W A T L O W

Auto-Tuning PID
Controllers
SD31
The SERIES SD family of PID
temperature controllers utilizes
today’s advanced micro-electronics
technology to provide the value,
benefits and accuracy you’ve come
to expect from Watlow. The SERIES
SD31 offers improved accuracy of
0.1 percent of span as well as a
faster sampling rate of 6.5Hz in a
1
⁄32 DIN package.
The SERIES SD31 controller delivers
many flexible, user-friendly options.
Easily choose factory or user

Single-Loop
Auto-Tuning PID
defaults and display either process
or set point values. Process inputs
are scalable and invertible from the
Output 1
front panel. Other features include
Variable Burst Fire and flexible Control
Input
Outputs, that users can select as Control or Alarm
On-Off, Heat/Cool or as Process or
Output 2
Deviation Alarms. Users can also
select between 11 different Thermo-
couples, a 100 Ohm RTD, a 0 to
Control, Alarm or
20mA or 0 to 10V process input - all Communications
from the front panel - which
eliminates the need for dip-switches.
With optional EIA-485 com- Variable burst fire Accuracy
munications, you can configure,
monitor and data log with such • Prolongs heater life • Calibration accuracy and sensor
optional software products like • Reduces replacement costs conformity: ±0.1 percent of span,
WATVIEW. ±1°C @ the calibrated ambient
“Save and Restore” feature
temperature and rated line voltage
Features and Benefits • Allows the user to save individual
• Calibration ambient temperature =
Simplified navigation or factory settings
25°C ±3°C (77°F ±5°F)
• Allows users to navigate forwards Specifications • Accuracy span: 540°C (1000°F)
or backwards from any menu minimum
Line Voltage/Power
INFOSENSE™ sensor technology • Temperature stability: ±0.1°C/°C
• 100 to 240VÅ(ac), +10/-15
• Thermal sensing technology percent; (85-264VÅ[ac]) 50/60Hz, (±0.2°F/°F) rise in ambient
improves accuracy by a minimum ±5 percent maximum
of 50 percent
• 24Vı(ac/dc), +10/-15 percent; Agency Approvals
Watlow’s patented User Defined 50/60Hz, ±5 percent • UL® 3121, C-UL®‚ CSA, CE,
Menu System
• 10VA maximum power IP65/NEMA 4X
• Allows users to define, save, and consumption
access their most important Menu • NSF for Type J, K, T and E
settings • Data retention upon power failure thermocouples
via nonvolatile memory
Agency approvals
Environment
• UL®‚ C-UL®, CE IP65/NEMA 4X,
plus CSA and NSF • -18 to 65°C (0 to 149°F) operating
temperature
• -40 to 85°C (-40 to 185°F) storage
UL® and C-UL® are registered trademarks of
Underwriter’s Laboratories, Inc. temperature
Modbus™ is a registered trademark of Schneider • 0 to 90 percent RH, non-condensing
Automation, Inc.
27
Auto-Tuning PID
Controllers F.O.B.: Winona, Minnesota

SD31 Type PTII: 0 to 1395°C current available for up to two


(32 to 2543°F) outputs is 60mA
Specifications Cont. Type R: 0 to 1760°C • Solid state relay, Form A, 0.5A @
(32 to 3200°F) 24VÅ(ac) minimum, 264VÅ(ac)
Controller
Type S: 0 to 1760°C maximum, opto-isolated, without
• Microprocessor based user- (32 to 3200°F) contact suppression
selectable control modes Type B: 0 to 1816°C • Process output (Non Isolated)
• Single universal input, up to three (32 to 3300°F) User-selectable 0-10VÎ(dc),
outputs RTD (DIN): -200 to 800°C 0-5VÎ(dc), 1-5VÎ(dc) @
• Control sampling rates: Input = (-328 to 1472°F) 1KΩ minimum, 0-20mA, 4-20mA
6.5Hz, Display = 10Hz and Process: -1999 to 9999 units @ 800Ω maximum
Outputs = 6.5Hz Control Outputs • Open collector 42VÎ(dc) @
Operator Interface Outputs 1 or 2 250mA maximum
• Single 4 digit, 7 segment LED • User selectable for heat/cool as • EIA-485 serial communications
display on-off, P, PI, PD, PID or with Modbus™ protocol
• “Set” infinity and up down keys Alarm action. (output 2 only)
• Isolated EIA-485 Modbus™ serial • Electromechanical relay. Form • 9600, 19.2K or 38.4 baud rates
communications, 9600, 19.2K A, rated 2A @ 120VÅ(ac), Communications
or 38.4K baud rates 2A @ 240VÅ(ac) or 2A @
• Modbus™ EIA-485
Wiring Termination-Touch Safe 30VÎ(dc)
• WATVIEW
Terminals • Switched dc non-isolated
minimum turn on voltage of Dimensions
• Input power and control outputs
12 to 22 AWG 6VÎ(dc) into a minimum 500Ω • 1⁄32 DIN size
load with a maximum on voltage • 97.8 mm (3.85 in.) behind panel
• Sensor inputs and process
of not greater than 12VÎ(dc) maximum
outputs 20 to 28 AWG
into an infinite load. Maximum
Universal Input • Width 52.6 mm (2.07 in.)
switched dc power supply
• Thermocouple, grounded or • Height 29.7 mm (1.17 in.)
ungrounded sensors
Ordering Information
• RTD 2- or 3-wire, platinum, 100Ω
@ 0°C calibration to DIN-curve To order, complete the model number on the right with the information below.
(0.00385 Ω/Ω/°C) S D 31 - _ _ _ A- A A_ _
• Process, 0-20mA @ 100Ω, or
DIN Size
0-10VÎ(dc) @ 20kΩ input 3 = 1⁄32 DIN
impedance; Scalable
Control Type
• Inverse scaling 1 = 1⁄32 DIN single display PID control
• >20MΩ input impedance Power Supply
• Maximum of 20Ω source resistance H = 100 to 240Vı(ac/dc)
Allowable Operating Range L = 24 to 28Vı(ac/dc)
Type J: 0 to 815°C Output 1
(32 to 1500°F) C = Switched dc
K = SSR, Form A, 0.5A
Type K: -200 to 1370°C
F = Universal process
(-328 to 2500°F)
J = Mechanical relay, Form A, 2A
Type T: -200 to 400°C
Output 2
(-328 to 750°F)
A = None
Type N: 0 to 1300°C C = Switched dc
(32 to 2372°F) K = SSR, Form A, 0.5A
Type E: -200 to 800°C J = Mechanical relay, Form A, 2A
(-328 to 1470°F) U = EIA-485 Modbus™ communications
Type C: 0 to 2315°C Display Colors and Custom Options
(32 to 4200°F) 0R = Red (Single display units)
Type D: 0 to 2315°C 0G = Green (Single display units)
28 (32 to 4200°F) XX = Custom options, special overlays, etc.
W A T L O W

Auto-Tuning PID
Controllers
SD_C
The features and performance
offered by SERIES SD_C controllers
make them ideally suited for a broad
range of applications in temperature
and process control.
The SERIES SD_C controllers
include a universal sensor input with
up to three outputs that can be
programmed for heat or cool temp-
erature control or to operate as
process or deviation alarms.
Programming inverse scaling is also

Single-Loop
simplified with the user-friendly set-

Auto-Tuning PID
up menu, providing additional value
without additional cost.
Advanced features of SERIES SD_C
controllers include EIA-485 Modbus™ Output 1
serial communications, Watlow’s SD
1 2 3 %
INFOSENSE™ sensor technology, Control Control or Alarm
infrared remote communications Input Output 2
operation, Watlow’s patented User
Definable Menu System and a “Save
Control, Alarm or Communications
and Restore” feature that allows the Output 3 *
restoration of either factory or user-
defined settings. Infrared
Configure** Control or Alarm
Available in ⁄32, ⁄16, ⁄8 and ⁄4 DIN-
1 1 1 1
Infrared
panel mount sizes, Watlow’s SERIES Monitor**
*1/32 DIN cannot have an Output 3.
SD_C controllers are backed by an **Infrared option is not available on 1/32 DIN.
industry leading three-year warranty
from Watlow Winona. The SERIES
SD_C controllers are NSF, UL® and WATVIEW HMI Specifications
C-UL® listed, CSA and CE certified (Human Machine Interface)
and include the NEMA 4X (IP65) seal. Line Voltage/Power
• Permits operation, configuration • 100 to 240VÅ(ac), +10/-15
Features and Benefits and data logging via a standard percent; (85-264VÅ[ac])
INFOSENSE™ sensor technology Windows® PC 50/60Hz, ±5 percent
• Improves sensor accuracy by a Infrared communications (optional) • 24Vı(ac/dc), +10/-15 percent;
minimum of 50 percent • Facilitates recipe management 50/60Hz, ±5 percent
User Defined Menu System and data logging • 10VA maximum power consumption
• Allows the user to assign up to • Allows easier controller setup, • Data retention upon power failure
20 parameters in the operations operation and monitoring via nonvolatile memory
menu Dual displays Environment
• Improves operational efficiency • Provides better recognition of • -18 to 65°C (0 to 149°F) operating
“Save and Restore” feature process changes temperature
• Allows the user to save individual • -40 to 85°C (-40 to 185°F) storage
or factory settings temperature
Variable burst fire • 0 to 90 percent RH, non-condensing
• Prolongs heater life
• Reduces replacement costs
Windows® is a registered trademark of Microsoft
Corporation. 29
Auto-Tuning PID
Controllers
SD_C Operator Interface Allowable Operating Range
• Dual 4 digit, 7 segment LED Type J: 0 to 815°C
Specifications Cont. displays (32 to 1500°F)
Accuracy • Advance, infinity and up down Type K: -200 to 1370°C
keys (-328 to 2500°F)
• Calibration accuracy and sensor
• Optional IrDA infrared port (not Type T: -200 to 400°C
conformity: ±0.1 percent of span,
available on 1⁄32 DIN) (-328 to 750°F)
±1°C @ the calibrated ambient
temperature and rated line Type N: 0 to 1300°C
• Isolated EIA-485 Modbus™ serial
voltage (32 to 2372°F)
communications. 9600, 19.2K or
38.4K baud rates Type E: -200 to 800°C
• Calibration ambient temperature
(-328 to 1470°F)
= 25°C ±3°C (77°F ±5°F) Wiring Termination -Touch Safe
Type C: 0 to 2315°C
• Accuracy span: 540°C (1000°F) Terminals
(32 to 4200°F)
minimum • Input power and control outputs Type D: 0 to 2315°C
• Temperature stability: ±0.1°C/°C 12 to 22 AWG (32 to 4200°F)
(±0.2°F/°F) rise in ambient • Sensor inputs and process Type PTII: 0 to 1395°C
maximum outputs 20 to 28 AWG (32 to 2543°F)
Agency Approvals Universal Input Type R: 0 to 1760°C
• UL® 3121, C-UL®‚ CSA, CE, • Thermocouple, grounded or (32 to 3200°F)
NEMA 4X/IP65 ungrounded sensors Type S: 0 to 1760°C
• Limit version features FM approval • RTD 2- or 3-wire, platinum, 100Ω (32 to 3200°F)
• NSF for Type J, K, T and E @ 0°C calibration to DIN- Type B: 0 to 1816°C
thermocouples curve (0.00385 Ω/Ω/°C) (32 to 3300°F)
Controller • Process, 0-20mA @ 100Ω, or RTD (DIN): -200 to 800°C
0-10VÎ(dc) @ 20kΩ input (-328 to 1472°F)
• Microprocessor based user-
impedance; Scalable Process: -1999 to 9999 units
selectable control modes
• Inverse scaling Control Outputs
• Single universal input, up to three
outputs • >20MΩ input impedance Outputs 1, 2 , 3 (Output 3 not
available on 1⁄32 DIN)
• Control sampling rates: • Maximum of 20Ω source
Input = 6.5Hz, Display = 10Hz, resistance • User selectable for heat/cool as
and Outputs = 6.5Hz on-off, P, PI, PD, PID or Alarm
action. Not valid for limit controls
Dimensions • Electromechanical relay. Form A,
rated 2A @ 120VÅ(ac), 2A @
DIN Size Behind Panel Width Height 240VÅ(ac) or 2A @ 30VÎ(dc)
(max.)
• Switched dc non-isolated
⁄32 DIN
1
97.8 mm 52.6 mm 29.7 mm
minimum turn on voltage of
(3.85 in.) (2.07 in.) (1.17 in.)
6VÎ(dc) into a minimum 500Ω
⁄16 DIN
1
97.8 mm 52.1 mm 52.1 mm load with a maximum on voltage
(3.85 in.) (2.05 in.) (2.05 in.) of not greater than 12VÎ(dc) into
⁄8 DIN
1
97.8 mm 52.8 mm 99.8 mm an infinite load. Maximum switched
Vertical (3.85 in.) (2.08 in.) (3.93 in.) dc power supply current available
for up to two outputs is 60mA
⁄8 DIN
1
97.8 mm 99.8 mm 52.8 mm
• Solid state relay, Form A, 0.5A @
Horizontal (3.85 in.) (3.93 in.) (2.08 in.)
24VÅ(ac) minimum, 264VÅ(ac)
1
⁄4 DIN 101.1 mm 99.8 mm 99.8 mm maximum, opto-isolated, without
(3.98 in.) (3.93 in.) (3.93 in.) contact suppression

30
W A T L O W

Auto-Tuning PID
Controllers
SD_C Advantages of IDC include
automated logging of key process
Specifications Cont. variables, increased accuracy
and ease of use for recipe or con-
• Process output (Non Isolated) figuration setups. Infrared data
User-selectable 0-10VÎ(dc), communications enhances controller
0-5VÎ(dc), 1-5VÎ(dc) @ data exchange in physically
1KΩ minimum, 0-20mA, 4-20mA restricting environments (such as
@ 800Ω maximum semiconductor clean rooms,
• Electromechanical relay. Form C, governmental radio-active test labs
rated 5A @ 120VÅ(ac), or those hard to reach areas) and
5A @ 240VÅ(ac) or 5A @ reduces the use of paper to record
30VÎ(dc) instrument information as well as
• Open collector 42VÎ(dc) @ human transposition errors.
250mA maximum Infrared Communications

Single-Loop
Auto-Tuning PID
• EIA-485 serial communications The Infrared Data Communications
with Modbus™ protocol (IDC) option is available on all
• 9600, 19.2K or 38.4K baud rates SERIES SD controller models except
the 1⁄32 DIN and can support complete
SERIES SD parameter configuration
and operation. The IDC option
supports wireless communications
with PDAs (personal digital assistants)
or other devices equipped with
infrared communications that support
the Infrared Data Association (IrDA)
1.0 Standard.
The actual user interface or
configuration is dependent on the
WATVIEW HMI master device application software.
WATVIEW, Watlow’s Windows® A source for this software is Instant
based HMI (Human Machine Inter- HMI from Software Horizons.
face) software, supports the SERIES For more information, visit
SD controllers. The software can be www.instanthmi.com/watlow.
used to setup, monitor and edit the
values of controller parameters, to
monitor and manage alarms and to
log and graph process data.
Typical Block Diagram
SERIES SD PID SERIES SD Limit Oven
SD LIMIT SD
1 2 3 % 1 2 3

Input 1 Output 1 Temperature


Sensor
Output 2 Limit
RESET Sensor
Alarm
Heaters

Form C Relay

Note: Consult user manual for proper wiring.


31
Auto-Tuning PID
Controllers F.O.B.: Winona, Minnesota

SD_C Ordering Information


To order, complete the model number on the right with the information below.
SERIES SD_C = Single channel PID controllers S D _C - _ _ _ _ - _ A _ _
DIN Sizes
3 = 1⁄32 DIN
6 = 1⁄16 DIN
8 = 1⁄8 DIN Vertical
9 = 1⁄8 DIN Horizontal
4 = 1⁄4 DIN
Control Type
C = PID Control Dual Display
INFOSENSE™ Sensor Technology Power Supply
H = 100 to 240Vı(ac/dc)
Watlow’s INFOSENSE™ sensor L = 24 to 28Vı(ac/dc)
technology improves temperature
Output 1
sensing accuracy by 50 percent.
C = Switched dc
Each INFOSENSE “smart” sensor K = SSR, Form A, 0.5A
contains four numeric values located F = Universal process
on tags attached to each sensor that J = Mechanical relay, Form A, 2A
are programmed into the SERIES SD Output 2
controller memory. These values A = None
characterize Watlow sensors and C = Switched dc
allow the controller to provide K = SSR, Form A, 0.5A
enhanced accuracy. J = Mechanical relay, Form A, 2A
U = EIA-485 Modbus™ communications
Output 3 (Not available on 1⁄32 DIN)
A = None
C = Switched dc/open collector
K = SSR, Form A, 0.5A
F = Universal process
E = Mechanical relay, Form C, 5A
Infrared Comms Options (IrDA)
A = None (Default selection on 1⁄32 DIN)
R = IrDA ready (Not available on 1⁄32 DIN)
Display Colors and Custom Options
RG= Red Green (Dual display units)
RR = Red Red (Not available on 1⁄32 DIN Dual Display)
XX = Custom options, special overlays, etc.

32
W A T L O W

Auto-Tuning PID
Controllers
SD6C_D
Watlow SERIES SD6C_D offers
excellent static Set Point control and
application flexibility in a 1⁄16th DIN
panel mount package. The SERIES
SD6C_D controller has been
successfully tested for use with both
ODVA and Semi-conductor SIG
standards for DeviceNet™ on CAN
networks.
The SD6C_D single channel
controller includes a universal
sensor input with two outputs that
can be configured as heat or cool or

Single-Loop
Auto-Tuning PID
alarm. The DeviceNet™ com-
munications interface is supplied
DeviceNet™
with either a five pin circular DIN
connector for Semiconductor SIG
specific applications, or with a five
position removable screw terminal
connector for traditional market
applications.
SD D-NET
SD
Additional features of the SD6C_D 1 2 3 % Output 1

family of controllers include Watlow’s


INFOSENSE™ sensor technology, a Control
Input Control or Alarm
user definable menu system and a
Save and Restore feature that allows Output 2
the restoration of factory and user NET MOD
defined parameter values.
Watlow SD6C_D DeviceNet™ Control or Alarm
controllers offer a three year
warranty; are UL®, C-UL® listed,
CSA, CE and NSF certified and
include IP65/NEMA 4 ratings.
Specifications Accuracy
Features and Benefits
Line Voltage/Power • Calibration accuracy and sensor
Variable burst fire conformity: ±0.1 percent of span,
• 100 to 240VÅ(ac), +10/-15
• Prolongs heater life percent; (85-264VÅ[ac]) 50/60Hz, ±1°C @ the calibrated ambient
Ordering Options including ±5 percent temperature and rated line
DeviceNet™ on CAN or voltage
• 24Vı(ac/dc), +10/-15 percent;
SEMI-SIG-ODVA protocols 50/60Hz, ±5 percent • Calibration ambient temperature =
• Provides DeviceNet™ on CAN for 25°C ±3°C (77°F ±5°F)
• 10VA maximum power
Semiconductor applications consumption • Accuracy span: 540°C (1000°F)
• DeviceNet™ on CAN for the minimum
• Data retention upon power failure
packaging or general industrial via nonvolatile memory • Temperature stability: ±0.1°C/°C
markets (±0.2°F/°F) rise in ambient
Environment
maximum
• -18 to 65°C (0 to 149°F) operating
temperature
• -40 to 85°C (-40 to 185°F) storage
temperature
• 0 to 90 percent RH, DeviceNet™ is a trademark of the Open DeviceNet
Vendors Association.
non-condensing 33
Auto-Tuning-PID
Controllers F.O.B.: Winona, Minnesota

SD6C_D Control Outputs • Process output (Non Isolated)


Outputs 1 and 2 User-selectable 0-10VÎ(dc),
0-5VÎ(dc), 1-5VÎ(dc) @
Specifications Cont. • User selectable for heat/cool as
1KΩ minimum, 0-20mA, 4-20mA
Agency Approvals on-off, P, PI, PD, PID or Alarm
@ 800Ω maximum
• UL® 3121, C-UL®‚ CSA, CE, action.
• Electromechanical relay. Form C,
IP65/NEMA 4X and NSF-2 • Electromechanical relay. Form A,
rated 5A @ 120VÅ(ac),
• Microprocessor based rated 2A @ 120VÅ(ac), 2A @
5A @ 240VÅ(ac) or 5A @
user-selectable control modes 240VÅ(ac) or 2A @ 30VÎ(dc)
30VÎ(dc)
• Switched dc non-isolated
• Single universal input, up to three • Open collector 42VÎ(dc) @
minimum turn on voltage of
outputs 250mA maximum
6VÎ(dc) into a minimum 500Ω
• Control sampling rates: Input = load with a maximum on voltage Dimensions
6.5Hz, Display = 10Hz and of not greater than 12VÎ(dc) into SD6C_D or SD6R_D or SD6L_D
Outputs = 6.5Hz an infinite load. Maximum switched • 1⁄16 DIN Size
Operator Interface dc power supply current available
• 97.8 mm (3.85 in.) behind panel
• Dual 4 digit, 7 segment LED for up to two outputs is 60mA
maximum
displays • Solid state relay, Form A, 0.5A @
• Width 52.1 mm (2.05 in.)
• Advance, infinity and up down 24VÅ(ac) minimum, 264VÅ(ac)
maximum, opto-isolated, without • Height 52.1 mm (2.05 in.)
keys
contact suppression
• DeviceNet™ on CAN or
SEMI-SIG-ODVA protocols
Ordering Information
Allowable Operating Range
To order, complete the model number on the right with the information below.
Type J: 0 to 815°C S D 6 C- _ _ _ A -D _ _ _
(32 to 1500°F)
Type K: -200 to 1370°C SERIES SD6C_D = 1⁄16 DIN panel mount PID controller
with DeviceNet™
(-328 to 2500°F)
Control Type
Type T: -200 to 400°C
C = PID controller
(-328 to 750°F) Power Supply
Type N: 0 to 1300°C H = 100 to 240Vı(ac/dc)
(32 to 2372°F) L = 24 to 28Vı(ac/dc)
Type E: -200 to 800°C Output 1
(-328 to 1470°F) C = Switched dc
K = SSR, Form A, 0.5A
Type C: 0 to 2315°C F = Universal process
(32 to 4200°F) J = Mechanical relay, Form A, 2A
Type D: 0 to 2315°C Output 2
(32 to 4200°F) A = None
Type PTII: 0 to 1395°C C = Switched dc
(32 to 2543°F) K = SSR, Form A, 0.5A
J = Mechanical relay, Form A, 2A
Type R: 0 to 1760°C U = EIA-485 Modbus™ communications
(32 to 3200°F)
DeviceNet™ Communications
Type S: 0 to 1760°C N = DeviceNet™ on CAN (packaging or general industrial markets)
(32 to 3200°F) S = SEMI-SG-ODVA compliant (semi-conductor markets)
Type B: 0 to 1816°C Display Colors and Custom Options
(32 to 3300°F) RG= Red Green (with Watlow name and SD logo)
RR = Red Red (with Watlow name and SD logo)
RTD (DIN): -200 to 800°C
AA = Red Green (SD logo only)
(-328 to 1472°F)
AB = Red Red (SD logo only)
Process: -1999 to 9999 units

34
W A T L O W

Auto-Tuning PID
Controllers
SERIES 96
Watlow’s SERIES 96 is a powerful
1
⁄16 DIN dual display controller that
offers many advanced functions.
This controller can be tailored to
perform hardware and software
needs with hardware modules that
are plugable and exchangeable,
and software menus that may be
user programmed to fit exact
application requirements.
With one universal input, a second
auxiliary input and four outputs the
SERIES 96 can be programmed to

Single-Loop
Auto-Tuning PID
perform: temperature measurement,
input event switching, remote set
point input, heating, boost heating,
cooling, alarms, digital communica- Input 1 96
tions and retransmit. Process 1 2 3 4 % Output 1
Control
With fast 10Hz sampling, variable
time base burst firing outputs, NEMA Output 2
4X front panel and 0.1 percent Control or Alarm
calibration accuracy, this controller
can easily handle some of the Output 3
toughest application needs. Alarm
Input 2
Features and Benefits Event Output 4
Alarm, Analog or
Burst fire Communications
• Increases heater life / better
temperature controllability
One input, one auxiliary input, four NEMA 4X (IP65)1 Specifications
outputs • Water and corrosion resistant front Operating Environment
• Powerful flexibility at a competitive panel can be washed down • 0 to 65°C (32 to 149°F)
price 16 programmable ramp and soak Controller
No dipswitches steps • Microprocessor-based, user
• Easily configurable from the front • Profiles of dynamic production selectable control modes
panel processes can be programmed • Heat and cool auto-tune for
into the controller control outputs
Multiple set points
Automatic-tuning • Universal input one, auxiliary
• Flexible automatic control
• Easy one step tuning of PID input two, four outputs
Plugable output modules
control parameters • Control outputs user selectable as
• Field expandable
Applications on-off, P, PI, PID
Fast 10Hz sampling
• Packaging Warranty2
• Improved control responsiveness • Industry leading three-years
• Semiconductor
Programmable menus (Patented)
• Food processing
• Can be self-tailored for exact user a To effect NEMA 4X (IP65) rating requires a
• Lab equipment
needs minimum mounting panel thickness of 1.5 mm
• Furnace and ovens (0.06 in.) and surface finish not rougher than
Open loop break protection 0.000812 mm (0.000032 in.).
• Plastics b Electromechanical relays warranted for 100,000
• Indication of thermal loop problem closures only. Solid state switching devices
recommended for applications requiring fast
cycle times or extended service life.

35
Auto-Tuning PID
Controllers
SERIES 96 • Input resolution 50,000 bits • Electrical life 100,000 cycles at
(approx.) at full scale rated current
Specifications Cont. • mV input impedance 20MΩ • For resistive loads only, must use
• Input sampling rates: Single input Input 2 RC suppression for inductive
10Hz (100ms), dual input 5Hz loads
Event Input
(200ms) digital filter adjustable Process
• Contact or voltage
• Display update: 2Hz (500ms), • Range selectable: 0-20mA,
time filter adjustable • 20KΩ input impedance
4-20mA, 0-5VÎ(dc), 1-5VÎ(dc),
• Output update: burst, 0.1 to 999.9 • Voltage input: event high state 0-10VÎ(dc)
seconds 3 to 36VÎ(dc), event low state
0 to 2VÎ(dc) • Reverse or direct acting
• Input/Output/Communication • 0 to 10VÎ(dc) voltage output into
isolation • Resistance/contact input: event
high state >23kΩ, event low state 1000Ω minimum load resistance
• Displayed in °C, °F, or process 0 to 2kΩ • 0 to 20mA current output into
units 800Ω maximum load resistance
Remote Set Point Input: mA or
Operator Interface VÎ(dc) Range Selectable • Resolution:
• Dual four-digit LED displays: • Voltage input impedance 20kΩ VÎ(dc) ranges = 2.5mV nominal
upper 10.2 mm (0.4 in.), lower mA ranges = 5µA nominal
6.2 mm (0.244 in.) • Current input impedance 100Ω
Output Types • Calibration accuracy:
• Advance, Up Arrow, Down Arrow,
Infinity tactile keys Open Collector/Switched DC VÎ(dc) ranges = ±15mV
• Open collector configuration: mA ranges = ±30µA
Standard Conditions For
Specifications Maximum voltage 42VÎ(dc) • Temperature stability 100ppm/°C
Maximum current 200mA Retransmit
• Ambient temperature 25°C (77°F)
Maximum on resistance 1.1Ω
±3°C, rated line voltage, • Range selectable: 0-20mA,
Maximum off state leakage
50 to 60Hz, 0 to 90 percent 4-20mA, 0-5VÎ(dc), 1-5VÎ(dc),
current 100µA
RH non-condensing, 15 minute 0-10VÎ(dc)
warm-up • Switched dc configuration:
• 0 to 10VÎ(dc) voltage output into
Switched dc supply voltage
Universal Input 1 a 1,000Ω minimum load
22 to 28VÎ(dc)
Thermocouple resistance
dc supply current limited to 30mA
• Type J, K, T, N, C (W5), E, Pt 2, D • 0 to 20mA current output into an
Solid State Relay
(W3), B, R, S thermocouple 800Ω maximum load resistance
• Optically isolated
• >20MΩ input impedance • Resolution:
• Zero cross switched
• Maximum 20Ω source resistance VÎ(dc) ranges = 2.5mV nominal
• Without contact suppression mA ranges = 5µA nominal
• 30µA open detection bias
• Minimum load current 0.5mA rms • Calibration accuracy:
RTD
• Maximum current 0.5A rms at VÎ(dc) ranges = ±15mV
• 2- or 3-wire platinum, 100Ω
20 to 280VÅ(ac) mA ranges = ±30µA
• JIS and DIN-curves
• Maximum off state leakage • Temperature stability 100ppm/°C
• Whole or tenth degree indication current 10µA rms
Communications
• 150µA nominal RTD excitation • For resistive loads only, must use
current • EIA/TIA-485, EIA/TIA-232
RC suppression for inductive
Process loads • Opto-isolated
• Range selectable: 0-10VÎ(dc), Electromechanical Relay • Modbus™ RTU protocol
0-5VÎ(dc), 1-5VÎ(dc), 0-20mA, • Form C contact configuration • 1200, 2400, 4800, 9600, 19200
4-20mA baud rates
• Minimum load current 10mA @
• Voltage input impedance 20kΩ 5VÎ(dc) • 32 maximum units can be
• Current input impedance 100Ω connected (With additional 485
• Rated resistive and inductive repeater hardware, up to 247
• Minimum current source loads: 2A @ 250VÅ(ac) or units may be connected)
resistance 1MΩ 30VÎ(dc) maximum
36
W A T L O W

Auto-Tuning PID
Controllers
SERIES 96 RTD Inputs Allowable Operating Ranges
• Calibration accuracy ±0.1 percent Type J 1.0 0 to 815°C
Specifications Cont. of span ±1°C at standard (32 to 1500°F)
Accuracy conditions
0.1 0 to 815°C
• Input ranges • Accuracy span: 540°C (1000°F) (32 to 1500°F)
Type J 0 to 750°C minimum
Type K 1.0 -270 to 1370°C
(32 to 1382°F) • Temperature stability: ±0.05 (-454 to 2500°F)
Type K -200 to 1250°C degree per degree change in
0.1 -200 to 1000°C
(-328 to 2282°F) ambient
(-328 to 1832°F)
Type T -200 to 350°C Process Inputs
Type T 1.0 -270 to 400°C
(-328 to 662°F) • Voltage input ranges (-454 to 750°F)
Type N 0 to 1250°C Accuracy ±15mV ±1 LSD at
0.1 -200 to 400°C
(32 to 2282°F) standard conditions
(-328 to 750°F)
Type E -200 to 900°C Temperature stability

Single-Loop
Type N 1.0 0 to 1300°C

Auto-Tuning PID
(-328 to 1470°F) ±100ppm/°C maximum
(32 to 2372°F)
Type C(W5) 0 to 2315°C • Milli-amp input ranges
0.1 0 to 1000°C
(32 to 4200°F) Accuracy ±30µA ±1 LSD at (32 to 1832°F)
Type D(W3) 0 to 2315°C standard conditions
Type E 1.0 -270 to 800°C
(32 to 4200°F) Temperature stability (-454 to 1470°F)
Pt 2 0 to 1393°C ±100ppm/°C maximum
(32 to 2540°F) 0.1 -200 to 800°C
Agency Approvals (-328 to 1472°F)
Type R 0 to 1450°C • UL® 916, File #E185611, C-UL®,
(32 to 2642°F) Type C 1.0 0 to 2315°C
CE, NEMA 4X (32 to 4200°F)
Type S 0 to 1450°C Terminals
(32 to 2642°F) 0.1 0 to 1000°C
• Touch safe (32 to 1832°F)
Type B 870 to 1700°C
• 22 to 12 AWG Type D 1.0 0 to 2315°C
(1598 to 3092°F)
Power (32 to 4200°F)
DIN -200 to 800°C
(-328 to 1472°F) • 100-240VÅ(ac) +10 percent, 0.1 0 to 1000°C
-15 percent; 50/60Hz, ±5 percent (32 to 1832°F)
JIS -200 to 630°C
(-328 to 1166°F) • 24-28VÅ(ac) or VÎ(dc) +10 Pt 2 1.0 0 to 1395°C
percent, -15 percent; 50/60Hz, (32 to 2543°F)
Process -1999 to 9999 units
±5 percent 0.1 0 to 1000°C
Thermocouple Inputs
• 7.0VA maximum power (32 to 1832°F)
• Calibration accuracy ±0.1 percent consumption
of span ±1°C at standard conditions Type R 1.0 0 to 1760°C
• Data retention upon power failure (32 to 3200°F)
Exceptions: via nonvolatile memory
Type T: 0.12 percent of span for Type S 1.0 0 to 1760°C
Operating Environment (32 to 3200°F)
-200°C to -50°C (-328°F to -58°F)
• 0 to 65°C (32 to 149°F) Type B 1.0 0 to 1816°C
Types R and S: 0.15 percent of
span for 0°C to 100°C (32°F to • 0 to 90 percent RH, non-condensing (32 to 3300°F)
212°F) • Storage temperature: -40 to 85°C DIN 1.0 -200 to 800°C
Type B: 0.24 percent of span (-40 to 185°F) (-328 to 1472°F)
for 870°C to 1700°C (1598°F to Controller Weight (approx.) 0.1 -200 to 800°C
3092°F) • 0.2 kg (0.4 lb) (-328 to 1472°F)
• Accuracy span: 540°C (1000°F) JIS 1.0 -200 to 630°C
minimum (-328 to 1166°F)
• Temperature stability: ±0.1 0.1 -200 to 630°C
degree per degree change in (-328 to 1166°F)
ambient
Process -1999 to 9999 units
37
Auto-Tuning PID
Controllers F.O.B.: Winona, Minnesota

SERIES 96 Ordering Information


To order, complete the code number on the right with the information below:
Functionality Matrix 96 __-____-____
SERIES 96 = Microprocessor-based 1⁄16 DIN, with universal
Retransmit

485 Comm
input 1. Options include: software, power supply, input 2,
Universal

Set Point
Event &
Remote

Control

outputs and display color.


Alarm
Input

232
Input 1 Power Supply
Input 2 A = 100-240Vı(ac/dc)
Output 1 B = 24-28Vı(ac/dc)
Output 2 Input 2
Output 3 0 = None
Output 4 1 = Event input and 0-5VÎ(dc)/4-20mA (Remote set point input)
Output 1
C = Switched dc/open collector
Dimensions
D = Electromechanical relay, Form C, 2A, without RC suppression
Overall F = Universal Process, range selectable: 0-20mA, 4-20mA,
Height: 52 mm (2.05 in.) 0-5VÎ(dc), 1-5VÎ(dc), 0-10VÎ(dc)
K = 0.5A solid state relay without RC suppression
Width: 52 mm (2.05 in.)
Output 2
Length: 107 mm (4.2 in.)
A = None
Depth behind panel surface C = Switched dc/open collector
98.4 mm (3.875 in.) D = Electromechanical relay, Form C, 2A, without RC suppression
F = Universal Process, range selectable: 0-20mA, 4-20mA,
0-5VÎ(dc), 1-5VÎ(dc), 0-10VÎ(dc)
K = 0.5A solid state relay without RC suppression
Output 3
A = None
D = Electromechanical relay, Form C, 2A, without RC suppression
Output 4
A = None
D = Electromechanical relay, Form C, 2A, without RC suppression
R = 232 Communications
U = 485 Communications
M = Universal Retransmit, range selectable: 0-20mA, 4-20mA,
0-5VÎ(dc), 1-5VÎ(dc), 0-10VÎ(dc)
Software/Preset Parameters
00 = Standard software
Display/Overlay
Upper/Lower Upper/Lower
RR = Red/Red display GR = Green/Red display
RG = Red/Green display GG = Green/Green display

107.747 mm
(4.242 in.) Panel Cutout
44.958 mm x 44.958 mm
98.425 mm
(3.875 in.) (1.77 in. x 1.77 in.)
52.070 mm
(2.050 in.)
96
1 2 3 4 %

59.182 mm
(2.330 in.)
52.070 mm
(2.050 in.)

9.322 mm
(0.367 in.)

38
W A T L O W

Auto-Tuning PID
Controllers
SERIES 988/989
Watlow's SERIES 988 (vertical)
and SERIES 989 (horizontal)
temperature/process controllers are
designed and manufactured for the
demanding requirements of the
industrial controller market. No other
controller offers the flexibility,
compact size and durability of the
SERIES 988/989. The controller’s
industry leading feature set is its
compact 1⁄8 DIN size and NEMA 4X1
(IP65) water and corrosion resistant
front panel.

Single-Loop
Auto-Tuning PID
The SERIES 988/989 has the auto-
tuning and alarm features you would
Auto-tune
expect. Additionally, several unique Heat/Cool
Output 1
control algorithms, not common to Closed Loop PID,
this price range, extend the SERIES on-off Control
WATL W Open Loop
Input 1
988/989’s application potential. From Type B, C, D, E, J, Percent Power
K, N, R, S, T or Pt 2
the long list of product features, the Thermocouple,
Output 2
SERIES 988/989's ability to provide DIN/JIS RTD or PROCESS
Closed Loop PID,
Process
single unit cascade control of a on-off Control
Open Loop
process is perhaps the most unique. Input 2 Percent Power
Other features include heater current Type B, C, D, E, J, L1 L2 L3 L4 Control Alarm
K, N, R, S, T or Pt 2 Transmitter Power Supply
monitoring, remote set point input, Thermocouple, DEV
DISPLAY
DIN/JIS RTD or % OUT
differential or ratio control. Process, Slidewire,
Output 3
AUTO Alarm
Current Transformer or
Performance Capabilities Digital Event MAN Transmitter Power Supply
Analog Retransmit
• Accuracy to 0.1 percent of span
Input 3 MODE
• Operating environment Digital Event Output 4
SERIES 988 Alarm
0 to 65°C (32 to 149°F) Transmitter Power Supply
Serial Communications
Features and Benefits Process Deviation
from Set Point
Three inputs and four outputs
Percent Power
• Provide application versatility
Universal high or low voltage
power supply, horizontal or vertical Serial communications Applications
mounting and display color options • Support for one-on-one as well as • Any process requiring cascade,
• Add to application versatility remote networking of controllers ratio, burst fire or slidewire
UL®, CE and NEMA 4X (IP65) feedback control
A 10Hz sampling rate, along with
the burst fire approvals • Food processing
• Provides precise process control • Help ensure product and operator • Packaging
safety • Plastics processing
Enhanced software option
Dual digital displays • Semiconductor manufacturing
• Provides advanced cascade, ratio
or dual PID control • Provide simultaneous viewing of
1 To effect NEMA 4X (IP65) rating requires a
the set point and the actual process
Signal conditioner power supply minimum mounting panel thickness of 1.5 mm
options Three-year warranty 2 (0.06 in.) and surface finish not rougher than
0.000812 mm (0.000032 in.).
• Eliminate the need for external • Provides Control Confidence® 2 Electromechanical relays warranted for 100,000
closures only. Solid state switching devices
devices recommended for applications requiring fast
cycle times or extended service life.

39
Auto-Tuning PID
Controllers
SERIES 988/989
Enhanced Software
Cascade Control
Cascade control is a control strategy
in which one control loop provides the Outer-Loop
set point for another loop. It allows the Thermocouple
process or part temperature to be
WATL W Oil In Oil Out
reached quickly while minimizing Input 1 Output 1
PROCESS

overshoot. Cascade is used to Input 2 L1 L2 L3 L4

optimize the performance of thermal DEV


% OUT
DISPLAY

AUTO

systems with long lag times.


MAN

MODE

Heater Inner-Loop
Limit
SERIES 988

• Precise control via cascade Thermocouple


Limit Sensor
configuration
Lube O il Ta nk
• Display of both process variables
• Low cost; one unit does the work
of two
• Increased operator productivity
with fast setup
Ratio Control
Whether mixing materials or
controlling temperature indirectly, WATL W

ratio control with the SERIES 988 4-20mA Valve Controller Output
provides automatic set point PROCESS

adjustments in response to system


L1 L2 L3 L4
changes. DEV
DISPLAY
Material A
% OUT Controlled Stream
• Simplified process control; one Analog
Input 1 AUTO

controller does the work of two Analog


MAN

MODE Material C
Input 2
• Low cost solution; one controller, SERIES 988 Mixed Material
Material B
display access - both process Wild Stream
Flow Sensor
variables Flow Sensor
• One controller for many applications
• Easy setup; increased operator
productivity
Current Monitor
Current monitoring provides system
performance and status information.
Power Controller
The SERIES 988 accepts current WATL W
Current
Circulation
transformer signal with no Controller
Output
Transformer
Heater
conditioning. PROCESS

• Easily accessible heater status L1 L2 L3 L4


Alarm
• System performance data for DEV
% OUT
DISPLAY
Output
troubleshooting or design Analog
Input 1
AUTO
MAN
enhancements Analog MODE
Input 2
• System protection; fast shut down SERIES 988

with overcurrent Current Monitor

• Easy setup: no external signal Thermocouple

conditioner required

40
W A T L O W

Auto-Tuning PID
Controllers
SERIES 988/989
Enhanced Software Cont.
Slidewire Feedback Valve Control
Valve positioning feedback (percent WATL W

open, percent close) provides


precise process control. The SERIES PROCESS

988 is configurable for a wide variety CCW - Open


Input 1
of valves. L1
DEV
L2 L3 L4
CW - Close
DISPLAY
% OUT
• Accepts virtually any valve input AUTO
MAN
• Front panel valve position display Input 2
MODE

• Increased valve life with SERIES 988

anti-hunting parameter Slide Wire Feedback / Position Sensor

Single-Loop
Thermocouple

Auto-Tuning PID
• Greater process efficiency with
precise control
• Easy setup; increased operator
productivity

Product Highlights
Easy to Operate Use Up To Four Outputs Three Inputs Allow Greater
The SERIES 988's operator interface The controller can have up to four Flexibility
features the simplicity you expect outputs total, including the standard To accommodate unique system
from a Watlow controller. The display Watlow output options, along with configurations, the SERIES 988
key allows the operator to view retransmit and communications. Up offers two universal analog inputs
information pertinent to the process, to three outputs can be defined as a and one event (digital) input. The
including, among others, deviation power supply output to power event input allows the operator to
from set point, percent output and external signal conditioners, select a function at the close of a
units of measurement. eliminating the need for an external switch. This can lock out the front
power supply. The output types are panel, switch PID values, go to a
The display key also returns the
recognized by the controller to remote or second set point, etc. The
operator to the process and set point
simplify setup and operation, with no inputs are optically isolated from all
display from anywhere in the menu
need for DIP switches. outputs, eliminating the need for
system. The setup menu is
external isolation circuitry.
segmented into input, output, global,
and communication parameters and
you can move forward or backward
throughout the parameter sequence.

Specifications • EN 50081-2: 1994 Emissions • MODE, AUTO/MAN, DISPLAY,


Control Mode • EN 50082-2: 1994 Immunity UP and DOWN keys
• Dual input, quad output, optional • 73/23/EEC Low Voltage Directive Accuracy
retransmit of set point or process • EN 61010-1: 1993 Safety • Calibration accuracy and sensor
variable conformity: ±0.1 percent of span,
• UL® #873, C-UL® File #43684
• Programmable direct and ±1 LSD, 25°C ±3°C (77°F ±5°F)
• NEMA 4X ambient and rated line voltage
reverse acting control outputs
Operator Interface ±10 percent
• One step auto-tuning
• Local/remote set point capability • Accuracy span: 540°C (1000°F)
Agency Approvals minimum
• Dual, 4 digit LED displays
• CE
Upper: 10 mm (0.4 in.) • Temperature stability: 0.1°C/°C
• 89/336/EEC Electromagnetic Lower: 8 mm (0.3 in.) (±0.2°F/°F) change in ambient
Compatibility Directive

41
Auto-Tuning PID
Controllers
SERIES 988/989 Type R 0 to 1760°C • Electromechanical relay2,
(32 to 3200°F) Form C, 5A @ 120/240VÅ(ac), 6A
@ 28VÎ(dc), 1⁄8 hp @ 120VÅ(ac),
Specifications Cont. Type S 0 to 1760°C
125VA @ 120VÅ(ac). With or
Sensors/Inputs (32 to 3200°F) without contact suppression. Off
• Contact input for software Type T -200 to 399°C state output impedance with RC
function select (event input) (-328 to 750°F) suppression is 20kΩ
• Thermocouple Types B, C1, D1, Pt 21 0 to 1395°C • Process, 0-20mAÎ(dc),
E, J, K, N, R, S, T and Pt 21 4-20mAÎ(dc) into 800Ω
(32 to 2543°F)
• RTD resolution in 1° or maximum, 0-5VÎ(dc), 1-5VÎ(dc),
0.1° increments RTD Resolution (DIN or JIS) or 0-10VÎ(dc) into 1kΩ minimum
• Process variables: 0-50mV, 1° (DIN) -200 to 800°C reverse acting, isolated
0-20mAÎ(dc), 4-20mAÎ(dc), (-328 to 1472°F) • Electromechanical relay2,
0-5VÎ(dc), 1-5VÎ(dc), 1° (JIS) -200 to 630°C Form A/B, 5A @ 120/240VÅ(ac),
0-10VÎ(dc) 6A @ 28VÎ(dc), 1⁄8 hp @
(-328 to 1166°F)
• Slidewire, digital event input or 120VÅ(ac), 125VA @ 120VÅ(ac),
0.1° (DIN and JIS) without contact suppression
heater current options
-73.3 to 537.7°C • External transmitter power supply,
• Sensor break protection
de-energizes system for safety, (-99.9 to 999.9°F) 5, 12 or 20VÎ(dc) @ 30mA
or selectable bumpless transfer to Process • EIA/TIA-232 communications or
manual operation. Latching 0-5VÎ(dc) -999 to 9999 units EIA/TIA-485, EIA/TIA-422
or non-latching communications, opto-isolated
1-5VÎ(dc) -999 to 9999 units
• °C or °F display or process units, • Retransmit: 0-20mAÎ(dc),
0-10VÎ(dc) -999 to 9999 units
user selectable 4-20mAÎ(dc) with 600Ω max.
0-20mAÎ(dc) -999 to 9999 units load impedance, or 0-5VÎ(dc),
Input Range
4-20mAÎ(dc) -999 to 9999 units 1-5VÎ(dc) and 0-10VÎ(dc) with
Specified temperature ranges 500Ω min. load impedance
represent the controller's operational 0-50mVÎ(dc) -999 to 9999 units
span. Refer to page 228 for ANSI Slidewire 100 to 1200Ω Line Voltage/Power
(thermocouple) and DIN/JIS (RTD) Current 0 to 50mA • 100-240Vı(ac/dc) +10 percent,
temperature sensor ranges/ -15 percent; 50/60Hz, ±5 percent
Potentiometer 0 to 1200Ω
tolerances. • 24-28Vı(ac/dc) +10 percent,
Output Options -15 percent; 50/60Hz ±5 percent
Thermocouple
• Solid state relay, Form A, 0.5A @ • Power consumption 16VA
Type B 870 to 1816°C 24VÅ(ac) min., 253VÅ(ac) max., maximum
(1598 to 3300°F) opto-isolated, burst fire switching. • Fused internally (factory
Type C 1 0 to 2316°C With or without contact replaceable only) Slo-Blo® type
suppression. Off state output (time-lag):
(32 to 4200°F)
impedance is 20kΩ with RC 2A, 250V for high voltage versions
Type D1 0 to 2316°C suppression, 31MΩ without 5A, 250V for low voltage versions
(32 to 4200°F) contact suppression • Data retention upon power failure
Type E -200 to 799°C • Open collector or switched dc via non-volatile memory
(-328 to 1470°F) signal provides a minimum turn on
Type J 0 to 816°C voltage of 3VÎ(dc) into a
minimum 500Ω load; maximum on
(32 to 1500°F) voltage not greater than 32VÎ(dc)
Type K -200 to 1371°C into an infinite load, isolated
1 Not an ANSI symbol.
(-328 to 2500°F) 2 Electromechanical relays warranted for 100,000
closures only. Solid state switching devices
Type N 0 to 1300°C recommended for applications requiring fast
cycle times or extended service life.
(32 to 2372°F)
Slo-Blo® is a registered trademark of Littelfuse, Inc.

42
W A T L O W

Auto-Tuning PID
Controllers F.O.B.: Winona, Minnesota

SERIES 988/989 Ordering Information


To order, complete the code number to the right with the information below:
Specifications Cont. 98__-____-____
Operating Environment SERIES 988/989 = Single channel, temperature/process controller,
• 0 to 65°C (32 to 149°F) 1 analog input, 1 digital input, 1 analog or digital input, 4 outputs.
Power Supply & Mounting
• 0 to 90 percent RH, non-condensing 6 = 24 to 28Vı(ac/dc) nominal, vertical mounting
Storage Temperature 7 = 24 to 28Vı(ac/dc) nominal, horizontal mounting
8 = 100 to 240Vı(ac/dc) nominal vertical mounting
• -40 to 85°C (-40 to 185°F)
9 = 100 to 240Vı(ac/dc) nominal horizontal mounting
Terminals Software
• #6 compression universal head A = Standard
B = Enhanced (Includes cascade, ratio, duplex, dual PID set)
screws, accepts 20-14 gauge S = Special customer feature
wire Input 1
1 = Thermocouple only (Excluding Type B, R and S)
Controller Weight
2 = Universal signal conditioner

Single-Loop
Auto-Tuning PID
• 0.45 kg (1.0 lb) Input 2
0 = None
Shipping Weight 1 = Thermocouple only (Excluding Type B, R and S)
• 1.35 kg (3.0 lbs) 2 = Universal signal conditioner
3 = Slidewire feedback
4 = Current transformerb
5 = Digital contact event (One digital event is standard on all units)
Output 1
B = Solid state relay, Form A, 0.5A, with RC suppression
C = Switched dc or open collector, isolated
D = Electromechanical relaya, Form C, 5A with RC suppression
E = Electromechanical relaya, Form C, 5A without contact suppression
F = Universal process, 0-5VÎ(dc), 1-5VÎ(dc), 0-10VÎ(dc), 0-20mA,
4-20mA, isolated
K = Solid state relay, Form A, 0.5A, without contact suppression
Output 1
A = None
B = Solid state relay, Form A, 0.5A, with RC suppression
C = Switched dc or open collector, isolated
D = Electromechanical relaya, Form C, 5A with RC suppression
E = Electromechanical relaya, Form C, 5A without contact suppression
F = Universal process 0-5VÎ(dc), 1-5VÎ(dc), 0-10VÎ(dc),
0-20mA, 4-20mA, isolated
K = Solid state relay, Form A, 0.5A, without contact suppression
T = External signal conditioner power supply, 5, 12 or 20VÎ(dc) @ 30mA
Output 3
A = None
B = Solid state relay, Form A, 0.5A, with RC suppression
Availability C = Switched dc, isolated
Four working days for orders less J = Electromechanical relaya, Form A or B, 5A without contact suppression
K = Solid state relay, Form A, 0.5A without contact suppression
than 20 units. For orders over 20 M = Retransmit, 0-20mA, 4-20mA
units, consult factory for release and N = Retransmit, 0-5VÎ(dc), 1-5VÎ(dc), 0-10VÎ(dc)
shipment schedules. T = External signal conditioner power supply, 5, 12 or 20VÎ(dc) @ 30mA
Output 4
A = None
B = Solid state relay, Form A, 0.5A, with RC suppression
C = Switched dc or open collector, isolated
D = Electromechanical relaya, Form C, 5A with RC suppression
E = Electromechanical relaya, Form C, 5A without contact suppression
K = Solid state relay, Form A, 0.5A without contact suppression
R = EIA/TIA-232 communications, opto-isolated
S = EIA/TIA-485/EIA/TIA-422 communications, opto-isolated
a Electromechanical relays warranted for 100,000 U = EIA/TIA-232/EIA/TIA-485 software selectable
closures only. Solid state switching devices T = External signal conditioner power supply, 5, 12 or 20VÎ(dc) @ 30mA
recommended for applications requiring fast Display
cycle times or extended service life.
b GG = Green/Green displays RR = Red/Red displays
A current transformer input cannot be used in
conjunction with a process output installed on GR = Green/Red displays XX = Custom overlays or default settings
output 1. RG = Red/Green displays 43
Auto-Tuning PID
Controllers
SERIES 988/989
100 mm
Dimensions WATL W (4.03 in.)

Vertical Orientation WATL W


PROCESS
Overall DSPY MODE

55 mm
Height: 100 mm (4.03 in.) 100 mm
PROCESS
(2.18 in.)
(4.03 in.) DEV AUTO
Width: 55 mm (2.18 in.) L1
DEV
L2 L3 L4
% OUT MAN
DISPLAY
Depth: 120 mm (4.74 in.) % OUT L1 L2 L3 L4 SERIES 989

AUTO
Bezel MAN

Height: 100 mm (4.03 in.) MODE

Width: 55 mm (2.18 in.) SERIES 988

Depth: 15 mm (0.68 in.) 55 mm


(2.18 in.)
Chassis Adjustable
Panel
Height: 90 mm (3.6 in.) Mounting Bracket

Width: 45 mm (1.7 in.)


Panel Cutout
Depth: 105 mm (4.06 in.)
Maximum Panel
Thickness
9.65 mm (0.38 in.)
90 mm
(3.6 in.)

92 mm + 0.8
(3.62 in. + 0.03 -0.00)

15 mm 105 mm
45 mm + 0.6
(0.68 in.) (4.06 in.)
(1.77 in. + 0.02 -0.00)

System Diagram
High Limit
DIN-A-MITE® Mechanical
Power Controller Contactor
Heater

Thermocouple Thermocouple
Limit Sensor Temperature Sensor

WATL W

PROCESS

SERIES LV
Limit
SERIES 982
Controller
Chart
Recorder

44
W A T L O W

Auto-Tuning PID
Controllers
SERIES F4P
The SERIES F4P 1⁄4 DIN temperature
process controllers offer the per-
formance and features to meet a
wide range of industrial processing
needs. The F4P process controllers
are ideally suited for semiconductor
manufacturing equipment, plastics
processing and packaging
equipment and industrial process
control applications.
This competitively priced controller
features a four line, high definition

Single-Loop
LCD interface display along with an

Auto-Tuning PID
information key that makes set up
and control operation significantly 1A
F4
1 or 3 Universal 2 Control
easier with less chance for error. A Analog Inputs
1B

Outputs
16 bit microprocessor supports all
the accuracy and performance 4 Digital …A larm 1 L o D eviation
–1 F 1
2 Alarm
Inputs A djusts V alue
Outputs
advantages you have come to
2
B ack N ext

expect from a Watlow controller. 2 Retransmit


The enhanced software option Outputs
1 Communication (Optional)
enables the SERIES F4P to support Input/Output

complex control applications such


as cascade, ratio and differential
control.
The four digital inputs can be used
to remotely modify the operation of Features and Benefits High performance 16-bit
the controller or enable the display Guided set-up microprocessor
of pre-defined operator messages. • Removes “guess work” from the • Provides precise process control
Advanced features include cascade, set up process with 20Hz update rate (input 1)
ratio, differential, slidewire and • Saves time by reducing • Calibration accuracy of
retransmit options. programming errors +/- 0.1 percent of span
Serial communication and dual High definition, four-line LCD display Universal input
alarm relays are included in the base • Simplifies the set up process and • Allows application versatility
unit. The SERIES F4P is packaged operations • Eliminates the need for dip switches
with a NEMA 4X front face to
withstand harsh environments and a • Quickly and easily identifies Modbus™ communications ready
four inch deep case with removable process, alarm and set point values • Equipped to handle RS-232 or
connectors for wiring convenience. Information “I” key EIA-485 communications
The SERIES F4P controller is manu- • Displays essential elements from Field upgradeable firmware
factured by ISO 9001 registered the user manual on board • Downloads available @ no charge
Watlow Winona and is backed with a Customized menuing from www.watlow.com/F4
three-year warranty. • Quickly displays up to 16 • Reduces downtime
parameters • Eliminates the need for an RMA
• Allows users to create custom
messaging and easily identify key
events or alarms

45
Auto-Tuning PID
Controllers
SERIES F4P Control Outputs systems with long lag times. Input 3
Heat/cool or reverse/direct action is measures the lube oil temperature
supported. Time based outputs can before it leaves the tank. Input 1
General Purpose Control Operation
be configured for variable burst fire or measures the heater temperature.
The SERIES F4P temperature a cycle time can be selected. On-off The input 3 process value is
process controller is a single channel boost heat or boost cool operation is compared to the set point which
PID controller that supports either also supported. Boost operation is generates and internal set point used
closed or open loop operation. The enabled based on load power to control the heater.
design utilizes the latest technology requirements.
to provide a controller capable to Specifications
meeting very complex processing Alarms Universal Analog Inputs 1 (2 and 3
needs while maintaining an easily Two alarms are included in the base optional)
understood operator interface. unit. These alarms are programmable • Update rates: IN1 = 20Hz, IN2
Full non-abbreviated parameter as process, deviation or rate.
and IN3 = 10Hz
choices are displayed using a four Serial Communications
Thermocouple
line liquid crystal display. The display Both EIA-232 and EIA-485
is back lit for wide angle viewing. The communications are included in the • Type J, K, T, N, C (W5), E, Pt 2,
firmware guides the operator through base unit. The SERIES F4P operates D (W3), B, R, S
parameter choices for feature via the Modbus™ RTU protocol. RTD
configuration. An information key (I) The F4P responds to requests for • 2- or 3-wire platinum, 100Ω
provides the operator with detailed information only when queried. Baud
help information regarding the rate selections are 9600 or 19200. • JIS or DIN-curves, 1.0 or 0.1
parameter or feature being indication
Retransmit
configured. The main page menu can • 500 or 1KΩ RTD available
be programmed to display output Up to two optional programmable
voltage or current signal retransmit Process
power through 16 control variables
including: bar graphs, set points and outputs are supported. Retransmit • Input resolution ≈ 50,000 bits at
operating ranges. Up to four sources include up to three process full scale
programmable messages can be variables, set point and output
• Range selectable: 0-10VÎ(dc),
activated remotely to let the operator percent power.
0-5VÎ(dc), 1-5VÎ(dc), 0-50mV,
know that the process requires their Enhanced Control Operation 0-20mA, 4-20mA
attention. When the enhanced operation option • Voltage input impedance 20KΩ
Five sets of PID values can be auto- is ordered, the F4P process controller
tuned to support varying system is supplied with two additional • Current input impedance 100Ω
reaction over the complete operating universal analog inputs (inputs 2 and Digital Inputs (4)
range. Up to 10 offset points can 3) and enhanced firmware to support • Update rate = 10Hz
programmed to compensate for numerous features that utilize the two
differences between the actual additional inputs. The enhanced • Contact or dc voltage; 36VÎ(dc)
process value and sensor readings control option can be configured to max
caused by sensor placement. support cascade control, differential • 10KΩ input impedance
Control Inputs control, ratio control and slidewire Control Outputs (1A, 1B)
valve control. The enhanced control
Up to three universal analog inputs option can also alternate between • Update rate = 20Hz
are supported. These inputs are control inputs, display up to three Open Collector/Switched dc
configured through software to process variables and support
support thermocouples, RTDs and • Internal load switching (nominal):
remote set point operation. Switched dc, 22 to 28VÎ(dc),
process (voltage/current) sensors.
Auxiliary inputs 2 and 3 can function In this sample application the SERIES limited @ 30mA
as a remote set point input, sources F4P process controller utilizes the
• External load switching max.:
for retransmission or as the outer loop enhanced cascade control feature to
heat lube oil to 51.6˚C (125˚F). Open collector 42VÎ(dc) @ 0.5A
for cascade operation.
Cascade control is a control strategy Solid-state Relay
Digital Inputs in which one control loop provides • Zero switched, optically coupled,
These four inputs are programmable the set point for another loop. It allows 0.5A @ 24VÅ(ac)
and can be used to remotely modify the process or part temperature to be minimum, 253VÅ(ac) max.
the operation of the controller as well reached quickly while minimizing
as displaying pre-programmed overshoot. Cascade is used to
messages on the operations display. optimize the performance of thermal
46
W A T L O W

Auto-Tuning PID
Controllers
SERIES F4P • 39VA maximum power Type E: -200 to 800°C
consumption (-328 to 1470°F)
• Data retention upon power failure Type C: 0 to 2315°C
Specifications Cont.
via nonvolatile memory. Sensor (32 to 4200°F)
Electromechanical Relay Type D: 0 to 2400°C
input isolation from input to input
• Form C, 2A @ 250VÅ(ac) or to output to communication (32 to 4352°F)
30VÎ(dc) max. circuitry is 500VÅ(ac). Type Pt 2: 0 to 1395°C
• Resistive or inductive load (32 to 2543°F)
Operating Environment
Type R: 0 to 1760°C
• Without contact suppression • 0 to 65°C (32 to 149°F) (32 to 3200°F)
Process Outputs (Optional • 0 to 90 percent RH, non-condensing Type S: 0 to 1760°C
Retransmit) (32 to 3200°F)
• Storage temperature: -40 to 70°C
• Update rate = 1Hz (-40 to 158°F) Type B: 0 to 1816°C
• User-selectable 0-10VÎ(dc), (32 to 3300°F)
Accuracy
0-5VÎ(dc), 1-5VÎ(dc) @1KΩ min., RTD (DIN): -200 to 800°C

Single-Loop
• Calibration accuracy and sensor

Auto-Tuning PID
0-20mA, 4-20mA @ 800Ω max. (-328 to 1472°F)
conformity: ±0.1 percent of span RTD (JIS): -200 to 800°C
• Resolution: ±1°C @ 25°C ±3°C (77°F ±5°F) (-328 to 1166°F)
dc ranges = 2.5mV nominal ambient, and rated line voltage Process: -19,999 to 30,000 units
mA ranges = 5µA nominal ±10 percent with the following Sensor Accuracy Ranges
• Calibration accuracy: exceptions:
Input ranges
dc ranges = ±15mV Type T: 0.12 percent of span for
Type J: 0 to 815°C
mA ranges = ±30µA -200°C to -50°C (-328°F to -58°F)
(32 to 1500°F)
• Temperature stability 100ppm/°C Types R and S: 0.15 percent of Type K: -200 to 1370°C
span for 0°C to 100°C (32°F to (-328 to 2500°F)
Alarm Outputs
212°F) Type T: -200 to 400°C
• Output update rate 1Hz
Type B: 0.24 percent of span for (-328 to 750°F)
• Electromechanical relay, Form C, 870°C to 1700°C (1598°F to Type N: 0 to 1300°C
2A @ 30VÎ(dc) or 240VÅ(ac) max. 3092°F) (32 to 2372°F)
Communications • Accuracy span: Less than or Type E: -200 to 800°C
• EIA-232 and EIA-485 serial equal to operating ranges, 540°C (-328 to 1470°F)
communications with Modbus™ (1000°F) minimum Type C: 0 to 2315°C
RTU protocol. 9600 or 19.2K (32 to 4200°F)
• Temperature stability: ±0.1°C/°C
baud rate Type D: 0 to 2400°C
(±0.1°F/°F) rise in ambient for
(32 to 4352°F)
Safety and Agency Approvals thermocouples
Type Pt 2: 0 to 1395°C
• UL®/C-UL® 916-listed, • ±0.05°C/°C (±0.05°F/°F) rise in (32 to 2543°F)
File # E185611 process control ambient for RTD sensors Type R: 0 to 1760°C
equipment Displays (32 to 3200°F)
• NEMA 4X and IP65 • Process: 5, seven-segment Type S: 0 to 1760°C
• CE to EN 61010-1 and 61326 LED red (32 to 3200°F)
Type B: 0 to 1816°C
Terminals • Control interface display:
(32 to 3300°F)
• Touch-safe, removable terminal high-definition LCD green
RTD (DIN): -200 to 800°C
blocks, accepts 12 to 22-gauge Sensor Operating Ranges (-328 to 1472°F)
wire Type J: 0 to 815°C RTD (JIS): -200 to 800°C
Power (32 to 1500°F) (-328 to 1166°F)
• 100-240VÅ(ac), -15 percent, Type K: -200 to 1370°C Process: -19,999 to 30,000 units
+10 percent; 50/60Hz, ±5 percent (-328 to 2500°F)
Type T: -200 to 400°C
• 24-28Vı(ac/dc), -15 percent, (-328 to 750°F)
+10 percent (order option) Type N: 0 to 1300°C
(32 to 2372°F)

47
Auto-Tuning PID
Controllers F.O.B.: Winona, Minnesota

SERIES F4P Ordering Information


To order, complete the code number to the right with the information below:
SERIES F4P = 1⁄4 DIN temperature process controller

F4 P - A -
Panel Cutout SERIES F4P
92 mm x 92 mm
(3.622 in. x 3.622 in.) Temperature/Process Controller
99.82 mm Single channel temperature/
(3.930 in.) process controller, two alarms,
EIA-232/485 comms, four
event inputs
99.82 mm Power Supply
(3.930 in.)
H = 100-240Vı(ac/dc)
108.81 mm L = 24-28Vı(ac/dc)
(4.824 in.)
Output 1A
C = Open collector/switched dc
E = Electromechanical relay, Form C
2 amp without contact suppression
K = Solid state Form A 0.5 amp relay
without contact suppression
F = Process, 0-5, 1-5, 0-10VÎ(dc),
0-20mA, 4-20mA
Output 1B
108.05 mm A = None
(4.254 in.) E = Electromechanical relay, Form C
2A without contact suppression
97.79 mm C = Open collector/switched dc
(3.850 in.)
K = Solid state Form A 0.5 amp relay
without contact suppression
F = Process, 0-5, 1-5, 0-10VÎ(dc),
0-20mA, 4-20mA
Enhanced Control Operation
A = Standard control operation
B = Enhanced control operation, dual universal
inputs, cascade, ratio, duplex, differential,
slidewire
Auxiliary Retransmit Module
0 = None
10.26 mm 1 = Single retransmit output 0-5, 1-5, 0-10VÎ(dc),
(.404 in.) 0-20mA, 4-20mA
2 = Dual retransmit outputs 0-5, 1-5, 0-10VÎ(dc),
0-20mA, 4-20mA
Language and RTD Options
1 = English with 100Ω RTD 5 = English with 500 & 1KΩ RTD
Specifications Cont. 2 = German with 100Ω RTD 6 = German with 500 & 1KΩ RTD
3 = French with 100Ω RTD 7 = French with 500 & 1KΩ RTD
Dimensions 4 = Spanish with 100Ω RTD 8 = Spanish with 500 & 1KΩ RTD
• Width x height x depth Display and Custom Options
99 mm x 99 mm x 97 mm panel RG= Red/Green display
mount (3.93 in. x 3.93 in. x 3.85 in.) XX = Custom options, software, setting parameters, overlays

48
W A T L O W

Auto-Tuning PID
Controllers
SERIES PD
Single Loop

Watlow’s new SERIES PD controller


utilizes embedded Ethernet tech-
nology to provide a convenient,
economical means for setting up
and viewing key process variables
such as temperature, pressure and
humidity. The DIN-rail mount SERIES
PD controller offers up to four
control/alarm outputs, as well as a
digital/current transformer input.
Watlow’s SERIES PD controller is

Single-Loop
Auto-Tuning PID
ideally suited for a wide range of
temperature or process control
applications where the operator
interface is supported from a remote
location. The SERIES PD provides
interfacing via embedded firmware
which serves dedicated web pages. Ethernet
Communications
These pages support key functions
including operation, alarm monitoring,
configuration and are displayed using
standard web browser software.
The SERIES PD is also capable of 1 Universal
Analog Input
generating e-mail messages for (Single Channel)
PD
remote alarm notification. PID Controller

Power
Ethernet-based products are rapidly
Ethernet Link
gaining popularity in industrial
Ethernet Activity 4 outputs
applications because they allow can be
an instantaneous exchange of configured or
event (alarm)
information between processing 1 Input Error outputs. Any
equipment and the company’s 2 Input Error
output can be
assigned
management system. Output 1 to either
channel 1 or 2.
Advanced features of the SERIES PD Output 2

controller include internal data Output 3


Output 4
logging of key control parameters, Address

INFOSENSE-P technology, heater


burn out detection and an enhanced
control algorithm.
The SERIES PD controller is backed
by a three-year warranty from Watlow
Winona and is UL® 508, C-UL®, CSA
and CE approved.

49
Auto-Tuning PID
Controllers
SERIES PD Advanced control algorithm
Single Loop • Tighter process control
Heater burn out detection
Features and Benefits • Improved process yields
Ethernet connectivity Internal data logging
• Convenient, easy to use operator • Reduces external hardware
interface demands
• Simplified process monitoring Virtual or hardware alarms with
e-mail delivery
DIN-rail sub panel mounting
• Remote alarm notification
• Quick, economic installation
Watlow INFOSENSE™ sensor
technology
• INFOSENSE™ technology Front View
improves sensor accuracy by a 8 mm
Bracket for
minimum of 50 percent Panel Mounting (0.318 in.)
(#6 Screw
or m3.5 Required) Top/Bottom
Mount
Hole Offset

Side View PD
PID Controller

Power

Ethernet Link
107 mm Ethernet Activity
(4.225 in.)

1 Input Error

146 mm 2 Input Error


(3.750 in.) DIN- 118 mm
rail Output 1
(4.650 in.)
Output 2 Min. Clearance
Output 3 Between Rail
Output 4 Centerlines
Address 146 mm
(5.750 in.)

129 mm
(5.062 in.)

Min. Clearance 51 mm
(2 in.)
73 mm 42 mm
(2.875 in.) (1.637 in.)

PD PD
PID Controller PID Controller
DIN-
rail Power Power

Ethernet Link Ethernet Link

Ethernet Activity Ethernet Activity

1 Input Error 1 Input Error

2 Input Error 2 Input Error

Output 1 Output 1

Output 2 Output 2
Attachment Angle 10°
Output 3 Output 3

Output 4 Output 4
Address Address

42 mm
(1.650 in.)

50
W A T L O W

Auto-Tuning PID
Controllers
SERIES PD Universal Inputs Control/Alarm Outputs (1 - 4)
Single Loop (Electrically Isolated) • User selectable as: on-off, P, PI,
• Thermocouple, grounded or PD, PID, heat, cool, alarm action
ungrounded sensors or retransmit with process output
Specifications type hardware
• RTD 2-or 3-wire, platinum,
Power 100Ω @ 0°C calibration to • Open collector/switched dc
• 24Vı(ac/dc), +10/-15 percent, DIN-curve (0.00385 Ω/Ω/°C) • Open collector 42VÎ(dc)
50/60Hz, ±5 percent • Process 0-20mA @ <100Ω, maximum @ 0.5A
• 12VA maximum power or 0-10VÎ(dc) @ 10kΩ input • Switched dc 22 to 28VÎ(dc)
consumption impedance (50,000 bits @ limited @ 30mA
• Data retention upon power failure full scale)
• Solid state relay, Form A, 0.5A @
via nonvolatile memory Digital Inputs 24VÅ(ac) minimum, 264VÅ(ac)
Environment • Contact or dc voltage maximum, opto-isolated, without
• 0 to 65°C (32 to 149°F) operating • 10KΩ input impedance contact suppression

Single-Loop
Auto-Tuning PID
temperature Current Transformer Inputs • User-selectable 0-10VÎ(dc), 1KΩ
• -40 to 85°C (-40 to 185°F) storage minimum, scalable, 0-20mA @
• 0 to 50mA CT input into 100Ω
temperature 800Ω maximum, scalable
impedance
• 0 to 90 percent RH, non-condensing • Electromechanical relay. Form C,
Allowable Input Operating Range
rated 5A @ 120VÅ(ac) or 5A @
Accuracy Type J: -200 to 1200°C 240VÅ(ac) or 5A @ 30VÎ(dc)
• Calibration accuracy and sensor (-328 to 2192°F)
Communications
conformity: ±0.1 percent of span, Type K: -270 to 1370°C
±1°C @ the calibrated ambient (-454 to 2500°F) • TCP/IP/Ethernet
temperature and rated line voltage Type T: -270 to 400°C • Modbus™ TCP
• Calibration ambient temperature (-454 to 750°F) • Ethernet RJ 45 connector,
= 25°C ±3°C (77°F ±5°F) Type N: -270 to 1300°C 10 base T
(-454 to 2372°F)
• Accuracy span: 540°C (1000°F) • HTTP interface
Type E: -270 to 975°C
minimum • DHCP, auto IP or fixed IP address
(-454 to 1790°F)
• Temperature stability: ±0.1°C/°C Type C: 0 to 2315°C Dimensions
(±0.2°F/°F) rise in ambient (32 to 4200°F) • Width x height x depth
maximum Type D: 0 to 2315°C
(32 to 4200°F) 42 mm x 116 mm x 132 mm
Agency Approvals
Type PTII: 0 to 1395°C (1.64 in. x 4.56 in. x 5.19 in.)
• UL® 508, C-UL®, CSA and CE DIN-rail or chassis mount, DIN-rail
(32 to 2543°F)
Controller spec DIN 5022
Type R: 0 to 1760°C
• Microprocessor based user- (32 to 3200°F) 35 mm x 7.5 mm (1.38 in. x 0.30 in.)
selectable control modes Type S: 0 to 1760°C
• Single or dual channel universal (32 to 3200°F)
inputs Type B: 0 to 1815°C
• Current transformer inputs/digital (32 to 3300°F)
inputs RTD (DIN): -200 to 800°C
(-328 to 1470°F)
• Up to four programmable outputs
Process V: 0 to 10VÎ(dc)
• Update rates, inputs = 10Hz, Process I: 0 to 20mA
outputs = 10Hz
Operator Interface
• Browser based HMI (Human
Machine Interface)
Wiring Termination
• Touch safe removable terminals
• 14 to 22 AWG
51
Auto-Tuning PID
Controllers F.O.B.: Winona, Minnesota

SERIES PD Ordering Information


Single Loop To order, complete the model number on the right with the information below.

P D S_ - _ _ _ _ - _ A _ _

Auxiliary Inputs
1 = Dual digital inputs
2 = One CT input and one digital input
3 = Dual CT inputs (dual channel only)
Output 1
C = Switched dc, open collector
K = SSR, Form A, 0.5A
F = Universal process
J = Mechanical relay, Form A, 2Aa
Output 2
A = None
C = Switched dc, open collector
K = SSR, Form A, 0.5A
E = Mechanical relay, Form C, 2Aa
Output 3
A = None
C = Switched dc, open collector
K = SSR, Form A, 0.5A
F = Universal process
E = Mechanical relay, Form C, 2Aa
Output 4
A = None
C = Switched dc, open collector
K = SSR, Form A, 0.5A
E = Mechanical relay, Form C, 2Aa
On Board Data Logging
0 = None
1 = 16 megabytes of memory
Custom Options
AA = Watlow logo
BB = No logo

a Electromechanical relays warranted for 100,000


closures only. Solid state switching devices
recommended for applications requiring fast cycle
times or extended service life.

52
W A T L O W

Auto-Tuning PID
Controllers
MICRODIN®

The Watlow MICRODIN® SERIES


controllers provide precise
measurement and control with easy
communication to personal
computers and programmable logic
controllers used in laboratories and
industry. This superior controller is
designed with simple and straight-
forward commands to make it easy to
set up and operate. The MICRODIN
is a high-performance controller that
is capable of stand-alone operation
and uses the popular Modbus™

Single-Loop
Auto-Tuning PID
communications protocol with a
standard EIA-485 serial interface for
parameter set up and viewing.
The behind-the-panel, DIN-rail mount
design of the MICRODIN controller
provides significant savings by MicroDIN
eliminating the need for expensive Single
Temperature Controller Control Output
PID or on-off
panel hole punching and by Thermocouple, Power

simplifying panel wiring. Combine or RTD Input


Comms

these savings with touch-safe Control


Output
removable connectors and the result
is low installation costs and minimal Alarm
Output
down time for service and repair. Alarm

MICRODIN is the perfect solution for Input


Error

applications that require top-of-the- Address

line dedicated temperature control


loops with no user interface
integrated into a complete control
system using digital communications.
The absence of an operator interface Touch-safe removable connectors Applications
makes the MICRODIN excellent for • Easy and quick to remove for • Food processing
use with PC-based software, such as replacement and servicing • Medical and dental equipment
WATVIEW. Single control output with alarm • Packaging
Performance Capabilities output
• Plastics processing
• Accuracy to ±0.1 percent of span • Provides simple programming and
• Scientific instrumentation
• Operating environment operation of controller
0 to 65°C (32 to 149°F) Discrete loops of control,
Features and Benefits: auto-tuning
EIA-485 serial communications • Gives performance equal to
with Modbus™ RTU protocol discrete panel-mount controllers,
• Provides easy remote set up and highly reliable
monitoring 10Hz update rate
DIN-rail/sub panel mounting • Improves input sampling and
• Offers fast, low cost installation, controllability
eliminating expensive panel hole
punch operations
53
Auto-Tuning PID
Controllers
MICRODIN Sensors Inputs Output 1: User selectable
• Sensor input sampling rate: • On-off; P, PI, PD, PID heat or cool
Specifications 10 samples/second 10Hz action adjustable switching
Control Mode • Thermocouple, grounded or differential: 1 to 9999 or 0.1 to
ungrounded sensors 999.9 °C or °F
• Microprocessor-based, user
selectable control modes • RTD 2- or 3-wire, platinum, 100Ω @ • Proportional band: 0 to 9999, or
0˚C calibration to JIS curve 0.0 to 999.9 °C or °F
• Single input, single output
(0.003916Ω/Ω/°C) or DIN-curve • Integral: 0.00 to 99.99 minutes per
• Heat or cool auto-tuning
(0.00385Ω/Ω/°C) repeat
Agency Approvals
• Sensor break protection de- • Reset: 0.00 to 99.99 repeats per
• UL®, C-UL® 508 recognized, File energizes control output to protect minute
#E102269 Industrial Control system or selectable bumpless
Equipment • Derivative/rate: 0.00 to 9.99 minutes
transfer to manual operation
• CE to EN 61010 • Cycle time: 0.1 to 60.0 seconds
• °F or °C, user selectable
Operator Interface Output 2: User selectable
• Sensor operating ranges:
• EIA-485 serial communications • Process or deviation alarm with
with Modbus™ RTU protocol Type B T/C 0 to 1816°C flashing alarm status indicator
(32 to 3300°F)
• 9600, 19200 user selectable baud • Alarm with separate high and low
rates Type C (W5) T/C 0 to 2315°C set points
(32 to 4200°F)
• One to 63 user selectable • Hysteresis: 1 to 9999° switching
address range Type D (W3) T/C 0 to 2315°C differential
(32 to 4200°F)
Accuracy Primary Control Output
• Calibration accuracy and sensor Type E T/C -200 to 800°C (heating or cooling)
conformity: ±0.1 percent of span (-328 to 1472°F)
• Output update rate: 10 per
25°C ±3°C (±1 @ 77°F ±5˚F) Type J T/C 0 to 815°C second, 10Hz (maximum)
ambient, and rated line voltage (32 to 1382°F)
• Internal load switching (nominal):
±10 percent with the following Type K T/C -200 to 1370°C Switched dc (isolated) signal, 22 to
exceptions: (-328 to 2500°F) 28VÎ(dc), current limited @ 30mA
Type T: 0.12 percent of span for Type N T/C 0 to 1300°C
-200°C to -50°C (-328°F to -58°F) • Overload current and short circuit
(32 to 2372°F) protection
Types R and S: 0.15 percent of
Pt 2 0 to 1395°C • External load switching
span for 0°C to 100°C (32°F to
(32 to 2543°F) (maximum): Open collector up to
212°F)
Type R T/C 0 to 1760°C 42VÎ(dc) @ 1A with external
Type B: 0.24 percent of span for
(32 to 3200°F) power supply
870°C to 1700°C (1598°F to
3092°F) Type S T/C 0 to 1760°C Alarm Output:
• Accuracy span: Less than or (32 to 3200°F) • Output update rate 2 per second
equal to operating ranges, 540°C Type T T/C -200 to 400°C (2Hz)
(1000°F) minimum (-328 to 750°F) • Electromechanical relay, Form A,
• Temperature stability: ±0.2°C/°C RTD (DIN) -200 to 800°C 2A @ 30VÎ(dc) or 240VÅ(ac),
(±0.2°F/°F) rise in ambient (-328 to 1472°F) • Alarm output can be latching or
maximum for thermocouples, non-latching, and process or
RTD (JIS) -200 to 630°C
±0.05°C/°C (±0.05°F/°F) rise in deviation with separate high and
(-328 to 1166°F)
ambient maximum for RTD sensors low values. Alarm silencing (inhibit)
• Tenth degree resolution
• Voltage stability: ±0.01 percent on power-up
selectable over sensor operating
of span per percent of rated line Electromagnetic Compatibility
range within limits of -199.9 to
voltage and Immunity
999.9, except for thermocouple
Types B, R and S • Complies with EN 50081,
EN 50082
54
W A T L O W

Auto-Tuning PID
Controllers F.O.B.: Winona, Minnesota

MICRODIN
Specifications Cont. Ordering Information
Terminals To order, complete the code number on the right with the information below:
• Touch-safe set screw type,
accepts 26-14 gauge wire
UD1A-1CES-____
Power
• 24-28V‡(ac/dc), -15 percent, MICRODIN = DIN-rail mount temperature control. 1 sensor input,
+10 percent (20.4 to 1 control output, 1 alarm output, no operator interface and EIA-485
30.8V‡(ac/dc); 50/60Hz, Modbus™ RTU serial communications with Quick Start Guide.
±5 percent for VÅ(ac) Hardware
• 5VA typical power consumption 1A = Single channel, low voltage1

• Data retention upon power failure Input

Single-Loop
Auto-Tuning PID
via nonvolatile memory 1 = Type B, C, D, E, J, K, N, Pt 2, R, S, T,
1°RTD, 0.1°RTD (JIS and DIN)
• Sensor input isolation to switched
Control Output
dc output and communication
circuitry 500VÅ(ac) dielectric C = Switched dc, logic signal, non-isolated1
Alarm Output
Operating Environment
E = Electromechanical relay, Form A, 2A, w/o contact suppression2
• 0 to 65°C (32 to 149°F)
Communications
• 0 to 90 percent RH, non-condensing
S = EIA/TIA-485 communications, opto-isolated, Modbus™ RTU protocol
• Storage temperature: -40 to 70°C Software
(-40 to 158°F)
00 = Standard
XX = Custom setup parameters
Custom Options
00 = None
AA = No Watlow logo on front bezel
XX = Custom bezel or label

1 An IEC 742 rated power supply is required for CE


compliance.
2 Electromechanical relays are warranted for
100,000 closures only.

Availability
Stock: Same day shipment on Non-Stock: 10 working days
orders of 10 units or less; 10 working
days on orders greater than 10
units.
Stock List

Code Number Input Output 1 Output 2 Power Front Bezel


UDIA-1CES-0000 T/C and RTD Switched dc Relay, 2A 24 to 28 V English

55
Auto-Tuning PID
Controllers
MICRODIN Mounting a MICRODIN controller

Dimensions Bracket for 8 mm


panel mounting (.318 in.)
(#6 screw
DIN-rail Side View
or m3.5 required) Top/bottom
mount
hole offset
Width: 42 mm (1.64 in.) MicroDIN
Temperature Controller

Height: 118 mm (4.65 in.) 107 mm Power


Front View
(4.225 in.) Comms

146 mm
Depth: 132 mm (5.19 in.) (3.750 in.)
DIN-
rail
Control
Output

118 mm
(4.650 in.)
Chassis Alarm

Input
Error
Min. Clearance
Address
between rail
Width: 42 mm (1.64 in.) centerlines
146 mm
(5.750 in.)
Height: 118 mm (4.65 in.) 129 mm
(5.062 in.) Min. Clearance 51 mm 42 mm
Depth: 129 mm (5.06 in.) (2 in.) (1.637 in.)

73 mm
(2.875 in.) MicroDIN MicroDIN
Temperature Controller Temperature Controller

Power Power

Comms Comms

Control Control
DIN- Output Output

rail
Alarm Alarm

Input Input
Error Error

Address Address

42 mm
(1.650 in.)
Attachment Angle 10°

System Diagram
High Limit
DIN-A-MITE® Mechanical
Power Controller Contactor
Heater

Thermocouple Thermocouple
Limit Sensor Temperature Sensor
MicroDIN
Temperature Controller

Power

Comms

Control
Output
SERIES LV
Limit
Alarm
Controller
Input
Error

Address

56