LV circuit breakers

EasyPact from 15 A to 250 A

Catalogue

2005

EasyPact

General contents

Presentation Circuit breakers Busbars Installation guide

545E1003TDM 545E2003TDM 545E3003TDM 545E4003TDM

25 novembre 2004 10:36

545E1003TDM_Ver1.0.fm/1

EasyPact

TM

Follow the way to simplicity


With only two sizes of circuit breakers, the EasyPact system is the simple and universal solution to fit all the needs in terms of low voltage protection.

EZC100-28

EZC250-37

EasyPact range complies to worldwide standards


b IEC 60947-2 b JIS 8370 b JIS 8201-2-1 A1 / A2 b GB 14048-2 b Nema-AB1 b UL508 b CSA22-2 b IACS for Merchant Marine.
(International Association of Classification Societies: Veritas, Germanisher Lloyd's, Rina, USSR, Lloyd's Register)

DB106479

with international certifications and approuvals by independant Laboratories


ASEFA, KEMA, TILVA, TV, UL.

545E1003_Ver4.0.fm/2

DB106478

9 fvrier 2005 13:41

Easy to choose
DB106480

50 mm

EasyPact brings you easy solutions b from 15 A to 250 A b up to 36 kA at 415 V b in only two frame sizes b with a complete range of auxiliaries and accessories.

Easy to install
60 mm 75 mm 105 mm

b common installation dimensions - same depth - same panel cut-out. b the smallest depth (60 mm) b no settings, no adjustments b field-installable auxiliaries and accessories b bare cables connected through cable lugs, screwed inside the breaker.

Easy to use
b a thermal calibration suitable for use at 50C without derating b safe and reliable with positive contact indication
(no risk for maintenance: when green flag is visible, main contacts of the breakers are effectively opened, and not welded).
DB106481

DB106482

9 fvrier 2005 13:41

545E1003_Ver4.0.fm/3

545E1003_Ver4.0.fm/4

9 fvrier 2005 13:41

EasyPact

Circuit breakers

General characteristics Characteristics Catalogue numbers


EZC100B 7.5 kA (400 V AC) EZC100F 10 kA (400 V AC) EZC100N 15 kA (400 V AC) EZC100H 30 kA (400 V AC) EZC250F 18 kA (400 V AC) EZC250N 25 kA (400 V AC) EZC250H 36 kA (400 V AC)

545E2003/2 545E2003/4 545E2003/6


545E2003/6 545E2003/6 545E2003/7 545E2003/8 545E2003/9 545E2003/9 545E2003/10

Electrical and mechanical accessories overview


EasyPact EZ100 EasyPact EZ250

545E2003/11
545E2003/11 545E2003/12

Electrical auxiliaries Direct rotary handle Extended rotary handle Power connections and cable lugs Power connections and insulation of live parts DIN rail adaptor, padlocking, sealing screws

545E2003/13 545E2003/15 545E2003/16 545E2003/17 545E2003/18 545E2003/19

14 dcembre 2004 09:58

545E2003TDM_Ver1.0.fm/1

Circuit breakers

General characteristics

Compliance with standards


EZC100H 100A

Ue(V) Icu / Ics(kA) IEC947-2 110/130 ~ 100 / 50 220/240 ~ 50 / 25 380/400 ~ 30 / 15 415 ~ 30 / 7.5 550 ~ 10 / 2.5 JIS C 8370 220 ~ 100 NEMA-AB1 240 ~ 100 (HIC) 277/480Y ~ 18 Ui=690V Uimp=6kV Cat.A 50/60Hz

EasyPact circuit breakers and auxiliaries comply with the following international standards: b IEC 60947-1 - general rules b IEC 60947-2 - low-voltage switchgear and controlgear, part 2 (circuit breakers) b European (EN 60947-1 and EN 60947-2) and the corresponding national standards b GB 14048-2 b JIS C 8370: Japanese industrial standard for molded case circuit breaker b JIS C 8201-2-1 Annex 1 and Annex 2 b NEMA AB1 (High Interrupting Capacity): American standard b UL508/CSA 22-2 No. 14.
EZC250H

DB106205

EZC100H
DB106207

TH01285

DB106206

Approvals and Certfications


b IEC certfication by independent laboratories (ASEFA, KEMA, TV) b b b

marking certified by third party Tilva certified by third party Underwriter Laboratories as a "Manual Motor Controller" (approval pending for EZC100).

Vibration and shock withstand test


EasyPact circuit breakers resist mechanical vibrations and shocks. Tests are carried out in compliance with standard IEC 60068-2-6 for the levels required by merchant-marine inspection organisation IACS: International Association of Classification Societies (Veritas, Germanisches Lloyds, Rina, USSR, Lloyds Register). b 2 to 13.2 Hz: amplitude 1 mm 13.2 to 100 Hz: acceleration 0.7g.
Standardised characteristics indicated on the rating plate: Ui: rated insulation voltage Uimp: rated impulse withstand voltage Icu: ultimate breaking capacity, for various values of the rated operational voltage Ue Cat: utilisation category Ics: service breaking capacity suitable for isolation

Pollution degree
EasyPact circuit breakers are certified for operation in pollution-degree III environments as defined by IEC standard 60947 (industrial environments).

Tropicalisation
EasyPact circuit breakers have successfully passed the tests prescribed by the following standards for extreme atmospheric conditions: b IEC 60068-2-1 - dry cold (- 55 C) b IEC 60068-2-2 - dry heat (+ 85 C) b IEC 60068-2-30 - damp heat (95% relative humidity at 55 C) b IEC 60068-2-52 - salt mist (severity level 2).

EZ101PR-20

EZ101PR-28

Positive contact indication


All EasyPact circuit breakers are suitable for isolation as defined in IEC standard 60947-2: b the isolation position corresponds to the O (OFF) position b the operating handle cannot indicate the O (OFF) position (green colour visible) unless the contacts are effectively open b padlocks may not be installed unless the contacts are open b installation of a rotary handle does not alter the reliability of the position-indication system. The isolation function is certified by tests guaranteeing: b the mechanical reliability of the position indication system b the absence of leakage currents b overvoltage withstand capacity between upstream and downstream connections.

Environmental protection
EasyPact circuit breakers take into account important concerns for environmental protection. Most components are recyclable and the parts are marked as specified in applicable standards.

545E2003_Ver5.0.fm/2

13 avril 2005 18:27

Circuit breakers

General characteristics

Ambient temperature
b EasyPact has been particularly designed to hold 100% In at 50 C without tripping in normal condition b EasyPact circuit breakers may be used between - 25 C and + 70 C b the permissible storage-temperature range for EasyPact circuit breakers in the original packing is - 35 C to + 85 C.

DB106003

Installation
EasyPact circuit breakers are designed for easy installation in the various types of switchboards. They may be mounted vertically, horizontally or flat on their back without any derating of characteristics
Installation positions

DB106037

Power supply
EasyPact circuit breaker can be supplied from either the top or the bottom (reverse feeding) without any reduction in performance. This capability facilitates connection when installed in a switchboard.

Degree of protection
As per standards IEC 60529 (IP degree of protection) and EN 50102 (IK degree of protection against external mechanical impacts).
Reverse feeding

Bare circuit breaker with terminal shields


With toggle
DB106013

IP20

IK07

With direct rotary handle standard


DB106014

IP40

IK07

Circuit breaker installed in a switchboard


With toggle
DB106015 DB106035

IP40

IK07

DB106016

With direct rotary handle standard/VDE MCC

IP54

IK07

With extended rotary handle


DB106017

IP54

IK08

13 avril 2005 18:27

545E2003_Ver5.0.fm/3

Circuit breakers

Characteristics

EasyPact circuit breakers


EZ110P-34

Number of poles Rated current (A)

In

at 40 C

Rated insulation voltage (V) Rated impulse withstand voltage (kV) Rated operational voltage (V) EZC100

Ui Uimp Ue

AC 50/60 Hz DC AC 50/60 Hz 110/130 V 220/230/240 V 380 V 400/415 V 440 V 550 V DC 125 V (1P) 250 V (2P in series) % Icu 110-400 V 415-550 V

Electrical characteristics as per IEC 60947-2 and EN 60947-2


Ultimate breaking capacity (kA rms) Icu

Rated service breaking capacity Suitability for isolation Utilisation category Pollution degree Endurance (C-O cycles)
PB101210-27

Ics

Mechanical Electrical In/415 V Icn AC 50/60 Hz 130 V 220 V 460 V AC 50/60 Hz 240 V 277/480Y V

Electrical characteristics as per JIS C8370


Breaking capacity (kA)

EZC250

Electrical characteristics as per NEMA-AB1 Breaking capacity (kA) Protection Overload protection Instantaneous protection Auxiliaries Indication contacts

HIC

Bimetal Magnetic Auxiliary switch Alarm switch Combined AX + AL Shunt trip release Undervoltage release Crimp lugs/bars Box lugs for bare cables Rotary handles Terminal extensions Spreaders Phase barriers Terminal shields Padlocking system DIN rail plate AX AL AXAL SHT UVR

Voltage releases

Installation
Connection Accessories

direct extended

Dimension and weight Dimensions (mm) Weight (kg)

DxH W

545E2003_Ver5.0.fm/4

13 avril 2005 18:27

Circuit breakers

Characteristics

EZC100B

EZC100F

EZC100N
1 15, 20, 25, 30, 40, 50, 60, 75, 80, 100 690 6 550 250 25 18 2.5 2.5 5 50% 50% A 3 8 500 1 500 15 10 10 (2) fixed fixed 3 15, 20, 25, 30, 40, 50, 60, 75, 80, 100 690 6 550 250 25 25 18 15 10 5 5 5 50% 50% A 3 8 500 1 500 25 25 10 25 10 fixed fixed

EZC100H
1 15, 20, 25, 30, 40, 50, 60, 75, 80, 100 690 6 550 250 50 25 5 5 10 50% 50% A 3 8 500 1 500 30 18 18 (2) fixed fixed 2-3 15, 20, 25, 30, 40, 50, 60, 75, 80, 100 690 6 550 250 100 100 (1) 30 30 20 10 10 10 50% 25% A 3 8 500 1 500 100 100 25 100 18 (3) fixed fixed

EZC250F EZC250N
3 100, 125, 150, 160, 175, 200, 225, 250 690 6 550 250 25 25 18 18 15 5 5 5 50% 50% A 3 10 000 5 000 30 30 15 25 15 fixed fixed 3 100, 125, 150, 160, 175, 200, 225, 250 690 6 550 250 50 50 25 25 20 8 20 20 50% 50% A 3 10 000 5 000 50 50 25 50 18 fixed fixed

EZC250H
2-3 100, 125, 150, 160, 175, 200, 225, 250 690 6 550 250 85 85 36 36 25 10 30 30 50% 50% A 3 10 000 5 000 85 85 35 85 25 (3) fixed fixed

3 3 15, 20, 25, 30, 40, 15, 20, 25, 30, 50, 60 40, 50, 60, 75, 80, 100 690 6 550 10 10 7.5 7.5 5 2.5 25% 25% A 3 8 500 1 500 10 10 5 fixed fixed 690 6 550 250 25 25 10 10 7.5 5 5 5 50% 50% A 3 8 500 1 500 25 25 7.5 fixed fixed

(3) (3)

(3)

60 x 130 75 0.78 60 x 130 75 0.78 60 x 130 25 0.28 60 x 130 75 0.78 60 x 130 25 0.28 60 x 130 60 x 165 50 (2P), 75 (3P) 105 0.6(2P), 0.78(3P) 1.3

60 x 165 105 1.3

60 x 165 105 1.1 (2P), 1.3 (3P)

(1) 50 kA for 2 poles (2) for 277 V only (3) for 3 poles only

13 avril 2005 18:27

545E2003_Ver5.0.fm/5

Circuit breakers

Catalogue numbers EZC100B 7.5 kA (400 V AC) EZC100F 10 kA (400 V AC)


EZC100B 15 to 60 A

EZ104P-20

Designation Current rating (A) Number of poles

EZC100B 15 - 20 - 25 - 30 - 40 - 50 - 60 3P
Icu (kA) 10 7.5 5 2.5 Icn (kA) 10 5 Ics (% Icu) 25% 25% 25% 25%

EZC100B 3 poles

Breaking capacities (kA rms) as per IEC 60947-2 Ue (V) Ue = 550 V AC 220/230/240 Ui = 690 V 380/400/415 Uimp = 6 kV 440 550 Breaking capacities (kA rms) as per JIS C8370 Ue (V) AC 220 460 Rating Cat. Nb 3P 15 A EZC100B3015 20 A EZC100B3020 25 A EZC100B3025 30 A EZC100B3030 40 A EZC100B3040 50 A EZC100B3050 60 A EZC100B3060

EZC100F 15 to 100 A
EZ105P-19

Designation Current rating (A) Number of poles

EZC100F 15 - 20 - 25 - 30 - 40 - 50 - 60 - 75 - 80 - 100 3P
Icu (kA) 25 10 7.5 5 5 5 Icn (kA) 25 7.5 Ics (% Icu) 50% 50% 50% 50% 50% 50%

EZC100F 3 poles

Breaking capacities (kA rms) as per IEC 60947-2 Ue (V) Ue = 550 V AC 220/230/240 Ui = 690 V 380/400/415 Uimp = 6 kV 440 550 DC 125 (1P) 250 (2P) Breaking capacities (kA rms) as per JIS C8370 Ue (V) AC 220 460 Rating Cat. Nb 3P 15 A EZC100F3015 20 A EZC100F3020 25 A EZC100F3025 30 A EZC100F3030 40 A EZC100F3040 50 A EZC100F3050 60 A EZC100F3060 75 A EZC100F3075 80 A EZC100F3080 100 A EZC100F3100

545E2003_Ver5.0.fm/6

13 avril 2005 18:27

Circuit breakers

Catalogue numbers EZC100N 15 kA (400 V AC)

EZC100N 15 to 100 A
EZ106P-10 EZ101P-19

Designation Current rating (A) Number of poles

EZC100N 15 - 20 - 25 - 30 - 40 - 50 - 60 - 75 - 80 - 100 1P and 3P


Ics (% Icu) 1P - 3P 50% 50% 50% 50% 50% 50% 50% 50%

EZC100N 1 pole

EZC100N 3 poles

Breaking capacities (kA rms) as per IEC 60947-2 Ue (V) Icu (kA) 1P Ue = 550 V AC 110/130 25 Ui = 690 V 220/230/240 18 Uimp = 6 kV 380 2.5 400/415 2.5 440 550 DC 125 (1P) 5 250 (2P) Breaking capacities (kA rms) as per JIS C8370 Ue (V) Icn (kA) AC 110/130 15 220 460 Breaking capacities (kA rms) as per NEMA-AB1 Ue (V) HIC (kA) AC 240 277 10 480 Rating Cat. Nb 1P 15 A EZC100N1015 20 A EZC100N1020 25 A EZC100N1025 30 A EZC100N1030 40 A EZC100N1040 50 A EZC100N1050 60 A EZC100N1060 75 A EZC100N1075 80 A EZC100N1080 100 A EZC100N1100

3P 25 18 15 10 5 5 5

25 10

25 10 Cat. Nb 3P EZC100N3015 EZC100N3020 EZC100N3025 EZC100N3030 EZC100N3040 EZC100N3050 EZC100N3060 EZC100N3075 EZC100N3080 EZC100N3100

13 avril 2005 18:27

545E2003_Ver5.0.fm/7

Circuit breakers

Catalogue numbers EZC100H 30 kA (400 V AC)

EZC100H 15 to 100 A
EZ108P-11 EZ101P-40

Designation Current rating (A) Number of poles

EZC100H 15 - 20 - 25 - 30 - 40 - 50 - 60 - 75 - 80 - 100 1P, 2P and 3P


Ics (% Icu) 1P 50% 50% 50% -

Breaking capacities (kA rms) as per IEC 60947-2 Ue (V) Icu (kA) 1P 2P 3P 110/130 50 100 220/230/240 25 50 100 380/400/415 5 30 30 440 20 20 550 10 10 DC 125 (1P) 10 10 10 250 (2P) 5 10 Breaking capacities (kA rms) as per JIS C8370 Ue (V) Icn (kA) AC 110/130 30 220 100 100 460 25 25 Breaking capacities (kA rms) as per NEMA-AB1 Ue (V) HIC (kA) AC 240 100 100 277 18 480 18 Rating Cat. Nb 1P Cat. Nb 2P 15 A EZC100H1015 EZC100H2015 20 A EZC100H1020 EZC100H2020 25 A EZC100H1025 EZC100H2025 30 A EZC100H1030 EZC100H2030 40 A EZC100H1040 EZC100H2040 50 A EZC100H1050 EZC100H2050 60 A EZC100H1060 EZC100H2060 75 A EZC100H1075 EZC100H2075 80 A EZC100H1080 EZC100H2080 100 A EZC100H1100 EZC100H2100 AC

EZC100H 1 pole

EZC100H 2 poles

Ue = 550 V Ui = 690 V Uimp = 6 kV

2P - 3P 50% 50% 50% 25% 25% -

EZ110P-34

EZC100H 3 poles

Cat. Nb 3P EZC100H3015 EZC100H3020 EZC100H3025 EZC100H3030 EZC100H3040 EZC100H3050 EZC100H3060 EZC100H3075 EZC100H3080 EZC100H3100

545E2003_Ver5.0.fm/8

13 avril 2005 18:27

Circuit breakers

Catalogue numbers EZC250F 18 kA (400 V AC) EZC250N 25 kA (400 V AC)


EZC250F 100 to 250 A

PB101208-27

Designation Current rating (A) Number of poles

EZC250F 100 - 125 - 150 - 160 - 175 - 200 - 225 - 250 3P


Icu (kA) 25 18 15 5 10 10 Icn (kA) 30 15 HIC (kA) 25 15 Ics (% Icu) 50% 50% 50% 50% 50% 50%

EZC250F 3 poles

Breaking capacities (kA rms) as per IEC 60947-2 Ue (V) Ue = 550 V AC 220/230/240 Ui = 690 V 380/400/415 Uimp = 6 kV 440 550 DC 125 (1P) 250 (2P) Breaking capacities (kA rms) as per JIS C8370 Ue (V) AC 220 460 Breaking capacities (kA rms) as per NEMA-AB1 Ue (V) AC 240 277/480 Rating Cat. Nb 3P 100 A EZC250F3100 125 A EZC250F3125 150 A EZC250F3150 160 A EZC250F3160 175 A EZC250F3175 200 A EZC250F3200 225 A EZC250F3225 250 A EZC250F3250

EZC250N 100 to 250 A


PB101209-27

Designation Current rating (A) Number of poles

EZC250N 100 - 125 - 150 - 160 - 175 - 200 - 225 - 250 3P


Icu (kA) 50 25 20 8 20 20 Icn (kA) 50 25 HIC (kA) 50 18 Ics (% Icu) 50% 50% 50% 50% 50% 50%

EZC250N 3 poles

Breaking capacities (kA rms) as per IEC 60947-2 Ue (V) Ue = 550 V AC 220/230/240 Ui = 690 V 380/400/415 Uimp = 6 kV 440 550 DC 125 (1P) 250 (2P) Breaking capacities (kA rms) as per JIS C8370 Ue (V) AC 220 460 Breaking capacities (kA rms) as per NEMA-AB1 Ue (V) AC 240 277/480 Rating Cat. Nb 3P 100 A EZC250N3100 125 A EZC250N3125 150 A EZC250N3150 160 A EZC250N3160 175 A EZC250N3175 200 A EZC250N3200 225 A EZC250N3325 250 A EZC250N3250

13 avril 2005 18:27

545E2003_Ver5.0.fm/9

Circuit breakers

Catalogue numbers EZC250H 36 kA (400 V AC)

EZC250H 100 to 250 A


PB101211-27

Designation Current rating (A) Number of poles

EZC250H 100 - 125 - 150 - 160 - 175 - 200 - 225 - 250 2P and 3P
Icu (kA) 2P 85 36 25 10 30 30 Icn (kA) 2P 85 35 HIC (kA) 2P 85 Ics (% Icu) 3P 85 36 25 10 30 30 50% 50% 50% 50% 50% 50%

Breaking capacities (kA rms) as per IEC 60947-2 Ue (V) Ue = 550 V Ui = 690 V Uimp = 6 kV EZC250H 2 poles 220/230/240 380/400/415 440 550 DC 125 (1P) 250 (2P) Breaking capacities (kA rms) as per JIS C8370 Ue (V) 220 460 Breaking capacities (kA rms) as per NEMA-AB1 Ue (V) AC Rating 100 A 125 A 150 A 160 A 175 A 200 A 225 A 250 A 240 277/480 Cat. Nb 2P EZC250H2100 EZC250H2125 EZC250H2150 EZC250H2160 EZC250H2175 EZC250H2200 EZC250H2225 EZC250H2250 AC AC

PB101210-27

3P 85 35

3P 85 25

EZC250H 3 poles

Cat. Nb 3P EZC250H3100 EZC250H3125 EZC250H3150 EZC250H3160 EZC250H3175 EZC250H3200 EZC250H3225 EZC250H3250

545E2003_Ver5.0.fm/10

13 avril 2005 18:27

Circuit breakers

Electrical and mechanical accessories overview EasyPact EZ100


EasyPact circuit breaker EZ100 comes with a full range of accessories to fulfill different application requirements and make it easy for the end-user.

Terminal shield
DB106047-120

Phase barriers

Sealing screw

DIN rail adaptor Spreaders

Cable lugs

Shunt trip, Undervoltage release

Direct rotary handle Auxiliary switch, Alarm switch, Auxiliary/Alarm switch Padlocking device

Spreaders Cable lugs

Extended rotary handle

Sealing screw Sealable terminal shield Phase barriers

13 avril 2005 18:27

545E2003_Ver5.0.fm/11

Circuit breakers

Electrical and mechanical accessories overview EasyPact EZ250


EasyPact circuit breaker EZ250 comes with a full range of accessories to fulfill different application requirements and make it easy for the end-user.

Terminal shield
DB106002-140

Phase barriers

Cable lugs Terminal extensions

Spreaders

Undervoltage release

Shunt trip

Direct rotary handle

Padlocking device

Auxiliary switch, Alarm switch, Auxiliary/Alarm switch

Extended rotary handle

Cable lugs Terminal extensions

Spreaders

Terminal shield Phase barriers

545E2003_Ver5.0.fm/12

13 avril 2005 18:27

Circuit breakers

Electrical auxiliaries

Electrical auxiliaries can be installed in either location (left or right) regardless of the function (AX - AL - AXAL)
PB101219-27

Indication contacts
Common-point changeover contacts provide remote circuit breaker status information. They can be used for indications, electrical locking, relaying, etc.. b Auxiliary switch AX (ON/OFF) indicates the position of the circuit breaker contacts. b Alarm switch AL (trip indication) indicates that the circuit breaker has tripped due to: v an overload v a short-circuit v operation of a voltage release It returns to de-energised state when the circuit breaker is reset.

Characteristics
Contacts
Rated thermal current (A) Minimum load Utilisation category (IEC 60947-5-1) Operational current (A) 24 V 48 V 125 V 250 V 5 10 mA at 24 V AC12 AC15 5 5 5 5 5 3 3 2

PB101220-27

DC12 4 2.5 0.4 0.2

DC14 3 1 0.4 0.2

Connections
Connection wire length Cross-section 500 mm EZC100: 1 mm2, EZC250: 1.5 mm2

Electrical auxiliaries are pre-wired


PB101223-15 PB101226-15

DB106033

All EasyPact electrical auxiliaires are "snapped in place"

Auxiliary switch (AX) EZAUX10

Auxiliary switch (AX) EZEAX

Designation
Auxiliary switch (AX) Alarm switch (AL) Auxiliary/Alarm switch (AX/AL)

Cat. number
EZC100 EZAUX10 EZAUX01 EZAUX11

Cat. number
EZC250 EZEAX EZEAL EZEAXAL

13 avril 2005 18:27

545E2003_Ver5.0.fm/13

Circuit breakers

Electrical auxiliaries

Remote tripping
Shunt Trip (SHT) or Under Voltage Release (UVR).
PB101222-27

b Shunt Trip (SHT) v this release trips the circuit breaker when the control voltage rises above 0.7 x Un v control signals can be of the impulse type (> 20 ms) or maintained. b Under Voltage Release (UVR) v this release trips the circuit breaker when the control voltage drops below a tripping threshold v tripping threshold between 0.35 and 0.7 times the rated voltage v circuit breaker closing is possible only if the voltage exceeds 0.85 times the rated voltage v circuit breaker tripping by an UVR release meets the requirements of standard IEC 60947-2. b Operation When the circuit breaker has been tripped by an UVR or SHT release, it must be reset locally: v UVR or SHT tripping takes priority over manual closing v in the presence of a standing trip order, closing of the contacts, even temporary, is not possible.

SHT (MX) and UVR (MN) voltage release on EZC100


PB101221-29

Characteristics
Mechanical
mechanical endurance 10% of MCCB mechnical endurance

Electrical
SHT UVR pick-up consumption response time seal-in consumption response time

EZC100
< 30 VA < 50 ms < 5 VA < 50 ms

EZC250 AC
< 30 VA < 50 ms < 5 VA < 50 ms

DC
< 35 W < 100 ms < 10 W < 100 ms

Connections
SHT (MX) and UVR (MN) voltage release on EZC250 SHT UVR

EZC100
pre-wired (1 mm2) pre-wired (1 mm2)

EZC250
pre-wired (0.5 mm2) screws (< 2 mm2)

b Installation v EZC100 SHT and UVR: internal mounting (left or right side) v EZC250: - SHT: internal mounting (right side) - UVR: external mounting (right side).
PB101229-15 PB101231-15

Designation
Shunt Trip Release (SHT) 100-130 V AC 200-277 V AC 380-480 V AC 24 V DC 48 V DC 110-130 V AC 200-240 V AC 277 V AC 380-415 V AC 440-480 V AC 24 V DC 48 V DC 125 V DC

Cat. number
EZC100 EZASHT100AC EZASHT200AC EZASHT380AC EZASHT024DC EZASHT048DC EZAUVR110AC EZAUVR200AC EZAUVR277AC EZAUVR380AC EZAUVR440AC EZAUVR024DC EZAUVR048DC EZAUVR125DC 100-120 V AC 120-130 V AC 200-240 V AC 277 V AC 380-440 V AC 440-480 V AC 24 V DC 48 V DC 110-130 V AC 200-240 V AC 277 V AC 380-415 V AC 440-480 V AC 24 V DC 48 V DC 125 V DC

Cat. number
EZC250 EZESHT100AC EZESHT120AC EZESHT200AC EZESHT277AC EZESHT400AC EZESHT440AC EZESHT024DC EZESHT048DC EZEUVR110AC EZEUVR200AC EZEUVR277AC EZEUVR400AC EZEUVR440AC EZEUVR024DC EZEUVR048DC EZEUVR125DC

Shunt Trip EZASHT


PB101230-15 PB101232-15

Shunt Trip EZESHT

Under Voltage Release (UVR)

Under Voltage Release EZAUVR

Under Voltage Release EZEUVR

545E2003_Ver5.0.fm/14

13 avril 2005 18:27

Circuit breakers

Direct rotary handle

PB101233-40

Direct rotary handle suitable for Motor Control Centre (MCC) switchboards
b Degree of protection IP40 or IP54, IK07 (IP54 with gasket provided with the EZAROTDS and EZEROTDS). b The direct rotary handle maintains: v suitability for isolation v indication of the three positions O (OFF), I (ON) and tripped v circuit breaker locking capability in the OFF position by one to three padlocks, (padlock not supplied) shackle diameter 5 for EZC100, 8 for EZC250 v door opening disabled when the circuit breaker is ON v circuit breaker closing is disabled if the door is open.

Direct rotary handle for EZC100

IP40 or IP54

DB106005

PB101234-40

DB106006

gasket for IP54

gasket for IP54

Direct rotary handle for EZC250

EZC100

EZC250

Padlocking

DB106007

EZC100

DB106008

EZC250

Designation
Direct rotary handle standard

Cat. number
EZC100 EZAROTDS

Cat. number
EZC250 EZEROTDS

13 avril 2005 18:27

545E2003_Ver5.0.fm/15

Circuit breakers

Extended rotary handle

Extended rotary handle


PB101235-40

This handle makes it possible to operate circuit breakers installed at the back of switchboards, from the switchboard front. b Degree of protection IP40 or IP54, IK08 (with gasket provided with the EZAROTE and EZEROTE) b The extended rotary handle maintains: v suitability for isolation v indication of the three positions O (OFF), I (ON) and tripped v circuit breaker locking capability in the OFF position by one to three padlocks, (padlock not supplied) shackle diameter: 5 for EZC100, 8 for EZC250 v door opening disabled when the circuit breaker is ON.
Extended rotary handle for EZC100

b The extended rotary handle is made up of: v a unit on the front cover of the circuit breaker (secured by screws) v an assembly (handle and front plate) on the door that is always secured in the same position, whether the circuit breaker is installed vertically or horizontally v an extension shaft that must be adjusted to the distance (min/max distance between back of circuit breaker and door is 145/422 mm). IP40 or IP54
DB106281

PB101236-40

Extended rotary handle for EZC250

EZC100

DB106282

EZC250

Padlocking

DB106028

Designation
Extended rotary handle

Cat. number
EZC100 EZAROTE

Cat. number
EZC250 EZEROTE

545E2003_Ver5.0.fm/16

13 avril 2005 18:27

Circuit breakers

Power connections and cable lugs

DB106029

All EasyPact circuit breakers are supplied with terminal screws 15 to 50 A Screw M5
E88221

60 to 100 A

Screw M8

E88222

100 to 250 A
DB106044

Screw M8

EZC100 with M5 / M8 screws

Connection of insulated bars or cables with lugs EZC100


Bars
DB106018 E50702

EZC250
< 25 d + 10 <8 <6 9

400 l L e
Crimp lugs

d L

L (mm) l (mm) d (mm) e (mm) (mm)

< 50 A > 50 A

< 17 d + 10 <7 <6 5.5 8.5

L (mm) d (mm) (mm) < 50 A > 50 A

< 50 A > 50 A

Tightening torque (N.m)

< 17 <9 5.5 8.5 2 N.m 5.5 N.m

< 25 <8 9 13 N.m

Connection of bare cables with cable lugs This connector screws directly to the standard connectors. It is used to connect: > 50 A (EZC100) > 100 A (EZC250) < 50 A (EZC100)
DB106045 E88190 E88189

cables from 2.5 to 16 mm2

cables from 10 to 50 mm2

cables from 42.2 to 150 mm2

DB106032

Designation
Cable lug up to 50 A (set of 2) Cable lug up to 50 A (set of 3) Cable lug from 60 A up to 100 A (set of 2) Cable lug from 60 A up to 100 A (set of 3) Cable lug from 100 A up to 250 A (set of 3)

Cat. number EZC100


EZALUG0502 EZALUG0503 EZALUG1002 EZALUG1003 -

Cat. number EZC250


EZELUG2503

Nota : For EZC250, when cable lugs are used on upstream side, breaking capacity is limited to 50 % of rated value.

13 avril 2005 18:27

545E2003_Ver5.0.fm/17

Circuit breakers

Power connections and insulation of live parts

Spreader
Increases the pitch of the circuit breaker terminals: b EZC100 from 25 mm to 35 mm b EZC250 from 35 mm to 45 mm.

Terminal extensions
Additional terminal extensions are available for EZC250.
DB106041 PB101240-25 PB101241-25 DB106046

Spreader Terminal extensions

Designation
Spreader (1 set of 3) Terminal Extensions (1 set of 3)

Cat. number EZC100


EZASPDR3P

Cat. number EZC250


EZESPDR3P EZETEX

Phase barriers
b safety accessories for maximum insulation at the power connection points b slide easily onto the circuit breaker b usable with all other connection accessories, except terminal shields b each breaker is delivered with a set of 2 phase barriers for a 3 poles breaker and 1 phase barrier for a 2 poles breaker b an additional set of phase barriers is available for insulation between 2 side by side mounted breakers or outgoings.
DB106021 DB106022 PB101243-20

Phase barriers

Designation
Phase barriers (set of 2)

Cat. number EZC100


EZAFASB2

Cat. number EZC250


EZEFASB2

Terminal shield
PB101244-25 PB101245-25

b insulating accessories used for protection against direct contact with power circuits b designed for front connection only (long terminal shield) b designed for 3 poles base only.
DB106026

Terminal shield (3P only) for EZC100

Terminal shield for EZC250

Designation
Terminal shield for 3P only (set of 2)

Cat. number EZC100


EZATSHD3P

Cat. number EZC250


EZETSHD3P

545E2003_Ver5.0.fm/18

13 avril 2005 18:27

Circuit breakers

DIN rail adaptor, padlocking, sealing screws

DIN rail adaptor


Mounting on a DIN rail is possible using a special adaptor (for EZC100 only).
PB101246-25 DB106011

DIN rail adaptor Mounting on DIN rail (optional)

Designation
DIN rail adaptor

Cat. number EZC100


EZADINR

Cat. number EZC250


-

Padlocking system
Locking in the OFF position guarantees isolation as per IEC 60947-2. Padlocking system can receive: b up to 2 padlocks 5 mm (padlocks not supplied) for EZC100 b up to 3 padlocks 8 mm for EZC250 (padlocks not supplied)
DB106010 PB101247-25 PB101248-25 DB106009

Padlocking device for EZC100

Padlocking device for EZC250

Toggle locking using a removable device : for EZC100

for EZC250

Designation
Padlocking system

Cat. number EZC100


EZALOCK

Cat. number EZC250


EZELOCK

Sealing screws
PB101249-25 DB106027

Sealing screws (set of 2)

Designation
Sealing screws (set of 2)

Cat. number EZC100


EZASSCR

Cat. number EZC250


-

13 avril 2005 18:27

545E2003_Ver5.0.fm/19

545E2003_Ver5.0.fm/20

13 avril 2005 18:27

EasyPact

Busbars

Introduction Busbars characteristics Main busbars and extension Accessories

545E3003/2 545E3003/4 545E3003/5 545E3003/6

15 novembre 2004 08:02

545E3003TDM_Ver1.0.fm

Busbars

Introduction

545E3003_Ver1.0.fm/2

DB106019

17 dcembre 2004 09:39

Busbars

Introduction

The EasyPact Busbar - engineered and certified together with the EasyPact MCCB to provide superior performance, flexibility and value. Simply the best solution for your distribution panel needs: b available for 250 A, 400 A or 630 A main incoming current b available for 4, 6, 8, 10 or 12 Ways (3 poles) EasyPact 100 A (max.) outgoing MCCBs b 400 A and 630 A systems can accept an additional 2 or 4 EasyPact 250 or Compact NS/NB160/250 A outgoing MCCBs b designed and tested to meet IEC 60439-1 requirements b completely assembled in ISO certified facility for easy installation into locally made enclosures.

EZ116P-70

Premium Materials make a premium busbar system:


b solid copper busbars and connectors for cool, care-free operation b electro-tin plating on all busbars and connectors for corrosion resistance in all environments b fiberglass reinforced nylon bus supports for strength and dimensional stability b molded thermoplastic phase barriers to maintain alignment and ensure electrical isolation between phases b a nameplate with Schneider Electric on the bottom line - stands for quality and reliability.

17 dcembre 2004 09:39

545E3003_Ver1.0.fm/3

Busbars

Busbars characteristics

Compliance with standards


The EasyPact Busbar System is designed and certified to meet all international requirements specified in IEC 60439-1 relating to construction of Low Voltage switchgear and controlgear assemblies, including: b verification of temperature - rise limits b verification of dielectric properties b verification of short-circuit withstand strength b verification of clearances and creepage distances. In addition, the system has been type-tested in ASTA labs to confirm the short-circuit and short-time withstand ratings.
EZ148P-60

Enclosed 10 ways Busbar 250 A with 250 A main incomer

EasyPact Busbar System


Number of outgoing MCCBs EasyPact 100 A (max.) 1P 2P 3P EZ/NS/NB branch breaker Electrical characteristics Rated incoming current (A) Rated operational voltage (V) AC 50/60 Hz Rated insulation voltage (V) Breaking capacity Rated short-time withstand 1 sec. current (kA rms) Dimensions Dimensions (mm) L x W x D 4 Ways 6 Ways 8 Ways 10 Ways 12 Ways

EZB250
4 6 8 Ways Ways Ways 12 18 24 6 8 12 4 6 8 No extension 10 Ways 30 14 10 12 Ways 36 18 12

EZB400
4 6 8 10 12 Ways Ways Ways Ways Ways 12 18 24 30 36 6 8 12 14 18 4 6 8 10 12 Yes (2 or 4 Ways)

EZB630
4 6 8 10 12 Ways Ways Ways Ways Ways 12 18 24 30 36 6 8 12 14 18 4 6 8 10 12 Yes (2 or 4 Ways) 630 550 690 40

250 400 550 550 690 690 Refer to cascading tables page 17 30 40

268.5 x 416 x 82.5 343.5 x 416 x 82.5 418.5 x 416 x 82.5 493.5 x 416 x 82.5 568.5 x 416 x 82.5

290 x 416 x 107 365 x 416 x 107 440 x 416 x 107 515 x 416 x 107 590 x 416 x 107

290 x 416 x 107 365 x 416 x 107 440 x 416 x 107 515 x 416 x 107 590 x 416 x 107

545E3003_Ver1.0.fm/4

17 dcembre 2004 09:39

Busbars

Main busbars and extension

Main busbar
EZ149P-60

The core of the EasyPact Busbar System includes the main busbars and outgoing connectors for EasyPact MCCBs. Designation Cat. number Type EZB250 Main busbar current rating 250 A
# Branch Ways (3 poles EasyPact MCCBs) 4 Ways 6 Ways 8 Ways 10 Ways 12 Ways

EZB 400 400 A

EZB630 630 A

EZB250W04 EZB250W06 EZB250W08 EZB250W10 EZB250W12

EZB400W04 EZB400W06 EZB400W08 EZB400W10 EZB400W12

EZB630W04 EZB630W06 EZB630W08 EZB630W10 EZB630W12

EasyPact Busbar EZB250W08


DB106004 DB106020 DB106023 DB106024

4 Ways with 3 poles

6 Ways with 3 poles

8 Ways with 3 poles

10 Ways with 3 poles

DB106025

DB106306

12 Ways with 3 poles

6 Ways with 1 pole

DB106307

6 Ways with 1 pole

EasyPact and Compact NS/NB branch extension


For applications calling for larger than 100 A outgoing MCCBs, EasyPact Busbar rated 400 A and 630 A can accept the 2 Ways or 4 Ways EasyPact and Compact NS/NB branch extension for up to four additional 250 A max. outgoing circuits. EasyPact and Compact NS/NB branch extensions simply connect directly to the terminals provided on the EZB400 and EZB630 EasyPact Busbar. Designation EZ/NS/NB branch breaker extention
2 Ways 4 Ways EasyPact and Compact NS/NB branch breaker extension 2 Ways
E88637-60

Cat. number

EZBNS2 EZB2NS2

17 dcembre 2004 09:39

545E3003_Ver1.0.fm/5

Busbars

Accessories

Main incoming connections


DB106042 ....... E88301-50

Incoming cables with crimped lugs can connect directly to the terminals provided.

>10

= 37

Main connectors
EZ117P-60

For installing a main disconnect device (EasyPact or Compact NS/NB MCCB or INS switch) ahead of EasyPact Busbar, use the tin-plated copper connector kits below. Designation Cat. number Main Busbar current rating 250 A
Main disconnect device for EasyPact or Compact NS/NB or INS switch EZB250MCNS

400 A
EZB400MCNS

630 A
EZB630MCNS

Mechanical lugs
E88309-50

For incoming cables without crimped lugs, use the mechanical lug kits below. Each kit contains three aluminium lugs suitable for copper or aluminium cables. Designation Cat. number Main Busbar current rating 250 A
Incoming cable size Lug kit
DB106043 DB106209

400 A
35-300mm2 EZB400MLUG

630 A
25-240 mm2 2 cables per phase EZB630MLUG

16-150 mm2 EZB250MLUG

Connector caps
Connector caps are available to isolate the ends of connectors in positions where branch breakers are not installed. Mounting screws are provided for an insulating barrier (locally provided) to cover the branch connectors when IP2X finger safety is specified. Designation
Connector caps (set of 3) EasyPact branch MCCB EasyPact or Compact NS/NB branch MCCB
DB10639 E88310-54

Cat. number
EZB100CAP EZB250CAP

545E3003_Ver1.0.fm/6

17 dcembre 2004 09:39

EasyPact

Installation guide

Dimensions
EasyPact 100 EasyPact 250 Busbar EZB250 Busbars EZB400/630 EasyPact or Compact NS/NB branch extensions layout

545E4003/2
545E4003/2 545E4003/3 545E4003/8 545E4003/9 545E4003/10

Safety clearances and minimum distances Temperature derating Tripping curves Current-limiting curves Cascading Cascading tables Motor protection Capacitor protection

545E4003/11 545E4003/12 545E4003/13 545E4003/15 545E4003/16 545E4003/17 545E4003/18 545E4003/20

17 dcembre 2004 09:47

545E4003TDM_Ver1.0.fm/1

Installation guide

Dimensions EasyPact 100

Dimensions
1P
DB106057 DB106059 DB106060

2P
DB106058

3P

Mounting on plate
1P
DB106061 DB106062

2P
DB106095
E88494

3P

Mounting on DIN rail

DB106096

545E4003_Ver5.0.fm/2

DB106097

13 avril 2005 17:43

Installation guide

Dimensions EasyPact 250

Dimensions
2P, 3P
DB106133 DB106134

Mounting on plate
2P, 3P
DB106135

13 avril 2005 17:43

545E4003_Ver5.0.fm/3

Installation guide

Dimensions EasyPact 100

Door cut-out (small)


1P, 3P
DB106098 DB106099 DB106119

2P

Door cut-out (large)


1P
DB106118 DB106099 DB106100

2P

3P
DB106101

545E4003_Ver5.0.fm/4

13 avril 2005 17:43

Installation guide

Dimensions EasyPact 250

Door cut-out (small)


2P, 3P
DB106136 DB106137

Door cut-out (large)


2P, 3P
DB106138 DB106139

13 avril 2005 17:43

545E4003_Ver5.0.fm/5

Installation guide

Dimensions EasyPact 100

Terminal shield
3P
DB106112 DB106113

Phase barrier
2P
DB106109 DB106110 DB106111

3P

Direct rotary handle


Dimensions
DB106114 DB106115 DB106116

Door cut-out

Extended rotary handle


Dimensions
DB106117 DB106115 DB106116

Door cut-out

545E4003_Ver5.0.fm/6

13 avril 2005 17:43

Installation guide

Dimensions EasyPact 250

Terminal shield
DB106140 DB106141 DB106142

Phase barrier
DB106143 DB106146 DB106146

Direct rotary handle


DB106144 DB106145

Extended rotary handle


DB106147 DB106145

28 fvrier 2005 16:07

545E4003_Ver4.0.fm/7

Installation guide

Dimensions Busbar EZB250

Layout installation EZB250


Panel layout using the EasyPact Busbar is simple using the guides below. In addition to the mounting locations for the busbar and main disconnect components (if required), make note of the minimum clearances required to the top, bottom and sides of the enclosure.

DB106102

EZB250 - 250 A main busbar rating

Trim cut-out
DB106120

DB106053

A
EZ250 incomer NS/NB incomer 4 ways 6 ways 8 ways 10 ways 12 ways

D
187.4 182.4

E
52 76

F
92.7 90.2

G
24 29

H
109.5 108

I
126 125

268.5 343.5 418.5 493.5 568.5

225 300 375 450 525

147 222 297 372 447

545E4003_Ver5.0.fm/8

13 avril 2005 17:43

Installation guide

Dimensions Busbars EZB400/630

Layout installation EZB400/630


DB106103 DB106052

EZB400 and EZB630 - 400 A and 630 A main busbar ratings

Trim cut-out
DB106132

A
4 ways 6 ways 8 ways 10 ways 12 ways 290 365 440 515 590

B
225 300 375 450 525

C
147 222 297 372 447

Nota : to avoid excess temperature rise on incoming MCCB terminals, panels using 630 A main breaker with these minimum enclosure dimensions require a 7000 mm2 ventilation opening (after subtracting effects of screening) at each of the 4 corners of the enclosure.

13 avril 2005 17:43

545E4003_Ver5.0.fm/9

Installation guide

Dimensions EasyPact or Compact NS/NB branch extensions layout


Layout installation for EasyPact or Compact NS/NB branch extensions

DB106104

EZBNS2 and EZBNS4 Compact NS/NB branch breaker extension.

DB106054

A
EZBNS2 EZBNS4 EZC250 NS/NB250 270 384

B
175 275

C
NA 85.5 90.5 85.5

D
57.5 78.5

E
24 29

F
61 45.5

G
52 76

H
249 232

Trim cut-out
DB106569

45E4003_Ver5.0.fm/10

13 avril 2005 17:43

Installation guide

Safety clearances and minimum distances

EasyPact
When installing a circuit breaker, minimum distances (safety clearances) must be maintained between the device and panels, bars and other protection devices installed nearby. These distances, which depend on the ultimate breaking capacity, are defined by tests carried out in accordance with standard IEC 60947-2. If installation conformity is not checked by type tests, it is also necessary to: b use insulated bars for circuit-breaker connections b block off the busbars using insulating screens. For EasyPact breaker, terminal shields, inter-phase barriers or an insulation isolator are recommended and may be mandatory depending on the utilisation voltage and the type of installation.
Minimal distance between two adjacent circuit breakers
E88230

Minimal distance between the circuit breaker and top, bottom or side panels
DB106055 DB106570

Minimal distance between the circuit breaker and front or rear panels

Dimensions (mm)
EasyPact circuit breaker

Bare or painted sheet metal; insulated bars


C1
D1
D2

Bare busbar under voltage


D1
D2
E

EZC100B/F/N 40 45 45 75 45 40 EZC100H 40 60 45 75 45 40 EZC250F/N 50 60 45 140 45 42.5 EZC250H 50 80 45 140 45 42.5 The mandatory distances when installing EasyPact circuit breakers are calculated from the device case, not taking into account the terminal shields or the inter-phase barriers.

W
E44458

Installation in an enclosure
EasyPact circuit breakers can be installed in a metal enclosure together with other devices (contacts, motor-protection circuit breakers, LEDs, etc.).

Minimum enclosure dimensions


H

Installation in an enclosure

Circuit breakers EZC100B/F/N EZC100H EZC250F/N EZC250H (*) with front door

Height (mm) 200 215 270 290

Depth (mm) (*) 90 90 90 90

Width (mm) 155 155 205 205

13 avril 2005 17:43

545E4003_Ver5.0.fm/11

Installation guide

Temperature derating

Ambient temperature
EasyPact devices are equipped with fixed thermal-magnetic trip units. b EasyPact has been particularly designed to hold 100% In at 50 C without tripping in normal condition b EasyPact circuit breakers may be used between - 25 C and + 70 C b EasyPact circuit breakers should be put into service under normal ambient operating temperature conditions. Exceptionally, the circuit breaker may be put into service when the ambient temperature is between - 35 C and - 25 C b the permissible storage-temperature range for EasyPact circuit breakers in the original packing is - 35 C to + 85 C. To determine tripping times using time/current curves, use Ir values corresponding to the thermal setting on the device, corrected as indicated in the tables below. Breaker Amperage EZC100
15 20 25 30 40 50 60 75 80 100

25 C 40 C 45 C 50 C 55 C 60 C 65 C 70 C
17.0 21.8 26.9 34.5 42.8 54.2 64.4 78.6 84.4 108.8 116.3 148.4 174.0 186.0 206.7 235.8 269.0 298.9 15.7 20.4 25.7 31.4 40.9 52.1 61.8 76.8 82.2 102.6 106.8 134.9 160.0 170.9 188.3 215.0 243.5 270.6 15.3 20.2 25.3 30.7 40.4 51.0 60.9 75.9 81.1 101.3 103.5 130.0 155.1 165.5 181.8 207.6 234.5 260.5 15.0 20.0 25.0 30.0 40.0 50.0 60.0 75.0 80.0 100.0 100.0 125.0 150.0 160.0 175.0 200.0 225.0 250.0 14.7 19.7 24.7 29.4 39.5 49.3 59.0 73.5 78.6 99.2 96.4 119.8 144.7 154.3 167.9 192.0 215.1 239.0 14.6 19.2 24.5 29.1 38.0 48.1 57.5 70.4 77.3 94.2 92.7 114.3 139.3 148.3 160.6 183.8 204.8 227.5 14.2 18.9 24.3 28.5 37.6 47.3 56.6 69.8 76.7 93.5 88.8 108.5 133.6 142.1 152.9 175.1 193.9 215.4 13.8 18.5 24.0 28.0 37.1 46.6 55.7 69.1 76.1 92.7 84.7 102.5 127.6 135.6 144.7 165.9 182.3 202.6

EZC250
100 125 150 160 175 200 225 250

45E4003_Ver5.0.fm/12

13 avril 2005 17:43

Installation guide

Tripping curves

EasyPact 100 TM magnetic trip units


15 A
DB106121 DB106122

20 A
DB106123

25 A

30 A
DB106124 DB106125

40 A
DB106126

50 A

60 A
DB106127 DB106128

75 A
DB106129

80 A

28 fvrier 2005 16:07

545E4003_Ver4.0.fm/13

Installation guide

Tripping curves

EasyPact 100 TM magnetic trip units (cont.)


100 A
DB106130

EasyPact 250 TM magnetic trip units


100-125 A
DB106148 DB106149

150-160-175-200 A
DB106150

225-250 A

45E4003_Ver5.0.fm/14

13 avril 2005 17:43

Installation guide

Current-limiting curves

The limiting capacity of a circuit breaker is its aptitude to limit short-circuit currents.
DB106049

The exceptional limiting capacity of the EasyPact range greatly reduces the forces created by fault currents in devices. The result is a major increase in breaking performance. The Ics value, defined by IEC standard 60947-2, is guaranteed by tests comprising the following operations: b break three times consecutively a fault current equal from 25% to 100% of Icu b check that the device continues to function normally: v it conducts the rated current without abnormal temperature rises v protection functions perform within the limits specified by the standard v suitability for isolation is not impaired.

Longer service life of electrical installations


Current-limiting circuit breakers greatly reduce the negative effects of short-circuits on installations. Thermal effects Less temperature rise in conductors, therefore longer service life for cables. Mechanical effects Reduced electrodynamic forces, therefore less risk of electrical contacts or busbars being deformed or broken. Electromagnetic effects Less disturbances for measuring devices located near electrical circuits.

Economy by means of cascading


Cascading is a technique directly derived from current limiting. Circuit breakers with breaking capacities less than the prospective short-circuit current may be installed downstream of a limiting circuit breaker. The breaking capacity is reinforced by the limiting capacity of the upstream device. It follows that substantial savings can be made on downstream equipment and enclosures.

Current-limiting curves
The current-limiting capacity of a circuit breaker is expressed by two curves which are a function of the prospective short-circuit current (the current which would flow if no protection devices were installed): b the actual peak current (limited current), b thermal stress (A2s), i.e. the energy dissipated by the short-circuit in a conductor with a resistance of 1 .

Current limiting curves 380/415 V AC


DB106151 DB106152

Thermal-stress curves 380/415 V AC

13 avril 2005 17:43

545E4003_Ver5.0.fm/15

Installation guide

Cascading

What is cascading?
Cascading is the use of the current limiting capacity of circuit breakers at a given point to permit installation of lower-rated and therefore lower-cost circuit breakers downstream. The upstream compact circuit breakers acts as a barrier against short-circuit currents. In this way, downstream circuit breakers with lower breaking capacities than the prospective short-circuit (at their point of installation) operate under their normal breaking conditions. Since the current is limited throughout the circuit controlled by the limiting circuit breaker, cascading applies to all switchgear downstream. It is not restricted to two consecutive devices.

General use of cascading


With cascading, the devices can be installed in different switchboards. Thus, in general, cascading refers to any combination of circuit breakers where a circuit breaker with a breaking capacity less than the prospective Isc at its point of installation can be used. Of course, the breaking capacity of the upstream circuit breaker must be greater than or equal to the prospective short-circuit current at its point of installation. The combination of two circuit breakers in cascading configuration is covered by the following standards: b IEC 60947-2 (construction) b NF C 15-100, 434.3.1 (installation).

Coordination between circuit breakers


The use of a protective device possessing a breaking capacity less than the prospective short-circuit current at its installation point is permitted as long as another device is installed upstream with at least the necessary breaking capacity. In this case, the characteristics of the two devices must be coordinated in such a way that the energy let through by the upstream device is not more than that which can be withstood by the downstream device and the cables protected by these devices without damage. Cascading can only be checked by laboratory tests and the possible combinations can be specified only by the circuit breaker manufacturer.

220/240 V network downstream from a 380/415 V network


For 1P + N or 2P circuit breakers connected between the phase and neutral on a 380/415 V network, with a TT or TNS neutral system, consult the 220/240 V cascading table to determine cascading possibilities between upstream and downstream circuit breakers.
DB106051

Economy by means of cascading


Thanks to cascading, circuit breakers with breaking capacities less than the prospective short-circuit current may be installed downstream from a current limiting circuit breaker. It follows that substantial savings can be made on downstream switchgear and enclosures.

Cascading tables
Merlin Gerin cascading tables are: b drawn up on the basis of calculations (comparison between the energy limited by the upstream device and the maximum permissible thermal stress for the downstream device) b verified experimentally in accordance with IEC standard 60947-2. For distribution systems with 220/240 V, 380/415 V and 440 V between phases, the tables of the following pages indicate cascading possibilities between upstream Compact/EasyPact and downstream Multi 9 and EasyPact circuit breakers.

45E4003_Ver5.0.fm/16

13 avril 2005 17:43

Installation guide

Cascading tables

Network 220/240 V
Upstream EZC100F EZC100N EZC100H Breaking capacity kA rms 25 25 100 Downstream Enhanced breaking capacity
NC45 NC45N NC45H C60a C60N C60H QO-E 6 10 15 10 20 30 10 10 15 25 25 25 25 10 15 25 25 25 25 15 25 50 50 65 65 50
DB106106

Upstream EZC250F EZC250N EZC250H Breaking capacity kA rms 25 50 85 Downstream Enhanced breaking capacity
EZC100B EZC100F EZC100N EZC100H 10 25 25 100 30 30 15 30 36

NS250H 100
20 50 50

Upstream NB400/630 NS400/630N NS400/630H Breaking capacity kA rms 85 85 100 Downstream Enhanced breaking capacity
EZC100B EZC100F EZC100N EZC100H EZC250F EZC250N EZC250H 10 25 25 100 25 50 85 20 50 50 50 20 50 50 50 20 50 50 50

Network 380/415 V
Upstream EZC100F EZC100N EZC100H Breaking capacity kA rms 10 15 30 Downstream Enhanced breaking capacity
NC45 NC45N NC45H C60a C60N C60H QO-E GV2M 5 8 10 6 10 15 5 15
DB106160

6 10 10

8 10 15 15 15 15

10

15 15 15 15 15 15 15

Upstream EZC250F EZC250N EZC250H Breaking capacity kA rms 18 25 36 Downstream Enhanced breaking capacity
EZC100B EZC100F EZC100N EZC100H 7.5 10 15 30 15 20 15 20 36

NS250H 70
15 30 50 70

Upstream NB400/630 NS400/630N NS400/630H Breaking capacity kA rms 30 50 70 Downstream Enhanced breaking capacity
EZC100B EZC100F EZC100N EZC100H EZC250F EZC250N EZC250H 7.5 10 15 30 18 25 36 20 20 30 20 45 20 36 45 30 50 20 40 50

Network 440 V
Upstream EZC250F EZC250N EZC250H Breaking capacity kA rms 15 20 25 Downstream Enhanced breaking capacity
EZC100B EZC100F EZC100N EZC100H 5 7.5 10 20 15 15

Upstream NB400/630 NS400/630N NS400/630H Breaking capacity kA rms 30 42 65 Downstream Enhanced breaking capacity
EZC100B EZC100F EZC100N EZC100H EZC250F EZC250N EZC250H 5 7.5 10 20 15 20 25 15 30 25 30 15 30 25 30 25 30 30 30

13 avril 2005 17:43

545E4003_Ver5.0.fm/17

Installation guide

Motor protection

A circuit supplying a motor may include one, two, three or four switchgear or controlgear devices fulfilling one or more functions. When a number of devices are used, they must be coordinated to ensure optimum operation of the motor. Protection of a motor circuit involves a number of parameters that depend on: b the application (type of machine driven, operating safety, starting frequency, etc.) b the level of service continuity imposed by the load or the application b the applicable standards to ensure protection of life and property. The necessary electrical functions are of very different natures: b short circuit protection b overload protection dedicated for motor b control (generally with high endurance levels) b isolation.

DB106108

DB106107

Protection functions
Disconnection functions: Isolate a motor circuit prior to maintenance operations. Short-circuit protection: Protect the starter and the cables against major overcurrents (> 10 In). Control: Start and stop the motor and, if applicable: b gradual acceleration b speed control. Overload protection: Protect the starter and the cables against minor overcurrents (< 10 In). Additional specific protection: b limitative fault protection (while the motor is running) b preventive fault protection (monitoring of motor insulation with motor off). Overloads (I < 10 In) An overload may be caused by: b an electrical problem, for instance on the mains (loss of a phase, voltage outside tolerances, etc.) b a mechanical problem, for instance excessive torque due to abnormally high demands by the process or motor damage (bearing vibrations, etc.). A further consequence of these two origins is excessively long starting. Impedance short-circuit (10 < I < 50 In) Deterioration of motor-winding insulation is the primary cause. Short-circuit (I > 50 In) This type of fault is relatively rare. A possible cause may be a connection error during maintenance. Overload protection Thermal relays provide protection against this type of fault. They may be: b integrated in the short-circuit protective device b separate. Short-circuit protection This type of protection is provided by a circuit breaker. Protection against insulation faults This type of protection may be provided by: b a residual current device (RCD) b an insulation monitoring device (IMD).

45E4003_Ver5.0.fm/18

DB106050

13 avril 2005 17:43

Installation guide

Motor protection

Motor protection - circuit breaker selection


P (kW)

220/230 V 240 V Circuit I (A) I (A) breaker


rating (In) 2 2.8 3.5 5 6.5 9 12 15 21 28 36 39 52 63 75 100 125 150 180 250 300 360 1.8 2.6 3.2 4.5 6 8 11 14 19 25 33 36 48 59 70 95 115 140 170 235 270 330 20 20 20 20 20 20 20 20 30 40 50 50 75/80 75/80 100 125 150 170 225 -

380/400 V 415 V Circuit


I (A) 1.2 1.6 2 2.8 3.7 5.3 7 9 12 16 19 21 23 30 37 43 59 72 85 105 138 170 205 I (A) breaker rating (In) 20 20 20 20 20 20 20 20 20 20 25 30 30 40 50 50 60 60 75/80 80 100 100 125 150 175 225

440 V Circuit I (A) breaker rating (In) 1 1.4 1.7 2.4 3.1 4.5 5.8 8 10.5 13.7 16.9 19 20 26.5 33 39 51 64 76 90 125 146 178 20 20 20 20 20 20 20 20 20 20 25 30 30 40 50 50 75/80 75/80 100 125 150 175 225

0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 9 10 11 15 18.5 22 22 25 30 37 37 45 55 75 90 110

1.1 1.5 1.8 2.6 3.4 4.8 6.5 8.2 11 14 17 19 21 28 34 40 47 55 66 80 100 135 165 200

13 avril 2005 17:43

545E4003_Ver5.0.fm/ 19

Installation guide

Capacitor protection

Thanks to its small size and short-circuit capacity, EasyPact circuit breaker is the most compact solution for any capacitor protection (eg: for each step of capacitor bank from 7.5 kVAR to 50 kVAR).
EZ101PR-25

EasyPact circuit breaker is suitable for capacitor protection following the rules below:
b Inc = Nominal current from the capacitor
Qc Inc = ----------U 3 Inc = Nominal Current Capacitor (A) Qc = Reactive power (kVAR) U = Nominal Voltage (V)

b Inb = Nominal current for the circuit breaker protection (EZC) v Inb = 1.36 x Inc for standard equipment v Inb = 1.5 x Inc for overrated type equipment v Inb = 1.19 x Inc for detuned type equipment: 3.8 tuning v Inb = 1.31 x Inc for detuned type equipment: 4.3 tuning v Inb = 1.12 x Inc for detuned type equipment: 2.7 tuning v the short-circuit (magnetic) protection-setting thresholds must enable passage of the energising transients: 10 x Inc for standard, overrated and detuned type equipment. b short-circuit level is given by the installation.
EZC100 EZC250

Example:
EZ151D

Table at 400 V AC - 3 phases 50 Hz for standard equipment.


Reactive power (kVAR) 7.5 10 15 20 30 40 50 60 75 100 Inc (A) 11 14 22 29 43 58 72 87 108 144 Inb (A) 15 20 30 40 60 80 100 118 147 196 Breaking capacity to Circuit Breaker 15 kA 30 kA EZC100N3015 EZC100H3015 EZC100N3020 EZC100H3020 EZC100N3030 EZC100H3030 EZC100N3040 EZC100H3040 EZC100N3060 EZC100H3060 EZC100N3080 EZC100H3080 EZC100N3100 EZC100H3100 EZC250F3125 EZC250H3125 EZC250F3150 EZC250H3150 EZC250F3200 EZC250H3200

545E4003_Ver5.0.fm/20

EZ152P-50

13 avril 2005 17:43

Catalogue numbers

EZC100N/H 1P/2P Circuit breaker

EasyPact EZC100N 1P 18 kA 220/240 V


With thermal magnetic trip unit
Rating 15 A 20 A 25 A 30 A 40 A 50 A 60 A 75 A 80 A 100 A 1P 1d EZC100N1015 EZC100N1020 EZC100N1025 EZC100N1030 EZC100N1040 EZC100N1050 EZC100N1060 EZC100N1075 EZC100N1080 EZC100N1100
DB100818

EasyPact EZC100H 1P 25 kA - 2P 50 kA 220/240 V


With thermal magnetic trip unit
Rating 15 A 20 A 25 A 30 A 40 A 50 A 60 A 75 A 80 A 100 A 1P 1d EZC100H1015 EZC100H1020 EZC100H1025 EZC100H1030 EZC100H1040 EZC100H1050 EZC100H1060 EZC100H1075 EZC100H1080 EZC100H1100 2P 2d EZC100H2015 EZC100H2020 EZC100H2025 EZC100H2030 EZC100H2040 EZC100H2050 EZC100H2060 EZC100H2075 EZC100H2080 EZC100H2100
DB100818

1P

545E5100_Ver1.2.fm/2

DB100819

2P

Catalogue numbers

EZC100N/H/B/F 3P Circuit breaker

EasyPact EZC100B 3P 7.5 kA 400/415 V


With thermal magnetic trip unit
Rating 15 A 20 A 25 A 30 A 40 A 50 A 60 A 3P 3d EZC100B3015 EZC100B3020 EZC100B3025 EZC100B3030 EZC100B3040 EZC100B3050 EZC100B3060
DB100820

EasyPact EZC100F 3P 10 kA 400/415 V


With thermal magnetic trip unit
Rating 15 A 20 A 25 A 30 A 40 A 50 A 60 A 75 A 80 A 100 A 3P 3d EZC100F3015 EZC100F3020 EZC100F3025 EZC100F3030 EZC100F3040 EZC100F3050 EZC100F3060 EZC100F3075 EZC100F3080 EZC100F3100
DB100820

EasyPact EZC100N 3P 15 kA 400/415 V


With thermal magnetic trip unit
Rating 15 A 20 A 25 A 30 A 40 A 50 A 60 A 75 A 80 A 100 A 3P 3d EZC100N3015 EZC100N3020 EZC100N3025 EZC100N3030 EZC100N3040 EZC100N3050 EZC100N3060 EZC100N3075 EZC100N3080 EZC100N3100
DB100820

EasyPact EZC100H 3P 30 kA 400/415 V


With thermal magnetic trip unit
Rating 15 A 20 A 25 A 30 A 40 A 50 A 60 A 75 A 80 A 100 A 3P 3d EZC100H3015 EZC100H3020 EZC100H3025 EZC100H3030 EZC100H3040 EZC100H3050 EZC100H3060 EZC100H3075 EZC100H3080 EZC100H3100
DB100820

545E5100_Ver1.2.fm/3

Catalogue numbers

EZC100N/H/B/F Accessories

Connection accessories
Cable lugs
y 50 A
DB100821

Cables from 2.5 to 16 mm2

Set of 2 Set of 3

EZALUG0502 EZALUG0503

> 50 A
DB100822

Cables from 10 to 50 mm2

Set of 2 Set of 3

EZALUG1002 EZALUG1003

Spreader
EZASPDR3P
DB100823

(*)

Terminal shield
Terminal shield for 3-pole breaker
DB100824

Set of 2

EZATSHD3P

Sealing screws
Set of 2
DB100825

EZASSCR

Phase barriers
Set of 2
DB100826

EZAFASB2

Electrical auxiliaries
Indication contacts
Auxiliary switch (AX)
DB100827

EZAUX10

Alarm switch (AL)


DB100828

EZAUX01

Aux. switch/Alarm switch (AX/AL)


DB100829

EZAUX11

(*) Consult us.

545E5100_Ver1.2.fm/4

Catalogue numbers

EZC100N/H/B/F Accessories

Electrical auxiliaries (cont.)


Voltage releases
AC
DB100830

Shunt trip (SHT)

DC
DB100831

Voltage 100-130 V 110-130 V 200-240 V 200-277 V 277 V 380-415 V 380-480 V 440-480 V Voltage 24 V 48 V 125 V

MX/SHT EZASHT100AC

MN/UVR EZAUVR110AC EZAUVR200AC

EZASHT200AC EZAUVR277AC EZAUVR380AC EZASHT380AC MX/SHT EZASHT024DC EZASHT048DC EZAUVR440AC MN/UVR EZAUVR024DC EZAUVR048DC EZAUVR125DC

Under voltage release (UVR)

Rotary handles
Direct rotary handle
Standard handle
DB100832

EZAROTDS

Extended rotary handle


Extended handle
DB100833

EZAROTE

Locks
Padlocking system
DB100834

EZALOCK

Installation accessory
Din rail adaptor
For 2 x 1 pole or 1 x 2 pole or 1 x 3 pole breaker
DB100835

EZADINR

545E5100_Ver1.2.fm/5

Catalogue numbers

EasyPact Busbar
"Type-tested solution IEC 60439"

Main Busbar
# Branch Ways (3-pole EasyPact MCCBs)
4 ways 6 ways 8 ways 10 ways 12 ways
DB100836

250 A
EZB250W04 EZB250W06 EZB250W08 EZB250W10 EZB250W12

400 A
EZB400W04 EZB400W06 EZB400W08 EZB400W10 EZB400W12

630 A
EZB630W04 EZB630W06 EZB630W08 EZB630W10 EZB630W12

4 ways (3-pole)
DB100837

8 ways (3-pole)

Compact NS/NB branch extension


DB100838

2 ways 4 ways

EZBNS2 EZBNS4

4 ways (3-pole)

Main incoming connections


Main connectors
DB100839

250 A
To connect the main incomer EZB250MCNS to EasyPact busbar (Compact NS/NB or INS switch)

400 A
EZB400MCNS

630 A
EZB630MCNS

Mechanical lugs
Incoming cable size
DB100840

250 A
16-150 mm2

400 A
35-300 mm2 EZB400MLUG

630 A
25-240 mm2 2 cables per phase EZB630MLUG

Lug kit for bare incoming cables EZB250MLUG

Connector caps
EasyPact branch MCCB Compact NS/NB branch MCCB To isolate connections when branch breaker not installed
DB100841

Set of 3 EZB100CAP Set of 3 EZB250CAP

545E5100_Ver1.2.fm/6

Schneider Electric Industries SAS


89, boulevard franklin-Roosevelt 92506 Rueil-Malmaison Cedex FRANCE Tl. : 0 810 012 999 http://www.schneider-electric.com As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication.

Publication: Schneider Electric SAS Printing: 545E-ABTED0000000EN 10-2004

ART00000 2004 - Schneider Electric - All rights reserved