Self-learning Room Temperature Controller


5 operating modes, menu selection via roller selector

REV12

Mains-independent room temperature controller Straightforward, self-explanatory menu selection via roller selector Self-learning 2-position controller providing PID mode (patented) Choice of operating modes: automatic with maximum 2 heating periods, continuously comfort mode, continuously economy mode, frost protection with one 24-hour operating mode and one heating period In automatic mode, one temperature setpoint can be adjusted for each heating period Use For the control of the room temperature in: Apartments, single-family or holiday houses Offices, individual rooms, consulting rooms or commercially used spaces For the control of the following pieces of equipment: Solenoid valves of instantaneous water heaters Solenoid valves of atmospheric gas burners Forced draft gas or oil burners Circulating pumps in heating systems, zone valves Electric direct heating systems or fans of electric storage heaters Thermic actuators

CE1N2261en 23.04.2002

Siemens Building Technologies HVAC Products

Functions Ordering Room temperature controller When ordering, please give the type reference. The controller is supplied complete with batteries. Technical design Display and operating elements REV12 PID mode with self-learning or selectable switching cycle 2-position control Automatic mode with one or 2 heating periods One temperature setpoint for each heating period 24-hour operating mode with one heating period Override button Sensor calibration and reset function Frost protection function Limitation of the minimum setpoint

Operating elements Selection of operating mode Warmer button Colder button Override button Roller selector for the menu, submenus and settings Confirm by pressing

2/10 Siemens Building Technologies HVAC Products Room temperature controller REV12 CE1N2261en 23.04.2002

Display Time of day


C

Room temperature Change batteries (display appears about 3 months before batteries are exhausted)

Selection of operating mode (only one operating mode is active)

Automatic mode

Comfort mode Economy mode Frost protection 24-hour mode with one heating period (heating period is automatically generated from the current 24-hour program) Temporary change of the current setpoint temperature (change only active until the next switching point is reached)

C
Override button

When pressing the + or button once, the adjusted setpoint temperature will be displayed. It can be readjusted in increments of 0.2 C (max. +/- 4 C).

In operating modes and , this button can be used to switch from comfort to economy temperature, or vice versa. The selection is maintained until the next switching point is reached or until the operating mode is changed.

Menu-driven user settings: 4 main menus available


Time of day Main menu Settings

Current time of day

Temperature

Main menu

Submenu

Factory settings Setpoint comfort mode Setpoint economy mode Setpoint frost protection 19 C 16 C 5 C

Time switch

Main menu

Submenu

Settings 1 heating period per day 2 heating periods per day

3/10 Siemens Building Technologies HVAC Products Room temperature controller REV12 CE1N2261en 23.04.2002

Selection of heating period start time Selection of heating period end time
T
C

Selection of heating period setpoint temperature

Menu-driven heating engineer settings

Menu items

Settings Sensor calibration Setpoint limitation 2-position control PID mode, self-learning PID mode with a switching cycle of 6 or 12 minutes

CAL

Temperature setpoints

In the automatic operating modes, temperature setpoints can be individually adjusted for every comfort period and for the continuous operating modes. The temperature setpoint of economy mode is the same in automatic and continuous operation. In frost protection mode, the room temperature is constantly monitored. If it falls below the adjusted setpoint, heating is switched on to maintain the adjusted frost protection setpoint temperature .

Protective function

24-hour operating mode

The controller generates the 24-hour operating mode from the current 24-hour program. It automatically selects the switch-on time of the first heating period and the switch-off time of the last heating period to generate and display a complete heating period. The comfort temperature used by the controller is the currently stored standard setpoint of the continuous operating mode . The self-generated 24-hour operating mode is maintained until another operating mode is selected.
C 22 20

Example

T
18

T
08 10 18 22 h

Automatically generated 24-hour operating mode

Current 24-hour switching program

4/10 Siemens Building Technologies HVAC Products Room temperature controller REV12 CE1N2261en 23.04.2002

2261Z01

Switching program

The switching program is used as the 24-hour program. It is also possible to select one of the continuous operating modes with which the switching program is not used. When a heating period is programmed, 2 different switching patterns are available. It is possible to select one or 2 heating periods. For each heating period, the start time, end time and comfort temperature setpoint are to be entered. In between heating periods, it is always the same economy temperature setpoint that is used. This economy temperature setpoint can be adjusted on the temperature menu.

22 20 Heating period 1 18 Heating period 2

16 08 10 18 22 h

Factory settings
Operating mode

Switching times

Temperatures in C
1st heating period 2nd heating period

Daily

06:00 00:00 00:00 00:00

09:00 24:00 24:00 24:00

17:00

22:00

19 19

20

16 5

Factory settings heating engineer Heating engineer level Accessing

Setpoint limitation

and self-learning PID mode

To access the heating engineer level, keep the warmer and colder buttons depressed and simultaneously roll the roller selector away from the display and then toward the display. If the displayed temperature does not correspond to the effective room temperature, the temperature sensor can be recalibrated (recalibration to be made on the heating engineer level). The displayed temperature can be matched to the effective room temperature in increments of 0.2 C (max. 2 C). Minimum setpoint limitation of 16 C prevents undesired heat transfer to neighboring apartments in buildings with several heating zones.

Sensor calibration

CAL

Limitation of setpoint

2261Z04

Example with 2 heating periods per day

5/10 Siemens Building Technologies HVAC Products Room temperature controller REV12 CE1N2261en 23.04.2002

Control

The REV12 is a 2-position controller providing PID mode. The room temperature is controlled through the cyclic switching of an actuating device. The controller generates the positioning signals depending on the deviation of the setpoint from the actual value acquired by the built-in temperature sensor. The rate of response to the deviation depends on the selected control algorithm.

Self-learning mode

The controller is supplied with an active self-learning operating mode, enabling it to automatically adapt to the controlled system (type of building construction, type of radiators, size of the rooms, etc.). After a certain learning period, the controller optimizes its parameters and then operates with the learned parameters. In exceptional cases, in which the self-learning mode may not be ideal, it is possible to select PID 12, PID 6 or 2-Pt mode: PID 12 mode Switching cycle of 12 minutes for normal or slow controlled systems (massive building structures, large spaces, cast-iron radiators, oil burners). Switching cycle of 6 minutes for fast controlled systems (light building structures, small spaces, plate radiators or convectors, gas burners). Pure 2-position control with a switching differential of 0.5 C (0.25 C) for very difficult controlled systems with considerable outdoor temperature variations.

Exceptions

PID 6 mode 2-Pt mode

Reset functions

User-defined data: Press the button behind the pin opening for at least one second: this resets the userspecific settings to their default values (the heating engineer settings will not be changed). The clock starts at 12:00. During the reset time, all sections of the display light up, enabling them to be checked. All user-defined data plus the heating engineer settings: Press the button behind the pin opening together with the warmer and colder buttons for at least one second. After this reset, all factory settings will be reloaded (also refer to section Factory settings).

Mechanical design Battery change About 3 months before the batteries are exhausted, the battery symbol appears on the display, but all functions will be fully maintained. When changing the batteries, the current data will be retained for a maximum of one minute. The REV12 has a plastic housing with a large display and easily accessible operating elements. The controller is removed from its base by sliding it upward. It is thus possible to replace the two 1.5 V alkaline batteries type AAA in the compartment at the rear of the controller. The base can be fitted to most types of commercially available recessed conduit boxes or directly on the wall for wiring. The base only houses the terminals for the electrical connection between the controller and the connected devices. The entire electronics (including the relay with a potentialfree N.O. contact) are accommodated in the controller.

Controller

Base

6/10 Siemens Building Technologies HVAC Products Room temperature controller REV12 CE1N2261en 23.04.2002

Notes Engineering The room temperature controller should be fitted in the main living room The place of installation should be chosen such that the sensor can capture the room temperature as accurately as possible, without being affected by direct solar radiation or other heating or cooling sources Mounting height is approximately 1.5 m above the floor The controller can be fitted to most commercially available recessed conduit boxes or directly on the wall Above the unit, there must be sufficient clearance to remove the controller from its base and to replace it

min. 10 cm

Mounting and installation

When installing the controller, the base must first be fitted and wired. Then, the unit can be slid onto the base from above For more detailed information, please refer to the installation instructions supplied with the controller For the electrical installation, the local safety regulations must be complied with The battery transit tab, which prevents inadvertent operation of the controller during transport and storage, must be removed The control mode can be changed on the heating engineer level If the reference room is equipped with thermostatic radiator valves, they must be set to their fully open position If the displayed room temperature does not correspond to the effective room temperature, the temperature sensor should be recalibrated (refer to Sensor calibration)

Commissioning

Technical data General unit data Operating voltage Batteries (alkaline AAA) Battery life Backup for batter change Switching capacity of relay Voltage Current Safety class Sensing element Measuring range Time constant Setpoint setting ranges Normal temperature Economy temperature Frost protection temperature DC 3 V 2 x 1.5 V approx. 2 years max. 1 min AC 24250 V 6 (2.5) A II to EN 60 730-1 NTC 10 k 1 % at 25 C 050 C max. 10 min 529 C 529 C 5...29 C (factory setting 5 C)

2261Z03

7/10 Siemens Building Technologies HVAC Products Room temperature controller REV12 CE1N2261en 23.04.2002

Resolution of settings and display Setpoints Switching times Measurement of actual value Display of actual value Display of time Norms and standards CE conformity Electromagnetic compatibility Low voltage directive C-Tick Product standards Automatic electrical controls for household and similar use Electromagnetic compatibility Immunity Emissions Operation Climatic conditions Perm. ambient temperature Humidity Storage and transport Climatic conditions Ambient temperature Humidity Mechanism Incl. package Housing Base Housing

0.2 C 10 min 0.1 C 0.2 C 1 min 89/336/EEC 73/23/EEC


N474

EN 60 730-1 EN 50082-1 EN 50081-1 class 3K3 to IEC 60 721-3 5...40 C < 85 % r.h. class 2K3 to IEC 60 721-3 -25+70 C < 93 % r.h. class 2M2 to IEC 60 721-3 0.270 kg signal-white RAL9003 grey RAL7038 128 x 96 x 30 mm

Environmental conditions

Weight Color Size

8/10 Siemens Building Technologies HVAC Products Room temperature controller REV12 CE1N2261en 23.04.2002

Connection diagram

AC 24...250 V

DC 3 V

L L1

N1

M1 Y1
N N

L L1 M1 N N1 Y1

Live, AC 24250 V N.O. contact, AC 24250 V / 6 (2.5) A Circulating pump Neutral conductor Room temperature controller REV12 Actuating device

Application example

2261S03

2261A01
F2
T

T T

F1 F2

F1
T

Y2 M1

Y2 M1
2261S01

N1
T

N1
T

Instantaneous water heater

Atmospheric gas burner

9/10 Siemens Building Technologies HVAC Products Room temperature controller REV12 CE1N2261en 23.04.2002

Y4
M

Y3
M

Y1

M1

N1
T

N1
T

2261S02

N1
T

2261S04

Zone valve

Circulating pump with precontrol by manual mixing valve

F1 F2 M1 N1 Y1 Y2 Y3 Y4 Dimensions

Limit thermostat Safety limit thermostat Circulating pump Room temperature controller REV12 2-port valve with manual adjustment Solenoid valve Motorized 3-port valve Motorized 2-port valve

30

115.10

96.20

78.80

60

11.75 83.50

10/10 Siemens Building Technologies HVAC Products

2001 Siemens Building Technologies AG Room temperature controller REV12

Subject to alteration CE1N2261en 23.04.2002

2261M01