Analog Programmable Controller Wiring Systems

(Catalog Number 1492-AIFM__-__-__) Product Data

Contents
This product data contains:
Section Description Wiring System Features and Benefits Features and Benefits of Pre-wired Cables AIFM Options and Features Feedthrough Modules Fusible Modules Accessories How to Order Pre-wired Cables and AIFMs AIFM Catalog Number Explanation Cable Catalog Number Explanation Pre-wired Cable and AIFM Selection Table for Analog I/O Modules Cable Technical Section Pre-wired Cable Specifications Pre-wired Cable Pinouts AIFM Technical Section Specifications, Application Notes, and Pinouts Dimensions Adhesive Label Cards Field-Side Wiring Diagrams Reference Publications Page 3 3 4 4 5 6 8 9 9 10 10 12 12 13 15 16 25 26 33 57

Analog Programmable Controller Wiring Systems

Description

The Bulletin 1492 Analog Programmable Controller Wiring System Product Line consists of Analog Interface Modules (AIFMs) and Pre-wired Cables. These products are designed to aid in the installation of Allen-Bradley Programmable Controller Analog I/O Modules. AIFMs and pre-wired cables replace the terminal blocks and up to 50% of the point-to-point wiring between the programmable controller and field devices. They are available for over 20 different 4-, 6-, 8-, and 16-channel 1746 SLC 500, 1756 ControlLogix, and 1771 PLC analog I/O modules. AIFMs allow you to conveniently incorporate additional terminations and overcurrent protection into your I/O circuitry.

Features and Benefits of Analog Wiring Systems

Faster Installation Time


Pre-wired cables have the I/O module terminal block or wiring arm already wired-up on one end and a D-shell connector on the other. No need to measure, cut, strip, label, and terminate 20 to 40 wires per I/O module. Simply attach the wiring arm or removable terminal block end of the cable to the I/O module and attach the D-shell connector end of the cable to the AIFM and you are ready to wire out to field devices.

Successful System Start-ups


The pre-wired cables are 100% tested for continuity. No more crossed wires and loose connections between the I/O module and the terminal blocks on the DIN rail. With the pre-wired cable and AIFM, your application will have a much higher rate of success at initial start-up.

Simplified Troubleshooting
Fusible AIFMs provide termination for input modules as well as the ability to incorporate overcurrent protection for transmitters. On-board 24V blown fuse indicators help to quickly identify which input had the fault reducing costly troubleshooting and downtime.

Reduced Panel Space


All of the AIFMs have field-side wiring terminals for the I/O channels as well as extra terminals for the I/O device shield connections. Most input AIFMs also have extra terminals that are internally commoned together and can be used as power busses for input devices. No additional terminal blocks are needed to provide power to the 2-, 3-, and 4-wire transmitters saving valuable panel/DIN rail space. Just bring in one power connection per group to the commoned terminals and terminate the other side of your input devices to the power bus. Complete and compact wiring all on one AIFM!

Quality-Looking Panel
The pre-wired cables and AIFMs organize your wiring and terminations for a consistent look to your panel. Pre-printed adhesive labels for the terminal wiring neatly identify field-side connections.

Analog Programmable Controller Wiring Systems

Features and Benefits of Pre-wired Cables

Pre-wired cables have the I/O module removable terminal block or wiring arm already wired up on one end and a D-shell connector on the other to attach to the AIFM. They are available for over 20 different 4-, 6-, 8-, and 16-channel 1746 SLC 500, 1756 ControlLogix, and 1771 PLC analog I/O modules. All of the pre-wired cables are 100% tested for continuity to help ensure a positive connection.

Cables Fit Your Panel


All of the Bulletin 1492 pre-wired analog cables are offered in four standard lengths of 0.5m, 1.0m, 2.5m, and 5.0m to fit a variety of applications. Custom length cables (made to order) are also available.

Secure Connections
All cables have a 15- or 25-pin D-shell connector with a slide-locking mechanism for secure connection to the AIFM.

Maintained Signal Integrity


Most cables utilize twisted pairs and all have an overall shield to aid noise immunity of low-level analog signals.

Convenient Grounding
Most cables have a prepared drain wire with a ring lug at the I/O module end of the cable for convenient grounding of the cable shield to the chassis, if desired. Other cables directly terminate the drain wire to an internally grounded shield terminal on the I/O module connector.

AIFM Options and Features

AIFMs, similar to groups of terminal blocks, are available with either 15or 25-pin D-shell connectors. The number of field-side wiring terminals varies with the type of module from three to five terminals per I/O channel. AIFMs are available as feed-through or fusible to customize the wiring system to your application. All of the AIFMs have the following features:

Large rectangular write-on area acts as built-in group marking carrier for programmable controller rack, module group, and/or slot information.

Polarized D-shell connector for easy installation. Pre-wired cable has mating D-shell connector with slide-locking mechanism for secure connection. Pre-printed and blank adhesive marking strips are provided to identify either the programmable controller I/O field-side wiring terminals or your own application requirements. High-density field-side wiring terminals allow more connections in less space and accommodate #22-12 AWG wire. Continuous current rating of 2 amps per circuit supports higher-current programmable controller output modules.

UL Component Recognized (File E113724 Guide NRAQ2); UL recognized per Canadian Safety Standards (cUR) (File E113724 Guide NRAQ2); and CE Approved.

Standard DIN #3 rail mounting for quick installation.

Analog Programmable Controller Wiring Systems

Feed-through Modules

Feed-through AIFMs have three terminals per I/O channel to wire the I/O module connections and device shield. The shield terminals are internally bussed together and also tied to the D-shell housing to connect with the cable shield. Some feed-through AIFMs also have special features listed below. The 1492-AIFM4-3, when used with the 1771-OFE2 and -OFE3, provides selectable current limiting resistors. Simply flip a DIP switch to add the 250 ohms series impedance into the output circuit. As a troubleshooting aid, test point loops access the circuit on either side of the series resistor and can be used to measure output circuit voltage/current. The limiting resistors are configured on a per channel basis. The 1492-AIFM6TC-3 for the 1756-IT6I provides on-board cold junction compensation to allow thermocouples to be connected remotely while still correcting for temperature at the termination point. The combination thermistor and isothermal bar acquire temperature data at the AIFM for the thermocouple module to adjust the input value. The 1492-AIFM8-3 has 8 extra terminals commoned together in a power bus that can be used for Module Common connections or power supply connections. The extra terminals and internal jumpering eliminate the need for some terminal blocks for power connections and jumper accessories. Below are examples of the field-side connections available on the feed-through AIFMs.
4-Wire Transmitter Input
AIFM 1+ Power Supply Transmitter 1 Channel 1 SHIELD Pre-wired Cable Channel 1+ Analog Input Module

Output
0 LOAD

AIFM Pre-wired Cable

Analog Output Module OUT 0

C ANL COM SH

Analog Programmable Controller Wiring Systems

Fusible Modules

Fusible AIFMs are available for analog input modules. These AIFMs enable you to fuse the input device power source on the field-side. The field-side power source is distributed through individual on-board 5 x 20mm fuse clips. The AIFMs have 24V DC blown fuse indicators to reduce the troubleshooting time to locate and replace a blown fuse. Standard fuse holders reside in the AIFM aiding in the removal of the fuse with a fuse puller (fuses are not included). Isolation switch plugs or dummy fuses (see Accessories, page 7) are also available to isolate an input circuit once power is removed. In addition, once the circuit has been isolated and power restored, the input loop current can be measured in 2-wire transmitter applications. The fusible AIFMs have five terminals per input channel (except the AIFM16-F-3 which has three terminals per channel) to wire the input module connections, device shield, and power connections for 2-, 3-, and 4-wire transmitters. The shield terminals are internally bussed together and also tied to the D-shell housing to connect with the cable shield. There are two separate power busses (from 4 to 16 terminals depending on the AIFM) that can be used for +V and DC COM connections and/or Module Common. The extra terminals and internal connections eliminate additional terminal blocks and jumpers reducing spare parts inventory, saving panel space, and simplifying installation. All of the fusible AIFMs have on-board DIP switches to easily connect unused inputs to module common reducing wiring on the field-side. You no longer need extra jumper wires or comb-style jumpers to properly terminate unused inputs as recommended on many 1746 and 1771 analog input modules. Inputs are jumpered via DIP switch on a per channel basis.

Analog Programmable Controller Wiring Systems

Fusible Modules, continued

The 1492-AIFM4I-F-5 and 1492-AIFM4C-F-5 both have test point loops on either side of the fuse clips for easier access and connection of metering equipment. Metering equipment can also be attached to the fuse clips on other AIFMs for measuring input loop current. Below are examples of the field-side connections for 2- and 4-wire transmitters available on the fusible AIFMs.

2-Wire Transmitter
AIFM +V Power Supply Transmitter V1 Analog Input Module 1+ SHIELD 1 Channel 1 VCOM Pre-wired Cable Channel 1+

4-Wire Transmitter
AIFM +V Power Supply V1 Analog Input Module 1+ Transmitter 1 Channel 1 SHIELD VCOM Pre-wired Cable Channel 1+

Analog Programmable Controller Wiring Systems

Accessories

Cat. No. 1492-IFMFH1 Fuse Holder

Cat. No. 1492-ISOSW-1 Isolation Switch Plug

Cat. No. 1492-SJM5-10 Insulated Side Jumper

Replacement Fuse Holders


The 1492-IFMFH1 fuse holders accommodate a 5 x 20mm fuse or the 1492-ISOSW-1 isolation switch plug and reside in the AIFM under normal operation. All of the fusible 1492 AIFMs come standard with the fuse holders (10 fuse holders with the 1492-AIFM4C-F-5, -AIFM4I-F-5, and -AIFM8-F-5; 20 fuse holders with the 1492-AIFM16-F-3, and -AIFM16-F-5). Replacement fuse holders are available in packages of 20.

Isolation Switch Plugs


The 1492-ISOSW-1 is an isolation switch or dummy fuse in a 5 x 20mm fuse form factor. The isolation switch plugs will fit into the 1492-IFMFH1 fuse holders. If fusing is not desired on a fusible AIFM, the 1492-ISOSW-1 can be used to provide feed-through functionality under normal operation and isolation switch functionality once power has been removed from the circuit. The isolation switch can then be opened for maintenance and troubleshooting. Metering equipment can also be inserted into a 2-wire transmitter circuit to measure input loop current. The 1492-ISOSW-1 isolation switch plugs are available in packages of 4.

Insulated Side Jumpers


The 1492-SJM5-10 is a 10-pole comb-style insulated side jumper. A side cutter can be used to cut the 10-pole jumper into smaller pole assemblies. The jumper fits the field-side terminal spacings on all of the 1492-AIFMs and is a convenient means of connecting unused inputs together on the feed-through AIFMs. The 1492-SJM5-10 insulated side jumpers are available in packages of 10.

Analog Programmable Controller Wiring Systems

How to Order Pre-wired Cables and AIFMs

To order the proper pre-wired cable and AIFM, you need to know: 1. The catalog number(s) of the analog I/O modules. 2. The desired cable length (0.5m, 1.0m, 2.5m, 5.0m or custom length). 3. If fusing for inputs is needed. 4. If additional terminals for field devices are needed. Refer to the pre-wired cable and AIFM selection table on page 10. For more information, refer to the technical section on pre-wired cables on page 11, and to the technical section on AIFMs on page 15.

AIFM Catalog Number Explanation


Important:
The following AIFM catalog number breakdown is for explanation purposes only. It is not a product configurator. All combinations of fields are not valid product catalog numbers. First, select the desired AIFM using the steps in How to Order Pre-wired Cables and AIFMs. Then use this breakdown for verification and explanation only.

1492 - AIFM
Bulletin Number
Product Type IFM Digital Interface Module AIFM Analog Interface Module

16 - F - 5
3 5 Input Fuse Clips & Blown Fuse Indication Blank No Fuse Clips F 5 x 20mm Fuse Clips with 24V DC Blown Fuse Indicators Number of Field-Side Terminals Three per I/O Channel Five per Input Channel

4 4C 4I 6S 6TC 8 16

Number of Analog I/O Channels Four Channels: Input, Output, or 2-In/2-Out Combination Four Channels: 2-In/2-Out Combination Four Channels: Input Six Channels: Isolated Input or Output Six Channels: Thermocouple Input Eight Channels: Input or Output Sixteen Channels: Input

Analog Programmable Controller Wiring Systems

Cable Catalog Number Explanation

The following cable catalog number explanation may be used as a product configurator. All combinations of fields indicated produce valid product catalog numbers.

1492 - ACABLE
Bulletin Number
ACABLE Product Type Analog Interface Cable

050

A
Cable Type A, B, C, D, L Pre-wired cables for 1746 Analog & RTD I/O Modules E, F, G, H, J Pre-wired cables for 1771 Analog & RTD I/O Modules X, Y, Z Pre-wired cables for 1756 Analog, RTD, & Thermocouple I/O Modules

Standard Cable Length 005 0.5 meter (1.64 feet) 010 1.0 meter (3.28 feet) 025 2.5 meter (8.20 feet) 050 5.0 meter (16.40 feet)

001020 020100 100990

Custom Cable Length 0.12.0 meter (0.3286.56 feet) 0.1 meter (0.328 feet) increments 2.010.0 meter (6.5632.8 feet) 0.5 meter (1.64 feet) increments 10.099.0 meter (32.8374.72 feet) 1.0 meter (3.28 feet) increments

Refer to cable selection table on page 10 for proper AIFM and I/O module compatibility.

Pre-wired Cable and AIFM Selection Table for Analog I/O Modules

To use: Locate your I/O Module in one of the shaded areas. Follow down the selected column to the cable selection code that indicates the compatible AIFMs. If the space is blank, the I/O Module and AIFM are not recommended for use together. Select the catalog number of the desired AIFM. Refer to the page number indicated for technical information on the AIFM.

Note:

To configure a cable catalog number, order 1492-ACABLE. Cables are available in 0.5, 1.0, 2.5, and 5.0m lengths. Insert the cable length code into the catalog number. Cable length codes are as follows: 005 = 0.5m, 010 = 1.0m, 025 = 2.5m, and 050 = 5.0m. All 1492 cables are also available in custom lengths. Contact your local Allen-Bradley distributor or sales office for availability.
Custom Cable Lengths Length
0.1m2.0m 2.0m10.0m 10.0m99.0m

Increment Size
0.1m 0.5m 1.0m

Cable Length Codes


001020 020100 100990

Examples
1492-ACABLE015A 1492-ACABLE075B 1492-ACABLE150F

Note:

Some I/O modules may have recommended maximum cable lengths. Refer to the appropriate I/O module Product Data Publication for more information. Insert cable selection code (see table on next page). Example: 1492-ACABLE005A is a 0.5m cable for the 1746-NI4 input module.

10

Analog Programmable Controller Wiring Systems

Pre-wired Cable and AIFM Selection Table for Analog I/O Modules, continued
I/O Module Catalog Number 1771-IFE (Single-Ended) 1771-IFE (Differential) 1756-IF6I (Current) { 1756-IF6I (Voltage) }

1746-NIO4V

1756-OF6CI[ Y

1771-OFE2

1771-OFE1

1771-OFE3

Description 4-Channel with 3 terminals per channel and selectable 250 current limit resistors for 1771-OFE. 6-Channel isolated with 34 terminals per channel.

Cat. No. 1492-

Page

AIFM4-3

16

1771-IR

1771-IL

Type of IFM

Feedthro ough

AIFM6S-3

17

D C E F H

8-Channel with 3 terminals per channel. AIFM8-3 Thermocouple 6-Channel with 3 AIFM6TC-3 terminals per channel. 2-Channel with 24V Blown Fuse Indicators, test points, 5 terminals AIFM4C-F-5 per input, and 3 terminals per output. 4-Channel with 24V Blown Fuse Indicators, AIFM4I-F-5 test points, and 5 terminals per input. 8-Channel with 24V Blown Fuse Indicators AIFM8-F-5 and 5 terminals per input. 16-Channel with 24V Blown Fuse Indicators AIFM16-F-3 and 3 terminals per input. 16-Channel with 24V Blown Fuse Indicators AIFM16-F-5 and 5 terminals per input. { } [ Fusible

18

19

20

21

22

23

24

All channels in 1492-ACABLE_ _ _X are configured for current mode. For each voltage channel, a jumper wire must be removed. All channels in 1492-ACABLE_ _ _Y are configured for voltage mode. For each current channel, a user-supplied jumper wire must be installed. All channels in 1492-ACABLE_ _ _Y are configured for 0550 ohm loads. For each channel with 5511000 ohm load, a wire must be moved to a different terminal.

1756-OF6VI Y

1746-FIO4V

1746-NO4V

1746-FIO4I

1746-NIO4I

1746-NO4I

1746-NR4

1756-IR6I

1746-NI4

1746-NI8

1756-IT6I

Analog Programmable Controller Wiring Systems

11

Cable Technical Section

Bulletin 1492 Pre-wired Cables are designed to minimize control wiring in a panel. When used with an AIFM, the cables replace the point-to-point wiring between Allen-Bradley programmable controller I/O modules and individual terminal blocks. The pre-wired cables have a 1746 or 1756 Removable Terminal Block or 1771 Wiring Arm on one end and a D-Shell connector on the other to connect to the AIFM. The broad offering of pre-wired cables supports over 20 different SLC 500, ControlLogix, and PLC analog, RTD and thermocouple I/O modules. Refer to the Selection Table on page 10 for proper I/O module, AIFM, and pre-wired cable coordination.

Analog Pre-wired Cable Specifications Cat. No. and Length


1492-ACABLEA 1492-ACABLEB 1492-ACABLEC 1492-ACABLED 1492-ACABLEE 1492-ACABLEF 1492-ACABLEG 1492-ACABLEH 1492-ACABLEJ 1492-ACABLEL 1492-ACABLEX 1492-ACABLEY 1492-ACABLEZ

I/O Module Connector


1746-RT28 12-Position Removable Terminal Block 1746-RT26 2-Position and 1746-RT27 8-Position Removable Terminal Block 1746-RT25G Green Removable Terminal Block 1746-RT25G Green Removable Terminal Block 1771-WG (21 terminal) Wiring Arm 1771-WG (21 terminal) Wiring Arm 1771-WC (10 terminal) Wiring Arm 1771-WF (18 terminal) Wiring Arm 1771-WF (18 terminal) Wiring Arm 1746-RT28 12-Position Removable Terminal Block 1756-TBNH 20-Position Removable Terminal Block 1756-TBNH 20-Position Removable Terminal Block 1756-TBNH 20-Position Removable Terminal Block

AIFM Connector
15-pin D-Shell 15-pin D-Shell 25-pin D-Shell 25-pin D-Shell 25-pin D-Shell 25-pin D-Shell 15-pin D-Shell 25-pin D-Shell 25-pin D-Shell 15-pin D-Shell 25-pin D-Shell 25-pin D-Shell 25-pin D-Shell

General Description
5 Twisted Pairs 5 Twisted Pairs 9 Twisted Pairs 20 Conductors 9 Twisted Pairs 20 Conductors 5 Twisted Pairs 9 Twisted Pairs 20 Conductors 5 Twisted Pairs 9 Twisted Pairs 9 Twisted Pairs 20 Conductors

Insulation Conductor Rating Size


300V 80_C 300V 80_C 300V 80_C 300V 80_C 300V 80_C 300V 80_C 300V 80_C 300V 80_C 300V 80_C 300V 80_C 300V 80_C 300V 80_C 300V 80_C #22 AWG #22 AWG #24 AWG #22 AWG #24 AWG #22 AWG #22 AWG #24 AWG #22 AWG #22 AWG #24 AWG #24 AWG #22 AWG

Nominal Outer Diameter .293 in. (7.44mm) .293 in. (7.44mm) .267 in. (6.78mm) .332 in. (8.43mm) .267 in. (6.78mm) .332 in. (8.43mm) .293 in. (7.44mm) .267 in. (6.78mm) .332 in. (8.43mm) .293 in. (7.44mm) .267 in. (6.78mm) .267 in. (6.78mm) .332 in. (8.43mm)

Cables are available in lengths of 0.5m, 1.0m, 2.5m and 5.0m. To order, insert the desired cable length code into the catalog number (005 = 0.5m, 010 = 1.0m, 025 = 2.5m, and 050 = 5.0m). Example: Cat. No. 1492-ACABLE005A is for a 0.5m cable for the 1746-NI4 I/O Module. See also Custom Cable Lengths table on page 9. All pre-wired analog cables have an overall shield. On 1492-ACABLEC and 1492-ACABLED, the drain wire is connected to the shield terminal on the I/O module connector. All other 1492-ACABLEs have a ring lug on the 7.87 (200mm) exposed drain wire at the I/O module end of the cable. 1 pair not wired to I/O module connector. 7 conductors not wired to I/O module connector; 1 additional conductor not used. 1 conductor not wired to I/O module connector; 1 additional conductor not used. 1 pair not used. 1 pair not wired to I/O module connector; 2 additional pairs not used. 2 pairs not used. D-Shell Connector Dimensions
15-Pin D-Shell
2.4 60mm 1.6 39mm 0.7 17mm 2.9 73mm

25-Pin D-Shell
0.7 17mm 1.6 39mm

1.8 44mm

2.3 58mm

12

Analog Programmable Controller Wiring Systems

Pre-wired Cable Pinouts

The following diagrams indicate how the analog pre-wired cables are pinned out on both ends. The description listed first is the wire color of the conductor connected to the screw terminal on the respective Wiring Arm or Removable Terminal Block. The number that follows in parentheses is the corresponding pin number in the D-Shell connector on the other end. For example:
Base Color Stripe Color

Blue (24) NC Black (23)

White/Green (22) D-Shell Connector Pin Number White/Red (19)

No Connection Twisted Pair Jumper Wire

Individual Conductor

0 1 2 3 4 5 6 7 8 9 10 11

Red (8) Black (15) NC White (14) Black (13) Yellow (2) Green (12) Black (11) NC Blue (10) Black (9) Black (1)

0 1

Yellow (2) Black (1)

0 1 2 3 4 5 6 7 8 9 10 11

Red (8) Black (15) NC White (14) Black (13) NC NC Green (11) Black (2) NC Blue (9) Black (1)

0 1 2 3 4 5 6 7

Red (8) Black (15) White (14) Black (13) Green (12) Black (11) Blue (10) Black (9)

1492-ACABLE_ _ _A Twisted pair. NC Red (3) Black (2) White (1) Black (14) Green (15) Black (16) Blue (17) Black (18) Yellow (12) Black (13) Brown (25) Black (24) Orange (23) Black (22) Red (20) White (21) Drain 1492-ACABLE_ _ _C NC

1492-ACABLE_ _ _B

1492-ACABLE_ _ _L

NC Blue (13) White/Blue (24) White/Violet (25) White/Green (23) Green (12) Yellow (11) NC NC White/Yellow (22) White/Red (19) White/Orange (21) White/Brown (18) Orange (9) Red (6) NC Drain 1492-ACABLE_ _ _D 1492-ACABLE_ _ _G Red (8) Black (15) White (14) Black (13) Green (12) Black (11) Blue (10) Black (9) NC NC A 0 1 2 3 4 5 6 7 B

Analog Programmable Controller Wiring Systems

13

Pre-wired Cable Pinouts, continued


18 16 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 NC Orange (23) Black (22) Red (20) White (21) Red (6) Green (19) NC Yellow (12) Black (13) Brown (25) Black (24) NC Green (15) Black (16) Blue (17) Black (18) Red (3) Black (2) White (1) Black (14) 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 Red (3) Brown (2) Black (1) White (14) Orange (4) White/Black (15) White/Brown (16) White/Red (17) White/Orange (18) Blue (10) Violet (12) Gray (13) White/Black/Brown (25) White/Gray (24) Green (8) White/Violet (23) White/Blue (22) White/Yellow (20) White/Green (21) Yellow (6) NC 1492-ACABLE_ _ _H 18 16 14 12 10 8 6 4 2 White/Violet (25) Green (12) Blue (13) White/Green (23) Yellow (11) White/Blue (24) White/Orange (21) Orange (9) White/Yellow (22) White/Brown (18) Red (6) White/Red (19) White (16) Brown (4) White/Black (17) Violet (14) Black (2) Gray (15) 2 8 6 4 12 10 NC NC Yellow (12) Black (13) Brown (25) Black (24) Orange (23) Black (22) Red (20) White (21) 14 Red (3) Black (2) White (1) Black (14) Green (15) Black (16) Blue (17) Black (18)

1492-ACABLE_ _ _E

1492-ACABLE_ _ _F

1492-ACABLE_ _ _J
2 1 2 1 2 1

Blue (24)

Red (13)

Blue (24) NC NC

Red (13)

White/Blue (24) Yellow (11)

Blue (13) Green (12) White/Violet (25) White/Yellow (22) Orange (9) White/Orange (21) NC White/Black (17) Brown (4) White (16)
20 19

Black (23) Yellow (19)

Black (25) White (22)

Black (23) Yellow (19) NC

Black (25) White (22)

White/Green (23) White/Red (19) Red (6)

Black (18) NC Orange (15) NC

Black (21)

Black (18) Brown (6) Black (20) Orange (15) NC

Black (21) NC Green (17) NC Black (16)


20 19

White/Brown (18) NC Gray (15) Black (2) Violet (14)

Green (17)

Black (14)
20 19

Black (16)

Black (14)

1492-ACABLE_ _ _X

1492-ACABLE_ _ _Y

1492-ACABLE_ _ _Z

14

Analog Programmable Controller Wiring Systems

AIFM Technical Section


AIFM Cat. No.
1492-AIFM4-3 1492-AIFM6S-3 1492-AIFM8-3 1492-AIFM6TC-3 1492-AIFM4C-F-5 1492-AIFM4I-F-5 1492-AIFM8-F-5 1492-AIFM16-F-3 1492-AIFM16-F-5

Page No. for Specifications, Application Notes & Pinout


15 16 17 18 19 20 21 22 23

Page No. for Adhesive Label Card


27 29 30 29 28 28 31 31 32

For all AIFM dimensions, see page 24. For general Adhesive Label Card information, see page 26. For Field-Side Wiring Diagrams per I/O module, see pages 3356.

Symbology Used Throughout Pinout and Wiring Sections


= 1492-AIFM Field-Side Terminal

1492 Pre-wired Cable

I/O Module Connection

Fuse and Blown Fuse Indicator

1-Pole DIP Switch

2-Pole DIP Switch

1492-AIFM and Cable Connection (D-shell pin)

Test Point

Field-Side Terminal Identification Convention:

C1

C2

C3 C4

C5 . . .

B1 B2 B3 B4 B5 . . .

B1

B2

B3

B4

B5 . . .

A1 A2 A3 A4 A5 . . .

A1 A2

A3 A4

A5 . . .

Analog Programmable Controller Wiring Systems

15

1492-AIFM4-3
Specifications
Approvals UL Component Recognized (File E113724 Guide NRAQ2) UL Recognized per Canadian Safety Standards (cUR) (File E113724 Guide NRAQ2) CE Approved 0132V AC/DC 600Vp 2A 12A 4 #22#12 AWG (0.24mm2) 0.32 (8mm) 3.54.5 lb.-in. (0.380.50 Nm) 0_C to +60_C

Voltage Rating Maximum Peak Voltage Maximum Current (per Circuit) Maximum Current (per Module) Indicator Circuit Current (Nominal) No. of Terminals per Shield Common Wire Range (Rated Cross Section) Wire Strip Length Recommended Tightening Torque Operating Temperature Range

For transients >600Vp, use a UL recognized suppression device rated at 2.5kV withstand. Maximum number of the same gauge stranded copper conductors allowed per wire funnel: AWG No. of Wires #22 3 #20
3

#18 3

#16 2

#14 1

#12
1

Application Notes
1. Compatibility To ensure proper operation with the I/O module, do not exceed the voltage and current ratings of the AIFM. 2. Wiring Refer to the Label Section on page 26 and the Field-Side Wiring Diagrams on page 33. 3. DIP Switches Selectable resistors are available to current limit the 1771-OFE2 and -OFE3 output circuits. By opening the switch (off or down position), 250 series impedance is inserted into the output circuit. Default switch position is on/closed/no series impedance. Do not exceed maximum loop impedance of output module (1200 for -OFE2; 450 for -OFE3). 4. Test Points With optional 250 series impedance in output circuit (see DIP Switches), test points can be used to measure loop voltage/current. Refer to the Pinout for test point circuit location. 5. Shield Terminals Four field-side terminals are jumpered together on the AIFM and internally connected to the D-shell housing. 6. Dimensions See page 24.

Pinout
2 1 TP1 8 TP2 A3 B3 A7 B7 A1

15 TP3 14 TP4

A2

A5

13 TP5 12 TP6

A6

B1

11 TP7 10 TP8

B2

B5

9 D-Shell Housing

B6

A4 A8 B4 B8

16

Analog Programmable Controller Wiring Systems

1492-AIFM6S-3
Specifications
Approvals UL Component Recognized (File E113724 Guide NRAQ2) UL Recognized per Canadian Safety Standards (cUR) (File E113724 Guide NRAQ2) CE Approved 0132V AC/DC 600Vp 2A 12A 6 #22#12 AWG (0.24mm2) 0.32 (8mm) 3.54.5 lb.-in. (0.380.50 Nm) 0_C to +60_C

Voltage Rating Maximum Peak Voltage Maximum Current (per Circuit) Maximum Current (per Module) Indicator Circuit Current (Nominal) No. of Terminals per Shield Common Wire Range (Rated Cross Section) Wire Strip Length Recommended Tightening Torque Operating Temperature Range

For transients >600Vp, use a UL recognized suppression device rated at 2.5kV withstand. Maximum number of the same gauge stranded copper conductors allowed per wire funnel: AWG No. of Wires #22 3 #20
3

#18 3

#16 2

#14 1

#12
1

Application Notes
1. Compatibility To ensure proper operation with the I/O module, do not exceed the voltage and current ratings of the AIFM. 2. Wiring Refer to the Label Section on page 26 and the Field-Side Wiring Diagrams on page 33. 3. Shield Terminals Six field-side terminals are jumpered together on the AIFM and internally connected to the D-shell housing. 4. Dimensions See page 24.

Pinout
13 12 25 24 11 23 22 9 21 19 6 18 17 4 16 15 2 14 D-Shell Housing A2 A4 A6 A8 A10 A12 B1 A1 B2 B3 A3 B4 B5 A5 B6 B7 A7 B8 B9 A9 B10 B11 A11 B12

Analog Programmable Controller Wiring Systems

17

1492-AIFM8-3
Specifications
Approvals UL Component Recognized (File E113724 Guide NRAQ2) UL Recognized per Canadian Safety Standards (cUR) (File E113724 Guide NRAQ2) CE Approved 0132V AC/DC 600Vp 2A 12A 8 #22#12 AWG (0.24mm2) 0.32 (8mm) 3.54.5 lb.-in. (0.380.50 Nm) 0_C to +60_C

Voltage Rating Maximum Peak Voltage Maximum Current (per Circuit) Maximum Current (per Module) Indicator Circuit Current (Nominal) No. of Terminals per Shield Common Wire Range (Rated Cross Section) Wire Strip Length Recommended Tightening Torque Operating Temperature Range

For transients >600Vp, use a UL recognized suppression device rated at 2.5kV withstand. Maximum number of the same gauge stranded copper conductors allowed per wire funnel: AWG No. of Wires #22 3 #20
3

#18 3

#16 2

#14 1

#12
1

Application Notes
1. Compatibility To ensure proper operation with the I/O module, do not exceed the voltage and current ratings of the AIFM. 2. Wiring Refer to the Label Section on page 26 and the Field-Side Wiring Diagrams on page 33. 3. Extra Terminals Eight field-side terminals are jumpered together on the AIFM. For some I/O modules, the terminals are also internally connected to module common through the pre-wired cable. Refer to the AIFM and ACABLE pinouts. 4. Shield Terminals Eight field-side terminals are jumpered together on the AIFM and internally connected to the D-shell housing. 5. Dimensions See page 24.

Pinout
3 2 1 14 15 16 17 18 12 13 25 24 23 22 20 21 B1 B2 B3 B4 B5 B6 B7 B8 B9 B10 B11 B12 B13 B14 B15 B16

4 6 8 10 19

A9 A10 A11 A12 A13 A14 A15 A16 D-Shell Housing A1 A2 A3 A4 A5 A6 A7 A8

18

Analog Programmable Controller Wiring Systems

1492-AIFM6TC-3
Specifications
Approvals UL Component Recognized (File E113724 Guide NRAQ2) UL Recognized per Canadian Safety Standards (cUR) (File E113724 Guide NRAQ2) CE Approved 0132V AC/DC 600Vp 2A 12A 6 #22#12 AWG (0.24mm2) 0.32 (8mm) 3.54.5 lb.-in. (0.380.50 Nm) 0_C to +60_C

Voltage Rating Maximum Peak Voltage Maximum Current (per Circuit) Maximum Current (per Module) Indicator Circuit Current (Nominal) No. of Terminals per Shield Common Wire Range (Rated Cross Section) Wire Strip Length Recommended Tightening Torque Operating Temperature Range

For transients >600Vp, use a UL recognized suppression device rated at 2.5kV withstand. Maximum number of the same gauge stranded copper conductors allowed per wire funnel: AWG No. of Wires #22 3 #20
3

#18 3

#16 2

#14 1

#12
1

Application Notes
1. Compatibility To ensure proper operation with the I/O module, do not exceed the voltage and current ratings of the AIFM. 2. Wiring Refer to the Label Section on page 26 and the Field-Side Wiring Diagrams on page 33. 3. Shield Terminals Six field-side terminals are jumpered together on the AIFM and internally connected to the D-shell housing. 4. Cold Junction Compensation This AIFM contains on-board cold junction compensation through a thermistor and isothermal bar mounted to the fieldside terminals. Do NOT install the additional cold junction sensor (provided with the 1756-IT6I thermocouple input module) on the removable terminal block of the pre-wired cable. 5. Dimensions See page 24.

Pinout
13 25 24 23 22 21 19 18 17 16 15 14 6 T 20 12 11 9 4 2 A1 A3 A5 A9 A11 B1 B2 B3 B4 B5 B6 B7 B8 B9 B10 B11 B12 A7

D-Shell Housing A2 A4 A6 A8 A10 A12

Analog Programmable Controller Wiring Systems

19

1492-AIFM4C-F-5
Specifications
Approvals UL Component Recognized (File E113724 Guide NRAQ2) UL Recognized per Canadian Safety Standards (cUR) (File E113724 Guide NRAQ2) CE Approved 1030V DC 600Vp 2A 12A 2mA 4 #22#12 AWG (0.24mm2) 0.32 (8mm) 3.54.5 lb.-in. (0.380.50 Nm) 0_C to +60_C

Voltage Rating Maximum Peak Voltage Maximum Current (per Circuit) Maximum Current (per Module) Indicator Circuit Current (Nominal) No. of Terminals per Shield Common Wire Range (Rated Cross Section) Wire Strip Length Recommended Tightening Torque Operating Temperature Range

For transients >600Vp, use a UL recognized suppression device rated at 2.5kV withstand. Maximum number of the same gauge stranded copper conductors allowed per wire funnel: AWG No. of Wires #22 3 #20
3

#18 3

#16 2

#14 1

#12
1

Application Notes
1. Compatibility To ensure proper operation with the I/O module, do not exceed the voltage and current ratings of the AIFM. 2. Wiring Refer to the Label Section on page 26 and the Field-Side Wiring Diagrams on page 33. 3. Fusing Ten fuse holders are included with the AIFM. Fuses (5 x 20mm) are not included. Do not exceed 2A per input, 12A per AIFM. 4. Isolation The fuse clips and blown fuse indicators are internally connected to one power source fieldside terminal. All inputs must reference the same power source. 5. DIP Switches For ease of wiring, unused inputs can be jumpered to module common by closing the DIP switches (ON position). Default switch position is OPEN/OFF/NOT jumpered together. 6. Test Points When using a 2-wire transmitter, test points can be used to measure input loop current. Refer to the Pinout for test point circuit location. 7. Extra Terminals Four field-side terminals are internally jumpered on the AIFM. They can be used for power source common connections. 8. Shield Terminals Four field-side terminals are jumpered together on AIFM and internally connected to the D-shell housing. 9. Dimensions See page 24.

Pinout
8 B1 B2

15

14

B3

13 12

B4

B5

11 2

B6

B7

10

B8

B9

B10 B11 TP1 TP2 A1 TP3 TP4 A2 B12 A5 . . . . A8 D-Shell Housing A9 . . . . A12

20

Analog Programmable Controller Wiring Systems

1492-AIFM4I-F-5
Specifications
Approvals UL Component Recognized (File E113724 Guide NRAQ2) UL Recognized per Canadian Safety Standards (cUR) (File E113724 Guide NRAQ2) CE Approved 1030V DC 600Vp 2A 12A 2mA 4 #22#12 AWG (0.24mm2) 0.32 (8mm) 3.54.5 lb.-in. (0.380.50 Nm) 0_C to +60_C

Voltage Rating Maximum Peak Voltage Maximum Current (per Circuit) Maximum Current (per Module) Indicator Circuit Current (Nominal) No. of Terminals per Shield Common Wire Range (Rated Cross Section) Wire Strip Length Recommended Tightening Torque Operating Temperature Range

For transients >600Vp, use a UL recognized suppression device rated at 2.5kV withstand. Maximum number of the same gauge stranded copper conductors allowed per wire funnel: AWG No. of Wires #22 3 #20
3

#18 3

#16 2

#14 1

#12
1

Application Notes
1. Compatibility To ensure proper operation with the I/O module, do not exceed the voltage and current ratings of the AIFM. 2. Wiring Refer to the Label Section on page 26 and the Field-Side Wiring Diagrams on page 33. 3. Fusing Ten fuse holders are included with the AIFM. Fuses (5 x 20mm) are not included. Do not exceed 2A per input, 12A per AIFM. 4. Isolation The fuse clips and blown fuse indicators are internally connected to one power source fieldside terminal. All inputs must reference the same power source. 5. DIP Switches For ease of wiring, unused inputs can be jumpered to module common by closing the DIP switches (ON position). Default switch position is OPEN/OFF/NOT jumpered together. 6. Test Points When using a 2-wire transmitter, test points can be used to measure input loop current. Refer to the Pinout for test point circuit location. 7. Extra Terminals Four field-side terminals are internally jumpered on the AIFM. They can be used for power source common connections. 8. Shield Terminals Four field-side terminals are jumpered together on the AIFM and internally connected to the D-shell housing. 9. Dimensions See page 24.

Pinout
8 B1 B2

15

14

B3

13

B4

12 11 2

B5

B6 B7

10

B8

B9

B10 B11 A1 . . . . . A4 B12 A5 . . . . . A8 D-Shell Housing A9 . . . . . A12

TP1

TP2

TP7

TP8

Analog Programmable Controller Wiring Systems

21

1492-AIFM8-F-5
Specifications
Approvals UL Component Recognized (File E113724 Guide NRAQ2) UL Recognized per Canadian Safety Standards (cUR) (File E113724 Guide NRAQ2) CE Approved 1030V DC 600Vp 2A 12A 2mA 18 #22#12 AWG (0.24mm2) 0.32 (8mm) 3.54.5 lb.-in. (0.380.50 Nm) 0_C to +60_C

Voltage Rating Maximum Peak Voltage Maximum Current (per Circuit) Maximum Current (per Module) Indicator Circuit Current (Nominal) No. of Terminals per Shield Common Wire Range (Rated Cross Section) Wire Strip Length Recommended Tightening Torque Operating Temperature Range

For transients >600Vp, use a UL recognized suppression device rated at 2.5kV withstand. Maximum number of the same gauge stranded copper conductors allowed per wire funnel: AWG No. of Wires #22 3 #20
3

#18 3

#16 2

#14 1

#12
1

Application Notes
1. Compatibility To ensure proper operation with the I/O module, do not exceed the voltage and current ratings of the AIFM. 2. Wiring Refer to the Label Section on page 26 and the Field-Side Wiring Diagrams on page 33. 3. Fusing Ten fuse holders are included with the AIFM. Fuses (5 x 20mm) are not included. Do not exceed 2A per input, 12A per AIFM. 4. Isolation The fuse clips and blown fuse indicators are internally connected to one power source fieldside terminal. All inputs must reference the same power source. 5. DIP Switches For ease of wiring on the 1771-IFE, unused inputs can be jumpered to module common by closing the DIP switches (ON position). Default switch position is OPEN/OFF/NOT jumpered together. 6. Extra Terminals Nine field-side terminals are internally jumpered on the AIFM. They can be used for power source common connections. 7. Shield Terminals Eighteen field-side terminals are jumpered together on the AIFM and internally connected to the D-shell housing. 8. Dimensions See page 24.

Pinout
3 C1 C2 C3

2 1

14 15

C4 C5

16 17

C6 C7

18 12

C8 C9

13 25

C10 C11

24 23

C12 C13 C14 C15

22 20

21 6 19

C16

B1 B2 . . . . . B9 B10 . . . . . B18 D-Shell Housing A1 . . . . . A18

22

Analog Programmable Controller Wiring Systems

1492-AIFM16-F-3
Specifications
Approvals UL Component Recognized (File E113724 Guide NRAQ2) UL Recognized per Canadian Safety Standards (cUR) (File E113724 Guide NRAQ2) CE Approved 1030V DC 600Vp 2A 12A 2mA 18 #22#12 AWG (0.24mm2) 0.32 (8mm) 3.54.5 lb.-in. (0.380.50 Nm) 0_C to +60_C

Voltage Rating Maximum Peak Voltage Maximum Current (per Circuit) Maximum Current (per Module) Indicator Circuit Current (Nominal) No. of Terminals per Shield Common Wire Range (Rated Cross Section) Wire Strip Length Recommended Tightening Torque Operating Temperature Range

For transients >600Vp, use a UL recognized suppression device rated at 2.5kV withstand. Maximum number of the same gauge stranded copper conductors allowed per wire funnel: AWG No. of Wires #22 3 #20
3

#18 3

#16 2

#14 1

#12
1

Application Notes
1. Compatibility To ensure proper operation with the I/O module, do not exceed the voltage and current ratings of the AIFM. 2. Wiring Refer to the Label Section on page 26 and the Field-Side Wiring Diagrams on page 33. 3. Fusing Twenty fuse holders are included with the AIFM. Fuses (5 x 20mm) are not included. Do not exceed 2A per input, 12A per AIFM. 4. Isolation The fuse clips and blown fuse indicators are internally connected to one power source fieldside terminal. All inputs must reference the same power source. 5. DIP Switches For ease of wiring, unused inputs can be jumpered to module common by closing the DIP switches (ON position). Default switch position is OPEN/OFF/NOT jumpered together. 6. Shield Terminals Eighteen field-side terminals are jumpered together on the AIFM and internally connected to the D-shell housing. 7. Dimensions See page 24.

Pinout
3 2 1 14 15 16 17 18 12 13 25 24 23 22 20 21 4 6 8 10 19 B2 B3 B4 B5 B6 B7 B8 B9 B10 B11 B12 B13 B14 B15 B16 B17 B18 B1 C1 . . . . . C16 D-Shell Housing A1 . . . . . A18

Analog Programmable Controller Wiring Systems

23

1492-AIFM16-F-5
Specifications
TB2

Approvals

UL Component Recognized (File E113724 Guide NRAQ2) UL Recognized per Canadian Safety Standards (cUR) (File E113724 Guide NRAQ2) CE Approved 1030V DC 600Vp 2A 12A 2mA 16 #22#12 AWG (0.24mm2) 0.32 (8mm) 3.54.5 lb.-in. (0.380.50 Nm) 0_C to +60_C

Voltage Rating Maximum Peak Voltage Maximum Current (per Circuit) Maximum Current (per Module) Indicator Circuit Current (Nominal) No. of Terminals per Shield Common
TB1

Wire Range (Rated Cross Section) Wire Strip Length Recommended Tightening Torque Operating Temperature Range

For transients >600Vp, use a UL recognized suppression device rated at 2.5kV withstand. Maximum number of the same gauge stranded copper conductors allowed per wire funnel: AWG No. of Wires #22 3 #20
3

#18 3

#16 2

#14 1

#12
1

Application Notes
1. Compatibility To ensure proper operation with the I/O module, do not exceed the voltage and current ratings of the AIFM. 2. Wiring Refer to the Label Section on page 26 and the Field-Side Wiring Diagrams on page 33. 3. Fusing Twenty fuse holders are included with the AIFM. Fuses (5 x 20mm) are not included. Do not exceed 2A per input, 12A per AIFM. 4. Isolation The fuse clips and blown fuse indicators are internally connected to two separate power source field-side terminals. All inputs within a group must reference the same power source. 5. DIP Switches For ease of wiring, unused inputs can be jumpered to module common by closing the DIP switches (ON position). Default switch position is OPEN/OFF/NOT jumpered together. 6. Extra Terminals Sixteen field-side terminals (C9C16 on TB1 and TB2) are internally jumpered on the AIFM and connected to module common. Eighteen field-side terminals (B10B18 on TB1 and TB2) are internally jumpered on the AIFM and can be used for power source common connections. There are two field-side terminals (A17 and A18 on TB1) which can be externally jumpered to connect the two groups of field-side terminals. 7. Shield Terminals Sixteen field-side terminals are jumpered together on the AIFM and internally connected to the D-shell housing. 8. Dimensions See page 24.

Pinout
TB1 3 2 1 14 15 16 17 18 C1 C2 C3 C4 C5 C6 C7 C8 C9 . . . . C16 A17 4 6 8 10 19 12 13 25 24 23 22 20 21 TB2 C1 C2 C3 C4 C5 C6 C7 C8 C9 . . . . C16

B1 B2 . . . . . B9

B1 B2 . . . . . B9

B10 . . . B18 A18

B10 . . . B18

D-Shell Housing

A1 . . . A8

A1 . . . A8

24

Analog Programmable Controller Wiring Systems

Dimensions
2.74 (69.5mm)

1492-AIFM4-3

2.19 (55.5mm) 1.67 (42.5mm) 2.36 (60mm)

3.27 (83mm)

2.74 1492-AIFM6S-3 1492-AIFM6TC-3 2.19 (69.5mm) (55.5mm)

1.67 (42.5mm)

3.15 (80mm)

3.27 (83mm)

1492-AIFM4C-F-5 1492-AIFM4I-F-5

1.67 (42.5mm)

2.74 (69.5mm) 2.19 (55.5mm)

3.15 (80mm)

3.27 (83mm)

2.74 1492-AIFM8-3 2.19 (69.5mm) (55.5mm)

1.67 (42.5mm) 4.33 (110mm)

3.27 (83mm)

1492-AIFM8-F-5 1492-AIFM16-F-3 4.72 (120mm) 3.27 (83mm)

1.67 (42.5mm)

2.19 (55.5mm)

2.74 (69.5mm)

1492-AIFM16-F-5

1.67 (42.5mm) 8.27 (210mm)

2.74 (69.5mm) 2.19 (55.5mm)

3.27 (83mm)

Analog Programmable Controller Wiring Systems

25

Adhesive Label Cards

All Bulletin 1492 AIFMs come with an adhesive label card. The label card provides the field-side connection descriptions for the programmable controller I/O module. The label cards list all of the compatible I/O modules and their respective wiring descriptions. Depending on the I/O module that is used, the label strip(s) are simply peeled from the label card and applied to the field-side terminals on the AIFM. The label strips basically copy the wiring descriptions from the I/O module in the chassis down to the AIFM terminals on the DIN rail. Fusible AIFMs come with the fuse clips/blown fuse indicators pre-numbered on the AIFM circuit board. Conversion label strip(s) are provided on the label card to change the numbering on the AIFM, if desired. The conversion labels would be placed directly on the circuit board of the AIFM. For example, if the fuse clips and blown fuse indicators were pre-numbered 03, a conversion label for 14 is provided. For AIFMs with extra terminals, pre-printed labels are provided to identify the shield connections (SH or SHIELD), module commons (MODULE COM, COM, or C), and power source commons (+V, V, COM, and VCOM). In addition, if generic numbering of the field-side terminals is desired, Numeric labels are provided. Examples: 120, 152, and evens and odds. For write-on identification, the label cards contain blank label strips (for field-side terminals) and rectangular boxes (for the large group marking area on each AIFM). The six different labels are shown actual size on pages 2631. This information is helpful for determining field-side wiring layouts prior to installation.
AIFM Cat. No. 1492-AIFM4-3 1492-AIFM4C-F-5, -AIFM4I-F-5 1492-AIFM6S-3, -AIFM6TC-3 1492-AIFM8-3 1492-AIFM8-F-5, -AIFM16-F-3 1492-AIFM16-F-5 Adhesive Label Card Page No.
26 27 28 29 30 31

An example of how the labels are applied is shown below:

26

Analog Programmable Controller Wiring Systems

Adhesive Label Card for Catalog Number 1492-AIFM4-3


I/O CAT. NO. 1746-NI4 2+ 0+ 1746-NIO4I, -NIO4V, -FIO4I, -FIO4V 1746-NO4I, -NO4V, 20O/0 0+ 2 0 2 0 1771-OFE 3+ 1+ 0C C C C 31C C C C +V +V

MODULE LABEL
SH SH SH SH SH SH SH SH SH SH 1+ 3 1 3 1 4+ 2+ 3+ 1+ 31O/1 1C C C C 42C C C C -V -V SH SH SH SH SH SH SH SH SH SH

LEVEL
UPPER LOWER UPPER LOWER UPPER LOWER UPPER LOWER UPPER LOWER

NUMERIC

1 9 1 2

2 10 3 4

3 11 5 6

4 12 7 8

5 13 9 10

6 14 11 12

7 15 13 14

8 16 15 16

45006-034-01 (A)

Analog Programmable Controller Wiring Systems

27

Adhesive Label Card for Catalog Numbers 1492-AIFM4C-F-5 and 1492-AIFM4I-F-5


I/0 CAT. NO. 1746-NI4 0+ V0 1746-NIO4I, -NIO4V, -FIO4I, -FIO4V 0+ V0 0V1 0V1 1+ V2 1+ 1V3 1-

MODULE LABEL
2+ 2VCOM O/0 C O/1 3+ 3+V VCOM SHIELD C +V VCOM

LEVEL UPPER LOWER UPPER LOWER

VCOM

SHIELD

LED NUMERIC 1 13 1 2

1 2 14 3 4 3 15 5 6

2 4 16 7 8 5 17 9 10

3 6 18 11 12 7 19 13 14

4 8 20 15 16 9 21 17 18 10 22 19 20 11 23 21 22 12 24 23 24

45006-021-02 (B)

28

Analog Programmable Controller Wiring Systems

Adhesive Label Card for Catalog Numbers 1492-AIFM6S-3 and 1492-AIFM6TC-3


I/0 CAT. NO. 1756-IT6I, -OF6CI, -OF6VI, -IF61 1756-IR6I 0 R0 SH A0 B0 1746-NR4 I0 R0 1771-IR A1 B1 R/C0 SH S0 SH C1 SH A1 B1 I1 R1 A2 B2 1 R1 SH R/C1 SH S1 SH C2 SH A2 B2 I2 R2 A3 B3 2

MODULE LABEL
R2 SH R/C2 SH S2 SH C3 SH A3 B3 I3 R3 A4 B4 3 R3 SH R/C3 SH S3 SH C4 SH A5 B5 C5 SH A6 B6 C6 SH A4 B4 4 R4 SH R/C4 SH A5 B5 5 R5 SH R/C5 SH

LEVEL
UPPER LOWER UPPER LOWER UPPER LOWER UPPER LOWER

NUMERIC

1 13 1 2

2 14 3 4

3 15 5 6

4 16 7 8

5 17 9 10

6 18 11 12

7 19 13 14

8 20 15 16

9 21 17 18

10 22 19 20

11 23 21 22

12 24 23 24

45006-021-01 (B)

Analog Programmable Controller Wiring Systems

29

Adhesive Label Card for Catalog Number 1492-AIFM8-3


I/0 CAT. NO. 1771-IFE SINGLE ENDED 1 2 3 4 5 6 7

MODULE LABEL
8 9 10 11 12 13 14 15 16

LEVEL UPPER LOWER 78+ 8UPPER LOWER 78+ 8UPPER LOWER 67+ 7UPPER LOWER

SHIELD 1771-IFE DIFFERENTIAL 1+ 12+ 23+ 34+ 45+ 56+

MODULE COM 67+

SHIELD 1771-IL 1+ 12+ 23+ 34+ 45+ 56+

MODULE COM 67+

SHIELD 1746-NI8 0+ 01+ 12+ 23+ 34+ 45+

COM 56+

SHIELD

COM

NUMERIC

1 17 1 2

2 18 3 4

3 19 5 6

4 20 7 8

5 21 9 10

6 22 11 12

7 23 13 14

8 24 15 16

9 25 17 18

10 26 19 20

11 27 21 22

12 28 23 24

13 29 25 26

14 30 27 28

15 31 29 30

16 32 31 32

UPPER LOWER UPPER LOWER

45006-019-01 (A)

30

Analog Programmable Controller Wiring Systems

Adhesive Label Card for Catalog Numbers 1492-AIFM16-F-3 and 1492-AIFM8-F-5


I/O CAT. NO. 1771-IFE SINGLE ENDED V1 +V 1 V2 2 V3 3 V4 4 V5 5 V6 6 V7 7 V8 8 MODULE LABEL V9 V10 9 SHIELD 1771-IFE DIFFERENTIAL 1+ +V 1V1 2+ V2 2V3 3+ V4 3V5 4+ V6 4V7 5+ V8 SHIELD 56+ 67+ 7V COM 8+ 8V11 10 V12 11 V13 12 V14 13 V15 14 V16 15 16 COM LEVEL Upper Middle Lower Upper Middle Lower

0+ 1746-NI8 +V

0V0

1+ V1

1V2

2+ V3

2V4

3+ V5

3V6

4+ V7

4-

5+

5-

6+

6V COM

7+

7-

Upper Middle Lower

SHIELD

LED LABEL NUMERIC

0 1 17 35 18 36 2 19

1 3 20 38 4 21 39 5

2 6 22 40 23 41 7 24

3 8 25 43 9 10 26 44

4 11 27 45 12 28 46

5 13 29 47 14 30 48

6 15 31 49 16 32 50 33 51

34 52

37

42

44006-274-01 (D)

Analog Programmable Controller Wiring Systems

31

Adhesive Label Card for Catalog Number 1492-AIFM16-F-5


I/0 CAT. NO. 1771-IFE SINGLE ENDED +V 1 V1 2 V2 3 V3 4 V4 5 V5 6 V6 7 V7 MODULE LABEL 8 V8 MODULE COM V COM 1J-1 14 V13 15 V14 16 V15 V16 MODULE COM V COM 1J-2 LEVEL UPPER LF MIDDLE LF LOWER LF UPPER RT MIDDLE RT LOWER RT

SHIELD 9 +V 10 V9 11 V10 12 V11 13 V12

SHIELD

NUMERIC 17

1 18

2 19

3 20

4 21

5 22

6 23

7 24

8 25

10 26 44 10 26 44 62 78 96 26 42 60

11 27 45 11 27 45 63 79 97 27 43 61

12 28 46 12 28 46 64 80 98 28 44 62

13 29 47 13 29 47 65 81 99 29 45 63

14 30 48 14 30 48 66 82 100 30 46 64

15 31 49 15 31 49 67 83 101 31 47 65

16 32 50 16 32 50 68 84 102 32 48 66 49 67 85 103 33 51 33 51

TB1 34 52 TB2 34 52

35 1 17 35 53 69 87 17 33 51

36 2 18 36 54 70 88 18 34 52

37 3 19 37 55 71 89 19 35 53

38 4 20 38 56 72 90 20 36 54

39 5 21 39 57 73 91 21 37 55

40 6 22 40 58 74 92 22 38 56

41 7 23 41 59 75 93 23 39 57

42 8 24 42 60 76 94 24 40 58

43 9 25 43 61 77 95 25 41 59

86 104

50 68

LED LABEL

1 8

2 9

3 10

4 11

5 12

6 13

7 14 15

LEFT RIGHT

45006-018-01 (A)

32

Analog Programmable Controller Wiring Systems

Field-Side Wiring Diagrams


I/O Module Cat. No. 1746-FIO4I, -FIO4V, -NIO4I, -NIO4V 1746-FIO4I, -FIO4V, -NIO4I, -NIO4V 1746-NI4 1746-NI4 1746-NI8 1746-NI8 1746-NO4I, -NO4V 1746-NR4 1756-IF6I 1756-IR6I 1756-IT6I 1756-OF6CI, -OF6VI 1771-IFE Differential 1771-IFE Differential 1771-IFE Single-ended 1771-IFE Single-ended 1771-IFE Single-ended 1771-IL 1771-IR 1771-OFE1, -OFE2, -OFE3 AIFM Cat. No. 1492-AIFM4-3 1492-AIFM4C-F-5 1492-AIFM4-3 1492-AIFM4I-F-5 1492-AIFM8-3 1492-AIFM8-F-5 1492-AIFM4-3 1492-AIFM6S-3 1492-AIFM6S-3 1492-AIFM6S-3 1492-AIFM6TC-3 1492-AIFM6S-3 1492-AIFM8-3 1492-AIFM8-F-5 1492-AIFM8-3 1492-AIFM16-F-3 1492-AIFM16-F-5 1492-AIFM8-3 1492-AIFM6S-3 1492-AIFM4-3 Page No.
33 35 37 38 39 40 41 42 43 45 46 47 48 49 50 51 52 53 54 55

Symbology Used Throughout Pinout and Wiring Sections


= = = = = 1492-AIFM Field-Side Terminal 1492 Pre-wired Cable I/O Module Connection Fuse and Blown Fuse Indicator 1-Pole DIP Switch

2-Pole DIP Switch

= =

1492-AIFM and Cable Connection (D-shell pin) Test Point

Field-Side Terminal Identification Convention:


C1 C2 C3 C4 C5 . . .

B1 B2 B3 B4 B5 . . .

B1

B2

B3

B4

B5 . . .

A1 A2 A3 A4 A5 . . .

A1 A2

A3 A4

A5 . . .

Analog Programmable Controller Wiring Systems

33

Field-Side Wiring Diagrams, continued


1746-FIO4I, -FIO4V, -NIO4I, -NIO4V Inputs with 1492-AIFM4-3
O/0 C SH O/1 C SH

0+ 0 C SH 1+ 1 C SH 1492-AIFM4-3

Single-Ended Signal Source or 2-Wire Transmitter


1492-AIFM4-3 Transmitter 0+ SH Power Supply 0 IN 0 C 1492-ACABLE_ _ _L IN 0+ 1746-FIO4I, -FIO4V, -NIO4I, -NIO4V

3-Wire Transmitter
1492-AIFM4-3 Transmitter 0+ SH Power Supply 0 IN 0 C 1492-ACABLE_ _ _L IN 0+ 1746-FIO4I, -FIO4V, -NIO4I, -NIO4V

Differential Signal Source or 4-Wire Transmitter


1492-AIFM4-3 0+ Power Supply Transmitter 0 IN 0 SH C 1492-ACABLE_ _ _L 1746-FIO4I, -FIO4V, -NIO4I, -NIO4V IN 0+

Unused Inputs
1492-AIFM4-3 0+ 0 IN 0 SH C 1492-ACABLE_ _ _L IN 0+ 1746-FIO4I, -FIO4V, -NIO4I, -NIO4V

Shield terminals on AIFM are connected to pre-wired cable shield through D-shell housing. Optional: 1492-SJM5-10.

34

Analog Programmable Controller Wiring Systems

Field-Side Wiring Diagrams, continued


1746-FIO4I, -FIO4V, -NIO4I, -NIO4V Outputs with 1492-AIFM4-3
O/0 C SH O/1 C SH

0+ 0 C SH 1+ 1 C SH 1492-AIFM4-3

Outputs
1492-AIFM4-3 O/0 LOAD C ANL COM SH 1492-ACABLE_ _ _L 1746-FIO4I, -FIO4V, -NIO4I, -NIO4V OUT 0

Unused Outputs Do not jumper unused outputs Shield terminals on AIFM are connected to pre-wired cable shield through D-shell housing.

Analog Programmable Controller Wiring Systems

35

Field-Side Wiring Diagrams, continued


1746-FIO4I, -FIO4V, -NIO4I, -NIO4V Inputs with 1492-AIFM4C-F-5
0+ 0 1+ 1 V0 V1 O/0 C VCOM O/1 C +V SHIELD 1492-AIFM4C-F-5 VCOM

Single-Ended Signal Source or 2-Wire Transmitter

1492-AIFM4C-F-5 +V

Power Supply Transmitter

V0 0+ SHIELD 0 VCOM 1492-ACABLE_ _ _L

1746-FIO4I, -FIO4V, -NIO4I, -NIO4V IN 0+

IN 0

3-Wire Transmitter

1492-AIFM4C-F-5 +V

Power Supply Transmitter

V0 0+ SHIELD 0 VCOM 1492-ACABLE_ _ _L

1746-FIO4I, -FIO4V, -NIO4I, -NIO4V IN 0+

IN 0

Differential Signal Source or 4-Wire Transmitter

1492-AIFM4C-F-5 +V

Power Supply

V0 0+ Transmitter 0 SHIELD VCOM 1492-ACABLE_ _ _L

1746-FIO4I, -FIO4V, -NIO4I, -NIO4V IN 0+ IN 0

Shield terminals on AIFM are connected to pre-wired cable shield through D-shell housing.

36

Analog Programmable Controller Wiring Systems

Field-Side Wiring Diagrams, continued


1746-FIO4I, -FIO4V, -NIO4I, -NIO4V Outputs with 1492-AIFM4C-F-5
0+ 0 1+ 1 V0 V1 O/0 C VCOM O/1 C +V SHIELD 1492-AIFM4C-F-5 VCOM

Outputs
1492-AIFM4C-F-5 O/0 LOAD C ANL COM SHIELD 1492-ACABLE_ _ _L 1746-FIO4I, -FIO4V, -NIO4I, -NIO4V OUT 0

Unused Outputs Do not jumper unused outputs Shield terminals on AIFM are connected to pre-wired cable shield through D-shell housing.

Analog Programmable Controller Wiring Systems

37

Field-Side Wiring Diagrams, continued


1746-NI4 with 1492-AIFM4-3
2+ 2 C SH 3+ 3 C SH

0+ 0 C SH 1+ 1 C SH 1492-AIFM4-3

Single-Ended Signal Source or 2-Wire Transmitter

Transmitter

1492-AIFM4-3 0+ SH

1746-NI4 1492-ACABLE_ _ _A IN 0+

Power Supply

0 C

IN 0

3-Wire Transmitter

Transmitter

1492-AIFM4-3 0+ SH

1746-NI4 1492-ACABLE_ _ _A IN 0+

Power Supply

0 C

IN 0

Differential Signal Source or 4-Wire Transmitter


1492-AIFM4-3 0+ Power Supply Transmitter 0 SH C 1746-NI4 1492-ACABLE_ _ _A IN 0+ IN 0

Unused Inputs
1492-AIFM4-3 0+ 0 SH C 1746-NI4 1492-ACABLE_ _ _A IN 0+ IN 0

Shield terminals on AIFM are connected to pre-wired cable shield through D-shell housing. Optional: 1492-SJM5-10.

38

Analog Programmable Controller Wiring Systems

Field-Side Wiring Diagrams, continued


1746-NI4 with 1492-AIFM4I-F-5
0+ 0 1+ 1 2+ 2 V0 V1 V2 V3 3+ 3 +V SHIELD VCOM VCOM

1492-AIFM4I-F-5

Single-Ended Signal Source or 2-Wire Transmitter


1492-AIFM4I-F-5 +V Power Supply Transmitter V0 1746-NI4 0+ SHIELD 0 IN 0 VCOM 1492-ACABLE_ _ _A IN 0+

3-Wire Transmitter

1492-AIFM4I-F-5 +V

Power Supply Transmitter

V0 0+ SHIELD 0 IN 0 VCOM 1746-NI4 1492-ACABLE_ _ _A IN 0+

Differential Signal Source or 4-Wire Transmitter


1492-AIFM4I-F-5 +V Power Supply V0 1746-NI4 0+ Transmitter 0 SHIELD VCOM 1492-ACABLE_ _ _A IN 0+ IN 0

Shield terminals on AIFM are connected to pre-wired cable shield through D-shell housing.

Analog Programmable Controller Wiring Systems

39

Field-Side Wiring Diagrams, continued


1746-NI8 with 1492-AIFM8-3
0+ 0 1+ 1 2+ 2 3+ 3 4+ 4 5+ 5 6+ 6 7+ 7 SHIELD COM 1492-AIFM8-3

Single-Ended Signal Source or 2-Wire Transmitter

1492-AIFM8-3 Transmitter Power Supply 0+ SHIELD 0 COM 1492-ACABLE_ _ _C

1746-NI8 Channel 0+

Channel 0

3-Wire Transmitter

1492-AIFM8-3 Transmitter Power Supply 0+ SHIELD 0 COM 1492-ACABLE_ _ _C

1746-NI8 Channel 0+

Channel 0

Differential Signal Source or 4-Wire Transmitter


1492-AIFM8-3 0+ Power Supply Transmitter 0 SHIELD COM 1492-ACABLE_ _ _C 1746-NI8 Channel 0+ Channel 0

Shield terminals on AIFM are connected to pre-wired cable shield through D-shell housing.

40

Analog Programmable Controller Wiring Systems

Field-Side Wiring Diagrams, continued


1746-NI8 with 1492-AIFM8-F-5
0+ 0 1+ 1 2+ 2 3+ 3 4+ 4 5+ 5 6+ 6 7+ 7

+V V0 V1 V2 V3 V4 V5 V6 V7

VCOM

1492-AIFM8-F-5
SHIELD

Single-Ended Signal Source or 2-Wire Transmitter


1492-AIFM8-F-5 +V Power Supply Transmitter V0 1746-NI8 0+ SHIELD 0 VCOM 1492-ACABLE_ _ _C Channel 0+

Channel 0

3-Wire Transmitter
1492-AIFM8-F-5 +V Power Supply Transmitter V0 0+ SHIELD 0 VCOM 1746-NI8 1492-ACABLE_ _ _C Channel 0+

Channel 0

Differential Signal Source or 4-Wire Transmitter


1492-AIFM8-F-5 +V Power Supply V0 1746-NI8 0+ Transmitter 0 SHIELD VCOM 1492-ACABLE_ _ _C Channel 0+ Channel 0

Shield terminals on AIFM are connected to pre-wired cable shield through D-shell housing.

Analog Programmable Controller Wiring Systems

41

Field-Side Wiring Diagrams, continued


1746-NO4I, -NO4V with 1492-AIFM4-3
2 C +V SH 3 C V SH 2 C SH 3 C SH

0 C +V SH 1 C V SH 1492-AIFM4-3

SH 1 C

SH

1746-NO4I, -NO4V with External Power

1746-NO4I, -NO4V without External Power

With External Power


1492-AIFM4-3 +V External Power Supply 1492-ACABLE_ _ _B 1746-NO4I, -NO4V +24V DC

V DC COM 0 OUT 0

LOAD

C ANL COM SH

Without External Power


1492-AIFM4-3 0 LOAD 1492-ACABLE_ _ _B OUT 0 C ANL COM SH 1746-NO4I, -NO4V

Unused Outputs Do not jumper unused outputs Shield terminals on AIFM are connected to pre-wired cable shield through D-shell housing.

42

Analog Programmable Controller Wiring Systems

Field-Side Wiring Diagrams, continued


1746-NR4 with 1492-AIFM6S-3
I0 S0 I1 S1 I2 S2 I3 S3 1492-AIFM6S-3 R0 SH R1 SH R2 SH R3 SH

2-Wire Potentiometer or RTD


1492-AIFM6S-3 I0 S0 R0 SH 1746-NR4 1492-ACABLE_ _ _D Channel 0 RTD Channel 0 Sense Channel 0 Return

3-Wire Potentiometer or RTD


1492-AIFM6S-3 I0 S0 R0 SH Channel 0 Sense Channel 0 Return 1746-NR4 1492-ACABLE_ _ _D Channel 0 RTD

4-Wire RTD
1492-AIFM6S-3 I0 S0 R0 SH Channel 0 Sense Channel 0 Return 1746-NR4 1492-ACABLE_ _ _D Channel 0 RTD

Leave One Sensor Wire Opened

Shield terminals on AIFM are connected to pre-wired cable shield through D-shell housing.

Analog Programmable Controller Wiring Systems

43

Field-Side Wiring Diagrams, continued


1756-IF6I with 1492-AIFM6S-3
0 R0 1 R1 2 R2 3 R3 4 R4 5 R5 1492-AIFM6S-3 SH SH SH SH SH SH

Current Input (1492-ACABLE_ _ _X)


1492-AIFM6S-3 0 + Analog Source R0 SH 1492-ACABLE_ _ _X IN-0/V IN-0/I RET-0 IN-2/V IN-2/I RET-2 Not Used IN-4/V IN-4/I RET-4 1756-IF6I

Current Input (1492-ACABLE_ _ _Y)


1492-AIFM6S-3 0 + Analog Source R0 SH 1492-ACABLE_ _ _Y IN-0/V IN-0/I RET-0 IN-2/V IN-2/I RET-2 Not Used IN-4/V IN-4/I RET-4 1756-IF6I

Shield terminals on AIFM are connected to pre-wired cable shield through D-shell housing. Important: Install IN-V to IN-I Jumper on RTB for each current input.

44

Analog Programmable Controller Wiring Systems

Field-Side Wiring Diagrams, continued


1756-IF6I with 1492-AIFM6S-3, continued
0 R0 1 R1 2 R2 3 R3 4 R4 5 R5 1492-AIFM6S-3 SH SH SH SH SH SH

Voltage Input (1492-ACABLE_ _ _Y)


1492-AIFM6S-3 0 + Analog Source R0 SH 1492-ACABLE_ _ _Y IN-0/V IN-0/I RET-0 IN-2/V IN-2/I RET-2 Not Used IN-4/V IN-4/I RET-4 1756-IF6I

Voltage Input (1492-ACABLE_ _ _X)


1492-AIFM6S-3 0 + Analog Source R0 SH 1492-ACABLE_ _ _X IN-0/V IN-0/I RET-0 IN-2/V IN-2/I RET-2 Not Used IN-4/V IN-4/I RET-4 1756-IF6I

Shield terminals on AIFM are connected to pre-wired cable shield through D-shell housing. Important: Remove IN-V to IN-I Jumper on RTB for each voltage input.

Analog Programmable Controller Wiring Systems

45

Field-Side Wiring Diagrams, continued


1756-IR6I with 1492-AIFM6S-3
A0 R/C0 A1 R/C1A2 R/C2 A3 R/C3 A4 R/C4 A5 R/C5 1492-AIFM6S-3 B0 SH B1 SH B2 SH B3 SH B4 SH B5 SH

3-Wire RTD
1492-AIFM6S-3 A0 B0 R/C0 SH 1492-ACABLE_ _ _Z IN-0/A IN-0/B RTN-0/C IN-2/A IN-2/B RTN-2/C Not used IN-4/A IN-4/B RTN-4/C 1756-IR6I

4-Wire RTD
1492-AIFM6S-3 A0 B0 R/C0 SH 1492-ACABLE_ _ _Z IN-0/A IN-0/B RTN-0/C IN-2/A IN-2/B RTN-2/C Not used IN-4/A IN-4/B RTN-4/C 1756-IR6I

Shield terminals on AIFM are connected to pre-wired cable shield through D-shell housing. Important: Leave sensor wire open.

46

Analog Programmable Controller Wiring Systems

Field-Side Wiring Diagrams, continued


1756-IT6I with 1492-AIFM6TC-3
0 R0 1 R1 2 R2 3 R3 4 R4 5 R5 1492-AIFM6TC-3 SH SH SH SH SH SH

1492-AIFM6TC-3 0 + R0 SH 1492-ACABLE_ _ _Y

1756-IT6I IN-0 Not Used RTN-0 IN-2 Not Used RTN-2 Not Used IN-4 Not Used RTN-4

Shield terminals on AIFM are connected to pre-wired cable shield through D-shell housing.

Analog Programmable Controller Wiring Systems

47

Field-Side Wiring Diagrams, continued


1756-OF6CI and -OF6VI with 1492-AIFM6S-3
0 R0 1 R1 2 R2 3 R3 4 R4 5 R5 1492-AIFM6S-3 SH SH SH SH SH SH

1756-OF6CI (0550)

1492-AIFM6S-3

1756-OF6CI 1492-ACABLE_ _ _Y
2 1

i
Analog Output Device +

0 R0 SH

OUT-0 ALT-0 RTN-0 OUT-2 ALT-2 RTN-2 Not Used OUT-4 ALT-4 RTN-4
20 19

1756-OF6CI (5501000)
1492-AIFM6S-3 1756-OF6CI 1492-ACABLE_ _ _Y
2 1

i
Analog Output Device +

0 R0 SH

OUT-0 ALT-0 RTN-0 OUT-2 ALT-2 RTN-2 Not Used OUT-4 ALT-4 RTN-4
20 19

1756-OF6VI

1492-AIFM6S-3 0 1492-ACABLE_ _ _Y

1756-OF6VI
2 1

Analog Output Device

+ R0 SH

OUT-0 Not Used RTN-0 OUT-2 Not Used RTN-2 Not Used OUT-4 Not Used RTN-4
20 19

Shield terminals on AIFM are connected to pre-wired cable shield through D-shell housing. Important: Move RTN wire in 1492-ACABLE_ _ _Y to ALT terminal for each output 5501000.

48

Analog Programmable Controller Wiring Systems

Field-Side Wiring Diagrams, continued


1771-IFE Differential with 1492-AIFM8-3
1+ 1 2+ 2 3+ 3 4+ 4 5+ 5 6+ 6 7+ 7 8+ 8 1492-AIFM8-3 SHIELD MODULE COM

2-Wire Transmitter
1492-AIFM8-3 1+ 1 SHIELD 1771-IFE 1492-ACABLE_ _ _E Channel 1+ Channel 1

Transmitter Power Supply

4-Wire Transmitter
1492-AIFM8-3 1+ Power Supply Transmitter 1 SHIELD 1771-IFE 1492-ACABLE_ _ _E Channel 1+ Channel 1

Shield terminals on AIFM are connected to pre-wired cable shield through D-shell housing.

Analog Programmable Controller Wiring Systems

49

Field-Side Wiring Diagrams, continued


1771-IFE Differential with 1492-AIFM8-F-5
1+ 1 2+ 2 3+ 3 4+ 4 5+ 5 6+ 6 7+ 7 8+ 8

+V V1 V2 V3 V4 V5

V6

V7

V8

VCOM

1492-AIFM8-F-5
SHIELD

2-Wire Transmitter
1492-AIFM8-F-5 +V Power Supply Transmitter V1 1771-IFE 1+ SHIELD 1 Channel 1 VCOM 1492-ACABLE_ _ _E Channel 1+

4-Wire Transmitter
1492-AIFM8-F-5 +V Power Supply V1 1771-IFE 1+ Transmitter 1 SHIELD VCOM 1492-ACABLE_ _ _E Channel 1+ Channel 1

Shield terminals on AIFM are connected to pre-wired cable shield through D-shell housing.

50

Analog Programmable Controller Wiring Systems

Field-Side Wiring Diagrams, continued


1771-IFE Single-Ended with 1492-AIFM8-3
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1492-AIFM8-3 SHIELD MODULE COM

2-Wire Transmitter

1492-AIFM8-3 Transmitter Power Supply 1 SHIELD MODULE COM 1492-ACABLE_ _ _F

1771-IFE Channel 1

Module Com

4-Wire Transmitter
1492-AIFM8-3 1 Power Supply Transmitter MODULE COM Module Com SHIELD 1492-ACABLE_ _ _F 1771-IFE Channel 1

Shield terminals on AIFM are connected to pre-wired cable shield through D-shell housing.

Analog Programmable Controller Wiring Systems

51

Field-Side Wiring Diagrams, continued


1771-IFE Single-Ended with 1492-AIFM16-F-3
V1 V2 V3 V4 V5 V6 V7 V8 V9 V10 V11 V12 V13 V14 V15 V16

+V

10

11

12

13

14

15

16 COM

1492-AIFM16-F-3
SHIELD

2-Wire Transmitter
1492-AIFM16-F-3 +V Power Supply Transmitter V1 1771-IFE 1 SHIELD COM Module Com 1492-ACABLE_ _ _F Channel 1

Shield terminals on AIFM are connected to pre-wired cable shield through D-shell housing.

52

Analog Programmable Controller Wiring Systems

Field-Side Wiring Diagrams, continued


1771-IFE Single-Ended with 1492-AIFM16-F-5
1 2 3 4 5 6 7 8 MODULE COM 9 10 11 12 13 14 15 16 MODULE COM

TB1

+V V1 V2 V3 V4 V5 V6 V7 V8

VCOM

+V V9 V10 V11V12 V13V14 V15V16

VCOM

TB2

SHIELD

1J-11J-2

SHIELD

1492-AIFM16-F-5

2-Wire Transmitter
1492-AIFM16-F-5 +V Power Supply Transmitter V1 1771-IFE 1 SHIELD MODULE COM Module Com 1492-ACABLE_ _ _F Channel 1

4-Wire Transmitter
1492-AIFM16-F-5 +V Power Supply V1 1771-IFE 1 Transmitter MODULE COM SHIELD VCOM 1492-ACABLE_ _ _F Channel 1 Module Com

Shield terminals on AIFM are connected to pre-wired cable shield through D-shell housing.

Analog Programmable Controller Wiring Systems

53

Field-Side Wiring Diagrams, continued


1771-IL with 1492-AIFM8-3
1+ 1 2+ 2 3+ 3 4+ 4 5+ 5 6+ 6 7+ 7 8+ 8 1492-AIFM8-3 SHIELD COM

1492-AIFM8-3 1+ Analog Source + 1 SHIELD 1492-ACABLE_ _ _H

1771-IL

18

Channel 1
16 14 12 10 8 6 4 2

Shield terminals on AIFM are connected to pre-wired cable shield through D-shell housing.

54

Analog Programmable Controller Wiring Systems

Field-Side Wiring Diagrams, continued


1771-IR with 1492-AIFM6S-3
A1 C1 A2 C2 A3 C3 A4 C4 A5 C5 A6 C6 1492-AIFM6S-3 B1 SH B2 SH B3 SH B4 SH B5 SH B6 SH

1771-IR 1492-AIFM6S-3 C1 B1 A1 SH 1492-ACABLE_ _ _J


18 16 14 12 10 8 6 4 2 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 C B Channel 1 A C B Channel 2 A C B Channel 3 A C B Channel 4 A C B Channel 5 A C B Channel 6 A

Shield terminals on AIFM are connected to pre-wired cable shield through D-shell housing.

Analog Programmable Controller Wiring Systems

55

Field-Side Wiring Diagrams, continued


1771-OFE1, -OFE2, -OFE3 with 1492-AIFM4-3
3+ 3 SH 4+ 4 SH

1+ 1

SH 2+ 2

SH 1492-AIFM4-3

1492-AIFM4-3 1+ LOAD 1 SH 1492-ACABLE_ _ _G

1771-OFE1, -OFE2, -OFE3


A 0 1 2 3 4 5 6 7 B

Channel 1(+) Channel 1()

Shield terminals on AIFM are connected to pre-wired cable shield through D-shell housing.

56

Analog Programmable Controller Wiring Systems

Reference Publications
1746-2.34 1746-2.37 1756-6.5.9 1771-2.183 1746 Analog Input and Output Modules 1746 RTD/Resistance Input Modules 1756 Analog Input and Output Modules 1771 Analog Input and Output Modules

Publication 14922.15 September 1997