General Availability: 6 weeks Custom versions and specials: ~10weeks

Mercury Range 12V, 24/27V, 48/54V, 130V & 375Vdc


Front-Ends / Rectifiers
Product Description Although commercial grade in construction and cost, these power modules possess features deserving of military grade products. The Mercury product range includes versions rated from 1,200W to 4,300W. Each module is available in both Rectifier (battery Charger) and Power Supply (Front End) versions. The modules are also available in 1U or 2U mechanical configurations. Various output voltage are available including 12, 24,27,48, 54, 130 &375Vdc. They are designed to be used with the corresponding shelf for system operation or with a custom backplane in OEM applications. Shelves may be connected to TDIs e-linkTM for system alarm communications. The modules are available with a CAN bus interface. For simple applications, output voltage control may be achieved with the use of a resistive network. Simple power systems employing Mercury modules and a shelf may be configured from this data-sheet. Systems employing this equipment plus Inverters, DCDC converters, distribution panels, batteries and controllers are available from TDIs systems group. Applications OEM Internal System power for Industrial, Communications and Datacom systems Wireless and Network Infrastructure Power as a system component in your Power system Key Features Extended/Wide Range Input (up to 300VAC for Limited Durations) Reliable Power for the Harshest Utility Environment Power Density & Reliability Industry leading Power Density and superb reliability at lowest lifetime cost. Global approvals UL and CE marked world wide application Thermal Design Front-to-back air flow suits embedded and parallel shelf system applications

www.tdipower.com

Contents
Page 3 4 5 6 7 Description 1200W standard products 1200W Custom product, CS2 1500W Standard products 2700W standard products 2700W custom product, CS1 3800W standard products 4300W standard products 10-11 12 Mercury Shelf Contacts

1,200 W Technical Specifications


AC INPUT Voltage: 90275VAC Over-voltage (tested to 300Vac) Frequency: 47-63Hz Peak Inrush Current: <20A Power Factor: 0.99 typical Efficiency: ~88% with 115VAC source, 50 to 100% load Hold-Up Time: 20mS min. Input Overcurrent: (internal) 20A Fuse DC OUTPUT Voltage: 12, 24V, 27V, 48V, 56V, 130 & 375Vdc. Custom outputs available, consult Factory. Power: 1,200W Accuracy: 50mV Ripple & Noise: 1% V P-P Measured with 20Mhz Bandwidth Line Regulation: Less than 0.25% Load Regulation: 1.0% from no load to full load (droop load share) Parallel Use: May be paralleled with other like units for increased system output, redundant diode included Current Sharing: Slope program current share, (droop) Temperature Coefficient: < 0.02% perC Acoustic Noise < 55dBA at nominal input and full load ELECTRONIC ALARMS (Basic Set, others available) AC OK: low when AC input is in range Output OK: low if the output voltage is within 10% of the actual voltage set point (low=<.6V@1mA) (high=open collector (I<50A) CAN Bus: available option VISUAL FAULT INDICATORS Output OK: A front panel Green Output OK LED will be lit if the units output is within the acceptable range. ELECTRONIC CONTROL INPUTS Remote Inhibit: Application of a TTL input signal will cause the supply to shut down and an output OK fault alarm will be issued. (TTL High = Inhibit) Remote Program: Provides +9%, -27% of set point voltage with 0 to 5V control signal TEMPERATURE Normal Operation: -20 to +55C High Temperature Operation: derate 10% perC, 55 to 65C Low Temperature Turn On: -40C Minimum Storage / Transportation: -40C to +85C Humidity Operating: 5% to 95% RH non-condensing Storage: 0% to 99% RH non-condensing PHYSICAL DIMENSIONS Packaging (both available in 1U and 2U) Dimensions: 1U, H44.5 x W223 x D375mm (1.75 x 8.75 x D14.75) 2U H88x W122 x D375mm (3.5 x 4.2 x 14.75) Weight: 4kg (9lbs) AGENCY COMPLIANCE CE Marked: Low Voltage Directive only standards Electrical safety: IEC 60950-1, UL 60950-1 EMI (conducted): FCC Part 15, Sub-part J, class A and EN55022, class A EMI (radiated): Stand alone module tested to EN55022 Class B. Harmonics: EN 61000-3-2 EN 61000-6-1 (Immunity, light industry) EN 61000-6-2 (Immunity, industry) EN 61000-6-3 (Emissions, light industry) EN 61000-6-4 (Emissions, industry) RoHS compliant Notes: Designed for use with Mercury shelf or custom Backplane Options: Variable Speed Fan Silicone RTV encapsulate Contact Factory for Options and full Product Specification

ORDERING INFORMATION
Part no. 136653-N48D00 136874-N54D00 136874-P27D00 139239-P12A00 Description 1,200W, 1U, 48Vdc, 1,200W, 2U, 54Vdc, 1,200W, 2U, 27Vdc, 1,200W, 2U, 12Vdc, Droop CS, standard alarms Droop CS, standard alarms Droop CS, standard alarms Active CS, standard alarms

www.tdipower.com
Copyright 2007, Transistor Devices, Inc.

Energy Solutions for the Next Generation

This document is believed to be correct at time of publication and Transistor Devices, Inc. accepts no responsibility for consequences from printing errors or inaccuracies. Specifications are subject to change without notice.

1,200 W Technical Specifications: CS2, 136874-P27D10


AC INPUT Voltage: 90275VAC Over-voltage (tested to 300Vac) Frequency: 47-63Hz Peak Inrush Current: <20A Power Factor: 0.99 typical Efficiency: ~88% with 115VAC source, 50 to 100% load Hold-Up Time: 20mS min. Input Overcurrent: (internal) 20A Fuse DC OUTPUT Voltage: 27V Power: 1,200W Accuracy: 50mV Ripple & Noise: 1% V P-P Measured with 20Mhz Bandwidth Line Regulation: Less than 0.25% Load Regulation: 1.0% from no load to full load (droop load share) Parallel Use: May be paralleled with other like units for increased system output, redundant diode included Current Sharing: Slope program current share, (droop) Temperature Coefficient: < 0.02% perC Acoustic Noise < 55dBA at nominal input and full load ELECTRONIC ALARMS (Basic Set, others available) AC OK: low when AC input is in range Output OK: low if the output voltage is within 10% of the actual voltage set point (low=<.6V@1mA) (high=open collector (I<50A) CAN Bus: available option VISUAL FAULT INDICATORS Output OK: A front panel Green Output OK LED will be lit if the units output is within the acceptable range. ELECTRONIC CONTROL INPUTS Remote Inhibit: Application of a TTL input signal will cause the supply to shut down and an output OK fault alarm will be issued. (TTL High = Inhibit) Remote Program: Provides +9%, -27% of set point voltage with 0 to 5V control signal TEMPERATURE Normal Operation: -20 to +55C High Temperature Operation: derate 10% perC, 55 to 65C Low Temperature Turn On: -40C Minimum Storage / Transportation: -40C to +85C Humidity Operating: 5% to 95% RH non-condensing Storage: 0% to 99% RH non-condensing PHYSICAL DIMENSIONS Dimensions: 2U, H88x W122 x D375mm (3.5 x 4.2 x 14.75) Weight: 4kg (9lbs) AGENCY COMPLIANCE CE Marked: Low Voltage Directive only standards Electrical safety: IEC 60950-1, UL 60950-1 EMI (conducted): FCC Part 15, Sub-part J, class A and EN55022, class A EMI (radiated): Stand alone module tested to EN55022 Class B. Harmonics: EN 61000-3-2 EN 61000-6-1 (Immunity, light industry) EN 61000-6-2 (Immunity, industry) EN 61000-6-3 (Emissions, light industry) EN 61000-6-4 (Emissions, industry) RoHS compliant Notes: Includes Fan-Speed control board Options: Packaging, 1U Contact Factory for Options and full Product Specification

ORDERING INFORMATION
Part no. 136874-P27D10 Description 1,200W, 2U, 27Vdc, Droop CS, standard alarms

www.tdipower.com
Copyright 2007, Transistor Devices, Inc.

Energy Solutions for the Next Generation

This document is believed to be correct at time of publication and Transistor Devices, Inc. accepts no responsibility for consequences from printing errors or inaccuracies. Specifications are subject to change without notice.

1,500 W Technical Specifications


AC INPUT Voltage: 176275VAC Over-voltage Frequency: 47-63Hz Peak Inrush Current: <20A Power Factor: 0.99 typical Efficiency: ~90% with 230VAC source, 50 to 100% load Hold-Up Time: 20mS min. Input Overcurrent: (internal) 20 A Fuse ** Meets SEMI F47 requirements DC OUTPUT Voltage: 48Vdc Power: 1,500W Accuracy: 50mV Ripple & Noise: 1% V P-P Measured with 20Mhz Bandwidth Line Regulation: Less than 0.25% Load Regulation: 1.0% from no load to full load (droop load share) Parallel Use: May be paralleled with other like units for increased system output, redundant diode included Current Sharing: Slope program current share, (droop) Temperature Coefficient: < 0.02% perC Acoustic Noise < 65dBA at nominal input and full load ELECTRONIC ALARMS (Basic Set, others available) AC OK: low when AC input is in range Output OK: low if the output voltage is within 10% of the actual voltage set point (low=<.6V@1mA) (high=open collector (I<50A) VISUAL FAULT INDICATORS Output OK: A front panel Green Output OK LED will be lit if the units output is within the acceptable range. CAN Bus: available option ELECTRONIC CONTROL INPUTS Remote Inhibit: Application of a TTL input signal will cause the supply to shut down and an output OK fault alarm will be issued. (TTL High = Inhibit) Remote Program: Provides +9%, -27% of set point voltage with 0 to 5V control signal TEMPERATURE Normal Operation: -20 to +55C Low Temperature Turn On: -40C Minimum Storage / Transportation: -40C to +85C Humidity Operating: 5% to 95% RH non-condensing Storage: 0% to 99% RH non-condensing PHYSICAL DIMENSIONS (available in 1U and 2U package) Dimensions: 1U, H44.5 x W223 x D375mm (1.75 x 8.75 x D14.75) 2U H88x W122 x D375mm (3.5 x 4.2 x 14.75) Weight: 4kg (9lbs) AGENCY COMPLIANCE CE Marked: Low Voltage Directive only standards Electrical safety: IEC 60950-1, UL 60950-1 EMI (conducted): FCC Part 15, Sub-part J, class A and EN55022, class A EMI (radiated): Stand alone module tested to EN55022 Class B. Harmonics: EN 61000-3-2 EN 61000-6-1 (Immunity, light industry) EN 61000-6-2 (Immunity, industry) EN 61000-6-3 (Emissions, light industry) EN 61000-6-4 (Emissions, industry) RoHS compliant Notes: Designed for use with Mercury shelf or custom Backplane ** SEMI F47 - a voltage sag immunity standard, SEMI F47 is an industry standard for voltage sag immunity. It says that industrial equipment must tolerate voltage sags, or dips, on the AC mains supply to specific depths and durations. It is such a good and useful standard that many other industries use it, either formally or informally. Options: Variable Speed Fan Silicone RTV encapsulate Contact Factory for Options and full Product Specification

ORDERING INFORMATION
Part no. 141543-N48D00 143467-N54D00 136874-P1HA01 Description 1U, 1500W, 48Vdc, Droop CS, standard alarms, Semi F47 mods 1U, 1500W, 54Vdc, Droop CS, standard alarms 2U, 1500W, 130Vdc OP, Droop CS, Standard Alarms

www.tdipower.com
Copyright 2007, Transistor Devices, Inc.

Energy Solutions for the Next Generation

This document is believed to be correct at time of publication and Transistor Devices, Inc. accepts no responsibility for consequences from printing errors or inaccuracies. Specifications are subject to change without notice.

2,700 W Technical Specifications


AC INPUT Voltage: 176275VAC Over-voltage tested to 300Vac Frequency: 47-63Hz Peak Inrush Current: <20A Power Factor: 0.99 typical Efficiency: ~93% with 230VAC source, 50 to 100% load Hold-Up Time: 10mS min. Input Overcurrent: (internal) 20 A Fuse DC OUTPUT Voltage: 24V, 27V, 48V, 56V standard. Custom outputs available, consult Factory Power: 2,700W Accuracy: 50mV Ripple & Noise: 1% V P-P Measured with 20Mhz Bandwidth Line Regulation: Less than 0.25% Load Regulation: 1.0% from no load to full load (droop load share) Parallel use: May be paralleled with other like units for increased system output, redundant diode included Current Sharing: Slope program current share, (droop) Temperature Coefficient: < 0.02% perC Acoustic Noise < 65dBA at nominal input and full load ELECTRONIC ALARMS (Basic Set, others available) AC OK: low when AC input is in range Output OK: low if the output voltage is within 10% of the actual voltage set point (low=<.6V@1mA) (high=open collector (I<50A) CAN Bus: available option VISUAL FAULT INDICATORS Output OK: A front panel Green Output OK LED will be lit if the units output is within the acceptable range. ELECTRONIC CONTROL INPUTS Remote Inhibit: Application of a TTL input signal will cause the supply to shut down and an output OK fault alarm will be issued. (TTL High = Inhibit) Remote Program: Provides +9%, -27% of set point voltage with 0 to 5V control signal TEMPERATURE Normal Operation: -20 to +55C High Temperature Operation: derate 10% perC, 55 to 65C Low Temperature Turn On: -40C Minimum Storage / Transportation: -40C to +85C Humidity Operating: 5% to 95% RH non-condensing Storage: 0% to 99% RH non-condensing PHYSICAL DIMENSIONS Packaging (both available in 1U and 2U) Dimensions: H88x W122 x D375mm (3.5 x 4.2 x 14.75) Weight: 4kg (9lbs) AGENCY COMPLIANCE CE Marked: Low Voltage Directive only standards Electrical safety: IEC 60950-1, UL 60950-1 EMI (conducted): FCC Part 15, Sub-part J, class A and EN55022, class A EMI (radiated): Stand alone module tested to EN55022 Class B. Harmonics: EN 61000-3-2 EN 61000-6-1 (Immunity, light industry) EN 61000-6-2 (Immunity, industry) EN 61000-6-3 (Emissions, light industry) EN 61000-6-4 (Emissions, industry) RoHS compliant Notes: Designed for use with Mercury shelf or custom Backplane Options: Variable Speed Fan Silicone RTV encapsulate Contact Factory for Options and full Product Specification

ORDERING INFORMATION
Part no. 138233-N54D00 139239-P27D00 138233-N54D04-LF Description 2,700W, 54Vdc, Droop CS, standard alarms 2,700W, 27Vdc, Droop CS, standard alarms 2,700W, 54Vdc, Droop CS, reversed alarms, Black front panel

www.tdipower.com
Copyright 2007, Transistor Devices, Inc.

Energy Solutions for the Next Generation

This document is believed to be correct at time of publication and Transistor Devices, Inc. accepts no responsibility for consequences from printing errors or inaccuracies. Specifications are subject to change without notice.

3,800 W Technical Specifications


AC INPUT Voltage: 176275VAC Over-voltage tested to 325Vac Frequency: 47-63Hz Peak Inrush Current: <50A Power Factor: 0.99 typical Efficiency: ~93% with 230VAC source, 50 to 100% load Hold-Up Time: 10mS min. Input Overcurrent: (internal) 25 A Fuse DC OUTPUT Voltage: +24V, +27V, -48V, -54.5V. Custom outputs available, consult Factory Power: 3,800W, -20 to +55C, 176-275Vac 2,700W, -20 to +75C, 176-275Vac 1,900W, -20 to +55C, 90-275Vac 810W, -20 to +75C, 90-275Vac Auxiliary output: 12V/ 0.1A Accuracy: 50mV Ripple & Noise: 1% V P-P Measured with 20Mhz Bandwidth Line Regulation: Less than 0.25% Load Regulation: 1.0% from no load to full load (droop load share) Parallel Use: May be paralleled with other like units for increased system output, redundant diode included Current Sharing: Slope program current share, (droop) Temperature Coefficient: < 0.02% perC Acoustic Noise < 63dBA at nominal input and full load ELECTRONIC ALARMS (Basic Set, others available) AC OK: low when AC input is in range Output OK: low if the output voltage is within 10% of the actual voltage set point (low=<.6V@1mA) (high=open collector (I<50A) CAN Bus: available option VISUAL FAULT INDICATORS Output OK: A front panel Green Output OK LED will be lit if the units output is within the acceptable range. ELECTRONIC CONTROL INPUTS Remote Inhibit: Application of a TTL input signal will cause the supply to shut down and an output OK fault alarm will be issued. (TTL High = Inhibit) Remote Program: Provides +9%, -27% of set point voltage with 0 to 5V control signal TEMPERATURE Normal Operation: -20 to +75C High Temperature Operation: See Notes in DC Output Section Low Temperature Turn On: -40C Minimum Storage / Transportation: -40C to +85C Humidity Operating: 5% to 95% RH non-condensing Storage: 0% to 99% RH non-condensing Fan Speed control: unit features a Variable Speed Fan circuit that adjusts the fan speed based on ambient air temperature and load.

PHYSICAL DIMENSIONS Packaging (both available in 1U and 2U) Dimensions: H88x W122 x D375mm (3.5 x 4.2 x 14.75) Weight: 4kg (9lbs) AGENCY COMPLIANCE CE Marked: Low Voltage Directive only standards Electrical safety: IEC 60950-1, UL 60950-1 EMI (conducted): FCC Part 15, Sub-part J, class A and EN55022, class A EMI (radiated): Stand alone module tested to EN55022 Class B. Harmonics: EN 61000-3-2 EN 61000-6-1 (Immunity, light industry) EN 61000-6-2 (Immunity, industry) EN 61000-6-3 (Emissions, light industry) EN 61000-6-4 (Emissions, industry) RoHS compliant Notes: Designed for use with Mercury shelf or custom Backplane Options: Silicone RTV encapsulate Contact Factory for Options and full Product Specification

ORDERING INFORMATION
Part no. 142151-N54D00 Description 3800W, 54Vdc, Droop CS, standard alarms

www.tdipower.com
Copyright 2007, Transistor Devices, Inc.

Energy Solutions for the Next Generation

This document is believed to be correct at time of publication and Transistor Devices, Inc. accepts no responsibility for consequences from printing errors or inaccuracies. Specifications are subject to change without notice.

4,300 W Technical Specifications


AC INPUT Voltage: 176275VAC Over-voltage tested to 325Vac Frequency: 47-63Hz Peak Inrush Current: <50A Power Factor: 0.99 typical Efficiency: ~93% with 230VAC source, 50 to 100% load Hold-Up Time: 10mS min. Input Overcurrent: (internal) 25 A Fuse DC OUTPUT Primary Voltage: +24V, +27V, -48V, -54.5V. Custom outputs available, consult Factory Power: 4,300W, -20 to +55C, 176-275Vac 3,500W, -20 to +75C, 176-275Vac 1,900W, -20 to +55C, 90-275Vac 810W, -20 to +75C, 90-275Vac Auxiliary output: 12V/ 0.1A Accuracy: 50mV Ripple & Noise: 1% V P-P Measured with 20Mhz Bandwidth Line Regulation: Less than 0.25% Load Regulation: 1.0% from no load to full load (droop load share) Parallel Use: May be paralleled with other like units for increased system output, redundant diode included Current Sharing: Slope program current share, (droop) Temperature Coefficient: < 0.02% perC Acoustic Noise < 67dBA at nominal input and full load ELECTRONIC ALARMS (Basic Set, others available) AC OK: low when AC input is in range Output OK: low if the output voltage is within 10% of the actual voltage set point (low=<.6V@1mA) (high=open collector (I<50A) CAN Bus: available option VISUAL FAULT INDICATORS Output OK: A front panel Green Output OK LED will be lit if the units output is within the acceptable range. ELECTRONIC CONTROL INPUTS Remote Inhibit: Application of a TTL input signal will cause the supply to shut down and an output OK fault alarm will be issued. (TTL High = Inhibit) Remote Program: Provides +9%, -27% of set point voltage with 0 to 5V control signal TEMPERATURE Normal Operation: -20 to +75C High Temperature Operation: See Notes in DC Output Section Low Temperature Turn On: -40C Minimum Storage / Transportation: -40C to +85C Humidity Operating: 5% to 95% RH non-condensing Storage: 0% to 99% RH non-condensing PHYSICAL DIMENSIONS Packaging (both available in 1U and 2U) Dimensions: H88x W122 x D375mm (3.5 x 4.2 x 14.75) Weight: 4kg (9lbs) AGENCY COMPLIANCE CE Marked: Low Voltage Directive only standards Electrical safety: IEC 60950-1, UL 60950-1 EMI (conducted): FCC Part 15, Sub-part J, class A and EN55022, class A EMI (radiated): Stand alone module tested to EN55022 Class B. Harmonics: EN 61000-3-2 EN 61000-6-1 (Immunity, light industry) EN 61000-6-2 (Immunity, industry) EN 61000-6-3 (Emissions, light industry) EN 61000-6-4 (Emissions, industry) RoHS compliant Notes: Designed for use with Mercury shelf or custom Backplane Options: Variable Speed Fan Silicone RTV encapsulate Contact Factory for Options and full Product Specification

ORDERING INFORMATION
Part no. 143592-N54D00 143592-P27D00 Description 4,300W, 54Vdc, Droop CS, standard alarms 4,300W, 27Vdc, Droop CS, standard alarms

www.tdipower.com
Copyright 2007, Transistor Devices, Inc.

Energy Solutions for the Next Generation

This document is believed to be correct at time of publication and Transistor Devices, Inc. accepts no responsibility for consequences from printing errors or inaccuracies. Specifications are subject to change without notice.

Technical Specifications: CS1, 139239-P27D01, 2700W module


AC INPUT Voltage: 176275VAC Over-voltage tested to 325Vac Frequency: 47-63Hz Peak Inrush Current: <20A Power Factor: 0.99 typical Efficiency: ~93% with 230VAC source, 50 to 100% load Hold-Up Time: 10mS min. Input Overcurrent: (internal) 25 A Fuse DC OUTPUT Voltage: 29.1Vdc Power: 2,700W Accuracy: 50mV Ripple & Noise: 1% V P-P Measured with 20Mhz Bandwidth Line Regulation: Less than 0.25% Load Regulation: 1.0% from no load to full load (droop load share) Parallel Use: May be paralleled with other like units for increased system output, redundant diode included Current Sharing: Slope program current share, (droop) Temperature Coefficient: < 0.02% perC Acoustic Noise < 65dBA at nominal input and full load ELECTRONIC ALARMS (Basic Set, others available) AC OK: low when AC input is in range Output OK: low if the output voltage is within 10% of the actual voltage set point (low=<.6V@1mA) (high=open collector (I<50A) CAN Bus: available option VISUAL FAULT INDICATORS Output OK: A front panel Green Output OK LED will be lit if the units output is within the acceptable range. ELECTRONIC CONTROL INPUTS Remote Inhibit: Application of a TTL input signal will cause the supply to shut down and an output OK fault alarm will be issued. (TTL High = Inhibit) Remote Program: Provides +9%, -27% of set point voltage with 0 to 5V control signal TEMPERATURE Normal Operation: -20 to +55C High Temperature Operation: derate 10% perC, 55 to 65C Low Temperature Turn On: -40C Minimum Storage / Transportation: -40C to +85C Humidity Operating: 5% to 95% RH non-condensing Storage: 0% to 99% RH non-condensing PHYSICAL DIMENSIONS Packaging (both available in 1U and 2U) Dimensions: H88x W122 x D375mm (3.5 x 4.2 x 14.75) Weight: 4kg (9lbs) Note: units are Silicone RTV encapsulated to suit harsh environment AGENCY COMPLIANCE CE Marked: Low Voltage Directive only standards Electrical safety: IEC 60950-1, UL 60950-1 EMI (conducted): FCC Part 15, Sub-part J, class A and EN55022, class A EMI (radiated): Stand alone module tested to EN55022 Class B. Harmonics: EN 61000-3-2 EN 61000-6-1 (Immunity, light industry) EN 61000-6-2 (Immunity, industry) EN 61000-6-3 (Emissions, light industry) EN 61000-6-4 (Emissions, industry) RoHS compliant Notes: Designed for use with Mercury shelf or custom Backplane Options: Varible speed fan Contact Factory for Options and full Product Specification

ORDERING INFORMATION
Part no. 139239-P27D01 Description 2,700W, 29.1Vdc, Droop CS, standard alarms, Silicone RTV encapsulate

www.tdipower.com
Copyright 2007, Transistor Devices, Inc.

Energy Solutions for the Next Generation

This document is believed to be correct at time of publication and Transistor Devices, Inc. accepts no responsibility for consequences from printing errors or inaccuracies. Specifications are subject to change without notice.

Technical Specifications: Mercury Shelf 1U and 2U


AGENCY COMPLIANCE CE Marked: Low Voltage Directive only standards Electrical safety: IEC 60950-1, UL 60950-1 RoHS compliant Contact Factory for Options and full Product Specification

19" 1U and 2U shelf varients


Shelf size 1U 1U 1U 1U 1U 1U 2U 2U 2U 2U 2U 2U 2U 2U 2U 3U 2U Connector AC input con- Input Connection Type nectors 15A IEC x2 15A IEC x2 20A Terminal blocks x2 20A Terminal blocks x2 20A Terminal blocks x2 20A Terminal blocks x2 15A IEC x4 20A Terminal blocks x4 20A Terminal blocks x4 Termianl block TTL alarms TTL & shelf summary alarms TTL alarms TTL & shelf summary alarms TTL alarms TTL & shelf summary alarms TTL alarms TTL alarms TTL alarms (1) 85A & (2) 65A Term.Blocks, 19" wide, No alarms 20A IEC inlets, 19" wide, No alarms Model Number Part Number Output Terminations

50A 50A 50A 50A 100A 100A 50A 50A 100A 50A 50A 50A 50A 50A 50A 50A Bus-Bar

MeS050A-60AAB00 MeS050A-60AAC00 MeS050A-60BAB00 MeS050A-60BAC00 MeS100A-60BAB00 MeS100A-60BAC00 MeS050B-60AAB00 MeS050B-60BAB00 MeS100B-60BAB00 MeS050B-60GAA01 MeS050B-60EAA00

139619-60AAB00 139619-60AAC00 139619-60BAB00 139619-60BAC00 140598-60BAB00 140598-60BAC00 139621-60AAB00 139621-60BAB00 139623-60BAB00 139621-60GAA01 139621-60EAA00 139621-60EAB00 139621-60GAB01 139621-60HAB01

TDI Dual Anti-rotational TDI Dual Anti-rotational TDI Dual Anti-rotational TDI Dual Anti-rotational TDI Dual Anti-rotational TDI Dual Anti-rotational TDI Dual Anti-rotational TDI Dual Anti-rotational TDI Dual Anti-rotational TDI Dual Anti-rotational Bus-Bar Bus-Bar Bus-Bar Bus-Bar

Three-phase connector Terminal block DC input

20A IEC inlets, 19" wide, TTL alarms MeS050B-60EAB00 (1) 85A Terminal Block, 19" wide, TTL alarms MeS050B-60GAB01 (2) 65A Terminal Blocks, 19" wide, TTL alarms MeS050B-60HAB01 1 custom connector, 19" wide, Alarms provided with -1 SPS5728, SPS5728-1 5600W, High line input, positive 27V output, 45A connector, 15"deep MeS056HIC-P27CAF01 DC Shelf: 50A rectifier connectors, DC busbars, TTL alarms MeS050B-60DAB00

141110, 141110-1 Bus-Bar 138681-P27CAF01 TDI Dual Anti-rotational 137524-60DAB00 TDI Dual Anti-rotational

1. All shelves use 25way Header for alarms and control interface with shelf

www.tdipower.com
Copyright 2007, Transistor Devices, Inc.

Energy Solutions for the Next Generation

This document is believed to be correct at time of publication and Transistor Devices, Inc. accepts no responsibility for consequences from printing errors or inaccuracies. Specifications are subject to change without notice.

Technical Specifications: Mercury Shelf 1U and 2U

www.tdipower.com
Copyright 2007, Transistor Devices, Inc.

Energy Solutions for the Next Generation

This document is believed to be correct at time of publication and Transistor Devices, Inc. accepts no responsibility for consequences from printing errors or inaccuracies. Specifications are subject to change without notice.

Design options
A. B. C. D. E. Variable Speed Fan option: Adjusts the fan speed based on ambient air temperature and PS load. UL Listing compliant front panel with gender insert (Black color only) Silicone RTV encapsulate Reversed alarm/control logic, to meet application requirements the polarity of standard alarm & control logic may be reversed (contact Factory for further details) CAN bus alarms

Notes: 1. Contact Factory for further details on the application of the Options and the available of custom versions 2. Full Product Specifications available on request.

Application Manual
The latest application manual for the Mercury and other products may be down-loaded from the TDI web-site products section. Alternatively please contact our applications engineers for application support and further documentation.

Design and Manufacturing


TDI Mercury modules are designed in TDIs North American Design labs and manufactured within our own manufacturing facilities in China and North & South America. To ensure consistency, TDI employs a global BOM and test equipment plus TDIs unique HASS process to assure manufacturing product quality. TDI maintains an industry leading customer satisfaction for out of box quality and product reliability. We are the industry leaders in proven high reliability commercial grade Power products.

RoHS Compliance
Lead Exempt: All variants (power range) are available with Lead-free components assembled using Lead/Tin Solder process. Lead- Free: RoHS Lead free units are available, Consult Factory for full details

Global Contact Information


Asia, Australia, New Zealand: T: +86 755 668 3376 F: +86 755 668 8797 EMEA: T: +353 21 4214573 F: +353 21 4214574 North / South America & Canada: T: +1 908 850 5088 F: +1 908 850 1607 ABOUT TDI TDI designs and manufactures power solutions ranging from individual power supplies to system-level installed power for telecommunications, computer, industrial, military, airborne, marine and outdoor applications. Strategically located in nine global facilities, TDI products include: AC-DC Power Supplies, DC-DC Converters, N+1 Redundant Power Systems, Rectifiers and Battery Plants, DC-AC Inverters, AC-AC Frequency Changers, Electronic Loads and Value-Added Cabinets.

www.tdipower.com
Copyright 2007, Transistor Devices, Inc.

Datasheet No.: 100260 V2 Issue: 072307

Energy Solutions for the Next Generation

This document is believed to be correct at time of publication and Transistor Devices, Inc. accepts no responsibility for consequences from printing errors or inaccuracies. Specifications are subject to change without notice.