You are on page 1of 4

RTU560

Data Sheet Fiber Optic Coupler 23OK24


Hence it follows the following applications:

Fiber Optic Coupler 23OK24

Substitution of the RTU560 electrical serial peripheral bus between the subracks of a station Coupling of digital protection relays with fiber optic interfaces according to IEC60870-5-103 - With point to point connection - In a multi-drop link connection - In a bus link Optical booster to extend a fiber optic link Connection to any other unit with optical interface The board 23OK24 occupies one slot in a RTU560 rack. It couples itself via the backplane direct with the RTU560 peripheral bus.

Application
The fiber optic coupler 23OK24 is intended for the use in the Remote Terminal Unit RTU560 or in other foreign devices. The module is used to transmit data via two independent optical links (Receive and Transmit). Optical fiber cables are not sensitive to inductive and capacitive interferences, as well for potential differences between the two data communication equipments. Fiber optic cables will be used to bridge over distances in critical environments, or if a potential isolation is required. The maximum distance can be up to 2600 m. The board can be used for signal conversion of the received and transmitted data for the following electrical interface standards: RTU560 I/O-Bus RS485 Bus RS232 C Figure 1: Principle block diagram

The board is available for 820 nm glass fiber optic cable with bajonet lock socket type BFOC/2.5 according to IEC 874-10 The fiber optic cable connection is done by the four lock sockets on the front plate. The maximum distance between two 23OK24 depends on the fiber optic cable type the number of fiber slices

Doc-No.: 1KGT 150 567 V002 1

RTU560
Data Sheet Fiber Optic Coupler 23OK24
The maximum transfer rate is only limited by the transmission rate of the electrical interface. Interface standard and output optical power can be selected and configured by jumper. The marking condition is defined to Light ON or Light OFF. Selectable time supervision (TSV) switches the receiver off, if the receive signal is active longer than 16 msec. The electrical RTU560 peripheral bus can be substituted by the 23OK24 board either between groups of subracks or as well completely. The real configuration can be adapted very easy to the actual local facts. The 23OK24 connects the subracks either in a star-configuration or in a multipoint-T configuration. The 23OK24 board allows direct connecting the digital protection relays either in a point-to-point link, in a multidrop link or in a bus link. One 23OK24 board can be used also as optical amplifier without additional wiring. Six light-emitting diodes on the front panel indicate the following operation states: Tx 1/2 Transmit data active Rx 1/2 Receive data active ST 1/2 Time supervision (TSV) occurred

Doc.-No.: 1KGT 150 567 V002 1

RTU560
Data Sheet Fiber Optic Coupler 23OK24

Technical Data
In addition to the RTU560 general data, the following applies:

Optical Interface
Fiber optic cable length with consideration of a 3 dB reserve:

Fiber optic coupler


Emission wave length Input optical power Transmission rate Marking condition 820 nm Min. 24,0 dBm Max. 10,0 dBm 1 Mbit/s max. (max. rate of serial interface) adjustable

Fiber optic cable type

Output optical power (dBm) -19,7 -15,9 -10,4 -5,4

Input optical power (dBm) -24

System power (dBm) 1,3 5,1 10,6 15,6

50/125 m *62,5/125 m *100/140 m 200 m

Electrical serial interfaces RTU560 I/O and RS485 Bus


Signals Input Voltage Output voltage (at 54 load) Input impedance Transmission rate Ready to receive after send No optical echo TA / TB; RxA / RxB -12 V bis + 15 V 5,0 V max. 1,5 V min. 12 k 19,2 kBit/s 10 sek. Approx.. 10 sek.

Attenuation through two plugs included * : Recommended cable types

Available fiber optic cable length


Fiber optic cable length with consideration of a 3 dBm reserve, in dependence of the output power and typical fiber optic cable attenuations:

Fiber optic cable type 50 m *62,5 m *100 m 200 m

System power (dBm)

Cable Plug attenuation attenuation (dB) (dB/km) 0,3 3,0 3,5 5,0 1,8 6,0

Fiber optic cable length (m) 447 1469 2128 2607

Interface RS232C
Output Signals Input Signals Input voltage Output voltage Input impedance Transmission rate RxD / TxDT TxD 30 V max. 5 V min. 3000 230 kBit/s

1,3 5,1 10,6 15,6

* : Recommended cable types

Doc.-No.: 1KGT 150 567 V002 1

RTU560
Data Sheet Fiber Optic Coupler 23OK24

Power Supply
Supply voltage 5 Volt: 260 mA max. 24 Volt: 4 mA

Connection Type
Connector Fiber Optic Cable Indirect, 48-pole Type F DIN 41612 Bajonet lock socket Type BFOC/2,5 (IEC 874-10)

Mechanical Layout
PCB Front plate Weight 3HE, Euro card format (160 x 100) 4R, 1 slot (20 mm) Approx. 0,2 kg

Environmental Conditions
Temperature 0 ... 70 C Relative Humidity 5 ... 95 % (non condensing)

Safety
Transmitter Class 1 LED

Ordering Information
Front plate 23OK24 R5001 light beige 1 KGT 011 800 R5001

Note: We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB AG does not accept any responsibility whatsoever for potential errors or possible lack of information in this document. We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization of its contents - in whole or in parts - is forbidden without prior written consent of ABB AG. Copyright 2011 ABB All rights reserved

Doc.-No.: 1KGT 150 567 V002 1