Protection and control Sepam range Sepam 1000+ Substation Transformer Motor Busbar

Trip 0o t ex ff Io n

1 I>5 on

51 I>>

51n Io>

n >51 Io>

I1 I2 I3

2A 16 = 61A 1 = 63A 1 =
res cle ar et

MERLIN GERIN

IN ER NG RLI MEm
sep a

Presentation

Contents
presentation / description selection table metering protection control and monitoring functional and connection schemes other connection schemes logic inputs and outputs optional modules communication metering functions diagnosis functions protection functions control and monitoring functions parameter and protection settings default parameter setting characteristics ordering information Sepam 1000 + is a simple, reliable range of protection and metering units designed for the operation of machines and the electrical distribution networks of industrial installations and utility substations for all levels of voltage. Sepam 1000+ provides you with:

page 2 6 7 8 12 13 15 16 18 19 22 26 30 60 64 66 68

More solutions
A protection unit suited to each application requirement, providing an optimum cost/function ratio. The Sepam 1000+ range includes different types of units for different applications: c Sepam 1000+ S20: substation (incomers and feeders) protection, c Sepam 1000+ T20: transformer protection, c Sepam 1000+ M20: motor protection, c Sepam 1000+ B21, B22: voltage metering and protection functions for busbars.

Diagnosis function The unit takes into account 3 levels of diagnostic information for better operation: c network diagnosis (tripping current, unbalance ratio, disturbance recording), c switchgear diagnosis (cumulative breaking current, operating time), c diagnosis of the protection unit and additional modules (self-testing results, watchdog,). Program logic and monitoring Preprogrammed circuit breaker and annunciation program logic that requires no auxiliary relays or additional wiring, for fast, dependable commissioning.

More modularity
In order to adapt to the greatest number of application cases and allow subsequent installation upgrading, the unit has optional modules that may be added at any time: c logic input/output module with parameterizable program logic, c communication, c temperature sensor module, c analog output module.

More simplicity
Installation c Motor thermal protection setting based on machine manufacturer data. For integration in cubicles without any constraints, the unit can be installed: c on the front panel of the cubicle, reduced depth (< 100 mm), c inside the cubicle low voltage compartment, with the UMI installed in the most appropriate operation location, c reduced steady state consumption (< 3.5 W) by the unit limits the sizing of auxiliary supply batteries. User-friendliness User-friendly and high-performing software provides the PC computer resources for Sepam 1000+ parameter setting and operation, such as: c uploading and downloading of setting files, c time setting in TMS (Time Multiplier Setting) or 10 I/Is mode, c language change for operating menus and messages. Operation All information such as metering, settings, events and disturbance records can be accessed locally, or remotely via the communication link. Clarity of information c Clear indication of faults, c Indication of the faulty phase by reading and storage of tripping currents on each phase, c Real primary value display of variables (A, kA, V, kV), c Instant indication whenever a set point is exceeded. User machine interface (UMI) Several levels of totally parameterizable UMI are available according to the user's needs. Sepam 1000+ can be adapted into the local operating language.

More performances
Protections Complete 3 phase (RMS current measurement) and earth fault protection unit, including 4 relays divided into 2 groups of 2 relays with a choice of tripping curves, with switching from one group to the other controlled by a logic input or remote control. c Earth fault protection insensitivity to transformer closing. c Detection of phase unbalance. c RMS thermal protection which takes into account external operating temperature and ventilation operating rates. Logic discrimination Sepam 1000+ utilizes logic discrimination, which ensures fast, selective overcurrent protection tripping without requiring the use of time intervals between upstream and downstream protection devices. Communication Totally compatible with MODBUS communication standard. Includes all the necessary accessories and connectors for ready-to-use 2-wire or 4-wire RS485 communication.

Sepam 1000+

Description

Flexible architecture

module MES 108 4 logic outputs, 4 logic inputs or MES 114 (1) 4 logic outputs, 10 logic inputs

(1)

ACE 949-2 (2-wire) module ACE 959 (4-wire) communication network interface Sepam 1000+ base unit

(1)

Trip Io 0o t ex ff n

51 I>> 1 I>5 on

51n Io>

n >51 Io>

CCA 612

2A 16 = 61A 1 I1 = 63A 1 I2 = I3
cle ar

res

et

CCA 772

(2)

RIN GE LIN ER Mpam e


s

MSA 141 module 1 analog output

(1)

CCA 783

CCA 770

(2)

MET 148 module 8 temperature sensor inputs

(1)

SFT 2841 parameter setting and operation software SFT 2826 disturbance recording restoring software

(1) (2)

Optional additional module. Example, the prefabricated cords come in 3 different lengths.

Sepam 1000+

Description (contd)

Front panel
Sepam 1000 + has two levels of UMI (User machine interface) suited to each operating requirement:

Standard UMI
This UMI includes: c 2 signal lamps indicating Sepam operating status: v green on indicator: device on, v red wrench indicator: device unavailable (initialization phase or detection of an internal failure), c 9 parameterizable yellow signal lamps equipped with standard text label (1), c reset button for clearing faults and resetting, c 1 connection port for the RS232 link with the PC (CCA783 cord), the port is protected by a sliding cover. This UMI offers a low-cost solution for installations that do no require local operation (run from a remote control and monitoring system) or to replace electromechanical or analog electronic protection devices without any additional operating requirements.
on I>51 I>>51 Io>51N Io>>51N ext 0 off I on Trip

reset

Example of standard UMI with standard indicator assignment.

Fixed advanced UMI


In addition to the standard UMI functions, this version provides: c a graphic LCD display for the display of measurements, parameter/protection settings and alarm and operating messages. The number of lines, size of characters and symbols are in accordance with screens and language versions. c a 9-key keypad with two modes of use: White keys for current operation: 1 display of measurements, 2 display of switchgear, network diagnosis data, 3 display of alarm messages, 4 resetting, 5 acknowledgment and clearing of alarms. Blue keys for parameter and protection setting: 7 access to protection settings, 8 access to Sepam parameter settings (2), 9 used to enter the 2 passwords required to change protection and parameter settings. The , , keys ( 4 , 5 , 6 ) are used to navigate in the menus and to scroll and accept the values displayed. 6 lamp test keys: switching on sequence of all the signal lamps. This UMI is an optimum solution for local operation facilitated by clear legibility and data content and access.

on

I>51

I>>51 Io>51N Io>>51N

ext

0 off

I on

Trip

I1 = 162A I2 = 161A I3 = 163A

1 2

clear

reset

Example of advanced UMI with standard indicator assignment.

Remote advanced UMI


This UMI may be added to the Sepam base unit via prefabricated CCA 770, CCA 772 or CCA 774 cords (depending on the distance). With reduced depth and the same functions as the fixed version, it may be installed on the front panel of the cubicle in the most appropriate location for operation.

(1) this removable label may be replaced by a customized label made using the SFT 2841 software package. (2) the "expert UMI" is required for parameterization of the program logic.

Sepam 1000+

Expert UMI
This UMI is available as a complement to the Standard or Advanced UMI on the screen of a PC equipped with the SFT2841 software package and connected to the RS232 link on the front panel of the Sepam (operating in a Windows > V95 or NT version). All the data used for the same task are grouped together in the same screen to facilitate operation. Menus and icons are used to provide fast, direct access to the information. Current operation c display of all metering and operating data, c display of alarm messages with the time format (date, hour, mn, s), c display of diagnostic data such as: v tripping current, v number of switchgear operations and cumulative breaking current, c display of all protection and parameter settings, c display of the logic status of inputs, outputs and signal lamps. This UMI offers the solution suited to occasional local operation or for demanding personnel who require fast access to all the information. Parameter - protection settings (1) c display and setting of all the parameters of each protection function on the same page, c program logic parameter setting, parameter setting of general installation and Sepam data, c input data may be prepared ahead of time and transferred into the corresponding Sepam units in a single operation (downloading function). Main functions performed by SFT2841: c changing of passwords, c entry of general parameters (ratings, integration period, ), c entry of protection settings, c changing of program logic assignments, c enabling/disabling of functions, c saving of files. Saving c protection and parameter setting data may be saved, c printing of reports is possible as well. This UMI may also be used to recover disturbance recording files and provide graphic display using the SFT2826 software package.
e.g. phase overcurrent protection setting screen.

e.g. measurement display screen (Sepam M20).

Operating assistance Access from all the screens to a help function which contains all the technical data required for Sepam installation and use.

(1)

modes available via 2 passwords (protection setting level, parameter setting level).

Sepam 1000+

Selection table

Sepam 1000+
functions protections ANSI code phase overcurrent (1) 50/51 earth fault (or neutral) (1) 50N/51N unbalance / negative sequence 46 thermal overload 49 RMS phase undercurrent 37 excessive starting time, locked rotor 48/51LR starts per hour 66 positive sequence undervoltage 27D/47 remanent undervoltage 27R phase-to-phase undervoltage 27 phase-to-neutral undervoltage 27S phase-to-phase overvoltage 59 neutral voltage displacement 59N overfrequency 81H underfrequency 81L rate of change of frequency 81R recloser (4 cycles) 79 thermostat / Buchholz temperature monitoring (2) 38/49T metering phase current I1,I2,I3 RMS residual current Io average current I1, I2, I3 peak demand phase current IM1,IM2,IM3 line voltage U21, U32, U13 phase-to-neutral voltage V1, V2, V3 residual voltage Vo positive sequence voltage / rotation direction frequency temperature measurement (2) network diagnosis tripping current I1,I2,I3, Io unbalance ratio / negative sequence current Ii running hours counter / operating time thermal capacity used remaining operating time before overload tripping waiting time after overload tripping starting current and time / overload start inhibit time delay, number of starts before inhibition disturbance recording switchgear diagnosis cumulative breaking current2 trip circuit supervision number of operations operating time operating time self-diagnosis watchdog output relay test (3) control and monitoring circuit breaker / contactor control (4) logic discrimination 4 addressable logic outputs additional modules MET 148 module - 8 temperature sensor inputs MSA 141 module - 1 low level analog output MES 108 module - (4I/4S) or MES 114 module - (10I/4O) ACE 949-2 module - (2-wire) or ACE 959 (4-wire) RS485 interface type of Sepam substation S20 4 4 1 transformer T20 4 4 1 2 motor M20 4 4 1 2 1 1 1 busbar B21(5) B22

2 1 2 1 2 2 1 2 v v v c c c c

2 1 2 1 2 2 1 2 1

v c c c c

c c c c

v c c c c c c c c

v c c c c c c c c c v v v v c v v v c v v v v

c c c c c

c c c c c

c c v v v v c v v v c v v v

c c v v v v c v v v c v v v v

c v

c v

c v v c v v v

c v v c v v v

c standard, v according to parameter setting and MES 108 or MES 114 input/output module options. (1) 4 relays with the exclusive possibility of logic discrimination or switching from one 2-relay group of settings to another 2-relay group. (2) with MET 148 sensor option, 2 set points per sensor. (3) with advanced UMI option only. (4) for shunt trip unit or undervoltage release coil according to parameter setting. (5) performs B20 type functions.

Sepam 1000+

Metering

Sepam 1000+ displays the measurements required for operation


The values are displayed as primary values with the related units: A, V, Hz, C, F, Currents c RMS measurement of the circuits 3 phase currents. c Residual current measurement. Average currents and peak demand currents Measurement of the average current on each of the 3 phases. Measurement of the greatest average current on each of the 3 phases. The peak demand currents give the current consumed at the time of peak loads. The average current is calculated over a period that may be parameterized from 5 to 60 mn. The clear key is used to reset the peak demand currents to zero when they are on the display. Tripping currents Storage of the greatest average value of the 3 phase currents and earth current at the time Sepam gave the last tripping order, to provide the fault breaking current (fault analysis). These values are stored until the next trip order is given. Thermal capacity used Measurement of the relative capacity used by the load. It is displayed as a percentage of the nominal thermal capacity. Voltages c Calculation or measurement of phase-to-neutral voltages V1, V2 and V3. c Calculation or measurement of phase-to-phase voltages U21, U32 and U13. c Calculation of positive sequence voltage Vd. c Calculation of residual voltage Vo. Frequency: measurement of frequency. Temperature Measurement of the temperature of each sensor.

Switchgear diagnosis assistance measurements


These measurements are to be compared with the data supplied by the switchgear manufacturer. Cumulative breaking current The displayed value may be used to evaluate the state of the circuit breaker poles. Operating time, charging time Measures the device operating time. These data may be used to evaluate the state of the pole and operating mechanism. Number of operations Cumulative number of breaker opening operations. Running hours counter / operating time Cumulative time during which the protected equipment (motor or transformer) is on load (I > 0.1 Ib). The cumulative value is displayed in hours (0 to 65535 h) and saved every 4 hours.

Characteristics
general parameters (set in the general settings menu) frequency 50 Hz or 60 Hz phase current 1 A or 5 A CT type sensor rated current In (1) LPCT type rated current In (1) residual current CSH 120/200 type sensor rated current Ino 1 A or 5 A CT + CSH type rated current Ino (1) voltage sensor rated primary voltage Unp (2) VT: 100, 110, 115, 120 V (Uns) TP : 200, 230 V ranges 0.1 to 1.5 In (1) 0.1 to 1.5 Ino (1) 0.1 to 1.5 In (1) 0.1 to 40 In (1) 0.1 to 20 Ino (1) 0 to 800 % (4) 10 to 500 % Ib (5) 0.05 to 1.2 Unp (2) or Vnp 0.05 to 1.5 Vnp (2) 0.015 to 3 Vnp (2) 50 / 60 Hz 5 Hz -30C to +200C (6) 20 to 100 ms 1 to 20 sec nb. (I1,I2,I3) or (I1,I3) 1 A to 6250 A number (I1, I2, I3) 25 A to 3150 A 2 A or 20 A or core balance CT 1 A to 6250 A 220 V to 250 kV V1, V2, V3 U21, U32 U21 V1, V2, V3 accuracy (7) (3) typically 1% 5% typically 1% 5% 5%
(3)

Motor operation assistance function


Motor starting current and time / motor overload Measures the maximum value of current absorbed by the motor during a starting sequence or at the time of an overload as well as the duration. Number of starts before inhibition / start inhibit time delay Indicates the remaining number of starts allowed by the starts per hour protection, then, if the number is zero, the waiting time before starting is allowed. Remaining operating time before overload tripping Indicates the time remaining before tripping by the thermal overload protection. Waiting time after overload tripping Indicates the time remaining before starting is allowed according to inhibition by the thermal protection.

metering functions phase current residual current peak demand current tripping current phase earth thermal capacity used unbalance ratio (negative sequence current) voltmeter voltages (ph-to-neutral or ph-to-ph) voltmeter positive sequence voltage voltmeter residual voltage frequency meter temperature operating time charging time running hours counter 1% or 0.5 h metering transducer
(1)

2% typically 1%
(3)

2% 5% 0.05 Hz 1C typically 1 ms 0.5 sec 0 to 65535 h 0.5%

(3) (3)

4-20; 0-20; 0-10 mA

In, Ino: CT primary rated current (2) Unp: rated primary phase-to-phase voltage; Vnp: primary phase-to-neutral voltage Vnp = (Unp/e) (3) measurements available in analog format according to parameter setting and MSA 141 module (4) 100% is the thermal capacity used of the equipment being protected under its rated load: I = Ib (5) Ib: base current of the equipment being protected (6) displayed in C or F according to parameter setting, typical accuracy from + 20C to +140C (7) in reference conditions (IEC 60255-4), typically at In or Un

Sepam 1000+

Protections

Phase overcurrent (ANSI 50/51) Three-phase protection against overloads and phase-to-phase short-circuits. The protection comprises four units: c IDMT or definite time, c instantaneous or time-delayed. Sepam 1000+ offers a number of tripping curves: c definite time (DT), c IDMT. The IDMT curves also include a reset time which is used for: c detection of restriking faults, c coordination with electromechanical relays. Earth fault (ANSI 50/51N or 50/51G) Connection and equipment earth fault protection. Earth faults may be detected by: c three phase currents (3I sum), c a special core balance CT, CSH120 or CSH200, according to the required diameter; this method provides the highest sensitivity. Selection between two ratings (2 A and 20 A) provides a very wide setting range. c a current transformer (1 A or 5 A), combined with a CSH30 interposing ring CT. The protection comprises four units: c IDMT or definite time, c instantaneous or time-delayed. The characteristic curves are the same as those for the phase current overcurrent protection. Each set point has a reset time setting (by an adjustable timer hold with definite time characteristic) that allows restriking faults to be detected. Each set point has a 2 nd harmonic restraint in order to ensure stability during transformer energizing. Negative sequence / unbalance (ANSI 46) Protection against phase unbalance. Sensitive protection against 2-phase faults on long feeders. Protection of equipment against temperature build-up caused by an unbalanced supply or wrong phase rotation or the loss of a phase and protection against low levels of phase-to-phase overcurrent. IDMT or definite time characteristics. Thermal overload (ANSI 49) Protection of equipment against thermal damage caused by overloads. The thermal capacity used is calculated according to a mathematical model which takes into account: c RMS current values, c ambient temperature. The function comprises: c an adjustable alarm set point, c an adjustable tripping set point, v transformer application. The model takes into account the transformer heat rise and cooling time constants according to whether natural or forced ventilation is used (ONAN, ONAF) by logic input. v motor application. The model takes into account: - two time constants: the heat rise time constant, used when the motor is running, and the cooling time constant, used when the motor is stopped, - effect of negative sequence current on rotor heating. An additional setting may be used to adapt the protection to fit the motor thermal withstand given by the experimental hot and cold curves provided by the equipment manufacturer. The thermal protection may be inhibited by a logic input when this is required by the process running conditions. Phase undercurrent (ANSI 37) Protection of pumps against the consequences of a loss of priming. The protection detects time-delayed current drops that correspond to motor no-load operation, characteristic of the loss of pump priming.

Sepam 1000+

Excessive starting time / locked rotor / (ANSI 48/51LR) (1) Protection of motors that are liable to start with overloads or insufficient supply voltage and/or that drive loads that are liable to jam (e.g. crushers). The locked rotor function is an overcurrent protection that is only confirmed after a time delay that corresponds to the normal starting time. Starts per hour (ANSI 66) (1) Protection against overheating caused by too frequent starts. Checking of the number of: c starts per hour (or adjustable time period), c consecutive starts. The protection inhibits motor energizing for a preset time period once the permissible limits have been reached. Recloser (ANSI 79) Automation device used to reclose the circuit breaker after tripping triggered by a transient fault on a line (the function includes 4 parameterizable reclosing cycles). Thermostat, Buchholz (temperature, gas and pressure detector) Protection of transformers against temperature rises and internal faults via logic inputs linked to devices integrated in the equipment. Temperature monitoring (RTDs) (ANSI 38/49T) Protection against abnormal overheating of motor windings and/or bearings equipped with RTDs. The protection includes 2 independent set points that are adjustable for each RTD. Positive sequence undervoltage (ANSI 27D), (ANSI 47) Motor protection against malfunctioning due to insufficient or unbalanced supply voltage. Detection of phase rotation. In order for this protection to be used, voltage transformers must be connected to Sepam to measure U21 and U32. Remanent undervoltage (ANSI 27R) Monitoring of the clearing of voltage sustained by rotating machines after circuit opening. The protection is used to prevent transient electrical and mechanical phenomena that are caused by fast re-energizing of motors. It monitors phase-to-phase voltage U21 or phase-to-neutral voltage V1. Phase-to-phase undervoltage (ANSI 27) Protection used either for automated functions (transfer, load shedding) or to protect motors against undervoltage. The protection monitors the drop in each of the phase-to-phase voltages being metered. Phase-to-neutral undervoltage (ANSI 27S) Protection used to detect phase-to-earth faults (in isolated neutral systems). Overvoltage (ANSI 59) Protection against abnormally high voltage or checking that there is sufficient voltage for power supply transfer (set point 1) and checking of phase-to-phase voltages U32 and U21 (set point 2). Neutral voltage displacement (ANSI 59N) Detection of insulation faults in ungrounded systems by measurement of neutral voltage displacement. The protection is generally used with transformer incomers or busbars. The function includes 2 set points. Overfrequency (ANSI 81H) Protection against abnormally high frequency. Underfrequency (ANSI 81L) Detection of variances with respect to the rated frequency, in order to maintain a high quality power supply. The protection may be used for overall tripping or for load shedding. Rate of change of frequency / ROCOF (ANSI 81R) Protection used for fast disconnection of a source feeding a power network when a fault occurs or to check load shedding.

(1)

possibility of motor re-acceleration to be taken into account by a logic input.

Sepam 1000+

Protections (contd)

Setting ranges
general parameters (set in general settings menu) frequency phase current sensor 50 Hz or 60 Hz 1 A or 5 A CT type rated current In LPCT type rated current In (3) CSH 120/200 type rated current Ino 1 A or 5 A CT + CSH type rated current Ino rated primary voltage Unp VT: 100, 110, 115, 120 V (Uns) VT: 200, 230 V settings number (I1, I2, I3) or (I1, I3) 1 A to 6250 A number (I1, I2, I3) 25 A to 3150 A 2 A or 20 A or core balance CT (2) 1 A to 6250 A 220 V to 250 kV V1, V2, V3 U21, U32 U21 V1, V2, V3 time delays holding time DT DT DT DT or IDMT DT or IDMT DT or IDMT definite time IDMT

residual current sensor

voltage sensor

functions phase overcurrent tripping curve

Is set point holding time earth fault tripping curve

definite time SIT, LTI, VIT, EIT, UIT (1) RI CEI : SIT/A, LTI/B, VIT/B, EIT/C IEEE : MI (D), VI (E), EI (F) IAC : I, VI, EI 0.1 to 24 In 0.1 to 2.4 In definite time (timer hold) IDMT (reset time)

Inst; 0.05 s to 300 s 0.1 s to 12.5 s at 10 Is Inst; 0.05 s to 300 s 0.5 s to 300 s

Is set point holding time negative sequence / unbalance definite time IDMT thermal overload

definite time SIT, LTI, VIT, EIT, UIT (1) RI IEC: SIT/A, LTI/B, VIT/B, EIT/C IEEE: MI (D), VI (E), EI (F) IAC: I, VI, EI 0.1 to 15 Ino 0.1 to 1 Ino definite time (timer hold) IDMT (reset time) 0.1 to 5 Ib 0.1 to 0.5 Ib negative sequence coefficient time constant alarm; tripping cold curve modification coefficient operating rate change condition maximum equipment temperature

holding time DT DT DT DT or IDMT DT or IDMT DT or IDMT definite time IDMT

Inst; 0.05 s to 300 s 0.1 s to 12.5 s at 10 Iso Inst; 0.05 s to 300 s 0.5 s to 300 s 0.1 s to 300 s 0.1 s to 1 s operating rate 1 operating rate 2

0 -2.25-4.5-9 heat rise T1: 5 to 120 mn T1: 5 to 120 mn cooling T2: 5 to 600 mn T2: 5 to 600 mn 50 to 300% of normal heat rise 0 to 100% by Is set point adjustable from 0.25 to 8 Ib (motor) by logic input I26 (transformer) 60 to 200 C 0.05 s to 300 s ST start time LT, LTS time delay 0.5 s to 300 s 0.05 s to 300 s
Sepam 1000+

phase undercurrent 0.15 to 1 Ib excessive starting time/ locked rotor 0.5 Ib to 5 Ib

10

Setting ranges (cont'd)


functions starts per hour settings 1 to 60 per hour 1 to 60 consecutive temperature (RTDs) 0 to 180 C (or 32 to 356F) positive sequence undervoltage 30 to 100 % of Vnp (Unp/e) remanent undervoltage 5 to 100 % of Unp phase-to-phase undervoltage 5 to 100 % of Unp phase-to-neutral undervoltage 5 to 100 % of Vnp phase-to-phase overvoltage 50 to 150 % of Unp neutral voltage displacement 2 to 80 % of Unp overfrequency 50 to 53 Hz or 60 to 63 Hz underfrequency set point 1 and set point 2 rate of change of frequency 0.1 to 10 Hz/s Inst; 0.15 s to 300 s
Note: In current, Unp rated voltage and Ino current are general parameters that are set at the time of Sepam commissioning. They are given as the values on the metering transformer primary windings. In is the current sensor rated current (CT rating) (adjustable from 1 to 6250 Amps), Unp is the rated phase-to-phase voltage of the voltage sensor primary windings (adjustable from 220V to 250KV), Ino is the core balance CT current rating, Ib is the current which corresponds to the motor power rating, adjustable from 0.4 to 1.3 In. The current, voltage and frequency values are set by direct entry of the values (resolution: 1 A, 1 V, 1 Hz, 1C or F). (1) tripping as of 1.2 Is. (2) with ACE 990 interface for core balance CT with ratio n of 50 to 1500 turns. (3) table of In values in Amps: 25, 50, 100, 125, 133, 200, 250, 320, 400, 500, 630, 666, 1000, 1600, 2000, 3150.

time delays hour time between starts 1 to 6 h 0 to 90 mn

0.05 s to 300 s 0.05 s to 300 s 0.05 s to 300 s 0.05 s to 300 s 0.05 s to 300 s 0.05 s to 300 s 0.1 s to 300 s 0.1 s to 300 s

45 to 50 Hz or 55 to 60 Hz

Sepam 1000+

11

Control and monitoring

Sepam 1000 + performs the basic control and monitoring functions necessary for the operation of the electrical network, thereby reducing the need for auxiliary relays. The control and monitoring functions may be parameterized using the SFT 2841 software package, however each type of Sepam has parameter setting by default which allows easier commissioning in the most frequent cases of use. Two control modes are available c Integrated circuit breaker control. This logical function deals with all the circuit breaker making and breaking conditions based on position data, external control and recloser protection functions, etc c Individual parameter setting of output relays. Control of output relays according to an allocation matrix. Breaking device control Sepam is used to control breaking devices equipped with different types of closing and tripping coils: c circuit breakers with shunt trip or undervoltage trip units (parameter setting on front panel (1) or via SFT 2841), c latching contactors with shunt-trip units. Output relay control (standard or fail-safe) may be set. By default, the program logic is adapted to control a circuit breaker with a shunt trip unit. Open and close control via the communication link. Latching / acknowledgment (ANSI 86) Output relay latching may be parameterized. Latched tripping orders are stored and must be acknowledged in order for the device to be put back into service. The user acknowledges via the keypad or remotely via a logic input or the communication link. Inhibit closing (ANSI 69) Sepam inhibits the closing of the circuit breaker or contactor according to the operation conditions. Inhibit thermal protection Thermal protection tripping may be inhibited via a logic input. Re-acceleration Allows a logic input to take into account the restarting of an unstopped motor. Remote tripping Circuit breakers or contactors may be remotecontrolled via a logic input or via the communication link. Inhibit remote control A logic input inhibits the circuit breaker remote control mode via the communication link. Switching of settings groups Used to switch from on group of phase current and earth fault protection settings to another one. The switch may be made by a logic input or via the communication link.

Logic discrimination (ANSI 68) This function allows quick, selective tripping of the phase overcurrent and earth fault protection relays, whether definite time or IDMT, without requiring the use of time intervals between upstream and downstream protection devices. The downstream relay transmits a blocking input signal if the protection devices set points are exceeded. The upstream relay receives the blocking input signal on the logic input, used for the inhibition function. A saving mechanism ensures the operation of the protection in the event of an inhibition link failure. Annunciation (ANSI 30) Sepam indicates the appearance of alarms by: c signal lamps on the front panel, c messages on the display. The addressing of the signal lamps may be parameterized. The sequence is as follows (advanced UMI): c when an event appears, the signal lamp goes on and the related message is displayed, c the user presses the clear key to erase the message, c after the fault disappears and the reset key is pressed, the signal lamp goes off and the protection is reset, c the list of alarm messages remains accessible ( key) and may be cleared by pressing the clear key. Remote annunciation Used to remote information via the communication link. Information such as circuit breaker position, SF6 fault alarm, etc. Trip circuit supervision Detects trip circuit faults (shunt trip units). Detects open/closed position discrepancy faults (undervoltage trip units). Watchdog Indicates Sepam unavailability. Output relay testing This function is used to activate each output relay (1).

List of main messages (1)


functions overcurrent earth fault thermal overload negative sequence / unbalance locked rotor excessive starting time starts per hour undercurrent overvoltage undervoltage positive sequence undervoltage neutral voltage displacement overfrequency underfrequency temperature thermostat Buchholz recloser recloser
(1)

messages (2) PHASE FAULT EARTH FAULT THERMAL ALARM THERMAL TRIP UNBALANCE ROTOR BLOCKING LONG START START INHIBIT UNDERCURRENT OVERVOLTAGE UNDERVOLTAGE UNDERVOLTAGE Vo FAULT OVER FREQ. UNDER FREQ. OVER TEMP TRIP THERMOST. TRIP BUCHH/GAS TRIP PERMANENT FAULT CLEARED FAULT

(3)

(3)

Sepam equipped with advanced UMI or SFT 2841. (2) messages by default, the wording of the messages may be changed (please consult us). (3) or Temperature, gas, pressure detector.

12

Sepam 1000+

Functional and connection schemes

S20 / T20 / M20 types


Connection to 1 / 5 A current transformers

L1 L2 L3

(1)
A

O1

5 4 8 7 11 10 15 14 13 1 2 17 +/~ /~

O2 S20
B

4 1 5 2 6 3

T20 46 49 50 51 50N 51N

M20 37 46 49 50 51 66 50N 51N 51LR O3

46 50 51 79 50N 51N

O4

18 19

communication

to communication network interface

to optional modules

L1 L2 L3 4 1 5 2 6 3
B

*
CSH30 18 19 Other connection scheme * 2 turns for 1 Amp CT, 4 turns for 5 Amps CT.

(1)

The connector marked A is available as an option for connection by 6.35 mm ring lug terminals.

Sepam 1000+

13

Functional and connection schemes (contd)

B21, B22 type

L1 L2 L3

B21
B

B22 27 27S 47 59 27D 27R 59N 81H 81L 81R


A

(3)

(1) 1 2 3 4 5 6 7 8 (2)

27 27S 47 59 27D 27R 59N 81H 81L

O1

5 4 8 7 11 10 15 14 13 1 2 17 +/~ /~

O2

O3

O4

communication

to communication network interface

to optional modules

(1) (2) (3)

this connection is used to calculate residual voltage. CCT 640 earthing terminal. The connector marked A is available as an option for connection by 6.35 mm eye lugs.

14

Sepam 1000+

Other connection schemes

Phase current
c Connection of two 1 / 5 A current transformers using the CCA 630 connector. c Connection of 3 LPCT type current transformers using the CCA 670 connector (the transformers are fitted with standard connection cables: L = 5 m).

L1 L2 L3 4 1 5 2 6 3 CCA 630

L1 L2 L3

L1 L2 L3

CCA 670

Residual current
c Connection of CSH interposing ring CTs to 1 A current transformers: make 2 turns through the CSH primary winding. c Connection of CSH interposing ring CTs to 5 A current transformers: make 4 turns through the CSH primary winding. (wiring combined with parameter setting of the type of CT and its rated current). c Connection of the ACE 990 interface to the core balance CT with ratio n of 50 to 1500 turns.

3 (L1, L2, L3)

3 (L1, L2, L3)

5 A CT

1 A CT : 2 turns 5 A CT : 4 turns

CSH 18 19

core balance n turns E1 En ACE 990

S1 18 S2 19

Phase voltage
Connection of 1 voltage transformer: (does not allow use of positive sequence undervoltage or neutral voltage displacement protections or measurement of residual and positive sequence voltages). Connection of 2 voltage transformers in V arrangement (does not allow use of neutral voltage displacement or measurement of residual voltage).

L1 L2 L3

L1 L2 L3

1 2 3 4 5 6 7 8

1 2 3 4 5 6 7 8 (2)

(2)

Residual voltages
Broken delta connection of voltage transformers for residual voltage measurement.

L1 L2 L3 (1)

(1) (2)

phase voltage metering with 1, 2 or 3 VTs (case shown). CCT 640 earthing terminal.

1 2 3 4 5 6 7 8

(2)

Sepam 1000+

15

Logic inputs and outputs

The Sepam 1000+ base unit has 4 outputs. The 4 basic outputs may be extended as an option by the addition of an MES module which is available in 2 versions: c MES 108 (4 outputs, 4 inputs) c MES 114 (4 outputs, 10 inputs) The assignment of the inputs and outputs may be set using the SFT 2841 software package. N.B. The inputs are potential-free, the DC supply is external.

base

MES108
O11

MES114
2 3 5 6 8 9 11 12
O11

2 3 5 6 8 9 11 12
M

O1

5 4
O12

O12

O2

8 7 11 10 15 14 13 1 2 17 +/~ /~

O13

O13

O3

O14

O14

Rear view of the MES 114 (MES 108) module


O4

M I11

1 2 4 5 7 8 10 11

I11

1 2 4 5 7 8 10 11

I12

I12

12 11 9 8 6 5 3 2 L

I13

O14 O13 O12 O11

I13

I14

I14

K I21

1 2 6 7 8 9 10 5 4

I22

I23

I24

I25

11 10 8 7 5 4 2 1 M

I26

I14 I26 I25 I24 I13 I23 I22 I12 I11 I21 K

10 9 8 7 6 5 4

2 1

Wiring for circuit breaker control Wiring for shunt trip unit and trip circuit supervision. Wiring for undervoltage trip unit and open/closed discrepancy fault monitoring.
A + _ O1 5 4 M I11 2 4 5 I12 2 4 5 D + _

A 5 O1 4 M I11 I12

outputs allocation O1 O2 O4 O11 tripping inhibit closing watchdog close control

16

Sepam 1000+

Input allocation by application chart In order for the predefined control and monitoring functions to be used, exclusive parameter setting and special wiring of the inputs are required according to the application of the inputs and the type of Sepam (refer to the Control and monitoring functions" section). ETOR I11 I12 I13 I14 I21 S20 open position closed position SSL receive BL external reset external tripping 1 (1) synchro external network A/B switching T20 open position closed position SSL receive BL external reset external tripping 1 (1) (Buchholz/Gas tripping message) external tripping 2 (1) (thermostat tripping message) Buchholz alarm (1) (Buchholz alarm message) thermostat alarmt (1) (thermostat alarm message) SF6-1 SF6-2 RC inhibition (1) change heat balance external tripping 3 (1) (pressure tripping message) end-of-loading mechanism synchro external network A/B switching

I22

external tripping 2 (1)

I23

external tripping 3 (1)

I24

end-ofcharging position RC inhibition (1) inhibit recloser

I25 I26

SF6-1 thermal protection inhibition SF6-2

ETOR(1) I11 I12 I13 I14 I21 I22 I23 I24 I25 I26

M20 open position closed position A/B switching external reset external tripping 1
(1)

B21 - B22 open position closed position external reset external network synchro motor re-acceleration motor shaft rotation end of loading mechanism SF6-1 change of thermal rate SF6-2 external tripping 1 (1) external tripping 2 (1) external tripping 3 (1) remote control inhibition (1) SF6-2 SF6-1 synchro external network

external tripping 2 (1) external tripping 3


(1)

remote control inhibition (1) thermal protection inhibition

Please note: all of the logic inputs are available via the communication link and may be accessed in the SFT 2841 matrix for other non predefined uses. (1) The settings of these inputs have the prefix NEG which represents undervoltage type operation.

Sepam 1000+

17

Connection of optional modules

Remote modules
Remote UMI (DSM 303) Temperature sensor inputs (MET 148)
A 2 3 4 n2 7 n3 8 9 10 11 12 8 9 10 11 12 5 6 5 6 7 n7 B 2 3 4 n6

DSM 303
n1

MET 148

1 n5

Da

Analog output (MSA 141)


n4

n8

1 2 Rc 3

MSA 141 Da
Da

+ Dd
Dd

Rc < 600 wiring included.

Sepam 1000 + CCA 772

Da
MERLIN GERIN
RIN GERIN RLIN GE 1000 MpERLIN am 00 se ME 10
sep am

Dd A

MSA 141 module

CCA 772 (or CCA 774) CCA 770 A Dd Da B remote UMI DSM 303

Wiring of inter-module links: The different module connection combinations are made possible by the use of prefabricated cords which come in 3 different lengths: c CCA 770 (L = 0.6 m, c CCA 772 (L = 2 m,. c CCA 774 (L = 4 m). The modules are linked by these cords which provide the power supply and act as functional links with the Sepam unit (D connector to Da connector, ). The DSM 303 module may only be connected at the end of the link. For the configuration using the 3 optionnals modules simultaneously, please refer to the schematic above.

MET 148 module

18

Sepam 1000+

Communication

Modbus communication (Jbus profile) may be used to connect the Sepam units to a remote monitoring and control system equipped with a master Modbus communication channel with an RS 485 type physical link.

Functions supported by Modbus communication


Sepams Modbus protocol supports 11 functions: c function 1: reading of n output or internal bits, c function 2: reading of n input bits, c function 3: reading of n output or internal words, c function 4: reading of n input words, c function 5: reading of 1 bit, c function 6: reading of 1 word, c function 7: high-speed reading of 8 bits, c function 8: reading of diagnosis counters, c function 11: reading of event counters, c function 15: writing of n bits, c function 16: writing of n words. The following exception codes are supported: c 1: unknown function code, c 2: incorrect address, c 7: not acknowledged (remote reading and setting).

Other functions c Sepam configuration and identification reading, c time-tagging of events (synchronization by network or externally via logic input I21), tagging of events within a millisecond accuracy, c remote reading of Sepam protection settings (remote reading), c remote setting of protections (remote setting), c remote control of analog output (1), c transfer of disturbance recording data.

Supervision zone
This zone includes all the data used by the remote monitoring and control system and may be accessed in a single reading operation.

Characteristics
type of transmission protocol rate data format asynchronous serial Modbus slave 4800, 9600, 19200, 38400 bauds 1 start, 8 bits, no parity, 1 stop 1 start, 8 bits, even parity, 1 stop 1 start, 8 bits, odd parity, 1 stop 2-wire differential, complies with EIA RS 485 standard screw terminals and tightening clamps/ shielding continuity less than 15 ms. number of Sepam connected: 5 10 20 25 320 1000 180 750 160 450 125 375

electrical interface type of connection

Data available
The data available depends on the type of Sepam.. Measurement readout c phase and earth fault currents, c peak demand phase currents, c tripping currents, c cumulative breaking current, c phase-to-phase, phase-to-neutral and residual voltages, c frequency, c temperatures, c thermal capacity used, c number of starts and inhibit time, c running hours counter, c motor starting current and time, c remaining operating time before overload tripping, c waiting time after tripping, c operating time and number of operations, c circuit breaker loading time. Program logic data readout c A table of 64 preassigned remote indications (TS) (depending on the type of Sepam) is used the status of the program logic data. c Reading the status of 10 digital inputs. Remote control orders Writing of 16 impulse type remote control orders (TC) in direct mode or in SBO (Select Before Operate) mode via 16 selection bits

response time maximum length of RS485 distributed power supply (in m) : 12 V distributed power supply 24 V distributed power supply

values obtained with a standard cable (2-pair AWG 24; resistance per unit length 78 / km). values multiplied by 3 with a maximum of 1300 m with specific cable, reference FILECA F2644-1; Schneider approved (refer to "RS485 - Modbus network connection accessories instruction manual", PCRED399074EN).

Implementation of the Modbus network


A set of adaptation accessories is used for dependable implementation of the communication network from both the electrical and environmental (electromagnetic compatibility) viewpoints: c network connection interface (ACE949) 1 including the Sepam interface connection cable 3 , c RS 485 / RS 232(ACE 909) or RS 485 / RS 485 converter (ACE 919) 2 . These accessories provide a 12 V distributed power supply, and may be used for polarization and terminal fitting of the communication link.
1

2
(1)

with MSA 141 option.

MERLIN GERIN

MERLIN GERIN

MERLIN GERIN

Sepam 1000+

19

Communication (contd)

c ACE 949-2 interface for 2-wire RS 485 network

Communication interface modules


These moduiles allow simple, dependable implementation of the RS485 link. The power supply for the RS485 communication interfaces is provided, via the network cable, by a single accessory that may be used to connect up to 25 modules. A shielded cable is used to wire the distributed power supply. The characteristics of the cable recommended for interconnecting the ACE 949-2 or ACE 959 modules are as follows: c twisted pair with tinned copper braid shielding, coverage: > 65%, c characteristic impedance:120 , c gauge: AWG 24, c resistance per unit length: < 100 / km, c capacitance between conductors: < 60 pF/ m, c capacitance between conductor and shielding: < 100 pF/ m. Example of compatible cable (2-wire network): c supplier: BELDEN, reference: 9842, c supplier: FILOTEX, reference: FMA- 2PS. Each module is equipped with a 3-meter long CCA 612 prefabricated cable connected to the C output of Sepam 1000+ .

RS485 network L- L+ V- V+ 1 2 3 4

ACE 949

4 3 2 1 L- L+ V- V+ RS485 network

CCA 612

to Sepam

Remote indications and remote control orders


c ACE 959 interface for 4-wire RS 485 network
ACE 959 (1) A VV+ Rx+ RxTx+ Tx-

The communication link provides Sepam 1000+ with: c 64 remote indications (TS) which correspond to the different states of the protection and monitoring functions, c 16 remote control orders (TC) may be used to control certain circuit breaker functions. The remote indications (TS) and remote control orders (TC) are pre-assigned according to the types of Sepam 1000+ in accordance with the chart opposite. c 10 digital inputs state. Remote control mode Remote control orders may be carried out in 2 modes (chosen by overall parameter setting for all remote control orders): c direct mode: the remote control order (TC, transmitted command) is effective as soon as it is received, c SBO (select before operate) mode. The SBO mode involves two steps: v selection of the remote control order to be sent (STC), v checking by reading over the selection again, v execution of the associated remote control order (TC). c remote control orders can be globally inhibited via the I25 logic input according to the program logic parameter setting.

(1) VV+ Rx+ RxTx+ Tx-

B CCA 612 C to Sepam

VV+ (2)

Assignment of CT (remote control orders)


TC 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 use trip close switching to settings group A switching to settings group B Sepam reset peak demand current zero reset inhibit thermal protection inhibit disturbance recording triggering confirm disturbance recording triggering manual disturbance recording triggering enable recloser disable recloser confirm thermal protection reserved reserved reserved S20 c c c c c c c c c c c T20 c c c c c c c c c c M20 c c c c c c c c c c B21 B22 c c c c

Rx+, Rx- : Sepam receiving (eq IN+, IN-) Tx+, Tx- : Sepam sending (eq OUT+, OUT-)
(1) distributed power supply with separate wiring or included in the shielded cable (3 pairs) (2) terminal block for connection to the distributed power supply module.

c c c

c c c

20

Sepam 1000+

Assignment of TS (remote indications)


TS use 1 2 3 4 5 6 7 8 9 10 11 12 13 protection 50/51 relay 1 group A protection 50/51 relay 2 group A protection 50/51 relay 1 group B protection 50/51 relay 2 group B protection 50N/51N relay 1 group A protection 50N/51N relay 2 group A protection 50N/51N relay 1 group B protection 50N/51N relay 2 group B protection 49 RMS alarm set point protection 49 RMS trip set point protection 37 (undercurrent) protection 46 (neg. seq./unbalance) c c S20 c c c c c c c c T20 c c c c c c c c c c M20 B21 B22 c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c 61 c 62 c c c c c c c c 63 64 53 54 55 56 57 58 59 60 TS 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 utilisation reserved recloser in service recloser in progress recloser permanent trip recloser successful trip send blocking input remote setting inhibited remote control inhibited Sepam not reset after faultt remote control / position discrepancy matching fault / trip circuit supervision disturbance recording memorized control fault disturbance recording inhibited thermal protection inhibited RTD fault protection 49T alarm set point sensor 1 protection 49T tripping set point sensor 1 protection 49T alarm set point sensor 2 protection 49T tripping set point sensor 2 protection 49T alarm set point sensor 3 protection 49T tripping set point sensor 3 protection 49T alarm set point sensor 4 protection 49T tripping set point sensor 4 protection 49T alarm set point sensor 5 protection 49T tripping set point sensor 5 protection 49T alarm set point sensor 6 protection 49T tripping set point sensor 6 protection 49T alarm set point sensor 7 protection 49T tripping set point sensor 7 protection 49T alarm set point sensor 8 protection 49T tripping set point sensor 8 S20 c c c c c c c c c c c c c T20 M20 B21 B22

c c c c c c c c c c c c c c c c c c c c c c c c c c c

c c c c c c c c c c c c c c c c c c c c c c c c c c c

c c c c c c c c

c c c c c c c c

protection 48/51LR (locked rotor) 14 rotor locking on start 15 16 17 excessive starting time protection 66 (starts per hour) protection 27D (pos. seq. undervoltage) relay 1 protection 27D (pos. seq. undervoltage) relay 2 protection 27 (ph.-to-ph. undervoltage) relay 1 protection 27 (ph.-to-ph. undervoltage) relay 2 protection 27R (remanent U/V) relay 1 protection 59 (ph.-to-ph. overvoltage) relay 1 protection 59 (ph.-to-ph. overvoltage) relay 2 protection 59N (ph-to-n. overvoltage) relay 1 protection 59N (ph-to-n. overvoltage) relay 2 protection 81H (overfrequency) protection 81L (underfrequency) relay 1 protection 81L (underfrequency) relay 2 protection 27S (undervoltage) phase 1 protection 27S (undervoltage) phase 2 protection 27S (undervoltage) phase 3 protection 81R (ROCOF)

18 19 20 21 22 23 24 25 26 27 28 29 30 31 32

Sepam 1000+

21

Metering functions

Phase current
Operation This function gives the RMS phase current values: c I1: phase 1 current, c I2: phase 2 current, c I3: phase 3 current. It is based on RMS current measurement and takes into account up to harmonics 17th. Readout The measurements may be accessed via: c c c c
(1)

the display (1) using the key, the screen of a PC with SFT 2841 software, the communication link, analog converter with the MSA 141 option.
Sepam equipped with advanced UMI option.

Characteristics measurement range unit accuracy 0.1 to 1.5 In (1) (3) A or kA typically 1% 1 digit (2) 2% from 0.3 to 1.5 In 5% if < 0.3 In 3 significant digits 1 second (typical)

display format averaging period


(1)

In rated current defined when the general parameters are set. (2) at In, in reference conditions (IEC 60255-6). (3) 0.1 A resolution.

Average currents and peak demand currents


Operation This function gives: c the average RMS current of each phase obtained over on adjustable period, c the greatest average RMS current value obtained since the last reset. These values are refreshed after each "integration period", a period that may be adjusted from 5 to 60 minutes. Readout The measurements may be accessed via: c the display (1) using the key, c the communication link (TC6). Clearing c by the clear key on the display (1) if the peak is displayed, c by the clear command in the SFT 2841 software, c by the communication link (TC6).
(1)

Sepam equipped with advanced UMI option.

Characteristics measurement range unit accuracy 0.1 to 1.5 In (1) (2) A or kA typically 1% (3) 2% from 0.3 to 1.5 In 5% if < 0.3 In 3 significant digits 5, 10, 15, 30, 60 mn

display format averaging period


(1)

In rated current defined when the general parameters are set. (2) 0.1 A resolution. (3) at In, in reference conditions (IEC 60255-6).

22

Sepam 1000+

Residual current
Operation This function gives the RMS value of the residual current Io. It is based on measurement of the fundamental component. Readout The measurements may be accessed via: c the display (1) using the key, c the screen of a PC with SFT 2841 software, c the communication link.
(1)

Characteristics measurement range connection to 3 phase CTs connection to 1 phase CT with CS30 interposing ring CT connection to core balance CT with ACE 990 connection to CSH core balance CT 2 A rating 20 A rating unit accuracy (2) 0.1 to 1.5 Ino (1) (3) 0.1 to 1.5 Ino (1) (3) 0.1 to 1.5 Ino (1) (3) 0.2 to 3 A (3) 2 to 30 A (3) A or kA typically 1% at Ino 2% from 0.3 to 1.5 Ino 5% if < 0.3 Ino 3 significant digits 1 second (typical)

display format refresh period


(1)

Sepam equipped with advanced UMI option.

Ino rated current defined when the general parameters are set. (2) at In, in reference conditions (IEC 60255-6), excluding sensor accuracy. (3) 0.1 A resolution.

Temperatures
Operation This function give the temperature value measured by RTDs: c Pt100 platinum RTD (100 at 0C) according to the IEC 751 and DIN 43760 standards, c nickel RTD 100 or 120 (at 0C). Each RTD channel gives one measurement: Tx = sensor x temperature. This function detects RTD faults: c RTD disconnected (t C < 205 C), c RTD shorted (t C < -35 C). In the event of a fault, display of the value is inhibited. The related monitoring function generates a maintenance alarm. Readout The measurement may be accessed via: c c c c
(1)

Characteristics range accuracy resolution refresh period


(1)

-30 C to 200 C (1)

-22 F to 392 F

1 C from +20 C to +140 C 2 C 1 C or 1 F 5 seconds (typical)

display possible in F.

Accuracy derating according to wiring c Connection in 3-wire mode: the error t is proportional to the length of the wire and inversely proportional to the wire cross-section: t (C) = 2 x I (km) S (mm2) v 2.1C/km for a cross-section of 0.93 mm2 , v 1C/km for a cross-section of 1.92 mm 2.

the display (1) using the key, the screen of a PC with SFT 2841 software, the communication link, analog converter with the MSA 141 option.
Sepam equipped with advanced UMI option.

Sepam 1000+

23

Metering functions (contd)

Phase-to-phase voltages
Operation This function gives the RMS value of the 50 or 60 Hz component of the phase-to-phase voltages (according to voltage sensors): c U21 voltage between phases 2 and 1, c U32 voltage between phases 3 and 2, c U13 voltage between phases 1 and 3. It is based on measurement of the fundamental component. Readout The measurements may be accessed via: c c c c
(1)

Characteristics measurement range unit accuracy


(2)

0.05 to 1.2 Unp V or kV

(1) (3)

display format refresh period


(1)

1% from 0.5 to 1.2 Unp 2% from 0.05 to 0.5 Unp 3 significant digits 1 second (typical)

Un rated voltage. (2) at Un, in reference conditions (IEC 60255-6). (3) 1 V resolution.

the display (1) using the key, the screen of a PC with SFT 2841 software, the communication link, analog converter with the MSA 141 option.
Sepam equipped with advanced UMI option.

Positive sequence voltage


Operation This function gives the calculated positive sequence voltage value. Readout The measurements may be accessed via: c the display (1) using the key, c the screen of a PC with SFT 2841 software, c the communication link.
(1)

Characteristics measurement range unit accuracy display format


(1)

0.05 to 1.2 Vnp (1) V or kV 5% at Vnp 3 significant digits

Un rated voltage.

Sepam equipped with advanced UMI option.

Phase-to-neutral voltages
Operation This function gives the RMS value of the 50 or 60 Hz component of the phase-to-neutral voltages: c V1 phase-to-neutral voltage of phase 1, c V2 phase-to-neutral voltage of phase 2, c V3 phase-to-neutral voltage of phase 3, It is based on measurement of the fundamental component. Readout The measurements may be accessed via: c c c c
(1)

Characteristics measurement range unit accuracy


(2)

0.05 to 1.2 Vnp (1) (3) V or kV 1% from 0.5 to 1.2 Vnp 2% from 0.05 to 0.5 Vnp 3 significant digits 1 second (typical)

display format refresh period


Un rated voltage. (2) at Vnp, in reference conditions (IEC 60255-6). (3) 1 V or 1 digit resolution.
(1)

the display (1) using the key, the screen of a PC with SFT 2841 software, the communication link, analog converter with the MSA 141 option.
Sepam equipped with advanced UMI option.

24

Sepam 1000+

Residual voltage
Operation This function gives the residual voltage value Vo = (V1 + V2 + V3). Vo is measured: c by taking the internal sum of the 3 phase voltages, c by a star / open delta VT. It based on measurement of the fundamental component. Readout The measurement may be accessed via: c the display (1) using the key, c the screen of a PC with SFT 2841 software, c the communication link,
(1)

Characteristics measurement range unit accuracy 0.015 Un to 3 Vnp V or kV 1% from 0.5 to 3 Vnp 2% from 0.05 to 0.5 Vnp 5% from 0.015 to 0.05 Vnp 3 significant digits 1 V, 1 digit 1 second (typical)
(1)

display format resolution refresh period


(1)

Vnp: rated primary phase-to-neutral voltage (Vnp = Unp/e).

Sepam equipped with advanced UMI option.

Frequency
Operation This function gives the frequency value. The frequency is measured using one of the following methods: c from U21 if only one phase-to-phase voltage is wired to the Sepam 1000 +, c from the positive sequence voltage if the Sepam includes U21 and U32 measurements. The frequency is not measured if: c the U21 voltage or Vd positive sequence voltage is less than 40% of Un, c the frequency is outside the measurement range. Readout The measurements may be accessed via: c c c c
(1)

Characteristics rated frequency range (2) accuracy


(1)

50 Hz, 60 Hz 50 Hz 60 Hz 45 Hz to 55 Hz 55 Hz to 65 Hz 0.05 Hz 3 significant digits 1 second (typical)

display format refresh period


(1) (2)

at Un, in reference conditions (IEC 60255-6). 0.01 Hz resolution.

the display (1) using the key, the screen of a PC with SFT 2841 software, the communication link, analog converter with the MSA 141 option.
Sepam equipped with advanced UMI option.

Sepam 1000+

25

Diagnosis functions

Tripping currents
Operation This function gives the RMS current values at the prospective tripping time: c TRIP1: phase 1 current, c TRIP2: phase 2 current, c TRIP3: phase 3 current, c TRIP0: residual current. It is based on measurement of the fundamental component.
I TRIP 1

Characteristics measurement range accuracy display format unit


(1)

phase current residual current

0.1 to 40 In

(1) (1)

0.1 to 20 Ino 5% 1 digit

3 significant digits A or kA

In, Ino rated current defined when the general parameters are set.

trip order 30 ms T0

This measurement is defined as the maximum RMS value measured during a 30 ms interval after the activation of the tripping contact on O1 output.

Readout The measurements may be accessed via: c the display (1) using the key, c the screen of a PC with SFT 2841 software, c the communication link.
(1)

Sepam equipped with advanced UMI option.

Unbalance ratio / negative sequence current


Operation This function gives the unbalance ratio according to negative sequence current: c T = Ii/Ib, The negative sequence current is determined according to the phase currents, c 3 phases 1 Ii = x (I1 + a2 I2 + a I3) 3 2 j with a = e 3 c 2 phases 1 Ii = x (I1 - a 2 I3) e with a = e j 2 3

Characteristics measurement range (1) unit accuracy display format refresh period
(1)

10 to 500 % Ib 2% 3 significant digits 1 second (typical)

1% resolution.

the two formulas are equivalent when there are no earth faults. Readout The measurements may be accessed via: c the display (1) using the key, c the screen of a PC with SFT 2841 software, c the communication link.
(1)

Sepam equipped with advanced UMI option.

26

Sepam 1000+

Starting current and time / overload


The starting time / overload is the period between the time at which one of the 3 phase currents exceeds 1.2 Ib and the time at which the 3 currents drop back below 1.2 Ib. The maximum phase current obtained during this period is the starting current / overload. Both these values are saved in the case of an auxiliary power failure.

Starting time / overload characteristics measurement range unit resolution display format refresh period 0 to 300 s s or ms 10 ms or 1 digit 3 significant digits 1 second (typical)

Starting current / overload characteristics measurement range unit 1.2 Ib to 24 In (1) A or kA 0.1 A or 1 digit 3 significant digits 1 second (typical)

Readout The measurements may be accessed via: c the display(1) using the key, c the screen of a PC with SFT 2841 software, c the communication link.
(1)

resolution display format refresh period


(1)

or 65.5 kA.

Sepam equipped with advanced UMI.

Running hours counter / operating time


This counter provides the cumulative time during which the protected device (motor or transformer) is running. The initial value of the counter may be modified using the SFT 2841 software. The counter is saved every 4 hours. Readout The measurements may be accessed via: c the display (1) using the key, c the screen of a PC with SFT 2841 software, c the communication link.
(1)

Characteristics range unit

0 to 65535 hours

Sepam equipped with advanced UMI.

Sepam 1000+

27

Diagnosis functions (cont'd)

Disturbance recording
Operation This function is used to record analog signals and logical states. Storage of the record is initiated according by a triggering event. The stored record begins before the triggering event and continues afterwards. The record comprises the following information: c values sampled from the different signals, c date, c characteristics of the recorded channels. The files are recorded in FIFO (First In First Out) type shift storage: the oldest record is erased when a new record is triggered. Transfer Files may be transferred locally or remotely: c locally: using a PC which is connected to the pocket terminal connector and includes the SFT 2841 software package, c remotely: using a software package specific to the remote monitoring and control system. Display The signals are displayed from a record by means of the SFT 2826 software package.

Principle
stored record

time

triggering event (1)

Characteristics record duration record content x periods before the triggering event (1) total 86 periods set-up file: date, channel characteristics, measuring transformer ratio, sample file 12 values per period/recorded signal 4 current channels (I1, I2, I3, Io) 4 voltage channels (V1, V2, V3, Vo) 10 digital inputs 2 COMTRADE 97

analog signals recorded (2) logical signals number of stored records file format
(1) (2)

according to parameter setting with SFT2841 (default setting 36 cycles). according to sensor type and connection.

28

Sepam 1000+

Cumulative breaking current and number of operations


Operation This function indicates the cumulative breaking current in square kilo-amperes (kA) 2 for five current ranges. It is based on measurement of the fundamental component. The current ranges displayed are: c 0 < I < 2 In c 2 In < I < 5 In c 5 In < I < 10 In c 10 In < I < 40 In c I > 40 In This function also provides the total number of operations as well as the total cumulative breaking current in square kilo-amps. Please refer to the breaking device documentation regarding the use of this information. The function is activated by the trip order (relay O1). Each value is saved in the event of an auxiliary power failure.

Characteristics number of operations range breaking current (kA) 2 range unit accuracy
(1)

0 to 65535 0 to 65535 (kA)2 primary (kA) 2

(1)

10% 1 digit

at In, in reference conditions (IEC 60255-6).

Readout The measurements may be accessed via: c the display (1) using the key, c the screen of a PC with SFT 2841 software, c the communication link. The initial values may be entered using the SFT 2841 software to take into account the real state of a used breaking device.

Operating time
Operation This function gives the operating time of a breaking device (1) determined according to the opening order (relay O1) and the change of status of the device open position contact wired to input I11 (3). The value is saved in the event of an auxiliary power failure. Readout The measurement may be accessed via: c the display (2) using the key, c the screen of a PC with SFT 2841 software, c the communication link.
(1)

Characteristics measurement range unit accuracy display format 20 to 100 ms typically 1 ms 3 significant digits

Please refer to the breaking device documentation regarding the use of this information. Sepam equipped with advanced UMI. (3) Operational MES module.
(2)

Charging time
Operation This function gives the control charging time of the breaking device (1) determined according to the change of status of the device closed position contact and the end-of-control charging contact wired to inputs I12 and I24 (3) respectively. The value is saved in the event of an auxiliary power failure. Readout The measurement may be accessed via: c the display (2) using the key, c the screen of a PC with SFT 2841 software, c the communication link,
Please refer to the breaking device documentation regarding the use of this information. (2) Sepam equipped with advanced UMI. (3) Operational MES 114 module.
(1)

Characteristics measurement range unit accuracy display format 1 to 20 s 0.5 sec 3 significant digits

Sepam 1000+

29

Protection functions

Phase overcurrent
ANSI code 50-51 The phase overcurrent function comprises 4 independant elements divided into two groups of 2 elements called Group A and Group B respectively. The use of the two groups may be chosen by parameter setting: c operation with Group A or Group B exclusively, with switching from one group to the other dependent on the state of logic input I13 exclusively, or by remote control (TC3, TC4), I13 = 0 group A I13 = 1 group B c operation with Group A and Group B active for 4-set point operation, c enabling/disabling of each group of 2 elements (A, B). Operation Phase overcurrent protection is three-pole. It picks up when one, two or three of the phase currents reaches the operation set point. It is time-delayed. The time delay may be definite time (DT) or IDMT according to the curves opposite. Definite time protection Is is the set point express in amperes, and T is the protection operating time delay.

The Is setting is the vertical asymptote of the curve, and T is the operation time delay for 10Is. The tripping time for I/Is values less than 1.2 depends on the type of curve selected. curve designation standard inverse time (SIT) very inverse time (VIT or LTI) extremely inverse time (EIT) ultra inverse time (UIT) RI curve IEC SIT / A IEC VIT or LTI / B IEC EIT / C IEEE moderately inverse (IEC / D) IEEE very inverse (IEC / E) IEEE extremely inverse (IEC / F) IAC inverse IAC very inverse IAC extremely inverse type 1.2 1.2 1.2 1.2 1 1 1 1 1 1 1 1 1 1

The equations of these curves are given in the "IDMT protections" chapter, p. 56.

The function takes into account current variations during the time delay. For currents with a very large amplitude, the protection has a definite time characteristic: c if I > 20 Is, tripping time is the time that corresponds to 20 Is. c if I > 40 In, tripping time is the time that corresponds to 40 In. (In: current transformer rated current defined when the general parameters are set).

Block diagram
I1 I2 I3 Is I "pick-up" signal and to logic discrimination I > Is t 0 time-delayed output

Principe de la protection temps indpendant.

Time delayed reset The function includes an adjustable holding time T1: v definite time (timer hold) for all the tripping curves.
I > Is time-delayed output

IDMT protection IDMT protection operates in accordance with the IEC (60255-3), BS 142 standards, IEEE (C-37112).

type 1 t type 1,2

I > Is instantaneous

T value of internal time delay counter

tripping

1.2

10

20

I/Is

T1

T1

T1

IDMT protection principle.

30

Sepam 1000+

v IDMT (reset time) for the IEC, IEEE and IAC curves.
I > Is time-delayed output

I > Is signal pick-up

T value of internal time-delay counter

tripping

T1

Characteristics tripping curve setting Is set point setting resolution accuracy (1) pick-up/drop-out ratio setting resolution accuracy (1) definite time IDMT holding time T1 definite time (timer hold) IDMT (reset time) (3) characteristic times operating time 0; 0.05 to 300 s 0.5 to 300 s pick up < 35 ms at 2 Is (25 ms typical) confirmed instantaneous < 50 ms at 2 Is (35 ms typical) overshoot time reset time
(1)

definite time, IDMT: choice according to list opposite definite time IDMT 0.1 In Is 24 In expressed in amperes 0.1 In Is 2,4 In expressed in amperes 1 A or 1 digit 5% 93.5 % 5 % (with min. reset time diff. 0.015 In) inst, 50 ms T 300 s 100 ms T 12.5 s or TMS (2) 10 ms or 1 digit 2 % or from -10 ms +25 ms class 5 or from -10 ms to +25 ms

T time delay (operating time at 10 Is) definite time IDMT

< 35 ms < 50 ms (for T1 = 0)

in reference conditions (IEC 60255-6). (2) setting ranges in TMS mode (Time Multiplier Setting) Standard inverse (SIT) and IEC SIT/A: 0.04 to 4.20 Very inverse (VIT) and IEC VIT/B: 0.07 to 8.33 Long time inverse (LTI) and IEC LTI/B: 0.01 to 0.93 Extremely inverse (EIT) and IEC EIT/C: 0.13 to 15.47 IEEE moderately inverse: 0.42 to 51.86 IEEE very inverse: 0.73 to 90.57 IEEE extremely inverse: 1.24 to 154.32 IAC inverse: 0.34 to 42.08 IAC very inverse: 0.61 to 75.75 IAC extremely inverse: 1.08 to 134.4 (3) only for standardized tripping curves of the IEC, IEEE and IAC type.

Sepam 1000+

31

Protection functions (contd)

Earth fault
ANSI code 50N-51N or 50G-51G The earth fault function comprises 4 independant elements divided into two groups of 2 settings called Group A and Group B respectively. The use of the two elements may be chosen by parameter setting: c operation with Group A or Group B exclusively, with switching from one group to the other dependent on the state of logic input I13 exclusively, or by remote control (TC3, TC4), 13 = 0 group A 13 = 1 group B c operation with Group A and Group B active for 4-set point operation, c enabling/disabling of each group of 2 elements (A, B). Operation Earth fault protection is single-pole. It picks up when the earth fault current reaches the operation set point. It is time-delayed. The time delay may be definite time (DT) or IDMT according to the curves opposite. The protection integrates a 2nd harmonic restraint which provides greater stability when the transformers energize (measurement of residual current by the sum of the 3 phase CTs). The restraint inhibits tripping, whatever the fundamental current. The restraint may be inhibited by parameter setting. Definite time protection Is is the operating set point expressed in amperes, and T is the protection operation time delay.

The Iso setting is the vertical asymptote of the curve, and T is the operation time delay for 10Iso. The tripping time for I/Iso values less than 1.2 depends on the type of curve selected. curve designation standard inverse time (SIT) very inverse time (VIT or LTI) extremely inverse time (EIT) ultra inverse time (UIT) RI curve IEC SIT / A IEC VIT or LTI / B IEC EIT / C IEEE moderately inverse (IEC / D) IEEE very inverse (IEC / E) IEEE extremely inverse (IEC / F) IAC inverse IAC very inverse IAC extremely inverse type 1.2 1.2 1.2 1.2 1 1 1 1 1 1 1 1 1 1

The equations of these curves are given in the "IDMT protections" chapter, p. 56.

The function also takes into account current variations during the time delay. For currents with a very large amplitude, the protection has a definite time characteristic: c if I > 20 Iso, tripping time is the time that corresponds to 20 Iso, c if I > 15 Ino, tripping time is the time that corresponds to 15 Ino. (Ino: current transformer rated current defined when the general parameters are set). Block diagram
I1 I2

Io > Iso t

I3

"pick-up" signal and to logic discrimination 0 time-delayed output

CSH core balance CT

CT+CSH30 core balance CT + ACE 990

H2

Iso Definite time protection principle.

Io

Time delayed reset The function includes an adjustable holding time T1: v definite time (timer hold) for all the tripping curves.
I > Iso time-delayed output

IDMT protection IDMT protection operates in accordance with the IEC 60255-3,BS 142 standards, and IEEE (C-37112).
type 1 t type 1,2

I > Iso instantaneous

T value of internal time delay counter

tripping

1.2

10

20

I/Is

T1

T1

T1

IDMT protection principle.

32

Sepam 1000+

v IDMT (reset time) for the IEC, IEEE and IAC curves.
I > Is time-delayed output

I > Is signal pick-up

T value of internal time-delay counter

tripping

T1

Characteristics tripping curve setting Iso set point definite time setting sum of CTs
(1)

definite time, IDMT: choice according to list opposite 0.1 Ino i Iso i 15 Ino expressed in amperes 0.1 Ino i Iso i 15 Ino 0.2 A to 30 A 2 A to 300 A 0.1 Ino i Iso i 15 Ino (min. 0.1 A) 0.1 Ino < Iso < 15 Ino 0.1 Ino i Iso i Ino sum of CTs
(1) (1)

with CSH sensor 2 A rating 20 A rating CT + CSH30 core bal. CT with ACE 990 IDMT setting with CSH sensor 2 A rating 20 A rating CT + CSH30 core bal. CT with ACE 990 resolution accuracy
(2)

expressed in amperes

0,1 In i Iso i Ino 0.2 A to 2 A 2 A to 20 A 0.1 Ino i Iso i 1 Ino (min. 0.1 A) 0.1 Ino i Iso i Ino 0.1 A or 1 digit 5% 93.5% 5% for Iso > 0.1 Ino 17% inst., 50 ms i T i 300 s 100 ms i T i 12.5 s 10 ms or 1 digit 2% or from -10 ms to +25 ms class 5 or from -10 ms to +25 ms 0; 0.05 to 300 s 0.5 to 300 s pick up < 35 ms at 2 Iso (25 ms typical) confirmed instantaneous < 50 ms at 2 Iso (35 ms typical)

pick-up/drop-out ratio 2nd harmonic restraint fixed set point setting


(1)

T time delay (operating time at 10 Iso) definite time IDMT (3)


(2)

Ino = In if the sum of the three phase currents is used for the measurement. Ino = sensor rating if the measurement is taken by a CSH core balance CT. Ino = In of the CT if the measurement is taken by a 1 A or 5 A current transformer. (2) setting ranges in TMS mode (Time Multiplier Setting) Standard inverse (SIT) and IEC SIT/A: 0.04 to 4.20 Very inverse (VIT) and IEC VIT/B: 0.07 to 8.33 Long time inverse (LTI) and IEC LTI/B: 0.01 to 0.93 Extremely inverse (EIT) and IEC EIT/C: 0.13 to 15.47 IEEE moderately inverse: 0.42 to 51.86 IEEE very inverse: 0.73 to 90.57 IEEE extremely inverse: 1.24 to 154.32 IAC inverse: 0.34 to 42.08 IAC very inverse: 0.61 to 75.75 IAC extremely inverse: 1.08 to 134.4 (3) only for standardized tripping curves of the IEC, IEEE and IAC type.

resolution accuracy definite time IDMT holding time T1 definite time (timer hold) IDMT (reset time) characteristic times operating time

overshoot time reset time

< 35 ms < 40 ms (for T1 = 0)

Sepam 1000+

33

Protection functions (contd)

Negative sequence / unbalance


ANSI code 46

The tripping curve is defined according to the following equations: c for Is/Ib i Ii/Ib i 0.5 t= 3.19 (Ii/Ib)1.5 .T

c for 0.5 i Ii/Ib i 5 Operation Negative sequence / unbalance protection: c picks up when the negative sequence component of the phase currents is greater than the set point, c it is time-delayed. The time delay may be definite or IDMT time (see curve). The negative sequence current Ii is calculated for the 3 phase currents: t= 4.64 (Ii/Ib)0.96 .T

c for Ii/Ib > 5 t=T The function also takes into account negative sequence current variations during the time delay. The negative sequence current ratio measurement, expressed as a percentage of the basis current, is available even if the protection is inhibited.

Ii =

1 3

x (I1 + a 2 I2 + a I3)

2 with a = e j 3 If Sepam is connected to 2 phase current sensors only, the negative sequence current is:

Block diagram
I1 I2 Ii > Is t 0 time-delayed output pick-up signal

Ii = 1 x (I1 - a 2 I3) e with a = e j 3 2

I3

the two formulas are equivalent when there is no residual current (earth fault). Definite time delay
t

Characteristics curve setting Is set point setting resolution definite time IDMT
(1)

definite, IDMT 10% Ib i Is i 500% Ib 10% Ib i Is i 50% Ib 1% 5% definite time IDMT 100 ms i T i 300 s 100 ms i T i 1 s 10 ms or 1 digit definite time IDMT 2% or 25 ms 5% or 35 ms 93.5% 5% < 55 ms pick up < 35 ms < 55 ms

accuracy setting
Is Ii

T time delay (operation time at 5 Ib)

Definite time protection.

resolution accuracy
(1)

For Ii > Is, the time delay is definite (independent of Ii) and equal to T. IDMT time delay For Ii > Is, the time delay depends on the value of Ii/Ib (Ib: basis current of the protected equipment defined when the general parameters are set) T corresponds to the time delay for Ii/Ib = 5.
t

pick-up/drop-out ratio characteristic times operating time overshoot time reset time
(1)

in reference conditions (IEC 60255-6).

Is IDMT protection.

5Ib

Ii

34

Sepam 1000+

Determination of tripping time for different negative sequence current values for a given curve Using the chart, the user finds the value of K that corresponds to the desired negative sequence current. The tripping time is equal to KT. Example Given a tripping curve with the T setting = 0.5 s. What is the tripping time at 0.6 Ib? Using the chart, find the value of K that corresponds to 60% of Ib. The chart gives K = 7.55. The tripping time is equal to: 0.5 x 7.55 = 3.755 s.

IDMT tripping curve


t(s) 10000 5000 2000 1000 500 200 100 50 20 max. curve (T=1s) 10 5 2 1 0.5 0.2 0.1 0.05 0.02 0.01 0.005 0.002 0.001 0.05 0.1 0.2 0.3 0.5 0.7 1 2 3 5 7 10 I/Ib 20 min. curve (T=0,1s)

Ii (% Ib) K

10 99.95

15 54.50 85 5.42 230 2.10 390 1.267

20 35.44 90 5.13 240 2.01 400 1.236

25

30

33.33 16.51 110 4.24 270 1.80 430 1.154

35

40

45 10.53 140 3.37 300 1.627 460 1.082

50 9.00 150 3.15 310

55 8.21 160 2.96 320

57.7 7.84 170 2.80 330 1.485 490 1.02

60 7.55 180 2.65 340 1.444 500 1

65 7.00 190 2.52 350

70 6.52 200 2.40 360

75 6.11 210 2.29 370 1.332

25.38 19.32 95 4.87 250 1.94 410 1.18 100 4.64 260 1.86 420 1.167

15.34 12.56 120 3.90 280 1.74 440 1.13 130 3.61 290 1.68 450 1.105

Ii (% Ib) cont'd 80 K cont'd 5.74

Ii (% Ib) cont'd 220 K cont'd 2.14

1.577 1.53 470 1.06 480 1.04

1.404 1.367

Ii (% Ib) cont'd 380 K cont'd 1.298

Sepam 1000+

35

Protection functions (contd)

Thermal overload
ANSI code 49 This function is used to protect equipment (motors, transformers, generators, lines, capacitors) against overloads, based on measurement of the current consumed.

effective when the machine is running than when it is stopped. Running and stopping of the equipment are calculated from the value of the current: c running if I > 0.1 Ib, c stopped if I < 0.1 Ib. Two time constants may be set: c T1: heat rise time constant: concerns equipment that is running, c T2: cooling time constant: concerns equipment that is stopped. Accounting for harmonics The current measured by the thermal protection is an RMS 3-phase current which takes into account harmonics up to number 17. Accounting for ambient temperature Most machines are designed to operate at a maximum ambient temperature of 40. The thermal overload function takes into account the ambient temperature (Sepam 1000+ equipped with the temperature sensor option (1)) to increase the calculated heat rise value when the temperature measured exceeds 40. Increase factor: fa = T max - 40 T max - T ambient

Operation
Operation curve The protection gives a trip order when the heat rise E, calculated according to the measurement of an equivalent current Ieq, is greater than the set point Es. The greatest permissible continuous current is I = Ib Es The protection tripping time is set by the time constant T. The calculated heat rise depends on the current consumed and the previous heat rise state. c The cold curve defines the protection tripping time based on zero heat rise. c The hot curve defines the protection tripping time based on 100% nominal heat rise.

T max is the machines maximum temperature. T ambient is the measured temperature.

Adaptation of the protection to motor thermal withstand Motor thermal protection is often set based on the hot and cold curves supplied by the machine manufacturer. To fully comply with these experimental curves, additional parameters must be set: c initial heat rise, Eso, is used to reduce the cold tripping time.

leq 2 - Eso t modified cold curve: = Log Ib 2 T leq Ib - Es


c a second group of parameters (time constants and set points) is used to take into account thermal withstand with locked rotors. This second set of parameters is taken into account when the current is greater than an adjustable set point Is. Accounting for negative sequence current In the case of motors with coiled rotors, the presence of a negative sequence component increases the heat rise in the motor. The negative sequence component of the current is taken into account in the protection by the equation leq = Iph + K. Ii
2 2

101 10
0

cold curve

10-1 10-2 10-3 0 hot curve

leq 2 t Ib = Log T leq 2 Ib - Es leq 2 -1 t = Log Ib 2 T leq Ib - Es

10

in

which Iph is the greatest phase current Ii is the negative sequence component of the current K is an adjustable factor

Alarm set point, tripping set point Two set points may be set for heat rise: c Es1: alarm. c Es2: tripping. Hot state set point When the function is used to protect a motor, this fixed set point is designed for detection of the hot state used by the number of starts function. Heat rise and cooling time constants For self-ventilated rotating machines, cooling is more
E 1 0.63 0.36 0 T1 Heat rise time constant. 0 E 1

K may have the following values: 0 - 2.25 - 4.5 - 9 For an asynchronous motor, K is determined as follows: k = 2. Cd . Cn 1 g. Id Ib
2

-1 in Cn, Cd: rated torque and starting torque Ib, Id: basis current and starting current g: rated slip

T2 Cooling time constant.

(1)

MET148 module, RTC 8 predefined for ambient temperature measurement.

36

Sepam 1000+

Start inhibit The thermal overload protection can inhibit the closing of the motors control device until the heat rise drops back down below a value that allows restarting. This value takes into account the heat rise produced by the motor when starting. The inhibition function is grouped together with the starts per hour protection and the indication START INHIBIT informs the user. Saving of heat rise When the protection trips, the current heat rise, increased by 10 %(1), is saved. The saved value is reset to zero when the heat rise decreases sufficiently for the time before starting to be zero. The saved value is used when the power returns after a Sepam power failure, so as to start up again with the heat rise that triggered tripping.
(1)

Characteristics set points setting Es1 alarm set point Es2 tripping set point Eso initial heat rise group A 50% to 300% 50% to 300% 0 to 100% 1% 1 mn to 120 mn 5 mn to 600 mn 1 mn group B 50% to 300% 50% to 300% 0 to 100% 1% 1 mn to 120 mn 5 mn to 600 mn 1 mn

resolution time constants setting resolution setting setting resolution tripping time accuracy
(1)

T1 running (heat rise) T2 stopped (cooling)

accounting for negative sequence component K 0 2.25 4.5 9 maximum equipment temperature (insulation class) Tmax 60 to 200 1 2% range 0% to 800% 0 to 999 mn 0 to 999 mn 0.25 to 8 Ib I26 resolution 1% 1 mn 1 mn

increasing by 10 % makes it possible to take into account the average heat rise of motors when starting.

Inhibition of tripping Tripping of the thermal overload protection may be inhibited by logic input I26 (according to parameter setting) when required by the process. Accounting for two operating rates A power transformer often has two operating modes (e.g. ONAN and ONAF). The two groups of parameters in the thermal overload protection take into account these two operating modes. Switching from one mode to the other is controlled by a logic input I26 (according to parameter setting). It is done without losing the heat rise value. User information The following information is available for the user: c time before restart enabled (in case of inhibition of starting), c time before tripping (with constant current), c heat rise.

measurements heat rise time before tripping time before start enabled change of setting parameters by current threshold for motor setting by digital input for transformer
(1)

In reference conditions (IEC 60255-8).

Block diagram

input I26 leq > Is

selection of parameter group Is Es1 Es2 T Eso E > Es1 leq . t t - Ek-1. Ib T T T max
2

K I ph I inverse calculation of equivalent current heat rise : leq Ek = Ek-1 +

fa E > Es2 input I26

alarm indication

& tripping indication

ambient temperature

correction by ambient temperature

inhibit start inhibit closing indication

Sepam 1000+

37

Protection functions (contd)

Example of thermal overload settings for a motor


Example 1
The following data are available: c time constants for on operation T1 and off operation T2: v T1 = 25 min, v T2 = 70 min. c maximum curve in steady state: Imax/Ib = 1.05. Setting of tripping set point Es2 Es2 = (Imax/Ib) 2 = 110% Please note: if the motor absorbs a current of 1.05 Ib in steady state, the heat rise calculated by the thermal overload protection will reach 110%. Setting of alarm set point Es1 Es1 = 90% (I/Ib = 0.95). Knegative: 4.5 (usual value) The other thermal overload parameters do not need to be set. They are not taken into account by default.

For an overload of 2*Ib, the value t/T1 = 0.0339 (2) is obtained. In order for Sepam to trip at the point 1 (t = 70 s), T1 is equal to 2065 sec 34 min. With a setting of T1 = 34 min, the tripping time is obtained based on a cold state (point 2). In this case, it is equal to t/T1 = 0.3216 t 665 sec, i.e. 11 min, which is compatible with the thermal resistance of the motor when cold. The negative sequence factor is calculated using the equation defined on page 34. The parameters of the second thermal overload relay do not need to be set. They are not taken into account by default.

Example 3
The following data are available: c motor thermal resistance in the form of hot and cold curves (see solid line curves in Figure 1), c cooling time constant T2, c maximum steady state current: Imax/Ib = 1.1. Setting of tripping set point Es2 Es2 = (Imax/Ib)2 = 120% Setting of alarm set point Es1 Es1 = 90% (I/Ib = 0.95). The time constant T1 is calculated so that the thermal overload protection trips after 100 s (point 1). With t/T1 = 0.069 (I/Ib = 2 and Es2 = 120%): T1 = 100s / 0.069 = 1449 sec 24 min. The tripping time starting from the cold state is equal to: t/T1 = 0.3567 t = 24 min*0.3567 = 513 s (point 2). This tripping time is too long since the limit for this overload current is 400 s (point 2). If the time constant T1 is lowered, the thermal overload protection will trip earlier, below point 2. There risk that motor starting when hot will not be possible also exists in this case (see Figure 2 in which a lower Sepam hot curve would intersect the starting curve with U = 0.9 Un). The Es0 parameter is a setting that is used to solve these differences by lowering the Sepam cold curve without moving the hot curve. In this example, the thermal overload protection should trip after 400 s starting from the cold state.

Example 2
The following data are available: c motor thermal resistance in the form of hot and cold curves (see solid line curves in Figure 1), c cooling time constant T2, c maximum steady state current: Imax/Ib = 1.05. Setting of tripping set point Es2 Es2 = (Imax/Ib) 2 = 110% Setting of alarm set point Es1: Es1 = 90% (I/Ib = 0.95). The manufacturers hot/cold curves (1) may be used to determine the heating time constant T1.

Figure 1: motor thermal resistance and thermal overload tripping curves

The following equation is used to obtain the Es0 value:


2

t necessary e
T1

motor cold curve Sepam cold curve time before tripping/s 665

E S0 =

I processed Ib

I processed Ib

E S2

with:
2

motor hot curve

t necessary: tripping time necessary starting from a cold state.


Sepam hot curve

70

I processed: equipment current.

1.05

I/Ib

(1) When the machine manufacturer provides both a time constant T1 and the machine hot/cold curves, the use of the curves is recommended since they are more accurate.

(2) The charts containing the numerical values of the Sepam hot curve may be used, or else the equation of the curve which is given on page 34.

38

Sepam 1000+

In numerical values, the following is obtained:


400 sec

E S0 = 4 e 24*60 sec . 4 1.2

= 0.3035

31%

Use of the additional setting group When a motor rotor is locked or is turning very slowly, its thermal behavior is different from that with the rated load. In such conditions, the motor is damaged by overheating of the rotor or stator. For high power motors, rotor overheating is most often a limiting factor. The thermal overload parameters chosen for operation with a low overload are no longer valid. In order to protect the motor in this case, excessive starting time protection may be used. Nevertheless, motor manufacturers provide the thermal resistance curves when the rotor is locked, for different voltages at the time of starting.

By setting Es0 = 31%, point 2 is moved downward to obtain a shorter tripping time that is compatible with the motors thermal resistance when cold (see Figure 3). Please note: A setting Es0 = 100% therefore means that the hot and cold curves are the same.

Figure 2: hot/cold curves not compatible with the motors thermal resistance

Figure 4: Locked rotor thermal resistance


motor running locked rotor

Sepam cold curve motor cold curve times / s motor hot curve 1

time before tripping/s

513 400

2 2

100

Sepam hot curve

3 2

starting at Un starting at 0.9*Un 1.05 2 I/Ib 1.1 2 Is

6 I/Ib

1 : thermal resistance, motor running 2 : thermal resistance, motor stopped 3 : Sepam tripping curve

Figure 3: hot/cold curves compatible with the motors thermal resistance via the setting of an initial heat rise Es0

4 : starting at 65% Un 5 : starting at 80% Un 6 : starting at 100% Un

adjusted Sepam cold curve time before tripping/s motor cold curve 400
2

In order to take these curves into account, the second thermal overload relay may be used. The time constant in this case is, in theory, the shortest one: however, it should not be determined in the same way as that of the first relay. The thermal overload protection switches between the first and second relay if the equivalent current Ieq exceeds the Is value (set point current).

motor hot curve

100

Sepam hot curve

starting at Un starting at 0.9*Un 1.1 2 I/Ib

Sepam 1000+

39

Protection functions (contd)

Cold curves for Eso = 0


I/Ib Es (%) 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 145 150 155 160 165 170 175 180 185 190 195 200 1.00 0.6931 0.7985 0.9163 1.0498 1.2040 1.3863 1.6094 1.8971 2.3026 1.05 1.10 1.15 0.4749 0.5376 0.6046 0.6763 0.7535 0.8373 0.9287 1.0292 1.1411 1.2670 1.4112 1.5796 1.7824 2.0369 2.3792 2.9037 1.20 0.4265 0.4812 0.5390 0.6004 0.6657 0.7357 0.8109 0.8923 0.9808 1.0780 1.1856 1.3063 1.4435 1.6025 1.7918 2.0254 2.3308 2.7726 1.25 1.30 1.35 0.3207 0.3592 0.3993 0.4411 0.4847 0.5302 0.5780 0.6281 0.6809 0.7366 0.7956 0.8583 0.9252 0.9970 1.0742 1.1580 1.2493 1.3499 1.4618 1.5877 1.7319 1.9003 2.1030 2.3576 2.6999 3.2244 1.40 1.45 1.50 0.2513 0.2803 0.3102 0.3409 0.3727 0.4055 0.4394 0.4745 0.5108 0.5486 0.5878 0.6286 0.6712 0.7156 0.7621 0.8109 0.8622 0.9163 0.9734 1.0341 1.0986 1.1676 1.2417 1.3218 1.4088 1.5041 1.6094 1.7272 1.8608 2.0149 2.1972 1.55 1.60 1.65 0.2029 0.2257 0.2490 0.2728 0.2972 0.3222 0.3479 0.3743 0.4013 0.4292 0.4578 0.4872 0.5176 0.5489 0.5812 0.6146 0.6491 0.6849 0.7220 0.7606 0.8007 0.8424 0.8860 0.9316 0.9793 1.0294 1.0822 1.1379 1.1970 1.2597 1.3266 1.70 1.75 1.80 0.1676 0.1860 0.2048 0.2239 0.2434 0.2633 0.2836 0.3043 0.3254 0.3470 0.3691 0.3917 0.4148 0.4384 0.4626 0.4874 0.5129 0.5390 0.5658 0.5934 0.6217 0.6508 0.6809 0.7118 0.7438 0.7768 0.8109 0.8463 0.8829 0.9209 0.9605

0.6042 0.5331 0.6909 0.6061 0.7857 0.6849 0.8905 0.7704 1.0076 0.8640 1.1403 0.9671 1.2933 1.0822 1.4739 1.2123 1.6946 1.3618 1.9782 1.5377 2.3755 1.7513 3.0445 2.0232 2.3979 3.0040

0.3857 0.3508 0.4339 0.3937 0.4845 0.4386 0.5379 0.4855 0.5942 0.5348 0.6539 0.5866 0.7174 0.6413 0.7853 0.6991 0.8580 0.7605 0.9365 0.8258 1.0217 0.8958 1.1147 0.9710 1.2174 1.0524 1.3318 1.1409 1.4610 1.2381 1.6094 1.3457 1.7838 1.4663 1.9951 1.6035 2.2634 1.7626 2.6311 1.9518 3.2189 2.1855 2.4908 2.9327

0.2945 0.2716 0.3294 0.3033 0.3655 0.3360 0.4029 0.3698 0.4418 0.4049 0.4823 0.4412 0.5245 0.4788 0.5686 0.5180 0.6147 0.5587 0.6630 0.6012 0.7138 0.6455 0.7673 0.6920 0.8238 0.7406 0.8837 0.7918 0.9474 0.8457 1.0154 0.9027 1.0885 0.9632 1.1672 1.0275 1.2528 1.0962 1.3463 1.1701 1.4495 1.2498 1.5645 1.3364 1.6946 1.4313 1.8441 1.5361 2.0200 1.6532 2.2336 1.7858 2.5055 1.9388 2.8802 2.1195 3.4864 2.3401 2.6237 3.0210

0.2333 0.2173 0.2600 0.2419 0.2873 0.2671 0.3155 0.2929 0.3444 0.3194 0.3742 0.3467 0.4049 0.3747 0.4366 0.4035 0.4694 0.4332 0.5032 0.4638 0.5383 0.4953 0.5746 0.5279 0.6122 0.5616 0.6514 0.5964 0.6921 0.6325 0.7346 0.6700 0.7789 0.7089 0.8253 0.7494 0.8740 0.7916 0.9252 0.8356 0.9791 0.8817 1.0361 0.9301 1.0965 0.9808 1.1609 1.0343 1.2296 1.0908 1.3035 1.1507 1.3832 1.2144 1.4698 1.2825 1.5647 1.3555 1.6695 1.4343 1.7866 1.5198

0.1900 0.1782 0.2111 0.1980 0.2327 0.2181 0.2548 0.2386 0.2774 0.2595 0.3005 0.2809 0.3241 0.3028 0.3483 0.3251 0.3731 0.3480 0.3986 0.3714 0.4247 0.3953 0.4515 0.4199 0.4790 0.4450 0.5074 0.4708 0.5365 0.4973 0.5666 0.5245 0.5975 0.5525 0.6295 0.5813 0.6625 0.6109 0.6966 0.6414 0.7320 0.6729 0.7686 0.7055 0.8066 0.7391 0.8461 0.7739 0.8873 0.8099 0.9302 0.8473 0.9751 0.8861 1.0220 0.9265 1.0713 0.9687 1.1231 1.0126 1.1778 1.0586

40

Sepam 1000+

Cold curves for Eso = 0


I/Ib Es (%) 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 145 150 155 160 165 170 175 180 185 190 195 200 1.85 1.90 1.95 0.1410 0.1562 0.1717 0.1875 0.2035 0.2197 0.2362 0.2530 0.2701 0.2875 0.3051 0.3231 0.3415 0.3602 0.3792 0.3986 0.4184 0.4386 0.4591 0.4802 0.5017 0.5236 0.5461 0.5690 0.5925 0.6166 0.6413 0.6665 0.6925 0.7191 0.7465 2.00 0.1335 0.1479 0.1625 0.1773 0.1924 0.2076 0.2231 0.2389 0.2549 0.2712 0.2877 0.3045 0.3216 0.3390 0.3567 0.3747 0.3930 0.4117 0.4308 0.4502 0.4700 0.4902 0.5108 0.5319 0.5534 0.5754 0.5978 0.6208 0.6444 0.6685 0.6931 2.20 2.40 2.60 0.0768 0.0849 0.0929 0.1011 0.1093 0.1176 0.1260 0.1344 0.1429 0.1514 0.1601 0.1688 0.1776 0.1865 0.1954 0.2045 0.2136 0.2228 0.2321 0.2414 0.2509 0.2604 0.2701 0.2798 0.2897 0.2996 0.3096 0.3197 0.3300 0.3403 0.3508 2.80 3.00 3.20 0.0501 0.0552 0.0604 0.0656 0.0708 0.0761 0.0813 0.0867 0.092 0.0974 0.1028 0.1082 0.1136 0.1191 0.1246 0.1302 0.1358 0.1414 0.147 0.1527 0.1584 0.1641 0.1699 0.1757 0.1815 0.1874 0.1933 0.1993 0.2052 0.2113 0.2173 3.40 3.60 3.80 0.0352 0.0388 0.0424 0.0461 0.0497 0.0533 0.0570 0.0607 0.0644 0.0681 0.0718 0.0755 0.0792 0.0830 0.0868 0.0905 0.0943 0.0982 0.1020 0.1058 0.1097 0.1136 0.1174 0.1213 0.1253 0.1292 0.1331 0.1371 0.1411 0.1451 0.1491 4.00 4.20 4.40 0.0262 0.0288 0.0315 0.0342 0.0368 0.0395 0.0422 0.0449 0.0476 0.0503 0.0530 0.0558 0.0585 0.0612 0.0640 0.0667 0.0695 0.0723 0.0751 0.0778 0.0806 0.0834 0.0863 0.0891 0.0919 0.0947 0.0976 0.1004 0.1033 0.1062 0.1090 4.60 0.0239 0.0263 0.0288 0.0312 0.0336 0.0361 0.0385 0.0410 0.0435 0.0459 0.0484 0.0509 0.0534 0.0559 0.0584 0.0609 0.0634 0.0659 0.0685 0.0710 0.0735 0.0761 0.0786 0.0812 0.0838 0.0863 0.0889 0.0915 0.0941 0.0967 0.0993

0.1579 0.1491 0.1752 0.1653 0.1927 0.1818 0.2106 0.1985 0.2288 0.2156 0.2474 0.2329 0.2662 0.2505 0.2855 0.2685 0.3051 0.2868 0.3251 0.3054 0.3456 0.3244 0.3664 0.3437 0.3877 0.3634 0.4095 0.3835 0.4317 0.4041 0.4545 0.4250 0.4778 0.4465 0.5016 0.4683 0.5260 0.4907 0.5511 0.5136 0.5767 0.5370 0.6031 0.5610 0.6302 0.5856 0.6580 0.6108 0.6866 0.6366 0.7161 0.6631 0.7464 0.6904 0.7777 0.7184 0.8100 0.7472 0.8434 0.7769 0.8780 0.8075

0.1090 0.0908 0.1206 0.1004 0.1324 0.1100 0.1442 0.1197 0.1562 0.1296 0.1684 0.1395 0.1807 0.1495 0.1931 0.1597 0.2057 0.1699 0.2185 0.1802 0.2314 0.1907 0.2445 0.2012 0.2578 0.2119 0.2713 0.2227 0.2849 0.2336 0.2988 0.2446 0.3128 0.2558 0.3270 0.2671 0.3414 0.2785 0.3561 0.2900 0.3709 0.3017 0.3860 0.3135 0.4013 0.3254 0.4169 0.3375 0.4327 0.3498 0.4487 0.3621 0.4651 0.3747 0.4816 0.3874 0.4985 0.4003 0.5157 0.4133 0.5331 0.4265

0.0659 0.0572 0.0727 0.0631 0.0796 0.069 0.0865 0.075 0.0935 0.081 0.1006 0.087 0.1076 0.0931 0.1148 0.0992 0.1219 0.1054 0.1292 0.1116 0.1365 0.1178 0.1438 0.1241 0.1512 0.1304 0.1586 0.1367 0.1661 0.1431 0.1737 0.1495 0.1813 0.156 0.1890 0.1625 0.1967 0.1691 0.2045 0.1757 0.2124 0.1823 0.2203 0.189 0.2283 0.1957 0.2363 0.2025 0.2444 0.2094 0.2526 0.2162 0.2608 0.2231 0.2691 0.2301 0.2775 0.2371 0.2860 0.2442 0.2945 0.2513

0.0442 0.0393 0.0487 0.0434 0.0533 0.0474 0.0579 0.0515 0.0625 0.0555 0.0671 0.0596 0.0717 0.0637 0.0764 0.0678 0.0811 0.0720 0.0858 0.0761 0.0905 0.0803 0.0952 0.0845 0.1000 0.0887 0.1048 0.0929 0.1096 0.0972 0.1144 0.1014 0.1193 0.1057 0.1242 0.1100 0.1291 0.1143 0.1340 0.1187 0.1390 0.1230 0.1440 0.1274 0.1490 0.1318 0.1540 0.1362 0.1591 0.1406 0.1641 0.1451 0.1693 0.1495 0.1744 0.1540 0.1796 0.1585 0.1847 0.1631 0.1900 0.1676

0.0317 0.0288 0.0350 0.0317 0.0382 0.0346 0.0415 0.0375 0.0447 0.0405 0.0480 0.0434 0.0513 0.0464 0.0546 0.0494 0.0579 0.0524 0.0612 0.0554 0.0645 0.0584 0.0679 0.0614 0.0712 0.0644 0.0746 0.0674 0.0780 0.0705 0.0813 0.0735 0.0847 0.0766 0.0881 0.0796 0.0916 0.0827 0.0950 0.0858 0.0984 0.0889 0.1019 0.0920 0.1054 0.0951 0.1088 0.0982 0.1123 0.1013 0.1158 0.1045 0.1193 0.1076 0.1229 0.1108 0.1264 0.1140 0.1300 0.1171 0.1335 0.1203

Sepam 1000+

41

Protection functions (contd)

Cold curves for Eso = 0


I/Ib Es (%) 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 145 150 155 160 165 170 175 180 185 190 195 200 4.80 0.0219 0.0242 0.0264 0.0286 0.0309 0.0331 0.0353 0.0376 0.0398 0.0421 0.0444 0.0466 0.0489 0.0512 0.0535 0.0558 0.0581 0.0604 0.0627 0.0650 0.0673 0.0696 0.0720 0.0743 0.0766 0.0790 0.0813 0.0837 0.0861 0.0884 0.0908 5.00 5.50 6.00 0.0140 0.0154 0.0168 0.0182 0.0196 0.0211 0.0225 0.0239 0.0253 0.0267 0.0282 0.0296 0.0310 0.0325 0.0339 0.0353 0.0368 0.0382 0.0397 0.0411 0.0426 0.0440 0.0455 0.0469 0.0484 0.0498 0.0513 0.0528 0.0542 0.0557 0.0572 6.50 0.0119 0.0131 0.0143 0.0155 0.0167 0.0179 0.0191 0.0203 0.0215 0.0227 0.0240 0.0252 0.0264 0.0276 0.0288 0.0300 0.0313 0.0325 0.0337 0.0349 0.0361 0.0374 0.0386 0.0398 0.0411 0.0423 0.0435 0.0448 0.0460 0.0473 0.0485 7.00 7.50 8.00 0.0078 0.0086 0.0094 0.0102 0.0110 0.0118 0.0126 0.0134 0.0142 0.0150 0.0157 0.0165 0.0173 0.0181 0.0189 0.0197 0.0205 0.0213 0.0221 0.0229 0.0237 0.0245 0.0253 0.0261 0.0269 0.0277 0.0285 0.0293 0.0301 0.0309 0.0317 8.50 9.00 9.50 0.0056 0.0061 0.0067 0.0072 0.0078 0.0083 0.0089 0.0095 0.0100 0.0106 0.0111 0.0117 0.0123 0.0128 0.0134 0.0139 0.0145 0.0151 0.0156 0.0162 0.0168 0.0173 0.0179 0.0185 0.0190 0.0196 0.0201 0.0207 0.0213 0.0218 0.0224 10.00 12.50 15.00 0.0022 0.0024 0.0027 0.0029 0.0031 0.0033 0.0036 0.0038 0.0040 0.0042 0.0045 0.0047 0.0049 0.0051 0.0053 0.0056 0.0058 0.0060 0.0062 0.0065 0.0067 0.0069 0.0071 0.0074 0.0076 0.0078 0.0080 0.0083 0.0085 0.0087 0.0089 17.50 20.00

0.0202 0.0167 0.0222 0.0183 0.0243 0.0200 0.0263 0.0217 0.0284 0.0234 0.0305 0.0251 0.0325 0.0268 0.0346 0.0285 0.0367 0.0302 0.0387 0.0319 0.0408 0.0336 0.0429 0.0353 0.0450 0.0370 0.0471 0.0388 0.0492 0.0405 0.0513 0.0422 0.0534 0.0439 0.0555 0.0457 0.0576 0.0474 0.0598 0.0491 0.0619 0.0509 0.0640 0.0526 0.0661 0.0543 0.0683 0.0561 0.0704 0.0578 0.0726 0.0596 0.0747 0.0613 0.0769 0.0631 0.0790 0.0649 0.0812 0.0666 0.0834 0.0684

0.0103 0.0089 0.0113 0.0098 0.0123 0.0107 0.0134 0.0116 0.0144 0.0125 0.0154 0.0134 0.0165 0.0143 0.0175 0.0152 0.0185 0.0161 0.0196 0.0170 0.0206 0.0179 0.0217 0.0188 0.0227 0.0197 0.0237 0.0207 0.0248 0.0216 0.0258 0.0225 0.0269 0.0234 0.0279 0.0243 0.0290 0.0252 0.0300 0.0261 0.0311 0.0270 0.0321 0.0279 0.0332 0.0289 0.0343 0.0298 0.0353 0.0307 0.0364 0.0316 0.0374 0.0325 0.0385 0.0334 0.0395 0.0344 0.0406 0.0353 0.0417 0.0362

0.0069 0.0062 0.0076 0.0068 0.0083 0.0074 0.0090 0.0081 0.0097 0.0087 0.0104 0.0093 0.0111 0.0099 0.0118 0.0105 0.0125 0.0112 0.0132 0.0118 0.0139 0.0124 0.0146 0.0130 0.0153 0.0137 0.0160 0.0143 0.0167 0.0149 0.0175 0.0156 0.0182 0.0162 0.0189 0.0168 0.0196 0.0174 0.0203 0.0181 0.0210 0.0187 0.0217 0.0193 0.0224 0.0200 0.0231 0.0206 0.0238 0.0212 0.0245 0.0218 0.0252 0.0225 0.0259 0.0231 0.0266 0.0237 0.0274 0.0244 0.0281 0.0250

0.0050 0.0032 0.0055 0.0035 0.0060 0.0038 0.0065 0.0042 0.0070 0.0045 0.0075 0.0048 0.0080 0.0051 0.0085 0.0055 0.0090 0.0058 0.0095 0.0061 0.0101 0.0064 0.0106 0.0067 0.0111 0.0071 0.0116 0.0074 0.0121 0.0077 0.0126 0.0080 0.0131 0.0084 0.0136 0.0087 0.0141 0.0090 0.0146 0.0093 0.0151 0.0096 0.0156 0.0100 0.0161 0.0103 0.0166 0.0106 0.0171 0.0109 0.0177 0.0113 0.0182 0.0116 0.0187 0.0119 0.0192 0.0122 0.0197 0.0126 0.0202 0.0129

0.0016 0.0013 0.0018 0.0014 0.0020 0.0015 0.0021 0.0016 0.0023 0.0018 0.0025 0.0019 0.0026 0.0020 0.0028 0.0021 0.0029 0.0023 0.0031 0.0024 0.0033 0.0025 0.0034 0.0026 0.0036 0.0028 0.0038 0.0029 0.0039 0.0030 0.0041 0.0031 0.0043 0.0033 0.0044 0.0034 0.0046 0.0035 0.0047 0.0036 0.0049 0.0038 0.0051 0.0039 0.0052 0.0040 0.0054 0.0041 0.0056 0.0043 0.0057 0.0044 0.0059 0.0045 0.0061 0.0046 0.0062 0.0048 0.0064 0.0049 0.0066 0.0050

42

Sepam 1000+

Hot curves for Eso = 0


I/Ib Es (%) 105 110 115 120 125 130 135 140 145 150 155 160 165 170 175 180 185 190 195 200 1.00 1.05 1.10 1.15 0.1685 0.3712 0.6257 0.9680 1.4925 2.6626 1.20 0.1206 0.2578 0.4169 0.6061 0.8398 1.1451 1.5870 2.3979 1.25 1.30 1.35 0.0627 0.1296 0.2013 0.2786 0.3623 0.4537 0.5543 0.6662 0.7921 0.9362 1.1047 1.3074 1.5620 1.9042 2.4288 3.5988 1.40 1.45 1.50 0.0408 0.0834 0.1278 0.1744 0.2231 0.2744 0.3285 0.3857 0.4463 0.5108 0.5798 0.6539 0.7340 0.8210 0.9163 1.0217 1.1394 1.2730 1.4271 1.6094 1.55 1.60 1.65 0.0295 0.0598 0.0911 0.1234 0.1568 0.1914 0.2271 0.2643 0.3028 0.3429 0.3846 0.4282 0.4738 0.5215 0.5717 0.6244 0.6802 0.7392 0.8019 0.8688 1.70 1.75 1.80 0.0226 0.0457 0.0693 0.0935 0.1183 0.1438 0.1699 0.1967 0.2243 0.2526 0.2817 0.3118 0.3427 0.3747 0.4077 0.4418 0.4772 0.5138 0.5518 0.5914

0.6690 0.2719 3.7136 0.6466 1.2528 3.0445

0.0931 0.0752 0.1957 0.1566 0.3102 0.2451 0.4394 0.3423 0.5878 0.4499 0.7621 0.5705 0.9734 0.7077 1.2417 0.8668 1.6094 1.0561 2.1972 1.2897 3.8067 1.5950 2.0369 2.8478

0.0535 0.0464 0.1100 0.0951 0.1699 0.1462 0.2336 0.2002 0.3017 0.2572 0.3747 0.3176 0.4535 0.3819 0.5390 0.4507 0.6325 0.5245 0.7357 0.6042 0.8508 0.6909 0.9808 0.7857 1.1304 0.8905 1.3063 1.0076 1.5198 1.1403 1.7918 1.2933 2.1665 1.4739 2.7726 1.6946 4.5643 1.9782 2.3755

0.0363 0.0326 0.0740 0.0662 0.1131 0.1011 0.1539 0.1372 0.1963 0.1747 0.2407 0.2136 0.2871 0.2541 0.3358 0.2963 0.3869 0.3403 0.4408 0.3864 0.4978 0.4347 0.5583 0.4855 0.6226 0.5390 0.6914 0.5955 0.7652 0.6554 0.8449 0.7191 0.9316 0.7872 1.0264 0.8602 1.1312 0.9390 1.2483 1.0245

0.0268 0.0245 0.0544 0.0497 0.0827 0.0755 0.1118 0.1020 0.1419 0.1292 0.1728 0.1572 0.2048 0.1860 0.2378 0.2156 0.2719 0.2461 0.3073 0.2776 0.3439 0.3102 0.3819 0.3438 0.4215 0.3786 0.4626 0.4146 0.5055 0.4520 0.5504 0.4908 0.5974 0.5312 0.6466 0.5733 0.6985 0.6173 0.7531 0.6633

I/Ib Es (%) 105 110 115 120 125 130 135 140 145 150 155 160 165 170 175 180 185 190 195 200

1.85

1.90

1.95

2.00 0.0168 0.0339 0.0513 0.0690 0.0870 0.1054 0.1241 0.1431 0.1625 0.1823 0.2025 0.2231 0.2442 0.2657 0.2877 0.3102 0.3331 0.3567 0.3808 0.4055

2.20 0.0131 0.0264 0.0398 0.0535 0.0673 0.0813 0.0956 0.1100 0.1246 0.1395 0.1546 0.1699 0.1855 0.2012 0.2173 0.2336 0.2502 0.2671 0.2842 0.3017

2.40

2.60

2.80 0.0073 0.0147 0.0222 0.0297 0.0372 0.0449 0.0525 0.0603 0.0681 0.0759 0.0838 0.0918 0.0999 0.1080 0.1161 0.1244 0.1327 0.1411 0.1495 0.1581

3.00

3.20

3.40 0.0047 0.0095 0.0143 0.0191 0.0240 0.0288 0.0337 0.0386 0.0435 0.0485 0.0535 0.0585 0.0635 0.0686 0.0737 0.0788 0.0839 0.0891 0.0943 0.0995

3.60

3.80

4.00 0.0033 0.0067 0.0101 0.0134 0.0168 0.0202 0.0236 0.0270 0.0305 0.0339 0.0374 0.0408 0.0443 0.0478 0.0513 0.0548 0.0583 0.0619 0.0654 0.0690

4.20

4.40

4.60 0.0025 0.0050 0.0075 0.0100 0.0125 0.0150 0.0175 0.0200 0.0226 0.0251 0.0277 0.0302 0.0328 0.0353 0.0379 0.0405 0.0431 0.0457 0.0483 0.0509

0.0209 0.0193 0.0180 0.0422 0.0391 0.0363 0.0639 0.0592 0.0550 0.0862 0.0797 0.0740 0.1089 0.1007 0.0934 0.1322 0.1221 0.1132 0.1560 0.1440 0.1334 0.1805 0.1664 0.1540 0.2055 0.1892 0.1750 0.2312 0.2127 0.1965 0.2575 0.2366 0.2185 0.2846 0.2612 0.2409 0.3124 0.2864 0.2639 0.3410 0.3122 0.2874 0.3705 0.3388 0.3115 0.4008 0.3660 0.3361 0.4321 0.3940 0.3614 0.4644 0.4229 0.3873 0.4978 0.4525 0.4140 0.5324 0.4831 0.4413

0.0106 0.0087 0.0212 0.0175 0.0320 0.0264 0.0429 0.0353 0.0540 0.0444 0.0651 0.0535 0.0764 0.0627 0.0878 0.0720 0.0993 0.0813 0.1110 0.0908 0.1228 0.1004 0.1347 0.1100 0.1468 0.1197 0.1591 0.1296 0.1715 0.1395 0.1840 0.1495 0.1967 0.1597 0.2096 0.1699 0.2226 0.1802 0.2358 0.1907

0.0063 0.0054 0.0126 0.0109 0.0189 0.0164 0.0253 0.0219 0.0317 0.0274 0.0382 0.0330 0.0447 0.0386 0.0513 0.0443 0.0579 0.0499 0.0645 0.0556 0.0712 0.0614 0.0780 0.0671 0.0847 0.0729 0.0916 0.0788 0.0984 0.0847 0.1054 0.0906 0.1123 0.0965 0.1193 0.1025 0.1264 0.1085 0.1335 0.1145

0.0042 0.0037 0.0084 0.0075 0.0126 0.0112 0.0169 0.0150 0.0211 0.0188 0.0254 0.0226 0.0297 0.0264 0.0340 0.0302 0.0384 0.0341 0.0427 0.0379 0.0471 0.0418 0.0515 0.0457 0.0559 0.0496 0.0603 0.0535 0.0648 0.0574 0.0692 0.0614 0.0737 0.0653 0.0782 0.0693 0.0828 0.0733 0.0873 0.0773

0.0030 0.0027 0.0060 0.0055 0.0091 0.0082 0.0121 0.0110 0.0151 0.0137 0.0182 0.0165 0.0213 0.0192 0.0243 0.0220 0.0274 0.0248 0.0305 0.0276 0.0336 0.0304 0.0367 0.0332 0.0398 0.0360 0.0430 0.0389 0.0461 0.0417 0.0493 0.0446 0.0524 0.0474 0.0556 0.0503 0.0588 0.0531 0.0620 0.0560

Sepam 1000+

43

Protection functions (contd)

Hot curves for Eso = 0


I/Ib Es (%) 105 110 115 120 125 130 135 140 145 150 155 160 165 170 175 180 185 190 195 200 4.80 0.0023 0.0045 0.0068 0.0091 0.0114 0.0137 0.0160 0.0183 0.0206 0.0229 0.0253 0.0276 0.0299 0.0323 0.0346 0.0370 0.0393 0.0417 0.0441 0.0464 5.00 0.0021 0.0042 0.0063 0.0084 0.0105 0.0126 0.0147 0.0168 0.0189 0.0211 0.0232 0.0253 0.0275 0.0296 0.0317 0.0339 0.0361 0.0382 0.0404 0.0426 5.50 0.0017 0.0034 0.0051 0.0069 0.0086 0.0103 0.0120 0.0138 0.0155 0.0172 0.0190 0.0207 0.0225 0.0242 0.0260 0.0277 0.0295 0.0313 0.0330 0.0348 6.00 6.50 7.00 0.0010 0.0021 0.0031 0.0042 0.0052 0.0063 0.0073 0.0084 0.0094 0.0105 0.0115 0.0126 0.0136 0.0147 0.0157 0.0168 0.0179 0.0189 0.0200 0.0211 7.50 8.00 8.50 0.0007 0.0014 0.0021 0.0028 0.0035 0.0042 0.0049 0.0056 0.0063 0.0070 0.0077 0.0085 0.0092 0.0099 0.0106 0.0113 0.0120 0.0127 0.0134 0.0141 9.00 9.50 10.00 0.0005 0.0010 0.0015 0.0020 0.0025 0.0030 0.0035 0.0040 0.0046 0.0051 0.0056 0.0061 0.0066 0.0071 0.0076 0.0081 0.0086 0.0091 0.0096 0.0102 12.50 15.00 17.50 0.0002 0.0003 0.0005 0.0007 0.0008 0.0010 0.0011 0.0013 0.0015 0.0016 0.0018 0.0020 0.0021 0.0023 0.0025 0.0026 0.0028 0.0030 0.0031 0.0033 20.00 0.0001 0.0003 0.0004 0.0005 0.0006 0.0008 0.0009 0.0010 0.0011 0.0013 0.0014 0.0015 0.0016 0.0018 0.0019 0.0020 0.0021 0.0023 0.0024 0.0025

0.0014 0.0012 0.0029 0.0024 0.0043 0.0036 0.0057 0.0049 0.0072 0.0061 0.0086 0.0073 0.0101 0.0085 0.0115 0.0097 0.0129 0.0110 0.0144 0.0122 0.0158 0.0134 0.0173 0.0147 0.0187 0.0159 0.0202 0.0171 0.0217 0.0183 0.0231 0.0196 0.0246 0.0208 0.0261 0.0221 0.0275 0.0233 0.0290 0.0245

0.0009 0.0008 0.0018 0.0016 0.0027 0.0024 0.0036 0.0032 0.0045 0.0040 0.0054 0.0048 0.0064 0.0056 0.0073 0.0064 0.0082 0.0072 0.0091 0.0080 0.0100 0.0088 0.0109 0.0096 0.0118 0.0104 0.0128 0.0112 0.0137 0.0120 0.0146 0.0128 0.0155 0.0136 0.0164 0.0144 0.0173 0.0152 0.0183 0.0160

0.0006 0.0006 0.0013 0.0011 0.0019 0.0017 0.0025 0.0022 0.0031 0.0028 0.0038 0.0034 0.0044 0.0039 0.0050 0.0045 0.0056 0.0051 0.0063 0.0056 0.0069 0.0062 0.0075 0.0067 0.0082 0.0073 0.0088 0.0079 0.0094 0.0084 0.0101 0.0090 0.0107 0.0096 0.0113 0.0101 0.0119 0.0107 0.0126 0.0113

0.0003 0.0002 0.0006 0.0004 0.0010 0.0007 0.0013 0.0009 0.0016 0.0011 0.0019 0.0013 0.0023 0.0016 0.0026 0.0018 0.0029 0.0020 0.0032 0.0022 0.0035 0.0025 0.0039 0.0027 0.0042 0.0029 0.0045 0.0031 0.0048 0.0034 0.0052 0.0036 0.0055 0.0038 0.0058 0.0040 0.0061 0.0043 0.0065 0.0045

44

Sepam 1000+

Phase undercurrent
ANSI code 37

Block diagram
15ms 0 &

I1

I < Is

time-delayed output pick-up signal

Operation This protection is single-phase: c it picks up when phase 1 current drops below the Is set point, c it is inactive when the current is less than 10% of Ib, c it is insensitive to current drops (breaking) due to circuit breaker tripping, c it includes a definite time delay T.
t

I> 0.1 Ib

Characteristics Is set point setting accuracy pick-up/drop-out ratio T time delay setting 50 ms i T i 300 s 2% or 25 ms 10 ms or 1 digit < 50 ms < 35 ms < 40 ms 15% Ib i Is i 100% Ib by steps of 1% 5% 106% 5% for Is > 0.1 In

0 0.1 Ib Operating principle

Is

accuracy (1) resolution characteristic times operating time overshoot time reset time
(1)

1.06 Is Is 0.1 Ib pick up signal time-delayed output Case of current sag

in reference conditions (IEC 60255-6).

1.06 Is Is 0.1 Ib pick up signal = 0 time-delayed output = 0 Case of circuit breaker tripping. <15 ms

Sepam 1000+

45

Protection functions (contd)

Excessive starting time, locked rotor


ANSI code
I

48 - 51LR

Is

0.1Ib excessive starting time locked rotor Case of normal starting. ST

Operation This function is three-phase. It comprises two parts: c excessive starting time: during starting, the protection picks up when one of the 3 phase currents is greater than the set point Is for a longer period of time than the ST time delay (normal starting time), c locked rotor: v at the normal operating rate (after starting), the protection picks up when one of the 3 phase currents is greater than the set point Is for a longer period of time than the LT time delay of the definite time type. v locked on start: large motors may have very long starting time, due to their inertia or the reduce voltage supply. This starting time is longer than the permissive rotor blocking time. To protect such a motor LTS timer initiate a trip if a start has been detected (I > Is) or if the motor speed is zero. For a normal start, the input I23 (zero-speed-switch) disable this protection. Motor re-acceleration When the motor re-accelerates, it consumes a current in the vicinity of the starting current (> Is) without the current first passing through a value less than 10% of Ib. The ST time delay, which corresponds to the normal starting time, may be reinitialized by a logic data input for particular uses (input I22). c reinitialize the excessive starting time protection, c set the locked rotor protection LT time delay to a low value. Starting is detected when the current consumed is 10% greater than the Ib curent.

Is

Block diagram
1 tripping output locked rotor output

0.1Ib I>0.1Ib excessive starting time locked rotor Case of excessive starting time. ST I1 I2 I3 input I22 1 I>Is LTS 0 input I23 Is & & ST 0 R & LT 0

starting time output

locked rotor at output

0.1Ib excessive starting time locked rotor Case of locked rotor. ST LT

Characteristics Is set point setting resolution accuracy


(1)

50% Ib i Is i 500% Ib 1% 5% 93.5% 5% ST LT LTS 500 ms i T i 300 s 50 ms i T i 300 s 50 ms i T i 300 s 10 ms or 1 digit 2% or 25 ms

pick-up/drop-out ratio ST and LT time delays setting

resolution accuracy
(1)

(1)

in reference conditions (IEC 60255-6).

46

Sepam 1000+

Starts per hour


ANSI code 66

The number of consecutive starts is the number starts counted during the last P/Nt minutes, Nt being the number of starts allowed per period. The motor hot state corresponds to the overshooting of the fixed set point (50% heat rise) of the thermal overload function. When the motor re-accelerates, it undergoes a stress similar to that of starting without the current first passing through a value less than 10% of Ib, in which case the number of starts is not incremented. It is possible however to increment the number of starts when a re-acceleration occurs by a logic data input (input I22). Block diagram

Operation This function is three-phase. It picks up when the number of starts reaches the following limits: c maximum number of starts allowed per period of time (P) (Nt), c maximum allowed number of consecutive hot starts (Nh), c maximum allowed number of consecutive cold starts (Nc), c the function indicates the number of starts still allowed before the maximum, if the protection has not picked up. The number of starts depends on the motors thermal state, c waiting time before a start is allowed, if the protection has picked up. Starting is detected when the current consumed becomes greater than 10% of the Ib current.

I1 I2 I3

& I>0.1Ib 0 T

k1>Nt P mn 1 k2>Nc P mn/Nt inhibit closing

input I22

&

k3>Nh P mn/Nt

Readout The number of starts and the waiting time may be accessed via: c the display (1) using the key, c the screen of a PC with SFT 2841 software, c the communication link. Clearing The number of starts counters may be cleared, using a password, via: c the display using the clear key (1), c the screen of a PC with SFT 2841 software.

thermal alarm (hot state) "Clear"

Characteristics period of time (P) setting resolution Nt total number of starts setting resolution setting
(2)

1 to 6 hour 1 1 to 60 1 1 to Nt 1 0 mn i T i 90 mn 1 mn or 1 digit 0 mn to 360 mn 1 mn 0 to 60 1

Nh and Nc number of consecutive starts resolution T time delay between starts setting resolution waiting time measurement measurement range resolution measurement range resolution
(1) (2)

measurement of the number N of starts allowed

Sepam equipped with advanced UMI. with Nh i Nc.

Sepam 1000+

47

Protection functions (contd)

Positive sequence undervoltage and phase rotation direction check


ANSI code Operation Positive sequence undervoltage The protection picks up when the positive sequence component Vd of a three-phase voltage system drops below the Vsd set point with: 27D - 47

Block diagram
Vd Vd < Vsd T 0 time-delayed output

pick-up signal Vd < 0.1Un


(2)

U21 (or V1)

U> 0.8 Un

&

rotation display

Vd = (1/3) [V1 + a V2 + a V3] Vd = (1/3) [U21 - a2 U32] U


2 j

Characteristics Vsd set point setting accuracy


(1)

15% Unp to 60% Unp 2% 103% 2.5% 1% 50 ms to 300 s


(1)

pick-up/drop-out ratio resolution T time delay setting accuracy resolution

with V =

and a = e

c it includes a definite time delay T, c it allows drops in motor electrical torque to be detected. Phase rotation direction This protection also allows the phase rotation direction to be detected. The protection considers that the phase rotation direction is inverse when the positive sequence voltage is less than 10% of Unp and when the phaseto-phase voltage is greater than 80% of Unp.

2%, or 25 ms 10 ms or 1 digit pick up < 55 ms < 35 ms < 35 ms

characteristic times operating time overshoot time reset time


(1) (2)

in reference conditions (IEC 60255-6). displays rotation instead of positive sequence voltage measurement.

Phase-to-phase undervoltage
ANSI code 27

Characteristics Us set point setting accuracy


(1)

5% Unp to 100% Unp 2% or 0.005 Unp 1% 103% 2.5% 50 ms to 300 s

resolution pick up/drop-out ratio T time delay setting accuracy


(1)

Operation This protection is three-phase: c it picks up when one of the phase-to-phase voltages concerned is less than the set point Us, c the protection includes a definite time delay.

2%, or 25 ms 10 ms or 1 digit pick up < 35 ms (25 ms typical) < 35 ms < 40 ms

resolution characteristic times operating time overshoot time

Block diagram
U21 U32 U13 T 0

reset time
time-delayed output
(1)

U < Us

in reference conditions (IEC 60255-6).

pick up signal

48

Sepam 1000+

Phase-to-neutral undervoltage
ANSI code 27S

Caracteristics VS set point setting accuracy


(1)

5% Vnp to 100% Vnp 2% or 0.005 Vnp 1% 103% 2.5% 50 ms to 300 s 2%, or 25 ms 10 ms or 1 digit pick up < 35 ms (25 ms typical) < 35 ms < 40 ms

resolution pick up/drop-out ratio T time delay Operation This protection is three-phase: c it picks up when one of the 3 phase-to-neutral voltages drops below the Vs set point. c it has 3 independent outputs available for the control matrix c it is operational if the number of VTs connected is V1, V2, V3 or U21, U32 with measurement of Vo. setting accuracy (1) resolution characteristic times operating time overshoot time reset time
(1)

in reference conditions (IEC 60255-6)

Block diagram
V1 T 0

V1 < Vs

time-delayed output

V2

V2 < Vs

time-delayed output

V3

V3 < Vs

time-delayed output

pick up signal

Phase-to-phase overvoltage
ANSI code 59

Characteristics Us set point setting accuracy


(1)

50% Unp to 150% Unp (2) 2% or 0.005 Unp 1% 97% 1% 50 ms to 300 s

resolution pick-up/drop-out ratio T time delay setting accuracy


(1)

Operation This protection is three-phase: c it picks up when one of the phase-to-phase voltages concerned is greater than the Us set point, c the protection includes a definite time delay. Block diagram
U21 U32 U13 T

2%, or 25 ms 10 ms or 1 digit pick up < 35 ms (25 ms typical) < 35 ms < 40 ms

resolution characteristic times operating time overrun time reset time


(1) (2)

U > Us

time-delayed output pick-up signal

in reference conditions (IEC 60255-6) 135% Unp with PTs 230 V / e

Sepam 1000+

49

Protection functions (contd)

Neutral voltage displacement


ANSI code 59N

Characteristics Vso set point setting 2% Unp to 80% Unp if Vnso 2% Unp to 80% Unp if Vnso 5% Unp to 80% Unp if Vnso
(1) (2) (2) (2)

Operation This protection picks up when the neutral voltage Vo is greater than a Vso set point with V0 = V1 + V2 + V3, c it includes a definite time delay T, c neutral voltage is either calculated from the 3 phase voltages or measured by an external VT. Block diagram
V1 V2 V3 V0 > Vso external VT T 0 time-delayed output pick-up signal

= sum 3 V = Uns / e = Uns / 3

accuracy

2% or 0.005 Unp 1% 97% +1% 50 ms to 300 s

resolution pick-up/drop-out ratio T time delay setting accuracy


(1)

2%, or 25 ms 10 ms or 1 digit pick up < 55 ms < 35 ms < 55 ms

resolution characteristic times operating time overshoot time reset time


(1) (2)

in reference conditions (IEC 60255-6). Vnso is one of the general parameters.

Remanent undervoltage
ANSI code 27R

Characteristics Us set point setting accuracy pick-up/drop-out ratio resolution T time delay setting accuracy
(1)

5% Unp to 100% Unp 5% or 0.005 Unp 103% 2.5% 1% 50 ms to 300 s 2%, or 25 ms 10 ms or 1 digit < 40 ms < 20 ms < 30 ms

Operation This protection is single-phase: c it picks up when the U21 phase-to-phase voltage is less than the Us set point, c the protection includes a definite time delay.

Block diagram
U21 (or V1) U < Us T 0 time-delayed output pick-up signal

resolution characteristic times operating time overrun time reset time


(1)

in reference conditions (IEC 60255-6).

50

Sepam 1000+

Overfrequency
ANSI code 81H Operation This function picks up when the frequency of the positive sequence voltage is greater than the set point and if the positive sequence voltage is more than 20% of Vnp (Unp/e). If only one VT is connected (U21), the function picks up when the frequency is greater than the set point and if the U21 voltage is more than 20% of Unp. It includes a definite time delay T.

Block diagram
U32 U21

Vd

&

F > Fs

time-delayed output pick-up signal

Vd > 0.2 Vnp (1)


(1)

or U21 > 0.2 Unp if only one VT

If there is only one sensor (U21), the voltage signal is connected to terminals 1 and 2 of the connector CCT 640, whatever the phase.

Characteristics Fs set point setting resolution accuracy


(1)

50 to 53 Hz or 60 to 63 Hz 0.1 Hz 0.1 Hz 0.2 Hz 0.1 Hz 100 ms to 300 s 2% or 25 ms 10 ms or 1 digit pick up < 100 ms (80 ms typical) < 100 ms < 100 ms

pick-up/drop-out difference T time delay setting accuracy


(1)

resolution characteristic times operating time overshoot time reset time


(1)

in reference conditions (IEC 60255-6) and df/dt < 3 Hz/s.

Sepam 1000+

51

Protection functions (contd)

Underfrequency
ANSI code 81L

Bloc diagram
U32 U21

Vd

&

F < Fs

time-delayed output pick-up signal

Operation This function picks up when the frequency of the positive sequence voltage is less than the set point and if the positive sequence voltage is more than 20% of Vnp (Unp/e). If only one VT is connected (U21), the function picks up when the frequency is less than the set point and if the U21 voltage is more than 20% of Unp. It includes a definite time delay T.
(1)

Vd > 0.2 Vnp (1) or U21 > 0.2 Unp if only one VT.

If there is only one sensor (U21), the voltage signal is connected to terminals 1 and 2 of the connector CCT 640, whatever the phase. Characteristics Fs set point setting resolution accuracy
(1)

45 to 50 Hz or 55 to 60 Hz 0.1 Hz 0.1 Hz 0.2 Hz 0.1 Hz 100 ms to 300 s

pick-up/drop-out difference T time delay setting accuracy


(1)

2% or 25 ms 10 ms or 1 digit pick up < 100 ms (80 ms typical) < 100 ms < 100 ms

resolution characteristic times operating time overshoot time reset time


(1)

in reference conditions (IEC 60255-6) and df/dt < 3 Hz/s

Rate of change of frequency


ANSI code 81R

Bloc diagram
< Fmax Vd f > Fmin & dF/dt 1 T 0 time delayed output signal pick up > 0.5 Vn < - dFs/dt > + dFs/dt

Operation This function picks up when the rate of change of frequency (ROCOF) of the positive sequence voltage overshoots the set point. If only one VT is connected (U21), the function is inhibited. It includes a definite time delay T.

Characteristics dFs / dt set point setting resolution accuracy tripping no tripping T time delay setting accuracy resolution temps caractristiques (1) operating time overshoot time reset time
(1)

0.1 to 10 Hz/s 0.1 Hz/s 5 % or 0.1 Hz/s 3 % or 0.05 Hz/s 100 ms to 300 s 2 % or 25 ms 10 ms or 1 digit pick up < 170 ms (130 ms typical) < 100 ms < 100 ms

in reference conditions (IEC 60255-6)

52

Sepam 1000+

Temperature monitoring
ANSI code 49T - 38

Block diagram

T < +205 C

&

T > Ts1

set point 1

Operation This protection is associated with an RTD of the Pt100 platinum (100 at 0C) or (nickel 100 , nickel 120 ) type in accordance with the IEC 60751 and DIN 43760 standards. c It picks up when the monitored temperature is greater than the Ts set point. c It has two independent set points: v alarm set point, v tripping set point. c When the protection is activated, it detects whether the RTD is shorted or disconnected: v RTD shorting is detected if the measured temperature is less than 35C (measurement displayed ****), v RTD disconnection is detected if the measured temperature is greater than +205C (measurement displayed -****). If an RTD fault is detected, the set point output relays are inhibited: the protection outputs are set to zero. The "RTD fault" item is also made available in the control matrix and an alarm message is generated.

RTD

T > Ts2

set point 2

T > -35 C

&

RTDs fault

Characteristics Ts1 and Ts2 set points setting accuracy


(1)

C
0C to 180C 1.5C 1C 3C 0.5 < 5 seconds

F
32F to 356F 2.7F 1F

resolution pick-up/drop-out difference characteristic times operating time


(1)

see temperature measurement chapter for accuracy derating according to wiring cross-section

Sepam 1000+

53

Protection functions (contd)

Recloser
ANSI code 79

Recloser initialization The recloser is ready to operate if all of the following conditions are met: c "circuit breaker control" function activated and recloser in service, c circuit breaker closed, c inhibition time delay not running, c none of the recloser inhibition conditions is true (see below). Cycles c Case of a cleared fault: v if, after a reclosing order, the fault does not appear after the disengaging time delay has expired, the recloser reinitializes and a message appears on the display (cf. example 1). c Case of a permanent fault, not cleared: v after the instantaneous or time-delayed protection has tripped, the isolation time delay associated with the first active cycle starts up. When it runs out, a closing order is given and this order starts up the disengagement time delay. If the protection detects the fault before the end of the time delay, a trip order is given and the next reclosing cycle is activated, v if the fault persists after all the active cycles have taken place, a permanent trip order is given, a message appears on the display and closing is inhibited until the user has acknowledged the fault, according to the protection parameter setting. c Closing on a fault If the circuit breaker closes when the fault occurs, or if the fault appears before the end of the inhibition time delay, the recloser is inhibited. Recloser inhibition conditions The recloser is inhibited according to the following conditions: c close or trip command, c recloser disabled, c receipt of an inhibition order on inhibition input I26, c appearance of a fault related to the switchgear, such as trip circuit or control fault, c receipt of an external tripping order via inputs I21, I22 or I23.

Characteristics reclosing cycles number of cycles activation of cycle 1 (1) O/C 1 O/C 2 E/F 1 E/F 2 O/C 1 O/C 2 E/F 1 E/F 2 setting 1 to 4 inst. / time-del. / inactive inst. / time-del. / inactive inst. / time-del. / inactive inst. / time-del. / inactive inst. / time-del. / inactive inst. / time-del. / inactive inst. / time-del. / inactive inst. / time-del. / inactive 0.05 to 300 s 0.05 to 300 s 0.05 to 300 s 0.05 to 300 s 0.05 to 300 s 0.05 to 300 s

activation of cycles 2, 3 and 4 (1)

time delays disengagement time delay isolation time delay cycle 1 cycle 2 cycle 3 cycle 4 2% or 25 ms 10 ms or 1 digit

inhibition time delay accuracy resolution


(1)

if, during a reclosing cycle, a protection set as inactive with respect to the recloser triggers tripping, the recloser is inhibited.

54

Sepam 1000+

Instantaneous O/C 300 ms Time-delayed O/C

I12 (closed position) inhibition time delay CB open command

I11 (open position)

cycle 1 isolation time delay disengagement time delay

CB close command

Reclosing in progress (TS35) Reclosing successful (TS37) cleared fault message

Example 1: case of successful reclosing after the first cycle. Activation with 300 ms time-delayed O/C protection.

Instantaneous O/C 300 ms Time-delayed O/C 300 ms 300 ms

I12 (closed position)

inhibition time delay

CB open command cycle 1 isolation time delay cycle 2 isolation time delay

I11 (open position)

CB close command

Reclosing in progress (TS35) Definitive tripping (TS37) permanent fault message

Example 2: case of definitive tripping after two cycles activated by 300 ms time-delayed O/C protection.

Sepam 1000+

55

Protection functions (contd)

IDMT protections
The operation time depends on the protected variable (phase current, earth fault current, ). Operation is represented by a characteristic curve: c t = f(I) curve for the phase overcurrent function, c t = f(Io) for the earth fault function. The rest of the document is based on t = f(I), but the reasoning can be extended to other variables such as Io, The curve is defined by: c type (standard inverse, very inverse, extremely inverse..), c Is current setting which corresponds to the vertical asymptote of the curve, c T time delay setting which corresponds to the operation time for I = 10 Is. The 3 settings are made in the following chronological order: type, Is current, T time delay. Changing the T time delay setting by x% changes all of the operation times in the curve by x%. Examples of problems to be solved Problem 1 Knowing the type of IDMT, determine the Is current and T time delay settings. Theoretically, Is current is set to the maximum current that can be continuous: it is generally the rated current of the protected equipment (cable, transformer). T time delay is set to the operation point at 10 Is on the curve. This setting is determined taking into account the discrimination constraints with respect to the upstream and downstream protection devices. The discrimination constraint leads to the definition of a point A on the operation curve (IA, tA), e.g. the point that corresponds to the maximum fault current affecting the downstream protection. Problem 2 Knowing the type of IDMT, the Is current setting and a point k (Ik, tk) on the operation curve, determine the T time delay setting. On the standard curve of the same type, read the operation time tsk that corresponds to the relative current: Ik Is and the operation time Ts10 that corresponds to the relative current: I = 10 Is

The time delay setting that should be made in order for the operation curve to pass through point k(Ik, tk) is: T = Ts10 x tk tsk
ts

tk tsk Ts10

Ik/Is

10

I/Is

Another practical method: The chart below gives the values of: I ts K= as a function of Is ts10 tsk In the column that corresponds to the type of time delay, read the value K = Ik Ts10 in the line that corresponds to Is The time delay setting to be used so that the operation curve pasees through tk the point k(Ik, Tk) is: T = K Example Given: c type of time delay: standard inverse time (SIT) c set point: Is c a point k on the operation curve: k (3.5 Is; 4 s) Question: what is the T time delay setting (operation time at 10 Is)? Chart reading: SIT column I line = 3.5 Is k = 1.86 Answer: the time delay setting is: T = 4 1.86 Problem 3 Knowing the Is current and T time delay settings for a type of time delay (standard inverse, very inverse, extremely inverse), find the operation time for a current value of IA. On the standard curve of the same type, read the operation time tsA that corresponds to the relative current: IA Is and the operation time Ts10 that corresponds to the relative current: I = 10 Is The operation time tA for the current IA with the Is and T settings is: tA = tsA x T Ts10
ts

= 2.15 s

tA T tsA Ts10

IA/Is

10

I/Is

56

Sepam 1000+

Other practical method: the chart below gives the values of: I ts K= as a function of Ts10 Is In the column that corresponds to the type of time tsA delay, read the value K= Ts10 on the line that corresponds to IA

Example Given: c type of time delay: very inverse time (VIT) c set point: Is c T time delay = 0.8 s Question: what is the operation time for the current IA = 6 Is? Chart reading: VIT column line I Is = 6

Is The operation time tA for the current IA with the Is and T settings is tA = K.T

K = 1.80 Answer: the operation time for the current IA is t = 1.80 x 0.8 = 1.44 s.

K values chart
I/Is 1.0 1.1 1.2 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.5 7.0 7.5 8.0 8.5 9.0 9.5 10.0 10.5 11.0 11.5 12.0 12.5 13.0 13.5 14.0 14.5 15.0 15.5 16.0 16.5 17.0 17.5 18.0 18.5 19.0 19.5 20.0
(1)

SIT and IEC/A 24.700(1) 12.901 5.788 3.376 2.548 2.121 1.858 1.676 1.543 1.441 1.359 1.292 1.236 1.188 1.146 1.110 1.078 1.049 1.023 1.000 0.979 0.959 0.941 0.925 0.910 0.895 0.882 0.870 0.858 0.847 0.836 0.827 0.817 0.808 0.800 0.792 0.784 0.777 0.770 0.763

VIT, LTI and IEC/B 90.000(1) 45.000 18.000 9.000 6.000 4.500 3.600 3.000 2.571 2.250 2.000 1.800 1.636 1.500 1.385 1.286 1.200 1.125 1.059 1.000 0.947 0.900 0.857 0.818 0.783 0.750 0.720 0.692 0.667 0.643 0.621 0.600 0.581 0.563 0.545 0.529 0.514 0.500 0.486 0.474

EIT and IEC/C 471.429(1) 225.000 79.200 33.000 18.857 12.375 8.800 6.600 5.143 4.125 3.385 2.829 2.400 2.063 1.792 1.571 1.390 1.238 1.109 1.000 0.906 0.825 0.754 0.692 0.638 0.589 0.546 0.508 0.473 0.442 0.414 0.388 0.365 0.344 0.324 0.307 0.290 0.275 0.261 0.248

UIT 545.905 179.548 67.691 35.490 21.608 14.382 10.169 7.513 5.742 4.507 3.616 2.954 2.450 2.060 1.751 1.504 1.303 1.137 1.000 0.885 0.787 0.704 0.633 0.572 0.518 0.471 0.430 0.394 0.362 0.334 0.308 0.285 0.265 0.246 0.229 0.214 0.200 0.188 0.176

RI 3.062 2.534 2.216 1.736 1.427 1.290 1.212 1.161 1.126 1.101 1.081 1.065 1.053 1.042 1.033 1.026 1.019 1.013 1.008 1.004 1.000 0.996 0.993 0.990 0.988 0.985 0.983 0.981 0.979 0.977 0.976 0.974 0.973 0.971 0.970 0.969 0.968 0.967 0.966 0.965 0.964

IEEE MI (IEC/D) 22.461 11.777 5.336 3.152 2.402 2.016 1.777 1.613 1.492 1.399 1.325 1.264 1.213 1.170 1.132 1.099 1.070 1.044 1.021 1.000 0.981 0.963 0.947 0.932 0.918 0.905 0.893 0.882 0.871 0.861 0.852 0.843 0.834 0.826 0.819 0.812 0.805 0.798 0.792 0.786

IEEE VI (IEC/E) 136.228 65.390 23.479 10.199 6.133 4.270 3.242 2.610 2.191 1.898 1.686 1.526 1.402 1.305 1.228 1.164 1.112 1.068 1.031 1.000 0.973 0.950 0.929 0.912 0.896 0.882 0.870 0.858 0.849 0.840 0.831 0.824 0.817 0.811 0.806 0.801 0.796 0.792 0.788 0.784

IEEE EI (IEC/F) 330.606 157.946 55.791 23.421 13.512 8.970 6.465 4.924 3.903 3.190 2.671 2.281 1.981 1.744 1.555 1.400 1.273 1.166 1.077 1.000 0.934 0.877 0.828 0.784 0.746 0.712 0.682 0.655 0.631 0.609 0.589 0.571 0.555 0.540 0.527 0.514 0.503 0.492 0.482 0.473

IAC I 62.005 19.033 9.413 3.891 2.524 2.056 1.792 1.617 1.491 1.396 1.321 1.261 1.211 1.170 1.135 1.105 1.078 1.055 1.035 1.016 1.000 0.985 0.972 0.960 0.949 0.938 0.929 0.920 0.912 0.905 0.898 0.891 0.885 0.879 0.874 0.869 0.864 0.860 0.855 0.851 0.848

IAC VI 62.272 45.678 34.628 17.539 7.932 4.676 3.249 2.509 2.076 1.800 1.610 1.473 1.370 1.289 1.224 1.171 1.126 1.087 1.054 1.026 1.000 0.977 0.957 0.939 0.922 0.907 0.893 0.880 0.868 0.857 0.846 0.837 0.828 0.819 0.811 0.804 0.797 0.790 0.784 0.778 0.772

IAC EI 200.226 122.172 82.899 36.687 16.178 9.566 6.541 4.872 3.839 3.146 2.653 2.288 2.007 1.786 1.607 1.460 1.337 1.233 1.144 1.067 1.000 0.941 0.888 0.841 0.799 0.761 0.727 0.695 0.667 0.641 0.616 0.594 0.573 0.554 0.536 0.519 0.504 0.489 0.475 0.463 0.450

values appropriate for IEC A, B and C curves only

Sepam 1000+

57

Protection functions (contd)

IDMT protections (contd)


Standard inverse time curve SIT Very inverse time curve VIT or LTI Extremely inverse time curve EIT Ultra inverse time curve UIT

t (s) 100.00

t (s) 1 000.00

100.00

10.00

curve (T = 1s)
curve (T = 1s)

10.00

1.00

RI standard inverse time SIT

1.00
very inverse time VIT or LTI

extremely inverse time EIT ultra inverse time UIT


I/Is 0.10 1 10 100

I/Is 0.10 1 10 100

IEEE curves
t (s) 10000.00

IAC curves
t (s) 1 000.00

1000.00

100.00

I VI
100.00

EI
MI VI EI

10.00

10.00

1.00
1.00

I/Is
0.10 1 10 100 I/Is

0.10 1 10 100

58

Sepam 1000+

Curve equations
IEC standard inverse type curve t d (I) = characteristic curves with: IEC standard inverse / A IEC very inverse / B IEC long time inverse / B IEC extremely inverse / C IEC RI type curve t d (I) = l 0.339-0.236 I Is IEC ultra inverse x T 3.1706 k 0.14 13.5 120 80 315.2 0.02 1 1 2 2.5 2.97 1.50 13.33 0.808 1 k T x I 1 Is

( )

( )

IEEE curves t d (I) =

( IIs )

+B x T 1

characteristic curves with: IEEE moderately inverse IEEE very inverse IEEE extremely inverse characteristic curves IAC inverse with: IAC very inverse IAC extremely inverse

A 0.010 3.922 5.64 A 0.208 0.090 0.004

B 0.023 0.098 0.0243 B 0.863 0.795 0.638 C 0.800 0.100 0.620

p 0.02 2 2 D E -0.418 0.195 -1.288 7.958 1.787 0.246

0.241 0.138 0.081 0.297 0.165 0.092

IAC curves t d (I) = A +

B + D 2+ E 3 x T I C I C I C Is Is Is

) (

) (

example:
ts IEC curve VIT type

TMS = 1

Time Multiplier Setting TMS The time delay of IDMT tripping curves (except for the RI curve) may be set: v by T sec (operating time at 10 x Is), v by TMS (setting that corresponds to T in the equations above). Example: t (I) = 13.5 x TMS I 1 Is T 1.5

T = 1.5 sec

( )

with: TMS =

The VIT type IEC curve is positioned in same way with TMS = 1 or T = 1,5 sec.

10

I/Is

example:
tr

Holding time T1 c definite time: allows the function to be triggered by an intermittent fault, c IDMT: used to emulate a disc type electromagnetic protective relay. T1 1- I Is T T = TMS

TMS = 1

t r (I) =
T1

( )

with

I/Is

T1 = holding time setting (holding time for I reset = 0 and TMS = 1) T = tripping time delay setting (at 10 Is) = value of standard tripping curve at 10 Is =

10 -1 The standardized or estimated values of T1 are available in the SFT 2841 help.

Sepam 1000+

59

Control and monitoring functions

Each control and monitoring function requires separate parameter setting and appropriate wiring. Therefore, not all of the functions are available at the same time. e.g. when the logic discrimination function is used, the switching of settings groups function may not be used.

Trip circuit supervision and matching


This monitoring function is intended for trip circuits: c Shunt-trip coil circuits. The function detects: v circuit continuity, v loss of power supply, v position contact discrepancy. The function inhibits closing of the breaking device.
M I11 I12 2 4 5 A O1 5 4 D + _

Output relay testing


This function is activated via the SFT 2841(1) and controls each output relay (2) individually. The relay changes status for a period of 5 s. This function is especially useful in the commissioning and fault tracking phases.
(1) (2)

or via advanced UMI. except for O4 is the output is declared as watchdog.

c Undervoltage release coil circuits. The function detects: v position contact discrepancy, in which case coil supervision is not necessary.
O1

A 5 4 M I11 I12 2 4 5 D + _

Discrepancy
This function is used to detect a discrepancy between the last remote control order received and the actual position of the circuit breaker. The data may be accessed via the TS42 remote indication.

Block diagram
TC1 received I11

(1)

Block diagram
I11

(1)

& 1 T = 1s TC/position discrepancy I12

& 1 t 0 reset 1 0 trip circuit supervision

T = 200 ms

TC2 received I12

&

&

Disturbance record triggering (OPG)


Triggering according to selected protection functions

pick-up 1 manual trig SFT 2841 TC10 & SFT 2841 TC8 SFT 2841 TC9 1
(1)

OPG trig

trig inhibit

&

trig enable

With MES option The function is activated if inputs I11 and I12 are set respectively as circuit breaker "open position" and circuit breaker "closed position".

manual trig

SFT 2841 TC10

60

Sepam 1000+

Circuit breaker / contactor control


Use This function controls the breaking device: c tripping by: v protections, v remote control, v external protection. c closing by: v recloser, v remote control. c inhibition of closing by: v device control fault, v SF6 pressure drop. It is coordinated with the recloser function. Block diagram(1) S20, T20, M20 types Sepam

In order for operation to take place in accordance with the block diagram, the Sepam 1000+ must have the necessary logic inputs (MES 108 or MES 114 module required) and the corresponding parameter setting and wiring must be done. The functions that trigger tripping may be latched individually at the time of parameter setting and reset according to several modes.

RESET key acknowledgment (TC5) & remote control disable (I25) external reset (I14) 1 reset

(I26) inhibition F49 inhibit start (thermal overload) protection 66: starts per hour &

(I25) pressure drop SF6.1 (I26) pressure drop SF6.2 protection functions valided for tripping - overcurrent - ... (I21) external tripping 1 (I22) external tripping 2 (I23) external tripping 3 (I26) inhibition F49 thermal overload 49 tripping open order by recloser TC2 close order (I25) remote control disable close order by recloser & 1 & 1 1 1 T 0 T = 200 ms

1 trip circuit fault 1 (2) O2 inhibit closing

. . 1 .

(TC1) open order

T = 200 ms

O1 tripping (shunt / undervoltage)

(I12) device closed

&

T &

T = 200 ms (I12) device closed

& close order

O11

B21(3), B22 type Sepam


(I25) pressure drop SF6.1 (I26) pressure drop SF6.2 1 T 0 trip circuit fault (I21) external tripping 1 (I22) external tripping 2 (I23) external tripping 3 1 (TC1) open order 1 1 (2) O2 inhibit closing T = 200 ms

T = 200 ms

O1 tripping (shunt / undervoltage)

(I12) device closed TC2 close order (I25) remote control disable
(1) (2) (3)

&

T (I12) device closed &

T = 200 ms

& close order

O11

&

data used in the logic block diagram depend on the Sepam type, availability of MES 108, 114 option and general parameters the usual case in which O2 is set to undervoltage coil (normaly closed) ralise les fonctions de type B20

Sepam 1000+

61

Control and monitoring functions (contd)

Logic discrimination
Use This function is used to obtain: c full tripping discrimination, c a substantial reduction in delayed tripping of the circuit breakers located nearest to the source (drawback of the classical time-based discrimination function). The system applies to the definite time (DT) and IDMT (standard inverse time SIT, very inverse time VIT, extremely inverse time EIT and ultra inverse time UIT) phase overcurrent and earth fault protections.

With this type of system, the time delays should be set with respect to the element to be protected without considering the discrimination aspect.

Operating principle
BI transmission

level n+1 Sepam

O3 I13

+ O3 outputs other level n Sepams

level n Sepam

O3 I13

td : X+0.9s

td : X+0.6s

BI receipt

td : X+0.3s

td : Xs

When a fault occurs in a radial network, the fault current flows through the circuit between the source and the location of the fault: c the protection devices upstream from the fault are triggered, c the protection devices downstream from the fault are not triggered, c only the first protection device upstream from the fault should trip. Each Sepam is capable of transmitting and receiving blocking input orders except for motor* Sepams which can only transmit blocking input orders. When a Sepam is triggered by a fault current: c it transmits a blocking input order from output O3 (1), c it trips the associated circuit breaker if it does not receive a blocking input order on input I13 (2). Transmission of the blocking input lasts for the time required to clear the fault. It is interrupted after a time delay that takes into account the breaking device operation time and the protection reset time. This system makes it possible to minimize the duration of the fault, optimize discrimination and guarantee safety in downgraded situations (wiring or switchgear failures).

e.g. radial distribution with use of time-based discrimination (td: tripping time, definite time curves).

td : Xs
MERLIN GERIN

td : Xs
MERLIN GERIN

td : Xs
MERLIN GERIN

order BI td : Xs
MERLIN GERIN

e.g. radial distribution with use of the Sepam logic discrimination system.

(*) Motor Sepams do not involve the receipt of blocking input orders since they are intended for loads only. (1) parameter setting by default. (2) according to parameter setting and presence of an additional MES 108 or 114 module.

62

Sepam 1000+

Block diagram: substation transformer applications

overcurrent inst relay 1 (group A) inst relay 2 (group A) earth fault inst relay 1 (group A) inst relay 2 (group A)
(2)

(2)

(1)

output Oxx : BI transmission 1 to BI transmission T 0 &

T = 0,2 s inhibition of BI transmission if fault is not cleared

BI transmission BI receipt time delay settings for time-based discrimination

overcurrent (time) time-delayed relay 1 (group B) time-delayed relay 2 (group B) earth fault (time) time-delayed relay 1 (group B) time-delayed relay 2 (group B) overcurrent (logic discrim) time-delayed relay 1 (group A) time-delayed relay 2 (group A) earth fault (logic discrim) time-delayed relay 1 (group A) time-delayed relay 2 (group A) 1 & 1 1 tripping (01)

time delay settings for logic discrimination

log. Input I13: AL receipt

Block diagram: motor applications


(2)

overcurrent inst. relay 1 (group A) inst. relay 2 (group A) earth fault


(2)

(1)

output Oxx : BI transmission 1 to BI transmission T 0 &

inst. relay 1 (group A) inst. relay 2 (group A) overcurrent time-delayed relay 1 (group B) time-delayed relay 2 (group B) earth fault time-delayed relay 1 (group B) time-delayed relay 2 (group B)
(1) (2)

T = 0.2 s inhibition of BI transmission

tripping

according to parameter setting (O3 by default). Instantaneous trip correspond to pick-up information

Pilot wire testing The pilot wire may be tested using the output relay testing function.

Sepam 1000+

63

Parameter and protection settings

Protection settings
The Sepam 1000+ can be set: c via the front panel when Sepam 1000+ is equipped with the advanced UMI function. Function keys (blue) may be used to navigate in the menu and to scroll and accept the displayed values. Main functions performed: v changing of passwords, v entry of general parameters, v entry of protection settings. c via a PC equipped with the SFT 2841 software package connected to the front panel for all types of Sepam 1000 +. Menus guide the user through the different phases of parameter and protection setting by a series of windows suited to each operation. The SFT 2841 software package may be used for Sepam 1000 + parameter and protection setting in connected or unconnected mode. The unconnected mode allows all the parameter settings to be prepared ahead of time and loaded in a single operation when the Sepam 1000 + is connected on site (downloading). Main functions performed by the SFT2841: c changing of passwords, c entry of general parameters (ratings, integration period, ), c entry of protection settings, c changing of program logic assignments, c enabling/disabling of functions, c saving of files.

on

I>51

I>>51 Io>51N Io>>51N

ext

0 off

I on

Trip

I1 = 162A I2 = 161A I3 = 163A

clear

reset

Example of advanced UMI with standard assignment of indicators.

Example of phase overcurrent protection setting screen.

Program logic parameter setting


Program logic parameter setting consists mainly of assigning the data from the protection function to the signal lamps and output relays. The parameter setting may be done by filling in the "control matrix" in the SFT 2841 software package.

Example of parameter setting.

64

Sepam 1000+

Program logic
Each Sepam 1000+ has program logic by default according to type (S20, T20,) as well as messages for the different signal lamps. The functions are assigned according to the most frequent use of the unit. This parameter setting may be customized if required using the SFT 2841 software package.

Example: Sepam S20 equipped with optionnal module MES 114 ES functions phase protection (latching) earth fault protection unbalance protection recloser open position closed position blocking input receipt line switch open (1) tripping by external protection 50/51-1 50/51-2 50N/51N-1 50N/51N-2 46 79 I11 I12 I13 I14 I21 I22 I23 I24 inhibit remote control SF6 pressure drop blocking input transmission pick-up signal I25 I26 c c c c c c logic selectivity disturbance recording triggering c
Signal lamps L1 - I > 51 L2 - I >> 51 L3 - Io > 51N L4 - Io >> 51N L5 - ext L6 L7 - off L8 - on L9 - Trip
(2)

output O1 O2 O3 O4 c c c c c c

signal lamps O11 O12 O13 O14 L1 L2 L3 L4 L5 L6 L7 L8 L9 c c c c c c c c c c c c c

associated functions breaker control

c c c c c c c c c c c

c c c c c

c c

trip circuit supervision logic selectivity

remote control

watchdog
Output O1 - tripping O2 - inhibit closing O3 - BI transmission O4 - watchdog O11 - close order O12 - phase fault indication O13 - earth fault indication O14 - permanent fault
(1) (2)

or CB withdrawned position. in service.

Sepam 1000+

65

Default parameter setting

The Sepam units are delivered with default parameter setting and protection setting according to the type of application. These factory settings are also used with the SFT 2841 software: c for the creation of new files in disconnected mode, c for a return to the factory settings in connected mode.

S20, T20 and M20 applications


Hardware configuration c Identification: Sepam xxxx c Model: UX c MES module: absent c MET module: absent c MSA module: absent c DSM module: present c ACE module: absent Output parameter setting c Outputs used: O1 to O4 c Shunt coils: O1, O3 c Undervoltage coils: O2, O4 c Impulse mode: no (latched) Program logic c Circuit breaker control: no c Logic discrimination: no c Use of logic inputs: not used General characteristics c Network frequency: 50 Hz c Setting group: A c Enable remote setting: no c Working language: English c CT rating: 5 A c Number of CTs: 3 (I1, I2, I3) c Rated current In: 630 A c Base current Ib: 630 A c Integration period: 5 min c Residual current: 3I sum c Pre-trig for disturbance recording: 36 periods Protections c All the protections are off. c The settings comprise values and choices that are informative and consistent with the general characteristics by default (in particular rated current In). c Tripping behavior v latching: yes, v activation of output O1: yes, v disturbance recording triggering: with. Command matrix c S20 application: v activation of output O2 upon protection tripping, v activation of indicators according to front panel markings, v watchdog on output O4, v disturbance recording triggering upon signal pick-up. c Complements for T20 application: v activation of O1 without latching upon tripping of temperature monitoring 1 to 7, v activation of O1 and indicator L9 without latching upon thermal overload tripping. c Complements for M20 application: v activation of outputs O1 and O2 and indicator L9 upon tripping of functions 37 (phase U/C) and 51 LR (locked rotor), v activation of output O2 upon tripping of function 66 (number of starts), v latching for function 51 LR.

66

Sepam 1000+

B21(1), B22 applications


Hardware configuration c Identification: Sepam xxxx c Model: UX c MES module: absent c MET module: absent c MSA module: absent c DSM module: present c ACE module: absent Output parameter setting c Outputs used: O1 to O4 c Shunt coils: O1 to O3 c Undervoltage coils: O4 c Impulse mode: no (latched) Program logic c Circuit breaker control: no c Assignment of logic inputs: not useds General characteristics c Network frequency: 50 Hz c Enable remote setting: no c Working language: English c Primary rated voltage (Unp): 20 kV c Secondary rated voltage (Uns): 100 V c Voltages measured by VTs: V1, V2, V3 c Residual voltage: 3V sum c Pre-trig for disturbance recording: 36 periods

Protections c All the protections are off c The settings comprise values and choices that are informative and consistent with the general characteristics by default c Latching: no c Disturbance recording triggering: with Command matrix c Assignment of output relays and indicators according to chart: functions B21 B22 27D-1 27D-1 27D-2 27D-2 27R 27-1 27-2 27R 27-1 27-2 c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c c output O1 O2 c indicators L1 L2 L3 c c c c

O3

O4

L4

L5

L6

L7

L8

L9

27S-1 27S-1 27S-2 27S-2 27S-3 27S-3 59-1 59-2 59-1 59-2

59N-1 59N-1 59N-2 59N-2 81H 81H 81L-1 81L-1 81L-2 81L-2 81R

c Disturbance recording triggering upon signal pick up. c Watchdog on output O4. Indicator marking L1: U < 27 L2: U < 27D L3: U < 27R L4: U > 59 L5: U > 59N L6: F > 81H L7: F < 81L L8: F << 81L L9: Trip

(1)

Type B21 performs the same functions as cancelled type B20.

Sepam 1000+

67

Characteristics

Size and weight Sepam 1000+ base unit


Front panel flush-mounting Top view Side view
mounting latch

Cutout
162 0.2

176

160 222 198 202 0.2

Mounting shown with advanced UMI and optional MES 114 module. Weight = approx. 1.2 kg without option. Weight = approx. 1.7 kg with option.

Mounting sheet thickness < 3 mm. 31 98

Terminal block mounting with AMT840 plate Used to mount the Sepam at the back of the compartment with access to the connectors on the rear panel. Mounting associated with the use of the remote advanced UMI (DSM303).

6,5 40

40

230

40

40

40 15 216 236

176

123

98

68

Sepam 1000+

DSM 303 module


T I on 0o SF6 51N Io>> ext ff

ACE 959 communication interface module


14 4

1 I>>5 I>51 on

51N Io>

7 11

res clea r

et

88 16 25 2 Weight: 0.25 kg 30 (1)

Weight approx. 0.3 kg The depth with the connection cord is less than 30 mm (lateral output).

MET 148 module


14 4

DSM 303 module cutout


144 0.2

98.5 0.5

88 Weight: 0.2 kg

Cutout dimensions for flush-mounting (mounting plate thickness < 3 mm).

30 (

1)

ACE 949-2 communication interface module

MSA 141 module


14 4

88

88 30 (1
)

72 Weight: 0.1 kg 30 (
1)

Weight: 0.2 kg

(1) depth with CCA77x connection cord: 70 mm.

Sepam 1000+

69

Characteristics (contd)

CSH 120, CSH 200 core balance CTs


The specially designed CSH 120 and CSH 200 core balance CTs are used for direct residual current measurement. The only difference between them is their diameter and they can both operate with 2 selected ratings: c 2 A rating: set points from 0.2 A to 30 A, c 20 A rating: set points from 2 A to 300 A. Characteristics: c dinner diameter: v CSH 120: dia. 120 mm v CSH 200: dia. 200 mm c accuracy: +5% at 20C c transformer ratio: 1/470 c maximum permissible current: 20 kA-1s c operating temperature: -25C to +70C c storage temperature: -40C to +85C c drift in accuracy related to temperature: +1% c the wiring resistance should be < 10 .

Dimensions
4 horizontal mounting holes dia. 5

4 vertical mounting holes dia. 5 J E L

dimensions (mm) A CSH 120 120 CSH 200 200 weight 256 46 0.6 kg 1.4 kg 274 120 60 257 104 37 CSH 120 CSH 200 164 44 190 76 40 166 62 35 B D E F H J K L

Mounted directly on cable.

Mounted on plate or rail.

CSH 30 interposing ring CT


The CSH 30 interposing ring CT is used when the residual current is measured using 1 A or 5 A current transformers. It should be installed near the Sepam input (max. distance 2 m).

Dimensions
60 8 29 4

30 82 5

50

16 2 4.5

2 4.5

Horizontal CSH 30 mounting

Vertical CSH 30 mounting

weight : 0.12 kg

70

Sepam 1000+

Electrical characteristics
analog inputs current transformer
(1)

input impedance consumption

< 0,001

1 A or 5 A CT (with CCA 630) 1 A to 6250 A ratings

< 0.01 VA to 1 A < 0.025 VA to 5 A steady state thermal resistance 3 In 1 second overload 100 In 100 to 120 V 480 V Ni 100 / 120 no 4 mA -20/+10% (from 19.2 to 275 Vdc) imp > 100 k input voltage 1 second overload

voltage transformer 220 V to 250 kV ratings input for RTD type of RTD isolation from earth current injected in the RTD logic inputs voltage (2) consumption logic outputs (O1, O2, O11 contacts) voltage continuous rating breaking capacity resistive load L/R load < 20 ms L/R load < 40 ms resistive load load p.f. > 0.3 making capacity logic outputs (O3, O4, O12, O13, O14 contacts) voltage continuous rating breaking capacity power supply 24 Vdc 48 / 250 Vdc 110 / 240 Vac
(2) (2) (2) (2)

steady state thermal resistance 230 V

Pt 100 no 4 mA 24 to 250 Vdc 3 mA typical DC AC (47.5 to 63 Hz) 8A 8/4A 6/2A 4/1A < 15 A for 200 ms 24 / 48 Vdc 2A L/R load < 20 ms load p.f. > 0.3 range -20% +50 % (19.2 to 36 Vdc) -20% +10 % -20% +10 % 47.5 to 63 Hz cancellation of transients 2/1A deactivated cons. 3 to 6 W 2 to 4.5 W 3 to 9 VA 10 ms or 1/2 period
(3)

24 / 48 Vdc

127 Vdc 8A 0.7 A 0.5 A 0.2 A

220 Vdc 100 to 240 Vac 8A 0.3 A 0.2 A 0.1 A 8A 5A 8A

DC AC (47.5 to 63 Hz)

127 Vdc 2A 0.5 A

220 Vdc 100 to 240 Vac 2A 0.15 A 1A

max. cons. (3) 7 to 11 W 6 to 8 W 9 to 15 VA

inrush current < 10 A for 10 ms < 10 A for 10 ms < 15 A for first half-period

analog output current load impedance accuracy


(1) (2)

4 - 20 mA, 0 - 20 mA, 0 - 10 mA < 600 (wiring included) 0.5%


(2)

wiring: maximum core cross-section 6 mm2 ( AWG 10) and ring lug terminal 4 mm. connection to screw terminal: 1 wire with max. cross-section 0.2 to 2.5 mm2 ( AWG 24-12) or 2 wires with max. cross-section 0.2 to 1 mm2 ( AWG 24-16), option: connection to 6.35 mm ring lug terminal for outputs O1,O2, O3, O4, power supply and CSH core balance CT. (3) according to configuration.

Sepam 1000+

71

Characteristics (contd)

Environmental characteristics
isolation dielectric withstand at power frequency 1.2/50 s impulse wave electromagnetic compatibility fast transient bursts 1 MHZ damped oscillating wave immunity to radiated fields immunity to conducted RF disturbances electrostatic discharge conducted disturbance emission disturbing field emission mechanical robustness degree of protection IEC 60529 IP 52 on front panel other sides closed (except for rear IP20) IEC 60255-22-4 IEC 61000-4-4 IEC 60255-22-1 IEC 60255-22-3 IEC 61000-4-3 IEC 61000-4-6 IEC 60255-22-2 IEC 61000-4-2 EN 55022 / CISPR 22 EN 55022 / CISPR 22 class IV level IV class III class X level III level III class III level III class B class A 30 V/m 10 V/m 10 V 6 kV / 8 kV (contact / air) on aux. supply
(4) (3)

IEC 60255-5 IEC 60255-5

2 kVrms 1 mn 5 kV (2)

(1)

vibrations shocks / jolts earthquakes fire resistance climatic withstand operation storage damp heat

IEC 60255-21-1 IEC 60255-21-2 IEC 60255-21-3 IEC 60695-2-1 IEC 60068-1 and 2 IEC 60068-1 and 2 IEC 60068-2-3

class II class II class II glow wire 630C -25C to +70C -25C to +70C 93% RH at 40C, 56 days (storage) 10 days (operation) class I

effect of corrosion
(1) (2) (3) (4)

IEC-68054-4

except for communication 1 kVrms. except for communication 3 kV common mode, 1 kV differential mode. generic EN 50081-1 standard. generic EN 50081-2 standard.

72

Sepam 1000+

Ordering information

When ordering, please enclose a photocopy of this page with your order, filling in the requested quantities in the spaces provided and ticking off the boxes to indicate your choices .

Sepam 1000+
Type de Sepam type Integrated advanced UMI(4) ring lug connector

quantity

substation ..................... S20 .... ........................................... .................. transformer ................... T20 .... ........................................... .................. motor ............................. M20 ... ........................................... .................. busbar ........................... B21 .... ........................................... .................. busbar ........................... B22 .... ........................................... .................. working language .......................... English / French ............................................. ....................................................... English / Spanish ........................................... ....................................................... English / Italian ............................................... ....................................................... English / Swedish ........................................... ....................................................... English / Polish ............................................... auxiliary power supply ................... 24 Vdc ............................................................ ....................................................... 48 to 250 Vdc or 100 to 240 Vda ...................

Separate modules and optional accessories


residual current sensors .................................... CSH 120 ........................... ........................................................................... CSH 200 ........................... interposing ring CT for residual current input ................................... CSH 30 ............................. core balance CT interface ................................. ACE 990 ........................... 4 input + 4 output module ................................. MES 108 .......................... 10 input + 4 output module ............................... MES 114 ........................... 8 temperature sensor module ........................... MET 148 ........................... analog output module ........................................ MSA 141 ........................... remote advanced UMI module (1) ...................................... DSM 303 .......................... mounting plate ................................................... AMT 840 ........................... 2-wire RS485 network interface 4-wire RS485 network interface
(2) (2) ..................................

quantity

ACE 949-2 ........................

.................... ACE 959 ...........................

remote module connection cable L = 0.6 m ...... CCA 770 ........................... remote module connection cable L = 2 m ......... CCA 772 ........................... remote module connection cable L = 4 m ......... CCA 774 ........................... PC parameter setting and operation software kit (3) .......................................................................................... SFT 2841 .......................... RS485 / RS232 converter ................................. ACE 909-2 ........................ RS485 / RS485 interface .................................. ACE 919 CA ..................... RS485 / RS485 interface .................................. ACE 919 CC ..................... use and commissioning manual ........................................... French ................................................. ....................................................... English .................................................
Notes: (1) not compatible with Sepam units equipped with integrated advanced UMI (2) including the CCA612 connection cord (3) kit including the CCA783 connection cord and SFT 2826 software (4) S10 UD model

Schneider Electric Industries SA


Postal address F-38050 Grenoble cedex 9 Tel : 33 (0)4 76 57 60 60 Telex : merge 320842 F http://www.schneider-electric.com Rcs Nanterre B 954 503 439 PCRED399039EN /3 ART.28274 As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication. Publishing: Schneider Electric Industries SA Design, production: Idra, HeadLines Printing: 09 / 2000