Auto-Tuning PID
Controllers
SD31
The SERIES SD family of PID
temperature controllers utilizes
today’s advanced micro-electronics
technology to provide the value,
benefits and accuracy you’ve come
to expect from Watlow. The SERIES
SD31 offers improved accuracy of
0.1 percent of span as well as a
faster sampling rate of 6.5Hz in a
1
⁄32 DIN package.
The SERIES SD31 controller delivers
many flexible, user-friendly options.
Easily choose factory or user
Single-Loop
Auto-Tuning PID
defaults and display either process
or set point values. Process inputs
are scalable and invertible from the
Output 1
front panel. Other features include
Variable Burst Fire and flexible Control
Input
Outputs, that users can select as Control or Alarm
On-Off, Heat/Cool or as Process or
Output 2
Deviation Alarms. Users can also
select between 11 different Thermo-
couples, a 100 Ohm RTD, a 0 to
Control, Alarm or
20mA or 0 to 10V process input - all Communications
from the front panel - which
eliminates the need for dip-switches.
With optional EIA-485 com- Variable burst fire Accuracy
munications, you can configure,
monitor and data log with such • Prolongs heater life • Calibration accuracy and sensor
optional software products like • Reduces replacement costs conformity: ±0.1 percent of span,
WATVIEW. ±1°C @ the calibrated ambient
“Save and Restore” feature
temperature and rated line voltage
Features and Benefits • Allows the user to save individual
• Calibration ambient temperature =
Simplified navigation or factory settings
25°C ±3°C (77°F ±5°F)
• Allows users to navigate forwards Specifications • Accuracy span: 540°C (1000°F)
or backwards from any menu minimum
Line Voltage/Power
INFOSENSE™ sensor technology • Temperature stability: ±0.1°C/°C
• 100 to 240VÅ(ac), +10/-15
• Thermal sensing technology percent; (85-264VÅ[ac]) 50/60Hz, (±0.2°F/°F) rise in ambient
improves accuracy by a minimum ±5 percent maximum
of 50 percent
• 24Vı(ac/dc), +10/-15 percent; Agency Approvals
Watlow’s patented User Defined 50/60Hz, ±5 percent • UL® 3121, C-UL®‚ CSA, CE,
Menu System
• 10VA maximum power IP65/NEMA 4X
• Allows users to define, save, and consumption
access their most important Menu • NSF for Type J, K, T and E
settings • Data retention upon power failure thermocouples
via nonvolatile memory
Agency approvals
Environment
• UL®‚ C-UL®, CE IP65/NEMA 4X,
plus CSA and NSF • -18 to 65°C (0 to 149°F) operating
temperature
• -40 to 85°C (-40 to 185°F) storage
UL® and C-UL® are registered trademarks of
Underwriter’s Laboratories, Inc. temperature
Modbus™ is a registered trademark of Schneider • 0 to 90 percent RH, non-condensing
Automation, Inc.
27
Auto-Tuning PID
Controllers F.O.B.: Winona, Minnesota
Auto-Tuning PID
Controllers
SD_C
The features and performance
offered by SERIES SD_C controllers
make them ideally suited for a broad
range of applications in temperature
and process control.
The SERIES SD_C controllers
include a universal sensor input with
up to three outputs that can be
programmed for heat or cool temp-
erature control or to operate as
process or deviation alarms.
Programming inverse scaling is also
Single-Loop
simplified with the user-friendly set-
Auto-Tuning PID
up menu, providing additional value
without additional cost.
Advanced features of SERIES SD_C
controllers include EIA-485 Modbus™ Output 1
serial communications, Watlow’s SD
1 2 3 %
INFOSENSE™ sensor technology, Control Control or Alarm
infrared remote communications Input Output 2
operation, Watlow’s patented User
Definable Menu System and a “Save
Control, Alarm or Communications
and Restore” feature that allows the Output 3 *
restoration of either factory or user-
defined settings. Infrared
Configure** Control or Alarm
Available in ⁄32, ⁄16, ⁄8 and ⁄4 DIN-
1 1 1 1
Infrared
panel mount sizes, Watlow’s SERIES Monitor**
*1/32 DIN cannot have an Output 3.
SD_C controllers are backed by an **Infrared option is not available on 1/32 DIN.
industry leading three-year warranty
from Watlow Winona. The SERIES
SD_C controllers are NSF, UL® and WATVIEW HMI Specifications
C-UL® listed, CSA and CE certified (Human Machine Interface)
and include the NEMA 4X (IP65) seal. Line Voltage/Power
• Permits operation, configuration • 100 to 240VÅ(ac), +10/-15
Features and Benefits and data logging via a standard percent; (85-264VÅ[ac])
INFOSENSE™ sensor technology Windows® PC 50/60Hz, ±5 percent
• Improves sensor accuracy by a Infrared communications (optional) • 24Vı(ac/dc), +10/-15 percent;
minimum of 50 percent • Facilitates recipe management 50/60Hz, ±5 percent
User Defined Menu System and data logging • 10VA maximum power consumption
• Allows the user to assign up to • Allows easier controller setup, • Data retention upon power failure
20 parameters in the operations operation and monitoring via nonvolatile memory
menu Dual displays Environment
• Improves operational efficiency • Provides better recognition of • -18 to 65°C (0 to 149°F) operating
“Save and Restore” feature process changes temperature
• Allows the user to save individual • -40 to 85°C (-40 to 185°F) storage
or factory settings temperature
Variable burst fire • 0 to 90 percent RH, non-condensing
• Prolongs heater life
• Reduces replacement costs
Windows® is a registered trademark of Microsoft
Corporation. 29
Auto-Tuning PID
Controllers
SD_C Operator Interface Allowable Operating Range
• Dual 4 digit, 7 segment LED Type J: 0 to 815°C
Specifications Cont. displays (32 to 1500°F)
Accuracy • Advance, infinity and up down Type K: -200 to 1370°C
keys (-328 to 2500°F)
• Calibration accuracy and sensor
• Optional IrDA infrared port (not Type T: -200 to 400°C
conformity: ±0.1 percent of span,
available on 1⁄32 DIN) (-328 to 750°F)
±1°C @ the calibrated ambient
temperature and rated line Type N: 0 to 1300°C
• Isolated EIA-485 Modbus™ serial
voltage (32 to 2372°F)
communications. 9600, 19.2K or
38.4K baud rates Type E: -200 to 800°C
• Calibration ambient temperature
(-328 to 1470°F)
= 25°C ±3°C (77°F ±5°F) Wiring Termination -Touch Safe
Type C: 0 to 2315°C
• Accuracy span: 540°C (1000°F) Terminals
(32 to 4200°F)
minimum • Input power and control outputs Type D: 0 to 2315°C
• Temperature stability: ±0.1°C/°C 12 to 22 AWG (32 to 4200°F)
(±0.2°F/°F) rise in ambient • Sensor inputs and process Type PTII: 0 to 1395°C
maximum outputs 20 to 28 AWG (32 to 2543°F)
Agency Approvals Universal Input Type R: 0 to 1760°C
• UL® 3121, C-UL®‚ CSA, CE, • Thermocouple, grounded or (32 to 3200°F)
NEMA 4X/IP65 ungrounded sensors Type S: 0 to 1760°C
• Limit version features FM approval • RTD 2- or 3-wire, platinum, 100Ω (32 to 3200°F)
• NSF for Type J, K, T and E @ 0°C calibration to DIN- Type B: 0 to 1816°C
thermocouples curve (0.00385 Ω/Ω/°C) (32 to 3300°F)
Controller • Process, 0-20mA @ 100Ω, or RTD (DIN): -200 to 800°C
0-10VÎ(dc) @ 20kΩ input (-328 to 1472°F)
• Microprocessor based user-
impedance; Scalable Process: -1999 to 9999 units
selectable control modes
• Inverse scaling Control Outputs
• Single universal input, up to three
outputs • >20MΩ input impedance Outputs 1, 2 , 3 (Output 3 not
available on 1⁄32 DIN)
• Control sampling rates: • Maximum of 20Ω source
Input = 6.5Hz, Display = 10Hz, resistance • User selectable for heat/cool as
and Outputs = 6.5Hz on-off, P, PI, PD, PID or Alarm
action. Not valid for limit controls
Dimensions • Electromechanical relay. Form A,
rated 2A @ 120VÅ(ac), 2A @
DIN Size Behind Panel Width Height 240VÅ(ac) or 2A @ 30VÎ(dc)
(max.)
• Switched dc non-isolated
⁄32 DIN
1
97.8 mm 52.6 mm 29.7 mm
minimum turn on voltage of
(3.85 in.) (2.07 in.) (1.17 in.)
6VÎ(dc) into a minimum 500Ω
⁄16 DIN
1
97.8 mm 52.1 mm 52.1 mm load with a maximum on voltage
(3.85 in.) (2.05 in.) (2.05 in.) of not greater than 12VÎ(dc) into
⁄8 DIN
1
97.8 mm 52.8 mm 99.8 mm an infinite load. Maximum switched
Vertical (3.85 in.) (2.08 in.) (3.93 in.) dc power supply current available
for up to two outputs is 60mA
⁄8 DIN
1
97.8 mm 99.8 mm 52.8 mm
• Solid state relay, Form A, 0.5A @
Horizontal (3.85 in.) (3.93 in.) (2.08 in.)
24VÅ(ac) minimum, 264VÅ(ac)
1
⁄4 DIN 101.1 mm 99.8 mm 99.8 mm maximum, opto-isolated, without
(3.98 in.) (3.93 in.) (3.93 in.) contact suppression
30
W A T L O W
Auto-Tuning PID
Controllers
SD_C Advantages of IDC include
automated logging of key process
Specifications Cont. variables, increased accuracy
and ease of use for recipe or con-
• Process output (Non Isolated) figuration setups. Infrared data
User-selectable 0-10VÎ(dc), communications enhances controller
0-5VÎ(dc), 1-5VÎ(dc) @ data exchange in physically
1KΩ minimum, 0-20mA, 4-20mA restricting environments (such as
@ 800Ω maximum semiconductor clean rooms,
• Electromechanical relay. Form C, governmental radio-active test labs
rated 5A @ 120VÅ(ac), or those hard to reach areas) and
5A @ 240VÅ(ac) or 5A @ reduces the use of paper to record
30VÎ(dc) instrument information as well as
• Open collector 42VÎ(dc) @ human transposition errors.
250mA maximum Infrared Communications
Single-Loop
Auto-Tuning PID
• EIA-485 serial communications The Infrared Data Communications
with Modbus™ protocol (IDC) option is available on all
• 9600, 19.2K or 38.4K baud rates SERIES SD controller models except
the 1⁄32 DIN and can support complete
SERIES SD parameter configuration
and operation. The IDC option
supports wireless communications
with PDAs (personal digital assistants)
or other devices equipped with
infrared communications that support
the Infrared Data Association (IrDA)
1.0 Standard.
The actual user interface or
configuration is dependent on the
WATVIEW HMI master device application software.
WATVIEW, Watlow’s Windows® A source for this software is Instant
based HMI (Human Machine Inter- HMI from Software Horizons.
face) software, supports the SERIES For more information, visit
SD controllers. The software can be www.instanthmi.com/watlow.
used to setup, monitor and edit the
values of controller parameters, to
monitor and manage alarms and to
log and graph process data.
Typical Block Diagram
SERIES SD PID SERIES SD Limit Oven
SD LIMIT SD
1 2 3 % 1 2 3
Form C Relay
32
W A T L O W
Auto-Tuning PID
Controllers
SD6C_D
Watlow SERIES SD6C_D offers
excellent static Set Point control and
application flexibility in a 1⁄16th DIN
panel mount package. The SERIES
SD6C_D controller has been
successfully tested for use with both
ODVA and Semi-conductor SIG
standards for DeviceNet™ on CAN
networks.
The SD6C_D single channel
controller includes a universal
sensor input with two outputs that
can be configured as heat or cool or
Single-Loop
Auto-Tuning PID
alarm. The DeviceNet™ com-
munications interface is supplied
DeviceNet™
with either a five pin circular DIN
connector for Semiconductor SIG
specific applications, or with a five
position removable screw terminal
connector for traditional market
applications.
SD D-NET
SD
Additional features of the SD6C_D 1 2 3 % Output 1
34
W A T L O W
Auto-Tuning PID
Controllers
SERIES 96
Watlow’s SERIES 96 is a powerful
1
⁄16 DIN dual display controller that
offers many advanced functions.
This controller can be tailored to
perform hardware and software
needs with hardware modules that
are plugable and exchangeable,
and software menus that may be
user programmed to fit exact
application requirements.
With one universal input, a second
auxiliary input and four outputs the
SERIES 96 can be programmed to
Single-Loop
Auto-Tuning PID
perform: temperature measurement,
input event switching, remote set
point input, heating, boost heating,
cooling, alarms, digital communica- Input 1 96
tions and retransmit. Process 1 2 3 4 % Output 1
Control
With fast 10Hz sampling, variable
time base burst firing outputs, NEMA Output 2
4X front panel and 0.1 percent Control or Alarm
calibration accuracy, this controller
can easily handle some of the Output 3
toughest application needs. Alarm
Input 2
Features and Benefits Event Output 4
Alarm, Analog or
Burst fire Communications
• Increases heater life / better
temperature controllability
One input, one auxiliary input, four NEMA 4X (IP65)1 Specifications
outputs • Water and corrosion resistant front Operating Environment
• Powerful flexibility at a competitive panel can be washed down • 0 to 65°C (32 to 149°F)
price 16 programmable ramp and soak Controller
No dipswitches steps • Microprocessor-based, user
• Easily configurable from the front • Profiles of dynamic production selectable control modes
panel processes can be programmed • Heat and cool auto-tune for
into the controller control outputs
Multiple set points
Automatic-tuning • Universal input one, auxiliary
• Flexible automatic control
• Easy one step tuning of PID input two, four outputs
Plugable output modules
control parameters • Control outputs user selectable as
• Field expandable
Applications on-off, P, PI, PID
Fast 10Hz sampling
• Packaging Warranty2
• Improved control responsiveness • Industry leading three-years
• Semiconductor
Programmable menus (Patented)
• Food processing
• Can be self-tailored for exact user a To effect NEMA 4X (IP65) rating requires a
• Lab equipment
needs minimum mounting panel thickness of 1.5 mm
• Furnace and ovens (0.06 in.) and surface finish not rougher than
Open loop break protection 0.000812 mm (0.000032 in.).
• Plastics b Electromechanical relays warranted for 100,000
• Indication of thermal loop problem closures only. Solid state switching devices
recommended for applications requiring fast
cycle times or extended service life.
35
Auto-Tuning PID
Controllers
SERIES 96 • Input resolution 50,000 bits • Electrical life 100,000 cycles at
(approx.) at full scale rated current
Specifications Cont. • mV input impedance 20MΩ • For resistive loads only, must use
• Input sampling rates: Single input Input 2 RC suppression for inductive
10Hz (100ms), dual input 5Hz loads
Event Input
(200ms) digital filter adjustable Process
• Contact or voltage
• Display update: 2Hz (500ms), • Range selectable: 0-20mA,
time filter adjustable • 20KΩ input impedance
4-20mA, 0-5VÎ(dc), 1-5VÎ(dc),
• Output update: burst, 0.1 to 999.9 • Voltage input: event high state 0-10VÎ(dc)
seconds 3 to 36VÎ(dc), event low state
0 to 2VÎ(dc) • Reverse or direct acting
• Input/Output/Communication • 0 to 10VÎ(dc) voltage output into
isolation • Resistance/contact input: event
high state >23kΩ, event low state 1000Ω minimum load resistance
• Displayed in °C, °F, or process 0 to 2kΩ • 0 to 20mA current output into
units 800Ω maximum load resistance
Remote Set Point Input: mA or
Operator Interface VÎ(dc) Range Selectable • Resolution:
• Dual four-digit LED displays: • Voltage input impedance 20kΩ VÎ(dc) ranges = 2.5mV nominal
upper 10.2 mm (0.4 in.), lower mA ranges = 5µA nominal
6.2 mm (0.244 in.) • Current input impedance 100Ω
Output Types • Calibration accuracy:
• Advance, Up Arrow, Down Arrow,
Infinity tactile keys Open Collector/Switched DC VÎ(dc) ranges = ±15mV
• Open collector configuration: mA ranges = ±30µA
Standard Conditions For
Specifications Maximum voltage 42VÎ(dc) • Temperature stability 100ppm/°C
Maximum current 200mA Retransmit
• Ambient temperature 25°C (77°F)
Maximum on resistance 1.1Ω
±3°C, rated line voltage, • Range selectable: 0-20mA,
Maximum off state leakage
50 to 60Hz, 0 to 90 percent 4-20mA, 0-5VÎ(dc), 1-5VÎ(dc),
current 100µA
RH non-condensing, 15 minute 0-10VÎ(dc)
warm-up • Switched dc configuration:
• 0 to 10VÎ(dc) voltage output into
Switched dc supply voltage
Universal Input 1 a 1,000Ω minimum load
22 to 28VÎ(dc)
Thermocouple resistance
dc supply current limited to 30mA
• Type J, K, T, N, C (W5), E, Pt 2, D • 0 to 20mA current output into an
Solid State Relay
(W3), B, R, S thermocouple 800Ω maximum load resistance
• Optically isolated
• >20MΩ input impedance • Resolution:
• Zero cross switched
• Maximum 20Ω source resistance VÎ(dc) ranges = 2.5mV nominal
• Without contact suppression mA ranges = 5µA nominal
• 30µA open detection bias
• Minimum load current 0.5mA rms • Calibration accuracy:
RTD
• Maximum current 0.5A rms at VÎ(dc) ranges = ±15mV
• 2- or 3-wire platinum, 100Ω
20 to 280VÅ(ac) mA ranges = ±30µA
• JIS and DIN-curves
• Maximum off state leakage • Temperature stability 100ppm/°C
• Whole or tenth degree indication current 10µA rms
Communications
• 150µA nominal RTD excitation • For resistive loads only, must use
current • EIA/TIA-485, EIA/TIA-232
RC suppression for inductive
Process loads • Opto-isolated
• Range selectable: 0-10VÎ(dc), Electromechanical Relay • Modbus™ RTU protocol
0-5VÎ(dc), 1-5VÎ(dc), 0-20mA, • Form C contact configuration • 1200, 2400, 4800, 9600, 19200
4-20mA baud rates
• Minimum load current 10mA @
• Voltage input impedance 20kΩ 5VÎ(dc) • 32 maximum units can be
• Current input impedance 100Ω connected (With additional 485
• Rated resistive and inductive repeater hardware, up to 247
• Minimum current source loads: 2A @ 250VÅ(ac) or units may be connected)
resistance 1MΩ 30VÎ(dc) maximum
36
W A T L O W
Auto-Tuning PID
Controllers
SERIES 96 RTD Inputs Allowable Operating Ranges
• Calibration accuracy ±0.1 percent Type J 1.0 0 to 815°C
Specifications Cont. of span ±1°C at standard (32 to 1500°F)
Accuracy conditions
0.1 0 to 815°C
• Input ranges • Accuracy span: 540°C (1000°F) (32 to 1500°F)
Type J 0 to 750°C minimum
Type K 1.0 -270 to 1370°C
(32 to 1382°F) • Temperature stability: ±0.05 (-454 to 2500°F)
Type K -200 to 1250°C degree per degree change in
0.1 -200 to 1000°C
(-328 to 2282°F) ambient
(-328 to 1832°F)
Type T -200 to 350°C Process Inputs
Type T 1.0 -270 to 400°C
(-328 to 662°F) • Voltage input ranges (-454 to 750°F)
Type N 0 to 1250°C Accuracy ±15mV ±1 LSD at
0.1 -200 to 400°C
(32 to 2282°F) standard conditions
(-328 to 750°F)
Type E -200 to 900°C Temperature stability
Single-Loop
Type N 1.0 0 to 1300°C
Auto-Tuning PID
(-328 to 1470°F) ±100ppm/°C maximum
(32 to 2372°F)
Type C(W5) 0 to 2315°C • Milli-amp input ranges
0.1 0 to 1000°C
(32 to 4200°F) Accuracy ±30µA ±1 LSD at (32 to 1832°F)
Type D(W3) 0 to 2315°C standard conditions
Type E 1.0 -270 to 800°C
(32 to 4200°F) Temperature stability (-454 to 1470°F)
Pt 2 0 to 1393°C ±100ppm/°C maximum
(32 to 2540°F) 0.1 -200 to 800°C
Agency Approvals (-328 to 1472°F)
Type R 0 to 1450°C • UL® 916, File #E185611, C-UL®,
(32 to 2642°F) Type C 1.0 0 to 2315°C
CE, NEMA 4X (32 to 4200°F)
Type S 0 to 1450°C Terminals
(32 to 2642°F) 0.1 0 to 1000°C
• Touch safe (32 to 1832°F)
Type B 870 to 1700°C
• 22 to 12 AWG Type D 1.0 0 to 2315°C
(1598 to 3092°F)
Power (32 to 4200°F)
DIN -200 to 800°C
(-328 to 1472°F) • 100-240VÅ(ac) +10 percent, 0.1 0 to 1000°C
-15 percent; 50/60Hz, ±5 percent (32 to 1832°F)
JIS -200 to 630°C
(-328 to 1166°F) • 24-28VÅ(ac) or VÎ(dc) +10 Pt 2 1.0 0 to 1395°C
percent, -15 percent; 50/60Hz, (32 to 2543°F)
Process -1999 to 9999 units
±5 percent 0.1 0 to 1000°C
Thermocouple Inputs
• 7.0VA maximum power (32 to 1832°F)
• Calibration accuracy ±0.1 percent consumption
of span ±1°C at standard conditions Type R 1.0 0 to 1760°C
• Data retention upon power failure (32 to 3200°F)
Exceptions: via nonvolatile memory
Type T: 0.12 percent of span for Type S 1.0 0 to 1760°C
Operating Environment (32 to 3200°F)
-200°C to -50°C (-328°F to -58°F)
• 0 to 65°C (32 to 149°F) Type B 1.0 0 to 1816°C
Types R and S: 0.15 percent of
span for 0°C to 100°C (32°F to • 0 to 90 percent RH, non-condensing (32 to 3300°F)
212°F) • Storage temperature: -40 to 85°C DIN 1.0 -200 to 800°C
Type B: 0.24 percent of span (-40 to 185°F) (-328 to 1472°F)
for 870°C to 1700°C (1598°F to Controller Weight (approx.) 0.1 -200 to 800°C
3092°F) • 0.2 kg (0.4 lb) (-328 to 1472°F)
• Accuracy span: 540°C (1000°F) JIS 1.0 -200 to 630°C
minimum (-328 to 1166°F)
• Temperature stability: ±0.1 0.1 -200 to 630°C
degree per degree change in (-328 to 1166°F)
ambient
Process -1999 to 9999 units
37
Auto-Tuning PID
Controllers F.O.B.: Winona, Minnesota
485 Comm
input 1. Options include: software, power supply, input 2,
Universal
Set Point
Event &
Remote
Control
232
Input 1 Power Supply
Input 2 A = 100-240Vı(ac/dc)
Output 1 B = 24-28Vı(ac/dc)
Output 2 Input 2
Output 3 0 = None
Output 4 1 = Event input and 0-5VÎ(dc)/4-20mA (Remote set point input)
Output 1
C = Switched dc/open collector
Dimensions
D = Electromechanical relay, Form C, 2A, without RC suppression
Overall F = Universal Process, range selectable: 0-20mA, 4-20mA,
Height: 52 mm (2.05 in.) 0-5VÎ(dc), 1-5VÎ(dc), 0-10VÎ(dc)
K = 0.5A solid state relay without RC suppression
Width: 52 mm (2.05 in.)
Output 2
Length: 107 mm (4.2 in.)
A = None
Depth behind panel surface C = Switched dc/open collector
98.4 mm (3.875 in.) D = Electromechanical relay, Form C, 2A, without RC suppression
F = Universal Process, range selectable: 0-20mA, 4-20mA,
0-5VÎ(dc), 1-5VÎ(dc), 0-10VÎ(dc)
K = 0.5A solid state relay without RC suppression
Output 3
A = None
D = Electromechanical relay, Form C, 2A, without RC suppression
Output 4
A = None
D = Electromechanical relay, Form C, 2A, without RC suppression
R = 232 Communications
U = 485 Communications
M = Universal Retransmit, range selectable: 0-20mA, 4-20mA,
0-5VÎ(dc), 1-5VÎ(dc), 0-10VÎ(dc)
Software/Preset Parameters
00 = Standard software
Display/Overlay
Upper/Lower Upper/Lower
RR = Red/Red display GR = Green/Red display
RG = Red/Green display GG = Green/Green display
107.747 mm
(4.242 in.) Panel Cutout
44.958 mm x 44.958 mm
98.425 mm
(3.875 in.) (1.77 in. x 1.77 in.)
52.070 mm
(2.050 in.)
96
1 2 3 4 %
59.182 mm
(2.330 in.)
52.070 mm
(2.050 in.)
9.322 mm
(0.367 in.)
38
W A T L O W
Auto-Tuning PID
Controllers
SERIES 988/989
Watlow's SERIES 988 (vertical)
and SERIES 989 (horizontal)
temperature/process controllers are
designed and manufactured for the
demanding requirements of the
industrial controller market. No other
controller offers the flexibility,
compact size and durability of the
SERIES 988/989. The controller’s
industry leading feature set is its
compact 1⁄8 DIN size and NEMA 4X1
(IP65) water and corrosion resistant
front panel.
Single-Loop
Auto-Tuning PID
The SERIES 988/989 has the auto-
tuning and alarm features you would
Auto-tune
expect. Additionally, several unique Heat/Cool
Output 1
control algorithms, not common to Closed Loop PID,
this price range, extend the SERIES on-off Control
WATL W Open Loop
Input 1
988/989’s application potential. From Type B, C, D, E, J, Percent Power
K, N, R, S, T or Pt 2
the long list of product features, the Thermocouple,
Output 2
SERIES 988/989's ability to provide DIN/JIS RTD or PROCESS
Closed Loop PID,
Process
single unit cascade control of a on-off Control
Open Loop
process is perhaps the most unique. Input 2 Percent Power
Other features include heater current Type B, C, D, E, J, L1 L2 L3 L4 Control Alarm
K, N, R, S, T or Pt 2 Transmitter Power Supply
monitoring, remote set point input, Thermocouple, DEV
DISPLAY
DIN/JIS RTD or % OUT
differential or ratio control. Process, Slidewire,
Output 3
AUTO Alarm
Current Transformer or
Performance Capabilities Digital Event MAN Transmitter Power Supply
Analog Retransmit
• Accuracy to 0.1 percent of span
Input 3 MODE
• Operating environment Digital Event Output 4
SERIES 988 Alarm
0 to 65°C (32 to 149°F) Transmitter Power Supply
Serial Communications
Features and Benefits Process Deviation
from Set Point
Three inputs and four outputs
Percent Power
• Provide application versatility
Universal high or low voltage
power supply, horizontal or vertical Serial communications Applications
mounting and display color options • Support for one-on-one as well as • Any process requiring cascade,
• Add to application versatility remote networking of controllers ratio, burst fire or slidewire
UL®, CE and NEMA 4X (IP65) feedback control
A 10Hz sampling rate, along with
the burst fire approvals • Food processing
• Provides precise process control • Help ensure product and operator • Packaging
safety • Plastics processing
Enhanced software option
Dual digital displays • Semiconductor manufacturing
• Provides advanced cascade, ratio
or dual PID control • Provide simultaneous viewing of
1 To effect NEMA 4X (IP65) rating requires a
the set point and the actual process
Signal conditioner power supply minimum mounting panel thickness of 1.5 mm
options Three-year warranty 2 (0.06 in.) and surface finish not rougher than
0.000812 mm (0.000032 in.).
• Eliminate the need for external • Provides Control Confidence® 2 Electromechanical relays warranted for 100,000
closures only. Solid state switching devices
devices recommended for applications requiring fast
cycle times or extended service life.
39
Auto-Tuning PID
Controllers
SERIES 988/989
Enhanced Software
Cascade Control
Cascade control is a control strategy
in which one control loop provides the Outer-Loop
set point for another loop. It allows the Thermocouple
process or part temperature to be
WATL W Oil In Oil Out
reached quickly while minimizing Input 1 Output 1
PROCESS
AUTO
MODE
Heater Inner-Loop
Limit
SERIES 988
ratio control with the SERIES 988 4-20mA Valve Controller Output
provides automatic set point PROCESS
MODE Material C
Input 2
• Low cost solution; one controller, SERIES 988 Mixed Material
Material B
display access - both process Wild Stream
Flow Sensor
variables Flow Sensor
• One controller for many applications
• Easy setup; increased operator
productivity
Current Monitor
Current monitoring provides system
performance and status information.
Power Controller
The SERIES 988 accepts current WATL W
Current
Circulation
transformer signal with no Controller
Output
Transformer
Heater
conditioning. PROCESS
conditioner required
40
W A T L O W
Auto-Tuning PID
Controllers
SERIES 988/989
Enhanced Software Cont.
Slidewire Feedback Valve Control
Valve positioning feedback (percent WATL W
Single-Loop
Thermocouple
Auto-Tuning PID
• Greater process efficiency with
precise control
• Easy setup; increased operator
productivity
Product Highlights
Easy to Operate Use Up To Four Outputs Three Inputs Allow Greater
The SERIES 988's operator interface The controller can have up to four Flexibility
features the simplicity you expect outputs total, including the standard To accommodate unique system
from a Watlow controller. The display Watlow output options, along with configurations, the SERIES 988
key allows the operator to view retransmit and communications. Up offers two universal analog inputs
information pertinent to the process, to three outputs can be defined as a and one event (digital) input. The
including, among others, deviation power supply output to power event input allows the operator to
from set point, percent output and external signal conditioners, select a function at the close of a
units of measurement. eliminating the need for an external switch. This can lock out the front
power supply. The output types are panel, switch PID values, go to a
The display key also returns the
recognized by the controller to remote or second set point, etc. The
operator to the process and set point
simplify setup and operation, with no inputs are optically isolated from all
display from anywhere in the menu
need for DIP switches. outputs, eliminating the need for
system. The setup menu is
external isolation circuitry.
segmented into input, output, global,
and communication parameters and
you can move forward or backward
throughout the parameter sequence.
41
Auto-Tuning PID
Controllers
SERIES 988/989 Type R 0 to 1760°C • Electromechanical relay2,
(32 to 3200°F) Form C, 5A @ 120/240VÅ(ac), 6A
@ 28VÎ(dc), 1⁄8 hp @ 120VÅ(ac),
Specifications Cont. Type S 0 to 1760°C
125VA @ 120VÅ(ac). With or
Sensors/Inputs (32 to 3200°F) without contact suppression. Off
• Contact input for software Type T -200 to 399°C state output impedance with RC
function select (event input) (-328 to 750°F) suppression is 20kΩ
• Thermocouple Types B, C1, D1, Pt 21 0 to 1395°C • Process, 0-20mAÎ(dc),
E, J, K, N, R, S, T and Pt 21 4-20mAÎ(dc) into 800Ω
(32 to 2543°F)
• RTD resolution in 1° or maximum, 0-5VÎ(dc), 1-5VÎ(dc),
0.1° increments RTD Resolution (DIN or JIS) or 0-10VÎ(dc) into 1kΩ minimum
• Process variables: 0-50mV, 1° (DIN) -200 to 800°C reverse acting, isolated
0-20mAÎ(dc), 4-20mAÎ(dc), (-328 to 1472°F) • Electromechanical relay2,
0-5VÎ(dc), 1-5VÎ(dc), 1° (JIS) -200 to 630°C Form A/B, 5A @ 120/240VÅ(ac),
0-10VÎ(dc) 6A @ 28VÎ(dc), 1⁄8 hp @
(-328 to 1166°F)
• Slidewire, digital event input or 120VÅ(ac), 125VA @ 120VÅ(ac),
0.1° (DIN and JIS) without contact suppression
heater current options
-73.3 to 537.7°C • External transmitter power supply,
• Sensor break protection
de-energizes system for safety, (-99.9 to 999.9°F) 5, 12 or 20VÎ(dc) @ 30mA
or selectable bumpless transfer to Process • EIA/TIA-232 communications or
manual operation. Latching 0-5VÎ(dc) -999 to 9999 units EIA/TIA-485, EIA/TIA-422
or non-latching communications, opto-isolated
1-5VÎ(dc) -999 to 9999 units
• °C or °F display or process units, • Retransmit: 0-20mAÎ(dc),
0-10VÎ(dc) -999 to 9999 units
user selectable 4-20mAÎ(dc) with 600Ω max.
0-20mAÎ(dc) -999 to 9999 units load impedance, or 0-5VÎ(dc),
Input Range
4-20mAÎ(dc) -999 to 9999 units 1-5VÎ(dc) and 0-10VÎ(dc) with
Specified temperature ranges 500Ω min. load impedance
represent the controller's operational 0-50mVÎ(dc) -999 to 9999 units
span. Refer to page 228 for ANSI Slidewire 100 to 1200Ω Line Voltage/Power
(thermocouple) and DIN/JIS (RTD) Current 0 to 50mA • 100-240Vı(ac/dc) +10 percent,
temperature sensor ranges/ -15 percent; 50/60Hz, ±5 percent
Potentiometer 0 to 1200Ω
tolerances. • 24-28Vı(ac/dc) +10 percent,
Output Options -15 percent; 50/60Hz ±5 percent
Thermocouple
• Solid state relay, Form A, 0.5A @ • Power consumption 16VA
Type B 870 to 1816°C 24VÅ(ac) min., 253VÅ(ac) max., maximum
(1598 to 3300°F) opto-isolated, burst fire switching. • Fused internally (factory
Type C 1 0 to 2316°C With or without contact replaceable only) Slo-Blo® type
suppression. Off state output (time-lag):
(32 to 4200°F)
impedance is 20kΩ with RC 2A, 250V for high voltage versions
Type D1 0 to 2316°C suppression, 31MΩ without 5A, 250V for low voltage versions
(32 to 4200°F) contact suppression • Data retention upon power failure
Type E -200 to 799°C • Open collector or switched dc via non-volatile memory
(-328 to 1470°F) signal provides a minimum turn on
Type J 0 to 816°C voltage of 3VÎ(dc) into a
minimum 500Ω load; maximum on
(32 to 1500°F) voltage not greater than 32VÎ(dc)
Type K -200 to 1371°C into an infinite load, isolated
1 Not an ANSI symbol.
(-328 to 2500°F) 2 Electromechanical relays warranted for 100,000
closures only. Solid state switching devices
Type N 0 to 1300°C recommended for applications requiring fast
cycle times or extended service life.
(32 to 2372°F)
Slo-Blo® is a registered trademark of Littelfuse, Inc.
42
W A T L O W
Auto-Tuning PID
Controllers F.O.B.: Winona, Minnesota
Single-Loop
Auto-Tuning PID
• 0.45 kg (1.0 lb) Input 2
0 = None
Shipping Weight 1 = Thermocouple only (Excluding Type B, R and S)
• 1.35 kg (3.0 lbs) 2 = Universal signal conditioner
3 = Slidewire feedback
4 = Current transformerb
5 = Digital contact event (One digital event is standard on all units)
Output 1
B = Solid state relay, Form A, 0.5A, with RC suppression
C = Switched dc or open collector, isolated
D = Electromechanical relaya, Form C, 5A with RC suppression
E = Electromechanical relaya, Form C, 5A without contact suppression
F = Universal process, 0-5VÎ(dc), 1-5VÎ(dc), 0-10VÎ(dc), 0-20mA,
4-20mA, isolated
K = Solid state relay, Form A, 0.5A, without contact suppression
Output 1
A = None
B = Solid state relay, Form A, 0.5A, with RC suppression
C = Switched dc or open collector, isolated
D = Electromechanical relaya, Form C, 5A with RC suppression
E = Electromechanical relaya, Form C, 5A without contact suppression
F = Universal process 0-5VÎ(dc), 1-5VÎ(dc), 0-10VÎ(dc),
0-20mA, 4-20mA, isolated
K = Solid state relay, Form A, 0.5A, without contact suppression
T = External signal conditioner power supply, 5, 12 or 20VÎ(dc) @ 30mA
Output 3
A = None
B = Solid state relay, Form A, 0.5A, with RC suppression
Availability C = Switched dc, isolated
Four working days for orders less J = Electromechanical relaya, Form A or B, 5A without contact suppression
K = Solid state relay, Form A, 0.5A without contact suppression
than 20 units. For orders over 20 M = Retransmit, 0-20mA, 4-20mA
units, consult factory for release and N = Retransmit, 0-5VÎ(dc), 1-5VÎ(dc), 0-10VÎ(dc)
shipment schedules. T = External signal conditioner power supply, 5, 12 or 20VÎ(dc) @ 30mA
Output 4
A = None
B = Solid state relay, Form A, 0.5A, with RC suppression
C = Switched dc or open collector, isolated
D = Electromechanical relaya, Form C, 5A with RC suppression
E = Electromechanical relaya, Form C, 5A without contact suppression
K = Solid state relay, Form A, 0.5A without contact suppression
R = EIA/TIA-232 communications, opto-isolated
S = EIA/TIA-485/EIA/TIA-422 communications, opto-isolated
a Electromechanical relays warranted for 100,000 U = EIA/TIA-232/EIA/TIA-485 software selectable
closures only. Solid state switching devices T = External signal conditioner power supply, 5, 12 or 20VÎ(dc) @ 30mA
recommended for applications requiring fast Display
cycle times or extended service life.
b GG = Green/Green displays RR = Red/Red displays
A current transformer input cannot be used in
conjunction with a process output installed on GR = Green/Red displays XX = Custom overlays or default settings
output 1. RG = Red/Green displays 43
Auto-Tuning PID
Controllers
SERIES 988/989
100 mm
Dimensions WATL W (4.03 in.)
55 mm
Height: 100 mm (4.03 in.) 100 mm
PROCESS
(2.18 in.)
(4.03 in.) DEV AUTO
Width: 55 mm (2.18 in.) L1
DEV
L2 L3 L4
% OUT MAN
DISPLAY
Depth: 120 mm (4.74 in.) % OUT L1 L2 L3 L4 SERIES 989
AUTO
Bezel MAN
92 mm + 0.8
(3.62 in. + 0.03 -0.00)
15 mm 105 mm
45 mm + 0.6
(0.68 in.) (4.06 in.)
(1.77 in. + 0.02 -0.00)
System Diagram
High Limit
DIN-A-MITE® Mechanical
Power Controller Contactor
Heater
Thermocouple Thermocouple
Limit Sensor Temperature Sensor
WATL W
PROCESS
SERIES LV
Limit
SERIES 982
Controller
Chart
Recorder
44
W A T L O W
Auto-Tuning PID
Controllers
SERIES F4P
The SERIES F4P 1⁄4 DIN temperature
process controllers offer the per-
formance and features to meet a
wide range of industrial processing
needs. The F4P process controllers
are ideally suited for semiconductor
manufacturing equipment, plastics
processing and packaging
equipment and industrial process
control applications.
This competitively priced controller
features a four line, high definition
Single-Loop
LCD interface display along with an
Auto-Tuning PID
information key that makes set up
and control operation significantly 1A
F4
1 or 3 Universal 2 Control
easier with less chance for error. A Analog Inputs
1B
Outputs
16 bit microprocessor supports all
the accuracy and performance 4 Digital …A larm 1 L o D eviation
–1 F 1
2 Alarm
Inputs A djusts V alue
Outputs
advantages you have come to
2
B ack N ext
45
Auto-Tuning PID
Controllers
SERIES F4P Control Outputs systems with long lag times. Input 3
Heat/cool or reverse/direct action is measures the lube oil temperature
supported. Time based outputs can before it leaves the tank. Input 1
General Purpose Control Operation
be configured for variable burst fire or measures the heater temperature.
The SERIES F4P temperature a cycle time can be selected. On-off The input 3 process value is
process controller is a single channel boost heat or boost cool operation is compared to the set point which
PID controller that supports either also supported. Boost operation is generates and internal set point used
closed or open loop operation. The enabled based on load power to control the heater.
design utilizes the latest technology requirements.
to provide a controller capable to Specifications
meeting very complex processing Alarms Universal Analog Inputs 1 (2 and 3
needs while maintaining an easily Two alarms are included in the base optional)
understood operator interface. unit. These alarms are programmable • Update rates: IN1 = 20Hz, IN2
Full non-abbreviated parameter as process, deviation or rate.
and IN3 = 10Hz
choices are displayed using a four Serial Communications
Thermocouple
line liquid crystal display. The display Both EIA-232 and EIA-485
is back lit for wide angle viewing. The communications are included in the • Type J, K, T, N, C (W5), E, Pt 2,
firmware guides the operator through base unit. The SERIES F4P operates D (W3), B, R, S
parameter choices for feature via the Modbus™ RTU protocol. RTD
configuration. An information key (I) The F4P responds to requests for • 2- or 3-wire platinum, 100Ω
provides the operator with detailed information only when queried. Baud
help information regarding the rate selections are 9600 or 19200. • JIS or DIN-curves, 1.0 or 0.1
parameter or feature being indication
Retransmit
configured. The main page menu can • 500 or 1KΩ RTD available
be programmed to display output Up to two optional programmable
voltage or current signal retransmit Process
power through 16 control variables
including: bar graphs, set points and outputs are supported. Retransmit • Input resolution ≈ 50,000 bits at
operating ranges. Up to four sources include up to three process full scale
programmable messages can be variables, set point and output
• Range selectable: 0-10VÎ(dc),
activated remotely to let the operator percent power.
0-5VÎ(dc), 1-5VÎ(dc), 0-50mV,
know that the process requires their Enhanced Control Operation 0-20mA, 4-20mA
attention. When the enhanced operation option • Voltage input impedance 20KΩ
Five sets of PID values can be auto- is ordered, the F4P process controller
tuned to support varying system is supplied with two additional • Current input impedance 100Ω
reaction over the complete operating universal analog inputs (inputs 2 and Digital Inputs (4)
range. Up to 10 offset points can 3) and enhanced firmware to support • Update rate = 10Hz
programmed to compensate for numerous features that utilize the two
differences between the actual additional inputs. The enhanced • Contact or dc voltage; 36VÎ(dc)
process value and sensor readings control option can be configured to max
caused by sensor placement. support cascade control, differential • 10KΩ input impedance
Control Inputs control, ratio control and slidewire Control Outputs (1A, 1B)
valve control. The enhanced control
Up to three universal analog inputs option can also alternate between • Update rate = 20Hz
are supported. These inputs are control inputs, display up to three Open Collector/Switched dc
configured through software to process variables and support
support thermocouples, RTDs and • Internal load switching (nominal):
remote set point operation. Switched dc, 22 to 28VÎ(dc),
process (voltage/current) sensors.
Auxiliary inputs 2 and 3 can function In this sample application the SERIES limited @ 30mA
as a remote set point input, sources F4P process controller utilizes the
• External load switching max.:
for retransmission or as the outer loop enhanced cascade control feature to
heat lube oil to 51.6˚C (125˚F). Open collector 42VÎ(dc) @ 0.5A
for cascade operation.
Cascade control is a control strategy Solid-state Relay
Digital Inputs in which one control loop provides • Zero switched, optically coupled,
These four inputs are programmable the set point for another loop. It allows 0.5A @ 24VÅ(ac)
and can be used to remotely modify the process or part temperature to be minimum, 253VÅ(ac) max.
the operation of the controller as well reached quickly while minimizing
as displaying pre-programmed overshoot. Cascade is used to
messages on the operations display. optimize the performance of thermal
46
W A T L O W
Auto-Tuning PID
Controllers
SERIES F4P • 39VA maximum power Type E: -200 to 800°C
consumption (-328 to 1470°F)
• Data retention upon power failure Type C: 0 to 2315°C
Specifications Cont.
via nonvolatile memory. Sensor (32 to 4200°F)
Electromechanical Relay Type D: 0 to 2400°C
input isolation from input to input
• Form C, 2A @ 250VÅ(ac) or to output to communication (32 to 4352°F)
30VÎ(dc) max. circuitry is 500VÅ(ac). Type Pt 2: 0 to 1395°C
• Resistive or inductive load (32 to 2543°F)
Operating Environment
Type R: 0 to 1760°C
• Without contact suppression • 0 to 65°C (32 to 149°F) (32 to 3200°F)
Process Outputs (Optional • 0 to 90 percent RH, non-condensing Type S: 0 to 1760°C
Retransmit) (32 to 3200°F)
• Storage temperature: -40 to 70°C
• Update rate = 1Hz (-40 to 158°F) Type B: 0 to 1816°C
• User-selectable 0-10VÎ(dc), (32 to 3300°F)
Accuracy
0-5VÎ(dc), 1-5VÎ(dc) @1KΩ min., RTD (DIN): -200 to 800°C
Single-Loop
• Calibration accuracy and sensor
Auto-Tuning PID
0-20mA, 4-20mA @ 800Ω max. (-328 to 1472°F)
conformity: ±0.1 percent of span RTD (JIS): -200 to 800°C
• Resolution: ±1°C @ 25°C ±3°C (77°F ±5°F) (-328 to 1166°F)
dc ranges = 2.5mV nominal ambient, and rated line voltage Process: -19,999 to 30,000 units
mA ranges = 5µA nominal ±10 percent with the following Sensor Accuracy Ranges
• Calibration accuracy: exceptions:
Input ranges
dc ranges = ±15mV Type T: 0.12 percent of span for
Type J: 0 to 815°C
mA ranges = ±30µA -200°C to -50°C (-328°F to -58°F)
(32 to 1500°F)
• Temperature stability 100ppm/°C Types R and S: 0.15 percent of Type K: -200 to 1370°C
span for 0°C to 100°C (32°F to (-328 to 2500°F)
Alarm Outputs
212°F) Type T: -200 to 400°C
• Output update rate 1Hz
Type B: 0.24 percent of span for (-328 to 750°F)
• Electromechanical relay, Form C, 870°C to 1700°C (1598°F to Type N: 0 to 1300°C
2A @ 30VÎ(dc) or 240VÅ(ac) max. 3092°F) (32 to 2372°F)
Communications • Accuracy span: Less than or Type E: -200 to 800°C
• EIA-232 and EIA-485 serial equal to operating ranges, 540°C (-328 to 1470°F)
communications with Modbus™ (1000°F) minimum Type C: 0 to 2315°C
RTU protocol. 9600 or 19.2K (32 to 4200°F)
• Temperature stability: ±0.1°C/°C
baud rate Type D: 0 to 2400°C
(±0.1°F/°F) rise in ambient for
(32 to 4352°F)
Safety and Agency Approvals thermocouples
Type Pt 2: 0 to 1395°C
• UL®/C-UL® 916-listed, • ±0.05°C/°C (±0.05°F/°F) rise in (32 to 2543°F)
File # E185611 process control ambient for RTD sensors Type R: 0 to 1760°C
equipment Displays (32 to 3200°F)
• NEMA 4X and IP65 • Process: 5, seven-segment Type S: 0 to 1760°C
• CE to EN 61010-1 and 61326 LED red (32 to 3200°F)
Type B: 0 to 1816°C
Terminals • Control interface display:
(32 to 3300°F)
• Touch-safe, removable terminal high-definition LCD green
RTD (DIN): -200 to 800°C
blocks, accepts 12 to 22-gauge Sensor Operating Ranges (-328 to 1472°F)
wire Type J: 0 to 815°C RTD (JIS): -200 to 800°C
Power (32 to 1500°F) (-328 to 1166°F)
• 100-240VÅ(ac), -15 percent, Type K: -200 to 1370°C Process: -19,999 to 30,000 units
+10 percent; 50/60Hz, ±5 percent (-328 to 2500°F)
Type T: -200 to 400°C
• 24-28Vı(ac/dc), -15 percent, (-328 to 750°F)
+10 percent (order option) Type N: 0 to 1300°C
(32 to 2372°F)
47
Auto-Tuning PID
Controllers F.O.B.: Winona, Minnesota
F4 P - A -
Panel Cutout SERIES F4P
92 mm x 92 mm
(3.622 in. x 3.622 in.) Temperature/Process Controller
99.82 mm Single channel temperature/
(3.930 in.) process controller, two alarms,
EIA-232/485 comms, four
event inputs
99.82 mm Power Supply
(3.930 in.)
H = 100-240Vı(ac/dc)
108.81 mm L = 24-28Vı(ac/dc)
(4.824 in.)
Output 1A
C = Open collector/switched dc
E = Electromechanical relay, Form C
2 amp without contact suppression
K = Solid state Form A 0.5 amp relay
without contact suppression
F = Process, 0-5, 1-5, 0-10VÎ(dc),
0-20mA, 4-20mA
Output 1B
108.05 mm A = None
(4.254 in.) E = Electromechanical relay, Form C
2A without contact suppression
97.79 mm C = Open collector/switched dc
(3.850 in.)
K = Solid state Form A 0.5 amp relay
without contact suppression
F = Process, 0-5, 1-5, 0-10VÎ(dc),
0-20mA, 4-20mA
Enhanced Control Operation
A = Standard control operation
B = Enhanced control operation, dual universal
inputs, cascade, ratio, duplex, differential,
slidewire
Auxiliary Retransmit Module
0 = None
10.26 mm 1 = Single retransmit output 0-5, 1-5, 0-10VÎ(dc),
(.404 in.) 0-20mA, 4-20mA
2 = Dual retransmit outputs 0-5, 1-5, 0-10VÎ(dc),
0-20mA, 4-20mA
Language and RTD Options
1 = English with 100Ω RTD 5 = English with 500 & 1KΩ RTD
Specifications Cont. 2 = German with 100Ω RTD 6 = German with 500 & 1KΩ RTD
3 = French with 100Ω RTD 7 = French with 500 & 1KΩ RTD
Dimensions 4 = Spanish with 100Ω RTD 8 = Spanish with 500 & 1KΩ RTD
• Width x height x depth Display and Custom Options
99 mm x 99 mm x 97 mm panel RG= Red/Green display
mount (3.93 in. x 3.93 in. x 3.85 in.) XX = Custom options, software, setting parameters, overlays
48
W A T L O W
Auto-Tuning PID
Controllers
SERIES PD
Single Loop
Single-Loop
Auto-Tuning PID
ideally suited for a wide range of
temperature or process control
applications where the operator
interface is supported from a remote
location. The SERIES PD provides
interfacing via embedded firmware
which serves dedicated web pages. Ethernet
Communications
These pages support key functions
including operation, alarm monitoring,
configuration and are displayed using
standard web browser software.
The SERIES PD is also capable of 1 Universal
Analog Input
generating e-mail messages for (Single Channel)
PD
remote alarm notification. PID Controller
Power
Ethernet-based products are rapidly
Ethernet Link
gaining popularity in industrial
Ethernet Activity 4 outputs
applications because they allow can be
an instantaneous exchange of configured or
event (alarm)
information between processing 1 Input Error outputs. Any
equipment and the company’s 2 Input Error
output can be
assigned
management system. Output 1 to either
channel 1 or 2.
Advanced features of the SERIES PD Output 2
49
Auto-Tuning PID
Controllers
SERIES PD Advanced control algorithm
Single Loop • Tighter process control
Heater burn out detection
Features and Benefits • Improved process yields
Ethernet connectivity Internal data logging
• Convenient, easy to use operator • Reduces external hardware
interface demands
• Simplified process monitoring Virtual or hardware alarms with
e-mail delivery
DIN-rail sub panel mounting
• Remote alarm notification
• Quick, economic installation
Watlow INFOSENSE™ sensor
technology
• INFOSENSE™ technology Front View
improves sensor accuracy by a 8 mm
Bracket for
minimum of 50 percent Panel Mounting (0.318 in.)
(#6 Screw
or m3.5 Required) Top/Bottom
Mount
Hole Offset
Side View PD
PID Controller
Power
Ethernet Link
107 mm Ethernet Activity
(4.225 in.)
1 Input Error
129 mm
(5.062 in.)
Min. Clearance 51 mm
(2 in.)
73 mm 42 mm
(2.875 in.) (1.637 in.)
PD PD
PID Controller PID Controller
DIN-
rail Power Power
Output 1 Output 1
Output 2 Output 2
Attachment Angle 10°
Output 3 Output 3
Output 4 Output 4
Address Address
42 mm
(1.650 in.)
50
W A T L O W
Auto-Tuning PID
Controllers
SERIES PD Universal Inputs Control/Alarm Outputs (1 - 4)
Single Loop (Electrically Isolated) • User selectable as: on-off, P, PI,
• Thermocouple, grounded or PD, PID, heat, cool, alarm action
ungrounded sensors or retransmit with process output
Specifications type hardware
• RTD 2-or 3-wire, platinum,
Power 100Ω @ 0°C calibration to • Open collector/switched dc
• 24Vı(ac/dc), +10/-15 percent, DIN-curve (0.00385 Ω/Ω/°C) • Open collector 42VÎ(dc)
50/60Hz, ±5 percent • Process 0-20mA @ <100Ω, maximum @ 0.5A
• 12VA maximum power or 0-10VÎ(dc) @ 10kΩ input • Switched dc 22 to 28VÎ(dc)
consumption impedance (50,000 bits @ limited @ 30mA
• Data retention upon power failure full scale)
• Solid state relay, Form A, 0.5A @
via nonvolatile memory Digital Inputs 24VÅ(ac) minimum, 264VÅ(ac)
Environment • Contact or dc voltage maximum, opto-isolated, without
• 0 to 65°C (32 to 149°F) operating • 10KΩ input impedance contact suppression
Single-Loop
Auto-Tuning PID
temperature Current Transformer Inputs • User-selectable 0-10VÎ(dc), 1KΩ
• -40 to 85°C (-40 to 185°F) storage minimum, scalable, 0-20mA @
• 0 to 50mA CT input into 100Ω
temperature 800Ω maximum, scalable
impedance
• 0 to 90 percent RH, non-condensing • Electromechanical relay. Form C,
Allowable Input Operating Range
rated 5A @ 120VÅ(ac) or 5A @
Accuracy Type J: -200 to 1200°C 240VÅ(ac) or 5A @ 30VÎ(dc)
• Calibration accuracy and sensor (-328 to 2192°F)
Communications
conformity: ±0.1 percent of span, Type K: -270 to 1370°C
±1°C @ the calibrated ambient (-454 to 2500°F) • TCP/IP/Ethernet
temperature and rated line voltage Type T: -270 to 400°C • Modbus™ TCP
• Calibration ambient temperature (-454 to 750°F) • Ethernet RJ 45 connector,
= 25°C ±3°C (77°F ±5°F) Type N: -270 to 1300°C 10 base T
(-454 to 2372°F)
• Accuracy span: 540°C (1000°F) • HTTP interface
Type E: -270 to 975°C
minimum • DHCP, auto IP or fixed IP address
(-454 to 1790°F)
• Temperature stability: ±0.1°C/°C Type C: 0 to 2315°C Dimensions
(±0.2°F/°F) rise in ambient (32 to 4200°F) • Width x height x depth
maximum Type D: 0 to 2315°C
(32 to 4200°F) 42 mm x 116 mm x 132 mm
Agency Approvals
Type PTII: 0 to 1395°C (1.64 in. x 4.56 in. x 5.19 in.)
• UL® 508, C-UL®, CSA and CE DIN-rail or chassis mount, DIN-rail
(32 to 2543°F)
Controller spec DIN 5022
Type R: 0 to 1760°C
• Microprocessor based user- (32 to 3200°F) 35 mm x 7.5 mm (1.38 in. x 0.30 in.)
selectable control modes Type S: 0 to 1760°C
• Single or dual channel universal (32 to 3200°F)
inputs Type B: 0 to 1815°C
• Current transformer inputs/digital (32 to 3300°F)
inputs RTD (DIN): -200 to 800°C
(-328 to 1470°F)
• Up to four programmable outputs
Process V: 0 to 10VÎ(dc)
• Update rates, inputs = 10Hz, Process I: 0 to 20mA
outputs = 10Hz
Operator Interface
• Browser based HMI (Human
Machine Interface)
Wiring Termination
• Touch safe removable terminals
• 14 to 22 AWG
51
Auto-Tuning PID
Controllers F.O.B.: Winona, Minnesota
P D S_ - _ _ _ _ - _ A _ _
Auxiliary Inputs
1 = Dual digital inputs
2 = One CT input and one digital input
3 = Dual CT inputs (dual channel only)
Output 1
C = Switched dc, open collector
K = SSR, Form A, 0.5A
F = Universal process
J = Mechanical relay, Form A, 2Aa
Output 2
A = None
C = Switched dc, open collector
K = SSR, Form A, 0.5A
E = Mechanical relay, Form C, 2Aa
Output 3
A = None
C = Switched dc, open collector
K = SSR, Form A, 0.5A
F = Universal process
E = Mechanical relay, Form C, 2Aa
Output 4
A = None
C = Switched dc, open collector
K = SSR, Form A, 0.5A
E = Mechanical relay, Form C, 2Aa
On Board Data Logging
0 = None
1 = 16 megabytes of memory
Custom Options
AA = Watlow logo
BB = No logo
52
W A T L O W
Auto-Tuning PID
Controllers
MICRODIN®
Single-Loop
Auto-Tuning PID
communications protocol with a
standard EIA-485 serial interface for
parameter set up and viewing.
The behind-the-panel, DIN-rail mount
design of the MICRODIN controller
provides significant savings by MicroDIN
eliminating the need for expensive Single
Temperature Controller Control Output
PID or on-off
panel hole punching and by Thermocouple, Power
Auto-Tuning PID
Controllers F.O.B.: Winona, Minnesota
MICRODIN
Specifications Cont. Ordering Information
Terminals To order, complete the code number on the right with the information below:
• Touch-safe set screw type,
accepts 26-14 gauge wire
UD1A-1CES-____
Power
• 24-28V‡(ac/dc), -15 percent, MICRODIN = DIN-rail mount temperature control. 1 sensor input,
+10 percent (20.4 to 1 control output, 1 alarm output, no operator interface and EIA-485
30.8V‡(ac/dc); 50/60Hz, Modbus™ RTU serial communications with Quick Start Guide.
±5 percent for VÅ(ac) Hardware
• 5VA typical power consumption 1A = Single channel, low voltage1
Single-Loop
Auto-Tuning PID
via nonvolatile memory 1 = Type B, C, D, E, J, K, N, Pt 2, R, S, T,
1°RTD, 0.1°RTD (JIS and DIN)
• Sensor input isolation to switched
Control Output
dc output and communication
circuitry 500VÅ(ac) dielectric C = Switched dc, logic signal, non-isolated1
Alarm Output
Operating Environment
E = Electromechanical relay, Form A, 2A, w/o contact suppression2
• 0 to 65°C (32 to 149°F)
Communications
• 0 to 90 percent RH, non-condensing
S = EIA/TIA-485 communications, opto-isolated, Modbus™ RTU protocol
• Storage temperature: -40 to 70°C Software
(-40 to 158°F)
00 = Standard
XX = Custom setup parameters
Custom Options
00 = None
AA = No Watlow logo on front bezel
XX = Custom bezel or label
Availability
Stock: Same day shipment on Non-Stock: 10 working days
orders of 10 units or less; 10 working
days on orders greater than 10
units.
Stock List
55
Auto-Tuning PID
Controllers
MICRODIN Mounting a MICRODIN controller
146 mm
Depth: 132 mm (5.19 in.) (3.750 in.)
DIN-
rail
Control
Output
118 mm
(4.650 in.)
Chassis Alarm
Input
Error
Min. Clearance
Address
between rail
Width: 42 mm (1.64 in.) centerlines
146 mm
(5.750 in.)
Height: 118 mm (4.65 in.) 129 mm
(5.062 in.) Min. Clearance 51 mm 42 mm
Depth: 129 mm (5.06 in.) (2 in.) (1.637 in.)
73 mm
(2.875 in.) MicroDIN MicroDIN
Temperature Controller Temperature Controller
Power Power
Comms Comms
Control Control
DIN- Output Output
rail
Alarm Alarm
Input Input
Error Error
Address Address
42 mm
(1.650 in.)
Attachment Angle 10°
System Diagram
High Limit
DIN-A-MITE® Mechanical
Power Controller Contactor
Heater
Thermocouple Thermocouple
Limit Sensor Temperature Sensor
MicroDIN
Temperature Controller
Power
Comms
Control
Output
SERIES LV
Limit
Alarm
Controller
Input
Error
Address