Device
Type
3AH
7.2 36
13.1 63
13.1 63
3AF 3AG
12, 36
25
25
7.2 15
25 44
25 44
Vacuum switches
s IEC 265-1 s DIN VDE 0670, Part 301
3CG
7.2 24
16 20
3TL
3.6 12
8 (1s)
Vacuum contactors
s IEC 470 s DIN VDE 0660, Part 103 s UL 347
Vacuum interrupter
VS
7.2 40.5
12.5 72
12.5 72
Switch disconnectors
s s s s
3CJ
7.2 24
16 20 (1s)
IEC 129 IEC 265-1 DIN VDE 0670, Part 2 DIN VDE 0670, Part 301
3D
7.2 36
16 ... 63 (1s)
HV HRC fuses
s IEC 282 s DIN VDE 0670, Part 4
HV HRC fuses
3GD
7.2 36
31.5 80
Fuse bases
3GH
7.2 36
IEC 185, 186 DIN VDE 0414 BS 3938, 3941 ANSI C57.13
3FA
3.6 36
3M
12 36
2/66
Applications/remarks
Page
800 4000
10,000 120,000
10,000 30,000
25 100
All applications, e.g. overhead lines, cables, transformers, motors, generators, capacitors, filter circuits, arc furnaces
2/68
1600
10,000
10,000
30 50
All applications, e.g. overhead lines, cables, transformers, motors, generators, capacitors, filter circuits
2/72
1250 3150
2/73
800
10,000
10,000
All applications, e.g. overhead lines, cables, transformers, motors, capacitors; high number of operations; fuses necessary for short-circuit protection All applications, especially motors with very high number of operating cycles
2/74
400 450
2/76
800 4000
10,000 30,000
10,000 30,000
25 100
2/77
630
1000
20
2/78
400 2500
2/79
6.3 250
2/80
400
2/80
2/81
2/82
2/67
17.5 15
12
breaker which covers the range between 7.2 kV and 24 kV. It has a lifetime of 10,000 operating cycles s 3AH2 the circuit breaker for 60,000 operating cycles in the range between 7.2 kV and 24 kV s 3AH3 the maintenancefree circuit breaker for high breaking capacities in the range between 7.2 kV and 36 kV. It has a lifetime of 10,000 operating cycles s 3AH4 the circuit breaker for up to 120,000 operating cycles s 3AH5 the economical circuit breaker in the lower range for 10,000 maintenancefree operating cycle The 3AH circuit breakers are suitable for:
s Rapid load transfer, synchronization s Automatic reclosing up to 31.5 kA s Breaking short-circuit currents with
7.2 Rated shortcircuit breaking current [kA] Rated current [A] 13.1 800 16 20 25 31.5 40 50 63
- 1250 1250 1250 800 800 800 800 800 1250 -1250 -1250 -2500 -1250 -1250 -2500 2500 -3150 -3150 -4000
3AH1
3AH2
3AH3
3AH4
3AH5
Properties of 3AH circuit breakers: No relubrication Nonwearing material pairs at the bearing points and nonaging greases make relubrication superfluous on 3AH circuit breakers up to 10,000 operating cycles, even after long periods of standstill. High availability Continuous tests have proven that the 3AHs are maintenancefree up to 10,000 operating cycles: accelerated temperature/ humidity change cycles between 25 and +60 C prove that the 3AH functions reliably without maintenance. Assured quality Exemplary quality control with some hundred switching cycles per circuit breaker, certified to DIN/ISO 9001. No readjustment Narrow tolerances in the production of the 3AH permanently prevent impermissible play: even after frequent switching the 3AH circuit breaker does not need to be readjusted up to 10,000 operating cycles.
s s s s s
very high initial rates of rise of the recovery voltage Switching motors Switching transformers and reactors Switching overhead lines and cables Switching capacitors Switching arc furnaces
2/68
Advantages of the vacuum switching principle The most important advantages of the principle of arc extinction in a vacuum have made the circuit breakers a technically superior product and the principle on which they work the most economical extinction method available: s Constant dielectric: In a vacuum there are no decomposition products and because the vacuum interrupter is hermetically sealed there are no environmental influences on it. s Constant contact resistance: The absence of oxidization in a vacuum keeps the metal contact surface clean. For this reason, contact resistance can be guaranteed to remain low over the whole life of the equipment. s Large total current: Because there is little burning of contacts, the rated normal current can be interrupted up to 30,000 times, the short-circuit breaking current an average of 50 times s Small chopping current: The chopping current in the Siemens vacuum interrupter is only 4 to 5 A due to the use of a special contact material. s High reliability: The vacuum interrupters need no sealings as conventional circuit breakers. This and the small number of moving parts inside makes it extremely reliable.
Fig. 113: Front view of vacuum circuit breaker 3AH1 with 160-mm pole center distance. Available up to 17.5 kV
2/69
3AH1, 12 kV
20 kA, up to 1250 A 25 kA, up to 1250 A 210
520 190
437
473
60 Dimensions in mm
3AH1, 3AH2, 12 kV
31.5 kA, 2500 A, 40 kA, 2500 A
550 190
437
583
3AH1, 24 kV
16 kA, up to 1250 A, 20 kA, up to 1250 A, 25 kA, up to 1250 A 275
565 190
535 437
60 Dimensions in mm
Fig. 114a: Dimensions of typical vacuum circuit breakers type 3AH (Examples)
2/70
3AH1, 3AH2, 24 kV
25 kA, 2500 A 275
595 190
437
648
3AH3, 12 kV
63 kA, 4000 A
211
483
564
733
Dimensions in mm
776
3AH3, 3AH4, 36 kV
31.5 kA, 2500 A, 40 kA, 2500 A
211
526
564
791 1000
Dimensions in mm
853
612
Fig. 114b: Dimensions of typical vacuum circuit breakers type 3AH (Examples)
2/71
Technical data Vacuum circuit-breaker type Rated voltage Rated frequency Rated lightningimpulse withstand voltage Rated power-frequency withstand voltage (dry and wet) Rated short-circuit breaking current Rated short-circuit making current Rated current [kV] [Hz] [kV] [kV] [kA] [kA] [A] Type 3AG
12 50/60 75
Type 3AF
36 50/60 170 70 25
28 25
63
63
1600
1600
Front view
1830 190 725 725
Side view
285 285
High reliability Negligible maintenance Suitable for rapid autoreclosing duty Long electrical and mechanical life Completely environmental-friendly
1217
450 650
2/72
High reliability Negligible maintenance Long electrical and mechanical life Completely environment-friendly Suitable for all switching duties Use of these parts allows the OEM to utilize Siemens know-how in the construction of air-insulated switchgear, with all the consequent advantages, such as: oped and manufactured to DIN/ISO 9001
process
s Wide product range
Ratings for withdrawable truck shown in Fig. 118 7.2 kV to 15 kV 1250 A to 3150 A 25 kA to 44 kA rated voltage rated current rated short-circuit breaking current
2/73
Technical data Rated voltage U Rated lightning-impulse withstand voltage Ul, Rated short-circuit making current I ma Rated short-time current I m (3s) Rated normal current I n Rated ring-main breaking current I c 1 Rated transformer breaking current Rated capacitor breaking current Rated cable-charging breaking current I c Rated breaking current for stalled motors I d Inductive switching capacity (cos 0.15) [kV] [kV] [kA] [kA] [A] [A] [A] [A] [A] [A] [A]
7.2 60 50 20 800 800 10 800 63 2500 2500 12 75 50 20 800 800 10 800 63 1600 1600 15 95 50 20 800 800 10 800 63 1250 1250 24 125 40 16 800 800 10 800 63 1250
Overhead lines Cables Transformers Motors Capacitors Switching under ground-fault conditions
3CG switches can be combined with all Siemens fuses (250 A) and comply with the specifications of IEC 420 and DIN VDE 0670 Part 303.
Switching capacity under ground fault conditions: Rated ground fault breaking current I e [A] [A] Rated cable-charging breaking current [A] Rated cable charging breaking current with superimposed load current Number of switching cycles with I n
Fig. 119: Ratings for vacuum switches type 3CG
630 63 63+800
630 63 63+800
630 63 63+800
630 63 63+800
10,000
10,000
10,000
10,000
2/74
264 435
482
43 170
24 kV switch
630 537 275 275
379 435
597
43 170
2/75
280 mm
1200 mm
780 mm 325 mm
340 mm
Fig. 122: Vacuum contactor type 3TL6 for fixed mounting
605 mm
Technical data Vacuum contactor type Rated voltage U e Rated frequency Rated normal current I e [kV] [Hz] [A] 3TL 60
3.6 50/60 450
3TL 61
7.2
3TL 65
12
3TL 81
7.2 50/60 400
Switching capacity according to [A] utilization category AC-4 (cos = 0.35) Rated making current Rated breaking current Mechanical life of the contactor switching cycles Mechanical life of the vacuum interrupter switching cycles Electrical life of the vacuum interrupter (switching cycles with rated current)
Fig. 124: Ratings for vacuum contactors type 3TL
4500 3600 3 x 106 2 x 106 1 x 106 3 x 106 2 x 106 1 x 106 1 x 106 1 x 106 1 x 106
220 mm
375 mm
390 mm
2/76
Vacuum interrupters
Vacuum interrupters for the medium-voltage range are available from Siemens for all applications on the international market from 1 kV up to 40.5 kV. Applications
s s s s s s s
Vacuum circuit breakers Vacuum switches Vacuum contactors Transformer tap switches Circuit breakers for railway applications Autoreclosers Special applications, e.g. in nuclear fusion
Compact design Vacuum interrupters provide a very high switching capacity within very compact dimensions: e.g. vacuum interrupters for 15 kV/40 kA with housing dimensions of 125 mm diameter by 168 mm length or for 12 kV/12.5 kA with 68 mm diameter by 124 mm length. Consistant quality assurance Complete quality assurance (TQM and DIN/ISO 9001), rigorous material checking of every delivery and 100% tests of the interrupters for vacuum sealing guarantee reliable operation and the long life of Siemens vacuum interrupters. Environmental protection In the manufacture of our vacuum interrupters we only use environmentally compatible materials, such as copper, ceramics and high-grade steel. The manufacturing processes do not damage the environment. For example, no CFCs are used in production (fulfilling the Montreal agreement), the components are cleaned in a ultrasonic cleaning plant. During operation vacuum interrupters do not affect the environment and are themselves not affected by the environment. Know-how for special applications If necessary, Siemens is prepared to supplement our wide standard program by way of tailored, customized concepts.
Un
In Isc
Un
In
1 kV 12 kV 450 A
2/77
Technical data Rated voltage Rated short-time current Rated short-circuit making current Rated normal current [kV] [kA]
7.2 20 12 20 15 16 24 16
[kA]
50
50
40
40
[A]
630
630
630
630
2/78
Technical data Rated voltage Rated short-time current Rated short-circuit making current Rated normal current [kV] [kA]
12 16 to 63 24 16 to 31.5 36 20 to 31.5
[kA]
40 to 160
40 to 80
50 to 80
[A]
400 to 2500
630 to 2500
630 to 2500
Technical data Rated voltage Rated short-time current Rated peak withstand current [kV] [kA]
12 20 to 63 24 20 to 31.5 36 20 to 31.5
[kA]
50 to 160
50 to 80
50 to 80
2/79
Technical data Rated voltage Rated short-circuit breaking current Rated normal current
[kV] [kA]
7.2 63 to 80
12 40 to 63
24 31.5 to 40
36 31.5
is made of pure silver s Thermal tripping s Absolutely watertight s Low power loss With our 30 years of experience in the manufacture of HV HRC fuse links and with production and quality assurance that complies with DIN/ISO 9001, Siemens HV HRC fuse links meet the toughest demands for safety and reliability.
[A]
6.3 to 250
6.3 to 160
6.3 to 100
6.3 to 40
3GH HV HRC fuse bases are available as single-phase and three-phase versions. On request, a switching state indicator with an auxiliary switch can be installed.
Fig. 135: Fuse bases type 3GH with HV HRC fuse links
3.6/7.2 44
12 44
24 44
36 44
[A]
400
400
400
400
2/80
Technical data Normal voltage Lightning-impulse withstand voltage Rated power-frequency withstand voltage Minimum failing load [kV] [kV] [kV] [kN]
3.6 60 to 65 27 to 40 3.75 to 16 12 65 to 90 35 to 50 3.75 to 25 24 100 to 145 55 to 75 3.75 to 25 36 145 to 190 75 to 105 3.75 to 16
U1 U U2
C1
L Conductor U Operating voltage U1 Partial voltage across C1 U2 Partial voltage across C2 and indicator
C2
Fig. 140: The principle of capacitive voltage indication with the 3FA4 divider post insulator
2/81
Technical data Current transformers Rated voltage Primary rated current [kV] [A]
12 10 to 2500 80 24 10 to 2500 80 36 10 to 2500 80 5 to 10 5 to 13 8 to 17
Voltage transformers
12 24 36
Max. thermal rated [kA] short time current Sec. thermal limit current [A]
2/82