation, make the main breaker cut off. By setting, equipment can also run on a current rating of 110% and 115% both cases.
16
JHB ESP H.V rectifier device use manual The equipment has sef-test function, when the control power on, it will detect A/D converter, current and voltage signal sampling, transformer failure, the main circuit connection, the security chain of 5 parts of the self-test hardware, the programme will sef-test the parameters of ROM store, only software and hardware self-test success, the equipment can start . Flash
17
JHB ESP H.V rectifier device use manual voltage, trigger angle, spark rate, trigger angle set, spark rate set, run state, control model, calendar clock, etc. and show the secondary current, secondary voltage curve.
18
JHB ESP H.V rectifier device use manual Synchronous signal detection has multiple anti-jamming designs and phase
compensation, and a combination of hardware and software to ensure the accuracy of detection. Hardware and software over-current detect independent of each other, ensure over-current detect reliable, when it is over-current,the main loop breaker QF1 will cut off.
CAN bus:the highest rates of CAN bus is 500Kbps RS485:support 1200 bps,2400 bps,4800 bps,9600 bps,19200 bps,38400bps,57600 bps,115200 bps 9) Working model: Allows continuous operation under the rating current.
10) Cooling: Cabinet cooling by air, H.V rectifier transformer cooling by oil inside. 11) Protection level: the Protection level of control cabinet is IP52, the protection level of H.V rectifier transformer is IP54. 12) H.V rectifier transformer parameters Input voltage : Output voltage: Output voltage: 0 ~ AC400V Rating DC voltageUnit:KVis 60,66,72,80,90,100. Rating output current Unit:Ais 0.1, 0.2, 0.3, 0.4, 0.5, 0.6,
0.7, 0.8, 1.0, 1.2, 1.4, 1.6, 1.8, 2.0 Impedance of the voltage: Transformer Oil : 30%~40%
Sampling resistance: secondary voltage is 5.00K,Secondary current is 2.00K. Negative H.V to grouding: the value of positive resistance is zero, the negative resistance is 52/65/78 M. Insulation resistance: Primary side to grouding
19
: 100M
JHB ESP H.V rectifier device use manual Secondary side to grouding : 100M
Primary side to Secondary side : 100M 13) H.V control cabinet structure: cold-used steel structure, surface electrostatic spray, power connect Copper row at the top of cabinet use standard GGD. 14) National Institute of Standards: the product JB/T 9588-1999 ESP H.V Rectifier Device National Standard.
20
4.1.1 GGAJ02-JHB-2
Dimension: 600mm 600mm 2000mm, refer to figure 15. Weight :200kg For cable input
4.1.2 GGAJ02-JHB-D
Dimension: 600mm 600mm 2200mm, refer to diagram 16. For bus bar input
22
1) flat wheel and rail wheel can be replaced by the other as well,and the angle of veer can be 90 degree. 235KV standard porcelain is needed in some dirty areas. Diagram 17 outline dimension of 60KV and 72KV outdoors rectifier transformer 335KV enhanced porcelain is needed in some heavy dirty areas.
4The length of 35KV standared is 495mm,and 582mm for the enhanced ones. Fig.17 Dimensions of 60KV and 72KV outdoors rectifier transformer The outline dimension of 60KV and 72KV outdoors H.V. rectifier transformer can be separate into total 7 kinds of Ab, Aa, A, B, C, D, E according to the rated secondary current. And the detailed
23
JHB ESP H.V rectifier device use manual data is showed in table 4, please contact us if you have the requirements for the dimension of transformer of other capacity. Table 4 dimension of 60KV and 70KV outdoors H.V. rectifier transformer Capacity Class current A 2.0 Ab 1.9 1.9 1.7 1.9 1.8 1.7 Aa 1.6 1.5 1.4 1.3 1.4 1.3 A 1.2 1.1 1.0 1.0 B 0.9 0.8 0.7 0.7 C 0.6 0.5 0.4 D E 0.4 0.3 0.2 0.1 60 60 60 60 72 72 72 60 60 60 72 72 72 560 560 710 660 910 748 100 120 940 940 650 650 1275 1275 790 740 630 580 800 600 350 290 250 210 560 750 950 100 1070 650 1405 830 670 1000 450 340 60 60 60 72 72 72 650 800 1100 150 1170 800 1545 880 720 1250 550 430 60 60 60 60 72 72 72 650 800 1100 150 1220 800 1595 880 720 1400 660 650 60 60 60 60 60 72 72 72 72 650 800 1100 150 1320 800 1695 880 720 1520 660 600 voltage KV 60 72 72 72 72 750 888 1660 252 1320 800 1720 980 820 2000 950 700 a b Main dimension (unit mm) c D H h G W T Weight(unit :Kg) Total wight Oil weight Core weight
24
Fig.18 Dimensions of 60KV and 72KV outdoors rectifier transformer The outline dimension of 60KV and 72KV indoor H.V. rectifier transformer can be separate into total 7 kinds of Ab, Aa, A, B, C, D, E according to the rated secondary current as well. And the detailed data is showed in table 5, please contact us if you have the requirements for the dimension of transformer of other capacity.
25
JHB ESP H.V rectifier device use manual Table 5 dimension of 60KV and 72KV rectifier transformer Capacity Clas s curren tA 2.0 Ab 1.9 1.9 1.7 1.9 1.8 1.7 Aa 1.6 1.5 1.4 1.3 1.4 1.3 A 1.2 1.1 1.0 1.0 B 0.9 0.8 0.7 0.7 C 0.6 0.5 0.4 D E 0.4 0.3 0.2 0.1 60 60 60 60 72 72 72 60 60 60 72 72 72 56 0 56 0 71 0 66 0 910 748 940 940 149 0 149 0 79 0 74 0 63 0 58 0 800 600 350 290 250 210 56 0 75 0 950 107 0 166 0 83 0 67 0 1000 450 340 60 60 60 72 72 72 65 0 80 0 1100 1170 176 0 88 0 72 0 1250 550 430 60 60 60 60 72 72 72 65 0 80 0 1100 122 0 181 0 88 0 72 0 1400 660 560 60 60 60 60 60 72 72 72 72 65 0 80 0 1100 132 0 191 0 88 0 72 0 1520 660 600 voltage KV 60 72 72 72 72 75 0 90 0 120 0 132 0 191 0 98 0 82 0 2000 950 700 a Main Dimension (unit: mm) b c H F W T Weight (unit :Kg) Total weigh t Oil weigh t Core weigh t
26
Fig.19 Dimension diagram of H.V. isolation switch cabinet Inlet and outlet directions of high-voltage isolation switch cabinet When the rectifier adopts the outdoor mode ,the high-voltage isolation switch cabinet should be ordered in addition .And when ordering the high-voltage isolation switch cabinet, please clarify its inlet and outlet directions .Here
27
JHB ESP H.V rectifier device use manual are the styles of inlet and outlet directions: Side in and back out: right in and back out, left in and back out. Side in and lower out: right in and lower out, left in and lower out Side in and side out: right in and left out, left in and right out. Back in and side out: back in and right out, back in and left out. Back in and lower out.
28
2 Technical requirment
GGAJ02-JHB H.V. rectifier units installing technology obeys the state standard<JB/T 8536-1997 PRECIPITATOR MECHANISM INSTALLATION TECHNOLOGY REQUIRMENT>.
3 Wiring
29
JHB ESP H.V rectifier device use manual The selection of cable and on-site wiring connection of unit should carry on according to <Matching Design Diagram of High and Low-Voltage Electricity>and Instruction of Unit Connecting in the Instruction Manual. The sampled signal of secondary current and secondary voltage must be connected with screened cable. The screened layer should be well earthed at the rectifier terminal and the control cabinet terminal. The direct-current resistance of the conducting wire should not be larger than 2, while the wire size should not be smaller than 1.5 mm2.
4 Unit earthing
The earthing of the control cabinet, high voltage rectifier and the case must be surely earthed. The operation earthing must be connected with precipitator case through the special ground wire. Connection line shouldnt be smaller than 16 mm2.
2) Measurement
Negative high voltage output to earth: forward: 0. adverse: 523M(60/66/72 KV), 654M(80KV). (Measured with 2500VM meter) UH2 To earth : 6.670.3K. (Measured with multi-meter) IH2 to earth: 20.1K. (Measured with multi-meter) The resistance of terminal A to X1,X2,X3 :<1 (Measured with multi-meter). The primary power supply input terminal to device body,the secondary high voltage output terminal to device body, and the primary power supply input terminal to the secondary high voltage output terminal are all 100M(Measured with 2500VM meter). Whether the oil thermometer can be closed and opened normally.
JHB ESP H.V rectifier device use manual standards and specifications, or if the value of earth resistance confirms to the standard (<2). The insulation resistance of cathode wire should be larger than 200M.
2) Stop Unit
The sequence to stop the equipment is: first press the stop button, then cut off the breaker of the main loop, and at last cut off the breaker of the control loop, the equipment will be off.
Adjust the lower limit item of oil thermometer on the transformer to make it closed with pointer, then trouble of transformer Light on the cabinet door and V7 light on the master control board shine.Adjust again the upper limit of oil thermometer to make it closed with pointer, then the alarm bell rings, the unit stops and the V5 light on the master control board shines. Cut off the breaker of control loop (QF2) to relieve the bell. (Here the reset button AJ1 on the master control board is
32
JHB ESP H.V rectifier device use manual not available to relieve) 2) Warning Test for Open Circuit
Hang up the negative high-voltage output terminal of rectiformer, and the unit should alarm in the event of boosting after start-up. And then the light of trouble of precipitator shines, alarm bell rings, the unit stops and the V9 light on the master control board shines. Press reset button AJ1 to disarm the bell. 3) Warning Test for Short Circuit
Make the high-voltage isolation switch at grounding position, and the unit should alarm in the event of boosting after start-up. Meanwhile, the light of trouble of precipitator shines, alarm bell rings, the unit stops and the V10 light on the master control board shines. Press reset button AJ1 to relieve the bell.
33
JHB ESP H.V rectifier device use manual transformers circulation. while boosting, make slow sync boosting to avoid damage to the unit caused by surcharge of single unit.
34
WARNING
Check whether high-voltage isolation switch is closed before supply, and it is prohibited to operate high-voltage isolation switch after operation.
ATTENTION
Its not allowed for the equipment to be operated in the empty load or open circuits condition that avoid over-voltage to destroy equipment.
DANGER
Prohibit to operat the air switch QF1 after start-up equipment.
DANGER
Must obey principal order and forbid presume to give power or cut power , must affirm nobody in electric field before run equipment
ATTENTION
Must inform principal to manage all people away from dust when give power. Operators should strengthen safety consciousness and strict administer to according to operation steps.
JHB ESP H.V rectifier device use manual 1) Check control loop of the equipment and the air switch keep cut state such as QF2 and QF1 2) 3) 4) When open the air switch QF2 small air switch, LCD screen will display When open the air switch QF1 big air switch,the light of the door will lignt green. Push the button startup on the door to run equipment.
Stop equipment, operation order 1) 2) 3) Push the button stop on the door to stop equipment. QF1.cut the air switch QF1
ESC
UP DEC_U
5.7
36
1 LCD screen
CON use 5.7 inch LCD screen, Chinese characters, display Resolution 320 240
2 Key-Press
CON have nine keys, respectively:
ENT
ESC
REAL
REAL: press the real key to enter real data monitoring, process date monitoring,when the current menu is the real data monitoring,press the key ,then enter work mode,set RC amend.
INC_U: when run equipment,press this key one time (key button), RC value add
INC_U
one,turu-onangle value add one degreesmost 153 degrees,And then increase the voltage. continued press the button 1s (L button),one key per 200ms effective, RC value add one, Until button put up.when equipment is stop, this key is invalid.
DEC_U
DEC_U: when run equipment,press this key one time (key button),,RC value minus one,,turu-onangle value minus one degreesleast zero degrees, and then lower the voltage continuous press the button 1s (L button),one key per 200ms effective,RC value minus one,Until button put up. When equipment is stop, this key is invalid.
UP
3 LED light
37
JHB ESP H.V rectifier device use manual CON have six LED lights:
/ POWER / RUN / LOCK
Power light: when open QF2 of control loop, CON have power, light Run light: when start up equipment, when run normal, run light will light. Lock light: when open H.V Switchgear, when run low-voltage control cabinet,
Spark light: when CON judge spark breakdown, spark light will light.
CAN communication light: two-color indicator light, when CAN communicate, when
receive data, then red light will light.when send data, then green light will light.
RS485
when receive data, then red light will light.when send data, then green light will be light.
JHB ESP H.V rectifier device use manual 1) When set the operating parameters screen, such as Figure 32. move the cursor to the "default value" option.If the system needs to set the default operating parameters,you must input password 2) When set the system parameters screen, such as Figure 41. Move the cursor to "set the system password" option, please input the password, after input the correct password, administrators can back up the system parameters and restore the system parameters, delete failure information, delete operation historical data,super-administrator can also set I2 and U2 rating rating. 3) When set real-time picture data, such as Figure 41. Move the cursor to "save data" option, if need to preserve all the calibration data, it must be input password, administrator and super administrator can carry out the calibration data and save.
39
If the device have trouble in other place ,you can test false load , specific methods to consult section 5.4.2
40
DANGER
When repairing components, break off firstly, confirm them without electricity by multi meter, electroprobe and so on. It is advisable to detect with the back of fingers, and then begin to repair.
DANGER
When checking and repairing in the electric field, break off all high or low voltage unit power. Cut off all connections between high-voltage output terminals of rectifier and electric fieldand the electric field should be earthed well.
41
DANGER
After electric fields earth through high-voltage isolation switch, connect the cathodic frame and body casing with wire or conductor at the manhole door when entering into electric field.
High-voltage transformer suspended operation of the transformer core itself may have
an adverse effect on the operation must be cautious.
WARNING
9 Order notice
9.1 Unit capacity, specifications and model
Designate the unit capacity, i.e. secondary rated current and secondary rated voltage. Designate the inlet mode of power supply for control cabinet, i.e. the height of control cabinet. When the cabinet height is below 2m, it uses down cable inlet. When the cabinet height is over 2.2m, it uses upper bus inlet. Designate the installation position of the high-voltage rectifying transformer, i.e. indoor mode or outdoor mode. In case of outdoor mode, the high-voltage isolation switch cabinet should be added in corresponding quantity.
43
10 Annex A
Current sampling, damping resistance, currentLimiting resistance Unit Capacity A 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.2 1.4 1.5 1.6 1.8 2.0 Current Sampling R11() 2.7//2.7 0.68 0.5//4.3 0.68//0.68 0.5//0.5 0.2 0.2//4.3 0.2//1 0.2//0.68 0.18//0.5 0.2//0.2 0.18//0.2 0.18//0.18 0.15//0.18 0.15//0.15 0.13//0.13 Samping Resistance 180/800W 180/800W 180/800W 180/800W 180/800W 180/800W 180/800W 180/800W 180/800W 180/800W 180/800W 180/800W 150/1000W 150/1000W 150/1000W 150/1000W CurrentLimiting Resistance 1000/500W 1000/500W 1000/500W 1000/500W 1000/500W 500/800W 500/800W 500/800W 500/800W 500/800W 300/1000W 300/1000W 300/1000W
Measured Value of Insulation Resistance of Transformer Negativehigh-handed Voltage Rank Output-to- Forward 60,66,72 80 90,100 0 0 0 Adverse 52M 65M 78M 6.67K 2K 100M UH2-to- IH2 -to- Primary-to-Crust Secondary-to-Shell Once -to-Shell
44