Professional Documents
Culture Documents
With horizontally installed flow-to-close control valves, the drain should be at the lowest point of the valve inlet side (and may be located within the valve body cavity) Piping downstream of a control valve should be self-draining with a minimum of a 1% continuous slope If the downstream piping is not selfdraining, reliable automatic drain of sufficient capacity should be installed at any low point of the pipe Drains must be properly sized and functioning Drains must be regularly checked locally by plant operating personnel for proper operation CCI Valve Doctors are available to provide a technical review of steam piping isometric drawings and drain arrangement
Only reasonably dry steam should flow through Control Valves Condensate from the main steam pipe should be drained before the branch connection to the Control Valve. The connection pipe from main steam lines should be self-draining for nonflowing conditions and should have a
Drain Sizing
The drip leg should have a diameter of 0.5 x pipe diameter and a minimum depth of 1.5 x pipe diameter. The required capacity for drains increases for cases where the steam velocity is low or the steam is within 10oC of saturation. When determining the minimum pressure drop between the pipe to be drained and the drain receiving system, all operating conditions must be considered. Drains should have sufficient capacity for condensate formed during all start-up conditions as well as other transient plant operating conditions CCI must be informed with the order about location and size of any required drain and pre-warming connection in the control valve body.
Motorized Valve
Steam Trap
When a steam trap is used for drainage, a motorized valve operates during start-up while the steam-trap removes condensate during normal operation. Steam traps are not always suitable for higher and/or variable pressure operation. For conditions where automatic steam traps are not suitable other means of drain valve control must be used. Alternatives to steam traps are automated drain valves triggered by measurement of condensate level or measurement or degree of superheat in the drain pot.
through the control valve can achieve the necessary pipe warming during plant operation. In addition, there are various arrangements which can keep control valves and piping warm with very low heat consumption.
CCI World Headquarters California Telephone: (949) 858-1877 Fax: (949) 858-1878 22591 Avenida Empresa Rancho Santa Margarita, California 92688 USA CCI Sweden (BTG Valves) Telephone: 46 533 426 00 Fax: 46 533 125 00 Box 602 661 29 Sffle Sweden
CCI Switzerland (Sulzer Valves) Telephone: 41 52 262 11 66 Fax: 41 52 262 01 65 Hegifeldstrasse 10 CH-8404 Winterthur Switzerland CCI Austria (Spectris Components GmbH) Telephone: 43 1 869 27 40 Fax: 43 1 865 36 03 Carlbergergasse 38/Pf.19 AT-1233 Vienna Austria
CCI Korea Telephone: 82 31 985 9430 Fax: 82 31 985 0552 26-17, Pungmu-Dong Kimpo City, Kyunggi-Do 415-070 South Korea CCI Japan Telephone: 81 726 41 7197 Fax: 81 726 41 7198 194-2, Shukunosho Ibaraki-City, Osaka 567-0051 Japan
CCI China Telephone: 86 10 6501 0350 Fax: 86 10 6501 0286 Room 567/569 Office Tower Poly Plaza 14 Dongzhimen South Avenue Beijing 100027 China CCI Italy (STI) Telephone: 39 035 29282 Fax: 39 035 2928247 Via G. Pascoli 10A-B 24020 Gozle, Bergamo Italy
543 - avoiding condensate accumulation in non-steam conditioning valves.doc / Rev.0 543 02/03