You are on page 1of 8

DIN EN ISO 9001

Quality requirements for certified welding

PREXTHERM RSH
High efficiency pressurised steel boilers the best degrees centigrade
UNI EN 729-2

PREXTHERM RSH

PREXTHERM RSH 80 - 800 Quadra series

PREXTHERM RSH 900 - 2600 Tonda series

The PREXTHERM RSH series heat generators are pressurised combustion boilers with flame reversal in the combustion chamber and three flue gas passes. The historical experience of the Ferroli S.p.A. Group in the design and production of steel boilers has ensured the development of a solid and reliable appliance with performance that puts it at the top of its category. PREXTHERM RSH in fact has a three star rating according to Directive 92/42 EEC. The main technical aspects of the design are: The careful design of the shapes, to ensure an optimum ratio between the combustion volumes and the heat exchange surfaces. The choice of materials used, for the long life of the boiler.

The range...
PREXTHERM RSH is made up of two series: QUADRA SERIES , 12 models from 80 to 800 kW TONDA SERIES 6 models from 900 to 2600 kW

Technical details

In order to increase the heat exchange between the flue gas and the central heating system, the PREXTHERM RSH boilers are fitted with a closed cylindrical furnace in which the flame produced by the burner is reversed from the bottom towards the door, from where the burned gas enters the rear collection chamber.

The tube bundle has been positioned above the combustion


chamber, so that the flue gas is always discharged into a hot environment, preventing the formation of condensate. The burner is not aligned with the combustion chamber, but rather has been moved downwards. This assists the reversal of the flame, reduces the pressure drop on the flue gas side and as a consequence extends the operating range of the generator. The combustion chamber is completely cooled (even at the rear), to ensure a greater heat exchange surface and improve the distribution of the heating load across the walls. The steel body is completely lined with an 80 mm thick layer of glass wool, in turn covered by a sturdy layer of tearproof material.

New turbulators have been designed for the PREXTHERM RSH, which improve the heat exchange of the flue gas and at the same time ensure a lower pressure drop than other solutions.

A baffle plate has been fitted at the central heating system return inlet to improve the circulation of cold water towards the bottom of the boiler. This solution ensures more uniform distribution of the heat exchange fluid across the boiler's heat exchange surface, achieving maximum heat exchange with less stress on the walls.

Central heating water return


3

PREXTHERM RSH

Technical details

FRONT DOOR To ensure the maximum flexibility in terms of positioning in the boiler room and assist the inspection and maintenance of the combustion chamber, the front door has been designed with a reversible opening, either on the right-hand or left-hand side. As well as sealing the combustion chamber, the door is an integral part of the flue gas path. Special attention has been focused on the insulation, so as to guarantee the least possible heat loss and maximum resistance to high temperatures. The door lining in the series Quadra is ceramic fibre, while the Tonda series has a double cement lining plus an extra layer of insulating material.

To avoid flue gas leaks at high temperatures (which may cause burning and deformations over time), the door has a double door stop with a new-concept locking and centring system. The door can be centred on the combustion chamber with just one simple operation, guaranteeing a perfect seal.

The tube bundle protrudes from the rear plate by a few millimetres so as to increase the temperature near the welding. This prevents the formation of condensate and the consequent corrosion of the materials.

Controls

KEY 1. Pump ON switch 2. Burner ON switch 3. Boiler ON switch 4. Test button 5. Safety button with manual reset 6. Boiler water temperature 7. Boiler ON LED 8. 1st burner flame LED 9. 2nd burner flame LED 10. Burner lockout LED 11. Safety pressure switch LED 12. 2nd boiler flame control thermostat TR1 13. 1st boiler flame control thermostat TR1 14. Space for optional temperature controller (not supplied)

9 10 11

14

13 12 6 5

Flue gas pass diagram

PREXTHERM RSH
PREXTHERM RSH 80-800
A F F1 D
T1-T3-T2

Technical specifications and dimensions

I B N
T3
??????? ?????? ??????? ???? ???????

E P
T2
??????? ?????? ???????? ??????

O
T1

T1-T3-T2

???? ?? ????

???? ? ????

T5

T5

T6

M G

T4

T4

L L1

Q S

KEY T1 Central heating flow outlet T2 Central heating return inlet T3 Expansion vessel attachment

T4 Boiler drain T5 Flue attachment T6 Burner attachment

PREXTHERM RSH Rated heat output kW kW Heat input kW kW Water content dm3 Useful efficiency at Pn max (Tm 70C) % Useful efficiency at Pn min (Tm 70C) % Useful efficiency at 30% Pn max (Tm 50C) % Energy marking (Directive 92/42 EEC) Operating pressure bar Water side pressure drop t 10C p mbar t 20C p mbar Flue gas side pressure drop p mbar Boiler weight when empty kg DIMENSIONS A mm B mm C mm D mm E mm F mm F1 mm G mm H mm I mm L mm L1 mm M mm N mm O mm P mm Q mm R mm S mm Hot water outlet T1 DN Hot water return T2 DN Expansion vessel attachment T3 DN Boiler drain T4 DN Flue gas outlet T5 min max min max

80 60 92 63,7 97,7 117 94,19 95,40 95,42 6 11 2 0,7 310 800 801 911 165 139 164 110 575 430 1104 100 52 980 176 150 250 750 761 905 50 50 1 1/4 3/4 200

90 70 107 74,3 113,5 154 94,27 95,50 95,52 6 20 5 1,2 330 800 1051 911 165 139 164 110 575 430 1354 100 52 980 176 250 400 750 1011 905 50 50 1 1/4 3/4 200

130 100 152 105,8 160,8 227 94,52 95,75 95,77 6 12 3 1,2 490 940 1053 1071 165 159 164 110 690 495 1376 100 50 1140 180 250 350 890 1013 1065 65 65 1 1/2 3/4 220

160 137 190 144,4 200,2 283 94,92 95,44 95,75 6 17 4 2,3 540 940 1303 1071 165 159 164 110 690 495 1626 100 50 1140 230 350 450 890 1263 1065 65 65 1 1/2 3/4 220

200 160 240 168,4 252,6 274 95,02 95,71 96,02 6 40 9 3,3 590 940 1304 1071 165 159 164 110 690 495 1627 100 50 1140 230 350 450 890 1264 1065 65 65 1 1/2 3/4 220

250 196 320 206 336,4 326 95,15 95,84 96,15 6 48 13 4,4 630 940 1554 1071 165 159 164 110 690 495 1877 100 50 1140 230 400 600 890 1514 1065 65 65 1 1/2 3/4 220

350 260 399 272,6 418,4 421 95,37 96,06 96,37 6 34 10 3,3 890 1050 1554 1181 165 185 254 110 730 518 1993 100 50 1250 228 400 600 1000 1514 1185 80 80 2 3/4 250

450 341 500 357 523,5 498 95,52 96,21 96,52 6 51 16 4,8 930 1050 1854 1181 165 185 254 200 730 518 2293 100 50 1250 228 400 800 1000 1814 1185 80 80 2 3/4 250

500 390 600 407,9 627,6 707 95,62 96,31 96,62 6 32 10 4,5 1250 1250 1856 1331 165 204 254 200 840 565 2314 100 48 1400 230 400 800 1200 1816 1354 100 100 65 3/4 350

600 468 720 489,8 753,6 802 95,56 96,25 96,56 6 40 18 5,6 1340 1250 2046 1331 165 204 254 200 840 565 2504 100 48 1400 230 390 1000 1200 2006 1354 100 100 65 3/4 350

700 533 820 558,4 859,1 727 95,47 96,16 96,47 6 51 16 5,4 1410 1250 2046 1331 165 204 254 200 840 565 2504 100 48 1400 230 390 1000 1200 2006 1354 100 100 65 3/4 350

800 611 940 638,9 982,9 819 95,65 96,34 96,65 6 65 20 6 1580 1250 2306 1331 165 204 254 200 840 565 2764 100 48 1400 230 650 1000 1200 2266 1354 100 100 65 3/4 350

PREXTHERM RSH 900-2600


A F N
T1-T3-T2
??????? ?????? ??????? ???? ???????

I B O T1 T3
??????? ?????? ???????? ??????

A E P T2 T1-T3-T2

???? ??????

???? ?????

T5 C M

T5

T6

T4 L

T4

L1

KEY T1 Central heating flow outlet T2 Central heating return inlet T3 Expansion vessel attachment PREXTHERM RSH Rated heat output Heat input Water content min max min max

T4 Boiler drain T5 Flue attachment T6 Burner attachment 900 kW kW kW kW dm3 689 1060 719,9 1107,6 1270 95,72 96,41 96,72 6 86 25 6,5 2250 1430 2460 1580 233 274 890 715 2967 120 71 1738 762 500 700 1000 125 125 80 1 1/2 400 1100 813 1250 848,2 1304,2 1363 95,86 96,55 96,87 6 110 32 6,8 2450 1430 2710 1580 233 274 890 715 3217 120 71 1738 812 550 850 1000 125 125 80 1 1/2 400 1300 962 1480 1004,4 1545,2 2000 95,80 96,49 96,81 6 100 29 7 3350 1660 2724 1810 243 274 1005 790 3241 120 69 1968 814 550 850 1000 150 150 100 1 1/2 450 6 150 42 7,2 3700 1660 3014 1810 243 274 1005 790 3531 120 69 1968 864 650 1000 1000 150 150 100 1 1/2 450 6 145 45 7,5 5050 1850 3366 2000 253 274 1100 850 3893 120 67 2158 866 1000 1000 1170 200 200 125 1 1/2 500 6 200 61 7,8 5500 1850 3666 2000 253 274 1100 850 4193 120 67 2158 866 1000 1000 1170 200 200 125 1 1/2 500 1600 1229 1845 1291,2 1938 2153 95,60 95,80 96,50 2000 1535 2360 1603,1 2454,7 3142 95,77 96,39 96,78 2600 1950 3000 2033,7 3128,8 3276 95,90 96,59 96,91

Useful efficiency at Pn max (Tm 70C) % Useful efficiency at Pn min (Tm 70C) % Useful efficiency at 30% Pn max (Tm 50C) % Energy marking (Directive 92/42 EEC) Operating pressure bar Water side pressure drop t 10C p mbar t 20C p mbar Flue gas side pressure drop p mbar Boiler weight when empty kg DIMENSIONS A B C E F G H I L L1 M N O P Q Hot water outlet T1 Hot water return T2 Expansion vessel attachment T3 Boiler drain T4 Flue gas outlet T5 mm mm mm mm mm mm mm mm mm mm mm mm mm mm mm DN DN DN DB

FERROLI

around the World

ITALY www.ferroli.it SPAIN www.ferroli.es FRANCE www.ferroli.fr UNITED KINGDOM www.ferroli.co.uk NETHERLANDS www.agpoferroli.nl GERMANY www.ferroli.de TURKEY www.ferroli.com.tr ROMANIA www.ferroli.ro POLAND www.ferroli.com.pl RUSSIA www.ferroli.msk.ru UKRAINE www.ferroli.ua BELARUS www.ferroli.by CHINA www.ferroli.com.cn BALKANS www.ferroli.hr IRAN www.ferroli.ir

Ferroli spa 37047 San Bonifacio (Verona) Italy Via Ritonda 78/A tel. +39.045.6139411 fax +39.045.6100233 www.gruppoferroli.com e-mail: export@ferroli.it

WARNING FOR TRADERS: As part of its efforts to constantly improve its range of products, with the aim of increasing the level of Customer satisfaction, the Company stresses that the appearance, dimensions, technical data and accessories may be subject to variation. Consequently, ensure that the Customer is provided with updated documents. The products described in this document are covered by warranty if purchased and installed in Italy.

Cod. 00000000/00 - 07.08