You are on page 1of 4

Modeion

MOTOR DRIVES

BH630N, BH630S

Technical information

3P 4P Description
It is used for remote control of the circuit breaker (switch off/on). Simple mounting on the circuit breaker after the circuit breaker cover of cavities is removed. Usage in industrial applications e.g. switching of stand by units etc. or wherever the automatic operation of electric devices is needed. In order to speed up the circuit breakers switch off (e.g. safety STOP button) the undervoltage release or shunt trip can be used. On the motor drive front panel there is a change-over switch to select the drive modes AUTO/MANUAL: - AUTO mode remote control. The circuit breaker is controlled by buttons for remote switch off/on, furthermore in this position mechanical control can be used on the front panel of the motor drive - MANUAL mode manual control. Control voltage is not needed. The circuit breaker can be switched on using the green switch on button and switched off using the red switch off button on the front part of the drive cover. Electric switch on is blocked. Electric switch off is functional. The accumulation of energy can be done by means of hinged lever. Possibility to indicate remotely the state of the AUTO/MANUAL switch. Switch S (external switch has to be bought separately) enables the choice of automatic accumulation of energy (circuit breaker loading). - automatic accumulation of energy is switched on (S switch closed): after tripping of the circuit breaker by the overcurrent release, by auxiliary release, or by TEST push button or by the switch off button on the motor drive, motor drive immediately accumulates energy (circuit breaker loading), motor drive is then ready to switch on the circuit breaker. - automatic accumulation of energy is switched off (S switch open): after tripping of the circuit breaker by the overcurrent release, by auxiliary release, or by TEST push button or by the switch off button on the motor drive, both motor drive and circuit breaker stay in position switched off by releases. In this position motor drive waits for the impulse from switch S. When the impulse is brought in the motor drive accumulates energy (turn on the circuit breaker) and after this loading the motor drive is ready to switch on the circuit breaker. It is not possible to switch on the circuit breaker when motor drive is not loaded. Front panel state indicating device of the stored energy signals the state of motor drive storage devices. The state can be signalled from a distance. The drive may be furnished with an electromechanical counter of cycles: - internal design on the motor drive cover - external design OD-BHD-PP01 for mounting on the switchboards door or inside the switchboard by means of metal holder, that is part of the delivery Motor drive can be sealed by means of bolt sealing insert (OD-BH-VP01). Drive can be locked in off position by up to three padlocks (shank diameter max. 4.3 mm). Switch on button can be covered and sealed (OD-BHDKT01). Drive is connected by multi-pole connector with cavities ( in order to connect cables special tongs have to be used). Drive can be furnished with cable (OD-BHD-KA02), that has on one side connector to the motor drive and on the other side free terminals for connection to etc. switchboards terminal block.

DIMENSIONS see page F29

Specifications
Type Operating voltage Cover of switch on button OD-BHD-KT01 Rated frequency Control impulse length for storage Control impulse length for switching on for switching off Time to switching on Time to switching off Frequency of cycles ON/OFF Frequency of cycles - instant successive ON/OFF Mechanical endurance Input power Protection Rated operating current of the change-over switch AUTO / MANUAL Type Number of conductors Conductor cross-section Conductor lengths 1) - for sequence of control impulses see page F69 Ue fn MP-BH-X, MP-BH-X-P 24, 48, 110, 230 V a.c. 24, 48, 110, 220 V d.c. 50/60 Hz 400 ms 1) 20 700 ms 1) 400 ms 1) < 60 ms 900 ms 3 cycles/min 10 cycles 20 000 cycles 100 VA 100 W LPN-4C-1; LPN-2C-1 LPN-DC-4C-1; LPN-DC-2C-1 5 A/250 V a.c. 0.5 A/250 V d.c. OD-BHD-KA02
12 0.35 mm2 0.6 m

Connecting cable OD-BHD-KA02

AC DC 24, 48, 110 V a.c.; 230 V a.c. 24, 48, 110 V d.c.; 220 V d.c. Ie /Ue

F66

BH630N, BH630S

Technical information

Modeion
3P 4P

MOTOR DRIVES
Specifications
Circuit breaker switching on by motor drive - electrically by ON push button
Main contacts
2 4 6 1 3 5

Circuit breaker switching off by motor drive - electrically by OFF push button
Main contacts

1 0

50 Auxiliary switch

2 4 6

1 3 5

1 0 Auxiliary switch

900

5.4 4.4 3.4 3.4

5.3 4.3 3.3 3.3

1 0

50 Auxiliary switch

5.4 4.4 3.4 3.4

5.3 4.3 3.3 3.3

1 0 Auxiliary switch

900

5.2 4.2 14 3.2

5.1 4.1 13 3.1

1 0

50 Relative switch

5.2 4.2 14 3.2

5.1 4.1 13 3.1

1 0 Relative switch 1

900

1
2.4 2.3

0 Relative switch 1

2.4

2.3

0 Relative switch 1

2.2

2.1

0 Early switch 1 20 Early switch 1 0 20

2.2

2.1

0 Early switch 1 900 Early switch 1 0 900

10.Y2 10.Y4

10.Y 1 10.Y 3

10.Y2 10.Y4

10.Y 1 10.Y 3

10.Y2 10.Y4

10.Y 1 10.Y 3

10.Y2 10.Y4

10.Y 1 10.Y 3

10 3 50 00

10 2 50 0

10 3 50 00

10 2 50 0

10 50

10

10 50

t [ms]

t [ms ]

Diagram
Circuit breaker switching on and off by motor drive - electrically by ON and OFF push button
Ovldac obvod motorovho pohonu Control circuit of motor drive

States and positions of circuit breaker/switch-disconnector lever


States of circuit breaker/switch-disconnector Switched on Lever position of circuit breaker/switch-disconnector

Q3 L+

ON S OF F B

Switched off by releases, TEST or by switch off button on the motor drive Switched off manually or by motor drive electrically (loaded state)

Motorov pohon Motor drive

Diagram description
7 3 4 1 5

X3

12

10 9

Symbol MP M P X3 X4

Description motor drive MP-BH-X... motor storage device connector for connection of control circuits connector for external counter of cycles switch to indicate AUTO (NO-C) / MANUAL (NC-C) modes switch to indicate full storage (ready to switch on: NO-C) external counter of cycles OD-BHD-PP01 recommended wiring of the control circuits (not included in motor drive order) switch on button switch off button switch for energy storage (switched on = automatic storage, may be continuously switched on) motor drive circuit breaker - see page F66

NC

NO NC

NO

S6
C
C

S5

S5 S6 YC

MP

B
11 X3

2 X4

ON OFF S
Po. cykl Cycle counter

PE

N-

Q3

10

1 5

1 5

F67

Modeion
MOTOR DRIVES
Specifications

BH630N, BH630S

Technical information

3P 4P

Switching off of the circuit breaker with motor drive by overcurrent release (switch S in switched on state-automatic storage)
Main contacts
2 4 6 1 3 5

Switching off of the circuit breaker with motor drive by shunt trip or undervoltage release (switch S in switched on state-automatic storage)
Main contacts
2 4 6 1 3 5

1 0

20 Auxiliary switch

1 0

20 Auxiliary switch

5.4 4.4 3.4 3.4

5.3 4.3 3.3 3.3

1 0

20 Auxiliary switch

5.4 4.4 3.4 3.4

5.3 4.3 3.3 3.3

1 0

30 Auxiliary switch

5.2 4.2 14 3.2

5.1 4.1 13 3.1

1 0

30 Relative switch

5.2 4.2 14 3.2

5.1 4.1 13 3.1

1 0

30 Relative switch

1
2.4 2.3

20 Relative switch

650
2.4 2.3

1 0

30 Relative switch

650

1
2.2 2.1

30 Signal switch

650
2.2 2.1

1 0

30

650

0 20 Signal switch 1 30 650 650

1
1.2 1.1

1 0

1 0

1.4

1.3

10 3 50 00

10 3 50 00

10 2 50 0

10 2 50 0

10 50

10 50

t [ms ]

10

t [ms ]

Diagram
Circuit breaker switching on by motor drive (electrically by ON push button) and tripping by shunt trip
Ovldac obvod Control circuit of motor drive

Circuit breaker switching on by motor drive (electrically by ON push button) and tripping by undervoltage release
Ovldac obvod Control circuit of motor drive

Q3 L+ L+

Q3

ON S OF F B B OF F

ON S

Motorov pohon Motor drive

Motorov pohon Motor drive

A1

A1

B1

X3

12

10 9

X3

12

10 9

SV -BHD-X...

B1

SP-BHD-X...

S6
C
C

S5

S6
C
C

S5

or

SP-BHD-X...

NC

NO NC

NO

NC

NO NC

NO

or

MP

MP

A2

B2

A2

X3

X4

X3

X4

cavity No.10 dutina .10

cavity No.10 dutina .10

PE

N-

N-

PE

N-

N-

Po. cykl Cycle counter

Po. cykl Cycle counter

F68

B2

11

11

SV -BHD-X...

10

1 5

1 5

BH630N, BH630S

Technical information

Modeion
3P 4P

MOTOR DRIVE
Specifications
Recommended control impulses Circuit breaker switching on and off by motor drive - S switch permanently closed (automatic storage) or open
800 HK 1 0 800 PS 1 0 > 1400 1 0 400 IMP OFF >100 20 700 IMP ON t [ms ]
1 0 R OFF

Circuit breaker switching off by overcurrent or auxiliary release and switching on by motor drive - S switch permanently closed (automatic storage)
50 HK 1 0 520 RS 1 0 > 1400 20 700 IMP ON t [ms ] > 880

50

> 600

Circuit breaker switching off by overcurrent or auxiliary release and switching on by motor drive - S switch closed only for storing up
50 HK 1 0 X+520 RS 1 0 X 1 0 R OFF > 1400 400 IMP S >100 20 700 IMP ON t [ms ] > 880

Description of graphs
Symbol HK PS RS R OFF IMP S IMP ON IMP OFF X Description main contacts auxiliary switch relative switch circuit breaker closing instant by release impulse to store up motor drive energy (generated by S switch) make impulse for the motor drive break impulse for the motor drive random segment of time

States and positions of circuit breaker/switch-disconnector lever


States of circuit breaker/switch-disconnector Switched on Switched off by releases, TEST or by switch off button on the motor drive Switched off manually or by motor drive electrically (loaded state) Lever position of circuit breaker/ switch-disconnector

F69