You are on page 1of 60

VoyagerTM II

Rooftop Units
Cooling-only TKD/TKH 155-175-200-250265-290-340
Heat pump WKD/WKH 125-155-200-265290-340
Gas-fired YKD/YKH 155-175-200-250

RT-PRC014-E4

2008Trane

RT-PRC014-E4

Contents
Features and Benefits

Options and Accessories

Selection Procedure

11

General Data

13

Performance Data

16

Cooling performances
Heating Performances
Hot water coil heating performances
Pressure Drops Through Accessories
Supply fan performances
Sound Levels

RT-PRC014-E4

16
29
35
38
39
48

Electrical Data

50

Dimensions and Weights

51

Controls

53

Mechanical Specifications

56

Features and Benefits


Figure 1 - High performance Scroll
compressor

The Micro requires no special tools to


run the unit through its paces. Simply
place a jumper between Test 1 and Test
2 terminals on the Low Voltage Terminal
Board and the unit will walk through its
operational steps automatically. The
unit automatically returns control to the
zone sensor after stepping through the
test mode a single time, even if the
jumper is left on the unit.
As long as the unit has power and the
LED is lit, the Micro is operational. The
light indicates that the Micro is
functioning properly.
The Micro features expanded
diagnostic capabilities when utilized
with Trane's Integrated Comfort
Systems.

Compressors
Voyager contains the best Scroll
compressor technology available, in
order to achieve the highest
performance possible. The Trane
Voyager rooftop has among the best
COP in its class. All performances are
Eurovent certified which provides the
assurance of accurate performance and
common comparison criteria
ReliaTel Micro Controls
The Micro provides unit control for
heating, cooling and ventilating
utilizing input from sensors that
measure outdoor and indoor
temperature.
The Micro improves quality and
reliability through the use of timetested
microprocessor controls and logic.

- prevents the unit from short


cycling, considerably improving
compressor life.
- ensures that the compressor will
run for a specific amount of time
which allows oil to return for
better lubrication, enhancing the
reliability of the compressor.
- reduces the number of
components required to operate
the unit, thereby reducing
possibilities for component
failure.

The Micro in the Voyager units has builtin anti-short-cycle timers, time delay
relays and minimum ''on'' time controls.
These controls are functions of the Micro
and are factory tested to assure proper
operation.
The Micro softens electrical ''spikes'' by
staging on fans, compressors and
heaters.
The Intelligent Fallback or Adaptive
Control is a benefit to the building
occupant. If a component goes astray,
the unit will continue to operate at
predetermined temperature set points.
Intelligent Anticipation is a standard
feature of the Micro. It functions
constantly as the Micro and zone
sensor work together in harmony to
provide tighter comfort control than
conventional electro-mechanical
thermostats.
Drum And Tube Heat Exchanger
The drum and tube heat exchanger is
designed for increased efficiency and
reliability and has utilized improved
technology incorporated in the large
rooftop commercial units for almost
20 years.

unique safety features.


The forced combustion blower supplies
a gas-air mixture through a single
stainless steel burner screen into a
sealed drum where ignition takes place.
It is more reliable to operate and
maintain than a multiple burner
system.
The hot surface ignitor is a gas ignition
device which doubles as a safety device
utilizing a continuous test to prove the
flame.
Weather Tight Top and Cabinet
Voyager units incorporate the TraneTite-Top (T3 ). Each part of the top
(three pieces) overlaps in such a way
that water cannot leak into the unit.
These overlapped edges are gasketed
and sealed to ensure superior water
integrity.
Quick- Access panels reduce the
number of possible water entry points.
For added water integrity, Voyager has
a raised 30 mm lip around the supply
and return of the downflow units to
prevent water from blowing into the
ductwork.
Quality And Reliability
The fan and idler arm assembly
designs have been tested to over
300,000 cycles each.
All of Voyager's designs were
rigorously rain tested at the factory to
ensure water integrity.
We perform a 100% coil leak test at the
factory. The evaporator and condenser
coils are leak tested at 1.4 MPa and
pressure tested to 3.1 MPa.
Every unit and its options receive a
100% unit run test before leaving the
production line to make sure it lives up
to Trane requirements.

The heat exchanger is manufactured


using aluminized steel with stainless
steel components for maximum
durability. The drum and tube design has
been tested and passed over
150,000 cycles.
The negative pressure gas valve will not
allow gas flow unless the combustion
blower is operating. This is one of our

RT-PRC014-E4

Features and Benefits


Figure 2 - Idler arm assembly

Ease Of Installation

Standardized Components

Voyager units provide many time and


money saving features.

Components are placed in the same


location for all Voyager units.

Conversionless Units

Easy Access Low Voltage Terminal


Board

The dedicated design units (either


downflow or horizontal) require no
panel removal or alteration time to
convert in the field.
Horizontal units come complete with
duct flanges so the contractor doesn't
have to field fabricate them.

Single Point Power

Improved Airflow

An Answer to Market
Needs

U-shaped airflow allows for improved


static capabilities.
Single Side Access
No more than three screws must be
removed to access components.
Trane's Idler Arm Assembly
On most units, our idler pulley provides
quick- adjustment for belt or motor
sheaves. No longer does one have to
adjust the motor to tighten the belt or
change the motor sheave setting.

Serviceability
Voyager's Simpler Design
The Voyager design uses up to 42%
fewer parts than previous units. Since it
is simpler in design, it is easier to
diagnose.
Micro

Figure 3 - RTRM (ReliaTel Refrigeration


Module)

The Micro requires no special tools to


run the Voyager unit through its paces.
Simply press the Test button located on
the right side of the control panel and
the unit will walk through its
operational steps automatically.
As long as the unit has power and the
LED is lit, the Micro is operational. The
light indicates that the Micro is
functioning properly.
The Micro features expanded
diagnostic capabilities when utilized
with Trane's Integrated Comfort TM
Systems.
One Zone Sensor option has central
control panel lights which indicate the
mode the unit is in and possible
diagnostic information (dirty filters for
example).

RT-PRC014-E4

The thermostat wires must be


connected to the terminals located on
the main board.

A single electrical connection powers


the unit.

Capacity Modulation
Voyager features dual Scroll
compressor units. The dual compressor
models are outstanding for humidity
control, light load cooling conditions
and system back-up applications.
Low Ambient Cooling
All Voyager units have cooling
capabilities down to -18C as standard.
Flexible Applications
Thanks to its high static pressure
capabilities, the Voyager can replace an
older machine with old ductwork and,
in some cases, improve the comfort
through better air distribution.
Indoor Air Quality
Filters - all rooftops are shipped with
throwaway filters to be used during the
first days of operation (usually the job
site is not completely clean, and high
efficiency filters would get dirty in a few
hours - this would be a waste of
money) or G4/EU4 filters for regular
operation.
Panels in the indoor air section have a
fire-resistant (MO) aluminum foil-faced
insulation. There is no more insulation
paticules carried in the air. It can be
cleaned which is paricuarly interesting
for restaurant applications.
All our drain pans are sloped. We thus
avoid water stagnation that engenders
corrosion and micro-organism life such
as mold and fungi.

Features and Benefits


Figure x - RTOM (ReliaTel Option
Module)

Micro Benefits
The Micro in the Voyager units has
built-in anti-short-cycle timers, time
delay relays and minimum ''on'' time
controls. These controls are functions of
the Micro and are factory tested to
assure proper operation.
The Micro softens electrical ''spikes'' by
staging on fans, compressors and
heaters.
The Intelligent Fallback or Adaptive
Control is a benefit to the building
occupant. If a component goes astray,
the unit will continue to operate at
predetermined temperature set points.

Figure 4 - Trane Communication Interface


(TCI-R)

Intelligent Anticipation is a standard


feature of the Micro. It functions
constantly as the Micro and zone
sensor work together in harmony to
provide tighter comfort control than
conventional electro-mechanical
thermostats.
Downflow And Horizontal Economizers
Economizers come with a comparative
enthalpy control.
Trane Communication Interface or TCI-R
is available factory installed. This module
when applied with the Micro easily
interfaces with Trane's Integrated
Comfort TM System.
Lon Communication Interface (LCI)
This is an electronic board mounted on
the main control panel. It is needed to
allow communication on a LonTalk
Network at the unit level.
Numerous options and accessories are
available, such as:
- Adjustable roof curb
- Economizer
- Electric heater
- Hot water coil
- Black epoxy fin coating
- CO2 sensor
- Fused disconnect switch
- Smoke detector
- Firestat
- Supply fan soft starter

RT-PRC014-E4

Options and Accessories


TKD

TKH

WKD

WKH

YKD

YKH

Application

Description

Fresh air needed in the


building, up to 25% of the
nominal airflow.

Manually sets a permanent amount of fresh air in the


unit, between 0-25% of the nominal airflow.

Incompatible with

FRESH AIR OPTIONS


0-25% manual fresh air
hood

0-50% motorized fresh


air hood

Economizer comparative
enthalpy control

Remote potentiometer

CO2 sensor

The economizer is composed of 2 sets of


0-25% manual hood,
temperature and humidity sensors that measure
0-50% motorized
ambient and room enthalpy, and of a fresh air damper hood.
connected to a return air damper. The permanent
fresh air function is identical to that of the 0-50%
motorized hood. The free-cooling function modulates
between the permanent set value (between 0-50%)
and 100% of the nominal airflow using the fresh air
enthalpy to cool down the building.

To remotely set the


permanent fresh air intake.

Connected to the potentiometer of the 0-50%


motorized hood or of the economizer, can modify
remotely the permanent fresh air amount brought
into the unit between 0-50% of the nominal airflow.

0-25% manual fresh


air hood, not
recommended with
CO2 sensor.

Hygienic control of the air.

Works with the 0-50% motorized hood or the


economizer and brings fresh air (modulating between
the permanent fresh air setpoint and 50% of the
nominal airflow) whenever the CO2 concentration in
the room meets or exceeds the adjustable threshold.
The sensor itself has to be mounted in a relevant
place in the room or in the ductwork.

0-25% manual hood,


not recommended
with remote
potentiometer.

To minimize overpressure in
the building caused by the
introduction of fresh air, when
the economizer fresh air
damper set at 40-50% OA
(permanent value), and/or
when the pressure drop in the
return duct is between the
building overpressure
accepted by the customer (1225 Pa) and 200 Pa (maximum
fan static pressure).

When the exhaust fans are off, the gravity dampers


open with increased building pressure to relieve the
air pressure. When the exhaust fans are on, around
50% of airflow can be exhausted, depending on the
pressure drop of the return.They turn on whenever
the position of the economizer fresh air dampers
meet or exceed the power exhaust setpoint (when
the supply fan is on).

0-50% motorized
fresh air damper

Fresh air needed in the


building, up to 50% of
nominal airflow, and
intelligent energy saving.
O

Exhaust fans

Fresh air needed in the


building, up to 50% of
nominal airflow.

Economizer, 0-50%
motorized hood, CO2
sensor, remote
potentiometer.
A motorized fresh air damper introduces a permanent 0-25% manual hood,
economizer.
amount of fresh air into the unit, between 0-50% of
the nominal airflow. The damper position is set by a
potentiometer located in the hood. Closes in
unoccupied mode when supply fan stops.

HEATING DEVICES

Hot water coil

Electric heaters

Need of heating or additional Avoids the power consumption of an electric heater


heating on cooling only units
by using the hot water loop available to heat the
or heat pump units. Hot water building.
loop available on site.
Need of heating or additional
heating on cooling only units
or heat pump units. Very
useful with a heat pump unit
to keep a good comfort level
during the defrost cycle.

Electric heaters, gas


fired units.

On a heat pump unit, in heating mode, turns on when Hot water coil, gas
the compressors job does not raise the temperature fired units.
fast enough. On a heat pump, in heating mode,
during the outdoor coil defrost cycle, the electric
heater turns on to avoid blowing cold air in the
building.

A = Accessory (to be mounted on site)


O = Option (factory mounted and tested)
Other options or configurations are available. Please contact your local sales office for more information.

RT-PRC014-E4

Options and Accessories


TKD

TKH

WKD

WKH

YKD

YKH

EU4 filters

Clogged filter detector

Soft starter

Application

Description

To filter the air.

Washable media, treat the return and fresh air, 90%


gravimetrical efficiency.

To facilitate maintenance of
the filters.

When the pressure drop of the filter exceeds the


selectable value, this differential pressostat report an
alarm via a dry contact to the micro-control.

Incompatible with

VENTILATION

To achieve a progressive
Located in the main control pannel. Starting time can
supply fan start and a reduced be adjusted from an actual range of 0 to 40 seconds
starting current.
(factory-set value: 40 s).

SAFETY

Fused disconnect switch

Fire thermostat

Smoke detector

High temperature safety


thermostat

To manually disconnect the


unit from the power supply
line and protect it from
internal short circuits

Cuts the 3 phases of the power supply, the fuses


blow up in case of short circuit into the unit. Cannot
be ordered with electric heaters because in that case
the unit is already fused

To stop the unit when


temperature of the air stream
rises abnormally.

A kit of 2 manual reset thermostats are delivered. The


first one, to be placed in the return duct, stops the
unit and put the unit in general fault when the
airstream rises above 57C, the second, to be placed
in the supply duct, reacts above 115C. Temperature
threshold cannot be changed.

Smoke detector.

To detect smoke in the


building.

Closes the return air damper if an economizer is


installed, stops the indoor fan, switches off the
electric heater if installed and energized, and put the
unit in general fault.

Fire thermostat.

For the French ERP regulation


only : additional security
thermostat for gas-fired units.

This manual reset thermostat switches off the burner


and the supply fan, and put the unit in general fault if
the supply temperature rises above 120C.

Connection between a flat


roof and the rooftop.

Supports the rooftop and ensures watertightness


roof/roofcurb/rooftop, and easy connection of the
ductwork .

Adjustable roofcurb.

Connection between a sloped


roof and the rooftop.

Supports the rooftop and ensures watertightness


roof/roofcurb/rooftop, and easy connection of the
ductwork, correcting up to 8% slope.

Standard roofcurb.

Connection between a
roofcurb and a rooftop unit
installed on a roof. Used to
comply to the French ERP
(Etablissement Recevant du
Public: Buildings open to the
public) regulations.

Avoids contact between the rooftop and the roof.


Openings on the sides allow natural ventilation.
Protection of the building in case of failure of the
rooftop causing overheating / fire.

Standard roofcurb

Adjustable roofcurb

ROOFCURBS

Ventilated roofcurb
extension (French ERP
regulations)

A = Accessory (to be mounted on site)


O = Option (factory mounted and tested)
Other options or configurations are available. Please contact your local sales office for more information.

RT-PRC014-E4

Options and Accessories


TKD

TKH

WKD

WKH

YKD

YKH

Application

Description

Incompatible with

CONTROL

ReliatelTM Options
Module
(RTOM)

TCI-R

LCI-R

THS01

THS02

Required for some optional


Communication interface between the ReliaTelTM
ReliaTelTM devices (frostat,
Refrigeration Module (RTRM) and some options.
clogged filter switch, fan
failure switch, discharge air
sensor (DAS) used for supply
air tempering and ICS input
data, smoke detector, external
on/off switch).

To communicate with Trane


Integrated Comfort Systems,
such as the Tracer SummitTM,
the TrackerTM or a VaritracTM
system (CCP2).

THP01

THS01-02-03/THP0103, remote sensors


for THS01-02/THP01,
LCI-R

To communicate on a LonTalk Communication interface between a LonTalk device


and a VoyagerTM.
network at the unit level.

THS01-02-03/
THP01-03, remote
sensors for THS0102/THP01, TCI-R

Control of 1 cooling-only / gas- Electronic thermostat, 2 stages cooling, 2 stages


fired rooftop.
auxiliary heating, LCD screen.

TCI-R, LCI-R

Control of 1 heat pump


rooftop .

Electronic thermostat, 2 stages cooling, 1 stage


compressor heating, 1 stage auxiliary heating, LCD
screen.

TCI-R, LCI-R,
WK*265-290-340

Control of 1 cooling-only, heat


pump or gas-fired rooftop.

Electronic thermostat, 2 stages cooling, 1 stage


compressor heating, 2 stages auxiliary heating. No
CTI card needed, communicates in the same
language as the rooftop micro-control and uses 100%
of its advanced control features

TCI-R, LCI-R

THS03

Communication interface between a Trane ICS device


and a VoyagerTM.

Control of 1 cooling-only / gas- Electronic programmable thermostat, 2 stages


fired rooftop.
cooling, 2 stages auxiliary heating, LCD screen.

TCI-R, LCI-R

Control of 1 cooling-only, heat


pump or gas-fired rooftop.

TCI-R, LCI-R

THP03

Electronic programmable thermostat, 2 stages


cooling, 1 stage compressor heating, 2 stages
auxiliary heating, LCD screen. Communicates in the
same language as the rooftop micro-control and uses
100% of its advanced control features.

Remote sensor box for


THS01-02/THP01

Need for remote or additional Senses the temperature and sends the information to
sensors with THS01-02/THP01. the THS01-02 THP01.

THS/P 03, TCI-R,


LCI-R

Remote sensor box for


THS/THP03

Need of remote or additional


sensors with THS/THP03

Senses the temperature and sends the information to


the THS/P 03.

THS01-02/THP01.

Additional device to prevent


the indoor coil from icing. Very
useful when a large amount of
cold air is blown into the unit
during the cooling mode.

A sensor is placed on the indoor coil and stops the


compressors for the period of time needed, as soon
as the coil approaches the freezing point (in cooling
mode).

To send alarms signals to a


local BMS.

Uses the compressor/heating/fan/power supply alarm


output signals from the micro-control and reports
them into one dry contact.

Antifreeze thermostat

Remote fault relay

A = Accessory (to be mounted on site)


O = Option (factory mounted and tested)
Other options or configurations are available. Please contact your local sales office for more information.

RT-PRC014-E4

Options and Accessories


TKD

TKH

WKD

WKH

YKD

YKH

Oversized drive / motor

Black epoxy coating on


condenser

Black epoxy coating on


condenser and
evaporator

Application

Description

Incompatible with

MISCELLANEOUS
High static pressure needs.

Increases the fans speed via oversized pulleys/belts


and/or oversized motors.

Sea side application.

The black epoxy coating slows down the corrosion


process on the aluminum fins.

Sea side application when a


fresh air device is used.

The black epoxy coating slows down the corrosion


process on the aluminum fins.

A = Accessory (to be mounted on site)


O = Option (factory mounted and tested)
Other options or configurations are available. Please contact your local sales office for more information.

10

RT-PRC014-E4

Selection Procedure
Cooling capacity
Step 1 - Calculate the building's total and
sensible cooling loads at design
conditions.
Example: The following are the building
cooling requirements:
Electrical characteristics: 400/50/3
Summer design conditions: Room
return air at 25C/50%, outdoor ambient
35C/35%
Total cooling load: 42.3 kW
Sensible cooling load: 30.0 kW
Airflow: 8500 m3/h
Fresh air percentage 20%
External static pressure: 176 Pa
Downflow configuration, heat pump
unit
Options - Economizer, Electric heater,
EU4 filters
Step 2 - Calculate the entering air
conditions on the indoor coil. It is the
mixture of 20% outside ambient air at
35C/35% and 80% room return air at
25C/50%. On the psychrometric chart,
Figure 5, point A represents the room
return condition, and point B the outside
ambient air condition. Draw a line
between point A and point B. The
resulting condition of the mixture will be
on this line, between point A and point B
and will be called point C. Find the dry
bulb temperature of the air mixture with
the following calculation :

To find capacities at intermediate


conditions not in the table
When design conditions are between
two numbers, interpolation is required.
Extrapolation outside the table
conditions is not recommended.
Step 4 - To determine the net cooling
capacity, fan motor heat must be
deducted from the gross cooling
capacity. To determine the total unit
static pressure:
External static pressure: 187 Pa
G4/EU4 filter: 34 Pa
Economizer: 12 Pa
Supplementary electric heat: 11 Pa
Total static pressure = 244 Pa
Notes: Pressure drop values are
interpolated. The evaporator fan
performance tables has deducted the
pressure drop for a filter already in the
downflow unit.
Therefore, the actual total static pressure
in 244-19=225 Pa. With 8500 m3/h and 225
Pa, Table 36 shows 1.63 kW.
The formula below can be used to
calculate Fan Motor Heat:

Outoor ambient air : 0.2 x 35 = 7

Fan Motor Heat = 1.375 x kW = kW

Room return air :0.8 x 25 = 20

1.375 x 1.63 kW = 2.2 kW

Final temp of mixture = 20 + 7 = 27C

Net Total Cooling Capacity = 46.9-2.2


=44.7 kW

In Figure 5, point C, representing the


resulting condition of the mixture, is
located on line AB at the point where it is
crossed be the vertical line of 27C. the
wet bulb temperature of the mixture is
19C. We have just found at that entering
indoor coil condition is 27C DB/19C WB.

RT-PRC014-E4

Step 3 - Size the equipment using


General Data tables. Match the cooling
loads at design conditions. Table 9 shows
that a WKD 155 has a gross cooling
capacity of 46.9 kW and 32.8 kW sensible
capacity at 8500 m3/h and 35C DB
outdoor ambient with 27C DB, 19C WB
air entering the evaporator.

Net Sensible Cooling Capacity = 32.8-2.2


= 30.6 kW
Step 5 - If the performance will not meet
the required load of the building, try a
selection at the next higher size unit.

11

Selection Procedure
Figure 5
30

25
60%
19

50%

20

40%
30%
B

C
15
A
10

10

15

20

25

27

30

35

40

Heating capacity

Air delivery selection

Step 1 - Calculate the building heating


load.

External static pressure drop through the


air distribution system has been
calculated to be 225 Pa.

Step 2 - Size the equipment using the


General Data tables to match the heating
loads at design conditions.
Total heating load: 39.5 kW
Outdoor Ambient (Winter): -8C DB

Enter Table 36 for a WKD 155 at


8500 m3/h and 225 Pa static pressure.
The oversized motor and drive at
780 RPM will give the desired airflow at
a rating of 1.63 kW

Room Return Temperature: 22C DB


Airflow: 8500 m3/h
Fresh air percentage: 20%
Resulting air mixture entering on the
indoor coil: 16C DB
Use Table 15 for WKD 155 to determine
capacity at winter design conditions. The
mechanical heating portion of the heat
pump will provide 25.2 kW.
Step 3 - Because 25.2 kW is less than the
building's required heating capacity at
winter design conditions, a
supplementary heater must be selected.
39.5 kW - 25.2 kW = 14.3 kW
The optional electric heater provides
25 kW and will be adequate to do the
job.

12

RT-PRC014-E4

General Data
Table 1 - General data TKD/TKH

Eurovent Performances (1)


Net Cooling Capacity
Total Power input in cooling
EER
Main Power supply
Outdoor sound power level env.
Indoor sound power level in duct
Outdoor sound pressure level env. (6)
Unit start-up amps
Unit rated amps (3)
Electric Heater
Heating Capacity
Capacity steps
Rated Amps
Compressor
Number/Type
Model
Rated Amps (1)
Locked rotor Amps (2)
Outdoor Coil
Type
Tube Size OD
Face Area
Rows / Fin series
Indoor Coil
Type
Tube Size OD
Face Area
Rows / Fin series
Refrigerant Control
Drain Connection No./Size
Outdoor Fan
Nominal Airflow
Type
Diameter
Drive type
Number
Motor HP
Motor Rated Amps (1)
Motor RPM
Indoor Fan
Nominal Airflow
Static pressure available (4)
Maximum static pressure available (5)
Type
Diameter / Width
Drive type
Number
Motor HP (Standard/Oversized)
Motor Rated Amps (Standard/Oversized)
Motor Locked rotor Amps (Standard/Oversized)
Motor RPM (Standard/Oversized)
Filters
Type Furnished
Operating limits
Minimum operating outdoor air temp.
Maximum operating outdoor air temp.
Minimum intake air temp. on the indoor coil
Dimensions (3)
Height
Length
Width
Operating Weight
Shipping Weight (TKD / TKH)
Unit construction
Sheet metal / Thickness
Paint
Insulation / Thickness
System Data
Number of refrigerant circuits
Capacity steps
Refrigerant Charge (3)
Circuit A (TKD / TKH)
Circuit B (TKD / TKH)

TKD - Cooling-only, downflow. TKH - Cooling-only, horizontal flow


TKD/H 265
Standard
R407C
72.9
24.6
2.96

TKD/H 290
Standard
R407C
87.5
32.8
2.67

TKD/H 340
Standard
R407C
94.9
37.1
2.56

89
77
57
146
42.6

TKD/H 250
Standard
R407C
62
20.7
3.00
400/3/50
90
82
58
147
43.8

88
83
56
157
62.9

90
83
58
237
82.0

90
85
58
240
84.6

25
12.5 / 12.5
36

37.5
25 / 12.5
54

37.5
25 / 12.5
54

37.5
25 / 12.5
54

37.5
25 / 12.5
54

37.5
25 / 12.5
54

9T / 5T
15.0 / 8.5
118 / 65.5

10T / 6.7T
15.1 / 11.4
118 / 101

9T / 9T
14.7 / 14.7
118 / 118

2/Scroll
10T / 10T
15.3 / 15.3
118 / 118

12T / 12T
22.0 / 22.0
118 / 118

15T / 15T
28.0 / 28.0
185 / 185

15T / 15T
28.0 / 28.0
185 / 185

(mm)
(m)
# / FPF

9.52
2.23
2 / 192

9.52
2.62
2 / 192

9.52
3
2 / 192

Wavy
9.52
3.39
2 / 192

9.52
3.58
2 / 192

9.52
3.58
2 / 192

9.52
3.58
2 / 192

(mm)
(m)
# / FPF

9.52
1.63
2 / 180

9.52
1.63
2 / 180

Wavy
9.52
9.52
2.42
2.42
2 / 180
2 / 180
Fixed Orifice'

9.52
2.42
3 / 180

9.52
2.42
3 / 180

(kW)
(kW)
V/Ph/Hz
(dBA)
(dBA)
(dBA)
(A)
(A)
(kW)
(kW)
(A)

TKD/H 155
Standard
R407C
42.4
14.5
2.92

TKD/H 175
Standard
R407C
48.1
17.6
2.73

TKD/H 200
Standard
R407C
57.8
21.1
2.74

86
74
54
136
33.1

86
77
54
143
40.1

25
12.5 / 12.5
36

#
(A)
(A)

(mm)

1 / 3/4" NPT

1 / 3/4" NPT

1 / 3/4" NPT

1 / 3/4" NPT

1 / 3/4" NPT

1 / 3/4" NPT

9.52
2.42
4 / 168
Expansion
Valve
1 / 3/4" NPT

(m3/h)

15350

19750

21000

28000

38000

38000

(mm)

660

660

660

710

710

710

#
(kW)
(A)
(rpm)

2
0.37
1.6
925

2
0.56
2.3
950

2
0.8
2.1
900

23500
Axial
710
Direct
2
0.8
2.1
900

2
1.1
2.5
915

3
1.1
2.5
915

3
1.1
2.5
915

(m3/h)
(Pa)
(Pa)

8500
175
325

9850
250
400

11210
200
375

16200
450
500

18000
450
500

(in / in)

15" / 15"

15" / 15"

18" / 18"

18" / 18"

18" / 18"

1
2.2 / 3.0
4.0 / 6.4
36.4 / 57
1450 / 2870

1
3.0 / 4.6
6.4 / 9.0
57 / 71.9
2870 / 2900

1
3.0 / 4.6
6.4 / 9.0
57 / 71.9
2870 / 2900

1
7.5 / 9
14.5 / 17.3
128 / 149
2900 / 2900

1
7.5 / 9
14.7 / 17.3
128 / 149
2900 / 2900

-18
46
18

-18
46
18

-18
46
18

-18
46
18

-18
46
18

-18
46
18

-18
46
18

1273
2726
1811
623
662 / 677

1273
2726
1811
660
680 / 695

1372
3107
2154
841
872 / 892

1372
3107
2154
866
921 / 941

1704
3107
2154
857
922

1704
3987
2154
1060
1125

1704
3987
2154
1086
1151

#
(kW)
(A)
(A)
(rpm)

2" Throwaway
C
C
C
(mm)
(mm)
(mm)
(kg)
(kg)
Type / mm
Type / RAL
Type / mm
#
%
(kg)
(kg)

GalvaSteel/ 1.2l
Polyester / 9002
M0 / 25
2
60 / 40

2
70 / 30

2
50 / 50

2
50 / 50

2
50 / 50

2
50 / 50

2
50 / 50

3.1
4.9

4.0
6.0

5.9
5.9

7.2
7.2

7.5
7.5

8.5
8.5

9.7
9.7

(1) At Eurovent rating conditions : Indoor return Air (27C DB / 19C WB) - Ambiant 35C
(2) Per motor
(3) For standard unit, without options
Also available with R22 refrigerant. For information, contact your local sales office.

RT-PRC014-E4

14100
14400
125
75
350
375
FC Centrifugal
18" / 18"
18" / 18"
Belt
1
1
4.6 / 4.6 / 5.5
9/9.0 / 10.5
71.9 / 69 / 95
2900 / 2900 / 2900

(4) At the nominal airflow with standard drive


(5) At the nominal airflow with oversized drive when available
(6) At 10m from the unit in a free field

13

General Data
Table 2 - General data WKD/WKH.

WKD - Heat pump, downflow. WKH - heat pump, horizontal flow

Eurovent Performances (1)


Net Cooling Capacity
Total Power input in cooling
EER
Main Power supply
Outdoor sound power level env.
Indoor sound power level in duct
Net Heating Capacity
Total Power input in Heating
COP
Outdoor sound pressure level env. (6)
Unit start-up amps
Unit rated amps (3)
Electric Heater
Heating Capacity
Capacity steps
Rated Amps
Compressor
Number/type
Model
Rated Amps (1)
Locked rotor Amps (2)
Outdoor Coil
Type
Tube Size OD
Face Area
Rows / Fin series
Refrigerant Control
Indoor Coil
Type
Tube Size OD
Face Area (WKD / WKH)
Rows / Fin series
Refrigerant Control
Drain Connection No./Size
Outdoor Fan
Nominal Airflow
Type
Diameter
Drive type
Number
Motor HP
Motor Rated Amps (1)
Motor RPM
Indoor Fan
Nominal Airflow
Static pressure available (4)
Maximum static pressure available (5)
Type
Diameter / Width
Drive type
Number
Motor HP (Standard/Oversized)
Motor Rated Amps (Standard/Oversized)
Motor Locked rotor Amps (Standard/Oversized)
Motor RPM (Standard/Oversized)
Filters
Type Furnished
Operating limits
Minimum operating outdoor air temp. (Cooling)
Minimum operating outdoor air temp. (Heating)
Maximum operating outdoor air temp. (Cooling)
Maximum operating outdoor air temp. (Heating)
Minimum intake air temp. on the indoor coil (Cooling)
Minimum intake air temp. on the indoor coil (Heating)
Dimensions (3)
Height
Length
Width
Operating Weight
Shipping Weight (WKD / WKH)
Unit construction
Sheet metal / Thickness
Paint
Insulation / Thickness
System Data
Refrigerant circuit
Capacity steps (Cooling)
Capacity steps (Heating)
Refrigerant Charge (3)
Circuit A (WKD / WKH)
Circuit B (WKD / WKH)

WKD/H 125
Standard
R407C

WKD/H 155
Standard
R407C

WKD/H 200
Standard
R407C

WKD/H 265
Standard
R407C

WKD/H 290
Standard
R407C

WKD/H 340
Standard
R407C

36.3
12.5
2.90

44.8
15.5
2.89

60.2
22.2
2.71

68.3
25.7
2.66

82.9
34.1
2.43

90.8
37.7
2.41

(dBA)
(A)
(A)

85
79
34.4
10.1
3.41
54
94
29.6

86
74
40.8
12.0
3.40
54
101
33.7

90
81
59.8
17.9
3.34
58
129
47.7

88
83
63.4
19.6
3.23
55
157
62.9

90
83
80.8
27.7
2.92
56
237
82.0

90
85
81.5
28.3
2.88
56
240
84.6

(kW)
(kW)
(A)

25
12.5 / 12.5
36

25
12.5 / 12.5
36

37.5
25 / 12.5
54

37.5
25 / 12.5
54

37.5
25 / 12.5
54

37.5
25 / 12.5
54

(A)
(A)

6T / 6T
10.0 / 10.0
74 / 74

7.5T / 7.5T
12.1 / 12.1
79 / 79

10T / 10T
17.5 / 17.5
98 / 98

12T / 12T
22.0 / 22.0
118 / 118

15T / 15T
28.0 / 28.0
185 / 185

15T / 15T
28.0 / 28.0
185 / 185

9.52
2.23
2 / 192

9.52
2.62
2 / 192

9.52
3.39
2 / 192

9.52
3.58
2 / 192

9.52
3.58
2 / 192

9.52
3.58
2 / 192

(kW)
(kW)
V/Ph/Hz
(dBA)
(dBA)
(kW)
(kW)

400/3/50

2/Scroll

Wavy
(mm)
(m)
# / FPF

Exp.Valve
Wavy
(mm)
(m)
# / FPF

9.52
1.47 / 1.63
3 / 180

9.52
1.63
2 / 180

9.52
2.42
3 / 180
Fixed Orifice

9.52
2.42
3 / 180

9.52
2.42
3 / 180

(mm)

1 / 3/4" NPT

1 / 3/4" NPT

1 / 3/4" NPT

1 / 3/4" NPT

1 / 3/4" NPT

9.52
2.42
4 / 168
Expansion
Valve
1 / 3/4" NPT

(m3/h)

#
(kW)
(A)
(rpm)

15300
Axial
660
Direct
2
0.37
1.6
925

15850
Axial
660
Direct
2
0.37
1.6
925

23600
Axial
710
Direct
2
0.8
2.1
900

28000
Axial
710
Direct
2
1.1
2.5
915

38000
Axial
710
Direct
3
1.1
2.5
915

38000
Axial
710
Direct
3
1.1
2.5
915

(m3/h)
(Pa)
(Pa)

7140
200
425

8500
175
325

16200
450
500

18000
450
500

(in / in)

15" / 15"

15" / 15"

18" / 18"

18" / 18"

1
2.2 / 3.0
4.0 / 6.4
36.4 / 57
1450 / 2870

1
2.2 / 3.0
4.0 / 6.4
36.4 / 57
1450 / 2870

1
7.5 / 9
14.5 / 17.3
128 / 149
2900 / 2900

1
7.5 / 9
14.7 / 17.3
128 / 149
2900 / 2900

-18
-14
46
18
18
10

-18
-14
46
18
18
10

-18
-14
46
18
18
10

-18
-14
46
18
18
10

-18
-14
46
18
18
10

-18
-14
46
18
18
10

1273
2726
1811
625
658 / 673

1273
2726
1811
642
680 / 695

1372
3107
2154
871
922 / 942

1704
3107
2154
877
942

1704
3987
2154
1080
1145

1704
3987
2154
1106
1171

(mm)

#
(kW)
(A)
(A)
(rpm)

2" Throwaway
C
C
C
C
C
C
(mm)
(mm)
(mm)
(kg)
(kg)
Type / mm
Type / RAL
Type / mm
#
%
%
(kg)
(kg)

GalvaSteel / 1.2
Polyester / 9002
M0 / 12.5
2
50 / 50
100

2
50 / 50
100

2
50 / 50
100

2
50 / 50
50 / 50

2
50 / 50
50 / 50

2
50 / 50
50 / 50

5.2
5.4

5.9
5.9

9.0
9.0

8.6
8.6

8.6
8.6

11.5
11.5

(1) At Eurovent rating conditions : Indoor return Air (27C DB / 19C WB) - Ambiant 35C
(2) per motor
(3) For standard unit, with oversized drive, without electric heater options

14

11210
14400
200
75
350
375
FC Centrifugal
18" / 18"
18" / 18"
Belt
1
1
3.0 / 4.6
4.6 / 5.5
6.4 / 9.0
9.0 / 10.5
57 / 71.9
69 / 95
2870 / 2900
2900 / 2900

(4) At the nominal airflow with standard drive


(5) At the nominal airflow with oversized drive when available
(6) At 10m from the unit in a free field

RT-PRC014-E4

General Data
Table 3 - General data YKD/YKH. YKD - Gas-fired, downflow. YKH - Gas-fired, horizontal flow

Eurovent Performances (1)


Net Cooling Capacity
Total Power input in cooling
EER
Main Power Supply
Outdoor Sound Power Level in Free Field
Indoor Sound Power Level in Duct
Outdoor sound pressure level env. (6)
Unit start-up amps
Unit rated amps (3)
Gas burner
Heating Models
Heating Input (G20)
Heating Output
Steady State Efficiency
Number of Burners
Number of Stages
Gas Connection Pipe Size
Compressor
Number/Type
Model
Rated Amps (1)
Locked Rotor Amps (2)
Outdoor Coil
Type
Tube Size OD
Face Area
Rows / Fin series
Indoor Coil
Type
Tube Size OD
Face Area
Rows / Fin series
Refrigerant Control
Drain Connection Number/Size
Outdoor Fan
Nominal Airflow
Type
Diameter
Drive type
Number / Voltage
Motor HP
Motor Rated Amps (1)
Motor Locked rotor Amps (2)
Motor RPM
Indoor Fan
Nominal Airflow
Static pressure available (4)
Maximum static pressure available (5)
Type
Diameter / Width
Drive type
Number
Motor HP (Standard/Oversized)
Motor Rated Amps (Standard/Oversized)
Motor Locked rotor Amps (Standard/Oversized)
Motor RPM (Standard/Oversized)
Filters
Type Furnished
Operating limits
Minimum operating outdoor air temp.
Maximum operating outdoor air temp.
Minimum intake air temp. on the indoor coil (Cooling)
Minimum intake air temp. on the indoor coil (Heating)
Dimensions (3)
Height
Length
Width
Operating Weight
Shipping Weight (YKD / YKH)
Unit construction
Sheet metal / Thickness
Paint
Insulation / Thickness
System Data
Number of Refrigerant Circuits
Capacity Steps
Refrigerant Charge (3)
Circuit A (YKD / YKH)
Circuit B (YKD / YKH)

YKD/H 155
Standard
R407C

YKD/H 175
Standard
R407C

YKD/H 200
Standard
R407C

YKD/H 250
Standard
R407C

42.3
14.4
2.94

48.0
17.6
2.73

57.5
21.1
2.73

62.0
20.7
3.00

86
74
54
136
33.1

86
77
54
143
40.1

89
77
57
146
42.6

90
82
58
147
43.8

(inches)

G350
77
69.3
90
1
2
3/4" NPT

G350
77
69.3
90
1
2
3/4" NPT

G350
77
69.3
90
1
2
3/4" NPT

G350
77
69.3
90
1
2
3/4" NPT

(A)
(A)

9T / 5T
15 .0/ 8.5
118 / 65.5

10T / 6.7T
15.1/11.4
118 / 101

9T / 9T
14.7 / 14.7
118 / 118

10T / 10T
15.3 / 15.3
118 / 118

(mm)
(m)
(Number / FPF)

9.52
2.23
2 / 192

9.52
2.62
2 / 192

9.52
3.00
2 / 192

9.52
3.39
2 / 192

(mm)
(m)
(Number / FPF)

9.52
1.63
2 / 180

9.52
1.63
2 / 180

9.52
2.42
2 / 180

9.52
2.42
2 / 180

1 / 3/4" NPT

1 / 3/4" NPT

21000

23500

660

710

(kW)
(kW)
(V/Ph/Hz)
(dB(A))
(dB(A))
(dBA)
(A)
(A)

400/3/50

(kW)
(kW)
(%)

2/Scroll

Wavy

Wavy

1 / 3/4" NPT

(m3/h)

15350

19750

(mm)

660

660

Axial
Direct
(kW)
(A)
(A)
(rpm)

2
0.37
1.6
3.8
925

2
0.56
2.3
5.8
925

2
0.80
2.1
5.8
900

2
0.80
2.1
5.8
900

(m3/h)
(Pa)
(Pa

8500
150
350

9850
75
375

11210
175
450

14100
75
375

15" / 15"

15" / 15"

18" / 18"

18" / 18"

1
2.2/3.0
4.6 / 6.4
36.4 / 57
1450 / 2870

1
3.0/4.6
6.4/9.0
57.0 / 71.9
2870 / 2900

1
3.0/4.6
6.4/9.0
57.0 / 71.9
2870 / 2900

1
4.6/9.0/71.9 / 2900 / -

-18
46
18
5

-18
46
18
5

-18
46
18
5

-18
46
18
5

1273
2726
1811
698
685 / 700

1273
2726
1811
735
740 / 755

1372
3107
2167
920
955 / 975

1372
3107
2167
946
1005 / 1025

M0 / 12.5

GalvaSteel / 1.2
Polyester / 9002
M0 / 12.5
M0 / 12.5

FC Centrifugal
(inches)

Belt
(kW)
(A)
(A)
(rpm)

2" Throwaway
(C)
(C)
(C)
(C)
(mm)
(mm)
(mm)
(kg)
(kg)
(Type / mm)
(Type / RAL)
(Type / mm)

M0 / 12.5

(%)

2
60/40

2
70/30

2
50/50

2
50/50

(kg)
(kg)

3.1
4.9

4.0
6.0

5.9
5.9

7.2
7.2

(1) At Eurovent rating conditions : Indoor return Air (27C DB / 19C WB) - Ambiant 35C
(2) Per motor
(3) For standard unit, without options
Also available with R22 refrigerant. For information, contact your local sales office.

RT-PRC014-E4

Fixed Orifice
1 / 3/4" NPT

(mm)

(4) At the nominal airflow with standard drive


(5) At the nominal airflow with oversized drive when available
(6) At 10m from the unit in a free field

15

Performance Data
Cooling performances
Table 4 - TK*/YK* 155 Gross Cooling Capacities (kW)
25 C
Indoor Entering Entering
Airflow
Dry
Wet
m3/h
bulb
bulb
HR

Total
Cap
(kW)

Sens.
Cap.
(kW)

Outdoor Air Temperature


35 C

30 C
CMP
(kW)

Total
Cap
(kW)

Sens.
Cap.
(kW)

CMP
(kW)

Total
Cap
(kW)

Sens.
Cap.
(kW)

CMP
(kW)

9,4 C
30 %
18 C
12,1 C
50 %
14,6 C
70 %
39.7
23.1
9.6
36.8
21.5
10.1
33.9
19.9
10.7
11.5 C
30 %
21 C
14.6 C
50 %
39.7
29.0
9.6
36.8
27.4
10.1
33.9
25.8
10.6
17.3 C
70 %
45.0
24.3
10.0
42.0
22.8
10.6
38.9
21.2
11.2
13.7 C
30 %
38.4
36.5
9.4
35.7
35.0
10.0
32.9
32.9
10.5
24 C
17.0 C
50 %
44.5
30.7
10.0
41.5
29.1
10.5
38.4
27.5
11.1
20.0 C
70 %
49.1
24.8
10.4
46.6
23.5
11.0
43.8
22.2
11.7
6800
15.8 C
30 %
42.3
38.7
9.8
39.4
37.1
10.3
36.5
35.5
10.9
27 C
19.5 C
50 %
48.5
31.7
10.3
45.9
30.4
11.0
43.1
28.9
11.6
22.8 C
70 %
52.2
24.9
10.6
50.0
23.7
11.4
47.5
22.5
12.1
17.9 C
30 %
46.2
40.6
10.1
43.4
39.1
10.7
40.4
37.6
11.3
30 C
22.0 C
50 %
51.6
32.0
10.6
49.3
30.9
11.3
46.7
29.7
12.0
25.5 C
70 %
54.9
24.7
10.9
52.8
23.6
11.7
50.5
22.5
12.4
20.0 C
30 %
49.6
41.5
10.4
47.0
40.4
11.0
44.2
39.2
11.7
33 C
24.5 C
50 %
54.3
31.7
10.8
52.2
30.7
11.6
49.8
29.7
12.3
28.2 C
70 %
57.3
24.5
11.1
55.3
23.5
11.9
53.0
22.4
12.7
9.4 C
30 %
18 C
12.1 C
50 %
36.3
28.6
9.3
14.6 C
70 %
40.8
23.9
9.7
37.8
22.3
10.2
34.7
20.6
10.8
11.5 C
30 %
21 C
14.6 C
50 %
40.8
30.5
9.7
37.8
28.8
10.2
34.7
27.1
10.8
17.3 C
70 %
46.0
25.1
10.1
43.1
23.6
10.7
39.9
22.0
11.3
13.7 C
30 %
39.6
38.9
9.6
36.7
36.7
10.1
34.3
34.3
10.7
24 C
17.0 C
50 %
45.6
32.1
10.1
42.6
30.6
10.7
39.4
28.9
11.2
7650
20.0 C
70 %
49.7
25.5
10.4
47.3
24.2
11.1
44.6
22.8
11.8
15.8 C
30 %
43.6
41.1
9.9
40.7
39.5
10.5
37.5
37.5
11.0
27 C
19.5 C
50 %
49.3
32.9
10.4
46.7
31.7
11.1
43.9
30.3
11.7
22.8 C
70 %
52.7
25.5
10.7
50.5
24.3
11.5
48.0
23.1
12.2
17.9 C
30 %
47.3
42.7
10.2
44.6
41.5
10.8
41.6
40.1
11.5
30 C
22.0 C
50 %
52.3
32.8
10.7
50.0
31.9
11.4
47.4
30.8
12.1
25.5 C
70 %
55.3
25.4
11.0
53.2
24.3
11.8
50.9
23.5
12.5
20.0 C
30 %
50.5
43.4
10.5
48.0
42.5
11.2
45.2
41.4
11.8
33 C
24.5 C
50 %
55.3
32.8
10.9
52.7
31.5
11.7
50.3
30.5
12.4
28.2 C
70 %
57.7
25.1
11.2
9.4 C
30 %
18 C
12.1 C
50 %
37.0
29.8
9.4
34.0
28.1
9.9
14.6 C
70 %
41.7
24.6
9.8
38.5
22.9
10.3
35.3
21.2
10.9
11.5 C
30 %
37.1
37.1
9.4
34.7
34.7
10.0
32.2
32.2
10.5
21 C
14.6 C
50 %
41.7
31.7
9.8
38.5
30.0
10.3
35.4
28.3
10.9
17.3 C
70 %
46.6
25.7
10.2
43.8
24.2
10.8
40.6
22.6
11.4
13.7 C
30 %
40.4
40.4
9.7
38.0
38.0
10.3
35.5
35.5
10.9
24 C
17.0 C
50 %
46.3
33.3
10.2
43.3
31.8
10.8
40.1
30.2
11.4
8500
20.0 C
70 %
50.1
26.0
10.5
47.7
24.7
11.2
45.0
23.4
11.9
15.8 C
30 %
44.6
43.3
10.0
41.4
41.4
10.6
38.9
38.9
11.2
27 C
19.5 C
50 %
49.8
33.8
10.5
47.2
32.7
11.1
44.4
31.4
11.8
22.8 C
70 %
53.0
26.0
10.8
50.8
24.9
11.5
48.3
23.7
12.3
17.9 C
30 %
48.1
44.5
10.3
45.4
43.5
10.9
42.6
42.3
11.6
30 C
22.0 C
50 %
52.7
33.5
10.7
50.4
32.6
11.5
47.8
31.6
12.2
25.5 C
70 %
20.0 C
30 %
51.1
44.9
10.5
48.6
44.2
11.3
45.8
43.2
11.9
33 C
24.5 C
50 %
55.6
33.2
11.0
53.5
32.6
11.8
50.7
31.2
12.5
28.2 C
70 %
57.8
25.1
11.2
55.9
24.2
12.1
9.4 C
30 %
18 C
12.1 C
50 %
37.5
30.8
9.5
34.4
29.0
10.0
31.3
27.3
10.5
14.6 C
70 %
42.3
25.1
9.9
39.0
23.4
10.4
35.8
21.7
11.0
11.5 C
30 %
38.1
38.1
9.5
35.6
35.6
10.1
33.1
33.1
10.7
21 C
14.6 C
50 %
42.3
32.8
9.9
39.0
31.1
10.4
35.8
29.4
11.0
17.3 C
70 %
46.9
26.1
10.3
44.2
24.6
10.9
41.1
23.1
11.5
13.7 C
30 %
41.6
41.6
9.8
39.1
39.1
10.4
36.5
36.5
11.0
24 C
17.0 C
50 %
46.7
34.2
10.2
43.8
32.9
10.9
40.6
31.3
11.4
9350
20.0 C
70 %
50.3
26.4
10.6
47.9
25.1
11.3
45.2
23.8
11.9
15.8 C
30 %
45.4
45.1
10.1
42.6
42.6
10.7
40.0
40.0
11.4
27 C
19.5 C
50 %
50.1
34.5
10.5
47.5
33.5
11.2
44.7
32.3
11.9
22.8 C
70 %
50.3
26.4
10.6
50.7
24.9
11.6
48.3
23.8
12.3
17.9 C
30 %
48.6
46.1
10.4
46.0
45.2
11.0
43.2
43.2
11.7
30 C
22.0 C
50 %
52.9
34.0
10.8
50.6
33.2
11.5
48.0
32.3
12.2
25.5 C
70 %
20.0 C
30 %
51.5
46.2
10.6
49.0
45.6
11.3
46.3
44.8
12.0
33 C
24.5 C
50 %
55.7
33.5
11.0
53.7
32.9
11.8
51.3
32.3
12.6
28.2 C
70 %
57.8
25.0
11.3
55.9
24.1
12.1
53.6
23.0
12.9
9.4 C
30 %
35.3
35.3
9.3
18 C
12.1 C
50 %
37.8
31.6
9.5
34.6
29.8
10.1
31.5
28.1
10.6
14.6 C
70 %
42.7
25.5
9.9
39.4
23.8
10.5
36.0
22.0
11.0
11.5 C
30 %
38.9
38.9
9.6
36.3
36.3
10.2
33.7
33.7
10.8
21 C
14.6 C
50 %
42.7
33.7
9.9
39.4
32.0
10.5
36.0
30.3
11.0
17.3 C
70 %
47.1
26.4
10.3
44.4
25.0
11.0
41.3
23.5
11.6
13.7 C
30 %
42.5
42.5
9.9
39.9
39.9
10.5
37.3
37.3
11.1
24 C
17.0 C
50 %
46.9
34.9
10.3
44.0
33.7
10.9
40.9
32.2
11.5
10200
20.0 C
70 %
50.2
26.4
10.6
47.8
25.3
11.3
45.2
24.1
12.0
15.8 C
30 %
45.8
45.8
10.2
43.4
43.4
10.8
40.8
40.8
11.5
27 C
19.5 C
50 %
50.2
34.9
10.6
47.6
34.1
11.3
44.8
33.0
11.9
22.8 C
70 %
52.9
26.0
10.9
50.7
24.9
11.6
48.2
23.8
12.4
17.9 C
30 %
48.9
47.3
10.4
46.2
46.2
11.1
43.8
43.8
11.8
30 C
22.0 C
50 %
52.9
34.3
10.8
50.6
33.6
11.6
48.1
32.8
12.3
25.5 C
70 %
55.6
25.5
11.1
20.0 C
30 %
51.7
47.2
10.7
49.3
46.8
11.4
46.6
46.1
12.1
33 C
24.5 C
50 %
55.7
33.6
11.1
53.6
33.1
11.9
50.8
31.9
12.6
28.2 C
70 %
57.6
24.7
11.3
55.8
23.9
12.2
53.5
22.9
13.0
Note: All capacities are gross cooling values and do not include indoor fan heat. To obtain net cooling, subtract indoor fan heat.

16

40 C
Total
Cap
(kW)

Sens.
Cap.
(kW)

30.9
30.9
35.8
30.6
35.3
40.9
33.6
40.0
44.7
37.4
43.9
47.8
41.3
47.1
50.4
31.6
31.6
36.7
31.9
36.2
41.6
35.1
40.8
45.2
38.3
44.5
48.2
42.2
47.6
32.1
29.8
32.1
37.3
33.0
36.8
42.0
36.4
41.3
45.5
39.7
44.9
43.0
47.9
32.5
30.5
32.5
37.7
33.9
37.2
42.2
37.4
41.6
45.5
40.6
45.1
43.3
48.1
50.9
28.4
32.6
31.0
32.7
38.0
34.6
37.5
42.3
38.2
41.8
45.5
41.3
45.2
43.9
48.1
50.8

18.3
24.2
19.6
30.6
25.9
20.7
33.6
27.5
21.2
36.1
28.4
21.3
37.9
28.6
21.6
19.0
25.5
20.4
31.9
27.3
21.4
35.1
28.9
21.8
38.3
29.6
22.0
40.2
29.5
19.6
29.8
26.6
21.0
33.0
28.6
22.0
36.4
30.1
22.4
39.7
30.5
42.1
32.0
20.0
30.5
27.7
21.5
33.9
29.7
22.4
37.4
31.0
22.6
40.6
31.2
43.3
30.7
21.9
26.4
20.3
31.0
28.6
21.9
34.6
30.6
22.7
38.2
31.8
22.7
41.3
31.8
43.9
31.0
21.7

45 C
CMP
(kW)

Total
Cap
(kW)

Sens.
Cap.
(kW)

CMP
(kW)

11.2
11.1
11.7
11.1
11.7
12.3
11.4
12.2
12.8
11.9
12.6
13.2
12.3
13.0
13.5
11.3
11.3
11.9
11.3
11.8
12.4
11.7
12.3
12.9
12.0
12.7
13.2
12.5
13.1
11.4
11.1
11.4
12.0
11.5
11.9
12.5
11.8
12.4
12.9
12.2
12.8
12.6
13.2
11.5
11.2
11.5
12.1
11.6
12.0
12.6
12.0
12.5
13.0
12.3
12.9
12.7
13.3
13.7
11.0
11.6
11.3
11.5
12.1
11.7
12.1
12.6
12.1
12.6
13.1
12.5
13.0
12.8
13.3
13.7

27.9
27.9
32.6
28.3
32.1
37.7
31.2
36.7
41.8
34.2
40.9
45.0
38.2
44.2
28.5
26.5
28.5
33.3
29.5
32.9
38.4
32.6
37.6
42.3
35.8
41.5
45.3
39.3
44.7
28.9
27.3
28.9
33.9
30.5
33.4
38.9
33.8
38.1
42.5
37.1
41.9
40.0
45.0
29.1
27.9
29.3
34.3
31.3
33.8
39.1
34.8
38.4
42.5
38.0
42.1
40.8
45.1
25.3
29.2
28.4
29.4
34.4
31.9
34.0
39.1
35.5
38.5
42.5
38.7
42.1
41.3
-

16.7
22.6
18.0
28.3
24.3
19.3
31.2
25.9
19.9
34.2
27.1
20.1
36.5
27.3
17.4
26.5
23.9
18.8
29.5
25.7
20.0
32.6
27.4
20.5
35.8
28.3
20.7
38.9
28.3
17.9
27.3
25.0
19.4
30.5
26.9
20.6
33.8
28.6
21.1
37.1
29.3
40.0
29.1
18.3
27.9
26.0
19.9
31.3
28.0
21.0
34.8
29.7
21.3
38.0
30.1
40.8
29.7
24.8
18.6
28.4
26.9
20.2
31.9
29.0
21.3
35.5
30.5
21.4
38.7
30.8
41.3
-

11.6
11.6
12.2
11.7
12.2
12.9
12.1
12.7
13.4
12.4
13.3
13.8
12.9
13.7
11.8
11.5
11.8
12.4
11.9
12.3
13.0
12.3
12.9
13.5
12.6
13.4
13.9
13.1
13.8
11.9
11.6
11.9
12.5
12.0
12.4
13.1
12.5
13.0
13.6
12.8
13.5
13.2
13.9
11.9
11.8
11.9
12.6
12.2
12.5
13.2
12.6
13.1
13.7
13.0
13.6
13.4
14.0
11.5
12.0
11.9
12.0
12.7
12.3
12.6
13.2
12.8
13.2
13.7
13.2
13.6
13.5
-

RT-PRC014-E4

Performance Data
Table 5 - TK*/YK* 175 Gross Cooling Capacities (kW)
25 C
Indoor Entering Entering
Airflow
Dry
Wet
m3/h
bulb
bulb
HR
18 C
21 C
24 C
7870
27 C
30 C
33 C
18 C
21 C
24 C
8860
27 C
30 C
33 C
18 C
21 C
24 C
9850
27 C
30 C
33 C
18 C
21 C
24 C
10840
27 C
30 C
33 C
18 C
21 C
24 C
11830
27 C
30 C
33 C

9.4 C
12.1 C
14.6 C
11.5 C
14.6 C
17.3 C
13.7 C
17.0 C
20.0 C
15.8 C
19.5 C
22.8 C
17.9 C
22.0 C
25.5 C
20.0 C
24.5 C
28.2 C
9.4 C
12.1 C
14.6 C
11.5 C
14.6 C
17.3 C
13.7 C
17.0 C
20.0 C
15.8 C
19.5 C
22.8 C
17.9 C
22.0 C
25.5 C
20.0 C
24.5 C
28.2 C
9.4 C
12.1 C
14.6 C
11.5 C
14.6 C
17.3 C
13.7 C
17.0 C
20.0 C
15.8 C
19.5 C
22.8 C
17.9 C
22.0 C
25.5 C
20.0 C
24.5 C
28.2 C
9.4 C
12.1 C
14.6 C
11.5 C
14.6 C
17.3 C
13.7 C
17.0 C
20.0 C
15.8 C
19.5 C
22.8 C
17.9 C
22.0 C
25.5 C
20.0 C
24.5 C
28.2 C
9.4 C
12.1 C
14.6 C
11.5 C
14.6 C
17.3 C
13.7 C
17.0 C
20.0 C
15.8 C
19.5 C
22.8 C
17.9 C
22.0 C
25.5 C
20.0 C
24.5 C
28.2 C

30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %

Total
Cap
(kW)

Sens.
Cap.
(kW)

40.4
45.6
39.9
45.6
50.6
44.1
50.3
53.9
48.5
53.6
56.6
52.0
56.3
59.0
54.9
59.0
60.9
37.7
41.6
46.9
41.4
47.0
51.3
45.7
51.2
54.4
49.7
54.3
56.9
52.9
56.9
59.3
55.7
59.6
61.2
39.1
42.6
47.9
43.0
47.9
51.8
47.1
51.7
54.7
50.7
54.7
57.4
53.6
57.3
59.5
56.2
59.8
61.4
40.2
43.3
48.4
44.3
48.5
52.1
48.2
52.1
54.8
51.3
55.0
57.5
54.1
57.4
59.5
56.6
59.9
61.4
41.2
43.9
48.7
45.4
48.9
52.1
49.0
52.3
54.8
51.6
55.1
57.5
54.3
57.8
59.5
56.8
59.9
61.3

31.5
26.7
39.8
33.6
27.6
42.4
35.1
27.7
44.8
35.3
27.6
45.8
34.8
27.4
45.9
34.4
26.7
37.7
33.2
27.7
41.4
35.4
28.4
45.2
36.5
28.5
47.2
36.3
28.0
47.8
35.7
27.6
47.5
35.1
26.8
39.1
34.7
28.6
43.0
36.9
29.0
47.0
37.5
28.8
49.3
37.1
28.4
49.5
36.3
27.6
48.9
35.5
26.8
40.2
36.0
29.1
44.3
38.1
29.6
48.2
38.4
29.0
51.0
37.7
28.5
50.9
36.7
27.6
50.0
35.7
26.7
41.2
37.2
29.7
45.4
39.2
29.8
49.0
39.1
29.1
51.6
38.2
28.4
52.0
37.2
27.4
51.0
35.8
26.6

Outdoor Air Temperature


35 C

30 C
CMP
(kW)

Total
Cap
(kW)

Sens.
Cap.
(kW)

10.4
10.8
10.4
10.8
11.2
10.7
11.2
11.5
11.0
11.5
11.8
11.3
11.7
12.0
11.5
12.0
12.2
10.2
10.5
10.9
10.5
10.9
11.3
10.8
11.3
11.6
11.1
11.5
11.8
11.4
11.8
12.1
11.6
12.0
12.3
10.3
10.6
11.0
10.6
11.0
11.4
11.0
11.4
11.6
11.2
11.6
11.9
11.5
11.9
12.1
11.7
12.1
12.3
10.5
10.7
11.1
10.8
11.1
11.4
11.1
11.4
11.7
11.3
11.7
12.0
11.5
11.9
12.2
11.8
12.1
12.3
10.6
10.8
11.2
10.9
11.2
11.5
11.2
11.5
11.7
11.4
11.7
12.0
11.6
12.0
12.2
11.8
12.2
12.4

41.7
41.8
47.7
40.6
47.2
52.3
44.9
51.8
55.6
49.3
55.1
58.4
53.0
57.9
60.9
37.9
43.0
38.4
43.0
48.9
42.1
48.4
53.0
46.5
52.5
56.2
50.6
55.8
58.8
54.0
59.0
61.4
38.7
43.9
39.8
43.9
49.6
43.7
49.3
53.5
47.6
53.1
56.3
51.5
56.2
59.2
54.7
59.3
61.6
37.0
39.3
44.6
41.0
44.6
50.1
45.1
49.8
53.6
48.9
53.5
56.5
51.9
56.5
59.4
55.2
59.5
61.6
37.8
39.7
45.2
42.0
45.2
50.3
46.2
50.1
53.8
49.8
53.7
56.6
52.6
56.6
59.4
55.5
59.5
61.6

24.6
31.5
26.1
40.3
33.5
26.6
42.8
34.7
26.6
45.1
34.7
26.5
46.0
34.1
26.3
31.0
25.6
38.4
33.2
27.0
42.1
35.2
27.4
45.8
36.0
27.5
47.6
35.7
27.0
48.2
35.5
26.6
32.4
26.5
39.8
34.8
27.8
43.7
36.7
28.1
47.6
37.1
27.7
49.9
36.6
27.3
50.0
36.0
26.6
37.0
33.7
27.2
41.0
36.2
28.4
45.1
37.9
28.6
48.9
38.0
28.0
51.9
37.2
27.4
51.6
36.3
26.6
37.8
34.9
27.8
42.0
37.5
28.9
46.2
39.0
28.8
49.8
38.8
28.1
52.6
37.7
27.4
52.9
36.7
26.5

CMP
(kW)

Total
Cap
(kW)

Sens.
Cap.
(kW)

11.5
11.5
12.0
11.4
12.0
12.4
11.8
12.4
12.8
12.1
12.7
13.1
12.5
13.0
13.3
11.2
11.6
11.2
11.6
12.1
11.5
12.1
12.5
11.9
12.5
12.8
12.3
12.8
13.1
12.6
13.1
13.4
11.3
11.7
11.4
11.7
12.2
11.7
12.2
12.6
12.0
12.5
12.9
12.4
12.9
13.2
12.7
13.2
13.5
11.1
11.4
11.8
11.5
11.8
12.3
11.8
12.3
12.7
12.2
12.6
13.0
12.4
12.9
13.3
12.7
13.2
13.5
11.2
11.4
11.9
11.6
11.9
12.4
12.0
12.3
12.7
12.3
12.7
13.0
12.5
13.0
13.3
12.8
13.3
13.6

37.9
37.9
43.6
37.2
43.0
49.6
41.1
48.6
53.7
45.5
52.9
57.1
50.0
56.3
59.8
38.9
38.9
44.8
38.9
44.2
50.5
42.6
49.7
54.4
47.1
53.7
57.6
51.3
57.0
60.3
39.7
36.6
39.7
45.8
40.4
45.2
51.1
44.3
50.4
54.8
48.2
54.2
57.7
52.2
57.4
60.6
40.3
37.6
40.3
46.5
41.6
45.9
51.5
45.8
50.9
54.9
49.5
54.6
57.8
52.8
57.7
60.7
35.7
40.7
38.5
40.8
46.9
42.7
46.4
51.6
46.9
51.2
55.0
50.4
54.8
57.9
53.2
57.8
60.7

22.5
29.4
24.0
37.2
31.3
25.2
40.8
33.1
25.5
43.2
33.9
25.5
45.2
33.8
25.3
23.4
31.0
25.0
38.9
33.1
26.2
42.6
34.9
26.3
46.3
35.3
26.3
48.0
34.9
25.9
24.2
36.6
32.5
25.9
40.4
34.8
26.9
44.3
36.3
27.1
48.2
36.5
26.6
50.3
35.8
26.1
24.9
37.6
33.9
26.7
41.6
36.3
27.5
45.8
37.6
27.4
49.5
37.4
26.8
52.2
36.4
26.2
32.7
25.5
38.5
35.2
27.3
42.7
37.6
28.0
46.9
38.7
27.6
50.4
38.2
26.9
53.2
36.9
26.1

40 C

CMP
(kW)

Total
Cap
(kW)

Sens.
Cap.
(kW)

12.2
12.2
12.7
12.1
12.7
13.3
12.5
13.2
13.7
12.9
13.6
14.1
13.3
14.0
14.4
12.3
12.3
12.9
12.3
12.8
13.4
12.6
13.3
13.8
13.1
13.7
14.2
13.5
14.1
14.5
12.4
12.1
12.4
13.0
12.5
12.9
13.5
12.8
13.4
13.9
13.2
13.8
14.2
13.6
14.2
14.6
12.5
12.2
12.5
13.1
12.6
13.0
13.6
13.0
13.5
14.0
13.3
13.9
14.3
13.7
14.2
14.6
12.1
12.6
12.3
12.6
13.2
12.7
13.1
13.6
13.1
13.6
14.0
13.5
14.0
14.4
13.7
14.3
14.7

39.4
38.9
45.4
37.6
44.3
51.0
41.5
49.7
54.8
46.1
53.8
58.1
40.4
35.7
39.9
46.6
39.3
45.4
51.8
43.1
50.7
55.4
47.5
54.5
35.4
35.5
41.2
37.0
40.7
47.4
40.9
46.3
52.2
44.8
51.3
55.6
48.6
55.0
35.9
36.0
41.8
38.1
41.3
48.0
42.2
46.9
52.5
46.3
51.7
55.8
49.9
55.4
36.2
35.0
36.4
42.2
39.1
41.7
48.3
43.3
47.4
52.5
47.4
51.9
56.0
50.8
55.5
59.0

21.9
29.2
23.3
37.6
31.1
24.2
41.1
32.6
24.2
43.5
33.1
24.2
22.9
35.7
30.9
24.4
39.3
33.0
25.0
43.1
34.4
25.1
46.6
34.4
22.0
30.3
23.7
37.0
32.5
25.2
40.9
34.7
25.8
44.8
35.8
25.7
48.6
35.6
22.7
31.7
24.4
38.1
34.0
25.9
42.2
36.1
26.4
46.3
37.1
26.0
49.9
36.5
23.2
35.0
32.9
25.1
39.1
35.3
26.5
43.3
37.5
26.8
47.4
38.1
28.3
50.8
37.3
25.6

45 C
CMP
(kW)

Total
Cap
(kW)

Sens.
Cap.
(kW)

13.4
13.4
14.1
13.2
13.9
14.7
13.6
14.5
15.1
14.1
14.9
15.5
13.6
13.0
13.5
14.2
13.4
14.1
14.8
13.8
14.6
15.2
14.3
15.1
13.1
13.1
13.7
13.2
13.6
14.3
13.6
14.2
14.9
14.0
14.7
15.3
14.4
15.1
13.2
13.2
13.8
13.4
13.7
14.4
13.8
14.3
14.9
14.2
14.8
15.3
14.6
15.2
13.2
13.1
13.2
13.9
13.5
13.8
14.5
14.0
14.4
15.0
14.4
14.9
15.4
14.7
15.3
15.8

35.1
34.6
40.8
34.4
39.7
47.0
37.8
45.3
51.9
41.8
50.5
35.9
35.4
41.8
36.0
40.7
48.0
39.6
46.4
43.4
51.3
36.5
33.6
36.1
42.6
37.4
41.5
48.6
41.2
47.2
45.2
51.9
37.0
34.6
36.6
43.2
38.5
42.0
49.1
42.6
47.7
46.6
37.3
35.4
36.9
43.6
39.5
42.4
49.3
43.7
48.0
47.7
-

19.8
27.1
21.2
34.4
29.0
22.5
37.8
30.8
22.9
41.5
32.0
20.7
28.8
22.2
36.0
30.8
23.4
39.6
32.7
43.4
33.7
21.5
33.6
30.3
23.1
37.4
32.4
24.2
41.2
34.4
45.2
35.1
22.2
34.6
31.8
23.9
38.5
34.0
25.0
42.6
35.9
46.6
22.8
35.4
33.1
24.5
39.5
35.4
25.6
43.7
37.2
47.7

CMP
(kW)
14.1
14.1
14.8
14.0
14.7
15.5
14.4
15.3
16.1
14.9
15.9
14.3
14.2
15.0
14.3
14.8
15.6
14.7
15.4
15.1
16.0
14.4
14.0
14.3
15.1
14.5
14.9
15.7
14.9
15.6
15.3
16.1
14.5
14.2
14.4
15.2
14.6
15.0
15.8
15.1
15.7
15.5
14.6
14.3
14.5
15.3
14.8
15.1
15.9
15.2
15.7
15.7
-

Note: All capacities are gross cooling values and do not include indoor fan heat. To obtain net cooling, subtract indoor fan heat.

RT-PRC014-E4

17

Performance Data
Table 6- TK*/YK* 200 Gross Cooling Capacities (kW)
25 C
Indoor Entering Entering
Airflow
Dry
Wet
m3/h
bulb
bulb
HR
18 C
21 C
24 C
8970
27 C
30 C
33 C
18 C
21 C
24 C
10090
27 C
30 C
33 C
18 C
21 C
24 C
11210
27 C
30 C
33 C
18 C
21 C
24 C
12330
27 C
30 C
33 C
18 C
21 C
24 C
13450
27 C
30 C
33 C

9.4 C
12.1 C
14.6 C
11.5 C
14.6 C
17.3 C
13.7 C
17.0 C
20.0 C
15.8 C
19.5 C
22.8 C
17.9 C
22.0 C
25.5 C
20.0 C
24.5 C
28.2 C
9.4 C
12.1 C
14.6 C
11.5 C
14.6 C
17.3 C
13.7 C
17.0 C
20.0 C
15.8 C
19.5 C
22.8 C
17.9 C
22.0 C
25.5 C
20.0 C
24.5 C
28.2 C
9.4 C
12.1 C
14.6 C
11.5 C
14.6 C
17.3 C
13.7 C
17.0 C
20.0 C
15.8 C
19.5 C
22.8 C
17.9 C
22.0 C
25.5 C
20.0 C
24.5 C
28.2 C
9.4 C
12.1 C
14.6 C
11.5 C
14.6 C
17.3 C
13.7 C
17.0 C
20.0 C
15.8 C
19.5 C
22.8 C
17.9 C
22.0 C
25.5 C
20.0 C
24.5 C
28.2 C
9.4 C
12.1 C
14.6 C
11.5 C
14.6 C
17.3 C
13.7 C
17.0 C
20.0 C
15.8 C
19.5 C
22.8 C
17.9 C
22.0 C
25.5 C
20.0 C
24.5 C
28.2 C

30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %

Total
Cap
(kW)

Sens.
Cap.
(kW)

52.6
52.6
59.5
50.9
58.4
65.0
56.0
64.3
69.1
61.3
68.3
72.8
65.7
72.3
76.0
53.9
54.0
60.9
52.0
60.3
65.8
57.8
65.2
69.8
62.7
69.1
73.3
66.8
73.1
76.5
48.8
55.0
49.4
55.0
61.7
54.1
61.2
66.3
58.4
65.8
70.0
63.7
69.7
73.7
67.6
73.5
76.8
49.4
55.8
50.6
55.8
62.1
55.4
61.7
66.5
59.9
66.1
70.1
64.4
69.9
73.8
68.0
73.7
76.9
46.9
49.8
56.2
51.7
56.3
62.2
56.6
61.9
66.3
60.9
66.2
70.0
64.3
69.9
73.7
68.3
73.7
76.7

30.8
38.9
32.4
49.2
40.7
33.0
52.1
42.4
33.0
54.6
42.7
32.8
55.9
42.9
32.5
31.8
40.8
33.4
52.0
43.0
33.8
55.4
44.0
33.9
57.6
43.9
33.7
58.4
43.7
33.2
39.8
32.7
49.4
42.5
34.2
54.0
44.6
34.5
58.4
45.2
34.3
60.2
44.8
34.0
60.5
44.3
33.2
41.2
33.4
50.6
43.9
34.7
55.4
46.0
35.0
59.9
46.2
34.5
62.3
45.5
34.0
62.3
44.7
33.1
46.9
42.3
33.9
51.7
45.2
35.1
56.6
47.0
35.1
60.9
46.9
34.5
64.3
46.0
33.8
63.7
45.1
32.8

Outdoor Air Temperature


35 C

30 C

CMP
(kW)

Total
Cap
(kW)

Sens.
Cap.
(kW)

13.1
13.1
13.3
13.0
13.3
13.6
13.2
13.5
13.8
13.4
13.7
14.0
13.6
13.9
14.1
13.1
13.1
13.4
13.0
13.4
13.6
13.3
13.6
13.8
13.5
13.8
14.0
13.6
13.9
14.2
12.9
13.2
12.9
13.2
13.5
13.1
13.4
13.7
13.3
13.6
13.9
13.5
13.8
14.1
13.7
14.0
14.2
13.0
13.2
13.0
13.2
13.5
13.2
13.5
13.7
13.4
13.7
13.9
13.6
13.9
14.1
13.7
14.0
14.3
12.9
13.0
13.3
13.1
13.3
13.5
13.3
13.5
13.7
13.5
13.7
13.9
13.6
13.9
14.1
13.8
14.1
14.3

49.4
49.4
56.2
47.5
55.6
62.6
52.9
61.7
67.1
58.2
66.1
71.0
63.1
70.0
74.5
50.7
50.7
57.6
49.7
57.0
63.5
53.8
62.7
67.8
59.8
67.0
71.6
64.3
70.8
75.0
51.6
46.8
51.6
58.6
51.2
58.0
64.0
55.7
63.3
68.2
61.0
67.5
71.7
65.1
71.7
75.3
46.2
52.2
47.9
52.2
59.2
52.5
58.6
64.2
57.2
63.7
68.1
61.4
67.8
71.7
65.7
72.0
75.3
46.5
52.6
48.8
52.6
59.4
53.7
58.9
64.3
58.4
63.8
68.1
62.2
67.9
72.0
66.0
71.9
75.2

29.0
37.1
30.6
47.5
39.3
31.7
50.3
41.0
31.8
53.0
41.7
31.7
55.0
41.5
31.5
30.0
38.9
31.7
49.5
41.3
32.5
53.8
42.9
32.7
56.4
43.1
32.6
57.8
42.6
32.4
30.8
46.8
40.6
32.6
51.2
43.0
33.2
55.7
44.3
33.4
59.2
44.2
32.9
60.2
44.1
32.4
39.3
31.5
47.9
42.0
33.2
52.5
44.4
33.8
57.2
45.4
33.6
61.4
45.1
33.0
62.2
44.7
32.3
40.4
32.0
48.8
43.3
33.6
53.7
45.7
34.2
58.4
46.3
33.6
62.2
45.7
33.1
63.9
45.1
32.1

CMP
(kW)

Total
Cap
(kW)

Sens.
Cap.
(kW)

14.2
14.2
14.5
14.0
14.5
14.8
14.3
14.7
15.0
14.6
15.0
15.3
14.8
15.2
15.5
14.2
14.2
14.6
14.2
14.6
14.9
14.4
14.8
15.1
14.7
15.0
15.3
14.9
15.2
15.5
14.3
14.0
14.3
14.7
14.3
14.6
14.9
14.5
14.9
15.1
14.7
15.1
15.4
14.9
15.3
15.6
14.1
14.4
14.1
14.4
14.7
14.4
14.7
15.0
14.6
14.9
15.2
14.8
15.1
15.4
15.0
15.3
15.7
14.1
14.4
14.2
14.4
14.8
14.5
14.7
15.0
14.7
14.9
15.2
14.8
15.2
15.5
15.0
15.4
15.7

46.1
46.1
52.6
45.2
52.0
59.6
48.8
58.3
64.6
54.8
63.6
68.7
60.0
67.7
72.3
47.2
47.2
53.9
46.8
53.3
60.6
51.0
59.6
65.3
56.4
64.3
69.3
61.3
68.4
73.2
47.9
44.0
48.0
54.9
48.3
54.3
61.2
52.8
60.3
65.7
57.2
64.9
69.4
62.3
68.9
73.1
48.5
45.0
48.5
55.5
49.6
54.9
61.5
54.3
60.7
65.9
58.9
65.2
69.5
62.3
69.1
73.2
43.0
48.8
45.8
48.8
55.9
50.6
55.3
61.5
55.4
60.9
65.7
59.7
65.3
69.4
63.1
69.7
73.1

27.1
35.2
28.8
44.8
37.4
30.2
48.8
39.4
30.5
51.2
40.6
30.5
53.6
40.6
30.7
28.1
37.0
29.9
46.8
39.4
31.1
51.0
41.3
31.4
54.7
42.1
31.8
56.8
41.9
32.3
28.9
44.0
38.6
30.7
48.3
41.1
31.8
52.8
43.1
32.1
57.2
43.4
31.8
59.5
42.9
31.5
29.5
45.0
40.0
31.4
49.6
42.6
32.4
54.3
44.4
32.7
58.9
44.4
32.1
62.3
43.6
31.4
38.5
30.0
45.8
41.3
31.9
50.6
43.9
32.8
55.4
45.5
32.6
59.7
45.2
31.9
63.1
45.0
31.2

40 C

CMP
(kW)

Total
Cap
(kW)

Sens.
Cap.
(kW)

15.5
15.5
15.8
15.4
15.8
16.2
15.6
16.1
16.5
15.9
16.4
16.7
16.2
16.6
17.0
15.6
15.5
15.9
15.5
15.9
16.3
15.8
16.2
16.6
16.0
16.5
16.8
16.3
16.7
17.1
15.6
15.4
15.6
16.0
15.6
16.0
16.3
15.9
16.3
16.6
16.1
16.5
16.9
16.4
16.8
17.1
15.7
15.5
15.7
16.1
15.7
16.0
16.4
16.0
16.3
16.7
16.2
16.6
16.9
16.4
16.8
17.2
15.4
15.8
15.6
15.7
16.1
15.8
16.1
16.4
16.1
16.4
16.7
16.3
16.6
17.0
16.5
16.9
17.2

42.6
42.6
48.9
42.2
48.3
55.8
46.1
54.6
61.7
51.2
60.4
66.1
56.4
64.8
69.8
43.5
43.6
50.1
43.9
49.5
57.0
48.1
55.8
62.4
52.4
61.2
66.6
57.9
65.6
70.3
44.2
41.0
44.2
50.9
45.3
50.3
57.8
49.7
56.6
62.8
54.2
61.8
66.9
58.4
66.0
44.6
42.0
44.7
51.5
46.5
50.9
58.2
51.1
57.1
63.0
55.7
62.1
66.8
59.6
66.3
70.6
39.3
44.8
42.7
44.9
51.8
47.4
51.2
58.2
52.2
57.4
62.8
56.7
62.2
66.6
60.5
66.3
70.5

25.2
33.3
26.9
42.2
35.5
28.4
46.1
37.6
29.1
49.4
39.1
29.2
52.0
39.5
29.1
26.2
35.1
27.9
43.9
37.4
29.4
48.1
39.6
29.9
52.4
40.9
30.1
55.4
40.9
30.5
26.9
41.0
36.6
28.8
45.3
39.1
30.2
49.7
41.3
30.7
54.2
42.4
30.8
58.4
42.1
27.5
42.0
38.0
29.5
46.5
40.6
30.8
51.1
42.9
31.3
55.7
43.5
30.8
59.6
42.9
30.4
36.5
27.9
42.7
39.3
30.0
47.4
42.0
31.3
52.2
44.1
31.5
56.7
44.5
30.9
60.5
43.6
30.3

45 C
CMP
(kW)

Total
Cap
(kW)

Sens.
Cap.
(kW)

CMP
(kW)

16.9
16.9
17.4
16.9
17.3
17.8
17.1
17.7
18.1
17.5
18.0
18.4
17.8
18.3
18.7
17.0
17.0
17.5
17.0
17.4
17.8
17.3
17.8
18.2
17.6
18.1
18.5
17.9
18.4
18.7
17.1
16.9
17.1
17.5
17.2
17.5
17.9
17.4
17.8
18.2
17.7
18.1
18.5
17.9
18.4
17.2
17.0
17.2
17.6
17.3
17.6
18.0
17.6
17.9
18.3
17.8
18.2
18.6
18.0
18.5
18.9
16.8
17.2
17.1
17.2
17.7
17.4
17.6
18.0
17.7
18.0
18.3
17.9
18.2
18.6
18.1
18.5
18.9

38.9
38.9
45.0
39.3
44.5
51.8
43.2
50.6
58.3
47.1
56.8
62.9
52.7
61.5
66.9
39.7
39.8
46.1
40.9
45.5
52.9
45.0
51.7
59.0
49.3
57.7
63.5
53.5
62.3
67.3
40.2
38.0
40.3
46.8
42.2
46.2
53.7
46.6
52.5
59.5
51.0
58.2
63.8
55.6
62.8
40.6
38.8
40.7
47.2
43.2
46.6
54.2
47.8
52.9
59.6
52.4
58.5
65.0
56.7
63.0
35.6
40.7
39.4
40.9
47.4
44.1
46.9
54.4
48.8
53.2
59.6
53.5
58.6
63.5
57.5
63.0
-

23.3
31.3
25.0
39.3
33.5
26.6
43.2
35.7
27.6
47.1
37.4
27.8
50.2
38.3
27.8
24.2
33.1
26.0
40.9
35.4
27.6
45.0
37.7
28.5
49.3
39.4
28.7
53.5
39.8
28.7
24.9
38.0
34.6
26.8
42.2
37.1
28.4
46.6
39.4
29.2
51.0
41.0
29.4
55.3
41.1
25.4
38.8
36.0
27.4
43.2
38.6
29.1
47.8
41.0
29.8
52.4
42.4
30.4
56.7
42.1
34.5
25.9
39.4
37.2
27.9
44.1
39.9
29.5
48.8
42.3
30.2
53.5
43.5
29.7
57.5
42.9
-

18.6
18.6
19.0
18.6
19.0
19.5
18.9
19.4
19.9
19.2
19.8
20.2
19.5
20.1
20.5
18.7
18.7
19.1
18.7
19.1
19.6
19.0
19.5
20.0
19.3
19.9
20.3
19.6
20.2
20.6
18.8
18.6
18.7
19.2
18.9
19.2
19.7
19.2
19.6
20.0
19.5
19.9
20.3
19.7
20.2
18.8
18.7
18.8
19.3
19.0
19.2
19.7
19.3
19.6
20.1
19.6
20.0
20.4
19.8
20.3
18.5
18.9
18.8
18.9
19.3
19.1
19.3
19.8
19.4
19.7
20.1
19.7
20.0
20.4
19.9
20.3
-

Note: All capacities are gross cooling values and do not include indoor fan heat. To obtain net cooling, subtract indoor fan heat.

18

RT-PRC014-E4

Performance Data
Table 7 - TK*/YK* 250 Gross Cooling Capacities (kW)
25 C
Indoor Entering Entering
Airflow
Dry
Wet
m3/h
bulb
bulb
18 C
21 C
24 C
11280
27 C
30 C
33 C
18 C
21 C
24 C
12690
27 C
30 C
33 C
18 C
21 C
24 C
14100
27 C
30 C
33 C
18 C
21 C
24 C
15510
27 C
30 C
33 C
18 C
21 C
24 C
16920
27 C
30 C
33 C

9.4 C
12.1 C
14.6 C
11.5 C
14.6 C
17.3 C
13.7 C
17.0 C
20.0 C
15.8 C
19.5 C
22.8 C
17.9 C
22.0 C
25.5 C
20.0 C
24.5 C
28.2 C
9.4 C
12.1 C
14.6 C
11.5 C
14.6 C
17.3 C
13.7 C
17.0 C
20.0 C
15.8 C
19.5 C
22.8 C
17.9 C
22.0 C
25.5 C
20.0 C
24.5 C
28.2 C
9.4 C
12.1 C
14.6 C
11.5 C
14.6 C
17.3 C
13.7 C
17.0 C
20.0 C
15.8 C
19.5 C
22.8 C
17.9 C
22.0 C
25.5 C
20.0 C
24.5 C
28.2 C
9.4 C
12.1 C
14.6 C
11.5 C
14.6 C
17.3 C
13.7 C
17.0 C
20.0 C
15.8 C
19.5 C
22.8 C
17.9 C
22.0 C
25.5 C
20.0 C
24.5 C
28.2 C
9.4 C
12.1 C
14.6 C
11.5 C
14.6 C
17.3 C
13.7 C
17.0 C
20.0 C
15.8 C
19.5 C
22.8 C
17.9 C
22.0 C
25.5 C
20.0 C
24.5 C
28.2 C

HR

Total
Cap
(kW)

Sens.
Cap.
(kW)

30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %

58.3
58.3
65.6
57.2
65.0
71.2
62.5
70.4
76.0
67.7
75.1
80.5
72.2
79.8
84.7
59.4
59.4
66.5
59.3
66.0
71.8
64.2
71.2
76.5
68.9
75.8
81.1
73.2
80.5
85.2
60.2
55.9
60.2
67.0
61.0
66.5
72.1
65.8
71.6
76.7
69.7
76.2
81.4
73.9
80.9
85.4
54.0
60.6
57.0
60.6
67.1
62.3
66.7
72.1
66.8
71.7
76.7
70.5
76.3
81.3
74.3
81.0
85.3
52.4
54.0
60.7
57.8
60.8
66.9
63.1
66.6
71.9
67.3
71.6
76.7
71.0
76.1
81.1
74.2
80.7
85.2

34.9
45.1
36.5
57.2
47.5
37.2
61.8
48.8
37.4
64.3
48.9
37.5
65.5
49.0
36.8
36.0
47.3
37.5
59.3
49.6
38.2
64.2
50.5
38.0
67.7
50.3
37.8
68.5
50.1
37.0
36.9
55.9
49.2
38.3
61.0
51.4
39.0
65.8
51.9
38.4
69.7
51.4
37.9
71.1
51.0
39.5
47.7
37.5
57.0
50.8
38.9
62.3
52.8
39.6
66.8
53.0
39.9
70.5
52.3
40.2
73.2
51.6
40.3
52.4
49.0
37.9
57.8
52.2
39.3
63.1
53.9
40.9
67.3
53.8
38.6
71.0
52.9
37.5
74.2
52.0
36.4

Outdoor Air Temperature


35 C

30 C
CMP
(kW)

Total
Cap
(kW)

Sens.
Cap.
(kW)

12.4
12.4
12.7
12.3
12.7
12.9
12.6
12.9
13.1
12.7
13.1
13.4
12.9
13.3
13.6
12.5
12.5
12.7
12.5
12.7
13.0
12.6
12.9
13.2
12.8
13.1
13.4
13.0
13.3
13.7
12.5
12.3
12.5
12.8
12.6
12.8
13.0
12.7
13.0
13.2
12.9
13.2
13.5
13.0
13.4
13.7
12.3
12.6
12.4
12.6
12.8
12.6
12.8
13.1
12.8
13.0
13.3
12.9
13.2
13.5
13.1
13.4
13.8
12.3
12.3
12.6
12.5
12.6
12.9
12.7
12.8
13.1
12.8
13.0
13.3
13.0
13.3
13.6
13.1
13.5
13.8

54.8
54.8
62.1
54.4
61.4
68.4
59.0
67.5
73.5
64.5
72.5
78.2
69.4
77.1
82.5
55.8
55.8
63.1
56.3
62.5
69.1
61.2
68.3
74.1
65.8
73.2
78.5
70.5
78.1
83.0
56.4
52.9
56.4
63.7
57.9
63.1
69.4
63.0
68.7
74.2
67.2
73.6
79.0
71.3
78.1
83.1
56.7
53.9
56.7
63.9
59.1
63.4
69.3
64.1
68.8
74.2
68.2
73.6
79.0
71.7
78.1
83.1
50.5
56.7
54.6
56.9
63.8
60.0
63.3
69.1
64.8
68.7
73.9
68.7
73.5
78.7
72.1
78.2
82.8

33.0
43.2
34.7
54.4
45.6
35.7
59.0
47.5
36.1
63.0
48.0
36.2
64.7
47.7
35.8
34.0
45.3
35.8
56.3
47.9
36.7
61.2
49.5
37.1
65.8
49.6
36.6
68.1
49.8
36.1
34.9
52.9
47.2
36.7
57.9
49.9
37.5
63.0
51.1
37.3
67.2
50.9
37.0
71.0
50.1
38.3
35.5
53.9
48.8
37.3
59.1
51.5
37.9
64.1
52.4
37.5
68.2
52.0
37.0
71.7
50.8
35.9
47.0
35.9
54.6
50.2
37.7
60.0
52.8
38.0
64.8
53.4
37.4
68.7
52.7
36.7
72.1
51.9
35.6

CMP
(kW)

Total
Cap
(kW)

Sens.
Cap.
(kW)

13.7
13.7
14.0
13.6
14.0
14.3
13.9
14.3
14.6
14.1
14.5
14.8
14.3
14.7
15.1
13.8
13.8
14.1
13.8
14.1
14.4
14.0
14.3
14.6
14.2
14.6
14.9
14.4
14.8
15.1
13.8
13.6
13.8
14.1
13.9
14.1
14.4
14.1
14.4
14.7
14.3
14.6
14.9
14.4
14.9
15.2
13.9
13.7
13.9
14.2
14.0
14.2
14.5
14.2
14.4
14.7
14.4
14.6
15.0
14.5
14.9
15.3
13.6
13.9
13.8
13.9
14.2
14.1
14.2
14.5
14.3
14.4
14.8
14.4
14.7
15.0
14.6
14.9
15.3

51.1
51.1
58.1
51.4
57.4
65.1
55.9
64.0
70.6
60.6
69.4
75.4
66.1
74.2
79.9
51.9
51.9
59.1
53.2
58.4
65.9
58.1
64.8
71.2
62.9
70.1
75.7
67.4
74.9
80.3
52.4
49.8
52.5
59.8
54.7
59.1
66.2
59.8
65.3
71.2
64.4
70.5
75.8
68.3
75.1
80.4
52.6
50.6
52.7
60.0
55.8
59.4
66.2
61.0
65.4
71.3
65.4
70.5
76.1
69.2
75.2
80.3
52.6
51.2
52.8
60.0
56.6
59.4
65.9
61.7
65.3
71.0
66.0
70.4
75.8
69.7
74.9
80.0

31.0
41.2
32.8
51.4
43.6
34.1
55.9
45.8
34.6
60.6
46.9
34.9
63.6
46.8
34.7
32.0
43.3
33.9
53.2
45.9
35.1
58.1
48.0
35.7
62.9
48.7
35.3
67.3
48.3
35.0
32.8
49.8
45.1
34.8
54.7
47.9
36.0
59.8
49.9
36.2
64.4
50.2
36.6
68.3
49.5
37.0
33.4
50.6
46.7
35.4
55.8
49.6
36.6
61.0
51.4
37.2
65.4
51.5
36.0
69.2
50.4
37.8
33.8
51.2
48.1
35.9
56.6
51.1
36.8
61.7
52.6
38.8
66.0
52.4
35.9
69.7
51.1
34.7

40 C

CMP
(kW)

Total
Cap
(kW)

Sens.
Cap.
(kW)

15.1
15.1
15.5
15.1
15.4
15.8
15.3
15.8
16.1
15.6
16.0
16.4
15.8
16.3
16.7
15.2
15.2
15.5
15.2
15.5
15.9
15.5
15.8
16.2
15.7
16.1
16.5
15.9
16.4
16.8
15.2
15.1
15.2
15.6
15.3
15.6
15.9
15.6
15.9
16.2
15.8
16.1
16.5
16.0
16.4
16.8
15.3
15.2
15.3
15.7
15.4
15.6
16.0
15.7
15.9
16.3
15.9
16.2
16.6
16.1
16.5
16.9
15.3
15.2
15.3
15.7
15.5
15.7
16.0
15.8
16.0
16.3
16.0
16.2
16.6
16.2
16.5
16.9

47.2
47.2
54.0
48.3
53.3
61.3
52.8
59.9
67.2
57.4
65.9
72.2
62.4
70.9
47.9
47.9
54.9
50.0
54.2
62.1
54.8
60.8
67.8
59.6
66.6
72.5
64.0
71.5
77.2
48.3
46.4
48.4
55.4
51.3
54.7
62.5
56.3
61.3
68.0
61.2
66.9
72.7
65.4
71.8
77.4
48.4
47.2
48.6
55.6
52.3
55.0
62.5
57.5
61.5
67.8
62.3
67.0
72.5
66.3
71.8
77.2
48.2
47.7
48.6
55.6
53.0
55.1
62.3
58.3
61.4
67.5
62.9
66.8
66.8
71.6
76.9

29.0
39.1
30.7
48.3
41.6
32.3
52.8
43.9
33.1
57.4
45.5
33.4
62.2
45.8
29.9
41.2
31.8
50.0
43.8
33.4
54.8
46.3
34.1
59.6
47.5
34.1
64.0
47.5
33.9
30.7
46.4
43.0
32.7
51.3
45.8
34.2
56.3
48.3
35.0
61.2
49.2
34.5
65.4
48.9
34.0
31.3
47.2
44.6
33.3
52.3
47.6
34.9
57.5
50.0
35.2
62.3
50.7
35.8
66.3
49.9
36.5
31.6
47.7
46.1
33.8
53.0
49.1
35.3
58.3
51.4
35.4
62.9
51.8
66.8
50.8
33.7

45 C
CMP
(kW)

Total
Cap
(kW)

Sens.
Cap.
(kW)

CMP
(kW)

16.6
16.6
17.0
16.6
17.0
17.4
16.9
17.3
17.8
17.2
17.7
18.1
17.5
18.0
16.7
16.7
17.1
16.8
17.1
17.5
17.1
17.4
17.8
17.3
17.7
18.2
17.6
18.0
18.5
16.7
16.6
16.7
17.2
16.9
17.1
17.6
17.2
17.5
17.9
17.5
17.8
18.2
17.7
18.1
18.5
16.8
16.7
16.8
17.2
17.0
17.2
17.6
17.3
17.5
17.9
17.6
17.8
18.3
17.8
18.2
18.6
16.9
16.8
16.9
17.3
17.1
17.2
17.6
17.4
17.6
18.0
17.6
17.9
17.9
18.2
18.7

43.1
43.2
49.6
45.0
49.0
56.8
49.5
55.4
63.4
54.0
61.9
68.7
58.6
67.2
43.7
43.8
50.4
46.6
49.8
57.6
51.3
56.3
64.0
56.1
62.6
69.1
60.7
67.8
43.9
43.0
44.2
50.8
47.8
50.2
58.1
52.7
56.8
64.2
57.7
62.9
69.0
62.2
68.0
43.9
43.6
44.4
50.9
48.6
50.4
58.2
53.8
57.0
64.0
58.8
62.9
68.9
63.1
68.0
43.7
44.0
44.4
50.8
49.2
50.5
58.0
54.5
57.0
63.7
59.5
62.7
63.6
67.8
-

26.9
37.0
28.7
45.0
39.5
30.3
49.5
41.9
31.4
54.0
43.9
31.9
58.6
44.6
27.8
39.1
29.7
46.6
41.7
31.4
51.3
44.2
32.5
56.1
46.1
33.0
60.7
46.5
28.5
43.0
40.9
30.5
47.8
43.7
32.3
52.7
46.3
33.3
57.7
48.0
33.2
62.2
48.0
29.1
43.6
42.5
31.2
48.6
45.4
33.0
53.8
48.2
33.8
58.8
49.6
33.4
63.1
49.3
29.4
44.0
44.0
31.6
49.2
47.0
33.5
54.5
49.8
34.1
59.5
50.9
63.6
50.3
-

18.2
18.2
18.7
18.3
18.6
19.1
18.7
19.0
19.5
18.9
19.4
19.9
19.2
19.8
18.3
18.3
18.8
18.5
18.7
19.2
18.8
19.1
19.6
19.1
19.5
20.0
19.4
19.8
18.4
18.3
18.4
18.8
18.6
18.8
19.3
18.9
19.2
19.7
19.2
19.6
20.0
19.5
19.9
18.4
18.4
18.4
18.9
18.7
18.9
19.3
19.1
19.3
19.7
19.3
19.6
20.1
19.6
19.9
18.5
18.5
18.5
18.9
18.8
18.9
19.4
19.2
19.3
19.8
19.4
19.6
19.7
20.0
-

Note: All capacities are gross cooling values and do not include indoor fan heat. To obtain net cooling, subtract indoor fan heat.

RT-PRC014-E4

19

Performance Data
Table 8 - TK* 265 Gross Cooling Capacities (kW)
Outdoor Air Temperature
25 C
Indoor
Airflow
m3/h

Entering
Dry
bulb
18 C
21 C

11520

24 C
27 C
30 C
33 C
18 C
21 C

12960

24 C
27 C
30 C
33 C
18 C
21 C

14400

24 C
27 C
30 C
33 C
18 C
21 C

15840

24 C
27 C
30 C
33 C
18 C
21 C

17280

24 C
27 C
30 C
33 C

Entering
Wet
bulb
9.4 C
12.1 C
14.6 C
11.5 C
14.6 C
17.3 C
13.7 C
17.0 C
20.0 C
15.8 C
19.5 C
22.8 C
17.9 C
22.0 C
25.5 C
20.0 C
24.5 C
28.2 C
9.4 C
12.1 C
14.6 C
11.5 C
14.6 C
17.3 C
13.7 C
17.0 C
20.0 C
15.8 C
19.5 C
22.8 C
17.9 C
22.0 C
25.5 C
20.0 C
24.5 C
28.2 C
9.4 C
12.1 C
14.6 C
11.5 C
14.6 C
17.3 C
13.7 C
17.0 C
20.0 C
15.8 C
19.5 C
22.8 C
17.9 C
22.0 C
25.5 C
20.0 C
24.5 C
28.2 C
9.4 C
12.1 C
14.6 C
11.5 C
14.6 C
17.3 C
13.7 C
17.0 C
20.0 C
15.8 C
19.5 C
22.8 C
17.9 C
22.0 C
25.5 C
20.0 C
24.5 C
28.2 C
9.4 C
12.1 C
14.6 C
11.5 C
14.6 C
17.3 C
13.7 C
17.0 C
20.0 C
15.8 C
19.5 C
22.8 C
17.9 C
22.0 C
25.5 C
20.0 C
24.5 C
28.2 C

HR
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %

Total
Cap.
(kW)
61.6
64.5
68.2
66.0
69.9
74.2
70.6
75.3
80.4
75.4
81.0
86.9
80.2
86.8
93.6
85.0
93.0
100.2
63.0
66.0
69.8
67.5
71.5
75.9
72.3
77.1
82.3
77.2
82.9
88.9
82.1
88.8
95.7
87.0
95.1
102.5
64.2
67.2
71.1
68.8
72.8
77.3
73.6
78.5
83.8
78.6
84.4
90.6
83.6
90.5
97.5
88.6
96.9
104.4
65.2
68.3
72.2
69.9
73.9
78.5
74.8
79.7
85.1
79.8
85.7
92.0
84.9
91.9
99.0
90.0
98.4
106.0
66.0
69.1
73.1
70.8
74.9
79.5
75.7
80.8
86.2
80.9
86.8
93.2
86.0
93.1
100.3
91.1
99.7
107.4

Sens.
Cap.
(kW)
61.6
53.8
40.0
66.0
55.5
39.6
70.6
56.5
38.5
75.4
57.0
37.1
79.6
57.0
34.8
82.7
56.5
32.9
63.0
55.1
40.9
67.5
56.7
40.5
72.3
57.8
39.4
77.2
58.3
38.0
81.5
58.3
35.6
84.6
57.8
33.7
64.2
56.1
41.7
68.8
57.8
41.3
73.6
58.9
40.1
78.6
59.4
38.7
83.0
59.4
36.3
86.2
58.9
34.3
65.2
57.0
42.4
69.9
58.7
41.9
74.8
59.8
40.7
79.8
60.3
39.3
84.3
60.3
36.9
87.6
59.8
34.8
66.0
57.7
42.9
70.8
59.5
42.5
75.7
60.6
41.3
80.9
61.1
39.8
85.4
61.1
37.3
88.7
60.6
35.3

30 C
CMP
(kW)
15.6
15.7
16.0
15.8
16.1
16.4
16.1
16.5
16.8
16.5
16.8
17.2
16.8
17.2
17.6
17.1
17.6
17.9
16.0
16.1
16.4
16.2
16.5
16.8
16.5
16.9
17.2
16.9
17.2
17.6
17.2
17.6
18.0
17.5
18.0
18.4
16.3
16.4
16.7
16.5
16.8
17.1
16.8
17.2
17.5
17.2
17.5
17.9
17.5
17.9
18.3
17.8
18.3
18.7
16.6
16.7
17.0
16.8
17.1
17.4
17.1
17.5
17.8
17.5
17.8
18.2
17.8
18.2
18.6
18.1
18.6
19.0
16.8
16.9
17.2
17.0
17.3
17.6
17.3
17.7
18.0
17.7
18.0
18.4
18.0
18.4
18.8
18.3
18.8
19.2

Total
Cap.
(kW)
58.8
61.3
64.8
63.1
66.4
70.5
67.5
71.8
76.4
72.0
77.2
82.7
76.8
82.9
89.1
81.6
88.8
95.8
60.2
62.7
66.3
64.6
67.9
72.2
69.0
73.4
78.1
73.6
79.0
84.6
78.5
84.8
91.2
83.4
90.8
98.0
61.3
63.9
67.5
65.8
69.2
73.5
70.3
74.8
79.6
75.0
80.5
86.2
80.0
86.4
92.9
85.0
92.5
99.8
62.3
64.9
68.6
66.8
70.3
74.7
71.4
76.0
80.8
76.2
81.8
87.6
81.3
87.8
94.4
86.3
93.9
101.4
63.1
65.7
69.4
67.7
71.2
75.6
72.3
76.9
81.9
77.2
82.8
88.7
82.3
88.9
95.6
87.4
95.2
102.7

Sens.
Cap.
(kW)
58.8
52.0
38.2
63.1
53.6
37.8
67.5
54.8
36.8
72.0
55.5
35.4
76.7
55.6
33.4
80.7
55.2
30.9
60.2
53.2
39.1
64.6
54.9
38.7
69.0
56.1
37.6
73.6
56.7
36.2
78.4
56.8
34.2
82.6
56.4
31.6
61.3
54.2
39.8
65.8
55.9
39.4
70.3
57.1
38.3
75.0
57.8
36.9
79.9
57.9
34.8
84.1
57.5
32.2
62.3
55.0
40.4
66.8
56.8
40.0
71.4
58.0
38.9
76.2
58.7
37.5
81.2
58.8
35.3
85.4
58.4
32.7
63.1
55.8
40.9
67.7
57.5
40.5
72.3
58.7
39.4
77.2
59.5
38.0
82.2
59.6
35.8
86.5
59.2
33.1

35 C
CMP
(kW)
17.3
17.5
17.7
17.6
17.8
18.1
17.8
18.2
18.5
18.1
18.5
19.0
18.5
19.0
19.4
18.9
19.4
19.9
17.7
17.9
18.1
18.0
18.2
18.6
18.3
18.7
18.9
18.6
18.9
19.4
18.9
19.4
19.8
19.3
19.8
20.3
18.0
18.2
18.4
18.3
18.5
18.9
18.6
19.0
19.3
18.9
19.3
19.8
19.3
19.8
20.2
19.7
20.2
20.7
18.3
18.5
18.7
18.6
18.8
19.2
18.9
19.3
19.6
19.2
19.6
20.1
19.6
20.1
20.5
20.0
20.5
21.0
18.5
18.7
18.9
18.8
19.0
19.4
19.1
19.5
19.9
19.4
19.9
20.4
19.9
20.4
20.8
20.3
20.8
21.3

Total
Cap.
(kW)
56.1
58.1
61.5
60.3
63.1
67.0
64.5
68.2
72.7
68.7
73.5
78.8
73.3
79.0
85.0
77.9
84.6
91.3
57.4
59.5
62.9
61.7
64.6
68.5
66.0
69.8
74.4
70.3
75.2
80.6
75.0
80.8
87.0
79.7
86.6
93.5
58.5
60.6
64.1
62.8
65.8
69.8
67.2
71.1
75.8
71.6
76.6
82.1
76.4
82.3
88.6
81.2
88.2
95.2
59.4
61.5
65.1
63.8
66.8
70.9
68.3
72.2
77.0
72.7
77.8
83.4
77.6
83.6
90.0
82.5
89.6
96.7
60.2
62.3
65.9
64.6
67.7
71.8
69.1
73.1
78.0
73.7
78.8
84.5
78.6
84.7
91.1
83.5
90.7
97.9

Sens.
Cap.
(kW)
56.1
50.2
36.5
60.3
51.9
36.1
64.5
53.1
35.2
68.7
49.3
33.9
73.3
54.0
32.0
77.8
53.7
29.6
57.4
51.3
37.3
61.7
53.1
36.9
66.0
54.3
36.0
70.3
52.7
34.7
75.0
55.3
32.7
79.6
55.0
30.2
58.5
52.3
38.0
62.8
54.1
37.6
67.2
55.3
36.7
71.6
56.0
35.3
76.4
56.3
33.3
81.1
56.0
30.8
59.4
53.1
38.6
63.8
54.9
38.2
68.3
56.2
37.3
72.7
59.4
35.9
77.6
57.2
33.8
82.4
56.9
31.3
60.2
53.8
39.1
64.6
55.7
38.7
69.1
56.9
37.8
73.7
62.7
36.3
78.6
57.9
34.3
83.4
57.6
31.7

40 C
CMP
(kW)
19.2
19.4
19.7
19.5
19.8
20.1
19.9
20.2
20.5
20.2
21.2
21.0
20.5
21.0
21.6
20.9
21.6
22.1
19.6
19.8
20.1
19.9
20.2
20.5
20.3
20.6
21.0
20.7
21.3
21.5
21.0
21.5
22.1
21.4
22.1
22.6
20.0
20.2
20.5
20.3
20.6
20.9
20.7
21.0
21.4
21.1
21.5
21.9
21.4
21.9
22.5
21.8
22.5
23.0
20.3
20.5
20.8
20.6
20.9
21.2
21.0
21.3
21.7
21.4
21.6
22.2
21.7
22.2
22.9
22.1
22.9
23.4
20.6
20.8
21.1
20.9
21.2
21.5
21.3
21.6
22.0
21.7
21.6
22.5
22.0
22.5
23.1
22.4
23.1
23.7

Total
Cap.
(kW)
53.3
55.1
58.1
57.4
59.7
63.5
61.5
64.7
69.0
65.6
69.8
74.7
69.9
74.9
80.7
74.3
80.4
86.8
54.6
56.4
59.5
58.7
61.1
65.0
62.9
66.2
70.6
67.1
71.4
76.5
71.5
76.7
82.6
76.0
82.3
88.8
55.6
57.4
60.6
59.8
62.2
66.2
64.1
67.4
71.9
68.4
72.7
77.9
72.8
78.1
84.1
77.4
83.8
90.5
56.5
58.3
61.5
60.7
63.2
67.2
65.1
68.5
73.0
69.5
73.8
79.1
73.9
79.3
85.4
78.6
85.1
91.9
57.2
59.0
62.3
61.5
64.0
68.1
65.9
69.3
74.0
70.4
74.8
80.1
74.9
80.3
86.5
79.6
86.2
93.1

Sens.
Cap.
(kW)
53.3
48.4
34.8
57.4
50.1
34.5
61.5
51.3
33.7
65.6
52.1
32.6
69.9
52.4
30.4
74.3
52.4
28.4
54.6
49.5
35.6
58.7
51.2
35.3
62.9
52.5
34.5
67.1
53.3
33.4
71.5
53.6
31.1
76.0
53.6
29.1
55.6
50.4
36.3
59.8
52.2
36.0
64.1
53.5
35.1
68.4
54.3
34.0
72.8
54.6
31.7
77.4
54.6
29.6
56.5
51.2
36.9
60.7
53.0
36.6
65.1
54.3
35.6
69.5
55.2
34.5
73.9
55.5
32.2
78.6
55.5
30.1
57.2
51.8
37.3
61.5
53.7
37.0
65.9
55.0
36.1
70.4
55.9
35.0
74.9
56.2
32.6
79.6
56.2
30.5

45 C
CMP
(kW)
21.4
21.6
21.9
21.8
22.0
22.4
22.2
22.5
22.9
22.5
22.9
23.4
22.9
23.4
24.0
23.4
24.0
24.6
21.9
22.1
22.4
22.3
22.5
22.9
22.7
23.0
23.5
23.1
23.5
24.0
23.5
24.0
24.5
24.0
24.5
25.1
22.3
22.5
22.8
22.7
22.9
23.3
23.1
23.4
23.9
23.5
23.9
24.4
23.9
24.4
25.0
24.4
25.0
25.6
22.6
22.9
23.2
23.1
23.3
23.7
23.5
23.8
24.3
23.9
24.3
24.8
24.3
24.8
25.4
24.8
25.4
26.0
22.9
23.1
23.5
23.4
23.6
24.0
23.8
24.1
24.6
24.2
24.6
25.1
24.6
25.1
25.7
25.1
25.7
26.3

Total
Cap.
(kW)
50.3
51.6
54.7
54.3
56.2
59.8
58.4
60.9
65.2
62.6
65.8
70.8
66.7
70.9
76.6
70.8
76.2
51.4
52.8
56.0
55.6
57.5
61.2
59.8
62.3
66.7
64.0
67.3
72.5
68.2
72.5
72.5
52.4
53.8
57.0
56.6
58.6
62.3
60.9
63.5
67.9
65.2
68.6
69.5
53.2
54.6
57.9
57.5
59.5
63.3
61.9
64.5
69.0
66.2
69.7
70.6
53.9
55.3
58.6
58.2
60.3
64.1
62.6
65.3
67.1
-

Sens.
Cap.
(kW)
50.3
46.4
33.0
54.3
48.2
32.8
58.4
49.5
32.0
62.6
50.6
31.0
66.7
51.0
29.5
70.8
51.0
51.4
47.5
33.8
55.6
49.3
33.6
59.8
50.7
32.8
64.0
51.7
31.7
68.2
52.1
72.5
52.4
48.4
34.4
56.6
50.2
34.2
60.9
51.6
33.4
65.2
52.7
69.5
53.2
49.2
34.9
57.5
51.0
34.7
61.9
52.4
33.9
66.2
53.5
70.6
53.9
49.8
35.4
58.2
51.6
35.2
62.6
53.1
67.1
-

CMP
(kW)
22.3
22.4
22.7
22.6
22.8
23.1
22.9
23.2
23.6
23.4
23.6
23.9
23.6
24.1
24.6
24.0
24.4
25.1
22.9
22.9
23.2
23.1
23.3
23.6
23.4
23.7
24.1
23.9
24.1
24.5
24.1
24.6
25.2
24.5
25.0
23.3
23.4
23.7
23.6
23.8
24.1
23.9
24.2
24.6
24.4
24.6
24.9
24.6
25.1
25.0
23.7
23.8
24.1
24.0
24.2
24.5
24.3
24.6
25.0
24.7
25.0
25.3
25.0
25.5
25.4
24.0
24.1
24.4
24.3
24.5
24.8
24.6
24.9
25.4
25.1
25.4
25.4
-

Note: All capacities are gross cooling values and do not include indoor fan heat. To obtain net cooling, subtract indoor fan heat.

20

RT-PRC014-E4

Performance Data
Table 9 - TK* 290 Gross Cooling Capacities (kW)
Outdoor Air Temperature
25 C
Indoor
Airflow
m3/h

Entering
Dry
bulb
18 C
21 C
24 C

12960
27 C
30 C
33 C
18 C
21 C
24 C
14580
27 C
30 C
33 C
18 C
21 C
24 C
16200
27 C
30 C
33 C
18 C
21 C
24 C
17820
27 C
30 C
33 C
18 C
21 C
24 C
19440
27 C
30 C
33 C

Entering
Wet
bulb
9.4 C
12.1 C
14.6 C
11.5 C
14.6 C
17.3 C
13.7 C
17.0 C
20.0 C
15.8 C
19.5 C
22.8 C
17.9 C
22.0 C
25.5 C
20.0 C
24.5 C
28.2 C
9.4 C
12.1 C
14.6 C
11.5 C
14.6 C
17.3 C
13.7 C
17.0 C
20.0 C
15.8 C
19.5 C
22.8 C
17.9 C
22.0 C
25.5 C
20.0 C
24.5 C
28.2 C
9.4 C
12.1 C
14.6 C
11.5 C
14.6 C
17.3 C
13.7 C
17.0 C
20.0 C
15.8 C
19.5 C
22.8 C
17.9 C
22.0 C
25.5 C
20.0 C
24.5 C
28.2 C
9.4 C
12.1 C
14.6 C
11.5 C
14.6 C
17.3 C
13.7 C
17.0 C
20.0 C
15.8 C
19.5 C
22.8 C
17.9 C
22.0 C
25.5 C
20.0 C
24.5 C
28.2 C
9.4 C
12.1 C
14.6 C
11.5 C
14.6 C
17.3 C
13.7 C
17.0 C
20.0 C
15.8 C
19.5 C
22.8 C
17.9 C
22.0 C
25.5 C
20.0 C
24.5 C
28.2 C

HR
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %

Total
Cap.
(kW)
70.9
75.1
80.5
76.2
81.8
88.1
82.3
88.7
96.2
88.3
96.1
104.7
94.2
103.8
113.2
100.7
111.9
123.3
72.8
77.1
82.6
78.2
83.9
90.5
84.5
91.1
98.8
90.7
98.6
107.5
96.7
106.5
116.2
103.4
114.8
126.6
74.4
78.8
84.5
80.0
85.8
92.5
86.4
93.1
101.0
92.7
100.8
109.9
98.9
108.9
118.8
105.7
117.4
129.4
75.8
80.3
86.1
81.5
87.4
94.2
88.0
94.8
102.9
94.4
102.7
111.9
100.7
110.9
121.0
107.7
119.6
131.8
77.0
81.6
87.5
82.8
88.8
95.7
89.4
96.4
104.5
95.9
104.3
113.8
102.4
112.7
123.0
109.4
121.5
133.9

Sens.
Cap.
(kW)
70.9
61.8
46.8
76.2
63.7
46.6
82.3
65.1
45.9
87.7
65.8
44.1
91.7
66.1
42.1
95.1
65.8
41.4
72.8
63.5
48.0
78.2
65.3
47.8
84.5
66.8
47.1
90.0
67.6
45.3
94.1
67.9
43.2
97.6
67.6
42.4
74.4
64.9
49.1
80.0
66.8
48.9
86.4
68.3
48.2
92.0
69.1
46.3
96.2
69.4
44.2
99.8
69.1
43.4
75.8
66.1
50.0
81.5
68.0
49.8
88.0
69.6
49.1
93.7
70.4
47.2
98.0
70.7
45.0
101.7
70.4
44.2
77.0
67.2
50.8
82.8
69.1
50.6
89.4
70.7
49.9
95.2
71.5
47.9
99.6
71.8
45.7
103.3
71.5
44.9

30 C
CMP
(kW)
20.5
20.9
21.2
21.0
21.3
21.9
21.4
22.0
22.7
21.9
22.7
23.5
22.5
23.4
24.4
23.1
24.3
25.5
21.0
21.4
21.8
21.5
21.9
22.5
22.0
22.6
23.3
22.5
23.3
24.2
23.1
24.1
25.0
23.7
24.9
26.2
21.5
21.9
22.3
22.0
22.4
23.0
22.5
23.1
23.8
23.0
23.8
24.7
23.6
24.6
25.6
24.2
25.5
26.8
21.9
22.3
22.7
22.4
22.8
23.4
22.9
23.5
24.2
23.4
24.2
25.2
24.0
25.1
26.1
24.7
26.0
27.3
22.3
22.7
23.1
22.8
23.2
23.8
23.3
23.9
24.6
23.8
24.6
25.6
24.4
25.5
26.5
25.0
26.4
27.7

Total
Cap.
(kW)
67.7
71.4
76.4
72.9
77.9
83.9
78.3
84.6
91.7
84.3
91.7
99.4
90.3
99.1
108.2
96.3
106.9
118.1
69.4
73.3
78.4
74.8
79.9
86.1
80.4
86.9
94.1
86.6
94.1
102.0
92.7
101.7
111.1
98.9
109.7
121.2
71.0
74.9
80.2
76.5
81.7
88.0
82.2
88.8
96.2
88.5
96.2
104.3
94.8
104.0
113.6
101.1
112.2
123.9
72.3
76.3
81.7
77.9
83.2
89.6
83.7
90.5
98.0
90.1
98.0
106.2
96.6
105.9
115.7
103.0
114.3
126.2
73.5
77.5
83.0
79.2
84.6
91.1
85.1
91.9
99.6
91.6
99.6
108.0
98.1
107.6
117.6
104.6
116.1
128.2

Sens.
Cap.
(kW)
67.7
59.7
44.7
72.9
61.7
44.6
78.3
63.1
43.5
84.3
63.9
42.1
89.4
64.4
41.2
92.8
64.1
40.5
69.4
61.3
45.9
74.8
63.3
45.8
80.4
64.7
44.7
86.6
65.6
43.2
91.7
66.1
42.3
95.3
65.8
41.6
71.0
62.7
46.9
76.5
64.7
46.8
82.2
66.2
45.7
88.5
67.1
44.2
93.8
67.6
43.2
97.4
67.3
42.5
72.3
63.9
47.8
77.9
65.9
47.7
83.7
67.4
46.6
90.1
68.3
45.0
95.5
68.9
44.0
99.2
68.6
43.3
73.5
64.9
48.5
79.2
67.0
48.4
85.1
68.5
47.3
91.6
69.5
45.7
97.1
70.0
44.7
100.8
69.7
44.0

35 C
CMP
(kW)
22.8
23.1
23.4
23.2
23.6
24.1
23.6
24.2
24.9
24.1
24.9
25.7
24.8
25.6
26.7
25.3
26.5
27.9
23.4
23.7
24.1
23.8
24.3
24.7
24.3
24.8
25.5
24.7
25.5
26.4
25.4
26.3
27.4
26.0
27.2
28.7
23.9
24.2
24.6
24.3
24.8
25.3
24.8
25.4
26.1
25.3
26.1
27.0
26.0
26.9
28.0
26.6
27.8
29.3
24.3
24.7
25.1
24.8
25.3
25.8
25.3
25.9
26.6
25.8
26.6
27.5
26.5
27.4
28.5
27.1
28.3
29.8
24.7
25.0
25.5
25.2
25.7
26.2
25.7
26.3
27.0
26.2
27.0
27.9
26.9
27.8
29.0
27.5
28.8
30.3

Total
Cap.
(kW)
64.1
67.3
72.0
69.3
73.6
79.2
74.5
80.1
86.7
80.1
87.0
94.9
86.0
94.1
103.1
92.1
101.7
111.4
65.8
69.1
73.9
71.1
75.5
81.3
76.5
82.3
89.0
82.3
89.3
97.4
88.3
96.6
105.8
94.5
104.4
114.3
67.3
70.6
75.6
72.7
77.2
83.1
78.2
84.1
91.0
84.1
91.3
99.6
90.3
98.8
108.2
96.6
106.7
116.9
68.6
71.9
77.0
74.1
78.6
84.6
79.7
85.7
92.7
85.7
93.0
101.5
92.0
100.6
110.2
98.4
108.7
119.1
69.7
73.1
78.2
75.2
79.9
86.0
80.9
87.0
94.2
87.0
94.5
103.1
93.5
102.3
112.0
100.0
110.4
121.0

Sens.
Cap.
(kW)
64.1
57.5
42.5
69.3
59.5
42.3
74.5
61.1
41.5
80.1
57.4
41.4
85.9
62.4
40.0
90.6
62.6
38.0
65.8
59.0
43.6
71.1
61.0
43.4
76.5
62.7
42.5
82.3
61.2
42.4
88.1
64.1
41.1
93.0
64.3
39.0
67.3
60.3
44.6
72.7
62.4
44.4
78.2
64.1
43.5
84.1
65.1
43.4
90.1
65.5
42.0
95.1
65.7
39.9
68.6
61.4
45.4
74.1
63.6
45.2
79.7
65.3
44.3
85.7
69.0
44.2
91.8
66.7
42.8
96.9
66.9
40.6
69.7
62.4
46.2
75.2
64.6
46.0
80.9
66.3
45.0
87.0
72.9
44.9
93.3
67.8
43.5
98.4
68.0
41.3

40 C
CMP
(kW)
25.2
25.3
25.8
25.5
25.9
26.6
26.0
26.7
27.3
26.6
28.3
28.3
27.3
28.2
29.3
27.9
29.1
30.6
25.8
26.0
26.5
26.2
26.6
27.3
26.7
27.4
28.1
27.3
28.5
29.0
28.0
29.0
30.0
28.7
29.8
31.4
26.4
26.6
27.1
26.8
27.2
27.9
27.3
28.0
28.7
27.9
28.7
29.7
28.6
29.6
30.7
29.3
30.5
32.1
26.9
27.1
27.6
27.3
27.7
28.4
27.8
28.5
29.2
28.4
28.9
30.3
29.1
30.2
31.3
29.8
31.1
32.7
27.3
27.5
28.0
27.7
28.2
28.9
28.3
29.0
29.7
28.9
29.1
30.7
29.6
30.6
31.8
30.3
31.6
33.2

Total
Cap.
(kW)
60.4
63.0
67.3
65.5
69.1
74.1
70.6
75.4
81.7
75.9
82.0
89.3
81.4
88.9
96.8
87.2
96.1
105.9
62.0
64.7
69.1
67.2
70.9
76.1
72.5
77.4
83.8
77.9
84.2
91.6
83.5
91.3
99.4
89.5
98.7
108.7
63.4
66.1
70.6
68.7
72.5
77.8
74.1
79.1
85.7
79.6
86.1
93.7
85.4
93.3
101.6
91.5
100.9
111.1
64.6
67.3
71.9
70.0
73.8
79.2
75.5
80.6
87.3
81.1
87.7
95.4
87.0
95.0
103.5
93.2
102.8
113.2
65.6
68.4
73.1
71.1
75.0
80.5
76.7
81.9
88.7
82.4
89.1
97.0
88.4
96.6
105.2
94.7
104.4
115.0

Sens.
Cap.
(kW)
60.4
55.1
40.2
65.5
57.3
39.9
70.6
59.0
39.9
75.9
60.0
39.3
81.4
60.7
37.0
87.1
60.7
36.9
62.0
56.5
41.3
67.2
58.8
41.0
72.5
60.5
41.0
77.9
61.6
40.3
83.5
62.3
38.0
89.4
62.3
37.9
63.4
57.8
42.2
68.7
60.1
41.9
74.1
61.9
41.9
79.6
63.0
41.2
85.4
63.7
38.8
91.4
63.7
38.7
64.6
58.9
43.0
70.0
61.2
42.7
75.5
63.1
42.7
81.1
64.2
42.0
87.0
64.9
39.5
93.1
64.9
39.4
65.6
59.8
43.7
71.1
62.2
43.4
76.7
64.1
43.4
82.4
65.2
42.6
88.4
65.9
40.2
94.6
65.9
40.1

45 C
CMP
(kW)
27.8
28.1
28.5
28.3
28.7
29.2
28.8
29.3
30.0
29.3
30.1
31.0
30.0
30.9
31.9
30.7
31.9
33.2
28.6
28.9
29.2
29.0
29.4
29.9
29.5
30.1
30.8
30.1
30.9
31.8
30.8
31.7
32.8
31.5
32.8
34.0
29.2
29.5
29.9
29.7
30.1
30.6
30.2
30.8
31.5
30.8
31.6
32.5
31.5
32.4
33.5
32.2
33.5
34.8
29.7
30.0
30.5
30.3
30.7
31.2
30.8
31.4
32.1
31.4
32.2
33.1
32.1
33.0
34.1
32.8
34.1
35.4
30.2
30.5
30.9
30.7
31.2
31.7
31.3
31.9
32.6
31.9
32.7
33.6
32.6
33.5
34.7
33.3
34.7
36.0

Total
Cap.
(kW)
56.5
58.4
62.3
61.5
64.2
69.0
66.5
70.3
75.9
71.6
76.7
83.3
76.7
83.4
91.4
82.0
90.3
58.0
60.0
64.0
63.1
65.9
70.8
68.3
72.2
78.0
73.5
78.7
85.5
78.7
85.6
84.2
92.7
59.3
61.3
65.4
64.5
67.4
72.4
69.8
73.8
79.7
75.1
80.5
87.4
80.5
87.5
86.1
60.4
62.4
66.6
65.7
68.7
73.7
71.1
75.2
81.2
76.5
82.0
82.0
61.4
63.4
67.7
66.8
69.8
74.9
72.2
76.4
82.5
77.7
83.3
83.3
-

Sens.
Cap.
(kW)
56.5
52.5
37.7
61.5
54.9
37.9
66.5
56.8
37.4
71.6
58.0
36.6
76.7
58.6
36.3
82.0
59.0
58.0
53.9
38.7
63.1
56.3
38.9
68.3
58.3
38.4
73.5
59.6
37.6
78.7
60.2
84.2
60.5
59.3
55.1
39.6
64.5
57.6
39.8
69.8
59.6
39.3
75.1
60.9
38.4
80.5
61.5
86.1
60.4
56.1
40.3
65.7
58.7
40.5
71.1
60.7
40.0
76.5
62.0
82.0
61.4
57.0
41.0
66.8
59.6
41.2
72.2
61.7
40.7
77.7
63.0
83.3
-

CMP
(kW)
30.9
31.1
31.4
31.4
31.6
32.2
31.9
32.3
33.0
32.5
33.1
33.9
33.1
34.0
35.2
33.7
34.9
31.7
31.9
32.3
32.2
32.5
33.1
32.8
33.2
33.8
33.4
33.9
34.8
33.9
34.9
34.6
35.8
32.4
32.6
33.0
32.9
33.2
33.8
33.5
33.9
34.6
34.1
34.7
35.6
34.7
35.7
35.4
33.0
33.2
33.6
33.5
33.8
34.4
34.1
34.5
35.2
34.7
35.3
35.3
33.5
33.7
34.2
34.1
34.4
35.0
34.7
35.1
35.8
35.3
35.9
35.9
-

Note: All capacities are gross cooling values and do not include indoor fan heat. To obtain net cooling, subtract indoor fan heat.

RT-PRC014-E4

21

Performance Data
Table 10 - TK* 340 Gross Cooling Capacities (kW)
Outdoor Air Temperature
25 C
Indoor
Airflow
m3/h

Entering
Dry
bulb
18 C
21 C
24 C

14400
27 C
30 C
33 C
18 C
21 C
24 C
16200
27 C
30 C
33 C
18 C
21 C
24 C
18000
27 C
30 C
33 C
18 C
21 C
24 C
19800
27 C
30 C
33 C
18 C
21 C
24 C
21600
27 C
30 C
33 C

Entering
Wet
bulb
9.4 C
12.1 C
14.6 C
11.5 C
14.6 C
17.3 C
13.7 C
17.0 C
20.0 C
15.8 C
19.5 C
22.8 C
17.9 C
22.0 C
25.5 C
20.0 C
24.5 C
28.2 C
9.4 C
12.1 C
14.6 C
11.5 C
14.6 C
17.3 C
13.7 C
17.0 C
20.0 C
15.8 C
19.5 C
22.8 C
17.9 C
22.0 C
25.5 C
20.0 C
24.5 C
28.2 C
9.4 C
12.1 C
14.6 C
11.5 C
14.6 C
17.3 C
13.7 C
17.0 C
20.0 C
15.8 C
19.5 C
22.8 C
17.9 C
22.0 C
25.5 C
20.0 C
24.5 C
28.2 C
9.4 C
12.1 C
14.6 C
11.5 C
14.6 C
17.3 C
13.7 C
17.0 C
20.0 C
15.8 C
19.5 C
22.8 C
17.9 C
22.0 C
25.5 C
20.0 C
24.5 C
28.2 C
9.4 C
12.1 C
14.6 C
11.5 C
14.6 C
17.3 C
13.7 C
17.0 C
20.0 C
15.8 C
19.5 C
22.8 C
17.9 C
22.0 C
25.5 C
20.0 C
24.5 C
28.2 C

HR
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %

Total
Cap.
(kW)
80.4
83.4
88.8
86.5
90.7
96.9
92.5
98.2
105.6
98.8
106.2
114.6
105.4
114.4
124.1
112.1
123.1
133.9
82.3
85.3
90.8
88.5
92.8
99.2
94.7
100.5
108.0
101.0
108.6
117.2
107.8
117.0
127.0
114.7
125.9
137.0
83.8
86.9
92.5
90.1
94.5
101.0
96.4
102.3
110.0
102.9
110.6
119.4
109.8
119.2
129.3
116.8
128.2
139.5
85.1
88.2
93.9
91.5
95.9
102.5
97.9
103.8
111.7
104.4
112.3
121.2
111.5
121.0
131.2
118.6
130.1
141.6
86.2
89.4
95.2
92.7
97.2
103.9
99.2
105.3
113.2
105.9
113.8
122.9
113.0
122.7
133.1
120.2
131.9
143.6

Sens.
Cap.
(kW)
80.4
71.3
54.0
86.5
73.9
54.3
92.5
75.7
53.9
98.8
77.2
52.9
105.3
78.0
51.3
110.9
78.2
49.0
82.3
73.0
55.3
88.5
75.6
55.6
94.7
77.5
55.2
101.0
78.9
54.1
107.7
79.8
52.4
113.4
80.0
50.1
83.8
74.3
56.3
90.1
77.0
56.6
96.4
78.9
56.2
102.9
80.4
55.1
109.7
81.3
53.4
115.5
81.5
51.0
85.1
75.4
57.1
91.5
78.2
57.5
97.9
80.1
57.0
104.4
81.6
55.9
111.4
82.5
54.2
117.2
82.7
51.8
86.2
76.5
57.9
92.7
79.2
58.2
99.2
81.2
57.8
105.9
82.7
56.7
112.9
83.7
55.0
118.9
83.9
52.5

30 C
CMP
(kW)
21.4
21.6
22.1
21.9
22.3
22.8
22.5
22.9
23.7
23.0
23.8
24.7
23.7
24.7
25.7
24.4
25.6
27.0
21.9
22.1
22.6
22.4
22.8
23.4
23.0
23.5
24.3
23.6
24.4
25.2
24.3
25.2
26.3
24.9
26.2
27.6
22.3
22.5
23.0
22.8
23.2
23.8
23.4
23.9
24.7
24.0
24.8
25.7
24.7
25.7
26.8
25.4
26.7
28.1
22.6
22.8
23.3
23.1
23.5
24.2
23.8
24.3
25.1
24.4
25.2
26.1
25.1
26.1
27.2
25.8
27.1
28.5
22.9
23.2
23.7
23.5
23.9
24.5
24.1
24.6
25.4
24.7
25.5
26.4
25.4
26.4
27.6
26.1
27.5
28.9

Total
Cap.
(kW)
76.6
79.0
84.2
82.5
86.0
92.1
88.6
93.5
100.5
94.6
101.1
109.2
100.8
109.0
118.1
107.4
117.5
127.6
78.4
80.8
86.1
84.4
88.0
94.2
90.6
95.6
102.8
96.8
103.4
111.7
103.1
111.5
120.8
109.9
120.2
130.5
79.8
82.3
87.7
86.0
89.6
95.9
92.3
97.4
104.7
98.6
105.3
113.8
105.0
113.6
123.0
111.9
122.4
132.9
81.0
83.5
89.0
87.3
90.9
97.3
93.7
98.9
106.3
100.1
106.9
115.5
106.6
115.3
124.9
113.6
124.2
134.9
82.1
84.7
90.3
88.5
92.2
98.7
95.0
100.2
107.7
101.5
108.4
117.1
108.1
116.9
126.6
115.2
126.0
136.8

Sens.
Cap.
(kW)
76.6
68.8
51.7
82.5
71.4
52.2
88.6
73.6
51.7
94.6
74.9
50.6
100.8
75.8
49.4
107.3
76.6
47.1
78.4
70.4
52.9
84.4
73.1
53.4
90.6
75.3
52.9
96.8
76.6
51.7
103.1
77.6
50.6
109.8
78.4
48.2
79.8
71.7
53.9
86.0
74.4
54.4
92.3
76.7
53.9
98.6
78.0
52.7
105.0
79.0
51.5
111.8
79.8
49.1
81.0
72.8
54.7
87.3
75.5
55.2
93.7
77.9
54.7
100.1
79.2
53.5
106.6
80.2
52.3
113.5
81.0
49.8
82.1
73.8
55.5
88.5
76.6
56.0
95.0
78.9
55.5
101.5
80.3
54.2
108.1
81.3
53.0
115.1
82.1
50.5

35 C
CMP
(kW)
23.6
23.8
24.3
24.2
24.5
25.1
24.8
25.2
25.9
25.3
26.0
26.9
25.9
26.9
28.0
26.7
27.9
29.3
24.2
24.4
24.8
24.7
25.0
25.6
25.3
25.8
26.5
25.9
26.6
27.5
26.5
27.5
28.7
27.3
28.6
29.9
24.6
24.8
25.3
25.2
25.5
26.1
25.8
26.3
27.0
26.4
27.1
28.0
27.0
28.0
29.2
27.8
29.1
30.5
25.0
25.2
25.7
25.6
25.9
26.5
26.2
26.7
27.4
26.8
27.5
28.4
27.4
28.4
29.6
28.2
29.5
31.0
25.3
25.5
26.0
25.9
26.2
26.9
26.6
27.1
27.8
27.2
27.9
28.8
27.8
28.8
30.0
28.6
29.9
31.4

Total
Cap.
(kW)
72.5
74.5
79.3
78.4
81.2
86.9
84.3
88.2
94.9
90.3
95.7
103.4
96.3
103.4
112.1
102.4
111.4
121.2
74.1
76.2
81.1
80.2
83.1
88.9
86.2
90.2
97.1
92.4
97.9
105.8
98.5
105.8
114.7
104.8
114.0
124.0
75.5
77.6
82.6
81.7
84.6
90.5
87.8
91.9
98.9
94.1
99.7
107.7
100.3
107.7
116.8
106.7
116.1
126.3
76.6
78.8
83.8
82.9
85.9
91.9
89.1
93.3
100.4
95.5
101.2
109.3
101.8
109.3
118.6
108.3
117.8
128.2
77.7
79.9
85.0
84.1
87.1
93.1
90.4
94.6
101.8
96.8
102.6
110.8
103.2
110.8
120.2
109.8
119.5
130.0

Sens.
Cap.
(kW)
72.5
66.3
49.3
78.4
69.0
49.6
84.3
71.0
49.5
90.3
66.6
48.8
96.3
73.7
47.7
102.4
74.6
45.5
74.1
67.9
50.5
80.2
70.6
50.8
86.2
72.7
50.7
92.4
71.2
49.9
98.5
75.4
48.8
104.8
76.3
46.5
75.5
69.1
51.4
81.7
71.9
51.7
87.8
74.0
51.6
94.1
75.7
50.8
100.3
76.8
49.7
106.7
77.7
47.4
76.6
70.1
52.2
82.9
73.0
52.5
89.1
75.1
52.4
95.5
80.2
51.6
101.8
78.0
50.4
108.3
78.9
48.1
77.7
71.1
52.9
84.1
74.0
53.2
90.4
76.2
53.1
96.8
84.8
52.3
103.2
79.0
51.1
109.8
80.0
48.8

40 C
CMP
(kW)
26.0
26.2
26.7
26.6
26.9
27.5
27.3
27.6
28.4
27.9
29.2
29.4
28.6
29.5
30.5
29.4
30.4
31.9
26.6
26.8
27.3
27.2
27.5
28.2
27.9
28.3
29.1
28.6
29.5
30.0
29.3
30.1
31.2
30.0
31.1
32.6
27.1
27.3
27.8
27.7
28.0
28.7
28.4
28.8
29.6
29.1
29.7
30.6
29.8
30.7
31.8
30.6
31.7
33.2
27.5
27.7
28.2
28.1
28.4
29.1
28.8
29.2
30.0
29.5
29.9
31.1
30.2
31.2
32.3
31.1
32.2
33.7
27.9
28.1
28.6
28.5
28.8
29.5
29.2
29.6
30.5
29.9
30.0
31.5
30.7
31.6
32.7
31.5
32.6
34.2

Total
Cap.
(kW)
68.2
69.6
74.2
74.0
76.1
81.5
79.8
82.8
89.3
85.6
89.9
97.3
91.5
97.3
105.8
97.4
105.1
114.5
69.8
71.2
75.9
75.7
77.9
83.4
81.6
84.7
91.3
87.6
92.0
99.6
93.6
99.6
108.2
99.7
107.5
117.1
71.1
72.5
77.3
77.1
79.3
84.9
83.1
86.3
93.0
89.2
93.7
101.4
95.3
101.4
110.2
101.5
109.5
119.3
72.2
73.6
78.5
78.3
80.5
86.2
84.4
87.6
94.4
90.5
95.1
102.9
96.7
102.9
111.9
103.0
111.1
73.2
74.6
79.5
79.3
81.6
87.4
85.5
88.8
95.7
91.8
96.4
104.3
98.1
104.3
113.4
104.5
112.7
-

Sens.
Cap.
(kW)
68.2
63.6
46.8
74.0
66.5
47.1
79.8
68.6
47.1
85.6
70.3
46.5
91.5
71.4
45.8
97.4
72.2
43.7
69.8
65.1
47.9
75.7
68.0
48.2
81.6
70.2
48.2
87.6
71.9
47.5
93.6
73.1
46.8
99.7
73.8
44.7
71.1
66.3
48.8
77.1
69.3
49.1
83.1
71.5
49.1
89.2
73.2
48.4
95.3
74.4
47.7
101.5
75.2
45.5
72.2
67.3
49.5
78.3
70.3
49.8
84.4
72.6
49.8
90.5
74.3
49.1
96.7
75.5
48.4
103.0
76.3
73.2
68.2
50.2
79.3
71.3
50.5
85.5
73.6
50.5
91.8
75.3
49.8
98.1
76.6
49.1
104.5
77.4
-

45 C
CMP
(kW)
28.8
28.9
29.4
29.3
29.6
30.2
29.9
30.3
31.1
30.6
31.2
32.2
31.4
32.2
33.3
32.3
33.2
34.7
29.5
29.6
30.0
29.9
30.2
30.9
30.6
31.0
31.8
31.3
31.9
32.9
32.1
32.9
34.1
33.0
34.0
35.4
30.0
30.1
30.6
30.5
30.8
31.5
31.2
31.6
32.4
31.9
32.5
33.5
32.7
33.5
34.7
33.6
34.6
36.1
30.5
30.6
31.1
31.0
31.3
32.0
31.7
32.1
32.9
32.4
33.0
34.0
33.2
34.0
35.2
34.1
35.1
30.9
31.0
31.5
31.4
31.7
32.4
32.1
32.5
33.3
32.8
33.4
34.5
33.7
34.5
35.7
34.6
35.6
-

Total
Cap.
(kW)
63.7
64.6
68.8
69.3
70.8
75.9
74.9
77.4
83.4
80.7
84.1
91.1
86.5
91.0
92.2
65.2
66.1
70.4
70.9
72.5
77.7
76.6
79.1
85.3
82.6
86.0
88.5
66.4
67.3
71.7
72.2
73.8
79.1
78.0
80.6
86.9
84.1
87.6
67.4
68.3
72.8
73.3
74.9
80.3
79.2
81.8
85.4
68.3
69.3
73.8
74.3
75.9
81.4
80.3
82.9
-

Sens.
Cap.
(kW)
63.7
60.9
44.3
69.3
63.8
44.9
74.9
66.1
45.2
80.7
68.0
44.5
86.5
69.1
92.2
65.2
62.3
45.3
70.9
65.3
46.0
76.6
67.7
46.2
82.6
69.5
88.5
66.4
63.4
46.1
72.2
66.5
46.8
78.0
68.9
47.1
84.1
70.8
67.4
64.4
46.8
73.3
67.5
47.5
79.2
69.9
85.4
68.3
65.2
47.4
74.3
68.4
48.2
80.3
70.9
-

CMP
(kW)
31.9
31.9
32.3
32.4
32.5
33.1
33.1
33.4
34.2
33.8
34.3
35.2
34.6
35.1
35.3
32.6
32.6
33.1
33.2
33.3
33.9
33.9
34.2
35.0
34.6
35.1
35.4
33.2
33.2
33.7
33.8
33.9
34.5
34.5
34.8
35.6
35.2
35.7
33.7
33.7
34.2
34.3
34.4
35.0
35.0
35.3
35.7
34.2
34.2
34.7
34.8
34.9
35.5
35.5
35.8
-

Note: All capacities are gross cooling values and do not include indoor fan heat. To obtain net cooling, subtract indoor fan heat.

22

RT-PRC014-E4

Performance Data
Table 11 - WK* 125 Gross Cooling Capacities (kW)
25 C
Indoor Entering Entering
Airflow
Dry
Wet
m3/h
bulb
bulb
HR
18 C
21 C
24 C
5720
27 C
30 C
33 C
18 C
21 C
24 C
6430
27 C
30 C
33 C
18 C
21 C
24 C
7140
27 C
30 C
33 C
18 C
21 C
24 C
7850
27 C
30 C
33 C
18 C
21 C
24 C
8560
27 C
30 C
33 C

9.4 C
12.1 C
14.6 C
11.5 C
14.6 C
17.3 C
13.7 C
17.0 C
20.0 C
15.8 C
19.5 C
22.8 C
17.9 C
22.0 C
25.5 C
20.0 C
24.5 C
28.2 C
9.4 C
12.1 C
14.6 C
11.5 C
14.6 C
17.3 C
13.7 C
17.0 C
20.0 C
15.8 C
19.5 C
22.8 C
17.9 C
22.0 C
25.5 C
20.0 C
24.5 C
28.2 C
9.4 C
12.1 C
14.6 C
11.5 C
14.6 C
17.3 C
13.7 C
17.0 C
20.0 C
15.8 C
19.5 C
22.8 C
17.9 C
22.0 C
25.5 C
20.0 C
24.5 C
28.2 C
9.4 C
12.1 C
14.6 C
11.5 C
14.6 C
17.3 C
13.7 C
17.0 C
20.0 C
15.8 C
19.5 C
22.8 C
17.9 C
22.0 C
25.5 C
20.0 C
24.5 C
28.2 C
9.4 C
12.1 C
14.6 C
11.5 C
14.6 C
17.3 C
13.7 C
17.0 C
20.0 C
15.8 C
19.5 C
22.8 C
17.9 C
22.0 C
25.5 C
20.0 C
24.5 C
28.2 C

30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %

Total
Cap
(kW)

Sens.
Cap.
(kW)

33.6
33.6
37.5
32.6
37.2
40.2
35.7
39.9
42.2
38.5
42.0
43.9
40.8
44.0
45.2
31.1
34.7
31.0
34.7
38.3
33.8
38.1
40.7
36.9
40.5
42.5
39.4
42.5
44.2
41.6
44.5
45.5
31.9
35.6
32.2
35.6
38.9
35.0
38.8
41.2
37.8
41.1
42.8
40.2
42.9
44.5
42.2
44.8
45.7
32.6
36.4
33.3
36.4
39.4
36.2
39.3
41.5
38.5
41.5
43.3
40.8
43.3
44.7
42.7
45.1
45.9
31.4
33.2
36.9
34.4
37.0
39.7
37.2
39.8
41.8
39.3
41.9
43.5
41.3
43.6
44.9
43.1
45.3
46.0

19.9
25.0
20.8
31.6
26.3
21.0
33.3
26.7
21.1
34.5
26.5
20.8
34.9
26.3
20.2
25.0
20.8
31.0
26.5
21.6
33.8
27.6
21.7
35.5
27.8
21.4
36.4
27.3
21.1
36.5
26.9
21.4
26.3
21.7
32.2
27.8
22.3
35.0
28.8
22.5
37.5
28.7
22.4
38.0
29.6
22.3
37.9
30.6
22.1
27.5
22.5
33.3
29.1
23.0
36.2
29.8
23.1
38.5
29.4
22.2
39.5
28.6
23.0
39.1
27.8
22.9
31.4
28.6
23.2
34.4
30.2
23.5
37.2
30.7
24.5
39.3
30.1
22.4
40.8
29.1
21.6
40.1
28.1
20.8

Outdoor Air Temperature


35 C

30 C
CMP
(kW)

Total
Cap
(kW)

Sens.
Cap.
(kW)

7.9
7.9
8.1
7.9
8.1
8.2
8.0
8.2
8.4
8.1
8.3
8.5
8.3
8.4
8.6
7.8
8.0
7.8
8.0
8.2
7.9
8.1
8.3
8.1
8.3
8.4
8.2
8.4
8.5
8.3
8.5
8.6
7.8
8.0
7.9
8.0
8.2
8.0
8.2
8.3
8.1
8.3
8.4
8.2
8.4
8.5
8.3
8.5
8.6
7.9
8.1
7.9
8.1
8.2
8.0
8.2
8.3
8.2
8.3
8.4
8.3
8.4
8.5
8.4
8.5
8.6
7.8
7.9
8.1
8.0
8.1
8.2
8.1
8.2
8.3
8.2
8.3
8.5
8.3
8.4
8.5
8.4
8.5
8.6

31.5
31.5
35.6
30.6
35.2
39.1
33.6
38.6
41.5
36.8
41.1
43.4
39.5
43.1
45.2
32.5
32.5
36.7
31.8
36.3
39.8
34.8
39.4
42.0
37.9
41.7
40.4
44.1
45.6
33.3
30.4
33.3
37.4
33.1
37.1
40.3
35.9
40.0
42.3
38.8
42.3
44.3
41.1
44.5
45.8
30.4
34.0
31.5
34.0
38.0
34.3
37.8
40.6
37.1
40.5
42.6
39.4
42.7
44.6
41.7
44.8
46.1
30.9
34.7
32.4
34.7
38.4
35.4
38.3
41.0
38.1
40.9
42.9
40.2
43.0
44.8
42.2
45.0
46.3

18.7
23.8
19.7
30.4
25.1
20.2
32.1
26.2
20.3
33.8
26.3
20.5
34.7
25.9
20.0
19.6
25.2
20.6
31.8
26.6
21.0
34.4
27.4
21.1
36.0
27.3
36.6
27.2
20.3
20.4
30.4
26.6
21.4
33.1
28.0
21.8
35.9
28.5
21.5
37.9
28.2
21.1
38.3
27.8
21.7
26.2
21.2
31.5
27.8
22.1
34.3
29.2
22.3
37.1
29.5
21.9
39.4
28.9
21.4
39.8
28.3
20.7
27.3
21.9
32.4
29.0
22.9
35.4
30.3
22.8
38.1
30.4
22.2
40.2
29.6
21.6
41.1
28.8
20.8

CMP
(kW)

Total
Cap
(kW)

Sens.
Cap.
(kW)

8.7
8.7
8.9
8.7
8.9
9.1
8.8
9.1
9.2
9.0
9.2
9.4
9.1
9.3
9.5
8.8
8.8
9.0
8.7
9.0
9.1
8.9
9.1
9.3
9.0
9.2
9.2
9.4
9.5
8.8
8.7
8.8
9.0
8.8
9.0
9.2
8.9
9.2
9.3
9.1
9.3
9.4
9.2
9.4
9.5
8.7
8.9
8.7
8.9
9.1
8.9
9.0
9.2
9.0
9.2
9.3
9.1
9.3
9.4
9.2
9.4
9.6
8.7
8.9
8.8
8.9
9.1
8.9
9.1
9.2
9.1
9.2
9.3
9.2
9.3
9.5
9.3
9.4
9.6

33.2
32.8
37.3
31.3
36.7
40.3
34.5
39.7
42.5
37.6
42.1
44.4
30.1
30.1
34.2
29.9
33.8
38.1
32.5
37.6
40.9
35.7
40.4
38.6
42.7
44.8
30.8
30.8
35.1
31.2
34.7
38.8
33.9
38.3
41.3
36.7
41.0
43.2
39.5
43.2
45.1
31.5
29.5
31.5
35.8
32.3
35.4
39.3
35.1
38.8
41.6
37.8
41.4
43.5
40.2
43.5
45.4
32.1
30.4
32.1
36.5
33.3
36.0
39.7
36.3
39.3
41.9
38.7
41.8
44.0
40.8
44.3
45.6

18.4
23.9
19.3
30.9
25.1
19.5
32.5
25.8
19.7
34.0
25.7
19.4
18.3
23.9
19.3
29.9
25.3
20.1
32.5
26.6
20.3
35.0
27.0
36.2
26.6
19.9
19.1
25.2
20.2
31.2
26.7
20.9
33.9
27.9
21.1
36.7
28.0
20.6
38.2
27.4
20.1
19.8
29.5
26.5
21.0
32.3
28.1
21.6
35.1
29.0
21.5
37.8
28.9
21.6
39.9
28.1
21.8
20.5
30.4
27.7
21.7
33.3
29.3
22.3
36.3
30.1
21.9
38.7
29.8
21.3
40.8
29.4
20.6

40 C

CMP
(kW)

Total
Cap
(kW)

Sens.
Cap.
(kW)

9.8
9.8
10.1
9.7
10.0
10.2
9.9
10.2
10.4
10.1
10.3
10.5
9.7
9.7
9.9
9.6
9.9
10.1
9.8
10.1
10.3
10.0
10.2
10.1
10.4
10.5
9.7
9.7
9.9
9.7
9.9
10.1
9.9
10.1
10.3
10.0
10.3
10.4
10.2
10.4
10.5
9.7
9.6
9.7
10.0
9.8
9.9
10.2
9.9
10.1
10.3
10.1
10.3
10.4
10.2
10.4
10.6
9.8
9.7
9.8
10.0
9.8
10.0
10.2
10.0
10.2
10.3
10.1
10.3
10.5
10.2
10.5
10.6

30.6
30.2
34.9
29.0
34.1
38.5
32.0
37.7
41.1
35.2
40.5
43.2
31.5
27.9
31.1
35.9
30.5
35.1
39.2
33.1
38.5
41.6
36.5
41.1
44.1
28.2
28.2
32.3
29.1
31.9
36.7
31.8
35.9
39.7
34.6
39.1
41.9
37.2
41.7
44.0
28.8
28.8
33.0
30.1
32.6
37.2
33.0
36.6
40.1
35.9
39.6
42.2
38.3
42.1
44.3
29.3
28.2
29.4
33.6
31.1
33.2
37.6
34.0
37.1
40.4
36.9
40.1
42.4
39.2
42.4
44.5

17.1
22.5
18.1
29.0
23.8
18.6
31.3
24.9
18.7
32.9
25.2
18.7
18.0
27.9
24.0
19.0
30.5
25.4
19.4
33.1
26.3
19.5
35.4
26.3
19.7
17.7
23.8
18.8
29.1
25.4
19.8
31.8
26.8
20.2
34.6
27.5
20.0
37.2
27.2
19.7
18.4
25.1
19.6
30.1
26.7
20.5
33.0
28.1
20.9
35.9
28.6
20.4
38.3
28.1
19.9
19.1
28.2
26.2
20.3
31.1
27.9
21.3
34.0
29.4
21.3
36.9
29.6
20.8
39.2
28.9
20.2

45 C
CMP
(kW)

Total
Cap
(kW)

Sens.
Cap.
(kW)

CMP
(kW)

10.8
10.8
11.1
10.7
11.0
11.3
10.9
11.2
11.4
11.1
11.4
11.6
10.9
10.6
10.8
11.1
10.8
11.1
11.3
11.0
11.3
11.5
11.1
11.4
11.6
10.7
10.7
10.9
10.7
10.9
11.2
10.9
11.1
11.3
11.0
11.3
11.5
11.2
11.5
11.6
10.7
10.7
11.0
10.8
10.9
11.2
11.0
11.2
11.4
11.1
11.3
11.5
11.2
11.5
11.7
10.7
10.7
10.7
11.0
10.8
11.0
11.2
11.0
11.2
11.4
11.2
11.4
11.5
11.3
11.5
11.7

27.9
27.5
32.0
26.9
31.2
36.3
29.4
35.2
39.3
32.5
38.4
41.5
28.7
28.3
32.9
28.3
32.1
37.0
30.9
36.1
39.8
33.6
39.1
42.6
29.4
26.8
29.0
33.7
29.5
32.9
37.6
32.3
36.7
40.2
35.1
39.6
26.0
26.0
30.0
27.8
29.6
34.4
30.6
33.5
38.0
33.5
37.3
40.6
36.3
40.1
26.4
25.8
26.6
30.5
28.7
30.2
35.0
31.6
34.1
38.4
34.6
37.7
40.8
37.3
40.5
42.9

15.8
21.2
16.7
26.9
22.5
17.5
29.4
23.7
17.9
31.6
24.4
18.3
16.6
22.6
17.6
28.3
24.0
18.4
30.9
25.2
18.6
33.6
25.7
18.9
17.4
26.8
23.9
18.5
29.5
25.4
19.2
32.3
26.6
19.4
35.1
26.8
17.0
23.6
18.2
27.8
25.2
19.3
30.6
26.8
19.9
33.5
27.9
20.2
36.3
27.8
17.6
25.8
24.8
18.9
28.7
26.5
20.0
31.6
28.1
20.6
34.6
29.1
20.2
37.3
28.7
19.7

11.9
11.9
12.2
11.8
12.1
12.4
12.0
12.3
12.6
12.2
12.5
12.7
12.0
11.9
12.2
11.9
12.2
12.4
12.1
12.4
12.6
12.2
12.6
12.8
12.0
11.8
12.0
12.2
12.0
12.2
12.5
12.2
12.4
12.7
12.3
12.6
11.8
11.8
12.0
11.9
12.0
12.3
12.1
12.2
12.5
12.2
12.5
12.7
12.4
12.6
11.8
11.8
11.8
12.1
11.9
12.0
12.3
12.1
12.3
12.5
12.3
12.5
12.7
12.4
12.7
12.9

Note: All capacities are gross cooling values and do not include indoor fan heat. To obtain net cooling, subtract indoor fan heat.

RT-PRC014-E4

23

Performance Data
Table 12 - WK* 155 Gross Cooling Capacities (kW)
25 C
Indoor Entering Entering
Airflow
Dry
Wet
m3/h
bulb
bulb
18 C
21 C
24 C
6800
27 C
30 C
33 C
18 C
21 C
24 C
7650
27 C
30 C
33 C
18 C
21 C
24 C
8500
27 C
30 C
33 C
18 C
21 C
24 C
9350
27 C
30 C
33 C
18 C
21 C
24 C
10200
27 C
30 C
33 C

9.4 C
12.1 C
14.6 C
11.5 C
14.6 C
17.3 C
13.7 C
17.0 C
20.0 C
15.8 C
19.5 C
22.8 C
17.9 C
22.0 C
25.5 C
20.0 C
24.5 C
28.2 C
9.4 C
12.1 C
14.6 C
11.5 C
14.6 C
17.3 C
13.7 C
17.0 C
20.0 C
15.8 C
19.5 C
22.8 C
17.9 C
22.0 C
25.5 C
20.0 C
24.5 C
28.2 C
9.4 C
12.1 C
14.6 C
11.5 C
14.6 C
17.3 C
13.7 C
17.0 C
20.0 C
15.8 C
19.5 C
22.8 C
17.9 C
22.0 C
25.5 C
20.0 C
24.5 C
28.2 C
9.4 C
12.1 C
14.6 C
11.5 C
14.6 C
17.3 C
13.7 C
17.0 C
20.0 C
15.8 C
19.5 C
22.8 C
17.9 C
22.0 C
25.5 C
20.0 C
24.5 C
28.2 C
9.4 C
12.1 C
14.6 C
11.5 C
14.6 C
17.3 C
13.7 C
17.0 C
20.0 C
15.8 C
19.5 C
22.8 C
17.9 C
22.0 C
25.5 C
20.0 C
24.5 C
28.2 C

HR

Total
Cap
(kW)

Sens.
Cap.
(kW)

30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %

40.6
40.6
45.6
39.3
45.3
49.1
43.1
48.7
51.8
46.8
51.4
54.0
49.8
53.7
55.9
37.5
42.0
37.1
42.0
46.7
40.8
46.4
49.9
44.7
49.6
52.4
48.0
52.2
54.5
50.8
54.8
56.4
38.5
43.2
38.7
43.2
47.5
42.0
47.3
50.5
45.9
50.3
52.7
49.0
52.8
55.0
51.6
55.2
56.8
39.4
44.2
40.0
44.2
48.2
43.5
48.0
51.0
46.9
50.9
53.1
49.8
53.2
55.3
52.3
55.6
57.0
37.8
40.2
45.0
41.3
45.0
48.7
44.9
48.6
51.3
47.7
51.4
53.4
50.4
53.7
55.6
52.8
55.9
57.3

24.0
30.0
25.2
37.6
31.6
25.5
39.7
32.4
25.5
41.4
32.3
25.3
42.1
31.8
25.0
29.9
25.1
37.1
31.8
26.1
40.2
33.3
26.4
42.5
33.7
26.7
43.7
33.4
26.0
44.1
33.0
25.4
31.4
26.2
38.7
33.4
27.0
42.0
34.7
27.2
44.8
34.8
26.8
45.7
36.3
26.3
45.8
37.8
26.8
32.8
27.1
40.0
34.9
27.8
43.5
35.9
28.0
46.9
35.8
27.3
47.5
34.9
26.6
47.4
34.2
27.7
37.8
34.2
27.9
41.3
36.3
28.6
44.9
37.0
28.2
47.7
36.6
27.5
49.2
35.7
26.8
48.7
34.7
26.0

Outdoor Air Temperature


35 C

30 C
CMP
(kW)

Total
Cap
(kW)

Sens.
Cap.
(kW)

10.0
10.0
10.3
10.0
10.2
10.4
10.1
10.4
10.5
10.3
10.5
10.6
10.4
10.5
10.6
9.9
10.1
9.9
10.1
10.3
10.0
10.3
10.4
10.2
10.4
10.5
10.3
10.5
10.6
10.4
10.6
10.7
9.9
10.2
9.9
10.1
10.3
10.1
10.3
10.4
10.3
10.4
10.5
10.4
10.5
10.6
10.4
10.6
10.7
10.0
10.2
10.0
10.2
10.4
10.2
10.3
10.5
10.3
10.4
10.5
10.4
10.5
10.6
10.5
10.6
10.7
9.9
10.0
10.2
10.1
10.2
10.4
10.2
10.4
10.5
10.3
10.5
10.6
10.4
10.5
10.6
10.5
10.6
10.7

38.2
38.2
43.3
37.0
42.8
47.7
40.7
47.1
50.8
44.7
50.2
53.3
48.2
52.8
55.3
39.4
39.4
44.7
38.3
44.2
48.6
42.2
48.1
51.5
46.1
51.1
53.8
49.3
53.5
55.8
36.0
40.5
36.6
40.5
45.7
39.9
45.3
49.3
43.3
48.9
52.0
47.2
51.7
54.1
50.2
54.6
56.2
36.8
41.4
37.9
41.4
46.4
41.4
46.1
49.8
44.9
49.5
52.3
48.2
52.3
54.7
50.9
55.0
56.6
37.5
42.2
39.1
42.2
47.0
42.7
46.7
50.2
46.1
50.1
52.6
48.7
52.7
55.0
51.6
55.4
56.8

22.7
28.6
23.9
36.3
30.3
24.6
38.4
31.5
24.7
40.4
31.9
24.6
41.6
31.6
24.3
23.7
30.3
25.0
38.3
32.1
25.5
41.1
33.1
25.6
43.0
33.1
25.5
43.9
32.5
25.0
30.0
24.7
36.6
31.9
26.0
39.9
33.7
26.4
43.3
34.4
26.5
45.3
34.1
25.9
45.9
33.9
25.2
31.4
25.6
37.9
33.4
26.8
41.4
35.1
27.2
44.9
35.6
26.7
47.4
35.0
26.3
47.7
34.5
25.5
32.7
26.5
39.1
34.8
27.6
42.7
36.4
27.8
46.1
36.6
27.1
48.7
35.8
26.5
49.3
35.1
25.7

CMP
(kW)

Total
Cap
(kW)

Sens.
Cap.
(kW)

11.1
11.1
11.3
11.0
11.3
11.5
11.2
11.4
11.6
11.4
11.6
11.7
11.5
11.6
11.8
11.1
11.1
11.4
11.1
11.3
11.5
11.3
11.5
11.6
11.4
11.6
11.7
11.5
11.7
11.8
10.9
11.2
11.0
11.2
11.4
11.1
11.4
11.5
11.3
11.5
11.6
11.4
11.6
11.7
11.5
11.7
11.8
11.0
11.2
11.0
11.2
11.4
11.2
11.4
11.6
11.4
11.5
11.7
11.5
11.6
11.7
11.6
11.7
11.8
11.0
11.3
11.1
11.3
11.4
11.3
11.4
11.6
11.4
11.6
11.7
11.5
11.7
11.8
11.6
11.8
11.8

35.5
35.5
40.5
40.0
45.6
38.1
44.9
49.2
42.0
48.5
52.0
45.9
51.4
54.3
36.7
36.7
41.8
36.1
41.3
46.6
39.3
45.9
50.0
43.5
49.4
52.6
47.2
52.2
37.6
37.6
42.9
37.7
42.4
47.4
41.0
46.8
50.6
44.9
50.1
52.9
48.2
52.8
55.2
38.5
35.6
38.5
43.9
39.0
43.3
48.0
42.5
47.5
51.0
45.8
50.7
53.3
49.1
53.3
55.6
34.7
39.2
36.7
39.2
44.7
40.3
44.2
48.5
43.9
48.1
51.3
47.0
51.2
53.5
49.8
53.7
55.8

21.2
27.2
22.4
28.8
23.5
37.0
30.3
23.8
39.0
31.2
23.8
40.8
31.1
23.6
22.2
28.8
23.5
36.1
30.6
24.4
39.3
32.1
24.7
41.8
32.5
24.7
43.3
32.2
23.2
30.3
24.5
37.7
32.2
25.4
41.0
33.5
25.6
44.5
33.7
25.2
45.6
33.1
24.7
24.1
35.6
31.8
25.5
39.0
33.7
26.2
42.5
34.9
26.4
45.8
34.8
25.7
47.6
34.0
25.0
31.1
24.9
36.7
33.2
26.4
40.3
35.2
27.0
43.9
36.1
26.6
47.0
35.8
25.9
49.4
34.7
25.2

40 C

CMP
(kW)

Total
Cap
(kW)

Sens.
Cap.
(kW)

12.2
12.2
12.4
12.4
12.7
12.3
12.6
12.8
12.5
12.8
12.9
12.7
12.9
13.0
12.3
12.3
12.5
12.2
12.5
12.7
12.4
12.7
12.8
12.6
12.8
12.9
12.7
12.9
12.3
12.3
12.6
12.3
12.5
12.7
12.5
12.7
12.8
12.6
12.8
12.9
12.7
12.9
13.0
12.3
12.2
12.3
12.6
12.4
12.6
12.7
12.5
12.7
12.9
12.7
12.8
12.9
12.8
12.9
13.0
12.1
12.4
12.3
12.4
12.6
12.4
12.6
12.8
12.6
12.7
12.9
12.7
12.8
13.0
12.8
12.9
13.0

32.7
32.7
37.5
37.0
42.8
35.1
41.8
47.1
39.1
46.2
50.2
43.2
49.4
52.7
33.7
33.7
38.7
33.8
38.2
44.1
36.9
43.1
48.0
40.6
47.1
50.8
44.6
50.2
34.6
34.6
39.7
35.2
39.2
44.9
38.6
44.2
48.6
41.9
47.9
51.3
45.7
50.9
35.3
33.2
35.3
40.5
36.5
40.0
45.6
40.0
44.9
49.1
43.6
48.5
51.5
46.5
51.4
54.0
36.0
34.2
36.0
41.3
37.7
40.8
46.2
41.3
45.5
49.4
44.8
49.0
51.8
47.6
51.8
54.3

19.6
25.6
20.9
27.3
22.1
35.1
28.9
22.7
37.5
30.1
22.8
39.5
30.4
22.7
20.6
27.2
22.0
33.8
29.0
23.2
36.9
30.7
23.6
40.3
31.6
24.0
42.3
31.6
21.6
28.7
23.0
35.2
30.6
24.1
38.6
32.3
24.5
41.9
33.0
24.6
44.8
32.7
22.4
33.2
30.2
23.9
36.5
32.1
25.0
40.0
33.8
25.4
43.6
34.3
24.8
46.5
33.7
24.4
23.2
34.2
31.5
24.7
37.7
33.6
25.8
41.3
35.2
25.9
44.8
35.4
25.3
47.6
34.6
24.7

45 C
CMP
(kW)

Total
Cap
(kW)

Sens.
Cap.
(kW)

CMP
(kW)

13.4
13.4
13.7
13.7
13.9
13.6
13.9
14.1
13.8
14.0
14.2
13.9
14.1
14.3
13.5
13.5
13.7
13.5
13.7
14.0
13.7
13.9
14.1
13.8
14.1
14.2
14.0
14.2
13.5
13.5
13.8
13.6
13.8
14.0
13.7
14.0
14.1
13.9
14.1
14.2
14.0
14.2
13.6
13.5
13.6
13.8
13.6
13.8
14.0
13.8
14.0
14.1
13.9
14.1
14.2
14.0
14.2
14.3
13.6
13.5
13.6
13.9
13.7
13.8
14.0
13.9
14.0
14.2
14.0
14.1
14.2
14.1
14.2
14.3

34.3
33.8
39.4
32.7
38.4
44.5
36.1
43.4
48.0
39.9
47.0
50.6
30.5
30.5
35.3
31.3
34.9
40.6
34.4
39.6
45.4
37.6
44.3
48.6
41.4
47.8
31.3
31.3
36.2
32.7
35.7
41.6
35.9
40.6
46.1
39.3
45.1
49.1
42.7
48.5
31.9
30.5
32.0
37.0
33.9
36.5
42.5
37.3
41.4
46.6
40.8
45.8
49.5
44.1
49.0
32.5
31.5
32.6
37.7
35.0
37.2
43.2
38.5
42.2
47.0
42.2
46.3
49.7
45.3
49.5
-

19.3
25.7
20.5
32.7
27.3
21.4
36.0
28.7
21.7
38.0
29.4
21.7
19.0
25.5
20.3
31.3
27.3
21.6
34.4
29.0
22.4
37.6
30.5
22.7
40.9
30.9
19.9
27.0
21.3
32.7
28.9
22.6
35.9
30.7
23.3
39.3
32.0
23.6
42.7
32.1
20.7
30.5
28.5
22.2
33.9
30.4
23.5
37.3
32.3
24.2
40.8
33.4
24.4
44.1
33.2
21.5
31.5
29.8
23.0
35.0
31.9
24.4
38.5
33.8
25.0
42.2
34.7
24.5
45.3
34.3
-

15.0
15.0
15.3
14.9
15.2
15.4
15.1
15.4
15.5
15.3
15.5
15.6
14.8
14.8
15.1
14.9
15.1
15.3
15.0
15.3
15.5
15.2
15.4
15.6
15.3
15.5
14.9
14.9
15.1
14.9
15.1
15.3
15.1
15.3
15.5
15.2
15.5
15.6
15.4
15.6
14.9
14.8
14.9
15.2
15.0
15.1
15.4
15.2
15.3
15.5
15.3
15.5
15.6
15.4
15.6
14.9
14.9
15.0
15.2
15.1
15.2
15.4
15.2
15.4
15.5
15.3
15.5
15.6
15.5
15.6
-

Note: All capacities are gross cooling values and do not include indoor fan heat. To obtain net cooling, subtract indoor fan heat.

24

RT-PRC014-E4

Performance Data
Table 13 - WK* 200 Gross Cooling Capacities (kW)
25 C
Indoor Entering Entering
Airflow
Dry
Wet
m3/h
bulb
bulb
HR
18 C
21 C
24 C
8970
27 C
30 C
33 C
18 C
21 C
24 C
10090
27 C
30 C
33 C
18 C
21 C
24 C
11210
27 C
30 C
33 C
18 C
21 C
24 C
12330
27 C
30 C
33 C
18 C
21 C
24 C
13450
27 C
30 C
33 C

9.4 C
12.1 C
14.6 C
11.5 C
14.6 C
17.3 C
13.7 C
17.0 C
20.0 C
15.8 C
19.5 C
22.8 C
17.9 C
22.0 C
25.5 C
20.0 C
24.5 C
28.2 C
9.4 C
12.1 C
14.6 C
11.5 C
14.6 C
17.3 C
13.7 C
17.0 C
20.0 C
15.8 C
19.5 C
22.8 C
17.9 C
22.0 C
25.5 C
20.0 C
24.5 C
28.2 C
9.4 C
12.1 C
14.6 C
11.5 C
14.6 C
17.3 C
13.7 C
17.0 C
20.0 C
15.8 C
19.5 C
22.8 C
17.9 C
22.0 C
25.5 C
20.0 C
24.5 C
28.2 C
9.4 C
12.1 C
14.6 C
11.5 C
14.6 C
17.3 C
13.7 C
17.0 C
20.0 C
15.8 C
19.5 C
22.8 C
17.9 C
22.0 C
25.5 C
20.0 C
24.5 C
28.2 C
9.4 C
12.1 C
14.6 C
11.5 C
14.6 C
17.3 C
13.7 C
17.0 C
20.0 C
15.8 C
19.5 C
22.8 C
17.9 C
22.0 C
25.5 C
20.0 C
24.5 C
28.2 C

30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %

Total
Cap
(kW)

Sens.
Cap.
(kW)

49.2
55.1
55.1
61.7
53.8
61.2
66.4
59.0
65.9
70.0
63.6
69.8
73.3
67.3
73.2
76.3
50.8
56.9
51.3
56.9
63.1
55.7
62.8
67.4
61.1
66.9
71.0
65.2
70.9
74.1
68.7
74.2
77.0
52.3
58.5
53.4
58.5
64.2
58.1
63.9
68.2
62.3
69.2
71.6
66.5
71.7
74.7
69.8
74.9
77.7
50.6
53.6
59.8
55.4
59.9
65.0
60.2
64.8
68.9
64.1
69.7
72.2
67.6
72.3
75.2
70.7
75.4
78.2
52.2
54.7
60.7
57.2
60.8
65.7
61.8
65.5
69.5
65.4
69.2
72.7
68.2
72.9
75.7
71.4
75.9
78.6

39.2
33.0
41.6
34.4
52.7
43.7
34.8
55.6
44.8
34.8
57.7
45.0
34.6
58.4
44.3
34.0
41.6
34.6
51.3
44.1
35.9
55.7
46.1
36.2
59.6
46.5
36.2
61.1
46.5
36.0
61.3
45.5
34.4
43.9
36.1
53.4
46.5
37.2
58.1
48.3
37.5
62.3
50.0
37.5
64.1
47.8
37.4
63.8
46.5
34.8
50.6
46.1
37.5
55.4
48.8
38.4
60.2
50.1
38.4
64.1
51.4
38.8
66.7
53.1
38.7
66.1
53.9
35.1
52.2
48.2
38.7
57.2
51.0
39.6
61.8
51.8
39.0
65.4
50.9
40.0
68.2
50.0
40.0
68.1
56.3
39.9

Outdoor Air Temperature


35 C

30 C
CMP
(kW)

Total
Cap
(kW)

Sens.
Cap.
(kW)

13.1
13.5
13.5
13.8
13.4
13.8
14.1
13.7
14.0
14.3
13.9
14.3
14.6
14.1
14.5
14.8
13.2
13.6
13.3
13.6
13.9
13.5
13.9
14.1
13.8
14.1
14.4
14.0
14.3
14.6
14.2
14.6
14.8
13.3
13.7
13.4
13.7
14.0
13.6
13.9
14.2
13.8
14.2
14.5
14.1
14.4
14.7
14.2
14.6
14.9
13.2
13.4
13.7
13.5
13.7
14.0
13.7
14.0
14.3
13.9
14.2
14.5
14.1
14.4
14.7
14.3
14.7
15.0
13.3
13.5
13.8
13.6
13.8
14.0
13.8
14.0
14.3
14.0
14.3
14.6
14.1
14.5
14.8
14.3
14.7
15.0

51.4
51.4
58.3
50.1
57.6
64.4
55.4
63.5
68.7
60.7
67.8
72.1
65.2
72.0
75.6
53.0
53.1
60.1
52.7
59.5
65.6
57.1
64.9
69.7
62.6
70.4
73.2
66.7
73.0
76.3
48.6
54.4
50.3
54.5
61.4
54.9
60.9
66.5
59.6
65.9
70.5
64.2
70.9
73.9
68.0
73.8
77.0
49.8
55.6
52.2
55.8
62.4
57.0
62.0
67.3
61.7
66.7
71.1
65.4
71.0
74.5
69.1
74.4
77.4
48.9
50.8
56.6
53.8
56.9
63.3
58.8
62.9
67.5
63.3
67.5
71.7
66.8
71.6
74.9
69.7
74.9
77.9

31.0
39.6
32.7
50.1
41.8
33.6
53.7
43.5
33.9
56.5
44.1
33.7
58.2
44.3
33.4
32.5
42.1
34.3
52.7
44.4
35.0
57.1
46.1
35.2
60.5
47.7
35.0
61.7
45.8
34.9
41.8
34.0
50.3
44.4
35.7
54.9
46.9
36.4
59.6
48.1
36.5
64.1
49.3
35.6
64.8
47.1
36.3
44.0
35.3
52.2
46.7
37.0
57.0
49.2
37.6
61.7
49.9
37.2
65.4
49.7
36.1
67.6
53.0
37.7
48.9
46.1
36.6
53.8
49.0
38.2
58.8
51.3
38.0
63.3
51.6
37.9
66.8
54.4
39.1
69.7
55.4
39.0

CMP
(kW)

Total
Cap
(kW)

Sens.
Cap.
(kW)

14.8
14.8
15.2
14.8
15.2
15.6
15.1
15.5
15.9
15.4
15.8
16.1
15.6
16.0
16.4
15.0
15.0
15.4
14.9
15.3
15.7
15.2
15.6
15.9
15.5
15.9
16.2
15.7
16.1
16.4
14.7
15.0
14.8
15.0
15.4
15.1
15.4
15.7
15.3
15.7
16.0
15.6
15.9
16.3
15.8
16.2
16.5
14.7
15.1
14.9
15.1
15.5
15.2
15.4
15.8
15.4
15.7
16.1
15.6
16.0
16.3
15.8
16.2
16.6
14.7
14.8
15.2
15.0
15.2
15.5
15.3
15.5
15.8
15.5
15.8
16.1
15.7
16.0
16.4
15.9
16.3
16.6

47.5
47.6
54.1
53.5
61.2
51.2
59.9
66.5
56.7
65.4
70.6
61.9
70.9
74.1
49.0
49.1
55.8
49.5
55.1
62.6
53.8
61.6
67.6
58.9
66.5
71.4
63.8
71.5
74.8
50.2
50.4
57.1
51.6
56.6
63.7
56.2
62.8
68.4
60.9
67.5
72.2
65.4
71.8
75.5
51.2
48.8
51.6
58.3
53.5
57.8
64.6
58.3
63.8
69.1
62.8
68.3
72.8
66.5
72.5
76.0
52.1
50.3
52.6
59.3
55.2
58.9
65.4
60.2
64.6
69.6
64.5
69.0
73.3
67.9
73.1
76.4

29.0
37.5
30.6
39.7
32.1
51.2
41.8
32.6
54.5
43.2
32.6
57.0
44.6
32.4
30.4
40.0
32.2
49.5
42.3
33.5
53.8
44.4
34.0
58.8
45.5
34.0
61.1
46.6
33.5
31.8
42.3
33.6
51.6
44.8
34.9
56.2
46.9
35.3
60.9
47.6
35.1
64.8
47.4
34.1
33.1
48.8
44.6
35.0
53.5
47.2
36.2
58.3
49.2
36.6
62.8
49.4
35.8
66.5
51.8
34.6
34.4
50.3
46.8
36.3
55.2
49.5
37.5
60.2
51.3
37.9
64.5
53.1
36.4
67.9
54.3
38.0

40 C

CMP
(kW)

Total
Cap
(kW)

Sens.
Cap.
(kW)

16.3
16.3
16.8
16.7
17.2
16.6
17.1
17.5
16.9
17.4
17.8
17.2
17.8
18.1
16.4
16.4
16.9
16.5
16.8
17.3
16.7
17.2
17.6
17.1
17.5
17.9
17.3
17.8
18.1
16.5
16.5
16.9
16.6
16.9
17.4
16.9
17.3
17.7
17.2
17.6
17.9
17.4
17.8
18.2
16.6
16.4
16.6
17.0
16.7
17.0
17.4
17.0
17.3
17.7
17.3
17.6
18.0
17.5
17.9
18.3
16.6
16.5
16.7
17.1
16.8
17.1
17.5
17.1
17.4
17.8
17.4
17.7
18.0
17.6
17.9
18.3

49.7
49.1
56.6
47.9
55.3
63.3
52.6
61.8
68.1
57.7
66.8
71.9
51.2
46.1
50.7
58.2
50.4
56.9
64.6
54.7
63.1
69.1
60.0
67.8
72.6
45.8
46.1
52.4
48.0
52.0
59.6
52.6
58.3
65.5
57.2
64.2
69.8
61.7
68.7
73.4
46.7
47.2
53.4
49.8
53.1
60.7
54.5
59.6
66.3
59.4
65.1
70.3
63.7
73.9
47.5
46.5
48.1
54.3
51.4
54.1
61.5
56.3
60.6
66.8
61.2
65.9
70.8
65.3
74.3

28.5
37.6
30.0
47.9
39.7
31.1
52.5
41.5
31.3
55.1
42.6
31.3
30.0
46.1
40.1
31.6
50.4
42.3
32.5
54.7
44.2
32.8
59.6
44.7
32.7
29.6
40.1
31.4
48.0
42.6
33.1
52.6
44.9
33.9
57.2
46.7
34.1
61.7
46.7
33.5
30.9
42.4
32.8
49.8
45.0
34.5
54.5
47.4
35.3
59.4
48.9
35.5
63.7
34.1
32.1
46.5
44.6
34.1
51.4
47.3
35.8
56.3
49.8
36.5
61.2
51.0
36.8
65.3
34.6

45 C
CMP
(kW)

Total
Cap
(kW)

Sens.
Cap.
(kW)

CMP
(kW)

18.4
18.4
18.9
18.3
18.8
19.3
18.6
19.2
19.6
18.9
19.5
19.9
18.5
18.1
18.5
19.0
18.4
18.9
19.4
18.7
19.3
19.7
19.1
19.6
20.0
18.1
18.1
18.6
18.3
18.6
19.1
18.6
19.0
19.4
18.9
19.3
19.7
19.2
19.6
20.0
18.2
18.2
18.7
18.4
18.6
19.1
18.7
19.0
19.5
19.0
19.4
19.8
19.3
20.1
18.2
18.2
18.3
18.7
18.5
18.7
19.2
18.8
19.1
19.5
19.1
19.4
19.8
19.4
20.1

34.5
45.1
44.6
51.7
44.4
50.4
58.9
48.5
56.9
53.2
34.5
46.3
42.5
45.9
53.1
46.7
51.9
51.0
58.4
55.4
47.4
44.3
47.1
54.3
48.7
53.2
53.3
57.9
42.6
48.3
45.9
48.2
55.3
50.5
54.3
55.3
42.5
42.6
43.5
49.1
47.3
49.1
56.2
52.2
55.3
57.1
-

31.0
26.3
35.4
27.8
44.4
37.5
29.2
48.5
39.4
53.0
34.5
27.8
42.5
37.9
29.4
46.7
40.1
51.0
42.2
55.4
29.1
44.3
40.3
30.8
48.7
42.7
53.3
57.9
40.1
30.5
45.9
42.7
32.2
50.5
45.1
55.3
29.7
42.6
42.3
31.7
47.3
45.0
33.6
52.2
47.6
57.1
-

19.1
20.1
20.1
20.6
20.1
20.5
21.1
20.4
21.0
20.7
19.1
20.2
19.9
20.2
20.7
20.3
20.6
20.6
21.1
20.9
20.3
20.1
20.3
20.8
20.4
20.7
20.7
21.1
19.9
20.4
20.2
20.4
20.9
20.6
20.8
20.9
19.9
19.9
20.0
20.4
20.3
20.5
20.9
20.7
20.9
21.0
-

Note: All capacities are gross cooling values and do not include indoor fan heat. To obtain net cooling, subtract indoor fan heat.

RT-PRC014-E4

25

Performance Data
Table 14 - WK* 265 Gross Cooling Capacities
25 C
Indoor Entering Entering
Airflow
Dry
Wet
m3/h
bulb
bulb
9.4 C
18 C
12.1 C
14.6 C
11.5 C
21 C
14.6 C
17.3 C
13.7 C
24 C
17.0 C
11520
20.0 C
15.8 C
27 C
19.5 C
22.8 C
17.9 C
30 C
22.0 C
25.5 C
20.0 C
33 C
24.5 C
28.2 C
9.4 C
18 C
12.1 C
14.6 C
11.5 C
21 C
14.6 C
17.3 C
13.7 C
24 C
17.0 C
12960
20.0 C
15.8 C
27 C
19.5 C
22.8 C
17.9 C
30 C
22.0 C
25.5 C
20.0 C
33 C
24.5 C
28.2 C
9.4 C
18 C
12.1 C
14.6 C
11.5 C
21 C
14.6 C
17.3 C
13.7 C
24 C
17.0 C
14400
20.0 C
15.8 C
27 C
19.5 C
22.8 C
17.9 C
30 C
22.0 C
25.5 C
20.0 C
33 C
24.5 C
28.2 C
9.4 C
18 C
12.1 C
14.6 C
11.5 C
21 C
14.6 C
17.3 C
13.7 C
24 C
17.0 C
15840
20.0 C
15.8 C
27 C
19.5 C
22.8 C
17.9 C
30 C
22.0 C
25.5 C
20.0 C
33 C
24.5 C
28.2 C
9.4 C
18 C
12.1 C
14.6 C
11.5 C
21 C
14.6 C
17.3 C
13.7 C
24 C
17.0 C
17280
20.0 C
15.8 C
27 C
19.5 C
22.8 C
17.9 C
30 C
22.0 C
25.5 C
20.0 C
33 C
24.5 C
28.2 C

HR
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %

Total
Cap
(kW)
59.3
61.6
65.7
63.6
66.7
71.3
68.0
71.9
77.2
72.3
77.2
83.2
76.6
82.7
89.1
81.0
88.1
95.4
60.6
63.0
67.1
65.0
68.2
72.9
69.5
73.5
78.9
73.9
78.9
85.0
78.3
84.5
91.1
82.8
90.0
97.5
61.7
64.1
68.3
66.2
69.4
74.2
70.7
74.8
80.3
75.2
80.3
86.5
79.7
86.0
92.7
84.3
91.6
99.2
62.6
65.1
69.3
67.2
70.4
75.3
71.8
75.9
81.5
76.3
81.5
87.8
80.9
87.3
94.1
85.6
93.0
100.7
63.5
65.9
70.3
68.1
71.4
76.3
72.7
76.9
82.6
77.4
82.6
89.0
82.0
88.5
95.4
86.7
94.2
102.0

Sens.
Cap.
(kW)
54.5
48.4
35.6
58.5
49.8
35.4
62.5
51.0
34.8
66.5
51.7
33.8
70.4
52.1
32.5
74.5
52.0
30.1
58.1
51.6
38.0
62.4
53.1
37.8
66.6
54.3
37.1
70.8
55.1
36.0
75.1
55.5
34.7
79.4
55.4
32.1
61.7
54.8
40.3
66.2
56.4
40.1
70.7
57.7
39.4
75.2
58.5
38.2
79.7
58.9
36.8
84.3
58.8
34.1
62.6
58.0
42.6
67.2
59.7
42.4
71.8
61.1
41.7
76.3
61.9
40.4
80.9
62.3
38.9
85.6
62.2
36.1
63.5
61.3
45.1
68.1
63.1
44.8
72.7
64.5
44.0
77.4
65.4
42.7
82.0
65.8
41.1
86.7
65.7
38.1

Outdoor Air Temperature


35 C

30 C
CMP
(kW)
15.7
15.8
16.1
16.0
16.2
16.4
16.2
16.5
16.7
16.5
16.7
17.0
16.7
17.0
17.3
16.9
17.2
17.5
15.8
15.9
16.2
16.1
16.3
16.5
16.3
16.6
16.8
16.6
16.8
17.1
16.8
17.1
17.4
17.0
17.3
17.6
15.8
15.9
16.2
16.1
16.3
16.5
16.3
16.6
16.8
16.6
16.8
17.1
16.8
17.1
17.4
17.0
17.3
17.6
15.9
16.0
16.3
16.2
16.4
16.6
16.4
16.7
16.9
16.7
16.9
17.2
16.9
17.2
17.5
17.1
17.4
17.7
16.0
16.1
16.4
16.3
16.5
16.7
16.5
16.8
17.0
16.8
17.0
17.3
17.0
17.3
17.6
17.2
17.5
17.8

Total
Cap
(kW)
56.7
58.6
62.4
60.9
63.4
67.9
65.1
68.4
73.5
69.3
73.5
79.2
73.5
78.7
84.9
77.6
83.9
90.6
57.9
59.8
63.7
62.1
64.7
69.3
66.4
69.8
75.0
70.7
75.0
80.8
75.0
80.3
86.6
79.2
85.6
92.5
58.9
60.8
64.8
63.2
65.8
70.5
67.6
71.0
76.3
71.9
76.3
82.2
76.3
81.7
88.1
80.6
87.1
94.1
59.8
61.8
65.8
64.2
66.8
71.6
68.7
72.1
77.5
73.0
77.5
83.5
77.5
83.0
89.5
81.9
88.5
95.6
60.5
62.5
66.6
64.9
67.6
72.4
69.5
73.0
78.4
73.9
78.4
84.5
78.4
83.9
90.5
82.8
89.5
96.7

Sens.
Cap.
(kW)
51.9
46.7
33.9
55.6
48.2
33.8
59.5
49.3
33.2
63.3
50.1
32.2
67.2
50.5
30.8
71.0
50.5
29.4
55.4
49.8
36.2
59.4
51.4
36.1
63.6
52.7
35.4
67.6
53.5
34.4
71.7
53.9
32.9
75.8
53.9
31.4
58.9
53.0
38.5
63.2
54.7
38.4
67.6
56.0
37.7
71.9
56.9
36.6
76.3
57.3
35.0
80.6
57.3
33.4
59.8
56.1
40.7
64.2
57.9
40.6
68.7
59.2
39.9
73.0
60.2
38.7
77.5
60.6
37.0
81.9
60.6
35.3
60.5
59.3
43.1
64.9
61.2
43.0
69.5
62.7
42.2
73.9
63.7
41.0
78.4
64.1
39.2
82.8
64.1
37.4

CMP
(kW)
17.3
17.4
17.7
17.6
17.7
18.0
17.8
18.0
18.3
18.1
18.3
18.6
18.3
18.6
18.9
18.5
18.8
19.1
17.4
17.5
17.8
17.7
17.8
18.1
17.9
18.1
18.4
18.2
18.4
18.7
18.4
18.7
19.0
18.6
18.9
19.2
17.4
17.5
17.8
17.7
17.8
18.1
17.9
18.1
18.4
18.2
18.4
18.7
18.4
18.7
19.0
18.6
18.9
19.2
17.5
17.6
17.9
17.8
17.9
18.2
18.0
18.2
18.5
18.3
18.5
18.8
18.5
18.8
19.1
18.7
19.0
19.3
17.6
17.7
18.0
17.9
18.0
18.3
18.1
18.3
18.6
18.4
18.6
18.9
18.6
18.9
19.2
18.8
19.1
19.4

Total
Cap
(kW)
54.1
55.6
59.2
58.1
60.3
64.4
62.2
65.1
69.8
66.3
69.9
75.2
70.4
74.8
80.6
74.3
79.7
86.2
55.2
56.7
60.4
59.3
61.5
65.7
63.4
66.4
71.2
67.7
71.3
76.7
71.8
76.3
82.2
75.8
81.3
87.9
56.1
57.7
61.4
60.3
62.5
66.8
64.5
67.5
72.4
68.8
72.5
78.0
73.0
77.6
83.6
77.1
82.7
89.4
56.9
58.5
62.2
61.1
63.4
67.7
65.4
68.4
73.4
69.7
73.5
79.1
74.0
78.7
84.8
78.2
83.8
90.6
57.6
59.3
63.1
62.0
64.2
68.6
66.3
69.4
74.4
70.7
74.5
80.2
75.0
79.7
85.9
79.2
85.0
91.9

Sens.
Cap.
(kW)
49.1
44.9
32.2
52.8
46.4
32.1
56.5
47.6
31.6
60.2
48.4
30.7
63.9
48.8
29.4
67.5
49.0
27.8
52.7
48.1
34.5
56.6
49.7
34.4
60.5
51.1
33.9
64.6
51.9
32.9
68.5
52.4
31.5
72.4
52.6
29.8
56.1
51.3
36.8
60.3
53.0
36.7
64.5
54.4
36.1
68.8
55.3
35.1
73.0
55.8
33.6
77.1
56.0
31.8
56.9
54.5
39.1
61.1
56.3
39.0
65.4
57.7
38.3
69.7
58.7
37.3
74.0
59.2
35.7
78.2
59.4
33.8
57.6
57.7
41.4
62.0
59.6
41.3
66.3
61.2
40.6
70.7
62.2
39.5
75.0
62.8
37.8
79.2
63.0
35.8

CMP
(kW)
19.1
19.2
19.5
19.4
19.5
19.8
19.6
19.9
20.2
19.9
20.2
20.5
20.2
20.4
20.7
20.4
20.6
20.9
19.2
19.3
19.6
19.5
19.6
19.9
19.7
20.0
20.3
20.0
20.3
20.6
20.3
20.5
20.8
20.5
20.7
21.0
19.3
19.4
19.7
19.6
19.7
20.0
19.8
20.1
20.4
20.1
20.4
20.7
20.4
20.6
20.9
20.6
20.8
21.1
19.3
19.4
19.7
19.6
19.7
20.0
19.8
20.1
20.4
20.1
20.4
20.7
20.4
20.6
20.9
20.6
20.8
21.1
19.4
19.5
19.8
19.7
19.8
20.1
19.9
20.2
20.5
20.2
20.5
20.8
20.5
20.7
21.0
20.7
20.9
21.2

40 C
Total
Cap
(kW)
51.4
52.6
56.0
55.4
57.0
61.0
59.4
61.7
66.2
63.3
66.3
71.3
67.2
70.9
76.6
71.1
75.7
81.7
52.4
53.6
57.1
56.5
58.2
62.2
60.5
62.9
67.5
64.5
67.6
72.7
68.5
72.3
78.1
72.5
77.1
83.3
53.3
54.5
58.0
57.4
59.1
63.2
61.5
63.9
68.6
65.6
68.7
73.9
69.6
73.5
79.4
73.7
78.4
84.7
54.0
55.2
58.8
58.2
59.9
64.0
62.3
64.7
69.5
66.5
69.6
74.9
70.5
74.5
80.4
74.7
79.4
85.8
54.7
55.9
59.5
58.9
60.6
64.9
63.1
65.6
70.4
67.3
70.5
75.8
71.4
75.4
81.5
75.6
80.5
86.9

Sens.
Cap.
(kW)
46.6
43.3
30.8
50.1
44.9
30.7
53.7
46.1
30.2
57.3
47.0
29.4
60.8
47.4
28.3
64.4
47.6
26.8
49.8
46.4
32.9
53.7
48.1
32.8
57.5
49.4
32.3
61.3
50.3
31.5
65.1
50.8
30.3
68.9
51.0
28.7
53.3
49.6
35.2
57.4
51.4
35.1
61.5
52.8
34.6
65.6
53.8
33.7
69.6
54.3
32.4
73.7
54.5
30.7
54.0
52.8
37.5
58.2
54.7
37.4
62.3
56.2
36.9
66.5
57.3
35.9
70.5
57.8
34.5
74.7
58.0
32.7
54.7
55.9
39.8
58.9
58.1
39.7
63.1
59.7
39.1
67.3
60.8
38.1
71.4
61.4
36.6
75.6
61.6
34.7

45 C
CMP
(kW)
21.3
21.4
21.7
21.6
21.7
22.0
21.9
22.0
22.4
22.1
22.4
22.7
22.4
22.6
23.0
22.6
22.9
23.2
21.4
21.5
21.8
21.7
21.8
22.1
22.0
22.1
22.5
22.2
22.5
22.8
22.5
22.7
23.1
22.7
23.0
23.3
21.5
21.6
21.9
21.8
21.9
22.2
22.1
22.2
22.6
22.3
22.6
22.9
22.6
22.8
23.2
22.8
23.1
23.4
21.5
21.6
21.9
21.8
21.9
22.2
22.1
22.2
22.6
22.3
22.6
22.9
22.6
22.8
23.2
22.8
23.1
23.4
21.6
21.7
22.0
21.9
22.0
22.3
22.2
22.3
22.7
22.4
22.7
23.0
22.7
22.9
23.3
22.9
23.2
23.5

Total
Cap
(kW)
49.1
50.1
53.3
53.0
54.3
58.1
56.8
58.7
63.0
60.6
63.1
68.0
64.5
67.8
68.3
50.1
51.1
54.4
54.1
55.5
59.3
58.0
59.9
64.3
61.9
64.4
65.8
50.8
51.8
55.2
54.9
56.3
60.2
58.8
60.7
65.3
62.8
65.4
66.8
51.6
52.7
56.1
55.8
57.2
61.2
59.8
61.7
66.3
63.8
66.4
67.9
52.2
53.3
56.7
56.4
57.8
61.9
60.5
62.4
67.1
64.5
67.2
68.6
-

Sens.
Cap.
(kW)
44.2
41.9
29.2
47.8
43.6
29.4
51.2
44.8
29.1
54.6
45.7
28.3
58.1
46.2
61.5
47.4
44.9
31.3
51.2
46.7
31.5
54.9
48.0
31.2
58.6
49.0
62.3
50.8
48.1
33.5
54.9
50.1
33.8
58.8
51.5
33.4
62.8
52.5
66.8
51.6
51.2
35.7
55.8
53.2
35.9
59.8
54.7
35.6
63.8
55.8
67.9
52.2
53.3
38.0
56.4
56.7
38.3
60.5
58.3
37.9
64.5
59.5
68.6
-

CMP
(kW)
23.3
23.4
23.7
23.6
23.7
24.0
23.9
24.2
24.4
24.3
24.4
24.7
24.4
24.8
24.6
23.4
23.5
23.8
23.7
23.8
24.1
24.0
24.3
24.5
24.4
24.5
24.5
23.5
23.6
23.9
23.8
23.9
24.2
24.1
24.4
24.6
24.5
24.6
24.6
23.5
23.6
23.9
23.8
23.9
24.2
24.1
24.4
24.6
24.5
24.6
24.6
23.6
23.7
24.0
23.9
24.0
24.3
24.2
24.5
24.7
24.6
24.7
24.7
-

Note: All capacities are gross cooling values and do not include indoor fan heat. To obtain net cooling, subtract indoor fan heat.

26

RT-PRC014-E4

Performance Data
Table 15 - WK* 290 Gross Cooling Capacities
25 C
Indoor Entering Entering
Airflow
Dry
Wet
m3/h
bulb
bulb
9.4 C
18 C
12.1 C
14.6 C
11.5 C
21 C
14.6 C
17.3 C
13.7 C
24 C
17.0 C
12960
20.0 C
15.8 C
27 C
19.5 C
22.8 C
17.9 C
30 C
22.0 C
25.5 C
20.0 C
33 C
24.5 C
28.2 C
9.4 C
18 C
12.1 C
14.6 C
11.5 C
21 C
14.6 C
17.3 C
13.7 C
24 C
17.0 C
14580
20.0 C
15.8 C
27 C
19.5 C
22.8 C
17.9 C
30 C
22.0 C
25.5 C
20.0 C
33 C
24.5 C
28.2 C
9.4 C
18 C
12.1 C
14.6 C
11.5 C
21 C
14.6 C
17.3 C
13.7 C
24 C
17.0 C
16200
20.0 C
15.8 C
27 C
19.5 C
22.8 C
17.9 C
30 C
22.0 C
25.5 C
20.0 C
33 C
24.5 C
28.2 C
9.4 C
18 C
12.1 C
14.6 C
11.5 C
21 C
14.6 C
17.3 C
13.7 C
24 C
17.0 C
17820
20.0 C
15.8 C
27 C
19.5 C
22.8 C
17.9 C
30 C
22.0 C
25.5 C
20.0 C
33 C
24.5 C
28.2 C
9.4 C
18 C
12.1 C
14.6 C
11.5 C
21 C
14.6 C
17.3 C
13.7 C
24 C
17.0 C
19440
20.0 C
15.8 C
27 C
19.5 C
22.8 C
17.9 C
30 C
22.0 C
25.5 C
20.0 C
33 C
24.5 C
28.2 C

HR
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %

Total
Cap
(kW)
69.6
72.9
77.9
74.9
79.2
85.0
80.2
85.8
92.5
85.5
92.5
100.2
91.4
99.5
108.1
97.3
106.6
116.1
71.4
74.7
79.8
76.8
81.2
87.2
82.2
87.9
94.8
87.6
94.8
102.6
93.6
102.0
110.8
99.7
109.2
119.0
72.8
76.2
81.4
78.3
82.8
88.9
83.8
89.7
96.7
89.4
96.7
104.7
95.5
104.0
113.0
101.7
111.4
121.4
74.1
77.5
82.8
79.7
84.3
90.5
85.3
91.3
98.4
91.0
98.4
106.5
97.2
105.8
115.0
103.5
113.4
123.5
75.1
78.6
84.0
80.8
85.5
91.7
86.5
92.6
99.8
92.3
99.8
108.1
98.6
107.3
116.6
105.0
115.0
125.3

Sens.
Cap.
(kW)
64.4
56.4
41.8
69.2
58.1
41.6
74.1
59.4
41.0
79.0
60.2
39.8
84.2
60.6
38.1
88.4
60.4
35.8
68.6
60.1
44.6
73.8
61.9
44.4
79.0
63.4
43.7
84.3
64.2
42.4
89.8
64.6
40.6
94.3
64.4
38.2
72.8
63.8
47.3
78.3
65.7
47.1
83.8
67.2
46.4
89.4
68.1
45.0
95.3
68.5
43.1
100.0
68.3
40.5
74.1
67.5
50.0
79.7
69.5
49.8
85.3
71.0
49.1
91.0
72.0
47.6
97.2
72.4
45.6
103.5
72.2
42.8
75.1
71.0
52.6
80.8
73.1
52.4
86.5
74.8
51.6
92.3
75.8
50.1
98.6
76.2
48.0
105.0
76.0
45.1

Outdoor Air Temperature


35 C

30 C
CMP
(kW)
20.7
21.0
21.4
21.1
21.4
21.9
21.5
21.9
22.6
21.9
22.5
23.2
22.4
23.1
24.0
22.9
23.8
24.8
20.8
21.1
21.5
21.2
21.5
22.0
21.6
22.0
22.7
22.0
22.6
23.3
22.5
23.2
24.1
23.0
23.9
24.9
21.0
21.3
21.7
21.4
21.7
22.2
21.8
22.2
22.9
22.2
22.8
23.5
22.7
23.4
24.3
23.2
24.1
25.1
21.1
21.4
21.8
21.5
21.8
22.3
21.9
22.3
23.0
22.3
22.9
23.6
22.8
23.5
24.4
23.3
24.2
25.2
21.3
21.6
22.0
21.7
22.0
22.5
22.1
22.5
23.2
22.5
23.1
23.8
23.0
23.7
24.6
23.5
24.4
25.4

Total
Cap
(kW)
66.6
69.3
74.1
71.7
75.5
81.1
76.9
81.8
88.3
82.1
88.4
95.8
87.3
95.1
103.4
93.1
102.0
111.3
68.1
71.0
75.9
73.4
77.3
83.0
78.7
83.7
90.4
84.0
90.5
98.0
89.4
97.4
105.9
95.3
104.4
113.9
69.5
72.4
77.4
74.9
78.8
84.7
80.3
85.4
92.2
85.7
92.3
100.0
91.2
99.3
108.0
97.2
106.5
116.2
70.6
73.6
78.7
76.1
80.1
86.1
81.6
86.8
93.7
87.1
93.8
101.6
92.7
100.9
109.8
98.8
108.2
118.1
71.7
74.7
79.8
77.3
81.3
87.4
82.8
88.1
95.1
88.4
95.2
103.1
94.1
102.4
111.4
100.3
109.8
119.9

Sens.
Cap.
(kW)
61.2
54.3
39.9
66.0
56.1
39.8
70.7
57.4
39.3
75.5
58.4
38.1
80.3
58.8
36.6
85.4
58.8
34.7
65.3
58.0
42.6
70.4
59.9
42.5
75.5
61.3
41.9
80.5
62.3
40.6
85.7
62.7
39.0
91.1
62.7
37.0
69.5
61.7
45.3
74.9
63.7
45.2
80.3
65.2
44.6
85.7
66.3
43.2
91.2
66.7
41.5
96.9
66.7
39.4
70.6
65.3
48.0
76.1
67.4
47.9
81.6
69.0
47.2
87.1
70.2
45.7
92.7
70.6
43.9
98.8
70.6
41.7
71.7
69.0
50.6
77.3
71.2
50.5
82.8
72.9
49.8
88.4
74.1
48.3
94.1
74.5
46.4
100.3
74.5
44.0

CMP
(kW)
23.0
23.2
23.6
23.3
23.7
24.2
23.7
24.2
24.8
24.1
24.7
25.4
24.6
25.3
26.2
25.1
26.0
27.0
23.2
23.4
23.8
23.5
23.9
24.4
23.9
24.4
25.0
24.3
24.9
25.6
24.8
25.5
26.4
25.3
26.2
27.2
23.3
23.5
23.9
23.6
24.0
24.5
24.0
24.5
25.1
24.4
25.0
25.7
24.9
25.6
26.5
25.4
26.3
27.3
23.5
23.7
24.1
23.8
24.2
24.7
24.2
24.7
25.3
24.6
25.2
25.9
25.1
25.8
26.7
25.6
26.5
27.5
23.6
23.8
24.2
23.9
24.3
24.8
24.3
24.8
25.4
24.7
25.3
26.0
25.2
25.9
26.8
25.7
26.6
27.6

Total
Cap
(kW)
63.1
65.4
70.0
68.2
71.4
76.8
73.3
77.6
83.8
78.3
83.9
91.1
83.4
90.4
98.5
88.6
97.0
105.9
64.6
67.0
71.7
69.8
73.2
78.6
75.0
79.4
85.8
80.2
85.9
93.3
85.4
92.6
100.8
90.7
99.3
108.5
65.9
68.3
73.1
71.2
74.6
80.2
76.5
81.0
87.5
81.8
87.6
95.1
87.1
94.4
102.8
92.5
101.3
110.6
67.0
69.5
74.4
72.4
75.9
81.6
77.8
82.4
89.0
83.2
89.1
96.7
88.6
96.0
104.6
94.1
103.0
112.5
67.9
70.4
75.4
73.4
76.9
82.7
78.9
83.5
90.2
84.3
90.3
98.0
89.8
97.3
106.0
95.4
104.4
114.0

Sens.
Cap.
(kW)
57.9
52.3
38.1
62.6
54.2
38.1
67.2
55.6
37.4
71.9
56.6
36.5
76.6
57.1
35.1
81.3
57.2
33.4
61.9
55.9
40.7
66.9
58.0
40.8
71.9
59.5
40.0
76.8
60.5
39.0
81.8
61.1
37.5
86.9
61.2
35.7
65.9
59.5
43.3
71.2
61.7
43.4
76.5
63.3
42.6
81.8
64.4
41.5
87.1
65.0
39.9
92.5
65.1
38.0
67.0
63.2
46.0
72.4
65.5
46.1
77.8
67.2
45.2
83.2
68.4
44.1
88.6
69.0
42.4
94.1
69.1
40.4
67.9
66.8
48.6
73.4
69.3
48.7
78.9
71.1
47.8
84.3
72.3
46.6
89.8
73.0
44.8
95.4
73.1
42.7

CMP
(kW)
25.4
25.7
26.1
25.8
26.1
26.7
26.2
26.7
27.3
26.7
27.2
27.9
27.1
27.8
28.7
27.6
28.5
29.4
25.6
25.9
26.3
26.0
26.3
26.9
26.4
26.9
27.5
26.9
27.4
28.1
27.3
28.0
28.9
27.8
28.7
29.6
25.7
26.0
26.4
26.1
26.4
27.0
26.5
27.0
27.6
27.0
27.5
28.2
27.4
28.1
29.0
27.9
28.8
29.7
25.8
26.1
26.5
26.2
26.5
27.1
26.6
27.1
27.7
27.1
27.6
28.3
27.5
28.2
29.1
28.0
28.9
29.8
26.0
26.3
26.7
26.4
26.7
27.3
26.8
27.3
27.9
27.3
27.8
28.5
27.7
28.4
29.3
28.2
29.1
30.0

40 C
Total
Cap
(kW)
59.6
61.5
65.9
64.6
67.3
72.5
69.6
73.3
79.2
74.6
79.3
86.2
79.6
85.6
93.3
84.5
92.0
100.5
61.0
62.9
67.4
66.1
68.8
74.1
71.2
74.9
81.0
76.3
81.1
88.2
81.4
87.6
95.4
86.4
94.1
102.8
62.1
64.1
68.6
67.3
70.1
75.5
72.5
76.3
82.5
77.7
82.6
89.8
82.9
89.2
97.2
88.0
95.8
104.7
63.2
65.2
69.8
68.4
71.3
76.8
73.7
77.6
83.9
79.0
84.0
91.3
84.3
90.7
98.8
89.5
97.4
106.5
64.1
66.1
70.8
69.4
72.3
77.9
74.8
78.7
85.1
80.1
85.2
92.6
85.5
92.0
100.3
90.8
98.8
108.0

Sens.
Cap.
(kW)
54.3
50.1
35.9
58.8
52.0
35.9
63.3
53.6
35.7
67.9
54.6
35.0
72.4
55.3
33.6
76.9
55.5
31.8
58.2
53.7
38.5
63.1
55.8
38.5
68.0
57.5
38.3
72.9
58.6
37.6
77.7
59.4
36.1
82.5
59.5
34.1
62.1
57.3
41.1
67.3
59.5
41.1
72.5
61.3
40.9
77.7
62.5
40.1
82.9
63.3
38.5
88.0
63.5
36.4
63.2
61.0
43.7
68.4
63.3
43.7
73.7
65.2
43.5
79.0
66.5
42.7
84.3
67.4
41.0
89.5
67.6
38.7
64.1
64.5
46.3
69.4
67.0
46.3
74.8
69.0
46.1
80.1
70.4
45.2
85.5
71.3
43.4
90.8
71.5
41.0

45 C
CMP
(kW)
28.1
28.3
28.8
28.5
28.8
29.3
28.9
29.3
29.9
29.3
29.9
30.6
29.8
30.4
31.3
30.2
31.1
32.1
28.3
28.5
29.0
28.7
29.0
29.5
29.1
29.5
30.1
29.5
30.1
30.8
30.0
30.6
31.5
30.4
31.3
32.3
28.5
28.7
29.2
28.9
29.2
29.7
29.3
29.7
30.3
29.7
30.3
31.0
30.2
30.8
31.7
30.6
31.5
32.5
28.6
28.8
29.3
29.0
29.3
29.8
29.4
29.8
30.4
29.8
30.4
31.1
30.3
30.9
31.8
30.7
31.6
32.6
28.7
28.9
29.4
29.1
29.4
29.9
29.5
29.9
30.5
29.9
30.5
31.2
30.4
31.0
31.9
30.8
31.7
32.7

Total
Cap
(kW)
56.3
57.9
61.9
61.1
63.5
68.3
66.1
69.1
74.9
71.1
75.1
81.7
75.9
81.1
80.8
87.3
57.6
59.3
63.4
62.6
65.0
70.0
67.7
70.8
76.7
72.8
76.9
83.7
77.7
83.1
82.7
89.4
58.8
60.4
64.6
63.8
66.3
71.3
69.0
72.1
78.2
74.2
78.4
85.3
79.2
84.7
84.3
59.7
61.4
65.6
64.8
67.3
72.5
70.1
73.3
79.4
75.4
79.7
86.6
80.5
86.0
85.7
60.6
62.3
66.6
65.8
68.3
73.5
71.1
74.4
80.6
76.5
80.9
87.9
81.7
87.3
86.9
-

Sens.
Cap.
(kW)
51.0
48.0
33.9
55.4
50.0
34.7
59.9
51.7
33.6
64.4
52.9
32.9
68.8
53.6
73.2
53.9
54.8
51.6
36.5
59.5
53.8
37.3
64.4
55.7
36.2
69.3
56.9
35.4
74.0
57.7
78.7
58.0
58.8
55.3
39.1
63.8
57.7
39.9
69.0
59.6
38.7
74.2
61.0
37.9
79.2
61.8
84.3
59.7
58.8
41.6
64.8
61.3
42.4
70.1
63.4
41.2
75.4
64.8
40.3
80.5
65.7
85.7
60.6
62.3
44.2
65.8
65.1
45.1
71.1
67.4
43.7
76.5
68.9
42.8
81.7
69.8
86.9
-

CMP
(kW)
30.8
31.0
31.3
31.2
31.5
32.0
31.7
32.0
32.6
32.1
32.4
33.3
32.5
33.1
32.9
33.6
31.0
31.2
31.5
31.4
31.7
32.2
31.9
32.2
32.8
32.3
32.6
33.5
32.7
33.3
33.1
33.8
31.0
31.2
31.5
31.4
31.7
32.2
32.0
32.2
32.8
32.4
32.6
33.5
32.7
33.3
33.1
31.3
31.5
31.8
31.7
32.0
32.5
32.2
32.5
33.1
32.6
32.9
33.8
33.0
33.6
33.4
31.3
31.6
31.9
31.8
32.1
32.6
32.3
32.6
33.2
32.7
33.0
33.9
33.1
33.7
33.5
-

Note: All capacities are gross cooling values and do not include indoor fan heat. To obtain net cooling, subtract indoor fan heat.

RT-PRC014-E4

27

Performance Data
Table 16 - WK* 340 Gross Cooling Capacities
25 C
Indoor Entering Entering
Airflow
Dry
Wet
m3/h
bulb
bulb
9.4 C
18 C
12.1 C
14.6 C
11.5 C
21 C
14.6 C
17.3 C
13.7 C
24 C
17.0 C
14400
20.0 C
15.8 C
27 C
19.5 C
22.8 C
17.9 C
30 C
22.0 C
25.5 C
20.0 C
33 C
24.5 C
28.2 C
9.4 C
18 C
12.1 C
14.6 C
11.5 C
21 C
14.6 C
17.3 C
13.7 C
24 C
17.0 C
16200
20.0 C
15.8 C
27 C
19.5 C
22.8 C
17.9 C
30 C
22.0 C
25.5 C
20.0 C
33 C
24.5 C
28.2 C
9.4 C
18 C
12.1 C
14.6 C
11.5 C
21 C
14.6 C
17.3 C
13.7 C
24 C
17.0 C
18000
20.0 C
15.8 C
27 C
19.5 C
22.8 C
17.9 C
30 C
22.0 C
25.5 C
20.0 C
33 C
24.5 C
28.2 C
9.4 C
18 C
12.1 C
14.6 C
11.5 C
21 C
14.6 C
17.3 C
13.7 C
24 C
17.0 C
19800
20.0 C
15.8 C
27 C
19.5 C
22.8 C
17.9 C
30 C
22.0 C
25.5 C
20.0 C
33 C
24.5 C
28.2 C
9.4 C
18 C
12.1 C
14.6 C
11.5 C
21 C
14.6 C
17.3 C
13.7 C
24 C
17.0 C
21600
20.0 C
15.8 C
27 C
19.5 C
22.8 C
17.9 C
30 C
22.0 C
25.5 C
20.0 C
33 C
24.5 C
28.2 C

HR
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %
30 %
50 %
70 %

Total
Cap
(kW)
79.5
82.2
87.6
85.1
89.1
95.4
90.8
95.9
103.2
96.4
102.9
110.8
101.7
110.1
119.3
107.6
117.2
127.3
81.2
84.1
89.6
87.0
91.1
97.5
92.8
98.0
105.5
98.5
105.2
113.3
104.0
112.6
122.0
110.0
119.8
130.1
82.7
85.6
91.2
88.6
92.7
99.3
94.5
99.8
107.4
100.3
107.1
115.3
105.9
114.6
124.2
112.0
122.0
132.5
84.0
87.0
92.6
90.0
94.2
100.9
96.0
101.4
109.1
101.9
108.8
117.1
107.6
116.4
126.2
113.8
123.9
134.6
85.1
88.1
93.8
91.2
95.4
102.2
97.2
102.7
110.5
103.2
110.2
118.6
109.0
117.9
127.8
115.2
125.5
136.3

Sens.
Cap.
(kW)
73.1
65.1
49.3
78.3
67.2
49.4
83.5
68.8
49.0
88.6
69.9
48.0
93.6
70.4
46.4
99.0
70.5
43.3
78.0
69.5
52.6
83.6
71.8
52.7
89.1
73.4
52.2
94.6
74.6
51.2
99.9
75.2
49.5
105.6
75.3
46.2
82.7
73.7
55.8
88.6
76.1
55.9
94.5
77.8
55.4
100.3
79.1
54.3
105.9
79.7
52.5
112.0
79.8
49.0
84.0
78.0
59.0
90.0
80.5
59.2
96.0
82.3
58.6
101.9
83.7
57.5
107.6
84.3
55.6
113.8
84.4
51.8
85.1
82.2
62.2
91.2
84.9
62.3
97.2
86.8
61.8
103.2
88.2
60.5
109.0
88.9
58.5
115.2
89.0
54.6

Outdoor Air Temperature


35 C

30 C
CMP
(kW)
21.1
21.4
21.9
21.5
21.9
22.5
22.0
22.5
23.2
22.4
23.1
24.0
22.9
23.8
24.8
23.5
24.6
25.8
21.3
21.6
22.1
21.7
22.1
22.7
22.2
22.7
23.4
22.6
23.3
24.2
23.1
24.0
25.0
23.7
24.8
26.0
21.5
21.8
22.3
21.9
22.3
22.9
22.4
22.9
23.6
22.8
23.5
24.4
23.3
24.2
25.2
23.9
25.0
26.2
21.6
21.9
22.4
22.0
22.4
23.0
22.5
23.0
23.7
22.9
23.6
24.5
23.4
24.3
25.3
24.0
25.1
26.3
21.8
22.1
22.6
22.2
22.6
23.2
22.7
23.2
23.9
23.1
23.8
24.7
23.6
24.5
25.5
24.2
25.3
26.5

Total
Cap
(kW)
75.8
78.3
83.4
81.6
84.8
90.9
87.0
91.6
98.6
92.4
98.4
106.0
98.0
105.3
114.2
103.4
112.3
122.0
77.4
80.0
85.2
83.3
86.6
92.8
88.9
93.5
100.7
94.4
100.5
108.3
100.1
107.6
116.6
105.6
114.6
124.6
78.8
81.4
86.7
84.8
88.2
94.5
90.5
95.2
102.5
96.1
102.3
110.2
101.9
109.5
118.7
107.5
116.7
126.8
80.0
82.7
88.1
86.1
89.6
96.0
91.9
96.7
104.1
97.6
103.9
111.9
103.5
111.2
120.6
109.2
118.5
128.8
81.0
83.7
89.2
87.2
90.7
97.2
93.1
97.9
105.4
98.8
105.2
113.3
104.8
112.6
122.1
110.5
120.0
130.4

Sens.
Cap.
(kW)
69.3
62.8
47.1
74.6
64.9
47.2
79.6
66.6
46.7
84.5
67.8
46.0
89.6
68.4
44.2
94.5
68.8
42.2
74.0
67.0
50.3
79.6
69.3
50.4
85.0
71.1
49.9
90.2
72.4
49.1
95.7
73.1
47.2
100.9
73.4
45.1
78.8
71.4
53.6
84.8
73.8
53.7
90.5
75.7
53.1
96.1
77.1
52.3
101.9
77.8
50.3
107.5
78.2
48.0
80.0
75.7
56.8
86.1
78.2
56.9
91.9
80.2
56.3
97.6
81.7
55.4
103.5
82.4
53.3
109.2
82.9
50.9
81.0
79.8
59.9
87.2
82.5
60.0
93.1
84.6
59.4
98.8
86.2
58.5
104.8
87.0
56.2
110.5
87.4
53.7

CMP
(kW)
23.4
23.6
24.1
23.8
24.1
24.7
24.2
24.7
25.4
24.6
25.3
26.2
25.1
25.9
27.0
25.7
26.7
27.9
23.6
23.8
24.3
24.0
24.3
24.9
24.4
24.9
25.6
24.8
25.5
26.4
25.3
26.1
27.2
25.9
26.9
28.1
23.8
24.0
24.5
24.2
24.5
25.1
24.6
25.1
25.8
25.0
25.7
26.6
25.5
26.3
27.4
26.1
27.1
28.3
23.9
24.1
24.6
24.3
24.6
25.2
24.7
25.2
25.9
25.1
25.8
26.7
25.6
26.4
27.5
26.2
27.2
28.4
24.1
24.3
24.8
24.5
24.8
25.4
24.9
25.4
26.1
25.3
26.0
26.9
25.8
26.6
27.7
26.4
27.4
28.6

Total
Cap
(kW)
72.0
74.0
78.9
77.7
80.3
86.1
83.2
86.9
93.6
88.6
93.5
101.1
93.9
100.2
108.7
99.2
107.0
116.2
73.6
75.5
80.6
79.4
82.0
87.9
85.0
88.7
95.6
90.5
95.5
103.3
95.9
102.4
111.0
101.3
109.3
118.7
74.8
76.8
81.9
80.7
83.4
89.4
86.4
90.2
97.2
92.0
97.1
105.0
97.5
104.1
112.9
103.0
111.1
120.7
75.9
77.9
83.1
81.9
84.6
90.7
87.6
91.5
98.6
93.3
98.5
106.5
98.9
105.6
114.5
104.5
112.7
122.4
76.9
78.9
84.2
82.9
85.7
91.9
88.8
92.7
99.9
94.6
99.8
107.9
100.2
107.0
116.0
105.9
114.2
124.1

Sens.
Cap.
(kW)
65.8
60.6
45.0
71.0
62.8
45.1
76.0
64.6
45.0
80.9
65.8
44.2
85.8
66.7
42.7
90.6
67.0
40.9
70.4
64.8
48.1
76.0
67.2
48.3
81.3
69.1
48.1
86.6
70.4
47.2
91.8
71.3
45.6
96.9
71.7
43.8
74.8
68.9
51.1
80.7
71.4
51.3
86.4
73.4
51.1
92.0
74.8
50.2
97.5
75.8
48.5
103.0
76.2
46.5
75.9
73.1
54.2
81.9
75.8
54.5
87.6
77.9
54.2
93.3
79.4
53.3
98.9
80.5
51.5
104.5
80.9
49.4
76.9
77.2
57.2
82.9
80.0
57.5
88.8
82.2
57.2
94.6
83.8
56.2
100.2
84.9
54.3
105.9
85.4
52.1

CMP
(kW)
25.9
26.1
26.7
26.3
26.6
27.3
26.8
27.2
27.9
27.2
27.8
28.6
27.7
28.4
29.4
28.2
29.1
30.2
26.1
26.3
26.9
26.5
26.8
27.5
27.0
27.4
28.1
27.4
28.0
28.8
27.9
28.6
29.6
28.4
29.3
30.4
26.3
26.5
27.1
26.7
27.0
27.7
27.2
27.6
28.3
27.6
28.2
29.0
28.1
28.8
29.8
28.6
29.5
30.6
26.4
26.6
27.2
26.8
27.1
27.8
27.3
27.7
28.4
27.7
28.3
29.1
28.2
28.9
29.9
28.7
29.6
30.7
26.6
26.8
27.4
27.0
27.3
28.0
27.5
27.9
28.6
27.9
28.5
29.3
28.4
29.1
30.1
28.9
29.8
30.9

40 C
Total
Cap
(kW)
68.0
69.2
73.9
73.4
75.5
81.0
78.9
81.8
88.2
84.2
88.2
95.5
89.4
94.7
102.8
94.6
101.1
110.0
69.4
70.7
75.5
75.0
77.1
82.7
80.6
83.6
90.1
86.0
90.1
97.6
91.3
96.7
105.1
96.6
103.3
112.3
70.6
71.9
76.8
76.2
78.4
84.1
81.9
85.0
91.6
87.4
91.6
99.2
92.8
98.3
106.8
98.2
105.0
114.2
71.6
72.9
77.9
77.3
79.5
85.3
83.1
86.2
92.9
88.6
92.9
100.6
94.1
99.7
108.3
99.6
106.5
115.8
72.6
73.9
79.0
78.4
80.6
86.5
84.2
87.4
94.2
89.9
94.2
102.0
95.4
101.1
109.8
101.0
108.0
117.4

Sens.
Cap.
(kW)
61.8
57.9
42.5
66.6
60.3
42.9
71.6
62.2
42.6
76.4
63.5
42.2
81.2
64.4
40.8
85.9
64.9
39.0
66.2
62.1
45.6
71.5
64.6
46.1
76.8
66.7
45.7
82.0
68.1
45.2
87.0
69.0
43.8
92.1
69.6
41.8
70.6
66.2
48.6
76.2
68.9
49.1
81.9
71.1
48.7
87.4
72.6
48.2
92.8
73.6
46.7
98.2
74.2
44.6
71.6
70.2
51.5
77.3
73.1
52.1
83.1
75.4
51.7
88.6
77.0
51.1
94.1
78.1
49.5
99.6
78.7
47.3
72.6
73.9
54.8
78.4
77.6
55.3
84.2
80.1
54.9
89.9
81.8
54.3
95.4
82.9
52.6
101.0
83.6
50.3

45 C
CMP
(kW)
28.8
29.0
29.5
29.2
29.4
30.1
29.6
30.0
30.8
30.1
30.6
31.5
30.6
31.2
32.3
31.1
31.9
33.1
28.9
29.1
29.6
29.3
29.5
30.2
29.7
30.1
30.9
30.2
30.7
31.6
30.7
31.3
32.4
31.2
32.0
33.2
29.1
29.3
29.8
29.5
29.7
30.4
29.9
30.3
31.1
30.4
30.9
31.8
30.9
31.5
32.6
31.4
32.2
33.4
29.2
29.4
29.9
29.6
29.8
30.5
30.0
30.4
31.2
30.5
31.0
31.9
31.0
31.6
32.7
31.5
32.3
33.5
29.4
29.6
30.1
29.8
30.0
30.7
30.2
30.6
31.4
30.7
31.2
32.1
31.2
31.8
32.9
31.7
32.5
33.7

Total
Cap
(kW)
64.6
65.3
69.7
70.0
71.4
76.6
75.1
77.5
83.7
80.5
83.7
85.7
90.7
65.9
66.7
71.2
71.4
72.9
78.2
76.7
79.1
85.4
82.1
85.4
87.4
66.9
67.7
72.3
72.5
74.1
79.4
77.9
80.3
83.4
86.8
88.8
68.1
68.9
73.5
73.8
75.3
80.8
79.2
81.7
84.8
88.2
90.3
68.8
69.6
74.3
74.6
76.1
81.7
80.1
82.6
85.7
89.2
91.3
-

Sens.
Cap.
(kW)
58.5
55.8
40.6
63.4
58.4
41.0
68.0
60.2
41.1
72.8
61.7
77.6
82.1
62.7
59.8
43.5
67.9
62.6
43.9
72.9
64.5
44.0
78.1
66.1
83.1
66.9
63.9
46.4
72.5
66.9
46.9
77.9
68.9
83.4
70.6
88.8
68.1
68.1
49.5
73.8
71.4
50.1
79.2
73.6
84.8
75.3
90.3
68.8
69.6
52.7
74.6
75.9
53.3
80.1
78.2
85.7
80.1
91.3
-

CMP
(kW)
31.2
31.4
31.8
31.6
31.8
32.4
31.9
32.3
33.0
32.4
32.9
32.9
33.4
31.4
31.6
32.1
31.8
32.0
32.7
32.2
32.6
33.2
32.7
33.2
33.2
31.6
31.8
32.3
32.0
32.2
32.9
32.4
32.8
32.9
33.4
33.4
31.7
31.9
32.4
32.1
32.3
33.0
32.5
32.9
33.0
33.5
33.5
31.7
31.9
32.4
32.1
32.3
33.0
32.5
32.9
33.0
33.5
33.5
-

Note: All capacities are gross cooling values and do not include indoor fan heat. To obtain net cooling, subtract indoor fan heat.

28

RT-PRC014-E4

Performance Data
Heating performances
Table 17 - WK* 125 Net Heating Capacities
-14 C
Indoor
Airflow
m3/h

5720

6430

7140

7850

8560

Entering
Dry
bulb
10 C
12 C
14 C
16 C
18 C
20 C
22 C
24 C
26 C
10 C
12 C
14 C
16 C
18 C
20 C
22 C
24 C
26 C
10 C
12 C
14 C
16 C
18 C
20 C
22 C
24 C
26 C
10 C
12 C
14 C
16 C
18 C
20 C
22 C
24 C
26 C
10 C
12 C
14 C
16 C
18 C
20 C
22 C
24 C
26 C

Total
Cap
(kW)
17.6
17.2
16.8
16.3
15.9
15.5
15.1
14.7
14.3
18.0
17.5
17.1
16.7
16.3
15.9
15.5
15.0
14.6
18.3
17.9
17.5
17.0
16.6
16.2
15.8
15.4
15.0
18.7
18.3
17.8
17.4
17.0
16.5
16.1
15.7
15.3
19.1
18.6
18.2
17.8
17.3
16.9
16.5
16.1
15.7

Power
Input
(kW)
6.6
6.7
6.7
6.8
6.9
7.0
7.0
7.1
7.2
6.7
6.8
6.9
6.9
7.0
7.1
7.2
7.2
7.3
6.8
6.9
7.0
7.1
7.2
7.3
7.3
7.4
7.5
7.1
7.2
7.2
7.3
7.4
7.5
7.6
7.6
7.7
7.3
7.4
7.5
7.6
7.7
7.7
7.8
7.9
7.9

-12 C
Total
Cap
(kW)
19.3
18.8
18.4
18.0
17.5
17.1
16.7
16.3
15.8
19.6
19.2
18.8
18.3
17.9
17.5
17.1
16.6
16.2
20.0
19.6
19.1
18.7
18.2
17.8
17.4
17.0
16.5
20.4
19.9
19.5
19.1
18.6
18.2
17.8
17.3
16.9
20.8
20.3
19.9
19.5
19.0
18.6
18.1
17.7
17.3

Power
Input
(kW)
6.8
6.9
7.0
7.1
7.2
7.2
7.3
7.4
7.5
6.9
7.0
7.1
7.2
7.3
7.4
7.4
7.5
7.6
7.1
7.2
7.3
7.4
7.4
7.5
7.6
7.7
7.7
7.3
7.4
7.5
7.6
7.6
7.7
7.8
7.9
8.0
7.5
7.6
7.7
7.8
7.9
8.0
8.0
8.1
8.2

-8 C
Total
Cap
(kW)
22.5
22.1
21.6
21.2
20.8
20.3
19.9
19.4
19.0
22.9
22.5
22.1
21.6
21.2
20.7
20.3
19.8
19.3
23.3
22.9
22.5
22.0
21.6
21.1
20.6
20.2
19.7
23.7
23.3
22.9
22.4
22.0
21.5
21.0
20.6
20.1
24.2
23.7
23.3
22.8
22.4
21.9
21.5
21.0
20.5

Power
Input
(kW)
7.3
7.4
7.5
7.6
7.7
7.8
7.9
8.0
8.1
7.4
7.5
7.6
7.7
7.8
7.9
8.0
8.1
8.2
7.5
7.6
7.7
7.8
7.9
8.0
8.1
8.2
8.3
7.7
7.8
7.9
8.0
8.1
8.2
8.3
8.4
8.5
7.9
8.0
8.2
8.3
8.4
8.5
8.5
8.6
8.7

-4 C
Total
Cap
(kW)
25.9
25.4
25.0
24.5
24.1
23.6
23.1
22.7
22.2
26.4
25.9
25.5
25.0
24.5
24.1
23.6
23.1
22.6
26.8
26.4
25.9
25.4
25.0
24.5
24.0
23.5
23.1
27.2
26.8
26.3
25.9
25.4
24.9
24.5
24.0
23.5
27.7
27.2
26.8
26.3
25.8
25.4
24.9
24.4
23.9

Power
Input
(kW)
7.8
7.9
8.0
8.1
8.2
8.3
8.4
8.6
8.7
7.8
8.0
8.1
8.2
8.3
8.4
8.5
8.6
8.7
8.0
8.1
8.2
8.3
8.4
8.5
8.6
8.8
8.9
8.1
8.2
8.4
8.5
8.6
8.7
8.8
8.9
9.0
8.3
8.5
8.6
8.7
8.8
8.9
9.0
9.2
9.3

Outdoor Air Temperature


0 C
4 C
Total
Cap
(kW)
29.4
28.9
28.5
28.0
27.5
27.0
26.5
26.1
25.6
29.9
29.5
29.0
28.5
28.0
27.5
27.1
26.6
26.1
30.4
29.9
29.5
29.0
28.5
28.0
27.5
27.0
26.6
30.9
30.4
29.9
29.5
29.0
28.5
28.0
27.5
27.0
31.4
30.9
30.4
29.9
29.5
29.0
28.5
28.0
27.5

Power
Input
(kW)
8.2
8.4
8.5
8.6
8.8
8.9
9.0
9.2
9.3
8.3
8.4
8.5
8.7
8.8
8.9
9.1
9.2
9.3
8.4
8.5
8.6
8.8
8.9
9.0
9.2
9.3
9.4
8.5
8.7
8.8
8.9
9.1
9.2
9.3
9.5
9.6
8.7
8.9
9.0
9.1
9.3
9.4
9.5
9.7
9.8

Total
Cap
(kW)
32.9
32.4
31.9
31.4
30.9
30.4
29.9
29.4
28.9
33.5
33.0
32.5
32.0
31.5
31.0
30.5
30.0
29.5
34.0
33.5
33.0
32.5
32.0
31.5
31.0
30.5
30.0
34.5
34.0
33.5
33.0
32.5
32.0
31.5
31.0
30.5
35.0
34.5
34.0
33.5
33.0
32.5
32.0
31.5
31.0

Power
Input
(kW)
8.7
8.8
9.0
9.1
9.3
9.4
9.6
9.8
9.9
8.7
8.9
9.0
9.2
9.3
9.5
9.6
9.8
9.9
8.8
8.9
9.1
9.2
9.4
9.5
9.7
9.8
10.0
8.9
9.1
9.2
9.4
9.5
9.7
9.8
10.0
10.1
9.1
9.3
9.4
9.6
9.7
9.9
10.0
10.2
10.3

8 C

12 C

16 C

18 C

Total
Cap
(kW)

Power
Input
(kW)

Total
Cap
(kW)

Power
Input
(kW)

Total
Cap
(kW)

Power
Input
(kW)

35.8
35.3
34.8
34.3
33.8
33.3
32.8
32.2

9.3
9.5
9.7
9.9
10.0
10.2
10.4
10.6

38.9
38.4
37.8
37.3
36.8
36.2
35.7

10.0
10.2
10.5
10.7
10.9
11.1
11.3

40.8
40.2
39.6
40.5
40.0
39.4

10.8
11.0
11.3
11.6
11.9
12.1

43.8
43.2
42.5
41.9
41.3

11.8
12.0
12.3
12.6
12.9

36.5
36.0
35.5
35.0
34.4
33.9
33.4
32.9

9.3
9.5
9.6
9.8
10.0
10.2
10.4
10.5

39.6
39.1
38.6
38.0
37.5
37.0
36.4

10.0
10.2
10.4
10.6
10.8
11.0
11.2

41.6
41.0
40.4
39.9
39.3
38.7

10.7
10.9
11.1
11.4
11.6
11.9

44.7
44.1
43.5
42.8
42.2

11.6
11.8
12.1
12.4
12.6

37.1
36.6
36.1
35.5
35.0
34.5
34.0
33.5

9.3
9.5
9.7
9.9
10.0
10.2
10.4
10.6

40.3
39.8
39.2
38.7
38.2
37.6
37.1

10.0
10.2
10.4
10.6
10.8
11.0
11.2

42.3
41.8
41.2
40.6
40.0
39.4

10.6
10.9
11.1
11.3
11.6
11.8

45.6
44.9
44.3
43.7
43.0

11.5
11.7
12.0
12.3
12.5

37.7
37.2
36.7
36.1
35.6
35.1
34.6
34.0

9.5
9.6
9.8
10.0
10.1
10.3
10.5
10.7

41.0
40.4
39.9
39.3
38.8
38.2
37.7

10.1
10.2
10.4
10.6
10.8
11.1
11.3

43.0
42.4
41.9
41.3
40.7
40.1

10.7
10.9
11.1
11.4
11.6
11.8

46.3
45.7
45.1
44.4
43.8

11.4
11.7
12.0
12.2
12.5

38.3
37.7
37.2
36.7
36.1
35.6
35.1
34.6

9.6
9.8
10.0
10.1
10.3
10.5
10.7
10.8

41.6
41.0
40.5
39.9
39.4
38.8
38.3

10.2
10.4
10.6
10.8
11.0
11.2
11.4

43.7
43.1
42.5
41.9
41.3
40.7

10.8
11.0
11.2
11.5
11.7
11.9

47.0
46.4
45.8
45.1
44.5

11.5
11.8
12.0
12.3
12.6

Total Power
Cap Input
(kW) (kW)

Notes:
1. Net heating capacity and power include indoor fan heat at ARI ESP. To obtain net heating at other conditions, subtract fan heat at this condition and add fan heat at new
condition.
2. Integrated heating capacities and power include the effects of defrost in the frost region. All heating capacities and power are at 70 % outdoor relative humidity and demand
defrost cycle.

RT-PRC014-E4

29

Performance Data
Table 18- WK* 155 Net Heating Capacities
-14 C
Indoor
Airflow
m3/h

6800

7650

8500

9350

10200

Entering
Dry
bulb
10 C
12 C
14 C
16 C
18 C
20 C
22 C
24 C
26 C
10 C
12 C
14 C
16 C
18 C
20 C
22 C
24 C
26 C
10 C
12 C
14 C
16 C
18 C
20 C
22 C
24 C
26 C
10 C
12 C
14 C
16 C
18 C
20 C
22 C
24 C
26 C
10 C
12 C
14 C
16 C
18 C
20 C
22 C
24 C
26 C

Total
Cap
(kW)
20.1
19.5
18.8
18.1
17.4
16.7
16.0
15.2
14.5
20.6
19.9
19.2
18.6
17.9
17.2
16.5
15.7
15.0
21.0
20.4
19.7
19.0
18.3
17.6
16.9
16.2
15.4
21.5
20.8
20.2
19.5
18.8
18.1
17.4
16.6
15.9
22.0
21.3
20.7
20.0
19.3
18.6
17.9
17.1
16.4

Power
Input
(kW)
7.8
7.7
7.7
7.7
7.7
7.7
7.6
7.6
7.5
8.0
8.0
7.9
7.9
7.9
7.9
7.8
7.8
7.7
8.2
8.2
8.2
8.2
8.1
8.1
8.1
8.0
8.0
8.5
8.5
8.5
8.4
8.4
8.4
8.4
8.3
8.3
8.8
8.8
8.8
8.8
8.7
8.7
8.7
8.6
8.6

-12 C
Total
Cap
(kW)
22.1
21.5
20.8
20.1
19.4
18.7
18.0
17.2
16.5
22.6
22.0
21.3
20.6
19.9
19.2
18.5
17.7
17.0
23.1
22.4
21.8
21.1
20.4
19.7
18.9
18.2
17.4
23.6
22.9
22.3
21.6
20.9
20.2
19.4
18.7
17.9
24.1
23.4
22.8
22.1
21.4
20.7
19.9
19.2
18.4

Power
Input
(kW)
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
7.9
8.2
8.2
8.2
8.2
8.2
8.2
8.2
8.2
8.1
8.4
8.5
8.4
8.5
8.4
8.4
8.4
8.4
8.4
8.7
8.7
8.7
8.7
8.7
8.7
8.7
8.7
8.6
9.0
9.0
9.0
9.1
9.0
9.0
9.0
9.0
8.9

-8 C
Total
Cap
(kW)
26.1
25.5
24.8
24.1
23.4
22.7
21.9
21.2
20.4
26.7
26.0
25.4
24.7
24.0
23.2
22.5
21.8
21.0
27.2
26.6
25.9
25.2
24.5
23.8
23.0
22.3
21.5
27.7
27.1
26.4
25.7
25.0
24.3
23.6
22.8
22.0
28.3
27.6
26.9
26.3
25.5
24.8
24.1
23.3
22.6

Power
Input
(kW)
8.6
8.6
8.6
8.7
8.7
8.7
8.7
8.7
8.7
8.7
8.8
8.8
8.8
8.9
8.9
8.9
8.9
8.9
8.9
9.0
9.0
9.1
9.1
9.1
9.1
9.1
9.1
9.2
9.2
9.3
9.3
9.3
9.4
9.4
9.4
9.4
9.5
9.5
9.6
9.6
9.6
9.7
9.7
9.7
9.7

-4 C
Total
Cap
(kW)
30.3
29.6
28.9
28.2
27.5
26.8
26.1
25.3
24.5
30.9
30.3
29.6
28.9
28.2
27.4
26.7
25.9
25.2
31.5
30.8
30.2
29.5
28.7
28.0
27.3
26.5
25.8
32.1
31.4
30.7
30.0
29.3
28.6
27.8
27.1
26.3
32.7
32.0
31.3
30.6
29.9
29.2
28.4
27.7
26.9

Power
Input
(kW)
9.1
9.2
9.3
9.3
9.4
9.4
9.5
9.5
9.5
9.3
9.3
9.4
9.5
9.5
9.6
9.6
9.7
9.7
9.4
9.5
9.6
9.7
9.7
9.8
9.8
9.9
9.9
9.7
9.8
9.8
9.9
10.0
10.0
10.1
10.1
10.1
10.0
10.0
10.1
10.2
10.3
10.3
10.4
10.4
10.4

Outdoor Air Temperature


0 C
4 C
Total
Cap
(kW)
34.7
34.0
33.3
32.6
31.9
31.1
30.4
29.6
28.8
35.4
34.7
34.0
33.3
32.6
31.8
31.1
30.3
29.5
36.1
35.4
34.7
34.0
33.2
32.5
31.7
31.0
30.2
36.7
36.0
35.3
34.6
33.9
33.1
32.4
31.6
30.8
37.3
36.6
35.9
35.2
34.5
33.7
33.0
32.2
31.4

Power
Input
(kW)
9.8
9.9
10.0
10.1
10.1
10.2
10.3
10.4
10.4
9.8
10.0
10.1
10.2
10.3
10.3
10.4
10.5
10.5
10.0
10.1
10.2
10.3
10.4
10.5
10.6
10.7
10.7
10.2
10.3
10.4
10.5
10.6
10.7
10.8
10.9
10.9
10.4
10.6
10.7
10.8
10.9
11.0
11.1
11.2
11.2

Total
Cap
(kW)
39.1
38.4
37.7
36.9
36.2
35.4
34.7
33.9
33.1
39.9
39.2
38.5
37.7
37.0
36.2
35.5
34.7
33.9
40.7
39.9
39.2
38.5
37.7
37.0
36.2
35.4
34.6
41.3
40.6
39.9
39.2
38.4
37.7
36.9
36.1
35.3
42.0
41.3
40.6
39.8
39.1
38.3
37.5
36.8
36.0

Power
Input
(kW)
10.4
10.5
10.7
10.8
10.9
11.0
11.1
11.2
11.3
10.4
10.6
10.7
10.9
11.0
11.1
11.2
11.3
11.4
10.5
10.7
10.8
11.0
11.1
11.2
11.3
11.4
11.5
10.7
10.9
11.0
11.2
11.3
11.4
11.5
11.6
11.7
10.9
11.1
11.3
11.4
11.5
11.7
11.8
11.9
12.0

8 C

12 C

Total
Cap
(kW)

Power
Input
(kW)

Total
Cap
(kW)

42.9
42.2
41.4
40.6
39.8
39.1
38.3
37.4

11.3
11.4
11.6
11.7
11.9
12.0
12.1
12.2

43.8
43.1
42.3
41.5
40.8
40.0
39.2
38.4

16 C

18 C
Total Power
Cap Input
(kW) (kW)

Power
Input
(kW)

Total
Cap
(kW)

Power
Input
(kW)

46.9
46.1
45.3
44.5
43.7
42.9
42.0

12.2
12.4
12.6
12.8
12.9
13.1
13.3

50.2
49.4
48.5
48.5
47.6
45.9

13.4
13.6
13.8
14.0
14.2
14.4

54.4
53.5
52.6
51.6
50.7

14.7
14.9
15.1
15.4
15.6

11.3
11.4
11.6
11.7
11.9
12.0
12.2
12.3

47.9
47.1
46.3
45.5
44.7
43.9
43.1

12.2
12.4
12.6
12.8
12.9
13.1
13.3

51.4
50.6
49.7
49.7
48.8
47.1

13.3
13.5
13.7
13.9
14.1
14.3

55.7
54.8
53.9
53.0
52.1

14.5
14.7
15.0
15.2
15.4

44.7
43.9
43.1
42.4
41.6
40.8
40.0
39.2

11.3
11.5
11.7
11.8
12.0
12.1
12.3
12.4

48.8
48.0
47.2
46.4
45.6
44.8
44.0

12.2
12.4
12.6
12.8
13.0
13.2
13.3

52.5
51.6
50.8
50.7
49.9
48.1

13.2
13.5
13.7
13.9
14.1
14.3

56.9
56.0
55.1
54.1
53.2

14.4
14.7
14.9
15.2
15.4

45.4
44.7
43.9
43.1
42.3
41.5
40.7
39.9

11.5
11.6
11.8
12.0
12.1
12.3
12.4
12.6

49.7
48.9
48.1
47.3
46.5
45.7
44.8

12.3
12.5
12.7
12.9
13.1
13.3
13.5

53.4
52.5
51.7
51.7
50.8
49.1

13.3
13.5
13.8
14.0
14.2
14.4

57.9
57.0
56.1
55.2
54.3

14.4
14.7
14.9
15.2
15.4

46.1
45.4
44.6
43.8
43.1
42.3
41.5
40.7

11.7
11.8
12.0
12.2
12.4
12.5
12.7
12.8

50.5
49.7
48.9
48.1
47.3
46.4
45.6

12.5
12.7
12.9
13.1
13.3
13.5
13.7

54.3
53.4
52.6
52.5
51.7
50.0

13.4
13.7
13.9
14.1
14.4
14.6

58.9
58.0
57.1
56.2
55.2

14.5
14.8
15.0
15.3
15.6

Notes:
1. Net heating capacity and power include indoor fan heat at ARI ESP. To obtain net heating at other conditions, subtract fan heat at this condition and add fan heat at new
condition.
2. Integrated heating capacities and power include the effects of defrost in the frost region. All heating capacities and power are at 70 % outdoor relative humidity and demand
defrost cycle.

30

RT-PRC014-E4

Performance Data
Table 19 - WK* 200 Net Heating Capacities
-14 C
Indoor
Airflow
m3/h

Entering
Dry
bulb
10 C
12 C
14 C
16 C
8970
18 C
20 C
22 C
24 C
26 C
10 C
12 C
14 C
16 C
10090
18 C
20 C
22 C
24 C
26 C
10 C
12 C
14 C
16 C
11210
18 C
20 C
22 C
24 C
26 C
10 C
12 C
14 C
16 C
12330
18 C
20 C
22 C
24 C
26 C
10 C
12 C
14 C
16 C
13450
18 C
20 C
22 C
24 C
26 C

Total
Cap
(kW)
29.5
28.9
28.2
27.6
27.0
26.3
25.6
24.8
24.0
30.0
29.4
28.8
28.2
27.5
26.9
26.1
25.4
24.7
30.6
30.0
29.4
28.8
28.1
27.5
26.7
26.0
25.3
31.2
30.6
30.0
29.4
28.8
28.1
27.4
26.7
26.0
31.9
31.3
30.7
30.1
29.5
28.8
28.1
27.4
26.6

Power
Input
(kW)
11.0
11.1
11.2
11.2
11.3
11.3
11.3
11.4
11.3
11.3
11.4
11.5
11.5
11.6
11.6
11.7
11.7
11.7
11.7
11.8
11.8
11.9
11.9
12.0
12.0
12.0
12.1
12.1
12.2
12.2
12.3
12.4
12.4
12.4
12.5
12.5
12.6
12.7
12.8
12.8
12.9
12.9
13.0
13.0
13.0

-12 C
Total
Cap
(kW)
32.3
31.7
31.1
30.4
29.7
29.0
28.3
27.6
26.7
32.9
32.3
31.7
31.0
30.3
29.7
28.9
28.2
27.4
33.5
32.9
32.3
31.7
31.0
30.3
29.6
28.9
28.1
34.1
33.6
32.9
32.3
31.7
30.9
30.2
29.5
28.8
34.8
34.3
33.6
33.0
32.4
31.7
31.0
30.2
29.5

Power
Input
(kW)
11.4
11.5
11.6
11.6
11.7
11.8
11.8
11.8
11.8
11.7
11.7
11.8
11.9
12.0
12.0
12.1
12.1
12.2
12.0
12.1
12.2
12.3
12.3
12.4
12.5
12.5
12.5
12.4
12.5
12.6
12.7
12.7
12.8
12.9
12.9
12.9
12.9
13.0
13.1
13.2
13.2
13.3
13.4
13.4
13.4

-8 C
Total
Cap
(kW)
38.0
37.4
36.7
36.0
35.3
34.6
33.8
33.0
32.2
38.7
38.1
37.4
36.7
36.0
35.3
34.5
33.7
33.0
39.4
38.7
38.1
37.4
36.7
36.0
35.2
34.5
33.7
40.0
39.4
38.8
38.1
37.4
36.7
35.9
35.2
34.4
40.8
40.1
39.5
38.8
38.1
37.4
36.7
35.9
35.1

Power
Input
(kW)
12.1
12.2
12.3
12.4
12.5
12.6
12.7
12.8
12.9
12.3
12.4
12.5
12.7
12.8
12.9
13.0
13.0
13.1
12.6
12.7
12.8
13.0
13.1
13.2
13.3
13.4
13.4
13.0
13.1
13.2
13.4
13.5
13.6
13.7
13.8
13.8
13.4
13.6
13.7
13.8
14.0
14.1
14.2
14.2
14.3

-4 C
Total
Cap
(kW)
44.0
43.3
42.6
41.8
41.1
40.3
39.5
38.7
37.9
44.8
44.1
43.4
42.6
41.9
41.1
40.3
39.5
38.7
45.5
44.8
44.1
43.4
42.6
41.9
41.1
40.3
39.5
46.2
45.6
44.8
44.1
43.4
42.6
41.9
41.1
40.2
47.0
46.3
45.6
44.9
44.2
43.4
42.7
41.9
41.0

Power
Input
(kW)
12.8
12.9
13.1
13.2
13.4
13.5
13.6
13.7
13.8
12.9
13.1
13.3
13.4
13.6
13.7
13.8
14.0
14.1
13.2
13.4
13.5
13.7
13.9
14.0
14.1
14.2
14.4
13.5
13.7
13.9
14.1
14.2
14.4
14.5
14.6
14.7
14.0
14.2
14.3
14.5
14.7
14.8
14.9
15.1
15.2

Outdoor Air Temperature


0 C
4 C
Total
Cap
(kW)
50.4
49.6
48.8
48.0
47.2
46.3
45.5
44.6
43.7
51.3
50.5
49.7
48.9
48.1
47.3
46.4
45.5
44.7
52.1
51.3
50.6
49.8
49.0
48.1
47.3
46.4
45.6
52.9
52.2
51.4
50.6
49.8
49.0
48.2
47.3
46.4
53.7
53.0
52.3
51.5
50.7
49.9
49.0
48.2
47.3

Power
Input
(kW)
13.5
13.7
13.9
14.1
14.3
14.4
14.6
14.7
14.9
13.6
13.8
14.0
14.2
14.4
14.6
14.7
14.9
15.1
13.8
14.1
14.3
14.5
14.6
14.8
15.0
15.2
15.3
14.1
14.4
14.6
14.8
15.0
15.2
15.3
15.5
15.7
14.5
14.8
15.0
15.2
15.4
15.6
15.8
15.9
16.1

Total
Cap
(kW)
56.7
55.9
55.0
54.2
53.3
52.4
51.5
50.6
49.6
57.7
56.9
56.1
55.2
54.4
53.5
52.5
51.6
50.7
58.7
57.9
57.1
56.2
55.4
54.5
53.5
52.6
51.7
59.6
58.8
58.0
57.2
56.3
55.4
54.5
53.6
52.7
60.5
59.7
58.9
58.1
57.2
56.4
55.5
54.5
53.6

Power
Input
(kW)
14.3
14.5
14.7
14.9
15.2
15.4
15.5
15.7
15.9
14.3
14.6
14.8
15.0
15.2
15.5
15.7
15.8
16.0
14.5
14.7
15.0
15.2
15.4
15.6
15.9
16.1
16.2
14.7
15.0
15.3
15.5
15.7
15.9
16.2
16.4
16.5
15.1
15.4
15.6
15.9
16.1
16.3
16.5
16.7
16.9

8 C

12 C

16 C

18 C

Total
Cap
(kW)

Power
Input
(kW)

Total
Cap
(kW)

Power
Input
(kW)

62.3
61.4
60.5
59.5
58.6
57.6
56.7
55.7

15.3
15.6
15.9
16.1
16.3
16.6
16.8
17.0

68.1
67.1
66.1
65.1
64.1
63.0
62.0

16.6
16.9
17.1
17.4
17.7
17.9
18.2

73.8
72.8
71.7
70.6
69.4
68.3

17.9
18.2
18.5
18.8
19.1
19.4

79.4
78.2
77.1
76.0
74.8

19.4
19.7
20.0
20.3
20.7

63.6
62.7
61.7
60.8
59.8
58.9
57.9
56.9

15.3
15.6
15.9
16.1
16.4
16.6
16.8
17.1

69.5
68.5
67.6
66.6
65.5
64.5
63.4

16.5
16.8
17.1
17.4
17.6
17.9
18.1

75.5
74.4
73.4
72.2
71.1
70.0

17.8
18.1
18.4
18.7
19.0
19.3

81.4
80.2
79.0
77.9
76.7

19.2
19.5
19.8
20.2
20.5

64.7
63.8
62.9
61.9
61.0
60.0
59.1
58.1

15.5
15.7
16.0
16.3
16.5
16.8
17.0
17.2

70.8
69.9
68.8
67.8
66.8
65.8
64.7

16.5
16.9
17.1
17.4
17.7
18.0
18.3

77.0
75.9
74.8
73.7
72.6
71.5

17.8
18.1
18.4
18.7
19.0
19.3

83.1
81.9
80.8
79.6
78.4

19.1
19.4
19.8
20.1
20.5

65.7
64.8
63.9
63.0
62.1
61.1
60.1
59.1

15.7
16.0
16.2
16.5
16.8
17.0
17.2
17.5

72.1
71.1
70.1
69.0
68.0
67.0
65.9

16.7
17.0
17.3
17.6
17.9
18.2
18.5

78.4
77.3
76.2
75.1
74.0
72.9

17.9
18.2
18.6
18.9
19.2
19.5

84.6
83.4
82.3
81.1
79.9

19.1
19.5
19.8
20.2
20.6

66.7
65.9
65.0
64.0
63.1
62.1
61.2
60.2

16.0
16.3
16.6
16.8
17.1
17.4
17.6
17.8

73.2
72.2
71.2
70.2
69.2
68.1
67.1

17.0
17.3
17.6
17.9
18.2
18.5
18.8

79.7
78.6
77.5
76.4
75.3
74.2

18.1
18.5
18.8
19.1
19.4
19.8

86.0
84.9
83.7
82.6
81.4

19.3
19.7
20.1
20.4
20.8

Total
Cap
(kW)

Power
Input
(kW)

Total Power
Cap Input
(kW) (kW)

Notes:
1. Net heating capacity and power include indoor fan heat at ARI ESP. To obtain net heating at other conditions, subtract fan heat at this condition and add fan heat at new
condition.
2. Integrated heating capacities and power include the effects of defrost in the frost region. All heating capacities and power are at 70 % outdoor relative humidity and demand
defrost cycle.

RT-PRC014-E4

31

Performance Data
Table 20 - WK* 265 Net Heating Capacities
-14 C
Indoor
Airflow
m3/h

11520

12960

14400

15840

17280

Entering
Dry
bulb
10 C
12 C
14 C
16 C
18 C
20 C
22 C
24 C
26 C
10 C
12 C
14 C
16 C
18 C
20 C
22 C
24 C
26 C
10 C
12 C
14 C
16 C
18 C
20 C
22 C
24 C
26 C
10 C
12 C
14 C
16 C
18 C
20 C
22 C
24 C
26 C
10 C
12 C
14 C
16 C
18 C
20 C
22 C
24 C
26 C

Total
Cap
(kW)
36.2
35.9
35.3
35.0
34.8
34.8
34.8
35.0
35.2
36.7
36.4
35.8
35.5
35.3
35.3
35.3
35.0
35.2
37.4
37.1
36.5
36.2
36.0
36.0
36.0
35.0
35.2
38.0
37.7
37.1
36.8
36.7
36.7
36.6
35.0
35.2
39.6
39.2
38.6
38.3
38.1
38.1
38.1
35.0
35.2

Power
Input
(kW)
9.9
10.3
10.6
11.1
11.6
12.2
12.6
13.3
14.0
10.0
10.5
10.7
11.2
11.7
12.4
12.8
13.3
14.0
10.2
10.7
10.9
11.5
12.0
12.6
13.1
13.3
14.0
10.4
10.8
11.1
11.7
12.2
12.8
13.3
13.3
14.0
10.0
10.4
10.6
11.2
11.7
12.3
12.7
13.3
14.0

-12 C
Total
Cap
(kW)
38.8
38.3
37.8
37.4
37.2
37.1
37.0
37.1
37.3
39.4
38.9
38.3
37.9
37.7
37.6
37.5
37.1
37.3
40.1
39.6
39.0
38.6
38.4
38.3
38.2
37.1
37.3
40.8
40.3
39.7
39.3
39.1
39.0
38.9
37.1
37.3
42.5
41.9
41.3
40.9
40.7
40.6
40.5
37.1
37.3

Power
Input
(kW)
10.1
10.5
10.7
11.2
11.7
12.3
12.8
13.4
14.1
10.2
10.6
10.9
11.4
11.9
12.5
13.0
13.4
14.1
10.4
10.8
11.1
11.6
12.1
12.7
13.2
13.4
14.1
10.6
11.0
11.3
11.8
12.3
12.9
13.4
13.4
14.1
10.2
10.5
10.8
11.3
11.8
12.4
12.9
13.4
14.1

-8 C
Total
Cap
(kW)
44.1
43.3
42.7
42.1
41.8
41.5
41.3
41.4
41.5
44.8
43.9
43.3
42.7
42.4
42.1
41.9
41.4
41.5
45.6
44.7
44.1
43.5
43.2
42.9
42.7
41.4
41.5
46.4
45.5
44.9
44.3
44.0
43.7
43.5
41.4
41.5
48.3
47.3
46.7
46.1
45.8
45.4
45.2
41.4
41.5

Power
Input
(kW)
10.5
10.7
11.1
11.5
12.0
12.5
13.1
13.7
14.3
10.6
10.9
11.3
11.7
12.2
12.7
13.3
13.7
14.3
10.8
11.1
11.5
11.9
12.4
12.9
13.5
13.7
14.3
11.0
11.3
11.7
12.1
12.6
13.1
13.7
13.7
14.3
10.5
10.8
11.2
11.6
12.1
12.6
13.2
13.7
14.3

-4 C
Total
Cap
(kW)
50.5
49.7
48.8
48.1
47.6
47.1
46.8
46.5
46.4
51.3
50.4
49.5
48.8
48.3
47.8
47.4
46.5
46.4
52.2
51.3
50.4
49.7
49.2
48.7
48.3
46.5
46.4
53.1
52.2
51.3
50.6
50.1
49.6
49.2
46.5
46.4
55.3
54.3
53.4
52.6
52.1
51.6
51.2
46.5
46.4

Power
Input
(kW)
10.8
11.2
11.5
12.0
12.5
13.0
13.5
14.0
14.6
11.0
11.4
11.7
12.2
12.7
13.2
13.6
14.0
14.6
11.2
11.6
11.9
12.4
12.9
13.4
13.9
14.0
14.6
11.4
11.8
12.1
12.6
13.1
13.6
14.2
14.0
14.6
10.9
11.3
11.6
12.1
12.6
13.1
13.6
14.0
14.6

Outdoor Air Temperature


0 C
4 C
Total
Cap
(kW)
57.9
56.8
55.8
54.9
54.3
53.7
53.0
52.7
52.5
58.7
57.6
56.6
55.7
55.1
54.5
53.8
52.7
52.5
59.8
58.7
57.6
56.7
56.1
55.5
54.8
52.7
52.5
60.9
59.8
58.6
57.7
57.1
56.5
55.8
52.7
52.5
63.3
62.2
61.0
60.1
59.4
58.8
58.0
52.7
52.5

Power
Input
(kW)
11.4
11.7
12.1
12.6
13.0
13.5
13.9
14.5
15.0
11.6
11.9
12.3
12.8
13.2
13.6
14.1
14.5
15.0
11.8
12.1
12.5
13.0
13.4
13.9
14.4
14.5
15.0
12.0
12.3
12.7
13.2
13.6
14.2
14.7
14.5
15.0
11.5
11.8
12.2
12.7
13.1
13.6
14.1
14.5
15.0

Total
Cap
(kW)
66.0
64.8
63.6
62.5
61.8
60.8
60.0
59.4
58.8
67.0
65.7
64.5
63.4
62.6
61.7
60.9
59.4
58.8
68.2
66.9
65.7
64.6
63.8
62.8
62.0
59.4
58.8
69.4
68.1
66.9
65.8
65.0
63.9
63.1
59.4
58.8
72.2
70.9
69.6
68.4
67.6
66.5
65.7
59.4
58.8

Power
Input
(kW)
12.1
12.5
12.8
13.2
13.6
14.0
14.6
15.1
15.7
12.3
12.7
13.0
13.4
13.8
14.2
14.8
15.1
15.7
12.5
12.9
13.2
13.6
14.1
14.5
15.1
15.1
15.7
12.7
13.1
13.4
13.8
14.4
14.8
15.4
15.1
15.7
12.2
12.6
12.9
13.3
13.8
14.2
14.7
15.1
15.7

8 C
Total
Cap
(kW)

12 C

Power
Input
(kW)

Total
Cap
(kW)

Power
Input
(kW)

16 C
Total
Cap
(kW)

18 C

Power
Input
(kW)

Total Power
Cap Input
(kW) (kW)

73.2
71.8
70.7
69.6
68.5
67.8
67.0
66.4

13.1
13.5
13.8
15.7
14.7
15.3
15.3
15.1

80.3
79.2
78.0
77.0
76.0
75.1
74.2

14.1
14.5
14.9
15.5
16.0
16.6
17.2

87.3
86.2
85.1
83.9
82.8
81.7

15.1
15.6
16.2
16.7
17.4
18.1

90.2
89.2
87.9
86.4
84.8

15.9
16.5
17.1
17.8
18.5

74.2
72.9
71.7
70.6
69.5
68.7
67.0
66.4

13.3
13.6
14.0
15.1
14.9
15.5
15.3
15.1

81.5
80.3
79.1
78.1
77.1
75.1
74.2

14.3
14.7
15.1
15.7
16.2
16.6
17.2

88.6
87.4
86.3
85.1
82.8
81.7

15.3
15.8
16.4
17.0
17.4
18.1

91.5
90.4
89.2
86.4
84.8

16.2
16.7
17.4
17.8
18.5

75.6
74.2
73.0
71.9
70.8
70.0
67.0
66.4

13.5
13.9
14.3
14.7
15.2
15.8
15.3
15.1

83.0
81.8
80.6
79.5
78.5
75.1
74.2

14.6
15.0
15.4
16.0
16.5
16.6
17.2

90.2
89.0
87.9
86.7
82.8
81.7

15.6
16.1
16.7
17.3
17.4
18.1

93.2
92.1
90.8
86.4
84.8

16.5
17.1
17.7
17.8
18.5

77.0
75.5
74.3
73.2
72.1
71.3
67.0
66.4

13.7
14.2
14.6
14.3
15.5
16.1
15.3
15.1

84.5
83.3
82.1
80.9
79.9
75.1
74.2

14.9
15.3
15.7
16.3
16.8
16.6
17.2

91.8
90.6
89.5
88.3
82.8
81.7

15.9
16.4
17.0
17.6
17.4
18.1

94.9
93.8
92.4
86.4
84.8

16.7
17.4
18.0
17.8
18.5

80.1
78.6
77.3
74.8
75.0
74.1
67.0
66.4

13.2
13.6
14.0
14.1
14.8
15.4
15.3
15.1

87.9
86.6
85.4
84.2
83.1
75.1
74.2

14.3
14.6
15.0
15.6
16.1
16.6
17.2

95.5
94.3
93.1
91.8
82.8
81.7

15.2
15.7
16.3
16.9
17.4
18.1

98.7
97.5
96.2
86.4
84.8

16.1
16.6
17.3
17.8
18.5

Notes:
1. Net heating capacity and power include indoor fan heat at ARI ESP. To obtain net heating at other conditions, subtract fan heat at this condition and add fan heat at new
condition.
2. Integrated heating capacities and power include the effects of defrost in the frost region. All heating capacities and power are at 70 % outdoor relative humidity and demand
defrost cycle.

32

RT-PRC014-E4

Performance Data
Table 21 - WK* 290 Net Heating Capacities
-14 C
Indoor
Airflow
m3/h

12960

14580

16200

17820

19440

Entering
Dry
bulb
10 C
12 C
14 C
16 C
18 C
20 C
22 C
24 C
26 C
10 C
12 C
14 C
16 C
18 C
20 C
22 C
24 C
26 C
10 C
12 C
14 C
16 C
18 C
20 C
22 C
24 C
26 C
10 C
12 C
14 C
16 C
18 C
20 C
22 C
24 C
26 C
10 C
12 C
14 C
16 C
18 C
20 C
22 C
24 C
26 C

Total
Cap
(kW)
37.3
37.0
36.6
36.0
35.7
35.5
35.0
35.0
35.2
38.0
37.8
37.4
36.8
36.4
36.2
35.7
35.0
35.2
38.8
38.5
38.1
37.5
37.1
36.9
36.4
35.0
35.2
39.5
39.2
38.8
38.1
37.8
37.6
37.0
35.0
35.2
41.0
40.7
40.3
39.6
39.2
39.0
38.4
35.0
35.2

Power
Input
(kW)
13.0
13.6
14.3
14.8
15.3
16.0
16.7
13.3
14.0
13.3
13.8
14.6
15.1
15.7
16.3
17.1
13.3
14.0
13.6
14.1
14.9
15.4
16.0
16.6
17.4
13.3
14.0
13.8
14.4
15.1
15.7
16.2
16.9
17.7
13.3
14.0
13.1
13.6
14.3
14.9
15.4
16.0
16.8
13.3
14.0

-12 C
Total
Cap
(kW)
40.9
40.6
40.2
39.6
39.2
38.9
38.5
37.1
37.3
41.7
41.4
41.0
40.4
40.0
39.7
39.3
37.1
37.3
42.5
42.2
41.8
41.2
40.8
40.5
40.0
37.1
37.3
43.3
43.0
42.6
42.0
41.6
41.3
40.7
37.1
37.3
45.0
44.6
44.2
43.6
43.2
42.8
42.3
37.1
37.3

Power
Input
(kW)
13.4
13.9
14.6
15.2
15.8
16.4
17.2
13.4
14.1
13.6
14.2
14.9
15.5
16.1
16.8
17.6
13.4
14.1
13.9
14.5
15.2
15.8
16.4
17.1
17.9
13.4
14.1
14.2
14.8
15.5
16.1
16.7
17.4
18.2
13.4
14.1
13.4
14.0
14.7
15.3
15.8
16.5
17.3
13.4
14.1

-8 C
Total
Cap
(kW)
48.1
47.7
47.3
46.8
46.3
45.9
45.5
41.4
41.5
49.1
48.7
48.3
47.8
47.3
46.8
46.4
41.4
41.5
50.0
49.6
49.2
48.7
48.2
47.7
47.3
41.4
41.5
50.9
50.5
50.1
49.6
49.1
48.6
48.2
41.4
41.5
52.9
52.5
52.0
51.5
51.0
50.5
50.0
41.4
41.5

Power
Input
(kW)
14.0
14.7
15.3
16.0
16.6
17.4
18.2
13.7
14.3
14.3
15.0
15.6
16.3
17.0
17.8
18.5
13.7
14.3
14.6
15.3
15.9
16.6
17.3
18.1
18.9
13.7
14.3
14.9
15.6
16.2
16.9
17.6
18.4
19.3
13.7
14.3
14.1
14.8
15.4
16.0
16.7
17.5
18.3
13.7
14.3

-4 C
Total
Cap
(kW)
56.3
55.8
55.1
54.6
54.0
53.6
53.1
46.5
46.4
57.4
56.9
56.2
55.7
55.2
54.7
54.2
46.5
46.4
58.5
58.0
57.3
56.8
56.2
55.7
55.2
46.5
46.4
59.6
59.1
58.4
57.9
57.2
56.7
56.2
46.5
46.4
61.9
61.4
60.6
60.1
59.4
58.9
58.4
46.5
46.4

Power
Input
(kW)
14.8
15.5
16.1
16.7
17.6
18.3
19.0
14.0
14.6
15.1
15.8
16.4
17.1
18.0
18.6
19.4
14.0
14.6
15.4
16.1
16.7
17.4
18.3
19.0
19.8
14.0
14.6
15.7
16.4
17.0
17.7
18.6
19.4
20.2
14.0
14.6
14.9
15.6
16.1
16.8
17.7
18.4
19.1
14.0
14.6

Outdoor Air Temperature


0 C
4 C
Total
Cap
(kW)
65.2
64.5
63.8
63.3
62.6
62.0
61.3
52.7
52.5
66.5
65.9
65.2
64.6
63.9
63.3
62.6
52.7
52.5
67.8
67.1
66.4
65.8
65.1
64.5
63.8
52.7
52.5
69.1
68.3
67.6
67.0
66.3
65.7
65.0
52.7
52.5
71.7
71.0
70.2
69.6
68.9
68.2
67.5
52.7
52.5

Power
Input
(kW)
15.6
16.3
16.9
17.7
18.5
19.2
20.0
14.5
15.0
15.9
16.6
17.3
18.1
18.8
19.6
20.4
14.5
15.0
16.2
16.9
17.6
18.4
19.2
20.0
20.8
14.5
15.0
16.5
17.2
17.9
18.7
19.6
20.4
21.2
14.5
15.0
15.6
16.3
17.0
17.8
18.5
19.3
20.1
14.5
15.0

Total
Cap
(kW)
75.2
74.7
73.7
72.9
72.2
71.3
70.5
59.4
58.8
76.7
76.3
75.2
74.4
73.7
72.7
71.9
59.4
58.8
78.2
77.7
76.6
75.8
75.1
74.1
73.3
59.4
58.8
79.7
79.1
78.0
77.2
76.5
75.5
74.7
59.4
58.8
82.7
82.2
81.0
80.2
79.4
78.4
77.5
59.4
58.8

Power
Input
(kW)
16.4
17.2
17.9
18.7
19.4
20.2
21.0
15.1
15.7
16.8
17.6
18.3
19.0
19.8
20.6
21.4
15.1
15.7
17.1
17.9
18.6
19.4
20.2
21.0
21.8
15.1
15.7
17.4
18.2
18.9
19.8
20.6
21.4
22.2
15.1
15.7
16.5
17.3
18.0
18.7
19.5
20.3
21.1
15.1
15.7

8 C

12 C

16 C

18 C

Total
Cap
(kW)

Power
Input
(kW)

Total
Cap
(kW)

Power
Input
(kW)

85.1
84.1
83.6
82.6
81.5
80.6
67.0
66.4

18.2
18.8
19.6
23.0
21.3
22.0
15.3
15.1

94.9
94.0
93.0
92.1
91.3
75.1
74.2

19.9
20.7
21.4
22.3
23.2
16.6
17.2

104.8
103.8
102.6
101.6
82.8
81.7

21.8
22.7
23.6
24.5
17.4
18.1

109.1
107.8
106.8
86.4
84.8

23.3
24.2
25.2
17.8
18.5

86.9
85.9
85.3
84.3
83.2
82.2
67.0
66.4

18.5
19.2
20.0
22.1
21.7
22.5
15.3
15.1

96.9
96.0
94.9
94.0
93.1
75.1
74.2

20.3
21.1
21.9
22.8
23.7
16.6
17.2

107.0
105.9
104.7
103.7
82.8
81.7

22.3
23.2
24.0
25.0
17.4
18.1

111.4
110.1
109.0
86.4
84.8

23.8
24.7
25.7
17.8
18.5

88.5
87.5
86.9
85.9
84.8
83.8
67.0
66.4

18.9
19.6
20.4
21.3
22.1
22.9
15.3
15.1

98.7
97.8
96.7
95.8
94.9
75.1
74.2

20.7
21.5
22.3
23.2
24.1
16.6
17.2

109.0
107.9
106.7
105.7
82.8
81.7

22.7
23.6
24.5
25.5
17.4
18.1

113.5
112.2
111.1
86.4
84.8

24.3
25.2
26.2
17.8
18.5

90.1
89.1
88.5
87.5
86.4
85.4
67.0
66.4

19.3
20.0
20.8
20.7
22.5
23.3
15.3
15.1

100.5
99.6
98.5
97.6
96.7
75.1
74.2

21.1
21.9
22.7
23.6
24.5
16.6
17.2

111.0
109.9
108.7
107.7
82.8
81.7

23.1
24.0
25.0
26.0
17.4
18.1

115.6
114.2
113.2
86.4
84.8

24.7
25.6
26.7
17.8
18.5

93.6
92.6
91.9
89.2
89.7
88.6
67.0
66.4

18.3
18.9
19.7
20.2
21.3
22.1
15.3
15.1

104.4
103.4
102.3
101.3
100.4
75.1
74.2

20.0
20.8
21.5
22.4
23.3
16.6
17.2

115.3
114.1
112.9
111.8
82.8
81.7

21.9
22.8
23.7
24.6
17.4
18.1

120.1
118.6
117.5
86.4
84.8

23.4
24.3
25.3
17.8
18.5

Total
Cap
(kW)

Power
Input
(kW)

Total Power
Cap Input
(kW) (kW)

Notes:
1. Net heating capacity and power include indoor fan heat at ARI ESP. To obtain net heating at other conditions, subtract fan heat at this condition and add fan heat at new
condition.
2. Integrated heating capacities and power include the effects of defrost in the frost region. All heating capacities and power are at 70 % outdoor relative humidity and demand
defrost cycle.

RT-PRC014-E4

33

Performance Data
Table 22 - WK*340 Net Heating Capacities
-14 C
Indoor
Airflow
m3/h

14400

16200

18000

19800

21600

Entering
Dry
bulb
10 C
12 C
14 C
16 C
18 C
20 C
22 C
24 C
26 C
10 C
12 C
14 C
16 C
18 C
20 C
22 C
24 C
26 C
10 C
12 C
14 C
16 C
18 C
20 C
22 C
24 C
26 C
10 C
12 C
14 C
16 C
18 C
20 C
22 C
24 C
26 C
10 C
12 C
14 C
16 C
18 C
20 C
22 C
24 C
26 C

Total
Cap
(kW)
43.8
43.6
43.2
42.9
42.4
42.2
41.8
35.0
35.2
44.8
44.6
44.2
43.8
43.3
43.1
42.7
35.0
35.2
45.7
45.5
45.1
44.8
44.3
44.0
43.6
35.0
35.2
46.8
46.5
46.1
45.8
45.3
45.0
44.6
35.0
35.2
49.0
48.8
48.4
48.0
47.5
47.2
46.8
35.0
35.2

Power
Input
(kW)
12.7
13.4
13.9
14.5
15.1
15.8
16.4
13.3
14.0
13.0
13.7
14.2
14.8
15.5
16.2
16.8
13.3
14.0
13.3
14.0
14.5
15.2
15.8
16.5
17.2
13.3
14.0
13.6
14.3
14.8
15.5
16.2
16.9
17.5
13.3
14.0
13.2
13.9
14.3
15.0
15.7
16.4
17.0
13.3
14.0

-12 C
Total
Cap
(kW)
47.0
46.7
46.3
46.0
45.5
45.2
44.9
37.1
37.3
48.0
47.7
47.3
47.0
46.5
46.2
45.8
37.1
37.3
49.0
48.7
48.3
48.0
47.5
47.2
46.8
37.1
37.3
50.1
49.8
49.4
49.1
48.6
48.3
47.9
37.1
37.3
52.6
52.2
51.8
51.5
50.9
50.6
50.2
37.1
37.3

Power
Input
(kW)
13.0
13.7
14.2
14.9
15.5
16.2
16.9
13.4
14.1
13.3
14.0
14.5
15.2
15.9
16.5
17.2
13.4
14.1
13.6
14.3
14.8
15.5
16.2
16.9
17.6
13.4
14.1
13.9
14.6
15.1
15.9
16.6
17.3
18.0
13.4
14.1
13.5
14.2
14.7
15.4
16.1
16.8
17.5
13.4
14.1

-8 C
Total
Cap
(kW)
53.3
52.8
52.4
52.2
51.8
51.4
51.0
41.4
41.5
54.4
54.0
53.6
53.4
52.9
52.5
52.1
41.4
41.5
55.6
55.1
54.7
54.5
54.0
53.6
53.2
41.4
41.5
56.9
56.4
56.0
55.8
55.2
54.8
54.4
41.4
41.5
59.6
59.1
58.7
58.5
57.9
57.5
57.1
41.4
41.5

Power
Input
(kW)
13.6
14.3
14.9
15.5
16.3
17.0
17.7
13.7
14.3
13.9
14.6
15.2
15.9
16.6
17.3
18.1
13.7
14.3
14.2
14.9
15.5
16.2
17.0
17.7
18.5
13.7
14.3
14.5
15.2
15.9
16.6
17.4
18.1
18.9
13.7
14.3
14.1
14.8
15.4
16.1
16.9
17.6
18.4
13.7
14.3

-4 C
Total
Cap
(kW)
60.3
59.8
59.4
58.9
58.6
58.0
57.5
46.5
46.4
61.6
61.1
60.7
60.2
59.8
59.2
58.8
46.5
46.4
62.9
62.4
62.0
61.5
61.1
60.5
60.0
46.5
46.4
64.4
63.8
63.4
62.9
62.5
61.9
61.4
46.5
46.4
67.5
66.9
66.5
66.0
65.5
64.9
64.4
46.5
46.4

Power
Input
(kW)
14.3
15.0
15.5
16.2
17.0
17.7
18.5
14.0
14.6
14.6
15.3
15.9
16.5
17.3
18.1
18.9
14.0
14.6
14.9
15.6
16.2
16.9
17.7
18.5
19.3
14.0
14.6
15.2
16.0
16.6
17.3
18.1
18.9
19.7
14.0
14.6
14.8
15.5
16.1
16.8
17.6
18.4
19.2
14.0
14.6

Outdoor Air Temperature


0 C
4 C
Total
Cap
(kW)
67.9
67.5
67.0
66.4
65.8
65.4
64.7
52.7
52.5
69.3
68.9
68.4
67.9
67.3
66.8
66.1
52.7
52.5
70.8
70.4
69.9
69.3
68.7
68.2
67.5
52.7
52.5
72.4
72.0
71.5
70.9
70.3
69.8
69.1
52.7
52.5
75.9
75.5
75.0
74.3
73.7
73.2
72.4
52.7
52.5

Power
Input
(kW)
15.0
15.5
16.3
17.0
17.6
18.5
19.3
14.5
15.0
15.3
15.9
16.6
17.3
18.0
18.9
19.7
14.5
15.0
15.6
16.2
17.0
17.7
18.4
19.3
20.1
14.5
15.0
16.0
16.6
17.4
18.1
18.8
19.7
20.6
14.5
15.0
15.5
16.1
16.9
17.6
18.3
19.2
20.0
14.5
15.0

Total
Cap
(kW)
76.8
76.1
75.2
74.8
74.0
73.3
72.7
59.4
58.8
78.4
77.8
76.9
76.4
75.6
74.9
74.3
59.4
58.8
80.1
79.4
78.5
78.0
77.2
76.5
75.9
59.4
58.8
81.9
81.2
80.3
79.8
79.0
78.3
77.7
59.4
58.8
85.9
85.2
84.2
83.7
82.8
82.1
81.4
59.4
58.8

Power
Input
(kW)
15.6
16.3
17.0
17.7
18.5
19.3
20.0
15.1
15.7
16.0
16.6
17.3
18.1
18.9
19.7
20.5
15.1
15.7
16.3
17.0
17.7
18.5
19.3
20.1
20.9
15.1
15.7
16.7
17.4
18.1
18.9
19.7
20.6
21.4
15.1
15.7
16.2
16.9
17.6
18.4
19.2
20.0
20.7
15.1
15.7

8 C

12 C

16 C

18 C

Total
Cap
(kW)

Power
Input
(kW)

Total
Cap
(kW)

Power
Input
(kW)

Total
Cap
(kW)

Power
Input
(kW)

85.3
84.5
83.8
83.1
82.2
81.5
67.0
66.4

17.1
17.8
18.5
21.9
20.1
21.0
15.3
15.1

94.0
93.3
92.4
91.6
90.9
75.1
74.2

18.7
19.4
20.2
21.0
21.9
16.6
17.2

102.8
102.0
101.0
100.3
82.8
81.7

20.4
21.2
21.9
22.9
17.4
18.1

106.8
105.7
105.0
86.4
84.8

21.7
22.4
23.4
17.8
18.5

87.2
86.4
85.6
84.9
84.0
83.2
67.0
66.4

17.4
18.2
18.9
21.1
20.6
21.4
15.3
15.1

96.1
95.3
94.4
93.6
92.8
75.1
74.2

19.1
19.8
20.7
21.4
22.3
16.6
17.2

105.1
104.2
103.2
102.4
82.8
81.7

20.9
21.6
22.4
23.4
17.4
18.1

109.1
108.0
107.2
86.4
84.8

22.1
22.9
23.9
17.8
18.5

89.0
88.2
87.4
86.7
85.8
85.0
67.0
66.4

17.8
18.6
19.3
20.2
21.0
21.9
15.3
15.1

98.1
97.3
96.4
95.6
94.8
75.1
74.2

19.5
20.2
21.1
21.9
22.8
16.6
17.2

107.3
106.4
105.4
104.6
82.8
81.7

21.3
22.1
22.9
23.9
17.4
18.1

111.4
110.3
109.5
86.4
84.8

22.6
23.4
24.5
17.8
18.5

91.1
90.2
89.4
88.7
87.8
87.0
67.0
66.4

18.2
19.0
19.7
20.0
21.5
22.4
15.3
15.1

100.4
99.5
98.6
97.8
97.0
75.1
74.2

19.9
20.7
21.6
22.4
23.3
16.6
17.2

109.8
108.9
107.8
107.0
82.8
81.7

21.8
22.6
23.4
24.5
17.4
18.1

114.0
112.8
112.0
86.4
84.8

23.1
23.9
25.0
17.8
18.5

95.5
94.6
93.7
90.9
92.0
91.2
67.0
66.4

17.7
18.5
19.2
19.6
20.8
21.7
15.3
15.1

105.2
104.4
103.4
102.5
101.7
75.1
74.2

19.4
20.1
20.9
21.7
22.6
16.6
17.2

115.1
114.1
113.1
112.2
82.8
81.7

21.1
21.9
22.7
23.7
17.4
18.1

119.5
118.3
117.5
86.4
84.8

22.4
23.2
24.3
17.8
18.5

Total Power
Cap Input
(kW) (kW)

Notes:
1. Net heating capacity and power include indoor fan heat at ARI ESP. To obtain net heating at other conditions, subtract fan heat at this condition and add fan heat at new
condition.
2. Integrated heating capacities and power include the effects of defrost in the frost region. All heating capacities and power are at 70 % outdoor relative humidity and demand
defrost cycle.

34

RT-PRC014-E4

Performance Data
Hot water coil heating performances
Table 23 - WK* 125 Hot water coil performances
Indoor
Airflow
m3/h
6430

7140

7850

8560

Entering /
Leaving Water
Temp
60C / 40C
70C / 50C
80C / 60C
90C / 70C
60C / 40C
70C / 50C
80C / 60C
90C / 70C
60C / 40C
70C / 50C
80C / 60C
90C / 70C
60C / 40C
70C / 50C
80C / 60C
90C / 70C

Heat.Cap
(kW)
15.3
42.6
58.1
72.4
15.7
45.7
62.0
77.3
16.1
48.5
65.6
81.8
25.9
51.1
68.9
86.1

Indoor return air temp : 20C


Leaving air
Water
Temp
Flow
(C)
(l/s)
0.2
27C
0.5
40C
0.7
47C
0.9
53C
0.2
27C
0.5
39C
0.7
46C
0.9
52C
0.2
26C
0.6
38C
0.8
45C
0.9
51C
0.3
29C
0.6
38C
0.8
44C
1.0
50C

Pressure
drop*
(kPa)
1.4
6.4
11.3
16.7
1.5
6.9
12.1
18.0
1.5
8.4
14.0
20.4
2.2
8.9
14.8
22.7

Indoor return air temp : 20C


Leaving air
Water
Temp
Flow
(C)
(l/s)
0.2
26C
0.6
38C
0.8
45C
1.0
51C
0.3
29C
0.6
38C
0.8
44C
1.0
50C
0.3
29C
0.6
37C
0.9
43C
1.1
49C
0.4
29C
0.7
36C
0.9
42C
1.1
48C

Pressure
drop*
(kPa)
1.5
7.2
13.7
20.0
2.2
8.8
14.7
22.6
3.5
9.4
16.7
25.1
3.8
10.9
17.7
27.7

Indoor return air temp : 20C


Leaving air
Water
Temp
Flow
(C)
(l/s)
0.3
29C
0.6
37C
0.8
43C
1.0
49C
0.4
29C
0.7
37C
0.9
42C
1.1
48C
0.4
29C
0.7
36C
0.9
41C
1.2
47C
0.4
29C
0.7
35C
1.0
41C
1.2
46C

Pressure
drop*
(kPa)
2.4
9.1
16.2
23.2
3.7
9.7
17.3
26.0
4.0
11.3
19.4
28.8
4.3
12.0
21.5
31.5

(*) Coil + Valve only

Table 24 - TK* /WK* 155 Hot water coil performances


Indoor
Airflow
m3/h
7650

8500

9350

10200

Entering /
Leaving Water
Temp
60C / 40C
70C / 50C
80C / 60C
90C / 70C
60C / 40C
70C / 50C
80C / 60C
90C / 70C
60C / 40C
70C / 50C
80C / 60C
90C / 70C
60C / 40C
70C / 50C
80C / 60C
90C / 70C

Heat.Cap
(kW)
16.0
47.7
64.6
80.6
25.7
50.9
68.6
85.7
28.8
53.8
72.4
90.5
31.3
56.5
75.9
95.0

(*) Coil + Valve only

Table 25 - TK* 175 Hot water coil performances


Indoor
Airflow
m3/h
8860

9850

10840

11830

Entering /
Leaving Water
Temp
60C / 40C
70C / 50C
80C / 60C
90C / 70C
60C / 40C
70C / 50C
80C / 60C
90C / 70C
60C / 40C
70C / 50C
80C / 60C
90C / 70C
60C / 40C
70C / 50C
80C / 60C
90C / 70C

Heat.Cap
(kW)
27.1
52.2
70.2
87.8
30.3
55.4
74.5
93.1
32.9
58.4
78.4
98.1
35.2
61.2
82.1
102.7

(*) Coil + Valve only

RT-PRC014-E4

35

Performance Data
Table 26 - TK* /WK* 200 Hot water coil performances
Indoor
Airflow
m3/h
10090

11210

12330

13450

Entering /
Leaving Water
Temp
60C / 40C
70C / 50C
80C / 60C
90C / 70C
60C / 40C
70C / 50C
80C / 60C
90C / 70C
60C / 40C
70C / 50C
80C / 60C
90C / 70C
60C / 40C
70C / 50C
80C / 60C
90C / 70C

Heat.Cap
(kW)
44.0
67.5
88.7
109.7
47.2
71.8
94.4
116.7
50.1
75.8
99.6
123.3
52.8
79.5
104.5
129.4

Indoor return air temp : 20C


Leaving air
Water
Temp
Flow
(C)
(l/s)
0.5
33C
0.8
40C
1.1
46C
1.3
52C
0.6
32C
0.9
39C
1.1
45C
1.4
51C
0.6
32C
0.9
38C
1.2
44C
1.5
50C
0.6
32C
1.0
37C
1.2
43C
1.5
48C

Pressure
drop*
(kPa)
7.6
16.5
27.6
40.2
9.1
18.6
30.5
45.2
9.7
20.7
34.4
50.1
11.2
22.7
37.2
54.9

Indoor return air temp : 20C


Leaving air
Water
Temp
Flow
(C)
(l/s)
0.6
32C
0.9
38C
1.2
44C
1.5
49C
0.6
31C
1.0
37C
1.3
43C
1.6
48C
0.7
31C
1.0
36C
1.3
42C
1.7
47C
0.7
30C
1.1
36C
1.4
41C
1.7
46C

Pressure
drop*
(kPa)
9.8
21.0
35.0
52.0
11.5
23.3
39.3
57.6
12.1
26.6
43.5
64.0
13.7
28.9
46.7
69.4

Indoor return air temp : 20C


Leaving air
Water
Temp
Flow
(C)
(l/s)
0.58
33 C
0.87
39 C
1.15
45 C
1.41
51 C
0.62
32 C
0.93
38 C
1.22
43 C
1.51
49 C
0.66
31 C
0.99
37 C
1.30
42 C
1.60
48 C
0.70
31 C
1.04
36 C
1.36
41 C
1.68
46 C
0.73
30 C
1.08
36 C
1.42
40 C
1.76
45 C

Pressure
drop*
(kPa)
4.4
9.9
17.0
25.9
5.1
11.3
19.4
29.6
5.7
12.7
21.7
33.2
6.3
14.0
24.0
36.7
6.9
15.2
26.2
40.1

(*) Coil + Valve only

Table 27 - TK* 250 Hot water coil performances


Indoor
Airflow
m3/h
12690

14100

15510

16920

Entering /
Leaving Water
Temp
60C / 40C
70C / 50C
80C / 60C
90C / 70C
60C / 40C
70C / 50C
80C / 60C
90C / 70C
60C / 40C
70C / 50C
80C / 60C
90C / 70C
60C / 40C
70C / 50C
80C / 60C
90C / 70C

Heat.Cap
(kW)
51.0
77.0
101.2
125.3
54.2
81.5
107.1
132.7
57.1
85.7
112.7
139.6
59.8
89.5
117.8
146.0

(*) Coil + Valve only

Table 28 - TK*/WK* 265 Hot water coil performances


Indoor
Airflow
m3/h
11520

12960

14400

15840

17280

Entering /
Leaving Water
Temp
60C / 40C
70C / 50C
80C / 60C
90C / 70C
60C / 40C
70C / 50C
80C / 60C
90C / 70C
60C / 40C
70C / 50C
80C / 60C
90C / 70C
60C / 40C
70C / 50C
80C / 60C
90C / 70C
60C / 40C
70C / 50C
80C / 60C
90C / 70C

Heat.Cap
(kW)
48.5
73.0
95.8
118.4
52.1
78.0
102.3
126.5
55.3
82.5
108.3
134.1
58.3
86.7
113.9
141.0
61.0
90.6
119.0
147.4

(*) Coil + Valve only

36

RT-PRC014-E4

Performance Data
Table 29 - TK*/WK* 290 Hot water coil performances
Indoor
Airflow
m3/h
12960

14580

16200

17820

19440

Entering /
Leaving Water
Temp
60C / 40C
70C / 50C
80C / 60C
90C / 70C
60C / 40C
70C / 50C
80C / 60C
90C / 70C
60C / 40C
70C / 50C
80C / 60C
90C / 70C
60C / 40C
70C / 50C
80C / 60C
90C / 70C
60C / 40C
70C / 50C
80C / 60C
90C / 70C

Heat.Cap
(kW)
52.1
78.0
102.3
126.5
55.7
83.0
109.0
135.0
59.0
87.7
115.2
142.6
61.9
91.9
120.8
149.7
64.6
95.9
126.1
156.3

Indoor return air temp : 20C


Leaving air
Water
Temp
Flow
(C)
(l/s)
0.62
32 C
0.93
38 C
1.22
43 C
1.51
49 C
0.67
31 C
0.99
37 C
1.30
42 C
1.61
48 C
0.71
31 C
1.05
36 C
1.38
41 C
1.70
46 C
0.74
30 C
1.10
35 C
1.44
40 C
1.79
45 C
0.77
30 C
1.15
35 C
1.51
39 C
1.86
44 C

Pressure
drop*
(kPa)
5.1
11.3
19.4
29.6
5.8
12.8
22.0
33.6
6.5
14.3
24.6
37.6
7.1
15.7
27.1
41.4
7.8
17.1
29.5
45.1

Indoor return air temp : 20C


Leaving air
Water
Temp
Flow
(C)
(l/s)
0.66
31 C
0.99
37 C
1.30
42 C
1.60
48 C
0.71
31 C
1.05
36 C
1.38
41 C
1.70
46 C
0.75
30 C
1.11
35 C
1.45
40 C
1.80
45 C
0.78
30 C
1.16
35 C
1.52
39 C
1.88
44 C
0.81
29 C
1.21
34 C
1.59
38 C
1.96
43 C

Pressure
drop*
(kPa)
5.7
12.7
21.7
33.2
6.5
14.3
24.6
37.6
7.2
15.9
27.3
41.8
7.9
17.4
30.0
45.9
8.6
18.8
32.6
49.8

(*) Coil + Valve only

Table 30 - TK*/WK* 340 Hot water coil performances


Indoor
Airflow
m3/h
14400

16200

18000

19800

21600

Entering /
Leaving Water
Temp
60C / 40C
70C / 50C
80C / 60C
90C / 70C
60C / 40C
70C / 50C
80C / 60C
90C / 70C
60C / 40C
70C / 50C
80C / 60C
90C / 70C
60C / 40C
70C / 50C
80C / 60C
90C / 70C
60C / 40C
70C / 50C
80C / 60C
90C / 70C

Heat.Cap
(kW)
55.3
82.5
108.3
134.1
59.0
87.7
115.2
142.6
62.2
92.4
121.4
150.5
65.2
96.7
127.2
157.6
67.9
100.6
132.6
164.3

(*) Coil + Valve only

RT-PRC014-E4

37

Performance Data
Static Pressure Drops Through Accessories
Table 31 - Static pressure drop through accessories
Filter
Airflow
EU2
5720
9
6430
11
WKD/WKH 125
7140
14
7850
17
8560
20
6800
13
TKD/TKH
7650
16
YKD/YKH
8500
19
WKD/WKH
9350
22
155
10200
26
7870
17
TKD/TKH
8860
21
YKD/YKH
9850
25
175
10840
30
11830
35
8970
12
WKD
10090
15
YKD
11210
19
TKD
12330
23
200
13450
27
8970
11
WKH
10090
14
TKH
11210
17
YKH
12330
20
200
13450
23
11280
18
TKD
12690
24
YKD
14100
29
250
15510
36
16920
43
11280
17
TKH
12690
21
YKH
14100
26
250
15510
31
16920
36
11520
20
12960
25
TKD
WKD
14400
31
265
15840
38
17280
45
11520
18
TKH
12960
22
WKH
14400
26
265
15840
31
17280
37
12960
25
TKD
14580
32
WKD
16200
40
290
17820
48
19440
57
12960
22
14580
27
TKH
WKH
16200
33
290
17820
39
19440
46
14400
31
TKD
16200
40
WKD
18000
49
340
19800
60
21600
71
14400
26
TKH
16200
33
WKH
18000
40
340
19800
47
21600
55
*Add only if greater than return air pressure drop

38

Filter
EU4
21
24
27
30
33
27
30
34
37
40
30
34
38
43
47
26
30
33
37
41
23
26
29
33
36
32
36
41
46
51
30
34
38
43
47
34
39
44
49
54
30
35
39
43
48
39
45
50
56
61
35
39
44
49
54
44
50
56
63
69
39
44
50
56
61

Economizer
100%
outside air
6
7
9
10
12
8
10
12
14
16
10
12
15
17
20
29
37
45
55
65
33
41
51
61
72
46
58
71
86
102
52
65
80
96
114
48
60
75
90
107
53
67
82
99
117
60
76
94
114
135
67
84
103
124
147
75
94
116
141
167
82
103
127
153
181

Economizer
100%
return air
5
6
6
7
8
6
7
8
9
10
7
8
9
11
12
6
8
9
11
13
6
8
9
11
13
10
12
14
17
19
10
12
14
17
19
10
12
15
18
21
10
12
15
18
21
12
15
18
22
26
12
15
18
22
26
15
18
22
26
31
15
18
22
26
31

Electric heater
(TK*/WK* only)
4
6
7
9
12
7
9
11
13
16
10
13
16
19
23
13
17
21
25
30
13
17
21
25
30
20
25
32
38
46
19
24
29
35
42
22
28
35
42
50
22
28
35
42
50
28
35
44
53
64
28
35
44
53
64
35
44
55
66
79
35
44
55
66
79

Hot water coil *


(TKD/WKD
only)
37
45
53
62
72
33
40
48
56
65
42
51
61
72
83
33
40
48
56
65
49
59
71
82
95
49
59
71
83
95
59
72
86
100
116
71
86
102
119
138
-

RT-PRC014-E4

Performance Data
Supply fan performances
Table 32 - TKD 155 - TKH 155 Available static Pressure
External Static Pressure (Pa)
25
m3/h

RPM kW

50
RPM

kW

75
RPM

kW

6800
7650
8500

100

125

150

175

200

225

250

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

565

0.7

599

0.77

633

0.85

665

0.93

697

1.02

728

1.1

758

1.19
1.44

571

0.82

603

0.9

634

0.99

665

1.07

694

1.16

723

1.25

752

1.34

780

580

0.97

613

1.07

643

1.16

672

1.25

700

1.34

727

1.43

754

1.53

781

1.63

807

1.73

9350

590

1.13

624

1.24

656

1.35

684

1.46

711

1.55

738

1.65

763

1.75

788

1.86

813

1.96

838

2.07

10200

637 1.44

670

1.57

699

1.69

727

1.81

753

1.92

777

2.02

801

2.13

825

2.24

848

2.35

871

2.46

m3/h

RPM kW

RPM

kW

RPM

kW

RPM

kW

6800

787 1.28

815

1.37

842

1.46

868

1.54

7650

808 1.53

836

1.63

862

1.74

8500

833 1.83

858

1.93

883

2.04

9350

862 2.18

885

2.29

909

2.40

10200

894 2.58

275

300

325

350

375
RPM

kW

400
RPM

425

450

475

500

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

200
kW

RPM

225
kW

RPM

250
kW

Standard Drive
Oversized Drive
Note: Data includes pressure drops for standard filters and wet coil.

Table 33 - TKD 175 - TKH 175 Available static Pressure


External Static Pressure (Pa)
25
50
m3/h
RPM kW RPM kW

RPM

75
kW

RPM

7870

100
kW

RPM

125
kW

RPM

150
kW

RPM

175
kW

593

0.95

623

1.03

651

1.11

679

1.19

706

1.28

733

1.37

761

1.47

788

1.57

815

1.68

653

1.31

680

1.40

706

1.49

731

1.58

756

1.67

780

1.77

805

1.87

829

1.97

853

2.08

2.47

897

2.58

3.07

945

3.18

3.77

996

3.89

475
kW
2.75

RPM

500
kW

8860

623 1.21

9850

687 1.64

714

1.75

739

1.85

763

1.95

786

2.05

809

2.15

831

2.25

853

2.36

875

10840

750 2.16

775

2.28

799

2.40

821

2.51

843

2.62

864

2.73

884

2.84

905

2.95

925

11830

814 2.78

837

2.92

860

3.05

881

3.17

901

3.29

921

3.41

940

3.53

959

3.65

978

m3/h
7870

275
RPM kW
842 1.79

RPM
869

300
kW
1.91

RPM
896

325
kW
2.03

RPM
921

350
kW
2.15

RPM
946

375
kW
2.27

RPM
970

400
kW
2.39

RPM
994

425
kW
2.51

RPM
1016

450
kW
2.63

RPM
1038

8860

877 2.19

901

2.31

925

2.43

949

2.56

973

2.69

997

2.83

1020

2.96

1043

3.1

9850

919

2.7

941

2.82

962

2.94

984

3.07

1006

3.2

1027

3.33

10840

965

3.3

985

3.43

1005

3.55

1025

3.68

1044

3.82

11830

1015 4.02

1033

4.15

Standard Drive
Oversized Drive
Note: Data includes pressure drops for standard filters and wet coil.

RT-PRC014-E4

39

Performance Data
Table 34 - TKD 200 - TKH 200 Available static Pressure
External Static Pressure (Pa)
25
50
m3/h
RPM kW RPM kW

75
kW

RPM

100
kW

RPM

125
kW

RPM

150
kW

RPM

175
kW

RPM

200
kW

RPM

225
kW

RPM

512

0.98

542

1.09

571

1.21

600

1.33

629

1.45

656

1.58

684

1.72

519

1.16

547

1.28

575

1.39

601

1.51

627

1.64

653

1.77

679

1.91

704

2.05

RPM

8970
10090
11210

250
kW

528

1.36

557

1.5

584

1.63

610

1.76

634

1.89

658

2.02

682

2.16

705

2.3

729

2.44

12330

537 1.58

568

1.74

596

1.9

622

2.05

647

2.19

670

2.33

692

2.47

714

2.62

735

2.77

757

2.92

13450

580 2.01

609

2.19

636

2.37

661

2.54

684

2.70

706

2.85

728

3.01

748

3.16

768

3.32

788

3.48

m3/h

RPM kW

275

300

325

350

375

400

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

759

2.14

783

2.27

805

2.41

827

2.55

8970

710

1.86

735

10090

729

2.2

753

2.35

777

2.5

800

2.66

823

2.81

11210

752

2.6

774

2.75

797

2.92

819

3.08

841

3.25

12330

778 3.08

799

3.24

820

3.4

841

3.57

13450

808 3.64

828

3.81

425

450

475

500

RPM

kW

RPM

kW

RPM

kW

RPM

kW

175
kW

RPM

200
kW

RPM

225
kW

RPM

250
kW

Standard Drive
Oversized Drive
Note: Data includes pressure drops for standard filters and wet coil.

Table 35 - TKD 250 - TKH 250 Available static Pressure


External Static Pressure (Pa)
25
50
m3/h
RPM kW RPM kW

RPM

75
kW

RPM

100
kW

606

1.63

9870
11280
12690

RPM

125
kW

RPM

150
kW

RPM

585

1.31

609

1.42

632

1.51

654

1.6

675

1.69

695

1.78

633

1.77

657

1.9

679

2.02

700

2.13

720

2.24

739

2.35

599

1.80

628

1.97

655

2.15

681

2.31

704

2.47

726

2.62

747

2.76

766

2.89

785

3.02

14100

631 2.20

654

2.38

679

2.57

705

2.76

729

2.96

752

3.14

774

3.32

795

3.49

814

3.65

832

3.8

15510

690 2.90

711

3.08

733

3.28

756

3.5

779

3.71

801

3.93

822

4.13

842

4.33

16920

749 3.73

768

3.92

788

4.14

809

4.36

m3/h

RPM kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

9870

714

1.86

733

1.94

751

2.02

769

2.10

786

2.17

802

2.25

818

2.32

834

2.39

849

2.46

864

2.53

11280

757 2.45

775

2.55

793

2.65

810

2.74

827

2.84

843

2.93

859

3.02

874

3.11

889

3.19

904

3.28

12690

803 3.14

820

3.26

837

3.38

853

3.49

869

3.61

885

3.72

901

3.83

916

3.93

931

4.04

14100

850 3.95

866

4.09

883

4.23

898

4.37

275

300

325

350

375

400

425

450

475

500

15510
16920

Standard Drive
Oversized Drive
Note: Data includes pressure drops for standard filters and wet coil.

40

RT-PRC014-E4

Performance Data
Table 36 - TKD 265 - TH 265 Available static pressure
External Static Pressure (Pa)
25
50
m3/h
RPM kW RPM kW
11520

RPM

75
kW

RPM

100
kW

RPM

125
kW

RPM

150
kW

RPM

175
kW

RPM

200
kW

RPM

225
kW

RPM

250
kW

609

1.8

633

2.0

656

2.1

679

2.2

701

2.4

723

2.5

745

12960

589 2.015

613

2.2

637

2.3

661

2.5

683

2.6

704

2.7

725

2.9

745

3.0

765

3.2

785

3.3

14400

645 2.705

668

2.9

691

3.0

714

3.2

734

3.4

754

3.5

773

3.7

792

3.8

811

4.0

829

4.2

15840

700 3.53

723

3.7

746

3.9

768

4.1

787

4.3

806

4.5

824

4.6

842

4.8

859

5.0

876

5.2

17280

756

778

4.7

800

4.9

822

5.2

840

5.4

m3/h

RPM kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

11520

766

2.8

787

3.0

808

3.1

829

3.3

850

3.4

870

3.6

890

3.8

910

4.0

929

4.1

12960

805

3.5

824

3.7

843

3.8

862

4.0

881

4.2

900

4.3

919

4.5

4.5

275

300

325

350

375

400

425

450

475

2.7

500
kW

14400

847

4.3

865

4.5

883

4.7

900

4.9

918

5.0

15840

893

5.3

17280

Standard Drive
Oversized Drive
Note: Data includes pressure drops for standard filters and wet coil.
Table 37 - TKD 290 - TH 290 Available static pressure
External Static Pressure (Pa)
25
50
m3/h
RPM kW RPM kW

RPM

75
kW

RPM

100
kW

RPM

125
kW

RPM

150
kW

RPM

175
kW

RPM

200
kW

RPM

225
kW

RPM

250
kW

12960

14580

741

3.4

760

3.6

16200

727

3.8

747

3.9

766

4.1

784

4.3

802

4.5

17820

738

4.3

757

4.5

776

4.7

794

4.9

812

5.1

829

5.3

846

5.5

19440

734

4.8

753

5.0

772

5.2

790

5.5

808

5.7

825

5.9

842

6.1

859

6.3

876

6.5

892

6.8

m3/h

RPM kW

275

300

325

350

375

400

425

450

475

500

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW
4.4

12960

740

760

3.2

779

3.3

797

3.5

815

3.6

832

3.8

850

3.9

867

4.1

884

4.2

900

14580

779

3.8

797

3.9

815

4.1

833

4.3

850

4.4

867

4.6

884

4.8

900

916

5.1

931

5.3

16200

820

4.7

838

4.9

855

871

5.2

888

5.4

904

5.6

920

5.8

935

951

6.2

966

6.4

17820

863

5.7

880

5.9

896

6.1

912

6.3

928

6.5

943

6.7

958

6.9

973

7.2

988

7.4

1002

7.6

19440

908

924

7.2

939

7.4

954

7.6

969

7.8

984

8.1

999

8.3

1013

8.5

1027

8.7

1041

9.0

Standard Drive
Oversized Drive
Note: Data includes pressure drops for standard filters and wet coil.

RT-PRC014-E4

41

Performance Data
Table 38 - TKD 340 - TH 340 Available static pressure
External Static Pressure (Pa)
25
50
m3/h
RPM kW RPM kW

RPM

75
kW

RPM

100
kW

RPM

125
kW

RPM

150
kW

RPM

175
kW

RPM

200
kW

RPM

225
kW

RPM

250
kW

4400

728

3.26

747

3.43

766

3.6

16200

740

3.88

759

4.06

778

4.24

796

4.425

814

4.61

5.81

18000

740

4.42

759

4.62

777

4.82

795

5.02

813

5.215

831

5.41

848

5.61

865

19800

764 5.285

782

5.5

800

5.715

818

5.93

835

6.15

852

6.37

869

6.59

885

6.81

901

7.03

917

7.25

21600

827 6.77

844

7.01

861

7.25

878

7.49

894

7.725

910

7.96

926

8.2

941

8.44

956

8.685

971

8.93

m3/h

RPM kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

4400

785 3.765

803

3.93

821

4.095

838

4.26

855

4.43

872

4.6

889

4.77

905

4.94

921

5.115

936

5.29

16200

832 4.79

849

4.97

866

5.16

882

5.35

898

5.535

914

5.72

930

5.905

946

6.09

961

6.285

976

6.48

18000

881 6.015

897

6.22

913

6.425

929

6.63

944

6.84

959

7.05

974

7.25

989

7.45

1004

7.66

1018

7.87

19800

933

7.47

948

7.69

963

7.915

978

8.14

993

8.365 1007

8.59

1021 8.815

21600

275

300

325

350

375

400

425

450

475

500

Standard Drive
Oversized Drive
Note: Data includes pressure drops for standard filters and wet coil.
Table 39 - WKD 125 - WKH 125 Available static Pressure
External Static Pressure (Pa)
25
50
m3/h
RPM kW RPM kW

RPM

75
kW

RPM

100
kW

548

0.6

5720
6430
7140
7850

RPM

125
kW

562

0.55

584

0.68
0.83

644

544

0.68

578

0.75

611

150
kW

RPM

175
kW

RPM

601

0.63

639

0.71

620

0.76

655

0.84

0.91

676

RPM

200
kW

RPM

225
kW

675

0.8

709

0.89

741

690

0.93

723

1.03

755

1.13

708

1.09

739

1.19

770

1.29

RPM

250
kW
0.98

542

0.77

577

0.85

609

0.93

640

1.01

670

1.1

700

1.19

730

1.28

759

1.38

788

1.48

578

0.96

612

1.05

643

1.14

671

1.23

699

1.32

727

1.41

755

1.51

782

1.61

809

1.71

8560

541 0.85

m3/h

RPM kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

5720

772 1.06

802

1.15

830

1.24

857

1.33

883

1.41

909

1.50

933

1.59

957

1.68

275

300

325

350

375

400

425

6430

786 1.23

815

1.32

843

1.42

871

1.52

897

1.62

922

1.72

947

1.82

7140

800 1.40

829

1.51

857

1.62

884

1.73

911

1.84

936

1.94

960

2.05

950

2.18

7850

816 1.59

844

1.70

872

1.82

898

1.94

925

2.06

8560

835 1.82

862

1.94

888

2.05

913

2.18

939

2.30

450

475
RPM

kW

500
RPM

kW

Standard Drive
Oversized Drive
Note: Data includes pressure drops for standard filters and wet coil.

42

RT-PRC014-E4

Performance Data
Table 40 - WKD 155 - WKH 155 Available static Pressure
External Static Pressure (Pa)
25
50
m3/h
RPM kW RPM kW

RPM

75
kW

RPM
566

0.7

599

571

0.82

604

0.9

634

6800
7650
8500

100
kW

RPM

125
kW

RPM

150
kW

RPM

175
kW

RPM

200
kW

RPM

0.77

632

0.99

664

225
kW

0.85

664

0.93

696

1.02

727

1.11

757

1.20

1.07

694

1.16

723

1.25

751

1.34

779

1.44

RPM

250
kW

578

0.95

612

1.05

644

1.15

673

1.25

700

1.34

727

1.43

754

1.53

780

1.63

806

1.73

9350

586 1.09

622

1.22

655

1.33

685

1.44

712

1.55

739

1.65

764

1.75

788

1.86

813

1.96

837

2.07

10200

633 1.39

667

1.53

698

1.66

726

1.78

753

1.90

778

2.02

803

2.13

826

2.24

848

2.35

871

2.47

m3/h

RPM kW

RPM

kW

RPM

kW

6800

787 1.29

816

1.38

843

1.47

7650

870 1.54

834

1.64

861

1.74

8500

832 1.83

857

1.94

882

2.04

9350

861 2.18

884

2.29

10200

893 2.58

275

300

325

350
RPM

kW

375
RPM

kW

400
RPM

425

450

475

500

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

250
kW

Standard Drive
Oversized Drive
Note: Data includes pressure drops for standard filters and wet coil.
Table 41 - WKD 200 - WKH 200 Available static Pressure
External Static Pressure (Pa)
25
50
m3/h
RPM kW RPM kW

RPM

75
kW

529

1.2

8970
10090
11210

100
kW

RPM

521

1.01

557

1.32

RPM

125
kW

RPM

150
kW

RPM

175
kW

RPM

200
kW

RPM

225
kW

RPM

550

1.12

579

1.24

608

1.36

636

1.49

664

1.62

691

1.76

584

1.44

610

1.56

636

1.68

662

1.82

687

1.95

712

2.10

540

1.42

569

1.56

595

1.69

621

1.82

645

1.95

669

2.08

692

2.22

715

2.36

738

2.51

582

1.82

610

1.98

635

2.13

659

2.27

681

2.41

704

2.55

725

2.70

747

2.85

768

3.00

2.30

651

2.47

675

2.64

698

2.80

720

2.95

741

3.11

761

3.26

781

3.42

801

3.58

2.80

692

3.01

716

3.20

740

3.39

762

3.58

783

3.75

803

3.92

735

3.61

761

3.85

12330

552 1.66

13450

597

2.11

625

14570

638 2.59

666

15690

677 3.10

707

3.37

16810

715 3.66

748

3.98

m3/h

RPM kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

58970

717 1.90

742

2.04

766

2.17

789

2.31

811

2.45

833

2.58

10090

737 2.25

761

2.40

785

2.56

808

2.71

830

2.87

11210

761 2.66

784

2.82

806

2.98

828

3.15

12330

789 3.16

810

3.32

831

3.49

13450

820 3.75

840

3.91

275

300

325

350

375

400

425
RPM

kW

450
RPM

kW

475
RPM

kW

500
RPM

kW

14570
15690
16810

Standard Drive
Oversized Drive
Note: Data includes pressure drops for standard filters and wet coil.

RT-PRC014-E4

43

Performance Data
Table 42 - WKD 265 - WKH 265 Available static pressure
External Static Pressure (Pa)
25
50
m3/h
RPM kW RPM kW
11520

RPM

75
kW

RPM

100
kW

RPM

125
kW

RPM

150
kW

RPM

175
kW

RPM

200
kW

RPM

225
kW

RPM

250
kW

609

1.84

633

1.97

656

2.09

679

2.23

701

2.36

723

2.51

745

2.65

12960

589 2.02

613

2.16

637

2.31

661

2.45

683

2.60

704

2.74

725

2.89

745

3.03

765

3.19

785

3.34

14400

645 2.71

668

2.87

691

3.04

714

3.20

734

3.36

754

3.52

773

3.68

792

3.84

811

4.01

829

4.17

15840

700 3.53

723

3.72

746

3.91

768

4.10

787

4.28

806

4.46

824

4.64

842

4.81

859

4.99

876

5.16

17280

756 4.50

778

4.72

800

4.94

822

5.16

840

5.36

m3/h

RPM kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

11520

766 2.80

787

2.95

808

3.11

829

3.27

850

3.44

870

3.61

890

3.78

910

3.95

929

4.13

12960

805 3.50

824

3.66

843

3.83

862

3.99

881

4.17

900

4.34

919

4.52

14400

847 4.34

865

4.51

883

4.69

900

4.86

918

5.04

15840

893 5.34

275

17280

300

325

350

375

400

425

450

475

500
kW

Standard Drive
Oversized Drive
Note: Data includes pressure drops for standard filters and wet coil.
Table 43 - WKD 290 - WKH 290 Available static pressure
External Static Pressure (Pa)
25
50
m3/h
RPM kW RPM kW

RPM

75
kW

RPM

100
kW

RPM

125
kW

RPM

150
kW

RPM

175
kW

RPM

200
kW

RPM

225
kW

RPM

250
kW

12960

14580

741

3.40

760

3.60

16200

727

3.80

747

3.90

766

4.10

784

4.30

802

4.50

17820

738

4.30

757

4.50

776

4.70

794

4.90

812

5.10

829

5.30

846

5.50

753

5.00

772

5.20

790

5.50

808

5.70

825

5.90

842

6.10

859

6.30

876

6.50

892

6.80

19440

734 4.80

m3/h

RPM kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

12960

740 3.00

760

3.20

779

3.30

797

3.50

815

3.60

832

3.80

850

3.90

867

4.10

884

4.20

900

4.40

14580

779 3.80

797

3.90

815

4.10

833

4.30

850

4.40

867

4.60

884

4.80

900

5.00

916

5.10

931

5.30

16200

820 4.70

838

4.90

855

5.00

871

5.20

888

5.40

904

5.60

920

5.80

935

6.00

951

6.20

966

6.40

17820

863 5.70

880

5.90

896

6.10

912

6.30

928

6.50

943

6.70

958

6.90

973

7.20

988

7.40

1002

7.60

19440

908

924

7.20

939

7.40

954

7.60

969

7.80

984

8.10

999

8.30

1013

8.50

1027

8.70

1041

9.00

275

7.00

300

325

350

375

400

425

450

475

500

Standard Drive
Oversized Drive
Note: Data includes pressure drops for standard filters and wet coil.

44

RT-PRC014-E4

Performance Data
Table 44 - WKD 340 - WKH 340 Available static pressure
External Static Pressure (Pa)
25
50
m3/h
RPM kW RPM kW

RPM

75
kW

RPM

100
kW

RPM

125
kW

RPM

150
kW

RPM

175
kW

RPM

200
kW

RPM

225
kW

RPM

250
kW

14400

728

3.26

747

3.43

766

3.60

16200

740

3.88

759

4.06

778

4.24

796

4.43

814

4.61

18000

740

4.42

759

4.62

777

4.82

795

5.02

813

5.22

831

5.41

848

5.61

865

5.81

19800

764 5.29

782

5.5

800

5.72

818

5.93

835

6.15

852

6.37

869

6.59

885

6.81

901

7.03

917

7.25

21600

827 6.77

844

7.01

861

7.25

878

7.49

894

7.73

910

7.96

926

8.2

941

8.44

956

8.69

971

8.93

m3/h

RPM kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

14400

785 3.77

803

3.93

821

4.10

838

4.26

855

4.43

872

4.6

889

4.77

905

4.94

921

5.12

936

5.29

16200

832 4.79

849

4.97

866

5.16

882

5.35

898

5.54

914

5.72

930

5.91

946

6.09

961

6.29

976

6.48

18000

881 6.02

897

6.22

913

6.43

929

6.63

944

6.84

959

7.05

974

7.25

989

7.45

1004

7.66

1018

7.87

19800

933

7.47

948

7.69

963

7.92

978

8.14

993

8.37

1007

8.59

1021

8.82

21600

275

300

325

350

375

400

425

450

475

500

Standard Drive
Oversized Drive
Note: Data includes pressure drops for standard filters and wet coil.
Table 45 - YKD 155 - YKH 155 Available static Pressure
External Static Pressure (Pa)
25
50
m3/h
RPM kW RPM kW

RPM

75
kW

RPM

100
kW

RPM

125
kW

564

1.00

587

1.07

610

1.15

633

1.23

560

1.14

583

1.23

605

1.31

627

1.39

648

1.48

669

1.56

606

1.50

628

1.60

649

1.69

669

1.78

689

1.87

708

1.97

694

2.14

713

2.24

732

2.34

750

2.45

6800
7650
8500

559 1.31

584

1.41

RPM

150
kW

RPM

175
kW

RPM

200
kW

225
kW

RPM

250
kW

655

1.31

677

1.39

690

1.65

710

1.74

727

2.06

746

2.16

767

2.55

785

2.65

RPM

9350

610

1.72

633

1.83

654

1.94

675

2.04

10200

661 2.21

683

2.33

703

2.45

722

2.56

m3/h

RPM kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

6800

699 1.47

719

1.55

739

1.63

758

1.71

777

1.79

795

1.86

813

1.94

830

2.01

847

2.09

863

2.16

7650

729 1.82

749

1.92

768

2.01

787

2.10

806

2.19

824

2.28

841

2.37

858

2.46

875

2.55

8500

764 2.25

782

2.35

800

2.45

818

2.55

275

300

325

350

375

400

425

450

475

500

9350
10200

Standard Drive
Oversized Drive
Note: Data includes pressure drops for standard filters and wet coil.

RT-PRC014-E4

45

Performance Data
Table 46 - YKD 175 - YKH 175 Available static Pressure
External Static Pressure (Pa)
25
50
m3/h
RPM kW RPM kW

RPM

75
kW

RPM

100
kW

726

1.58

751

1.96

772

2.05

792

2.13

7870
8860

RPM

125
kW

150
kW

RPM

748

1.66

811

2.22

RPM

175
kW

RPM

770

1.74

791

831

2.31

850

200
kW

RPM

225
kW

1.83

813

1.92

835

2.02

2.40

869

2.5

888

2.60

RPM

250
kW

9850

779 2.41

801

2.52

822

2.62

841

2.72

859

2.82

877

2.91

895

3.01

912

3.11

929

3.21

947

3.31

10840

852 3.19

874

3031

893

3.42

911

3.53

928

3.64

945

3.75

961

3.85

977

3.96

993

4.07

1009

4.18

11830

926 4.12

946

4.25

m3/h

RPM kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

7870

857 2.12

879

2.22

900

2.33

921

2.44

942

2.55

962

2.65

981

2.75

1000

2.86

1018

2.86

1036

3.06

8860

907 2.70

927

2.81

946

2.92

965

3.03

985

3.15

9850

964 3.42

981

3.53

998

3.64

1016

3.76

1033

3.88

10840

1024 4.29

275

300

325

350

375

400

425

450

475

500

11830

Standard Drive
Oversized Drive
Note: Data includes pressure drops for standard filters and wet coil.
Table 47 - YKD 200 - YKH 200 Available static Pressure
External Static Pressure (Pa)
25
50
m3/h
RPM kW RPM kW

RPM

75
kW

RPM

100
kW

RPM

125
kW

529

1.71

548

1.83

8970
10090
11210

RPM

150
kW

RPM

175
kW

RPM

530

1.50

567

1.94

200
kW

RPM

551

1.61

586

2.06

572

1.74

593

604

2.18

623

225
kW

RPM

250
kW

1.87

614

2.00

2.31

641

2.45

530

1.99

551

2.12

570

2.24

588

2.36

606

2.48

623

2.61

640

2.74

657

2.87

673

3.01

693

3.54

709

3.69

12330

548 2.41

573

2.58

594

2.73

613

2.87

630

3.00

646

3.13

662

3.27

678

3.40

13450

593 3.10

617

3.29

638

3.46

656

3.61

672

3.76

688

3.90

703

4.05

718

4.19

m3/h

RPM kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

8970

633 2.14

652

2.27

670

2.4

688

2.54

705

2.67

721

2.8

737

2.93

753

3.06

768

3.19

783

3.31

10090

660 2.60

679

2.75

697

2.91

714

3.06

731

3.21

747

3.35

763

3.50

778

3.65

793

3.80

808

3.95

11210

690 3.16

707

3.31

724

3.47

741

3.64

757

3.81

773

3.98

789

4.14

804

4.31

12330

724 3.84

739

3.99

754

4.15

770

4.31

275

300

325

350

375

400

425

450

475

500

13450

Standard Drive
Oversized Drive
Note: Data includes pressure drops for standard filters and wet coil.

46

RT-PRC014-E4

Performance Data
Table 48 - YKD 250 - YKH 250 Available static Pressure
xternal Static Pressure (Pa)
25
50
m3/h
RPM kW RPM kW

RPM

75
kW

RPM

100
kW

RPM

125
kW

RPM

150
kW

RPM

175
kW

603

1.88

620

1.97

637

2.07

9870
11280
12690

200
kW

RPM

606

1.62

653

2.17

RPM

225
kW

RPM

250
kW

625

1.72

643

1.82

670

2.27

686

2.37

602

2.18

622

2.30

640

2.41

657

2.52

673

2.63

688

2.74

704

2.85

719

2.96

733

3.08

14100

639 2.77

660

2.92

679

3.06

696

3.19

712

3.32

727

3.44

742

3.56

756

3.68

770

3.80

784

3.92

15510

699 3.65

719

3.82

736

3.98

753

4.13

768

4.27

782

4.40

796

4.54

810

4.67

823

4.81

836

4.94

16920

758 4.70

777

4.89

794

5.06

810

5.23

824

5.39

838

5.54

m3/h

RPM kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

9870

662 1.92

681

2.03

699

2.15

717

2.26

735

2.36

752

2.48

768

2.59

784

2.69

800

2.81

815

2.91

11280

702 2.48

718

2.59

734

2.70

750

2.82

767

2.94

783

3.08

800

3.20

815

3.33

831

3.46

846

3.59

12690

748

3.19

762

3.30

776

3.42

791

3.54

805

3.66

819

3.79

834

3.92

848

4.05

14100

797 4.05

810

4.17

823

4.30

836

4.43

849

4.55

15510

848 5.08

275

300

325

350

375

400

425

450

475

500

16920

Standard Drive
Oversized Drive
Note: Data includes pressure drops for standard filters and wet coil.

RT-PRC014-E4

47

Performance Data
Sound Levels
Data is given at 300Pa and 35C ambient air temperature.
Sound Power Reference = 10-12 Watts

Table 49 - Overall Outdoor Sound Power Level (in a Free Field)


TKD/H 155
TKD/H 175
TKD/H 200
TKD/H 250
TKD/H 265
TKD/H 290
TKD/H 340
WKD/H 125
WKD/H 155
WKD/H 200
WKD/H 265
WKD/H 290
WKD/H 340
YKD/H 155
YKD/H 175
YKD/H 200
YKD/H 250

63 Hz
51 dB(A)
53 dB(A)
52 dB(A)
55 dB(A)
64 dBA
66 dBA
66 dBA
48 dB(A)
51 dB(A)
55 dB(A)
64 dB(A)
66 dB(A)
66 dB(A)
51 dB(A)
53 dB(A)
52 dB(A)
55 dB(A)

125 Hz
73 dB(A)
73 dB(A)
73 dB(A)
73 dB(A)
73 dBA
74 dBA
74 dBA
73 dB(A)
73 dB(A)
73 dB(A)
73 dB(A)
74 dB(A)
74 dB(A)
73 dB(A)
73 dB(A)
73 dB(A)
73 dB(A)

250 Hz
77 dB(A)
77 dB(A)
79 dB(A)
79 dB(A)
78 dBA
80 dBA
80 dBA
77 dB(A)
77 dB(A)
79 dB(A)
78 dB(A)
80 dB(A)
80 dB(A)
77 dB(A)
77 dB(A)
79 dB(A)
79 dB(A)

500 Hz
80 dB(A)
80 dB(A)
83 dB(A)
84 dB(A)
81 dBA
83 dBA
83 dBA
80 dB(A)
80 dB(A)
84 dB(A)
81 dB(A)
83 dB(A)
83 dB(A)
80 dB(A)
80 dB(A)
83 dB(A)
84 dB(A)

1000 Hz
80 dB(A)
81 dB(A)
85 dB(A)
85 dB(A)
84 dBA
86 dBA
86 dBA
80 dB(A)
80 dB(A)
85 dB(A)
84 dB(A)
86 dB(A)
86 dB(A)
80 dB(A)
81 dB(A)
85 dB(A)
85 dB(A)

2000 Hz
78 dB(A)
79 dB(A)
83 dB(A)
83 dB(A)
80 dBA
82 dBA
82 dBA
77 dB(A)
79 dB(A)
83 dB(A)
80 dB(A)
82 dB(A)
82 dB(A)
78 dB(A)
79 dB(A)
83 dB(A)
83 dB(A)

4000 Hz
73 dB(A)
73 dB(A)
77 dB(A)
78 dB(A)
75 dBA
77 dBA
77 dBA
72 dB(A)
73 dB(A)
78 dB(A)
76 dB(A)
78 dB(A)
78 dB(A)
73 dB(A)
73 dB(A)
77 dB(A)
78 dB(A)

8000 Hz
66 dB(A)
67 dB(A)
68 dB(A)
69 dB(A)
67 dBA
70 dBA
70 dBA
65 dB(A)
66 dB(A)
69 dB(A)
68 dB(A)
70 dB(A)
70 dB(A)
66 dB(A)
67 dB(A)
68 dB(A)
69 dB(A)

Global
86 dB(A)
86 dB(A)
89 dB(A)
90 dB(A)
88 dBA
90 dBA
90 dBA
85 dB(A)
86 dB(A)
90 dB(A)
88 dB(A)
90 dB(A)
90 dB(A)
86 dB(A)
86 dB(A)
89 dB(A)
90 dB(A)

Table 50 - Supply Indoor Sound Power Level (In Duct)


TKD/H 155
TKD/H 175
TKD/H 200
TKD/H 250
TKD/H 265
TKD/H 290
TKD/H 340
WKD/H 125
WKD/H 155
WKD/H 200
WKD/H 265
WKD/H 290
WKD/H 340
YKD/H 155
YKD/H 175
YKD/H 200
YKD/H 250

48

63 Hz
61 dBA
63 dBA
63 dBA
68 dBA
69 dBA
50 dBA
52 dBA
66 dBA
61 dBA
67 dBA
69 dBA
50 dBA
52 dBA
61 dBA
63 dBA
63 dBA
63 dBA

125 Hz
61 dBA
67 dBA
67 dBA
71 dBA
73 dBA
67 dBA
68 dBA
66 dBA
61 dBA
71 dBA
73 dBA
67 dBA
68 dBA
61 dBA
67 dBA
67 dBA
66 dBA

250 Hz
61 dBA
66 dBA
66 dBA
70 dBA
72 dBA
71 dBA
74 dBA
66 dBA
61 dBA
70 dBA
72 dBA
71 dBA
74 dBA
61 dBA
66 dBA
66 dBA
65 dBA

500 Hz
62 dBA
69 dBA
69 dBA
75 dBA
75 dBA
76 dBA
77 dBA
67 dBA
62 dBA
73 dBA
75 dBA
76 dBA
77 dBA
62 dBA
69 dBA
69 dBA
70 dBA

1000 Hz
63 dBA
69 dBA
69 dBA
74 dBA
75 dBA
78 dBA
80 dBA
68 dBA
63 dBA
73 dBA
75 dBA
78 dBA
80 dBA
63 dBA
69 dBA
69 dBA
69 dBA

2000 Hz
64 dBA
68 dBA
68 dBA
74 dBA
74 dBA
73 dBA
75 dBA
69 dBA
64 dBA
72 dBA
74 dBA
73 dBA
75 dBA
64 dBA
68 dBA
68 dBA
69 dBA

4000 Hz
64 dBA
67 dBA
67 dBA
73 dBA
73 dBA
70 dBA
72 dBA
69 dBA
64 dBA
71 dBA
73 dBA
70 dBA
72 dBA
64 dBA
67 dBA
67 dBA
68 dBA

8000 Hz
57 dBA
58 dBA
58 dBA
64 dBA
64 dBA
64 dBA
66 dBA
62 dBA
57 dBA
62 dBA
64 dBA
64 dBA
66 dBA
57 dBA
58 dBA
58 dBA
59 dBA

Global
71 dBA
76 dBA
76 dBA
81 dBA
82 dBA
82 dBA
84 dBA
76 dBA
71 dBA
80 dBA
82 dBA
82 dBA
84 dBA
71 dBA
76 dBA
76 dBA
76 dBA

RT-PRC014-E4

Performance Data
Table 51 - Return Indoor Sound Power Level (In Duct)
TKD/H 155
TKD/H 175
TKD/H 200
TKD/H 250
TKD/H 265
TKD/H 290
TKD/H 340
WKD/H 125
WKD/H 155
WKD/H 200
WKD/H 265
WKD/H 290
WKD/H 340
YKD/H 155
YKD/H 175
YKD/H 200
YKD/H 250

63 Hz
63 dBA
56 dBA
56 dBA
61 dBA
62 dBA
48 dBA
50 dBA
68 dBA
63 dBA
60 dBA
62 dBA
48 dBA
50 dBA
63 dBA
56 dBA
56 dBA
56 dBA

125 Hz
61 dBA
61 dBA
61 dBA
65 dBA
67 dBA
63 dBA
65 dBA
66 dBA
61 dBA
65 dBA
67 dBA
63 dBA
65 dBA
61 dBA
61 dBA
61 dBA
60 dBA

250 Hz
57 dBA
57 dBA
57 dBA
61 dBA
63 dBA
68 dBA
71 dBA
62 dBA
57 dBA
61 dBA
63 dBA
68 dBA
71 dBA
57 dBA
57 dBA
57 dBA
56 dBA

500 Hz
64 dBA
62 dBA
62 dBA
68 dBA
68 dBA
72 dBA
73 dBA
69 dBA
64 dBA
66 dBA
68 dBA
72 dBA
73 dBA
64 dBA
62 dBA
62 dBA
63 dBA

1000 Hz
66 dBA
68 dBA
68 dBA
73 dBA
74 dBA
74 dBA
76 dBA
71 dBA
66 dBA
72 dBA
74 dBA
74 dBA
76 dBA
66 dBA
68 dBA
68 dBA
68 dBA

2000 Hz
61 dBA
64 dBA
64 dBA
75 dBA
70 dBA
70 dBA
72 dBA
66 dBA
61 dBA
68 dBA
70 dBA
70 dBA
72 dBA
61 dBA
64 dBA
64 dBA
70 dBA

0 dB
0 dB
0 dB
0 dB
0 dB
0 dB
0 dB
0 dB
0 dB
0 dB
0 dB
0 dB
0 dB
0 dB
0 dB
0 dB
0 dB

10200 m3/h
11820 m3/h
13452 m3/h
16920 m3/h
17280 m3/h
19440 m3/h
21600 m3/h
10200 m3/h
11820 m3/h
13452 m3/h
17280 m3/h
19440 m3/h
21600 m3/h
10200 m3/h
11820 m3/h
13452 m3/h
16920 m3/h

+ 3 dB
+ 3 dB
+ 3 dB
+ 3 dB
+ 3 dB
+ 3 dB
+ 3 dB
+ 3 dB
+ 3 dB
+ 3 dB
+ 3 dB
+ 3 dB
+ 3 dB
+ 3 dB
+ 3 dB
+ 3 dB
+ 3 dB

4000 Hz
56 dBA
59 dBA
59 dBA
65 dBA
65 dBA
67 dBA
69 dBA
61 dBA
56 dBA
63 dBA
65 dBA
67 dBA
69 dBA
56 dBA
59 dBA
59 dBA
60 dBA

8000 Hz
48 dBA
51 dBA
51 dBA
58 dBA
58 dBA
61 dBA
63 dBA
53 dBA
48 dBA
55 dBA
58 dBA
61 dBA
63 dBA
48 dBA
51 dBA
51 dBA
53 dBA

Global
71 dBA
71 dBA
71 dBA
78 dBA
78 dBA
78 dBA
80 dBA
76 dBA
71 dBA
75 dBA
78 dBA
78 dBA
80 dBA
71 dBA
71 dBA
71 dBA
73 dBA

Table 52 - Indoor Sound Level Correction with Airflow


TKD/H 155
TKD/H 175
TKD/H 200
TKD/H 250
TKD/H 265
TKD/H 290
TKD/H 340
WKD/H 125
WKD/H 155
WKD/H 200
WKD/H 265
WKD/H 290
WKD/H 340
YKD/H 155
YKD/H 175
YKD/H 200
YKD/H 250

RT-PRC014-E4

6800 m3/h
7880 m3/h
8968 m3/h
11280 m3/h
11520 m3/h
12960 m3/h
14400 m3/h
6800 m3/h
7880 m3/h
8968 m3/h
11520 m3/h
12960 m3/h
14400 m3/h
6800 m3/h
7880 m3/h
8968 m3/h
11280 m3/h

- 3 dB
- 3 dB
- 3 dB
- 3 dB
- 3 dB
- 3 dB
- 3 dB
- 3 dB
- 3 dB
- 3 dB
- 3 dB
- 3 dB
- 3 dB
- 3 dB
- 3 dB
- 3 dB
- 3 dB

8500 m3/h
9850 m3/h
11210 m3/h
14100 m3/h
14400 m3/h
16200 m3/h
18000 m3/h
8500 m3/h
9850 m3/h
11210 m3/h
14400 m3/h
16200 m3/h
18000 m3/h
8500 m3/h
9850 m3/h
11210 m3/h
14100 m3/h

49

Electrical Data
Table 53 - Unit wiring
Standard Evaporator

Model
and
size

Oversized Evaporator

Main
Power
Supply

Minimum
Circuit
Ampacity

Maximum
Overcurrent
Protective Device
(Fuse or Circuit
Breaker)

Minimum
Circuit
Ampacity

Maximum
Overcurrent
Protective Device
(Fuse or Circuit
Breaker)

(V/Ph/Hz)

(A)

(A)

(A)

(A)

Without Electric heat option


TKD/H 155
TKD/H 175
TKD/H 200
TKD/H 250
TKD/H 265
TKD/H 290
TKD/H 340
WKD/H 125
WKD/H 155
WKD/H 200
WKD/H 265
WKD/H 290
WKD/H 340
YKD/H 155
YKD/H 175
YKD/H 200
YKD/H 250

400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50

35
41
44
46.4
61.4
82
82
31.9
35.1
50.4
61.4
82
82
35.6
42.3
44.6
46.4

50
50
63
63
80
125
125
40
50
63
80
125
125
50
50
63
63

36.9
41.9
44.5
62.9
82
85
33.8
37
50.9
62.9
82
85
37.5
43.2
45.1
-

50
50
63
80
125
125
40
50
63
80
125
125
50
50
63
-

With Electric heat option


TKD/H 155
TKD/H 175
TKD/H 200
TKD/H 250
TKD/H 265
TKD/H 290
TKD/H 340
WKD/H 125
WKD/H 155
WKD/H 200
WKD/H 265
WKD/H 290
WKD/H 340

400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50

41
43
61
62
62
82
82
68
71.2
104.5
115.5
136.1
136.1

63
63
80
80
80
125
125
80
80
125
160
160
160

43
43
61
62,9
82
85
69.9
73.1
105
117
136.1
138.7

63
63
80
80
125
125
80
80
125
160
160
160

Maximum length
Table 54 - Zone sensor wire size

Thermostat
THS/P 03

Conventional Thermostat
THS/P 01
THS 02

CO2 sensor

50

Wire size
(mm2)
0.33
0.50
0.75
1.30
2.00
0.33
0.50
0.75
1.30
2.00
0.25
0.50
1.00

Maximum wire length


(m)
45
76
115
185
300
10
15
23
37
60
50
100
200

RT-PRC014-E4

Dimensions and Weights


Figure 6

Dimensions, Weights and Clearances


Overall unit dimensions, shipping weights and operating weights are given
in the General Data tables.
Table 55 - Minimum recommended clearances
Model and size
TKD/TKH 155
TKD/TKH 175
TKD/TKH 200
TKD/TKH 250
TKD/TKH 265
TKD/TKH 290
TKD/TKH 340
WKD/WKH 125
WKD/WKH 155
WKD/WKH 200
WKD/WKH 265
WKD/WKH 290
WKD/WKH 340
YKD/YKH 155
YKD/YKH 175
YKD/YKH 200
YKD/YKH 250

1
1900
1900
1900
1900
1900
1900
1900
1900
1900
1900
1900
1900
1900
1900
1900
1900
1900

Minimum clearances (mm)


2
3
1800
1220
1800
1220
1800
1220
1800
1220
1800
1220
1800
1220
1800
1220
1800
1220
1800
1220
1800
1220
1800
1220
1800
1220
1800
1220
1800
1220
1800
1220
1800
1220
1800
1220

4
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000

5
1300
1300
1300
1300
1300
1300
1300
1300
1300
1300
1300
1300
1300
1300
1300
1300
1300

Weights of Factory-installed Accessories


Net weight should be added to unit weight when ordering factory-installed accessories. To estimate shipping weight,
add 2.3 kg to net weight.
Table 56 - Factory-installed Accessories Net Weights (kg)
Model
and
size
TKD 155
TKD 175
TKD 200
TKD 250
TKD 265
TKD 290
TKD 340
TKH 155
TKH 175
TKH 200
TKH 250
TKH 265
TKH 290
TKH 340
WKD 125
WKD 155
WKD 200
WKD 265
WKD 290
WKD 340
WKH 125
WKH 155
WKH 200
WKH 265
WKH 290
WKH 340
YKD 155
YKD 175
YKD 200
YKD 250
YKH 155
YKH 175
YKH 200
YKH 250

RT-PRC014-E4

Standard
Roofcurb
93
93
107
107
107
107
107
93
93
107
107
107
107
93
93
107
107
-

Adjustable
Roofcurb
220
220
260
260
260
260
260
180
220
260
260
260
260
220
220
260
260
-

Economizer
30
30
37
37
37
37
37
30
30
37
37
37
37
37
20
30
37
37
37
37
20
30
37
37
37
37
30
30
37
37
30
30
37
37

Manual
0-25%
Air Damper
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15

Motorized
0-50%
Air Damper
27
27
34
34
34
34
34
27
27
34
34
34
34
34
27
27
34
34
34
34
27
27
34
34
34
34
27
27
34
34
27
27
34
34

Electric
heater
14
14
18
18
18
18
18
14
14
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
-

Hot
water
coil
85
85
110
110
110
110
110
85
85
110
110
110
110
-

Power
exhaust
fan
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
-

51

Dimensions and Weights


Filters
Table 57 - Filter arrangement
G2/EU2
Model and size
YKH/YKD/TKH/TKD 155 - 175
YKH/TKH 200-250
YKD/TKD 200-250
WKH/WKD 125 - 155
TKH/WKH 200-265-290-340
TKD/WKD 200-265-290-340

52

G4/EU4

Number

Dimensions (mm)

Number

Dimensions (mm)

2x

(508x508x50)

2x

(498x498x40)

4x

(508x635x50)

4x

(500x625x50)
(500x625x50)

8x

(508x635x50)

8x

4x

(508x508x50)

4x

(498x498x40)

4x

(508x635x50)

4x

(500x625x50)

2x

(508x508x50)

2x

(498x498x40)

4x

(508x635x50)

4x

(500x625x50)

8x

(508x635x50)

8x

(500x625x50)

4x

(508x508x50)

4x

(498x498x40)

4x

(508x635x50)

4x

(500x625x50)

RT-PRC014-E4

Controls
Equipment Protection/Operation
Timings and Features

Built In Fan Delay Relay (FDR)


Function

Increased reliability

Provides custom indoor fan timing


sequences for the different types of
equipment, enhancing efficiency
and reliability. Standard

Fewer components (moving


electromechanical parts); less
likelihood of equipment down time
or failure. Standard
Proportional Integral (PI) Control
Proportional - sets corrective action
proportional to deviation from
setpoint. Integral - fine-tunes the
rate of corrective action proportional
to the error (results in superior
temperature control). Standard
Built In "TEST" Mode
Aids in quick verification of system
and control operation; exercises
both hardware and software (no
special tools required). Standard
On Board Diagnostics
Assists with equipment
troubleshooting if a problem should
occur. Standard

Built in Evaporator Defrost Control


Function
Provides low ambient cooling down
to -18C. Standard
Intelligent Fallback
Built-in Default Control provides
adaptive operation, which allows
the equipment to continue to
operate, and provide comfort in the
event of certain input failures. Also,
allows temporary operation without
a thermostat. Standard
Emergency Stop Terminals on Low
Voltage Terminal Board
Provides a convenient point to
disable the equipment completely
and immediately. Standard
Lower Installation Cost

Low Ambient Start Timer (LAST)


Function
Bypasses low pressure control when
a compressor starts, eliminating
nuisance compressor lockouts.
Standard
Anti Short Cycle Timer (ASCT)
Function
Provides a three minute minimum
"ON" time and a three minute
minimum "OFF" time for
compressors; enhances compressor
reliability by ensuring proper oil
return. Standard

When using a Trane THS03 or THP03,


control voltage wiring may be run
up to five times further than any
electromechanical system with no
increase in wire section. Example:
Electromechanical System - 22 m
using 0.5 mm2 wire. Microcontrol
System (THS/P 03) 110 m 0.5 mm2
wire. Standard
Alternating Lead/Lag
During periods of part load
operation, each compressor cycles
alternately as circuit number one,
equalizing compressor wear and run
time. Enable by cutting the wire at
RTRM junction number J3-8.

Time Delay Relay (TDR) Function


Provides an incremental staging
delay between compressors;
minimizes equipment current inrush
and consumption by keeping
compressors from starting
simultaneously. Standard
RT-PRC014-E4

Demand defrost - Heat pump


Defrost only if needed; not based on
time like most other systems.
Adapts to changing weather
conditions and lowers operating
costs. Standard
53

Controls
Heat pump Soft Start
Provides a smooth transition into
heating after defrost, minimizing
noise and compressor stress
associated with switch over.
Standard
Heat pump Smart Recovery and
Smart Staging
Inhibits auxiliary heat operation if
the space is recovering adequately
(0.6C /min) with the heat pump
alone, providing considerable
savings in operating costs. Standard

Economizer Preferred Cooling


Provides fully integrated operation.
Will not turn on a compressor with
the economizer, if the space is
recovering adequately with the
economizer alone (0.1C./minute).
Allows the equipment to be utilized
in more varied applications.
Standard with economizer

Field-installed Control
Options
Zone sensors
Zone sensors are the building
occupants' comfort control devices.
They replace the conventional
electromechanical thermostats.
Zones sensors are to be used with
the Voyager II units with the Micro
control. These sensors are available
in the following options:
TZS001: Sensor only, used when
connected with CCP2 or Tracker
TZS002: Sensor and setpoint
adjustable thumbwheel
TZS004: Sensor, override button,
and setpoint adjustment
thumbwheel

Features lost when using a


conventional thermostat
When a Conventional Thermostat
is applied, equipment operation
differs significantly. The basic
equipment protection features
remain intact, and the following
features end benefits are lost :

TZS004 zone sensor

Proportional Integral (PI) control is


lost, equipment is controlled by a
thermostat or generic building
automation system device.
Intelligent Fall Back is lost, if a
failure occures in the device
controlling the equipment,
operation will cease.
Heat Pump Smart Recovery and
Smart Staging is not available.
Heat Pump operation becomes
more costly unless the generic
control applied can accomplish
this.

54

RT-PRC014-E4

Controls
Room thermostats
Trane Communication Interface
(TCI)
This microprocessor interface
allows the unit to communicate to
Trane's Integrated Comfort system
(CCP2,Tracker).
THS/P01,THS02 room thermostat

THS03, room thermostat

THP03 room thermostat

Table 58 - Characteristics of Room thermostats


Non-programmable
Programmable
Electronic
Control type design
For Cooling Only units
For Heat Pump units
For Gas Fired units
Number of Cooling stages
Auxiliary heating stages
(electric heater, hot water coil,)
Heating stages (heat pump mode)
Liquid crystal display

RT-PRC014-E4

THS01
X
X
electromech.
X
X
2

THP01
X
X
electromech.
X
X
2

THS02
X
X
electromech.
X
2

THS03
X
X
Reliatel
X
X
X
2

THP03
X
X
Reliatel
X
X
X
2

2
X

2
X

1
1
X

2
1
-

2
1
X

55

Mechanical Specifications
General

Compressors

Units shall be dedicated downflow


or horizontal airflow. Operating
range shall be between 46C and 18C cooling as standard from the
factory for all units. All units shall be
factory assembled, internally wired,
fully charged with refrigerant, and
100 percent run-tested before
leaving the factory. Wiring internal
to the unit shall be colored and
numbered for simplified
identification.

All units shall have direct-drive,


hermetic, scroll type compressors
with self-lubrication. Motor shall be
suction gas-cooled and shall have a
voltage utilization range of plus or
minus 10 percent of unit nameplate
voltage. All scroll compressors shall
be provided with internal overloads.

Casing
Unit casing shall be constructed of
heavy gauge galvanized steel.
Exterior surfaces shall be cleaned,
phosphatized, and finished with a
weather-resistant powder polyester
paint. Unit's surface shall be tested
675 hours in a salt spray test in
compliance with NFX 41.002.
Cabinet construction shall allow for
all maintenance on one side of the
unit. Service panels shall have lifting
handles and be removed and
reinstalled by removing not more
than three screws while providing a
water and air tight seal. All exposed
vertical panels, top covers and the
base in the indoor air section shall
be insulated with fire-resistant,
permanent, odorless, foil-faced
insulation. Minimum foil thickness
shall be 0.030 mm. The downflow
unit's base pan shall have no
penetrations within the perimeter of
the curb other than the raised 29
mm high supply/ return openings to
provide an added water integrity
precaution, if the condensate drain
backs up. The base of the unit shall
have provisions for forklift and
crane lifting.
Unit Top
The top cover shall be one piece or
where seams exist, it shall be
double hemmed and gasket sealed
to prevent water leakage.
Filters
Fifty mm filters shall be factory
supplied.

56

Refrigerant Circuits
Each refrigerant circuit shall have
independent fixed orifice expansion
devices, service pressure ports, and
refrigerant line filter driers factoryinstalled as standard. On the reverse
cycle of the heat pump unit, each
circuit shall have an independent
fixed thermal expansion valve.
Evaporator And Condenser Coils
Internally finned 9.5 mm (3/8 inch, in
diameter) copper tubes
mechanically bonded to configured
aluminum plate fin shall be
standard. Coils shall be leak tested
at the factory to ensure pressure
integrity. The evaporator coil and
condenser coil shall be pressure
tested to 3.1 mPa and leak tested to
1.4 mPa. Sloped condensate drain
pans are standard.
Gas Heating Section
The heating section shall have a
drum and tube heat exchanger
design using corrosion resistant
steel components. A forced
combustion blower shall supply
premixed fuel to a single burner
ignited by a pilotless hot surface
ignition system. In order to provide
reliable operation, a negative
pressure gas valve shall be used
that requires blower operation to
initiate gas flow. On an initial call for
heat, the combustion blower shall
purge the heat exchanger 45
seconds before ignition. After three
unsuccessful ignition attempts, the
entire heating system shall be
locked out until manually reset at
the thermostat. Units shall be
suitable for use with natural gas or
propane.

RT-PRC014-E4

Mechanical Specifications
Outdoor Fans

Options and Accessories

The outdoor fans shall be directdrive, statically and dynamically


balanced, draw-through in the
vertical discharge position. The fan
motors shall be permanently
lubricated and shall have built-in
thermal overload protection.

Roof Curb - Downflow - The roof


curb shall be designed to mate with
the downflow unit and provide
support and watertight installation
when installed properly. The roof
curb design shall allow fieldfabricated rectangular supply/return
ductwork to be connected directly to
the curb. Curb shall be shipped
knocked down for field assembly
and shall include wood nailer strips.

Supply Fan
All units shall have belt driven, with
forward-curved blades and
adjustable motor sheaves. All units
shall have an adjustable idler-arm
assembly for quick-adjustment to
fan belts and motor sheaves. All
motors shall be thermally protected.
Oversized motors shall be available
for high static operations.
Controls
Unit shall be completely factory
wired with necessary controls and
contactor pressure lugs or terminal
block for power wiring. Units shall
provide an external location for
mounting a disconnect device.
Microprocessor controls shall be
provided for all 24 volt control
functions. The resident control
algorithms shall make all heating,
cooling, and/or ventilating decisions
in response to electronic signals
from sensors measuring indoor and
outdoor temperatures. The control
algorithm (proportional integral)
maintains accurate temperature
control, minimizes drift from
setpoint, and provides better
building comfort. A centralized
microprocessor shall provide antishort cycle timing and time delay
between compressors to provide a
higher level of machine protection.

Adjustable Roof Curb - This factoryassembled accessory is adjustable


on site and allows correction of the
slope of the roof up to 5%.
Hot Water Coil - Downflow - This
option shall be factory mounted and
placed horizontally in the discharge
section. It shall be shipped with one
3-way valve and a field adjustable
2-step control and frostat protection.

Exhaust fan - This accessory is used


to minimize overpressure in the
building caused by the introduction
of fresh air, when the economizer
fresh air damper is set at 40-50% of
outdoor air (permanent value),
and/or when the pressure drop in
the return duct is between the
building overpressure accepted by
the customer (12-25 Pa) and 200 Pa
(maximum fan static pressure).
When the exhaust fans are off, the
gravity dampers open with
increased building pressure to
relieve the air pressure. When the
exhaust fans are on, around 50% of
airflow can be exhausted,
depending on the pressure drop of
the return.They turn on whenever
the position of the economizer fresh
air dampers meet or exceed the
power exhaust setpoint (when the
supply fan is on).

Electric Heater - Electric heater


elements shall be constructed of
heavy duty nickel chromium
elements internally wire connected.
Each heater package shall have
automatically reset high limit
operating through heating element
contactors. Electric heaters shall be
protected with fuses. Power supply
shall come from the main unit
power supply. All electric heaters
shall be supplied with overheat
thermostat protection.
Economizer - Downflow - This
assembly includes fully modulating
0-100% motor and dampers,
barometric relief, minimum position
setting, preset linkage, wiring
harness and differential enthalpy
control.
Economizer - Horizontal - This
accessory shall be factory-installed
only. The horizontal economizer
shall contain the same features as
the downflow economizer with the
exception of barometric relief.

RT-PRC014-E4

57

Mechanical Specifications
Remote Potentiometer - The
minimum position setting of
economizer and 0-50% motorized
hood can be adjusted with this
accessory.

Smoke Detector - This option shall


trip off in the case of presence of
smoke in the supply side of the unit
and shall close the fresh air damper,
if any, and stop the unit.

Motorized Outside Air Dampers This accessory shall be factory


mounted. Manually set outdoor air
dampers shall provide up to 50%
outside air. Once set, outdoor air
dampers shall open to set position
when indoor fan starts. The damper
shall close to the full closed position
when indoor fan shuts down. This
shall be available for all models.

Firestat - This accessory shall be


field installed in the ductwork and
shall cut out at either 57C or 115C,
depending on the model installed.

Manual Outside Air Damper - Field


installed rain hood and screen shall
provide up to 25% outside air.

Black Epoxy Fin Coating - A


corrosion resistant coating shall
protect indoor and outdoor
aluminium fins as an option.
Fused Disconnect Switch
- These options shall insulate the
unit from the main power supply.

Oversized Motors - Oversized


motors shall be available for high
static applications.
CO2/VOC Sensor - This accessory
shall be compatible with 0-50%
hood and economizer options. It
shall measure CO2 (or CO2 and
Volatile Organic Compounds) in
order to increase or decrease the
fresh air amount in the building.
Figures 7 and 8 - Downflow configuration (A) and Horizontal flow configuration (B)

R = Return
S = Supply
F = Fresh air
E = Exhaust

58

RT-PRC014-E4

Mechanical Specifications
Control Options and
Accessories
Trane Communication Interface
TCI-R - This option shall be provided
to interface with the Trane Integrated
Comfort TM systems (CCP2, Tracker).
Thermostats and Zone Sensors These accessories shall be provided
to interface with the Micro equipped
Voyagers and shall be available in
either manual, automatic or
programmable mode.
Clogged Filter Switch - This option
allows for individual dirty filter
indication. The switch will light the
Service LED on the zone sensor and
will allow continued unit operation.

RT-PRC014-E4

59

www.trane.com
For more information, contact your local
sales office or e-mail us at comfort@trane.com

Literature Order Number

RT-PRC014-E4

Date

0308

Supersedes

RT-PROC014-E4_0607

Stocking Location

Europe

Trane has a policy of continuous product and product data improvement and reserves the right to
change design and specifications without notice. Only qualified technicians should perform the
installation and servicing of equipment referred to in this publication.
Trane bvba
Chausse de Wavre 1789 - 1160 Brussels, Belgium
ON 0888.048.262 - RPR BRUSSELS