INSTALLATION INSTRUCTIONS

Generator Paralleling Controller, GPC-3 Generator Protection Unit, GPU-3/GPU-3 Hydro Paralleling and Protection Unit, PPU-3
Mounting Board slot positions I/O lists Wiring

Document no.: 4189340582E SW version 3.0x.x or later

GPC/GPU/GPU Hydro/PPU

Installation Instructions

This document is valid for the following products: GPC/GPU/GPU Hydro/PPU Software version 3.0X.X

DEIF A/S

Page 2 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

Table of contents 1. ABOUT THIS DOCUMENT ............................................................ 5 GENERAL PURPOSE............................................................................... 5 INTENDED USERS .................................................................................. 5 CONTENTS/OVERALL STRUCTURE .......................................................... 5 DEFINITIONS ......................................................................................... 5 2. WARNINGS AND LEGAL INFORMATION ................................... 7 LEGAL INFORMATION AND RESPONSIBILITY ............................................. 7 ELECTROSTATIC DISCHARGE AWARENESS ............................................. 7 SAFETY ISSUES ..................................................................................... 7 3. MOUNTING..................................................................................... 8 MOUNTING OF THE UNIT......................................................................... 8 PANEL CUTOUT ..................................................................................... 8 MOUNTING INSTRUCTIONS ..................................................................... 8 4. 5. 6. 7. GENERAL HARDWARE DESCRIPTION ...................................... 9 HARDWARE ........................................................................................... 9 GPU/GPU HYDRO I/O LIST ........................................................ 12 GPC/PPU I/O LIST ....................................................................... 26 WIRINGS ....................................................................................... 41 AC CONNECTIONS (3-PHASE) .............................................................. 41 AC CONNECTIONS (1-PHASE) .............................................................. 42 AC CONNECTIONS (2-PHASE) .............................................................. 43 MODBUS, RS485 (OPTION H2) ............................................................ 44 MODBUS, RS232 (OPTION H9.2) ......................................................... 47 PROFIBUS DP (OPTION H3) ................................................................. 48 CANBUS ENGINE COMMUNICATION (OPTION H5) .................................. 49 CANBUS ENGINE COMMUNICATION (OPTION H7) .................................. 50 LOAD SHARING LINES........................................................................... 51 MECHANICAL SPEED GOVERNOR.......................................................... 51 AVR WITH RELAY OUTPUTS ................................................................. 52 ELECTRONIC SPEED GOVERNOR .......................................................... 53 AVR WITH ANALOGUE OUTPUTS .......................................................... 54 DIGITAL INPUTS ................................................................................... 55

DEIF A/S

Page 3 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

DIGITAL INPUTS WITH WIRE BREAK SUPERVISION (OPTION M4) ............. 55 MULTI-FUNCTIONAL INPUTS (OPTION M4) ............................................. 56 MAGNETIC PICK-UP (MPU) INPUT (OPTION M4) ................................... 58 ANALOGUE INPUTS (OPTION M15.X) .................................................... 59 STOP COIL WITH WIRE BREAK DETECTION (OPTION M4)........................ 59 TRANSISTOR OUTPUTS ........................................................................ 60 ADDITIONAL DISPLAY UNIT, DU-2 (OPTION X2) ..................................... 61 ADDITIONAL OPERATORS PANEL, AOP-1 (OPTION X3)......................... 62 ADDITIONAL OPERATOR'S PANEL, AOP-2 (OPTION X4) ......................... 63 8. GENERAL DATA .......................................................................... 64 TECHNICAL SPECIFICATIONS ................................................................ 64 DIMENSIONS ....................................................................................... 71

DEIF A/S

Page 4 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

1. About this document


General purpose This document is the Installation Instructions for DEIFs GPC-3, PPU-3, GPU-3 and GPU-3 Hydro. The document mainly includes general hardware description, I/O lists and wiring descriptions. The general purpose of these installation instructions is to give the user important information to be used in the installation of the controllers.

Please make sure that you read this manual before starting to work with the controllers. Failure to do this could result in damaging the equipment or, even worse, injury of personnel.

Intended users These installation instructions are mainly intended for the panel builder designer in charge. On the basis of this document, the panel builder designer will give the electrician the information he needs in order to install the controllers, e.g. detailed electrical drawings. In some cases the electrician may use these installation instructions himself. Contents/overall structure This document is divided into chapters, and in order to make the structure simple and easy to use, each chapter will begin from the top of a new page. Definitions Throughout this document a number of notes and warnings will be presented. To ensure that these are noticed, they will be highlighted in order to separate them from the general text.

DEIF A/S

Page 5 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

Notes The notes provide general information which will be helpful for the reader to bear in mind. Warnings The warnings indicate a potentially dangerous situation which could result in death, personal injury or damaged equipment, if certain guidelines are not followed.

DEIF A/S

Page 6 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

2. Warnings and legal information


Legal information and responsibility DEIF takes no responsibility for installation or operation of the generator sets. If there is any doubt about how to install or operate the generator sets controlled by the controllers, the company responsible for the installation or the operation of the sets must be contacted. The controllers are not to be opened by unauthorised personnel. If opened anyway, the warranty will be lost. Electrostatic discharge awareness Sufficient care must be taken to protect the terminals against static discharges during the installation. Once the system is installed and connected, these precautions are no longer necessary. Safety issues Installing the controllers implies work with dangerous currents and voltages. Therefore, the installation should only be carried out by authorised personnel who understand the risks involved in working with live electrical equipment. Be aware of the hazardous live currents and voltages. Do not touch any AC measurement inputs as this could lead to injury or death.

DEIF A/S

Page 7 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

3. Mounting
Mounting of the unit The unit is designed for mounting inside the switchboard. The display can be installed on the switchboard door and connected to the main unit with a display cable. The technical specifications in chapter 8 include detailed information about: Unit dimensions Panel cutout Screw hole positions and dimensions Panel cutout In order to ensure optimum mounting, the switchboard door must be cut out according to the panel cutout illustration presented in chapter 8. Mounting instructions For land applications the units can be either DIN-rail or base mounted. For marine applications the units have to be mounted with screws to the rear side of the cabinet. Six screw holes are available for this mounting method. DEIF recommends using the screw hole fastening.

DEIF A/S

Page 8 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

4. General hardware description


Hardware The unit housing is divided into board slot positions. This means that the unit consists of a number of printed circuit boards (PCBs) mounted in numbered slots. The green terminal blocks are then mounted in the PCBs. Some of these board slots are standard, and some are intended for options. The board slot positions are arranged as illustrated below.
Slot Slot #1 Slot #2 Term. 1-28 29-36 GPU/GPU Hydro Standard Option GPC/PPU Standard Option Description Power supply board Option: H2 (Modbus RS485) H3 (Profibus) H8.2 (Beckhoff ext. I/Os) H9.2 (Modbus RS232) GPC/PPU: Load sharing and I/O board GPU/GPU Hydro: I/O extension Option: E1 (2 x +/-25 mA output) E2 (2 x 0(4)...20 mA output) EF2 (1 x +/-25 mA, 1 x 0(4)...20 mA) EF4 (1 x +/-25 mA, 2 x relay outputs) EF5 (1 x PWM, +/-20 mA, 2 x relay outputs) M14.4 (4 x relay outputs) AC measuring Option: F1 (2 x analogue outputs) M13.6 (7 x binary inputs) M14.6 (4 x relay outputs) M15.6 (4 x analogue inputs) M4 (engine interface board or I/O extension) - CAN I/F A (H7 - J1939) - CAN I/F B (reserved)

Slot #3

37-64

Option M12 Option

Standard

Slot #4

65-72

Option M14.4 as std.

Slot #5 Slot #6

73-89 90-97

Standard Option

Standard Option

Slot #7

98-B3

Option

Option

DEIF A/S

Page 9 of 72

GPC/GPU/GPU Hydro/PPU Slot Slot #8 Term. 126-133 GPU/GPU Hydro Option GPC/PPU Option Description

Installation Instructions

Option: M13.8 (7 x binary inputs) M14.8 (4 x relay outputs) M15.8 (4 x analogue inputs) H5, H6 (engine comm.) H8.8 (Beckhoff ext. I/Os)

Only hardware options which will affect the hardware of the unit are represented in the table. The software options can be seen through the PC utility software. The software options are described in the data sheet.

DEIF A/S

Page 10 of 72

Slot #1 Slot #2

DEIF A/S

GPC/GPU/GPU Hydro/PPU

Unit top side overview

Slot #3
51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72
Service port Display

Slot #4

37 38 39 40 41 42 43 44 45 46 47 48 49 50

Engine CAN PMS CAN

Power Self check ok Alarm inhibit

73 74 75 76 77 78

79 80 81 82 83 84

85 86 87 88 89

90 91 92 93 94 95 96 97

Slot #6

Slot #5 Slot #7

Installation Instructions

Slot #8

An overview of the terminals is presented below. The slot positions are the following:

Page 11 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

5. GPU/GPU Hydro I/O list


Terminal strip description Slot #1, power supply and binary I/O For the relay outputs the following terms will be used: NO means Normally Open NC means Normally Closed Com. means common terminal for the relay in question
Term. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 Function +12/24V DC 0V DC NC Com. NO Com. NC NO Com. NC NO Com. NC NO Com. NC NO Com. NC Open collector 1 Open collector 2 Com. Binary input Technical data 8-36V DC Status relay 24 V/1 A Relay 5 250V AC/8 A Relay 8 250V AC/8 A Relay 11 250V AC/8 A Relay 14 250V AC/8 A Relay 17 250V AC/8 A Transistor out (relay 20) Transistor out (relay 21) Common Optocoupler Description Power supply Normally closed relay, processor/power supply status supervision Alarm horn/configurable

Configurable

Configurable

Open GB

Configurable

Configurable as standard relay output Configurable as standard relay output Common terminal for terminals 20 and 21 Alarm inhibit 1/configurable

DEIF A/S

Page 12 of 72

GPC/GPU/GPU Hydro/PPU 24 25 26 27 28 Binary input Binary input Binary input Binary input Com. Optocoupler Optocoupler Optocoupler Optocoupler Common

Installation Instructions Remote alarm acknowledge/ configurable Configurable Configurable Configurable Common for terminals 23-27

The power supply must be protected with a 2 A slowblow fuse.

DEIF A/S

Page 13 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

Slot #2, external communication (optional) Option H2 (Modbus RS485)


Term. 29 30 31 32 33 34 35 36 Function DATA + (A) Not used DATA - (B) Not used DATA + (A) Not used DATA - (B) Not used Description Modbus RTU/ASCII, RS485

The serial communication line should be terminated between DATA + and DATA - with a resistor equal to the cable impedance. The terminals 29/33 and 31/35 are internally connected. Option H3 (Profibus DP)
Term. 29 30 31 32 33 34 35 36 Function DATA + (B) GND DATA - (A) DATA + (B) GND DATA - (A) Not used Not used Description Pin 3 on 9-pole sub-D connector Pin 5 on 9-pole sub-D connector Pin 8 on 9-pole sub-D connector

DEIF A/S

Page 14 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

Option H8.2 CANbus interface for external I/O modules.


Term. 29 30 31 32 33 34 35 36 Function Not used Not used CAN-L Not used CAN-H CAN-L Not used CAN-H Description CANbus communication for Beckhoff external I/O modules

Option H9.2 (Modbus RS232)


Term. 29 30 31 32 33 34 35 36 Function DATA GND TxD RxD Description Modbus RTU/ASCII, RS232

DEIF A/S

Page 15 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

Slot #3, digital I/Os (option M12)


Term. 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 Function Technical data Description Not available Not available Not available Not available Not available Not available Configurable Configurable Configurable Configurable Configurable Configurable Configurable Configurable Configurable Configurable Configurable Configurable Configurable Common for terminals 43-55 GOV/AVR control or configurable GOV/AVR control or configurable GOV/AVR control or configurable GOV/AVR control or configurable

Binary input Binary input Binary input Binary input Binary input Binary input Binary input Binary input Binary input Binary input Binary input Binary input Binary input Com. NO Com. NO Com. NO Com. NO Com.

Optocoupler Optocoupler Optocoupler Optocoupler Optocoupler Optocoupler Optocoupler Optocoupler Optocoupler Optocoupler Optocoupler Optocoupler Optocoupler Common Relay 57 6 250V AC 8 A Relay 59 7 250V AC 8 A Relay 61 8 250V AC 8 A Relay 63 9 250V AC 8 A

GOV control requires option G2. AVR control requires options G2 and D1.

DEIF A/S

Page 16 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

Slot #4, GOV/AVR (optional) GOV control requires option G2. AVR control requires options G2 and D1. Option M14.4 GOV/AVR or configurable relay output card.
Term. 65 66 67 68 69 70 71 72 Function Relay 65 250V AC, 8 A Relay 67 250V AC, 8 A Relay 69 250V AC, 8 A Relay 71 250V AC, 8 A Description GOV/AVR or configurable GOV/AVR or configurable GOV/AVR or configurable GOV/AVR or configurable

Option E1 GOV/AVR or transducer output card.


Term. 65 66 67 68 69 70 71 72 Function Not used +/-20 mA out 0 Not used Not used +/-20 mA out 0 Not used Description Speed governor/AVR setpoint output or transducer (Analogue output 66)

Speed governor/AVR voltage setpoint output or transducer (Analogue output 70)

DEIF A/S

Page 17 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

Option E2 GOV/AVR or transducer output card.


Term. 65 66 67 68 69 70 71 72 Function Not used 0-20 mA out 0 Not used Not used 0-20 mA out 0 Not used Description Speed governor/AVR setpoint output or transducer (Analogue output 66)

Speed governor/AVR voltage setpoint output or transducer (Analogue output 70)

Option EF2 GOV/AVR or transducer output card.


Term. 65 66 67 68 69 70 71 72 Function Not used +/-20 mA 0 Not used Not used 0(4)-20 mA out 0 Not used Description Speed governor/AVR setpoint output or transducer (Analogue output 66)

Speed governor/AVR setpoint output or transducer (Analogue output 70)

Option EF4 GOV/AVR or transducer combination output card.


Term. 65 66 67 68 69 70 71 72 Function ANA + ANA Not used Not used Relay 69 250V AC, 8 A Relay 71 250V AC, 8 A Description Speed governor/AVR setpoint output or transducer (Analogue output 66)

GOV/AVR control or configurable GOV/AVR control or configurable

DEIF A/S

Page 18 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

Option EF5 PWM GOV and AVR combination output card.


Term. 65 66 67 68 69 70 71 72 Function +/-25 mA out 0 PWM + PWM Relay 69 250V AC, 8A Relay 71 250V AC, 8 A Description AVR setpoint output PWM speed governor signal GOV/AVR control or configurable GOV/AVR control or configurable

Slot #5, AC measuring


Term. 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 Function I L1 s1 I L1 s2 I L2 s1 I L2 s2 I L3 s1 I L3 s2 U L1 Not used U L2 Not used U L3 U neutral U L1 Not used U L2 U neutral U L3 Technical data Generator current L1 Generator current L2 Generator current L3 Generator voltage L1 Generator voltage L2 Generator voltage L3 Generator voltage neutral Bus voltage L1 Bus voltage L2 Bus voltage neutral Bus voltage L3 Description 1/5A AC input 1/5A AC input 1/5A AC input Max. 690V AC phase-phase value Max. 690V AC phase-phase value Max. 690V AC phase-phase value Max. 690V AC phase-phase value Max. 690V AC phase-phase value Max. 690V AC phase-phase value

Current inputs are galvanically separated. Max. 0.3 VA per phase. Voltage measurements are available (phase to phase) from 100V AC to 690V AC.

DEIF A/S

Page 19 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

Slot #6, I/O extension (optional) Option F1 Transducer output card.


Term. 90 91 92 93 94 95 96 97 Function Not used 0 0(4)-20 mA out Not used Not used 0 0(4)-20 mA out Not used Description Analogue output 91, selectable

Analogue output 95, selectable

Option M13.6 7 x binary inputs.


Term. 90 91 92 93 94 95 96 97 Function Common Digital input 91 Digital input 92 Digital input 93 Digital input 94 Digital input 95 Digital input 96 Digital input 97 Description Common Configurable Configurable Configurable Configurable Configurable Configurable Configurable

Option M14.6 4 x relay outputs.


Term. 90 91 92 93 94 95 96 97 Function Relay 90 250V AC, 8 A max. Relay 92 250V AC, 8 A max. Relay 94 250V AC, 8 A max. Relay 96 250V AC, 8 A max. Description Configurable Configurable Configurable Configurable

DEIF A/S

Page 20 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

Option M15.6 4 x analogue 4-20 mA inputs.


Term. 90 91 92 93 94 95 96 97 Function Input 90 common Analogue input 91+ Input 92 common Analogue input 93+ Input 94 common Analogue input 95+ Input 96 common Analogue input 97+ Description Common 4-20 mA in Common 4-20 mA in Common 4-20 mA in Common 4-20 mA in

DEIF A/S

Page 21 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

Slot #7, engine interface board (option M4)


Term. 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 A1 A2 A3 Function +12/24V DC 0V DC MPU input MPU GND A B C A B C A B C Com. Digital input 112 Digital input 113 Digital input 114 Digital input 115 Digital input 116 Digital input 117 Digital input 118 NO NO Com. NO Com. NO CAN-H CAN GND CAN-L Technical data 8-36V DC 0.5-70V AC/ 10-10000 Hz 0(4)-20 mA Digital w/wire break Pt100 Pt1000 VDO 0-40V DC Description/preconfiguration DC power supply Magnetic pick-up (RPM) Multi-input 1 Preselected to digital input with wire break detection Multi-input 2 Preselected to digital input with wire break detection Multi-input 3 Preselected to digital input with wire break detection Common for terminals 112-117 Configurable Configurable Shutdown override/configurable Configurable Running feedback/configurable Configurable Emergency stop and common for 119 and 120 Run coil/configurable Start prepare/configurable Crank (starter)/configurable Stop coil w/wire break/configurable CANbus J1939 engine interface (option H7)

Common Optocoupler Optocoupler Optocoupler Optocoupler Optocoupler Optocoupler Optocoupler Relay 24V DC/5A Relay 24V DC/5A Relay 24V DC/5A Relay 24V DC/5A CANbus

DEIF A/S

Page 22 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

Slot #8, communication and I/O (optional) Option H5 CANbus engine interface card.
Term. 126 127 128 129 130 131 132 133 Function Not used Not used CAN-L Not used CAN-H CAN-L Not used CAN-H Description CANbus communication for engine interface J1939 or MTU MDEC/MTU ADEC

Option H8.8 CANbus interface for external I/O modules.


Term. 126 127 128 129 130 131 132 133 Function Not used Not used CAN-L Not used CAN-H CAN-L Not used CAN-H Description CANbus communication for Beckhoff external I/O modules

Option M13.8 7 x binary inputs.


Term. 126 127 128 129 130 131 132 133 Function Common Digital input 127 Digital input 128 Digital input 129 Digital input 130 Digital input 131 Digital input 132 Digital input 133 Description Common Configurable Configurable Configurable Configurable Configurable Configurable Configurable

DEIF A/S

Page 23 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

Option M14.8 4 x relay outputs.


Term. 126 127 128 129 130 131 132 133 Function Relay 126 250V AC, 8 A max. Relay 128 250V AC, 8 A max. Relay 130 250V AC, 8 A max. Relay 132 250V AC, 8 A max. Description Configurable Configurable Configurable Configurable

Option M15.8 4 x analogue 4-20 mA inputs.


Term. 126 127 128 129 130 131 132 133 Function Input 127 common Analogue input 127+ Input 129 common Analogue input 129+ Input 131 common Analogue input 131+ Input 133 common Analogue input 133+ Description Common 4-20 mA in Common 4-20 mA in Common 4-20 mA in Common 4-20 mA in

DEIF A/S

Page 24 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

Digital inputs
Term. 23 24 25 26 27 Name Alarm inhibit 1/ configurable Remote alarm acknowledge/configurable Configurable/start sync./ control (option G2) Configurable/GB open (option G2) Configurable/GB closed (option G2) Function External input for inhibit of selected alarms

Option G2: Activates synchronisation. The Deload function is used to open the breaker Option G2: Breaker feedback signal. The connection breaker is in position OFF Option G2: Breaker feedback signal. The connection breaker is in position ON

Relay outputs
Term. 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 Name Status relay Function The status relay on the power supply board is a normally closed relay with the purpose of processor and power supply supervision The relay is activated on any alarm that appears. The output can be normally open (terminal 5-6) or normally closed (terminal 6-7)

Alarm horn relay/ configurable Configurable

Configurable

Open GB

Configurable/close GB

Configurable Configurable

Generator breaker OFF signal. The output can be selected to be normally open (NO, terminal 14-15) or normally closed (NC, terminal 15-16) Option G2: Generator breaker ON signal. The output can be selected to be normally open (NO, terminal 17-18) or normally closed (NC, terminal 18-19) Configurable digital output (transistor output type) Configurable digital output (transistor output type)

DEIF A/S

Page 25 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

6. GPC/PPU I/O list


Terminal strip description Slot #1, power supply and binary I/O For the relay outputs the following terms will be used: NO means Normally Open NC means Normally Closed Com. means common terminal for the relay in question
Term. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 Function +12/24V DC 0V DC NC Com. NO Com. NC NO Com. NC NO Com. NC NO Com. NC NO Com. NC Open collector 1 Open collector 2 Com. Binary input Technical data 8-36V DC Status relay 24 V/1 A Relay 5 250V AC/8 A Relay 8 250V AC/8 A Relay 11 250V AC/8 A Relay 14 250V AC/8 A Relay 17 250V AC/8 A Transistor out (relay 20) Transistor out (relay 21) Common Optocoupler Description Power supply Normally closed relay, processor/power supply status supervision Alarm horn/configurable

Configurable

Configurable

Open GB

Close GB

Configurable as standard relay output Configurable as standard relay output Common terminal for terminals 20 and 21 Alarm inhibit 1/configurable

DEIF A/S

Page 26 of 72

GPC/GPU/GPU Hydro/PPU 24 25 26 27 28 Binary input Binary input Binary input Binary input Com. Optocoupler Optocoupler Optocoupler Optocoupler Common

Installation Instructions Remote alarm acknowledge/ configurable Start sync./control/configurable GB open GB closed Common for terminals 23-27

The power supply must be protected with a 2 A slowblow fuse.

DEIF A/S

Page 27 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

Slot #2, external communication (optional) Option H2 (Modbus RS485)


Term. 29 30 31 32 33 34 35 36 Function DATA + (A) Not used DATA - (B) Not used DATA + (A) Not used DATA - (B) Not used Description Modbus RTU/ASCII, RS485

The serial communication line should be terminated between DATA + and DATA - with a resistor equal to the cable impedance. The terminals 29/33 and 31/35 are internally connected. Option H3 (Profibus)
Term. 29 30 31 32 33 34 35 36 Function DATA + (B) GND DATA - (A) DATA + (B) GND DATA - (A) Not used Not used Description Pin 3 on 9-pole sub-D connector Pin 5 on 9-pole sub-D connector Pin 8 on 9-pole sub-D connector

DEIF A/S

Page 28 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

Option H8.2 CANbus interface for external I/O modules.


Term. 29 30 31 32 33 34 35 36 Function Not used Not used CAN-L Not used CAN-H CAN-L Not used CAN-H Description CANbus communication for Beckhoff external I/O modules

Option H9.2 (Modbus RS232)


Term. 29 30 31 32 33 34 35 36 Function DATA GND TxD RxD Description Modbus RTU/ASCII, RS232

DEIF A/S

Page 29 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

Slot #3, digital I/O


Term. 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 Function -505V DC Com. -505V DC -10010V DC Com. -10010V DC Binary input Binary input Binary input Binary input Binary input Binary input Binary input Binary input Binary input Binary input Binary input Binary input Binary input Com. NO Com. NO Com. NO Com. NO Com. Technical data Analogue I/O Common Analogue I/O Analogue input Common Analogue input Optocoupler Optocoupler Optocoupler Optocoupler Optocoupler Optocoupler Optocoupler Optocoupler Optocoupler Optocoupler Optocoupler Optocoupler Optocoupler Common Relay 57 6 250V AC 8 A Relay 59 7 250V AC 8 A Relay 61 8 250V AC 8 A Relay 63 9 250V AC 8 A Description Active load sharing line Common for load sharing lines Reactive load sharing f/P setpoint (passive) Common for 40/42 U/Q setpoint (passive) Deload/configurable Man. GOV UP/configurable Man. GOV DOWN/configurable Man. AVR UP/configurable Man. AVR DOWN/configurable Fixed frequency/configurable P load sharing/configurable Ext. GOV setpoint/configurable Fixed voltage/configurable Q load sharing/configurable Ext. AVR setpoint/configurable Configurable Configurable Common for terminals 43-55 GOV/AVR control or configurable GOV/AVR control or configurable GOV/AVR control or configurable GOV/AVR control or configurable

AVR control requires option D1.

DEIF A/S

Page 30 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

Slot #4, GOV/AVR AVR control requires option D1. Option M14.4 (standard) GOV/AVR or configurable relay output card.
Term. 65 66 67 68 69 70 71 72 Function Relay 65 250V AC, 8 A Relay 67 250V AC, 8 A Relay 69 250V AC, 8 A Relay 71 250V AC, 8 A Description GOV/AVR or configurable GOV/AVR or configurable GOV/AVR or configurable GOV/AVR or configurable

Option E1 GOV/AVR or transducer output card.


Term. 65 66 67 68 69 70 71 72 Function Not used +/-20 mA out 0 Not used Not used +/-20 mA out 0 Not used Description Speed governor/AVR setpoint output or transducer (Analogue output 66)

Speed governor/AVR voltage setpoint output or transducer (Analogue output 70)

DEIF A/S

Page 31 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

Option E2 GOV/AVR or transducer output card.


Term. 65 66 67 68 69 70 71 72 Function Not used 0-20 mA out 0 Not used Not used 0-20 mA out 0 Not used Description Speed governor/AVR setpoint output or transducer (Analogue output 66)

Speed governor/AVR voltage setpoint output or transducer (Analogue output 70)

Option EF2 GOV/AVR or transducer output card.


Term. 65 66 67 68 69 70 71 72 Function Not used +/-20 mA 0 Not used Not used 0(4)-20 mA out 0 Not used Description Speed governor/AVR setpoint output or transducer (Analogue output 66)

Speed governor/AVR setpoint output or transducer (Analogue output 70)

Option EF4 GOV/AVR or transducer combination output card.


Term. 65 66 67 68 69 70 71 72 Function ANA + ANA Not used Not used Relay 69 250V AC, 8 A Relay 71 250V AC, 8 A Description Speed governor/AVR setpoint output or transducer (Analogue output 66)

GOV/AVR control or configurable GOV/AVR control or configurable

DEIF A/S

Page 32 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

Option EF5 PWM GOV and AVR combination output card.


Term. 65 66 67 68 69 70 71 72 Function +/-25 mA out 0 PWM + PWM Relay 69 250V AC, 8 A Relay 71 250V AC, 8 A Description AVR setpoint output PWM speed governor signal GOV/AVR control or configurable GOV/AVR control or configurable

Slot #5, AC measuring


Term. 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 Function I L1 s1 I L1 s2 I L2 s1 I L2 s2 I L3 s1 I L3 s2 U L1 Not used U L2 Not used U L3 U neutral U L1 Not used U L2 U neutral U L3 Technical data Generator current L1 Generator current L2 Generator current L3 Generator voltage L1 Generator voltage L2 Generator voltage L3 Generator voltage neutral Mains bus voltage L1 Mains bus voltage L2 Mains bus voltage neutral Mains bus voltage L3 Description 1/5A AC input 1/5A AC input 1/5A AC input Max. 690V AC phase-phase value Max. 690V AC phase-phase value Max. 690V AC phase-phase value For land-based applications only Max. 690V AC phase-phase value Max. 690V AC phase-phase value For land-based applications only Max. 690V AC phase-phase value

Current inputs are galvanically separated. Max. 0.3 VA per phase. Voltage measurements are available (phase to phase) from 100V AC to 690V AC.

DEIF A/S

Page 33 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

Slot #6, I/O extension (optional) Option F1 Transducer output card.


Term. 90 91 92 93 94 95 96 97 Function Not used 0 0(4)-20 mA out Not used Not used 0 0(4)-20 mA out Not used Description Analogue output 91, selectable

Analogue output 95, selectable

Option M13.6 7 x binary inputs.


Term. 90 91 92 93 94 95 96 97 Function Common Digital input 91 Digital input 92 Digital input 93 Digital input 94 Digital input 95 Digital input 96 Digital input 97 Description Common Configurable Configurable Configurable Configurable Configurable Configurable Configurable

Option M14.6 4 x relay outputs.


Term. 90 91 92 93 94 95 96 97 Function Relay output 90 250V AC, 8 A max. Relay output 92 250V AC, 8 A max. Relay output 94 250V AC, 8 A max. Relay output 96 250V AC, 8 A max. Description Configurable Configurable Configurable Configurable

DEIF A/S

Page 34 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

Option M15.6 4 x analogue 4-20 mA inputs.


Term. 90 91 92 93 94 95 96 97 Function Input 90 common Analogue input 91+ Input 92 common Analogue input 93+ Input 94 common Analogue input 95+ Input 96 common Analogue input 97+ Description Common 4-20 mA in Common 4-20 mA in Common 4-20 mA in Common 4-20 mA in

DEIF A/S

Page 35 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

Slot #7, engine interface board (option M4)


Term. 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 A1 A2 A3 Function +12/24V DC 0V DC MPU input MPU GND A B C A B C A B C Com. Digital input 112 Digital input 113 Digital input 114 Digital input 115 Digital input 116 Digital input 117 Digital input 118 NO NO Com. NO Com. NO CAN-H CAN GND CAN-L Technical data 8-36V DC 0.5-70V AC/ 10-10000 Hz 0(4)-20 mA Digital w/wire break Pt100 Pt1000 VDO 0-40V DC Description/preconfiguration DC power supply Magnetic pick-up Multi-input 1 Preselected to digital input with wire break detection Multi-input 2 Preselected to digital input with wire break detection Multi-input 3 Preselected to digital input with wire break detection Common for terminals 112-117 Configurable Configurable Shutdown override/configurable Configurable Running feedback/configurable Configurable Emergency stop and common for 119 and 120 Run coil/configurable Start prepare/configurable Crank (starter)/configurable Stop coil w/wire break/configurable CANbus J1939 engine interface (option H7)

Common Optocoupler Optocoupler Optocoupler Optocoupler Optocoupler Optocoupler Optocoupler Relay 24V DC/5 A Relay 24V DC/5 A Relay 24V DC/5 A Relay 24V DC/5 A CANbus

DEIF A/S

Page 36 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

Slot #8, communication and I/O (optional) Option H5 CANbus engine interface card.
Term. 126 127 128 129 130 131 132 133 Function Not used Not used CAN-L Not used CAN-H CAN-L Not used CAN-H Description CANbus communication for engine interface J1939 or MTU MDEC/MTU ADEC

Option H8.8 CANbus interface for external I/O modules.


Term. 126 127 128 129 130 131 132 133 Function Not used Not used CAN-L Not used CAN-H CAN-L Not used CAN-H Description CANbus communication for Beckhoff external I/O modules

Option M13.8 7 x binary inputs.


Term. 126 127 128 129 130 131 132 133 Function Common Digital input 127 Digital input 128 Digital input 129 Digital input 130 Digital input 131 Digital input 132 Digital input 133 Description Common Configurable Configurable Configurable Configurable Configurable Configurable Configurable

DEIF A/S

Page 37 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

Option M14.8 4 x relay outputs.


Term. 126 127 128 129 130 131 132 133 Function Relay output 126 250V AC, 8 A max. Relay output 128 250V AC, 8 A max. Relay output 130 250V AC, 8 A max. Relay output 132 250V AC, 8 A max. Description Configurable Configurable Configurable Configurable

Option M15.8 4 x analogue 4-20 mA inputs.


Term. 126 127 128 129 130 131 132 133 Function Input 127 common Analogue input 127+ Input 129 common Analogue input 129+ Input 131 common Analogue input 131+ Input 133 common Analogue input 133+ Description Common 4-20 mA in Common 4-20 mA in Common 4-20 mA in Common 4-20 mA in

DEIF A/S

Page 38 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

Digital inputs
Term. 23 24 25 26 27 43 44 45 46 47 48 49 50 Name Alarm inhibit 1/configurable Remote alarm acknowledge/ configurable Start sync./control/ configurable GB open GB closed Deload/configurable Manual GOV UP/ configurable Manual GOV DOWN/ configurable Manual AVR UP/ configurable Manual AVR DOWN/ configurable Fixed frequency/configurable P load sharing/configurable Ext. GOV setpoint/ configurable Fixed voltage/configurable Q load sharing/configurable Ext. AVR setpoint/ configurable Configurable Configurable Function External input for inhibit of selected alarms Remote alarm acknowledge Activates the regulation and synchronisation. Works together with Deload (43) Breaker feedback signal. The connection breaker is in position OFF Breaker feedback signal. The connection breaker is in position ON Activates the deload sequence. Works together with start sync./control (25) Increase engine speed Decrease engine speed Option D1: Increase generator voltage Option D1: Decrease generator voltage Activates frequency controller Activates load sharing controller The nominal frequency setpoint will be controlled from the analogue inputs terminal 40/41. The internal setpoint will not be used Activates voltage controller Activates Q load sharing controller The nominal voltage setpoint will be controlled from the analogue inputs terminal 41/42. The internal setpoint will not be used

51 52 53

54 55

DEIF A/S

Page 39 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

Relay outputs
Term. 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 65 66 67 68 69 70 71 72 Name Status relay Function The status relay on the power supply board is a normally closed relay with the purpose of processor and power supply supervision The relay is activated on any alarm that appears. The output can be normally open (terminal 5-6) or normally closed (terminal 6-7)

Alarm horn relay/ configurable Configurable

Configurable

Open GB

Close GB

Configurable Configurable Configurable Configurable Configurable Configurable

Generator breaker OFF signal. The output can be selected to be normally open (NO, terminal 14-15) or normally closed (NC, terminal 15-16) Generator breaker ON signal. The output can be selected to be normally open (NO, terminal 17-18) or normally closed (NC, terminal 18-19) Configurable digital output (transistor output type) Configurable digital output (transistor output type) GOV/AVR control or configurable GOV/AVR control or configurable GOV/AVR control or configurable GOV/AVR control or configurable

DEIF A/S

Page 40 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

7. Wirings
AC connections (3-phase)

BUSBAR
L1 L2 L3 N
89 88 87 85

ML2
UL3 N UL2 UL1 BUSBAR VOLTAGE

17 18

14 15

84 83 81 79

N UL3 UL2 UL1 GENERATOR VOLTAGE

s2

78 77 76 75 74 73

I3

s1 s2

I2

GENERATOR CURRENT

s1 s2

I1

s1

GENERATOR
The neutral line (N) connection is not necessary for correct measurement. 3-phase without neutral is also possible. The current transformer ground connection can be on the s1 or s2 connection, whichever is preferred. Fuses: 2 A slow-blow.
DEIF A/S Page 41 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

AC connections (1-phase)

BUSBAR
L1 N
89 88 87 85 UL1 N BUSBAR VOLTAGE

ML2

17 18

14 15

84 83 81 79

N GENERATOR VOLTAGE UL1

78 77 76 75
s2

GENERATOR CURRENT

74 73

I1

s1

GENERATOR
DEIF A/S Page 42 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

AC connections (2-phase)

BUSBAR
L1 L3 N
89 88 87 85

ML2
UL3 N UL2 UL1 BUSBAR VOLTAGE

17 18

14 15

84 83 81 79

N UL3 UL2 UL1 GENERATOR VOLTAGE

s2

78 77 76 75

I3

s1

I2

GENERATOR CURRENT

s2

74 73

I1

s1

GENERATOR
DEIF A/S Page 43 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

Modbus, RS485 (option H2) Connection with 2-wire screened cable (recommended): Multi-line
DATA + (A) DATA + (A) DATA - (B) DATA + (A) DATA - (B) Not used Not used Not used

Multi-line
DATA + (A) DATA + (A) DATA - (B) DATA - (B) Not used Not used Not used

Multi-line
DATA + (A) DATA + (A) DATA - (B) DATA - (B) Not used Not used Not used

COM

COM

29 30 31 32 33 34 35 36

PLC or other device

DEIF A/S

COM

29 30 31 32 33 34 35 36

29 30 31 32 33 34 35 36

COM DATA - (B)

Connect shield to ground at one end only. Shield ends must be insulated with tape or insulation tubing. Use shielded twisted cable.

Page 44 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

Connection with 3-wire shielded cable: Multi-line


DATA + (A) DATA + (A) DATA - (B) DATA + (A) DATA - (B) Not used Not used Not used

Multi-line
DATA + (A) DATA + (A) DATA - (B) DATA - (B) Not used Not used Not used

Multi-line
DATA + (A) DATA + (A) DATA - (B) DATA - (B) Not used Not used Not used

29 30 31 32 33 34 35 36

PLC or other device

DEIF A/S

COM

29 30 31 32 33 34 35 36

COM

29 30 31 32 33 34 35 36

COM

COM DATA - (B)

Connect shield to ground at one end only. Shield ends must be insulated with tape or insulation tubing. Use shielded twisted cable.

This solution is only feasible if the COM line is insulated. Check PLC/other device before connecting. A non-insulated COM line may result in damage to the equipment.

Page 45 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

Normally, the Modbus does not need bias resistors (end terminators). These are only needed in case of very long lines and/or many nodes (>32) on the Modbus network. If bias resistors are needed, the calculation should be based on the following data: A line internal pull-up bias resistor: B line internal pull-down bias resistor: Receiver input sensitivity: Receiver input impedance: 22 k 22 k +/-200 mV 12 k
2

Cable: Belden 3105 A or equivalent. 22 AWG (0.6 mm ) twisted pair, shielded, <40 m/m, min. 95% shield coverage.

DEIF A/S

Page 46 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

Modbus, RS232 (option H9.2) Connection to an external controller (PLC, PC, etc.) or a modem (GSM or RTC): Multi-line
GND RxD Gnd TxD RxD TxD

29 30 31 32 33 34 35 36 > H9.2 option

External controller or modem

Connect shield to earth at one end only. Shield ends must be insulated with tape or insulation tubing. This solution is only feasible if the COM line is insulated. Check PLC/other device before connecting. A non-insulated COM line may result in damage to the equipment. Cable: Belden 3106 A or equivalent. 22 AWG (0.6 mm ) shielded, <40 m/m, min. 95% shield coverage.
2

DEIF A/S

Page 47 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

Profibus DP (option H3) Connection with 2-wire screened cable (recommended): Multi-line
DATA + (B) DATA + (B) DATA - (A) DATA + (B) DATA - (A) Not used Not used Not used

Multi-line
DATA + (B) DATA + (B) DATA - (A) DATA - (A) Not used Not used Not used

Multi-line
DATA + (B) DATA + (B) DATA - (A) DATA - (A) Not used Not used Not used

29 30 31 32 33 34 35 36

PLC or other device

DEIF A/S

COM

29 30 31 32 33 34 35 36

COM

29 30 31 32 33 34 35 36

COM

COM DATA - (A)

Connect shield to ground at one end only. Shield ends must be insulated with tape or insulation tubing. Use shielded twisted cable.

Page 48 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

CANbus engine communication (option H5)

Multi-line CAN option H5


CAN-L R CAN-H GND

Engine Controller
CAN-H CAN-L GND

131 132 133

Connect shield to ground at one end only. Shield ends must be insulated with tape or insulation tubing. Use shielded twisted cable. End resistor R = 120 Ohm. The terminating resistor at the engine side might not be needed, please refer to the engine manufacturers literature.

DEIF A/S

Page 49 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

CANbus engine communication (option H7)


Multi-line CAN option H7
CAN-L R CAN-H GND

Engine Controller
CAN-H CAN-L GND

A3 A2 A1

Connect shield to ground at one end only. Shield ends must be insulated with tape or insulation tubing. Use shielded twisted cable. End resistor R = 120 Ohm. The terminating resistor at the engine side might not be needed, please refer to the engine manufacturers literature.

DEIF A/S

Page 50 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

Load sharing lines Screened, twisted cable is recommended to prevent disturbances on the load sharing lines.

Mechanical speed governor The illustration below shows the necessary connections to carry out speed control using relay outputs.

DEIF A/S

Page 51 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

In order to extend the lifetime of the internal relays and prevent unwanted switching noise, it is recommended to use free wheel diodes (1N4007), if a DC voltage is used for the regulation. If an AC voltage is used for the regulation, it is recommended to use a varistor. The diode/varistor must be placed across the terminals of the pilot motor/external regulation relay coil. AVR with relay outputs

DEIF A/S

Page 52 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

Electronic speed governor

If necessary, the current outputs can be converted to voltage using a resistor across the terminals (250 will convert the +/-20 mA into +/-5V DC). For further information on how to connect the analogue output to the most common speed governors please refer to: Application Notes, Interfacing DEIF equipment to governors and AVRs, document number 4189340149 at www.deif.com.

DEIF A/S

Page 53 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

AVR with analogue outputs

If necessary, the current outputs can be converted to voltage using a resistor across the terminals (250 will convert the +/-20 mA into +/-5V DC). For further information on how to connect the analogue output to the most common AVRs please refer to: Application Notes, Interfacing DEIF equipment to governors and AVRs, document number 4189340149 at www.deif.com.

DEIF A/S

Page 54 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

Digital inputs All digital inputs are 12/24V DC bi-directional optocoupler. Typical input is: 12/24V DC

0V DC

Digital inputs with wire break supervision (option M4) The digital inputs with wire break supervision only need potential free contacts.

The resistor value should be 270 +/-10%.

DEIF A/S

Page 55 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

Multi-functional inputs (option M4) If the predefined binary inputs with cable supervision are not used, they can be used for the following.

0(4)-20 mA Active transducer

+24V DC 0V DC

Passive transducer

+24V DC 0V DC

If the passive sensor has its own battery supply, the voltage must not exceed 30V DC.

DEIF A/S

Page 56 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

Pt100/Pt1000 2-wire 3-wire

VDO 1-wire 2-wire

DEIF A/S

Page 57 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

Magnetic pick-up (MPU) input (option M4) Magnetic pick-up (MPU)


ML-2

NPN sensor
ML-2

C = 22 nF, 100 V foil type R = 1200@24V DC, 600@12V DC PNP sensor


ML-2

C = 22 nF, 100 V foil type R = 1200@24V DC, 600@12V DC Charger, W output


ML-2

C = 22 nF, 100 V foil type

DEIF A/S

Page 58 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

Analogue inputs (option M15.x) The analogue 0(4)...20 mA inputs are passive and require an external power supply:
Inputs + Transmitter + 24V DC supply + -

or:
Inputs + + _ Transmitter 24V DC supply + -

Stop coil with wire break detection (option M4)


24V DC

ML-2

0V DC

To avoid faulty activation of the stop coil caused by the wire break circuit, use a stop coil with the following specifications: 24V DC: ION>10 mA/RCOIL<1650 12V DC: ION>10 mA/RCOIL<800 Remember to mount the free wheel diode.
DEIF A/S Page 59 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

Transistor outputs The open collector outputs can be used as kWh and kVArh counter outputs or as relay outputs. The outputs are low power outputs. For that reason one of the following circuits must be applied. External counter:
24V DC

Relay outputs:
24V DC

ML-2 0V DC

ML-2

0V DC

Connection to PLC:
24V DC

ML-2

0V DC

Remember to mount the free wheel diode. Max. load: 10 mA.


DEIF A/S Page 60 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

Additional display unit, DU-2 (option X2)

End resistor: 2 units connected: 3 units connected: Dip switch no. 1 has to be set to ON on both units. Dip switch no. 1 has to be set to ON on unit 1 and unit 3.

The maximum length of the CANbus line is 200 m. A DC/DC converter for the DC supply voltage and 2 x 1 m cable with an RJ45 plug in one end and stripped wires in the other end are included in the DU-2 (option X2) delivery.

DEIF A/S

Page 61 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

Additional operators panel, AOP-1 (option X3)

The maximum distance between the DU-2 and the AOP-1 is 0.5 m. The cable for connection between the AOP-1 and the DU-2 is included in the AOP-1 delivery.

DEIF A/S

Page 62 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

Additional operator's panel, AOP-2 (option X4)

It is recommended to keep a fair distance to power cables. A DC/DC converter for the DC supply voltage and 2 x 1 m cable with an RJ12 plug in one end and stripped wires in the other end are included in the AOP-2 delivery. The cable between the terminal blocks should be shielded twisted pair. The maximum length of the CANbus line is 200 m.

DEIF A/S

Page 63 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

8. General data
Technical specifications Accuracy: Class 1.0 Positive, negative and zero sequence alarms: Class 1 within 5% voltage unbalance Class 1.0 for negative sequence current Fast overcurrent: 3% of 350%*In Analogue outputs: Class 1.0 according to total range Option EF4: Class 4.0 according to total range To IEC/EN 60688 Operating temp.: -2570C (-13...158 F) (UL/cUL Listed: Max. surrounding air temp.: 55C/131F) -4070C (-40...158 F) 97% RH to IEC 60068-2-30 100-690V AC +/-20% (UL/cUL Listed: 480V AC phase-phase) Max. 0.25 VA/phase -/1 or -/5A AC (UL/cUL Listed: From CTs 1-5A) Max. 0.3 VA/phase

Storage temp.: Climate: Meas. voltage: Consumption: Meas. current: Consumption:

DEIF A/S

Page 64 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

Current overload:

4 x In continuously 20 x In, 10 sec. (max. 75 A) 80 x In, 1 sec. (max. 300 A) 3070 Hz Terminals 1 and 2: 12/24V DC (8...36 V continuously, 6 V 1 sec.) Max. 11 W consumption Terminals 98 and 99: 12/24V DC (8...36 V continuously, 6 V 1 sec.) Max. 5 W consumption The aux. supply inputs are to be protected by a 2 A slow-blow fuse (UL/cUL Listed: AWG 24)

Meas. frequency: Aux. supply:

Binary inputs:

Optocoupler, bi-directional ON: 836V DC Impedance: 4.7 k OFF: <2V DC 0(4)20 mA Impedance: 50 Not galvanically separated RPM (MPU): 270V AC, 1010000 Hz, 2503000

Analogue inputs:

Multi-inputs:

0(4)20 mA: 0-20 mA, +/-1% Not galvanically separated Binary: Max. resistance for ON detection: 100 Not galvanically separated Pt100/1000: -40250C, +/-1% Not galvanically separated To IEC/EN 60751

DEIF A/S

Page 65 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

VDO: 01700 , +/-2% Not galvanically separated V DC: 040V DC, +/-1% Not galvanically separated Relay outputs: Electrical rating: 250V AC/30V DC, 5 A (UL/cUL Listed: 250V AC/24V DC, 2 A resistive load) Thermal rating @ 50C: 2 A: Continuously 4 A: tON = 5 sec., tOFF = 15 sec. (Unit status output: 1 A) Open collector outputs: Supply: 836V DC, max. 10 mA

Analogue outputs: 0(4)...20 mA and +/-25 mA Galvanically separated Active output (internal supply) Load max. 500 (UL/cUL Listed: Max. 20 mA output) Update rate: Transducer output: 250 ms Regulator output: 100 ms Analogue load sharing lines: Galv. separation: -50+5V DC, Impedance: 23.5 k Between AC voltage, AC current and other I/Os: 3250V AC, 50 Hz, 1 min. Between analogue outputs and other I/Os: 500V DC, 1 min. Between binary input groups and other I/Os: 500V DC, 1 min.

DEIF A/S

Page 66 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

Response times: (Delay set to minimum) Busbar: Over-/undervoltage: < 50 ms Over-/underfrequency: < 50 ms Voltage unbalance: <200 ms Generator: Reverse power: Overcurrent: Fast overcurrent: Over-/undervoltage: Over-/underfrequency: Overload: Current unbalance: Voltage unbalance: React. power import: React. power export: Overspeed: Digital inputs: Emergency stop: Multi-inputs: Wire failure: Mains: df/dt (ROCOF): Vector jump: Positive sequence: Mounting: Safety: <200 ms <200 ms < 40 ms <200 ms <300 ms <200 ms <200 ms <200 ms <200 ms <200 ms <400 ms <250 ms <200 ms <800 ms <600 ms <130 ms (4 periods) < 40 ms < 60 ms DIN rail mount or base mount with 6 screws To EN 61010-1, installation category (overvoltage category) III, 600 V, pollution degree 2 To UL 508 and CSA 22.2 no. 14-05, overvoltage category III, 300 V, pollution degree 2

DEIF A/S

Page 67 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

EMC/CE:

To EN 61000-6-1/2/3/4 IEC 60255-26 IEC 60533 power distr. zone IACS UR E10 power distr. zone 313.2 Hz: 2 mmpp 13.2100 Hz: 0.7 g To IEC 60068-2-6 & IACS UR E10 1060 Hz: 0.15 mmpp 60150 Hz: 1 g To IEC 60255-21-1 Response (class 2) 10150 Hz: 2 g To IEC 60255-21-1 Endurance (class 2)

Vibration:

Shock (base mount):

10 g, 11 msec, half sine To IEC 60255-21-2 Response (class 2) 30 g, 11 msec, half sine To IEC 60255-21-2 Endurance (class 2) 50 g, 11 msec, half sine To IEC 60068-2-27

Bump: Material: Plug connections:

20 g, 16 msec, half sine To IEC 60255-21-2 (class 2) All plastic materials are self-extinguishing according to UL94 (V1) AC current: 2 0.2-4.0 mm stranded wire (UL/cUL Listed: AWG 18) AC voltage: 2 0.2-2.5 mm stranded wire (UL/cUL Listed: AWG 20) Relays: (UL/cUL Listed: AWG 22)

DEIF A/S

Page 68 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

Terminals 98-116: 2 0.2-1.5 mm stranded wire (UL/cUL Listed: AWG 24) Other: 2 0.2-2.5 mm stranded wire (UL/cUL Listed: AWG 24) Display: 9-pole Sub-D female Service port: USB A-B Protection: Unit: IP20 Display: IP52 (IP54 with gasket: Option L) (UL/cUL Listed: Type Complete Device, Open Type) To IEC/EN 60529 Governors: Multi-line 2 interfaces to all governors, including GAC, Barber-Colman, Woodward and Cummins See interfacing guide at www.deif.com Approvals: Marine approved by all major classification societies UL/cUL Listed to UL508 Wiring: Use 60/75C copper conductors only Mounting: For use on a flat surface of type 1 enclosure Installation: To be installed in accordance with the NEC (US) or the CEC (Canada)

UL markings:

DEIF A/S

Page 69 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

AOP-2:

Maximum ambient temperature: 60C Wiring: Use 60/75C copper conductors only Mounting: For use on a flat surface of type 3 (IP54) enclosure Main disconnect must be provided by installer Installation: To be installed in accordance with the NEC (US) or the CEC (Canada)

DC/DC converter for AOP-2:

Tightening torque: 0.5 Nm (4.4 lb-in) Wire size: AWG 22-14 1.6 kg (3.5 lbs.) 0.2 kg (0.4 lbs.) 0.4 kg (0.9 lbs.) 0.4 kg (0.9 lbs.)

Weight:

Base unit: Option J1/J3/J6: Option J2: Display:

DEIF A/S

Page 70 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

Dimensions Unit

Dimensions are given in mm (inches).

DEIF A/S

Page 71 of 72

GPC/GPU/GPU Hydro/PPU

Installation Instructions

Panel cutout

Dimensions are given in mm.

DEIF A/S reserves the right to change any of the above.