You are on page 1of 4

BAHWAN ENGINEERING CO.

LLC
P. O. Box 703, Ruwi 112 Sultanate of Oman Tel.: (968) 24597510, Fax: (968) 24597511 Email: mukesh.mechprod@becoman.com Msg.No. Date: 30-May-2011

To: Shamel International Ind. Trading & Contracting LLC.


Fax No.: Attn:

24501684

Mr. Nayankumar Pawar OurRef.: MPD/09/170/R/MK YourRef.: Discn dtd 30.05.11 (Total No. of Pages including cover page : 4) Subject : Supply of Carrier Air cooled Screw Chiller, Air handling Units & Chilled water Fan Coil Units for College of Science North Bldg Sultan Qaboos University. We refer to our discussion at your office and are pleased to submit our quote for Carrier equipments as mentioned below. A. 2Nos. Carrier (France) Air Cooled Screw Chiller Model: 30XA1102, operating on refrigerant R134a, rated to deliver an actual cooling capacity of 914 KW at an ambient temperature of 46 Deg C and chilled water leaving/entering temperatures of 6.7 / 12.2 Deg C. The fouling factor considered is 0.0180 Sqm deg K / KW. Each chiller shall comprise: Twin Screw Compressor designed to operate on R134a Mechanically cleanable Shell & tube evaporator High Efficiency All Aluminium Micro Channel Heat Exchanger. Main Disconnect Switch/ circuit breaker Low noise type aerofoil, Statically & dynamically balanced FLYING BIRDTM condenser fans discharging air vertically upwards IP55, Class F insulated condenser fan motors Electronic Expansion Valve Touch screen Pro-Dialog control.

The performance report details is enclosed for your perusal. PRICE : Our Price for supply only of Equipment, ex warehouse Ghala, shall be as under : Cooling Cooling Ambient Chiller Capacity water In / (deg C) model (KW) Out (deg C) A 914 12.2 / 6.7 46 30XA1102 Ttl. Rial Omani Ninety Six Thousand Six Hundred Only Item. Amount (RO) 96,600/96,600/-

Qty Rate (RO) 2 48,300/-

B. 10Nos. Carrier (Saudi) - 39FX Series, Eurovent Certified make Air Handling Units constructed out of 50mm thick sandwich insulated panels comprising 40Kg/m3 density, Polyurethane Insulation, 0.6mm thick Galvanised Steel Internal and External Prepainted Sheet, G.I. frame work. The cooling coils included in the AHUs offered by us are with copper tube / Al fins and Al Casing. Drain pan is of SS. construction. The AHUs shall comprise of the following: ..2

:2: Ref : MPD/09/170/R/MK Date : 30-May-2011 Mixing Box with fresh air damper. Filter section with G4 prefilters and F7 bag filters. Chilled water Cooling Coil , with copper tube / Al fins and S.S. drain pan. DIDW Forward / Backward curved supply fan with TEFC Class F insulated Motor Access Doors. Weather proof Canopy for FA AHU-5,6 We have not include for any special filtration for the fume cupboards.

The computerized selection sheet is enclosed herewith for your perusal. PRICE : Our price for Supply only, ex warehouse Ghala,is tabulated as under :
Sr. No Tag No. Total (LPS) Cooling Cap. (KW) AHU Model Qty SPRate (RO) SPAmt (RO)

1 2 3 4 5 6 7

FAHU-1 FAHU-2 FAHU- 3 & 4 FAHU- 5 & 6 FC-FAHU-1 FC-FAHU-2 FC-FAHU-3& 4

944 1085 1133 661 2124 1180 1652

65.7 75.6 79 46.4 148 82.1 115

39FX240 39FX240 39FX240 39FX230 39FX350 39FX330 39FX340

1 1 2 2 1 1 2

1,300 1,300 1,500 1,200 2,400 1,600 2,100

1,300 1,300 3,000 2,400 2,400 1,600 4,200


16,200

Total - Rial Omani Sixteen Thousand Two Hundred Only

C. 164 Nos. Carrier ( Malaysia) Chilled water Ducted Concealed type Fan Coil Units complete with blower, blower motor, copper tube/aluminum fins cooling coil, filter, etc., all as per manufacturers standard specifications as detailed below : We have assumed the following while selecting the fan coil units : (a) Chilled water entering and leaving temperature of 6.70C and 12.20C respectively. (b) On coil dry and wet bulb temperature 250C and 180C (c) Selection carried out at Medium Fan speed. (d) External static of 50Pa for ducted units as specified in the schedule. (e) Cooling only units. Other accessories like thermostats, valves, 3-speed switch, etc., NOT included. The selection sheets are enclosed for your perusal.

..3

:3: Ref : MPD/09/170/R/MK Date : 19-July-2010

PRICE : Our price for Supply only of units, ex warehouse Ghala, is tabulated as under
FCU No Type Required Air Cooling Flow Capacity Selected Air Flow Qty Cooling Capacity 24 42 18 33 15 7 17 5 3 164 Rate (RO) Amt (RO)

Model

LPS KW LPS KW FCU-1 Ducted 189 3.50 42CET063R 207.0 3.83 FCU-2 Ducted 283 5.27 42CET083R 294.6 5.40 FCU-3 Ducted 377 7.03 42CET123R 422.2 7.17 FCU-4 Ducted 472 8.79 42DC12 500.2 9.46 FCU-5 Ducted 566 10.54 42DC14 618.3 11.88 FCU-6 Ducted 661 12.30 42DC14 618.3 11.88 FCU-7 Ducted 755 14.06 42DC16 751.3 14.43 FCU-8 Ducted 850 15.82 42DC18 848.3 16.33 FCU-9 Ducted 944 17.58 42DC20 873.3 17.25 Total : Rial Omani Twenty Nine Thousand Two Hundred Only

100 140 170 200 230 230 240 250 290

2400 5880 3060 6600 3450 1610 4080 1250 870 29,200

Please note that our offer does not include any options/ accessories other than those clearly stated above and/or in the enclosures to this offer. We request you to kindly check the offer carefully and advise us if any other options are required to be provided to enable us submit our revised offer. VFD for the fans (if required), thyristor controls for heaters, sound attenuators, control panel for the AHU, electrical cabling and earthing, terminations, etc., are NOT included in our scope. PAYMENT : 100% by way of confirmed & irrevocable LC payable at sight. VALIDITY: 30 days from the date hereof and thereafter subject to our written confirmation. DELIVERY : 12 to 14 weeks from the date of confirmed order and receipt of approved MAS / clearance of shop drawing. MAS shall be submitted within one week of receipt of order by us. Kindly note that exact delivery period can be confirmed at time of placing the order based on the Carrier factory holidays for Ramadan ( Saudi factory) / Spring holidays ( France factory). WARRANTY : The equipment is warranted free from manufacturing defects and bad workmanship for a period of 12 months from the date of commissioning or 15 months from the date of supply, whichever ends earlier. The warranty is, however, null and void in case of misuse, damage, burnouts due to extreme voltage fluctuations, and in case repairs are carried out without our prior written approval. Please note that as a matter of policy, the manufacturer DOES NOT offer any warranty against corrosion and as such, our offer does not include any warranty against corrosion. ....4

:4: Ref : MPD/09/170/R/MK Date : 30-May-2011 CANCELLATION : In the unlikely event of cancellation of an order either in part or in full, for any reason, you undertake to reimburse us such cancellation charges as may be levied by the manufacturer plus 10% subject, in all cases, to a minimum of 10% of the order value. We trust the above is in line with your requirements. Thanking you and assuring you of our best attention at all times. Yours faithfully,

Mukesh Kadamba Asst. Sales Manager Mechanical Products Division (GSM : 98233023)