You are on page 1of 55

[active thermal envelope]version 5.

0
columbia building intelligence project - integrated design studio - spring 2012

KARL H. BENGZON COLUMBIA BUILDING INTELLIGENCE PROJECT INTEGRATED DESIGN STUDIO - COLUMBIA GSAPP SPRING 2012

[active thermal envelope] version 5.0

current building practice:

statement:
Current building envelope design is thermally inefficient, fractured into several layers. Perimeter heat gain/loss add significant loads to the mechanical system which must then be over-designed to compensate for this inefficiency. This increases the size/cost of the mechanical system and adds cost to the buildings operation and maintenance during its lifetime. A simpler, cheaper, and more thermally effective envelope may be obtained by combining the enclosure with a radiant heating system into a single layer, creating a heat exchange-relation between the envelope and the occupants. In order to test this hypothesis, the following process-design is used to measure the proposed assembly. By measuring its value within the domains of aesthetics, structural performance, mechanical performance, material cost and profit, one is able to obtain a qualitative and quantitative understanding of the many design permutations that the system can generate.

cooling s/r

heating s/r

ventilation s/r

exteriors/ cladding

airspace/ vapor barrier

exterior sheathing

masonry or stud backup

interior finishes

EXTERIOR

INTERIOR

KARL H. BENGZON COLUMBIA BUILDING INTELLIGENCE PROJECT INTEGRATED DESIGN STUDIO - COLUMBIA GSAPP SPRING 2012

[active thermal envelope] version 5.0

radiant curtain wall:

statement:
Current building envelope design is thermally inefficient, fractured into several layers. Perimeter heat gain/loss add significant loads to the mechanical system which must then be over-designed to compensate for this inefficiency. This increases the size/cost of the mechanical system and adds cost to the buildings operation and maintenance during its lifetime. A simpler, cheaper, and more thermally effective envelope may be obtained by combining the enclosure with a radiant heating system into a single layer, creating a heat exchange-relation between the envelope and the occupants. In order to test this hypothesis, the following process-design is used to measure the proposed assembly. By measuring its value within the domains of aesthetics, structural performance, mechanical performance, material cost and profit, one is able to obtain a qualitative and quantitative understanding of the many design permutations that the system can generate.

exteriors/ cladding + airspace/ vapor barrier + interior finish

chilled / heated water supply

ventilation s/r

EXTERIOR

INTERIOR

summer

heat radiates from the warmer body to the cooler body

winter

water return

KARL H. BENGZON COLUMBIA BUILDING INTELLIGENCE PROJECT INTEGRATED DESIGN STUDIO - COLUMBIA GSAPP SPRING 2012

[active thermal envelope] version 5.0

radiant curtain wall:

statement:
Current building envelope design is thermally inefficient, fractured into several layers. Perimeter heat gain/loss add significant loads to the mechanical system which must then be over-designed to compensate for this inefficiency. This increases the size/cost of the mechanical system and adds cost to the buildings operation and maintenance during its lifetime. A simpler, cheaper, and more thermally effective envelope may be obtained by combining the enclosure with a radiant heating system into a single layer, creating a heat exchange-relation between the envelope and the occupants. In order to test this hypothesis, the following process-design is used to measure the proposed assembly. By measuring its value within the domains of aesthetics, structural performance, mechanical performance, material cost and profit, one is able to obtain a qualitative and quantitative understanding of the many design permutations that the system can generate.

exteriors/ cladding + airspace/ vapor barrier + interior finish

chilled / heated water supply

ventilation s/r

design scorecard:
EXTERIOR INTERIOR

aesthetics

summer
heat input
heat radiates from the warmer body to the cooler body

profit from new sf

evaluation of system

winter
radiative heat transfer

material cost
water return

structural performance

KARL H. BENGZON COLUMBIA BUILDING INTELLIGENCE PROJECT INTEGRATED DESIGN STUDIO - COLUMBIA GSAPP SPRING 2012

[active thermal envelope] version 5.0

general process design map:

statement:
Current building envelope design is thermally inefficient, fractured into several layers. Perimeter heat gain/loss add significant loads to the mechanical system which must then be over-designed to compensate for this inefficiency. This increases the size/cost of the mechanical system and adds cost to the buildings operation and maintenance during its lifetime. A simpler, cheaper, and more thermally effective envelope may be obtained by combining the enclosure with a radiant heating system into a single layer, creating a heat exchange-relation between the envelope and the occupants.

INPUTS

RADIANT CURTAIN WALL

OUTPUTS

EVALUATION

QUALITATIVE + QUANTITATIVE INPUTS

SYSTEM QUALITATIVE OUTPUTS

In order to test this hypothesis, the following process-design is used to measure the proposed assembly. By measuring its value within the domains of aesthetics, structural performance, mechanical performance, material cost and profit, one is able to obtain a qualitative and quantitative understanding of the many design permutations that the system can generate.
process design map version 3.0
DESIGN PERMUATATION SCORECARD
user inputs surface area required code + radiant heat info excel data geometric output design iterations output data to inform next iteration?

MATERIAL PROPERTIES

SYSTEM MATERIAL PROPERTIES OUTPUTS

EF 3: LIMIT HEAT LOSS THROUGH EXTERIOR WALLS

EF 4: PROMOTE SUPER-INSULATED EXTERIOR WALLS

EF 3: LIMIT HEAT LOSS THROUGH EXTERIOR WALLS


ANSI/ASHRAE/IESNA 90.1 (2007) and the Energy Conservation Construction Code of New York State Proposal developed by Energy & Ventilation Committee

EF 4: PROMOTE SUPER-INSULATED EXTERIOR WALLS


Zoning Resolution of the City of New York Proposal developed by the Energy & Ventilation Committee

Summary
Issue: Building envelope design has a major impact on both heat loss in winter and solar gain in summer. Using the flexibility in current energy codes, designers can meet energy-efficiency requirements by trading off the efficiency of mechanical and lighting equipment against the thermal integrity of the envelope. Since the building envelope will be in use for a century or more, this trade-off is short-sighted. Recommendation: Establish fixed performance requirements for building envelopes with respect to heat loss, independent of mechanical and lighting equipment choices.

Summary
Issue: The Citys definition of floor area, which determines how large a building can be, includes exterior wall thickness. This penalizes thick, energy-efficient walls, and rewards poorly insulated thin-wall construction. Recommendation: For super-insulated walls, exclude up to eight inches of the exterior wall thickness from the floor area calculation.

DESIGN PERMUATATION
ENVIRONMENTAL INPUTS SYSTEM QUANTITATIVE OUTPUTS

Proposed Legislation, Rule or Study


Amendments to ANSI/ASHRAE/IESNA 90.1 (2007), as incorporated in Chapter 13 of the New York City Building Code: 1. Add a new Section 5.4.4 as follows: 5.4.4 Maximum Exterior Building Envelope Heat Transfer. 5.4.4.1 Exterior building envelopes shall comply either with the prescriptive option of subsection 5.4.4.2 or the performance option of subsection 5.4.4.3 notwithstanding whether the overall building design complies with the requirements of the Energy Cost Budget Method of Section 11. In addition to the foregoing, if the energy cost budget trade off option as set forth in Section 11 is chosen as a compliance path and requires a lower average U-factor than .25 Btu/hr-sf-oF, then that lower value must be utilized in the proposed design. Exception: Any building with a peak design rate of energy usage less than 3.4 Btu/hr-sf or 1.0 watt/sf of floor area for space conditioning purposes. 5.4.4.2 Exterior building envelopes excluding the roof but including skylight area in excess of 5% of roof area shall have a maximum average U-factor of 0.25 Btu/hr-sf-oF for buildings receiving permits before July 1, 2016, 0.20 Btu/hr-sf-oF o for buildings receiving permits after July 1, 2016 but before July 1, 2022, or 0.16 Btu/hr-sf- F for buildings receiving permits after July 1, 2022, notwithstanding whether the exterior building envelope has a sufficiently high envelope performance factor as set forth in Section 5.6, except as permitted in subsection 5.4.4.3 The maximum average Ufactor shall be calculated by averaging the U-factor of each component of the exterior building envelope excluding roof but including skylights over the entire above-ground wall and fenestration areas that enclose heated spaces but excluding semiheated spaces. The average U-factor shall be calculated as follows: Average U-factor = UAref/Atotal = (UA1 + UA2 + . . . UAn) / Atotal where UA = the U-factor for each individual exterior building envelope component excluding the roof but including skylights (except those over semiheated spaces) multiplied by the total area of such component incorporated in the exterior building envelope. The U-factor for each component shall be calculated by taking into account thermal bridging at metal studs and members, shelf angles, floor edges, projecting balconies, window frames, and other components passing through the thermal barrier. U-factors can be determined using test results as required by this standard, tabulations provided by this standard, Standard NFRC-100-2004 methods, or two-dimensional or three-dimensional heat flow modeling, provided that three-dimensional heat flow modeling shall not be used to determine the U-value for standard wall-types listed in the above referenced tables. For residential construction with exposed slab edges, the following table must be used for U-factors.

Proposed Legislation, Rule or Study


Amendments to Zoning Resolution of the City of New York 1. Amend Section 12-10 to add the following definition: Exterior Building Envelope: the elements of a building that separate conditioned spaces from the exterior; Definition of Roof; the upper portion of the building envelope, including opaque areas and fenestration, that is horizontal or tilted at an angle of less than 60o from the horizontal; Definition of Skylight: a fenestration surface having a slope of less than 60o from the horizontal plane. (All definitions from ASHRAEA 90.1, 2007) 2. Amend Section 12-10 as follows: However the floor area of a building shall not include: <Add the following to the list> (12) Floor area used to add thermal insulation to the exterior of an existing building or to super-insulate a new building, subject to the following: (i) In buildings constructed or permitted prior to July 1, 2011, the exempted floor area is the thickness of the insulated wall assembly added to the existing exterior side wall, rear wall, or rear wall equivalent, limited to a maximum of 8" added to any wall, and provided that the added insulated wall assembly achieves a minimum R-value of 3.5 times its thickness in inches, the windows achieve a minimum of R-3.5, and within the walls being insulated, the window area does not exceed 50% of the wall area. (ii) In buildings or additions permitted after July 1, 2011, the exempted floor area is up to 8 of exterior wall thickness in excess of 8 thickness (i.e. for exterior wall thickness between 8 and 16), measured at a point 30 above the finished floor, provided that the thermal performance of the building envelope meets the minimum prescriptive or performance requirements listed below, that the total exempted floor area does not exceed 5% of the allowable floor area, and that the building implement measurement and verification protocols to determine whether the envelope is performing as predicted with respect to thermal transmission. The minimum prescriptive requirement is that average U-value of the exterior building envelope excluding roof but including skylights is less than .75 the average U-value allowed by the New York City Energy Conservation Code. The minimum performance requirement is that on an annual basis the modeled envelope must perform better than or equal to an envelope where average U-value of the exterior building envelope excluding roof but including skylight area in excess of 5% of roof area is less than .70 the average U-value allowed by the New York City Energy Conservation Code and the vision glass has a SHGC of less than 0.4; but in no case can the average U-value of the exterior building envelope excluding roof but including skylight area in excess of 5% of roof area be greater than the average U-value allowed by the New York City Energy Conservation Code. (iii) The calculation of R-values, the average U-value, and any modeling shall be as per the requirements of the New York City Energy Conservation Code and submitted to the Department of Buildings. URBAN GREEN NYC GREEN CODES TASK FORCE: FULL PROPOSALS EF 4 1

output parameters surface area volume of concrete solid / void ratio square footage gained

URBAN GREEN

NYC GREEN CODES TASK FORCE: FULL PROPOSAL

EF 3

output data to drive other elements? user design input parameters amount of heat to radiate geometric inputs evaluation metrics design scorecard material costs

process design map version 1.0


FINANCIAL INPUTS SYSTEM FINANCIAL OUTPUTS

KARL H. BENGZON COLUMBIA BUILDING INTELLIGENCE PROJECT INTEGRATED DESIGN STUDIO - COLUMBIA GSAPP SPRING 2012

precedent studies + design phase

00

KARL H. BENGZON COLUMBIA BUILDING INTELLIGENCE PROJECT INTEGRATED DESIGN STUDIO - COLUMBIA GSAPP SPRING 2012

[active thermal envelope] version 5.0


precedent studies + research
EF 3: LIMIT HEAT LOSS THROUGH EXTERIOR WALLS

SANAA - zolleverin management school

EF 3: LIMIT HEAT LOSS THROUGH EXTERIOR WALLS


ANSI/ASHRAE/IESNA 90.1 (2007) and the Energy Conservation Construction Code of New York State Proposal developed by Energy & Ventilation Committee

Summary
Issue: Building envelope design has a major impact on both heat loss in winter and solar gain in summer. Using the flexibility in current energy codes, designers can meet energy-efficiency requirements by trading off the efficiency of mechanical and lighting equipment against the thermal integrity of the envelope. Since the building envelope will be in use for a century or more, this trade-off is short-sighted. Recommendation: Establish fixed performance requirements for building envelopes with respect to heat loss, independent of mechanical and lighting equipment choices.

Proposed Legislation, Rule or Study


Amendments to ANSI/ASHRAE/IESNA 90.1 (2007), as incorporated in Chapter 13 of the New York City Building Code: 1. Add a new Section 5.4.4 as follows: 5.4.4 Maximum Exterior Building Envelope Heat Transfer. 5.4.4.1 Exterior building envelopes shall comply either with the prescriptive option of subsection 5.4.4.2 or the performance option of subsection 5.4.4.3 notwithstanding whether the overall building design complies with the requirements of the Energy Cost Budget Method of Section 11. In addition to the foregoing, if the energy cost budget trade off option as set forth in Section 11 is chosen as a compliance path and requires a lower average U-factor than .25 o Btu/hr-sf- F, then that lower value must be utilized in the proposed design. Exception: Any building with a peak design rate of energy usage less than 3.4 Btu/hr-sf or 1.0 watt/sf of floor area for space conditioning purposes. 5.4.4.2 Exterior building envelopes excluding the roof but including skylight area in excess of 5% of roof area shall have o o a maximum average U-factor of 0.25 Btu/hr-sf- F for buildings receiving permits before July 1, 2016, 0.20 Btu/hr-sf- F for buildings receiving permits after July 1, 2016 but before July 1, 2022, or 0.16 Btu/hr-sf-oF for buildings receiving permits after July 1, 2022, notwithstanding whether the exterior building envelope has a sufficiently high envelope performance factor as set forth in Section 5.6, except as permitted in subsection 5.4.4.3 The maximum average Ufactor shall be calculated by averaging the U-factor of each component of the exterior building envelope excluding roof but including skylights over the entire above-ground wall and fenestration areas that enclose heated spaces but excluding semiheated spaces. The average U-factor shall be calculated as follows: Average U-factor = UAref/Atotal = (UA1 + UA2 + . . . UAn) / Atotal where

plaNYC 2030 + greencodes

UA =

the U-factor for each individual exterior building envelope component excluding the roof but including skylights (except those over semiheated spaces) multiplied by the total area of such component incorporated in the exterior building envelope. The U-factor for each component shall be calculated by taking into account thermal bridging at metal studs and members, shelf angles, floor edges, projecting balconies, window frames, and other components passing through the thermal barrier. U-factors can be determined using test results as required by this standard, tabulations provided by this standard, Standard NFRC-100-2004 methods, or two-dimensional or three-dimensional heat flow modeling, provided that three-dimensional heat flow modeling shall not be used to determine the U-value for standard wall-types listed in the above referenced tables. For residential construction with exposed slab edges, the following table must be used for U-factors.

URBAN GREEN

NYC GREEN CODES TASK FORCE: FULL PROPOSAL

EF 3

reiser + umemoto O-14 building

thermally active surfaces in architecture by kiel moe

KARL H. BENGZON COLUMBIA BUILDING INTELLIGENCE PROJECT INTEGRATED DESIGN STUDIO - COLUMBIA GSAPP SPRING 2012

[active thermal envelope] version 5.0

allied works - clyfford still museum

erwin hauer

system application sketches

concept sketches

CATIA workshop

CATIA workshop

KARL H. BENGZON COLUMBIA BUILDING INTELLIGENCE PROJECT INTEGRATED DESIGN STUDIO - COLUMBIA GSAPP SPRING 2012

[active thermal envelope] version 5.0

version 1.0

version 2.0

version 3.0

early development sketches v1.0 - v3.0 version 5.0

KARL H. BENGZON COLUMBIA BUILDING INTELLIGENCE PROJECT INTEGRATED DESIGN STUDIO - COLUMBIA GSAPP SPRING 2012

[active thermal envelope] version 5.0

udf instantiation - version 5.0:

v50kb2543ActiveThermalEnvelopePC03

kb2543XshapeUDF06

KARL H. BENGZON COLUMBIA BUILDING INTELLIGENCE PROJECT INTEGRATED DESIGN STUDIO - COLUMBIA GSAPP SPRING 2012

[active thermal envelope] version 5.0

active thermal envelope - version 5.0:

typical floor existing slab

typical floor existing slab

KARL H. BENGZON COLUMBIA BUILDING INTELLIGENCE PROJECT INTEGRATED DESIGN STUDIO - COLUMBIA GSAPP SPRING 2012

[active thermal envelope] version 5.0


water storage location

heating riser diagram:


earth air water tower courtney hunt - CBIP 2012

solar hot water heater gravity-fed hot water distribution

window water chamber heidi werner - CBIP 2012 solar ivy ben brennan - CBIP 2012

heat radiates from the warmer body to the cooler body

pump water up to roof storage location for re-use

pump water up to greywater system

KARL H. BENGZON COLUMBIA BUILDING INTELLIGENCE PROJECT INTEGRATED DESIGN STUDIO - COLUMBIA GSAPP SPRING 2012

[active thermal envelope] version 5.0


water storage location

cooling riser diagram:


earth air water tower courtney hunt - CBIP 2012

solar hot water heater gravity-fed hot water distribution

window water chamber heidi werner - CBIP 2012 solar ivy ben brennan - CBIP 2012

heat radiates from the warmer body to the cooler body

pump water up to roof storage location for re-use

pump water up to greywater system

KARL H. BENGZON COLUMBIA BUILDING INTELLIGENCE PROJECT INTEGRATED DESIGN STUDIO - COLUMBIA GSAPP SPRING 2012

process design map

01

KARL H. BENGZON COLUMBIA BUILDING INTELLIGENCE PROJECT INTEGRATED DESIGN STUDIO - COLUMBIA GSAPP SPRING 2012

[active thermal envelope] version 5.0

INPUTS

RADIANT CURTAIN WALL

OUTPUTS

EVALUATION

QUALITATIVE + QUANTITATIVE INPUTS

SYSTEM QUALITATIVE OUTPUTS

MATERIAL PROPERTIES

SYSTEM MATERIAL PROPERTIES OUTPUTS

DESIGN PERMUATATION
ENVIRONMENTAL INPUTS SYSTEM QUANTITATIVE OUTPUTS

DESIGN PERMUATATION SCORECARD

FINANCIAL INPUTS

SYSTEM FINANCIAL OUTPUTS

KARL H. BENGZON COLUMBIA BUILDING INTELLIGENCE PROJECT INTEGRATED DESIGN STUDIO - COLUMBIA GSAPP SPRING 2012

[active thermal envelope] version 5.0

version 5.0 - process design map


INPUTS RADIANT CURTAIN WALL OUTPUTS EVALUATION

horizontal opening ratio vertical opening ratio horizontal grid deformation vertical grid deformation deformation factor surface thickness projection from edge of slab material density specific heat Cp temp T1 temp T2 surface temp T3 surface temp T4

qualitative inputs

design variations

system qualitative outputs

solid to void ratio

UDF instantiation upon hosting surface physical properties user defined feature (UDF) system physical properties
total surface area (interior) radiating surface area (interior) total volume volume of radiating surface

comparison of design variations

number of rows number of columns

quantitative inputs

system quantitative outputs

mass of radiating surface heat input required to heat water radiant heat transfer (surface to body)

rentable price per sf material unit cost

financial inputs

SURFACE DRIVING INPUTS BY OTHERS

design scorecard

system financial outputs

new rentable square footage added value of new rentable square footage

KARL H. BENGZON COLUMBIA BUILDING INTELLIGENCE PROJECT INTEGRATED DESIGN STUDIO - COLUMBIA GSAPP SPRING 2012

INPUTS

RADIANT CURTAIN WALL

OUTPUTS

horizontal opening ratio vertical opening ratio horizontal grid deformation vertical grid deformation deformation factor surface thickness projection from edge of slab material density specific heat Cp temp T1 temp T2 surface temp T3 surface temp T4

qualitative inputs

design variations

system qualitative outputs

UDF instantiation upon hosting surface physical properties user defined feature (UDF) system physical properties

number of rows number of columns

quantitative inputs

system quantitativ horizontal opening ratio + vertical opening ratio outputs

02a

rentable price per sf material unit cost

financial inputs

SURFACE DRIVING INPUTS BY OTHERS

design scorecard

system financia outputs

KARL H. BENGZON COLUMBIA BUILDING INTELLIGENCE PROJECT INTEGRATED DESIGN STUDIO - COLUMBIA GSAPP SPRING 2012

[active thermal envelope] version 5.0


INPUTS opening ratio H opening ratio V horizontal divisons vertical divisions deformation factor grid deformation H grid deformation V envelope thickness facade projection rental price per SF $ price per cu.ft. conc. $

0.3 0.3 10 10 0 0 0 24 12 200 60

OUTPUTS opening percentage new sf added value new sf added $ total wt. concrete total material cost $ emitting surface area required heat input radiation loss rate

18.7 % 60 11,999 268,546 lb 21,518 2,141 sf 319,570 btu 44.39 btu/hr

KARL H. BENGZON COLUMBIA BUILDING INTELLIGENCE PROJECT INTEGRATED DESIGN STUDIO - COLUMBIA GSAPP SPRING 2012

[active thermal envelope] version 5.0


INPUTS opening ratio H opening ratio V horizontal divisons vertical divisions deformation factor grid deformation H grid deformation V envelope thickness facade projection rental price per SF $ price per cu.ft. conc. $

0.5 0.5 10 10 0 0 0 24 12 200 60

OUTPUTS opening percentage new sf added value new sf added $ total wt. concrete total material cost $ emitting surface area required heat input radiation loss rate

35.8 % 60 11,999 212,023 lb 16,989 1,690 sf 252,308 btu 35.05 btu/hr

KARL H. BENGZON COLUMBIA BUILDING INTELLIGENCE PROJECT INTEGRATED DESIGN STUDIO - COLUMBIA GSAPP SPRING 2012

[active thermal envelope] version 5.0


INPUTS opening ratio H opening ratio V horizontal divisons vertical divisions deformation factor grid deformation H grid deformation V envelope thickness facade projection rental price per SF $ price per cu.ft. conc. $

0.7 0.7 10 10 0 0 0 24 12 200 60

OUTPUTS opening percentage new sf added value new sf added $ total wt. concrete total material cost $ emitting surface area required heat input radiation loss rate

52.9 % 60 11,999 155,510 lb 12,460 1,239 sf 185,057 btu 25.71 btu/hr

KARL H. BENGZON COLUMBIA BUILDING INTELLIGENCE PROJECT INTEGRATED DESIGN STUDIO - COLUMBIA GSAPP SPRING 2012

[active thermal envelope] version 5.0


INPUTS opening ratio H opening ratio V horizontal divisons vertical divisions deformation factor grid deformation H grid deformation V envelope thickness facade projection rental price per SF $ price per cu.ft. conc. $

0.9 0.9 10 10 0 0 0 24 12 200 60

OUTPUTS opening percentage new sf added value new sf added $ total wt. concrete total material cost $ emitting surface area required heat input radiation loss rate

70.0 % 60 11,999 99,005 lb 7,933 789 sf 117,816 btu 16.37 btu/hr

KARL H. BENGZON COLUMBIA BUILDING INTELLIGENCE PROJECT INTEGRATED DESIGN STUDIO - COLUMBIA GSAPP SPRING 2012

INPUTS

RADIANT CURTAIN WALL

OUTPUTS

horizontal opening ratio vertical opening ratio horizontal grid deformation vertical grid deformation deformation factor surface thickness projection from edge of slab material density specific heat Cp temp T1 temp T2 surface temp T3 surface temp T4

qualitative inputs

design variations

system qualitative outputs

UDF instantiation upon hosting surface physical properties user defined feature (UDF) system physical properties

number of rows number of columns

quantitative inputs

system quantitativ horizontal divisions + vertical divisions outputs

02b

rentable price per sf material unit cost

financial inputs

SURFACE DRIVING INPUTS BY OTHERS

design scorecard

system financia outputs

KARL H. BENGZON COLUMBIA BUILDING INTELLIGENCE PROJECT INTEGRATED DESIGN STUDIO - COLUMBIA GSAPP SPRING 2012

[active thermal envelope] version 5.0


INPUTS opening ratio H opening ratio V horizontal divisons vertical divisions deformation factor grid deformation H grid deformation V envelope thickness facade projection rental price per SF $ price per cu.ft. conc. $

0.9 0.9 8 8 0 0 0 24 12 200 60

OUTPUTS opening percentage new sf added value new sf added $ total wt. concrete total material cost $ emitting surface area required heat input radiation loss rate

70.0 % 60 11,999 99,004 lb 7,933 789 sf 117,815 btu 16.37 btu/hr

KARL H. BENGZON COLUMBIA BUILDING INTELLIGENCE PROJECT INTEGRATED DESIGN STUDIO - COLUMBIA GSAPP SPRING 2012

[active thermal envelope] version 5.0


INPUTS opening ratio H opening ratio V horizontal divisons vertical divisions deformation factor grid deformation H grid deformation V envelope thickness facade projection rental price per SF $ price per cu.ft. conc. $

0.9 0.9 10 10 0 0 0 24 12 200 60

OUTPUTS opening percentage new sf added value new sf added $ total wt. concrete total material cost $ emitting surface area required heat input radiation loss rate

70.0 % 60 11,999 99,004 lb 7,933 789 sf 117,815 btu 16.37 btu/hr

KARL H. BENGZON COLUMBIA BUILDING INTELLIGENCE PROJECT INTEGRATED DESIGN STUDIO - COLUMBIA GSAPP SPRING 2012

[active thermal envelope] version 5.0


INPUTS opening ratio H opening ratio V horizontal divisons vertical divisions deformation factor grid deformation H grid deformation V envelope thickness facade projection rental price per SF $ price per cu.ft. conc. $

0.9 0.9 13 13 0 0 0 24 12 200 60

OUTPUTS opening percentage new sf added value new sf added $ total wt. concrete total material cost $ emitting surface area required heat input radiation loss rate

70.0 % 60 11,999 99,004 lb 7,933 789 sf 117,815 btu 16.37 btu/hr

KARL H. BENGZON COLUMBIA BUILDING INTELLIGENCE PROJECT INTEGRATED DESIGN STUDIO - COLUMBIA GSAPP SPRING 2012

[active thermal envelope] version 5.0


INPUTS opening ratio H opening ratio V horizontal divisons vertical divisions deformation factor grid deformation H grid deformation V envelope thickness facade projection rental price per SF $ price per cu.ft. conc. $

0.9 0.9 15 15 0 0 0 24 12 200 60

OUTPUTS opening percentage new sf added value new sf added $ total wt. concrete total material cost $ emitting surface area required heat input radiation loss rate

70.0 % 60 11,999 99,004 lb 7,933 789 sf 117,815 btu 16.37 btu/hr

KARL H. BENGZON COLUMBIA BUILDING INTELLIGENCE PROJECT INTEGRATED DESIGN STUDIO - COLUMBIA GSAPP SPRING 2012

INPUTS

RADIANT CURTAIN WALL

OUTPUTS

horizontal opening ratio vertical opening ratio horizontal grid deformation vertical grid deformation deformation factor surface thickness projection from edge of slab material density specific heat Cp temp T1 temp T2 surface temp T3 surface temp T4

qualitative inputs

design variations

system qualitative outputs

UDF instantiation upon hosting surface physical properties user defined feature (UDF) system physical properties

number of rows number of columns

quantitative inputs

system quantitativ deformation factor outputs

02c

rentable price per sf material unit cost

financial inputs

SURFACE DRIVING INPUTS BY OTHERS

design scorecard

system financia outputs

KARL H. BENGZON COLUMBIA BUILDING INTELLIGENCE PROJECT INTEGRATED DESIGN STUDIO - COLUMBIA GSAPP SPRING 2012

[active thermal envelope] version 5.0


INPUTS opening ratio H opening ratio V horizontal divisons vertical divisions deformation factor grid deformation H grid deformation V envelope thickness facade projection rental price per SF $ price per cu.ft. conc. $

0.9 0.9 10 10 0 0 0 24 12 200 60

OUTPUTS opening percentage new sf added value new sf added $ total wt. concrete total material cost $ emitting surface area required heat input radiation loss rate

70.0 % 60 11,999 99,005 lb 7,933 789 sf 117,816 btu 16.37 btu/hr

KARL H. BENGZON COLUMBIA BUILDING INTELLIGENCE PROJECT INTEGRATED DESIGN STUDIO - COLUMBIA GSAPP SPRING 2012

[active thermal envelope] version 5.0


INPUTS opening ratio H opening ratio V horizontal divisons vertical divisions deformation factor grid deformation H grid deformation V envelope thickness facade projection rental price per SF $ price per cu.ft. conc. $

0.9 0.9 10 10 1 0 0 24 12 200 60

OUTPUTS opening percentage new sf added value new sf added $ total wt. concrete total material cost $ emitting surface area required heat input radiation loss rate

69.5 % 60 11,999 100,678 lb 8,067 802 sf 119,807 btu 16.65 btu/hr

KARL H. BENGZON COLUMBIA BUILDING INTELLIGENCE PROJECT INTEGRATED DESIGN STUDIO - COLUMBIA GSAPP SPRING 2012

[active thermal envelope] version 5.0


INPUTS opening ratio H opening ratio V horizontal divisons vertical divisions deformation factor grid deformation H grid deformation V envelope thickness facade projection rental price per SF $ price per cu.ft. conc. $

0.9 0.9 10 10 2 0 0 24 12 200 60

OUTPUTS opening percentage new sf added value new sf added $ total wt. concrete total material cost $ emitting surface area required heat input radiation loss rate

73.5% 60 11,999 87,440 lb 7,006 697 sf 104,054 btu 14.45 btu/hr

KARL H. BENGZON COLUMBIA BUILDING INTELLIGENCE PROJECT INTEGRATED DESIGN STUDIO - COLUMBIA GSAPP SPRING 2012

[active thermal envelope] version 5.0


INPUTS opening ratio H opening ratio V horizontal divisons vertical divisions deformation factor grid deformation H grid deformation V envelope thickness facade projection rental price per SF $ price per cu.ft. conc. $

0.9 0.9 10 10 3 0 0 24 12 200 60

OUTPUTS opening percentage new sf added value new sf added $ total wt. concrete total material cost $ emitting surface area required heat input radiation loss rate

70.3% 60 11,999 92,288 lb 7,875 784 sf 116,963 btu 16.25 btu/hr

KARL H. BENGZON COLUMBIA BUILDING INTELLIGENCE PROJECT INTEGRATED DESIGN STUDIO - COLUMBIA GSAPP SPRING 2012

INPUTS

RADIANT CURTAIN WALL

OUTPUTS

horizontal opening ratio vertical opening ratio horizontal grid deformation vertical grid deformation deformation factor surface thickness projection from edge of slab material density specific heat Cp temp T1 temp T2 surface temp T3 surface temp T4

qualitative inputs

design variations

system qualitative outputs

UDF instantiation upon hosting surface physical properties user defined feature (UDF) system physical properties

number of rows number of columns

quantitative inputs

system quantitativ horizontal deformation outputs

02d

rentable price per sf material unit cost

financial inputs

SURFACE DRIVING INPUTS BY OTHERS

design scorecard

system financia outputs

KARL H. BENGZON COLUMBIA BUILDING INTELLIGENCE PROJECT INTEGRATED DESIGN STUDIO - COLUMBIA GSAPP SPRING 2012

[active thermal envelope] version 5.0


INPUTS opening ratio H opening ratio V horizontal divisons vertical divisions deformation factor grid deformation H grid deformation V envelope thickness facade projection rental price per SF $ price per cu.ft. conc. $

0.9 0.9 10 10 0 0 0 24 12 200 60

OUTPUTS opening percentage new sf added value new sf added $ total wt. concrete total material cost $ emitting surface area required heat input radiation loss rate

70.0 % 60 11,999 99,005 lb 7,933 789 sf 117,816 btu 16.37 btu/hr

KARL H. BENGZON COLUMBIA BUILDING INTELLIGENCE PROJECT INTEGRATED DESIGN STUDIO - COLUMBIA GSAPP SPRING 2012

[active thermal envelope] version 5.0


INPUTS opening ratio H opening ratio V horizontal divisons vertical divisions deformation factor grid deformation H grid deformation V envelope thickness facade projection rental price per SF $ price per cu.ft. conc. $

0.9 0.9 10 10 0 12 0 24 12 200 60

OUTPUTS opening percentage new sf added value new sf added $ total wt. concrete total material cost $ emitting surface area required heat input radiation loss rate

69.9 % 60 11,999 99,140 lb 7,933 790 sf 117,977 btu 16.39 btu/hr

KARL H. BENGZON COLUMBIA BUILDING INTELLIGENCE PROJECT INTEGRATED DESIGN STUDIO - COLUMBIA GSAPP SPRING 2012

[active thermal envelope] version 5.0


INPUTS opening ratio H opening ratio V horizontal divisons vertical divisions deformation factor grid deformation H grid deformation V envelope thickness facade projection rental price per SF $ price per cu.ft. conc. $

0.9 0.9 10 10 0 36 0 24 12 200 60

OUTPUTS opening percentage new sf added value new sf added $ total wt. concrete total material cost $ emitting surface area required heat input radiation loss rate

69.9 % 60 11,999 99,449 lb 7,968 792 sf 118,344 btu 16.44 btu/hr

KARL H. BENGZON COLUMBIA BUILDING INTELLIGENCE PROJECT INTEGRATED DESIGN STUDIO - COLUMBIA GSAPP SPRING 2012

[active thermal envelope] version 5.0


INPUTS opening ratio H opening ratio V horizontal divisons vertical divisions deformation factor grid deformation H grid deformation V envelope thickness facade projection rental price per SF $ price per cu.ft. conc. $

0.9 0.9 10 10 0 56 0 24 12 200 60

OUTPUTS opening percentage new sf added value new sf added $ total wt. concrete total material cost $ emitting surface area required heat input radiation loss rate

65.9 % 60 11,999 112,747 lb 9,034 898 sf 134,169 btu 18.64 btu/hr

KARL H. BENGZON COLUMBIA BUILDING INTELLIGENCE PROJECT INTEGRATED DESIGN STUDIO - COLUMBIA GSAPP SPRING 2012

INPUTS

RADIANT CURTAIN WALL

OUTPUTS

horizontal opening ratio vertical opening ratio horizontal grid deformation vertical grid deformation deformation factor surface thickness projection from edge of slab material density specific heat Cp temp T1 temp T2 surface temp T3 surface temp T4

qualitative inputs

design variations

system qualitative outputs

UDF instantiation upon hosting surface physical properties user defined feature (UDF) system physical properties

number of rows number of columns

quantitative inputs

system quantitativ vertical deformation outputs

02e

rentable price per sf material unit cost

financial inputs

SURFACE DRIVING INPUTS BY OTHERS

design scorecard

system financia outputs

KARL H. BENGZON COLUMBIA BUILDING INTELLIGENCE PROJECT INTEGRATED DESIGN STUDIO - COLUMBIA GSAPP SPRING 2012

[active thermal envelope] version 5.0


INPUTS opening ratio H opening ratio V horizontal divisons vertical divisions deformation factor grid deformation H grid deformation V envelope thickness facade projection rental price per SF $ price per cu.ft. conc. $

0.9 0.9 10 10 0 0 0 24 12 200 60

OUTPUTS opening percentage new sf added value new sf added $ total wt. concrete total material cost $ emitting surface area required heat input radiation loss rate

70.0 % 60 11,999 99,005 lb 7,933 789 sf 117,816 btu 16.37 btu/hr

KARL H. BENGZON COLUMBIA BUILDING INTELLIGENCE PROJECT INTEGRATED DESIGN STUDIO - COLUMBIA GSAPP SPRING 2012

[active thermal envelope] version 5.0


INPUTS opening ratio H opening ratio V horizontal divisons vertical divisions deformation factor grid deformation H grid deformation V envelope thickness facade projection rental price per SF $ price per cu.ft. conc. $

0.9 0.9 10 10 0 0 12 24 12 200 60

OUTPUTS opening percentage new sf added value new sf added $ total wt. concrete total material cost $ emitting surface area required heat input radiation loss rate

69.9 % 60 11,999 99,163 lb 7,945 790 sf 118,005 btu 16.39 btu/hr

KARL H. BENGZON COLUMBIA BUILDING INTELLIGENCE PROJECT INTEGRATED DESIGN STUDIO - COLUMBIA GSAPP SPRING 2012

[active thermal envelope] version 5.0


INPUTS opening ratio H opening ratio V horizontal divisons vertical divisions deformation factor grid deformation H grid deformation V envelope thickness facade projection rental price per SF $ price per cu.ft. conc. $

0.9 0.9 10 10 0 36 0 24 12 200 60

OUTPUTS opening percentage new sf added value new sf added $ total wt. concrete total material cost $ emitting surface area required heat input radiation loss rate

69.8 % 60 11,999 99,402 lb 7,972 793 sf 118,395 btu 16.44 btu/hr

KARL H. BENGZON COLUMBIA BUILDING INTELLIGENCE PROJECT INTEGRATED DESIGN STUDIO - COLUMBIA GSAPP SPRING 2012

[active thermal envelope] version 5.0


INPUTS opening ratio H opening ratio V horizontal divisons vertical divisions deformation factor grid deformation H grid deformation V envelope thickness facade projection rental price per SF $ price per cu.ft. conc. $

0.9 0.9 10 10 0 0 56 24 12 200 60

OUTPUTS opening percentage new sf added value new sf added $ total wt. concrete total material cost $ emitting surface area required heat input radiation loss rate

68.0 % 60 11,999 105,764 lb 8,474 843 sf 125,860 btu 17.48 btu/hr

KARL H. BENGZON COLUMBIA BUILDING INTELLIGENCE PROJECT INTEGRATED DESIGN STUDIO - COLUMBIA GSAPP SPRING 2012

RADIANT CURTAIN WALL

OUTPUTS

EVALUATION

design variations

system qualitative outputs

solid to void ratio

UDF instantiation upon hosting surface user defined feature (UDF) system physical properties
total surface area (interior) radiating surface area (interior) total volume volume of radiating surface

comparison design variatio

system quantitative outputs

mass of radiating surface design scorecard heat input required to heat water+ design radiant heat transfer (surface to body)

variations

03

SURFACE DRIVING INPUTS BY OTHERS

design scorecard

system financial outputs

new rentable square footage added value of new rentable square footage

KARL H. BENGZON COLUMBIA BUILDING INTELLIGENCE PROJECT INTEGRATED DESIGN STUDIO - COLUMBIA GSAPP SPRING 2012

[active thermal envelope] version 5.0

scorecard diagram:

heat input benchmark 1 boiler horsepower BHP = 33,445.6 Btu or tbd by mechanical engineer aesthetics tbd by architect profit from new sf tbd by real estate input or tbd by owner

idealized design variation all domains held in equilibrium

design variation biased toward aesthetics domain


aesthetics

heat input

profit from new sf

material cost

radiative heat transfer

radiative heat transfer benchmark 28 btu/h/sf tbd by mechanical engineer structural performance benchmark 10 psf DL, 6 kip WL, typ. aluminum curtain wall typical DL + LL for cavity wall tbd by structural engineer material cost current cost per unit area for a given material glass fiber reinforced concrete or lightweight structural concrete size of circle magnitude relative to benchmark proximity to dominant domain describes influence of biased domain to peripheral domain (closer = stronger connection)

structural performance

biased domain takes the center marginalized domain moved to the periphery driven by dominant domain

aesthetics

profit from new sf

structural radiative heat transfer performance

material cost

heat input

KARL H. BENGZON COLUMBIA BUILDING INTELLIGENCE PROJECT INTEGRATED DESIGN STUDIO - COLUMBIA GSAPP SPRING 2012

[active thermal envelope] version 5.0


INPUTS opening ratio H opening ratio V horizontal divisons vertical divisions deformation factor grid deformation H grid deformation V envelope thickness facade projection rental price per SF $ price per cu.ft. conc. $

0.9 0.9 20 5 0 0 0 24 12 40 residential 60

OUTPUTS opening percentage new sf added value new sf added $ total wt. concrete total material cost $ emitting surface area required heat input radiation loss rate
aesthetics

71.9 % 90 3,591 44,013 lb 3,526 345 sf 52,376 btu 7.17 btu/hr/person

heat input

profit from new sf

material cost

radiative heat transfer

structural performance

KARL H. BENGZON COLUMBIA BUILDING INTELLIGENCE PROJECT INTEGRATED DESIGN STUDIO - COLUMBIA GSAPP SPRING 2012

[active thermal envelope] version 5.0


INPUTS opening ratio H opening ratio V horizontal divisons vertical divisions deformation factor grid deformation H grid deformation V envelope thickness facade projection rental price per SF $ price per cu.ft. conc. $

0.9 0.9 20 5 0 0 0 24 60 40 residential 60

OUTPUTS opening percentage new sf added value new sf added $ total wt. concrete total material cost $ emitting surface area required heat input radiation loss rate
aesthetics

71.9 % 421 16,850 44,013 lb 3,526 345 sf 52,376 btu 7.17 btu/hr/person

heat input

PROFIT FROM NEW SF

material cost

radiative heat transfer

structural performance

KARL H. BENGZON COLUMBIA BUILDING INTELLIGENCE PROJECT INTEGRATED DESIGN STUDIO - COLUMBIA GSAPP SPRING 2012

[active thermal envelope] version 5.0


INPUTS opening ratio H opening ratio V horizontal divisons vertical divisions deformation factor grid deformation H grid deformation V envelope thickness facade projection rental price per SF $ price per cu.ft. conc. $

0.9 0.9 20 5 0 0 0 4 60 60 office 60

OUTPUTS opening percentage new sf added value new sf added $ total wt. concrete total material cost $ emitting surface area required heat input radiation loss rate
aesthetics

71.9 % 421 25,276 7,213 lb 578 345 sf 8,583 btu 7.17 btu/hr/person

heat input

PROFIT FROM NEW SF

material cost

radiative heat transfer

structural performance

KARL H. BENGZON COLUMBIA BUILDING INTELLIGENCE PROJECT INTEGRATED DESIGN STUDIO - COLUMBIA GSAPP SPRING 2012

[active thermal envelope] version 5.0


INPUTS opening ratio H opening ratio V horizontal divisons vertical divisions deformation factor grid deformation H grid deformation V envelope thickness facade projection rental price per SF $ price per cu.ft. conc. $

0.9 0.8 15 10 0 0 0 4 30 60 office 60

OUTPUTS opening percentage new sf added value new sf added $ total wt. concrete total material cost $ emitting surface area required heat input radiation loss rate
aesthetics

67.9 % 304 18,289 8,057 lb 645 386 sf 9,588 btu 8.00 btu/hr/person

heat input

profit from new sf

material cost

radiative heat transfer

STRUCTURAL PERFORMANCE

KARL H. BENGZON COLUMBIA BUILDING INTELLIGENCE PROJECT INTEGRATED DESIGN STUDIO - COLUMBIA GSAPP SPRING 2012

[active thermal envelope] version 5.0


INPUTS opening ratio H opening ratio V horizontal divisons vertical divisions deformation factor grid deformation H grid deformation V envelope thickness facade projection rental price per SF $ price per cu.ft. conc. $

0.9 0.9 10 10 0 0 0 4 30 60 office 60

OUTPUTS opening percentage new sf added value new sf added $ total wt. concrete total material cost $ emitting surface area required heat input radiation loss rate
aesthetics

71.9 % 304 18,289 7,051 lb 565 387 sf 7,390 btu 7.00 btu/hr/person

heat input

profit from new sf

material cost

radiative heat transfer

STRUCTURAL PERFORMANCE

KARL H. BENGZON COLUMBIA BUILDING INTELLIGENCE PROJECT INTEGRATED DESIGN STUDIO - COLUMBIA GSAPP SPRING 2012

[active thermal envelope] version 5.0


INPUTS opening ratio H opening ratio V horizontal divisons vertical divisions deformation factor grid deformation H grid deformation V envelope thickness facade projection rental price per SF $ price per cu.ft. conc. $

0.3 0.3 20 5 0 0 0 4 60 60 office 60

OUTPUTS opening percentage new sf added value new sf added $ total wt. concrete total material cost $ emitting surface area required heat input radiation loss rate
aesthetics

23.9 % 421 25,276 19,565 lb 1,568 937 23,283 btu 19.44 btu/hr/person

heat input

profit from new sf

material cost

RADIATIVE HEAT TRANSFER

structural performance

KARL H. BENGZON COLUMBIA BUILDING INTELLIGENCE PROJECT INTEGRATED DESIGN STUDIO - COLUMBIA GSAPP SPRING 2012

[active thermal envelope] version 5.0


INPUTS opening ratio H opening ratio V horizontal divisons vertical divisions deformation factor grid deformation H grid deformation V envelope thickness facade projection rental price per SF $ price per cu.ft. conc. $

0.7 0.8 20 10 2 8 2 12 30 60 office 60

OUTPUTS opening percentage new sf added value new sf added $ total wt. concrete total material cost $ emitting surface area required heat input radiation loss rate

38.9 % 214 12,845 47,488 lb 3,805 1,168 25,561 btu 24.22 btu/hr/person

AESTHETICS

heat input

profit from new sf

material cost

radiative heat transfer

structural performance

KARL H. BENGZON COLUMBIA BUILDING INTELLIGENCE PROJECT INTEGRATED DESIGN STUDIO - COLUMBIA GSAPP SPRING 2012

[active thermal envelope] version 5.0


INPUTS opening ratio H opening ratio V horizontal divisons vertical divisions deformation factor grid deformation H grid deformation V envelope thickness facade projection rental price per SF $ price per cu.ft. conc. $

0.7 0.8 30 7 0 6 2 6 30 60 office 60

OUTPUTS opening percentage new sf added value new sf added $ total wt. concrete total material cost $ emitting surface area required heat input radiation loss rate

63.8 % 214 12,845 28,138 lb 2,254 852 33,485 btu 17.67 btu/hr/person

AESTHETICS

heat input

profit from new sf

material cost

radiative heat transfer

structural performance

KARL H. BENGZON COLUMBIA BUILDING INTELLIGENCE PROJECT INTEGRATED DESIGN STUDIO - COLUMBIA GSAPP SPRING 2012

[active thermal envelope] version 5.0


INPUTS opening ratio H opening ratio V horizontal divisons vertical divisions deformation factor grid deformation H grid deformation V envelope thickness facade projection rental price per SF $ price per cu.ft. conc. $

0.7 0.8 20 10 0 8 2 12 30 60 office 60

OUTPUTS opening percentage new sf added value new sf added $ total wt. concrete total material cost $ emitting surface area required heat input radiation loss rate

76.8 % 214 12,845 18,041 lb 1,445 587 21,469 btu 12.18 btu/hr/person

AESTHETICS

heat input

profit from new sf

material cost

radiative heat transfer

structural performance

KARL H. BENGZON COLUMBIA BUILDING INTELLIGENCE PROJECT INTEGRATED DESIGN STUDIO - COLUMBIA GSAPP SPRING 2012

[active thermal envelope] version 5.0


INPUTS opening ratio H opening ratio V horizontal divisons vertical divisions deformation factor grid deformation H grid deformation V envelope thickness facade projection rental price per SF $ price per cu.ft. conc. $

0.7 0.8 20 10 0 8 2 12 30 60 office 60

OUTPUTS opening percentage new sf added value new sf added $ total wt. concrete total material cost $ emitting surface area required heat input radiation loss rate

54.1 % 304 18,289 17,358 lb 1,391 565 20,656 btu 11.72 btu/hr/person

AESTHETICS

heat input

profit from new sf

material cost

radiative heat transfer

structural performance

KARL H. BENGZON COLUMBIA BUILDING INTELLIGENCE PROJECT INTEGRATED DESIGN STUDIO - COLUMBIA GSAPP SPRING 2012

[active thermal envelope] version 5.0

KARL H. BENGZON COLUMBIA BUILDING INTELLIGENCE PROJECT INTEGRATED DESIGN STUDIO - COLUMBIA GSAPP SPRING 2012

You might also like