Zelio Control measurement and control relays

RM4 : 4233256 - 4233414


Selection guide
Available 2nd Quarter 2001

Applications

Current measurement a and c

Voltage measurement a and c

Control of single-phase supplies Undervoltage and overvoltage (2 controlled thresholds)

Control of 3-phase supplies

Overcurrent

Undercurrent or overcurrent

Overvoltage

Undervoltage or overvoltage

Measurement or control

Adjustable threshold 0.0031 A

Adjustable thresholds 0.0031 A or 0.315 A depending on model

Adjustable thresholds 0.055 V or 1100 V or 30500 V depending on model

Adjustable thresholds undervoltage: 80120 V or 160220 V overvoltage: 160220 V or 220330 V depending model

Control: rotational direction and presence of phases 200500 V

Supply voltage

c 24 V c 110130 V c 220240 V

z 24240 V c 110130 V c 220240 V c 380415 V

c 24 V c 110130 V c 220240 V

z 24240 V c 110130 V c 220240 V c 380415 V

Self-powered relays

Number of output relay contacts

1 C/O

2 C/O

1 C/O

2 C/O

Output relay state

Energised when threshold is exceeded

Energised during fault free operation. De-energised on detection of a fault.

Built-in time delay

None

Adjustable 0.05 to 30 s

None

Adjustable 0.05 to 30 s

None

Type

RM4-JA0

RM4-JA3

RM4-UA0

RM4-UA3

RM4-UB3

RM4-TG20

Pages

3/35

3/35

3/41

3/41

3/52

3/48

3/28

Te

Available 2nd Quarter 2001

Control of 3-phase supplies

Liquid level control

Control: rotational direction and presence of phases, undervoltage 200...500 V, adjustable threshold

Control: rotational direction and presence of phases, undervoltage, overvoltage 200...500 V, adjustable or fixed thresholds

Control: rotational direction and presence, of phases, asymmetry of phases 200500 V.

Measurement of liquid resistance by submersible probes

Self-powered relays

c 24 V c 110130 V c 220240 V c 380415 V

z 24240 V c 110130 V c 220240 V c 380415 V

2 C/O

1 C/O

2 C/O

1 C/O

2 C/O

Energised during fault free operation. De-energised on detection of a fault.

Empty function: Energised: high electrode immersed. De-energised: low electrode not immersed. Fill function: Energised: low electrode not immersed. De-energised: high electrode immersed. Adjustable 0.1 to 10 s None 0.1 to 10 s Adjustable

None

Adjustable 0.1 to 10 s

Fixed 0.5 s

RM4-TU

RM4-TR

RM4-TA0

RM4-TA3

RM4-LG01

RM4-LA32

3/48

3/48

3/48

3/48

3/56

3/56

Te

3/29

Zelio Control - measurement and control relays


Current and voltage measurement relays : pages 3/32 to 3/43 3-phase supply control relays : pages 3/44 to 3/49 Single-phase supply control relays : pages 3/50 to 3/53 Liquid level control relays : pages 3/54 to 3/57

General characteristics

Environment
Conforming to standards Product approvals marking Ambient air temperature around the device Permissible relative humidity range Vibration resistance Storage Operation Conforming to IEC 60721-3-3 Conforming to IEC 6068-2-6, 10 to 55 Hz Conforming to IEC 6068-2-27 Casing Terminals Degree of pollution Overvoltage category Rated insulation voltage Conforming to IEC 60664-1 Conforming to IEC 60664-1 Conforming to IEC Conforming to CSA Test voltage for insulation tests Voltage limits Frequency limits Disconnection value Mounting position without derating Connection Maximum c.s.a. Tightening torque Dielectric test Shock wave Power supply circuit Power supply circuit Power supply circuit In relation to normal vertical mounting plane Flexible cable without cable end Flexible cable with cable end mm2 mm2 N.m V V kV kV C C IEC 60255-6, EN 60255-6 CSA, GL, UL, pending Zelio Control measurement relays conform to European regulations relating to marking - 40+ 85 - 20+ 65 1585 % Environmental class 3K3 a = 0.35 ms 15 gn - 11 ms IP 50 IP 20 3 III 500 (1) 2.5 4.8 0.851.1 Uc (2) 50/60 5 % > 0.1 Uc (2) Any position 2 x 2.5 2 x 1.5 0.61.1

Shock resistance Degree of protection

Immunity to electromagnetic interference (EMC) (Application class 2 conforming to EN 61812-1)


Electrostatic discharge Electromagnetic fields Fast transients Shock waves Radiated and conducted emissions (1) Value not communicated. (2) Except RM4-T, see page 3/47. Conforming to IEC 61000-4-2 Conforming to IEC 61000-4-3 Conforming to IEC 61000-4-4 Conforming to IEC 61000-4-5 CISPR11 CISPR22 Level 3 (6 kV contact, 8 kV air) Level 3 (10 V/m) Level 3 (2 kV) Level 3 (2 kV) Group 1 class A Class A

3/30

Te

Zelio Control - measurement and control relays


Current and voltage measurement relays : pages 3/32 to 3/43 3-phase supply control relays : pages 3/44 to 3/49 Single-phase supply control relays : pages 3/50 to 3/53 Liquid level control relays : pages 3/54 to 3/57

General characteristics (continued)

Output circuit characteristics


Mechanical durability Current limit Ith Rated operational limits at 70 C Conforming to IEC 60947-5-1/1991 and VDE 0660 In millions of operating cycles A 30 8 24 V AC-15 DC-13 Minimum switching capacity Switching voltage Rated Max Contact material a.c. load Curve 1 Electrical durability of the contacts on a resistive load in millions of operating cycles Curve 2 Reduction factor k for inductive loads (applies to values taken from the durability curve opposite) V V A A 3 2 12 V/10 mA c 250 c 440 Nickel Silver 90/10 d.c. load Load limit curve 115 V 3 0.3 250 V 3 0.1

Millions of operating cycles

Reduction factor k

Voltage in V

10

1 0,9 0,8 0,7 0,6 0,5

300 200

100

3 2 1

0,1 0,4

50 40 30 20

0,01

0,3 0 1 2 3 4 5 6 7 8 Current broken in A 1 0,8 0,6 0,5 0,4 0,3 0,2 Power factor on breaking (cos )

10 0,1

0,2

0,5

10 20 Current in A

Example: An LC1-F185 contactor supplied with 115 V/50 Hz for a consumption of 55 VA or a current consumption equal to 0.1 A and cos = 0.3 For 0.1 A, curve 1 indicates durability of approximately 1.5 million operating cycles. As the load is inductive, it is necessary to apply a reduction coefficient k to this number of cycles, as indicated by curve 2. For cos = 0.3 : k = 0.6 The electrical durability therefore becomes: 1.5 106 operating cycles x 0.6 = 900 000 operating cycles

1 L/R = 20 ms 2 L/R with load protection diode 3 Resistive load

+
RM4

Te

3/31

Zelio Control - measurement and control relays


Characteristics : page 3/34 References : page 3/35 Dimensions, schemes : page 3/36 Setting-up : page 3/37

Current measurement relays RM4-JA Presentation

Functions
These devices are designed to detect when a preset current threshold is exceeded, on a.c. or d.c. supply. They have a transparent, hinged flap on their front face to prevent any accidental alteration of the settings. This flap can be directly sealed. Type of relay RM4-JA01 RM4-JA31 RM4-JA01 RM4-JA32 Overcurrent control Yes Yes Yes Overcurrent or undercurrent control (1) No Yes Yes Measuring range 3 mA1 A 3 mA1 A 0.3 A15 A

Applications: - excitation control of d.c. machines, - control of load state of motors and generators, - control of current drawn by a 3-phase motor, - monitoring of heating or lighting circuits, - control of pump draining (undercurrent), - control of overtorque (crushers). - monitoring of electromagnetic brakes or clutches.

Description
RM4-JA32 RM4-JA01 Width 22.5 mm RM4-JA31 Width 22.5 mm RM4-JA32 Width 45 mm

1 2
R U R U

1 2 3 4

R U

1 2 3 4

1 Adjustment of current threshold as % of setting range max. value. 2 Hysteresis adjustment from 5 to 30 % (2). 3 Fine adjustment of time delay as % of setting range max. value. 4 10-position switch combining: - selection of the timing range: 1 s, 3 s, 10 s, 30 s, no time delay. - selection of overcurrent (>) or undercurrent (<) detection. See table below. R Yellow LED: indicates relay state. U Green LED: indicates that supply to the RM4 is on. Table showing details for switch 4 Switch position <0 <1 <3 < 10 < 30 >0 >1 >3 > 10 > 30 Function Undercurrent detection Undercurrent detection Undercurrent detection Undercurrent detection Undercurrent detection Overcurrent detection Overcurrent detection Overcurrent detection Overcurrent detection Overcurrent detection Time delay (t) No time delay 0.05 to 1 s 0.15 to 3 s 0.5 to 10 s 1.5 to 30 s No time delay 0.05 to 1 s 0.15 to 3 s 0.5 to 10 s 1.5 to 30 s

(1) Selection by switch on front face. (2) Value of current difference between energisation and de-energisation of the output relay (% of the current threshold to be measured). 3/32

Te

Zelio Control - measurement and control relays


Current measurement relays RM4-JA
References : page 3/35 Dimensions, schemes : page 3/36 Setting-up : page 3/37

Presentation (continued)

Operating principle
The supply voltage is connected to terminals A1-A2. The current to be monitored is connected to terminals B1, B2, B3 and C. See diagram below. Hysteresis is adjustable between 5 and 30 %: for overcurrent h = (IS1 - IS2) / IS1, for undercurrent h = (IS2 - IS1) / IS1. A measuring cycle lasts only 80 ms, which allows rapid detection of changes in current. Relay set for overcurrent detection (RM4-JA01 or selector on > for model RM4-JA3i). If the current is greater than the setting threshold IS1, the output relay is energised with or without a time delay, depending on the model. When the current returns to a value IS2 below the threshold, depending on the hysteresis setting, the relay is instantaneously de-energised. Relay set for undercurrent detection (selector on <, model RM4-JA3i only). If the current is less than the threshold setting IS1, the output relay is energised with or without a time delay, depending on the model. When the current returns to a value IS2 above the threshold, depending on the hysteresis setting, the relay is instantaneously de-energised. Function diagrams: Overcurrent detection
Function > U supply Current measured Relay

A1-A2

IS1 IS2
15-18 15-16 25-28 25-26

t:

time delay

<t

Undercurrent detection
Function < U supply Current measured A1-A2 IS2 IS1 Relay
15-18 15-16 25-28 25-26

<t

B1, B2, B3

C RM4-JA

Measurement circuit

U drop < 1 V

Load

Note: The measurement ranges can be extended by means of a current transformer, the secondary of which is connected to the terminals of the corresponding RM4, or by means of a resistor connected in parallel with the measuring input (see example page 3/37 Setting-up).

Te

3/33

Zelio Control - measurement and control relays


Current measurement relays RM4-JA
References : page 3/35 Dimensions, schemes : page 3/36 Setting-up : page 3/37

Characteristics

Power supply circuit characteristics


Type of relay Rated supply voltage (Un) c 50/60 Hz a Average consumption at Un c a V V VA W RM4-JA01 24 2 110...130 1.93.3 220...240 2.73.5 RM4-JA31 and RM4-JA32 24...240 24...240 1.53.3 1.2 110130 1.93.3 220...240 2.73.4 380...415 2.73

Output relay and operating characteristics


Type of relay Number of C/O contacts Output relay state RM4-JA01 1 Energised when: current measured > threshold setting RM4-JA31 and RM4-JA32 2 Energised when: current measured > threshold setting (> function) current measured < threshold setting (< function)

Setting accuracy of the switching threshold Switching threshold drift % % Hysteresis (adjustable) Setting accuracy of the time delay Time delay drift % %

As % of the full scale value: 5 %

0.06 per degree centigrade, depending on the permissible ambient temperature 0.5, within the supply voltage range (0.851.1 Un) 530 of the current threshold setting As % of the full scale value: 10 %

0.07 per degree centigrade, depending on temperature 0.5, within the supply voltage range (0.851.1 Un)

Measuring cycle

ms

80

Measuring input characteristics


Internal input resistance and permissible overload depending on the current measurement ranges Type of relay Measurement range c 50-60 Hz and a Internal input resistance Ri Permissible continuous overload Permissible non repetitive overload for t 3 s A A RM4-JA01 and RM4-JA31 330 mA 10100 mA 0.11 A RM4-JA32 0.31.5 A 15 A 315 A

33 0.05 0.2

10 0.15 0.5

1 1.5 5

0.06 2 10

0.02 7 15

0.006 20 100

3/34

Te

Zelio Control - measurement and control relays


Current measurement relays RM4-JA
Presentation : pages 3/32 and 3/33 Characteristics : page 3/34 Setting-up : page 3/37

References

Available 2nd Quarter 2001

Current measurement relays: overcurrent detection


Time delay Current to be measured Width depending on connection c or a mm 3...30 mA 10...100 mA 0.1...1 A 22.5 Output relay Basic reference. Complete with code indicating the voltage code (1) RM4-JA01i Weight kg 1 C/O 0.172

None

RM4-JA01

3
Current measurement relays: overcurrent or undercurrent detection
Adjustable time delay s 0.05...30 Current to be measured Width depending on connection c or a mm 3...30 mA 10...100 mA 0.1...1 A 22.5 Output relay Basic reference. Complete with code indicating the voltage code (1) RM4-JA31ii Weight kg 2 C/O 0.172

RM4-JA32 0.3...1.5 A 1...5 A 3...15 A 45 2 C/O RM4-JA32ii 0.204

(1) Standard supply voltages RM4-JA01 Volts c 50/60 Hz RM4-JA31 Volts and RM4-JA32 c 50/60 Hz a

24 B 24...240 MW MW

110...130 F 110...130 F

220...240 M 220...240 M

380...415 Q

Te

3/35

Zelio Control - measurement and control relays


Current measurement relays RM4-JA
Presentation : pages 3/32 and 3/33 Characteristics : page 3/34 Setting-up : page 3/37

Dimensions, schemes

Dimensions
Dimensions RM4-JA (common side view) Rail mounting RM4-JAi1 RM4-JA32 6 78 78 80 22,5 45 89,5 82 Screw fixing

3
Schemes, connection
Terminal blocks RM4-JA01
A1 B1
B1 B2

RM4-JA31
C B3
15

RM4-JA32
A2 B2 C B3
15 25

A2 B2
B3

A1 B1
B1 B2 B3

A1
B1

A2
B2

C
B3

B1
15

B2
25

B3

C
16 18

C
16 18 26 28

C
16 18 26 28

A1

A2

A1

A1

18

16

15

28 18

A2

26 16

25 15

18

16

A2

15

28

26

25

A1-A2 B1, B2. B3, C

Supply voltage Currents to be measured (see table opposite)

Connection and current values to be measured, depending on type of RM4-JA RM4-JA01 B1-C and RM4-JA31 B2-C B3-C 330 mA 10100 mA 0.11 A RM4-JA32 B1-C B2-C B3-C 0.31.5 A 15 A 315 A

Application schemes Example: detection of blockage on a crusher (overcurrent function) Current measured 15 A
1/L1 3/L2 5/L3

Current measured > 15 A


1/L1 3/L2 5/L3

Q1

Q1

1 2

3 4

1 2

3 4

5 6

Q2

Q2

2/T1

2/T1

4/T2

6/T3

4/T2

6/T3

5 6

26

28

16

26

28

16

18

18

B3 C RM4-JA3

A1 A2

B3 C

A1 A2

25

25

15

RM4-JA3

KM1

Stop 2 4 W1 6 U1 V1

KM1

Stop U1 2 V1 4 W1 6

15

Overtorque

Start

KM1

Overtorque

Start

KM1

M1 3 N KM1

M1 3 N KM1

3/36

Te

6 4

78

Zelio Control - measurement and control relays


Presentation : pages 3/32 and 3/33 Characteristics : page 3/34 References : page 3/35 Dimensions, schemes : page 3/36

Current measurement relays RM4-JA Setting-up

Example of overcurrent to be measured Overcurrent threshold at: 13 A. Output relay time delay: 5 s. Reset current threshold: 11 A. Supply voltage: 127 V a. i Product selected RM4-JA32MW Connection of current to be measured B3-C (3 to 15 A) 1 2 3 4

R U

3
Adjustments: i Adjustment of function and timing range, switch 4 : - determine whether overcurrent or undercurrent detection is required; in this example, overcurrent. - determine the timing range, immediately greater than the time required; in this example, 10 s. - position switch 4 according to the above 2 criteria; in this example, switch 4 on > 10. i Fine adjustment of time delay: Depending on the max. range setting displayed at 4 (in this example: 10 s) use potentiometer 3 to set the required time delay as a % of value 4. In this example, the required time = 5 s therefore : t x 100 = 5 x 100 = 50 % 4 10 Set the time delay potentiometer 3 to 50.

i Set the current threshold setting potentiometer 1 as a percentage of the maximum value of the measuring range selected when wiring. In this example: wiring B3-C, max. value of measuring range = 15 A, therefore: Setting 1 = 13 x 100 = 87 % 15 Set the current threshold setting potentiometer 1 to 87.

i Set the hysteresis 2 as a % of the threshold value; in this example: Setting 2 = 13 - 11 = 15.4 % 13 Set the hysteresis 2 to 15 (13 - 11 = 2 i.e. 15.4 % of the current to be measured).

Extension of the measuring range d.c. or a.c. supply Simply connect a resistor Rs to terminals B1-C (or B2, B3-C) on the measuring input. The relay energisation threshold will be towards the middle of the setting potentiometer range if the value of Rs is in the region of: Rs = Ri where : Ri Internal resistance of input B1-C. (2I/Im) - 1 Im Maximum value of threshold setting range. I Current threshold to be measured.

RM4-JA B1 Ri C

Im

Rs

Power dissipated by Rs: P = Rs (I -Im/2)2 Application: Use of relay RM4-JA31ii (10 to 100 mA). Connection B2-C to measure a threshold of 1 A, knowing that Ri = 10 for this rating and that Im = 100 mA 10 The value of Rs will be: = 0.526 (2 x 1/0.1) - 1 0.1 2 P = (1 ) x 0.526 i.e. 0.47 W 2 Select a resistor Rs capable of dissipating at least twice the calculated value, i.e. 1 W for this example, in order to limit temperature rise. On an a.c. supply, it is also possible to use a current transformer.

Te

3/37

Zelio Control - measurement and control relays


Characteristics: page 3/40 References: page 3/41 Dimensions, schemes: page 3/42 Setting-up: page 3/43

Voltage measurement relays RM4-UA Presentation

Functions
These devices are designed to detect when a preset voltage threshold is exceeded, on a.c. or d.c. supply. They have a transparent, hinged flap on their front face to prevent any accidental alteration of the settings. This flap can be directly sealed. Type of relay RM4-UA0i RM4-UA3i Overvoltage control Yes Yes Overvoltage or undervoltage control (1) No Yes Measuring range 50 mV500 V 50 mV500 V

RM4-UA01

Applications: - d.c. motor overspeed control, - battery monitoring, - monitoring of a.c. or d.c. supplies, - speed monitoring (with tacho-generator).

Presentation
RM4-UA0i Width 22.5 mm RM4-UA3i Width 22.5 mm

1 2
R U R U

1 2 3 4

1 Adjustment of voltage threshold as % of setting range max. value. 2 Hysteresis adjustment from 5 to 30 % (2). 3 Adjustment of time delay as % of setting range max. value. 4 Switch combining: - selection of the timing range: 1s, 3s, 10s, 30s, no time delay, - selection of overvoltage (>) or undervoltage (<) detection. See table below. R Yellow LED: indicates relay state. U Green LED: indicates that supply to the RM4 is on. Table showing details for switch 4 Switch position <0 <1 <3 < 10 < 30 >0 >1 >3 > 10 > 30 Function Undervoltage detection Undervoltage detection Undervoltage detection Undervoltage detection Undervoltage detection Overvoltage detection Overvoltage detection Overvoltage detection Overvoltage detection Overvoltage detection Time delay (t) No time delay 0.05 to 1 s 0.15 to 3 s 0.5 to 10 s 1.5 to 30 s No time delay 0.05 to 1 s 0.15 to 3 s 0.5 to 10 s 1.5 to 30 s

(1) Selection by switch on front face. (2) Value of voltage difference between energisation and de-energisation of the output relay (% of the voltage threshold to be measured). 3/38

Te

Zelio Control - measurement and control relays


Characteristics: page 3/40 References: page 3/41 Dimensions, schemes: page 3/42 Setting-up: page 3/43

Voltage measurement relays RM4-UA Presentation (continued)

Operating principle
The supply voltage is connected to terminals A1-A2. The voltage to be monitored is connected to terminals B1, B2 or B3 and C. Hysteresis is adjustable between 5 and 30 %: for overvoltage h = (US1 - US2) / US1, for undervoltage h = (US2 - US1) / US1. A measurement cycle lasts only 80 ms, which allows rapid detection of changes in voltage. Relays set for overvoltage detection (RM4-UA0i or selector on > for model RM4-UA3i): If the voltage is greater than the threshold setting US1, the output relay is energised, with or without a time delay. When the voltage returns to a value US2 below the threshold, depending on the hysteresis setting, the relay is instantaneously de-energised. Relays set for undervoltage detection (selector on <, model RM4-UA3i only): If the voltage is less than the threshold setting US1, the output relay is energised, with or without a time delay. When the voltage returns to a value US2 above the threshold, depending on the hysteresis setting, the relay is de-energised. Function diagrams Overvoltage control
Function > U supply A1-A2

Voltage measured Relay t:

US1 US2
15-18 15-16 25-28 25-26

time delay

<t

Undervoltage control
Function < U supply A1-A2 Voltage measured Relay

US2 US1
15-18 15-16 25-28 25-26

<t

Note: the measurement ranges can be extended above 500 V by adding a resistor, see page 3/43. The measurement range on c supply can be extended by means of a voltage transformer, the secondary of which is connected to the measuring terminals of the corresponding RM4 .

Te

3/39

Zelio Control - measurement and control relays


Presentation: pages 3/38 and 3/39 References: page 3/41 Dimensions, schemes: page 3/42 Setting-up: page 3/43

Voltage measurement relays RM4-UA Characteristics

Power supply circuit characteristics


Type of relay Rated supply voltage (Un) c 50/60 Hz a Average consumption at Un c a V V VA W RM4-UA0i 24 2 110...130 1.93.3 220...240 2.73.5 RM4-UA3i 24...240 24...240 1.53.3 1.2 110130 1.93.3 220...240 2.73.4 380...415 2.73

Output relay and operating characteristics


Type of relay Number of C/O contacts Output relay state RM4-UA0i 1 Energised when: voltage measured > threshold setting RM4-UA3i 2 Energised when: voltage measured > threshold setting (> function ) voltage measured < threshold setting (< function)

Setting accuracy of the switching threshold Switching threshold drift % % Hysteresis (adjustable) Setting accuracy of the time delay Time delay drift % %

As % of the full scale value: 5 %

0.06 per degree centigrade, depending on the permissible ambient temperature 0.5, within the supply voltage range (0.851.1 Un) 530 of the voltage threshold setting As % of the full scale value: 10 %

0.5, within the supply voltage range (0.851.1 Un) 0.07 per degree centigrade, depending on the rated operating temperature

Measuring cycle

ms

80

Measuring input characteristics


Internal input resistance and permissible overload depending on the current measurement ranges Type of relay Measurement range c 50-60 Hz and a Internal input resistance Ri Permissible continuous overload Permissible non repetitive overload for t 1 s V k V V RM4-UAi1 0.050.5 6.6 20 25 0.33 43 60 80 0.55 71 80 100 RM4-UAi2 110 23 90 100 550 112 150 200 10100 225 300 400 RM4-UAi3 30300 668 400 500 50500 1111 550 550

3/40

Te

Zelio Control - measurement and control relays


Presentation: pages 3/38 and 3/39 Characteristics: page 3/40 Dimensions, schemes: page 3/42 Setting-up: page 3/43

Voltage measurement relays RM4-UA References


Available 2nd Quarter 2001

Voltage measurement relays: overvoltage detection


Time delay Voltage to be measured depending on connection c or a V 0.05...0.5 0.33 0.55 Width mm 22.5 1 C/O RM4-UA01i Output relay Basic reference. Complete with code indicating the voltage code (1) Weight kg 0.168

None

1...10 550 10100

22.5

1 C/O

RM4-UA02i

0.168

RM4-UA01

30...300 50500

22.5

1 C/O

RM4-UA03i

0.168

Voltage measurement relays: overvoltage or undervoltage detection


Adjustable time delay s 0.05...30 Voltage to be measured depending on connection c or a V 0.05...0.5 0.33 0.55 Width mm 22.5 2 C/O RM4-UA31ii Output relay Basic reference. Complete with code indicating the voltage code (1) Weight kg 0.168

1...10 550 10100

22.5

2 C/O

RM4-UA32ii

0.168

30...300 50500

22.5

2 C/O

RM4-UA33ii

0.168

(1) Standard supply voltages RM4-UA0i Volts c 50/60 Hz RM4-JA3i Volts c 50/60 Hz a

24 B 24...240 MW MW

110...130 F 110...130 F

220...240 M 220...240 M

380...415 Q

Te

3/41

Zelio Control - measurement and control relays


Presentation: pages 3/38 and 3/39 Characteristics: page 3/40 References: page 3/41 Setting-up: page 3/43

Voltage measurement relays RM4-UA Dimensions, schemes

Dimensions
Dimensions RM4-UA Rail mounting Screw fixing

78

80

22,5

89,5 82

Schemes, connection
Terminal blocks RM4-UA01, UA02
A1 B1
B1 B2

RM4-UA03
C B3
15

RM4-UA31, UA32
A2 B2
B3

RM4-UA33
C B3 A1
25 B2 B3

A2 B2
B3

A1
B2

C B3
15

A1 B1
B1 B2 B3

A2 B2
15

A2 B2
15

C B3
25

C
16 18

C
16 18

C
16 18 26 28

C
16 18 26 28

A1

A1

A2

A2

A1

A1

A2

18

16

15

18

16

15

28 18

26 16

25 15

28 18

A2

26 16

25 15

A1-A2 Supply voltage B1, B2. Voltages to be measured B3, C (see table opposite)

Connection and voltage values to be measured, depending on type of RM4-UA RM4-UAi1 B1-C B2-C B3-C 0.050.5 V 0.33 V 0.55 V RM4-UAi2 B1-C B2-C B3-C 110 V 550 V 10100 V RM4-UAi3 B2-C B3-C 30300 V 50500 V

Application scheme Example: overspeed monitoring (undervoltage function)


1/L1 3/L2 5/L3

Q1

26

28

16

A1 A2

18

2 Q3 1 2 Q2 1

1 Q4 2

B1 C

U v

25

RM4-UA

KM1

Stop 2 4 W1 6 U1 V1 Overspeed Start


KM1

M1 3

15

Tachogenerator

KM1

3/42

Te

78

Zelio Control - measurement and control relays


Presentation: pages 3/38 and 3/39 Characteristics: page 3/40 References: page 3/41 Dimensions, schemes: page 3/42

Voltage measurement relays RM4-UA Setting-up

Example of undervoltage to be measured Undervoltage threshold to be measured: 12 V a. Time delay of the output relay: 20 s. Reset voltage threshold: 13.2 V. Supply voltage: 230 V c 60 Hz. i Product selected RM4-UA32M Connection of voltage to be measured B2-C (5 to 50 V)

R U

1 2 3 4

3
Adjustments: i Adjustment of function and timing range, switch 4: - determine the timing range, immediately greater than the time required, in this example 30 s. - determine whether overvoltage or undervoltage detection is required, in this example undervoltage. - position switch 4 according to the above 2 criteria, in this example, switch 4 on < 30. i Fine adjustment of time delay: Depending on the max. range setting displayed at 4 (in this example: 30 s) use potentiometer 3 to set the required time delay as a % of value 4. In this example, the required time = 20 s therefore: Set the time delay potentiometer 3 to 66. t x 100 = 20 x 100 = 66 % 4 30 i Set the voltage threshold setting potentiometer 1 as a percentage of the maximum value of the measuring range selected when wiring. In this example: wiring B2-C, max. value of measuring range = 50 V, therefore: Setting 1 = 12 x 100 = 24 % 50 Set the voltage threshold setting potentiometer 1 to 24.

i Set the hysteresis 2 as a % of the threshold value; in this example: Setting 2 = 13.2 - 12 = 10 % 12 Set the hysteresis 2 to 10.

Extension of the measuring range


RM4-UA33

Rs U > 500 V

d.c. or a.c. supply Simply connect an additional resistor (Rs) in series with the measuring input B3 or C. If the value of Rs is in the region of: Rs = Ri ( U - 1) where: Ri Internal resistance of input B3-C. Um Maximum value of threshold setting range. Um U Voltage threshold to be measured. The tripping threshold of the relay will be towards the maximum graduation on the threshold setting potentiometer. In general, the power consumed by the resistor does not exceed 0.5 W. For a.c. voltages, it is also possible to use a voltage transformer.

Ri B3

Supply by the measured voltage For monitoring mains and power supplies, the RM4-UA can be supplied by the voltage to be controlled, provided that:
A1

- the measurement threshold is within the operating range of the product's power supply (0.851.1 Uc).
B2/B3

RM4-UA C A2

- variations of the voltage to be measured are compatible with the supply and measurement voltage ranges.

Te

3/43

Zelio Control - measurement and control relays


3-phase supply control relays RM4-T
Characteristics : page 3/47 References : page 3/48 Dimensions, schemes : page 3/49

Presentation

Functions
These devices are designed to monitor 3-phase supplies and to protect motors and other loads against the faults listed in the table below. They have a transparent, hinged flap on their front face to prevent any accidental alteration of the settings. This flap can be directly sealed. RM4-TG RM4-TU RM4-TR RM4-TA Monitoring of rotational direction of phases Detection of complete failure of one or more of the phases RM4-T Undervoltage detection Overvoltage and undervoltage detection (2 thresholds) Detection of phase asymmetry (imbalance) Function performed Function not performed

Applications
i Control for connection of moving equipment (site equipment, agricultural equipment, refrigerated trucks). i Control for protection of persons and equipment against the consequences of reverse running (lifting, handling, elevators, escalators, etc.). i Control of sensitive 3-phase supplies. i Protection against the risk of a driving load (phase failure). i Normal/emergency power supply switching.

Presentation
RM4-TG RM4-TU

<U

1
R R

Yellow LED: indicates relay output state.

R Yellow LED: indicates relay output state. < U Red LED: undervoltage fault. 1 Undervoltage setting potentiometer. RM4-TA3 RM4-TA0

RM4-TR31. RM4-TR32

RM4-TR33. RM4-TR34

>U <U P R U

3 4 1 2

>U <U P R U

A P

1
R

1 2

R U

Time delay function selector: Fault detection delayed. Fault detection extended. 2 Potentiometer for setting time delay in seconds. 3 Potentiometer for setting overvoltage as a direct value. 4 Potentiometer for setting undervoltage as a direct value. R Yellow LED: indicates relay state. U Green LED: indicates that supply to the RM4 is on. > U Red LED: overvoltage fault < U Red LED: undervoltage fault P Red LED: phase failure or incorrect rotational direction of phases.

1 2 R U A P

Asymmetry threshold setting potentiometer, from 5 to 15 % Potentiometer for setting time delay, 0.1 to 10 s. Yellow LED: indicates relay state. Green LED: indicates that supply to the RM4 is on. Red LED: phase asymmetry. Red LED: phase failure or incorrect rotational direction of phases.

3/44

Te

Zelio Control - measurement and control relays


3-phase supply control relays RM4-T
Characteristics : page 3/47 References : page 3/48 Dimensions, schemes : page 3/49

Presentation (continued)

Operating principle
The supply voltage to be monitored is connected to terminals L1, L2, L3 of the product. There is no need to provide a separate power supply for RM4-T relays; they are self-powered by terminals L1, L2, L3. i Monitoring rotational direction of phases and detection of complete failure of one of more of the phases (RM4-T all models) When terminals L1, L2, L3 are energised, the relay is energised and the yellow LED comes on if the rotational direction of phases is correct and if all 3 phases are present. If one or more of the phases have failed or if the rotational direction is incorrect, the relay is not energised at switchon. In normal operation (no fault) the relay is energised; it de-energises instantaneously in the event of failure of one or more of the phases (any time delay set is not active on these faults). In the event of failure or absence of a single phase, a voltage greater than the detection threshold ( 130 V on RM4-TG, undervoltage threshold setting on RM4-TU and RM4-TR) can be generated back through the control circuit, thus preventing detection of the phase failure. In this case, we recommend the use of RM4-TA relays. The absence of a phase is signalled, on RM4-TR and RM4-TA, by illumination of led P. i Overvoltage and undervoltage detection (RM4-TR): In normal operation, the relay is energised and LEDs U and R are illuminated. If the average of the 3 voltages between phases goes outside the range to be monitored, the output relay is deenergised: - overvoltage: the Red LED > U illuminates. - undervoltage: the Red LED < U illuminates. When the supply returns towards its rated value, the relay is re-energised according to the hysteresis value (5%) and the corresponding red LED goes out. A selector switch allows selection of an adjustable time delay from 0.1 s to 10 s. With function transient over or under voltages are not taken into account. With function all variations above or below are taken into account and re-energisation of the relay is delayed. In all cases, in order to be detected, the duration of the overvoltage or undervoltage must be greater than the measuring cycle time (80 ms). Function diagram (RM4-TR31, RM4-TR32)
RM4-TR31 RM4-TR32 Setting > U 0.95 x Setting > U 1.05 x Setting < U Setting < U UL1 L2 L3 t Function
15/18 25/28 15/16 25/26

<t

<t t

0 Volt

t Function
15/18 25/28 15/16 25/26

t: time delay

Function diagram (RM4-TR33, RM4-TR34)


RM4-TR33 RM4-TR34 TR33 242 V 230 V 208 V 198 V TR34 440 V 418 V 378 V 360 V UL1 L2 L3 t Function
15/18 25/28 15/16 25/26

<t

<t t

0 Volt

t Function
15/18 25/28 15/16 25/26

t: time delay

Te

3/45

Zelio Control - measurement and control relays


3-phase supply control relays RM4-T
Characteristics : page 3/47 References : page 3/48 Dimensions, schemes : page 3/49

Presentation (continued)

Operating principle (continued)


i Undervoltage detection only (RM4-TU) In normal operation, the output relay is energised and the yellow LED is illuminated. If the average of the 3 voltages between phases is less than the undervoltage threshold setting, the relay is deenergised after 550 ms and the red LED < U illuminates. Function diagram

1.05 x Setting < U Setting < U UL1 L2 L3


t
15/18 25/28 15/16 25/26

<t

0 volt

t: fixed time delay = 550 ms i Detection of phase asymmetry (RM4-TA) In normal operation, the output relay is energised and the yellow and green LEDs are illuminated. In the event of an asymmetry fault, after a time delay set between 0.1 s and 10 s (on RM4-TA3 only), the output relay is de-energised, the yellow LED goes out and red LED A illuminates (RM4-TA3i only). The relay re-energises when the asymmetry value measured is less than half of the asymmetry value setting (hysteresis). Function diagram

L1

L2

L3

Asymmetry > set threshold

Asymmetry > set threshold

L3 L2 L1 L3 L2 L1

15-18 15-16

Relay
25-28 25-26

t: time delay

Example: asymmetry set at 10 %, mains supply voltage 400 V - relay de-energisation threshold: 400 - 10 % = 360 V. 10 % - relay re-energisation threshold: 400 V = 380 V. 2

3/46

Te

Zelio Control - measurement and control relays


3-phase supply control relays RM4-T
Presentation : pages 3/44 to 3/46 References : page 3/48 Dimensions, schemes : page 3/49 Type of relay

Characteristics

RM4-TG

RM4-TU

RM4-TR

RM4-TA

Output relay and operating characteristics


Number of C/O contacts 2 2 2 RM4-TA3i: 2 RM4-TA0i: 1 Energised during fault free operation. De-energised on detection of asymmetry fault, phase failure or rotational direction fault

Output relay state

Energised during fault free operation. De-energised or unable to energise on detection of rotational direction fault or failure of one or more phases

Energised during fault free operation. De-energised on detection of undervoltage or rotational direction fault or failure of one or more phases

Energised during fault free operation. De-energised on detection of overvoltage, undervoltage or rotational direction fault or phase failure

Accuracy of switching threshold setting

As % of the set value

3%

3%

3%

Switching threshold drift

Depending on the permissible ambient temperature Within the measuring range

0.06 % per 0.06 % per 0.06 % per degree centigrade degree centigrade degree centigrade 0.5 % 0.5 % 0.5 %

Accuracy of time delay setting

As % of the full scale value

10 %

10 %

10 %

Time delay drift

Within the measuring range Depending on the rated operational temperature

0.5 %

0.5 %

0.5 %

0.07 % per 0.07 % per 0.07 % per degree centigrade degree centigrade degree centigrade About 5 % of the de-energisation threshold 80 About 5 % of the de-energisation threshold 80 About 50 % of the asymmetry percentage 80

Hysteresis

Fixed

Measuring cycle

ms

80

Measuring input characteristics


Minimum operational voltage (1) L1 L2 or L2 L3 or L1 L3 V 140 RM4-TU01: 160 RM4-TU02: 290 RM4-TR31, RM4-TR33: 160 RM4-TR32, RM4-TR34: 290 RM4-TA01, RM4-TA31: 160 RM4-TA02, RM4-TA32: 290

Maximum permissible voltage between phases

L1 L2 L3

580

RM4-TU01: 300 RM4-TU02: 580

RM4-TR31, RM4-TR33: 300 RM4-TR32, RM4-TR34: 580

RM4-TA01, RM4-TA31: 300 RM4-TA02, RM4-TA32: 580

(1) Minimum voltage required for operation of indicators and of the time delay.

Te

3/47

Zelio Control - measurement and control relays


3-phase supply control relays RM4-T
Presentation : pages 3/44 to 3/46 Characteristics : page 3/47 Dimensions, schemes : page 3/49

References

Control relays: rotational direction and presence of phases


Time delay s None Rated mains supply voltage (1) V 200...500 50/60 Hz Width mm 22.5 2 C/O RM4-TG20 Output relay Reference Weight kg 0.110

Control relays: rotational direction and presence of phases + undervoltage


Time delay RM4-TG20 s Rated mains supply voltage (1) V 200240 50/60 Hz 380500 50/60 Hz Control threshold V Undervoltage 160220 Undervoltage 300430 Width mm 22.5 22.5 2 C/O 2 C/O RM4-TU01 RM4-TU02 Output relay Reference Weight kg 0.110 0.110

None

Control relays: rotational direction and presence of phases + overvoltage and undervoltage
Relays with fixed voltage thresholds Adjustable Rated Control time delay mains supply threshold voltage (1) s V V 0.1...10 220 50/60 Hz Undervoltage 198 Overvoltage 242 Undervoltage 360 Overvoltage 440 Width mm 22.5 2 C/O RM4-TR33 Output relay Reference Weight kg 0.110

400 50/60 Hz

22.5

2 C/O

RM4-TR34

0.110

RM4-TR33

Relays with adjustable voltage thresholds Adjustable Rated Control time delay mains supply threshold voltage (1) s V V 0.110 200240 50/60 Hz Undervoltage 160220 Overvoltage 220300 Undervoltage 300430 Overvoltage 420580

Width mm 22.5

Output relay

Reference

Weight kg

2 C/O

RM4-TR31

0.110

380500 50/60 Hz

22.5

2 C/O

RM4-TR32

0.110

Control relays: rotational direction and presence of phases + asymmetry


Time delay on de-energisation s Fixed 0.5 Rated mains supply voltage (1) V 200...240 50/60 Hz 380500 50/60 Hz Adjustable 0.110 200...240 50/60 Hz Control threshold % Asymmetry 515 Asymmetry 515 Asymmetry 515 Width mm 22.5 22.5 22.5 1 C/O 1 C/O 2 C/O RM4-TA01 RM4-TA02 RM4-TA31 Output relay Reference Weight kg 0.110 0.110 0.110

RM4-TA01

380...500 Asymmetry 22.5 2 C/O RM4-TA32 0.110 50/60 Hz 515 (1) Can be used on other supply voltages provided that the minimum operational voltages, maximum voltage between phases and compatibility with the control threshold ranges are complied with, see page 3/47.

3/48

Te

Zelio Control - measurement and control relays


3-phase supply control relays RM4-T
Presentation : pages 3/44 to 3/46 Characteristics : page 3/47 References : page 3/48 Dimensions RM4-T

Dimensions, schemes

Rail mounting

Screw fixing

78

80

22,5

89,5 82

6
4

78

3
Schemes, connection Terminal blocks RM4-TG20, TU0i i
L1
L1 L2 L3

RM4-TR3i , TA3i i i
L1
L1 L2 L3

RM4-TA0i i
L3
25

L2
15 (11)

L3
25 (21)

L2
15

L1

L2
15 16 18

L3

16 (12) 18 (14) 26 (22) 28 (24)

18

16

28 (24) 18 (14)

25 (21) 15 (11)

26 (22) 16 (12)

28 18

25 15

26

28

26 16

18

L1 L2 L3

15

16

L1, L2, L3 15(11)-18(14) 15(11)-16(12) 25(21)-28(24) 25(21)-26(22)

Supply to be monitored 1 C/O contact of the output relay 2nd C/O contact of the output relay
st

L1, L2, L3 15-18 15-16 25-28 25-26

Supply to be monitored 1 C/O contact of the output relay 2nd C/O contact of the output relay
st

L1, L2, L3 15-18 15-16

Supply to be monitored 1st C/O contact of the output relay

Application scheme Example


1/L1 3/L2 4 5/L3 6

Q1
2 26 28 16

L3 L2 L1 RM4-T

25

Q2

Stop

Fault

Start

15

18

KM1

5 6/T3

1 2/T1

3 4/T2

KM1 N

KM1
U1 2 V1 4 W1 6

M1 3

Te

3/49

Zelio Control - measurement and control relays


Single-phase supply control relays RM4-UB
Characteristics : page 3/51 References : page 3/52 Dimensions, schemes : page 3/53

Presentation

Functions
These devices are designed for monitoring single-phase mains and power supplies. They have a transparent, hinged flap on their front face to prevent any accidental alteration of the settings. The flap can be directly sealed.

Applications
- Protection of electronic or electromechanical devices against overvoltage and undervoltage. - Normal/emergency power supply switching. RM4-UB

Presentation

RM4-UB

>U <U R U

1 2 3 4

1 2 3

Overvoltage setting potentiometer. Undervoltage setting potentiometer. Time delay function selector: Fault detection delayed. Fault detection extended. 4 Potentiometer for setting time delay in seconds. R Yellow LED: indicates relay state. U Green LED: indicates that supply to the RM4 is on. > U Red LED: overvoltage fault < U Red LED: undervoltage fault

Operating principle
The supply voltage to be monitored is connected to terminals L1, L3 of the product. There is no need to provide a separate power supply for RM4-UB relays; they are self-powered by terminals L1, L2, L3. If the voltage goes outside the range to be monitored, the output relay is de-energised: - overvoltage: red LED > U illuminates. - undervoltage: red LED < U illuminates. When the supply returns towards its rated value, the relay is re-energised according to the hysteresis value (5%) and the corresponding red LED goes out. A selector switch allows selection of an adjustable time delay from 0.1 s to 10 s. With function , transient over or under voltages are not taken into account. With function , all variations above or below are taken into account and re-energisation of the relay is delayed. In all cases, in order to be detected, the duration of the overvoltage or undervoltage must be greater than the measuring cycle time (80 ms). Function diagram
RM4-UB34 RM4-UB35 Setting > U 0.95 x Setting > U 1.05 x Setting < U Setting < U UL1 L3 t Function
15/18 25/28 15/16 25/26

<t

<t t

0 Volt

t Function
15/18 25/28 15/16 25/26

t: time delay 3/50

Te

Zelio Control - measurement and control relays


Single-phase supply control relays RM4-UB
Presentation : page 3/50 References : page 3/52 Dimensions, schemes : page 3/53

Characteristics

Output relay and operational characteristics


Number of C/O contacts 2

Output relay state

Energised during fault free operation. De-energised on detection of an overvoltage or undervoltage fault.

Setting accuracy of switching threshold

As % of the setting value

3%

Switching threshold drift

Depending on the permissible ambient temperature Within the measuring range

0.06 % per degree centigrade

0.5 %

Accuracy of time delay setting

As % of the full scale value

10 %

Time delay drift

Within the measuring range

0.5 %

Depending on the rated operational temperature Hysteresis Fixed

0.07 % per degree centigrade

About 5 % of the de-energisation threshold

Measuring cycle

ms

80

Measuring input characteristics


Minimum operational voltage V RM4-UB34: 60 RM4-UB35: 160

Maximum permissible voltage between L1 and L3

RM4-UB34: 300 RM4-UB35: 300

Te

3/51

Zelio Control - measurement and control relays


Single-phase supply control relays RM4-UB
Presentation : page 3/50 Characteristics : page 3/50 Dimensions, schemes : page 3/53

References

Available 2nd Quarter 2001

Relays with adjustable thresholds


Adjustable time delay s 0.110 Rated Control mains supply threshold voltage (1) V V 100200 50/60 Hz Undervoltage 80120 Overvoltage 160220 Width mm 22.5 2 C/O RM4-UB34 Output relay Reference Weight kg 0.110

RM4-UB

180270 50/60 Hz

Undervoltage 160220 Overvoltage 220300

22.5

2 C/O

RM4-UB35

0.110

(1) Can be used on other supply voltages provided that the minimum operational voltages, maximum voltage between phases and compatibility with the control threshold ranges are complied with, see page 3/51.

3/52

Te

Zelio Control - measurement and control relays


Single-phase supply control relays RM4-UB
Presentation : page 3/50 Characteristics : page 3/51 References : page 3/52 Dimensions RM4-UB

Dimensions, schemes

Rail mounting

Screw fixing

78

80

22,5

89,5 82

6
4

78

3
Scheme, connection Terminal block RM4-UB
L1
15

L3
L3
25 26

L1

18

28 18

16

25 15

L1, L3 15-18 15-16 25-28 25-26

Supply to be monitored 1st C/O contact of the output relay 2nd C/O contact of the output relay

Application scheme Example


Q1

1/L1 3/L2 5/L3

2 4 6

16

RM4-UB
L3 15

18

Q4

L1

Q2

Q2

28

26 16

To sensitive loads

Te

3/53

Zelio Control - measurement and control relays


Characteristics : page 3/56 References : page 3/56 Dimensions : page 3/57 Setting-up : page 3/57

Liquid level control relays Presentation

Functions
These devices monitor the levels of conductive liquids. They control the actuation of pumps or valves to regulate levels, and are also suitable for protecting submersible pumps against running empty, or protecting tanks from overflow. They can also be used to control dosing of liquids in mixing processes and to protect heating elements in the event of non immersion. They have a transparent, hinged flap on their front face to prevent any accidental alternation of the settings. This flap can be directly sealed. i Compatible liquids: - spring, town, industrial and sea water, - metallic, acid or basic salt solutions, - liquid fertilizers, - non concentrated alcohol (< 40 %), - liquids in the food processing industry: milk, beer, coffee, etc. i Non-compatible liquids: - chemically pure water, - fuels, liquid gasses (inflammable), - oil, concentrated alcohol (> 40 %), - ethylene, glycol, paraffin, varnish and paints.

RM4-LG01

Description
RM4-LG01 Width 22.5 mm RM4-LA32 Width 22.5 mm

RM4-LA32

R U

2 3

R U

1 2 3 4

1 Fine adjustment of time delay (as % of maximum value of setting range). 2 Fine adjustment of response sensitivity (as % of maximum value of setting range). 3 Function selector switch: - empty or fill . 4 Switch combining: - selection of the response sensitivity range, - selection of time delay on energisation or on de-energisation R Yellow LED: indicates relay state. U Green LED: indicates that supply to the RM4 is on Table showing details for switch 3 Switch position 500 500 50 50 5 5 Time delay On-delay Off-delay On-delay Off-delay On-delay Off-delay Sensitivity High = 500 k range High = 500 k range Medium = 50 k range Medium = 50 k range Low = 5 k range Low = 5 k range

of the relay.

3/54

Te

Zelio Control - measurement and control relays


Characteristics : page 3/56 References : page 3/56 Dimensions : pages 3/57 Setting-up : page 3/57

Liquid level control relays Presentation (continued)

Operating principle
The operating principle is based on a change in the resistance measured between immersed or non immersed electrodes. Low resistance between electrodes: liquid present. High resistance between electrodes: no liquid present. The electrodes may be replaced by other sensors or probes which transmit values representing variations in resistance. The a.c. measuring voltage, which is < 30 V and galvanically insulated from the supply and contact circuits, ensures safe use and the absence of any electrolysis phenomena. RM4-L relays may be used: i For detection of a liquid level, operating with 2 electrodes, one reference electrode and one high level electrode, or an LA9-RM201 probe. Example: prevention of tank overflow. i For regulating a liquid level between a minimum and a maximum level, operating with 3 electrodes, or an LA9-RM201 probe. Example: water tower. The state of the output relay can be configured: i Empty function : the output relay is energised when high level electrode B2 is immersed and is de-energised when low level electrode B3 is dry (1). i Fill function : the output relay is energised when the low level electrode is dry and is de-energised when the high level electrode is immersed (1). On model RM4-LA32, a time delay can be set on energisation or de-energisation of the output relay in order to raise the maximum level (function ) or to lower the minimum level (function ). This function also makes it possible to avoid pulsing of the output relay (wave effect) when operating with 2 electrodes.

Empty function, maximum level detection (2 electrodes or 1 probe LA9-RM201)


B1
Time delay switch 4

B2

B1

B2

B1

B2

Type RM4-

Function switch 3

U supply A1/A2 15/18 15/16

LG01 LA32 LA32

t
15/18 25/28 15/16 25/26 15/18 25/28 15/16 25/26

Empty function, regulation between a maximum and a minimum level (3 electrodes or 2 probes LA9-RM201)
B1 B3 B2
Time delay switch 4

B1 B3 B2

B1 B3 B2

B1 B3 B2

Type RM4-

Function switch 3

U supply A1/A2 15/18 15/16

LG01 LA32 LA32

t
15/18 25/28 15/16 25/26 15/18 25/28 15/16 25/26

Fill function, maximum level detection (2 electrodes or 1 probe LA9-RM201)


B1
Time delay switch 4

B2

B1

B2

B1

B2

Type RM4-

Function switch 3

U supply A1/A2 15/18 15/16

LG01 LA32 LA32

t
15/18 25/28 15/16 25/26 15/18 25/28 15/16 25/26

Empty function, regulation between a maximum and a minimum level (3 electrodes or 2 probes LA9-RM201)
B1 B3 B2
Time delay switch 4

B1 B3 B2

B1 B3 B2

B1 B3 B2

Type RM4-

Function switch 3

U supply A1/A2 15/18 15/16

LG01 LA32 LA32

t
15/18 25/28 15/16 25/26 15/18 25/28 15/16 25/26

B1: reference electrode B2: high level electrode B3: low level electrode (1) When operating with 2 electrodes, the high level electrode performs both high and low level functions.

Te

3/55

Zelio Control - measurement and control relays


Liquid level control relays
Presentation : pages 3/54 and 3/55 Dimensions : page 3/57 Setting-up : page 3/57 Type of relay

Characteristics, references

Available 2nd Quarter 2001

RM4-LG01

RM4-LA32

Power supply circuit characteristics


Rated supply voltage (Un) Average consumption at Un c 50/60 Hz a c a V V VA W 24 1.9 110...130 2.6 220...240 2.4 380...415 2.9 24...240 24...240 2.7 2.4 24 3.1 110...130 2.7 220...240 2.6 380...415 3.4

Output relay and operating characteristics


Number of C/O contacts Output relay state 1 Can be configured by switch: empty /fill 2

Electrode circuit characteristics (1)


Sensitivity scale Maximum a.c. electrode voltage (peak to peak) Maximum current in the electrodes Maximum cable capacity Maximum cable length k V mA nF m 5100 (adjustable) 24 1 10 100 0.255 24 1 200 1000 1 25 100 1 4 20 2.550 25500

References
Liquid level control relays Time delay Sensitivity scale k None 5100 Width mm 22.5 1 C/O RM4-LG01i Output relay Basic reference. Complete with code indicating the voltage (2) Weight kg 0.165

RM4-LG01

Adjustable 0.1...10 s

0.25 ...5 2.5 ...50 25 ...500

22.5

2 C/O

RM4-LA32ii

0.165

Liquid level control probe Type of installation

Maximum operating temperature C 100

Reference

Weight kg

RM4-LA32

Suspended by cable

LA9-RM201

0.100

LA9-RM201 3/56

(1) The electrodes may also be incorporated in the probes. The probes are normally designed for fixing to a tank by means of a bracket with a seal (closed tanks) or suspended by their own electrical connecting cable (boreholes, etc.). See page 3/57 Setting-up Probe LA9-RM201. (2) Standard supply voltages RM4-LG01 Volts 24 110...130 220...240 380...415 c 50/60 Hz B F M Q RM4-LA32 Volts 24...240 24 110...130 220...240 380...415 c 50/60 Hz MW B F M Q a MW

Te

Zelio control - measurement and control relays


Liquid level control relays
Presentation : pages 3/54 and 3/55 Characteristics : page 3/56 References : page 3/56 Dimensions RM4-LG01, LA32

Dimensions, schemes, setting-up

Rail mounting

Screw fixing 6

78

80 Probe LA9-RM201

22,5

89,5 82

16

6 4

78

150

3
RM4-LA32
A1 B1 15 B2 25 B3

Schemes, connection RM4-LG01


A1 B1 15 B2

B3

18

16

A2

28 18

26 16

A1-A2 Supply voltage B1, B2, B3 Electrodes (see table opposite) 15-18 1st C/O contact 15-16 of the output relay 25-28 2nd C/O contact 25-26 of the output relay

B1

B1

B2

B3

B2

B3

15

15

25

Electrodes and level controlled B1 B2 B3 Reference or tank earth electrode High level Low level

16

18

26

16

18

A1

A1

A2

A2

A2

Setting-up i Select the empty /fill function according to the sequence to be performed. i If necessary, set potentiometer 1 to minimum (time delay). i Set potentiometer 2 to minimum; on RM4-LA select the lowest sensitivity range using potentiometer 4 (5 or 5 ). i With all the electrodes immersed, turn the sensitivity potentiometer towards maximum until the relay is energised ( function) or de-energised ( function), then exceed the threshold by about 10 % to compensate for variation in the supply voltage. If the relay is not able to energise, a higher sensitivity scale must be used (selector 4 on RM4-LA32) or relay RM4-LG must be replaced by an RM4-LA32 relay and the adjustment procedure must be started again. i Then check that the relay de-energises ( function) or energises ( function) as soon as electrodes B3 and B2 are out of the liquid. If the relay does not de-energise, select a lower sensitivity scale. i The electrode connection point must be protected against corrosion by sticking or sealing. In areas where thunderstorms are likely to occur, measures must also be taken to protect the electrode lines. Note: the high level can be raised by means of the adjustable time delay from 0.1 to 10 seconds with function . The low level can be lowered by means of this same time delay with function . Probe LA9-RM201 This probe is of the suspended type. It is coaxial, i.e. in addition to the normal (central) electrode, the stainless steel skirt can also act as earth (reference) electrode, which means that there is no need to install a separate reference probe. In this way, for controlling one level, only one probe is required instead of 2; for controlling 2 levels, only 2 probes are required instead of 3. The connecting cable must be of the 2-conductor type, with common cylindrical PVC sheath, having a maximum diameter of 6.3 mm. The skirt also acts as a calming chamber, so avoiding inaccuracy due to an agitated surface of the liquid (waves). Maximum operating temperature: 100 C. Probe LA9-RM201 can also be fixed on various containers (cisterns, tanks,...) by means of a bracket or other suitable fixing device. Connection examples Control by electrodes Control by probes

R U

2 3

R U

1 2 3 4

RM4-LG01

RM4-LA32

2-conductor cable in cylindrical sheath (max. 6.3 mm) Level electrode

Reference electrode (skirt)

LA9-RM201

28

RM4-LG01

Supply voltage

A1
B1 B2 B3

B1

B2

B3

High level Low level

B2 B3 B1

B2 B1

A2
2 levels 1 level

Te

3/57