You are on page 1of 112

file:///C:/Users/Ranjitha/Downloads/Accessibility for the Disabled.

htm

Accessibility for the Disabled


[_headerthemes.htm]

Theme: Accessibility

Accessibility for the Disabled A Design Manual for a Barrier Free Environment
TABLE OF CONTENTS PREFACE INTRODUCTION I. URBAN DESIGN CONSIDERATIONS

1. OBSTRUCTIONS 2. SIGNAGE 3. STREET FURNITURE 4. PATHWAYS 5. CURB RAMPS 6. PEDESTRIAN CROSSINGS 7. PARKING

II. ARCHITECTURAL DESIGN CONSIDERATIONS

1. RAMPS 2. ELEVATORS 3. LIFTS 4. STAIRS 5. RAILINGS AND HANDRAILS 6. ENTRANCES 7. VESTIBULES 8. DOORS 9. CORRIDORS 10. REST ROOMS

III. BUILDING TYPES IV. IMPLEMENTATION CHECKLISTS

PART 1 | PART 2 | PART 3

V. APPENDICES

TROUBLE SHOOTING ANTHROPOMETRICS [ PART 1 | PART 2 ] COMPARATIVE TABLES HEIGHT LIMITS

REFERENCES / ACKNOWLEDGMENTS Next

[_headerthemes.htm]

Theme: Accessibility

Accessibility for the Disabled - A Design Manual for a Barrier Free Environment
Previous : Next

PREFACE
Ministry of Social Affairs National Committee for the Disabled The Ministry of Social Affairs devotes special attention to the question of disability, striving to provide the various facilities required to ensure that every disabled person has work opportunities that will help him or her to become a productive member of society. The Ministry of Social Affairs is cooperating in the area with the National Committee for the Disabled in an integrated approach and a programme to ensure that the question of disability will be dealt with in every regard: quality of services offered, ease of procedures followed, current legislation, and standards criteria to be adopted for training and rehabilitation. The approach followed by the Lebanese Company for

the Development and Reconstruction of Beirut Central District (SOLIDERE) - an approach that developed into the present Accessibility for the Disabled, a Design Manual for a Barrier Free Environment, met the requirements of the Ministry of Social Affairs, and the two parties were largely in agreement on both goals and methods of implementation. The Ministry of Social Affairs therefore decided to adopt the content of this program pending the promulgation of new laws currently being sought in Parliament. The Ministry of Social Affairs and the National Committee for the Disabled wish to thank all those who took part in the drafting of this manual, in particular the Lebanese Company for the Development and Reconstruction of Beirut Central District (SOLIDERE) and ESCWA. It is hoped that joint efforts will continue to be exerted to safeguard the rights of disabled persons indeed of all citizens without exception. Ministry of Social Affairs National Committee for the Disabled United Nations Economic and Social Commission for Western Asia Twenty years have passed since the General Assembly adopted resolution 31/123 of 16 December 1976, proclaiming 1981 the International Year of Disabled Persons, an event that constituted a landmark in the long struggle towards recognizing the rights of the disabled and creating a better understanding of their needs and appreciation of their capabilities. After the International Year of Disabled Persons came the World Programme of Action concerning Disabled Persons, adopted by the General Assembly in its resolution 37/52 of 3 December 1982. In its resolution 37/53 of the same date, the General Assembly proclaimed the period 1983-1992 the United Nations Decade of Disabled Persons. These actions prompted considerable activity in the field of disability at the international, regional and national levels. The Conference on the Capabilities and Needs of Disabled Persons in the ESCWA Region, which was held in November 1989, provided a regional forum for the discussion of the many issues related to disability between individuals, organizations and officials. The issue of accessibility for the disabled in the urban environment was given due attention and the Conference recommended that city planning and building and construction legislation, should take into account the conditions that facilitate the movement of disabled persons and ensure their safety, including in the design of infrastructural services, transport and the entrances and interiors of buildings. Early in 1994, ESCWA was requested to provide Lebanon with assistance in developing construction standards and policy recommendations to

accommodate disabled people. ESCWA began with an assessment of the magnitude of the issue on the national level, hoping to devise a long-term strategy and aiming at placing urgent short-term measures within an integral capacious perspective. No dependable statistics exist at present defining the extent of disability in Lebanese society. However, given the severity and duration of war and unrest that the country has experienced and the damage to the urban fabric, which is especially evident in the urban centres, and particularly visible in the Beirut Central District, one can deduce that the disabled form a significant sector of the community. Some estimates put the figure at 150,000 to 250,000, of which 80,000 are physically disabled as a result of the war. A good database on disability in Lebanon is essential for any future development effort in this field. The present state of development in Lebanon calls for a dual-track approach in handling the issue of accessibility for the disabled. The first track should aim at influencing the development and reconstruction of the Beirut Central District (BCD). At the time of preparation of this Manual, the planning and design processes of the BCD were at a fairly advanced stage, calling for the application of established standards and recommendations, with appropriate review procedures. The contribution of this Manual should be viewed in this context. The second track should have the long-term aim of addressing the issue on the national level. At the core, this approach is the development and legal enforcement of standards and regulations. Although the second track would have a wider geographical and social effect throughout the country, implementation of the first track would certainly serve to make the BCD an excellent demonstration case on both the national and regional levels. In physical terms, the provision of a barrier-free environment can be undertaken in four complementary domains:

(a) Inside buildings; (b) In the immediate vicinity of buildings; (c) On local roads and paths; (d) In open spaces and recreational areas.

The idea for this Manual first came to surface in early 1994 during meetings that were held with a number of government officials and representatives of organizations concerned with disability in Lebanon. The

Manual represents the first phase in a broad effort to provide a barrier-free environment throughout the country. It is designed so as to facilitate application in the planning of new environments as well as in the renovation of existing ones. The Manual can also be uesd as a reference by designers and planners throughout the Arab region. Experience gained from the application of the Manual to new constructions and restored buildings within the BCD will help in future development of the Manual and in arriving at appropriate legislation on accessibility. Future efforts to implement essential parts of this Manual on the national level will be coordinated with other concerned Lebanese agencies, and it is hoped that the Manual will become a reference for the promotion of nonhandicapping environments in the region. The Lebanese National Council for the Affairs of the Disabled carried out a pre-publication review of the Manual under the chairmanship of H.E. the Minister of Social Affairs. This Manual is the product of a joint effort between the Lebanese Company for the Development and Reconstruction of Beirut Central District (SOLIDERE) and the United Nations Economic and Social Commission for Western Asia (ESCWA). Hazem El-Beblawi Executive Secretary United Nations Economic and Social Commission for Western Asia (ESCWA) Previous : Next

[_headerthemes.htm]

Theme: Accessibility

Accessibility for the Disabled - A Design Manual for a Barrier Free Environment INTRODUCTION
We are all physically disabled (1) at some time in our

lives. A child, a person with a broken leg, a parent with a pram, an elderly person, etc. are all disabled in one way or another. Those who remain healthy and able-bodied all their lives are few. As far as the built-up environment is concerned, it is important that it should be barrier-free and adapted to fulfill the needs of all people equally. As a matter of fact, the needs of the disabled coincide with the needs of the majority, and all people are at ease with them. As such, planning for the majority implies planning for people with varying abilities and disabilities. PURPOSE This publication is an attempt to provide for the first time in Lebanon a design manual on accessibility for the disabled. It is a design guidebook made for the purpose of providing architects and designers with the basic information and data necessary for a barrier- free environment. Its intent is to establish standards and recommendations that will not only influence the development and reconstruction of the BCD but assume national importance as well. The manual is expected to be a stimulus that will lead, in the long run, to the establishment of national building and planning legislation covering access for disabled people. APPLICATION The manual does not cover all the requirements of disabled people in detail. It is a straightforward guide expected to be the first in a series of publications having the same theme. Most of the recommended measures have been tested in developed countries, and while some have proven to be effective, the outcome of others is still unknown. To determine the reliability and efficacy of these measures for Lebanon, it is important to conduct experimental trials of all provisions. This will be of great help in determining the positive and negative aspects of each measure. Practical advice from legal, professional and academic institutions as well as individuals with disabilities is also of the utmost importance in shaping the final form of an accessibility code which can be applied on a national level, as an integral part of the Lebanese building law. THE BCD - A CASE-STUDY Since the BCD is a pilot project in the reconstruction process of Lebanon, implementing accessibility requirements for the disabled will help to make the BCD a case-study or a demonstration project on a national level. This will include the design of the traffic infrastructure and new buildings plus the renovation of the existing infrastructure and buildings.

AIM The social aim of this study is to integrate disabled people into society in order for them to take an active part in society and lead a normal life. To be active, a disabled person should be able to commute between home, work and other destinations. The technical aim of the manual is to provide a barrier-free environment for the independence, convenience and safety of all people with disabilities. TARGET GROUP The target group is composed of five major categories:

(a) Wheelchair users (b) People with limited walking abilities (c) The sightless (d) The partially sighted (e) The hearing impaired

Other categories that may benefit to some extent from the proposed measures include the mentally disabled, people susceptible to physical fits, people with extreme physical proportions, and people with functional disabilities of the arm or hand. As for the composition and size of the target group, no dependable statistics currently exist to define the extent of disability in Lebanese society. However, taking into consideration the duration of the war, one can deduce that the disabled form a significant percentage of the population. A good database on disability in Lebanon is essential for any future development in this field. CONTENT The manual deals with the technical considerations and design provisions or measures to be taken into account in the planning of the built-up environment. This includes issues related to the design of several complementary domains: open spaces and recreational areas, local roads and pathways, the immediate vicinity of buildings, building entrances and the interiors of buildings. For the purposes of this manual, all information is divided into five sections:

I. URBAN DESIGN CONSIDERATIONS II. ARCHITECTURAL DESIGN CONSIDERATIONS III. BUILDING TYPES

IV. IMPLEMENTATION CHECKLISTS V. APPENDICES

I. URBAN DESIGN CONSIDERATIONS This section deals with the design requirements of open spaces, recreational areas and pedestrian routes. It introduces solutions to the principal problems in the design of an accessible outdoor environment. It is subdivided into seven chapters:

1. OBSTRUCTIONS 2. SIGNAGE 3. STREET FURNITURE 4. PATHWAYS 5. CURB RAMPS 6. PEDESTRIAN CROSSINGS 7. PARKING

II. ARCHITECTURAL DESIGN CONSIDERATIONS This section deals with the design requirements of vertical and horizontal access in both new and existing constructions. It is subdivided into 10 chapters:

1. RAMPS 2. ELEVATORS 3. PLATFORM LIFTS 4. STAIRS 5. RAILINGS AND HANDRAILS 6. ENTRANCES 7. VESTIBULES 8. DOORS 9. CORRIDORS 10. REST ROOMS

III. BUILDING TYPES This section deals briefly with the accessibility requirements of selected building types. Special buildings for people with disabilities, such as health and residential facilities and schools, do not fall within the scope of this section. To establish building and planning legislation regarding access for disabled people, this section needs to be thoroughly developed by local authorities, based on the size of the target group, a classification of the various building types and a study of the specific needs of each district.

IV. IMPLEMENTATION CHECKLISTS This section can be used by both designers and inspectors to identify and assess physical barriers in the built-up environment, for both new and existing constructions. The checklists are arranged according to the categories listed in sections I and II. Questions on almost all problem areas are asked, and possible solutions are offered. V. APPENDICES 1. TROUBLESHOOTING 2. ANTHROPOMETRICS 3. COMPARATIVE TABLES 4. HEIGHT LIMITS CHAPTER ORGANIZATION Each chapter is composed of four parts: 1) Problem identification This part defines problems encountered by the disabled in the built-up environment owing to the absence or improper application of a certain measure or provision. 2) Planning principle This part defines the target group, the general goal and the need for a certain measure. 3) Design considerations This part deals with the technical and architectural aspects of implementing certain measures with regard to general and particular application characteristics, criteria, minimum dimensions and measurements, materials, etc. 4) Existing constructions This part defines the problems encountered in existing constructions which hinder the implementation of a certain measure. Accordingly, alternative solutions and modifications are suggested. REFERENCES The information provided is based on the accessibility codes and relevant knowledge available in various countries. A comparative study of the available sources was conducted regarding each measure. The information was then synthesized and organized

according to the needs of the target group. (See the list of references at the end of the book). DIMENSIONAL DATA Dimensional data are given in metric units. The graphic illustrations show only the minimum allowable dimensions. Where appropriate, the maximum or approximate dimension or an allowable range is given. Notes: (1) It should be noted that a handicap is not a synonym for disability. A disability refers to a physical, sensory or mental limitation that interferes with a person's ability to move, see, hear or learn; a handicap refers to a condition or barrier imposed by the environment, society or oneself. As such, physical obstructions of the built-up environment constitute a handicap to a disabled person. For example, a stairway is a handicap to a wheelchair user. On the other hand, feeling different and inferior to other people constitutes a handicap imposed by oneself

[_headerthemes.htm]

I. URBAN DESIGN CONSIDERATIONS 1. OBSTRUCTIONS


1. PROBLEM IDENTIFICATION Obstacles and protruding elements in the path of travel. Low overhanging signs. Lack of warning signs around obstructions. 2. PLANNING PRINCIPLE To design a barrier-free path for the safety and independence of disabled people, especially the sightless.

3. DESIGN CONSIDERATIONS 3.1 General Obstructions include street furniture, traffic signs, direction signs, street plans, bollards, plants, trees, shop awnings and advertising signs, etc. Obstructions should be placed outside the path of travel wherever possible. Obstructions in the pathway should be easy to detect, and if possible, should be placed along one continuous line. Protruding elements should be avoided. The minimum width of a clear unobstructed path should be 0.90 m. 3.2 Obstructions on the pathway surface Obstructions on the pathway surface should have one of the following design features in order to be detected by the cane of a sightless person:

Fig. 1 Obstructions with 0.10 m raised platform

Fig. 2

Fig. 3

(a) A straight shape rising from the pathway surface (fig. 1). (b) A 0.10 m raised platform (fig. 2). (c) Tactile warning markings on the ground around the obstruction. The warning markings should extend over a width of at least 0.60 m outside the projected area at the base of the obstacle (fig. 3).

Fig. 4

Fig. 5

Fig. 6

3.3 Overhanging obstructions Overhanging signs in accessible pathways should be mounted at a minimum clear height of 2.00m to allow a sightless person to pass safely (fig. 4). Overhanging vegetation should be clipped to a minimum clear height of 2.00 m (fig. 5). Undetectable obstacles mounted lower than 2.00 m may project a maximum distance of 0.10m into the pathway. Otherwise they should be recessed or covered (fig. 6). 3.4 Fixed poles Fixed poles should have contrasting durable colour marking strips of at least 0.30 m in length, placed with the centre line at a height between 1.40 m and 1.60 m, to warn pedestrians with limited vision (fig. 1). 3.5 Garbage bins Garbage bins attached to lampposts should not face the line of pedestrian flow so as to minimize collisions and should be painted in a contrasting colour so that people with limited vision may easily identify them (fig. 7). 3.6 Spaces below ramps and stairs Spaces below ramps and stairs should be blocked out completely by protective rails or raised curbs or marked with a tactile surface (fig. 8). 3.7 Bicycle stands Bicycle stands should be located on a raised platform. 3.8 Wires Stabilizing wires and wire netting should be painted in a Fig 8.

Fig. 7

contrasting colour or blocked out. 3.9 Bollards (1) (fig. 9) Bollards should be painted in a contrasting colour or in coloured stripes. The distance between guiding posts should be around 1.20 m. 3.10 Roadworks Excavations and roadworks form temporary obstructions within the route of travel. They should be protected by easily detected continuous barriers, scaffolding, and fences for safety reasons. Barriers should be identified by stripped colour markings and should be lit at night, to guide people with limited vision. The barrier height should be between 0.75 m and and 0.95 m. The distance between the bottom of the barrier and the pathway surface should not exceed 0.10 m. 4. EXISTING CONSTRUCTIONS Existing obstructions within the path of travel should be redesigned to conform to all the above requirements Notes: (1) Bollards or guard posts are placed to keep out undesired motor traffic from pedestrian areas or to indicate a non parking area. Previous : Next

Fig. 9

[_headerthemes.htm]

Theme: Accessibility : Accessibility for the Disabled - A Design Manual for a Barrier Free Environment

Previous : Next

I. URBAN DESIGN CONSIDERATIONS 2. SIGNAGE


1. PROBLEM IDENTIFICATION Orientation difficulties resulting from illegible directional signs, street names and numbering and/or the lack of them. Pedestrian accidents due to badly positioned signs. Hazards due to lack of warning and traffic signals. Non-identification of access routes and accessible facilities. 2. PLANNING PRINCIPLE To facilitate orientation mainly for the disabled. 3. DESIGN CONSIDERATIONS 3.1 General Signage include direction signs, signs of locality, street names and numbering, information signs, etc. All types of signs should be visible, clear, simple, easy to read and understand, and properly lit at night. In general, signs should not be placed behind glass because of possible reflection. Signage placed on the pedestrian path of travel are Fig. 5 Fig. 6 Fig. 7 Fig. 1 Fig. 2 Fig. 3 Fig. 4 International Symbol of Accessibility

considered obstructions; thus, they should be detectable (see Obstructions). 3.2 International symbol of accessibility Accessible spaces and facilities should be identified by the international symbol of accessiblity (fig. 1). The symbol is composed of a wheelchair figure with either a square background or a square border (fig. 2). Contrasting colours should be used to differentiate the figure from the background. The commonly employed colours are white for the figure and blue for the background. The wheelchair figure should always be seen from drawn facing right. For completely accessible buildings, it is enough to have one explanatory sign at the entrance. 3.3 Direction signs Graphic or written directions should be used to indicate clearly the type and location of the available facility (fig. 3). Directional signs need not be excessive in number, but they should be placed at main entrances and doors and in places where changes in direction or level occur. 3.4 Street names Fixed signs indicating street names should be placed at a maximum height of 2.50 m (fig. 4). 3.5 House numbers Fixed signs indicating house numbers should be placed at Character width-to-height ratios

a maximum height of 2.00 m (fig. 4). 3.6 Maps and information panels Maps and information panels at building entrances, along roads, and on public buildings should be placed at a height between 0.90 m and 1.80 m (fig. 5). 3.7 Installation Signs can be wall-mounted, suspended or pole-mounted. (a) Wall-Mounted signs:

Wall-mounted signs, such as those indicating room numbers, should be placed with the centre line at a height between 1.40 m and 1.60m from the finished floor level.

(b) Overhanging signs:

Overhanging signs should allow a minimum clearance of 2.00 m (see Obstructions).

(c)Pole-Mounted signs:

(see Obstructions)

3.8 Shape of signboards Information signboards should be rectangular. Warning signboards should be triangular. Interdictory signboards should

be circular. 3.9 Colour The colour of signs should contrast with the surrounding surface so as to be clearly distinguishable. The commonly used colours are: white, black, yellow, red, blue and green. The colour combinations red/green and yellow/blue should not be used in order to avoid confusing colour- blind persons. 3.10 Surface The sign surface should be processed to prevent glare. Engraved texts should be avoided unless they are coloured. Relief prints are advisable. Key plans, orientation signs and push buttons in lifts must have a text in Braille or in relief. (1) 3.11 Lettering The size of letters should be in proportion to the reading distance (fig. 6). Character width-to-height ratio should be between 3:5 and 1:1 and the character stroke width-to-height ratio should be between 1:5 and 1:10 (fig. 7). The letters and signs should preferably be raised at least 1 mm from the background, to enable sightless people to read the information using the tips of their fingers. The smallest letter type should not be less than 15 mm. Normal spacing between words and letters should be

used. 4. EXISTING CONSTRUCTIONS The international symbol of accessibility should be added to mark accessible spaces and facilities. Directional signs should be added to indicate clearly the location and function of accessible spaces and facilities. Signs that do not comply with the above design requirements should be modified or replaced. Notes: (1) Not all sightless persons are familiar with Braille. Previous : Next

[_headerthemes.htm]

I. URBAN DESIGN CONSIDERATIONS 3. STREET FURNITURE


1. PROBLEM IDENTIFICATION Lack of or improper design of street furniture. Obstructed pathways. Inaccessible street facilities. 2. PLANNING PRINCIPLE To design accessible amenities Fig. 1 Rest areas at intervals of 100-200 m.

convenient to all people, without obstructing the free passage of pedestrians along travel routes. 3. DESIGN CONSIDERATIONS 3.1 General Street furniture includes bus stops, benches, mail boxes, lampposts, signboards, telephone booths, public toilets, newspaper kiosks, planting tubs, garbage bins, etc. 3.2 Location (1) Street furniture should be located so as to allow for the free passage of all people without creating hazards. Textural changes in the footpath surface help sightless people to identify the location of public amenities (see Obstructions). 3.3 Resting facilities Level rest areas with seats are helpful for all pedestrians, especially for those with mobility problems. Resting facilities should be placed outside the main circulation path in public parks, recreational places, pathway crossings, in front of accessible entrances and exits and wherever necessary. Resting facilities should be provided at regular intervals between 100.00 m and 200.00 m (2) (fig. 1). Some seating accommodations should be placed close to public toilets, telephones, etc. Resting spaces with benches should allow a minimum of 1.20 m of adjoining space for a wheelchair (fig. 2).

Fig. 2 Fig. 3 Fig. 4 Fig. 5

Specifications for public phone booths.

Fig. 6 Fig. 7

Public seats and benches should be approximately 0.45 m above floor level, with backrests at approximately 0.70 m above floor level (fig. 3). The height of a table should be between 0.75 m and 0.90 m and the minimum depth under the table should be 0.60 m, in order to fit a wheelchair under all sides (fig. 4). 3.4 Public telephone booths (3) At public telephone booths, one telephone should be accessible to a wheelchair user and another to a person with a hearing impairment. Telephones for the hearing impaired should be equipped with hearing aid devices and amplifiers. The location of telecommunication devices should be indicated by signs. A push-button telephone numbering system, with raised letters which can also be read by touch, should be used for the convenience of sightless users and other disabled people. A dial numbering system is not recommended unless the dial tension is reduced so as to require less effort to rotate the dial. A folding seat should be provided in accessible telephone booths for the convenience of people with mobility problems. The minimum unobstructed area in front of the telephone counter should be 1.20 m x 0.85 m, allowing either a parallel or a frontal approach (fig. 5). The coin slot should be mounted at an accessible comfortable height between 0.90 m and 1.20 m. The telephone cord length

should be at least 0.75m. Accessible public telephones should be marked by appropriate signs. 3.5 Mailboxes Mailbox slots should be mounted at an accessible height between 0.90 m and 1.20 m (fig. 6). 3.6 Water Fountains (fig. 7) Drinking fountain spouts should be located at an approximate height of 0.90 m. Drinking fountains can have two spouts located at different heights, one convenient to wheelchair users at approximately 0.85 m, and one at approximately 0.95 m for non-disabled people. 3.7 Signs (see Signage; Pedestrian Crossings) 3.8 Garbage bins (see Obstructions) 3.9 Public toilets (see Rest Rooms) 3.10 Ticket vending machines (see Height Limits) 4. EXISTING CONSTRUCTIONS Resting facilities should be rearranged where possible to allow an adjoining space for a wheelchair. Facilities mounted at a maximum height of 1.40 m are acceptable, while those located at a higher level should be modified. Notes: (1) Landscaped strips act as a buffer zone between pedestrian and vehicular zones, and street furniture can be located within these strips.

(2) It might be beneficial to locate rest areas at more frequent intervals on long gradients (3) Public telephone requirements also include those in hotels, information booths and other public areas.

[_headerthemes.htm]

I. URBAN DESIGN CONSIDERATIONS 4. PATHWAYS


1. PROBLEM IDENTIFICATION Uneven curbs with obstacles and holes. Inconvenient or dangerous interruptions in the path of travel. Insufficient width. Changes in level. 2. PLANNING PRINCIPLE To provide clear, obstructionfree, level and wide pathways for the convenience of all users, especially the sightless and people with mobility problems. 3. DESIGN CONSIDERATIONS 3.1 General Street pavements, pedestrian passages in open spaces and recreational areas, pedestrian underpasses and overpasses are all considered pathways or Fig. 3 Fig. 1 Fig. 2

Fig. 4

ramps. Pedestrian routes in recreational areas and open spaces should be broken regularly by detectable obstructions such as plants and/or by changing the alignment to discourage bicyclists (see Obstructions). 3.2 Guide strips The path of travel should be easy to detect by a sightless person using a long white cane. Natural guide lines (1) and guide strips are used to help identify travel routes. A guide strip is a line means constructed in or on the road surface to facilitate orientation for sightless pedestrians in the following manner: (a) To replace missing natural guidelines fill gaps of more than 10.00 m in a guide strip (fig.1); (b) To guide to pedestrian crossings (fig.2) (see Curb Ramps; Pedestrian Crossings). Guide strips should be laid in a simple and logical manner and should not be located close to manholes or drains to avoid confusing sightless people. Guide strips should have a colour which contrasts with the surrounding surface for the benefit of people with sight problems. The guide strip ridge profile should be parallel to the main direction of movement and should be flush with the top layer of the adjacent road surface so as not to hinder people with mobility problems. Fig. 5 Fig. 6

Gratings on a pathway.

Fig. 7

Fig. 8

Where travel routes change direction, there should be a gradual change in the direction of the guiding strip (fig. 3). 3.3 Tactile marking Tactile tiling on the pedestrian route of travel should be placed at the following locations: (a) On a guide strip where alternative routes exist or at a junction of guide strips (fig. 4). (b) At a pedestrian crossing (see Curb Ramps; Pedestrian Crossings ). (c) Around obstructions which are difficult for the sightless to detect (see Obstructions). A tactile guiding area, preferably of rubber tiles (2) with minimum dimensions of 0.90 m x 0.90 m, should be constructed in a guide strip at cross pathways where the route branches off in several directions (fig.4). 3.4 Curbs The height of a curb should be between 0.07 m and 0.15m. Stepped curbs should be avoided, as they are hazardous to all pedestrians, especially in darkness. 3.5 Curb ramps Curbs should not obstruct the free passage of physically disabled people, mainly wheelchair users (see Curb Ramps). 3.6 Width (fig. 5) The minimum width of an unobstructed pathway

Beveled edges of pathways.

should be 0.90 m. The minimum width of a two-way wheelchair traffic passage is 1.50 m. The preferable width is 1.80 m. 3.7 Slope The slope of an accessible path should not exceed 1:20. Pathways with a slope of more than 1:20 should be designed as ramps (see Ramps). The slope across a path should not exceed 1:50. 3.8 Surface The surface of an accessible pathway should be smooth, continuous, non-slip and even. Pathways which are level and even with adjacent surfaces should be given a different texture and colour finish for differentiation. Intersecting pathways should blend at one common level. 3.9 Gratings (fig. 6) Gratings can be hazardous to wheelchair users, cane and crutch users, parents with prams and women with high heels. Manholes, drains and gratings should generally be placed outside the pedestrian pathway. Gratings should be flush with the pathway surface and should have narrow patterns of not more than 13 mm. Elongated grating openings should be perpendicular to the

pedestrian travel path. 3.10 Guards For changes in level of more than 13 mm between the pathway and the surrounding surface, guards, upstands or other types of barriers should be used. Guards with a minimum height of 0.15 m should be used to separate pathways from planting areas, pools and landscape features (fig. 7). The edges of the pathway should be beveled wherever changes in level between 6 mm and 13 mm exist between the pathway and the surrounding area (fig. 8). 3.11 Landscaping Plant varieties and locations within the travel route should be chosen with caution. Thorny and poisonous plants should not be used immediately adjacent to pedestrian paths. Plants that drop seeds and leaves creating a hazard underfoot should be avoided. Trees with shallow roots are hazardous as the roots may breakthrough the pathway surface. 3.12 Obstacles and Signs (see Obstructions) 4. EXISTING CONSTRUCTIONS Textured rubber adhesive tiles can be applied to existing pavement to avoid slipping and to warn sightless people.

Existing curbs that obstruct the pedestrian flow should be ramped (see Curb Ramps) Existing pathways with steps, stairs or steep slopes need not be modified if an alternative accessible route exists. Notes: (1) A guiding line is a straight continuous line of detectable natural objects and defined edges (i.e., building frontages, grass verges, raised platforms, continuous railing, curbs, guards, low barriers, etc.). (2) The acoustic effect of the rubber tiles as compared with the surrounding surface will provide both a tactile and audible warning of the change in direction.

[_headerthemes.htm]

I. URBAN DESIGN CONSIDERATIONS 5. CURB RAMPS


1. PROBLEM IDENTIFICATION Improperly designed transition or no transition at all between the curb and the street at pedestrian crossings and in the vicinity of building entrances. 2. PLANNING PRINCIPLE To overcome changes in level between the pavement and the road surface and also on the Fig. 1 Fig. 2 Fig. 3 Fig. Standard curb ramp

Returned curb ramp.

road surface and also on the pavement itself. 3. DESIGN CONSIDERATIONS 3.1 General Curb ramps are used wherever there is a difference in level on pedestrian paths or cross paths. To avoid confusing sightless pedestrians, curb ramps should be positioned out of the usual line of pedestrian flow. The unobstructed width of the pathway should be not less than 0.90 m (see Pathways). Curb ramps should be located away from places where water accumulates. 3.2 Types (a) Standard curb ramps: Cut back into the pavement with flared sides providing transition in three directions (fig. 1). (b) Returned curb ramps: (1) Providing slope in one direction. This could be a dangerous measure if the sides are not protected (fig. 2). (c) Built-up curb ramps: (2) Usually with flared edges (fig. 3). 3.3 Application At each quadrant of each street intersection (fig. 4). At each pedestrian crossing, on opposite sides of the street (fig. 4). At drop-off zones, near building entrances (fig. 5). Between accessible parking areas and pathways (fig. 6).

4 Fig. 5 Fig. 6

Built up curb ramp.

Curb ramp in a drop-off zone.

3.4 Curb ramps at intersections At intersections, curb ramps can be installed in any of the following ways: (a) Directly in the path of travel (fig. 4). (b) Diagonally across the corner (3) (fig. 7). (c) Continuously wrapped around the corner (fig. 8). 3.5 Narrow pavement Where the construction of curb ramps would affect the width of the travel route, the whole pavement should be lowered, at a maximum slope of 1:12, to provide the necessary level transition (fig. 9). For narrow pavements lowered at a corner, the tactile tiling indicating the location of the pedestrian crossing could be constructed as indicated in figure 10. 3.6 Width The minimum width of a curb ramp should be 0.90 m, excluding the sloping sides. The recommended width is 1.20 m (4) (fig. 11). 3.7 Slope The maximum slope of a curb ramp should be 1:12. The maximum slope of flares should be 1:12. Level transfer is recommended between the curb ramp and the surface of a pathway. A lip not exceeding 15 mm can be used (fig. 11). 3.8 Guide strips Fig. 10 Fig. 8 Fig. 7

Fig. 9

A guide strip painted in a contrasting colour should be constructed to guide sightless and partially sighted pedestrians to the location of the curb ramp (fig. 4). (see Pathway; Pedestrian Crossings) 3.9 Surface and colour Curb ramps, including flares, should have a rough texture or ground pattern to make them detectable and slip-resistant. The surface colour should be distinct and should contrast with the surrounding surfaces to guide pedestrians with limited vision. 4. EXISTING CONSTRUCTIONS The maximum allowable slope for a curb ramp constructed along high pavements should not be more than 1:10. The maximum slope of the flares should also be 1:10. If existing curb ramps do not comply with the above mentioned requirements, they should be modified. For narrow pavements more than 0.15 m high, where the construction of curb ramps would obstruct the free passage of pedestrians: (a) The pavement can be lowered to the road level to obtain the required transition between the pavement and the road surface (fig. 9) (fig.10). (b) Built-up curb ramps can be constructed if they would not obstruct the required width of the road (fig. 3). Notes:

Fig. 11

(1) Returned curb ramps are unaccepted measures in some countries. (2) In some countries, such as Canada, built-up curb ramps are accepted only as remedial measures to overcome existing barriers, but not on public streets or pathways. (3) Corner curb ramps could be dangerous to wheelchair users if the pedestrian crossing is not wide enough. (4) The curb ramp construction at pedestrian crossings does not need to cover the whole width of the crossing.

[_headerthemes.htm]

I. URBAN DESIGN CONSIDERATIONS 6. PEDESTRIAN CROSSINGS


1. PROBLEM IDENTIFICATION Uneven road surface. Lack of guide strips. Lack of warning marking for crossings. Gratings on the road surface. 2. PLANNING PRINCIPLE To facilitate the safe and independent crossing of disabled people. 3. DESIGN CONSIDERATIONS 3.1 General Guide strips used in pedestrian crossings.

Pedestrian crossings should be equipped with traffic control signals. Low-traffic crossings frequently used by disabled people can be controlled by a pedestrian push-button system. Constructing traffic islands to reduce the length of the crossing is recommended for the safety of all road users. 3.2 Guide strips (fig. 1) Guide strips should be constructed to indicate the position of pedestrian crossings for the benefit of sightless pedestrians (see Pathways; Curb Ramps). A guide strip should lead to pedestrian light poles with push buttons for the benefit of the visually disabled. 3.3 Traffic signals Pedestrian traffic lights should be provided with clearly audible signals for the benefit of sightless pedestrians. Acoustic devices (1) should be installed on a pole at the point of origin of crossing and not at the point of destination. The installation of two adjacent acoustic devices such as bleepers is not recommended in order to avoid disorientation. The time interval allowed for crossing should be programmed according to the slowest crossing persons. 3.4 Push buttons Push buttons should be easy to locate and operate and should be placed between 0.90 m and 1.20 m off the ground

Fig. 1

Raised pedestrian crossing.

Fig. 2

0.90 m and 1.20 m off the ground for the benefit of wheelchair users. 3.5 Traffic islands The traffic island depth should not be less than 1.50 m. The width of a traffic island should not be less than 1.50 m. A coloured tactile marking strip at least 0.60 m wide should mark the beginning and the end of a traffic island, to guide pedestrians with impaired vision to its location. 3.6 Road hump The road surface at pedestrian crossings can be raised to the same level as the pathway so that wheelchair users do not have to overcome differences in height (2) (fig. 2). 3.7 Surface The road surface should be firm, well-drained, non-slip and free of construction joints. 3.8 Drains and gratings (see Pathways) 4. EXISTING CONTRUCTIONS The road surface should be firm, well-drained, non-slip and free of construction joints. Notes: (1) Experience shows that acoustical signals encourage safer crossing behavior among children as well (2) Road bumps are also helpful in reducing the speed of traffic approaching the intersection.

[_headerthemes.htm]

I. URBAN DESIGN CONSIDERATIONS 7. PARKING


1. PROBLEM IDENTIFICATION Poor parking facilities. Insufficient width of the parking aisle. No allocation of parking space for the disabled. 2. PLANNING PRINCIPLE To provide accessible parking facilities as close as possible to the point of destination. 3. DESIGN CONSIDERATIONS 3.1 General Accessible parking provisions apply to both outdoor and underground facilities. For multi-storey indoor parking facilities, at least one level should be served by an accessible elevator. 3.2 Number For parking facilities of less than 50 cars, at least one accessible parking space should be provided in every parking facility. For parking facilities of a maximum number of 400 spaces, accessible parking spaces should at least be provided in the ratio of 1:50 (one accessible space for every 50 spaces). Fig. 1 Fig. 2 Fig. 3

For parking facilities of more than 400 spaces, at least 8 accessible parking spaces should be provided plus 1 space for each additional increment of 100 cars over 400. 3.3 Location For outdoor parking, accessible parking spaces should be located not more than 50 m from accessible building entrances. For indoor parking, accessible parking spaces should be located right next to accessible elevators, or as close as possible to exits. The ends of rows are preferable for vans with lifts for wheelchair users. 3.4 Dimensions The minimum width of an accessible parking space is 3.60 m. The recommended width is 3.90 m (fig. 1). An access aisle 1.20 m wide can be located between two ordinary parking spaces (fig. 2). For indoor parking, the minimum height clearance for vans with hydraulic lifts is 2.40 m. Where parking spaces are angled, the extra space at the end of a row can be used as a parking aisle for disabled persons (fig. 3). 3.5 Parking curb If a curb exists, curb ramps should be provided to link accessible parking spaces to accessible pathways (fig. 2). If no curb exists, a textured surface at least 0.60 m wide is needed to separate the pathway from the vehicular area; otherwise bollards should be used

Fig. 4

Fig. 5 Drop off area dimensions.

Fig. 6

Fig. 7

(see Street Furniture). Pre-cast wheelstops can also be used to set apart a passage at least 0.90 m wide (fig. 4) (fig. 5). 3.6 Curbside parking Curbside parking is dangerous for disabled people unless it is designed as an accessible drop-off area. 3.7 Drop-off areas (fig. 6) Drop-off areas are beneficial for picking up and dropping off people with physical limitations, parents with children, people carrying loads, etc. Drop-off zones should be provided at public transport stops such as bus stops, and not more than 30.00 m from accessible building entrances. The drop-off area should be at least be 3.60 m wide and incorporate an aisle 1.20 m wide to allow for manoeuvring. The length should accommodate at least two cars. Appropriate curb ramps should be provided to facilitate circulation over paved surfaces. Where no curb exists to mark the separation between pedestrian and vehicle zones, the installation of a cue is necessary to guide sightless pedestrians: (a) Bollards may be used (see Street Furniture); (b) A tactile marking strip at least 0.60 m wide can be constructed at the edge of the pathway to warn of the transition to a vehicular area. A protected shelter or canopy with seating facilities is a recommended design feature at passenger loading zones. Signs should be installed to identify a drop-off zone and

Fig. 8

Fig. 9

prevent its misuse as a parking space. 3.8 Surface The surface of a parking facility should beuniform and smooth. The slope of a parking ramp should not exceed 1:20. 3.9 Signs (fig. 7) Accessible parking areas should be marked by the international symbol of accessibility. (1) 4. EXISTING CONSTRUCTIONS If the parking area is more than 50.00 m from the building entrance, a vehicular drop-off area within 30.00 m of the entrance should be built or an accessible parking space close to the entrance should be constructed. If no accessible parking space is available, one of the following measures should be implemented: (a) Block a peripheral regular stall with bollards to get one accessible parking space (fig. 8). (b) Block a central regular stall with bollards to get two accessible parking spaces (fig. 9). (c) Two accessible parking aisles (fig. 9). For indoor parking spaces with clear height of less than 2.40 m, alternative outdoor provisions for vans carrying disabled people should be provided. Notes: (1) An exacting fine can be imposed on non-disabled drivers who park in a parking space designated for the

disabled.

[_headerthemes.htm]

II. ARCHITECTURAL DESIGN CONSIDERATIONS 1. RAMPS


1. PROBLEM IDENTIFICATION Inaccessible building entrances due to difference between indoor and outdoor levels. Inaccessible routes due to differences in level. Lack of or improper design of ramps. Very steep and/or long ramps with no resting landings. 2. PLANNING PRINCIPLE To provide ramps wherever stairs obstruct the free passage of pedestrians, mainly wheelchair users and people with mobility problems. 3. DESIGN CONSIDERATIONS 3.1 General An exterior location is preferred for ramps. Indoor ramps are not recommended because they take up a great deal of space. Ideally, the entrance to a ramp should be immediately adjacent to the stairs. 3.2 Ramp configuration (1) Ramps can have one of the following configurations: Fig. 3 Fig. 4 Fig. 5 Fig. 1 Straight run ramp with a landing.

Fig. 2

(a) Straight run (fig. 1);

(b) 90 turn (fig. 2); (c) Switch back or 180 turn (fig. 3). Maximum recommended slope is 1:20.

3.3 Width Width varies according to use, configuration and slope. The minimum width should be 0.90 m. 3.4 Slope The maximum recommended slope of ramps is 1:20. Steeper slopes may be allowed in special cases depending on the length to be covered (fig. 4).

Maximum slope 1:20 i.e., 9% 1:16 i.e., 6% 1:14 i.e., 7% 1:12 i.e., 8% 1:10 i.e., 10% 1:08 i.e., 12%

Maximum length 8m 5m 2m 1.25 m 0.5 m

Maximum rise 0.50 m 0.35 m 0.15 m 0.12 m 0.06 m

3.4 Landings Ramps should be provided with landings for resting, maneuvering and avoiding excessive speed. Landings should be provided every 10.00 m, at every change of direction and at the top and bottom of every ramp.

The landing should have a minimum length of 1.20 m and a minimum width equal to that of the ramp 3.5 Handrail A protective handrail at least 0.40 m high must be placed along the full length of ramps. For ramps more than 3.00 m wide, an intermediate handrail could be installed (fig. 5). The distance between handrails when both sides are used for gripping should be between 0.90 m and 1.40 m (fig. 5). 3.6 Surface The ramp surface should be hard and non-slip. Carpets should be avoided. 3.7 Tactile marking A coloured textural indication at the top and bottom of the ramp should be placed to alert sightless people as to the location of the ramp. The marking strip width should not be less than 0.60 m. 3.8 Drainage n Adequate drainage should be provided to avoid accumulation of water. 3.9 Obstacles The same clearance considerations that apply to pathways apply to ramps (see Obstructions). 3.10 Mechanical Ramps Mechanical ramps can be used in large public buildings but are not recommended for use by persons with physical impairments. If the ramp is to be used by a wheelchair-confined person, the

slope should not exceed 1:12. The maximum width should be 1.00 m to avoid slipping. 4. EXISTING CONSTRUCTIONS If the topography or structure of the existing building is restrictive, minor variations of gradient are allowed as a function of the ramp length:

Maximum slope 1:20 i.e., 9% 1:16 i.e., 6% 1:14 i.e., 7% 1:12 i.e., 8% 1:10 i.e., 10% 1:08 i.e., 12%

Maximum length 8m 5m 2m 1.25 m 0.5 m

Maximum rise 0.50 m 0.35 m 0.15 m 0.12 m 0.06 m

A non-slip surface finish should be added to slippery ramps. Notes: (1) Circular or curved ramps are not recommended

[_headerthemes.htm]

II. ARCHITECTURAL DESIGN CONSIDERATIONS 2. ELEVATORS

1. PROBLEM IDENTIFICATION Inadequate space inside the elevator cab. High position of switches, buttons and control panel. Narrow entry doors. Insufficient opening time interval. 2. PLANNING PRINCIPLE To provide well-dimensioned elevators, that disabled people can use conveniently. 3. DESIGN CONSIDERATIONS 3.1 General The accessible elevator should serve all floors normally reached by the public. Key-operated elevators should be used only in private facilities or when an elevator operator is present. Wide elevator cabs are preferable to long ones. 3.2 Elevator cab The minimum internal elevator dimensions, allowing for one wheelchair passenger alone, are 1.00 m x 1.30 m (fig. 1). The door opening should not be less than 0.80 m. The inside of the elevator should have a handrail on three sides mounted 0.80 to 0.85 m from the floor (fig. 2). The maximum tolerance for stop precision should be 20 mm. 3.3 Control panel Fig. 3 Fig. 2

Fig. 1

The control panel can be mounted at one of the alternative locations shown in figure 3. For ease of reach, the control panel should be mounted 0.90 m to 1.20 m from the floor (fig. 2). Control buttons should be in an accessible location and illuminated. Their diameter should be no smaller than 20 mm. The numerals on the floor selector buttons should be embossed so as to be easily identifiable by touch. 3.4 Call buttons For ease of reach, call buttons should be mounted 0.90 m to 1.20 m from the floor (fig. 4). 3.5 Floor identifiers Tactile numerals should be placed on both sides of the door jambs at an approximate height of 1.50 m to help a lone sightless passenger to identify the floor reached (fig. 4). 3.6 Hall signal The elevator hall signal should be placed at an approximate height of 1.80 m (fig. 4). 3.7 Door re-opening activators The door opening interval should be no less than five seconds. Re-opening activators should be provided. 3.8 Audiovisual signals The elevator should signal arrival at each floor by means of a bell and a light to alert sightless and hearing-impaired passengers simultaneously. 3.9 Floor surface The floor of the elevator and

Fig. 4

the area in front of the elevetor on each floor should have a non skid resilient surface or a low-pile fixed carpet. 3.10 Colour The colour of the elevator door should contrast with the surrounding surface so as to be easily distinguishable by persons with visual impairments. 4. EXISTING CONSTRUCTIONS The minimum acceptable size of an existing elevator cab, allowing for a single wheelchair passenger, is 0.95 m x 1.25 m. Smaller cabs should be replaced. The minimum acceptable width of an existing elevator door opening is 0.75 m. Call buttons and control panels mounted higher than the recommended height may be left in place if they are within 1.40 m of the floor, this being the maximum reach of a wheelchair user. Controls mounted higher than 1.40 m should be replaced. Where there are two identical control panels, only one need be replaced.

[_headerthemes.htm]

II. ARCHITECTURAL DESIGN CONSIDERATIONS 3. PLATFORM LIFTS (1)


1. PROBLEM IDENTIFICATION Fig. 1

Changes in level between indoor and outdoor areas. Changes in level inside a building. Insufficient space for ramps. 2. PLANNING PRINCIPLE To allow people with mobility problems to have free vertical access between different levels. 3. DESIGN CONSIDERATIONS 3.1 General Platform lifts are special passenger-elevating devices for the disabled. Platform lifts can have either a vertical or an inclined movement. 3.2 Vertical movement platform lifts For maximum level changes of 2.50 m, vertical movement platform lifts may be installed adjacent to the stairs (fig. 1). For level changes of more than 1.20 m, the lift should be placed in a closed structure with doors at the different accessible levels (fig. 2). Vertical platform lifts can have a variety of opening for entry and exit (fig. 3). 3.3 Inclined movement platform lifts Inclined movement platform lifts consist of three elements: a railing, an electric generator and a moving platform or seat. Fig. 3 Fig. 4 Fig. 5 Fig. 2

The operating system of the lift can be either lateral (fig. 4) or suspended (fig. 5). Inclined movement platform lifts can be installed along the stair wall, as long as they do not obstruct the required width of the exit. The seat or platform can be folded when not in use. The minimum width of the stairs should be 0.90 m to allow the installation of a lift (fig. 6). Platform lifts can be installed on all types of stairs including switchback stairs i.e. those with a rotation angle of 180 (fig. 7) and spiral staircases (fig. 5). 3.4 Lift size The minimum width of the lift platform should be 0.90 m and the minimum length should be 1.20 m (fig. 3). 4. EXISTING CONSTRUCTIONS Platform lifts can provide access to existing buildings where it would be difficult or unfeasible to install a ramp or an elevator. Inclined movement platform lifts are usually used to connect one or more floors or to overcome split levels in existing buildings. In buildings that are or would be frequently used by persons with mobility problems, such devices should not be utilized. Notes: (1) Platform lifts are also Fig. 7 Fig. 6

known as stairway lifts or wheelchair lifts.

[_headerthemes.htm]

II. ARCHITECTURAL DESIGN CONSIDERATIONS 4. STAIRS


1. PROBLEM IDENTIFICATION Steep staircases. Poorly designed steps that hinder foot movement. 2. PLANNING PRINCIPLE To provide safe and welldimensioned staircases for the comfort of all people, especially those with mobility problems. 3. DESIGN CONSIDERATIONS 3.1 General Differences in level should be illuminated or minimized as much as possible for the comfort of disabled people. A complementary ramped route, elevator or lift should be provided where there are steps in an otherwise accessible path. All steps should be uniform. Circular stairs and stepped landings should be avoided (fig. 1). Open risers are not recommended. 3.2 Width Fig. 2

Fig. 1

The minimum width of a stairway should be 0.90 m for one-way traffic and 1.50 m for two-way traffic. For indoor stairs, the riser should be between 0.12 m and 0.18 m, and the tread between 0.28 m and 0.35 m. For outdoor stairs, the maximum riser should be 0.15 m and the minimum tread should be 0.30 m. 3.3 Landing (fig. 2) (fig. 3) An intermediate landing should be provided when the stairs cover a difference in level of more than 2.50 m. The length of the landing should be at least 1.20 m extending along the full width of the stairs. 3.4 Nosing (fig. 4) Sharp edges and overhanging nosing should not be used for treads. Nosing should be flush or rounded and should not project more than 40 mm. 3.5 Handrails Handrails must be installed on both sides of the stairs and around the landing for gripping (fig. 3). For stairs more than 3.00 m wide, one or more intermediate handrails could be provided (fig. 5). The distance between the handrails when both sides are used for gripping should be between 0.90 m and 1.40 m (fig. 5). Handrails must extend a distance between 0.30 m and 0.45 m at the top and bottom of the stairs (see Railings and

Fig. 3 Recommended nosing types.

Fig. 4: Recommended nosing types Intermediate handrail for wide staircases.

Fig. 5

Fig. 6

Handrails) (fig. 3). 3.6 Tactile marking (fig. 2) (fig. 3) A textural marking strip should be placed at the top and bottom of the stairs and at intermediate landings to alert sightless people as to the location of the stairs. The tactile marking strip should be at least 0.60 m wide and should extend over the full width of the stairs. To guide users with poor vision, the colour of the strip should contrast with the surrounding surface. 3.7 Surface Landings, treads and nosing should be slip-resistant and free of projections. Exterior stairs should be pitched forward at 10 mm per metre to drain surface water. Slip-resistant stair nosing should be used to fix carpets on stairs. 3.8 Emergency stairs Emergency stairs should be identified by tactile markings. 3.9 Mechanical stairs (escalators) Mechanical stairs can be provided with an adaptable tread at least 1.20 m long, if they are to be used by persons confined to wheelchairs (fig. 6). The edges of escalators should be painted in a contrasting colour for the benefit of poor- sighted users. 4. EXISTING CONSTRUCTIONS When the configuration of the nosing cannot be modified, slip-resistant strip scould be applied to the nosing as an Fig. 7

alternative solution (fig. 7). Slip-resistant strips should be 40 mm wide and should not extent more than 1 mm above the tread surface. To guide people with sight problems, the colour of the strips should contrast with that of the stairs. Previous : Next

[_headerthemes.htm]

II. ARCHITECTURAL DESIGN CONSIDERATIONS 5. RAILINGS AND HANDRAILS


1. PROBLEM IDENTIFICATION Unsafe railings. Hard to grip handrails. No railings or handrails. 2. PLANNING PRINCIPLE To install adequate railing, wherever needed for the comfort and safety of all people, especially those with mobility problems. 3. DESIGN CONSIDERATIONS 3.1 General Safety guards or railings should be installed around hazardous areas, stairs, ramps, accessible roofs, mezzanines, galleries, balconies and raised platforms more than 0.40 Fig. 1

and raised platforms more than 0.40 m high. On stairways, windows positioned less than 1.00 m from the landing should have railings. Handrails should be installed to assist disabled persons in bathrooms and toilets (see Rest Rooms). Spacing between the vertical and horizontal bars of railings should be narrow for the safety of children. Handrails should not obstruct the path of travel. 3.2 Height (fig. 1) (1) To facilitate use by ambulant disabled and elderly people, handrails should be mounted between 0.85 m and 0.95 m above the finished floor level. For the benefit of wheelchair users, a second handrail can be mounted between 0.70 m and 0.75 m from the floor. To facilitate use by children and short people, a third handrail can be mounted at a height of 0.60 m. To guide sightless people using a long cane, a rail should be mounted at a height between 0.10 m and 0.15 m (fig. 1); or a low curb should be installed at a height between 50 mm and 75 mm (fig. 2). Low curbs also act as wheelstops. 3.3 Mounting Railings should be securely attached to the wall or to a supporting structure so as to withstand heavy loads. Railings should not end abruptly but extend to the floor or blend into the wall so as not

Fig. 2

Fig. 3

Fig. 4

Fig. 5 Fig. 6

to create a hazard for sightless people. 3.4 Form (fig. 3) Handrails should allow a firm and easy grip. Circular cross-sections with a diameter of 40 mm are preferable. Sharp edges should be avoided. 3.5 Handrails for ramps and stairs Handrails should continue uninterrupted (except for doorways) on both sides and around the landing. Handrails should extend horizontally for a distance between 0.30 m and 0.45 m at the top and bottom of stairs and ramps, except in places where extensions could obstruct the pedestrian flow (fig.4). For stairs or ramps more than 3.00 m wide, a continuous intermediate handrail could be provided (see Ramps; Stairs). 3.6 Wall-mounted handrails The space between the handrail and the wall should be between 40 mm and 50 mm for smooth walls and 60 mm for rough textured walls (fig. 5). Where handrails are fully recessed into walls, a space of at least 0.15 m should be allowed between the top of the rail and the top of the recess (fig. 6). 3.7 Tactile marking For emergency exit stairs or ramps, a contrasting tactile strip at least 0.90 m long should be applied to the top and bottom edges of the handrail to alert the partially sighted.

3.8 Colour A contrasting colour is recommended for handrails to alert people with sight problems. 4. EXISTING CONSTRUCTIONS If existing railings and handrails do not comply with the above requirements, they should be modified or replaced. Notes: (1) Measurements are taken from the front of the tread.

[_headerthemes.htm]

II. ARCHITECTURAL DESIGN CONSIDERATIONS 6. ENTRANCES


1. PROBLEM IDENTIFICATION No distinct accessible entrance. Inadequate space in front of the entrance. 2. PLANNING PRINCIPLE To provide accessible and easy-to-find building entrances. 3. DESIGN CONSIDERATIONS 3.1 General For new accessible constructions, all main public entrances should be accessible to an ambulant disabled person. Fig. 1

At least one entrance per facility should be accessible to a wheelchair user. In new buildings, the accessible entrance(s) should be the main entrance(s) intended for use by the general public. Each accessible entrance should be connected by accessible pathways to accessible indoor or outdoor parking areas, local public transit stops and drop-off areas (fig. 1). In multi-storey buildings, the accessible entrance should permit access to a conveniently located accessible elevator or lift. 3.2 Signs Accessible entrances should be clearly identified using the international symbol of accessibility including alternate locations of accessible entrances (fig. 2). No signs are needed if the whole building is accessible. 3.3 Entrance landing Where the entrance door opens outward, the minimum landing dimensions should comply with figure 3. Where the entrance door opens inward, the minimum landing dimensions should comply with figure 4. The surface of the landing should have a slope of 2% for drainage. The finish material should be non-slippery. Fig. 4 Fig. 3 Fig. 2

Fig. 5

Jute door mats should be avoided. When used however, the upper surface of the mat should be level with the floor finish (fig. 5). Sheltered landings are preferable. 3.5 Threshold Thresholds should be removed wherever possible (see Doors). 3.6 Colour The colour of the entrance door should contrast with the surrounding surface so as to be distinguishable by people with sight problems. 3.7 Entrance vestibules (see Vestibules) 3.8 Entrance doors (see Doors) 4. EXISTING CONSTRUCTIONS Public buildings should have at least one accessible entrance. Wherever possible, this should be the main entrance intended for use by the general public (1) (see Building Types). If for architectural or technical reasons the main entrance cannot be made accessible, an alternative accessible entrance should be provided. The location of the alternative entrance should be clearly indicated by signs. To allow for an accessible entrance, one of the following solutions can be adapted: (a) Ramps, bridges or mechanical lifts be used; (2)

(b) The entrance level might be modified earthfill, or by changing the grade or the landscaping of the surrounding site; (c) A window or another door at ground might be converted into an accessible entrance. Notes: (1) For existing constructions, a service entrance can be used temporarily as an accessible entrance, but it should not be the only accessible entrance. (2) Mechanical lifts are recommended for buildings where modifications are impossible or unacceptable.

[_headerthemes.htm]

II. ARCHITECTURAL DESIGN CONSIDERATIONS 7. VESTIBULES


1. PROBLEM IDENTIFICATION Fig. 1 Narrow doorways and vestibules. 2. PLANNING PRINCIPLE To provide sufficient space to manoeuvre a wheelchair between two sets of doors. 3. DESIGN CONSIDERATIONS 3.1 General Vestibule entrance doors can be either the sliding type or the swinging type. For swinging doors, the door Fig. 3 Fig. 4 Fig. 5 Fig. 6 Fig. 2

mechanism should allow the maximum opening swing. 3.2 Layout The layout of two swinging doors in a series can be one of the following: (a) Outward-swinging (fig. 1); (b) Double-swinging (fig. 2); (c) Swinging in the same direction (1) (fig. 3); (d) Inward-swinging (fig. 4). 4. EXISTING CONSTRUCTIONS For narrow vestibules either of the following solutions can be employed: (a) Replace swinging doors with sliding doors; (b) Change the direction of the door swing so that both doors can be made to swing outwards, if possible (fig. 5). (c) Install double-swinging doors for small exit vestibules with a minimum width of 1.20 m. (d) Remove the inside or second door. (e) Enlarge the existing vestibule if possible (2) (fig. 6). Notes: (1) Doors swinging in the same direction can be aligned, offset on opposite walls or offset on adjacent walls. (2) This is recommended for vestibules that also serve as emergency exits because other solutions, such as changing the direction of the door swing, might not solve the problem.

Fig. 6

Dimensions for inward swinging doors.

Enlarging existing vestibule.

[_headerthemes.htm]

II. ARCHITECTURAL DESIGN CONSIDERATIONS 8. DOORS


1. PROBLEM IDENTIFICATION Narrow doorways. Doors hinged on the wrong side, thus hindering accessibility. Doorways with high thresholds. Heavy and hard-to-operate door leaves. 2. PLANNING PRINCIPLE To facilitate the passage of a wheelchair user through doors. 3. DESIGN CONSIDERATIONS 3.1 General Accessible doors should be so designed as to permit operation by one person in a single motion with little effort. Power-operated doors are the best for people with disabilities. The activator system should be automatic or placed within easy reach. An accessible door should have the following features: a sign, a door handle, an extra pull handle, glazing and a kick plate. 3.2 Door types (a) Automatic doors: - Can be of the sliding or swinging type. In general sliding doors are preferable to swinging doors (fig. 1) (fig. 2). Fig. 2 Fig. 1 Activating mat for automatic doors.

Fig. 3 Fig. 4

- Automatic doors are useful when traffic is heavy. - Automatic doors should have an adequate opening interval. -Guardrails can be installed near doubleswinging doors to indicate a dooropening area and to prevent people from being hit by the door. (b) Revolving doors: - Revolving doors are not suitable for the use of disabled people or people with prams. - Wherever there are revolving doors, an adjacent accessible swinging or sliding door should be provided (fig. 3). - Auxiliary gates should be provided next turnstiles (fig. 3). (c) Pivoted doors: - Pivoted doors should swing away from the direction of travel wherever possible. - Pivoted doors in series are considered as vestibules (see Vestibules). (d) Sliding and folding doors: Manual sliding and folding doors are recommended for narrow spaces not heavily used by the public (fig. 4). 3.3 Door opening For exterior doors, the minimum opening is 0.90 m when the door is open. For interior doors, the minimum opening is 0.80 m when the door is open. The minimum door opening can be 0.75 m if the access is straight or if the door can stay open by itself (fig. 5). The minimum door width of rest rooms should be 0.75 m. For doors installed in an opening more than 0.60 m in Fig. 6 Fig. 7 Fig. 8

Fig. 5

depth, the clear door opening should be at least 0.90 m (fig. 6). For double-leaf doors, at least one leaf should have a minimum clear width of 0.80 m (fig. 7). 3.4 Manual door hardware Operational devices on doors, such as handles, pulls, latches and locks, should be easy to grasp with one hand (fig. 8). (a) Handles: - Lever-type handles, push plates or pull handles are recommended for swinging doors because they are easy to open. (1) - Round knobs are not recommended. - Door handles should be located at a comfortable height between 0.90 m and 1.00 m from the floor surface. (b) Locks: Locks on entrance doors should be mounted at a comfortable height between 0.90 m and 1.00 m from the floor. (c) Extra pull handle: To facilitate closing, a door fitted with spring closers should be equipped with an extra pull handle approximately 0.30 m in length, located between 0.20 m and 0.30 m from the hinged side of the door and mounted between 0.90 m and 1.20 m from the floor. 3.5 Automatic doors hardware Automatic doors can be activated by: (a) Push buttons located at a comfortable height between 0.90 m and 1.20 m; (b) Activating mats, which can also serve as a location cue (fig. 2); (c) Card-insert switch; (d) Remote control. 3.6 Threshold (fig. 8)

Thresholds should be omitted wherever possible. Weatherstripping at the door bottom is preferred to thresholds. The threshold should not be more than 20 mm higher than the finished floor level. Thresholds higher than 6 mm should be beveled or have sloped edges to facilitate the passage of a wheelchair. 3.7 Exit doors landing The exit landing should not be lower than the finished floor level by more than 20 mm. 3.8 Glazing and glazed doors Outward swinging doors and doors in public corridors should have low windows to enable users to see oncoming traffic. The bottom edge of the window should not be higher than 1.00 m from the finished floor level (fig. 8). Completely glazed doors should be avoided in buildings frequented by people with visual impairments. Glazed doors should be clearly marked with a coloured band or mark placed for the benefit of all users at a height between 1.40 m and 1.60 m (fig. 2). 3.9 Kick plates Kick plates are useful in protecting the finish on the lower part of the door. Kick plates should be between 0.30 m and 0.40 m in height (fig. 8). 3.10 Signage In public buildings, the function or room number, incorporating international symbols should be identified at eye level, i.e. between 1.40 m and 1.60 m (fig. 8).

Room numbers should be placed on door frames and not on doors themselves so that the room number is visible even when the door is open. 3.11 Colour The door or the door frame can be painted in a colour that contrasts with the adjoining wall to facilitate its identification by people with visual impairments. 4. EXISTING CONSTRUCTIONS It is recommended that automatic doors replace heavy, hard-to-open swinging doors. Door openings narrower than 0.75 m should be widened. A swing-clear hinged door may be used to slightly enlarge an opening. Notes: (1) Lever type handles can be activated by hand, elbow or other means.

[_headerthemes.htm]

II. ARCHITECTURAL DESIGN CONSIDERATIONS 9. CORRIDORS


1. PROBLEM IDENTIFICATION Long and narrow corridors creating orientation difficulties. 2. PLANNING PRINCIPLE To provide well-dimensioned corridors to facilitate the passage

and maneuvering of a wheelchair. 3. DESIGN CONSIDERATIONS 3.1 General Wide corridors are useful for wheelchair users, service equipment, high traffic areas, etc. 3.2 Width The unobstructed width of a low-traffic corridor should not be less than 0.90 m. This also allows maneuverability in 90 turns (fig. 1). The unobstructed width of a public corridor should not be less than 1.50 m. The recommended width is 1.80 m (1) (fig. 2). To allow maneuverability in 180 turns, the minimum circulation space should be as shown in figure 3. The corridor width should allow maneuverability through the doors located along its length (fig. 2) (fig. 4). 3.3 Obstructions Obstacles protruding into the corridor, such as drinking fountains or public telephones, should be placed outside the circulation path, in alcoves or cul-de-sacs (fig. 5). Overhanging signs and obstacles should be mounted at least 2.00 m high (fig. 6). 3.4 Surface Changes in surface level of more than 13 mm should be ramped. Floor surfaces should be nonslip and even. Carpets should be securely fastened. Fig. 4 Fig. 3 Fig. 1

Fig. 2

4. EXISTING CONSTRUCTIONS Narrow corridors should be widened along their full length if feasible; otherwise, passing areas should be located at appropriate intervals along the corridor length. The minimum width of the passing area should be 1.50 m and the minimum length should be 2.40 m. In highly restricted spaces, the height of an obstacle or sign can be dropped to 1.95 m. Notes: (1) 1.50 m is the minimum width for two wheelchairs to pass each other or for one wheelchair to make a full turn. Fig. 5 Fig. 6

[_headerthemes.htm]

II. ARCHITECTURAL DESIGN CONSIDERATIONS 10. REST ROOMS


1. PROBLEM IDENTIFICATION Insufficient space inside a rest room. Poor design and positioning of fixtures and fittings. Taps that are difficult to grip. 2. PLANNING PRINCIPLE Fig. 1 Fig. 2

Fig. 3

To provide sufficient accessible space inside rest rooms, with all fixtures and fittings being within easy reach. 3. DESIGN CONSIDERATIONS 3.1 General Turning circles of 1.50 m diameter are recommended inside the rest room to allow for full-turn maneuvering of a wheelchair. The ease of transfering from a wheelchair to a toilet seat or bidet depends on the approach. In general there are four different approaches: (a) The parallel approach, which is the easiest (fig. 1); (b) The diagonal approach, which is difficult (fig. 2); (c) The perpendicular approach, which is also difficult (fig. 3); (d) The frontal approach which is the most difficult and needs particular care (fig. 4). 3.2 Public rest rooms In any public rest room, at least one compartment for each sex should be accessible to an ambulant disabled person. In any public rest room at least one unisex com partment should be accessible to a wheelchair user. Accessible rest Fig. 5 Fig 6. Fig. 7 Fig. 4

Fig. 8

Fig. 9 Fig. 10 Fig. 11 Fig. 12 Fig. 13

rooms should be marked with the international symbol of accessibility. No indication is needed if all rest rooms are accessible. Pivoted doors should open outward unless sufficient space is provided within the toilet stall. 3.3 Special public rest rooms Installation of a separate unisex unit is always desirable in public buildings, even when all rest rooms are accessible, so as to allow a disabled person to be assisted by an attendant of the opposite sex. Special rest rooms should be marked with the international symbol of accessibility but should not be the only accessible rest rooms. A water-closet and a lavatory should be provided within special rest rooms. The size and layout of special rest rooms should comply with the minimum requirements (fig. 5). 3.4 Residential rest rooms Residential rest rooms include those in private residences, health facilities, dormitories and other residential institutional settings. Residential bathrooms are usually equipped with a toilet, a bidet, a wash-basin and a

bath-tub or shower. In multiple-rest-room arrangements (such as dormitories): (a) Only one wash-basin per rest room needs to be accessible; (b) At least one shower stall and one toilet stall should be designed for a wheelchair user. To save space in private occupancies: (a) The tiled floor area adjacent to the tub can be used as a shower space; (b) The wash-basin seat might be used as a seat during the use of the washbasin or the hand shower. The size and layout of residential rest rooms should comply with the minimum requirements (fig. 6). 3.5 Rest room fixtures 1) Water closets: The size and layout of water-closets and toilet stalls should comply with the minimum requirement (fig. 7) (fig. 8). The height of the toilet seat should be between 0.45 m and 0.50 m from the finished floor level. (1) The distance between the center line of the toilet seat and the adjacent wall, if provided with a grip bar, should be between 0.45 m and 0.50 m. Grab bars should be mounted on the wall behind the water Requirements for wash basins.

Requirements for wash basins. closet, if it is of the tankless type, and on the side wall closest to the water closet, or mounted on the floor at the edges of the seat. (2) Grab bars should be mounted at a height between 0.85 m and 0.95 m from the floor. Flushing arrangements and toilet paper should be placed within reach at a height between 0.50 m and 1.20 m. Accessible handoperated flushing controls, located on the open side of the watercloset, are recommended. Wall-mounted water closets are recommended. 2) Lavatories: The dimensions of lavatories should comply with the minimum requirements (fig. 9). The height of a wash basin should be between 0.80 m and 0.85 m above the finished floor level. The distance between the center line of the wash-basin and the adjacent side wall should at least be 0.45 m. The wash-basin may be drawn forward from the wall a distance between 0.15 m and 0.20 m. No shelves must be located above the wash- basin.

Minimum requirements for bathtubs.

Minimum requirments for shower stalls

3)Bath-tubs: In general bath-tubs are difficult to use by those confined to a wheelchair without the help of an attendant. The dimensions of bath-tubs should comply with the minimum requirements (fig. 10). The minimum dimensions of the bath-tub should be 1.60 m x 0.70 m. The height of the tub should be between 0.45 m and 0.50 m from finished floor level. An in-tub seat or a seat at the same height of the tub should be provided at the head side of the tub. (1) A grab bar should be mounted on the wall between 0.85 m and 0.95 m from the finished floor level. (2) Tubs with a toe recess are recommended. 4) Showers: The dimensions of showers should comply with the minimum requirements (fig. 11) (fig. 12). The shower should have a seat conveniently positioned for the shower head at a height of 0.45 m and 0.50 m. (1) The shower seat should be of the Minimum requirments for urinals.

Minimum requirments for shower stalls

hinged pull-down or removable type, not springloaded. A grab bar should be placed on the wall opposite the seat and around the back wall, mounted at a height between 0.85 m and 0.95 m. Drain openings should be placed in a corner of the stall so that slip-resistant rubber mats can be used. The floor of the shower stall should not be more than 20 mm below the level of the surrounding floor area. The shower stall should have a beveled threshold not exceeding 13 mm above the finished floor. 5) Bidets: The dimensions of bidets should comply with the minimum requirements. The upper edge of the bidet should be between 0.45 m and 0.50 m from the finished floor level. (1) The distance between the center line of the bidet and the adjacent wall should be at least 0.45 m. Wall mounted bidets are recommended. 6) Urinals: (fig. 13) At least one accessible urinal should be provided in public rest rooms.

Urinals should have a clear space on both sides. A full-length urinal is the most accessible. Urinals with a protruding lip should be mounted at a height of 0.45 m from the finished floor level. 3.6 Rest room door The clear door opening should be at least 0.75 m with the door in the open position. Doors should be lockable from inside and releasable from outside under emergency situations. Regardless of the door type, a handle should be placed on the door from the inside to facilitate closing. Another handle should be provided on the outside (see Doors). 3.7 Accessories All accessories, such as soap, towel and toilet paper dispensers, should be placed at a height between 0.50 m and 1.20 m from the finished floor level. 3.8 Grab bars Grab bars should be installed in waterclosets, bath-tubs and showers to assist disabled persons to use the facilities safely and easily. (2) Grab bars should have a diameter of 30 mm to 40 mm.

Wall-mounted grab bars should extent between 35 mm and 45 mm from the wall. Grab bars should be firmly fixed with stand loads and should have non-slip surfaces; knurled surfaces usually prevent slipping. 3.9 Mirrors Mirrors should be suitable for use by both standing and seated persons. Low mirrors or downward tilted mirrors can be used. The bottom edge of mirrors should be located at a maximum height of 1.00 m from the finished floor level (fig. 9). 3.10 Faucets Single-lever mixingtype faucets, which are easily operated by hand or elbow, are recommended. Faucets with push buttons are also convenient. The clearance between the grip of the tap and any adjacent vertical surface should not be less than 35 mm. The space between two taps should not be less than 0.20 m. The left tap should be connected to the hot water supply. Telephone fixtures with a cord at least 1.50 m long are recommended for use in

showers and bath-tubs. These can be hand-held or fixed at an adjustable height between 1.20 m and 1.80 m from the floor to suit all users. 3.11 Flooring Rest rooms must not have doorsteps. The gradient of the floor should be as low as possible. Thresholds should be avoided. When inevitable, the maximum threshold height should be 20 mm (see Doors). Flooring materials should be skid-proof and easy to clean. The floor should be well-drained and provided with adequate waterproofing. 3.12 Alarms Rest rooms should be equipped with an alarm system. 3.13 Pipes All exposed hot water pipes should be insulated or covered. It is preferable that pipes be fitted in the wall. 4. EXISTING CONSTRUCTIONS 4.1 Public rest rooms For accessible buildings, at least one accessible unisex rest room should be provided per facility (see Building Types).

4.2 Wate-closets To obtain an accessible toilet combine two adjacent stalls by removing one water-closet and the mutual partition, provided that the number of remaining fixtures is sufficient for the floor population. 4.3 Urinals Existing high urinals need not be replaced if accessible toilet fixtures are available. One urinal per rest room can be lowered. 4.4 Rest room vestibules For narrow vestibules, replace doors with automatic door openers or use swing clear hinges. Doors that restrict maneuvering space, should be removed so long as this does not inhibit privacy. 4.5 Grab bars If grab bars are not provided in the initial construction, walls should be reinforced to withstand loads. 4.6 Accessories Rest room accessories located at a maximum height of 1.40 m need not be modified if they are accessible. 4.7 Mirrors If existing mirrors are too high, they can be tilted or a full-length mirror can be installed on

another wall. Notes: (1) Toilet seats, bidets, shower seats and bath-tub seats are required to be mounted at the same height of the wheelchair seat, i.e. between 0.45m and 0.50 m above floor level. (2) Grab bars are manufactured in various dimensions and shapes. They can either be wallmounted or floor-mounted. Retractable bars are also available.

[_headerthemes.htm]

III. BUILDING TYPES


1. PROBLEM IDENTIFICATION Lack of special provisions for the disabled regarding accessible buildings and facilities. 2. PLANNING PRINCIPLE To design, to the extent possible, public buildings accessible to all. 3. DESIGN CONSIDERATIONS 3.1 General Buildings that have to comply with accessibility requirements for the disabled include all public buildings, governmental facilities and institutions, office buildings, residential buildings, commercial buildings, health facilities, educational institutions restaurants, recreational facilities, sports facilities, religious buildings

and all other building types normally used by the general public. Except as specified below, only buildings for private use, such as private residences, clubs, offices or studios, etc. need not comply with requirements for accessibility for the disabled. For accessible buildings, at least one entrance per facility should be accessible to a wheelchair user. For new buildings, the accessible entrance(s) should be the main entrance(s) intended for use by the general public. Wherever waiting areas, coffee shops, display areas, merchandising departments, service areas, ticket counters, refreshment stands, etc. are provided for public use, these facilities should be accessible to disabled people, mainly to wheelchair users. All work areas in which physically disabled persons may be employed should be accessible. In any public rest room, at least one unisex compartment should be accessible to a wheelchair user. 3.2 Residential buildings Private residences may be left inaccessible to a wheelchair user. However, it is desirable to consider a minimum of accessibility requirements so as to accommodate disabled guests. In new apartment buildings constructed for rent or sale, provisions for disabled persons should be considered. The number of wheelchair housing units should be provided at a rate of one unit for a typical population of 1000.
(1)

3.3 Office buildings

New office buildings should be as accessible as possible so as to accomodate all persons and not hinder employment of disabled persons. New low-rise office blocks with no elevators need not be accessible to a wheelchair user. Office space at ground level, if any, should be accessible. For small office buildings where the floor area limits the provision of accessible rest rooms on each floor, one accessible rest room could be provided to serve the entire building. The accessible rest room should be located adjacent to an accessible elevator. Where an office building is subdivided among various tenants, wheelchair rest rooms should be provided on each floor. 3.4 Commercial uses Accessibility requirements for wheelchair users should be applied to all new large speciality shops having a sales area of 100 m or more.(2) In small shops, provisions for wheelchair users should be applied wherever possible. In large multi-storey department stores and supermarkets, accessible elevators should be installed to provide access to lower and/or upper levels for the benefit of wheelchair users and people with mobility problems. Merchandise display areas in accessible shops should be as conveniently located as possible to a wheelchair user. Angled mirrors can be placed above high shelves for visibility. In accessible clothes shops, at least one changing room should allow for a full 360 turn of a wheelchair.

3.5 Assembly halls Under this category fall movietheaters, lecture halls, spectator seating in sports centres, and other assembly halls with fixed seating. The number of spaces designated for wheelchair users in a seating area can be estimated according to the following table:

Number of seats in a seating area

Number of required spaces for wheelchair users 6 i.e. 1/100 6+2 8+1 for each additional increment of 1000 seats Fig. 1

up to 600 up to 1000 over 1000

Some seats with removable or flip-up armrests should be provided at row ends to accommodate a wheelchair user or a person with limited ambulatory mobility. A level floor area for wheelchair users should be placed at row ends and should be scattered on different levels so as to have a variety of seating and viewing locations (fig. 1). 3.7 Cafeterias and restaurants New restaurants or parts of new restaurants and eating spaces should be as accessible as possible to a wheelchair user. In self-service restaurants tray slides and counters should be mounted approximatly 0.90 m from the floor. Food shelves should

Fig. 2

be mounted at a maximum height of 1.20 m (fig. 2). Cantilevered tables or tables with straight legs at each corner are preferable to central pedestals that might restrict wheelchair access. Stools and high tables are not suitable for wheelchair users. Low tables should be provided as well. 3.8 Hotels At least one room per new hotel or motel should be accessible to a wheelchair user. Bathrooms connected to these rooms have to be fully equipped. The layout should allow a lateral transfer to the toilet seat. Rooms designated for wheelchair users should, where possible, be placed at ground level so as to have a direct means of escape in case of fire. 3.9 Hospitals and health facilities All entrances should be accessible to a wheelchair user. All rooms should be accessible for the benefit of patients, disabled visitors and disabled staff members. All clinics on all floors should be accessible. All patients' rest rooms should be accessible to wheelchair user. All administrative departments should be accessible to staff members confined to wheelchairs. 3.10 Educational buildings All teaching, administrative and common areas should be accessible to a wheelchair user.

Fig. 2

Suitable arrangements should be made for stepped lecture halls or auditoriums (see table above). At least one accessible unisex rest room should be provided in each building other than student dormitories and residential accommodations. All recreational facilities should be usable by disabled people, to the extent possible. Colleges for physical education, police or military training and other activities requiring full physical abilities need not be accessible to disabled people. However, provisions should be made for disabled administrative staff members. 3.11 Libraries All open book stacks should be accessible. All library facilities and equipment should be accessible. A special room should be provided for sightless and for hearing-impaired people who need assistance while reading. 3.12 Sports buildings Sports halls should be as accessible as possible to a wheelchair user. At least one shower room, one rest room and one changing room per facility should be accessible to a wheelchair user. Spectators' seating areas should be provided for wheelchair users as specified (see table above). 3.13 Public transit buildings All public areas used by passengers such as banks,

shops, waiting areas, customs areas baggage halls, booking halls, waiting areas, inquiry offices, etc. should be accessible to a wheelchair user, wherever possible. In bus, air and sea terminals, adjoining spaces next to seating facilities should be provided for wheelchair users. 3.14 Industrial buildings Arrangements for disabled employees are directly related to the type of work they perform. Arrangements for disabled people need not be considered in heavy manufacturing factories. Arrangements for all disabled people should be incorporated into the design of new light manufacturing factories where disabled people may be employed. 4. EXISTING CONSTRUCTIONS The highest degree of accessibility to all people should be provided to the extent possible in accordance with the requirements mentioned above. For historic buildings, impossible to adapt to suit the requirements of disabled people without affecting the historical character, the challenge is to find alternative solutions or other innovative methods that do not conflict with preservation requirements. However, under all circumstances the character of a historical building should be preserved. Any modification that seriously harms its character, material, features or spaces is prohibited. Notes: (1) This figure is just a preliminary estimation based on a summary of suggested housing provisions by Selwyn Goldsmith in Designing for

the Disabled (p .418). It is up to every local authority to determine the exact number and the distribution of housing accommodations for disabled people, mainly those confined to a wheelchair, based on the needs of individual districts. (2) This figure is also a preliminary estimation based on the same source.

[_headerthemes.htm]

III. IMPLEMENTATION CHECKLISTS


Part 1/3 Text in italics refers to existing constructions only. Part 1 : Part 2 : Part 3

1. OBSTRUCTIONS
Question Can all protruding objects within the path of travel be detected by a sightless person with a cane? Possible solutions Remove or block out protruding parts. Place tactile markings in an area extending at least 0.60 m beyond the projection area of the obstruction. Construct a raised platform 0.10m high around the obstacle. Place an object, easily detectable with a cane, on the ground or floor beneath low-mounted overhanging obstructions. Mark obstructions at eye level with contrasting colour marking strips at least 0.30 m long in a contrasting colour.

Are all overhanging obstructions mounted at a minimum height of 2.00 m (1.95 m)?

Can all obstacles within the path of travel be easily identified by a person with partial sight?

2. SIGNAGE

Question Are accessible spaces identified by the international symbol of accessibility? Are there directional signs indicating the location of accessible facilities? Are maps, information panels and wall-mounted signs placed at a height between 0.90 m and 1.80 m.? Are signs clear, simple and easy to read?

Possible solutions Mark accessible spaces with the international symbol of accessibility. Provide directional signs.

Adjust the height of signs mounted too high or too low.

Colour engraved texts. Replace sign.

Is the colour of signs clearly distinguishable? Is the surface of the sign processed so as to prevent glare? Is the sign supplement by a text in embossed letters or in Braille available next to information signs? Is the lettering size proportional to the reading distance?

Use contrasting colours.

Provide a non-gloss surface.

Add a text in embossed letters or in Braille. Change the lettering size.

3. STREET FURNITURE
Question Does the location of street furniture obstruct the free passage of pedestrians? Possible solutions Change the location of street furniture. Mark the location of street furniture with tactile marking.

Resting facilities Are resting facilities provided at regular intervals?

Provide seating facilities at regular intervals between 100.00 m and

200.00m. Is there an adjoining space for a wheelchair next to benches and public seats? Are public seats between 0.45 m and 0.50 m high? Are the tops of tables between 0.75 m and 0.90 m high? Are knee spaces at accessible tables at least 0.70 m high, 0.85 m wide and 0.60 m deep? Public telephones Is there at least one telephone accessible to a wheelchair user? Is there at least one telephone equipped with hearing aids? Are the numerals on the telepone raised to allow identification by touch? Is the coin slot mounted at a maximum height of 1.20 m (1.40 m)? Are accessible facilities identified? Rearrange the layout of seats to allow an adjoining space of at least 1.20 m. Modify or replace seats and tables that are too low or too high.

Enlarge or adjust one telephone booth. Install volume controls and induction loops. Install push-buttons with raised numerals. Reduce the mounting height.

Add signage.

Mailboxes Are mail box slots mounted at a maximum height of 1.20 m (1.40 m)? Water fountains Are water fountain spouts mounted at an approximate height of 0.90 m? Are controls easy to operate with one closed fist?

Modify the height of the letter slot.

Modify the height of high drinking fountains. Install a double-tiered fountain. Replace controls.

4. PATHWAYS
Question Possible solutions

Is the pathway clear of obstructions?

Remove or relocate obstructions. Mark obstructions with tactile marking.

Is the path of travel free of steps or stairs?

Provide an alternative accessible pathway. Construct a ramp.

Is the path of travel easy to detect?

Continue natural guide lines. Construct guide strips. Provide a tactile marking area of at leat 0.90 m x 0.90 m at changes in the pathway direction Construct tactile marking to indicate the location of curb ramps, stairs, ramps and obstructions.

Is the pathway at least 0.90 m wide?

Widen the pathway. Remove obstructions and landscape features that limit the pathway width.

Is the surface, level, smooth and non-slip? Does the pathway have a different colour and texture than the adjacent surfaces?

Replace gravel paths with a surface of uniform texture. Repair holes and uneven paving. Apply textured rubber stick - on tiles to slippery paving.

Are manholes placed outside the pedestrian path of travel? Is grating flush with the surface of the pathway? Are the grating openings narrow, not more than 13 mm?

Relocate grating outside the path of travel. Make grating flush with the pathway surface. Replace gratings with wide opening patterns.

Are the edges of raised pathways protected? Are there barriers separating the pathway from planting areas, pools and other landscape features?

Construct guards with a minimum height of 0.15 m.

Are the plant varieties used obstructive to the pathway ? Are the plant varieties used harmful? Are the plant varieties used harmful to the surface of the pathway?

Replace plant varieties. Relocate plant varieties. Clean pathway surface constantly. Erect warning signs.

5. CURB RAMPS
Question Are curb ramps provided to overcome differences in level between the road surface and pathway level at: * Pedestrian crossings? * Drop-off zones? * Accessible parking spaces? * Building entrances? Are curb ramps located at each corner of each street intersection? Is every curb ramp faced by another curb ramp on the opposite side of the street? Are curb ramps easy to identify? Possible solutions Install curb ramps. Slope narrow pavements to street level.

Install curb ramps.

Apply a coloured texture to the surface of the curb ramp. Construct guide lines to direct pedestrians to the location of curb ramps. Widen pathway. Add a small built-up curb ramp.

Are curb ramps placed outside the usual line of pedestrian flow?

Is the maximum slope of a curb ramp 1:12 (1:10)?

Redesign or replace steep, unsafe curb ramps.

6. PEDESTRIAN CROSSINGS

Question Is the road surface even and slipresistant at pedestrian crossings? Is the road surface at pedestrian crossings easy to identify? Are pedestrian traffic lights installed? Do traffic lights have both audible and visual signals? Is the minimum time interval for crossing adapted to the slowest person? Are push-buttons located at a maximum height of 1.20 m? Do traffic islands have street-level pathways cut through them? Is the minimum width of the cut 1.50 m?

Possible solutions Add a slip-resistant surface.

Mark the pedestrian crossing area on the road surface with coloured stripes. Install traffic lights.

Provide both audible and visual traffic light signals. Delay the crossing time interval.

Install push-buttons at a maximum height of 1.20 m. Cut a level area, at least 1.50 m wide through traffic islands.

[_headerthemes.htm]

III. IMPLEMENTATION CHECKLISTS


Part 2/3 Text in italics refers to existing constructions only. Part 1 : Part 2 : Part 3

7. PARKING
Question Possible solutions

Are there accessible parking facilities? Is the number of accessible parking spaces sufficient? Are the designated spaces wide enough?

Re-strip to obtain the required number of spaces. Combine two parking spaces to obtain one accessible space. Combine three parking spaces to obtain two accessible spaces.

Are accessible indoor parking spaces located closest to accessible elevators or lifts? Are accessible parking spaces within 50.00 m of building entrances?

Locate accessible parking spaces close to accessible elevators. Construct accessible parking spaces close to the accessible entrance. Provide a drop-off zone near the accessible entrance. Modify the parking slab height. Provide alternate outdoor provisions for disabled peoples' vans.

Is the minimum height clearance in indoor parking 2.40 m?

Do curb ramps connect accessible parking spaces with side curbs? If there is no curbs, can the parking space be differentiated from the pedestrian path?

Construct curb ramps.

Provide a tactile marking at least 0.60 m wide to separate the pathway from the vehicular area. Use pre-cast wheel stops. Use bollards.

Are accessible parking spaces marked by the international symbol of accessibility? Are there enforcement procedures to ensure that accessible parking spaces are not misused or used by non-disabled people? Is there a 3.60 m wide drop-off area within 30.00 m of the accessible entrance? If the drop-off area has a curb, is there a curb ramp leading to the pathway? If the drop-off area has no curb, is there a warning to sightless

Add signage.

Provide a drop-off area.

Provide a curb-ramp.

Provide a tactile marking at least 0.60 m wide to separate the

people?

pathway from the vehicular area. Use pre-cast wheel stops. Use bollards.

Is the drop-off area marked by signage? Is there an accessible path of travel from the drop-off area to the main entrance?

Add signage.

Provide an accessible route. Use another entrance, accessible from the drop-off area.

8. RAMPS
Question Is there a complementary ramped route next to stairs or steps? Is the ramp slope no greater than 1:20? Do steeper ramps comply with requirements? Possible solutions Construct a ramp.

Redesign or relocate ramp. Lengthen ramp to reduce slope.

Is there a landing of at least 1.20 m length, at 10.00 m intervals, at every change in direction and at the top and bottom of every ramp? Are ramps with a rise of 0.45 m or more protected on both sides? Are wide ramps( more than 3.00 m) provided with an intermediate handrail? Is the width of the ramp at least 0.90 m? Is the surface of ramps non-slip?

Remodel or relocate the ramp.

Add railings.

Add an intermediate handrail where necessary. Widen the ramp.

Add non-slip surface material.

Is the ramp surface clear of obstructions? Is the location of the ramp clearly identifiable

Remove obstructions.

Construct coloured tactile marking strips at least 0.60 m wide at the top and bottom of the landing and at every change of direction.

9. ELEVATORS
Question Is there an accessible path leading to the elevator? Are all levels generally used by the public accessible? Possible solutions Add a ramp or a platform lift if stairs exist.

Are the minimum internal dimensions of a residential elevator cab no less than 1.00 m x 1.30 m.(0.95 m x 1.25 m)?

Enlarge the elevator dimensions. Install a new cab.

Is the clear door opening no less than 0.80 m (0.75 m)?

Enlarge the door opening. Install new doors.

Is the elevator cab provided with handrails on three sides? Are the handrails mounted at a height between 0.80 m and 0.85 m? Is the maximum tolerance for stop precision 20 mm? Is the control panel mounted at a height between 0.90 m and 1.20 m (not exceeding 1.40 m)? Are control buttons large and provided with embossed numerals?

Install handrails.

Modify height of handrails.

Adjust the stop precision.

Modify the height of control panels.

Change control panel. Install tactile or Braille numerals next to buttons.

Are lobby call buttons placed at a height between 0.90 m and 1.20 m (not exceeding 1.40 m)? Is the elevator provided with audible and visual warning signals indicating arrival at a floor? Is the finish of the elevator cab non skid-resistant? Is the elevator door easy to identify?

Adjust the position of call buttons.

Add bells and flashing light signals.

Change finish.

Change the colour of the elevator door frame. Replace the communication system. Add simple tactile instructions.

Is the emergency intercom usable without voice communication? Are there tactile or Braille instructions for the communication system? Is the door opening/closing interval long enough? Is there a sign on the jamb of the elevator door identifying the floor number in raised or Braille letters?

Install devices to delay the motion of the door. Install tactile signs at an approximate height of 1.40 m from the floor to identify the floor number.

10. PLATFORM LIFTS


Question Can the lift be used without assistance? Possible solutions Post clear instructions for use of the lift at each stopping level. Provide a call button.

When vertical movement platform lifts are installed, is the maximum level change 2.50 m? Is the lift placed within a closed structure for level changes of 1.20 m or more? Where inclined movement platform lifts are installed, is the minimum

Replace the special platform lift with an elevator. Place the lift within an enclosed structure. Widen the stairs.

width of the stairs 0.90 m? Is the minimum lift size 0.90 m x 1.20 m? Are controls placed at a height not exceeding 1.20 m (1.40 m)? Replace the lift.

Lower the controls.

11. STAIRS
Question Is the minimum width of the stairs 0.90 m? Is an intermediate handrail installed for stairs 3.00 m wide or more? Is there an intermediate landing with a length no less than 1.20 m, when the stairs cover a difference in level of more than 2.50 m? Is the landing length at the top and at bottom of the stairs no less than 1.20 m? Do stairs have flush or rounded nosing? Possible solutions Widen the stairs.

Install an intermediate handrail, where necessary. Remodel the stairs.

Enlarge the landing space.

Remodel nosing. Add slip-resistant strips to nosing.

Do treads have a non-slip surface?

Change finish material.

Is the location of the stairs clearly identifiable?

Construct coloured tactile marking strips at least 0.60 m wide, at the top and bottom of the stairs and intermediate landings of each stairs. Identify emergency stairs with signage.

12. RAILINGS AND HANDRAILS

Question Are safety guards or railings installed around all hazardous areas and raised platforms more than 0.40 m high? Is the spacing between the vertical and horizontal elements of railing around dangerous areas narrow? Are handrails mounted at a height between 0.85 m and 0.90 m? Are handrails easy to grip?

Possible solutions Install safety guards or railings.

Change railings.

Change handrails.

Are railings securely attached?

Reinforce the fixtures.

Do handrails extend horizontally between 0.30 m and 0.45 m at the top and bottom of every staircase or ramp? Are handrails continuous throughout the full length of ramps and stairs? Are handrails continuous throughout the landing of ramps and stairs except when interrupted by doorways? Are low positioned windows at landings protected by railings? Is the space between the handrail and the wall no less than 40 mm for smooth walls, and 60 mm for rough textured walls? For fully recessed handrails, is the distance between the top of the rail and the top of the recess no less than 0.15 m? Are handrails easy to identify?

Add or replace railings.

Continue or replace handrails.

Install railings.

Adjust the location of the handrail.

Paint the handrail in a contrasting colour. Provide a tactile strip indication for emergency stairs.

[_headerthemes.htm]

III. IMPLEMENTATION CHECKLISTS


Part 3/3 Text in italics refers to existing constructions only. Part 1 : Part 2 : Part 3

13. ENTRANCES
Question Are the primary entrances to buildings accessible? Is the approach to the entrance free of stairs and steps? In multi-storey buildings, does the accessible entrance permit access to a conveniently located elevator? Is the accessible entrance clearly identifiable? Possible solutions Redesign the entrance so that it will be accessible. Construct a ramp.

Provide an accessible route.

Add the international symbol of accessibility. Paint the entrance door with a colour that will contrast with the surrounding surface. Enlarge the landing area.

Are the entrance landing dimensions sufficient? Is the landing surface level and nonslippery? Can entrance doors operate independently?

Add a slip-resistant finish.

Install a lighter door. Change the door opening mechanism.

Is the clear door width at least 0.90 m?

Enlarge the door opening. Install automatic sliding doors. Use swing clear hinge doors.

14. VESTIBULES
Question Is there enough space to maneuver between two sets of doors? Possible solutions Enlarge the vestibule space. Install automatic sliding doors. n Install double-swinging doors. Remove the inside or second set of doors. Change the direction of the swing of the door.

15. DOORS
Question Can doors be opened without much effort? Possible solutions Install lighter doors. Install power-assisted door openers.

Do automatic doors have a sufficiently long opening interval? Are push-buttons for automatic doors located at a maximum height of 1.20 m (not exceeding 1.40 m)? Is there sufficient space beside the latch side of the door?

Adjust the opening interval.

Lower the height of buttons.

Move the door. Move or remove obstructing partitioning.

Are accessible doors placed adjacent to revolving doors and turnstiles?

Install adjacent sliding or pivoting doors.

Are glazed doors marked with a coloured band at eye level? Is the clear width of straight access interior doors at least 0.75 m? Is the minimum clear width of interior doors at least 0.80 m? For double leaf doors, is the width of one of the leaves at least 0.80 m? Do door handles have a shape that is easy to grasp with one hand?

Add a coloured band.

Enlarge door opening. Install offset or swing clear hinges.

Install lever-type handles easy to operate with a closed fist. Install power-assisted door openers.

Do bathrooms doors and doors fitted with spring closers have an extra pull handle? Is manual door hardware (handles, locks, pulls, etc.) located no higher than 1.20 m (not exceeding 1.40 m)? Are door mats flush with the floor surface and secured to the floor at all edges?

Install an extra pull handle.

Adjust the height of the door hardware.

Replace or remove mats. Secure mats at edges.

Is the threshold no more than 20 mm high and beveled?

Remove high thresholds. Bevel both sides.

16. CORRIDORS
Question Is the minimum unobstructed width of low traffic corridors no less than 0.90 m? Is the unobstructed width of a public corridor no less than 1.50 m? Possible solutions Widen the corridor. Locate passing areas at frequent intervals.

Does the corridor width allow maneuvring through doors located along its length?

Change the direction of the door swing. Widen the corridor. Remove door if possible.

Are differences in level bridged by ramps or lifts?

Install a lift. Construct a ramp.

17. REST ROOMS


Question Public rest rooms Is there at least one unisex rest room accessible to a wheelchair user? Possible solutions

Reconfigure rest rooms. Combine two water-closet stalls to create one unisex accessible rest room. Widen toilet stalls by moving one of the side partitions and/or installing outward-swinging door. Place the international symbol of accessibility.

Is the accessible rest room identified by a sign? Residential rest rooms Is there sufficient space inside the rest room to maneuver a wheelchair? Is there at least one accessible shower and/or bath-tub?

Enlarge rest room space.

Reconfigure shower stalls. Enlarge rest room. Use the tiled floor area inside the rest room as a shower space.

Fixtures Are water-closets and bidets mounted at a height between 0.45 m and 0.50 m?

Adjust the height of wall mounted fixtures. Replace low floor mounted fixtures.

Is the distance between the toilet seat and the closest adjacent wall fitted with a grab bar between 0.45 and 0.50 m?

Adjust the location of fixtures. Install floor-mounted grab bars.

Is the accessible wash-basin mounted at a height between 0.80 m and 0.85 m?

Adjust the height of wall-mounted fixtures. Replace floor-mounted fixtures.

Are the accessible shower and the bath-tub provided with folding seats ?

Install a shower seat at a height between 0.45 m and 0.50 m. Adjust the height of seats.

Is the floor of the tub slip-resistant?

Change the finish material. Install a slip-resistant rubber mat.

Does the shower tub have a beveled threshold not exceeding 13 mm above the finished floor? Is the shower tub floor no lower than 20 m below the surrounding floor area? Are grab bars installed in water closets, bath tubs and showers at a height between 0.85 m and 0.95 m? Do grab bars have a diameter between 30 mm and 40 mm? Do wall mounted grab bars have a clearance between 35 mm and 40 mm? Are grab bars non slip?

Modify the shower tub.

Install grab bars. Adjust mounting height.

Replace grab bars. Add a knurled slip-resistant surface.

Can grab bars withstand loads?

Reinforce walls on which grab bars are installed. Replace faucets with single lever or push-button type.

Faucets Are faucets easy to grip and

operate with one hand? Are telephone like shower fixtures with at least 1.50 m long hoses used in showers and bath tubs? Pipes Are hot water pipes insulated or covered? Accessories and controls Is the lower edge of mirrors positioned at a height not exceeding 1.00 m? Replace hose.

Insulate or cover hot water pipes.

Lower or tilt high mirrors. Install another mirror on another wall.

Is the rest room equipped with an alarm system? Are flushing arrangements, dispensers and toilet paper mounted between 0.50 m and 1.20 m? Are flushing mechanisms easy to operate? Flooring Is the flooring material skid-proof, well drained and waterproofed? Doors Is the door opening at least 0.75 m?

Install an alarm that can be set off by a push-button located at a maximum height of 1.20 m. Adjust the height of too high and too low fixtures.

Change the flushing mechanism.

Change flooring material.

Enlarge the door opening. Remove doors if privacy is not diminished.

Can doors be lockable from inside and releasable from outside under emergency situations? Do pivoted doors open outward?

Adjust door lock mechanism.

Change the direction of the swing of the door. Previous : Next

[_headerthemes.htm]

V. IMPLEMENTATION CHECKLISTS TROUBLESHOOTING 1. Wheelchair users


Problem Overcoming differences in level between road and pavement Bridging great differences in height usually tackled by providing stairs Maneuvering in tight spaces Measure Install curb ramps

Provide ramps, wide elevator cabs or platform lifts Provide wide routes and spaces

Passing through narrow door openings and over high thresholds Reaching high-mounted controls and objects Maneuvering in rest rooms

Provide sufficiently wide door openings with low beveled thresholds or none at all Provide low-mounted controls

Install grab bars, bath-tub and shower seats

2. People with limited walking abilities


Problem Overcoming differences in level Measure Provide curb ramps, ramps, elevators or platform lifts Increase the pedestrian crossing

Maneuvering in situations requiring

speed

time interval Increase the opening interval of elevators and automatic doors

Climbing stairs and ramps

Provide handrails for gripping

Maneuvering in rest rooms

Provide sufficiently wide rest rooms Provide grab bars, bath-tub and a shower seat

Passing through narrow door openings and over high thresholds

Provide sufficiently wide door openings with low beveled thresholds or none at all

3. People with limited use of hands or arms


Problem Opening heavy doors Measure Use automatic or easy-to-open doors Use lever-type door handles

Gripping door knobs

Gripping faucets

Use lever-type or push-buttons faucets

4. The sightless
Problem Orientation Measure Provide guide strips within the pathway surface Provide raised curbs and other detectable guiding elements Provide tactile marking strips to indicate changes in direction and the location of stairs and ramps

Identifying obstructions within the path of travel Crossing roads

Provide textured paving or tactile marking strips around obstructions Provide audible traffic signals

Maneuvering in elevators

Provide audible signals and call buttons with tactile text Provide audible alarm signals

Recognizing emergency situations

Locating exit doors and stairs

Provide tactile marking around the knobs of exit doors and the handrails of exit

5. The partially sighted


Problem Identifying obstructions within the path of travel Orientation Measure Provide bright-coloured markings or signals to identify obstructions Provide clearly legible lettering and sufficiently large dimensions for direction signs Provide audible traffic signals

Crossing roads

Maneuvering in elevators and in emergency situations Locating facilities

Use contrasting colour for doors, handrails, tactile signs, etc Provide alarm signals

6. The hearing impaired


Problem Crossing roads Measure Provide clearly visible coloured

signs and traffic signals Managing in situations involving the use of speech messages, verbal transmission and interaction Not hearing door, elevator and emergency Use clearly written messages, especially in emergency situations Install induction loops in assembly halls and in public telephones Provide flashing light signals

[_headerthemes.htm]

V. IMPLEMENTATION CHECKLISTS ANTHROPOMETRICS (part 1 of 2)


Dimensional data varies from one person to another, and the average dimensions vary from one country to another. The dimensions of the individual human being vary with time. The tables below provide a range of dimensions derived from various studies (see Comparative Tables). The given measurements take into consideration size variation between males and females as well as between different persons of the same sex. Wheelchair Dimensions (fig.1) Dimensions shown in the figure are of a conventional manual wheelchair. The larger, encircled dimensions refer to electric wheelchairs.

Wheelchair dimensions.

Wheelchair dimensions.

Fig.1

Dimensional data to a normal person (fig. 2) Fig. 2

Height Eye Shoulder

1.50 m 1.90 m 1.40 m 1.75 m 1.20 m 1.55 m

Dimensional data of a wheelchair user

Fig. 3

Dimensional data of a wheelchair user.

Reaching zones of a normal person (fig. 4)

Max. Reach Up Oblique Reach Up Forward Reach

1.85 m 2.10 m 1.65 m 2.00 m 1.30 m 1.45 m

Fig. 4

Vertical reaching zones of a wheelchair user

Vertical reaching zones of a wheelchair user

Fig. 5

Horizontal forward reach of a wheelchair user (fig. 6) Fig. 6 Eye Shoulder 1.16 m 1.33 m 0.99 m 1.14 m

Common reaching zone Common reaching zone

Fig. 7

[_headerthemes.htm]

V. IMPLEMENTATION CHECKLISTS ANTHROPOMETRICS (part 2 of 2)

Field of Vision

5-02-01.gif (16743 bytes)

Fig.8

Pathway dimensions

Visually impaired person using a long white cane.

Person using a cane

Persons using crutches

Detectable path dimension

Fig. 9 Wheelchair maneuvering space

Fig. 10

Wheelchair maneuvering space dimensions

Maneuvering at doors

Fig 11.

Maneuvering at doors. 1.50-1.80 m allowance.

[_headerthemes.htm] [_headerthemes.htm] [_headerthemes.htm]

REFERENCES
"Accessibility in Public Accommodations". 581: Readily Achievable Checklist .ADA Compliance Guide, USA, Thompson Publishing Group, December 1991. pp. 113-119.

Adaptive Environments Center, Inc., Access Boston. Boston Redevelopment Authority, 1990. 42 pages. Adaptive Environments Center, Inc. and Barrier Free Environments, Inc., "The Americans with Disabilities Act Checklist for Readibly Achievable Barrier Removal." USA, 31 March 1992. 12 pages. American National Standards Institute. American National Standard for Buildings and Facilities: Providing Accessibility and Usability for Physically Handicapped People. New York, 1986. 84 pages. Beckman, Mats. Building for Everyone. Stockholm, Ministry of Housing and Physical Planning, 1976. 108 pages. The Canadian Paraplegic Association, Manitoba Division. Access: A Guide for Architects and Designers. Second Edition, Manitoba, Canada, the Canadian Paraplegic Association, Manitoba Division, 1989. Central Coordinating Committee for the Promotion of Accessibility for the Disabled (CCPT). Accessibility of Buildings and the Outdoor Environment. Delft, Dutch Standard Institute, 1988. 67 pages. Dansk Ingenirforning (Danish Engineering Association) Planning of Open Spaces as regards Access for Disabled People. Translated by Eva Eriksen, Copenhagen, Forlag Normstyrelsen Publicationer, 1984. 51 pages. Denmark. Ministry of Housing, Circular No.49 of 23 MARCH 1972. 6 pages. Goldsmith, Selwyn, Designing for the Disabled. Third Edition. London, RIBA Publications Ltd, 1976. 525 pages. Grosbois, Louis- Pierre. Handicap Physique et Construction. Third Edition. Paris: Le Moniteur, 1991. 327 pages. The Housing Committee for the Handicapped (NKB). "Accessibility of Buildings to Handicapped Persons: Guidlines for Nordic Building Regulation" (preliminary draft). Copenhagen, 1973. 14 pages. _____. "Bathrooms and Toilets for Everybody". Copenhagen, 1974. 5 pages. _____. "Dwelling for Everybody". Copenhagen, 1974. 5 pages. Netherlands. Ministry of Transport and Public Works. Manual Traffic Provisions for people with a Handicap. The Hague, 1986. 138 pages. Park, Sharon C. and Thomas C Jester "Strategies for Making Historic Properties Accessible to Persons with Disabilities". United States National Park Service, Preservation Assistance Division. 6 pages. The Swedish International Development Authority (SIDA) in collaboration with the United Nations and Habitat. Designing with Care: A guide to Adaptation of the built Environment for Disabled People. United Nations, International year of Disabled Persons (IYDP) 1981. 102 pages. The Research & Training Center of Independent Living. Guidelines for Reporting and Writing About People With Disabilities. Third Edition.

Lawrence, Kansas, USA, 1990. 4 pages.

ACKNOWLEDGMENTS
This manual has been prepared by SOLIDERE in collaboration with ESCWA and with the approval of the Ministry of Social Affairs and the National Committee for the Disabled.

RIAD TAPPUNI ESCWA expert

MONA KHECHEN Research and text preparation

KHALED AL-AZHARI ISMAIL ALTAWIL Autocad illustration

ORESTES PLASENCIA (ESCWA) Editing

LORI SATRISI (ESCWA) Proofreading

Saudi Arabia Research Institute (SARI) Arabic translation

The Communications DivisionSOLIDERE Production

You might also like