HazardWatch Integrated Fire and Gas Alarm System Supplement

The information and technical data disclosed in this document may be used and disseminated only for the purposes and to the extent specifically authorized in writing by General Monitors. Instruction Manual 11-05 General Monitors reserves the right to change published specifications and designs without prior notice. MANTS4000 Part No. Revision MANHAZARDWATCH 1/09-05

HazardWatch

This page intentionally left blank

ii

HazardWatch

Table of Contents
1.0 HAZARDWATCH SPECIFICATIONS AND DATA SHEETS ................................................. 6
1.1 Local Panel Equipment ..............................................................................................................6 1.1.1 PLC Equipment .............................................................................................................6 1.1.2 Local HMI ....................................................................................................................12 1.1.3 Communication Modules ............................................................................................14 1.1.3.1 Controlnet Module..........................................................................................14 1.1.3.2 Ethernet Module.............................................................................................15 1.1.3.3 Modbus Module..............................................................................................15 1.1.4 Fiber Optic Communication Module............................................................................16 1.1.5 DC to DC Converter ....................................................................................................16 1.1.6 DC Power Supply and Batteries .................................................................................17 1.1.7 Current Shunt and MV Transmitter .............................................................................20 1.1.8 Battery Disconnect Switch and Polarized Connectors................................................22 Coaxial Cable...........................................................................................................................24 Fiber Optic Cable .....................................................................................................................24 Central Station Equipment .......................................................................................................24 1.4.1 UL 864 Computer Station ...........................................................................................24 1.4.2 Central Station UPS ....................................................................................................25 1.4.3 Central Station Fiber Optic Converter.........................................................................27 1.4.4 Central Station Printer.................................................................................................27 GMI Field Devices....................................................................................................................28 1.5.1 GM S4000C Combustible Gas Detector .....................................................................28 1.5.2 GM S4000T H2S Gas Detector ..................................................................................30 1.5.3 GM IR2100/IRFMD IR Gas Detector ..........................................................................31 1.5.4 GM IR 5000 Open Path Gas Detector ........................................................................34 1.5.5 GM FL3100/3101UV/IR Flame Detector.....................................................................35 1.5.6 GM FL3102 DFIR Flame Detector ..............................................................................37 Smoke and Thermal Fire Detection Equipment.......................................................................38 1.6.1 Pyrotronics DI-3 Ionization Type Smoke Detector......................................................38 1.6.2 Pyrotronics PE-11 Photoelectric Type Smoke Detector .............................................39 1.6.3 Pyrotronics DT-11 Thermal Detector ..........................................................................40 1.6.4 Kidde Fenwal Detect-a-fire Thermal Detector ............................................................41 1.6.5 Apollo Series 60 Ionization Type Smoke Detector .....................................................42 1.6.6 Apollo Series 60 Photoelectric Type Smoke Detector ................................................44 Audible Devices .......................................................................................................................46 1.7.1 Federal Signal Model 50 GC Selectone Horn.............................................................46 1.7.2 Federal Signal Model 300 GCX Selectone Horn ........................................................46 1.7.3 Federal Signal Model 300X & 302X Selectone Horn..................................................47 1.7.4 Federal Signal Model 41-X Selectone Horn ...............................................................48 1.7.5 MEDC XB3 Horn .........................................................................................................49 1.7.6 Notifier Spectralert Horn .............................................................................................54 1.7.7 Notifier Spectralert Horn .............................................................................................54 1.7.8 Crouse Hinds ESR Fire Alarm Bell .............................................................................54 1.7.9 Pyrotronics MBDC-6 Fire Alarm Bell...........................................................................57 Visual Devices..........................................................................................................................58 1.8.1 Federal Signal Model 191 X Strobe Light ...................................................................58 1.8.2 Federal Signal Model 151 XST Strobe Light ..............................................................58 1.8.3 Federal Signal Model 27XST Strobe Light .................................................................59 iii

1.2 1.3 1.4

1.5

1.6

1.7

1.8

HazardWatch

1.8.4 1.8.5 1.8.6 1.8.7

Federal Signal Model 121 X Rotating Light ................................................................60 MEDC XB-3 Strobe Light ............................................................................................62 MEDC XB-11 Strobe Light ..........................................................................................65 Notifier Spectralert Strobe...........................................................................................67

iv

HazardWatch

HazardWatch

1.0 HazardWatch Sheets


1.1.1 PLC Equipment

Specifications

and

Data

1.1 Local Panel Equipment

ControlLogix Controller Specifications - 1784-CF64 Industrial CompactFlash Card Specifications: User Available Memory: Nonvolatile Memory: Weight: Operating Temperature: 64M bytes Yes 14.2 g (0.5 oz) IEC 60068-2-1 (Test Ad, Operating Cold) IEC 60068-2-2 (Test Bd, Operating Dry Heat) IEC 60068-2-14 (Test Nb, Operating Thermal Shock) 0 60C (32 140F) IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold) IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat) IEC 60068-2-14 (Test Na, Un-packaged Nonoperating Thermal Shock) -40 85C (-40 185F) IEC 60068-2-30 (Test Db, Un-packaged Nonoperating Damp Heat): 5% 95% non-condensing IEC60068-2-6 (Test Fc, Operating): 2g @ 10-500Hz IEC60068-2-27 (Test Ea, Unpackaged Shock): 30g IEC60068-2-27 (Test Ea, Unpackaged Shock): 50g CISPR 11: Group 1, Class A IEC 61000-4-2: 6kV contact discharges 8kV air discharges IEC 61000-4-3: 10V/m with 1kHz sine-wave 80%AM from 30MHz 2000MHz 10V/m with 200Hz 50% Pulse 100%AM at 900Mhz 10V/m with 200Hz 50% Pulse 100%AM at 1890Mhz IEC 61000-4-4: 4kV at 5kHz on power ports 4kV at 5kHz on communications ports IEC 61000-4-5: 1kV line-line (DM) and 2kV line-earth (CM) on AC power ports 6

Storage Temperature:

Relative Humidity: Vibration: Operating Shock: Non-Operating Shock: Emissions: ESD Immunity: Radiated RF Immunity:

EFT/B immunity: Surge Transient Immunity:

HazardWatch

2kV line-earth (CM) on communications ports IEC 61000-4-6: 10Vrms with 1kHz sine-wave 80%AM from 150kHz 80MHz Enclosure Type Rating: None (open-style) Isolation Voltage: 30V Series A controllers: Tested to withstand 500V ac for 60 seconds Series B controllers: Tested to withstand 720V dc for 60 seconds Wiring Category*: Category 3 on communication ports Programming Cable: For 1756- CP3 or 1747-CP3 serial cable * Use this Conductor Category information for planning conductor routing. Refer to Publication 1770-4.1, Industrial Automation Wiring and Grounding Guidelines Conducted RF Immunity: Replacement Battery For this component: 1756-L1, 1756-L1M1, 1756-L1M2, 1756-L1M3 1756-L55, 1756-L55M12,1756L55M13, 1756-L55M14, 1756L55M16, 1756-L55M22, 1756L55M23, 1756-L55M24 1756-L61/A, 1756-L62/A, 1756-L63/A 1756-L61/B, 1756-L62/B, 1756-L63/B Use this battery: 1756-BA1 (0.59g lithium) 1756-BA1 (0.59g lithium)

1756-BA1 (0.59g lithium) 1756-BA2 (0.50g lithium)

Certifications: When marked, the components have the following certifications. See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and other certification details. Catalog Number 1756-L1 Certificate Description UL UL Listed Industrial Control Equipment CSA CSA Certified Process Control Equipment CSA CSA Certified Process Control Equipment for Class I, Division 2 Group A, B, C, D Hazardous Locations CE European Union 89/336/EEC EMC Directive, compliant with: EN 50082-2; Industrial Immunity EN 61326; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions C-Tick Australian Radio communications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions EEX European Union 94/9/EC ATEX Directive, compliant with: EN 50021; Potentially Explosive Atmospheres, Protection "n" (Zone 2)

HazardWatch

ControlLogix Controllers Specifications: Catalog Number: Memory Data and Logic: U/0**: Nonvolatile Memory Backplane @ 5.1V dc: @ 24V dc: Power Dissipation: Thermal Dissipation: Weight: 1.20A 14mA 3.5 11.9 BTU/hr 0.35 kg (12.4 oz) 2M bytes 478K bytes Yes*** 1756-L61/B

*Data and logic memory stores: tags other than I/0, produced, or consumed tags; logic routines; and communication with OPC/DDE tags that use RSLinx software (also uses I/O memory) **I/O memory stores: I/O tags, produced tags, consumed tags, communication via Message (MSG) instructions, communication with workstations, and communication with OPC/DDE tags that use RSLinx software (also uses data and logic memory). ***Requires a 1784-CF64 Industrial CompactFlash card. 1756-OB16D Specifications: Number of Outputs: Module Location: Backplane Current: Max. Power Dissipation (Module): Thermal Dissipation: Output Voltage Range: Output Current Rating Per Point: Per Module: Surge Current per Point: Minimum Load Current: Maximum On-State Voltage Drop: Max. Off-State Leakage Current: Output Delay Time OFF to ON: ON to OFF: Diagnostic Functions: Short trip: No load: Output verification: Pulse test: 8 16 (8 points/common) 1756 ControlLogix Chassis 250mA @ 5.1V dc & 140mA @ 24V dc (Total backplane power 4.64W) 3.3W @ 60oC 11.25 BTU/hr 19.2-30V dc 2A max. @ 30C & 1A max. @ 60C (Linear derating) 8A max. @ 30C & 4A max. @ 60C (Linear derating) 4A for 10ms each, repeatable every 1s 3mA per point 1.2V dc @ 2A 1mA per point 1ms maximum 5ms maximum
8A 180ms minimum 10A 120ms minimum OFF STATE detection only ON STATE detection only User selectable maximum pulse width

HazardWatch

Time stamp of diagnostics: Configurable Fault States/Point: Configurable States in Program: Mode/Point Scheduled Outputs: Fusing: Reverse Polarity Protection: Isolation Voltage Group to group: User to system: RTB Screw Torque (Cage clamp): Module Keying (Backplane): RTB Keying: RTB and Housing: Environmental Conditions Operating Temperature: Storage Temperature: Relative Humidity: Conductors Wire Size:

+/- 1ms Hold Last State, ON or OFF (OFF is the default) Hold Last State, ON or OFF (OFF is the default) Synchronization within 16.7s maximum, reference to the Coordinated System Time Electronically fused per point None - If module is wired incorrectly, outputs may be damaged. 100% tested at 2546V dc for 1s (250V ac max. continuous voltage between groups) 100% tested at 2546V dc for 1s 4.4 inch-pounds (0.4Nm) maximum Software configurable User defined mechanical keying 36 Position RTB (1756-TBCH or TBS6H)1

0 to 60C (32 to 140F) -40 to 85C (-40 to 185F) 5 to 95% non-condensing 2-14-gauge (2mm2) stranded 1 3/64 inch (1.2mm) insulation maximum Category: 12, 3 Screwdriver Blade Width for RTB: 1/8 inch (3.2mm) maximum Agency Certification: UL -Listed Industrial Control Equipment (When product or packaging is marked) CSA - Approved Class I, Division 2, Group A, B, C, D FM - Approved Class I, Division 2, Group A, B, C, D CE - Marked for all applicable directives Maximum wire size will require extended housing - 1756-TBE. Use this conductor category information for planning conductor routing as described in the system level installation manual. Refer to publication 1770-4.1 Industrial Automation Wiring and Grounding Guidelines. NOTE: The ControlLogix system must be mounted within a suitable enclosure to prevent personal injury resulting from accessibility to live parts. The interior of this enclosure must be accessible only by the use of a tool. 1756-IB32, Input Module Specifications: Number of Inputs: Module Location: Backplane Current: Maximum Power Dissipation (Module): 9 4.5W @ 60oC 32 (16 points/common) 1756 ControlLogix Chassis 150mA @ 5.1V dc & 2mA @ 24V dc (Total backplane power 0.81W)

HazardWatch

Thermal Dissipation: On-State Voltage Range: Nominal Input Voltage: ON-State Current @ 10V dc: @ 31.2V dc: Maximum Off-State Voltage: Maximum Off-State Current: Maximum Input Impedance @ 31.2V dc: Input Delay Time OFF to ON: Hardware delay: ON to OFF: Hardware delay: Diagnostic Functions Change of state: Time stamp on inputs: Short/Inrush Current: Cyclic Update Time: Reverse Polarity Protection: Isolation Voltage Group to group: User to system: RTB Screw Torque (Cage clamp): Module Keying (Backplane): RTB Keying: Field Wiring Arm and Housing: Environmental Conditions Operating Temperature:

16.37 BTU/hr @ 60oC 10-31.2V dc 24V dc 2.mA 5.5mA 5V dc 1.5mA 5.67k Programmable filter:0ms, 1ms or 2ms 1ms maximum plus filter time Programmable filter: 0ms, 1ms, 2ms, 9ms or 18ms 2ms maximum plus filter time Software configurable +/- 200s 250mA peak (decaying to <37% in 22ms, without activation) User selectable (100_s minimum/750ms maximum) Yes 250V maximum continuous/100% tested at 2546V dc for 1s 250V maximum continuous/100% tested at 2546V dc for 1s 4.4 inch-pounds (0.4Nm) maximum Software configurable User defined mechanical keying 36 Position RTB (1756-TBCH or TBS6H)(1) IEC 60068-2-1 (Test Ad, Operating Cold) IEC 60068-2-2 (Test Bd, Operating Dry Heat) IEC 60068-2-14 (Test Nb, Operating Thermal Shock) 0 to 60C (32 to 140F) IEC 60068-2-1 (Test Ab, Un-packaged Nonoperating Cold) IEC 60068-2-2 (Test Bb, Un-packaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Un-packaged Nonoperating Thermal Shock): 40 to 85C (40 to 185F) IEC 60068-2-30 (Test Db, Un-packaged Nonoperating Damp Heat): 5 to 95% non-condensing IEC60068-2-6 (Test Fc, Operating): 10

Storage Temperature:

Relative Humidity: Vibration:

HazardWatch

2g @ 10-500Hz IEC60068-2-27 (Test Ea Unpackaged shock): 30g 50g CISPR 11: Group 1, Class A IEC 61000-4-2: 6kV contact discharges 8kV air discharges Radiated RF Immunity: IEC 61000-4-3: 10V/m with 1kHz sine-wave 80%AM from 30MHz to 1000MHz 10V/m with 200Hz 50% Pulse 100%AM at 900Mhz EFT/B Immunity: IEC 61000-4-4: 4kV at 2.5kHz on power ports 4kV at 2.5kHz on signal ports Surge Transient Immunity: IEC 61000-4-5: 1kV line-line (DM) and 2kV line-earth (CM) on power ports 1kV line-line (DM) and 2kV line-earth (CM) on signal ports Conducted RF Immunity: IEC 61000-4-6: 10Vrms with 1kHz sine-wave 80%AM from 150kHz to 80MHz Enclosure Type Rating: None (open-style) Conductors - Wire Size: #22 to #14 AWG (0.324 to 2.08 sq. mm) stranded1 3/64 inch (1.2mm) insulation maximum Category: 12, 3 Screwdriver Blade Width for RTB: 1/8 inch (3.2mm) maximum Certifications: UL -UL Listed Industrial Control Equipment (When product is marked) CSA -CSA Certified Process Control Equipment CSA -CSA Certified Process Control Equipment for Class I, Division 2 Group A, B, C, D Hazardous Locations FM- FM Approved Equipment for use in Class I Division 2 Group A, B, C, D Hazardous Locations CE4 -European Union 89/336/EEC EMC Directive, compliant with: EN 50082-2; Industrial Immunity EN 61326; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions C-Tick4 Australian Radio communications Act, compliant with: AS/NZS 2064; Industrial Emissions EEx4 European Union 94/9/EEC ATEX Directive, compliant with: EN 50021; Potentially Explosive Atmospheres, Protection n 1. Maximum wire size will require extended housing - 1756-TBE. Shock: Operating: Non-operating: Emissions: ESD Immunity: 2. Use this conductor category information for planning conductor routing as described in the 11

HazardWatch

system level installation manual. 3. Refer to publication 1770-4.1 Industrial Automation Wiring and Grounding Guidelines. 4. See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and other certification details. ControlLogix ControlNet Bridge 1756-CNBR Specifications:
ControlNet Interface

Connectors: Cable: Ground isolation: Electrical Power dissipation: Thermal dissipation: Backplane current: Environmental Operational temperature: Storage temperature: Relative humidity: Physical Location: Weigh: Agency Certification (When product or packaging is marked)

2 BNC connectors for redundant media operation 1 NAP (RJ-45 8-pin with shield) Quad shield RG-6 coaxial cable Transformer 5.14 W 17.5 BTU/hr
1.0 A @ 5.1 V

1.7 mA @ 24 V 0 to 60C (32 to 140F) 40 to 85C (40 to 185F) 5 to 95% (without condensation) Any slot in a 1756 chassis 0.260 kg (0.57 lb.) 0.293 kg (0.64 lb.) UL -Listed Industrial Control Equipment CSA -Approved Class I, Division 2, Group A, B, C, D FM - Approved Class I, Division 2, Group A, B, C, D CE -Marked for all applicable directives

1.1.2 Local HMI


PanelView Plus 1000 Specifications: Display Size: Type: Resolution: Input Method: Communication Options Flash Memory: RAM: I/O and Slots: Input Voltage: 12 Standard: 32 MB; extended: 128 MB Standard: 64 MB; extended: 128 MB 1 serial port, 2 USB ports, 1 10/100 Mbps Ethernet port, 1 Compact Flash memory card slot DC: 18-32V dc 10.4 in Color active matrix thin film transistor (TFT) 640 x 480, 24 bit color Keypad, touch, or combination keypad/touch

HazardWatch

Operating Temperature Storage Temperature: Humidity: Vibration Operating Non Operating: Shock Operating/ Non-Operating: Ratings: Certifications: Mechanical Weight: Dimensions Overall (H x W x D): Touch only: 248 x 329 x 55 mm (9.77 x 12.97 x 2.17 in) Keypad or Keypad/Touch: 248 x 399 x 55 mm (9.77 x 15.72 x 2.17 in) Touch only: 224 x 305 mm (8.8 x 12 in) Keypad or Keypad/Touch: 224 x 375 mm (8.8 x 14.75 in) Touch: 2.6 kg (5.7 lb.) 2.9 kg (6.3 lb.) 15g/30g NEMA Type 12, 13, 4X*, IP54, IP65 UL, C-UL approved; Class 1/2/3 - Div 2 Groups A, B, C, D; CE marked 0.012 in pp, 1057 Hz, 2g peak, 57500 Hz 25...70C (13...158F) 5...95%, non-condensing @ 0...55C

Cutout Dimensions

PanelView Plus Specifications: Display Size: Type: Resolution: Input Method: Communication Options: Flash Memory: RAM: I/O and Slots: Input Voltage: Operating Temperature: Storage Temperature: Humidity: Vibration Operating and Non-Operating: Shock Operating and Non-Operating PanelView Plus 1000 10.4 in Color active matrix thin film transistor (TFT) 640 x 480, 24 bit color Keypad, touch, or combination keypad touch ControlNet, DH+, Remote I/O, DH485, DF1 Ethernet/IP, and user configurable non-RA networks Standard: 32 MB; extended: 128 MB Standard: 64 MB; extended: 128 MB 1 serial port, 2 USB ports, 1 10/100 Mbps Ethernet port, 1 Compact Flash memory card slot DC: 18-32V dc 0...55C (32...131F) -25...70C (-13...158F) 5...95%, non-condensing @ 0...55C 0.012 in p-p, 1057 Hz, 2g peak, 57500 Hz

15g/30g

13

HazardWatch

Ratings: Certifications: Mechanical Weight Dimensions

Overall (H x W x D)

Cutout Dimensions

NEMA Type 12, 13, 4X*, IP54, IP65 UL, C-UL approved; Class 1/2/3 Touch: 2.6 kg (5.7 lb.) Keypad or Keypad/Touch: 2.9 kg (6.3 lb.) Touch only: 248 x 329 x 55 mm (9.77 x 12.97 x 2.17 in) Keypad or Keypad/Touch: 248 x 399 x 55 mm (9.77 x 15.72 x 2.17 in) Touch only: 224 x 305 mm (8.8 x 12 in) Keypad or Keypad/Touch: 224 x 375 mm (8.8 x 14.75 in)

1.1.3 Communication Modules


1.1.3.1 Controlnet Module
Module 1756-CNBR Specifications: ControlNet Interface connectors Cable Ground isolation Electrical Power dissipation Thermal dissipation Backplane current Environmental Operational temperature Storage temperature Relative humidity Physical Location: Weight: Agency Certification (When product or packaging is marked) Any slot in a 1756 chassis 0.293 kg (0.64 lb.) Listed Industrial Control Equipment Certified Process Control Equipment Certified Class I, Division 2, Group A, B, C, D Marked for all applicable directives Marked for all applicable acts Approved class I, Division 2, Group A, B, C, D 0 to 60C (32 to 140F) 40 to 85C (40 to 185F) 5 to 95% (without condensation) 5.14 W 17.5 BTU/hr 1.0 A @ 5.1 V 1.7 mA @ 24 V V 2 BNC connectors for redundant media operation 1 NAP (RJ-45 8-pin with shield) Quad shield RG-6 coaxial cable Transformer

14

HazardWatch

1.1.3.2 Ethernet Module


Specifications: Module Location: Maximum Backplane Current Load: Power Dissipation: Shock (Unpackaged) Vibration (Unpackaged) Conductors Wiring Category Ethernet Connector User Manual Publication Agency Certifications When product is marked Industrial Control Equipment Any slot in the ControlLogix chassis 700mA @ 5.1V DC 3mA @ 24V DC from I/O chassis backplane 3.65W maximum 30g operational 50g non-operational 5g from 10 to 150 Hz 802.3 compliant - twisted pair 2(1) RJ45 Category 5 1756-UM050 Certified Process Control Equipment Certified Class I, Division 2, Groups A, B, C, D Marked for all applicable directives Marked for all applicable acts Approved Class I, Division 2, Groups A,B,C,D N223 0 to 60 C (32 to 140 F) -40 to 85 C (-40 to 185 F) 5 to 95%, non-condensing

Listed

Environmental Operating Temperature Storage Temperature Relative Humidity

1.1.3.3 Modbus Module


Modbus Master/Slave Communications Interface Module MVI56-MCM Specifications: Local or Remote Rack Backplane Current Load: Operating Temperature: Storage Temperature: Shock: Vibration: Relative Humidity: LED Indicators: 800 mA @ 5 V 0 to 60 Deg C (32 to 140 Deg F) -40 to 85 Deg C (-40 to 185 Deg F) 30g Operational 50g non-operational 5 g from 10 - 150 Hz 5-95% (w/o condensation) Module Status Backplane Transfer Status Application Status Serial Activity and Error LED Status DB-9M PC Compatible RS-232 only Hardware handshaking 15

Configuration Serial Port (PRT1):

HazardWatch

Application PRT2):

Serial

ports

(PRT1,

RJ45 (RJ45 to DB-9M PC Compatible connector is supplied) RS232/422/485 jumper selectable RS232 handshaking configurable 500V Optical isolation from backplane

1.1.4 Fiber Optic Communication Module


PheonixDigital Specifications: Fiber Optic Cable Type: Mating Connector: Transmit Launch Power: Receive Sensitivity: Power Supply Plug-In Modules: Standalone Panelmount Modules: Environmental Operating Temperature: Storage Temperature: Relative Humidity: Dimensions 1771 Plug-In Modules: 1746 Plug-In Modules: 1756 Plug-In Modules: Standalone, Panelmount: Modules: Single Slot, 1771 Chassis Installation Single Slot, 1746 Chassis Installation Single Slot, 1756 Chassis Installation 10.38 H x 1.76 W* x 6.14 D (26.36cm H x 4.47cm W* x 15.60cm D * Add 1.00 (2.54cm) for rear panel flange 0 to 60 C (32 to 140 F) -40 to 85 C (-40 to 185 F) 0 to 95% RH, non-condensing +5 VDC, 1.8 Amps (Typical 120/220 VAC, 24 VDC, or 125 VDC.... 10 Watts Multimode or Singlemode ST or SMA 15dbm (Typical, Multimode); -18dbm (Singlemode) -32dbm

1.1.5 DC to DC Converter
Cosel Power Module CBS100 Specifications: Isolation Input Input Output DC1, 500V, or AC1, 000V 1 minute, Cutoff current = 10 mA, DC500V 50 ML2 min (2015C) Case Pin, Base Plate DC1, 500V, or AC1, 000V 1 minute, Cutoff current = 10 mA, DC500V 50 ML2 min (2015C) Case Pin, Base Plate AC500V 1minute, Cutoff current 10mA, DC500V 50 ML2 min (2015C)

Output

Environment Operating Temp. Humid and Altitude 16 -40 to 100C (On aluminum base plate), 20 95% RH (Non condensing) (Refer to DERATING

HazardWatch

CURVE), 3,000m (10,000 feet) max Storage Temp, Humid and Altitude Vibration Impact -40 to 100C, 20 95% RH (Non condensing), 9,000m (30,000 feet) max 10-55 Hz, 49.0m/s2 (5G), 3 minutes period, 60 minutes each along X, Y, and Z axis 196.1 m/s2 (20G), 11ms, once each along X, Y, and Z axis

Safety Agency Approvals Others Case Size/Weight Cooling Method 57.9 x 12.7X 61.0mm (WX HXD)/83g max Conduction cooling (e.g. heat radiation from the aluminum base plate to the attached heat sink) UL60950, C-UL, EN60950

1.1.6 DC Power Supply and Batteries


LaMarche Power Supply /Battery Charger Specifications: Electrical AC Input Voltages: Single Phase 60Hz: 120,208,240,480 or 575 Single Phase 50Hz: 220/240,380 or 415 Three Phase 60Hz: 208,240,480 or 575 Three Phase 50Hz: 220/240,380 or 415 DC Fuse, DC Voltage Regulation and Current Limit Protection DC Amps: 3 to 400 amperes DC Volts: 12, 24, 48 & 130VDC (Others available such as 32 & 36VDC) 30mV RMS for single phase models and 100mV RMS for three-phase models when connected to a battery with an ampere-hour capacity of four times the output current capacity of the charger. Plus or minus 0.5% of setting from no load to full load over the specified input voltage, frequency and ambient temperature ranges. 0 to 50O C (32 to 122O F) Storage Temperature: -40 to 85O C (-40 to 185O F) Relative Humidity: 0 to 95% (non-condensing) Overall dimensions and weights are listed here-in. Case specifications are subject to change due to innovative product development and design. When space requirements are critical, please consult the factory. Floor or wall units are available. Mounting flanges 17

Output Power Protection: DC Output Voltages: Output Filtering:

DC Voltage Regulation:

Environmental Operating Temperature: Dimensions:

Mounting:

HazardWatch

Finish:

are supplied as integral part of cabinet back plate on wall mounted models. Pretreated with three-step iron phosphate wash and de-ionized rinse. Finished with environmentally safe water based ANSI 61 gray baked enamel. File E 25701,Guide BBHZ Std.No.1564 File S2768, Guide UTRZ Std.No. 1481 File LR14209, Std. C22.2 No. 107

Agency Approvals U.L. Industrial Battery Charger: U.L. Fire Alarm System / Power Supply Application: CSA Rectifiers:

UPS12-370 Specifications: Cells Per Unit Voltage Per Unit Weight Electrolyte Max. Discharge Current Short Circuit Current Ohms Imped. 60 Hz Capacity 6 12.84 74 lbs, 34 kg. Absorbed H2SO SG = 1.300 800 Amps 5100Amps @ 0.1 sec 0.0025 Ohms 391 watts per cell at the 15-minute rate to 1.67 volts per cell at 77F (25C). 100 Ah @ 20 hr. rate to 1.75 volts per cell @ 77F (25C). 85 Ah @ 10 hr. rate to 1.80 volts per cell @ 20C (68F). Discharge; -40F (-40C) to +160F (71C). Charge; -10F (-23C) to + 140F (60C). (with temperature compensation) +74F (23C) to +80F (27C) 13.5 to 13.8 VDC/unit Average at 77F (25C) C/5 amperes (20 amperes @ 100% depth of discharge) @ 20 hour rate. 14.4 to 14.8 VDC/unit Average at 77F (25C) 0.5% RMS or 1.5% P-P of float charge voltage recommended for best results Maximum voltage allowed = 1.4% RMS (4% P-P) Maximum current allowed = 5 amperes RMS (C/20) Dynasty UPS batteries may be stored for up to 6 months at 77F (25C) and then a freshening charge is required. For higher temperatures the time interval will be shorter. Inter unit connectors; racks and cabinet systems are available. "L" terminal with 0.28" clearance hole to accept 0.25" (6mm) bolt. 65 in.-lbs. (7.4 N-m). 52 in.-lbs. (5.88 N-m).

Operating Temperature Range Nominal Operating Temperature Range Float Charging Voltage Recommended Maximum Charging Current Limit Equalization and Cycle Service Charging Voltage Maximum AC Ripple (Charger)

Self Discharge

Accessories Terminal Terminal Hardware Initial Torque Terminal Hardware Annual Retorque 18

HazardWatch

NOTE: Batteries to be mounted with 0.5 in (1.25 cm) spacing minimum and free air ventilation. Specifications are subject to change without notification.

UPS12-475 Specifications: Cells Per Unit Voltage Per Unit Weight Electrolyte Max. Discharge Current Short Circuit Current Ohms Imped. 60 Hz Capacity 6 12.84 100 lbs, 45 kg. Absorbed H2S0, SG = 1.300 800 Amps 5100Amps @ 0.1 sec 0.0023 Ohms 475 watts per cell at the 15-minute rate to 1.67 volts per cell at 77F (25C). 134 Ah @ 20 hr. rate to 1.75 volts per cell @ 77F (25C). 122 Ah @ 10 hr. rate to 1.80 volts per cell @ 20C (68F). Discharge; -40F (-40C) to +160F (71C). Charge; -10F (-23C) to + 140F (60C). (With temperature compensation) +74F (23C) to +80F (27C) 13.5 to 13.8 VDC/unit Average at 77F (25C) C/5 amperes (27amperes @ 100% depth of discharge) 14.4 to 14.8 VDC/unit Average at 77F (25C) 0.5% RMS or 1.5% P-P of float charge voltage recommended for best results Maximum voltage allowed = 1.4% RMS (4% P-P) Maximum current allowed = 6.7 amperes RMS (C/20) Dynasty UPS batteries may be stored for up to 6 months at 77F (25C) and then a freshening charge is required. For higher temperatures the time interval will be shorter. Inter unit connectors; racks and cabinet systems are available.
Threaded brass inserts to accept 0.25" (6mm) bolt. 110 in.-lbs. (12.4 N-m)

Operating Temperature Range Nominal Operating Temperature Range Float Charging Voltage Recommended Maximum Charging Current Limit Equalization and Cycle Service Charging Voltage Maximum AC Ripple (Charger)

Self Discharge

Accessories Terminal Terminal Hardware Torque 19

HazardWatch

NOTE: Batteries to be mounted with 0.5 in. spacing minimum and free air ventilation. Specifications subject to change without notification.

1.1.7 Current Shunt and MV Transmitter


801A Alarms Specifications: DC Millivolt Input DC Millivolt/Voltage Input Ranges: Millivolt Accuracy: Thermocouple Input Thermocouple Input Ranges: Thermocouple type user configured. Signal linearization, cold-junction compensation, and open circuit or lead break detection is included. TC C Range (F Range) Accuracy J -210 to 760C (-346 to 1400F) 0.5C K -200 to 1372C (-328 to 2502F) 0.5C T -260 to 400C (-436 to 752F) 0.5C R -50 to 1768C (-58 to 3214F) 1.0C S -50 to 1768C (-58 to 3214F) 1.0C E -200 to 1000C (-328 to 1832F) 0.5C B 260 to 1820C (500 to 3308F) 1.0C N -230 to 1300C (-382 to 2372F) 0.5C 100. Pt, 120. Ni, or 10. Cu; user-configured. RTD C Range (F Range) Accuracy Pt1 -200 to 850C (-328 to 1562F) 0.25C Pt2 200 to 850C (-328 to 1562F) 0.25C Ni -80 to 320C (-112 to 608F) 0.25C Cu -200 to 260C (-328 to 500F) 1.00C Alpha: Pt1 ( = 1.3850), Pt2 ( = 1.3911), Ni ( = 1.6720), Cu ( = 1.4272). 1.0V, 125mV, 31.25mV, 500mV, 62.5mV, 15.625mV, 250mV Better than 0.05% of input span.

RTD Input RTD Input Ranges:

20

HazardWatch

RTD Excitation Current: RTD Lead-Wire Compensation: RTD Break Detection: Resistance Input Resistance Input Range: Resistance Accuracy: Output Relay (801A-0100 models) Relays (801A-0200 models) Relay Ratings (CSA ratings) Expected Mechanical Life Environmental Ambient Temperature Operating: Storage: Relative Humidity: Power Requirements: Isolation: Radiated Field Immunity (RFI): Electromagnetic Field Immunity (EMI):

2, 3, or 4-wire configurations supported. Module provides sensor excitation, linearization, lead-wire compensation, and sensor break detection 1mA DC typical, all types 25 ohms per lead Configurable for either upscale or downscale 0 to 500 ohms. 0.05 ohms. One DPDT electro-mechanical relay. Contact material Silver Nickel (AgNi 90/10). Two independent SPDT electro-mechanical relays. Contact material Silver-Cadmium Oxide (AgCdO). 25V DC @ 5A. 120/240V AC @ 5A. 20 million operations.

25 to 70C (-13 to 158F) 40 to 85C (-40 to 185F) 5 to 95%. 10 to 36V DC. 55mA @ 24V. 75mA @ 15V. 3-way (input/output/power). 1500V AC for 60 seconds or 250V AC continuous. EN61000-4-3, EN50082-1. No relay trips will occur beyond 0.25% of input span from set point under the influence of electromagnetic fields from switching solenoids, commutator motors, and drill motors. EN61000-4-4, EN50082-1. EN61000-4-5, EN50082-1. EN61000-4-2, EN50082-1. EN50081-1 for Class B equipment. CE marked, UL, cUL listed (USA, Canada). UL3121 - general product safety. Units are fully programmable via the Windows 95/98/ME/2000/NT/XP IntelliPack Configuration Program. Configuration downloads from PC through EIA232 serial port using Acromag 800CSIP kit. Set point and deadband are configurable via pushbuttons and a standard calibrator. LEDs indicate power, status, and alarm. 21

Electrical Fast Transient (EFT): Surge Withstanding Capability (SWC): Electrostatic Discharge (ESD): Radiated Emissions: Approvals: Configuration Software Configuration:

Field Configuration: LED Indicators: Physical

HazardWatch

Enclosure Case: Connectors (Removable terminal blocks): Printed Circuit Boards: Dimensions: Shipping Weight:

Self-extinguishing NYLON type 6.6 polyamide thermoplastic UL94 V-2, color beige; generalpurpose NEMA Type 1 enclosure. Wire Range: AWG #14-22 (AWG #12 stranded only). Military grade FR-4 epoxy glass circuit board. 1.05W x 4.68H x 4.35D inches. 26.7W x 118.9H x 110.5D millimeters. 1 pound (0.45 Kg) packed.

1.1.8 Battery Disconnect Switch and Polarized Connectors


Connector Model SB 50 Specifications: UL Current Rating (Amperes)*: UL Voltage Ratings (Volts): Contact Barrel Wire Size (AWG): (mm): Maximum Wire Insulation Diameter (inches): (mm): AVG Contact Resistance*: Insulation Withstanding: Contact Retention Force (lbs): Life No load (Contact/Disconnect Cycles): Under Load (Hot Plug 250 cycles @ 120V): Avg. Connection/Disconnect high detent: With lower extraction force: Operating Temperature Range C**: Flammability Rating of Housing Material UL94 V: * UL Rated for 75C rated wire or cable size ** Contact factory for higher temperature rated connector SB, UL and CSA Reference: This equipment is an Underwriters Laboratories Inc recognized component. It is also listed by the Canadian Standards Association as certified. To 10,000 50A 15(lbs) 10(lbs) 20 to 105 0 50* 600* #6 to #16 13.3 to 1.3 0.44 11.18 200 (micro-ohms) 2200 Test Voltage (Volts AC/DC) 50

22

HazardWatch

Connector Model SB 120 Specifications: UL Current Rating (Amperes)*: UL Voltage Ratings (Volts): Contact Barrel Wire Size (AWG): (mm) : Maximum Wire Insulation Diameter (inches): (mm): AVG Contact Resistance*: Insulation Withstanding: Contact Retention Force (lbs): Life No load (Contact/Disconnect Cycles): Under Load (Hot Plug 250 cycles @ 120V): Avg. Connection/Disconnect (lbs): Operating Temperature Range C**: Flammability Rating of Housing Material: * UL Rated for 75C rated wire or cable size ** Contact factory for higher temperature rated connector SB, UL and CSA Reference: This equipment is an Underwriters Laboratories Inc recognized component. It is also listed by the Canadian Standards Association as certified. To 10,000 60A 20 -20 to 105 UL94 V-0 120* 600* #2 to #6 33.3 to 13.3 0.575 14.6 136 (micro-ohms) 2200 Test Voltage (Volts AC/DC) 100

23

HazardWatch

1.2 Coaxial Cable 1.3 Fiber Optic Cable 1.4 Central Station Equipment
1.4.1 UL 864 Computer Station
7890UL_B Specifications: Physical Size: Weight: Environmental Temperature: Shock: Vibration: Humidity: Altitude: Storage: Electrical Power: Voltage: Frequency: 300 Watt 115/230 Volts 10% 50/60Hz 0 - 50C (32 - 122F) 10G, 3 Axis, 11ms 1.5G, 3 Axis, 10-150Hz, .75mm 0 - 95% RHNC Up to 10000 feet (3 km) -10 to +65C (14 - 149F) 17.62"W x 6.9"H x 16.87"D (447mm x 175mm x 428mm) 38 lbs (17.24kg) Typical

Options
PIII 850MHz or P4 up to 2.8 GHz EIDE Hard Drive 24

HazardWatch

CD-ROM, CD- R/W Drive 40GB Tape Back Up PCI Sound Card 10/100 BTX Ethernet Card Quad Serial RS232/422/485 PCI 17", 19", 21" CRT 15", 17", 19" LCD Resistive Touchscreen Serial or USB TS Controllers 101 Key PS/2 Compact Keyboard PS/2 Mouse with Scroll Bar

1.4.2 Central Station UPS


APCSmart UPS Specifications:

Technical Specifications
Output

Output power capacity 750 VA Output power capacity 600 watts Max Configurable Power 750 VA Max Configurable Power 600 watts Nominal output voltage 120V Output Voltage Distortion less than 5% at full load Output Frequency (sync to mains) 47-53Hz for 50Hz nominal , 57-63Hz for 60Hz nominal Crest Factor up to 5 : 1 Waveform type Sinewave Output Connections (8) NEMA 5-15R
Input

Nominal input voltage 120V Input frequency 50/60 Hz +/- 3 Hz (auto sensing) Input Connection Type NEMA 5-15P Cord Length 6 feet ( 1.83 meters ) Input voltage range for main operations 82 - 144 V Input voltage adjustable range for mains operation 75 - 154 V
Batteries & Runtime

Battery type Maintenance-free sealed Lead-Acid battery with suspended electrolyte : leakproof Replacement battery cartridge RBC7 RBC Quantity 1
Communications & Management

Interface port DB-9 RS-232 , SmartSlot , USB Available Smart Slot Interface Quantity 1 Control panel LED status display with load and battery bar-graphs and On Line : On Battery : Replace Battery: and Overload Indicators 25

HazardWatch

Audible alarm Alarm when on battery: distinctive low battery alarm : configurable delays Emergency Power Off (EPO) Optional
Surge Protection and Filtering

Surge energy rating 459 Joules Filtering Full time multi-pole noise filtering: 0.3% IEEE surge let-through: zero clamping Response time: meets UL 1449
Physical

Maximum height 9 inches ( 21.59 cm ) Maximum width 7 inches ( 17.02 cm ) Maximum depth 17 inches ( 43.94 cm ) Net weight 53 lbs. ( 24.09 kg ) Shipping Weight 58 lbs. ( 26.36 kg ) Shipping Height 15 inches ( 38.74 cm ) Shipping Width 13 inches ( 32.00 cm ) Shipping Depth 23 inches ( 59.06 cm ) Color Black Units per Pallet 24
Environmental

Operating Environment 0 - 40 C ( 32 - 104 F ) Operating Relative Humidity 0 - 95 % Operating Elevation 0-10000 feet ( 0-3000 meters ) Storage Temperature -15 - 45 C ( 5 - 113 F ) Relay I/O SmartSlot Card Specifications: Physical: Net weight Maximum height Maximum Width: Maximum Depth Shipping Weight Shipping Height Shipping Width Shipping Depth Color Units per Pallet Environmental Operating Environment Storage Temperature Operating Relative Humidity Storage Relative Humidity Operating Elevation Storage Elevation Approvals 0-40C (32-104F) -14-65C (5-149F) 0-95% 0-95% 0-10000ft (0-3000m) 0-50000ft (0-15000m) C-tick, CE, DOC/Industry Canada, EN 55022 Class B. EN 55024, EN 55082, FCC Part 15 Class B, VCCI 0.30lbs, (.14kg) 1.50in, (38mm) 4.75in (121mm) 4.25in (108mm) 1.00lbs, (0.45kg) 2.86in (73mm) 6.50in (165mm) 9.00in (229mm) Black 672.00

26

HazardWatch

1.4.3 Central Station Fiber Optic Converter


PheonixDigital Specifications: Fiber Optic Cable Type: Mating Connector: Transmit Launch Power: Receive Sensitivity: Power Supply Plug-In Modules: Standalone Panelmount Modules: Environmental Operating Temperature: Storage Temperature: Relative Humidity: Dimensions 1771 Plug-In Modules: 1746 Plug-In Modules: 1756 Plug-In Modules: Standalone, Panelmount: Modules: Single Slot, 1771 Chassis Installation Single Slot, 1746 Chassis Installation Single Slot, 1756 Chassis Installation 10.38 H x 1.76 W* x 6.14 D (26.36cm H x 4.47cm W* x 15.60cm D * Add 1.00 (2.54cm) for rear panel flange 0 to 60 C (32 to 140 F) -40 to 85 C (-40 to 185 F) 0 to 95% RH, non-condensing +5 VDC, 1.8 Amps (Typical 120/220 VAC, 24 VDC, or 125 VDC.... 10 Watts Multimode or Singlemode ST or SMA 15dbm (Typical, Multimode); -18dbm (Singlemode) -32dbm

1.4.4 Central Station Printer


LA36W Specifications: Printing Technology Print Method Print Speed (cps) Print Head Bar Codes LQ: NLQ: Draft: Serial impact dot matrix Bi-directional, logic-seeking or uni-directionalseeking 10 cpi, 12 cpi 113 135 225 270 360 432 24-wire; 0.0079" (0.20 mm) dia. Code 3 of 9, Interleaved 2 of 5, EAN-8, EAN-13, Codabar a/t, Codabar b/n, Codabar c/*, Codabar d/e, UPC-A, UPC-E, POSTNET, Industrial 2 of 5, Code 93, MSI mod 101/10, Code 128 (EAN 128), Matrix 2 of 5 Draft, Courier, Sans Serif, Script, Prestige, Orator, OCR-A/B, Roman Character Spacing: 10, 12, 15, 17.1, 18, and 20 cpi; LF Interval: 60 ms per line at 6 lpi; Print Line: LA36N: 8.0 in.; LA36W: 13.6 in.; Dot Graphics (dpi): 120 to 360H x 180 to 360V Paper parking, automatic fanfold positioning for zero tear off Push tractors (rear feed), pull tractors (bottom 27

Fonts Printing

Paper Handling Features: Paper Drive:

HazardWatch

Paper Dimensions: Continuous Forms Width: Continuous Forms Length: Cut Sheet Width: Cut Sheet Length: Paper Type:

Number of Copies: Maximum Forms Thickness: Emulations Interfaces & Connectivity Baud Rate: Download Buffer: Physical Specifications Size Weight: Acoustics: Operating Environment Voltage: Temperature: Operating: Storage: Humidity: Reliability MTBF: Print Head Life: Ribbon Life: Regulatory Compliance Warranty

feed), and friction-feed platen for cut sheet; LA36N - LA36W 4-10.5 in. (102-267mm), 4-16.5 in. (102-420mm) 4 in. or more (102mm), 4 in. or more (102mm) 4-10.5 in. (102-267 mm), 4-16.5 in. (102-420 mm) 3-14.3 in. (76-364 mm), 3-16.5 in. (76-420 mm) 1 to 5-part side-glued or paper stapled fanfold continuous forms or label sheets with sprocket holes; 1 to 5-part top-glued cut sheets and envelopes 5 (original + 4 copies) Up to 0.014 in. (0.35 mm); Paper Slew: 5.6 ips DEC ANSI PPL2, IBM ProPrinter XL24e, Epson ESC/P2 RS-232 Serial and bitronics parallel with DEC423 adapter; From 600 to 38,400 bps; Data Buffer Size: Up to 64K; Up to 128K (HxWxD): LA36N: 5.2 x 17 x 13in. (133 x 434 x 330mm); LA36W: 5.1 x 22.4 x 13in. (133 x 570 x 330 mm); LA36N: 16.5 lbs (7.5 kg); LA36W: 18.7 lbs (8.5 kg); LA36N: Averages 54 dB(A); LA36W: Averages 56 dB(A) 100 to 120 VAC +/-10%; 50-60Hz; 200 to 230 VAC +6%-10%; 50-60Hz; 41 to 104 F (5 to 38 C); 4 to 104 F (-15 to 60 C); 10% to 90% relative 15,000 hours @ 5% duty cycle; 400 million impacts; Black: Up to 2 million characters UL 1950, CSA C22.2/950, TUVEN 60950/08, EMKO-TSE (74-SEC) 207/94, Class B of FCC Part 15B, CE marking One year return to depot

1.5 GMI Field Devices


1.5.1 GM S4000C Combustible Gas Detector
System Specifications 28

HazardWatch

Sensor Type: Accuracy: Zero Drift: Response Time: Measuring Ranges: Modes: Electrical Classification:

Approvals:

Continuous diffusion, low temperature catalytic bead +3% LEL up to 50% LEL +5% LEL > 51% LEL Less than 5% of full scale per year T50<10 sec. T90<30 sec. with 100% LEL methane applied 0-100% LEL Calibration, gas check, setup CSA/FM Class I, Division 1, Groups B, C & D; Class I, Zone 1, Ex d IIB+H2, T6 ATEX EEx d IIB: T5 (Tamb = -40C to +70C) CSA, FM, ATEX approved, CE Complies with ANSI/ISA-12.13.01-2000 performance requirements. Electronics: -40F to 167F (-40C to 75C) Standard Sensor: -65F to 200F (-55C to 93C) High Temp Sensor: -65F to 400F (-55C to 200C) -58F to 158F (-50C to 85C) 5% to 100% RH, non-condensing 6.4 inches (161mm) 3.4 inches (86mm) 4.1 inches (104mm) 5.5 lbs. (2.5 kg) 5.0 inches (127mm)(center to center) 24 VDC nominal, 20 to 36 VDC 250mA max. 8A @ 250 VAC / 8A @ 30 VDC res. max. (3x) SPDT - Warning, Alarm & Fault 0-20mA (650 ohms max. load) Malfunction 0mA Gas Check 1.5mA Setup mode 1.5mA Zero reading 4mA+0.2mA 0-100% LEL 4-20mA Over-range 20-22mA Complies with EN50081-2, EN50082-2 Three-digit digital display with gas concentration, Warn and Alarm LEDs, calibration prompts, fault odes, and setup options Dual redundant MODBUS RTU, suitable for linking up to 128 units or up to 247 units with repeaters 2400, 4800, 9600, or 19200 BPS Calibration error, open AO, sensor error, low DC 29

Environmental Specifications Operating Temperature Range: Storage Temperature Range: Operating Humidity Range: Mechanical Specifications Length: Height: Width: Weight: Mounting Holes: Electrical Specifications Input Power: Relay Ratings: Analog Signal:

RFI/EMI Protection: Status Indicators: RS-485 Output: Baud Rate: Faults Monitored:

HazardWatch

supply, EEPROM, EPROM, setup error, gas check time exceeded, switch error Cable Requirements: 3 wire shielded cable. Max. distance between S4000C and power source on the remote sensor @ 24 VDC nominal (20 ohm loop): 14 AWG - 3000 ft. (910m) Max. distance for analog output (650 ohms max): 14 AWG - 9000 ft. (2740m)

1.5.2 GM S4000T H2S Gas Detector


System Specifications Sensor Type: Sensor Life: Repeatability: Response Time: Measuring Ranges: Modes: Electrical Classification: CSA/FM Class I, Division 1, Groups B, C & D; Class I, Zone 1 Ex d IIB+H2, T6 (Tamb = -40C to +60C) ATEX EEx d IIB: T6 (Tamb = -40C to +40C) Two years CSA, FM, ATEX, CE Marking. Complies with ISA-92.0.01, Part 1-1998 performance requirements. Electronics -40F to 167F (-40C to 75C) Standard Sensor -40F to 167F (-40C to 75C) High Temp Sensor -40F to 195F (-40C to 90C) -58F to 185F (-50C to 85C) 5% to 100% RH, non-condensing 6.4 inches (161mm) 3.4 inches (86mm) 4.1 inches (104mm) 5.5 lbs. (2.5 kg) 5.0 inches (127mm) (center to center) 24 VDC nominal, 20 to 36 VDC 350mA max. 30 Continuous diffusion, adsorption type Metal Oxide Semiconductor (MOS) 3 to 5 years typical +2 ppm or 10% of the applied gas, whichever is greater T50<1 minute (screen), T50<2 minutes (sintered) with full scale gas applied 0-20 ppm, 0-50 ppm, 0-100 ppm Calibration, gas check, setup

Warranty: Approvals:

Environmental Specifications Operating Temperature Range: Storage Temperature Range: Operating Humidity Range: Mechanical Specifications Length: Height: Width: Weight: Mounting Holes: Electrical Specifications Input Power:

HazardWatch

Relay Ratings: Analog Signal:

8A @ 250 VAC / 8A @ 30 VDC res. Max (3x) SPDT - Warning, Alarm & Fault 0-20mA (650 ohms max. load) Malfunction 0mA Gas Check 1.5mA Setup mode 1.5mA Zero reading 4mA+0.2mA 0-100% scale 4-20mA Over-range 20-22mA Complies with EN50081-2, EN50082-2 Three-digit digital display with gas concentration, Warn and Alarm LEDs, calibration prompts, fault codes, and setup options Dual redundant MODBUS RTU, (optional) suitable for linking up to 128units or up to 247 units with repeaters 2400, 4800, 9600, or 19200 BPS Open AO, calibration error, sensor heater error, low DC supply, EEPROM, EPROM, setup error, gas check time exceeded, switch error 3 wire shielded cable. Max. distance between S4000T and power source or remote sensor @ 24 VDC nominal (20 ohm loop): 14 AWG - 2000 ft. (610m) Max. distance for analog output (650 ohms max):14 AWG - 9000 ft. (2740m)

RFI/EMI Protection: Status Indicators: RS-485 Output: Baud Rate: Faults Monitored:

Cable Requirements:

1.5.3 GM IR2100/IRFMD IR Gas Detector


System Specifications Sensor Type: Measuring Range: Infrared Absorption Type 0 to 100% LEL 0 to 100% by Volume (methane only) Gases: Methane, propane, ethane, butane, hexane, ethylene, pentane & benzene (For other gases contact factory) Greater than 5 years + 3% LEL at < 50% LEL reading + 5% LEL at > 50% LEL reading < 2% per year (With 100% LEL Methane applied) T50 < 7 sec. & T90 < 10 sec. without splash guard Power-on self-test, normal operation, calibration (zero only or complete calibration) Flow block, junction box with optional zero switch, display and/or relays, duct mount junction box, splash guard with optional test cell, rain guard, remote gassing guard, field mounted display, multi31

Sensor Life: Accuracy: Zero Drift: Response Time: Modes: Accessories:

HazardWatch

Classification: Warranty: Approvals: Environmental Specifications Operating Temperature Range:

channel controller Class I, Division 1, Groups B, C & D EExd IIB+H2T5, IP66, Type 4X Two years ATEX, CE Marking and CSA 22.2 No. 152-M1984 Performance Approved

-40F to +167F (-40C to +75C) Pentane, Hexane, Benzene only*: -40F to +140F (-40C to +60C) Storage Temperature Range: -58F to +167F (-50C to +75C) Pentane, Hexane, Benzene only: -40F to +140F (-40C to +60C) * For higher temperature range, consult factory Humidity: 5% to 100% RH, non-condensing Electrical Specifications Input Power: 20-36 VDC 24 VDC @ 0.4 amp (nominal) 4-20 mA (600 ohms max.) Fault 0 mA Cal & Zero 1.5 mA Dirty Optics 2.0 mA Zero Reading 4 mA +0.2mA 0 to 100% LEL 4 to 20 mA (proportional) Over-range 20 to 22 mA Link up to 128 units, 247 with repeaters Complies with EN50081-1, EN50082-1 Max. distance between IR2100 and power source @ 24 VDC nominal (10 ohm loop) 14 AWG (2.0 mm2) 1800 ft (550 m) Calibration errors, EPROM and EEPROM checksum errors, optics failure/blockage, low supply voltage 2.87 inches (73 mm) 10.6 inches (269 mm) 3 lbs (1.4 kg) aluminum 6 Ibs (2.7 kg) - stainless steel 3/4" NPT Aluminum (stainless steel optional) 32

MODBUS Output: RFI/EMI Protection: Cable Requirements: Faults Monitored:

Mechanical Specifications Diameter: Length: Weight: Mounting: Housing:

HazardWatch

33

HazardWatch

1.5.4 GM IR 5000 Open Path Gas Detector


System Specifications Sensor Type: Ranges: Path Length: Response Time: Repeatability: Linearity: Calibration: Modes: Optional: Mechanical Housing Size: Source: Receiver Enclosure Material: Weight: Source: Receiver: Mount: Conduit Entries: Stainless Steel: Environmental Operating Temperature: Operating Humidity: Vibration: Weatherproof rating: Certification: Accessories: Electrical Operating Voltage: Power Consumption: Source: Receiver: Outputs: Analog Signals: 34 24 VDC nominal, 20 32 VDC range 24 VDC @ 1.25 amp (Maximum) 24 VDC @ 1.05 amp (Maximum) Two (2) analog signals and four (4) SPDT relays 600-ohm load max. -40F to +140F (-40C to +60C) To 95% RH (Non-condensing) Per ISA/CSA C22.2 No 152 and BS2011 Part 2.1 standards Type 4X, IP66 Class 1, Div. 1, Groups C & D / EExd IIB T4 CSA-CUS, ATEX & GOST Test gas filters, Mounting arm 6.4 Dia x 12.0 Length (163mm Dia x 305mm Length) 5.4 Dia x 16.7 Length (137mm Dia x 424mm Length) Copper-free Aluminum or 316 Stainless Steel 10 lbs (5 Kg) Aluminum 28 lbs (12.7 Kg) Stainless Steel 9 lbs (4.1 Kg) Aluminum25 lbs (11.3 Kg) Stainless Steel 11 lbs (5.0 Kg) Stainless Steel only (2) Aluminum: 3/4 NPT M20 x 1.5-6H Infrared absorption Light Hydrocarbon Methane unit 0 to 5000 ppmmeter and 0 to 5 LELmeter 5 to 100 m (16 to 328 ft) T50 4.5 seconds and T90 8 seconds when exposed to full scale gas concentration in ppm range 10% of last reading for each scale 10% over full scale for each scale No traditional calibration required. Field background zero adjustment provided Test gas, setup, alignment Heavy Hydrocarbon Propane unit 0 to 2000 ppmmeter and 0 to 1 LELmeter detection ranges

HazardWatch

Relays:

Digital Display: Fault Codes:

0-5000 ppmmeter 0-5 LELmeter 0 mA Malfunction Malfunction 1.5 mA Beam Block Beam Block or test gas or test gas 4-20 mA 0 - 5000 ppmmeter 0-5 LELmeter 20-22 mA Overrange Overrange Four (4) SPDT 5 amp @ 30 VDC res. max; 250 VAC; ppm Alarm; LEL Warning; LEL Alarm and Fault Software Selectable: Latching/Non-Latching Warning and Alarm Energized/De-Energized Warning and Alarm Warning & Alarm level set-points Two digit, seven segment (auto range change) LED indication of scale displayed F1 - Close to minimum signal level F2 - Timing error F3 - Low IR energy F4 - High IR energy F5 - Large sudden change (blockage) 30 second Fault delay F6 - Low voltage F7 - Internal system failure F8 - Failed to zero/Excessive negative drift due to background gas changes F9 - Open current loop(s)

1.5.5 GM FL3100/3101UV/IR Flame Detector


System Specifications Wave Lengths: Field of View: Sensitivity: 185 to 260 nm (UV) 4.35 microns (IR) Hydrogen FL3100: 2.7 to 3.2 microns (IR) 120 horizontal, 115 vertical (FL3100) 140 horizontal, 135 vertical (FL3101) Approved performance specifications - 50 feet (15.2m) Distance for a 1 sq. ft (0.092m2) Gasoline fire. For H2, contact factory. < 3 sec @ 50 ft. (FL3100) < 1 sec @ 50 ft. (FL3101) UV/IR FL3100 <500 ms UV- FL3101 <100 ms Swivel elbow union, mounting bracket, air shield, test lamp Class I, Division 1and 2, Groups B, C & D 35

Typical Response Time: Minimum Sensor Response Time: Accessories: Classification:

HazardWatch

Approvals: Environmental Specifications Operating Temperature Range: Storage Temperature Range: Operating Humidity Range: Electrical Specifications Input Power: Analog Signal: Fault Signal: COPM Fault: Ready Signal: IR Signal: UV Signal: WARN Signal: ALARM Signal: Baud Rate: Relay Contact Rating: Dip Switch Selectable Options:

Class II, Groups E, F & G; Class III, Type 4X, EE x d IIC, T5, IP66 CSA, FM, ATEX, CE Marking. Patent Number 5,914,489 40F to +185F (40C to +85C) 58F to +185F (50C to +85C) 0% to 100% RH, non condensing 20-36 VDC, 24 VDC @ 150mA max. (3.6w max.) 4-20 mA (600 Ohms Max.) 0mA 2mA, 0.2mA 4mA, 0.2mA 8mA, 0.2mA (FL3100 only) 12mA, 0.2mA (FL3100 only) 16mA, 0.2mA 20mA, 0.2mA 2400, 4800, 9600 or 19200 BPS 8A 250 VAC, 8A @ 24 VDC resistive (North America) 8A @ 30 VDC resistive (Europe) Sensitivity: 100%, 75%, 50% Alarm Time Delay: 2, 4, 8, or 10 seconds Warn & Alarm Relays: Latching/Non-Latching Energized/De-Energized MODBUS RTU, suitable for linking up to 128 units in series and up to 247 units with repeaters. Optional Dual MODBUS Complies with EN50081-2, EN50082-2 Max. distance between detector and power source @ 24 VDC nominal (20 ohm loop), 14 AWG - 3000 ft (930 m) Terminal Blocks -12-22 AWG LED with status, fault and alarm indication EPROM and EEPROM checksum errors, optics failure/blockage, low supply voltage Aluminum (Stainless steel optional) 6 inches (152 mm) 5.5 inches (140 mm) 5 lbs (2.27kg) Aluminum 16 lbs (7.26kg) Stainless Steel 3/4" NPT (2 ports) or surface mounting (ATEX) 2 x 3/4 NPT or 2 x m25 or 2 x m20

RS-485 Output RFI/EMI Protection: Cable Requirements:

Status Indicator: Faults Monitored: Mechanical Specifications Housing: Diameter: Length: Weight: Mounting: Cable Entry:

36

HazardWatch

1.5.6 GM FL3102 DFIR Flame Detector


System Specifications IR Center Wavelength: Field of View: Sensitivity: Typical Response Time: Minimum Sensor Response Time: Accessories: Classification: Approvals: Environmental Specifications Operating Temperature Range: Storage Temperature Range: Operating Humidity Range: Mechanical Specifications Housing: Diameter: Length: Weight: Mounting: Electrical Specifications Input Power: Analog Signal: Fault Signal: COPM Fault: Ready Signal: WARN Signal: ALARM Signal: Relay Contact Rating: Dip Switch Selectable Options: 20-36 VDC 24 VDC @ 150mA max. (3.6w max.) 0-20mA (600 ohms max.) 0mA 2.0mA, 0.2mA 4.0mA, 0.2mA 16.0mA, 0.2mA 20.0mA, 0.2mA SPDT, 8A @ 250 VAC, 8A @ 24 VDC resistive max. Sensitivity: 100%, 75%, 50% Alarm Time Delay: 2, 4, 8, or 10 seconds Warn & Alarm Relays: Latching/Non-Latching Energized/De-Energized MODBUS RTU, suitable for linking up to 128 units or up to 247 units with repeaters Dual MODBUS 37 Aluminum (Stainless steel optional) 6 inches (152 mm) 5.5 inches (140 mm) 5 lbs (2.27kg) Aluminum 16 lbs (7.26kg) Stainless Steel 3/4 NPT (2 ports) 40F to +167F ( 40C to +75C) 40F to +167F ( 40C to +75C) 0% to 100% RH, non condensing 4.35 microns 110 maximum Approved performance specifications - 50 feet (15.2m) distance for a 1 sq. ft (0.092m2) gasoline fire. <3 seconds @ 50 ft. <500 ms Swivel elbow union, mounting bracket, air shield, test lamp Class I, Division 1and 2, Groups B, C & D; Class II, Groups E, F & G; Class III, Type 4X, II2G EE xd IIC T5, IP66 FM, CSA, ATEX & CE Marking Patent Number: 6,150,659

RS-485 Output: Option:

HazardWatch

Baud Rate: RFI/EMI Protection: Cable Requirements:

Status Indicator: Faults Monitored:

2400, 4800, 9600 or 19200 BPS Complies with EN50081-2, EN50082-2 Max. distance between detector and power source @ 24 VDC nominal (20 ohm loop), 14 AWG - 4500ft (1370 m) Terminal Blocks - 12-22 AWG LED provides status and fault information EPROM and EEPROM checksum errors, optics failure/blockage and low supply voltage

1.6 Smoke and Thermal Fire Detection Equipment


1.6.1 Pyrotronics DI-3 Ionization Type Smoke Detector
Engineer and Architect Specifications: Adjustable Sensitivity Dual Chamber Sensitivity Test Points Simple Twist/Lock Assembly Optional Auxiliary Relay Screw-Clamp Terminals Alarm LED Listed, ULC Listed, NYMEA, FM, CSFM Approved

The ionization smoke detector shall be a dual chamber plug-in unit, which mounts to a twist/lock base, and shall be UL listed. The smoke detector shall operate on a two-wire circuit and shall contain an alarm indicating LED, which will illuminate to signal actuation of the detector. DI-A3 ONLY The detector shall be specifically designed for use in high air velocity applications of between 0 and 1200 ft./min. Detectors which are not UL listed for the stated air velocity range shall not be accepted. DI-B3 ONLY The detector shall be specifically designed for use in air ducts with air velocities between 500-4000 FPM when used with Cerberus Pyrotronics Series 3 air duct housings. Detectors not listed to UL 268A for the stated air velocity range shall not be accepted. The detector shall be available in a model that is acceptable for and UL listed for use in altitudes of 3000-8000 feet above sea level if desired models DI-3H, DI-A3H or DI-B3H. Field adjustment* and monitoring of the detector sensitivity shall be possible without removal of the detector head from its base. The measurement of detector sensitivity shall provide a 38

HazardWatch

discrete electrical value. Test methods, which do not provide an output signal proportional to smoke concentrations, shall not be considered equal. The base assembly into which the detector is installed shall be of the twist/lock design with screw clamp terminals. The base shall utilize self-wiping contacts for reliability and shall accept other compatible plug-in detectors. A security lock shall be installed in those areas where tamper resistant installation is required as indicated on the drawings. The detector, or group of detectors, shall require a two wire circuit of #18 AWG thermoplastic fixture wire enclosed in conduit, or #18 AWG limited energy shielded cable without conduit, if permitted by local codes. Optional auxiliary DPDT relays or remote alarm lamps shall be installed where indicated. The detector assembly shall be a Cerberus Pyrotronics DI (insert number) with DB-3S mounting base, ADB-3 audible or Series 3 air duct housing.** *DI-3, DI-3H only **DI-B3, DI-B3H only Technical Specifications Current Requirements: Voltage Range: Operating Temperature: Humidity: Air Velocity: Normal 100uA (350uA peak surge upon application of power) Alarm 80mA 21 +3 VDC +32F (0C) to +100F (38C) per UL 0-93% Relative Humidity 0-300 ft./min. Model DI-3 0-1200 ft./min. Model DI-A3 500-4000 ft./min. Model DI-B3 (Requires air duct housing)

Note:

Consult factory for special application requirements. For additional product information, refer to Cerberus Pyrotronics DI-3 technical bulletin, P/N 315- 082300.

1.6.2 Pyrotronics PE-11 Photoelectric Type Smoke Detector


Engineer and Architect Specifications: Advanced Field Cleanable Chamber Design Self Diagnostic Multi-Color LED for Normal, Trouble or Alarm Indication Low-Profile Design Easy Twist-In Base Design Made in USA at ISO 9001 Facility Listed, ULC Listed, CSFM NYMEA, FM Approved 39

HazardWatch

The photoelectric smoke detector shall be a plug-in unit, which mounts to a twist/in base, and shall be UL listed. The smoke detector shall operate on a two-wire circuit and shall contain a multi-color LED indicator indicating the detector is operational by flashing green, trouble by flashing amber, and alarm by flashing red. The detector shall be continually self-testing with visual operation indication and not require additional hardware or contact with the detector for testing purposes. The detector shall allow for easy cleaning or replacement of screens and/or chamber components without affecting calibration. The base assembly into which the detector is installed shall be a twist/in design with screw clamp terminals. A security lock shall be installed in those areas where tamper resistant installation is required as indicated in the drawings. The detector or group of detectors shall require a two wire circuit of #18 AWG thermoplastic fixture wire enclosed in conduit, or #18 AWG limited energy shielded cable without conduit, if permitted by local building codes. All wiring shall be approved for fire alarm use and in compliance with national and local codes. When required, the smoke detector shall contain a 135F fixed temperature self-restoring heat sensor. Actuation of this device shall lock the detector alarm circuit. The detector shall be Pyrotronics Model PE-11 or Model PE-11T with a DB-11 surfacemounting base. Technical Specifications Current Requirements: Voltage Range: Operating Temperature: Humidity: Normal - 100mA peak Alarm - 40mA 16 - 26.6 VDC 0 - 39C 93% non-condensing

1.6.3 Pyrotronics DT-11 Thermal Detector


Engineer and Architect Specifications: Self Testing with Status Indicating Multi-Color LED Simple Twist /Lock Assembly Alarm Lock-in Remote Function Output Screw-clamp Terminals Listed, ULC Listed, CSFM,FM and NYMEA Approved

The thermal fire detector shall be a Pyrotronics Model DT-11 and shall be of the fixed temperature type. The detector shall plug into its base and have a lamp to indicate the initiation of an alarm. The detector shall be listed by Underwriters Laboratories, Inc and FM. The plug-in thermal detector shall insert into the standard Series 11 base and shall be compatible with 40

HazardWatch

Pyrotronics ionization detectors, photoelectric detectors, flame detectors, and manual stations on the same circuit. The installing contractor shall install the detectors with #18 AWG thermoplastic wire with 300 volt insulation rating, housed in conduit or limited energy cable where permitted by local codes. Technical Specifications Environmental Temperature: Humidity: Air Pressure: Alarm Temperature: Electrical Voltage: Ripple: Supervisory Current: Alarm Current: 16-27 VDC 3V peak-to-peak 110A max 33-50 mA 32F (0C) to 100F (38C) Up to 93% RH, non-condensing No effect 135F (57C)

1.6.4 Kidde Fenwal Detect-a-fire Thermal Detector


Engineer and Architect Specifications: Detect-A-Fire Models Explosion Proof Self-Restoring Detector Element Models Available in both Normally Open and Normally Closed Contacts in a Wide Range of Temperature Settings Factory Set and Hermetically Sealed in Stainless Steel Shell Listed and FM Approved as Fenwal Model Series 27120 and 27121 Manufactured for Siemens Cerberus Division by Fenwal

The explosion proof thermal fire detector shall be a Detect-A-Fire explosion proof model, Fenwal ( Model # ), also for purchasing purposes referred to as Pyrotronics ( Model # ), and shall be of the rate compensated type. The explosion proof detector shall have a self-restoring element and shall be factory set and hermetically sealed in stainless steel. These detectors shall be mounted in an approved explosion proof junction box. The explosion proof detectors must be UL listed and FM approved 41

HazardWatch

Model Cross-Reference Chart Normally Open Contact F Setting 140 160 190 210 225 275 325 360 450 500 600 725 F Tolerance (+7,-8) (+7,-8) (+7,-8) (+7,-8) (+7,-8) (+/-10) (+/-10) (+/-10) (+/-15) (+/-15) (+/-20) (+/-25) Color Coding Yellow Yellow White White White Blue Red Red Green Orange Orange Orange Fenwal Model 27121-140 27121-160 27121-190 27121-210 27121-225 27121-275 27121-325 27121-360 27121-450 27121-500 27121-600 27121-725 Cerberus Pyrotronics Model DT-140EP DT-160EP DT-190EP DT-210EP DT-225EP DT-275EP DT-325EP DT-360EP DT-450EP DT-500EP DT-600EP DT-725EP Normally Closed Contact Fenwal Model 27120-140 27120-160 27120-190 27120-210 27120-225 27120-275 27120-325 27120-360 27120-450 Cerberus Pyrotronics Model * * * * * * * * *

* Normally Closed Contact Detectors do not operate with any Cerberus Pyrotronics Control Panels. These Normally Closed Contact Detectors are offered for special applications only.

1.6.5 Apollo Series 60 Ionization Type Smoke Detector


Technical Data - Ionization Specications are typical and given at 23C and 50% relative humidity unless specied otherwise. Detector Type: Detection Principle: Chamber Conguration: Radioactive Isotope: Activity: Supply Wiring: Terminal Functions: Supply Voltage: Ripple Voltage: Quiescent Current: Switch-on Surge Current: Alarm Voltage: Normal Alarm Current: Alarm Indicator: Design Alarm Load: Holding Voltage: Holding Current: Products of combustion (smoke) detector. Ionization chamber. Twin compensating chambers using one single sided ionizing radiation source. Americium 241. 33.3 k Becquerels, 0.9 Cie. Two wire monitored supply, polarity insensitive. L1 IN and L2: supply in connections (polarity insensitive) L1 OUT and L2: supply out connections (polarity insensitive) -R: remote indicator negative connection 17 to 28V DC 2V peak to peak maximum at 0.1Hz to 100kHz 30 to 45A at 24V 80A 6 to 28V 61mA at 28V 52mA at 24V 18mA at 10V Red Light Emitting Diode (LED) 450 in series with a 3V drop (LED open circuit) 6V (min) 10mA (min) 42

HazardWatch

Minimum Voltage Required to Illuminate Indicator: Alarm Reset Voltage: Alarm Reset Time: Remote Output Characteristics:

12V 1V 1 second 900 in series with a 3V drop at 24V with 500 line impedance gives: 1mA at 9V 4.5mA at 5V 8.0mA at 1V Factory set to V of 1.3V Nominal threshold Y value of 0.7 to EN54 Part 7 1984; (BS 5445 Part 7 1984) Maximum continuous operating temperature 60C Minimum continuous operating temperature 0C Minimum operating temperature (no condensation or icing) -20C Automatic compensation by dual chambers to comply with EN 54 Part 7 1984; (BS 5445 Part 7 1984) across the operating temperature range 0% to 95% relative humidity Automatic compensation by dual chambers to maintain sensitivity up to a height of 2000m 2 m/s maximum (constant) 10 m/s maximum (transient) To EN 54 Part 7 1984 (BS 5445 Part 7 1984) To EN 54 Part 7 1984 (BS 5445 Part 7 1984) To EN 54 Part 7 1984 (BS 5445 Part 7 1984) IEC 801-2 (BS 6667 Part 2 1985) Severity Level 3. Tested to 12,000V positive and negative to the case and supply terminals from a 250pF capacitor BS 6527 Class B IEC 801 Part 3 Class 3 (10V/m). Tested to 90V/m from 27MHz to 1GHz. 43 Detector: 100mm x 42mm (diameter x height) Detector in Base: 100mm x 50mm (diameter x height) Detector: 102 grams. Detector in Base: 153 grams. Detector housing: White polycarbonate V-O rated to UL 94 Stainless steel

Calibration: Sensitivity: Temperature Range:

Temperature Compensation: Humidity: Atmospheric Pressure: Wind Speed: Vibration: Impact: Shock: Static: Radiated Emissions: Radiated Susceptibility: IP Rating: Dimensions: Weights: Materials: Terminals:

43

HazardWatch

1.6.6 Apollo Series 60 Photoelectric Type Smoke Detector


Technical Data Optical Specifications are typical and given at 23C and 50% relative humidity unless specified. Detector Type: Detection Principle: Chamber Conguration: Sensor: Emitter: Sampling Frequency: Confirmation Frequene: Number of Consecutive Sensed Alarm Signals Needed to Trigger Detector Alarm: Supply Wiring: Terminal Functions: Products of combustion (smoke) detector Photoelectric detection of light scattered in a forward direction by smoke particles Horizontal optical bench housing an infrared emitter and sensor arranged radially to detect forward scattered light Silicon PIN photo-diode GaAs Infrared light emitting diode Once every 10 seconds Once every 2 seconds 3 Two wire monitored supply, polarity insensitive L1 IN and L2: supply in connections (polarity insensitive) L1 OUT and L2; supply out connections (polarity insensitive) R; remote indicator negative connection 17 to 28V DC 2V peak to peak maximum at 0.1Hz to 100kHz 30 to 45A at 24V 90A at 24V 6 to 28V 61mA at 28V 52mA at 24V 18mA at 10V Red Light Emitting Diode (LED) emitting red light 450 in series with a 3V drop (LED open circuit) 6V (min) 10mA (min) 12V 1V 1 second 900 in series with a 3V drop at 24V with 500 line impedance gives: 1mA at 9V 4.5mA at 5V 8.0mA at 1V Nominal threshold of 3.0% light grey smoke obscuration per meter to EN 54 Part 7 1984; (BS 5445 Part 7 1984) -20C to +60C Negative temperature coefficient thermistor 0% to 95% relative humidity (no condensation) 44

Supply Voltage: Ripple Voltage: Quiescent Current: Switch-on Surge Current: Alarm Voltage: Normal Alarm Current: Alarm Indicator: Design Alarm Load: Holding Voltage: Holding Current: Minimum Voltage Required to Light Alarm Indicator: Alarm Reset Voltage: Alarm Reset Time: Remote Output Characteristics:

Sensitivity: Temperature Range: Temperature Compensation: Humidity:

HazardWatch

Wind Speed: Atmospheric Pressure: Vibration: Impact: Shock: Static:

Radiated Emissions: Radiated Susceptibility: IP Rating: Dimensions: Weights: Materials: Terminals:

Insensitive to wind Insensitive to atmospheric pressure To EN 54 Part 7 1984 (BS 5445 Part 7 1984) To EN 54 Part 7 1984 (BS 5445 Part 7 1984) To EN 54 Part 7 1984 (BS 5445 Part 7 1984) IEC 801-2 (BS 6667 Part 2 1985) Severity Level 3. Tested to 12,000V positive and negative to the case and supply terminals from a 250pF capacitor BS 6527 Class B IEC 801 Part 3 Class 3 (10V/m). Tested to 90V/m from 27MHz to 1GHz 43 Detector: 100mm x 42mm (diameter x height) Detector in Base: 100mm x 50mm (diameter x height) Detector: 99 grams Detector in Base: 150 grams Detector housing: White polycarbonate V-O rated to UL 94 Stainless steel

45

HazardWatch

1.7 Audible Devices


1.7.1 Federal Signal Model 50 GC Selectone Horn
Specifications: Solid-state circuitry Available in 24VAC/24VDC, 120VAC and 230/240VAC Built-in gain control Produces 64dB to 88dB @ 10' (74dB to 98dB @ 1m) UL and cUL Listed, CSA Certified, CSFM Approved (California State Fire Marshal) Flush or surface mount NEMA 3R, IP55 enclosure Operating Temperature: Net Weight: Shipping Weight: Height: Width: Depth: Model 50GC 50GC 50GC 50GC Voltage 24VDC 24VAC 50/60Hz 120VAC 50/60Hz 230/240VAC 50/60Hz -31F to 161F, -35C to 72C 1.7 lbs., 0.8 kg 2.2 lbs., 1.0 kg 4.50", 14 mm 4.50", 114 mm 3.44", 87 mm Operating System 0.07 amps 0.22 amps 0.04 amps 0.02 amps Sys. Standby Current 0.025 amps 0.095 amps 0.027 amps 0.013 amps Decibels @ 101M 88 98 88 98 88 98 88 98

1.7.2 Federal Signal Model 300 GCX Selectone Horn


Specifications: Designed for use in Hazardous locations Reliable, solid-state circuitry Available in 24VAC/DC, 120VAC and 240VAC Built-in gain control allows volume adjustment from 86dBA to 110dBA at 10' (96dBA to 120dBA at 1m) UL-Listed CSA-Approved & CSFM Approved 46

HazardWatch

NEMA Type 3R enclosure; constructed to IP55 Operating Temperature: Net Weight: Shipping Weight: Height: Width: Depth: -31F to 161 F, -35C to 72 C 5.2 lbs., 2.4 kg 6.7 lbs., 3 kg 12.25", 311 mm 8.00", 203 mm 8.25", 210 mm

Federal Signals SelecTone Model 300GCX provides audible signals for warning in areas where hazardous materials are stored. The unit has a built-in volume control and a choice of many separate tones that can be heard clearly despite the many ambient noises in a plant. This unit can be used as a single audible device or as part of a SelecTone system activated by automatic detection devices or a push-button command control. The SelecTone model 300GCX is offered in 24VAC/DC, 120VAC or 240VAC voltages. Its sturdy construction consists of a die-cast aluminum amplifier housing and a spun aluminum speaker projector, which are both coated with a gray enamel finish. A conformal coating protects the units PC board and components. The internal gain control allows tone output to be adjusted for 86dBA to a maximum of 110dBA at 10 feet (96dBA to 120dBA at 1m). The SelecTone model 300GCX can be used as a stand-alone, single signal audible warning device or as part of a plant-wide communication and paging system. Model 300GCX is recommended for use in Division 2 environments where flammable dusts, liquids, and gases are confined in closed containers,but present potential dangers in the form of accidental ruptures or spillages. This unit is UL(Underwriters Laboratories) listed and CSA (Canadian Standards Association) approved for Class I, Division 2, Groups A, B, C and D; Class II, Division 2, Groups F & G hazardous locations. Like the 300GC, Federal Signals model 300GCX allows for volume to be adjusted to overcome ambient noise levels. Model 300GCX is approved for use in Division 2 environments. Typical applications include emergency warning, start and dismissal, general alarm, evacuation and paging. Model 300GCX 300GCX 300GCX 300GCX Voltage 24VDC 24VAC 50/60Hz 120VAC 50/60Hz 2240VAC 50/60Hz Operating System 0.55 amps 1.25 amps 0.27 amps 0.14 amps Sys. Standby Current 0.06 amps 0.13 amps 0.03 amps 0.02 amps Decibels @ 101M 110 120 110 120 110 120 110 120

1.7.3 Federal Signal Model 300X & 302X Selectone Horn


Specifications: Explosion proof environments Available in 24VAC/DC, 120VAC and 240VAC 47

HazardWatch

Built-in gain control allows volume adjustment On the 300X: from 80dB to 104dB at 10' (90dB to 114dB at 1m); On the 302X: from 90dB to 114dB at 10'; 100dB to 124dB at 1m UL-Listed, CSA- & CSFM Approved NEMA Type 3R enclosure; rated for IP44 Specifications for 300X: Net Weight: Shipping Weight: Height: Width: Depth: 18 lbs., 8.2 kg 19 lbs., 8.6 kg 14.75", 375 mm 8.88", 225 mm 14.75", 375 mm

Model
300X 300X 300X 300X 302X 302X

Voltage
24VDC 24VAC 50/60Hz 120VAC 50/60Hz 2240VAC 50/60Hz 24VDC 24VAC 50/60Hz

Operating System 0.50 amps 1.30 amps 0.27 amps 0.13 amps 1.10 amps 1.10 amps

Sys. Standby Current 0.06 amps 0.13 amps 0.03 amps 0.02 amps 0.13 amps 0.03 amps

Decibels @ 10-1M 104 114 104 114 104 114 104 114 114 124 114 124

1.7.4 Federal Signal Model 41-X Selectone Horn


Specifications: Designed for use in explosion proof atmospheres Resonating and vibrating horns Featuring corrosion-resistant cast aluminum housings Decibel ratings range from 100-107dB @ 10' (110-117dB @ 1m) Meets NEMA 4X specifications; constructed to IP44 These Federal Signal explosion proof horns are constructed for safety in hazardous environments. They have heavy-duty die cast aluminum housings which are tapped for 3/4 conduit. Models 31X and 41X Federal Signal models 31X and 41X are corrosion-resistant vibrating horns with stainless steel diaphragms. Model 41X is available in 24VDC while model 31X is available in 120VAC, and features an internal volume control.

48

HazardWatch

Both models are UL listed (Underwriters Laboratories) for Class I, Division 1, Groups C & D; Class I, Division 2, Groups C & D; Class II, Division 1, Groups E, F, and G and Class III. Both are CSA (Canadian Standards Association) approved. Models 55X and 56X Federal Signal models 55X and 56X are resonating electric horns which produce sound by means of a diaphragm which resonates a column of air. Their gray enamel finished housings are tapped for 3/4 conduit. Model 55X is available in 120VAC, while model 56X is available in 125VDC. Model 55X is UL listed for Class I, Division 1, Groups C & D; Class I, Division 2, Groups C & D; Class II, Division 1, Groups E, F & G and Class III. Both model 55X and 56X are CSA (Canadian Standards Association) approved. These vibrating and resonating explosion-proof horns are designed for locations such as refineries, laboratories, mines or grain elevators where the danger of explosion or fire exists. Operating Temperature: -31F to 150F, -35C to 66C Net Weight: (31X) 7.5 lbs., 3.4 kg (41X) 9.0 lbs., 4.1 kg (55X) 10.5 lbs., 4.8 kg (56X) 10.5 lbs., 4.8 kg Shipping Weight: (31X) 8.1 lbs., 3.7 kg (41X) 10.3 lbs., 4.7 kg (55X) 12.5 lbs., 5.7 kg (56X) 15.5 lbs., 7kg Model Voltage Amperage Decibels @ 101M 31X 120VAC 50/60Hz 0.20 100 110 31X 240VAC 50/60Hz 0.10 100 110 41X 24VDC 1.20 100 110 55X 120VAC 60Hz 0.65 105 115 56X 125VDC 0.50 107 117

1.7.5 MEDC XB3 Horn


Zone 1, Zone 2 and non-Ex use. EExde IIC T5. ATEX approved, Ex II 2GD. Optional Exe terminal chamber. BASEEFA certified. UL Listed for USA and Canada 49

HazardWatch

Hazardous locations: Class I, Div 2, Groups A-D. Class I, Zones 1 & 2, AExd IIC T4. Ordinary locations: Audible-Signal Device. GOST R & K certified. Chinese (CQST) certified. Australian (SAA) certified. IP66 and IP67. *Certified temperature 55C to +70C. All GRP corrosion free flamepaths. Up to 118dBA output. Integral volume control. 27 tones, user selectable. Tones comply with UK00A/PFEER guidelines. Any two tones may be switched via the external voltage supply. Tones may be programmed to customer specification. d.c. version accepts any voltage between12V d.c. and 48V d.c. End of line resistor option. Sounder/Beacon Combination Unit available. *Depending on version. Certifications: CENELEC EN50014, 18, 19. BASEEFA Cert. No. BAS00ATEX2097X, EExd IIC. BASEEFA Cert. No. BAS00ATEX2098X, EExde IIC. Zones 1 and 2. UL Listed for USA and Canada Hazardous locations: Class I Div 2, Groups A-D. Class I Zones 1 & 2, AExd IIC T4. Listing No: E203310. Ordinary locations: Audible-Signal Device. Listing No. S8116. Refer to UL data sheet at rear of catalogue for 50

HazardWatch

Material: Finish: Sound Output: Short Flare: Volume Control Nominal Output (dBA) 93 105 108 111 112 114 115 Weight: Ingress Protection: Fire Retardancy: Voltage: Certified Temperature EExd DB3 & DB3P DB3L & DB3LP -20C to +70C -55C to +55C V 12V d.c. 24V d.c. 48V d.c. 110V a.c 120V a.c. 220V a.c. 240V a.c. 254V a.c. Terminals: Earth Continuity: Mounting: EExde -20C to +45C -55C to +70C

complete information. GOST R Certification: 1Exd IIC T4 & 1Exde IIC T4. GOST K Certification: 1Exd IIC T4. Chinese (CQST) Certification: Exd IIC T4. Body & horn in anti-static, UV stable, glass reinforced polyester. Swivel bracket & captive cover screws in stainless steel. Body and horn, natural black or epoxy paint coated to clients colour requirements. Long Flare: 115dB(A) 3dB(A) (tone dependent). 108dB(A) 3dB(A) (tone dependent).

Input Current (mA) 50 100 150 200 250 300 350 6.0kg approx. dependent on model (+0.5kg for EExe). IP66 and IP67 GRP is fire retardant to ISO 1210 Up to 48V d.c. Up to 254V a.c UL -55C to +70C n/a GOST R&K -20C to +50C -55C to +55C GOST R Exde -20C to +40C -55C to +55C I 760mA 380mA 190mA 135mA 124mA 68mA 62mA 59mA 4 x 2.5mm2 (a.c.), 6 x 2.5mm2 (d.c.). Included on EExde version. Stainless steel bracket with ratchet facility. 51 Chinese Exd -20C to +55C n/a

*Output measured with 24V input voltage. Tone set to 970Hz continuous.

Current Consumption

HazardWatch

Labels: Cable Entries:

Duty and tag labels optional. Up to 2 x 20mm EExd 2 x 20mm EExe. Up to 2 x 1/2" NPT UL. Note: ATEX/UL Dual Listed version only up to 1/2" NPT available. 27 user selectable tones. The DB3 may be combined with an MEDC beacon to create a combined audio/visual alarm. Contact MEDC for price and specification Switchable between any two tones by either: (i) Reversing the polarity of the supply, or (ii) by a 3 wire common +ve system, switching between the two ve lines. Note: Two-stage unit available in d.c. versions only. Remote 3 or 4 tone available contact sales office for details.

Tone Selection: Sounder/Beacon Unit:

Two Stage Unit DB3P:

3/4 Tone Unit:

52

HazardWatch

53

HazardWatch

1.7.6 Notifier Spectralert Horn


Specifications: Horn shall be a System Sensor SpectrAlert Model capable of operating at 12 and 24 volts. Horn shall be listed to UL 464 for fire protective signaling systems. The horn shall have two-tone options, two audibility options (at 24 volts) and the option to switch between a temporal 3 pattern and a non-temporal continuous pattern. All horn models shall operate on a coded power supply. Walk Test SpectrAlert horn/strobe and horn only work on walk tests with time durations of 4 seconds or greater. Input Terminals Dimensions Strobe and horn/strobe with universal plate: Strobe and horn/strobe with small footprint plate: Horn with universal mounting plate: Horn without mounting plate: Weight, horn only: Weight, strobe and horn/strobe: Mounting: Environment Indoor Operating Temperature: Weatherproof (horn and horn/strobes) Operating Temperature: (Outdoor strobe only): ULC Canadian Models: Electrical Voltages Operating voltage range* Operating voltage range* 12 or 24VDC and FWR unfiltered 12V: 10.5-17V; 24V: 20-30V 12V, 11-17V; 24V, 20-30V (with SyncCircuit module, MDL) 32F to 120F (0C to 49C) 32F to 150F (0C to 66C) -40F to 158F (-40C to 70C) -40C to 66C 5" x 5 5/8" x 215/16" 33/8" x 5 5/8" x 25/16" 5" x 5 5/8" x 15/16" 215/16" x 5 5/16" x 15/16" 7.2 oz. 8.8 oz. 4" x 4" x 1 1/2" or 2" x 4" x 1 7/8" standard boxes 12 to 18 AWG

* These products should be operated within their rated voltage range; UL does, however, test functional integrity to -20% and +10% of manufacturer's stated ranges.

1.7.7 Notifier Spectralert Horn 1.7.8 Crouse Hinds ESR Fire Alarm Bell
Specifications: Application: ESR bell signals are used: for call signals, alarms, or in various other signaling applications in specific hazardous atmospheres such as in chemical plants, oil and gas refineries, bulk loading stations, paint and varnish manufacturing plants, grain processing industries and 54

HazardWatch

grain elevators, as well as in certain metal, coal, combustible fiber processing or handling areas in conduit systems, and mounted on a vertical flat surface with the striker at the bottom Features: The conduit hub contains an integral bushing. The body cover assembly permits the location of a hub at the top, bottom or either side (the striker must be located at the bottom for proper operation). There are no external seals required except when used in Group B hazardous areas. The ac signal does not have arcing contacts. The dc signal is provided with a GUAC junction box, with factory sealed wire leads in the interconnecting nipple and hub. Binding screw terminals are provided in ac signals for supply conductors. A vibrating or single stroke striker mechanism is furnished with 6 or 10 inch diameter gongs. Standard Materials: Body - Feraloy iron alloy Cover - copper-free aluminum Junction box - body - Feraloy iron alloy - cover - copper-free aluminum Gong - steel Standard Finishes: Feraloy iron alloy - electrogalvanized and aluminum acrylic paint Aluminum - natural Steel - gray matte Size Ranges: Hub - one 3/4" size

Operating Current in Amperes at the Nominal Voltage For Bell Signals Amperes NOM Volts 12 24 48 115 230 All Vibrating 25 to 60 Hertz AC 1.67 .53 .44 .189 .092 55 All Single Stroke 50 to 60 Hertz ACDC 2.40 1.53 .95 .42

DC 1.69 1.75 .63 .62 .65 .41 135 .189 .086

HazardWatch

Bell S i g n a l s
Single Stroke Hammer (50 to 60 hertz) Cat. # ESR2665 ESR2664

Vibrating Hammer (25 to 60 hertz) Standard Hub Size Supply Nom. Volts 12 24 Voltage Range 9.6 to 13.2 19.2 to 26.4 Dia. Bell Units Units# ESR2675ESR2674Group B

Sound Pressure Levels at 10' Exceed (dB) 67 82

Sound Pressure Levels at 10' Exceed (dB) 64 64

Cat. # Cat. # ESR2675 GB ESR2674 GB ESR2673 GB ESR2672 GB

ESR267388 ESR267288 ESR2662 67 ESR2663 67

48 115

38.4 to 52.8 92 to 126.5

'% a

AC AC

230

184 to 253

ESR2671 GB ESR2615 GB ESR2614 GB 10 ESR2613 GB ESR2612 GB ESR2611 GB ESR2875 ESR2874 6 ESR2873 ESR2872 ESR2815 ESR2814
10

ESR267185 ESR261582 ESR261485 ESR261385 ESR261291 ESR261185 85 88 88 85 88 85 88 88 ESR2621 ESR2865 ESR2864 ESR2863 ESR2862 ESR2825 ESR2824 ESR2823 ESR2822 67 64 67 70 67 67 67 73 76 ESR2622 67 ESR2623 67 ESR2624 64 ESR2625 64 ESR2661 67

12 24 48 115

9.6 to 13.2 19.2 to 26.4 38.4 to 52.8 92 to 126.5

230 12 24 48 'A DC 115 12 24 48 115

184 to 253 9.6 to 13.2 19.2 to 26.4 38.4 to 52.8 92 to 126.5 9.6 to 13.2 19.2 to 26.4 38.4 to 52.8 92 to 126.5

ESR2813 ESR2812

56

HazardWatch

1.7.9 Pyrotronics MBDC-6 Fire Alarm Bell


Series MBDC Motor Bells & Strobe Bells UL Listed for Fire Protective Service. High Sound output with low current draw. Low frequency aluminum shells for better audibility through walls, doors and other structures. Both 6 and 10 shell sizes in 24 VDC models. Integral RFI suppression to minimize induced noise on the alarm lines. Mounting options for surface, semi-flush, outdoor and concealed conduit installation. Built-in trimplate makes semi-flush mounting simpler and less expensive. Screw terminals permit fast in-out field wiring of 12-22 AWG wire. Polarized for DC supervision of alarm lines. Operate on filtered or unfiltered DC over a wide voltage range. Strobe bells for combined audible and visual signaling have single input to save wiring time for 2-wire tandem operation of bell and strobe.

Architects Specifications The alarm signals shall be Pyrotronics Series MBDC vibrating Motor Bells or approved equal. They shall be UL Listed for Fire Protective Service. Shells shall be aluminum in 6 or 10 diameter. Sound output at 10 feet shall be 92 dBA. The bells shall incorporate a carbon brush motor and suppression to minimize RFI. They shall include a built-in trimplate for semi-flush mounting to standard 4 backboxes, or surface mounting to Pyrotronics indoor IBH-2 backbox or outdoor WBK-3 backbox. Strobe bell models shall include an integral flashing strobe light with white polycarbonate lens and red Fire lettering. The strobe shall be factory wired to operate in unison with the bell and shall produce 8000 peak candlepower at approximately one flash per second. The strobe bells shall semi-flush mount to standard 4 square backboxes, or surface mount using Pyrotronics SB backbox. All bell and strobe bell models shall be polarized for line supervision and shall have screw terminals for in-out field wiring of 12-22 AWG wire. Operating voltage shall range from 19.2-28.8 VDC. Finish on all models shall be textured red enamel.

57

HazardWatch

1.8 Visual Devices


1.8.1 Federal Signal Model 191 X Strobe Light
Specifications: 24 to 250 VAC or VDC Six tempered glass dome colors Uses standard A-19 incandescent lamp (40W-100W) 3/4-inch pipe mount Dome Guard included UL Listed, CSA Certified for in door/outdoor use NEMA 4X, IP66 enclosure Lamp Style: Operating Voltage: Mount: Net Weight: Shipping Weight: Height: Diameter: Operating Temperature Chart Hazardous Environment Class I, Division 2 Max. Temperature*/ UL Temp. Code 350C/T2 325C/T2 260C/T2B 215C/T2D 200C/T3 Dome Color Blue Red, Amber Clear All All Green, Lamp Wattage 100 (A-19) 100 (A-19) 100(A-19) 40(A-19) 40(A-19) Supply Wire Insulation Rating 125C 125C 125C 85C 85C Incandescent A-19s (40W-100W) 24-250VAC/DC, 24-250VAC/DC 3/4" Pipe, 3/4" Pipe 3.3 lbs., 1.5 kg 4.2 lbs., 1.9 kg 8.75", 222.25 mm 5.5", 139.7 mm

Class II, Div. 1 Groups E, F * at 40 ambient

1.8.2 Federal Signal Model 151 XST Strobe Light


Specifications: Available in 12-24VDC, 120VAC and 240VAC Six dome colors 58

HazardWatch

10,000-hour high-intensity strobe 3/4-inch pipe mount Dome guard included UL Listed, CSA Certified for indoor/outdoor use NEMA 4X, IP66 enclosure Marine Rated Lamp Life*: Lamp Style: Operating Temperature Net Weight: Shipping Weight: Height: Diameter: * Optimal hours under ideal conditions. Model
151XST 151XST 151XST
1

10,000 hours, 10,000 hours Strobe, Strobe -31F to 150F, -35C to 66C 3.8 lbs., 1.7 kg 4.5 lbs., 2.0 kg 8.75", 222.25 mm 5.5", 139.7 mm ECP2
165 165 165

Voltage
12-24VDC 120VAC 50/60Hz 240VAC 50/60Hz

Operating Current
1.3-0.60 amps 0.32 amps 0.16 amps

Flash Rate/Minute
80 80 80

Candlepower Peak1
520,000 520,000 520,000

Mount

" Pipe " Pipe " Pipe

Peak candlepower is the maximum light intensity generated by a flashing light during its light pulse ECP (Effective Candlepower) is the intensity that would appear to an observer if the light were burning steadily
2

1.8.3 Federal Signal Model 27XST Strobe Light


Specifications: Available in 24VDC, 120VAC and 240VAC Six lens colors 10,000 hour, strobe tube 3/4-inch pendant mount standard Dome guard optional UL Listed, CSA Certified 59

HazardWatch

NEMA 4X, IP66 enclosure Marine Rated Lamp Life*: Lamp Style: Net Weight: Shipping Weight: Height: Diameter: * Optimal hours under ideal conditions. Model Voltage Operating Current 1.25 amps 0.60 amps 0.30 amps Flash Rate/ Minute 80 80 80 Candlepower Peak1 2,000,000 2,000,000 2,000,000 ECP2 Mount 10,000 hours, 10,000 hours Strobe, Strobe 14 lbs., 6.4 kg 18.1 lbs., 8.2 kg 15.63", 397 mm 8.82", 224 mm

27XST 27XST 27XST


1

24VDC 120VAC 50/60Hz 240VAC 50/60Hz

850 850 850

"
Pendent

"
Pendent

"
Pendent

Peak candlepower is the maximum light intensity generated by a flashing light during its light pulse ECP (Effective Candlepower) is the intensity that would appear to an observer if the light were burning steadily
2

1.8.4 Federal Signal Model 121 X Rotating Light


Specifications: Available in 24VDC and 120VAC Five lens colors 3/4-inch pendant mount standard; other options available UL Listed, CSA Certified, Marine Rated Dome guard optional NEMA 4X, IP66 enclosure Lamp Style Lamp Life*: Operating Temp: Net Weight: Shipping Weight: Incandescent, Incandescent 800 Hours, 800 Hours -31F to 150F, -35C to 66C 14.75 lbs., 6.69 kg 18.9 lbs., 8.57 kg 60

HazardWatch

Height: Diameter:
* Optimal hours under ideal conditions.

15.63", 397 mm 8.82", 224 mm

Model

Voltage

Operating Current
1.05 amps 0.33 amps

121X 121X

24VDC 120VAC 60Hz

Flash Rate/ Minute 90 90

Candlepower

Mount

2,350 1,800

"
Pendent

"
Pendent

61

HazardWatch

1.8.5 MEDC XB-3 Strobe Light


Specifications: Zone 1 and Zone 2 use. Class 1, Div. 1 EExd, EExde IICT4/T6. CENELEC approved. BASEEFA Certified. CSA Certified. UL Listed (SM87 HXBA only). GOST Certified. IP66 and IP67. Stainless steel or marine grade alloy. Xenon or LED versions. Optional EExe terminal chamber. Various lens colours. Optional lens guard. Telephone or relay initiated. Certification BASEEFA EExdIIC T6 (HXB & LED). EExde IIC T6 (XB3 & LED3). Cert. No. Ex88B1232 (HXB & LED). Ex 92C 1389 (XB3 & LED3). CENELEC EN50014 and EN50018 and EN50019. CSA Certification to C22.2 Nos. 0, 0.4, 0.5, 9, 30M1986, 94-M91, 137-M1981. Class 1. Div 1. Group D. Enclosure 3/4. Cert. No. 96406. (SM87 HXB only). UL Listed for Class 1, Div. 1, Groups C + D (SM87 HXB only). GOST Certification: Contact MEDC for specification HXBS and LEDS Grade 316 ANC4B Stainless Steel. HXBA & LEDA LM25 TF Marine Grade Alloy. Toughened Glass Epoxy paint finish as standard or to customer's specification

Material: Lens: Finish:

NOTE: Terminal Chamber available only in Stainless Steel. UL version is available only in marine grade alloy. CSA version available only in stainless steel 62

HazardWatch

For Colored Lenses Color Multiplying Factor Red 0.15 Blue 0.12 Amber 0.51 Green 0.49 Yellow 0.86

The photometric data has been verified by BSI. A report is available if required.

63

HazardWatch

LED Light Output Steady or Flashing (Customer selectable)

Color Red Amber Green Blue

Total LED Output (Candela) 192 64 17 64 Red, Blue, Green, Amber, Yellow (not LED) or Clear (not LED). HXBS & LEDS 3.8kg each (approx). XB3 & LED3 4.5kg (approx). 2kg. each (approx.). HXB = 55C to +55C. XB3 = 20C to +40C. LED = 20C to +40C. 20C to +40C.

LED/Lens Color: Weight: HXBA & LEDA: BASEEFA Operating Temperature: LED3:

Versions are available certified up to +55C maximum with a T4 rating. UL Operating Temperature: Ingress Protection: Terminals: HXB: LED: Termination: HXB = 25C to +40C. IP66 & IP67. XB3&LED36offsuitableforupto6mm2 cable. (With telephone initiate 8 x 2.5mm2). 4 off suitable for up to 2.5mm2 cable. 6 off suitable for up to 2.5mm2 cable. Models HXB & LED use a single Exd chamber.

Models XB3 & LED3incorporate an Exe chamber for termination. Telephone initiation or relay interface: Initiation by telephone ringing tone or low voltage control signals. Labels: Entries: Duty & Tag Labels optional. Up to 4 x 20mm / 25mm ISO or 1/2" / 3/4" NPT. (HXB, LED). 3 x 20mm or 25mm ISO (XB3, LED3)

64

HazardWatch

1.8.6 MEDC XB-11 Strobe Light


Specifications: Zone 1 and Zone 2 use. Exd IIB T4, T5 & T6. ATEX approved, Ex II 2GD. BASEEFA certified. UL Listed for USA and Canada Hazardous locations: Class I, Div 2, Groups C & D. Class I, Zones 1 & 2, AExd IIB T4/T5. Ordinary locations: Visual-Signal Device. Australian (SAA) certified. Chinese (CQST) certified. I P66 and IP67. Certified temperature 55C to +70C. Corrosion resistant GRP. Optional stainless steel backstrap. Various lens colours. Optional lens guard. Optional telephone initiation. 2 x M20 cable entries or 2 x 1/2" NPT*. Earth continuity option (model dependent). Filament version (20W) available. Fluorescent version (10W) available. Beacon/Sounder Combination Unit available. *Model dependent. See FL11, FB11, FL12, FB12 data sheet.

65

HazardWatch

Certification: CENELEC EN50014 and EN50018. Cert. No. BAS99 ATEX 2195X. EExd IIB +40C) T6. 135C (-55 t.amb +70C) T4., 100C (-55 t.amb +55C) T5., 85C (-55 t.amb

UL Listed for USA and Canada to: Hazardous locations: Class I, Div 2 Groups C & D. Class I, Zones 1 & 2 AExd IIB T4/T5. UL Listing No: E187894. Ordinary locations: Visual-Signal Device. UL listing No. S8128. Refer to UL Datasheet at rear of catalogue for complete information. Chinese (CSQT) Certification: Exd IIB T5/T6. Material: Lens: Cover Screws + Backstrap: Finish: Body: Glass reinforced polyester (GRP) Glass Stainless steel 316 Natural black or painted to customer specification

DC Voltage 24 XB11 Tube Energy (Joules) 5 Peak Current Consumption (mA) 320 Effective Intensity (Cd) 29 Peak Intensity (Cd) 22213 Power Consumption (Watts) 8 NOTE: The Cd figures are for a clear lens @ 1Hz flash rate For Colored Lenses Color Multiplying Factor Red 0.15 Blue 0.12 Amber 0.51

AC50/60 Hz 110 240

5 100 29 22213 11

5 60 29 22213 18

Green 0.49

Yellow 0.86

The photometric data has been verified by BSI. A report is available if required. Weight: Certified Temperature: 2.5Kg. EExd 55C to +70C (T4). 55C to +55C (T5). 55C to +40C (T6). UL 55C to +70C (hazardous locations). 66

HazardWatch

Ingress Protection: Fire Retardancy: Earth Continuity: Terminals: Telephone initiation: Labels: Entries: Beacon/Sounder Unit:

55C to +55C (ordinary locations). IP66 & IP67 GRP is fire retardant to ISO 1210 Optional for metal glands provided via a brass plate. (Not available for UL version). 6 x 2.5mm2 Initiation by telephone ringing tone Duty/Tag Label optional 2 x 20mm ISO EExd. 2 x " NPT UL. The beacon may be combined with an MEDC sounder to create a visual/audible alarm. Contact MEDC for price and specification.

NOTE: ATEX/UL Dual Listed unit has up to 2 x " NPT entries only.

1.8.7 Notifier Spectralert Strobe


Specification: Walk test: SpectrAlert horn/strobe and horn only work on walk tests with time durations of 4 seconds or greater. Input terminals: Dimensions, strobe and horn/strobe with universal plate: Weight, strobe and horn/strobe: Mounting: Operating temperature 12 to 18 AWG (3.25 mm to 0.51 mm) 5" (12.7 cm) wide x 5.625" (14.288 cm) high x 2.938" (7.461 cm) deep; with small footprint plate: 3.375" (8.573 cm) wide x 5.625" (14.288 cm) high x 2.938" (7.461 cm) deep. 8.8 oz. (250 g) Standard boxes 4" x 4" x 1.5" deep (10.16 x 10.16 x 3.81 cm) or 2" x 4" x 1.875" deep (5.08 x 10.16 x 4.763 cm). Indoor: 32F to 120F (0C to 49C) Outdoor: Weatherproof Horn/Strobe 32F to 150F (0C to 66C) Strobe -40F to 158F (-40C to 70C), ULC Canadian strobe model -40C to 66C. 95% as tested per UL 464. 12 or 24 VDC and FWR unfiltered. 12V 8 17.5 V 24V: 16 33 V. With Sync-Circuit module MDL*: 12V: 9 17.5 V. 24V: 17 33 V. 5,593,569. 5,914,665. 6,049,446.

Maximum humidity: Voltages: Operating voltage range*: U.S. Patent Numbers:

*Note for Strobe: Do not exceed; 1) 16-33 or 8-17.5 voltage range limit; 2) maximum number of 70 strobe lights when connecting the MDL Sync Module with a maximum line impedance of 4 ohms per loop and; 3) maximum line impedance as required by the fire alarm control manufacturer.

67

HazardWatch

Engineering Specifications General SpectrAlert horns, strobes and horn/strobes shall be capable of mounting to a standard 4" x 4" x 1.5" (10.16 x 10.16 x 3.81 cm) backbox or a single-gang 2" x 4" x 1.875" (5.08 x 10.16 x 4.763 cm) backbox using the universal mounting plate included with each SpectrAlert product. Also, SpectrAlert products, when used in conjunction with the accessory SyncCircuit Module, shall be powered from a non-coded power supply and shall operate on 12 or 24 volts. 12-volt rated devices shall have an operating voltage range of 9 17.5 volts. 24-volt rated devices shall have an operating voltage range of 17-33 volts. SpectrAlert products shall have an indoor operating temperature range of 32F to 120F (0C to 49C) and operate from a regulated DC or full-wave rectified, unfiltered power supply. Strobe Strobe shall be a System Sensor SpectrAlert model _________ Listed to UL 1971 and be approved for fire protective service. The strobe shall be wired as a primary signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobes entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Horn/Strobe Combination Horn/strobe shall be a System Sensor SpectrAlert model _________ Listed to UL 1971 and UL 464 and shall be approved for fire protective service. Horn/strobe shall be wired as a primary signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobes entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have two tone options, two audibility options (at 24 volts) and the option to switch between a temporal 3 pattern and a non-temporal continuous pattern. Strobes shall be powered independently of the sounder with the removal of factory-installed jumper wires. The horn on horn/strobe models shall operate on a coded or non-coded power supply (the strobe must be powered continuously). Synchronization Module Module shall be a System Sensor SyncCircuit model _________ Listed to UL 464 and shall be approved for fire protective service. The module shall synchronize SpectrAlert strobes at 1 Hz and horns at temporal 3. Also, the module shall silence the horns on horn/strobe models, while operating the strobes, over a single pair of wires. The module shall be capable of mounting to a 4.688" (11.906 cm) square x 2.125" (5.398 cm) deep backbox and shall control two Style Y (Class B) or one Style Z (Class A) circuit. Module shall be capable of multiple zone synchronization by daisy-chaining multiple modules together and resynchronizing each other along the chain. The module shall NOT operate on a coded power supply.

68

HazardWatch

69